Energy System Protection for Grid Resilience. Xianyong Feng, PhD, PE Center for Electromechanics The University of Texas at Austin October 31, 2017

Size: px
Start display at page:

Download "Energy System Protection for Grid Resilience. Xianyong Feng, PhD, PE Center for Electromechanics The University of Texas at Austin October 31, 2017"

Transcription

1 Energy System Protection for Grid Resilience Xianyong Feng, PhD, PE Center for Electromechanics The University of Texas at Austin October 31, 1

2 Presentation Outline Overview Mission Critical Energy Systems Energy System Fault Mgmt. CEM Approach Ctrl. & Prot. Energy System Protection (3 cases) Conclusion 2

3 Overview Resilience is different from reliability A resilient system 1. Acknowledges that power outages can occur 2. Be prepared and minimizes their impact 3. Quickly restores service 4. Draws lessons from experience to improve robustness * page 3 * Flynn, S.E America the resilient: Defying terrorism and mitigating natural disasters. Foreign Affairs 87: 2 8.

4 Mission Critical Energy System All-electric ship DC datacenter Wind collection system PV farm Electric aircraft Oil & gas platform page 4

5 Energy System Fault Management Detection Real-time monitoring Detect electrical abnormal Fault type identification (permanent or temporary) PREPARE Location Isolation Quickly and accurately locate fault Minimize system impact Open protective device Minimize load interruption AMELIORATE Restoration Restart interrupted power equipments Restore interrupted loads to normal QUICK RECOVERY page 5

6 CEM Approach - Control & Protection Simulation Test: New control and protection strategies are initially implemented in modeling software and verified in numerical simulation. The tools include but not limited to: 1. Matlab / Simulink 2. PSCAD 3. ETAP 4. OpenDSS Simulated control block 1 Simulated control block N Numerical simulation environment Control signal Measured signal Simulated circuit The control or protection strategies are implemented as software blocks in simulation tools; the control system performance can be evaluated and controller parameters can be optimally selected in off-line simulations. i Power Hardware-in-the-Loop (PHIL) Simulation Test: Design the interface between HIL simulator and real power systems such as hardware microgrid system at CEM. Power amplifiers (power converters and emulators) are the interfaces between real-time simulator and real power system. Key features: 1. Complicated network model is implemented in HIL simulator 2. Power electronics converters and active sources serve as the interface between software simulator and the real system 3. NI FPGA simulator enables the fast response of PE devices Real Hardware Microgrid System MV bus HIL simulator Controlled voltage source ~ Voltage signal Hardware Interface Current measurement I/Os Simulated network Power Amplifier Current signal Active Source iii Control Hardware-in-the-Loop (CHIL) Simulation Test: New control and protection strategies are implemented in hardware controllers. The controller is validated and tested in the HIL simulation environment to de-risk field test and demonstration. Main procedures include: 1. Model the circuit 2. Implement control strategy in hardware 3. Configure the communication interface between real-time simulator and hardware controllers 4. Perform real-time HIL tests Distributed control Advanced protection strategies Simulated switching devices in NI PXI simulator PXIe Real-Time/FPGA HIL System Sensors High speed communication link Control and Protection Hardware Control Center Simulated Distribution Network in Opal-RT Opal-RT Simulator I/O or other comm. Interfaces NI controllers Tertiary Controls SCADA System IED Real Hardware Test and Field Demonstration: The control and protection strategies are ultimately implemented in the control platform of real hardware power system for final testing and validation. Main benefits include: 1. Obtain validated engineering data 2. Demonstrate the control system performance in the real operation environment MW-scale Microgrid page 6 ii iv

7 LVDC Distribution System Protection DC fault current DC Protection Challenges No zero-crossing in fault current Lower line impedance in tightly coupled system High di/dt Power electrics device can not tolerate high fault current Extremely fast capacitor discharge AC fault current DC distribution system example DC Power Supply Fault 1 Fault 2 ~ = = = L Fault 3 L L L page 7

8 LVDC Distribution System Protection Inductance-based dc fault location* Estimate fault inductance with local measured v(t) and i(t) Use estimated L to locate fault Equivalent inductance L 1 Line inductance distribution L 2 L 3 Distance + - v Equivalent fault circuit i R *X. Feng, L. Qi, and J. Pan, A novel fault location method for dc distribution protection, IEEE Trans. Industrial Applications, vol. 53, no. 3, May-June,. L RF DC UPS 380 VDC ~ = = = level 1 level 2 level 3 Fault 1 Fault 2 Zone 1 (20 m) Zone 2 (65 m) Zone 3 (10.2 m) L L L L L L Fault 3 page 8 Zone 4 (1.5 m)

9 LVDC Distribution System Protection Protection Scheme Implementation Online moving-window least square method Algorithm on embedded controller Fault detection v i di/dt and location routine ADC ADC ADC v (1) i (1) di/dt (1) PRUs read data sequentially and store them in memory 7 analog inputs with A/D converters k = k + 1 Yes di ( k M 1) dt di A ( k M 2) dt di ( k) dt Start Fault detected? Yes k = 0 Read in measurements v(k), i(k), and di/dt(k) if k < M No No i( k M 1) v ( k M 1) i( k M 2) v ( k M 2 ) B i( k) v ( k ) Go to next time interval Yes di (0) dt di A (1) dt di ( k) dt i(0) v(0) i(1) v(1) B i( k) v( k ) Request new data once finishing the previous cycle N Main program executes the fault detection and location routine Locate fault? Y Send tripping PRUs 65 digital I/Os Processor (AM3358) if t < T max No No L R R F T 1 T A A A B if 0 < L < L th Yes Send tripping signal End page 9

10 Inductance (H) Inductance (H) LVDC Distribution System Protection Numerical Simulation Fault 1 15 m from breaker 1 Fault R: 2 mω Fault 2 50 m from breaker 2 Fault R: 2 mω 10 x x ms Zone 2 Zone 1 Estimated inductance Threshold time (sec) DC UPS 380 VDC ~ = = = Fault 1 Fault 2 Zone 1 (20 m) 0.77 mf mω mω 4.5 mω µh µh 13.8 µh Zone 2 (65 m) 1.35 mω 4.15 µh Zone 3 (10.2 m) L L L L L L Fault 3 Zone 4 (1.5 m) ms Zone 3 Zone time (sec) 10

11 LVDC Distribution System Protection User interface Control-HIL Test Opal-RT simulator Ethernet Opal-RT simulator Simulated DC network Simulated a 380 V dc system Convert v(t)/i(t) to analog Read in breaker status through D in Embedded controller Read in v(t)/i(t) signals Execute prot. algorithm Send a trip signal for internal fault Analog outputs: current/voltage signal Microcontroller A/D converters Breaker status wired back to Opal-RT simulator Fault detection and location algorithm Trip command 24 V 47uF Breaker page 11

12 LVDC Distribution System Protection Control-HIL Test Results Estimated error < 8.4% Fault location time < 0.7 ms current signal tripping signal ID Actual L (µh) / fault R (mω) Estimated L (µh) Error (%) Fault location time (ms) 1 18 / ~ / ~ / ~ / ~ / ~ / ~ / ~ / ~ / ~0.55 current signal voltage signal page 12

13 Estimated L (H) Estimated L (H) Estimated L (H) LVDC Distribution System Protection Sensitivity Analysis* Voltage error: 0.025% % * V rated (380 V) Current error: 0.005% - 1.5% * I max (2000 A) Improve accuracy using digital filter x Original method (L) Improved method (L) 3.2 Level 6 Lower lower Boundary boundary Inductance (H) 2.5 x x Voltage sensitivity Voltage error: 0.025% Voltage error: 0.125% Voltage error: 0.25% Voltage error: 0.5% Voltage error: 1.25% Base Scenario 1 Scenario 2 Scenario 3 Scenario time (sec) Current sensitivity Inductance (H) time (sec) *X. Feng, L. Qi, and J. Pan, Fault inductance based protection for DC distribution systems, Proc. of the 13th International Conference on Developments in Power System Protection, Edinburgh, Scotland, March Inductance (H) Current error: 0.005% Current error: 0.01% Current error: 0.025% Current error: 0.05% Current error: 0.25% Current error: 0.5% Current error: 1% Current error: 1.5% Base case Scenario 1 Scenario 2 Scenario 3 Scenario 4 Scenario 5 Scenario 6 Scenario 7 Level 4 boundary time (sec) page 13

14 Voltage Current LVDC Distribution System Protection Hardware Test Low voltage circuit 7.07 mf capacitor is charged to 12 V Inductors are used to emulate lines Short-circuit fault is created by closing a breaker Embedded controller Read in v(t), i(t), di/dt Execute prot. algorithm Send a trip signal for internal fault + 12 V DC - Switch Capacitor (7.07 mf) Inductor (6 µh) SLD diagram Current sensor Analog circuit of di/dt calculation Real circuit Line (6-12 µh) BeagleBone Black board with Tripping fault detection & signal location Emax page 14

15 Time (ms) Time (ms) LVDC Distribution System Protection Hardware Test Results L estimation error < 20% Detection/location time < 0.7 ms L = 18 µh and R = 20 mω L = 30 µh and R = 2 mω ID Actual L (µh) / fault R (mω) Estimated L (µh) Error (%) Fault location time (ms) 1 18 / / / / / / / / / Error (%) Error (%) page 15

16 LVDC Distribution System Protection Improvement Level 1 Level 2 Level 3 No boundary inductor Equivalent inductance distribution Zonal boundary inductors Equivalent inductance ΔL 1 ΔL 2 ΔL 3 Level 4 L 4 Equivalent inductance L 2 L 3 Inserted ΔL 3 L 3 L 1 Distance L 2 Inserted ΔL 2 level 1 level 2 level 3 L 1 Inserted ΔL 1 level 1 level 2 level 3 level 4 Distance DC UPS 380 VDC ~ = = = Fault 1 Fault 2 Zone 1 (20 m) Zone 2 (65 m) Zone 3 (10.2 m) L L L L L L Fault 3 Zone 4 (1.5 m) page 16

17 LVDC Distribution System Protection Summary The prot. method uses local measurements only to locate fault 1. Detection and location time < 0.7 ms 2. L estimation error in HIL test < 8.4% 3. L estimation error in hardware test < 20% The prot. method can accurately locate short-circuit faults if: 1. Voltage measurement error < 0.5% 2. Current measurement error < 1% Boundary inductors improve prot. selectivity Next Step More test on real MW-level dc microgrid page 17

18 MVDC Shipboard Power System Protection MVDC Prot. Challenges Multiple sources Distributed capacitors Mesh network Low line impedance Fast fault isolation Convert FCL Pulse load (high di/dt) 1.1 kv 2 MW 200 Hz M PMM PROPULSON LOAD PGM 850 V 0.8 MW 60 Hz 3-ph 850 V 1.2 MW 60 Hz 3-ph PCM PGM PFN Railgun MISSION LOAD 1.15 kvdc/ 1.0 kvdc = = 60 Hz Loads IPNC 1.15 kvdc PCM1-A = = 60 Hz AC Distribution 400 Hz Loads 60 Hz Loads 1.15 kvdc 60 Hz Loads 60 Hz AC Distribution IPNC = = = = 1.15 kvdc/ 1.0 kvdc PCM1-A 400 Hz Loads page 18

19 MVDC Shipboard Power System Protection Two power generation modules FCL in dc-dc converters One propulsion load One pulse load High di/dt Two dc circuit breakers Isolate fault on main dc bus Protection strategy* FCL + differential protection PMM M 1.1 kv 2 MW 200 Hz 3 NC PROPULSON LOAD Toshiba 1 & 4 NC = Normally closed CL = Current Limit 1 = Capacitor 2 = Mechanical Circuit Breakers 3 = Contactors 4 = Line Reactor kv main dc bus 2 2 NC NC 850 V, 0.8 MW 60 Hz, 3-phase Lab Power CL = = PGM CL = = 1 & 4 NC NC PGM 850 V, 1.2 MW 60 Hz, 3-phase Lab Power NC NC Equivalent DC zonal Load PCM MISSION LOAD PFN Railgun *S. Strank, X. Feng, A. Gattozzi, D. Wardell, S. Pish, J. Herbst, and R. Hebner, Experimental test bed to de-risk the navy advanced development model, Proc. of Electric Ship Technology Symposium, Arlington, VA, Aug., pp page 19

20 Voltage (V) Current (A) MVDC Shipboard Power System Protection Main results Fault: ms, 20 mω, on dc bus Prot. strategy: FCL + diff. prot PGM V 60 Hz 3-Ph ac Current differential: i 1 (t) + i 2 (t) = = Reactor 1 CB mh 0.39 mh 5 mf 0.5 mf Load MW Diff. prot. zone i 1 (t) 80 µh 9 mω time (ms) PGM V 60 Hz 3-Ph ac = = 5 mf Reactor mh 0.39 mh 0.5 mf 1 MW Load 2 CB2 i 2 (t) 80 µh 9 mω Main dc bus 1150 V dc time (ms) page 20

21 Current (A) Current (A) MVDC Shipboard Power System Protection Sensitivity analysis Current diff. with different fault R Current diff. with measurement time differences Internal fault Current differential: i 1 (t) + i 2 (t) Fault R = 1 mohm Fault R = 10 mohm Fault R = 20 mohm Fault R = 50 mohm Fault R = 200 mohm time (ms) Next step work Test the prot. strategy on a MWlevel MVDC test bed External fault delta t = 2 us delta t = 5 us delta t = 10 us delta t = 20 us delta t = 50 us time (ms) page 21

22 Current (p.u.) (p.u.) Current (p.u.) (p.u.) AC Distribution System Fault Location Fault type identification Permanent or temporary Impedance-based Fault Location Use impedance model and fault waveform Currents for a permanent fault Currents for a permanent fault Time (Seconds) Time (Seconds) Currents for a transient fault Currents for a transient fault Time (Seconds) Time (Seconds) page 22

23 AC Distribution System Fault Location Traveling Wave Method Requirement GPS synchronization High sampling rate sensors Fast processing speed Benefit Incipient fault location (sub-cycle fault) Simple algorithm Extra-fast fault location Proposed intelligent sensors GPS signals Traveling wave s 2 s 1 s 3 fault Intelligent sensor page 23

24 Conclusion 1. Reliable and fast prot. strategy improves grid reliability and resilience 2. DC prot. is enabling tech. for large-scale deployment of dc systems 3. Extra-fast fault location and restoration are keys for grid resilience 4. Control/power-HIL tests effectively evaluate new prot. technology page 24

25 Thanks Contact information: Xianyong Feng Center for Electromechanics The University of Texas at Austin Phone: page 25

Experiences of a microgrid research laboratory and lessons learned for future smart grids

Experiences of a microgrid research laboratory and lessons learned for future smart grids Experiences of a microgrid research laboratory and lessons learned for future smart grids Olimpo Anaya-Lara, Paul Crolla, Andrew J. Roscoe, Alberto Venturi and Graeme. Burt Santiago 2013 Symposium on icrogrids

More information

Medium Voltage DC Solid State Circuit Protection

Medium Voltage DC Solid State Circuit Protection Medium Voltage DC Solid State Circuit Protection DISTRIBUTION STATEMENT A. Approved for public release: distribution unlimited. Patrick J. McGinnis PE R&D Project Manager April 12, 2019 1 PJM CV Aerospace

More information

Under-Frequency Load Shedding based on PMU Estimates of Frequency and ROCOF

Under-Frequency Load Shedding based on PMU Estimates of Frequency and ROCOF Under-Frequency Load Shedding based on PMU Estimates of Frequency and ROCOF Asja Derviškadić, Yihui Zuo, Guglielmo Frigo and Mario Paolone Swiss Federal Institute of Technology (EPFL) Distributed Electrical

More information

Model Description Document Notional Four Zone MVDC Shipboard Power System Model ONR GRANT # N

Model Description Document Notional Four Zone MVDC Shipboard Power System Model ONR GRANT # N Model Design Document Notional Four Zone MVDC Shipboard Power System Model Model Description Document Notional Four Zone MVDC Shipboard Power System Model Document developed by ESRDC Team 10/20/2017 Version

More information

Synchrophasor Applications for Distribution Networks Enhancing T&D Operation and Information Exchange

Synchrophasor Applications for Distribution Networks Enhancing T&D Operation and Information Exchange Synchrophasor Applications for Distribution Networks Enhancing T&D Operation and Information Exchange Luigi Vanfretti, Hossein Hooshyar, Farhan Mahmood, Ravi Shankar Singh, Ali Bidadfar, Narender Singh,

More information

Highgate Converter Overview. Prepared by Joshua Burroughs & Jeff Carrara IEEE PES

Highgate Converter Overview. Prepared by Joshua Burroughs & Jeff Carrara IEEE PES Highgate Converter Overview Prepared by Joshua Burroughs & Jeff Carrara IEEE PES Highgate Converter Abstract Introduction to HVDC Background on Highgate Operation and Control schemes of Highgate 22 Why

More information

Investigation and Correction of Phase Shift Delays in Power Hardware in Loop Real-Time Digital Simulation Testing of Power Electronic Converters

Investigation and Correction of Phase Shift Delays in Power Hardware in Loop Real-Time Digital Simulation Testing of Power Electronic Converters Investigation and Correction of Phase Shift Delays in Power Hardware in Loop Real-Time Digital Simulation Testing of Power Electronic Converters MASOUD DAVARI and FARID KATIRAEI Quanta Technology Toronto,

More information

Texas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event

Texas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event Texas Reliability Entity Event Analysis Event: May 8, 2011 Loss of Multiple Elements Category 1a Event Texas Reliability Entity July 2011 Page 1 of 10 Table of Contents Executive Summary... 3 I. Event

More information

Electric Grid Modernization Enabled by SiC Device based Solid State Transformers and Innovations in Medium Frequency Magnetics

Electric Grid Modernization Enabled by SiC Device based Solid State Transformers and Innovations in Medium Frequency Magnetics 1/31 Electric Grid Modernization Enabled by SiC Device based Solid State Transformers and Innovations in Medium Frequency Magnetics Dr. Subhashish Bhattacharya Department of Electrical and Computer Engineering

More information

DC 4Q POWER AMPLIFIER 200kW 2 RANGES HIGH POWER RS232

DC 4Q POWER AMPLIFIER 200kW 2 RANGES HIGH POWER RS232 PERFORMANCES High accuracy High stability Fast transients High inrush current facilities Very low noise Very low output impedance Quadrant change without transition Power analyzer included Reverse polarity

More information

The HIL Based Model Validation Paradigm - Tools, Challenges, and Application Examples

The HIL Based Model Validation Paradigm - Tools, Challenges, and Application Examples The HIL Based Model Validation Paradigm - Tools, Challenges, and Application Examples Michael Mischa Steurer Leader Power Systems Research Group at FSU-CAPS Email: steurer@caps.fsu.edu, phone: 850-644-1629

More information

EH2741 Communication and Control in Electric Power Systems Lecture 2

EH2741 Communication and Control in Electric Power Systems Lecture 2 KTH ROYAL INSTITUTE OF TECHNOLOGY EH2741 Communication and Control in Electric Power Systems Lecture 2 Lars Nordström larsno@kth.se Course map Outline Transmission Grids vs Distribution grids Primary Equipment

More information

AORC Technical meeting 2014

AORC Technical meeting 2014 http : //www.cigre.org B4-112 AORC Technical meeting 214 HVDC Circuit Breakers for HVDC Grid Applications K. Tahata, S. Ka, S. Tokoyoda, K. Kamei, K. Kikuchi, D. Yoshida, Y. Kono, R. Yamamoto, H. Ito Mitsubishi

More information

Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages

Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages Waruna Chandrasena, Bruno Bisewski, and Jeff Carrara Abstract-- This paper describes several system

More information

22 kw 4Q POWER AMPLIFIER RS232

22 kw 4Q POWER AMPLIFIER RS232 22 kw 4Q POWER AMPLIFIER PERFORMANCES High accuracy High stability Fast transients High inrush current facilities Very low noise Very low output impedance Quadrant change without transition Power analyzer

More information

How Full-Converter Wind Turbine Generators Satisfy Interconnection Requirements

How Full-Converter Wind Turbine Generators Satisfy Interconnection Requirements How Full-Converter Wind Turbine Generators Satisfy Interconnection Requirements Robert Nelson Senior Expert Engineering Manager and Manager of Codes, Standards, and Regulations Siemens Wind Turbines -

More information

MMC (Modular Multilevel Converter)

MMC (Modular Multilevel Converter) MMC (Modular Multilevel Converter) Lisbon September 29 2017 Susana Apiñániz Smart Grids Energy and environment Division Tecnalia susana.apinaniz@tecnalia.com INDEX 1. General information 2. Power sub-modules

More information

ENOSERV 2014 Relay & Protection Training Conference Course Descriptions

ENOSERV 2014 Relay & Protection Training Conference Course Descriptions ENOSERV 2014 Relay & Protection Training Conference Course Descriptions Day 1 Generation Protection/Motor Bus Transfer Generator Protection: 4 hours This session highlights MV generator protection and

More information

MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR)

MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR) VOL. 4, NO. 4, JUNE 9 ISSN 89-668 6-9 Asian Research Publishing Network (ARPN). All rights reserved. MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR) Rosli Omar and Nasrudin Abd Rahim

More information

Automated Fault Detection With PQ Monitors

Automated Fault Detection With PQ Monitors Automated Fault Detection With PQ Monitors Theo Laughner, PE Sr. Program Manager of Power Quality Acknowledgements: Anthony Murphy, PE October 12, 2015 Background Case Studies (5) Needs Tools Conclusion

More information

ISLANDING DETECTION USING DEMODULATION BASED FFT

ISLANDING DETECTION USING DEMODULATION BASED FFT ISLANDING DETECTION USING DEMODULATION BASED FFT Kumaravel.K 1 and Vetrivelan. P.L 2 Department of Electrical and Electronics Engineering, Er.Perumal Manimekalai College of Engineering, Hosur, India Abstract

More information

Control of Power Converters for Distributed Generation

Control of Power Converters for Distributed Generation Mechatronics Industrial Advisory Board 2004 Control of Power Converters for Distributed Generation Ph.D. Student: Min Dai Advisor: Prof. Ali Keyhani Department of Electrical and Computer Engineering The

More information

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL Basically the HVDC transmission consists in the basic case of two convertor stations which are connected to each other by a transmission link consisting of an overhead

More information

Validation of Frequency- and Time-domain Fidelity of an Ultra-low Latency Hardware-in-the-Loop (HIL) Emulator

Validation of Frequency- and Time-domain Fidelity of an Ultra-low Latency Hardware-in-the-Loop (HIL) Emulator Validation of Frequency- and Time-domain Fidelity of an Ultra-low Latency Hardware-in-the-Loop (HIL) Emulator Elaina Chai, Ivan Celanovic Institute for Soldier Nanotechnologies Massachusetts Institute

More information

A Novel Islanding Detection Technique for Distributed Generation (DG) Units in Power System

A Novel Islanding Detection Technique for Distributed Generation (DG) Units in Power System A Novel Islanding Detection Technique for Distributed Generation (DG) Units in Power System Amin Safari Department of Electrical Engineering, Ahar Branch, Islamic Azad University, Ahar, Iran a-safari@iau-ahar.ac.ir

More information

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS 84 CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS 4.1 INTRODUCTION Now a days, the growth of digital economy implies a widespread use of electronic equipment not only in the industrial

More information

Z-Source Circuit Breaker Utilizing Ultra-Fast Mechanical Switch for High Efficiency DC Circuit Protection

Z-Source Circuit Breaker Utilizing Ultra-Fast Mechanical Switch for High Efficiency DC Circuit Protection Z-Source Circuit Breaker Utilizing Ultra-Fast Mechanical Switch for High Efficiency DC Circuit Protection Landon Mackey, Md Rifat Kaisar Rachi, Chang Peng, Iqbal Husain College of Electrical and Computer

More information

Fixed Series Compensation

Fixed Series Compensation Fixed Series Compensation High-reliable turnkey services for fixed series compensation NR Electric Corporation The Fixed Series Compensation (FSC) solution is composed of NR's PCS-9570 FSC control and

More information

Hamdy Faramawy Senior Application Specialist ABB Sweden

Hamdy Faramawy Senior Application Specialist ABB Sweden Design, Engineering and Application of New Firm Capacity Control System (FCCS) Mohammed Y. Tageldin, MSc. MIET Senior Protection Systems Engineer ABB United Kingdom mohammed.tageldin@gb.abb.com Hamdy Faramawy

More information

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar Electrical Engineering department, Jabalpur Engineering College Jabalpur, India Abstract:

More information

Arizona Public Service Company and the Transmission Partnership for National Electric Power Company of Jordan

Arizona Public Service Company and the Transmission Partnership for National Electric Power Company of Jordan Arizona Public Service Company and the Transmission Partnership for National Electric Power Company of Jordan Mark Hackney October 5-8, 2009 Amman, Jordan Energy Control Center Layout 2 Energy Control

More information

Power Quality Basics. Presented by. Scott Peele PE

Power Quality Basics. Presented by. Scott Peele PE Power Quality Basics Presented by Scott Peele PE PQ Basics Terms and Definitions Surge, Sag, Swell, Momentary, etc. Measurements Causes of Events Possible Mitigation PQ Tool Questions Power Quality Measurement

More information

Past CIGRE and Emerging IEEE Guide Documents on FCLs

Past CIGRE and Emerging IEEE Guide Documents on FCLs Past CIGRE and Emerging IEEE Guide Documents on FCLs Michael Mischa Steurer Leader Power Systems Research Group at FSU-CAPS Email: steurer@caps.fsu.edu, phone: 850-644-1629 Presented by W. Hassenzahl Advanced

More information

POWER AMPLIFIERS 4 QUADRANTS 3x500 VA to 3x1500 VA - THREE-PHASES

POWER AMPLIFIERS 4 QUADRANTS 3x500 VA to 3x1500 VA - THREE-PHASES PERFORMANCES High accuracy High stability Fast transients High inrush current facilities Wide bandwidth Very low distortion Quadrant change without transition Very low output impedance Low noise RS232

More information

Development and testing of an experimental power system fault demonstrator

Development and testing of an experimental power system fault demonstrator Development and testing of an experimental power system fault demonstrator C. Rose, D. W. P. Thomas, M. Sumner, E. Christopher University of Nottingham, UK, eexcr@nottingham.ac.uk Keywords: Protection;

More information

Mitigation of the Statcom with Energy Storage for Power Quality Improvement

Mitigation of the Statcom with Energy Storage for Power Quality Improvement Mitigation of the Statcom with Energy Storage for Power Quality Improvement Mohammed Shafiuddin 1, Mohammed Nazeeruddin 2 1 Royal institute of Engineering & Technology (Affliated to JNTUH), India 2 Nawab

More information

Z-Source Circuit breaker design and protection schemes for DC micro grid systems

Z-Source Circuit breaker design and protection schemes for DC micro grid systems Clemson University TigerPrints All Theses Theses 5-2017 Z-Source Circuit breaker design and protection schemes for DC micro grid systems Atif Maqsood Clemson University, amaqsoo@g.clemson.edu Follow this

More information

2015 Relay School Bus Protection Mike Kockott March, 2015

2015 Relay School Bus Protection Mike Kockott March, 2015 2015 Relay School Bus Protection Mike Kockott March, 2015 History of Bus Protection Circulating current differential (1900s) High impedance differential (1940s) Percentage restrained differential (1960s)

More information

Inverter-Based Resource Disturbance Analysis

Inverter-Based Resource Disturbance Analysis Inverter-Based Resource Disturbance Analysis Key Findings and Recommendations Informational Webinar February 15, 2018 August 16, 2016 Blue Cut Fire Disturbance Key Findings and Recommendations 2 Western

More information

RT- HIL Implementation of Hybrid Synchrophasor and GOOSE- based Passive Islanding Schemes

RT- HIL Implementation of Hybrid Synchrophasor and GOOSE- based Passive Islanding Schemes RT- HIL Implementation of Hybrid Synchrophasor and - based Passive Islanding Schemes M. Shoaib Almas E- mail: msalmas@kth.se PhD Candidate Electric Power Systems Department KTH Royal Institute of Technology

More information

COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR)

COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR) 7 February 2018 RM Zavadil COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR) Brief Overview of Sub-Synchronous Resonance Series

More information

A New Fault Detection Tool for Single Phasing of a Three Phase Induction Motor. S.H.Haggag, Ali M. El-Rifaie,and Hala M.

A New Fault Detection Tool for Single Phasing of a Three Phase Induction Motor. S.H.Haggag, Ali M. El-Rifaie,and Hala M. Proceedings of the World Congress on Engineering 013 Vol II,, July 3-5, 013, London, U.K. A New Fault Detection Tool for Single Phasing of a Three Phase Induction Motor S.H.Haggag, Ali M. El-Rifaie,and

More information

ALP-UDR Universal Detection Relay user-defined protection, automation, and monitoring

ALP-UDR Universal Detection Relay user-defined protection, automation, and monitoring ALP-UDR Universal Detection Relay user-defined protection, automation, and monitoring The first Real-Time Protection and Automation platform that can be adapted to a wide variety of applications. While

More information

Power Hardware-in-the-Loop testing for the Inverterbased Distributed Power Source

Power Hardware-in-the-Loop testing for the Inverterbased Distributed Power Source Power Hardware-in-the-Loop testing for the Inverterbased Distributed Power Source Dip.-Ing Ziqian Zhang Bsc 1, Univ.-Prof. Dipl.-Ing. Dr. Lothar Fickert 1 1 Technische Universität Graz, Institut für Elektrische

More information

Power systems Protection course

Power systems Protection course Al-Balqa Applied University Power systems Protection course Department of Electrical Energy Engineering 1 Part 5 Relays 2 3 Relay Is a device which receive a signal from the power system thought CT and

More information

Study on Voltage Controller of Self-Excited Induction Generator Using Controlled Shunt Capacitor, SVC Magnetic Energy Recovery Switch

Study on Voltage Controller of Self-Excited Induction Generator Using Controlled Shunt Capacitor, SVC Magnetic Energy Recovery Switch Study on Voltage Controller of Self-Excited Induction Generator Using Controlled Shunt Capacitor, SVC Magnetic Energy Recovery Switch Abstract F.D. Wijaya, T. Isobe, R. Shimada Tokyo Institute of Technology,

More information

WP4-Hardware in the Loop Validation of the EFCC Scheme

WP4-Hardware in the Loop Validation of the EFCC Scheme WP4-Hardware in the Loop Validation of the EFCC Scheme Mingyu Sun, Dr Mazaher Karimi, Rasoul Azizipanah-Abarghooee Prof Vladimir Terzija Ben Marshall University of Manchester National Grid 0 Presentation

More information

A Pyrotechnic Fault Current Limiter Model for Transient Calculations in Industrial Power Systems

A Pyrotechnic Fault Current Limiter Model for Transient Calculations in Industrial Power Systems A Pyrotechnic Fault Current Limiter Model for Transient Calculations in Industrial Power Systems T. C. Dias, B. D. Bonatto, J. M. C. Filho Abstract-- Isolated industrial power systems or with high selfgeneration,

More information

EFCC Academia dissemination event

EFCC Academia dissemination event EFCC Academia dissemination event WP4-Hardware in the Loop Validation of the EFCC Scheme Mingyu Sun, Dr Mazaher Karimi, Rasoul Azizipanah-Abarghooee Prof Vladimir Terzija Ben Marshall University of Manchester

More information

Grounding and Fault Location in Power Electronic based MVDC Shipboard Power and Energy Systems

Grounding and Fault Location in Power Electronic based MVDC Shipboard Power and Energy Systems Grounding and Fault Location in Power Electronic based MVDC Shipboard Power and Energy Systems Ben Ford Hepburn and Sons LLC Manassas, VA USA Isaac Leonard, Matt Bosworth, Mischa Steurer Center for Advanced

More information

200 kw 4Q POWER AMPLIFIER RS232

200 kw 4Q POWER AMPLIFIER RS232 200 kw 4Q POWE AMPLIFIE PEFOMANCES High accuracy High stability Fast transients High inrush current facilities Very low noise Very low output impedance Quadrant change without transition Power analyzer

More information

A Demonstrator for Experimental Testing Integration of Offshore Wind Farms With HVDC Connection. S.D'Arco, A. Endegnanew, SINTEF Energi

A Demonstrator for Experimental Testing Integration of Offshore Wind Farms With HVDC Connection. S.D'Arco, A. Endegnanew, SINTEF Energi A Demonstrator for Experimental Testing Integration of Offshore Wind Farms With HVDC Connection S.D'Arco, A. Endegnanew, SINTEF Energi BEST PATHS PROJECT BEyond State-of-the-art Technologies for re-powering

More information

Non-detection zone of LOM protection for converter connected wind turbines

Non-detection zone of LOM protection for converter connected wind turbines - 1 - Non-detection zone of LOM protection for converter connected wind turbines Ontrei Raipala, Tampere University of Technology, Finland Table of contents Table of contents... 1 Introduction... 2 Loss

More information

Analysis, Modeling and Simulation of Dynamic Voltage Restorer (DVR)for Compensation of Voltage for sag-swell Disturbances

Analysis, Modeling and Simulation of Dynamic Voltage Restorer (DVR)for Compensation of Voltage for sag-swell Disturbances IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 9, Issue 3 Ver. I (May Jun. 2014), PP 36-41 Analysis, Modeling and Simulation of Dynamic Voltage

More information

Short-Circuit Analysis IEC Standard Operation Technology, Inc. Workshop Notes: Short-Circuit IEC

Short-Circuit Analysis IEC Standard Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Short-Circuit Analysis IEC Standard 1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Purpose of Short-Circuit Studies A Short-Circuit Study can be used to determine any or all of

More information

Fault Location Using Sparse Wide Area Measurements

Fault Location Using Sparse Wide Area Measurements 319 Study Committee B5 Colloquium October 19-24, 2009 Jeju Island, Korea Fault Location Using Sparse Wide Area Measurements KEZUNOVIC, M., DUTTA, P. (Texas A & M University, USA) Summary Transmission line

More information

UPGRADING SUBSTATION RELAYS TO DIGITAL RECLOSERS AND THEIR COORDINATION WITH SECTIONALIZERS

UPGRADING SUBSTATION RELAYS TO DIGITAL RECLOSERS AND THEIR COORDINATION WITH SECTIONALIZERS UPGRADING SUBSTATION RELAYS TO DIGITAL RECLOSERS AND THEIR COORDINATION WITH SECTIONALIZERS 1 B. RAMESH, 2 K. P. VITTAL Student Member, IEEE, EEE Department, National Institute of Technology Karnataka,

More information

Poornima G P. IJECS Volume 3 Issue 6 June, 2014 Page No Page 6453

Poornima G P. IJECS Volume 3 Issue 6 June, 2014 Page No Page 6453 www.ijecs.in International Journal Of Engineering And Computer Science ISSN:2319-7242 Volume 3 Issue 6 June, 2014 Page No. 6453-6457 Role of Fault Current Limiter in Power System Network Poornima G P.1,

More information

Design and Simulation of superconducting fault current limiter

Design and Simulation of superconducting fault current limiter Research Inventy: International Journal of Engineering And Science Vol.5, Issue 3 (March 2015), PP -06-13 Issn (e): 2278-4721, Issn (p):2319-6483, www.researchinventy.com Design and Simulation of superconducting

More information

Investigation and Correction of Phase Shift Delays in Power Hardware in Loop Real-Time Digital Simulation Testing of Power Electronic Converters

Investigation and Correction of Phase Shift Delays in Power Hardware in Loop Real-Time Digital Simulation Testing of Power Electronic Converters 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2015 Grid of the Future Symposium Investigation and Correction of Phase Shift Delays in Power Hardware in Loop Real-Time

More information

Investigation of Inter-turn Fault in Transformer Winding under Impulse Excitation

Investigation of Inter-turn Fault in Transformer Winding under Impulse Excitation Investigation of Inter-turn Fault in Transformer Winding under Impulse Excitation P.S.Diwakar High voltage Engineering National Engineering College Kovilpatti, Tamilnadu, India S.Sankarakumar Department

More information

Sarma (NDR) Nuthalapati, PhD

Sarma (NDR) Nuthalapati, PhD SYNCHROPHASOR TECHNOLOGY PMU USE CASE EXAMPLES Sarma (NDR) Nuthalapati, PhD Research Scientist Texas A&M University, College Station, TX Control Room Solutions Task Team NASPI Work Group meeting and first

More information

Application for A Sub-harmonic Protection Relay. ERLPhase Power Technologies

Application for A Sub-harmonic Protection Relay. ERLPhase Power Technologies Application for A Sub-harmonic Protection Relay ERLPhase Power Technologies 1 Outline Introduction System Event at Xcel Energy Event Analysis Microprocessor based relay hardware architecture Sub harmonic

More information

CHAPTER 3 APPLICATION OF THE CIRCUIT MODEL FOR PHOTOVOLTAIC ENERGY CONVERSION SYSTEM

CHAPTER 3 APPLICATION OF THE CIRCUIT MODEL FOR PHOTOVOLTAIC ENERGY CONVERSION SYSTEM 63 CHAPTER 3 APPLICATION OF THE CIRCUIT MODEL FOR PHOTOVOLTAIC ENERGY CONVERSION SYSTEM 3.1 INTRODUCTION The power output of the PV module varies with the irradiation and the temperature and the output

More information

Comparison Of DC-DC Boost Converters Using SIMULINK

Comparison Of DC-DC Boost Converters Using SIMULINK IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, PP 34-42 www.iosrjournals.org Comparison Of DC-DC Boost Converters Using SIMULINK Anupa Ann Alex

More information

No. SSIEC-SEW SHINSUNG. Solid Insulation Eco Load Break Switch (SILO) SILO SERIES 15kV, 27kV 400A, 630A

No. SSIEC-SEW SHINSUNG. Solid Insulation Eco Load Break Switch (SILO) SILO SERIES 15kV, 27kV 400A, 630A SHINSUNG Solid Insulation Eco Load Break Switch (SILO) SILO SERIES 15kV, 27kV 400A, 630A Enhanced Self Healing System General SILO is 3 phase, solid insulated load break switch (LBS) and vacuum interruption

More information

ABB AG - EPDS. I S -limiter The worldʼs fastest limiting and switching device

ABB AG - EPDS. I S -limiter The worldʼs fastest limiting and switching device ABB AG - EPDS The worldʼs fastest limiting and switching device Agenda The world s fastest limiting and switching device Customers Function: Insert-holder with insert Comparison: I S -limiter Circuit-breaker

More information

CHAPTER-IV EXPERIMENTAL AND SIMULATION PROGRAM

CHAPTER-IV EXPERIMENTAL AND SIMULATION PROGRAM 49 CHAPTER-IV EXPERIMENTAL AND SIMULATION PROGRAM 4.0 INTRODUCTION This chapter covers in detail the experimental set up of proposed Z source Matrix (ZSMC) based UPFC and compares with a lab scale model

More information

Protect and survive. Fault protection analysis in low-voltage DC microgrids with photovoltaic generators

Protect and survive. Fault protection analysis in low-voltage DC microgrids with photovoltaic generators Fault protection analysis in low-voltage DC microgrids with photovoltaic generators MARCO CARMINATI, ENRICO RAGAINI The connection of renewableenergy-based microgrids to national power grids has many advantages.

More information

In power system, transients have bad impact on its

In power system, transients have bad impact on its Analysis and Mitigation of Shunt Capacitor Bank Switching Transients on 132 kv Grid Station, Qasimabad Hyderabad SUNNY KATYARA*, ASHFAQUE AHMED HASHMANI**, AND BHAWANI SHANKAR CHOWDHRY*** RECEIVED ON 1811.2014

More information

ECE 528 Understanding Power Quality. Paul Ortmann (voice) Lecture 6

ECE 528 Understanding Power Quality.   Paul Ortmann (voice) Lecture 6 ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 6 1 Today more on voltage sags Motor starting mitigation Impacts

More information

A Novel H Bridge based Active inductor as DC link Reactor for ASD Systems

A Novel H Bridge based Active inductor as DC link Reactor for ASD Systems A Novel H Bridge based Active inductor as DC link Reactor for ASD Systems K Siva Shankar, J SambasivaRao Abstract- Power converters for mobile devices and consumer electronics have become extremely lightweight

More information

IMPLEMENTATION OF FM-ZCS-QUASI RESONANT CONVERTER FED DC SERVO DRIVE

IMPLEMENTATION OF FM-ZCS-QUASI RESONANT CONVERTER FED DC SERVO DRIVE IMPLEMENTATION OF FM-ZCS-QUASI RESONANT CONVERTER FED DC SERVO DRIVE 1 K. NARASIMHA RAO, 2 DR V.C. VEERA REDDY 1 Research Scholar,Department of Electrictrical Engg,S V University, Tirupati, India 2 Professor,

More information

FAULT PROTECTION OF A LOOP TYPE LOW VOLTAGE DC BUS BASED MICROGRIDS

FAULT PROTECTION OF A LOOP TYPE LOW VOLTAGE DC BUS BASED MICROGRIDS INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET) Proceedings of the International Conference on Emerging Trends in Engineering and Management (ICETEM14) ISSN 0976 6545(Print) ISSN 0976

More information

WILEY CONTROL OF POWER INVERTERS IN RENEWABLE ENERGY AND SMART GRID INTEGRATION. Qing-Chang Zhong. Tomas Hornik IEEE PRESS

WILEY CONTROL OF POWER INVERTERS IN RENEWABLE ENERGY AND SMART GRID INTEGRATION. Qing-Chang Zhong. Tomas Hornik IEEE PRESS CONTROL OF POWER INVERTERS IN RENEWABLE ENERGY AND SMART GRID INTEGRATION Qing-Chang Zhong The University of Sheffield, UK Tomas Hornik Turbo Power Systems Ltd., UK WILEY A John Wiley & Sons, Ltd., Publication

More information

Success Story. 1. Context

Success Story. 1. Context Collaboration between VIZIMAX and OPAL-RT leads to early certification of the VIZIMAX PMU and to the validation of OPAL-RT s accurate PMU algorithm test suite against official certification lab results.

More information

DC Interfaces for Naval Applications

DC Interfaces for Naval Applications Dr. Norbert Doerry Naval Sea Systems Command DC Interfaces for Naval Applications ABSTRACT MIL-STD-1399-300 and MIL-STD-1399-680 have established a.c. voltage interface requirements for U.S. naval surface

More information

Real-time Visualization, Monitoring and Controlling of Electrical Distribution System using MATLAB

Real-time Visualization, Monitoring and Controlling of Electrical Distribution System using MATLAB Real-time Visualization, Monitoring and Controlling of Electrical Distribution System using MATLAB Ravi Prakash Saini 1, Vijay Kumar 2, J. Sandeep Soni 3 UG Student, Dept. of EE, B. K. Birla Institute

More information

ISSN Vol.07,Issue.11, August-2015, Pages:

ISSN Vol.07,Issue.11, August-2015, Pages: ISSN 2348 2370 Vol.07,Issue.11, August-2015, Pages:2063-2068 www.ijatir.org LCL Filter Design and Performance Analysis for Grid-Interconnected Systems T. BRAHMA CHARY 1, DR. J. BHAGWAN REDDY 2 1 PG Scholar,

More information

Christopher S. Edrington, PhD, PE. Energy Conversion and Integration Thrust. Electrical and Computer Engineering/Center for Advanced Power Systems

Christopher S. Edrington, PhD, PE. Energy Conversion and Integration Thrust. Electrical and Computer Engineering/Center for Advanced Power Systems We bring expertise in: Distributed control for power and energy management Fault tolerant control via advanced methodologies from the actuator to system Advanced methodologies to seamlessly incorporate

More information

Chapter 3 : Closed Loop Current Mode DC\DC Boost Converter

Chapter 3 : Closed Loop Current Mode DC\DC Boost Converter Chapter 3 : Closed Loop Current Mode DC\DC Boost Converter 3.1 Introduction DC/DC Converter efficiently converts unregulated DC voltage to a regulated DC voltage with better efficiency and high power density.

More information

Design and Implementation of Modern Digital Controller for DC-DC Converters

Design and Implementation of Modern Digital Controller for DC-DC Converters Design and Implementation of Modern Digital Controller for DC-DC Converters S.Chithra 1, V. Devi Maheswaran 2 PG Student [Embedded Systems], Dept. of EEE, Rajalakshmi Engineering College, Chennai, Tamilnadu,

More information

p. 1 p. 6 p. 22 p. 46 p. 58

p. 1 p. 6 p. 22 p. 46 p. 58 Comparing power factor and displacement power factor corrections based on IEEE Std. 18-2002 Harmonic problems produced from the use of adjustable speed drives in industrial plants : case study Theory for

More information

Mitigation of voltage disturbances (Sag/Swell) utilizing dynamic voltage restorer (DVR)

Mitigation of voltage disturbances (Sag/Swell) utilizing dynamic voltage restorer (DVR) Research Journal of Engineering Sciences ISSN 2278 9472 Mitigation of voltage disturbances (Sag/Swell) utilizing dynamic voltage restorer (DVR) Abstract Srishti Verma * and Anupama Huddar Electrical Engineering

More information

DESIGN OF A MODE DECOUPLING FOR VOLTAGE CONTROL OF WIND-DRIVEN IG SYSTEM

DESIGN OF A MODE DECOUPLING FOR VOLTAGE CONTROL OF WIND-DRIVEN IG SYSTEM IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 8, Issue 5 (Nov. - Dec. 2013), PP 41-45 DESIGN OF A MODE DECOUPLING FOR VOLTAGE CONTROL OF

More information

PAPER-II (Subjective)

PAPER-II (Subjective) PAPER-II (Subjective) 1.(A) Choose and write the correct answer from among the four options given in each case for (a) to (j) below: (a) Improved commutation in d.c machines cannot be achieved by (i) Use

More information

ETAP PowerStation. Electrical Transient Analyzer Program. ETAP PowerStation. Short Circuit Analysis. ANSI Standard 3-Phase Fault Currents

ETAP PowerStation. Electrical Transient Analyzer Program. ETAP PowerStation. Short Circuit Analysis. ANSI Standard 3-Phase Fault Currents Page: 1 Electrical Transient Analyzer Program Short Circuit Analysis ANSI Standard 3-Phase Fault Currents Number of Buses: Swing Generator Load Total 1 0 4 5 Number of Branches: XFMR2 XFMR3 Reactor Line/Cable

More information

Real-time Volt/Var Optimization Scheme for Distribution Systems with PV Integration

Real-time Volt/Var Optimization Scheme for Distribution Systems with PV Integration Grid-connected Advanced Power Electronic Systems Real-time Volt/Var Optimization Scheme for Distribution Systems with PV Integration 02-15-2017 Presenter Name: Yan Chen (On behalf of Dr. Benigni) Outline

More information

Fault Current Limiter Selection Considerations for Utility Engineers

Fault Current Limiter Selection Considerations for Utility Engineers 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http: //www.cigre.org 2014 Grid of the Future Symposium Fault Current Limiter Selection Considerations for Utility Engineers K. TEKLETSADIK,

More information

Differential Current Sensor acc. to the standard UL2231 Ed.2.0. Customer: Standard type Page 1 of 7. Electrical data Ratings min. typ. max.

Differential Current Sensor acc. to the standard UL2231 Ed.2.0. Customer: Standard type Page 1 of 7. Electrical data Ratings min. typ. max. Customer: Standard type Page 1 of 7 Electrical data Ratings min. typ. max. Unit I P Primary nominal RMS current (1phase / 3phase) 32 40 A I N1 Rated residual operating current 1 5 ma rms I N2 Rated residual

More information

CHAPTER-5 DESIGN OF DIRECT TORQUE CONTROLLED INDUCTION MOTOR DRIVE

CHAPTER-5 DESIGN OF DIRECT TORQUE CONTROLLED INDUCTION MOTOR DRIVE 113 CHAPTER-5 DESIGN OF DIRECT TORQUE CONTROLLED INDUCTION MOTOR DRIVE 5.1 INTRODUCTION This chapter describes hardware design and implementation of direct torque controlled induction motor drive with

More information

Protective Relaying for DER

Protective Relaying for DER Protective Relaying for DER Rogerio Scharlach Schweitzer Engineering Laboratories, Inc. Basking Ridge, NJ Overview IEEE 1547 general requirements to be met at point of common coupling (PCC) Distributed

More information

Mitigation of Power Quality Problems Using DVR in Distribution Network for Welding Load

Mitigation of Power Quality Problems Using DVR in Distribution Network for Welding Load IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 10, Issue 4 Ver. I (July Aug. 2015), PP 106-112 www.iosrjournals.org Mitigation of Power Quality

More information

CHAPTER 6 DEVELOPMENT OF A CONTROL ALGORITHM FOR BUCK AND BOOST DC-DC CONVERTERS USING DSP

CHAPTER 6 DEVELOPMENT OF A CONTROL ALGORITHM FOR BUCK AND BOOST DC-DC CONVERTERS USING DSP 115 CHAPTER 6 DEVELOPMENT OF A CONTROL ALGORITHM FOR BUCK AND BOOST DC-DC CONVERTERS USING DSP 6.1 INTRODUCTION Digital control of a power converter is becoming more and more common in industry today because

More information

Renewable Interconnection Standard & Experimental Tests. Yahia Baghzouz UNLV Las Vegas, NV, USA

Renewable Interconnection Standard & Experimental Tests. Yahia Baghzouz UNLV Las Vegas, NV, USA Renewable Interconnection Standard & Experimental Tests Yahia Baghzouz UNLV Las Vegas, NV, USA Overview IEEE Std 1547 Voltage limitations Frequency limitations Harmonic limitations Expansion of IEEE Std

More information

A Three-Phase AC-AC Buck-Boost Converter using Impedance Network

A Three-Phase AC-AC Buck-Boost Converter using Impedance Network A Three-Phase AC-AC Buck-Boost Converter using Impedance Network Punit Kumar PG Student Electrical and Instrumentation Engineering Department Thapar University, Patiala Santosh Sonar Assistant Professor

More information

Optimizing HV Capacitor-Bank Design Protection & Testing

Optimizing HV Capacitor-Bank Design Protection & Testing Optimizing HV Capacitor-Bank Design Protection & Testing Benton Vandiver III ABB Inc. 71st Annual Conference for Protective Relay Engineers Texas A&M University Introduction Shunt Capacitor Bank Considerations

More information

THE RTDS SIMULATION AND ANALYSIS ON CSG OPERATION CHARACTERS

THE RTDS SIMULATION AND ANALYSIS ON CSG OPERATION CHARACTERS THE RTDS SIMULATION AND ANALYSIS ON CSG OPERATION CHARACTERS Mengjun Liao, Weiqiang Han, Qi Guo, Yunwen Guo Electrical Power Research Institute, China Southern Power Grid, Guangzhou, P.R.China 510000 Abstracts:

More information

Response of Grid Interconnected Solar PV inverters to Transmission System Faults

Response of Grid Interconnected Solar PV inverters to Transmission System Faults Response of Grid Interconnected Solar PV inverters to Transmission System Faults David Piper, P.E. Operations Planning & Analysis SCE Grid Control Center July 18, 2017 1 OVERVIEW 1. Overview of the event

More information

II. RESEARCH METHODOLOGY

II. RESEARCH METHODOLOGY Comparison of thyristor controlled series capacitor and discrete PWM generator six pulses in the reduction of voltage sag Manisha Chadar Electrical Engineering Department, Jabalpur Engineering College

More information