Curso de Transmissão em Corrente Continua Rio de Janeiro, de Junho, 2007

Size: px
Start display at page:

Download "Curso de Transmissão em Corrente Continua Rio de Janeiro, de Junho, 2007"

Transcription

1 Curso de Transmissão em Corrente Continua Rio de Janeiro, de Junho, 2007 DC Harmonic Filters Page 1 of 9

2 1 Function of the DC-Side Harmonic Filters Harmonic voltages which occur on the dc-side of a converter station cause ac currents which are superimposed on the direct current in the transmission line. These alternating currents of higher frequencies can create interferences in neighbouring telephone systems despite limitation by smoothing reactors. Harmonic currents of lower frequency can cause risks for human beings and devices through induced voltages. DC filter circuits, which are connected in parallel to the station poles, are an effective tool for combating these problems. DC Filters will always be used if a telephone line is in close proximity to an HVDC overhead line and adequate shielding is not present on both the telephone line and the HVDC line. DC filters are not required in HVDC cable connections and HVDC back-toback links. It can often be more economical to shield individually exposed sections of telephone lines than to install a filter combination to handle the "worst case". Besides the dc filters there are other equipment in the dc circuit, which has significant contribution for limitation of harmonic currents on the dc line and thus shall be considered in the dc filter design as well: smoothing reactor and neutral bus surge capacitor. The smoothing reactors in the hvdc converter stations have following main duties: to avoid resonance at low order harmonics, especially at the fundamental and the second harmonic frequency to limit the high order harmonics in the dc line under the specified limits to smooth the ripple in the dc current, so that the current will not get discontinued in the whole operating range. to limit the overcurrents in case of a failure in the dc circuit Selection of the smoothing reactor size for a hvdc project shall consider all these different aspects. Together with the dc filters the smoothing reactor makes a considerable contribution to reduce the value of harmonic currents in the dc systems. The harmonic currents along the dc line should be calculated for different operation conditions. However, if an active dc filter is used, the harmonic currents on dc line can be effectively damped by the active filter alone. Therefore, the smoothing reactor size can be selected smaller than conventional scheme if the active part has enough power output to meet the performance criteria. The smoothing reactor can also reduce the fault current and its rise rate through the valves at inverter side in case of some dc faults (by pass or bushing fault). This is primary of importance if a long dc cable is used for the transmission. For an overhead line transmission the current stress in valves is lower than the stress which will occur during valve short circuit. Neutral bus surge capacitor has the function to provide a low ohmic path within converter station for the so called triple harmonic currents caused by the stray capacitance in the converter equipment. This capacitor will significantly reduce the triple harmonics on the hvdc lines and the electrode lines as well. The selection of a proper size of this neutral bus capacitor is also a subject in the dc filter design. 2 Design Criteria for DC Filter Circuits The harmonic currents on the HVDC line create a magnetic alternating field. If a telephone line is in the vicinity of the dc line, harmonic voltages will be induced in the telephone line by the magnetic field. These harmonics in the telephone line and the Page 2 of 9

3 associated acoustic noise can significantly impair the quality of the telephone system. Therefore it is common practice to use the telephone interference caused by the dc line as a measure for the design of the dc filter circuits. The harmonic currents flowing in the hvdc lines can be generally split into components of balance mode and ground mode. While the currents in balance mode do not cause any interference in the remote telephone lines, the ground mode currents are actually responsible for the interference. Therefore the ground mode harmonic currents of all conductors at line tower including earth wires are referred as harmonic disturbing currents. The most often used dc filter performance criteria is the equivalent disturbing current Ieq, which is a psophometric weighted equivalent ground mode (=residual) current of all harmonics up to an order defined by the Specification. The equivalent disturbing current Ieq (x) at any location is calculated as geometric sum of contributions form both converter stations: I eq ( x) = I e ( x) r I e ( x) i Where Ieq(x) is the 800 Hz equivalent disturbing current in ma psophometric weighted at any location along the transmission lines Ie(x)r is the magnitude of equivalent disturbing current due to harmonic voltages at rectifier Ie(x)i is the magnitude of equivalent disturbing current due to harmonic voltages at inverter The equivalent disturbing current at any point due to harmonics from either station is calculated as follows: I ( x) = e Where n = m n= 1 [ I ( n, x) P( n) H ] g f 2 Ig(n,x) is the magnitude of residual rms current at harmonic order n in ma at location x P(n) is the psophometric weighting factor at harmonic order n as per CCITT Hf is the coupling factor which represents the frequency dependent coupling effect to open wire circuits. m is the maximum harmonic order, usually 50, to be considered in the calculation. The interference voltage induced on the telephone line can be characterized by the following equation: m ( ) V in(x) = Z Hµ Cµ Iµ ( x) 1 2 = Z I eq Page 3 of 9

4 where V in(x) = Interference voltage on the telephone line at point x (in mv/km) Z = Mutual coupling impedance between the telephone and HVDC lines at 1000 Hz H µ = Weighting factors which reflect the frequencydependency of the coupling between telephone and HVDC lines C µ = "C message" - weighting factors I µ(x) = Resulting harmonic current of the ordinal number µ in the HVDC line at point x as the vector sum of the currents caused by the two HVDC stations I eq = Psophometric weighted equivalent disturbing current It is apparent from the above equation that the interference voltage is dependent only on the equivalent disturbing current and the impedance between the HVDC and the telephone lines. At the time when the system is being designed, this impedance is often unknown. Therefore, in practice, often only the equivalent disturbing current is specified as a design criteria. There are no uniform standards for the maximum permissible equivalent disturbing current. It is dependant on conditions in the vicinity of the HVDC lines and the philosophy of the telephone and power system companies. The intensity of interference currents is strongly dependant on the operating condition of the HVDC. In monopolar operation, telephone interference is significantly stronger than in bipolar operation due to higher ground mode currents. As an example, the following values can be used as guideline for the maximum permissible equivalent interference current: bipolar operation: I eq 500 ma monopolar operation: I eq 1000 ma In light of the above, it is not possible to precisely calculate in advance the equivalent disturbing current caused by a planned HVDC system in existing or planned telephone lines. For this reason, the permissible induced interference voltage in an assumed telephone line, over a length of 1 km parallel to the HVDC system, at a distance of 1 km is in some cases specified. The ground resistance has to be specified, possibly with different values for different sections of the prospective line. The equivalent disturbing current can then be derived from the interference voltage (in mv/km). 3 Calculation of Equivalent Disturbing Current The task is now to determine the most unfavourable combination of harmonic voltages which can occur at one time in view of the operating modes and conditions of the HVDC system which are to be considered, incorporating the anticipated unsymmetries and tolerances. "Most unfavourable" means that combination which produces the highest equivalent disturbing current. In making this calculation, the dependency of the parameters of overhead lines, smoothing reactors, ground electrodes, etc., on frequency must be taken into consideration. Page 4 of 9

5 The harmonic currents which are emanating from a station undergo a frequencydependent phase shift. Standing waves are formed along the HVDC line. These standing waves are the superposition of the waves which are emanating from the two stations. The resulting harmonic profile is derived from the vector addition of the harmonic currents of the same frequency, emanating from the two sources, and being present at a particular location. As the difference of phase angles between the two harmonic currents sources are normally unknown, an angle of 90 is generally assumed. 4 Three Pulse Model for Harmonic Calculation Figure 1 shows the classic equivalent circuit for the calculation of dc-side harmonics of an HVDC converter with the voltage source U 12p. This generates the characteristic harmonic voltages of ordinal numbers k*12. The voltage spectrum will not be altered if the leakage capacitance C s is added. Figure 1 : DC-side equivalent circuit of the 12-pulse converter A 12-pulse HVDC converter can be decomposed into 4 series-connected 3-pulse commutation groups. The state of the art of dc filter design shall base on the 3 pulse model described above. The first step in the dc filter design is to determine the no-load dc harmonic voltages for these four 3 pulse sources. The simplest way for calculating the 3 pulse voltage magnitudes is using a theoretically derived trigonometric Fourier series expressions, which is based on the symmetric ac voltages: 1 = k U3 P Udio cosα cos( α u) (( 1) ( a cos(ϖt) + b3 k sin(ϖt))) 4 k=1 with a b cos( α(1 + )) + cos(( α + u)(1 + )) cos( a(1 )) + cos(( a + u)(1 )) = sin( a(1 + )) + sin(( a + u)(1 + )) sin( a(1 )) + sin(( a + u)(1 )) = Page 5 of 9

6 In order to consider all unsymmetries, a more precise method is needed to calculate the instantaneous voltage/current values for each valve switching interval. The twelve pulse voltage is indeed a superposition of the voltage of 4 three pulse bridges. The voltage wave form of each three pulse source will be constructed piecewise in the time domain. Then the results will be analyzed by Fourier series. Using this method all harmonic distortion on the ac voltage and all unbalances in the firing angle, transformer reactance etc. can be well represented for each chosen combinations of asymmetries. 5 DC Harmonic Filter Configurations DC filter circuits are usually arranged as parallel filters between the dc busbars and the station neutral bus or ground. Series dc filters (so called blocking filter) have been used only in isolated instances and therefore will not be discussed further in this paper. The configuration of the dc filters very strongly resembles the filters on the ac side of the HVDC station. There are several types of filter designs. Single and double tuned filters with or without the high-pass feature are common in the past. In the new scheme triple tuned dc filters are also used due to various technical and economical advantages. One or several types of dc filters can be utilized in a converter station. Basically the same type of ac harmonic filters can also be used in dc side (refer to Chapter AC Harmonic Filters ). Despite the many similarities, there are several important differences between dc and ac filter circuits. AC filter circuits are essentially responsible for providing reactive power of fundamental frequency. Therefore they are usually designed for higher reactive power than would be necessary for the required filter effect. This design aspect does not apply in the case of dc filters. The high voltage capacitor of the dc filter must withstand a high direct voltage. The uniform distribution of voltage among the many series-connected capacitor units, which can be automatically assumed in the case of ac filters due to capacitive current, does not apply for dc filters. It is necessary to ensure the distribution of voltage by means of parallel resistors. The ac system, to which the ac filter is connected in parallel, has a wide impedance range. Thus a resonance can occur under certain network conditions between filter capacitance and ac network inductance. For this reason a certain damping is necessary even in the case of sharply tuned ac filter circuits. In contrast, the impedance of the dc circuit is largely constant and therefore permits the use of sharply tuned filters. The determination of filter configuration is made on the basis of achieving the smallest equivalent disturbing current caused by the HVDC line and with minimum filter costs. Since the characteristic harmonic currents have the largest amplitudes, the dc filters are usually matched to these harmonics (i.e. ordinal numbers 12, 24, 36,...). The portion of cost of the entire HVDC system as represented by the dc filter circuits is normally not great. The most cost-intensive element in a dc filter is the high voltage capacitor. Therefore an effort is always to be made in the design of dc filter circuits to optimize the cost of high voltage capacitors, i.e., to keep them as small as possible, typically in the range from 0.5 uf to 2 uf. One means to this is the construction of double or multiple tuned filter circuits which have a common high voltage capacitor. Page 6 of 9

7 In connection with the dc filter circuits the capacitor between the station neutral bus and station ground must also be mentioned. It represents a low resistance path for transient overvoltages and also for dc-side harmonics. In particular when the dc filter is connected to ground, the capacitor prevents the harmonic currents from flowing through earth electrodes and electrode lines to the station neutral point, causing telephone interference or inducing unacceptable voltages. The harmonic currents described in the previous section, which flow out through leakage capacitances, pass through this capacitor to the station neutral point, which customarily has a capacitance of several uf. 6 Steady- state Stresses of DC Filter Circuits Steady- state stress of the dc filter capacitors is composed of two components: (1) direct voltage, which causes a breakdown risk on the dielectric but will not result in any heat generation, if the resistors built in for voltage grading are ignored, and (2) the harmonic currents of the tuned frequency. In filter reactors and resistors, these harmonic currents account for the entire steady state stresses. In order to determine the maximum steady state stress of individual filter elements, extensive calculations for various operating conditions are required. In particular, the following parameters and/or operating conditions should be taken into consideration: The specified maximum continuous direct voltage The maximum characteristic harmonic voltages which can occur in the steady-state (function of control angle and system direct current) If high-pass filters are provided, the maximum high frequency non-characteristic harmonic voltages which can occur at the same time If low order filters are provided: unsymmetries of the ac side and leakage capacitances in the station, so that the maximum filter current is achieved Harmonic currents flowing from the opposite station Fluctuations of ac-network frequency Filter detuning as a result of temperature fluctuation, manufacturing tolerance, aging of the elements, loss of capacitor sections, and failure of capacitor cans Operating mode of the HVDC system (bipolar, monopolar, reduced direct voltage, etc.) Outage of a filter unit (if several are present) 7 Transient Stresses of DC Filter Circuits Filter circuit components are subjected to various transient stresses as a result of faults and switching procedures. For this reason, the reactors and the resistors in the filter circuit have to be protected from over voltages by arresters where necessary just as in ac filters. The following two types of faults ordinarily result in the most severe stresses for dc filter components: A flash-over to ground occurring when the voltage at the dc busbar prior to the fault is equal to the arrester switching surge protective level. A line to ground fault occurring in the HVDC line at a certain distance from the converter station. Page 7 of 9

8 8 Design Considerations of Filter Equipment Basically the same aspects apply for the components of a dc filter circuit as were presented for ac filter circuits. The high voltage capacitor represents an exception. Since only harmonic currents produce heating, the electric power is very low: This means that only a few capacitor units have to be connected in parallel. In contrast, the direct voltage, which is usually high, requires the series connection of a large number of capacitors. If the classic tiered arrangement on an insulating table is selected, a super slim tower will be obtained which is very sensitive to wind and earthquake stresses. This requires appropriate anchoring. For this reason it might be sometimes advantageous from a cost standpoint to suspend the high voltage capacitor from a mast or portal by elastically fixed insulators. 9 Active Filter "Active" filters represent a rather new development. In contrast to traditional filters, active filters have a controlled voltage source which feeds certain harmonic currents into the line through a power amplifier. These harmonic currents act to cancel the harmonic currents from the converter. The converter, however, represents a voltage source with respect to dc-side harmonics. The theoretically correct action would therefore be to place a controlled harmonic voltage source in series to the converter and to control it in such a manner that the harmonic voltages are precisely cancelled. A series source might present great difficulties since the transmission direct current has to pass it. The active filters placed in service to date are therefore integrated into the passive filter as an auxiliary device in the form of a harmonic voltage source, which injecting an harmonic currents. The high voltage capacitor in the passive filter is used to decouple the active filter from the high dc voltage. 10 Development Trends While ac filters simultaneously provide reactive power compensation, dc filters have no other function than to provide a low impedance path for dc-side harmonic currents and to filter them out of the HVDC line. In view of the growing demand for more cost effective designs of HVDC stations, the question of how to reduce telephone interference more economically has to be addressed. A more precise and realistic specification with respect to telephone interference could significantly reduce the costs of dc filter circuits. In the past, limit values were often specified for telephone interference which were based on the telephone technology of twenty years ago. The interference effect of harmonic currents occurs primarily in openwire analog telephone systems. During recent years telecommunications technology has developed to the extent that higher harmonic currents could well be permitted on HVDC lines. Modern digital transmission technology and mobile phones are both immune to electromagnetic interference by an HVDC line. The need for dc filter circuits in HVDC systems appears, at least in countries with well developed telecommunications technology, to be becoming smaller. In the recent HVDC projects there are rarely telephone interference problems along the DC lines reported. It is often more economical Page 8 of 9

9 to take measures to shield telephone lines which are still sensitive to interference than to install expensive dc filters. This would entail converting sections of telephone lines which are subjected to interference from HVDC overhead lines to cable. For questions please contact: Mario Nelson Lemes Siemens Ltda Tel: Fax: Page 9 of 9

Insulation Co-ordination For HVDC Station

Insulation Co-ordination For HVDC Station Insulation Co-ordination For HVDC Station Insulation Co-ordination Definitions As per IEC 60071 Insulation Coordination is defined as selection of dielectric strength of equipment in relation to the operating

More information

Design and Simulation of Passive Filter

Design and Simulation of Passive Filter Chapter 3 Design and Simulation of Passive Filter 3.1 Introduction Passive LC filters are conventionally used to suppress the harmonic distortion in power system. In general they consist of various shunt

More information

High Voltage DC Transmission 2

High Voltage DC Transmission 2 High Voltage DC Transmission 2 1.0 Introduction Interconnecting HVDC within an AC system requires conversion from AC to DC and inversion from DC to AC. We refer to the circuits which provide conversion

More information

HVDC High Voltage Direct Current

HVDC High Voltage Direct Current HVDC High Voltage Direct Current Typical HVDC Station BACK TO BACK CONVERTER STATION MONO POLAR WITH GROUND RETURN PA Back to Back Converters indicates that the Rectifiers & Inverters are located in the

More information

SYSTEM STUDIES for HVDC

SYSTEM STUDIES for HVDC INTRODUCTION The design of HVDC requires Careful study coordination, which must be achieved in compliance with the Owner s requirements. To achieve these objectives, number of highly interactive system

More information

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL Basically the HVDC transmission consists in the basic case of two convertor stations which are connected to each other by a transmission link consisting of an overhead

More information

Unit-II----Analysis of HVDC Converters

Unit-II----Analysis of HVDC Converters Unit-II----Analysis of HVDC Converters Introduction: HVDC converters converts AC to DC and transfer the DC power, then DC is again converted to AC by using inverter station. HVDC system mainly consists

More information

HVDC CAPACITOR COMMUTATED CONVERTERS IN WEAK NETWORKS GUNNAR PERSSON, VICTOR F LESCALE, ALF PERSSON ABB AB, HVDC SWEDEN

HVDC CAPACITOR COMMUTATED CONVERTERS IN WEAK NETWORKS GUNNAR PERSSON, VICTOR F LESCALE, ALF PERSSON ABB AB, HVDC SWEDEN HVDC CAPACITOR COMMUTATED CONVERTERS IN WEAK NETWORKS GUNNAR PERSSON, VICTOR F LESCALE, ALF PERSSON ABB AB, HVDC SWEDEN Summary Capacitor Commutated Converters (CCC) were introduced to the HVDC market

More information

High-Voltage Direct Current Technology - Part 2

High-Voltage Direct Current Technology - Part 2 High-Voltage Direct Current Technology - Part 2 Course No: E03-033 Credit: 3 PDH Velimir Lackovic, Char. Eng. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P:

More information

Topics in JNTU Syllabus Modules and Sub Modules Lecture. Basic characteristics L21 T1-Ch4, T2-Ch14 Characteristics. Modification of the control

Topics in JNTU Syllabus Modules and Sub Modules Lecture. Basic characteristics L21 T1-Ch4, T2-Ch14 Characteristics. Modification of the control SESSION PLAN Sl. Topics in JNTU Syllabus Modules and Sub Modules UNIT-III 9 Principal of DC link control Introduction Steady state equivalent circuit of a 2 terminal DC link Lecture L20 Suggested Books

More information

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

FGJTCFWPKPUVKVWVGQHVGEJPQNQI[ FGRCTVOGPVQHGNGEVTKECNGPIKPGGTKPI VGG246JKIJXQNVCIGGPIKPGGTKPI FGJTFWP"KPUKWG"QH"GEJPQNQI[" FGRTOGP"QH"GNGETKEN"GPIKPGGTKPI" GG"46"JKIJ"XQNIG"GPIKPGGTKPI Resonant Transformers: The fig. (b) shows the equivalent circuit of a high voltage testing transformer (shown

More information

1. Introduction to Power Quality

1. Introduction to Power Quality 1.1. Define the term Quality A Standard IEEE1100 defines power quality (PQ) as the concept of powering and grounding sensitive electronic equipment in a manner suitable for the equipment. A simpler and

More information

Power Electronics. Exercise: Circuit Feedback

Power Electronics. Exercise: Circuit Feedback Lehrstuhl für Elektrische Antriebssysteme und Leistungselektronik Technische Universität München Prof Dr-Ing Ralph Kennel Aricsstr 21 Email: eat@eitumde Tel: +49 (0)89 289-28358 D-80333 München Internet:

More information

TECHNICAL SPECIFICATION

TECHNICAL SPECIFICATION TECHNICAL SPECIFICATION IEC TS 60071-5 First edition 2002-06 Insulation co-ordination Part 5: Procedures for high-voltage direct current (HVDC) converter stations Coordination de l isolement - Partie 5:

More information

(2) New Standard IEEE P (3) Core : (4) Windings :

(2) New Standard IEEE P (3) Core : (4) Windings : (d) Electrical characteristics (such as short-circuit withstand, commutating reactance, more number of windings, etc); (e) Longer life expectancy; (f) Energy efficiency; (g) more demanding environment.

More information

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services edarat group INTRODUCTION Harmonics are a mathematical way of describing distortion

More information

Digital Fault Recorder Deployment at HVDC Converter Stations

Digital Fault Recorder Deployment at HVDC Converter Stations Digital Fault Recorder Deployment at HVDC Converter Stations On line continuous monitoring at HVDC Converter Stations is an important asset in determining overall system performance and an essential diagnostic

More information

Do Capacitor Switching Transients Still Cause Problems?

Do Capacitor Switching Transients Still Cause Problems? Do Capacitor Switching Transients Still Cause Problems? Mark McGranaghan We have been evaluating problems related to capacitor switching transients for many years. Capacitor banks have been used on distribution

More information

2 Grounding of power supply system neutral

2 Grounding of power supply system neutral 2 Grounding of power supply system neutral 2.1 Introduction As we had seen in the previous chapter, grounding of supply system neutral fulfills two important functions. 1. It provides a reference for the

More information

COOPERATIVE PATENT CLASSIFICATION

COOPERATIVE PATENT CLASSIFICATION CPC H H02 COOPERATIVE PATENT CLASSIFICATION ELECTRICITY (NOTE omitted) GENERATION; CONVERSION OR DISTRIBUTION OF ELECTRIC POWER H02M APPARATUS FOR CONVERSION BETWEEN AC AND AC, BETWEEN AC AND DC, OR BETWEEN

More information

Earth Fault Protection

Earth Fault Protection Earth Fault Protection Course No: E03-038 Credit: 3 PDH Velimir Lackovic, Char. Eng. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774

More information

Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter

Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter 1 Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter Nee, Staffan Norrga, Remus Teodorescu ISBN-10: 1118851560

More information

About the High-Frequency Interferences produced in Systems including PWM and AC Motors

About the High-Frequency Interferences produced in Systems including PWM and AC Motors About the High-Frequency Interferences produced in Systems including PWM and AC Motors ELEONORA DARIE Electrotechnical Department Technical University of Civil Engineering B-dul Pache Protopopescu 66,

More information

Residual Current Operated Circuit-Breakers (RCCBs)

Residual Current Operated Circuit-Breakers (RCCBs) Product Overview Residual Current Operated Circuit-Breakers (RCCBs) Residual current operated circuit-breakers Number of poles Rated current A Rated residual current ma MW Auxiliary contacts can be mounted

More information

HVDC. for beginners and beyond

HVDC. for beginners and beyond for beginners and beyond PIONEERING HVDC SINCE 1962 Our timeline 1962 1968 1989 1996 1998 2004 Stafford UK English Electric GEC GEC - Alsthom Alstom AREVA France CGEE - Alsthom USA GE Germany AEG ( German

More information

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network Preface p. iii Introduction and General Philosophies p. 1 Introduction p. 1 Classification of Relays p. 1 Analog/Digital/Numerical p. 2 Protective Relaying Systems and Their Design p. 2 Design Criteria

More information

LECTURE NOTES FUNDAMENTALS OF HVDC AND FACTS DEVICES. IV B.Tech II Sem (JNTU R15) Prepared by. Ms. B. Manogna Assistant Professor

LECTURE NOTES FUNDAMENTALS OF HVDC AND FACTS DEVICES. IV B.Tech II Sem (JNTU R15) Prepared by. Ms. B. Manogna Assistant Professor LECTURE NOTES ON FUNDAMENTALS OF HVDC AND FACTS DEVICES IV B.Tech II Sem (JNTU R15) Prepared by Ms. B. Manogna Assistant Professor ELECTRICAL AND ELECTRONICS ENGINEERING INSTITUTE OF AERONAUTICAL ENGINEERING

More information

2. Current interruption transients

2. Current interruption transients 1 2. Current interruption transients For circuit breakers or other switching facilities, transient voltages just after the current interruptions are of great concern with successful current breakings,

More information

Fatima Michael college of Engineering and Technology

Fatima Michael college of Engineering and Technology Fatima Michael college of Engineering and Technology DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE2303 TRANSMISSION AND DISTRIBUTION SEM: V Question bank UNIT I INTRODUCTION 1. What is the electric

More information

Coil Products Beginnings 1960 State of the Art. Customer partnership around the globe. Continuous innovation since 1900

Coil Products Beginnings 1960 State of the Art. Customer partnership around the globe. Continuous innovation since 1900 Coil Products Coil Products Customer partnership around the globe More than 250,000 coil products delivered to more than 170 countries. More than 60 years of operational experience. 35,000 in Europe 13,000

More information

Harmonic Filters and Reactors

Harmonic Filters and Reactors Harmonic Filters and Reactors Harmonics are invisible but costly If one looks up the meaning of harmonics in any one of several technical dictionaries, it is normally defined as being A sinusoidal component

More information

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY 9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor

More information

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre. General PQ: Power Quality has multiple issues involved. Thus, need to have some benchmarking standards. Very little is spoken about the LT supply installation within an industry. There is need to understand

More information

BHARATHIDASAN ENGINEERING COLLEGE, NATTRAMPALLI DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING UNIT I

BHARATHIDASAN ENGINEERING COLLEGE, NATTRAMPALLI DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING UNIT I BHARATHIDASAN ENGINEERING COLLEGE, NATTRAMPALLI DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING FAQ-EE6010 HIGH VOLTAGE DC TRANSMISSION UNIT I Part -A 1. List out two merits of AC and DC transmission

More information

p. 1 p. 6 p. 22 p. 46 p. 58

p. 1 p. 6 p. 22 p. 46 p. 58 Comparing power factor and displacement power factor corrections based on IEEE Std. 18-2002 Harmonic problems produced from the use of adjustable speed drives in industrial plants : case study Theory for

More information

Bipole III Transmission Project

Bipole III Transmission Project Bipole III Transmission Project Clean Environment Commission Public Hearings Fall 2012 System Planning Ronald Mazur BP III Keewantinoow Limestone Kettle Kelsey Jenpeg Grand Rapids OVERVIEW Transmission

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements Division 502 Technical Applicability 1(1) Section 502.1 applies to: Expedited Filing Draft August 22, 2017 the legal owner of an aggregated generating facility directly connected to the transmission system

More information

Power Factor. Power Factor Correction.

Power Factor. Power Factor Correction. Power Factor. Power factor is the ratio between the KW and the KVA drawn by an electrical load where the KW is the actual load power and the KVA is the apparent load power. It is a measure of how effectively

More information

)454 / 03/0(/-%4%2 &/2 53% /. 4%,%0(/.%490% #)2#5)43 30%#)&)#!4)/.3 &/2 -%!352).' %15)0-%.4 %15)0-%.4 &/2 4(% -%!352%-%.4 /&!.!,/'5% 0!2!

)454 / 03/0(/-%4%2 &/2 53% /. 4%,%0(/.%490% #)2#5)43 30%#)&)#!4)/.3 &/2 -%!352).' %15)0-%.4 %15)0-%.4 &/2 4(% -%!352%-%.4 /&!.!,/'5% 0!2! INTERNATIONAL TELECOMMUNICATION UNION )454 / TELECOMMUNICATION (10/94) STANDARDIZATION SECTOR OF ITU 30%#)&)#!4)/.3 &/2 -%!352).' %15)0-%.4 %15)0-%.4 &/2 4(% -%!352%-%.4 /&!.!,/'5% 0!2!-%4%23 03/0(/-%4%2

More information

Caution - leakage currents! Leakage currents in fault-current protected environments

Caution - leakage currents! Leakage currents in fault-current protected environments Caution - leakage currents! Leakage currents in fault-current protected environments Herbert Blum Product Manager EMC > General situation > Leakage current vs. fault current > Leakage currents from frequency

More information

Introduction to HVDC Transmission. High Voltage Direct Current (HVDC) Transmission

Introduction to HVDC Transmission. High Voltage Direct Current (HVDC) Transmission Lecture 29 Introduction to HVDC Transmission Series Compensation 1 Fall 2003 High Voltage Direct Current (HVDC) Transmission Update to Edison s Vision AC Power Generation at Relatively Lower Voltage» Step

More information

ELECTRICAL POWER ENGINEERING

ELECTRICAL POWER ENGINEERING Introduction This trainer has been designed to provide students with a fully comprehensive knowledge in Electrical Power Engineering systems. The trainer is composed of a set of modules for the simulation

More information

High Voltage Direct Current Transmission Proven Technology for Power Exchange

High Voltage Direct Current Transmission Proven Technology for Power Exchange High Voltage Direct Current Transmission Proven Technology for Power Exchange 2 Contents Chapter Theme Page Contents 3 1 Why High Voltage Direct Current? 4 2 Main Types of HVDC Schemes 6 3 Converter Theory

More information

OVERVIEW OF SVC AND STATCOM FOR INSTANTANEOUS POWER CONTROL AND POWER FACTOR IMPROVEMENT

OVERVIEW OF SVC AND STATCOM FOR INSTANTANEOUS POWER CONTROL AND POWER FACTOR IMPROVEMENT OVERVIEW OF SVC AND STATCOM FOR INSTANTANEOUS POWER CONTROL AND POWER FACTOR IMPROVEMENT Harshkumar Sharma 1, Gajendra Patel 2 1 PG Scholar, Electrical Department, SPCE, Visnagar, Gujarat, India 2 Assistant

More information

Low Voltage High Current Controlled Rectifier with IGBT A.C Controller on Primary Side of the Transformer

Low Voltage High Current Controlled Rectifier with IGBT A.C Controller on Primary Side of the Transformer AU J.T. 6(4):193-198 (Apr. 2003) ow Voltage High Current Controlled Rectifier with IGBT A.C Controller on Primary Side of the Transformer Seshanna Panthala Faculty of Engineering, Assumption University

More information

Voltage and Current Waveforms Enhancement using Harmonic Filters

Voltage and Current Waveforms Enhancement using Harmonic Filters Voltage and Current Waveforms Enhancement using Harmonic Filters Rajeb Ibsaim rabsaim@yahoo.com, Azzawia University, Libya Amer Daeri ibnjubair1@yahoo.co.uk Azzawia University, Libya Abstract The demand

More information

This is a preview - click here to buy the full publication. Performance of high-voltage direct current (HVDC) systems with linecommutated

This is a preview - click here to buy the full publication. Performance of high-voltage direct current (HVDC) systems with linecommutated TECHNICAL REPORT IEC/TR 60919-1 Edition 3.1 2013-04 colour inside Performance of high-voltage direct current (HVDC) systems with linecommutated converters Part 1: Steady-state conditions INTERNATIONAL

More information

New Pulse Multiplication Technique Based on Six-Pulse Thyristor Converters for High-Power Applications

New Pulse Multiplication Technique Based on Six-Pulse Thyristor Converters for High-Power Applications IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 38, NO. 1, JANUARY/FEBRUARY 2002 131 New Pulse Multiplication Technique Based on Six-Pulse Thyristor Converters for High-Power Applications Sewan Choi,

More information

22.0 Harmonics in Industrial Power Systems

22.0 Harmonics in Industrial Power Systems 1.0 Harmonics in Industrial Power Systems Harmonic frequencies are multiples of the line (fundamental) frequency, which in North America is usually 60 Hz, while it is 50 Hz elsewhere. Figure 1 shows a

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary circuit and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary circuit and the secondary circuit. Current Transducer CTSR 0.6-TP/SP2 I PRN = 600 ma For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary circuit and the secondary circuit. Features

More information

High Voltage DC Transmission Prof. Dr. S. N. Singh Department of Electrical Engineering Indian Institute of Technology Kanpur

High Voltage DC Transmission Prof. Dr. S. N. Singh Department of Electrical Engineering Indian Institute of Technology Kanpur High Voltage DC Transmission Prof. Dr. S. N. Singh Department of Electrical Engineering Indian Institute of Technology Kanpur Module No. # 01 Lecture No. # 03 So, in last two lectures, we saw the advantage

More information

Index. b back-flashover 245 biomass 207 breakers 74 buchholz protection 235 busbar sectionalizer 193 business enterprises 18

Index. b back-flashover 245 biomass 207 breakers 74 buchholz protection 235 busbar sectionalizer 193 business enterprises 18 331 Index a activity plan 318 agricultural enterprise 21 annual increase factor 12 annuity factor 44, 156 annuity method 38 ANSI code numbers 237 arrester, protection level 245 assessment of losses 38

More information

Control Strategies and Inverter Topologies for Stabilization of DC Grids in Embedded Systems

Control Strategies and Inverter Topologies for Stabilization of DC Grids in Embedded Systems Control Strategies and Inverter Topologies for Stabilization of DC Grids in Embedded Systems Nicolas Patin, The Dung Nguyen, Guy Friedrich June 1, 9 Keywords PWM strategies, Converter topologies, Embedded

More information

ELECTRICAL POWER TRANSMISSION TRAINER

ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER This training system has been designed to provide the students with a fully comprehensive knowledge in Electrical Power Engineering

More information

Utility System Lightning Protection

Utility System Lightning Protection Utility System Lightning Protection Many power quality problems stem from lightning. Not only can the high-voltage impulses damage load equipment, but the temporary fault that follows a lightning strike

More information

Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment

Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment Christian Suttner*, Stefan Tenbohlen Institute of Power Transmission and High Voltage Technology (IEH), University of

More information

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. This document may be subject to changes. Contact ARTECHE to confirm the characteristics and availability of the products

More information

Chapter 11. Alternating Current

Chapter 11. Alternating Current Unit-2 ECE131 BEEE Chapter 11 Alternating Current Objectives After completing this chapter, you will be able to: Describe how an AC voltage is produced with an AC generator (alternator) Define alternation,

More information

Power Quality Analysis in Power System with Non Linear Load

Power Quality Analysis in Power System with Non Linear Load International Journal of Electrical Engineering. ISSN 0974-2158 Volume 10, Number 1 (2017), pp. 33-45 International Research Publication House http://www.irphouse.com Power Quality Analysis in Power System

More information

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING YEAR / SEM : IV / VII UNIT I OVER VOLTAGES IN ELECTRICAL POWER SYSTEMS 1. What

More information

ABB Power Systems AB Sweden

ABB Power Systems AB Sweden Ingvar Hagman Tomas Jonsson ABB Power Systems AB Sweden This paper presents the first high power verification of ABB s Capacitor Commutated Converter (CCC) concept. The high power tests were performed

More information

Power Quality Requirements for Connection to the Transmission System

Power Quality Requirements for Connection to the Transmission System Power Quality Requirements for Connection to the Transmission System Revision: 1.0 Date: September 2015 Introduction and Purpose of this Document The purpose of this document is to provide clarity to Customers

More information

Optimum dimensioning of a flicker compensator in three-phase electric-arc furnaces supply systems

Optimum dimensioning of a flicker compensator in three-phase electric-arc furnaces supply systems Optimum dimensioning of a flicker compensator in three-phase electric-arc furnaces supply systems Abstract Three-phase electric arc furnaces, the design power ratings of which are in many cases above 100

More information

East-South HVDC Interconnector II, India : in commercial operation since 2003

East-South HVDC Interconnector II, India : in commercial operation since 2003 8006/0 5 HVDC / FACTS Highlights http://www.siemens.com/facts http://www.siemens.com/hvdc NEW! >>> Welcome to Siemens Highlights & Innovations in Transmission and Distribution East-South HVDC Interconnector

More information

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 07, 2014 ISSN (online):

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 07, 2014 ISSN (online): IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 07, 2014 ISSN (online): 2321-0613 Control and Analysis of VSC based High Voltage DC Transmission Tripti Shahi 1 K.P.Singh

More information

Electrical Theory. Power Principles and Phase Angle. PJM State & Member Training Dept. PJM /22/2018

Electrical Theory. Power Principles and Phase Angle. PJM State & Member Training Dept. PJM /22/2018 Electrical Theory Power Principles and Phase Angle PJM State & Member Training Dept. PJM 2018 Objectives At the end of this presentation the learner will be able to: Identify the characteristics of Sine

More information

LIMITS FOR TEMPORARY OVERVOLTAGES IN ENGLAND AND WALES NETWORK

LIMITS FOR TEMPORARY OVERVOLTAGES IN ENGLAND AND WALES NETWORK LIMITS FOR TEMPORARY OEROLTAGES IN ENGLAND AND WALES NETWORK This document is for internal and contract specific use only. Disclaimer NGG and NGET or their agents, servants or contractors do not accept

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements Applicability 1(1) Section 502.1 applies to the ISO, and subject to the provisions of subsections 1(2), (3) and (4) to any: (a) a new wind aggregated generating facility to be connected to the transmission

More information

Literature Review for Shunt Active Power Filters

Literature Review for Shunt Active Power Filters Chapter 2 Literature Review for Shunt Active Power Filters In this chapter, the in depth and extensive literature review of all the aspects related to current error space phasor based hysteresis controller

More information

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E.

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E. Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E. HP Critical Facility Services delivered by EYP MCF What is VOLTAGE? Difference of Electric Potential

More information

Lecture 19 - Single-phase square-wave inverter

Lecture 19 - Single-phase square-wave inverter Lecture 19 - Single-phase square-wave inverter 1. Introduction Inverter circuits supply AC voltage or current to a load from a DC supply. A DC source, often obtained from an AC-DC rectifier, is converted

More information

Harmonic control devices

Harmonic control devices ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 24 1 Today Harmonic control devices In-line reactors (chokes)

More information

Zambezi (previously Caprivi) Link HVDC Interconnector: Review of Operational Performance in the First Five Years

Zambezi (previously Caprivi) Link HVDC Interconnector: Review of Operational Performance in the First Five Years 21, rue d Artois, F-758 PARIS B4-18 CIGRE 216 http : //www.cigre.org Zambezi (previously Caprivi) Link HVDC Interconnector: Review of Operational Performance in the First Five Years T G MAGG, Power System

More information

High voltage engineering

High voltage engineering High voltage engineering Overvoltages power frequency switching surges lightning surges Overvoltage protection earth wires spark gaps surge arresters Insulation coordination Overvoltages power frequency

More information

ANALYSIS OF EFFECTS OF VECTOR CONTROL ON TOTAL CURRENT HARMONIC DISTORTION OF ADJUSTABLE SPEED AC DRIVE

ANALYSIS OF EFFECTS OF VECTOR CONTROL ON TOTAL CURRENT HARMONIC DISTORTION OF ADJUSTABLE SPEED AC DRIVE ANALYSIS OF EFFECTS OF VECTOR CONTROL ON TOTAL CURRENT HARMONIC DISTORTION OF ADJUSTABLE SPEED AC DRIVE KARTIK TAMVADA Department of E.E.E, V.S.Lakshmi Engineering College for Women, Kakinada, Andhra Pradesh,

More information

ABSTRACT. The high voltage direct current (HVDC) converter is a nonlinear load that injects

ABSTRACT. The high voltage direct current (HVDC) converter is a nonlinear load that injects ABSTRACT GUJARATI, AKASH MAYUR. Performance and Control of a Hybrid Active Filter Enabled Interface of a HVDC Converter Station for Weak AC Systems. (Under the direction of Dr. Subhashish Bhattacharya).

More information

Principles of HVDC Transmission

Principles of HVDC Transmission Principles of HVDC Transmission Course No: E04-036 Credit: 4 PDH Velimir Lackovic, Char. Eng. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F:

More information

CHAPTER 4 HARMONICS AND POWER FACTOR

CHAPTER 4 HARMONICS AND POWER FACTOR 4.1 Harmonics CHAPTER 4 HARMONICS AND POWER FACTOR In this research a comparative study of practical aspects of mixed use of diode and Thyristor converter technologies in Aluminium Smelters has been carried

More information

Harmonic control devices. ECE 528 Understanding Power Quality

Harmonic control devices. ECE 528 Understanding Power Quality ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 12 1 Today Harmonic control devices In-line reactors (chokes)

More information

Filter Considerations for the IBC

Filter Considerations for the IBC APPLICATION NOTE AN:202 Filter Considerations for the IBC Mike DeGaetano Application Engineering Contents Page Introduction 1 IBC Attributes 1 Input Filtering Considerations 2 Damping and Converter Bandwidth

More information

Introduction to Rectifiers and their Performance Parameters

Introduction to Rectifiers and their Performance Parameters Electrical Engineering Division Page 1 of 10 Rectification is the process of conversion of alternating input voltage to direct output voltage. Rectifier is a circuit that convert AC voltage to a DC voltage

More information

Power Supplies in Accelerators

Power Supplies in Accelerators Power Supplies in Accelerators Neil Marks, ASTeC, Cockcroft Institute, Daresbury, Warrington WA4 4AD, neil.marks@stfc.ac.uk Tel: (44) (0)1925 603191 Fax: (44) (0)1925 603192 Contents 1. Basic elements

More information

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM Anna Tjäder Chalmers University of Technology anna.tjader@chalmers.se Math Bollen Luleå University of Technology math.bollen@stri.se ABSTRACT Power

More information

Analysis of Harmonic Distortion in Non-linear Loads

Analysis of Harmonic Distortion in Non-linear Loads Analysis of Harmonic Distortion in Non-linear Loads Anne Ko Department of Electrical Power Engineering Mandalay Technological University, Mandalay, Myanmar.Phone:+95-09-2225761 anneko101082@gmail.com Wunna

More information

DRIVE FRONT END HARMONIC COMPENSATOR BASED ON ACTIVE RECTIFIER WITH LCL FILTER

DRIVE FRONT END HARMONIC COMPENSATOR BASED ON ACTIVE RECTIFIER WITH LCL FILTER DRIVE FRONT END HARMONIC COMPENSATOR BASED ON ACTIVE RECTIFIER WITH LCL FILTER P. SWEETY JOSE JOVITHA JEROME Dept. of Electrical and Electronics Engineering PSG College of Technology, Coimbatore, India.

More information

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge The University of New South Wales School of Electrical Engineering and Telecommunications High Voltage Systems ELEC9712 Appendix Partial Discharge Content Introduction Quantities measured Test circuits

More information

IMPORTANCE OF VSC IN HVDC

IMPORTANCE OF VSC IN HVDC IMPORTANCE OF VSC IN HVDC Snigdha Sharma (Electrical Department, SIT, Meerut) ABSTRACT The demand of electrical energy has been increasing day by day. To meet these high demands, reliable and stable transmission

More information

MODELLING & SIMULATION OF ACTIVE SHUNT FILTER FOR COMPENSATION OF SYSTEM HARMONICS

MODELLING & SIMULATION OF ACTIVE SHUNT FILTER FOR COMPENSATION OF SYSTEM HARMONICS JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY Journal of Electrical Engineering & Technology (JEET) (JEET) ISSN 2347-422X (Print), ISSN JEET I A E M E ISSN 2347-422X (Print) ISSN 2347-4238 (Online) Volume

More information

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company P2 Power Solutions Pvt. Ltd. An ISO 9001:2008 Company Quality Power within your Reach P2 Power Magnetics P2 Power Solutions Pvt. Ltd. P2 Power Solutions Pvt. Ltd. provides EMC and power quality solutions,

More information

CHAPTER 4 MULTI-LEVEL INVERTER BASED DVR SYSTEM

CHAPTER 4 MULTI-LEVEL INVERTER BASED DVR SYSTEM 64 CHAPTER 4 MULTI-LEVEL INVERTER BASED DVR SYSTEM 4.1 INTRODUCTION Power electronic devices contribute an important part of harmonics in all kind of applications, such as power rectifiers, thyristor converters

More information

Electromagnetic Harmonic Filters Technical Guide

Electromagnetic Harmonic Filters Technical Guide Eliminator Series Electromagnetic Harmonic Filters Technical Guide Neutral Eliminator TM (NCE TM ) Parallel connected, 3-phase, 4-wire passive electromagnetic device that diverts 3rd and other triplen

More information

Power Converters. Neil Marks. STFC ASTeC/ Cockcroft Institute/ U. of Liverpool, Daresbury Laboratory, Warrington WA4 4AD, U.K.

Power Converters. Neil Marks. STFC ASTeC/ Cockcroft Institute/ U. of Liverpool, Daresbury Laboratory, Warrington WA4 4AD, U.K. Power Converters Neil Marks STFC ASTeC/ Cockcroft Institute/ U. of Liverpool, Daresbury Laboratory, Warrington WA4 4AD, U.K. n.marks@dl.ac.uk Contents 1. Requirements. 2. Basic elements of power supplies.

More information

SECTION NEUTRALIZATION BELOW VHF NEUTRALIZATION

SECTION NEUTRALIZATION BELOW VHF NEUTRALIZATION SECTION 5 NEUTRALIZATION A completely neutralized amplifier must fulfill two conditions. The first is that the interelectrode capacitance between the input and output circuits be cancelled. The second

More information

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services Introduction The term power quality may take on any one of several definitions. The strict definition of power quality

More information

Electrical Power Systems

Electrical Power Systems Electrical Power Systems CONCEPT, THEORY AND PRACTICE SECOND EDITION SUBIR RAY Professor MVJ College of Engineering Bangalore PHI Learning Pfcte tofm Delhi-110092 2014 Preface xv Preface to the First Edition

More information

Chapter 4. Hybrid series active filter. 4.1 Introduction

Chapter 4. Hybrid series active filter. 4.1 Introduction Chapter 4 Hybrid series active filter 4.1 Introduction The lowest harmonics in the source current spectrum of a 12-pulse converter are theoretically the 11 th and the 13 th harmonics but some residual

More information

Long lasting transients in power filter circuits

Long lasting transients in power filter circuits Computer Applications in Electrical Engineering Vol. 12 2014 Long lasting transients in power filter circuits Jurij Warecki, Michał Gajdzica AGH University of Science and Technology 30-059 Kraków, Al.

More information

Electromagnetic Transient Simulation for Study on Commutation Failures in HVDC Systems

Electromagnetic Transient Simulation for Study on Commutation Failures in HVDC Systems Electromagnetic Transient Simulation for Study on Commutation Failures in HVDC Systems Xia Chengjun, Xu Yang, Shan Yuanda Abstract--In order to improve reliability of HVDC transmission system, commutation

More information

Reactive Power and AC Voltage Control of LCC HVDC System with Digitally Tunable Controllable Capacitors

Reactive Power and AC Voltage Control of LCC HVDC System with Digitally Tunable Controllable Capacitors International Journal for Modern Trends in Science and Technology Volume: 03, Issue No: 06, June 2017 ISSN: 2455-3778 http://www.ijmtst.com Reactive Power and AC Voltage Control of LCC HVDC System with

More information

Hybrid PWM switching scheme for a three level neutral point clamped inverter

Hybrid PWM switching scheme for a three level neutral point clamped inverter Hybrid PWM switching scheme for a three level neutral point clamped inverter Sarath A N, Pradeep C NSS College of Engineering, Akathethara, Palakkad. sarathisme@gmail.com, cherukadp@gmail.com Abstract-

More information