Measuring Electric Parameters in Street Lighting Networks

Size: px
Start display at page:

Download "Measuring Electric Parameters in Street Lighting Networks"

Transcription

1 Measuring Electric Parameters in Street Lighting Networks PETER JANIGA, DIONÝZ GAŠPAROVSKÝ, FRANTIŠEK JANÍČEK, ANTON BELÁŇ, ŽANETA ELESCHOVÁ, DOMINIK VIGLAŠ Department of Electrical Power Engineering Slovak University of Technology in Bratislava Ilkovičova 3, Bratislava SLOVAKIA Abstract: - Public lighting networks represent important electric consumption. These networks can be found in all cities in Slovakia and other countries. Operation Costs associated with the operation significantly influence the budgets of municipalities. Incorrect or suboptimal design increases the cost of public lighting operation. For this reason is the effort to assess public lighting network not only in terms of lighting but also in terms of energy. The aim of this paper is to show the results of measurements in public lighting networks of current status in terms of electrical characteristics. Based on the measurements is possible to create an image of the actual power proportions in public lighting networks and also about the problems that arise after incorrect design. The optimal solution to the energy aspects of public lighting networks requires an assessment of a several technical and electrical inputs. Key-Words: - public lighting networks, energetic aspects, power measuring, smart metering 1 Introduction Public lighting networks are major purchaser of electricity and this is significant factor of spending. Factories and scientist are constantly looking for ways to reduce costs. Recently investigated method is the use of renewable energy to supply public lighting networks. These sources provide us theoretically infinite amount of energy. In some cases, etc. solar energy or wind energy no need fuel, which further eliminates costs. Financial calculation showed that the use of these resources is not so convenient for the public lighting network. As a secondary effect was found method for solar panels and wind power can provide power supply for public lighting in off grid operation. The creation of the described solutions requires a comlex analysis of the electrical parameters of the networks of public lighting. It is consequence of mutual interference. On the one hand, power systems affect lights functionality and other lights affect network functionality. Incorrect network design can cause many problems, etc. a control units malfunctions, incorrect measurement, influence to luminous flux, lamp life reducing and others. Network Design in off grid operation can cause other specific problems. For example, power supply for discharge lamps. If such lamps supplied by inverters, they can produce problems related to deformed voltage. Off grid inverters typically generate voltage, which contains fundamental harmonic and higher harmonics. This distorted voltage causes a more distorted current flow and strain of network elements such as capacitors or inductors. Fig.1 Small wind power plant (300 Wp), photovoltaic panel (130 Wp) and LED luminarie 31 W [1] ISBN:

2 2 Measurement of electrical parameters in networks of public lighting Lamp is a major appliance in public lighting networks. If we are investigating the exact consumption in the network then, we can not only calculate the final consumption of installed power by multiplying the time of operation. For better understanding the particularity of public lighting networks were measured electrical parameters in switchboards and endpoints of line. 3 Measured data The aim of the measurements was to determine the consumption of public lighting networks and analyze the effects to power consumption. From the measurements is possible to identify specifics of public lighting networks in terms of electrical parameters. Measured were voltages and currents values. Stored were effective values and transients. Values were analyzed at start, during, and after stabilization. Values were measured in the switchboard and in selected line endpoints. From waveforms can be determined voltage and current harmonic analysis at start and after stabilization. Fig. 2 Analyzer connected to switchboard Analyzed were networks in Slovak Republic. Analyzed networks have various Year of construction; some were also reconstructed or newly built. A totally was analyzed 130 public lighting networks. Tab. 1 The analyzed public lighting networks Municipality Michalovce Dunajská Streda Number of measured switchboards Line Cable, overhead lines Cable, overhead lines In terms of distribution network impact to the public lighting network measurements were made at the time of the minimum and maximum load distribution networks. Consumption affects the size of the surrounding customers and distorted supply voltage. Fig. 3 Examples of measured data: Voltage, current, active power, reactive power in Dunajska Streda, switchboard 40, branch 1 ISBN:

3 4 Specifics of public lighting networks in determining the energy consumption In the public lighting networks is a major appliance lamp. Exact determination of network power consumption in time is nearly impossible. This is due to many influences and variable network characteristics. Lamps and network analysis identified the following impacts on immediate consumption: - Voltage drop, - The impact of electrical equipment of switchboard, line, connectors, fuse and luminaries, - Power variability of lamp during stabilisation, - Passive consumption of the network, - Control, measurement and communication equipment consumption, - Effect of harmonic voltages and currents - distortion power, - Installed regulators, - Variable operating time during the year, - Reactive power, - Load assymetry, - Connected other devices (kiosk lighting, building illumination, etc.) Voltage drop The wires design in public lighting networks requires check current capacity and voltage drops too. Especially if is use the lighting regulator. This could be the case reduced voltage by regulator and great voltage drops at the end of the line. Great voltage drops cause problem with stabile discharge in lamp. This problem occurs mainly when the lamps with magnetic ballasts. Electronic ballasts can solve problem with voltage drop. From measurements realized in Matúškovo can see that at the end of the line was voltage out off the boundaries of EN Although at the beginning of the branch almost nominal voltage. This situation occurred when at the beginning of the line were almost nominal voltage. This network was just before reconstruction and almost half of the lights are broken. Some lamp were connected to another phase but it is expected that already during the construction of the network with a 250 W mercury lamps were low voltage in lighting network and lamps were switched more often due to unstable discharge. This could cause the state where the two phases are broken. Fig. 4 Voltage at the beginning of line (green) and at the end of line (red). Measuring in Matuskovo Power variability of lamp during stabilisation Lamps used in street lighting used discharge lamps. For these sources are characterized progressive fixer parameters. Stabilize the discharge and the electrical parameters are no longer than 15 minutes. Fig. 5 Variable current during stabilisation of lamp in public lighting network (inductive ballasts upper, electronic ballasts bottom) Control, measurement and communication equipment consumption The calculations consider only resistance lines. Reactance is ignored because it is several times smaller. By measuring in real networks with nine lamps confirmed little impact on the course of the ISBN:

4 current reactance. The following figure shows the harmonic content does not change with distance, but only due to distorted voltages, slight differences due to age lamps (lifetime lamps are changing the electrical parameters) and small variations of electrical parts (the same lighting parameters are slightly different). Passive consumption of the network Consumption in network consists of the consumption of lamp and consumption of other equipment. Usually these elements are placed in the switchboard. Passive consumption and the consumption of auxiliary equipment can be divided into two groups: - Consumption depends on the installed power consumption, - Consumption is independent of the installed power consumption. Passive consumption in public lighting networks is caused by loss of breakers, power control circuit (timer or sensor light intensity). This group includes the consumption of the controller. Effect of harmonic voltages and currents - distortion power Currently dominate in the public lighting networks lamps with inductive ballast. These lamps have a nonlinear VA characteristic and non-harmonic currents cause flows. Size current distortion increases with the size of voltage distortion. Undistorted power supply voltage does not occur. Fig. 7 Vector diagram of power Distorted currents cause issue distortion power which is necessary to take into account when calculating the power consumption. [ VA] S = P + Q + D (8) Finally distorted currents cause increased losses, voltage distortion and greater stress of network elements. Deformed currents flows are eliminated in lamps with electronic ballasts. Harmonic generation in the LED lamps is depending on the power supply. If the power supply to the LED does not harmonics filter then generate this lamp strong distorted currents. Installed regulators Fig. 8 Voltage and current regulation Fig. 6 Sample of the current flowing in public lighting network In order to reduce the consumption of network regulates power lights. Technically regulation is designed individually in lamps or in the central switchboard. Deeper analysis showed that the ISBN:

5 change in voltage is changing power factor and harmonic content of current. These changes are caused by changing discharge and capacitor in lamp. In the case of voltage regulation on lamps with electronic ballasts, is to some extent this regulation is ineffective. Some newer regulators do not change only the amplitude but also the supply voltage waveform. In such cases, it is strongly influenced by the current flowing deformation in lamps. Load assymetry From several measurements carried out in the elderly and reconstructed networks indicated that the load unbalance is a common phenomenon. In terms of power quality is not a danger. Does not even increased operating costs, because depending on the distribution network is small unbalance charging customers. Load asymmetry in new networks is caused by the irresponsible connecting lights to different phases. Except the problem with uneven lighting pronounced in case of failure of one phase may be a problem with overloading phase, because the design is considered with uniform distribution. Very significantly, this problem is seen from measurements in Galante, where all the lights are connected to one phase even if the divorce was made the new three-phase cable. If the new networks connecting the unevenness caused by irresponsible lighting are very large, it may lead to switch off fusing the line. 4 Conclusion In determining consumption in public lighting networks, it is important to first determine whether the assessed immediate consumption or annual. Solving immediate consumption is easier to take into account, however, setting the operating time. When comparing the calculated values with the measured then differences may exist due to other influences such as: - connecting other devices (phone box lighting, buildings ilumination, fountains power source) - connecting a special occasional light (Christmas decoration, lighting used during holiday) Because the measurements obtained during the large amount of data, the results are still analyzed readings. For solving power balance network of public lighting with LED lighting are not some of the problems. Also in these luminaires can be clearly defined behavior when a certain voltage. In this case, you can build a network model and make a calculation taking into account the most impact. Acknowledgement This paper was supported by the Slovak Research and Development Agency under the contract No. APVV Integrated Analysis of the Solar Power Plants. This paper was supported by the agency VEGA MŠVVaŠ SR under Grant No. 1/1100/12. References: [1] Novák, T., Mišák, S., Sokanský, K. (2010). Využití obnovitelných zdrojú energie pro napájení svítidel verějného osvětlen, III. konference LUMEN V4, Brno [2] Sankaran, C., Power Quality, CRC Press, [3] Sokanský, K., Vzájemné vlivy osvětlovacích soustav a elektrizační soustavy, VŠB-TU, Ostrava, [4] Sokanský, K., Orság, F., Vzájemné ovlivňování kompaktních záživek a napájecí site, Internation conference Svetlo, Bratislava, [5] EN , Voltage characteristics of electricity supplied by public electricity networks, [6] Szathmáry, P., Kvalita elektrickej energie, ABB Elektro, s.r.o, Bratislava, [7] Šimic, J. Gros, S., Lasic, M., Third Harmonic in Low Voltage Networks, International conference Electrical Installations, Vedograf, Zahreb, ISBN:

Voltage Sags Evaluating Methods, Power Quality and Voltage Sags Assessment regarding Voltage Dip Immunity of Equipment

Voltage Sags Evaluating Methods, Power Quality and Voltage Sags Assessment regarding Voltage Dip Immunity of Equipment s Evaluating Methods, Power Quality and s Assessment regarding Voltage Dip Immunity of Equipment ANTON BELÁŇ, MARTIN LIŠKA, BORIS CINTULA, ŽANETA ELESCHOVÁ Institute of Power and Applied Electrical Engineering

More information

Tripping of circuit breakers in PV installations due to zero sequence field impedance

Tripping of circuit breakers in PV installations due to zero sequence field impedance Tripping of circuit breakers in PV installations due to zero sequence field impedance B. Verhelst 1,2, C. Debruyne 1,2, J. Desmet 1,2 1 dept. Electrical Engineering - Lemcko HoWest Kortrijk, Belgium bart.verhelst@howest.be

More information

Analysis of Transients during the Power System Restoration

Analysis of Transients during the Power System Restoration Transactions on Electrical Engineering, Vol. 7 (2018), No. 4 73 Analysis of Transients during the Power System Restoration Žaneta Eleschová 1), Martin Jedinák 2) and Rastislav Šmidovič 3) 1) Inst. of Power

More information

Analysis of Harmonic Distortion in Non-linear Loads

Analysis of Harmonic Distortion in Non-linear Loads Analysis of Harmonic Distortion in Non-linear Loads Anne Ko Department of Electrical Power Engineering Mandalay Technological University, Mandalay, Myanmar.Phone:+95-09-2225761 anneko101082@gmail.com Wunna

More information

PROPOSAL OF GRADUAL CONTROLLER FOR STATIC COMPENSATOR OF REACTIVE POWER

PROPOSAL OF GRADUAL CONTROLLER FOR STATIC COMPENSATOR OF REACTIVE POWER PROPOSAL OF GRADUAL CONTROLLER FOR STATIC COMPENSATOR OF REACTIVE POWER M. Liška Slovak University of Technology in Bratislava, Faculty of Electrical Engineering and Information Technology, Ilkovičova

More information

22.0 Harmonics in Industrial Power Systems

22.0 Harmonics in Industrial Power Systems 1.0 Harmonics in Industrial Power Systems Harmonic frequencies are multiples of the line (fundamental) frequency, which in North America is usually 60 Hz, while it is 50 Hz elsewhere. Figure 1 shows a

More information

The Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller

The Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller The Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller This paper deals with the general problem of utilizing of renewable energy sources to generate electric

More information

HVDC CAPACITOR COMMUTATED CONVERTERS IN WEAK NETWORKS GUNNAR PERSSON, VICTOR F LESCALE, ALF PERSSON ABB AB, HVDC SWEDEN

HVDC CAPACITOR COMMUTATED CONVERTERS IN WEAK NETWORKS GUNNAR PERSSON, VICTOR F LESCALE, ALF PERSSON ABB AB, HVDC SWEDEN HVDC CAPACITOR COMMUTATED CONVERTERS IN WEAK NETWORKS GUNNAR PERSSON, VICTOR F LESCALE, ALF PERSSON ABB AB, HVDC SWEDEN Summary Capacitor Commutated Converters (CCC) were introduced to the HVDC market

More information

ENERGY SAVING WITH OPTIMIZATION OF VOLTAGE AND CURRENT QUALITY

ENERGY SAVING WITH OPTIMIZATION OF VOLTAGE AND CURRENT QUALITY ENERGY SAVING WITH OPTIMIZATION OF VOLTAGE AND CURRENT QUALITY Approximation based on the know-how of SEMAN S.A. The non-linear nature of modern electric loads makes the reception of measures for the confrontation

More information

1. Introduction to Power Quality

1. Introduction to Power Quality 1.1. Define the term Quality A Standard IEEE1100 defines power quality (PQ) as the concept of powering and grounding sensitive electronic equipment in a manner suitable for the equipment. A simpler and

More information

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services edarat group INTRODUCTION Harmonics are a mathematical way of describing distortion

More information

Laboratory no. 3 FLUORESCENT LAMPS FITTINGS

Laboratory no. 3 FLUORESCENT LAMPS FITTINGS Laboratory no. 3 FLUORESCENT LAMPS FITTINGS 3.1 General information The fluorescent lamps powered at industrial frequency voltage act as nonlinear resistors, non-inertial, with a dynamic symmetric volt-ampere

More information

Harmonic Filters for Single Phase Equipment

Harmonic Filters for Single Phase Equipment POWER QUALITY Harmonic Filters for Single Phase Equipment Agriculture Call Centers Casino Slot Machines Computer Centers Distributed Generation Electronic Power Converter Oil & Gas On-Line UPS Power Electronics

More information

Performance and measurement of power quality due to harmonics from street lighting networks

Performance and measurement of power quality due to harmonics from street lighting networks European Association for the Development of Renewable Energies, Environment and Power Quality International Conference on Renewable Energies and Power Quality (ICREPQ 9) Valencia (Spain), 15th to 17th

More information

1 Exam Prep Photovoltaic System Design Questions and Answers

1 Exam Prep Photovoltaic System Design Questions and Answers 1 Exam Prep Photovoltaic System Design Questions and Answers 1. All of the following are major elements to consider when properly designing PV system EXCEPT? A. energy use B. energy storage C. energy conservation

More information

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013 A Statcom-Control Scheme for Power Quality Improvement of Grid Connected Wind Energy System B.T.RAMAKRISHNARAO*, B.ESWARARAO**, L.NARENDRA**, K.PRAVALLIKA** * Associate.Professor, Dept.of EEE, Lendi Inst.Of

More information

Power Factor. Power Factor Correction.

Power Factor. Power Factor Correction. Power Factor. Power factor is the ratio between the KW and the KVA drawn by an electrical load where the KW is the actual load power and the KVA is the apparent load power. It is a measure of how effectively

More information

POWER PLANT MODEL DESIGN USING MATLAB/SIMSCAPE

POWER PLANT MODEL DESIGN USING MATLAB/SIMSCAPE POWER PLANT MODEL DESIGN USING MATLAB/SIMSCAPE M. Ernek, J. Murgaš Ústav riadenia a priemyselnej informatiky, Slovenská technická univerzita, Fakulta elektrotechniky a informatiky Ilkovičova 3, 812 19

More information

Understanding Power Quality

Understanding Power Quality Understanding Power Quality Produced by Dr Bruce Girdwood For Energy Mad Ltd Version 1: 23 October 2007 The electronics revolution and the growing number of utility programmes promoting compact fluorescent

More information

p. 1 p. 6 p. 22 p. 46 p. 58

p. 1 p. 6 p. 22 p. 46 p. 58 Comparing power factor and displacement power factor corrections based on IEEE Std. 18-2002 Harmonic problems produced from the use of adjustable speed drives in industrial plants : case study Theory for

More information

Harmonics and Their Impact on Power Quality. Wayne Walcott Application Engineering Manager June, 2017

Harmonics and Their Impact on Power Quality. Wayne Walcott Application Engineering Manager June, 2017 Harmonics and Their Impact on Power Quality Wayne Walcott Application Engineering Manager June, 2017 Presentation Overview A little about harmonics What are harmonics What are NOT harmonics What creates

More information

Cetronic Power Products Ltd. REGUVOLT CONSTANT VOLTAGE TRANSFORMERS. Technical Information

Cetronic Power Products Ltd. REGUVOLT CONSTANT VOLTAGE TRANSFORMERS. Technical Information Cetronic Power Products Ltd. REGUVOLT COSTAT VOLTAGE TRASFORMERS Technical nformation Sinusoidal Output Voltage f the CVT is to be used as an AC voltage stabiliserthe sinusoid must be restored by a filter

More information

TECHNICAL BULLETIN 004a Ferroresonance

TECHNICAL BULLETIN 004a Ferroresonance May 29, 2002 TECHNICAL BULLETIN 004a Ferroresonance Abstract - This paper describes the phenomenon of ferroresonance, the conditions under which it may appear in electric power systems, and some techniques

More information

CAPACITIVE EARTH-FAULT CURRENT IN DISTRIBUTION NETWORKS OPERATED WITH THE ISOLATED NEUTRAL POINT

CAPACITIVE EARTH-FAULT CURRENT IN DISTRIBUTION NETWORKS OPERATED WITH THE ISOLATED NEUTRAL POINT 25 TH Expert Meeting "KOMUNALNA ENERGETIKA / POWER ENGINEERING", Maribor, 2016 1 CAPACITIVE EARTH-FAULT CURRENT IN DISTRIBUTION NETWORKS OPERATED WITH THE ISOLATED NEUTRAL POINT Lucie NOHÁČOVÁ, František

More information

ELECTRICAL POWER TRANSMISSION TRAINER

ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER This training system has been designed to provide the students with a fully comprehensive knowledge in Electrical Power Engineering

More information

Operation of a Three-Phase PWM Rectifier/Inverter

Operation of a Three-Phase PWM Rectifier/Inverter Exercise 1 Operation of a Three-Phase PWM Rectifier/Inverter EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the block diagram of the three-phase PWM rectifier/inverter.

More information

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

FGJTCFWPKPUVKVWVGQHVGEJPQNQI[ FGRCTVOGPVQHGNGEVTKECNGPIKPGGTKPI VGG246JKIJXQNVCIGGPIKPGGTKPI FGJTFWP"KPUKWG"QH"GEJPQNQI[" FGRTOGP"QH"GNGETKEN"GPIKPGGTKPI" GG"46"JKIJ"XQNIG"GPIKPGGTKPI Resonant Transformers: The fig. (b) shows the equivalent circuit of a high voltage testing transformer (shown

More information

Contents. Core information about Unit

Contents. Core information about Unit 1 Contents Core information about Unit UEENEEH114A - Troubleshoot resonance circuits......3 UEENEEG102A Solve problems in low voltage AC circuits...5 TextBook...7 Topics and material Week 1...9 2 Core

More information

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at   Modeling and Analysis of Transformer ISSN: 2454-132X Impact factor: 4.295 (Volume 3, Issue 6) Available online at www.ijariit.com Modeling and Analysis of Transformer Divyapradeepa.T Department of Electrical and Electronics, Rajalakshmi Engineering

More information

Thyristorised Automatic Power Factor

Thyristorised Automatic Power Factor Thyristorised Automatic Power Factor Correction with 7% D Tune Harmonics Suppression (Reactor/Filtering) System Power quality? In the present Low voltage (LV) industrial distribution system the power factor

More information

Single-Phase Grid-Tied Inverter (PWM Rectifier/Inverter)

Single-Phase Grid-Tied Inverter (PWM Rectifier/Inverter) Exercise 2 Single-Phase Grid-Tied Inverter (PWM Rectifier/Inverter) EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the singlephase grid-tied inverter. DISCUSSION OUTLINE

More information

Measuring Power Line Impedance

Measuring Power Line Impedance By Florian Hämmerle & Tobias Schuster 2017 by OMICRON Lab V1.1 Visit www.omicron-lab.com for more information. Contact support@omicron-lab.com for technical support. Page 2 of 13 Table of Contents 1 MEASUREMENT

More information

Drives 101 Lesson 5. Power Input Terminology for a VFD

Drives 101 Lesson 5. Power Input Terminology for a VFD Drives 101 Lesson 5 Power Input Terminology for a VFD This lesson covers the terminology associated with the incoming power to a Variable Frequency Drive (VFD) and the efforts to protect both the VFD and

More information

TO LIMIT degradation in power quality caused by nonlinear

TO LIMIT degradation in power quality caused by nonlinear 1152 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 13, NO. 6, NOVEMBER 1998 Optimal Current Programming in Three-Phase High-Power-Factor Rectifier Based on Two Boost Converters Predrag Pejović, Member,

More information

VOLTAGE OPTIMIZATION FOR INDUSTRY, TRADE, BUSINESS AND LOCAL NETWORKS

VOLTAGE OPTIMIZATION FOR INDUSTRY, TRADE, BUSINESS AND LOCAL NETWORKS VOLTAGE OPTIMIZATION FOR INDUSTRY, TRADE, BUSINESS AND LOCAL NETWORKS Employing a voltage control system in a low-tension network provides independence from network fluctuations. In addition, energy-using

More information

VOLTAGE REGULATOR R 449. Installation and maintenance. This manual must be sent to the end user R 449 X2 Z1 X1 Z2 E+ E- (12V - 10A)

VOLTAGE REGULATOR R 449. Installation and maintenance. This manual must be sent to the end user R 449 X2 Z1 X1 Z2 E+ E- (12V - 10A) This manual must be sent to the end user X2 Z1 X1 Z2 E+ E- J1 t (12V - 10A) ~ 10 ohms Exciter field + - Isolated DC power supply Installation and maintenance WARNING TO AVOID HARM EITHER TO PEOPLE OR TO

More information

ECET Modern Power

ECET Modern Power ECET 273000 Modern Power Course Instructors Course Philosophy This course is an introduction to a wide range of electrical energy systems technologies. Topics include fundamentals of energy conversion,

More information

Power Quality Analysis in Power System with Non Linear Load

Power Quality Analysis in Power System with Non Linear Load International Journal of Electrical Engineering. ISSN 0974-2158 Volume 10, Number 1 (2017), pp. 33-45 International Research Publication House http://www.irphouse.com Power Quality Analysis in Power System

More information

Effects of Harmonic Distortion I

Effects of Harmonic Distortion I Effects of Harmonic Distortion I Harmonic currents produced by nonlinear loads are injected back into the supply systems. These currents can interact adversely with a wide range of power system equipment,

More information

Transformers and power quality Part II. Modelling and researching generation of higher harmonics in small three-phase transformers

Transformers and power quality Part II. Modelling and researching generation of higher harmonics in small three-phase transformers EVENTS TRANSFORMER IN GRID ABSTRACT This article investigates the generation of high harmonics in the magnetizing current of small three-phase transform ers using the magnetic field ana lysis, the Finite

More information

Harmonic Solutions. Clean Power Drive Solution to Harmonic Distortion

Harmonic Solutions. Clean Power Drive Solution to Harmonic Distortion Harmonic Solutions Clean Power Drive Solution to Harmonic Distortion UTILITY GRID UTILITY SWITCH YARD IN THE FACILITY IEEE-519 POINT OF COMMON COUPLING POWER PLANT GENERATION TRANSMISSION MEDIUM VOLTAGE

More information

Figure.1. Block of PV power conversion system JCHPS Special Issue 8: June Page 89

Figure.1. Block of PV power conversion system JCHPS Special Issue 8: June Page 89 Soft Switching Converter with High Voltage Gain for Solar Energy Applications S. Hema*, A. Arulmathy,V. Saranya, S. Yugapriya Department of EEE, Veltech, Chennai *Corresponding author: E-Mail: hema@veltechengg.com

More information

Tuningintobetter power quality

Tuningintobetter power quality Technology Review Third harmonic filters Tuningintobetter power quality Jouko Jaakkola Your PC screen flickers, stops flickering, starts again... Irritating to be sure, and perhaps the first visible sign

More information

Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive Active Filtering Method Suresh Reddy D 1 Chidananda G Yajaman 2

Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive Active Filtering Method Suresh Reddy D 1 Chidananda G Yajaman 2 IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 03, 2015 ISSN (online): 2321-0613 Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive

More information

Design and Simulation of Shunt Passive Filter. Design and Simulation of Shunt Passive Filter for Harmonics Mitigation of Non-Linear Loads

Design and Simulation of Shunt Passive Filter. Design and Simulation of Shunt Passive Filter for Harmonics Mitigation of Non-Linear Loads Design and Simulation of Shunt Passive Filter for Harmonics Mitigation of Non-Linear Loads Design and Simulation of Shunt Passive Filter for Harmonics Dung Vo Tien, Mitigation Radomir Gono and ofzbigniew

More information

Realisation of the galvanic isolation in customer-end DC to AC inverters for the LVDC distribution

Realisation of the galvanic isolation in customer-end DC to AC inverters for the LVDC distribution Realisation of the galvanic isolation in customer-end DC to AC inverters for the LVDC distribution Background: The electric distribution network in Finland has normally voltage levels of 20 kv and 400

More information

FAQ for SIMOREG 6RA70 and Control Module

FAQ for SIMOREG 6RA70 and Control Module I DT LD CS 28 / February / 2011 FAQ for SIMOREG 6RA70 and Control Module Question: What requirements apply for line quality and what line interference can occur? Answer: Line requirements: Voltage: rated

More information

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company P2 Power Solutions Pvt. Ltd. An ISO 9001:2008 Company Quality Power within your Reach P2 Power Magnetics P2 Power Solutions Pvt. Ltd. P2 Power Solutions Pvt. Ltd. provides EMC and power quality solutions,

More information

Power Quality Solutions

Power Quality Solutions Power Quality Solutions What is Power Quality? For electrical systems to function in their intended manner without significant loss of performance or life, they require a supply of electricity that is

More information

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology Riya Philip 1, Reshmi V 2 Department of Electrical and Electronics, Amal Jyothi College of Engineering, Koovapally, India 1,

More information

ANALYSIS OF TRANSIENT ACTIONS INFLUENCE IN POWER TRANSFORMER

ANALYSIS OF TRANSIENT ACTIONS INFLUENCE IN POWER TRANSFORMER ANALYSIS OF TRANSIENT ACTIONS INFLUENCE IN POWER TRANSFORMER Jozef JURCIK 1, Miroslav GUTTEN 1, Daniel KORENCIAK 1 1 Department of Measurement and Applied Electrical Engineering, Faculty of Electrical

More information

CHAPTER 2 A SERIES PARALLEL RESONANT CONVERTER WITH OPEN LOOP CONTROL

CHAPTER 2 A SERIES PARALLEL RESONANT CONVERTER WITH OPEN LOOP CONTROL 14 CHAPTER 2 A SERIES PARALLEL RESONANT CONVERTER WITH OPEN LOOP CONTROL 2.1 INTRODUCTION Power electronics devices have many advantages over the traditional power devices in many aspects such as converting

More information

International Journal of Advance Engineering and Research Development

International Journal of Advance Engineering and Research Development Scientific Journal of Impact Factor(SJIF): 3.134 e-issn(o): 2348-4470 p-issn(p): 2348-6406 International Journal of Advance Engineering and Research Development Volume 2,Issue 4, April -2015 Reduction

More information

Demagnetization of Power Transformers Following a DC Resistance Testing

Demagnetization of Power Transformers Following a DC Resistance Testing Demagnetization of Power Transformers Following a DC Resistance Testing Dr.ing. Raka Levi DV Power, Sweden Abstract This paper discusses several methods for removal of remanent magnetism from power transformers.

More information

Line protection with transformer in the protection zone

Line protection with transformer in the protection zone Line protection with transformer in the protection zone www.siemens.com/siprotec5 Three-end line protection with transformer in the protection range SIPROTEC 5 Application Three-end line protection with

More information

Chapter 11. Alternating Current

Chapter 11. Alternating Current Unit-2 ECE131 BEEE Chapter 11 Alternating Current Objectives After completing this chapter, you will be able to: Describe how an AC voltage is produced with an AC generator (alternator) Define alternation,

More information

P2 Power Solutions Pvt. Ltd.

P2 Power Solutions Pvt. Ltd. P2 Power Solutions Pvt. Ltd. An ISO 9001:2008 Company Active Current Conditioners P2 Power Solutions Pvt. Ltd. P2 Power Solutions works to deliver Innovative Engineering solutions with specific focus on

More information

Extensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network

Extensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network Copyright 2017 ABB. All rights reserved. 1. Introduction Many distribution networks around the world have limited earth-fault current by a resistor located in the LV winding neutral point of for example

More information

A Three Phase Seven Level Inverter for Grid Connected Photovoltaic System by Employing PID Controller

A Three Phase Seven Level Inverter for Grid Connected Photovoltaic System by Employing PID Controller A Three Phase Seven Level Inverter for Grid Connected Photovoltaic System by Employing PID Controller S. Ragavan, Swaminathan 1, R.Anand 2, N. Ranganathan 3 PG Scholar, Dept of EEE, Sri Krishna College

More information

Understanding Harmonics

Understanding Harmonics Understanding Harmonics Terry Gaiser Sensus What Are Harmonics? 1 » What is Power Quality?» Power quality is the degree to which both the utilization and delivery of electric power affects the performance

More information

Investigation and Analysis of Interleaved Dc- Dc Converter for Solar Photovoltaic Module

Investigation and Analysis of Interleaved Dc- Dc Converter for Solar Photovoltaic Module Volume 119 No. 12 2018, 3019-3035 ISSN: 1314-3395 (on-line version) url: http://www.ijpam.eu ijpam.eu Investigation and Analysis of Interleaved Dc- Dc Converter for Solar Photovoltaic Module 1 S. Sankar

More information

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System 1 G.Balasundaram, 2 Dr.S.Arumugam, 3 C.Dinakaran 1 Research Scholar - Department of EEE, St.

More information

Compensation of Reactive Power Case Study

Compensation of Reactive Power Case Study 15 Compensation of Reactive Power Case Study Stefan Fassbinder and Alan Ascolari C15.1 FLUORESCENT LAMP Fluorescent lamps are the only common device where putting the most efficient way of compensation,

More information

A Color LED Driver Implemented by the Active Clamp Forward Converter

A Color LED Driver Implemented by the Active Clamp Forward Converter A Color LED Driver Implemented by the Active Clamp Forward Converter C. H. Chang, H. L. Cheng, C. A. Cheng, E. C. Chang * Power Electronics Laboratory, Department of Electrical Engineering I-Shou University,

More information

Construction Electrician/Industrial Electrician/Power Electrician Common Core Level 2

Construction Electrician/Industrial Electrician/Power Electrician Common Core Level 2 Common Core Level 2 Unit: B1 Commercial Electrical Code Level: Two Duration: 60 hours Theory: Practical: 60 hours 0 hours Overview: This unit is designed to provide the apprentice with the knowledge about

More information

Importance of Transformer Demagnetization

Importance of Transformer Demagnetization Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 00 (2017) 000 000 www.elsevier.com/locate/procedia 4th International Colloquium "Transformer Research and Asset Management Importance

More information

TAMING THE POWER ABB Review series

TAMING THE POWER ABB Review series TAMING THE POWER ABB Review series 54 ABB review 3 15 Beating oscillations Advanced active damping methods in medium-voltage power converters control electrical oscillations PETER AL HOKAYEM, SILVIA MASTELLONE,

More information

Power Quality Analysers

Power Quality Analysers Power Quality Analysers Review of Power Quality Indicators and Introduction to Power Analysers ZEDFLO Australia 6-Mar-2011 www.zedflo.com.au Power Quality Indicators Review of main indicators of electrical

More information

B.Tech Academic Projects EEE (Simulation)

B.Tech Academic Projects EEE (Simulation) B.Tech Academic Projects EEE (Simulation) Head office: 2 nd floor, Solitaire plaza, beside Image Hospital, Ameerpet Ameerpet : 040-44433434, email id : info@kresttechnology.com Dilsukhnagar : 9000404181,

More information

NJWA - Harmonics and Drives Proper System Design

NJWA - Harmonics and Drives Proper System Design Session Goals Larry Stanley, Sr. Regional Business Development Engineer, Water Segment Matthew LaRue, ABB Drives Product Manager Philadelphia District, Baldor of Philadelphia NJWA - Harmonics and Drives

More information

Single switch three-phase ac to dc converter with reduced voltage stress and current total harmonic distortion

Single switch three-phase ac to dc converter with reduced voltage stress and current total harmonic distortion Published in IET Power Electronics Received on 18th May 2013 Revised on 11th September 2013 Accepted on 17th October 2013 ISSN 1755-4535 Single switch three-phase ac to dc converter with reduced voltage

More information

What does Power Factor mean?

What does Power Factor mean? What does Power Factor mean? By: Wouter Ryckaert (Laboratory of lighting technology /Green Light Flanders), Koen Putteman (Eandis) and Dirk Van Kerckhoven (Infrax) Introduction In the lighting world, there

More information

CHAPTER 4 HARMONICS AND POWER FACTOR

CHAPTER 4 HARMONICS AND POWER FACTOR 4.1 Harmonics CHAPTER 4 HARMONICS AND POWER FACTOR In this research a comparative study of practical aspects of mixed use of diode and Thyristor converter technologies in Aluminium Smelters has been carried

More information

Tap Changer Analyzer & Winding Ohmmeter RMO60TD

Tap Changer Analyzer & Winding Ohmmeter RMO60TD Tap Changer Analyzer & Winding Ohmmeter RMO60TD Test current 5 ma 60 A DC Rapid automatic demagnetization AC Current monitoring channel Lightweight 13 kg Measuring range 0,1-2 k Two voltage sense channels

More information

Capacitor protection relay

Capacitor protection relay Capacitor Protection Relay FEATURES Capacitor unbalance protection Line current unbalance protection Overvoltage protection Overheating protection Ground fault protection Overcurrent protection Undercurrent

More information

EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION

EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION David TOPOLANEK Petr TOMAN Michal PTACEK Jaromir DVORAK Brno University of Technology - Czech

More information

Low Pass Harmonic Filters

Low Pass Harmonic Filters Exclusive e-rated Provider PRODUCT SHEET HARMITIGATOR TM Low Pass Harmonic Filters A solution for electrical distribution systems that require stable, reliable power, characterized by unparalleled power

More information

Study of High Voltage AC Underground Cable Systems Silva, Filipe Miguel Faria da; Bak, Claus Leth; Wiechowski, Wojciech T.

Study of High Voltage AC Underground Cable Systems Silva, Filipe Miguel Faria da; Bak, Claus Leth; Wiechowski, Wojciech T. Aalborg Universitet Study of High Voltage AC Underground Cable Systems Silva, Filipe Miguel Faria da; Bak, Claus Leth; Wiechowski, Wojciech T. Published in: Proceedings of the Danish PhD Seminar on Detailed

More information

Solar Home Systems. Manual for the Design and Modification of Solar Home System Components. M. R.Vervaart F. D. J. Nieuwenhout

Solar Home Systems. Manual for the Design and Modification of Solar Home System Components. M. R.Vervaart F. D. J. Nieuwenhout Solar Home Systems Manual for the Design and Modification of Solar Home System Components M. R.Vervaart F. D. J. Nieuwenhout ECN Netherlands Energy Research Foundation Petten,The Netherlands Copyright

More information

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL Basically the HVDC transmission consists in the basic case of two convertor stations which are connected to each other by a transmission link consisting of an overhead

More information

Synchronous rectifier in DC/DC converters

Synchronous rectifier in DC/DC converters 1 Portál pre odborné publikovanie ISSN 1338-0087 Synchronous rectifier in DC/DC converters Šaštinský Peter Elektrotechnika, Študentské práce 05.10.2009 This paper is presented design of synchronous rectifiers

More information

A Versatile Control Scheme for UPQC for Power Quality Improvement using fuzzy controller

A Versatile Control Scheme for UPQC for Power Quality Improvement using fuzzy controller IOSR Journal of Engineering (IOSRJEN) ISSN (e): 2250-3021, ISSN (p): 2278-8719 Vol. 04, Issue 09 (September. 2014), V3 PP 11-20 www.iosrjen.org A Versatile Control Scheme for UPQC for Power Quality Improvement

More information

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero Consider a bus and its associated circuits consisting of lines or transformers. The algebraic

More information

Harmonic Distortion and Variable Frequency Drives

Harmonic Distortion and Variable Frequency Drives Harmonic Distortion and Variable Frequency Drives Definitions Variable Frequency Drives (VFDs); sometimes referred to as variable speed drives. Harmonic Distortion is a measure of the amount of deviation

More information

POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics

POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics EE589-Power System Quality & Harmonics Electrical Engineering Department School of Engineering University of Jordan 1 Control of Harmonics

More information

BALLAST HANDBOOK. Basic Reference Manual. Integral Ballast Characteristics and Performance Data High Pressure Sodium Metal Halide HL-301 5/03

BALLAST HANDBOOK. Basic Reference Manual. Integral Ballast Characteristics and Performance Data High Pressure Sodium Metal Halide HL-301 5/03 BALLAST Basic Reference Manual Integral Ballast Characteristics and Performance Data High Pressure Sodium Metal Halide HL-301 5/03 BALLAST Why Use Ballasts? The high intensity discharge lamps -high pressure

More information

Characterization of a High Current Measurement System with Rogowski Current Sensor

Characterization of a High Current Measurement System with Rogowski Current Sensor Characterization of a High Current Measurement System with Rogowski Current Sensor Rastislav Malych 1, Ondrej Barczi 1 and Peter Vrabček 2 1 Applied Precision, Ltd., Staviteľská 1, 831 04 Bratislava, Slovakia,421232662301,

More information

Three-Phase Transformer Demagnetizer DEM60

Three-Phase Transformer Demagnetizer DEM60 Three-Phase Transformer Demagnetizer DEM60 Fully automatic demagnetization Demagnetization currents 5 ma 60 A DC Automatic discharging circuit Lightweight 13,1 kg High DC Current Source for Automatic Transformers

More information

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY 9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor

More information

REDUCTION OF TRANSFORMER INRUSH CURRENT BY CONTROLLED SWITCHING METHOD. Trivandrum

REDUCTION OF TRANSFORMER INRUSH CURRENT BY CONTROLLED SWITCHING METHOD. Trivandrum International Journal of Scientific & Engineering Research, Volume 7, Issue 4, April-216 628 REDUCTION OF TRANSFORMER INRUSH CURRENT BY CONTROLLED SWITCHING METHOD Abhilash.G.R Smitha K.S Vocational Teacher

More information

Advanced electromagnetism and electromagnetic induction

Advanced electromagnetism and electromagnetic induction Advanced electromagnetism and electromagnetic induction This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit

More information

Peteris Spels, ABB Inc., WMEA, November 18, 2011 HARMONICS. ABB Group December 14, 2011 Slide 1

Peteris Spels, ABB Inc., WMEA, November 18, 2011 HARMONICS. ABB Group December 14, 2011 Slide 1 Peteris Spels, ABB Inc., WMEA, November 18, 2011 HARMONICS December 14, 2011 Slide 1 Agenda Harmonics: What they are? Where do they come from? Why bother? Regulations How to detect? How to avoid? Summary

More information

Hardware Implementation of Interleaved Converter with Voltage Multiplier Cell for PV System

Hardware Implementation of Interleaved Converter with Voltage Multiplier Cell for PV System IJSTE - International Journal of Science Technology & Engineering Volume 1 Issue 12 June 2015 ISSN (online): 2349-784X Hardware Implementation of Interleaved Converter with Voltage Multiplier Cell for

More information

Simulation of Ferroresonance Phenomena in Power Systems

Simulation of Ferroresonance Phenomena in Power Systems Proc. of the 5th WSEAS/IASME Int. Conf. on Electric Power Systems, High Voltages, Electric Machines, Tenerife, Spain, December 68, 5 (pp37377) Simulation of Ferroresonance Phenomena in Power Systems JIŘÍ

More information

Curso de Transmissão em Corrente Continua Rio de Janeiro, de Junho, 2007

Curso de Transmissão em Corrente Continua Rio de Janeiro, de Junho, 2007 Curso de Transmissão em Corrente Continua Rio de Janeiro, 13 15 de Junho, 2007 DC Harmonic Filters Page 1 of 9 1 Function of the DC-Side Harmonic Filters Harmonic voltages which occur on the dc-side of

More information

Generator Advanced Concepts

Generator Advanced Concepts Generator Advanced Concepts Common Topics, The Practical Side Machine Output Voltage Equation Pitch Harmonics Circulating Currents when Paralleling Reactances and Time Constants Three Generator Curves

More information

Low Voltage Products. Enclosed Third Harmonic Filter THF and THF star Enclosed units. Brochure THFS1GB 03_04 1SCC330003C0201

Low Voltage Products. Enclosed Third Harmonic Filter THF and THF star Enclosed units. Brochure THFS1GB 03_04 1SCC330003C0201 Low Voltage Products Enclosed Third Harmonic Filter and star Enclosed units Brochure S1GB 3_4 1SCC333C21 The Third Harmonic - a Growing Problem Today's electrical networks and plants are under much more

More information

Adaptive ANN based STATCOM and DVR for optimal integration of wind energy with grid using permanent magnet synchronous generator

Adaptive ANN based STATCOM and DVR for optimal integration of wind energy with grid using permanent magnet synchronous generator Adaptive ANN based STATCOM and DVR for optimal integration of wind energy with grid using permanent magnet synchronous generator Priyanka Sahu Columbia Institute of Engineering and Technology, Raipur,

More information

ANALYSIS OF TRANSIENT ACTIONS INFLUENCE IN POWER

ANALYSIS OF TRANSIENT ACTIONS INFLUENCE IN POWER POWER ENGINEERING AND ELECTRICAL ENGINEERING, VOL. 9, NO. 2, JUNE 2011 65 ANALYSIS OF TRANSIENT ACTIONS INFLUENCE IN POWER TRANSFORMER Jozef JURCIK.1, Miroslav GUTTEN 1, Daniel KORENCIAK 1 1 Department

More information

Chapter L Power factor correction and harmonic filtering

Chapter L Power factor correction and harmonic filtering Chapter L Power factor correction and 1 2 3 4 5 6 7 8 9 10 Contents Reactive energy and power factor 1.1 The nature of reactive energy L2 1.2 Equipment and appliances requiring reactive energy L2 1.3 The

More information