ON THE USE OF MULTI-HARMONIC LEAST-SQUARES FITTING FOR THD ESTIMATION IN POWER QUALITY ANALYSIS

Size: px
Start display at page:

Download "ON THE USE OF MULTI-HARMONIC LEAST-SQUARES FITTING FOR THD ESTIMATION IN POWER QUALITY ANALYSIS"

Transcription

1 Metrol. Meas. Syst., Vol. XIX (2012), No. 2, pp METROLOGY AND MEASUREMENT SYSTEMS Index , ISSN ON THE USE OF MULTI-HARMONIC LEAST-SQUARES FITTING FOR THD ESTIMATION IN POWER QUALITY ANALYSIS Pedro M. Ramos 1), Fernando M. Janeiro 2), Tomáš Radil 3) 1) Instituto de Telecomunicações, DEEC, Instituto Superior Técnico, Tecnical University of Lisbon, Av. Rovisco Pais 1, Lisbon, Portugal ( pedro.m.ramos@ist.utl.pt, ) 2) Instituto de Telecomunicações, Universidade de Évora, Departamento de Física, Rua Romão Ramalo, nº. 59, Évora, Portugal (fmtj@uevora.pt) 3) Instituto de Telecomunicações, Av. Rovisco Pais 1, Lisbon, Portugal (tomas.radil@lx.it.pt) Abstract Te quality of te supplied power by electricity utilities is regulated and of concern to te end user. Power quality disturbances include interruptions, sags, swells, transients and armonic distortion. Te instruments used to measure tese disturbances ave to satisfy minimum requirements set by international standards. In tis paper, an analysis of multi-armonic least-squares fitting algoritms applied to total armonic distortion (THD) estimation is presented. Te results from te different least-squares algoritms are compared wit te results from te discrete Fourier transform (DFT) algoritm. Te algoritms are assessed in te different testing states required by te standards. Keywords: Harmonic analysis, Power quality, Signal reconstruction, Spectral analysis, Harmonic distortion Polis Academy of Sciences. All rigts reserved 1. Introduction Power quality issues are of major concern to power producers, distributors and consumers [1]. Due to te increase in use of nonlinear loads, armonic distortions are an ever increasing important issue in power quality analysis. Wile many of te typical disturbances tat directly affect consumers are related wit power outages (i.e., interruptions), armonic distortions can also cause major damages wile not perceived by end users except wen equipment fails. Traditionally, in measurements of power quality disturbances, te main strain on te measurement system is caused by te detection and classification of transients due to te required ig sampling rate [2]. However, regulatory bodies are usually not concerned wit transients, as Quality of Service (QoS) is mainly associated wit RMS variations (e.g., sags, swells, interruptions), frequency sifts, flicker, voltage unbalance and armonic distortion. Terefore, a measurement device used for te assessment of quality of service must measure tese parameters in real-time [3] and generate aggregate values according to te regulatory norms in effect in eac country [4-6]. From te list of disturbances tat must be assessed in quality of service related wit power quality, te estimation of te armonic component amplitudes and te total armonic distortion (THD) is te most complex measurement [7]. For example, in IEC [4] for te Class I (equivalent to Class A in IEC [5]) te suggested metod to determine te armonic components is to estimate te FFT of te acquired signal and ten estimate te individual amplitudes of te armonic components to determine te THD. However, te estimation of te FFT requires a furter strain on te acquisition system because it requires syncronous acquisition to ensure tat any frequency variations do not cause spectral leakage and errors in te estimation of te armonic amplitudes and on te final THD Article istory: received on Feb. 3, 2012; received in revised form on Apr. 16, 2012; accepted on Apr. 17, 2012; available online on May 18, 2012.

2 P.M. Ramos, F.M. Janeiro, T. Radil: ON THE USE OF MULTI-HARMONIC LEAST-SQUARES FITTING value [8]. In [9] an efficient alternative to te use of coerent sampling was proposed for active power estimation, based on windowing. Time-frequency algoritms suc as te Gabor- Wigner Transform (GWT) ave also been proposed for power quality assessment [10]. Tis paper describes te DSP implementation of an alternative metod for te estimation of te armonic amplitudes and THD value tat does not require syncronous acquisition. Te metod is based on least-squares fitting of te acquired samples [11]. Te outputs of tis metod are te armonic amplitudes, te armonic pases (not directly relevant for te assessment of power quality armonic distortions) and te THD. As a by-product, te use of tis algoritm enables te estimation of a new parameter called total interarmonic distortion (TIHD) wic accounts for te distortion present in te signal tat does not correspond to armonic distortion. Tis new parameter is estimated by removing, from te initially acquired signal, te signal reconstructed from te estimated armonics (using te amplitudes and pases of eac armonic) and ten estimating te RMS value of tese residuals. Tis parameter enables te detection of events caused by non-armonics of te fundamental signal. Tis paper includes a detailed description of te algoritm and also of te details required for implementation in a DSP-based standalone QoS measurement system. Extensive tests of te proposed algoritm will demonstrate its compliance wit te uncertainty limits set in IEC in te tree testing states wic include oter disturbances besides armonic distortions (namely frequency variations, flicker, voltage amplitude variations and presence of interarmonics). Te standard IEC requires tat, in tese tree test states and wit te presence of te oter disturbances, te armonic evaluation must remain witin certain boundaries for eac specific armonic. Te accuracy requirements depend on te Class of instrument: Class I of te IEC corresponds to Class A of IEC , wile Class II of te IEC corresponds to Class S of IEC Te requirements are based on te relation between te magnitudes of te measured armonics and te nominal voltage range. In te end, te decision to implement a specific algoritm in a standalone DSP-based measurement system [12, 13] depends on te suitability of te algoritm to estimate te desired parameter (in tis case te armonic amplitudes and te THD), on te speed wit wic te algoritm can be executed (of particular importance for real-time systems suc as power quality QoS assessment) and te amount of memory te algoritm requires (crucial in standalone measurement systems were memory is scarce and an expensive add-on tat can also slow down algoritm execution). 2. Power quality standard and armonic estimation In tis section, an overview of te standards tat specify te conditions for power metering instrument testing is presented. Te IEEE 1159 standard [6] classifies armonics in an electric power system as te steady-state waveform distortions tat are in te range 0 Hz to 9 khz wit a magnitude up to 20% of te fundamental. Te general instrument used to measure armonic distortion is described in standard IEC [4]. Altoug te standard proposes a DFT-based instrument, it allows te use of different algoritms. Measurement metods in power quality parameters are defined in IEC [5] wic requires tat at least 50 armonics are estimated. Te accuracy requirements for armonic estimation are defined in standard and are divided into two classes: Class I and Class II. Te classes correspond to different accuracy requirements in te relation between te magnitude of te measured armonics u and te nominal voltage range u nom. A tird class of instruments, (Class B in IEC ), is also defined for instruments wose performance is defined by te manufacturer. Te accuracy requirements for Class I and Class II are sown in Table

3 Metrol. Meas. Syst., Vol. XIX (2012), No. 2, pp Standard IEC specifies te measuring range using te compatibility levels defined in standard IEC [14] for low-frequency disturbances in industrial environments. Te compatibility levels depend on te maximum disturbance levels tat a device may be subjected to. For Class A devices te measuring range sould be from 10% to 200% of te Class 3 compatibility levels defined in IEC , wile for te lessaccurate Class S it sould be from 10% to 100% of te same Class 3 levels. Tese Class 3 compatibility levels are sown in Table 2. Te compatibility levels for odd armonics are iger tan tose for te even armonics, as it is usual in power systems to ave dominant odd armonics. Tis standard also defines tat, for class 3, te maximum total armonic distortion is 10%. Table 1. Accuracy requirements for Class I and Class II voltage armonics measurement. Class Condition Maximum Error I u 1% unom ± 5% u u < 1% unom ± 0.05% u nom II u 3% unom ± 5% u u < 3% unom ± 0.15% u nom Table 2. Voltage armonics compatibility levels defined in IEC for Class 3. Harmonic order Class 3 compatibility level % of fundamental Harmonic order Class 3 compatibility level % of fundamental < 50 ( even) < ( odd multiples of tree) < 49 ( odd) 4.5 (17/) 0.5 Te test signals used in te classification of te measurement instruments sould include oter disturbances besides te armonic content. Tree testing states are defined in IEC corresponding to different levels of disturbances. Te conditions for eac testing state are described in Table 3. Te nominal power frequency is f nom and P st is te sort-term flicker severity. Table 3. IEC testing state conditions for Class A and Class S instruments. Quantity Testing State 1 Testing State 2 Testing State 3 Frequency f ± 0.5 Hz f 1 Hz ± 0.5 Hz f + 1 Hz ± 0.5 Hz nom Flicker P st < 0.1 P st = 1± 0.1 P st = 4 ± 0.1 Determined by flicker and Determined by flicker and Voltage u nom ± 1% interamonics interamonics Inter-armonics 0% to 0.5% of u nom 1% ± 0.5% of unom at 7.5f nom 1% ± 0.5% of unom at 3.5f nom 3. Least-squares fitting algoritms In tis section, te least-squares fitting algoritms are described and teir use for te estimation of te total armonic distortion is detailed. In [15] and [16], two basic sine-fitting nom nom 297

4 P.M. Ramos, F.M. Janeiro, T. Radil: ON THE USE OF MULTI-HARMONIC LEAST-SQUARES FITTING algoritms were standardized for ADC and waveform records testing. Tese algoritms are not multi-armonic in te sense tat tey only estimate te parameters of te fundamental. Multi-armonic versions of te sine-fitting algoritms were developed in [11] and improved in [17]. Tese algoritms were successfully used in impedance measurements [18, 19]. Modern power quality analyzers are based on acquisition systems were an analog-todigital converter (ADC) is used to sample te voltage sensor output at a given sampling rate (for 3-pase systems tere is one ADC for eac pase). Typically a digital signal processor (DSP) retrieves te digital output of te ADC samples and algoritms implemented in te DSP are ten used to estimate te desired parameters of te acquired signal (for example, frequency, RMS value, average value, armonic amplitudes and total armonic distortion). Specifically for te estimation of te armonic distortion, it is usual to consider tat te distortion is of a steady-state nature in te sense tat te causes of armonic distortion are not completely random in nature and tat te duration of suc distortions largely exceeds te period of te acquired signal. Terefore, te acquired signal is modeled by H ( ) = + cos( 2π ) + sin ( 2π ) + ε ( ) = + cos( 2π + ϕ ) + ε ( ) (1) u t C A ft B ft u t C D ft u t = 1 = 1 were C is te DC component, f is te signal frequency, H is te number of armonics considered in te model, A is te in-pase amplitude of armonic, B is te in-quadrature amplitude of armonic, D is te amplitude of armonic, ϕ is te pase of armonic and u ( t) ε accounts for te residuals of te model (wic will include iger armonics, interarmonics, noise and oter disturbances suc as transients). Te signal fundamental corresponds to = 1 wile te armonics correspond to > 1. Ideally, all te armonics sould ave zero amplitude. Note tat bot representations in (1) are equivalent and related by H ( ) D = A + B ϕ = atan 2 B, A (2) 2 2 or reciprocally by A = D cos( ϕ ) and B D sin ( ) = ϕ. Te Total Harmonic Distortion (THD) is an indicator used to express te total amount of armonic components. It is defined as te ratio between te RMS of te armonics and te RMS of te fundamental THD 2 H D = = 2 D1. (3) Te THD is usually expressed in relative units or in percentage. Te use of logaritmic units (db) is usually limited to te analysis of distortion in linear systems were distortion is muc smaller tan in power systems. For stationary signals wose lengt is exactly 10 cycles for 50 Hz power systems or 12 in case of 60 Hz power systems, te wole energy of a armonic component is concentrated in one frequency bin of te FFT (i.e., tere is no spectral leakage). However, if te signal s parameters cange suc as its fundamental frequency, te energy will leak into nearby frequency bins due to spectral leakage. To take into account tis effect, standard IEC defines two more indicators: te group total armonic distortion (THDG) and te subgroup total armonic distortion (THDS). Te group total armonic distortion is defined as 298

5 Metrol. Meas. Syst., Vol. XIX (2012), No. 2, pp THDG 2 H U g, = = 2 U g,1 2 2, were U g, U [ P k] 2 P P 2 P U P 1 U P = + +, (4) 2 2 P k = were P is te number of periods in te acquisition segment and U [ k ] is te amplitude of eac individual frequency component obtained from te FFT. Te subgroup total armonic distortion is defined as THDS 2 H U sg, = = 2 U sg,1 2 2, were U sg, = U [ P + k] 1, (5) meaning tat te RMS value of eac armonic is obtained from te tree FFT elements closer to te ideal armonic frequency. Note tat tese two parameters are solely defined and of relevance to enable te use of te FFT under spectral leakage conditions. Te use of leastsquares fitting directly estimates te armonic amplitudes and is immune to spectral leakage since it does not require te use of te FFT. Te Total InterHarmonic Distortion (TIHD) is an indicator used to express te total value of RMS not associated wit te fundamental or te armonics in te acquired signal 1 N 2 TIHD uε n N n= 1 [ ] k = 1 =, (6) were N is te number of samples in te acquisition segment and u [ n] ε is te residual associated wit sample n. In te following subsections te four basic least-squares algoritms are presented. Teir use to estimate te THD will be addressed in Section Tree-parameter sine-fitting Te tree-parameter sine-fitting estimates tree parameters of te signal model: te inpase amplitude, te in-quadrature amplitude and te DC component. It requires te knowledge of te signal frequency and it is a multiple linear regression. Te estimated parameters x are obtained from T T 1 T x [ C A B ] D D D u wit = [ ] = 1 1 = D 1 c s, (7) 1 1 were u is te vector wit te N samples and 1 is a vector wit N rows all equal to 1, = cos 2πf s = sin 2πft and t is te N rows vector wit te timestamps c ( t ), ( ) corresponding to eac sample. Tis algoritm is not iterative and terefore it is quite straigtforward to be used. However, due to te fact tat te frequency is not estimated and tat te frequency in power systems can cange, it is not actually suited for direct use in te assessment of te armonic amplitudes. To also estimate te signal frequency, te four-parameter sine-fitting sould be used. If te DC component is not required, te algoritm can be adapted by removing te first element of vector x and te first column of matrix D. Tis modification does not cange te estimation results. 299

6 P.M. Ramos, F.M. Janeiro, T. Radil: ON THE USE OF MULTI-HARMONIC LEAST-SQUARES FITTING 3.2. Four-parameter sine-fitting Te four-parameter sine-fitting is iterative (due to te fact tat te frequency must also be estimated, it is no longer a multiple linear regression) and te estimated parameters in ( i) ( i) T = C A1 B 1 ω iteration i are x were ( i) ω is te angular frequency correction in iteration i wic is used to update te estimated angular frequency correction of te previous ( i) ( i) ( i 1) ( i) iteration wit ω = 2π f = ω + ω. Te estimated parameters are obtained wit [ ] D = 1 c s α were ( i 1) ( i 1) ( ) ( ) α = A t os + B t o c ( o is te Hadamard product or entrywise product). Note tat D must be recalculated in eac iteration because te frequency canges and te amplitudes estimated in te previous iteration are used to determine α. Te criterion to detect convergence is to stop te iterations wen te absolute relative frequency correction is below a tresold, i.e., wen ω ω <ε = 10. ( i) ( i) 7 ω In tis algoritm it is crucial to begin wit te best estimated values for te frequency and amplitudes. If improper estimations are used, te algoritm may require many iterations to converge or even fail to converge. To ensure a reduced number of iterations, te initial frequency estimation is usually obtained from te IpDFT [20] and te in-pase and inquadrature amplitudes are obtained from te tree-parameter sine-fitting algoritm (using te IpDFT estimated signal frequency). By complying wit tese basic rules, te number of iterations is typically below Non-iterative multi-armonic fitting Te non-iterative multi-armonic fitting can estimate te amplitudes of te armonics for a given frequency. Te 2H+1 estimated parameters are x = [ C A1 B1 A2 B2 L AH BH ] T 1 T wic are obtained from x D D D u wit D = [ 1 c s c s L c s ] T. Note tat D = H H as N rows and 2H+1 columns. Te elements of x can be used to estimate te THD using (2) and (3). If te DC component is not required, te algoritm can also be adapted by removing te first element of x and te first column of D witout canging te THD estimation results Iterative multi-armonic fitting Te iterative multi-armonic fitting also estimates te signal frequency muc like te fourparameter sine-fitting algoritm. Te 2H+2 estimated parameters are H x ( i) T = C A1 B1 A2 B L 2 AH B H ω and D = 1 c s c s L c H sh α. = 1 Obviously, tis is te most direct algoritm to estimate te THD but it comes wit a cost bot memory-wise and computationally. 4. Use of least-squares fitting algoritms for THD estimation Tree different options to use te least-squares fitting algoritms for THD estimation are presented in tis section. In all situations, te outcome is te armonic amplitudes, teir pases, te fundamental frequency and te DC component. Ten, te THD is directly obtained from (3) wile TIHD can be obtained from (6) using te residuals of te fit. 300

7 Metrol. Meas. Syst., Vol. XIX (2012), No. 2, pp Te first option is to use te four-parameter sine-fitting on te acquired signal to estimate te signal frequency, te DC component and te fundamental parameters. Te residuals of tis fit are ten applied to te tree-parameter sine-fitting (witout DC component) to estimate te parameters of te second armonic (=2) and so on until all te armonics are estimated. Te main drawbacks of tis metod are tat te errors of te signal frequency are propagated into te armonics and te need to estimate te residuals is an added computational burden. Te second option is to apply te four-parameter sine-fitting to obtain te frequency and parameters of te fundamental and ten apply te non-iterative multi-armonic fitting to its residuals. Tis estimates, in one step, te parameters of all armonics and reduces te computational burden of estimating te residuals of te tree-parameter sine-fitting for eac armonic. Te drawback is caused by te fact tat te frequency is estimated in te first step and its errors are accumulated in te multi-armonic fit. Anoter disadvantage is te fact tat te burden of te multi-armonic fit is considerably iger tan tat of te tree-parameter sine-fitting. However, since te multi-armonic is applied only once and te tree-parameter fitting must be applied to eac armonic, te overall computational burden must be assessed. Te tird option is to use solely te iterative multi-armonic fitting. Tis option is straigtforward but it is te most demanding, computationally and memory-wise. 5. Developed power quality analyzer In tis section, te developed power quality analyzer is described. Different sensor modules are available using a wide selection of ranges (namely for te current). Eac of tese modules can be used to interface te power system and te acquisition and processing module. In addition tere is one module responsible for power management wic includes a backup recargeable Li-Ion battery to power te system in case of sags and interruptions. Wen power is restored te battery is recarged. If te battery is totally drained during a longer interruption, te system suts down and restarts wen power is restored. Te acquisition and processing module includes some analog signal conditioning for eac cannel (from te current and voltage sensors), one 16-bit analog to digital converter (ADC) per cannel, a memory module to add storage capacity during processing and one digital signal processor were te samples are processed and te algoritms are implemented. Te system block diagram is presented in Fig. 1. V I Signal conditioning ADC ADC Data A CLK CS Data B RAM DSP Tx SD Memory card Rx USB USB Power management Li-Ion DC/DC DC/DC 1.2V 3.3V 5V -5V 15V -15V 5V L N Power System Load PQ Analyzer Fig. 1. Basic block diagram of te implemented PQ analyzer. Te system can be interfaced by a SD memory card or a USB connection. Basically tese interfaces are used to store te detected events and monitor in real time te operation of te PQ analyzer. Te acquisition itself is controlled by te DSP wic sets te sampling rate of te ADCs to 50 ks/s. Eac acquisition segment lasts 3 s wic corresponds to

8 P.M. Ramos, F.M. Janeiro, T. Radil: ON THE USE OF MULTI-HARMONIC LEAST-SQUARES FITTING samples. DMA is used to transfer te acquired samples, during te segment acquisition, into te external memory. Wile one segment is being acquired, te previous segment must be completely processed by te DSP. Altoug tis paper is focused on te estimation of te total armonic distortion, in DSP all te algoritms for detection of events are implemented. In Fig. 2, te complete block diagram of te algoritms is presented. After a pre-processing stage, te algoritms are divided into two sections. In te lower section of Fig. 2, te RMS values are estimated and tresolds are used to determine if an event was detected and if so, te classification stage determines its amplitude, duration and type (sag, swell, overvoltage, undervoltage or interruption) from te RMS values [21]. c la s si fi ca t i o n c la s si f ic a t io n Fig. 2. Block diagram of te algoritms implemented in te PQ analyzer. Te second section deals wit te detection of transients and waveform distortions. Here, te first algoritm to be applied is te four-parameter sine-fitting to separate te fundamental from te rest of te signal (te residuals include armonics, interarmonics, transients and noise). To estimate if an event is present in te current segment, te morpological operation closing [22, 23] is used wit a structuring element of lengt equivalent to 50 ms. Wit tis operation, tresolding is ten a straigtforward operation to detect if an event is present since it groups multiple crossings of te tresold for a single event. Te duration of te event, as estimated from te closing operation, is ten used to assess wic class of event occurred. If te event duration is above 50 ms or if it is above 20 ms and te THD exceeds te THD tresold, ten it is a waveform distortion (eiter caused by THD armonic distortion or TIHD interarmonic waveform distortion). If tis condition is not verified, ten te event is a transient and anoter morpological closing operation is applied wit a smaller structuring element (equivalent to 4 ms) to separate transients tat migt be close to eac oter in te residuals and also to estimate wit better accuracy te duration of te transient. Te evaluation of te THD and TIHD is done using one of te algoritms defined in section IV in te gray block of Fig. 2. Notice, owever, tat te 4-parameter sine-fitting as already been applied and terefore te burden is reduced in te first two cases, wile in te tird case te full algoritm of te iterative multi-armonic sine-fitting must neverteless be applied. 6. Results Fig. 3 depicts an acquired waveform (50 Hz nominal frequency) wit some clear armonic distortion near te zero crossings of te rising edge of te sine signal. Also visible but less 302

9 Metrol. Meas. Syst., Vol. XIX (2012), No. 2, pp discernable are some armonic distortions near te signal peaks. Tis is a clear example of a power voltage distorted by te presence of non-linear loads. In Fig. 3, te amplitude units (pu) correspond to te traditional normalization wit respect to te nominal RMS value of te distribution voltage. Tis normalization is useful wen comparing systems wit different nominal RMS voltages and is widely used in PQ u (pu) u Time (s) Fig. 3. Example of distorted voltage signal in a power system. Since for Class A instruments, te measuring range is up to 200%, te armonic amplitudes can reac twice te values of te armonic levels of Table 2. Neverteless, te maximum total armonic distortion is 20% and if all te armonics ave teir maximum value, te THD would exceed tis limit value. Terefore, te signal used for testing can ave armonic amplitudes up to twice tose of Table 2 but making sure tat te THD does not exceed 20%. In Table 4, te armonic amplitudes of te test signals are presented. Tey represent a compromise between te maximum amplitude of te armonics and te desired THD value. Wit tese values, te THD is 20%. Table 4. Harmonic content of te test signal. For te armonic amplitudes presented in Table 4, te maximum allowed error for eac armonic for Class I and Class II (from Table 1) is presented in Fig. 4. Notice tat, for te iger order armonics, teir amplitude is muc lower and terefore, te maximum error is a percentage of te nominal system voltage and does not depend on te armonic amplitudes temselves. For all te testing states, te signals contained wite Gaussian noise wit 75 db SNR. For eac state, signals were tested and te maximum error of individual armonics amplitudes were registered. Maximum allowed error (%) Maximum allowed error (%) a) Harmonic a) Maximum allowed error (%) Maximum allowed error (%) b) Harmonic Fig. 4. Maximum allowed error in te estimation of eac armonic for te test signal wit te armonic content sown in Table 4 for: a) Class I instruments; b) Class II instruments. b) 6.1. Testing State 1 In tis testing state, relatively low flicker is applied, as well as low amplitude interarmonics, te frequency is centered on te nominal value and te nominal voltage can 303

10 P.M. Ramos, F.M. Janeiro, T. Radil: ON THE USE OF MULTI-HARMONIC LEAST-SQUARES FITTING cange by 1%. Te results obtained wit te four algoritms are presented in Fig. 5 te DFT results are also included for comparison. It can be seen tat almost all algoritms comply wit te requirements for Class A. Te combined four-parameter and tree-parameter sine-fitting algoritm only complies wit Class S Testing State 2 Fig. 5. Accuracy in te armonic amplitude estimation in testing state 1. In testing state 2 te frequency is centered 1 Hz below te nominal value wit some small variation and a moderate amount of flicker is included. A moderate-valued interarmonic is added at frequency 7.5f nom. Te results in tis testing state are presented in Fig. 6 and it can be seen tat bot iterative and noniterative multi-armonic algoritms satisfy te minimum requirements for instruments of bot Class A and Class S. Te combined four-parameter and tree-parameter sine-fitting algoritm only complies wit te requirements for Class S instruments as its maximum error at iger order armonics is just below 0.3% and well above 0.1%. Notice tat te results obtained in tis testing state are similar to te ones obtained in testing state Testing State 3 Fig. 6. Accuracy in te armonic amplitude estimation in testing state 2. In te tird testing state, te frequency is centered 1 Hz above its nominal value wit some small variation and a severe amount of flicker is included in te signal. Te included interarmonic as a moderate amplitude and is located at 3.5 f nom. Fig. 7 sows te results for tis testing state wit all te algoritms, including te DFT for comparison. Once again bot multi-armonic algoritms are fully compliant wit te requirements for bot instrument classes and perform better tan te DFT algoritm. Te combined four-parameter and treeparameter sine-fitting algoritm again only complies wit Class S instruments. Te maximum error results for all te tested algoritms are similar in all testing states. Fig. 7. Accuracy in te armonic amplitude estimation in testing state

11 Metrol. Meas. Syst., Vol. XIX (2012), No. 2, pp THD estimation comparison In Fig. 8, a comparison of te maximum error obtained wen estimating te THD value wit te different algoritms an as a function of te applied THD is presented for testing state 3. It can be seen tat te worst results are obtained for te THDG metod for THD values below 5% (caused by te interarmonics influencing te computation of THDG according to (4)) and tat for iger distortions, te worst algoritm is again te combined four-parameter and tree-parameter sine-fitting algoritm Max. error of THD estimation (%) Maximum error of THD estimation (%) DFT (THD) DFT (THDG) DFT (THDS) 4- and 3-par. sine fitting Non-iterative multiarmonic Multiarmonic THD (%) 7. Conclusions Fig. 8. Comparison of te THD accuracy for te tested algoritms in testing state 3. In tis paper a detailed comparison of least-squares fitting algoritms for THD estimation for power quality analyzers is presented. Tere are tree options tat can be used wit te main difference being te computational complexity and burden of te algoritms. One of te presented solutions (te combined four-parameter and tree-parameter sine-fitting algoritm) is only viable for Class S instruments wic correspond to instruments used for statistical applications suc as surveys or power quality assessment. For Class A instruments (used wen precise measurements are required) eiter multi-armonic algoritm may be used. It sould be noted tat te computational burden of tese algoritms puts added pressure on DSP-based systems. To reduce te computational burden of te least-squares fitting algoritms, decimation can be applied to te complete set of acquired samples. Tis is a valid approac because te maximum armonic to be assessed sould be near 9 khz and te sampling rate is muc iger (50 ks/s). Terefore if only one sample in eac 2 is used, te sampling rate would be reduced to 25 ks/s wic would still be enoug to estimate armonics up to 9 khz. If only 50 armonics are needed, te decimation factor can be increased and te computational burden furter reduced. Note tat te decimation sould be applied only before te Least Squares fitting block of Fig. 2 but tat te complete acquired signal must be used for te four-parameter sine-fitting to estimate transients. Te developed system (described in Fig. 1 and Fig. 2) is capable of monitoring, in realtime, te power quality of a single-pase power system. It includes data logging capabilities and an internal backup power source to sustain operation during interruptions and sags. Te system as been used to generate a database of real recorded power quality events wic is available online for te use of te scientific community working in power quality. References [1] Dugan, R.C., McGranagan, M.F., Santoso, S., Beaty, H.W.(2003). Electrical Power Systems Quality. NY: McGraw-Hill, 2 nd edition. 305

12 P.M. Ramos, F.M. Janeiro, T. Radil: ON THE USE OF MULTI-HARMONIC LEAST-SQUARES FITTING [2] Radil, T., Ramos, P.M., Janeiro, F.M., Serra, A.C. (2008). PQ monitoring system for real-time detection and classification of disturbances in a single-pase power system. IEEE Trans. Instrum. Meas., 57(8), [3] Ardeleanu, A.S., Ramos, P.M. (2011). Real time PC implementation of power quality monitoring system based on multiarmonic least-squares fitting. Metrol. Meas. Syst., 18(4), [4] IEC Electromagnetic compatibility (EMC) Part 4-7: Testing and measurement tecniques General guide on armonics and interarmonics measurements and instrumentation, for power supply systems and equipment connected tereto, Edition 2.1, IEC, [5] IEC Electromagnetic compatibility (EMC) Part 4-30: Testing and measurement tecniques Power quality measurement metods, Edition 2.0, [6] IEEE Std IEEE Recommended Practice for Monitoring Electric Power Quality. IEEE Power & Energy Society, [7] Tarasiuk, T., Mindykowski, J. (2012). An extended interpretation of THD concept in te wake of sip electric power systems researc. Measurement, 45(2), [8] Bollen, M.H.J., Gu, I.Y.H.(2006). Signal Processing of Power Quality Disturbances. NJ: Wiley. [9] Sedlacek, M., Stoudek, Z. (2011). Active power measurements - an overview and comparison of DSP algoritms by noncoerent sampling. Metrol. Meas. Syst., 18(2), [10] Szmajda, M., Górecki, K., Mroczka, J. (2010). Gabor Transform, SPWVD, Gabor-Wigner Transform and Wavelet Transform - Tools for Power Quality monitoring. Metrol. Meas. Syst., 17(3), [11] Ramos, P.M., Silva, M.F., Martins, R.C., Serra, A.C. (2006). Simulation and experimental results of multiarmonic least-squares fitting algoritms applied to periodic signals. IEEE Trans. Instrum. Meas., 55(2), [12] Radil, T., Janeiro, F.M., Ramos, P.M., Serra, A.C. (2008). An efficient approac to detect and classify power quality disturbances. International Journal for Computation and Matematics in Electrical and Electronic Engineering (COMPEL), 27(5), [13] Radil, T., Ramos, P.M., Serra, A.C. (2009). Single-pase power quality analyzer based on a new detection and classification algoritm. In Procedings of IMEKO World Congress. Lisbon, Portugal, [14] IEC Electromagnetic compatibility (EMC) Part 2-4: Environment Compatibility levels in industrial plants for low-frequency conducted disturbances, Edition 2, IEC, [15] IEEE Std , IEEE Standard for Digitizing Waveform Recorders, New York, April [16] IEEE Std , IEEE Standard for Terminology and Test Metods for Analog-to-Digital Converters, New York, [17] Ramos, P.R., Serra, A.C. (2007). Least Squares Multiarmonic fitting: Convergence improvements. IEEE Trans. Instrum. Meas., 56(4), [18] Ramos, P.R., Serra, A.C. (2008). Impedance measurement using multiarmonic least-squares waveform fitting algoritm. Computer Standards and Interfaces, Elsevier, 30(5), [19] Janeiro, F.M., Ramos, P.M. (2009). Impedance measurements using genetic algoritms and multiarmonic signals. IEEE Trans. Instrum. Meas., 58(2), [20] Renders, H., Scoukens, J., Vilain, G. (1984). Hig-accuracy spectrum analysis of sampled discrete frequency signals by analytical leakage compensation. IEEE Trans. Instrum. Meas., 33(4), [21] Styvaktakis, E., Bollen, M.H.J., Gu, I.Y.H. (2002). Automatic classification of power system events using RMS voltage measurements. IEEE Power Engineering Society Summer Meeting, [22] Serra, J. (1982). Image Analysis and Matematical Morpology, 1. Academic Press. [23] Radil, T., Ramos, P.M., Janeiro, F.M., Serra, A.C. (2007). DSP Based Power Quality Analyzer for Detection and Classification of Disturbances in a Single-pase Power System. Metrol. Meas. Syst., 14(4),

We are IntechOpen, the world s leading publisher of Open Access books Built by scientists, for scientists. International authors and editors

We are IntechOpen, the world s leading publisher of Open Access books Built by scientists, for scientists. International authors and editors We are IntechOpen, the world s leading publisher of Open Access books Built by scientists, for scientists 3,5 18, 1.7 M Open access books available International authors and editors Downloads Our authors

More information

Power Quality Analysis Using An Adaptive Decomposition Structure

Power Quality Analysis Using An Adaptive Decomposition Structure Power Quality Analysis Using An Adaptive Decomposition Structure Doğan Gökan Ece 1 and Ömer Nezi Gerek 1 (1) Dept. of Electrical and Elctronics Engineering, Anadolu University, Scool of Engineering and

More information

A REVIEW OF THE NEW AUSTRALIAN HARMONICS STANDARD AS/NZS

A REVIEW OF THE NEW AUSTRALIAN HARMONICS STANDARD AS/NZS A REVIEW OF THE NEW AUSTRALIAN HARMONICS STANDARD AS/NZS 61000.3.6 Abstract V. J. Gosbell 1, P. Muttik 2 and D.K. Geddey 3 1 University of Wollongong, 2 Alstom, 3 Transgrid v.gosbell@uow.edu.au Harmonics

More information

Lecture-3 Amplitude Modulation: Single Side Band (SSB) Modulation

Lecture-3 Amplitude Modulation: Single Side Band (SSB) Modulation Lecture-3 Amplitude Modulation: Single Side Band (SSB) Modulation 3.0 Introduction. 3.1 Baseband Signal SSB Modulation. 3.1.1 Frequency Domain Description. 3.1. Time Domain Description. 3. Single Tone

More information

COMPUTATION OF THE NETWORK HARMONIC IMPEDANCE WITH CHIRP-Z TRANSFORM

COMPUTATION OF THE NETWORK HARMONIC IMPEDANCE WITH CHIRP-Z TRANSFORM METROLOGY AND MEASUREMENT SYSTEMS Index 330930, ISSN 0860-8229 www.metrology.pg.gda.pl COMPUTATION OF THE NETWORK HARMONIC IMPEDANCE WITH CHIRP-Z TRANSFORM Krzysztof Duda, Dariusz Borkowski, Andrzej Bień

More information

Calculation of Antenna Pattern Influence on Radiated Emission Measurement Uncertainty

Calculation of Antenna Pattern Influence on Radiated Emission Measurement Uncertainty Calculation of Antenna Pattern Influence on Radiated Emission Measurement Uncertainty Alexander Kriz Business Unit RF-Engineering Austrian Researc Centers GmbH - ARC A-444 Seibersdorf, Austria alexander.kriz@arcs.ac.at

More information

Loading transformers with non sinusoidal currents

Loading transformers with non sinusoidal currents LES00070-ZB rev. Loading transformers wit non sinusoidal currents K Factor Loading transformers wit non sinusoidal currents... Interpretation / example... 6 Copyrigt 007 ABB, All rigts reserved. LES00070-ZB

More information

ON THE IMPACT OF RESIDUAL CFO IN UL MU-MIMO

ON THE IMPACT OF RESIDUAL CFO IN UL MU-MIMO ON THE IMPACT O RESIDUAL CO IN UL MU-MIMO eng Jiang, Ron Porat, and Tu Nguyen WLAN Group of Broadcom Corporation, San Diego, CA, USA {fjiang, rporat, tun}@broadcom.com ABSTRACT Uplink multiuser MIMO (UL

More information

Power Quality Issues, Problems and Related Standards Avinash Panwar1,ASSISTANT PROFESSOR, MADHAV UNIVERSITY ABU ROAD INDIA

Power Quality Issues, Problems and Related Standards Avinash Panwar1,ASSISTANT PROFESSOR, MADHAV UNIVERSITY ABU ROAD INDIA Power Quality Issues, Problems and Related Standards Avinas Panwar1,ASSISTANT PROFESSOR, MADHAV UNIVERSITY ABU ROAD INDIA 1 apanwar84@gmail.com, Summary: Te growt in power electronics as impacted many

More information

Application of two-stage ADALINE for estimation of synchrophasor

Application of two-stage ADALINE for estimation of synchrophasor International Journal of Smart Grid and Clean Energy Application of two-stage ADALINE for estimation of syncropasor Ceng-I Cen a, Yeong-Cin Cen b, Cao-Nan Cen b, Cien-Kai Lan b a a National Central University,

More information

PQ Monitoring Standards

PQ Monitoring Standards Characterization of Power Quality Events Charles Perry, EPRI Chair, Task Force for PQ Characterization E. R. Randy Collins, Clemson University Chair, Working Group for Monitoring Electric Power Quality

More information

Design of Electrical Parameter Measurement System for Three Phase AC Motor Based on STM32

Design of Electrical Parameter Measurement System for Three Phase AC Motor Based on STM32 Sensors & Transducers 2014 by IFSA Publising, S. L. ttp://www.sensorsportal.com Design of Electrical Parameter Measurement System for Tree Pase AC Motor Based on STM32 Haiong Xiao, Jiming Luo, Scool of

More information

MULTIFUNCTION POWER QUALITY MONITORING SYSTEM

MULTIFUNCTION POWER QUALITY MONITORING SYSTEM MULTIFUNCTION POWER QUALITY MONITORING SYSTEM V. Matz, T. Radil and P. Ramos Department of Measurement, FEE, CVUT, Prague, Czech Republic Instituto de Telecomunicacoes, IST, UTL, Lisbon, Portugal Abstract

More information

DSP Based Power Quality Analyzer

DSP Based Power Quality Analyzer DSP Based Power Quality Analyzer Pedro A. Xavier 1, Pedro M. Ramos 1 1 Instituto Superior Técnico, Universidade Técnica de Lisboa, Lisbon, Portugal email: peaxavier@gmail.com, pedro.ramos@lx.it.pt Abstract

More information

On the relation between radiated and conducted RF emission tests

On the relation between radiated and conducted RF emission tests Presented at te 3 t International Zuric Symposium on Electromagnetic Compatibility, February 999. On te relation between radiated and conducted RF emission tests S. B. Worm Pilips Researc Eindoven, te

More information

ENGINEERING RECOMMENDATION G5/5

ENGINEERING RECOMMENDATION G5/5 ENGINEERING RECOMMENDATION G5/5 EMISSION LIMITS FOR HARMONIC VOLTAGE DISTORTION AND THE CONNECTION OF NON-LINEAR AND RESONANT EQUIPMENT TO TRANSMISSION SYSTEMS AND DISTRIBUTION NETWORKS IN THE UNITED KINGDOM

More information

ON TWO-PLANE BALANCING OF SYMMETRIC ROTORS

ON TWO-PLANE BALANCING OF SYMMETRIC ROTORS Proceedings of ME Turbo Expo 0 GT0 June -5, 0, openagen, Denmark GT0-6806 ON TO-PLNE BLNING OF YMMETRI ROTOR Jon J. Yu, P.D. GE Energy 63 Bently Parkway out Minden, Nevada 8943 U Pone: (775) 5-5 E-mail:

More information

Abstract 1. INTRODUCTION

Abstract 1. INTRODUCTION Allocating armonic emission to MV customers in long feeder systems V.J. Gosbell and D. Robinson Integral nergy Power Quality Centre University of Wollongong Abstract Previous work as attempted to find

More information

ANALYSIS OF HARMONIC DISTORTION LEVELS ON A DISTRIBUTION NETWORK

ANALYSIS OF HARMONIC DISTORTION LEVELS ON A DISTRIBUTION NETWORK Presented in AUPEC 7, Pert, Western Australia, 9- December, 7 ANALYSIS OF HARMONIC DISTORTION LEVELS ON A DISTRIBUTION NETWORK Glenn Nicolson - Manukau Institute of Tecnology, Auckland, New Zealand Professor

More information

Effects of Harmonic Pollution on Three-Phase Electrical Motors

Effects of Harmonic Pollution on Three-Phase Electrical Motors t nternational Conference on Electrical and Electronics Engineering (CEEE-7) Oct. -, 07 Bali (ndonesia) Effects of Harmonic Pollution on Tree-Pase Electrical Motors Eleonora. Darie, Emanuel. Darie Abstract

More information

5.3 Sum and Difference Identities

5.3 Sum and Difference Identities SECTION 5.3 Sum and Difference Identities 21 5.3 Sum and Difference Identities Wat you ll learn about Cosine of a Difference Cosine of a Sum Sine of a Difference or Sum Tangent of a Difference or Sum Verifying

More information

POWER QUALITY (PQ) monitoring has become an important

POWER QUALITY (PQ) monitoring has become an important IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT 1 PQ Monitoring System for Real-Time Detection and Classification of Disturbances in a Single-Phase Power System Tomá s Radil, Pedro M. Ramos, Member,

More information

Research on harmonic analysis and Simulation of grid connected synchronous motor Jian Huang1,a, Bingyang Luo2,b

Research on harmonic analysis and Simulation of grid connected synchronous motor Jian Huang1,a, Bingyang Luo2,b 5t nternational Conference on Environment, Materials, Cemistry and Power Electronics (EMCPE 06) Researc on armonic analysis and Simulation of grid connected syncronous motor Jian Huang,a, Bingyang Luo,b

More information

Published in: Proceedings of 8th Annual IEEE Energy Conversion Congress & Exposition (ECCE 2016)

Published in: Proceedings of 8th Annual IEEE Energy Conversion Congress & Exposition (ECCE 2016) Aalborg Universitet A Multi-Pulse Front-End Rectifier System wit Electronic Pase-Sifting for Harmonic Mitigation in Motor Drive Applications Zare, Firuz; Davari, Pooya; Blaabjerg, Frede Publised in: Proceedings

More information

DWT ANALYSIS OF SELECTED TRANSIENT AND NOTCHING DISTURBANCES

DWT ANALYSIS OF SELECTED TRANSIENT AND NOTCHING DISTURBANCES XIX IMEKO World Congress Fundamental and Applied Metrology September 6 11, 29, Lisbon, Portugal DWT ANALYSIS OF SELECTED TRANSIENT AND NOTCHING DISTURBANCES Mariusz Szweda Gdynia Mari University, Department

More information

Energy Savings with an Energy Star Compliant Harmonic Mitigating Transformer

Energy Savings with an Energy Star Compliant Harmonic Mitigating Transformer Energy Savings wit an Energy Star Compliant Harmonic Mitigating Transformer Tony Hoevenaars, P.Eng, Vice President Mirus International Inc. Te United States Environmental Protection Agency s Energy Star

More information

Measurement Time Optimization of Impedance Spectroscopy Techniques Applied to a Vibrating Wire Viscosity Sensor

Measurement Time Optimization of Impedance Spectroscopy Techniques Applied to a Vibrating Wire Viscosity Sensor 20th IMEKO TC4 International Symposium and 18th International Workshop on ADC Modelling and Testing Research on Electric and Electronic Measurement for the Economic Upturn Benevento, Italy, September 15-17,

More information

ON THE BIAS OF TERMINAL BASED GAIN AND OFFSET ESTIMATION USING THE ADC HISTOGRAM TEST METHOD

ON THE BIAS OF TERMINAL BASED GAIN AND OFFSET ESTIMATION USING THE ADC HISTOGRAM TEST METHOD Metrol. Meas. Syst., Vol. XVIII (2011), No. 1, pp. 3-12 METROLOGY AND MEASUREMENT SYSTEMS Index 330930, ISSN 0860-8229 www.metrology.pg.gda.pl ON THE BIAS OF TERMINAL BASED GAIN AND OFFSET ESTIMATION USING

More information

DYNAMIC BEAM FORMING USING CHIRP SIGNALS

DYNAMIC BEAM FORMING USING CHIRP SIGNALS BeBeC-018-D04 DYNAMIC BEAM FORMING USING CHIRP SIGNALS Stuart Bradley 1, Lily Panton 1 and Matew Legg 1 Pysics Department, University of Auckland 38 Princes Street, 1010, Auckland, New Zealand Scool of

More information

Unit 5 Waveguides P a g e 1

Unit 5 Waveguides P a g e 1 Unit 5 Waveguides P a g e Syllabus: Introduction, wave equation in Cartesian coordinates, Rectangular waveguide, TE, TM, TEM waves in rectangular guides, wave impedance, losses in wave guide, introduction

More information

Punctured Binary Turbo-Codes with Optimized Performance

Punctured Binary Turbo-Codes with Optimized Performance Punctured Binary Turbo-odes wit Optimized Performance I. atzigeorgiou, M. R. D. Rodrigues, I. J. Wassell Laboratory for ommunication Engineering omputer Laboratory, University of ambridge {ic1, mrdr, iw}@cam.ac.uk

More information

A POWER QUALITY INSTRUMENT FOR HARMONICS INTERHARMONICS AND AMPLITUDE DISTURBANCES MEASUREMENTS

A POWER QUALITY INSTRUMENT FOR HARMONICS INTERHARMONICS AND AMPLITUDE DISTURBANCES MEASUREMENTS Proceedings, XVII IMEKO World Congress, June 7, 003, Dubrovnik, Croatia Proceedings, XVII IMEKO World Congress, June 7, 003, Dubrovnik, Croatia XVII IMEKO World Congress Metrology in the 3rd Millennium

More information

Damping Algorithm based on Phasor Estimation

Damping Algorithm based on Phasor Estimation Damping Algoritm based on Pasor Estimation Lennart Ängquist, Non-member IEEE ABB Power Systems AB S-7 64 Västerås, Sweden Abstract: Te paper describes a new metod to generate te reactance reference for

More information

Analysis of High Neutral Currents and Harmonic Impacts on Losses and Capacities of Distribution Transformers

Analysis of High Neutral Currents and Harmonic Impacts on Losses and Capacities of Distribution Transformers roceedings of te World Congress on Engineering 06 Vol I WCE 06, June 9 - July, 06, London, U.K. Analysis of Hig Neutral Currents and Harmonic Impacts on Losses and Capacities of Distribution Transformers

More information

Spectrum Sharing with Multi-hop Relaying

Spectrum Sharing with Multi-hop Relaying Spectrum Saring wit Multi-op Relaying Yong XIAO and Guoan Bi Scool of Electrical and Electronic Engineering Nanyang Tecnological University, Singapore Email: xiao001 and egbi@ntu.edu.sg Abstract Spectrum

More information

Cooperative Request-answer Schemes for Mobile Receivers in OFDM Systems

Cooperative Request-answer Schemes for Mobile Receivers in OFDM Systems Cooperative Request-answer Scemes for Mobile Receivers in OFDM Systems Y. Samayoa, J. Ostermann Institut für Informationsverarbeitung Gottfried Wilelm Leibniz Universität Hannover 30167 Hannover, Germany

More information

SIGNAL PROCESSING OF POWER QUALITY DISTURBANCES

SIGNAL PROCESSING OF POWER QUALITY DISTURBANCES SIGNAL PROCESSING OF POWER QUALITY DISTURBANCES MATH H. J. BOLLEN IRENE YU-HUA GU IEEE PRESS SERIES I 0N POWER ENGINEERING IEEE PRESS SERIES ON POWER ENGINEERING MOHAMED E. EL-HAWARY, SERIES EDITOR IEEE

More information

Image Feature Extraction and Recognition of Abstractionism and Realism Style of Indonesian Paintings

Image Feature Extraction and Recognition of Abstractionism and Realism Style of Indonesian Paintings Image Feature Extraction and Recognition of Abstractionism and Realism Style of Indonesian Paintings Tieta Antaresti R P and Aniati Murni Arymurty Faculty of Computer Science University of Indonesia Depok

More information

Modelling Capture Behaviour in IEEE Radio Modems

Modelling Capture Behaviour in IEEE Radio Modems Modelling Capture Beaviour in IEEE 80211 Radio Modems Cristoper Ware, Joe Cicaro, Tadeusz Wysocki cris@titruoweduau 20t February Abstract In tis paper we investigate te performance of common capture models

More information

Machine Vision System for Automatic Weeding Strategy in Oil Palm Plantation using Image Filtering Technique

Machine Vision System for Automatic Weeding Strategy in Oil Palm Plantation using Image Filtering Technique Macine Vision System for Automatic Weeding Strategy in Oil Palm Plantation using Image Filtering Tecnique Kamarul Hawari Gazali, Mod. Marzuki Mustafa, and Aini Hussain Abstract Macine vision is an application

More information

Estimation of Dielectric Constant for Various Standard Materials using Microstrip Ring Resonator

Estimation of Dielectric Constant for Various Standard Materials using Microstrip Ring Resonator Journal of Science and Tecnology, Vol. 9 No. 3 (017) p. 55-59 Estimation of Dielectric Constant for Various Standard Materials using Microstrip Ring Resonator Pek Jin Low 1, Famiruddin Esa 1*, Kok Yeow

More information

CAPACITY OF MULTIPLE ACCESS CHANNELS WITH CORRELATED JAMMING

CAPACITY OF MULTIPLE ACCESS CHANNELS WITH CORRELATED JAMMING CAPACITY OF MULTIPLE ACCESS CHANNELS WITH CORRELATED JAMMING Sabnam Safiee and Sennur Ulukus Department of Electrical and Computer Engineering University of Maryland College Park, MD ABSTRACT We investigate

More information

ELEC 546 Lecture #9. Orthogonal Frequency Division Multiplexing (OFDM): Basic OFDM System

ELEC 546 Lecture #9. Orthogonal Frequency Division Multiplexing (OFDM): Basic OFDM System ELEC 546 Lecture #9 Ortogonal Frequency Division Multiplexing (OFDM): Basic OFDM System Outline Motivations Diagonalization of Vector Cannels Transmission of one OFDM Symbol Transmission of sequence of

More information

HIGHLY ACCURATE CALIBRATION SYSTEM FOR ELECTRONIC INSTRUMENT TRANSFORMERS

HIGHLY ACCURATE CALIBRATION SYSTEM FOR ELECTRONIC INSTRUMENT TRANSFORMERS Metrol. Meas. Syst., Vol. XVIII (2011), No. 2, pp. 315-322 METROLOGY AND MEASUREMENT SYSTEMS Index 330930, ISSN 0860-8229 www.metrology.pg.gda.pl HIGHLY ACCURATE CALIBRATION SYSTEM FOR ELECTRONIC INSTRUMENT

More information

Power quality as a reliability problem for electronic equipment

Power quality as a reliability problem for electronic equipment Power quality as a reliability problem for electronic equipment A. Victor A. Anunciada1,3, Hugo Ribeiro2,3 1 Department of Electrical and Computer Engineering, Instituto Superior Técnico, Universidade

More information

A Filtering Scheme for Reducing Harmonics Penetration into Transmission Systems (V1.0)

A Filtering Scheme for Reducing Harmonics Penetration into Transmission Systems (V1.0) A Filtering Sceme for Reducing Harmonics Penetration into Systems (V.) J. W. Hagge, Senior Member, IEEE, and L. L. Grigsby, Fellow, IEEE Abstract--Tis paper presents a novel sceme to reduce armonics penetration

More information

Channel Estimation Filter Using Sinc-Interpolation for UTRA FDD Downlink

Channel Estimation Filter Using Sinc-Interpolation for UTRA FDD Downlink { Cannel Estimation Filter Using Sinc-Interpolation for UTA FDD Downlink KLAUS KNOCHE, JÜGEN INAS and KAL-DIK KAMMEYE Department of Communications Engineering, FB- University of Bremen P.O. Box 33 4 4,

More information

Overview of MIMO Radio Channels

Overview of MIMO Radio Channels Helsinki University of Tecnology S.72.333 Postgraduate Course in Radio Communications Overview of MIMO Radio Cannels 18, May 2004 Suiyan Geng gsuiyan@cc.ut.fi Outline I. Introduction II. III. IV. Caracteristics

More information

Research on Three-level Rectifier Neutral-Point Voltage Balance. Control in Traction Power Supply System of High. Speed Train

Research on Three-level Rectifier Neutral-Point Voltage Balance. Control in Traction Power Supply System of High. Speed Train Researc on Tree-level Rectifier Neutral-Point Voltage Balance Control in Traction Power Supply System of Hig Speed Train LU XIAO-JUAN, WANG XIN-JU, GUO QI, LI SHU-YUAN Scool of Automation and Electric

More information

VARIABLE-FREQUENCY PRONY METHOD IN THE ANALYSIS OF ELECTRICAL POWER QUALITY

VARIABLE-FREQUENCY PRONY METHOD IN THE ANALYSIS OF ELECTRICAL POWER QUALITY Metrol. Meas. Syst., Vol. XIX (2012), No. 1, pp. 39-48. METROLOGY AND MEASUREMENT SYSTEMS Index 330930, ISSN 0860-8229 www.metrology.pg.gda.pl VARIABLE-FREQUENCY PRONY METHOD IN THE ANALYSIS OF ELECTRICAL

More information

Grid Filter Design for a Multi-Megawatt Medium-Voltage Voltage Source Inverter

Grid Filter Design for a Multi-Megawatt Medium-Voltage Voltage Source Inverter Grid Filter Design for a Multi-Megawatt Medium-Voltage Voltage Source Inverter A.A. Rockill, Grad. Student Member, IEEE, Marco Liserre, Senior Member, IEEE, Remus Teodorescu, Member, IEEE and Pedro Rodriguez,

More information

Modelling and Control of Gene Regulatory Networks for Perturbation Mitigation

Modelling and Control of Gene Regulatory Networks for Perturbation Mitigation Tis article as been accepted for publication in a future issue of tis journal, but as not been fully edited. Content may cange prior to final publication. Citation information: DOI.9/TCBB.., IEEE/ACM IEEE/ACM

More information

Optimal DG Placement and Sizing in Distribution System for Loss and THD Reduction

Optimal DG Placement and Sizing in Distribution System for Loss and THD Reduction International Journal of Electronic and Electrical Engineering. ISSN 0974-2174 Volume 5, Number 3 (2012), pp. 227-237 International Researc Publication House ttp://www.irpouse.com Optimal Placement and

More information

IMAGE ILLUMINATION (4F 2 OR 4F 2 +1?)

IMAGE ILLUMINATION (4F 2 OR 4F 2 +1?) IMAGE ILLUMINATION ( OR +?) BACKGROUND Publications abound wit two differing expressions for calculating image illumination, te amount of radiation tat transfers from an object troug an optical system

More information

Image Reconstruction Based On Bayer And Implementation On FPGA Sun Chen 1, a, Duan Xiaofeng 2, b and Wu Qijing 3, c

Image Reconstruction Based On Bayer And Implementation On FPGA Sun Chen 1, a, Duan Xiaofeng 2, b and Wu Qijing 3, c 2nd International Worksop on Materials Engineering and Computer Sciences (IWMECS 2015) Image Reconstruction Based On Bayer And Implementation On FPGA Sun Cen 1, a, Duan Xiaofeng 2, b and Wu Qijing 3, c

More information

Performance analysis and comparison of m x n zero forcing and MMSE equalizer based receiver for mimo wireless channel

Performance analysis and comparison of m x n zero forcing and MMSE equalizer based receiver for mimo wireless channel Songklanakarin J. Sci. Tecnol. 33 (3), 335-340, May - Jun. 0 ttp://www.sjst.psu.ac.t Original Article Performance analysis and comparison of m x n zero forcing and MMSE equalizer based receiver for mimo

More information

School of Electrical and Computer Engineering, Cornell University. ECE 303: Electromagnetic Fields and Waves. Fall 2007

School of Electrical and Computer Engineering, Cornell University. ECE 303: Electromagnetic Fields and Waves. Fall 2007 Scool of Electrical and Computer Engineering, Cornell University ECE 303: Electromagnetic Fields and Waves Fall 007 Homework 11 Due on Nov. 9, 007 by 5:00 PM Reading Assignments: i) Review te lecture notes.

More information

A Guide for the Assessment and Mitigation of Bleed, Gloss Change, and Mold in Inkjet Prints During High-humidity Conditions

A Guide for the Assessment and Mitigation of Bleed, Gloss Change, and Mold in Inkjet Prints During High-humidity Conditions A Guide for te Assessment and Mitigation of Bleed, Gloss Cange, and Mold in Inkjet Prints During Hig-umidity Conditions Jennifer Burger; University of Rocester and Daniel Burge; Image Permanence Institute,

More information

Detection and Identification of PQ Disturbances Using S-Transform and Artificial Intelligent Technique

Detection and Identification of PQ Disturbances Using S-Transform and Artificial Intelligent Technique American Journal of Electrical Power and Energy Systems 5; 4(): -9 Published online February 7, 5 (http://www.sciencepublishinggroup.com/j/epes) doi:.648/j.epes.54. ISSN: 36-9X (Print); ISSN: 36-9 (Online)

More information

Polyphase Filter Approach for High Performance, FPGA-Based Quadrature Demodulation

Polyphase Filter Approach for High Performance, FPGA-Based Quadrature Demodulation Polypase Filter Approac for Hig Performance, FPGA-Based Quadrature Demodulation J.M.P. Langlois 1, D. Al-Kalili 1, R.J. Inkol 1 Department of Electrical and Computer Engineering, Royal Military College

More information

This study concerns the use of machine learning based

This study concerns the use of machine learning based Modern AI for games: RoboCode Jon Lau Nielsen (jlni@itu.dk), Benjamin Fedder Jensen (bfje@itu.dk) Abstract Te study concerns te use of neuroevolution, neural networks and reinforcement learning in te creation

More information

Fundamentals of Power Quality

Fundamentals of Power Quality NWEMS Fundamentals of Power Quality August 20 24, 2018 Seattle, WA Track D Anaisha Jaykumar (SEL) Class Content» Introduction to power quality (PQ)» Causes of poor PQ and impact of application» PQ characteristics»

More information

Distribution Transformer Losses Evaluation under Non-Linear Load

Distribution Transformer Losses Evaluation under Non-Linear Load Distribution Transformer Losses Evaluation under Non-Linear Load *Dalila M.S., Kalid M. N. and Md Sa M. Centre of Electrical Energy System, Faculty of Electrical Engineering, Universiti Teknologi Malaysia,

More information

Modeling and Characterization of Leakage Inductances for Transformer Winding Fault Studies

Modeling and Characterization of Leakage Inductances for Transformer Winding Fault Studies Modeling and Caracterization of Leakage Inductances for ransformer Winding Fault Studies Luís M.R. Oliveira 1,3 and A.J. Marques Cardoso,3 1 Instituto Superior de Engenaria, Universidade do Algarve, Faro,

More information

Aalborg Universitet. Published in: IET Power Electronics. DOI (link to publication from Publisher): /iet-pel Publication date: 2018

Aalborg Universitet. Published in: IET Power Electronics. DOI (link to publication from Publisher): /iet-pel Publication date: 2018 Aalborg Universitet Load-Independent Harmonic Mitigation in SCR-Fed Tree-Pase Multiple Adjustable Speed Drive Systems wit Deliberately Dispatced Firing Angles Yang, Yongeng; Davari, Pooya; Blaabjerg, Frede;

More information

Compatibility and Safety Volume for Electromagnetic Exposure Limits in Shared Sites for 2G and 3G Wireless Communications

Compatibility and Safety Volume for Electromagnetic Exposure Limits in Shared Sites for 2G and 3G Wireless Communications Compatibility and Safety Volume for Electromagnetic Exposure imits in Sared Sites for G and 3G Wireless Communications Rogelio Jiménez Jiménez*, Diego Ortega abajos*, Florentino Jiménez **, Rafael Herradón**

More information

LOADING OF TRANSFORMERS BEYOND NAMEPLATE RATING

LOADING OF TRANSFORMERS BEYOND NAMEPLATE RATING LOADING OF TRANSFORMERS BEYOND NAMEPLATE RATING by K. B. M. I. Perera and J. R. Lucas Abstract Te application of a load in excess of nameplate ratings, and/or an ambient temperature iger tan designed of

More information

Complex-valued restricted Boltzmann machine for direct learning of frequency spectra

Complex-valued restricted Boltzmann machine for direct learning of frequency spectra INTERSPEECH 17 August, 17, Stockolm, Sweden Complex-valued restricted Boltzmann macine for direct learning of frequency spectra Toru Nakasika 1, Sinji Takaki, Junici Yamagisi,3 1 University of Electro-Communications,

More information

Optimal Multiobjective Design of Hybrid Active Power Filters Considering a Distorted Environment

Optimal Multiobjective Design of Hybrid Active Power Filters Considering a Distorted Environment Optimal Multiobjective Design of Hybrid Active Power Filters Considering a Distorted Environment Abstract Te development of new passive, active and ybrid filtering tecniques is important, and te issues

More information

Indirect Measurement

Indirect Measurement exploration Georgia Performance Standards M6G1.c, M6A2.c, M6A2.g Te eigts of very tall structures can be measured indirectly using similar figures and proportions. Tis metod is called indirect measurement.

More information

Development of Mathematical Models for Various PQ Signals and Its Validation for Power Quality Analysis

Development of Mathematical Models for Various PQ Signals and Its Validation for Power Quality Analysis International Journal of Engineering Research and Development ISSN: 227867X, olume 1, Issue 3 (June 212), PP.3744 www.ijerd.com Development of Mathematical Models for arious PQ Signals and Its alidation

More information

Jurnal Teknologi HYBRID ACTIVE POWER FILTER METHOD IN FREQUENCY DOMAIN FOR QUALITY IMPROVEMENT IN VARIABLE FREQUENCY DRIVE APPLICATIONS.

Jurnal Teknologi HYBRID ACTIVE POWER FILTER METHOD IN FREQUENCY DOMAIN FOR QUALITY IMPROVEMENT IN VARIABLE FREQUENCY DRIVE APPLICATIONS. Jurnal Tenologi HYBRID ACTIVE POWER FILTER METHOD IN FREQUENCY DOMAIN FOR QUALITY IMPROVEMENT IN VARIABLE FREQUENCY DRIVE APPLICATIONS Min Hoang Hac Le, Kim-An Nguyen 2*, Viet Hung Ngo 3 R&D project, PowerMore

More information

Closed-Form Optimality Characterization of Network-Assisted Device-to-Device Communications

Closed-Form Optimality Characterization of Network-Assisted Device-to-Device Communications Closed-Form Optimality Caracterization of Network-Assisted Device-to-Device Communications Serve Salmasi,EmilBjörnson, Slimane Ben Slimane,andMérouane Debba Department of Communication Systems, Scool of

More information

Analog to Digital Converters Testing

Analog to Digital Converters Testing Analog to Digital Converters Testing António Manuel da Cruz Serra Department of Electrical Engineering and Computers, Instituto Superior Técnico / Instituto de Telecomunicações, Technical University of

More information

ON THE VALIDITY OF THE NOISE MODEL OF QUANTIZATION FOR THE FREQUENCY-DOMAIN AMPLITUDE ESTIMATION OF LOW-LEVEL SINE WAVES

ON THE VALIDITY OF THE NOISE MODEL OF QUANTIZATION FOR THE FREQUENCY-DOMAIN AMPLITUDE ESTIMATION OF LOW-LEVEL SINE WAVES Metrol. Meas. Syst., Vol. XXII (215), No. 1, pp. 89 1. METROLOGY AND MEASUREMENT SYSTEMS Index 3393, ISSN 86-8229 www.metrology.pg.gda.pl ON THE VALIDITY OF THE NOISE MODEL OF QUANTIZATION FOR THE FREQUENCY-DOMAIN

More information

Enhanced HARQ Technique Using Self-Interference Cancellation Coding (SICC)

Enhanced HARQ Technique Using Self-Interference Cancellation Coding (SICC) MITUBIHI ELECTRIC REEARCH LABORATORIE ttp://www.merl.com Enanced HARQ Tecnique Using elf-interference Cancellation Coding (ICC) Wataru Matsumoto, Tosiyuki Kuze, igeru Ucida, Yosida Hideo, Pilip Orlik,

More information

Roadmap For Power Quality Standards Development

Roadmap For Power Quality Standards Development Roadmap For Power Quality Standards Development IEEE Power Quality Standards Coordinating Committee Authors: David B. Vannoy, P.E., Chair Mark F. McGranghan, Vice Chair S. Mark Halpin, Vice Chair D. Daniel

More information

POWER QUALITY REPORT

POWER QUALITY REPORT Power Quality Research Lab., I-7, Wyb. Wyspiaoskiego 27, 50-370 Wrocław, Poland phone +48713202626, fax +48713202006, email: zbigniew.leonowicz@pwr.wroc.pl Facility: XXX POWER QUALITY REPORT Start Monitoring:

More information

GENERALLY, the power loss in the winding of an

GENERALLY, the power loss in the winding of an INTL JOURNAL OF ELECTRONICS AND TELECOMMUNICATIONS, 00, VOL. 6, NO., PP. 7-6 Manuscript received July 0, 00: revised September, 00. DOI: 0.78/v077-00-00- Foil Winding Resistance and Power Loss in Individual

More information

An Experimental Downlink Multiuser MIMO System with Distributed and Coherently-Coordinated Transmit Antennas

An Experimental Downlink Multiuser MIMO System with Distributed and Coherently-Coordinated Transmit Antennas An Experimental Downlink Multiuser MIMO System wit Distributed and Coerently-Coordinated Antennas Dragan Samardzija, Howard Huang, Reinaldo Valenzuela and Teodore Sizer Bell Laboratories, Alcatel-Lucent,

More information

A Visible Light Localization Aided Optical Wireless System

A Visible Light Localization Aided Optical Wireless System 2nd IEEE Worksop on Optical Wireless Communications A Visible Ligt Localization Aided Optical Wireless System Giulio Cossu, Marco Presi, Raffaele Corsini, Pallab Coudury, Amir Masood Kalid and Ernesto

More information

Effect of Harmonics on Distribution Transformer Losses and Capacity

Effect of Harmonics on Distribution Transformer Losses and Capacity nternational Journal of Engineering Tecnology Science and Researc SSN 394 3386 June 017 Effect of Harmonics on Distribution Transformer Losses and Capacity Jaspreet Sing Sanjeev Sing Amanpreet Sing unjab

More information

OPTI-502 Optical Design and Instrumentation I John E. Greivenkamp Homework Set 5 Fall, 2018

OPTI-502 Optical Design and Instrumentation I John E. Greivenkamp Homework Set 5 Fall, 2018 Homework Set 5 all, 2018 Assigned: 9/26/18 Lecture 11 Due: 10/3/18 Lecture 13 Midterm Exam: Wednesday October 24 (Lecture 19) 5-1) Te following combination of tin lenses in air is in a telepoto configuration:

More information

Virtual FFT Analyser for identification of harmonics and inter-harmonics metrological aspects

Virtual FFT Analyser for identification of harmonics and inter-harmonics metrological aspects NPL seminar 30 of November 005 Virtual FFT Analyser for identification of harmonics and inter-harmonics metrological aspects M. Jerzy Korczyński Institute of Theoretical Electrotechnics, Metrology and

More information

POWER QUALITY AND SAFETY

POWER QUALITY AND SAFETY POWER QUALITY AND SAFETY Date : November 27, 2015 Venue : 40 th IIEE Annual National Convention and 3E XPO 2015 PRESENTATION OUTLINE Power Quality I. INTRODUCTION II. GRID CODE REQUIREMENTS III. ERC RESOLUTION

More information

FOURIER ANALYSIS OF A SINGLE-PHASE FULL BRIDGE RECTIFIER USING MATLAB

FOURIER ANALYSIS OF A SINGLE-PHASE FULL BRIDGE RECTIFIER USING MATLAB -774 FOURIER ANALYSIS OF A SINGLE-PHASE FULL BRIDGE RECTIFIER USING MATLAB Bruno Osorno California Sate University Nortridge 8 Nordoff St Nortridge CA 933 Email: bruno@ecs.csun.edu Pone: (88)677-3956 Abstract

More information

On the Downlink Capacity of WCDMA Systems with Transmit Diversity

On the Downlink Capacity of WCDMA Systems with Transmit Diversity On te Downlink Capacity of WCDMA Systems wit ransmit Diversity Vaibav Sing, Oya Yilmaz, Jialing Wang, Kartigeyan Reddy, and S. Ben Slimane Radio Communication Systems Department of Signals, Sensors, and

More information

MEASUREMENT METHODS OF THE CHARACTERISTICS AND TARGET VALUES OF THE VOLTAGE QUALITY SUPPLIED BY HYDRO-QUEBEC SYSTEM

MEASUREMENT METHODS OF THE CHARACTERISTICS AND TARGET VALUES OF THE VOLTAGE QUALITY SUPPLIED BY HYDRO-QUEBEC SYSTEM MEASREMENT METHODS OF THE CHARACTERISTICS AND TARGET VALES OF THE VOLTAGE QALITY SPPLIED BY HYDRO-QEBEC SYSTEM Report no.: IREQ-99-0 Revision #1 This document is a translated version of the French document

More information

Low distortion signal generator based on direct digital synthesis for ADC characterization

Low distortion signal generator based on direct digital synthesis for ADC characterization ACTA IMEKO July 2012, Volume 1, Number 1, 59 64 www.imeko.org Low distortion signal generator based on direct digital synthesis for ADC characterization Walter F. Adad, Ricardo J. Iuzzolino Instituto Nacional

More information

Performance Analysis for LTE Wireless Communication

Performance Analysis for LTE Wireless Communication IOP Conference Series: Materials Science and Engineering PAPER OPEN ACCESS Performance Analysis for LTE Wireless Communication To cite tis article: S Tolat and T C Tiong 2015 IOP Conf. Ser.: Mater. Sci.

More information

On the Sum Capacity of Multiaccess Block-Fading Channels with Individual Side Information

On the Sum Capacity of Multiaccess Block-Fading Channels with Individual Side Information On te Sum Capacity of Multiaccess Block-Fading Cannels wit Individual Side Information Yas Despande, Sibi Raj B Pillai, Bikas K Dey Department of Electrical Engineering Indian Institute of Tecnology, Bombay.

More information

The deterministic EPQ with partial backordering: A new approach

The deterministic EPQ with partial backordering: A new approach Omega 37 (009) 64 636 www.elsevier.com/locate/omega Te deterministic EPQ wit partial backordering: A new approac David W. Pentico a, Mattew J. Drake a,, Carl Toews b a Scool of Business Administration,

More information

Application of Hilbert-Huang Transform in the Field of Power Quality Events Analysis Manish Kumar Saini 1 and Komal Dhamija 2 1,2

Application of Hilbert-Huang Transform in the Field of Power Quality Events Analysis Manish Kumar Saini 1 and Komal Dhamija 2 1,2 Application of Hilbert-Huang Transform in the Field of Power Quality Events Analysis Manish Kumar Saini 1 and Komal Dhamija 2 1,2 Department of Electrical Engineering, Deenbandhu Chhotu Ram University

More information

Multi-agent coordination via a shared wireless spectrum

Multi-agent coordination via a shared wireless spectrum 217 IEEE 56t Annual Conference on Decision and Control (CDC) December 12-15, 217, Melbourne, Australia Multi-agent coordination via a sared wireless spectrum Cameron Nowzari Abstract Tis paper considers

More information

ENGINEERING FOR RURAL DEVELOPMENT Jelgava, EDUCATION METHODS OF ANALOGUE TO DIGITAL CONVERTERS TESTING AT FE CULS

ENGINEERING FOR RURAL DEVELOPMENT Jelgava, EDUCATION METHODS OF ANALOGUE TO DIGITAL CONVERTERS TESTING AT FE CULS EDUCATION METHODS OF ANALOGUE TO DIGITAL CONVERTERS TESTING AT FE CULS Jakub Svatos, Milan Kriz Czech University of Life Sciences Prague jsvatos@tf.czu.cz, krizm@tf.czu.cz Abstract. Education methods for

More information

Combined Noise Tools. i Development i Innovation i Cooperation i Responsibility XI AN WELL-SUN ELECTRONIC TECHNOLOGY PLC.

Combined Noise Tools. i Development i Innovation i Cooperation i Responsibility XI AN WELL-SUN ELECTRONIC TECHNOLOGY PLC. i Development i Innovation i Cooperation i Responsibility Overview A leaking well can damage te environment and result in production loss. Te Noise Tool ouses a sensitive ydropone tat is igly effective

More information

A Study of Grounding Grid Characteristics with Conductive Concrete

A Study of Grounding Grid Characteristics with Conductive Concrete A Study of Grounding Grid Caracteristics wit Conductive Concrete Cun-Yao Lee and Siang-Ren Wang Abstract e purpose of tis paper is to improve electromagnetic caracteristics on grounding grid by applying

More information

Measurement of RMS values of non-coherently sampled signals. Martin Novotny 1, Milos Sedlacek 2

Measurement of RMS values of non-coherently sampled signals. Martin Novotny 1, Milos Sedlacek 2 Measurement of values of non-coherently sampled signals Martin ovotny, Milos Sedlacek, Czech Technical University in Prague, Faculty of Electrical Engineering, Dept. of Measurement Technicka, CZ-667 Prague,

More information

A STATISTICALLY VALID METHOD FOR USING FIA PLOTS TO GUIDE SPECTRAL CLASS REJECTION IN PRODUCING STRATIFICATION MAPS

A STATISTICALLY VALID METHOD FOR USING FIA PLOTS TO GUIDE SPECTRAL CLASS REJECTION IN PRODUCING STRATIFICATION MAPS A STATISTICALLY VALID METHOD FOR USING FIA PLOTS TO GUIDE SPECTRAL CLASS REJECTION IN PRODUCING STRATIFICATION MAPS Micael L. Hoppus and Andrew J. Lier ABSRACT. A Landsat TM classification metod (iterative

More information

DESIGN AND ANALYSIS OF MIMO SYSTEM FOR UWB COMMUNICATION

DESIGN AND ANALYSIS OF MIMO SYSTEM FOR UWB COMMUNICATION DESIGN AND ANAYSIS OF IO SYSTE FOR UWB COUNICATION iir N. oanty, onalisa Bol, axmi Prasad isra 3, Sanjat Kumar isra 4 ITER, Siksa O Anusandan University, Bubaneswar, Odisa, 75030, India Seemanta Engineering

More information