1 Impact of High PV Penetration on Grid Operation Yahia Baghzouz Professor of Electrical engineering University of Nevada Las Vegas

2 Overview Introduction/Background Effects of High PV Penetration on Distribution System Operation A the system level At the distribution level Experimental Setup for Testing a Smart Inverter Autonomous Functionalities Non-Unity power factor operation OV/UV and OF/UF ride through Dynamic Volt/Var control Islanding test Harmonic Analysis

3 Introduction Over the past decade, electric power generation by means of (PV) has experienced a rapid growth worldwide, and in some areas, electric distribution feeders have already reached a penetration level of over 25%. At the system level, high PV penetration requires more ramping and frequency regulation capabilities. At the distribution level, high PV penetration leads to several technical issues related to power quality, voltage sags and swells, excessive operations of voltage regulating equipment, reverse power flow, and over-voltages.

4 Higher ramp rates - California s net estimated load curve Source: CAISO 2013

5 Impact of Large-Scale PV Integration in Southern Nevada Case Study [1] The study evaluated the impact of large-scale photovoltaic (PV) and distributed generation output on NV Energy s electric grid system in southern Nevada. It analyzed the ability of NV Energy s generation to accommodate increasing amounts of utility-scale PV and DG, and the resulting cost of integrating renewable resources. It also quantified the impact of variable PV generation output on NV Energy s system operations, including balancing reserve requirements. [1]

6 Existing and proposed large PV installations Cases Studied:

7 Solar irradiance and PV Power Since ground-based irradiance data is not available at the PV plant sites, a method* was developed by SNL to simulate timesynchronized minute-by-minute irradiance at each of the PV sites using estimates of irradiance from geostationary satellite imagery. (*)Simulation of One-Minute Power Output from Utility-Scale Photovoltaic Generation Systems, C. Hansen, J. Stein,A. Ellis, Sandia National Laboratories, August 2011

8 PV Output Profiles One year of AC power output, at one-minute intervals, were produced for each PV plant. PV output profiles for a typical clear day and for a cloudy day under a high PV penetration are illustrated below. Note: variability becomes smaller when PV plants are installed over a large area.

9 Study Results Integration of large-scale PV increases regulation and load following requirements that must be supplied by NV Energy s generating resources, mostly from combined cycle units. On average, 1 MW of additional thermal generating capacity must be reserved for regulation for each 25 MW of PV capacity installed in NV Energy s southern Nevada system. On average, 1 MW/min of additional ramping capability must be reserved for regulation for each 75 MW of PV in NV Energy s southern system.

10 Balancing Service Ramp Statistics More solar generation causes higher frequency of regulation movements. Base Case Case 5A

11 Voltage-Related PV Impacts High penetrations of PV can impact circuit voltage in a number of ways. Voltage rise and voltage variations caused by fluctuations in solar PV generation are two of the most prominent and potentially problematic impacts of high penetrations of PV. These effects are particularly pronounced when large amounts of solar PV are connected near the end of long and lightly loaded feeders.

12 Overvoltage Pockets of high voltage can occur on the distribution circuit during low-load conditions. Higher voltage can cause DG (including PV inverters) to trip off-line.

13 Substation Transformer Net Power Flow (25% PV Penetration under cloudy days) Load with PV Load without PV PV Power 12 Load and PV Power (MW) /11/10 0:00 7/11/10 6:00 7/11/10 12:00 7/11/10 18:00 7/12/10 0:00 7/12/10 6:00 7/12/10 12:00 7/12/10 18:00 Time (mm/dd/yy hh:mm) 7/13/10 0:00 7/13/10 6:00 7/13/10 12:00 7/13/10 18:00 7/14/10 0:00

14 Distribution Voltage Regulation The under-load-tap-changing transformer(ultc), or load tap changer(ltc), allows the transformer taps to be changed while the transformer is energized. A typical range of regulation is ±10% with 32 steps - each corresponds to (5/8)%. Voltage control is also achieved by means of voltage regulators and/or switched capacitors along the feeder.

15 Concern Over Voltage Flicker One main concern over such fluctuations is the possibility of voltage flicker - a voltage quality problem that is annoying to the eyes. The borderline of visibility of flicker at 1 minute interval is 0.7% voltage dip.

16 Functions of Conventional Grid-Tied PV Inverters Maximum Power Tracking Grid synchronization Grid Monitoring - Disconnect

17 Advanced Inverters Newer gird codes have been developed in Europe which require advanced inverters that can provide additional functions to help mitigate or reduce the severity of these problems. In the USA, IEEE recently updated its Interconnection Standard 1547 through an amendment, i.e., IEEE Std. 1547a that allows many of the advanced inverter functionalities. At the regional level, the State of California which has the highest penetration of PV systems has already begun to adopt advanced inverter capabilities.

18 Required system response time to abnormal voltages (IEEE Std. 1547a)

19 Required system response time to abnormal frequencies (IEEE Std. 1547a)

20 Common Inverter Functionalities Advanced inverters are controlled by software applications; and many of their electrical characteristics can be modified through software settings and commands. With pre-established settings, many inverter-based distributed resources can operate autonomously by adjusting their output to local conditions: Common functions: Inverters have the capability of riding through minor disturbances to frequency or voltage. These functions are called under/over frequency ride-through and under/over voltage ride-through.

21 Common Inverter Functionalities Injecting or absorbing reactive power into or from the grid (i.e., dynamic reactive power control). These functions make system stability maintenance easier by keeping voltage and frequency within specified limits. Oversizing an inverter allows reactive power generation/absorption even during peak irradiance. Soft start involves staggering the timing of reconnection of inverters on a single distribution circuit, to avoid spikes in the active power being fed onto the grid as it returns to normal functioning, limiting the risk of triggering another grid disturbance.

22 Advanced Inverter Testing Methods Typically, PV and grid simulators are used to test the advanced functionalities of smart inverters. Instead, we used a real PV system and local generation to test five key autonomous functions of an advanced inverter: soft-reconnect, non-unity power factor operation, over/under-voltage ride through, over/underfrequency ride through, dynamic Volt/Var control.

23 Experimental Set-up 12 kw PV array, 12 kva, 480 V advanced inverter, 30 kva, 480V /208 V transformer 25 kw resistive load bank (adjustable) 9 kvar inductive load bank (adjustable) 1.8 kvar capacitive load (adjustable) 208 V local grid supply.

24 Adjusting inverter parameters The inverter has a controller that provides a gateway for system monitoring and recording. The controller is equipped with a communication protocol (Modbus) that is commonly used by the solar industry for communication in PV power plants. Changing the default values of various parameters embedded in software requires a special code that was obtained from the manufacturer. Communication with the inverter is achieved wirelessly by means of a control panel through a router.

25 Communication with SMA inverter

26 Generator voltage & frequency control Voltage Control: The AVR set-point control is biased externally by bucking or boosting the sensing voltage input to the built-in generator controller, and this was accomplished by using of an external variac. Frequency Control: The governor set-point control is externally triggered by means of a DC control signal that is asserted by a microcontroller circuit.

27 Under-Frequency Ride Through Advanced PV inverters can assist the grid with frequency regulation during load-generation mismatch.

28 Over-frequency ride through

29 Under-Voltage Ride Through Advanced PV inverters can improve power quality by remaining connected to the grid during temporary faults.

30 Over-voltage ride-through

31 Non-unity power factor operation Non-unity power factor operation help compensate for drop in the overall feeder power factor, and regulate the voltage.

32 Dynamic Volt/Var Control Advanced PV inverters can assist the grid with localized voltage regulation by absorbing/generating reactive power.

33 Concern over Islanding Concern has been raised over the interference of these advanced control functions with islanding detection schemes embedded in these inverters. Reason for concern: some of these grid support functions are intended to stabilize the voltage and frequency, while some active islanding detection methods are based on destabilizing these electrical quantities. Such concern is amplified under load matching and/or when multiple inverters from different manufacturers share the same distribution circuit.

34 Islanding Detection Several passive and active methods exist to prevent an islanding condition. Starting with the classical over-under voltage (OUV) and over-under frequency (OUF) detection of conventional inverters, consider the system below.

35 Let Islanding Detection P G /P DR = α, and Q G /Q DR = β In conventional inverters, it is fair to assume that P DR and Q DR are constant. P Q DR DR (1 ) (1 ) V 2 old R V, 2 old old L (1 2 old LC).

36 V V new old new old 1, 1 b b 2d 2 4d, 1 b (1 d), 1 d 2 old LC. Case of R-L load (with no capacitance): new old 1. 1 Islanding Detection Changes in voltage and frequency after utility outage:

37 Islanding Detection The deviations in voltage and frequency depend on the magnitude and direction of the net power flow into the grid. When local generation closely matches the local demand, the voltage and/or frequency deviations will be too small, and the thresholds for the OUV and OUF relays cannot be set arbitrarily small. Due to the this non-detection zone (NDZ), grid-tied inverters incorporate one or more active methods to detect and prevent islanding even when the net active and reactive power flow into the grid is negligible.

38 Islanding Detection These active schemes basically push against the grid to determine to what degree it resists voltage and/or frequency changes; either the grid is stiff (not islanded) or movable (islanded). Some published active methods for islanding prevention include voltage harmonic monitoring, phase jump detection; slide-mode frequency shift, impedance measurement, and active frequency drift. The means by which commercial inverters detect and prevent unintentional islands are not standardized, and manufacturers rarely if ever share such detail.

39 Islanding Detection The most popular grid support function available in advanced inverters is the Volt/Var control that is designed to assist the electric utility with local voltage regulation. Perhaps the second important function the Hz/Watt control that helps regulate the system frequency, but this requires the incorporation of an energy storage system. When these functions are activated, they respond to voltage and frequency deviations by modifying the inverter real and reactive powers, P DR and Q DR, in a manner that reduces the impact of abnormal grid conditions. The resulting voltage and frequency responses depend on the coefficients that define the F-P and V-Q curves and delay time associated with the control system.

40 Typical Q-V and P-f Curves Let Q DR = g(v) and P DR = h(f).

41 Islanding Detection After an outage, the new voltage and frequency will lead to new inverter powers Q DR,new = g(v new ) and P DR,new = h(f new ). This will in turn lead to newer values of voltage and frequency, and the process continues until steady state values are reached. Meanwhile, if the inverter is equipped with the active frequency drift method, it will continuously attempt to cause larger and larger deviations in frequency. The concern is clear as these grid support functions work against this active anti-islanding method if they operate during the same time period, the result can possibly lead to an unacceptable islanded operation.

42 UNLV Microgrid Facility

43 Smart Inverter Islanding Test Sampling rate of power recorder: 500 milliseconds, Transient recorder triggered after sensing an abnormality.

44 Unity power factor operation (Case 1) Case No. P DR /Q DR (kw/kvar) PF (%) P G /Q G (kw/kvar) α β t (ms) / / ,020

45 Unity power factor operation (Case 2) Case No. P DR /Q DR (kw/kvar) PF (%) P G /Q G (kw/kvar) α β t (ms) / /

46 Unity power factor operation (Case 3) Case No. P DR /Q DR (kw/kvar) PF (%) P G /Q G (kw/kvar) α β t (ms) / /

47 Case No. Non-Unity power factor (Case 4) P DR /Q DR (kw/kvar) PF (%) P G /Q G (kw/kvar) α β t (ms) / /

48 Unity power factor operation (Case 5) Case No. P DR /Q DR (kw/kvar) PF (%) P G /Q G (kw/kvar) α β t (ms) / /

49 Dynamic Volt/Var Control (Case 6) Case No. P DR /Q DR (kw/kvar) PF (%) P G /Q G (kw/kvar) α β t (ms) / / ,330

50 Analysis of Inverter Current Distortion A secondary concern is that PV inverters may add to power quality problems that are associated with the proliferation of nonlinear loads, i.e., the impact of noise and harmonics generated by these static power converters. This concern led to the development of industry standards that limit these disturbances. In the United States, PV inverters are required to meet UL 1741 Std. which is based IEEE Std.. Herein, the total distortion of the current, in percent of the inverter rated current is limited to 5%. This quantity is sometimes referred to as Total Demand Distortion (or TDD) a term which was originally derived for nonlinear loads

51 TDD vs. THD TDD is often confused with the conventional Total Harmonic Distortion (THD) that is calculated in percent of the fundamental-frequency current component. TDD and THD are identical only under rated power operation. Otherwise, THD is always larger than TDD(sometimes by orders of magnitude). To satisfy the limit set IEEE 1547 Std., manufacturers install carefully-designed passive harmonic and EMI filters at the inverter terminals in order minimize current distortion and switching noise when operating at rated condition.

52 Effect of distortion in supply voltage Since the inverters are not at fault when the voltage supply already contains some distortion, the Standard further specifies that the harmonic current injections shall be exclusive of any harmonic currents due to harmonic voltage distortion present in the Area EPS without the DR connected. Although PV inverters rarely (if ever) operate at their specified power rating, interconnection standards do not address harmonic emissions when such systems operate below rated conditions. Next, a 14 kva inverter is tested for harmonic content under sub-rated conditions.

53 Trend of RMS value of supply voltage over a 24-hour period

54 Trend of low-order harmonics of supply voltage over 24 hr a period IEEE Std allows supply voltages below 1 kv to contain up to 8% THD and 5% limit for each individual harmonic.

55 Current waveform variation with solar irradiance grid operation

56 Harmonic content of current waveforms (% of fundamental) under different levels of solar irradiance grid operation

57 Harmonic content of current waveforms (in Ampere) under different levels of solar irradiance grid operation.

58 Current waveform variation under different power factor operation

59 Harmonic content of current waveforms (% of fundamental) under different power factor operation.

60 Islanded Operation

61 Current waveform variation with solar irradiance islanded operation.

62 Harmonic content of voltage and current waveforms islanded operation

63 Variation of current THD with inverter power generation

64 Conclusion No firm conclusion could be drawn on the impact of such functions and the islanding detection methods embedded in the inverter as the inverter ride time varied erratically even under very similar (but not exact) conditions. Future work will concentrate on determining the MPPT and anti-islanding methods used in the inverter through rigorous field tests and the dynamic response of the Volt/VAr function, so that its ride time during a utility outage can be predicted with a high level of confidence. The lesson learned here is that events are difficult to exactly duplicate when using real-life systems.

65 END!

Renewable Interconnection Standard & Experimental Tests. Yahia Baghzouz UNLV Las Vegas, NV, USA

Renewable Interconnection Standard & Experimental Tests. Yahia Baghzouz UNLV Las Vegas, NV, USA Renewable Interconnection Standard & Experimental Tests Yahia Baghzouz UNLV Las Vegas, NV, USA Overview IEEE Std 1547 Voltage limitations Frequency limitations Harmonic limitations Expansion of IEEE Std

More information

INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs

INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES Technical Requirements for Grid-Tied DERs Projects Division 6/29/2017 Contents 1 Definitions and Acronyms... 1 2 Technical Interconnection

More information

IEEE sion/1547revision_index.html

IEEE sion/1547revision_index.html IEEE 1547 IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces http://grouper.ieee.org/groups/scc21/1547_revi sion/1547revision_index.html

More information

POWER QUALITY IMPACTS AND MITIGATION OF DISTRIBUTED SOLAR POWER

POWER QUALITY IMPACTS AND MITIGATION OF DISTRIBUTED SOLAR POWER POWER QUALITY IMPACTS AND MITIGATION OF DISTRIBUTED SOLAR POWER Presented by Ric Austria, Principal at Pterra Consulting to the IEEE San Francisco Chapter Feb 17, 2016 California Public Utilities Commission,

More information

Phase-phase/phase-neutral: 24/13.8 kv star, 13.8 kv delta, 12/6.9 kv star.

Phase-phase/phase-neutral: 24/13.8 kv star, 13.8 kv delta, 12/6.9 kv star. Summary Of Interconnection Technical Guidelines for Renewable Energy Systems 0-100 kw under Standard Offer Contract (Extract from JPS Guide to Interconnection of Distributed Generation) This document is

More information

BED INTERCONNECTION TECHNICAL REQUIREMENTS

BED INTERCONNECTION TECHNICAL REQUIREMENTS BED INTERCONNECTION TECHNICAL REQUIREMENTS By Enis Šehović, P.E. 2/11/2016 Revised 5/19/2016 A. TABLE OF CONTENTS B. Interconnection Processes... 2 1. Vermont Public Service Board (PSB) Rule 5.500... 2

More information

IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces

IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces IEEE PES Boston Chapter Technical Meeting IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces P1547 Chair David

More information

Grid Converters for Photovoltaic

Grid Converters for Photovoltaic Grid Converters for Photovoltaic and Wind Power Systems by R. Teodorescu, M. Liserre and P. Rodriguez ISBN: 978 0 470 05751 3 Copyright Wiley 2011 Chapter 3 Grid Requirements for PV Grid connection requirements

More information

Study of Centralized Anti-Islanding Method on Large-Scale Photovoltaic Power Plants

Study of Centralized Anti-Islanding Method on Large-Scale Photovoltaic Power Plants 4th International Conference on Machinery, Materials and Information Technology Applications (ICMMITA 2016) Study of Centralized Anti-Islanding Method on Large-Scale Photovoltaic Power Plants Chen-Xin

More information

Implementation of Revised IEEE Standard 1547

Implementation of Revised IEEE Standard 1547 MAY 31, 2017 HOLYOKE, MASSACHUSETTS Implementation of Revised IEEE Standard 1547 Presentation to ISO-TO Operations Committee David Forrest Key Points As New England adds significant amounts of Distributed

More information

Grid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017

Grid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017 Grid codes and wind farm interconnections CNY Engineering Expo Syracuse, NY November 13, 2017 Purposes of grid codes Grid codes are designed to ensure stable operating conditions and to coordinate the

More information

DP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation

DP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation DP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation Technical Requirements for Interconnection and Parallel Operation of Distributed Generation Single Phase

More information

Intermittent Renewable Resources (Wind and PV) Distribution Connection Code (DCC) At Medium Voltage (MV)

Intermittent Renewable Resources (Wind and PV) Distribution Connection Code (DCC) At Medium Voltage (MV) Intermittent Renewable Resources (Wind and PV) Distribution Connection Code (DCC) At Medium Voltage (MV) IRR-DCC-MV 1. Introduction 1 IRR-DCC-MV 2. Scope 1 IRR-DCC-MV 2.1. General 1 IRR-DCC-MV 2.2. Affected

More information

ECE 528 Understanding Power Quality

ECE 528 Understanding Power Quality ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 22 1 Today Homework 5 questions Homework 6 discussion More on

More information

Hybrid Anti-Islanding Algorithm for Utility Interconnection of Distributed Generation

Hybrid Anti-Islanding Algorithm for Utility Interconnection of Distributed Generation Hybrid Anti-Islanding Algorithm for Utility Interconnection of Distributed Generation Maher G. M. Abdolrasol maher_photo@yahoo.com Dept. of Electrical Engineering University of Malaya Lembah Pantai, 50603

More information

The Connecticut Light and Power Company

The Connecticut Light and Power Company The Connecticut Light and Power Company and The United Illuminating Company Exhibit B - Generator Interconnection Technical Requirements May 12, 2010 Page 1 of 26 Table of Contents 1. SCOPE... 3 2. GENERAL

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements Division 502 Technical Applicability 1(1) Section 502.1 applies to: Expedited Filing Draft August 22, 2017 the legal owner of an aggregated generating facility directly connected to the transmission system

More information

E N G I N E E R I N G M A N U A L

E N G I N E E R I N G M A N U A L 1 1 1.0 PURPOSE The purpose of this document is to define policy and provide engineering guidelines for the AP operating companies (Monongahela Power Company, The Potomac Edison Company, and West Penn

More information

Proposed test procedure for the laboratory characterisation of gridconnected

Proposed test procedure for the laboratory characterisation of gridconnected Proposed test procedure for the laboratory characterisation of gridconnected micro-inverters. Mac Leod, B., Vorster, FJ., van Dyk, EE. Nelson Mandela Metropolitan University Centre for Renewable and Sustainable

More information

Technical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks

Technical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks 2014 Technical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks This document specifies the technical requirement for connecting sspv to the low voltage distribution

More information

Wind Power Facility Technical Requirements CHANGE HISTORY

Wind Power Facility Technical Requirements CHANGE HISTORY CHANGE HISTORY DATE VERSION DETAIL CHANGED BY November 15, 2004 Page 2 of 24 TABLE OF CONTENTS LIST OF TABLES...5 LIST OF FIGURES...5 1.0 INTRODUCTION...6 1.1 Purpose of the Wind Power Facility Technical

More information

Possible Future Modifications to IEEE 1547

Possible Future Modifications to IEEE 1547 California Rule 21 SWIG Possible Future Modifications to IEEE 1547 Michael Sheehan, P.E IREC mikes@irecusa.com PV Significant Trends Installed prices for distributed PV installations fell by at least 11

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements Applicability 1(1) Section 502.1 applies to the ISO, and subject to the provisions of subsections 1(2), (3) and (4) to any: (a) a new wind aggregated generating facility to be connected to the transmission

More information

Islanding Detection Method Based On Impedance Measurement

Islanding Detection Method Based On Impedance Measurement Islanding Detection Method Based On Impedance Measurement Chandra Shekhar Chandrakar 1, Bharti Dewani 2 Department of Electrical and Electronics Engineering Chhattisgarh Swami Vivekananda Technical University

More information

IEEE sion/1547revision_index.html

IEEE sion/1547revision_index.html IEEE 1547 IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces http://grouper.ieee.org/groups/scc21/1547_revi sion/1547revision_index.html

More information

A Novel Active Anti-Islanding Protection Scheme for Grid-Interactive Roof-Top Solar PV System

A Novel Active Anti-Islanding Protection Scheme for Grid-Interactive Roof-Top Solar PV System A Novel Active Anti-Islanding Protection Scheme for Grid-Interactive Roof-Top Solar PV System Rohith Varier, Student member, IEEE and Naran M. Pindoriya, Member, IEEE Electrical Engineering, Indian Institute

More information

Table of Contents. Introduction... 1

Table of Contents. Introduction... 1 Table of Contents Introduction... 1 1 Connection Impact Assessment Initial Review... 2 1.1 Facility Design Overview... 2 1.1.1 Single Line Diagram ( SLD )... 2 1.1.2 Point of Disconnection - Safety...

More information

Modelling Parameters. Affect on DER Impact Study Results

Modelling Parameters. Affect on DER Impact Study Results Modelling Parameters Affect on DER Impact Study Results Agenda Distributed Energy Resources (DER) Impact Studies DER Challenge Study Steps Lessons Learned Modeling Reverse Power Transformer Configuration

More information

Dynamic Grid Edge Control

Dynamic Grid Edge Control Dynamic Grid Edge Control Visibility, Action & Analytics at the Grid Edge to Maximize Grid Modernization Benefits The existence of greater volatility at the grid edge creates a set of problems that require

More information

Testing Advanced Photovoltaic Inverters Conforming to IEEE Standard 1547 Amendment 1

Testing Advanced Photovoltaic Inverters Conforming to IEEE Standard 1547 Amendment 1 > REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < Testing Advanced Photovoltaic Inverters Conforming to IEEE Standard 547 Amendment Anderson Hoke, Student Member,

More information

Voltage Support and Reactive Power Control in Micro-grid using DG

Voltage Support and Reactive Power Control in Micro-grid using DG International OPEN ACCESS Journal Of Modern Engineering Research (IJMER) Voltage Support and Reactive Power Control in Micro-grid using DG Nagashree. J. R 1, Vasantha Kumara. T. M 2, Narasimhegowda 3 1

More information

Measurement tools at heart of Smart Grid need calibration to ensure reliability

Measurement tools at heart of Smart Grid need calibration to ensure reliability Measurement tools at heart of Smart Grid need calibration to ensure reliability Smart grid; PMU calibration position 1 The North American interconnections, or electric transmission grids, operate as a

More information

T-68 Protecting Your Equipment through Power Quality Solutions

T-68 Protecting Your Equipment through Power Quality Solutions T-68 Protecting Your Equipment through Power Quality Solutions Dr. Bill Brumsickle Vice President, Engineering Nov. 7-8, 2012 Copyright 2012 Rockwell Automation, Inc. All rights reserved. 2 Agenda What

More information

Experiences in Integrating PV and Other DG to the Power System

Experiences in Integrating PV and Other DG to the Power System Experiences in Integrating PV and Other DG to the Power System (Radial Distribution Systems) Prepared by: Philip Barker Founder and Principal Engineer Nova Energy Specialists, LLC Schenectady, NY Phone

More information

Revised IEEE 1547 Standard for Interconnecting Distributed Energy Resources with Electric Power Systems- National Grid Solar Program

Revised IEEE 1547 Standard for Interconnecting Distributed Energy Resources with Electric Power Systems- National Grid Solar Program 1 Revised IEEE 1547 Standard for Interconnecting Distributed Energy Resources with Electric Power Systems- National Grid Solar Program Babak Enayati, PhD, PE Lead Engineer, National Grid Waltham, MA Email:

More information

Inverter-Based Resource Disturbance Analysis

Inverter-Based Resource Disturbance Analysis Inverter-Based Resource Disturbance Analysis Key Findings and Recommendations Informational Webinar February 15, 2018 August 16, 2016 Blue Cut Fire Disturbance Key Findings and Recommendations 2 Western

More information

Protective Relaying for DER

Protective Relaying for DER Protective Relaying for DER Rogerio Scharlach Schweitzer Engineering Laboratories, Inc. Basking Ridge, NJ Overview IEEE 1547 general requirements to be met at point of common coupling (PCC) Distributed

More information

Roadmap For Power Quality Standards Development

Roadmap For Power Quality Standards Development Roadmap For Power Quality Standards Development IEEE Power Quality Standards Coordinating Committee Authors: David B. Vannoy, P.E., Chair Mark F. McGranghan, Vice Chair S. Mark Halpin, Vice Chair D. Daniel

More information

II. RESEARCH METHODOLOGY

II. RESEARCH METHODOLOGY Comparison of thyristor controlled series capacitor and discrete PWM generator six pulses in the reduction of voltage sag Manisha Chadar Electrical Engineering Department, Jabalpur Engineering College

More information

CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS

CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS 66 CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS INTRODUCTION The use of electronic controllers in the electric power supply system has become very common. These electronic

More information

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre. General PQ: Power Quality has multiple issues involved. Thus, need to have some benchmarking standards. Very little is spoken about the LT supply installation within an industry. There is need to understand

More information

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW ELECTRIC UTILITY CONTACT INFORMATION Consumers Energy Interconnection Coordinator 1945

More information

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS 84 CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS 4.1 INTRODUCTION Now a days, the growth of digital economy implies a widespread use of electronic equipment not only in the industrial

More information

Islanding Detection Techniques for Distributed Energy Resources-Review

Islanding Detection Techniques for Distributed Energy Resources-Review Islanding Detection Techniques for Distributed Energy Resources-Review Janki N. Patel 1 P.G. Student, Department of Electrical Engineering, SCET, Surat, Gujarat, India 1 ABSTRACT: Distributed generators

More information

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 86 CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 5.1 POWER QUALITY IMPROVEMENT This chapter deals with the harmonic elimination in Power System by adopting various methods. Due to the

More information

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services Introduction The term power quality may take on any one of several definitions. The strict definition of power quality

More information

Harmonics Issues that Limit Solar Photovoltaic Generation on Distribution Circuits

Harmonics Issues that Limit Solar Photovoltaic Generation on Distribution Circuits WREF 01 Paper # 048 Harmonics Issues that Limit Solar Photovoltaic Generation on Distribution Circuits Ketut Dartawan Ricardo Austria, Le Hui and Mark Suehiro* Pterra Consulting Maui Electric Company*

More information

TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR INTERCONNECTION OF GENERATION FACILITIES NOT SUBJECT TO FERC JURISDICTION

TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR INTERCONNECTION OF GENERATION FACILITIES NOT SUBJECT TO FERC JURISDICTION TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR INTERCONNECTION OF GENERATION FACILITIES NOT SUBJECT TO FERC JURISDICTION Document 9022 Puget Sound Energy, Inc. PSE-TC-160.70 December

More information

RENEWABLE ENERGY SUB-CODE for Distribution Network connected Variable Renewable Energy Power Plants in Ghana

RENEWABLE ENERGY SUB-CODE for Distribution Network connected Variable Renewable Energy Power Plants in Ghana RENEWABLE ENERGY SUB-CODE for Distribution Network connected Variable Renewable Energy Power Plants in Ghana JANUARY 2015 i Table of Content PART A: 1 1 Introduction 1 1.1 Scope 1 1.2 Status 1 1.3 Terms

More information

Transmission Interconnection Requirements for Inverter-Based Generation

Transmission Interconnection Requirements for Inverter-Based Generation Transmission Requirements for Inverter-Based Generation June 25, 2018 Page 1 Overview: Every generator interconnecting to the transmission system must adhere to all applicable Federal and State jurisdictional

More information

Anti-IslandingStrategyforaPVPowerPlant

Anti-IslandingStrategyforaPVPowerPlant Global Journal of Researches in Engineering: F Electrical and Electronics Engineering Volume 15 Issue 7 Version 1.0 Type: Double Blind Peer Reviewed International Research Journal Publisher: Global Journals

More information

PowerMonitor 5000 Family Advanced Metering Functionality

PowerMonitor 5000 Family Advanced Metering Functionality PowerMonitor 5000 Family Advanced Metering Functionality Steve Lombardi, Rockwell Automation The PowerMonitor 5000 is the new generation of high-end electrical power metering products from Rockwell Automation.

More information

IEEE Major Revision of Interconnection Standard

IEEE Major Revision of Interconnection Standard IEEE 1547-2018 - Major Revision of Interconnection Standard NRECA & APA s Emerging Priorities in Energy Research Day, Anchorage, AK Charlie Vartanian PE Secretary, IEEE 1547 Working Group October 31, 2018

More information

Risk of unintentional islanding in the presence of multiple inverters or mixed generation types

Risk of unintentional islanding in the presence of multiple inverters or mixed generation types Risk of unintentional islanding in the presence of multiple inverters or mixed generation types presented by: Chris Mouw Northern Plains Power Technologies Brookings, SD USA Brief introduction to NPPT

More information

POWER QUALITY AND SAFETY

POWER QUALITY AND SAFETY POWER QUALITY AND SAFETY Date : November 27, 2015 Venue : 40 th IIEE Annual National Convention and 3E XPO 2015 PRESENTATION OUTLINE Power Quality I. INTRODUCTION II. GRID CODE REQUIREMENTS III. ERC RESOLUTION

More information

EE 742 Power System Components. Y. Baghzouz ECE Department UNLV

EE 742 Power System Components. Y. Baghzouz ECE Department UNLV EE 742 Power System Components Y. Baghzouz ECE Department UNLV Desire to have a system with high reliability and power quality High reliability ensured by High quality of components High level of system

More information

Fuel cell power system connection. Dynamics and Control of Distributed Power Systems. DC storage. DC/DC boost converter (1)

Fuel cell power system connection. Dynamics and Control of Distributed Power Systems. DC storage. DC/DC boost converter (1) Dynamics and Control of Distributed Power Systems Fuel cell power system connection Ian A. Hiskens University of Wisconsin-Madison ACC Workshop June 12, 2006 This topology is fairly standard, though there

More information

Impact of Distributed Generation on Voltage Regulation by ULTC Transformer using Various Existing Methods

Impact of Distributed Generation on Voltage Regulation by ULTC Transformer using Various Existing Methods Proceedings of the th WSEAS International Conference on Power Systems, Beijing, China, September -, 200 Impact of Distributed Generation on Voltage Regulation by ULTC Transformer using Various Existing

More information

OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS

OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS AND MEDIUM-SIZE FACILITIES (5,000-25,000KW) CONNECTED

More information

Islanding Detection and Frequency Circuit Measurement by Power Distribution Relation Depending on the Angle

Islanding Detection and Frequency Circuit Measurement by Power Distribution Relation Depending on the Angle 215 International Journal of Smart Electrical Engineering, Vol.5, No.4, Fall 2016 ISSN: 2251-9246 pp. 215:220 Islanding Detection and Frequency Circuit Measurement by Power Distribution Relation Depending

More information

1200 MW Fault Induced Solar Photovoltaic Resource Interruption Disturbance Report

1200 MW Fault Induced Solar Photovoltaic Resource Interruption Disturbance Report 1200 MW Fault Induced Solar Photovoltaic Resource Interruption Disturbance Report Rich Bauer Associate Director Reliability Risk Management / Event Analysis Mid C Seminar July 19, 2017 Western Interconnection

More information

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar Electrical Engineering department, Jabalpur Engineering College Jabalpur, India Abstract:

More information

Sizing Generators for Leading Power Factor

Sizing Generators for Leading Power Factor Sizing Generators for Leading Power Factor Allen Windhorn Kato Engineering 24 February, 2014 Generator Operation with a Leading Power Factor Generators operating with a leading power factor may experience

More information

Damping and Harmonic Control of DG Interfacing. Power Converters

Damping and Harmonic Control of DG Interfacing. Power Converters University of Alberta Damping and Harmonic Control of DG Interfacing Power Converters by Jinwei He A thesis submitted to the Faculty of Graduate Studies and Research in partial fulfillment of the requirements

More information

TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR SMALL GENERATION INTERCONNECTIONS

TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR SMALL GENERATION INTERCONNECTIONS TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR SMALL GENERATION INTERCONNECTIONS Puget Sound Energy, Inc. PSE-ET-160.60 October 30, 2007 TABLE OF CONTENTS 1. INTRODUCTION...1 1.1 GENERAL

More information

A Simple Technique for Islanding Detection with Negligible Nondetection Zone

A Simple Technique for Islanding Detection with Negligible Nondetection Zone A Simple Technique for Islanding Detection with Negligible Nondetection Zone The MIT Faculty has made this article openly available. Please share how this access benefits you. Your story matters. Citation

More information

Improvement of Islanding Detector Using Interharmonics Current Injection Method and Its Applications

Improvement of Islanding Detector Using Interharmonics Current Injection Method and Its Applications FEATURED TOPIC Improvement of Islanding Detector Using Interharmonics Current Injection Method and Its Applications Sadayuki ISHIKURA*, Hideyuki NAKATANI, Junya TAKAGI, Tsutomu FUKADA, Shoji NISHIMURA

More information

900 MW Fault Induced Solar Photovoltaic Resource Interruption Disturbance Report

900 MW Fault Induced Solar Photovoltaic Resource Interruption Disturbance Report 900 MW Fault Induced Solar Photovoltaic Resource Interruption Disturbance Report Southern California Event: October 9, 2017 Joint NERC and WECC Staff Report February 2018 NERC Report Title Report Date

More information

Distributed Solar Integration Experiences

Distributed Solar Integration Experiences Distributed Solar Integration Experiences Prepared by: Philip Barker Founder and Principal Engineer Nova Energy Specialists, LLC Schenectady, NY Phone (518) 346 9770 Website: novaenergyspecialists.com

More information

Technical information Grid Support Utility Interactive Inverters for Sunny Central-US and Sunny Central Storage-US

Technical information Grid Support Utility Interactive Inverters for Sunny Central-US and Sunny Central Storage-US Technical information Grid Support Utility Interactive Inverters for Sunny Central-US and Sunny Central Storage-US ENGLISH SC-US-GridServices-TI-en-10 Version 1.0 Table of Contents SMA Solar Technology

More information

Ameren Illinois Company d/b/a Ameren Illinois Smart Inverter Specifications

Ameren Illinois Company d/b/a Ameren Illinois Smart Inverter Specifications 1. SCOPE OF WORK 1.1 Purpose This document is formulated to provide guidance to SMART inverter installers in Illinois. The document provides the minimum specification for inverters that interconnect with

More information

EH2741 Communication and Control in Electric Power Systems Lecture 2

EH2741 Communication and Control in Electric Power Systems Lecture 2 KTH ROYAL INSTITUTE OF TECHNOLOGY EH2741 Communication and Control in Electric Power Systems Lecture 2 Lars Nordström larsno@kth.se Course map Outline Transmission Grids vs Distribution grids Primary Equipment

More information

Manjeet Baniwal 1, U.Venkata Reddy 2, Gaurav Kumar Jha 3

Manjeet Baniwal 1, U.Venkata Reddy 2, Gaurav Kumar Jha 3 Application of to alleviate voltage sag and swell Manjeet Baniwal 1, U.Venkata Reddy 2, Gaurav Kumar Jha 3 123 (Electrical Engineering, AGPCE Nagpur/ RTMNU, INDIA) ABSTRACT : This paper deals with modelling

More information

Power Quality Compensation by using UPFC

Power Quality Compensation by using UPFC ISSN: 2454-132X Impact factor: 4.295 (Volume 4, Issue 2) Available online at: www.ijariit.com Power Quality Compensation by using UPFC P. Madhumathi madhumathi9196@gmail.com Vivekanada College of Engineering

More information

Generation Interconnection Requirements at Voltages 34.5 kv and Below

Generation Interconnection Requirements at Voltages 34.5 kv and Below Generation Interconnection Requirements at Voltages 34.5 kv and Below 2005 March GENERATION INTERCONNECTION REQUIREMENTS AT 34.5 KV AND BELOW PAGE 1 OF 36 TABLE OF CONTENTS 1. INTRODUCTION 5 1.1. Intent

More information

TECHNICAL GUIDELINE FOR THE INTERCONNECTION OF DISTRIBUTED ENERGY RESOURCES TO EPCOR DISTRIBUTION AND TRANSMISSION INC. S DISTRIBUTION SYSTEM

TECHNICAL GUIDELINE FOR THE INTERCONNECTION OF DISTRIBUTED ENERGY RESOURCES TO EPCOR DISTRIBUTION AND TRANSMISSION INC. S DISTRIBUTION SYSTEM TECHNICAL GUIDELINE FOR THE INTERCONNECTION OF DISTRIBUTED ENERGY RESOURCES TO EPCOR DISTRIBUTION AND TRANSMISSION INC. S DISTRIBUTION SYSTEM January 5, 2017 Francesco Mannarino SVP, Electricity Operations

More information

IEEE SCC Standards Update

IEEE SCC Standards Update IEEE SCC21 1547 Standards Update Michael Coddington, Tom Basso National Renewable Energy Laboratory Presented at the Solar Power International Conference IEEE Std 1547a Amendment 1, May 2014 (Amendment

More information

COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR)

COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR) 7 February 2018 RM Zavadil COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR) Brief Overview of Sub-Synchronous Resonance Series

More information

Harmonics and Their Impact on Power Quality. Wayne Walcott Application Engineering Manager June, 2017

Harmonics and Their Impact on Power Quality. Wayne Walcott Application Engineering Manager June, 2017 Harmonics and Their Impact on Power Quality Wayne Walcott Application Engineering Manager June, 2017 Presentation Overview A little about harmonics What are harmonics What are NOT harmonics What creates

More information

2012 Grid of the Future Symposium. Impacts of the Decentralized Photovoltaic Energy Resources on the Grid

2012 Grid of the Future Symposium. Impacts of the Decentralized Photovoltaic Energy Resources on the Grid 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2012 Grid of the Future Symposium Impacts of the Decentralized Photovoltaic Energy Resources on the Grid B. ENAYATI, C.

More information

GUIDE FOR GENERATOR INTERCONNECTION THE WIRES OWNER DISTRIBUTION SYSTEM

GUIDE FOR GENERATOR INTERCONNECTION THE WIRES OWNER DISTRIBUTION SYSTEM DATE: 200/06/2 PAGE 1 of GUIDE FOR GENERATOR INTERCONNECTION TO THE WIRES OWNER DISTRIBUTION SYSTEM The intent of this Guide is to establish the interconnection requirements of Distributed Resources with

More information

Harmonic Analysis of 1.5 kw Photovoltaic System in the Utility Grid

Harmonic Analysis of 1.5 kw Photovoltaic System in the Utility Grid Harmonic Analysis of 1.5 kw Photovoltaic System in the Utility Grid V.Tamilselvan 1, V.Karthikeyan 2 Associate Professor, Dept. of EEE, Adhiyamaan College of Engineering, Hosur, Tamilnadu, India 1,2 ABSTRACT:

More information

GENERATOR INTERCONNECTION APPLICATION Category 3 For All Projects with Aggregate Generator Output of More Than 150 kw but Less Than or Equal to 550 kw

GENERATOR INTERCONNECTION APPLICATION Category 3 For All Projects with Aggregate Generator Output of More Than 150 kw but Less Than or Equal to 550 kw GENERATOR INTERCONNECTION APPLICATION Category 3 For All Projects with Aggregate Generator Output of More Than 150 kw but Less Than or Equal to 550 kw ELECTRIC UTILITY CONTACT INFORMATION Consumers Energy

More information

Connection Impact Assessment Application

Connection Impact Assessment Application Connection Impact Assessment Application This form is for generators applying for Connection Impact Assessment (CIA) and for generators with a project size >10 kw. Please return the completed form by email,

More information

MICROPROCESSOR-BASED METERING EQUIPMENT SECTION 16901C PART 2

MICROPROCESSOR-BASED METERING EQUIPMENT SECTION 16901C PART 2 PART 1 PART 2 PRODUCTS 2.01 MANUFACTURERS A. Eaton products B.. C.. The listing of specific manufacturers above does not imply acceptance of their products that do not meet the specified ratings, features

More information

Thyristorised Automatic Power Factor

Thyristorised Automatic Power Factor Thyristorised Automatic Power Factor Correction with 7% D Tune Harmonics Suppression (Reactor/Filtering) System Power quality? In the present Low voltage (LV) industrial distribution system the power factor

More information

Poornima G P. IJECS Volume 3 Issue 6 June, 2014 Page No Page 6453

Poornima G P. IJECS Volume 3 Issue 6 June, 2014 Page No Page 6453 www.ijecs.in International Journal Of Engineering And Computer Science ISSN:2319-7242 Volume 3 Issue 6 June, 2014 Page No. 6453-6457 Role of Fault Current Limiter in Power System Network Poornima G P.1,

More information

Embedded Generation Connection Application Form

Embedded Generation Connection Application Form Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed

More information

Unit.2-Voltage Sag. D.Maharajan Ph.D Assistant Professor Department of Electrical and Electronics Engg., SRM University, Chennai-203

Unit.2-Voltage Sag. D.Maharajan Ph.D Assistant Professor Department of Electrical and Electronics Engg., SRM University, Chennai-203 Unit.2-Voltage Sag D.Maharajan Ph.D Assistant Professor Department of Electrical and Electronics Engg., SRM University, Chennai-203 13/09/2012 Unit.2 Voltage sag 1 Unit-2 -Voltage Sag Mitigation Using

More information

1. Introduction to Power Quality

1. Introduction to Power Quality 1.1. Define the term Quality A Standard IEEE1100 defines power quality (PQ) as the concept of powering and grounding sensitive electronic equipment in a manner suitable for the equipment. A simpler and

More information

Embedded Generation Connection Application Form

Embedded Generation Connection Application Form Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed

More information

Optimal sizing of battery energy storage system in microgrid system considering load shedding scheme

Optimal sizing of battery energy storage system in microgrid system considering load shedding scheme International Journal of Smart Grid and Clean Energy Optimal sizing of battery energy storage system in microgrid system considering load shedding scheme Thongchart Kerdphol*, Yaser Qudaih, Yasunori Mitani,

More information

EE Grid-Tied PV Systems. Y. Baghzouz Spring 2011

EE Grid-Tied PV Systems. Y. Baghzouz Spring 2011 EE 495-695 Grid-Tied PV Systems Y. Baghzouz Spring 2011 Applicable Codes & Standards Most Important: NEC IEEE Std 1547 Summary of Content of NEC NEC (Voltage Drop Requirement) NEC requires that the voltage

More information

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75 PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion

More information

Technical information SUNNY TRIPOWER CORE1-US

Technical information SUNNY TRIPOWER CORE1-US Technical information SUNNY TRIPOWER CORE1-US Grid Support Utility Interactive Inverters ENGLISH STP50-US-40-GridServices-TI-en-10 Version 1.0 Table of Contents SMA Solar Technology America LLC Table of

More information

DYNAMIC VOLTAGE RESTORER FOR VOLTAGE SAG MITIGATION IN OIL & GAS INDUSTRY

DYNAMIC VOLTAGE RESTORER FOR VOLTAGE SAG MITIGATION IN OIL & GAS INDUSTRY Department of Electrical Engineering Senior Design Project ELEC 499 DYNAMIC VOLTAGE RESTORER FOR VOLTAGE SAG MITIGATION IN OIL & GAS INDUSTRY Student Names: Chresteen Baraket Marina Messiha Supervised

More information

Protection of Microgrids Using Differential Relays

Protection of Microgrids Using Differential Relays 1 Protection of Microgrids Using Differential Relays Manjula Dewadasa, Member, IEEE, Arindam Ghosh, Fellow, IEEE and Gerard Ledwich, Senior Member, IEEE Abstract A microgrid provides economical and reliable

More information

Dynamic Harmonic Mitigation and Power Factor Correction

Dynamic Harmonic Mitigation and Power Factor Correction Dynamic Harmonic itigation and Power Factor Correction Cesar Chavez, Eng Engineering Dept., Arteche. Naucalpan, Edo. de éxico, éxico John A. Houdek, ember, IEEE President, Allied Industrial arketing ilwaukee,

More information

Power Quality Basics. Presented by. Scott Peele PE

Power Quality Basics. Presented by. Scott Peele PE Power Quality Basics Presented by Scott Peele PE PQ Basics Terms and Definitions Surge, Sag, Swell, Momentary, etc. Measurements Causes of Events Possible Mitigation PQ Tool Questions Power Quality Measurement

More information

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss Siemens AG, EV NP3 P.O. Box 3220 91050 Erlangen, Germany e-mail: Michael.Weinhold@erls04.siemens.de

More information