Islanding Detection and Control of Islanded Single and Two-Parallel Distributed Generation Units
|
|
- Alexandra Wilson
- 5 years ago
- Views:
Transcription
1 Islanding Detection and Control of Islanded Single and Two-Parallel Distributed Generation Units by Behrooz Bahrani A thesis submitted in conformity with the requirements for the degree of Master of Applied Science Department of Electrical and Computer Engineering University of Toronto c Copyright by Behrooz Bahrani 28
2 Islanding Detection and Control of Islanded Single and Two-Parallel Distributed Generation Units Behrooz Bahrani Master of Applied Science Graduate Department of Electrical and Computer Engineering University of Toronto 28 Abstract This thesis experimentally validates the performance of an active islanding detection method under various scenarios. The method actively injects a negative-sequence current through the interface voltage-sourced converter (VSC) of a distributed generation (DG) unit, as a disturbance signal for islanding detection. The estimated magnitude of the corresponding negative-sequence voltage at the PCC is used as the islanding detection signal. It is also analytically shown that the islanding detection method has a non-detection zone (NDZ), and a method to eliminate the NDZ is proposed. Moreover, the effectiveness of the modified method in eliminating the NDZ is verified based on simulation results in PSCAD/EMTDC software environment and experimental tests. Moreover, the performance of an autonomous mode controller for islanded DG units is experimentally evaluated. Based on a robustness analysis, it is shown that the controller which is basically designed for the nominal plant, can maintain the stability of the system despite of significant load uncertainties. Then adopting the islanding detection method and the proposed controller, the viability of uninterruptible operation of a single-dg system subsequent to an islanding event is experimentally validated. The feasibility of the islanding detection method for islanding detection in two-dg systems is also experimentally investigated. Moreover, based on the analyzed controller, a control strategy for autonomous operation of two-dg systems is proposed, and its performance is experimentally evaluated. Then, adopting the islanding detection method and the proposed control strategy, the viability of smooth transitions from grid-connected modes to autonomous (islanded) modes in two-parallel DG systems is experimentally validated. ii
3 Dedication study. To my family and Fateme, for their patience, unconditional love, and support during my iii
4 Acknowledgements I would like to express my deep and sincere gratitude to my supervisor, Prof. M. R. Iravani. His wide knowledge and logical way of thinking have been great assets for me. Without his invaluable guidance, support, patience, and financial support, this work would not be possible. The financial support of the University of Toronto is also gratefully acknowledged. Many thanks go in particular to Prof. A. Prodic. I am greatly indebted to him for his invaluable advice and guidance all throughout my study in the University of Toronto and especially, during the courses he taught me. I wish also to thank my entire committee: Prof. P. Lehn, Prof. A. Prodic, and Prof. Kschischang for their effort, discussions and constructive comments. It is a pleasure to pay tribute also to Dr. H. Karimi for his helpful collaboration in the experimental tests. Moreover, I am appreciative of my colleagues in the energy systems group as well as my friends in the University of Toronto, and especially, Dr. Maryam Saeedifard and Mr. Amir Parayandeh for their invaluable helps, supports, and advices. I cannot end without thanking my lovely family, on whose constant encouragement, support, and love, I have relied throughout my studies. iv
5 Table of Contents Introduction. Statement of the Problem and Thesis Objectives Literature Review Islanding Detection Methods Passive Resident Methods Active Resident Methods Communication-Based Methods Control Strategies for Autonomous Operation of Islanded Systems Thesis Outline Experimental Validation of an Islanding Detection Method Based on Current Injection 9 2. Introduction Islanding Detection Based on Negative-Sequence Currents Injection Test System Performance Evaluation Performance Under UL74 Test Conditions Sensitivity to the Level of Injected Negative-Sequence Currents Sensitivity to the Variation in Load Resistance Sensitivity to Variation in Load Inductance Effect of Grid Imbalance Effect of Load Imbalance Conclusions v
6 3 Non-Detection Zone Analysis of the Negative-Sequence Current Injection Method Introduction Formulation of the Non-Detection Zone Simulation Results Experimental Results Eliminating the NDZ Simulation Results Experimental Results Effect of SCR on the Enhanced Method Conclusions Assessment of an Autonomous Mode Controller for Islanded Single-DG Systems Introduction System Description Control Strategy Robust Stability Analysis Performance Evaluation Voltage Tracking Active Load Change of Load Parameters: Capacitance Change Change of Load Parameters: Resistance Change Nonlinear Load Motor Startup Uninterruptible Operation of a DG Unit During and Subsequent to Islanding Events Transition from a Grid-Connected mode to an Islanded Mode in a Matched Power Condition vi
7 4.6.2 Transition from a Grid-Connected mode to an Islanded Mode in a Mismatched Power Condition Conclusion Islanding Detection and Control of a Two-Parallel DG System Introduction Test System Control Strategy Islanding Detection in a Microgrid under UL74 Test Conditions Islanding Detection in a Two-Parallel DG System Islanding Detection in a Double-DG System Performance Evaluation of the SISO Controller in a Two-Parallel DG System Load Change Disturbance Rejection Transition form a Grid-connected mode to an Islanded mode in a Two-Parallel DG system Transition in a Matched Power Condition Transition in a Mismatched Power Condition Conclusions Conclusions Summary and Conclusions Islanding Detection Method Autonomous Mode Controllers for Single- and multi-dg Systems Contributions Future Work Appendices A SISO Controller 98 A. Introduction A.2 System Description vii
8 A.3 SISO System A.3. Mathematical Model of Islanded System A.3.2 Control Strategy B Robustness Analysis Tools 6 B. Introduction B.2 Definitions B.3 Theorems References viii
9 List of Tables 2. Parameters of the system of Figure Load Parameters The parameters of the system of Figure The parameters of the systems of Figure 5. and Figure A. Parameters of the system of Figure A ix
10 List of Figures 2. Block diagrams of (a) the positive-sequence currents controller and the corresponding subsystem (outlined), and (b) the positive-sequence voltages/currents resolver with embedded PLL [29] Block diagrams of (a) the negative-sequence currents controller and the corresponding subsystem (outlined), and (b) the negative-sequence voltages/currents resolver [29] Schematic diagram of the test system illustrating positive- and negativesequence current injection [3] Schematic diagram of the experimental setup Schematic diagram of the experimental setup based on the UL74 anti islanding test conditions Test system waveforms Under UL74 test conditions: (a) PCC voltages, (b) converter currents, and (c,d) estimated instantaneous positive- and negativesequence components of the PCC voltages Test system waveforms Under UL74 test conditions: (a,b) estimated magnitudes of positive- and negative-sequence PCC voltages and (c) estimated frequency The estimated magnitude of the negative-sequence component of the PCC voltages for three different levels of injected negative-sequence currents Test system waveforms corresponding to different levels of injected current (R=9.6% of rated value): (a) estimated frequency and (b,c) the estimated magnitudes of positive- and negative-sequence components of the PCC voltages 2 x
11 2. Test system waveforms corresponding to different levels of injected current (R=8.3% of rated value): (a) estimated frequency and (b,c) estimated magnitudes of positive- and negative-sequence components of the PCC voltages Test system waveforms when L is changed from its rated value to 2% of the rated value: (a,b) the estimated magnitudes of positive-, and negativesequence PCC voltages and (c) estimated frequency Test system waveforms under unbalanced grid conditions: (a,b) estimated magnitudes of positive- and negative-sequence components of PCC voltages and (c) estimated frequency at the PCC Test system waveforms under load (R) imbalance conditions: (a,b) the estimated magnitudes of positive- and negative-sequence components of PCC voltages and (c) estimated frequency Simulation results of the system in the NDZ: (a) instantaneous voltages at the PCC, (b) positive-sequence component of the PCC voltages, and (c) negativesequence component of the PCC voltages Simulation results of the system of Figure 2.4 for which the system is not within the NDZ: (a) instantaneous voltages at the PCC, (b) positive-sequence component of the PCC voltages, and (c) negative-sequence component of the PCC voltages Experimental results of the system of Figure 2.4 for which the system is in the NDZ: (a) instantaneous voltages at the PCC, (b) positive-sequence component of the PCC voltages, and (c) negative-sequence component of the PCC voltages The negative-sequence current reference signal and its controller Simulation results of the system that uses the enhanced current injection method: (a) instantaneous voltages at the PCC, (b) positive-sequence component of the PCC voltages, and (c) negative-sequence component of the PCC voltages Experimental results of the enhanced current injection method: (a) instantaneous voltages at the PCC, (b) positive-sequence component of the PCC voltages, and (c) negative-sequence component of the PCC voltages xi
12 3.7 The magnitude of the negative-sequence component of the PCC voltages for different values of grid short circuit ratio Schematic diagram of the test system Convex hulls related to the mapping theorem Dynamic response of the islanded system to two step voltage commands: (a) instantaneous voltages of the PCC, (b) converter (load) currents, and (c) control signal Dynamic response of the islanded system to two reference signal changes in the presence of an active load: (a) instantaneous voltages of the PCC, (b) DG unit currents, (c) active load currents, and (d) control signal Dynamic response of the islanded system to a load capacitance change: (a) instantaneous voltages of the PCC, (b) converter (load) currents, and (c) control signal Dynamic response of the islanded system to the load resistance change: (a) instantaneous voltages of the PCC, (b) converter (load) currents, and (c) control signal Dynamic response of the islanded system to the nonlinear load: (a) instantaneous voltages of the PCC, (b) converter (load) currents, and (c) control signal Dynamic response of the islanded system to the motor startup issue: (a) instantaneous voltages of the PCC, (b) motor currents (per unit values based on the motor current rating), and (c) control signal Dynamic response of the SISO-controlled system of Figure 4. to a preplanned islanding event: (a) instantaneous voltages of the PCC and (b) phase-a of the converter currents Dynamic response of the SISO-controlled system of Figure 4. to an accidental islanding event (a) instantaneous voltages of the PCC and (b) phase-a of the converter currents The schematic diagram of the experimental setup xii
13 5.2 The simulation results of the system of Figure 5. under UL74 test conditions during a preplanned islanding event: (a) the PCC instantaneous voltages, (b) the magnitude of the positive-sequence voltages at the PCC, and (c) the magnitude of the negative-sequence voltages at the PCC The simulation results of the system of Figure 5. under UL74 test conditions during a preplanned islanding event: (a) the first DG unit currents and (b) the second DG unit currents The experimental results of the system of Figure 5. under UL74 test conditions during a preplanned islanding event: (a) the PCC instantaneous voltages, (b) the magnitude of the positive-sequence voltages at the PCC, and (c) the magnitude of the negative-sequence voltages at the PCC The experimental results of the system of Figure 5. under UL74 test conditions during a preplanned islanding event: (a) the first DG unit currents and (b) the second DG unit currents The schematic diagram of a microgrid with two PCCs The simulation results of the islanded system of Figure 5.6 under UL74 test conditions during a preplanned islanding event: (a) the PCC instantaneous voltages, (b) the magnitude of the positive-sequence voltages at the PCC, and (c) the magnitude of the negative-sequence voltages at the PCC The simulation results of the islanded system of Figure 5.6 under UL74 test conditions during a preplanned islanding event: (a) the first DG unit currents and (b) the second DG unit currents The simulation results of the islanded system of Figure 5. during load resistance changes: (a) the PCC instantaneous voltages, (b) the magnitude of the positive-sequence voltages at the PCC, (c) the slave DG unit currents, and (d) the master DG unit currents The experimental results of the islanded system of Figure 5. during load resistance changes: (a) the PCC instantaneous voltages, (b) the magnitude of the positive-sequence voltages at the PCC, (c) the slave DG unit currents, and (d) the master DG unit currents xiii
14 5. The simulation results of the islanded system of Figure 5. during disturbances made by the salve DG unit: (a) the PCC instantaneous voltages, (b) the magnitude of the positive-sequence voltages at the PCC, (c) the slave DG unit currents, and (d) the master DG unit currents The experimental results of the islanded system of Figure 5. during disturbances made by the salve DG unit: (a) the PCC instantaneous voltages, (b) the magnitude of the positive-sequence voltages at the PCC, (c) the slave DG unit currents, and (d) the master DG unit currents The simulation results of the system of Figure 5. during a transition from a grid-connected mode to an islanded mode in a matched power condition: (a) the PCC instantaneous voltages, (b) the magnitude of the positive-sequence voltages at the PCC, and (c) the magnitude of the negative-sequence voltages at the PCC The simulation results of the system of Figure 5. during a transition from a grid-connected mode to an islanded mode in a matched power condition: (a) the slave DG unit currents and (b) the master DG unit currents The experimental results of the system of Figure 5. during a transition from a grid-connected mode to an islanded mode in a matched power condition: (a) the PCC instantaneous voltages, (b) the magnitude of the positive-sequence voltages at the PCC, and (c) the magnitude of the negative-sequence voltages at the PCC The experimental results of the system of Figure 5. during a transition from a grid-connected mode to an islanded mode in a matched power condition: (a) the slave DG unit currents and (b) the master DG unit currents The simulation results of the system of Figure 5. during a transition from a grid-connected mode to an islanded mode in a mismatched power condition: (a) PCC instantaneous voltages, (b) the magnitude of the positive-sequence voltages at the PCC, and (c) the magnitude of the negative-sequence voltages at the PCC xiv
15 5.8 The simulation results of the system of Figure 5. during a transition from a grid-connected mode to an islanded mode in a mismatched power condition: (a) the slave DG unit currents and (b) the master DG unit currents The experimental results of the system of Figure 5. during a transition from a grid-connected mode to an islanded mode in a mismatched power condition: (a) PCC instantaneous voltages, (b) the magnitude of the positive-sequence voltages at the PCC, and (c) the magnitude of the negative-sequence voltages at the PCC The experimental results of the system of Figure 5. during a transition from a grid-connected mode to an islanded mode in a mismatched power condition: (a) the slave DG unit currents and (b) the master DG unit currents A. Schematic diagram of a grid-interfaced DG unit and its controller [3].... A.2 Structure of SISO controller for the islanded system [3] B. Geometry associated with the Mapping Theorem [3] xv
16 List of Abbreviations DER: DG: dq: PCC: NDZ: UL: OFP/UFP: OVP/UVP: PJD: SFS: SVS: AFD: SMS: PLC: SCADA: UPS: SISO: MIMO: MISO: LTI: VSC: PLL: PWM: UTSP: SCR: FFT: KVL: Distributed Energy Resource Distributed Generation direct-quadrature Point of Common Coupling Non-Detection Zone Underwriters Laboratories, Inc. Over/Under Frequency Protection Over/Under Voltage Protection Phase Jump Detection Sandia Frequency Shift Sandia Voltage Shift Active Frequency Drift Slip Mode frequency Shift Power Line Carrier Supervisory Control And Data Acquisition Uninterruptible Power Supply Single-Input Single-Output Multiple-Input Multiple-Output Multiple-Input Single-Output Linear Time Invariant Voltage-Sourced Converter Phase-Locked Loop Pulse Width Modulated Unified Three-phase Signal Processor Short-Circuit-Ratio Fast Fourier Transform Kirchhoff Voltage Law xvi
17 List of Symbols e: error signal f sw : switching frequency f res : load resonant frequency i: AC current s: Laplace transform variable t: continuous time u: input signal v: voltage x: state variable y: output signal θ: phase angle ω o : center frequency xvii
18 Chapter Introduction. Statement of the Problem and Thesis Objectives In the context of distributed energy resource (DER) units, an island is formed when one or more DER units are disconnected from the rest of the power system and remain operational. This process is called an islanding phenomenon and can occur due to preplanned or accidental events. The accidental islanding events, which can take place due to faults, may result in a host of steady-state operational issues, control problems, and protection shortcomings including safety issues and inadequate grounding []. Therefore, the current utility practice and standards [,2] require that the islanding event be detected as fast as possible, and the island be de-energized upon detection of the islanding phenomenon. However, the trends in the utilization of DER units indicate that the islanded operation will be accepted in the future. If the islanded operation of a DER unit is permitted [3,4], the islanding event should be detected as fast as possible to allow smooth transition from a grid-connected mode to the islanded mode of operation. Thus, whether the autonomous operation is permitted or not, fast islanding detection is required. In grid-connected modes, the existing electronically-coupled distributed generation (DG) units adopt conventional dq current control schemes [5,6] to control power flow. Prior to an DER units are described as small-scale electric power generators located next to and connected to the load being fed either with or without the utility grid. The DER units are also referred to as distributed generation (DG) units.
19 islanding event, the frequency and the voltages at the point of common coupling (PCC) of a DG unit is mainly imposed by the grid. However, subsequent to the islanding event, lack of control over the voltages and the frequency, based on the dq current control strategy, can result in instability of the island. Therefore, subsequent to an islanding phenomenon and upon its detection, if the islanded mode of operation is permitted, the control strategy has to be changed or modified to retain control over the voltage and the frequency of the island. Therefore, two major challenges of the islanded mode of operation are (i) providing DG units with fast islanding detection capability and (ii) adopting controllers that are capable of controlling DG units in both grid-connected and islanded modes. An islanding detection method may have a non-detection zone (NDZ). The NDZ is mainly associated with a range of local loads, i.e., loads inside the potential island, for which the islanding detection method fails to detect islanding events [7]. All passive islanding detection methods suffer from NDZs [8]. However, active islanding methods, which are commonly based on intentional injection of a disturbance signal to the system, exhibit smaller NDZs. In order to fully eliminate any NDZ, islanding detection methods that are not resident in the inverter, i.e., communication-based islanding detection methods, are required. Any islanding detection method is usually evaluated by its NDZ and islanding detection time (run-on time 2 ). Therefore, a desirable islanding detection method must have a short run-on time and a small NDZ. Note that there are usually several small DG units operating in an island rather than a large one. Thus, to specify the NDZ of an islanding detection method, both single and multiple DG unit systems should be analyzed. A relatively fast and accurate islanding detection method for a single-dg unit, based on injection of a negative-sequence current component has been introduced in [3]. Reference [3] also introduces several control strategies for a DG unit subsequent to an islanding event. The NDZ of the proposed islanding detection method is neither identified nor discussed. The main objectives of this thesis are: To experimentally validate the performance of the islanding detection method of [3] for a single DG unit under various conditions, including: UL74 test conditions, 2 Run-on time is the time interval between the instant at which the islanding event occurs and the instant that the islanding event is detected. 2
20 various levels of injected negative-sequence current component, grid imbalance, and load imbalance. To analytically investigate and formulate the NDZ of the islanding detection method of [3]. To propose a method to prevent/minimize the NDZ of the proposed islanding detection method. To experimentally demonstrate that the NDZ can occur and verify that it can be prevented based on the proposed countermeasure. To analytically determine the robustness margin of an autonomous mode controller originally proposed in [3] and to experimentally evaluate its performance. To experimentally evaluate the impact of the proposed islanding detection method of [3] on the control and transients of a DG unit, subsequent to an islanding event. To evaluate this effect, transition from a grid-connected mode of operation to an islanded mode of operation, in both matched and mismatched power conditions are carried out by adopting the islanded mode controller proposed in [3]. To evaluate the performance of the islanding detection method in a two-parallel DG system, based on digital time-domain simulation and experimentation. To propose a control strategy for an islanded two-parallel DG system and to experimentally evaluate its performance. To evaluate the effect of the islanding detection method on the control and transients of a two-parallel DG system, based on digital time-domain simulation and experimentation. 3
21 .2 Literature Review.2. Islanding Detection Methods This section provides an overview of various islanding detection methods. There are three major categories for islanding detection methods: passive resident methods, active resident methods, and communication-based methods. Principles of operation, merits, and drawbacks of these islanding detection methods are detailed in [9]..2.. Passive Resident Methods Passive resident methods are based on the detection of abnormalities in electrical signals at the PCC of a DG unit. The three main passive methods, resident in the coupling-converter of a DG unit, are based on [9-]: over/under voltage and over/under frequency protection (OVP/UVP and OFP/UFP), phase jump detection (PJD) or power factor detection, detection of voltage harmonics. Subsequent to an islanding event, deviations in the magnitude and rates of the change of electrical signals at the PCC, e.g., voltages and frequency, can violate permitted thresholds and be exploited for islanding detection. However, in a matched power condition between the PCC and the grid, these deviations are not noticeable and do not violate the permitted thresholds within acceptable time intervals. In such cases, the islanding detection method is within its NDZ. The NDZ can be reduced by decreasing the thresholds values, however, this can result in nuisance/unwanted trips. Therefore, any passive resident method suffers from a considerable size NDZ Active Resident Methods An active resident method artificially creates abnormalities in the PCC signals that can be detected subsequent to an islanding event. The proposed/applied active resident islanding detection methods include: 4
22 Sandia Frequency Shift (SFS) and Sandia Voltage Shift (SVS) [2], frequency bias or active frequency drift (AFD) [3], slip mode frequency shift (SMS) or phase-locked loop slip [4], frequency jump or Zebra method [9], negative-sequence currents injection [3]. Due to the artificial creation of abnormalities in the PCC signals, an active resident method usually has a smaller NDZ compared to that of a passive method. The reason is that in a matched power condition between the PCC and the grid, the creation of abnormalities often result in a mismatched power condition. Therefore, the monitored electrical signals violate their thresholds and the islanding event can be detected. However, in a mismatched power condition, the injected signal by the interface converter may coincidentally create a matched-power condition. Therefore, an island can be formed while the islanding detection method fails to detect it. Although active methods provide more reliable islanding detection methods than passive methods, they can adversely affect the power quality of the system in the grid-connected mode. Under specific conditions, the injected signal for islanding detection may even result in instability of the system in a grid-connected mode [5]. In this thesis, an active method, based on negative-sequence currents injection [3], is used to detect islanding events. This method, which is detailed in Section 2.2, can be in its NDZ when the load parameters are not balanced. In such a case, the load imbalance can produce a small negative-sequence voltages component at the PCC. This negative-sequence voltages component can either add to or cancel out the negative-sequence voltages produced by the negative-sequence currents injection. When the two negative-sequence voltages components cancel out, the method is within its NDZ. To overcome this shortcoming, a modified approach for negative-sequence currents injection is proposed in this thesis. 5
23 .2..3 Communication-Based Methods Communication-based methods are based on transmission of data between a DG unit and the host utility system. The data is analyzed by the DG unit to determine if the operation of the DG should be halted. The three major methods of this classification are based on using: power line carrier (PLC) communications [6,7], signal produced by disconnect switches [9], supervisory control and data acquisition (SCADA) [9]. All communication-based methods are fast and practically have no NDZ. However, a PLC-based method fails to detect an islanding event if the system external to the DG replicates the carrier signal. The main drawbacks of these islanding detection methods are their high cost and complexity. The infrastructure required to transmit the data to all DG units in the potential island is relatively expensive. Moreover, the signal, which is supposed to be transmitted as an indication of islanding event can be polluted by other communication signals, e.g., automatic meter reading [9] schemes. Currently, the communication-based methods are not considered as economically viable islanding detection methods for relatively small-size DG units..2.2 Control Strategies for Autonomous Operation of Islanded Systems In this section, some of the existing control strategies for the autonomous operation of multiple DG units are briefly explained. Note that since prior to an islanding event, the voltages and the frequency of the PCC are mainly dictated by the grid, subsequent to an islanding event and due to the disconnection of the grid, the islanded mode control strategies should be capable of maintaining both voltages and frequency. The augmented dq-current control strategy, which is based on frequency/power and voltage/reactive-power droop characteristics, is usually adopted for multiple DG units in 6
24 an islanded system. This method is based on frequency/power and voltage/reactive-power droop characteristics of each DG unit and has been extensively investigated [4,8-22]. In this strategy, every DG unit is equipped with two droop characteristics: (i) voltage magnitude as a linear function of reactive power and (ii) frequency as a linear function of real power. Using the droop characteristics, the voltage profile is dominantly maintained by the reactive power flow of the DG units, and the frequency is regulated by the real power flow. Since this approach does not directly incorporate the load dynamics in the control loop, large and/or fast load changes may result in either poor dynamic response or even voltage/frequency instability. Another approach that is utilized to control DG units in an islanded mode of operation is reported in [23]. This method, which also regulates the magnitude of the PCC voltages and the frequency of the island, can fail if the load dynamics are fairly fast and/or dynamic reactive power sources, e.g., synchronous machine-based DG units and/or static compensators, exist in the island. In addition to the above control strategies, several robust control strategies have been reported for uninterruptible power supply (UPS) systems [24-28] that can be tailored for islanded systems including DG units. Reference [3] provide an overview of each method and the potential merits and limitations. Reference [3] also presents three control strategies for the autonomous operation of an islanded DG unit. One of them, i.e., the single-input single-output (SISO) controller, is widely utilized in this thesis to regulate the voltages and frequency of islanded systems under balanced conditions. The SISO controller utilizes an internal oscillator to regulate the frequency of the island and uses a feedback loop to control the magnitude of the PCC voltages. The second controller proposed in [3] is a MIMO controller, which also uses an internal oscillator to maintain the frequency. However, in the MIMO control strategy both d- and q-component of the voltage are maintained at their reference values. The third controller proposed in [3] is an abc-frame controller that is designed to control the islanded systems under unbalanced conditions. The abc-frame controller also adopts an internal oscillator to control the frequency in an open loop manner and utilizes sinusoidal references to regulate the voltages of the island in a closed loop manner. 7
25 .3 Thesis Outline This thesis consists of six chapters: Chapter 2 experimentally validates the performance of the islanding detection method of [3]. The islanding detection method is evaluated under UL74 test conditions. Moreover, several experiments are carried out to investigate the sensitivity of the method with respect to (i) the variations in the load resistance and inductance, (ii) the level of injected negative-sequence currents, and (iii) the grid and load imbalance. In Chapter 3, the non-detection zone (NDZ) of the islanding detection method of Chapter 2 is analytically determined, and it is shown that the method has a non-zero NDZ. The analytical results are validated based on simulation results in PSCAD/EMTDC software environment, and test results. Moreover, to eliminate the NDZ of the method, the negative-sequence current injection approach is modified. The new approach in also validated based on both simulation and experimental results. In Chapter 4, the robustness margin of the SISO controller of [3] is analytically determined, and moreover, its performance is experimentally evaluated. Then, adopting the islanding detection method of Chapter 2, the viability of transition phenomenon in a single-dg system from a grid connected mode to an islanded mode is experimentally validated. Chapter 5 investigates the performance of the islanding detection method of Chapter 2 in systems including two DG units and moreover, proposes a new control strategy for islanded multi-dg systems. It also shows that adopting the proposed control strategy, the islanding detection method can be adopted for a smooth transition from a grid-connected mode to an islanded mode of operation in two-parallel DG systems. The studies are conducted based on time-domain simulations in the PSCAD/EMTDC environment and validated based on test results. Chapter 6 presents the thesis conclusions. 8
26 Chapter 2 Experimental Validation of an Islanding Detection Method Based on Current Injection 2. Introduction In the context of Distributed Energy Resource (DER) units, an island is formed by the disconnection of one or more distributed generation (DG) units from the utility grid due to accidental or preplanned events, while they are still operational. Although existing standards [,2] prohibit the autonomous operation of DG units due to potential safety issues and inadequate grounding, the high depth of penetration of DG units and economical aspects indicate that the islanded mode of operation of DG units will be a viable operational mode [3]. The most significant challenges of the islanded mode of operation are providing DG units with (i) fast islanding detection methods and (ii) controllers that are capable of controlling DG units in both grid-connected and islanded mode of operations. For a smooth transition from a grid-connected mode to an islanded mode of operation of a DG unit, fast islanding detection is essential. The reason is that subsequent to the islanding event, based on the existing and prevalent dq current control strategies adopted in the grid-connected mode, there is no control over the frequency and the voltages of the Point of Common Coupling (PCC). In an accidental islanding event, the grid and the PCC 9
27 may be in a mismatched power condition, and therefore, subsequent to the islanding event, the voltages and the frequency of the island rapidly deviate from their rated values. Such deviations may violate permissible limits [2], and therefore, the island shuts down shortly after the islanding event. Moreover, such deviations may result in long transients and/or even instability of the island. Therefore, for a smooth transition to an autonomous mode of operation, the islanding event has to be rapidly detected, and upon its detection, a new control strategy has to be activated to regulate the voltages and the frequency of the island. This chapter presents the experimental validation of an active islanding detection method for a DG unit, which is coupled to a utility grid through a three-phase Voltage-Sourced Converter (VSC) [3]. The method is based on injecting a negative-sequence currents component through the VSC and detecting and quantifying the corresponding negative-sequence voltages at the PCC of the DG unit. The negative-sequence currents component is injected by a negative-sequence currents controller, which is adopted as a complementary part of the conventional VSC current control scheme [5,6]. To evaluate the performance of the islanding detection method, an experimental test system is adopted, which initially works in a grid-connected mode of operation and adopts the conventional dq current control scheme [5,6] to regulate power flow. Subsequent to an islanding event, which can be preplanned or accidental, the islanding detection method detects the event, while the system is still utilizing the dq current control strategy. Adopting the UL74 anti-islanding standard test, the performance of the method is experimentally validated and reported in this chapter. In addition, the impacts of grid voltage imbalance, load imbalance, and deviations in the UL74 test conditions are experimentally investigated. The experimental results show that based on the injection of a pre-specified amount of negative-sequence currents, islanding events can be detected within the maximum of 6 ms. This chapter is organized as follows. Section 2.2 briefly explains the principles of operation of the islanding detection method. The test system is described in Section 2.3. The performance of the method is experimentally evaluated and reported in Section 2.4, and Section 2.5 concludes the chapter.
28 2.2 Islanding Detection Based on Negative-Sequence Currents Injection This active islanding detection method is originally proposed and detailed in [3]. The method is based on the injection of negative-sequence, fundamental-frequency currents component through the interface VSC, and detecting and quantifying the corresponding negative-sequence voltages at the PCC of the DG unit. To inject the negative-sequence currents, the conventional positive-sequence currents controller of the VSC is augmented with a negative-sequence currents controller [29]. Figure 2. (a) shows a block diagram of the VSC d- and q-axis current controllers, the decoupling stage, and a model of the VSC system for positive-sequence voltages/currents components [5]. Figure 2. (b) shows the abc to dq transformation block and its related PLL, which provides the required transformation angle, i.e., θ. Figure 2.2 (a) is a negative-sequence version of Figure 2. (a) and shows the control strategy adopted for the negative-sequence currents injection. Figure 2.2 (b) shows the abc to dq transformation block for the negative-sequence voltages and currents. Note that in contrast to the positive-sequence control scheme, the transformation angle is θ, while θ is provided by the PLL of the positive-sequence currents controller. Figure 2.3 shows a simplified schematic representation of the test system. In the gridconnected mode, adopting the conventional and the complementary dq current control schemes, the VSC operates as a current source and injects both negative- and positivesequence currents. When switch S is closed, the voltages and frequency at the PCC are dominantly dictated by the grid. Therefore, balanced positive-sequence voltages form at the PCC, which contain no negative-sequence component. Setting a matched power condition between the PCC and the grid, the RLC load draws all of the positive-sequence currents injected by the VSC, and the injected negative-sequence currents are absorbed by the grid, as shown in Figure 2.3. Subsequent to an islanding event, due to the opening of switch S, the negative-sequence currents also flow into the load, and consequently, the PCC voltages become unbalanced. If the per-unit value of the negative-sequence voltages at the PCC is greater than a pre-specified level, e.g., three percent, the system is considered to be in the islanded mode.
29 + V sd + I dref + I d F n (s) F n (s) + Î d + e d K i (s) + u d + Vˆsd ωˆ L f + V sd + V td ω L f L f s + R f + I d + I q + I qref + V sq F n (s) F n (s) + Î q + e q K i (s) + u q ωˆ L f + Vˆsq + V tq ω L f + V sq L f s + R f + I q v sa v sb v sc i ta i tb i tc T (θˆ) θˆ ωˆ H(s) + V sd + V sq ˆ ω ω ˆ θ θ + T (θˆ) I d + I q Figure 2.. Block diagrams of (a) the positive-sequence currents controller and the corresponding subsystem (outlined), and (b) the positive-sequence voltages/currents resolver with embedded PLL [29] Note that if the matched power condition between the grid and the PCC is not satisfied, the islanding detection method is still applicable. The only difference is that in a mismatched power condition, prior to the islanding event, not only the negative-sequence currents are absorbed by the grid, but also either a portion of the injected positive-sequence currents flows into the grid or an amount of positive-sequence currents flows from the grid into the load. However, subsequent to the islanding event, the converter injected negative- and positive-sequence currents are absorbed by the load branch, and thus, the per-unit value of the negative-sequence voltages at the PCC, corresponding to the negative-sequence currents, is detected and quantified as the islanding detection signal. 2
30 V sd I dref I d F n (s) F n (s) Î d e d K i (s) u d Vˆsd ωˆ L f V td V sd ω L f L f s + R f I d I q I qref V sq F n (s) F n (s) Î q e q K i (s) u q ωˆ L f Vˆsq V tq ω L f V sq L f s + R f I q v sa v sb v sc T ( θˆ) V sd V sq θˆ i ta i tb i tc T ( θˆ) I d I q Figure 2.2. Block diagrams of (a) the negative-sequence currents controller and the corresponding subsystem (outlined), and (b) the negative-sequence voltages/currents resolver [29] Figure 2.3. Schematic diagram of the test system illustrating positive- and negative-sequence current injection [3] 2.3 Test System This section presents the experimental setup that is used to validate the performance of the negative-sequence currents injection method. To implement the control system, a Real 3
31 Figure 2.4. Schematic diagram of the experimental setup Time (RT)-Linux based controller, which provides a C programming environment, is used. Control and/or signal processing algorithms are first discretized and then developed into C codes. The RT-Linux system runs the C programming codes in real time. Figure 2.4 shows a single-line diagram of the experimental setup in which the DG unit includes a DC source (V dc ), a VSC unit, and a series filter. The VSC filter is represented by inductor L t for each phase. The load at the PCC is a parallel RLC. The study system parameters are given in Table 2.. In order to extract the magnitude of the positive- and negative-sequence voltages and the frequency of the PCC voltages, a unified three-phase signal processor (UTSP) [3] is utilized. The UTSP system, which is basically a three-phase enhanced PLL, is capable of decomposing a set of three-phase signals into its symmetrical components, even in a highly polluted environment. To implement the UTSP system, also the C programming environment of the RT-Linux system is used. Data acquisition is accomplished by a Yokogawa PZ4 Power Analyzer. This power analyzer is capable of capturing input waveforms with high-precision sampling (maximum 5 MS/s) while its measurement bandwidth covers a wide range from DC to 2 MHz. It is also equipped with Fast Fourier Transform (FFT) functions, harmonic analysis tools (up to 4
32 Table 2.. Parameters of the system of Figure 2.4 Quantity Value P.U. Comment L t 3 mh.2 pu Inductance of VSC filter VSC rated power 2.4 kw pu S base = 2.4 kva VSC terminal voltage (line-line) 5 V (rms) pu V base = 5 V f sw 3 khz PWM carrier frequency R 5.5 Ω pu Load nominal resistance L 7.8 mh.53 pu Load nominal inductance C 9 µf.87 pu Load nominal capacitance C Q = R L.87 Load quality factor f res = 2π LC 6 Hz Load resonant frequency f 6 Hz System nominal frequency V s (line-line) 5 V (rms) pu Grid nominal voltage V dc 23 V DC bus voltage 5 th order), and the capability of power calculations on fluctuating inputs. The acquired data are first stored on the PZ4 internal memory and then, transferred to a PC and plotted/displayed using MATLAB software. 2.4 Performance Evaluation In this section, UL74 standard test is adopted to test the proposed islanding detection method. In addition, several tests including sensitivity to (i) variations in load parameters, (ii) various levels of injected negative-sequence currents, (iii) grid imbalance, (iv) and load imbalance are carried out. Note that in these case studies, the VSC does not inject reactive power (unity power factor at the PCC), and the reference value for the q-component of the converter current is set at A. 5
33 Figure 2.5. Schematic diagram of the experimental setup based on the UL74 anti islanding test conditions 2.4. Performance Under UL74 Test Conditions In this experiment, the performance of the method is evaluated under the UL74 antiislanding test conditions [2]. Figure 2.5 presents the schematic diagram of the test system for islanding detection according to UL74 standard. The UL74 standard anti-islanding test requires that a three-phase VSC be connected to a utility grid, and a parallel RLC load be applied to each phase. The load circuit should have a quality factor Q = R.8 or less. Moreover, the inductance and the capacitance of the load should be selected such that their resonant frequency equals the fundamental frequency of the system, i.e., 2π LC C of L = 6 ±. Hz. Satisfying this condition, the overall load circuit has a unity power factor and appears to be purely resistive. Moreover, the test circuit real power dissipation should be equal to the rated power output of the VSC [2]. The load and system parameters for the experimental setup are given in Table 2.. Prior to the islanding event, the VSC is injecting %5 of the rated load current as the negativesequence currents for islanding detection. Moreover, the positive-sequence currents are set such that the grid currents are zero, i.e., there is a matched power condition between the 6
34 grid and the PCC. Thus, the positive-sequence currents of the VSC are almost equal to their rated values. The islanding event is imposed by opening switch S at instant t = 57 ms. Since there is a matched power condition between the grid and the PCC, subsequent to the islanding event, the PCC voltages and the converter currents do not change significantly and therefore, cannot be used for islanding detection. Figures 2.6 (a) and (b) show the instantaneous PCC voltages and the converter currents, respectively. Mainly due to the injection of the negative-sequence currents, the PCC voltages (subsequent to the islanding event) and the converter currents (prior and subsequent to the islanding event) are not balanced. Figures 2.6 (c) and (d) show the estimated instantaneous waveforms of the positiveand negative-sequence voltages at the PCC, respectively. The positive-sequence voltages have no significant change due to the islanding event. However, subsequent to the islanding event, the negative-sequence voltages component appears at the load terminals and reaches the steady state level in about three cycles and can be used to reliably identify the islanding event. It should be noted that the UL74 anti-islanding test asks for run-on times of two seconds and less while the proposed method can identify islanding events within 6 ms if the load parameters are not in the non-detection zone. The estimated magnitudes of the positive- and negative-sequence components of the PCC voltages, and the estimated frequency are shown in Figure 2.7 (a), (b), and (c), respectively. Figure 2.7 shows that the estimated frequency and the magnitude of the positive-sequence component of the PCC voltages are within the acceptable limits [2] prior to and after the islanding event and therefore, cannot be used for islanding detection. However, the magnitude of the negative-sequence voltages provides a reliable islanding detection signal Sensitivity to the Level of Injected Negative-Sequence Currents In this section, the performance of the islanding detection method with respect to the level of negative-sequence currents injection is evaluated. Three values for the injected negativesequence currents, i.e.,.5%, 3%, and 5% of the rated current, are considered. The system 7
CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE
98 CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE 6.1 INTRODUCTION Process industries use wide range of variable speed motor drives, air conditioning plants, uninterrupted power supply systems
More informationCONVERTERS IN POWER VOLTAGE-SOURCED SYSTEMS. Modeling, Control, and Applications IEEE UNIVERSITATSBIBLIOTHEK HANNOVER. Amirnaser Yazdani.
VOLTAGE-SOURCED CONVERTERS IN POWER SYSTEMS Modeling, Control, and Applications Amirnaser Yazdani University of Western Ontario Reza Iravani University of Toronto r TECHNISCHE INFORMATIONSBIBLIOTHEK UNIVERSITATSBIBLIOTHEK
More informationIslanding Detection Techniques for Distributed Energy Resources-Review
Islanding Detection Techniques for Distributed Energy Resources-Review Janki N. Patel 1 P.G. Student, Department of Electrical Engineering, SCET, Surat, Gujarat, India 1 ABSTRACT: Distributed generators
More informationCHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS
66 CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS INTRODUCTION The use of electronic controllers in the electric power supply system has become very common. These electronic
More informationLavopa, Elisabetta (2011) A novel control technique for active shunt power filters for aircraft applications. PhD thesis, University of Nottingham.
Lavopa, Elisabetta (211) A novel control technique for active shunt power filters for aircraft applications. PhD thesis, University of Nottingham. Access from the University of Nottingham repository: http://eprints.nottingham.ac.uk/1249/1/elisabetta_lavopa_thesis.pdf
More informationCHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS
86 CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 5.1 POWER QUALITY IMPROVEMENT This chapter deals with the harmonic elimination in Power System by adopting various methods. Due to the
More informationA Static Synchronous Compensator for Reactive Power Compensation under Distorted Mains Voltage Conditions
10 th International Symposium Topical Problems in the Field of Electrical and Power Engineering Pärnu, Estonia, January 10-15, 2011 A Static Synchronous Compensator for Reactive Power Compensation under
More informationIslanding Detection and Frequency Circuit Measurement by Power Distribution Relation Depending on the Angle
215 International Journal of Smart Electrical Engineering, Vol.5, No.4, Fall 2016 ISSN: 2251-9246 pp. 215:220 Islanding Detection and Frequency Circuit Measurement by Power Distribution Relation Depending
More informationPower Quality enhancement of a distribution line with DSTATCOM
ower Quality enhancement of a distribution line with DSTATCOM Divya arashar 1 Department of Electrical Engineering BSACET Mathura INDIA Aseem Chandel 2 SMIEEE,Deepak arashar 3 Department of Electrical
More informationCHAPTER 5 DESIGN OF DSTATCOM CONTROLLER FOR COMPENSATING UNBALANCES
86 CHAPTER 5 DESIGN OF DSTATCOM CONTROLLER FOR COMPENSATING UNBALANCES 5.1 INTRODUCTION Distribution systems face severe power quality problems like current unbalance, current harmonics, and voltage unbalance,
More informationLoad Compensation at a Reduced DC Link Voltage by Using DSTATCOM with Non-Stiff Source
International Journal of Emerging Engineering Research and Technology Volume 2, Issue 3, June 2014, PP 220-229 ISSN 2349-4395 (Print) & ISSN 2349-4409 (Online) Load Compensation at a Reduced DC Link Voltage
More informationAn Adaptive V-I Droop Scheme for Improvement of Stability and Load Sharing In Inverter-Based Islanded Micro grids
IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331 PP 33-40 www.iosrjournals.org An Adaptive V-I Droop Scheme for Improvement of Stability and Load Sharing
More informationISLANDING DETECTION IN DISTRIBUTION SYSTEM EMBEDDED WITH RENEWABLE-BASED DISTRIBUTED GENERATION. Saurabh Talwar
ISLANDING DETECTION IN DISTRIBUTION SYSTEM EMBEDDED WITH RENEWABLE-BASED DISTRIBUTED GENERATION by Saurabh Talwar B. Eng, University of Ontario Institute of Technology, Canada, 2011 A Thesis Submitted
More informationInvestigation of D-Statcom Operation in Electric Distribution System
J. Basic. Appl. Sci. Res., (2)29-297, 2 2, TextRoad Publication ISSN 29-434 Journal of Basic and Applied Scientific Research www.textroad.com Investigation of D-Statcom Operation in Electric Distribution
More informationBED INTERCONNECTION TECHNICAL REQUIREMENTS
BED INTERCONNECTION TECHNICAL REQUIREMENTS By Enis Šehović, P.E. 2/11/2016 Revised 5/19/2016 A. TABLE OF CONTENTS B. Interconnection Processes... 2 1. Vermont Public Service Board (PSB) Rule 5.500... 2
More informationA Novel Active Anti-Islanding Protection Scheme for Grid-Interactive Roof-Top Solar PV System
A Novel Active Anti-Islanding Protection Scheme for Grid-Interactive Roof-Top Solar PV System Rohith Varier, Student member, IEEE and Naran M. Pindoriya, Member, IEEE Electrical Engineering, Indian Institute
More informationImprovement of Power Quality Using Hybrid Active Power Filter in Three- Phase Three- Wire System Applied to Induction Drive
Improvement of Power Quality Using Hybrid Active Power Filter in Three- Phase Three- Wire System Applied to Induction Drive B. Mohan Reddy 1, G.Balasundaram 2 PG Student [PE&ED], Dept. of EEE, SVCET, Chittoor
More informationDRIVE FRONT END HARMONIC COMPENSATOR BASED ON ACTIVE RECTIFIER WITH LCL FILTER
DRIVE FRONT END HARMONIC COMPENSATOR BASED ON ACTIVE RECTIFIER WITH LCL FILTER P. SWEETY JOSE JOVITHA JEROME Dept. of Electrical and Electronics Engineering PSG College of Technology, Coimbatore, India.
More informationMODELING AND ANALYSIS OF IMPEDANCE NETWORK VOLTAGE SOURCE CONVERTER FED TO INDUSTRIAL DRIVES
Int. J. Engg. Res. & Sci. & Tech. 2015 xxxxxxxxxxxxxxxxxxxxxxxx, 2015 Research Paper MODELING AND ANALYSIS OF IMPEDANCE NETWORK VOLTAGE SOURCE CONVERTER FED TO INDUSTRIAL DRIVES N Lakshmipriya 1* and L
More informationIslanding Detection Technique based on Simulation of IEEE16 Bus System
Islanding Detection Technique based on Simulation of IEEE16 Bus System 1 Mahesh M, 2 Kusuma Devi G.H. 1 PG Scholar, 2 Research Scholar Jain University Bengaluru. Dept. of Electrical and Electronics Engineering.
More informationWILEY CONTROL OF POWER INVERTERS IN RENEWABLE ENERGY AND SMART GRID INTEGRATION. Qing-Chang Zhong. Tomas Hornik IEEE PRESS
CONTROL OF POWER INVERTERS IN RENEWABLE ENERGY AND SMART GRID INTEGRATION Qing-Chang Zhong The University of Sheffield, UK Tomas Hornik Turbo Power Systems Ltd., UK WILEY A John Wiley & Sons, Ltd., Publication
More informationChapter 10: Compensation of Power Transmission Systems
Chapter 10: Compensation of Power Transmission Systems Introduction The two major problems that the modern power systems are facing are voltage and angle stabilities. There are various approaches to overcome
More informationHybrid Anti-Islanding Algorithm for Utility Interconnection of Distributed Generation
Hybrid Anti-Islanding Algorithm for Utility Interconnection of Distributed Generation Maher G. M. Abdolrasol maher_photo@yahoo.com Dept. of Electrical Engineering University of Malaya Lembah Pantai, 50603
More informationStudy of Centralized Anti-Islanding Method on Large-Scale Photovoltaic Power Plants
4th International Conference on Machinery, Materials and Information Technology Applications (ICMMITA 2016) Study of Centralized Anti-Islanding Method on Large-Scale Photovoltaic Power Plants Chen-Xin
More informationChapter 2 MODELING AND CONTROL OF PEBB BASED SYSTEMS
Chapter 2 MODELING AND CONTROL OF PEBB BASED SYSTEMS 2.1 Introduction The PEBBs are fundamental building cells, integrating state-of-the-art techniques for large scale power electronics systems. Conventional
More informationImpact of High PV Penetration on Grid Operation. Yahia Baghzouz Professor of Electrical engineering University of Nevada Las Vegas
Impact of High PV Penetration on Grid Operation Yahia Baghzouz Professor of Electrical engineering University of Nevada Las Vegas Overview Introduction/Background Effects of High PV Penetration on Distribution
More informationImprovement of Voltage Profile using D- STATCOM Simulation under sag and swell condition
ISSN (Online) 232 24 ISSN (Print) 232 5526 Vol. 2, Issue 7, July 24 Improvement of Voltage Profile using D- STATCOM Simulation under sag and swell condition Brijesh Parmar, Prof. Shivani Johri 2, Chetan
More informationStability Enhancement for Transmission Lines using Static Synchronous Series Compensator
Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator Ishwar Lal Yadav Department of Electrical Engineering Rungta College of Engineering and Technology Bhilai, India
More informationChapter 2 Shunt Active Power Filter
Chapter 2 Shunt Active Power Filter In the recent years of development the requirement of harmonic and reactive power has developed, causing power quality problems. Many power electronic converters are
More informationA novel active current disturbance method
, pp.60-64 http://dx.doi.org/10.14257/astl.2015.111.12 A novel active current disturbance method Wu Tiezhou *, Xiong Jinlong, Wu Xiaomin, Luo Meng Hubei University of technology, Hubei collaborative Innovation
More informationA Simple Technique for Islanding Detection with Negligible Nondetection Zone
A Simple Technique for Islanding Detection with Negligible Nondetection Zone The MIT Faculty has made this article openly available. Please share how this access benefits you. Your story matters. Citation
More informationMicrogrid Connection Management based on an Intelligent Connection Agent
Microgrid Connection Management based on an Intelligent Connection Agent J. Rocabert 1, Student Member, IEEE, G. Azevedo 2, Student Member, IEEE, I. Candela 1, Member, IEEE, R. Teoderescu 3, Member, IEEE,
More informationSUPERVISORY HYBRID CONTROL OF A WIND ENERGY CONVERSION AND BATTERY STORAGE SYSTEM
SUPERVISORY HYBRID CONTROL OF A WIND ENERGY CONVERSION AND BATTERY STORAGE SYSTEM by Muhammad Shahid Khan A dissertation submitted in conformity with the requirements for the degree of Doctor of Philosophy
More informationPERFORMANCE OF DISTRIBUTION STATIC COMPENSATOR IN LOW VOLTAGE DISTRIBUTION SYSTEM
PERFORMANCE OF DISTRIBUTION STATIC COMPENSATOR IN LOW VOLTAGE DISTRIBUTION SYSTEM Bhupali P. Kumbhar 1, Prof. V. V. Khatavkar 2 1 PG Student, Dept. of Electrical Engineering, 2 Asst. Professor, Dept. of
More informationControl of Power Converters for Distributed Generation
Mechatronics Industrial Advisory Board 2004 Control of Power Converters for Distributed Generation Ph.D. Student: Min Dai Advisor: Prof. Ali Keyhani Department of Electrical and Computer Engineering The
More informationCHAPTER 3 COMBINED MULTIPULSE MULTILEVEL INVERTER BASED STATCOM
CHAPTER 3 COMBINED MULTIPULSE MULTILEVEL INVERTER BASED STATCOM 3.1 INTRODUCTION Static synchronous compensator is a shunt connected reactive power compensation device that is capable of generating or
More informationSHUNT ACTIVE POWER FILTER
75 CHAPTER 4 SHUNT ACTIVE POWER FILTER Abstract A synchronous logic based Phase angle control method pulse width modulation (PWM) algorithm is proposed for three phase Shunt Active Power Filter (SAPF)
More informationCoordinated Control of Power Electronic Converters in an Autonomous Microgrid
University of South Carolina Scholar Commons Theses and Dissertations 1-1-2013 Coordinated Control of Power Electronic Converters in an Autonomous Microgrid Gholamreza Dehnavi University of South Carolina
More informationMitigation of the Statcom with Energy Storage for Power Quality Improvement
Mitigation of the Statcom with Energy Storage for Power Quality Improvement Mohammed Shafiuddin 1, Mohammed Nazeeruddin 2 1 Royal institute of Engineering & Technology (Affliated to JNTUH), India 2 Nawab
More informationICCCES Application of D-STATCOM for load compensation with non-stiff sources
Application of D-STATCOM for load compensation with non-stiff sources 1 Shubhangi Dhole, 2 S.S.Gurav, 3 Vinayak Patil, 4 Pushkraj Kharatmal, 5 Magdum Ranjit 1 Dept of Electrical Engg. AMGOI, VATHAR TERF
More informationIMPROVED CONTROL STRATEGY OF GRID INTERACTIVE INVERTER SYSTEM WITH LCL FILTER USING ACTIVE AND PASSIVE DAMPING METHODS
IMPROVED CONTROL STRATEGY OF GRID INTERACTIVE INVERTER SYSTEM WITH LCL FILTER USING ACTIVE AND PASSIVE DAMPING METHODS A THESIS SUBMITTED IN PARTIAL FULFILLMENT OF THE REQUIREMENTS FOR THE DEGREE OF Master
More informationAnti-IslandingStrategyforaPVPowerPlant
Global Journal of Researches in Engineering: F Electrical and Electronics Engineering Volume 15 Issue 7 Version 1.0 Type: Double Blind Peer Reviewed International Research Journal Publisher: Global Journals
More informationIEEE sion/1547revision_index.html
IEEE 1547 IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces http://grouper.ieee.org/groups/scc21/1547_revi sion/1547revision_index.html
More informationVoltage Support and Reactive Power Control in Micro-grid using DG
International OPEN ACCESS Journal Of Modern Engineering Research (IJMER) Voltage Support and Reactive Power Control in Micro-grid using DG Nagashree. J. R 1, Vasantha Kumara. T. M 2, Narasimhegowda 3 1
More informationPower Quality Improvement using Shunt Passive Filter
Power Quality Improvement using Shunt Passive Filter Assistant Professor, Department of Electrical Engineering Bhutta Group of Institutions, India Abstract: The electricity supply would, ideally, show
More informationIMPORTANCE OF VSC IN HVDC
IMPORTANCE OF VSC IN HVDC Snigdha Sharma (Electrical Department, SIT, Meerut) ABSTRACT The demand of electrical energy has been increasing day by day. To meet these high demands, reliable and stable transmission
More informationDesign and Simulation of Fuzzy Logic controller for DSTATCOM In Power System
Design and Simulation of Fuzzy Logic controller for DSTATCOM In Power System Anju Gupta Department of Electrical and Electronics Engg. YMCA University of Science and Technology anjugupta112@gmail.com P.
More informationVOLTAGE HARMONIC CONTROL OF WEAK UTILITY GRID THROUGH DISTRIBUTED ENERGY SYSTEMS. A Thesis. Presented to
VOLTAGE HARMONIC CONTROL OF WEAK UTILITY GRID THROUGH DISTRIBUTED ENERGY SYSTEMS A Thesis Presented to The Graduate Faculty of The University of Akron In Partial Fulfillment of the Requirements for the
More informationIndirect Current Control of LCL Based Shunt Active Power Filter
International Journal of Electrical Engineering. ISSN 0974-2158 Volume 6, Number 3 (2013), pp. 221-230 International Research Publication House http://www.irphouse.com Indirect Current Control of LCL Based
More informationINSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE
INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE Ms. K. Kamaladevi 1, N. Mohan Murali Krishna 2 1 Asst. Professor, Department of EEE, 2 PG Scholar, Department of
More informationMITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR)
VOL. 4, NO. 4, JUNE 9 ISSN 89-668 6-9 Asian Research Publishing Network (ARPN). All rights reserved. MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR) Rosli Omar and Nasrudin Abd Rahim
More informationDesign and Simulation of Three Phase Shunt Active Power Filter Using SRF Theory
Advance in Electronic and Electric Engineering. ISSN 2231-1297, Volume 3, Number 6 (2013), pp. 651-660 Research India Publications http://www.ripublication.com/aeee.htm Design and Simulation of Three Phase
More informationCHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS
84 CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS 4.1 INTRODUCTION Now a days, the growth of digital economy implies a widespread use of electronic equipment not only in the industrial
More informationSIMULATION OF D-STATCOM AND DVR IN POWER SYSTEMS
SIMUATION OF D-STATCOM AND DVR IN POWER SYSTEMS S.V Ravi Kumar 1 and S. Siva Nagaraju 1 1 J.N.T.U. College of Engineering, KAKINADA, A.P, India E-mail: ravijntu@gmail.com ABSTRACT A Power quality problem
More informationIJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 01, 2016 ISSN (online):
IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 01, 2016 ISSN (online): 2321-0613 Study of Bidirectional AC/DC Converter with Feedforward Scheme using Neural Network Control
More informationControl of grid connected inverter system for sinusoidal current injection with improved performance
Control of grid connected inverter system for sinusoidal current injection with improved performance Simeen. S. Mujawar. Electrical engineering Department, Pune University /PVG s COET, Pune, India. simeen1990@gmail.com
More informationA New Control Strategy for Three- Phase Inverter Applied To Induction Motor of Micro Grid
Research Inventy: International Journal of Engineering And Science Vol.5, Issue 3 (March 2015), PP -01-05 Issn (e): 2278-4721, Issn (p):2319-6483, www.researchinventy.com A New Control Strategy for Three-
More informationHybrid Islanding Detection Method for Distributed Generators
Hybrid Islanding Detection Method for Distributed Generators Priyanka Patil 1, Mrs. S.U.Kulkarni 2 PG Scholar, Dept. Of Electical Engg, Bharati Vidyapeeth University College Of Engineering, Pune, Maharashtra,
More informationSTATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads
STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads Ponananthi.V, Rajesh Kumar. B Final year PG student, Department of Power Systems Engineering, M.Kumarasamy College of
More informationDamping and Harmonic Control of DG Interfacing. Power Converters
University of Alberta Damping and Harmonic Control of DG Interfacing Power Converters by Jinwei He A thesis submitted to the Faculty of Graduate Studies and Research in partial fulfillment of the requirements
More informationLiterature Review for Shunt Active Power Filters
Chapter 2 Literature Review for Shunt Active Power Filters In this chapter, the in depth and extensive literature review of all the aspects related to current error space phasor based hysteresis controller
More informationCurrent Rebuilding Concept Applied to Boost CCM for PF Correction
Current Rebuilding Concept Applied to Boost CCM for PF Correction Sindhu.K.S 1, B. Devi Vighneshwari 2 1, 2 Department of Electrical & Electronics Engineering, The Oxford College of Engineering, Bangalore-560068,
More informationFuel cell power system connection. Dynamics and Control of Distributed Power Systems. DC storage. DC/DC boost converter (1)
Dynamics and Control of Distributed Power Systems Fuel cell power system connection Ian A. Hiskens University of Wisconsin-Madison ACC Workshop June 12, 2006 This topology is fairly standard, though there
More informationSpace Vector Modulation of Multi-Level and Multi-Module Converters for High Power Applications. Maryam Saeedifard
Space Vector Modulation of Multi-Level and Multi-Module Converters for High Power Applications by Maryam Saeedifard A thesis submitted in conformity with the requirements for the degree of Doctor of Philosophy
More informationImproved Islanding Detection Scheme for Multiple Inverter Based DG Systems
Improved Islanding Detection Scheme for Multiple Inverter Based DG Systems Veenaj K V, P.G. Scholar, & Manju Padma, Assistant Professor, Department of Electrical & Electronics Engineering, Thejus Engineering
More informationChapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two
Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL Basically the HVDC transmission consists in the basic case of two convertor stations which are connected to each other by a transmission link consisting of an overhead
More informationModelling of Modular Multilevel Converter Using Input Admittance Approach
Modelling of Modular Multilevel Converter Using Input Admittance Approach Chalmers University of Technology Division of Electric Power Engineering Master s Thesis in Electric Power Engineering ADULIS ABUN
More informationActive Rectifier in Microgrid
03.09.2012 Active Rectifier in Microgrid - Developing a simulation model in SimPower - Dimensioning the filter - Current controller comparison - Calculating average losses in the diodes and transistors
More informationA Comparative Study between DPC and DPC-SVM Controllers Using dspace (DS1104)
International Journal of Electrical and Computer Engineering (IJECE) Vol. 4, No. 3, June 2014, pp. 322 328 ISSN: 2088-8708 322 A Comparative Study between DPC and DPC-SVM Controllers Using dspace (DS1104)
More informationAS THE depth of penetration of distributed energy resources
2122 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 27, NO. 4, OCTOBER 2012 Control of a Multiple Source Microgrid With Built-in Islanding Detection and Current Limiting Jeffrey M. Bloemink, Student Member,
More informationDevelopment of Dynamic Estimators for Islanding Detection of Inverter-Based DG
428 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 30, NO. 1, FEBRUARY 2015 Development of Dynamic Estimators for Islanding Detection of Inverter-Based DG Mohamed Al Hosani, Member, IEEE, Zhihua Qu, Fellow,
More informationp. 1 p. 6 p. 22 p. 46 p. 58
Comparing power factor and displacement power factor corrections based on IEEE Std. 18-2002 Harmonic problems produced from the use of adjustable speed drives in industrial plants : case study Theory for
More informationThree Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology
Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology Riya Philip 1, Reshmi V 2 Department of Electrical and Electronics, Amal Jyothi College of Engineering, Koovapally, India 1,
More informationPERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER
International Journal of Electrical and Electronics Engineering Research (IJEEER) ISSN 2250-155X Vol. 3, Issue 2, Jun 2013, 309-318 TJPRC Pvt. Ltd. PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID
More informationFUZZY CONTROLLED DSTATCOM FOR HARMONIC COMPENSATION
FUZZY CONTROLLED DSTATCOM FOR HARMONIC COMPENSATION Aswathy Anna Aprem 1, Fossy Mary Chacko 2 1 Student, Saintgits College, Kottayam 2 Faculty, Saintgits College, Kottayam Abstract In this paper, a suitable
More informatione-issn: p-issn:
Available online at www.ijiere.com International Journal of Innovative and Emerging Research in Engineering e-issn: 2394-3343 p-issn: 2394-5494 PFC Boost Topology Using Average Current Control Method Gemlawala
More informationA Control Method of Parallel Inverter for Smart Islanding of a Microgrid
A Control Method of Parallel Inverter for Smart Islanding of a Microgrid M. Hojo 1, K. Amo 1, T. Funabashi 2 and Y. Ueda 2 1 Institute of Technology and Science, the University of Tokushima 2-1 Minami-josanjima,
More informationRenewable Interconnection Standard & Experimental Tests. Yahia Baghzouz UNLV Las Vegas, NV, USA
Renewable Interconnection Standard & Experimental Tests Yahia Baghzouz UNLV Las Vegas, NV, USA Overview IEEE Std 1547 Voltage limitations Frequency limitations Harmonic limitations Expansion of IEEE Std
More informationIslanding Detection Method Based On Impedance Measurement
Islanding Detection Method Based On Impedance Measurement Chandra Shekhar Chandrakar 1, Bharti Dewani 2 Department of Electrical and Electronics Engineering Chhattisgarh Swami Vivekananda Technical University
More informationApplication of Fuzzy Logic Controller in UPFC to Mitigate THD in Power System
International Journal of Engineering Research and Development e-issn: 2278-067X, p-issn: 2278-800X, www.ijerd.com Volume 9, Issue 8 (January 2014), PP. 25-33 Application of Fuzzy Logic Controller in UPFC
More informationISSN: Page 20. International Journal of Engineering Trends and Technology- Volume2Issue3-2011
Design of Shunt Active Power Filter to eliminate the harmonic currents and to compensate the reactive power under distorted and or imbalanced source voltages in steady state Sangu Ravindra #1, Dr.V.C.Veera
More informationEnhancement of Power Quality in Distribution System Using D-Statcom for Different Faults
Enhancement of Power Quality in Distribution System Using D-Statcom for Different s Dr. B. Sure Kumar 1, B. Shravanya 2 1 Assistant Professor, CBIT, HYD 2 M.E (P.S & P.E), CBIT, HYD Abstract: The main
More informationPower Control Scheme of D-Statcom
ISSN : 48-96, Vol. 4, Issue 6( Version 3), June 04, pp.37-4 RESEARCH ARTICLE OPEN ACCESS Power Control Scheme of D-Statcom A. Sai Krishna, Y. Suri Babu (M. Tech (PS)) Dept of EEE, R.V.R. & J.C. College
More informationDesign of Shunt Active Power Filter by using An Advanced Current Control Strategy
Design of Shunt Active Power Filter by using An Advanced Current Control Strategy K.Sailaja 1, M.Jyosthna Bai 2 1 PG Scholar, Department of EEE, JNTU Anantapur, Andhra Pradesh, India 2 PG Scholar, Department
More informationIEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces
IEEE PES Boston Chapter Technical Meeting IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces P1547 Chair David
More informationMODELING AND CONTROL OF DISTRIBUTED ENERGY SYSTEMS DURING TRANSITION BETWEEN GRID CONNECTED AND STANDALONE MODES. A Dissertation.
MODELING AND CONTROL OF DISTRIBUTED ENERGY SYSTEMS DURING TRANSITION BETWEEN GRID CONNECTED AND STANDALONE MODES A Dissertation Presented to The Graduate Faculty of The University of Akron In Partial Fulfillment
More informationSynchronous Reference Frame Theory (SRF) along with PI Controller Based Dynamic Voltage Restorer
Research Inventy: International Journal of Engineering And Science Vol.5, Issue 5 (May 2015), PP 59-64 Issn (e): 2278-4721, Issn (p):2319-6483, www.researchinventy.com Synchronous Reference Frame Theory
More informationCurrent Control for a Single-Phase Grid-Connected Inverter Considering Grid Impedance. Jiao Jiao
Current Control for a Single-Phase Grid-Connected Inverter Considering Grid Impedance by Jiao Jiao A dissertation submitted to the Graduate Faculty of Auburn University in partial fulfillment of the requirements
More informationSimulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System
Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System 1 G.Balasundaram, 2 Dr.S.Arumugam, 3 C.Dinakaran 1 Research Scholar - Department of EEE, St.
More informationProject acronym: Multi-island
Technical report for The Experimental investigation on the performance characteristics of anti-islanding techniques in the prospect of high PV penetration level Project acronym: Multi-island USER PROJECT
More informationImproved Real/Reactive Power Management and Controls for Converter-Based DERs in Microgrids
Improved Real/Reactive Power Management and Controls for Converter-Based DERs in Microgrids Masoud Karimi and Thaer Qunais Mississippi State University karimi@ece.msstate.edu 1. Introduction: Electric
More information[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785
IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY POWER QUALITY IMPROVEMENT OF GRID CONNECTED WIND ENERGY SYSTEM BY USING STATCOM Mr.Mukund S. Mahagaonkar*, Prof.D.S.Chavan * M.Tech
More informationA Simple Control Algorithm for Three-Phase Shunt Active Power Filter for Reactive Power and Current Harmonic Compensation
International Journal of Electrical Engineering. ISSN 0974-2158 Volume 6, Number 4 (2013), pp. 473-483 International Research Publication House http://www.irphouse.com A Simple Control Algorithm for Three-Phase
More informationINVESTIGATION OF HARMONIC DETECTION TECHNIQUES FOR SHUNT ACTIVE POWER FILTER
IOSR Journal of Electronics & Communication Engineering (IOSR-JECE) ISSN(e) : 2278-1684 ISSN(p) : 2320-334X, PP 68-73 www.iosrjournals.org INVESTIGATION OF HARMONIC DETECTION TECHNIQUES FOR SHUNT ACTIVE
More informationImproving Passive Filter Compensation Performance With Active Techniques
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 50, NO. 1, FEBRUARY 2003 161 Improving Passive Filter Compensation Performance With Active Techniques Darwin Rivas, Luis Morán, Senior Member, IEEE, Juan
More informationImprovement Voltage Sag And Swell Under Various Abnormal Condition Using Series Compensation
Improvement Voltage Sag And Swell Under Various Abnormal Condition Using Series Compensation Sumit Borakhade #1, Sumit Dabhade *2, Pravin Nagrale #3 # Department of Electrical Engineering, DMIETR Wardha.
More informationDevelopment of Passive Anti-Islanding Strategies for Distributed Generation Systems
Development of Passive Anti-Islanding Strategies for Distributed Generation Systems by Abdualah S. Aljankawey Previous Degree (M.Sc.E, University of New Brunswick, 2007) A DISSERTATION SUBMITTED IN PARTIAL
More informationControl of a Back-to-Back VSC from Grid Connection to Islanded Modes in Microgrids
1 Control of a Back-to-Back VSC from Grid Connection to Islanded Modes in Microgrids Ling Xu, Student Member, IEEE, Zhixin Miao, Senior Member, IEEE, and Linglnig Fan, Senior Member, IEEE Abstract VSC
More informationPower Quality improvement of a three phase four wire system using UPQC
International Research Journal of Engineering and Technology (IRJET) e-issn: 2395-56 Volume: 2 Issue: 4 July-215 www.irjet.net p-issn: 2395-72 Power Quality improvement of a three phase four wire system
More informationImplementation of SRF based Multilevel Shunt Active Filter for Harmonic Control
International Journal of Engineering Research and Development e-issn: 2278-067X, p-issn: 2278-800X, www.ijerd.com Volume 3, Issue 8 (September 2012), PP. 16-20 Implementation of SRF based Multilevel Shunt
More information