USER MANUAL Version: 1.1

Size: px
Start display at page:

Download "USER MANUAL Version: 1.1"

Transcription

1 AE-LIFT MOTOR DRIVER USER MANUAL Version: 1.1

2 Index SECTION 1-WARNINGS...1 SECTION 2-TECHNICAL SPECIFICATIONS ELECTRICAL SPECIFICATIONS MECHANICAL SPECIFICATIONS...3 SECTION 3-TECHNICAL SPECIFICATION OF AUXILIARY UNITS...4 SECTION 4-ELECTRICAL CONNECTIONS and TERMINAL LIST MOTOR DRIVER MAIN CONNECTIONS DRIVER MOTOR CONNECTIONS CONTROL OF MOTOR CONTACTORS Control of Motor Contactors by AE-Lift Control of Motor Contactors by Control Panel BRAKE COIL SWITCHING CONTROL CIRCUIT TERMINALS ENCODER TERMINALS Asynchronous Motor Synchronous (Gearless) Motor...14 SECTION 5-LCD DISPLAY and KEYPAD KEYPAD WARNING LEDS MAIN SCREEN and INFORMATION SCREENS Startup Screen Main Screen Version and Serial Number Information Screens Input-Output Screens...17 SECTION 6-DİL SEÇİMİ / LANGUAGE...18 SECTION 7-SERVICES...18 SECTION 8-PARAMETER SETTINGS SPEED PARAMETERS Speed Selection Acceleration Deceleration Stopping TIMINGS Timings on Startup Timings on Stopping CONTROL PARAMETERS General Control Parameters PID Control Open Loop Control Lift Rescue Operation Control MOTOR PARAMETERS PROGRAMMABLE INPUTS PROGRAMMABLE OUTPUTS PASSWORD CHANGE PROCESS MOTOR TUNING...42 SECTION 9-ERROR LOGS ERROR LOG ANALYZING Main Menu Screen Error Log Screen Error Detail Screen Error Detail Screen SECTION 10-COMPUTER (SERIAL PORT) and SERIAL COMMUNICATION CONNECTIONS (CANBus) COMPUTER CONNECTION (ETHERNET) SERIAL COMMUNICATION CONNECTION (CANBus)...46 ANNEX1 PARAMETER LIST...47 ANNEX2 AE-LIFT SPEED TIME DIAGRAM...50

3 AE-Lift is a lift motor driver frequency inverter. It uses space vector control, has the ability of high floor level sensitivity and high comfort. Main controller DSP calculates all required calculations so fast than any microcontrollers. Standard terminal and functions for lift operations are predefined for control inputs and outputs. Brake coil and contactors are driven directly by device, Error output, reset input and output for early door open functions are standard in AE-Lift motor driver. All terminals are pluggable and placed out of the box. No need to open device box for any connection. Some information on this manual may out of date or missing due to system evaluation. You can download the latest version of the manual from our website Aybey Elektronik

4 SECTION 1-WARNINGS Read user manual carefully before installation. Cut off power (line, UPS or battery) and wait at least 10 minutes before if you have to open device cover. Connect earth (PE) terminal before power on. Do not connect or disconnect a terminal when the device power is on. Release minimum air gap on installation. Minimum distances for up and down sides are 100 mm; minimum distances for right and left sides are 50 mm as mentioned in Figure 1.1. Otherwise there may be not enough air circulation. Do not mount device to wet, hot, cold, dusty or chemical vapor area. Do not install device the area can affect from sunlight directly. Figure 1.1 Preferred Space Distance for Installation F/ R:1 1 AE-LIFT

5 SECTION 2-TECHNICAL SPECIFICATIONS 2.1 ELECTRICAL SPECIFICATIONS AE-Lift motor driver technical specifications and maximum capacities are listed in Table 2.1. Device can be damaged if loaded more than maximum capacities or installed without proper auxiliary units. For this reason, select device model according to motor current, voltage and other specifications and select other parts in control panel according to values listed in Table 3.1. Table 2.1 Technical Specifications MODEL AEL05 AEL07 AEL11 AEL15 AEL22 Nominal Motor Power 5.5 kw (7.5 hp) 7.5 kw (10 hp) 11 kw (15 hp) 15 kw (20 hp) 22 kw (30 hp) Nominal Output Current 14 A 18 A 25 A 32 A 45 A Maximum Current Allowed Time 28 A 5 s 36 A 5 s 50 A 5 s 64 A 5 s 90 A 5 s Control Circuit Input Voltage 1-Phase 100V...240V AC 50/60 Hz +- %5 Nominal Power Input Voltage 3-Phase 340V...420V AC 50/60 Hz +- %5 Nominal Power Output Voltage Carrier Frequency 3-Phase 0V...420V AC Hz KHz Braking Resistor Minimum Power (1) 72 Ω 1200 W 60 Ω 1500 W 40 Ω 2200 W 30 Ω 3000 W Cooling 2 Fans 3 Fans 20 Ω 4400 W Weight 7 kg 7 kg 8 kg 12 kg 12 kg (1) Minimum preferred power of resistor listed in table. Use higher powered resistor than listed for long period travel applications. F/ R:1 2 AE-LIFT

6 2.2 MECHANICAL SPECIFICATIONS AE-LIFT motor driver box is shown in Figure 2.1. Dimensions are listed in Table 2.2 and box installation holes are shown in Figure 2.2. Table 2.2 Mechanical Dimensions Driver Model H W D d1 d2 AEL05 / AEL AEL AEL15 / AEL F/ R:1 3 AE-LIFT

7 SECTION 3-TECHNICAL SPECIFICATION OF AUXILIARY UNITS Technical informations about power, connection, switching and filter equipments for AE-Lift are listed in Table 3.1. Table 3.1 Technical Information about Part List for AE-LIFT Contactor Selection AEL05 AEL07 AEL11 AEL15 AEL22 Motor Contactors (K1-K2) 18 A A 32 A 40 A 50 A Line Input Contactors (MC) 18 A 18 A 25 A 32 A 50 A Aux. Power Input Contactors (KUPS) (Rescue Circuit) 9 A 9 A 12 A 18 A 25 A Circuit Breaker Selection AEL05 AEL07 AEL11 AEL15 AEL22 Power Input Supply Circuit Breaker (F3X) Input Power Circuit Breaker (F4) (Control Circuit) 20 A 25 A 32 A 40 A 63 A Battery Circuit Breaker (FBAT) 16 A 16 A 25 A 25 A 32 A UPS Circuit Breaker (FUPS) 1 A 6 A (1000 VA UPS için) 8 A (1200 VA UPS için) 10 A (1500 VA UPS için) 16 A (2000 VA UPS için) 20 A (3000 VA UPS için) 25 A (4000 VA UPS için) 32 A (5000 VA UPS için) Minimum Cable Diameters AEL05 AEL07 AEL11 AEL15 AEL22 Power Input and Motor Cables 2.5 mm 2 4 mm 2 4 mm 2 6 mm 2 10 mm 2 Braking Resistor Cables 2.5 mm mm mm mm mm 2 Control Terminal Cables 0.75 mm 2 Encoder Terminal Cables 0.35 mm 2 UPS Cables Battery Cables 0.75 mm 2 (For VA UPS) 1.5 mm 2 (For VA UPS) 2.5 mm 2 (For VA UPS) 4 mm 2 (For 5000 VA UPS) 4 mm 2 (For 7Ah Battery) / 6 mm 2 (For 12Ah Battery) F/ R:1 4 AE-LIFT

8 Rescue Function AEL05 AEL07 AEL11 AEL15 AEL22 UPS-PowerCircuit 1500 VA 2000 VA 3000 VA 4000 VA 5000 VA UPS-Control Circuit Battery-Power Circuit 5 x 7Ah 60V DC 1000 VA 5 x 12Ah 60V DC * Selection of battery, UPS and cable is made according to the parameter of Rescue Direction [C18] is set to EASY DIRECTION. ** Minimum level of battery voltage must be 60V DC when battery is using for rescue operation supplier and [C18] Rescue Direction is Command Direction. Braking Resistor AEL05 AEL07 AEL11 AEL15 AEL22 Resistor Value 72 Ω 60 Ω 40 Ω 30 Ω 20 Ω Minimum Power (1) 1200 W 1500 W 2200 W 3000 W 4400 W (1) Minimum preferred power of resistor listed in table. Use higher powered resistor than listed for long period travel applications. Line Filter (EMC) AEL05 AEL07 AEL11 AEL15 AEL22 Current Capacity 20 A 20 A 30 A 40 A 60 A F/ R:1 5 AE-LIFT

9 SECTION 4-ELECTRICAL CONNECTIONS and TERMINAL LIST 4.1 MOTOR DRIVER MAIN CONNECTIONS Figure 4.1 AE-LIFT Main Connection Diagram F/ R:1 6 AE-LIFT

10 4.2 DRIVER MOTOR CONNECTIONS Connections of motor contactor are changing according to motor type. Output terminals, contactors and motor connections of induction motor are shown in Figure 4.2; connections of gearless machine are shown in Figure 4.3. Figure 4.2 Induction / Asynchronous Motor (Geared Machine) Connections Figure 4.3 Synchronous Motor (Gearless Machine) Connections Contactor, which has 2 Open 2 Close (2NO-2NC) main contacts used to bridge motor phases over K2 contactor in gearless machine connection. F/ R:1 7 AE-LIFT

11 4.3 CONTROL OF MOTOR CONTACTORS Control of Motor Contactors by AE-Lift AE-Lift has hardware and software ability to control motor contactors directly. Control of contactor can be very accurate by contactor release and timing parameters. In Figure 4.4, control panel activates ENB input and AE-Lift motor driver controls the contactors. Due to contactor and ENB signal comes from different sources, synchronization of the control achieved by MCF (Contactor Feedback) function as defined to programmable input I1. In this application, no current transferred to motor without ENB, K1 and K2 activation. Figure 4.5 is same control with REN relay. REN relay triggers ENB input also. Both of these 2 connections can be use. Figure 4.4 Motor Contactors are Driven by AE-LIFT Figure 4.5 Motor Contactors are Driven by AE-LIFT (ENB Triggers from REN Relay) F/ R:1 8 AE-LIFT

12 4.3.2 Control of Motor Contactors by Control Panel When switching of contactors is achieved by control panel, use connections in Figure 4.6. In this application, when control panel send motion command, it activates K1 and K2 contactor coils and REN relay. Then K1, K2 and REN relay triggers ENB input. When control panel release contact to stop motion, REN relay deactivates ENB input faster than the main contactor and stop motor outputs so delay of contactor release have no risk. For this reason, REN relay is a must when contactor activation is controlled by control panel. Both of ENB input and motor driver current output are controlled by the contactor if no REN relay is used. If there is a risk when the lift in motion that has to stop motor immediately like safety circuit interruption, main contactor starts to release however auxiliary contacts may still triggering ENB input. In this scenario, main contacts of contactor and driver output may be damaged. REN relay is a must in Gearless machine connection. Type of REN relay has to meet the release time requirement that maximum 20 ms. Figure 4.6 Motor Contactors are Driven by AE-LIFT (ENB triggers from REN relay) NOTE : Supply of the contactors in Figure 4.4, 4.5 and 4.6 is shown as AC. When the supply of contactor is DC, connect a diode to contactor coils instead of RC filter. Do not connect diode to REN relay contacts. 4.4 BRAKE COIL SWITCHING Connection of brake coil is shown in Figure 4.7. Figure 4.7 Brake Coil Connection Switching DC circuit of brake coil from main contacts of motor contactors (K1-K2); switching AC circuit of brake coil from main contacts of brake contactor (KF) is advised. A varistor according to brake coil voltage has to connect parallel to brake coil as shown in Figure 4.7. F/ R:1 9 AE-LIFT

13 4.5 POWER CIRCUIT TERMINALS Terminals of power circuit are placed at the bottom side of the device. Detailed informations about terminals are listed in Table 4.1. Table 4.1 Power Circuit Terminals POWER TERMINALS FUNCTION DEFINITION L1, L2,L3 Line Inputs Connect 3-Phase line cables. U, V, W Motor Outputs Connect 3-Phase motor cables. P+, DB Braking Resistor Connect braking resistor cables. L, N Supply of Control Circuit Connect 1-Phase line ( V AC) cables. PE Earth Connect earth cable. 4.6 CONTROL CIRCUIT TERMINALS Terminals of control circuit are placed at the right side of the device. Detailed information about input terminals are listed in Table 4.2 and output terminals are listed in Table 4.3. Table 4.2 Control Circuit Input Terminals TERMINAL FUNCTION DEFINITION COM Common Common of input terminals. (0V) V1, V2,..., V6 Speeds Speed inputs ENB Enable Enable signal of the device. RST Fault Reset Reset fault message and gets device to normal mode. FW Up Direction Up direction signal RV Down Direction Down direction signal RSC Rescue Mode Rescue mode input I1 I2 I3 Programmable Input I1 Programmable Input I2 Programmable Input I3 Programmable Input 1 (Detailed information is in Section 8.5) Programmable Input 2 (Detailed information is in Section 8.5) Programmable Input 3 (Detailed information is in Section 8.5) F/ R:1 10 AE-LIFT

14 Table 4.3 Control Circuit Output Terminals TERMINAL FUNCTION DEFINITION CONTACTS MC1 - MC4 (COM - NO) BR1 - BR4 (COM - NO) ER1 ER2 - ER4 (COM - NC - NO) DB1 - DB4 (COM - NO) O11 - O14 (COM - NO) O21 - O24 (COM - NO) 4.7 ENCODER TERMINALS Asynchronous Motor Auxiliary Relay of Motor Contactor Auxiliary Relay of Brake Contactor Fault Relay Door Bridging Speed Relay Programmable Output O1 Programmable Output O2 Switching relay of motor output contactors (K1-K2). Switching relay of brake contactor (KF). Sends fault signal. Output of preopening door function. Sends signal when the driver speeds is lower than the parameter [S20] in stopping phase. Programmable Relay Output 1 (Detailed information is in Section 8.6) Programmable Relay Output 2 (Detailed information is in Section 8.6) 250V AC/10A 30V DC/10A 250V AC/10A 30V DC/10A 250V AC/10A 30V DC/10A 250V AC/3A 30V DC/3A 250V AC/3A 30V DC/3A 250V AC/3A 30V DC/3A Connections of encoder cable to the terminals have to be established in closed loop control. Terminals of encoder placed at the right side of the device. Incremental encoder connection is listed in Table 4.4. Be sure to set ppr value of the encoder to [M10] properly. Connection diagrams of mostly used encoders are shown in Figure 4.8 and connection between simulation outputs of device and control panel diagram is in Figure 4.9. Table 4.4 Incremental Encoder Terminals TERMINAL FUNCTION DEFINITION GND 0V DC Supply Common of supply voltage (0V/GND) 15V +15V DC Supply Supply voltage (HTL encoder) 5V +5V DC Supply Supply voltage (TTL enkoder) A A Phase Encoder A phase signal input A A Phase Encoder A phase signal input B B Phase Encoder B phase signal input B B Phase Encoder B phase signal input OA OB Simulation A Phase Encoder simulation output A phase Simulation B Phase Encoder simulation output B phase PE Earth Encoder earth (cable screening) screw F/ R:1 11 AE-LIFT

15 Figure 4.8 Incremental Encoder Connections Figure 4.9 Connections of Simulation Outputs Between AE-Lift and Control Panel F/ R:1 12 AE-LIFT

16 Figure 4.10 Connection Types According to Different Encoder Models! Check encoder supply voltage information before connection.! Do not connect or disconnect any terminal when the device drives motor.! Refer to supplier installation manual for other brand/model encoders. F/ R:1 13 AE-LIFT

17 4.7.2 Synchronous (Gearless) Motor Synchronous motor connection requires an additional encoder board. AE-Lift driver supports Endat, SSI, BISS and SinCos encoder types. Terminals of connection are listed in Table 4.5. Table 4.5 Absolute Encoder Terminals TERMINALS EnDat, SSI and BISS Encoder SinCos Encoder 5V GND A A B B DT DT CK CK C C D D GND OA OB PE 5V DC (UP) and (UP Sensor) Supply Voltage 0V DC (UP) and (UP Sensor) Supply Ground DATA DATA CLOCK CLOCK A A B B Common of Simulation Outputs Encoder Simulation Output A Phase Encoder Simulation Output B Phase Encoder Earth (Cable Screening) C C D D F/ R:1 14 AE-LIFT

18 SECTION 5-LCD DISPLAY and KEYPAD 2 lines 16 characters LCD display and 6 keys are located for parameter adjustment and observing. Extra 2 warning leds are placed above LCD display. 5.1 KEYPAD 5.2 WARNING LEDS Figure 5.1 Keypad Table 5.1 Warning Leds COLOR Yellow Green DFEFINITION HATA / ERROR : This led works as an indicator of error mode. DURUM / STATUS : This led works as an indicator of system run. Led run frequency of 2 Hz illustrates the system is in Standby Mode. Led run frequency of 1 Hz illustrates system drives the motor. Led is already ON or OFF means that the system is not working properly. F/ R:1 15 AE-LIFT

19 5.3 MAIN SCREEN and INFORMATION SCREENS All informations about AE-Lift are display on the LCD Startup Screen A E - L i f t v n C This screen displays on start-up. 1.08n characters illustrates the version of microcontroller. Motion counter (1672) and temperature is shown at the bottom line of LCD Main Screen Main screen has two different display screens according to motion mode Main Screen on Standby Mode E : 0 r pm 0. 0 A S T ANDB Y MOD E This screen is shown when no motion command in system. E character illustrates the measured speed from encoder and A illustrates the output current Main Screen on Travel Mode: Reference Speed S: 0rpm B:1 E: 0rpm 0.0A Status Encoder Speed Output Current Figure 5.2 Main Screen (Travel Mode) Screen turns to this mode automatically by motion command. S illustrates reference speed, B illustrates status, E illustrates encoder speed and A illustrates output current Version and Serial Number Information Screens Version screen displays by ESC button. When ESC button hold pressed until 3 sec, serial number and device power (kw) will display Version Information Screen A E - L i f t v n C This screen has version number and motion counter informations Serial Number Screen S N : kw A Y B E Y E L E K T RON i K This screen has serial number (SN) and device power (kw) informations. F/ R:1 16 AE-LIFT

20 5.3.4 Input-Output Screens Press ( ) button to display input/output screens. Display the next input/output screens by ( / ) buttons. [ ] symbols means that the input is active and [ ] symbol means that the input is passive Command Input Screen EN[ ] R S[ ] FW[ ] RV[ ] R C[ ] I 1[ ] I 2[ ] I 3[ ] Status of command inputs displays in this screen Speed Input Screen V 1[ ] V 2[ ] V 3[ ] V 4[ ] V 5[ ] V 6[ ] Status of speed inputs displays in this screen Output Screen MC[ ] B R[ ] DB[ ] E R[ ] O1[ ] 0 2[ ] Status of outputs displays in this screen Input-Output Summary Screen I : O : Summary list of inputs and outputs. Definition of digits is listed in Table 5.2. Every digit symbolizes one input/output. 0 means that the input/output is passive and 1 means that input/output is active. Table 5.2 Definition of Input-Output Screen INPUTS (I) Sequence No Status Terminal Code EN FW RV RS RC V1 V2 V3 V4 V5 V6 I1 I2 I3 OUTPUTS (O) Sequence No Status Terminal Code MC BR ER DB O1 O2 F/ R:1 17 AE-LIFT

21 SECTION 6-DİL SEÇİMİ / LANGUAGE User can set menu language as TURKISH or ENGLISH. SECTION 7-SERVICES This service is for authorized person. User can use this menu to clear error logs, reset counter and set to factory defaults that listed below. Code Command 399 Erase all error messages 356 Reset Travel Counter 161 Reset to Factory Defaults 834 Erase Permanent Error (Eg:Parameter Loss Error) F/ R:1 18 AE-LIFT

22 SECTION 8-PARAMETER SETTINGS!!! User cannot reach parameter menu while the device drives motor. Likewise the device cannot drive motor if system is in parameter menu. 8.1 SPEED PARAMETERS This section has parameters about speed adjustments. Parameter list and informations are listed in Table 8.1. Table 8.1 Speed Parameters Speed Selection CODE PARAMETER NAME SECTION S01 V1 Speed (Slow speed) Speed Selection S02 V2 Speed (Inspection speed) Speed Selection S03 V3 Speed (Middle speed) Speed Selection S04 V4 Speed (High speed) Speed Selection S05 V5 Speed (Ultra speed) Speed Selection S06 V6 Speed (Releveling speed) Speed Selection S07 VR Rescue Speed Speed Selection S08 Start Mode Speed Selection S09 Start Speed Speed Selection S10 Acceleration Acceleration S11 Acc Curve Acceleration S12 Acc Curve Acceleration S13 Deceleration Deceleration S14 Deceleration Curve Deceleration S15 Deceleration Curve Deceleration S16 Deceleration Mode Deceleration S17 Stop Speed Stopping S18 Stop Speed Reference Stopping S19 Speed Input Speed Selection S20 DB Speed Speed Selection S21 Speed Format Speed Selection Speed of lift assign by [S01]-[S07] parameters. Functions in speed input parameter are only for guidance. All speed input parameters can be use as desired speed function Speed Triggering 1) If [S19] = 0, all speed input has functionality with own speed parameter, 2) If [S19] = 1, only S1,S2 and S3 inputs have functionality with Binary Code. 3) If [S19] = 2, only S1,S2 and S3 inputs have functionality with Gray Code. F/ R:1 19 AE-LIFT

23 Speed Input Precedence Precedence of active speed inputs are detailed below. 1) Device drives motor at VR speed in rescue operation mode. 2) Device drives motor with the highest active input reference speed. When V1 and V4 inputs are active both, If V4 speed is higher than V1 speed, system accepts V4; otherwise sytems accepts V1 as reference speed. ([S19] = 0) Speed Qualification S01 V1 SPEED (CREEPING SPEED) Min: 0.01 m/s Max: 5 m/s Default: 0.07 m/s Creeping speed of motor. S02 V2 SPEED (INSPECTION SPEED) Min: 0.01 m/s Max: 5 m/s Default: 0.3 m/s Inspection mode speed of motor. S03 V3 SPEED (MIDDLE SPEED) Min: 0.01 m/s Max: 5 m/s Default: 0.5 m/s Middle speed of motor if more than one travel speed required. S04 V4 SPEED (NORMAL SPEED) Min: 0.01 m/s Max: 5 m/s Default: 1 m/s Travel speed of motor. S05 V5 SPEED (HIGH SPEED) Min: 0.01 m/s Max: 5 m/s Default: 1 m/s High speed of motor. (if required) S06 V6 SPEED (RELEVELING SPEED) Min: 0.01 m/s Max: 5 m/s Default: 0.03 m/s Releveling speed of lift. S07 VR SPEED (RESCUE SPEED) Min: 0.01 m/s Max: 0.20 m/s Default: 0.05 m/s Motor speed in rescue operation. System does not accepts any speed input and use VR speed as reference speed. S08 START MODE Min: 0 Max: 2 Default: 0 Do not change this parameter. F/ R:1 20 AE-LIFT

24 Figure 8.1 Speed-Time Diagram S09 START SPEED Min: 0 m/s Max: 0.1 m/s Default: 0 m/s Device not passes directly acceleration (ACC) mode. Firstly, device drive motor with a constant acceleration until reaches to [S09] start speed. Period of reach is assigned with [T04] parameter. Device drive with [S09] speed while [T05] period. Then system accelerates with defined acceleration values to target speed. Reach to start speed and motion on start speed is shown in Figure 8.2. If [S09] start speed defined as 0, device directly passes to acceleration mode. F/ R:1 21 AE-LIFT

25 S19 SPEED SELECTION REFERENCE Min: 0 Max: 1 Default: 0 This parameter assigns the speed input reference. Options are: [S19] 0 Parallel Reference Speed System accepts speed inputs from V1, V2, V3, V4, V5 and V6 terminals. Speed Input V1 V2 V3 V4 V5 V6 Device Target Speed V1 speed, value in parameter[s01]. V2 speed, value in parameter[s02]. V3 speed, value in parameter[s03]. V4 speed, value in parameter[s04]. V5 speed, value in parameter [S05]. V6 speed, value in parameter [S06]. System accepts speed inputs only from V1, V2 and V3 terminals in binary mode. Reference speed selection table is below. 1 Binary Terminal Inputs V3 V2 V1 Selected Reference Speed V1 speed, value in parameter [S01] V2 speed, value in parameter [S02] V3 speed, value in parameter [S03] V4 speed, value in parameter [S04] V5 speed, value in parameter [S05] V6 speed, value in parameter [S06] System accepts speed inputs only from V1, V2 and V3 terminals in gray code mode. Reference speed selection table is below. 2 Gray Terminal Inputs V3 V2 V1 Selected Reference Speed V1 speed, value in parameter [S01] V2 speed, value in parameter [S02] V3 speed, value in parameter [S03] V4 speed, value in parameter [S04] V5 speed, value in parameter [S05] V6 speed, value in parameter [S06] S20 DB (DOOR BRIDGING) SPEED Min: 0 m/s Max: 0.2 m/s Default: 0 m/s On stop mode, system sends a signal from DB output while system speed is below than this parameter value. This output is for preopening door function and has to be connected serialy to door open circuit. F/ R:1 22 AE-LIFT

26 S21 SPEED UNIT Min: 0 Max: 2 Default: 1 Speed unit of the system. All speed parameters unit is displays according to this parameter value. Options are: Acceleration [S10]-Acceleration [S21] VALUE 0 m/s 1 rpm 2 Hz When lift receives higher speed command on stopping or moves with a constant speed, system increase motion speed gradually to command speed. As seen on Figure 8.3, speed time curve is linear. Gradient of line is acceleration (ACC) value. [S10] parameter is the acceleration value of the device. In Figure 8.3, system receives a 1m/s target speed command when stopping. [S10] value is the period of passing to target speed. Lift reaches target speed in 2.5 seconds, so the acceleration value is: [S10]= SPEED / TIME = (1,0 m/s) / (2,5 sec) = 0,4 m/s 2 'dir. If [S10] increases, system reaches target speed in a short period however it causes less transition comforts. If [S10] decreases, system has more transition comfort however it increases motion periods. S10 ACCELERATION Min: 0.01 m/s 2 Max: 1 m/s 2 Default: 0.4 m/s 2 Acceleration value of the system. If value increases then system reaches to target speed in a shorter period; otherwise reaches to target speed in a longer period. F/ R:1 23 AE-LIFT

27 S12 ACCELERATION CURVE 2 Min: 0.01 m/s 3 Max: 1 m/s 3 Default: 0.33 m/s 3 Curve value at the end of acceleration. If value increases then pass to constant speed period decreases; otherwise pass to constant speed period increases Deceleration [S13]-Deceleration When lift receives lower speed command on motion, system decrease motion speed gradually to command speed. As seen on Figure 8.5, speed time curve is linear. Gradient of line is deceleration (DEC) value. [S13] parameter is the deceleration value of the device. In Figure 8.5, system receives stop command in 6 th second when move in constant speed (0.9 m/s). [S13] value is the period of passing to stop speed. Lift reaches target speed in 8 th seconds, so the deceleration value is: [S13]= SPEED DIFFERENCE / TIME DIFFERENCE = (0,9-0,0) m/s / (8,0-6,0) sec 0,9 m/s / 2,0 sec = 0,45 m/s 2. If [S13] increases, system reaches target speed in a short period however it causes less transition comforts. If [S13] decreases, system has more transition comfort however it increases motion periods. S13 DECELERATION Min: 0.01 m/s 2 Max: 1 m/s 2 Default: 0.5 m/s 2 Deceleration value of the system. If value increases then system reaches to target speed in a shorter period; otherwise reaches to target speed in a longer period. F/ R:1 24 AE-LIFT

28 S-Curve on Stopping Device decelerate with [S13] deceleration when receives speed command lower than motion speed. Passengers on car senses when the system directly passes to deceleration directly. Comfortable passes to slow speed can be only with increases on start and decreases on finish deceleration slowly named as S- Curve. As seen on Figure 8.6 in [S14] section, deceleration starts with zero and increases slowly to [S13] value. Device move with [S13] deceleration value and at the end of the deceleration ([S15] section), deceleration decreasing slowly to 0 value. [S14] value is the increasing ratio of deceleration from 0 to [S13]; [S15] value is the decreasing ratio of deceleration from [S13] to 0. Lower ratio of [S14] and [S15] means soft transition, however lower ratios increases total motion periods. S14 DECELERATION CURVE 1 Min: 0.01 m/s 3 Max: 1 m/s 3 Default: 0.42 m/s 3 Curve value at the beginning of deceleration. If value increases then pass to deceleration period decreases; otherwise pass to deceleration period increases. S15 DECELERATION CURVE 2 Min: 0.01 m/s 3 Max: 1 m/s 3 Default: 0.25 m/s 3 Curve value at the end of deceleration. If value increases then pass to constant speed period decreases; otherwise pass to constant speed period increases. S16 DECELERATION MODE Min: 0 Max: 1 Default: 0 Do not change this parameter Stopping System passes to stop mode when system speed is below than [S17] stop speed as shown in Figure 8.7. However reference speed has to be selected from [S18] parameter. Real speed represents encoder speed and setpoint represents device drive speed. Real speed may differs from setpoint value speed. F/ R:1 25 AE-LIFT

29 S17 STOP SPEED Min: 0.0 m/s Max: 0.02 m/s Default: m/s System accepts stop command when the system speed is below than [S17] parameter value. Be sure that stop reference speed parameter [S18] is set properly. S18 STOP SPEED REFERENCE Min: 1 Max: 2 Default: 1 Reference speed of the stop speed [S17]. Options are: [S18] VALUE DEFINITION 1 REAL SPEED Reference speed is the encoder speed of motor. Preferred in closed loop. 2 DRIVE SPEED Reference speed is the setpoint value of drive speed. May differs from real speed. F/ R:1 26 AE-LIFT

30 8.2 TIMINGS This section parameters contains the all timing parameters of the system. Timings are so important for comfortable drive and stopping processes. All informations about parameters are listed in Table 8.2. CODE PARAMETER Table 8.2 Timing Parameters SECTION T01 CONTACTOR WAIT PERIOD Timings on Startup T02 BRAKE WAIT PERIOD Timings on Startup T03 HOLD PERIOD on STARTUP Timings on Startup T04 START SPEED RAMP PERIOD Timings on Startup T05 START SPEED PERIOD Timings on Startup T06 BRAKE RELEASE PERIOD Timings on Stopping T07 DC BRAKE PERIOD Timings on Stopping T08 CONTACTOR RELEASE PERIOD Timings on Stopping Timings on Startup Figure 8.8 Timings on Startup Adjustable timing parameters at startup are listed in Table 8.8 and triggering points are signed with (>). When device receives motion command, it activates main contactors over MC output. System waits during [T01] period for eliminating contactor mechanical delay and starts zero speed process to hold motor stationary. After [T02] period, driver activates BR contactor and wait during [T03] period to start motion. If Start Speed [S09] is defined (not 0), device rise up the [S09] until [T04] period and waits at [S09] speed during [T05] period. After [T05] period, system accelerates with the acceleration values of system. T01 CONTACTOR WAIT PERIOD Min: 0.1 s Max: 5 s Default: 0.1 s When driver receives motion command, system activates main contactor over MC output firstly. Systems waits until [T01] period to overcome failure from contactor mechanical activation delay. After [T01] period, driver starts zero speed process to hold motor stationary. T02 BRAKE WAIT PERIOD Min: 0.1 s Max: 5 s Default: 0.2 s Brake wait period triggers at the end of [T01] period. Driver activates brake coils after [T02] period. F/ R:1 27 AE-LIFT

31 T03 HOLD TIME on STARTUP Min: 0.1 s Max: 5 s Default: 0.3 s Driver does not starts to rotate motor when mechanical brake releases. Slip may happen due to weight difference on brake releasing. To overcome slip on startup, driver holds motor during zero speed period between end of [T01] period to end of [T03] period. Acceleration starts after this period. T04 START SPEED RAMP Min: 0.1 s Max: 5 s Default: 0.4 s Motor hold process finished at the end of [T03] period and motion starts. Reference speed rise to [S09] speed until this parameter period. If [T04] increase, acceleration of start speed will decrease; if decrease, acceleration of start speed will increase. [T04] parameter is disabled if [S09] parameter is set to 0. T05 START SPEED WAIT PERIOD Min: 0.1 s Max: 5 s Default: 0.3 s This parameter assigns the period of reference speed waits at [S09] speed. At the end of this period, system accelerates with the acceleration parameter. [T05] parameter is disabled if [S09] parameter is set to Timings on Stopping Figure 8.9 Timings on Stopping Stopping phase starts when the motor speed is below [S17] parameter. Motor hold command triggers at that point. After [T06] period, driver release brake contactor over BR output. [T07] triggers with the end of [T06] period and drivers terminate motor outputs. After [T08] period, driver release main contactors over MC output and pass no WAIT MODE. T06 BRAKE RELEASE DELAY Min: 0.1 s Max: 5 s Default: 0.2 s Stopping phase triggers [T06] period and at the end of the period, driver release brake contactor over BR output. T07 DC BRAKE PERIOD Min: 0.1 s Max: 5 s Default: 0.3 s Driver has to hold motor until releasing of brake contactors. [T06] triggers [T07] period and motor hold process is active until this period. T08 CONTACTOR RELEASE DELAY Min: 0.1 s Max: 5 s Default: 0.1 s End of [T07] triggers [T08] period and at the end of the period, driver releases main contactors over MC output and motion process finishes. F/ R:1 28 AE-LIFT

32 8.3 CONTROL PARAMETERS Control parameter includes other than speed, timing and motor specification process parameters. CODE PARAMETER C01 Drive Type C02 Encoder Filter C03 Zero Speed Kp C04 Zero Speed Kd C05 Start Speed Kp C06 Start Speed Ti C07 Low Speed Kp C08 Low Speed Ti C09 High Speed Kp C10 High Speed Ti C11 PI Low Limit C12 PI High Limit C13 Carrier Frequency C14 DC Brake Level C15 Reserved - C16 V/f Boost Frequency C17 V/f Boost Voltage C18 Rescue Direction C19 Rescue Voltage C20 Field Weakening C21 Current Torque Kp C22 Current Torque Ti General Control Parameters Table 8.3 Control Parameters SECTION General Control Parameters General Control Parameters PID Control PID Control PID Control PID Control PID Control PID Control PID Control PID Control PID Control PID Control General Control Parameters Open Loop Control Open Loop Control Open Loop Control Rescue Operation Control Rescue Operation Control General Control Parameters PID Control PID Control C01 DRIVE TYPE Min: 1 Max: 2 Default: 1 Motor drive tpe parameter. [C01] VALUE 1 CLOSED KOOP 2 OPEN LOOP DEFINITION Encoder is used for feedback of motor rotation speed and direction. Floor level sensitivity and travel comfort are at high level. Check Section 4.7 for encoder connection. [C01] automatically set to 1 if [M01] is SYNCHRONOUS. No feedback from encoder. Floor level sensitivity may change according to load on lift. F/ R:1 29 AE-LIFT

33 C02 ENCODER FILTER Min: 1 Max: 5 Default: 3 Filter of encoder signals. If value is too low then drive gets sharper and system reaction gets faster; if value is too high then drive gets softer but reaction gets slower. Set lower than 3 if ppr value of encoder is less than 500. [C02] VALUE 1 1 ms 2 2 ms 3 4 ms 4 8 ms 5 16 ms C13 CARRIER FREQUENCY Min: 1 Max: 6 Default: 2 Carrier frequency of the driving process. Carrier frequency means that all calculation and measuring processes are achieved by frequency value times in 1 second. Preferred value is 8 Khz. [C13] VALUE 1 6 khz 2 8 khz 3 10 khz 4 12 khz 5 14 khz 6 16 khz Source of motor sound is carrier frequency. User can adjust the noise of motor by [C13] parameter. Noise will be higher if value is less; lower if value is high. C20 FIELD WEAKENING Min: 0 Max: 2 Default: 0 If motor is driven by more than nominal speed, magnetizing current have to be decreased. This process named as Field Weakening. [C20] parameter assigns that field weakening is active or passive. Method 1 and Method 2 have differences on process frequencies and weakening power. [C20] DISABLED DEFINITION No field weakening. Magnetizing current will not decrease. (Motor may not reach to set speed) ENABLE 1 Field weakening is activated. (Method 1) ENABLE 2 Field weakening is activated. (Method 2) F/ R:1 30 AE-LIFT

34 8.3.2 PID Control AE-Lift is as vector controlled lift motor driver. It calculates required data carrier frequency times and assigns voltage and frequency of motor signals. Device receives motor speed via encoder of motor. If the reference speed is differs from the motor speed, device makes calculations to zero this difference. PID control is the definitions of the adjustment procedure. PID is a control loop with feedback and use in most of industrial processes. It is a pre-defined procedure of output refinement process. Figure 8.10 is a typical PID motor speed control system. e(t) is the difference between motor speed and reference speed named as error signal. e(t) signal processed from 3 different channels in parallel. These are Proportional (P), Integral (I) and Derivative (D) processes. All channels calculates correction signals with defined parameters and send refinement signal to B point. Sum of refinement signals creates output signal u(t). Main functions of processes are described in below table. F/ R:1 31 AE-LIFT

35 TERM PROCESS COEF DEFINITION P Proportional Kp Main correction process of the control loop. I Integral Ki Sum of past errors correction process. Improves the accuracy level. D Derivative Kd Correction process of error transitions. Improves the dynamic correction ability Zero Speed PD Control Zero speed process is used to overcome slip when mechanical brake open on start-up. PD coefficients use in zero speed control. [C03] and [C04] parameters are coefficients of PD control on zero speed control. C03 ZERO SPEED Kp Min: 1 Max: 200 Default: 16 Kp coefficient in Zero speed control. C04 ZERO SPEED Kd Min: 1 Max: 200 Default: 20 Kd coefficient in zero speed control Start Speed PI Control Device only performs PI (Proportional and Integral) process on motion. Kp and Ti coefficients may differs in high and low speeds. So system has different Kp and Ti parameters for start speed, low speed and high speed. C05 START SPEED Kp Min: 0.1 Max: 100 Default: 24 Kp coefficient on PID process when reference speed is lower than Start Speed [S09] parameter. C06 START SPEED Ti Min: 0 ms Max: 9999 ms Default: 300 ms Ti (1/Ki) coefficient on PID process when reference speed is lower than Start Speed [S09] parameter. F/ R:1 32 AE-LIFT

36 Motion PI Control When speed reference speed is higher than start speed, then Kp and Ti parameters are selected form [C07]-[C12] parameters according to reference speed. [C07] and [C08] is used when the reference speed is lower than [C11] PI Low Speed; [C09] and [C10] is used when the reference speed is higher than [C12] PI High Speed. Between C11 and C12 reference speed, Kp and Ti parameters are changes linearly. C07 LOW SPEED Kp Min: 0.1 Max: 100 Default: 24 Kp coefficient when the system speed is lower than [C11] parameter. C08 LOW SPEED Ti Min: 0 ms Max: 9999 ms Default: 300 ms Ti coefficient when the system speed is lower than [C11] parameter. C09 HIGH SPEED Kp Min: 0.1 Max: 100 Default: 24 Kp coefficient when the system speed is higher than [C12] parameter. C10 HIGH SPPED Ti Min: 0 ms Max: 9999 ms Default: 300 ms Ti coefficient when the system speed is higher than [C12] parameter. C11 PI LOW SPEED Min: 0 m/s Max: 5 m/s Default: 0.3 m/s When system speed is between value in [C11] and [C12] parameters, Kp and Ti coefficients are selected according to system speed shown in Figure When system speed is below [C11], system use [C07] and [C08] coefficient parameters. C12 PI HIGH SPEED Min: 0 m/s Max: 5 m/s Default: 0.6 m/s When system speed is between [C11] and [C12] parameters value, Kp and Ti coefficients are selected according to system speed shown in Figure When system speed is above [C12], system use [C09] and [C10] coefficient parameters. C21 CURRENT-TORQUE Kp Min: 0.1 Max: 10 Default: 1 Kp coefficient of the system current and torque control components. C22 CURRENT-TORQUE Ti Min: 10 ms Max: 9999 ms Default: 100 ms Ti coefficient of the system current and torque control components. F/ R:1 33 AE-LIFT

37 8.3.3 Open Loop Control AE-Lift is designed for lift operation operate with space vector control algorithm. Vector control requires a feedback from motion. This system is more effective method for lift operations. However due to mechanical obstacles, encoder cannot mount to motor. Feedback of motor cannot receives in this system named as open loop control. Due to feedback loss, stopping sensitivity can changes according to load on system. Use this system below 1m/s and low load capacity lift operations. Open loop control use voltage/frequency (V/f) curve. As seen on Figure 8.12, all frequencies have different voltage values. Increase on frequency increases drive voltage. However on low frequencies, system cannot drive a motor because of the low voltage values. Adjust low frequency settings by [C16] and [C17] parameters shown in Figure C14 DC BRAKE LEVEL (Percentage) Min: 0 Max: 100 Default: 10 [C14] parameter defines the DC brake level on startup and stopping. Rotor stabled with DC brake before mechanical brake releasing on startup and after mechanical brake activating on stopping. Level of this parameter is directly proportional to electrical brake power. DC brake is a DC load on motor coils and may warm up motor. If value is lower than required, motor may move out of control. C15 RESERVED Min: 0 Max: 1 Default: 0 Has no functionality. C16 V/f LOW SPEED Min: 0.01 m/s Max: 5 m/s Default: 0.1 m/s In V/f mode due to the static load, system cannot startup with linear curve. Instead of this, device drives motor with a constant voltage below a frequency point. [C16] parameter is the start point of V/f curve. C17 V/f LOW SPEED VOLTAGE Min: 0 Max: 1 Default: 0.1 Minimum voltage level when the system speed is below [C16]-V/f Low Speed on acceleration and decelaration. [C17] parameter affects directly stopping and startup power. If value is more than nominal, motor may vibrates; otherwise device can not drives smoothly on low speeds. F/ R:1 34 AE-LIFT

38 8.3.4 Lift Rescue Operation Control AE-Lift motor driver has the ability of rescue operation with battery or UPS when a failure occurs on line. Main connection diagrams are in Figure 8.15 and When a failure occurs on line, control panel detects it and stops motion immediately. Device can powered with UPS or battery and operate with speed [S07]=Rescue Speed/VR. AE-Lift motor driver rescue mode activated by: 1- Control circuit supply (L-N terminals) must be supplied by V AC. 2- RSC input must be activated. 3- Device rescue mode power supply is assigned by [C19] parameter. 4- [C18] parameter is advised to set EASY DIRECTION ([C18] = 1). By this way rescue operation established with minimum power.t1 : 5 sn (min) is recommended. t2 : 2 sn (min) is recommended. Figure 8.14 Timings on Rescue Mode F/ R:1 35 AE-LIFT

39 Figure 8.15 Battery Powered Rescue Circuit Diagram Figure 8.16 UPS Powered Rescue Circuit Diagram F/ R:1 36 AE-LIFT

40 C18 RESCUE DIRECTION SELECTION Min: 0 Max: 1 Default: 1 This parameter defines the selection of motion direction when the device is in rescue mode. [C18] SELECTION DEFINITION 0 1 COMMAND DIRECTION EASY DIRECTION Control panel selects rescue motion direction. Rescue operation power supply must be at least 110V and the power is at least half power of the motor. Device selects rescue motion direction. Device test both directions and calculates motor currents and decide rescue direction. Rescue operation power supply information is given in Table 3.1. C19 RESCUE VOLTAGE Min: 0 Max: 5 Default: 0 Rescue operation power supply voltage information. Values are: [C19] VOLTAGE 0 220V AC 1 380V AC 2 110V AC 3 60V DC 4 48V DC F/ R:1 37 AE-LIFT

41 8.4 MOTOR PARAMETERS This section has parameters about motor and encoder specifications. Some of the parameters have to set by the user before tuning process and some of the parameters set automatically by tuning process. CODE PARAMETER M01 Motor Type M02 Motor Speed M03 Motor RPM Value M04 Motor Frequency M05 Motor Current M06 Motor Voltage M07 Motor Cos Value M08 Motor Poles Table 8.4 Motor Parameters SOURCE M09 Motor Noload Current Set by user Set from motor label value Set from motor label value Set from motor label value Set from motor label value Set from motor label value Set from motor label value Set from motor label value Set from motor label value M10 Encoder Pulse Count Set from encoder label value M11 Motor Rs M12 Motor Ls M13 Motor Rr M14 Motor Lm M15 Motor Tr Automatically set by tuning process Automatically set by tuning process Automatically set by tuning process Automatically set by tuning process Automatically set by tuning process M16 Motor Cable Sequence Change if required M17 Encoder Direction M18 Encoder Type M19 Encoder Offset Change if required Set by user Automatically set by tuning process M01 MOTOR TYPE Min: 1 Max: 2 Default: 1 This parameter assignes the motor type. [M01] 1 2 SELECTION ASYNCHRONOUS MOTOR SYNCHRONOUS MOTOR M02 MOTOR SPEED Min: 0.1 m/s Max: 5 m/s Default: 1 m/s Nominal speed of motor. Get this information from motor label or contact with motor supplier. F/ R:1 38 AE-LIFT

42 M03 MOTOR RPM VALUE Min: 100 Max: 3000 Default: 1500 Rpm value of motor. Get this information from motor label or contact with motor supplier. M04 MOTOR FREQUENCY Min: 5 Hz Max: 100Hz Default: 50 Hz Nominal frequency of motor. Get this information from motor label or contact with motor supplier. M05 MOTOR CURRENT Min: 1 A Max: 45 A Default: 10 A Nominal current of motor. Get this information from motor label or contact with motor supplier. M06 MOTOR VOLTAGE Min: 100 V Max: 500 V Default: 380 V Nominal voltage of motor. Get this information from motor label or contact with motor supplier. M07 MOTOR COS VALUE Min: 0.1 Max: 1.0 Default: 0.85 Cos value of motor. Get this information from motor label or contact with motor supplier. M08 MOTOR POLES Min: 2 Max: 64 Default: 4 Number of poles of motor. Get this information from motor label. If not the formula of the pole calculation is below. Number of Poles = 120 x f d Here f: frequency [Hz], d: Rpm value [rpm] Example: Determine the number of poles which frequncy (f) is 50Hz and rpm value (d) is 1500 Number of Poles = 120 x 50 = M09 MOTOR NOLOAD CURRENT (%) Min: 10 Max: 100 Default: 35 Ratio of motor noload current and motor nominal current. If the value is high, motor might use more current, otherwise if the value is low then motor startup might be noisy or can not startup. M10 ENCODER PULSE Min: 100 Max: 5000 Default: 1024 Pulse value of encoder. Get this information from encoder label or contact with encoder supplier. M11 MOTOR Rs Min: 0.1 Ohm Max: 10 Ohm Default: 0.7 Ohm Resistor value of stator. Automatically set by tuning process. M12 MOTOR Ls Min: 10 mh Max: 3000 mh Default: 100 mh Inductance value of stator. Automatically set by tuning process. M13 MOTOR Rr Min: 0.1 Ohm Max: 10 Ohm Default: 0.9 Ohm Resistor value of rotor. Automatically set by tuning process. F/ R:1 39 AE-LIFT

43 M14 MOTOR Lm Min: 10 mh Max: 3000 mh Default: 110 mh Mutual inductance value of motor. Automatically set by tuning process. M15 MOTOR Tr Min: 10 ms Max: 3000 ms Default: 85 ms Rotor time constant of motor. Automatically set by tuning process. M16 COMMAND DIRECTION Min: 1 Max: 2 Default: 1 This parameter changes the direction of FWD and REV commands. [M16] COMMAND DIRECTION 1 FWD->UP 2 FWD->DOWN M17 ENCODER DIRECTION Min: 1 Max: 2 Default: 1 This parameter changes the precedence of encoder channels. Change this parameter only if there is a fault in zero speed section of motion. [M17] DIRECTION 1 CLOCKWISE 2 COUNTERCLOCKWISE M18 ENCODER TYPE Min: 0 Max: 4 Default: 0 Encoder type of the system. [M18] ENCODER TYPE 0 INCREMENTAL 1 ENDAT 2 SINCOS 3 SSI 4 BISS M19 ENCODER OFFSET Min: 0 Max: Default: 0 Encoder offset in synchronous motor. Automatically set by tuning process. F/ R:1 40 AE-LIFT

44 8.5 PROGRAMMABLE INPUTS AE-Lift has extra 3 programmable inputs (I1,I2,I3). Functions of inputs are listed in Table 8.5. INPUT CODE Table 8.5 Definitions of Programmable Inputs FUNCTION DEFINITION 00 No function 01 MCF 02 BRF MC CONTROL: Feedback check of motor contactors. Device not drive motor until activation of this input. If input is not activated during [T01] period, then system reports Error 16-Contactor Error. Connection diagram of contacts are drawn in Figure BRAKE CONTROL: Feedback check of mechanical brake control contacts. Device not drive motor until activation of this input. If input is not activated during [T02] period, then system reports Error 17-Brake Error. Connection diagram of contacts are drawn in Figure Figure 8.17 Brake and Contactor Feedback 8.6 PROGRAMMABLE OUTPUTS AE-Lift has extra 2 programmable outputs (O1 and O2). Informations about contacts are listed in Table 4.3 and functions are listed in Table 8.6. OUTPUT CODE FUNCTION Table 8.6 Programmable Output Codes and Definitions DEFINITION 00 No function 01 STP No motion in system 02 MTN Motion in system 03 NLA Output current is above noload current of motor 04 NLB Output current is below noload current of motor 8.7 PASSWORD CHANGE PROCESS AE-Lift has menu password protection feature. Factory default of password is which means passive. Password activated by 5 digits value between and System warns you with PASSWORD CHANGED after completion of password change process. F/ R:1 41 AE-LIFT

45 8.8 MOTOR TUNING Motor tuning is the process of motor parameter definition. No rotation of motor required in tuning process. When entering Tuning Menu, PRESS UP ARROW for TUNING PROCESS message displays on the screen. If K1 and K2 motor contactor controlled by control panel, hold activated during tuning process. By up arrow, tuning process will start and after 30 seconds, system completed process if no fault occurs. After process, release motor contactors if controlled by control panel. Set these parameters before tuning process: [M01]-Motor Type [M02]-Motor Speed [M03]-Motor RPM [M04]-Motor Frequency [M05]-Motor Current [M06]-Motor Voltage [M07]-Motor Cos Value [M08]-Motor Poles [M10]-Encoder Pulse [M18]-Encoder Type *** In synchronous motor, hold activated ENB input during tuning process. F/ R:1 42 AE-LIFT

TECO F510 Inverter. Quick Start Guide. Step 1. Supply & Motor connection

TECO F510 Inverter. Quick Start Guide. Step 1. Supply & Motor connection Quick Start Guide TECO F510 Inverter This guide is to assist you in installing and running the inverter and verify that it is functioning correctly for it s main and basic features. For detailed information

More information

CHAPTER 8 PARAMETER SUMMARY

CHAPTER 8 PARAMETER SUMMARY CHAPTER PARAMETER SUMMARY Group 0: System Parameter VFD-V Series 00-00 Identity Code Based on the model type 00-01 Rated Current Display 00-02 Parameter Reset 00-03 00-04 Star-up Display of the Drive Definitions

More information

NICE900 -Door Drive Setup Manual for Asynchronous / Synchronous Motor with Encoder Feedback (Document Release Dt ) Sr. No

NICE900 -Door Drive Setup Manual for Asynchronous / Synchronous Motor with Encoder Feedback (Document Release Dt ) Sr. No Inova Automation Pvt Ltd., NIBHI Corporate Centre, 3 rd Floor, No.7, CBI Colony, 1 st Main Link Road, Perungudi, Chennai-600096. Ph:-+91 (0)44 4380 0201 Email:- info.inovaindia@inova-automation.com Website:-

More information

ADTECH Solar inverter

ADTECH Solar inverter ADTECH Solar inverter 1. Product description Thank you very much for your selection of special solar inverter launched by ADTECH (SHENZHEN) TECHNOLOGY CO., LTD. Solar energy special inverter is designed

More information

Operating Instructions

Operating Instructions 4XH35QB151210 Small General Frequency Converter Operating Instructions 220V 0.75KW 5.5KW 400V 0.75KW 15KW Please read the instruction carefully and understand the contents so that it can be installed and

More information

D SERIES LM16. COMPACT DRIVE V/f and SLV CONTROL. LM16 COMPACT DRIVE V/f and SLV CONTROL

D SERIES LM16. COMPACT DRIVE V/f and SLV CONTROL. LM16 COMPACT DRIVE V/f and SLV CONTROL D SERIES LM16 COMPACT DRIVE V/f and SLV CONTROL LM16 COMPACT DRIVE V/f and SLV CONTROL 1 2 SERIES 1 2 page 4 page 6 Introduction Fields of application 3 page 7 4 page 8 Designation Product offer 5 6 page

More information

Jaguar Motor Controller (Stellaris Brushed DC Motor Control Module with CAN)

Jaguar Motor Controller (Stellaris Brushed DC Motor Control Module with CAN) Jaguar Motor Controller (Stellaris Brushed DC Motor Control Module with CAN) 217-3367 Ordering Information Product Number Description 217-3367 Stellaris Brushed DC Motor Control Module with CAN (217-3367)

More information

HPVFP High Performance Full Function Vector Frequency Inverter

HPVFP High Performance Full Function Vector Frequency Inverter Advanced User Manual HPVFP High Performance Full Function Vector Frequency Inverter HP VER 1.00 1. HPVFP Parameter Set Overview...3 1.1. About this section...3 1.2. Parameter Structure Overview...3 1.3.

More information

Invertek Optidrive E3 Frequency Inverter (IP20, 3ph output) Easy Start Guide

Invertek Optidrive E3 Frequency Inverter (IP20, 3ph output) Easy Start Guide Invertek Optidrive E3 Frequency Inverter (IP20, 3ph output) Easy Start Guide The Invertek Optidrive E3 Frequency Inverter range is available to order from inverterdrive.com This guide is intended to complement

More information

CHAPTER AC DRIVE PARAMETERS. In This Chapter...

CHAPTER AC DRIVE PARAMETERS. In This Chapter... CHAPTER AC DRIVE 4 PARAMETERS In This Chapter... GS2 Parameter Summary....................4 2 Detailed Parameter Listings.................4 11 Motor Parameters........................4 11 Ramp Parameters.........................4

More information

GS1 Parameter Summary Detailed Parameter Listings...4 9

GS1 Parameter Summary Detailed Parameter Listings...4 9 CHAPTER AC DRIVE 4 PARAMETERS Contents of this Chapter... GS1 Parameter Summary...............................4 2 Detailed Parameter Listings..............................4 9 Motor Parameters.........................................4

More information

MA7200 PLUS INVERTER SERIES PID Quick Start Manual For Fan and Pump Applications

MA7200 PLUS INVERTER SERIES PID Quick Start Manual For Fan and Pump Applications MA7200 PLUS INVERTER SERIES PID Quick Start Manual For Fan and Pump Applications 3 to 75 HP Models- MA7200-2003-N1 Thru MA7200-2040-N1 (230V) & MA7200-4003-N1 Thru MA7200-4075-N1 (460V) speed time Rev.

More information

STEPPING MOTOR EMULATION

STEPPING MOTOR EMULATION OPERATING MANUAL SERIES SMTBD1 OPTIONAL FUNCTIONS (Version 2.0) European version 2.0 STEPPING MOTOR EMULATION OPTION C This manual describes the option "C" of the SMT-BD1 amplifier: Stepping motor emulation.

More information

[ 4 ] Using pulse train input (F01 = 12)

[ 4 ] Using pulse train input (F01 = 12) [ 4 ] Using pulse train input (F01 = 12) Selecting the pulse train input format (d59) A pulse train in the format selected by the function code d59 can give a frequency command to the inverter. Three types

More information

Variable Frequency Drive / Inverter (0.4 ~ 280kW)

Variable Frequency Drive / Inverter (0.4 ~ 280kW) Variable Frequency Drive / Inverter (0.4 ~ 280kW) & Standard Features Configuration Comparison Comparison Table Enclosure IP00 IP20 NEMA 1 Rating Single phase 0.4 2.2kW 0.4 1.5kW Three phase 0.4 4kW Constant

More information

INDEX. i 1. B Braking Resistor Dimensions: A 24 Braking Resistors: A 20 Braking Units: A 20. DURAPULSE AC Drive User Manual

INDEX. i 1. B Braking Resistor Dimensions: A 24 Braking Resistors: A 20 Braking Units: A 20. DURAPULSE AC Drive User Manual INDEX A AC Drive Cover: 1 6 Dimensions: 2 4 External Parts and Labels: 1 6 Heat Sink Fins: 1 6 Input Mode Switch (Sink/Source): 1 6 Introduction to DuraPulse GS3 AC drive: 1 3 Keypad: 1 6 Model Number

More information

D SERIES EM16 IP 20 / NEMA 1 & IP 66 / NEMA 4X COMPACT VECTOR CONTROL DRIVE EM 16 COMPACT VECTOR CONTROL DRIVE

D SERIES EM16 IP 20 / NEMA 1 & IP 66 / NEMA 4X COMPACT VECTOR CONTROL DRIVE EM 16 COMPACT VECTOR CONTROL DRIVE D SERIES EM16 IP 20 / NEMA 1 & IP 66 / NEMA 4X COMPACT VECTOR CONTROL DRIVE EM 16 COMPACT VECTOR CONTROL DRIVE 1 2 SERIES 1 2 pag. 4 pag. 5 Applications Model identification 3 pag. 5 4 pag. 6 Capacity

More information

HV580L Series Frequency Inverter User Manual

HV580L Series Frequency Inverter User Manual User Manual HNC Electric Limited Contents Contents... 2 Chapter 1 Safety Information and Precautions... 4 1.1 Safety Information... 4 1.2 General Precautions... 7 Chapter 2 Product Information... 10 2.1

More information

L E C T U R E R, E L E C T R I C A L A N D M I C R O E L E C T R O N I C E N G I N E E R I N G

L E C T U R E R, E L E C T R I C A L A N D M I C R O E L E C T R O N I C E N G I N E E R I N G P R O F. S L A C K L E C T U R E R, E L E C T R I C A L A N D M I C R O E L E C T R O N I C E N G I N E E R I N G G B S E E E @ R I T. E D U B L D I N G 9, O F F I C E 0 9-3 1 8 9 ( 5 8 5 ) 4 7 5-5 1 0

More information

Tarocco Closed Loop Motor Controller

Tarocco Closed Loop Motor Controller Contents Safety Information... 3 Overview... 4 Features... 4 SoC for Closed Loop Control... 4 Gate Driver... 5 MOSFETs in H Bridge Configuration... 5 Device Characteristics... 6 Installation... 7 Motor

More information

NX series Constant and variable torque Variable Speed Drives for induction motors

NX series Constant and variable torque Variable Speed Drives for induction motors Honeywell All in One Application Manual NX series Constant and variable torque Variable Speed Drives for induction motors Subject to changes without notice CONTENTS NX "All in One" APPLICATION MANUAL INDEX

More information

vacon nx all in one application manual ac drives Phone: Fax: Web: -

vacon nx all in one application manual ac drives Phone: Fax: Web:  - vacon nx ac drives all in one application manual vacon 1 INDEX Document ID:DPD00903A Revision release date: 30.3.2012 1. Basic Application...5 1.1. Introduction...5 1.1.1. Motor protection functions in

More information

AC Drive Technology. An Overview for the Converting Industry. Siemens Industry, Inc All rights reserved.

AC Drive Technology. An Overview for the Converting Industry.  Siemens Industry, Inc All rights reserved. AC Drive Technology An Overview for the Converting Industry www.usa.siemens.com/converting Siemens Industry, Inc. 2016 All rights reserved. Answers for industry. AC Drive Technology Drive Systems AC Motors

More information

Multi-function, Compact Inverters. 3G3MV Series

Multi-function, Compact Inverters. 3G3MV Series Multi-function, Compact Inverters 3G3MV Series There has been a great demand for inverters with more functions and easier motor control than conventional i OMRON's powerful, compact 3G3MV Series with versat

More information

The Drive & Control Company. Frequency Converter. VFC 3610 / VFC 5610 Series. Quick Start Guide R Edition 10

The Drive & Control Company. Frequency Converter. VFC 3610 / VFC 5610 Series. Quick Start Guide R Edition 10 The Drive & Control Company Frequency Converter VFC 3610 / VFC 5610 Series Quick Start Guide R912005518 Edition 10 Bosch Rexroth AG VFC 3610 / VFC 5610 Record of Revision Edition Release Date Notes DOK-RCON04-VFC-X610***-QU01-EN-P

More information

Brushed DC Motor Control. Module with CAN (MDL-BDC24)

Brushed DC Motor Control. Module with CAN (MDL-BDC24) Stellaris Brushed DC Motor Control Module with CAN (MDL-BDC24) Ordering Information Product No. MDL-BDC24 RDK-BDC24 Description Stellaris Brushed DC Motor Control Module with CAN (MDL-BDC24) for Single-Unit

More information

HV580 Series Frequency Inverter User Manual

HV580 Series Frequency Inverter User Manual User Manual HNC Electric Limited Contents Contents...2 Chapter 1 Safety Information and Precautions...4 1.1 Safety Information... 4 1.2 General Precautions...7 Chapter 2 Product Information...10 2.1 Designation

More information

Intelligent Drive Systems, Worldwide Services SK 700E F 3070 GB

Intelligent Drive Systems, Worldwide Services SK 700E F 3070 GB Intelligent Drive Systems, Worldwide Services SK 700E Universal application Modular High-Performance Inverter NORDAC SK 700E The NORDAC SK 700E frequency inverter is designed for the power range between

More information

Absolute Encoders - Singleturn

Absolute Encoders - Singleturn The Sendix 5853 and Sendix 5873 singleturn encoders with SSI or BiSS interface and optical sensor technology can achieve a resolution of max. 7 bits. These encoders are also available with an optional

More information

MD310 Quick Start Manual. General-Purpose AC Drive

MD310 Quick Start Manual. General-Purpose AC Drive MD310 Quick Start Manual General-Purpose AC Drive ersion 0.1 Dated 14 th OCT, 2013 CONTENTS CHAPTER 1 PRODUCT INFORMATION... 1 1.1 Designation... 1 1.2 Nameplate... 1 1.3 General Specifications... 2 CHAPTER

More information

FUJI Inverter. Standard Specifications

FUJI Inverter. Standard Specifications FUJI Inverter o Standard Specifications Norminal applied motor The rated output of a general-purpose motor, stated in kw. That is used as a standard motor. Rated capacity The rating of an output capacity,

More information

TAC ATV38, IP55. Variable Speed Drives for Asynchronous Motors. 3-phase. 380/460 V, Hz

TAC ATV38, IP55. Variable Speed Drives for Asynchronous Motors. 3-phase. 380/460 V, Hz TAC ATV8, IP55 Variable Speed Drives for Asynchronous Motors. -phase. 80/460 V, 50-60 Hz E-60-24 24 May 2004 ATV 8 IP55 drives are specifically designed for pump and fan applications powered by a three-phase

More information

Sensors and Sensing Motors, Encoders and Motor Control

Sensors and Sensing Motors, Encoders and Motor Control Sensors and Sensing Motors, Encoders and Motor Control Todor Stoyanov Mobile Robotics and Olfaction Lab Center for Applied Autonomous Sensor Systems Örebro University, Sweden todor.stoyanov@oru.se 13.11.2014

More information

HITACHI. L100-M Series Inverter Quick Reference Guide. Hitachi Industrial Equipment Systems Co., Ltd. Single-phase Input 100V Class

HITACHI. L100-M Series Inverter Quick Reference Guide. Hitachi Industrial Equipment Systems Co., Ltd. Single-phase Input 100V Class HITACHI L1-M Series Inverter Quick Reference Guide Single-phase Input 1V Class Hitachi Industrial Equipment Systems Co., Ltd. Manual No. NB5741XD December 23 Caution: Be sure to read the L1 Inverter Manual

More information

30-80V, 8.2A Peak, No Tuning, Nulls loss of Synchronization

30-80V, 8.2A Peak, No Tuning, Nulls loss of Synchronization 2-phase Hybrid Servo Drive 30-80V, 8.2A Peak, No Tuning, Nulls loss of Synchronization Closed-loop, eliminates loss of synchronization Broader operating range higher torque and higher speed Reduced motor

More information

Software Operational Manual

Software Operational Manual Software Operational Manual for Easy Servo Drives ES-D508/808/1008 www.leadshine.com SM-ES-R20121030 ii Leadshine reserves the right to make changes without further notice to any products herein to improve

More information

Users Manual SM5 INVERTER. Subject to changes without notice December, 2001

Users Manual SM5 INVERTER. Subject to changes without notice December, 2001 Users Manual SM5 INVERTER Subject to changes without notice December, 2001 1 SM5 Contents 1. SAFETY... 3 1.1 Warnings...3 1.2 Safety Instructions...3 1.3 Earthing...4 1.4 Running The motor...4 2. RECEIVING...

More information

CL86T. 24~80VDC, 8.2A Peak, Closed-loop, No Tuning. Descriptions. Closed-loop. Stepper. Applications. Datasheet of the Closed-loop Stepper CL86T

CL86T. 24~80VDC, 8.2A Peak, Closed-loop, No Tuning. Descriptions. Closed-loop. Stepper. Applications. Datasheet of the Closed-loop Stepper CL86T CL86T Closed-loop Stepper 24~80VDC, 8.2A Peak, Closed-loop, No Tuning Closed-loop, eliminates loss of synchronization Broader operating range higher torque and higher speed Reduced motor heating and more

More information

Rexroth Frequency Converter Fe 0.75 kw to 7.5 kw / 400 VAC

Rexroth Frequency Converter Fe 0.75 kw to 7.5 kw / 400 VAC Electric Drives and Controls Hydraulics Linear Motion and Assembly Technologies Pneumatics Rexroth Frequency Converter Fe 0.75 kw to 7.5 kw / 400 VAC Simple, scalable and economical Service Bosch Rexroth

More information

IRT Mini Evo. Technical Manual. quality IN MOTION. quality IN MOTION

IRT Mini Evo. Technical Manual. quality IN MOTION.   quality IN MOTION IRT quality IN MOTION www.irtsa.com 2000 Mini Evo Technical Manual IRT quality IN MOTION Contents 1. INTRODUCTION 3 2. DESCRIPTION 5 3. TECHNICAL DATA 7 3.1 GENERAL DATA FOR ALL TYPES 7 3.2 SPECIFIC DATA

More information

ig5a 0.4~1.5kW (0.5~2HP) 1phase 200~230Volts 0.4~22kW (0.5~30HP) 3Phase 200~230Volts 0.4~22kW (0.5~30HP) 3Phase 380~480Volts Compact & Powerful Drive

ig5a 0.4~1.5kW (0.5~2HP) 1phase 200~230Volts 0.4~22kW (0.5~30HP) 3Phase 200~230Volts 0.4~22kW (0.5~30HP) 3Phase 380~480Volts Compact & Powerful Drive Compact & Powerful Drive iga ~1.kW (0.~2HP) 1phase 200~230Volts ~22kW (0.~30HP) 3Phase 200~230Volts ~22kW (0.~30HP) 3Phase 380~480Volts Drive Starvert iga LS Starvert iga is very competitive in its price

More information

SJ100 Series Inverter Quick Reference Guide. Single-phase Input 200V Class Three-phase Input 200V Class Three-phase Input 400V Class

SJ100 Series Inverter Quick Reference Guide. Single-phase Input 200V Class Three-phase Input 200V Class Three-phase Input 400V Class HITACHI SJ1 Series Inverter Quick Reference Guide Single-phase Input 2V Class Three-phase Input 2V Class Three-phase Input 4V Class Hitachi Industrial Equipment Systems Co., Ltd. Manual No. NB5821XD Dec.

More information

6.9 Jump frequency - Avoiding frequency resonance

6.9 Jump frequency - Avoiding frequency resonance E581595.9 Jump frequency - Avoiding frequency resonance : Jump frequency : Jumping width Function Resonance due to the natural frequency of the mechanical system can be avoided by jumping the resonant

More information

Hitachi P1 Closed Loop Hoist Basic Instruc on Manual

Hitachi P1 Closed Loop Hoist Basic Instruc on Manual Hitachi P1 Closed Loop Hoist Basic Instruc on Manual DH Firmware V.18 DETROIT HOIST AND CRANE LLC, CO. 6650 STERLING DRIVE NORTH STERLING HEIGHTS MICHIGAN 48312 Introduction This manual only applies to

More information

VVVF Control ( Variable Voltage and Variable Feriquency)

VVVF Control ( Variable Voltage and Variable Feriquency) VVVF Control ( Variable Voltage and Variable Feriquency) In order to run, stop, motor direction definition, motor current consumption control and a lot of other geared or gearless elevator motors parameters,

More information

vacon nxp arfiff30 user manual generator application ac drives

vacon nxp arfiff30 user manual generator application ac drives vacon nxp ac drives arfiff30 generator application user manual vacon 1 Vacon Generator application INDEX Document code: DPD01916A Software code: ARFIFF30V073 Date: 15.11.2016 VACON GENERATOR APPLICATION...

More information

Datasheet of the Easy Servo Drive ES-D VAC or VDC, 8.2A Peak, Close-loop, No Tuning. Version

Datasheet of the Easy Servo Drive ES-D VAC or VDC, 8.2A Peak, Close-loop, No Tuning. Version Datasheet of the Easy Servo Drive ES-D1008 0-70 V or 30-100VDC, 8.A Peak, Close-loop, No Tuning Version 0.1.0 http://www.leadshine.com Features Step and direction control Closed position loop for no loss

More information

MEGA Servo setup procedure for driving PMS motor

MEGA Servo setup procedure for driving PMS motor Application Note AN-MEGA-0016-v105EN MEGA Servo setup procedure for driving PMS motor Inverter type FRENIC MEGA (-EAQ Type) Software version 1700 Required options OPC-G1-PG, OPC-G1-PG2, OPC-G1-PG22, OPC-G1-PMPG

More information

ig5a Compact AC Drive 0.4~1.5kW(0.5~2HP) 1-phase 200~230Volts 0.4~22kW(0.5~30HP) 3-Phase 200~230Volts 0.4~22kW(0.5~30HP) 3-Phase 380~480Volts

ig5a Compact AC Drive 0.4~1.5kW(0.5~2HP) 1-phase 200~230Volts 0.4~22kW(0.5~30HP) 3-Phase 200~230Volts 0.4~22kW(0.5~30HP) 3-Phase 380~480Volts iga Compact AC Drive ~1.kW(0.~2HP) 1-phase 200~230Volts ~22kW(0.~30HP) 3-Phase 200~230Volts ~22kW(0.~30HP) 3-Phase 380~480Volts Drive STARVERT iga LS Starvert iga is very competitive in its price and shows

More information

System configuration. Ratings 400 V Class three-phase 90 to 800 kw 690 V Class three-phase 90 to 1000 kw SX-D. Frequency inverters.

System configuration. Ratings 400 V Class three-phase 90 to 800 kw 690 V Class three-phase 90 to 1000 kw SX-D. Frequency inverters. ~ ~ SX High performance Vector Control IP54 full range. Compact design & Robustness Built-in Filter according to C3 Class Built-in Fusses (From 200 kw) Safety according EN13849-1 and EN62061 standards

More information

Absolute Encoders Multiturn

Absolute Encoders Multiturn The Sendix F36 multiturn with the patented Intelligent Scan Technology is an optical multiturn encoder in miniature format, without gears and with 00% insensitivity to magnetic fields. With a size of just

More information

Before you operate the inverter, the parameters that you must first program are the basic parameters.

Before you operate the inverter, the parameters that you must first program are the basic parameters. . Main parameters Before you operate the inverter, the parameters that you must first program are the basic parameters..1 Searching for changes using the history function () : History function History

More information

MITOS VT6 AIR USER MANUAL. 02/10/2015 Manual_MITOS_VT6_AIR_ver3p3_eng

MITOS VT6 AIR USER MANUAL. 02/10/2015 Manual_MITOS_VT6_AIR_ver3p3_eng MITOS VT6 AIR USER MANUAL 02/10/2015 Manual_MITOS_VT6_AIR_ver3p3_eng Summary: GENERAL DESCRIPTION... 3 GENERAL FEATURES... 3 FUNCTIONING PARAMETERS... 4 FUNCTIONING MODE OF THE MITOS VT6 AIR... 7 FUNCTIONING

More information

The GS1 Digital Keypad LED Display Function Keys Displaying the Status of the GS1 AC Drive Programming the GS1 AC Drive...

The GS1 Digital Keypad LED Display Function Keys Displaying the Status of the GS1 AC Drive Programming the GS1 AC Drive... CHAPTER KEYPAD OPERATION 3 AND QUICKSTART Contents of this Chapter... The GS1 Digital Keypad................................3 2 LED Display..............................................3 2 Function Keys............................................3

More information

Sensors and Sensing Motors, Encoders and Motor Control

Sensors and Sensing Motors, Encoders and Motor Control Sensors and Sensing Motors, Encoders and Motor Control Todor Stoyanov Mobile Robotics and Olfaction Lab Center for Applied Autonomous Sensor Systems Örebro University, Sweden todor.stoyanov@oru.se 05.11.2015

More information

user's manual nx frequency converters beam pump application asfiff13

user's manual nx frequency converters beam pump application asfiff13 user's manual nx frequency converters beam pump application asfiff13 2 vacon Introduction INDEX 1. Introduction... 3 2. Commissioning... 4 2.1 Commissioning unbalanced load... 4 2.2 Commissioning balanced

More information

Experiment 3. Performance of an induction motor drive under V/f and rotor flux oriented controllers.

Experiment 3. Performance of an induction motor drive under V/f and rotor flux oriented controllers. University of New South Wales School of Electrical Engineering & Telecommunications ELEC4613 - ELECTRIC DRIVE SYSTEMS Experiment 3. Performance of an induction motor drive under V/f and rotor flux oriented

More information

Preface. Notes. Thank you for purchasing the VTP8 series AC drive.

Preface. Notes. Thank you for purchasing the VTP8 series AC drive. Preface Thank you for purchasing the VTP8 series AC drive. The VTP8 series AC drive is a general-purpose high-performance current vector control AC drive. It can implement the control of asynchronous motor.

More information

NXL HVAC APPLICATION MANUAL Programming manual for NXL HVAC drives

NXL HVAC APPLICATION MANUAL Programming manual for NXL HVAC drives NXL HVAC APPLICATION MANUAL Programming manual for NXL HVAC drives Page 2 (68) Index Honeywell HVAC Application (Software [ALFIQ105] Ver.2.09) INDEX 1. INTRODUCTION... 3 2. CONTROL I/O... 3. HVAC APPLICATION

More information

Compact & Powerful Inverter STARVERT ig5a 0.4~1.5kW 1phase 200~230Volts 0.4~22kW 3Phase 200~230Volts 0.4~22kW 3Phase 380~480Volts

Compact & Powerful Inverter STARVERT ig5a 0.4~1.5kW 1phase 200~230Volts 0.4~22kW 3Phase 200~230Volts 0.4~22kW 3Phase 380~480Volts Compact & Powerful Inverter STARVERT ig5a 0.4~1.5kW 1phase 200~230Volts 0.4~22kW 3Phase 200~230Volts 0.4~22kW 3Phase 380~480Volts Inverter STARVERT ig5a LS Starvert ig5a is very competitive in its price

More information

NX Series Inverters. HVAC Pocket Programming Guide

NX Series Inverters. HVAC Pocket Programming Guide NX Series Inverters HVAC Pocket Programming Guide HVAC Pocket Programming Guide HVAC Pocket Programming Guide / Contents This guide provides a single reference document for the user of NXL HVAC (product

More information

ES86 Series Closed-loop Stepper Drive + Motor System (Drive+ Motor/Encoder)

ES86 Series Closed-loop Stepper Drive + Motor System (Drive+ Motor/Encoder) ES86 Series Closed-loop Stepper Drive + Motor System (Drive+ Motor/Encoder) Traditional stepper motor drive systems operate open loop providing position control without feedback. However, because of this,

More information

AV-300i Specifications. Saftronics Inc. VG10 Product Specifications VG10. Dynamic Vector Drive

AV-300i Specifications. Saftronics Inc.   VG10 Product Specifications VG10. Dynamic Vector Drive Saftronics Inc. www.saftronics.com TM AV-300i Specifications VG10 Product Specifications VG10 Dynamic Vector Drive 1 Category Item Description Nominal Motor 230 VAC, 3 Phase 1/4 Hp to 125 Hp 460 VAC, 3

More information

Fan and Pump AC Inverter

Fan and Pump AC Inverter Fan and Pump AC Inverter Key Features for Fan and Pump Applications PID and Auto Energy Saving Functions. Input Phase Loss and Output Phase Loss Protection. LCD Keypad can be used to copy parameter settings

More information

CHAPTER KEYPAD OPERATION AND QUICKSTART. In This Chapter... The GS2 Digital Keypad GS2 Quickstart...3 6

CHAPTER KEYPAD OPERATION AND QUICKSTART. In This Chapter... The GS2 Digital Keypad GS2 Quickstart...3 6 CHAPTER KEYPAD OPERATION 3 AND QUICKSTART In This Chapter... The GS2 Digital Keypad.....................3 2 LED Display.........................................3 2 LED Indicators.......................................3

More information

Integrated Easy Servo

Integrated Easy Servo ies 1706 Integrated Easy Servo Motor + Drive + Encoder, 18 32VDC, NEMA17, 0.6Nm Features Easy servo control technology to combine advantages of open loop stepper systems and brushless servo systems Closed

More information

Goodrive inverter for air compressor. Preface

Goodrive inverter for air compressor. Preface Goodrive 300-01 Series Inver ter for Air Compressor GD300-01-037G-4 Preface Preface Goodrive300-01 series inverter for air compressor is developed based on Goodrive300 hardware platform and can be widely

More information

Datasheet of the Easy Servo Drive ES-D VDC, 8.0A Peak, Closed-loop, No Tuning

Datasheet of the Easy Servo Drive ES-D VDC, 8.0A Peak, Closed-loop, No Tuning Datasheet of the Easy Servo Drive ES-D508 0-45VDC, 8.0A Peak, Closed-loop, No Tuning Version 1. http://www.leadshine.com Features Step and direction control Closed position loop for no loss of movement

More information

The Drive & Control Company. Frequency Converter. VFC 3610 / VFC 5610 Series. Quick Start Guide R Edition 15

The Drive & Control Company. Frequency Converter. VFC 3610 / VFC 5610 Series. Quick Start Guide R Edition 15 The Drive & Control Company Frequency Converter VFC 3610 / VFC 5610 Series Quick Start Guide R912005518 Edition 15 Bosch Rexroth AG VFC 3610 / VFC 5610 Record of Revision Edition Release Date Notes DOK-RCON04-VFC-X610***-QU06-EN-P

More information

ES86 Series Closed-loop Stepper Drive + Motor System (ES-D808 Drive+ Motor/Encoder)

ES86 Series Closed-loop Stepper Drive + Motor System (ES-D808 Drive+ Motor/Encoder) ES86 Series Closed-loop Stepper Drive + Motor System (ES-D808 Drive+ Motor/Encoder) Traditional stepper motor drive systems operate open loop providing position control without feedback. However, because

More information

Using CME 2 with AccelNet

Using CME 2 with AccelNet Using CME 2 with AccelNet Software Installation Quick Copy (with Amplifier file) Quick Setup (with motor data) Offline Virtual Amplifier (with no amplifier connected) Screen Guide Page 1 Table of Contents

More information

QUICK GUIDE PUMP CONTROL. Frequency inverter for pump control and HVAC applications. Date Version 24/10/

QUICK GUIDE PUMP CONTROL. Frequency inverter for pump control and HVAC applications. Date Version 24/10/ QUICK GUIDE PUMP CONTROL Frequency inverter for pump control and HVAC applications Date Version 24/1/28 1..4 Version Details Date Applied Revised Approved English Translation from J. M. Ibáñez J. Català

More information

Manual Overview...1 2

Manual Overview...1 2 GETTING STARTED CHAPTER 1 Contents of this Chapter... Manual Overview.....................................1 2 Overview of this Publication..................................1 2 Who Should Read This Manual...............................1

More information

S11 Adjustable Speed Drive Engineering Specification

S11 Adjustable Speed Drive Engineering Specification PART 1 - GENERAL 1.0 Scope This specification shall cover Toshiba S11 AC Variable Frequency Drives, 6 pulse for 3- phase 200-240VAC, 380-500VAC and single phase 200V to 240VAC. 1.1 References A. National

More information

VSD Series II Variable Speed Micro Drives (VSM II) FS1 FS5

VSD Series II Variable Speed Micro Drives (VSM II) FS1 FS5 New Information Electric Current! Danger to Life! Only skilled or instructed persons may carry out the following operations. Variable Speed Micro Drives for Machinery Applications () VSxxx0_, VSxxx2x4_,

More information

Quick Reference Guide. DF5-... Frequency Inverters 02/02 AWB GB

Quick Reference Guide. DF5-... Frequency Inverters 02/02 AWB GB DF5-... Frequency Inverters 1 st published 22, edition 02/02 Moeller GmbH, 53105 Bonn Author: Holger Friedrich Editor: Michael Kämper Translator: Dominik Kreuzer All brand and product names are trademarks

More information

This operation manual is intended for users with basic knowledge of electricity and electric devices.

This operation manual is intended for users with basic knowledge of electricity and electric devices. This operation manual is intended for users with basic knowledge of electricity and electric devices. Safety Information Safety Information Read and follow all safety instructions in this manual precisely

More information

SV9000 SVReady USER MANUAL CONTENTS OPEN SV9000 USER MANUAL. SV9000 Page 0-1

SV9000 SVReady USER MANUAL CONTENTS OPEN SV9000 USER MANUAL. SV9000 Page 0-1 SV9000 Page 0-1 SV9000 SVReady USER MANUAL CNTENTS A General...0-2 B Application selection...0-2 C Restoring default values of application parameters...0-2 D Language selection...0-2 1 Standard Control

More information

Absolute Encoders Singleturn

Absolute Encoders Singleturn The absolute singleturn encoders Sendix 5853 SIL and 5873 SIL are perfectly suited for use in safety-related applications up to SIL3 according to DIN EN ISO 6800-5- or PLe to DIN EN ISO 3849. The extra

More information

TOSVERT TM VF-nC3 Parameter List

TOSVERT TM VF-nC3 Parameter List TOSVERT TM VF-nC Parameter List E658664 - Setting information * Please fill it in if necessary. Item Content Item Content Setting date / person Customer Application Application model Motor manufacturer

More information

DeviceCraft Revision #1 11/29/2010

DeviceCraft Revision #1 11/29/2010 DeviceCraft Revision #1 11/29/2010 DC Wiper Motor H-Bridge Servo / Speed Controller P/N 1020 Features: Dip Switch selectable mode of operation Both PID servo or speed controller Forward/Reverse operation

More information

CHAPTER 5 DESCRIPTION OF PARAMETER SETTINGS

CHAPTER 5 DESCRIPTION OF PARAMETER SETTINGS CHAPTER DESCRIPTION OF PARAMETER SETTINGS.1 Group 0: System Parameter VFD-V Series 00-00 Identity Code Factory setting Read Only Settings Based on the model type 00-01 Rated Current Display Factory setting

More information

ES86 Series Closed-loop Stepper Drive + Motor System (Drive+ Motor/Encoder)

ES86 Series Closed-loop Stepper Drive + Motor System (Drive+ Motor/Encoder) ES86 Series Closed-loop Stepper Drive + Motor System (Drive+ Motor/Encoder) Traditional stepper motor drive systems operate open loop providing position control without feedback. However, because of this,

More information

Index 2. G Gain settings 4 31 Glossary of terms A 2 Grommets 2 13

Index 2. G Gain settings 4 31 Glossary of terms A 2 Grommets 2 13 Index A A Group functions 3 9 AC reactors 5 3 Acceleration 1 15, 3 8 characteristic curves 3 26 second function 3 24 two-stage 4 19 Acceleration stop function 3 21 Access levels 3 5, 3 36, 4 25 Access

More information

Rotary Measurement Technology Absolute Encoders, Multiturn

Rotary Measurement Technology Absolute Encoders, Multiturn Mechanical drive Safety-LockTM High rotational speed -40 to 90 C IP Temperature High IP High shaft load capacity Shock/ vibration resistant Magnetic field proof Short-circuit proof Reverse polarity protection

More information

Illustration 1: Wiper Motor Controller, Sensor, and optional programmer. DC Wiper Motor H-Bridge Servo / Speed Controller

Illustration 1: Wiper Motor Controller, Sensor, and optional programmer. DC Wiper Motor H-Bridge Servo / Speed Controller DeviceCraft Revision #2 4/13/2014 Illustration 1: Wiper Motor Controller, Sensor, and optional programmer DC Wiper Motor H-Bridge Servo / Speed Controller P/N 4900 Features: Powerfull servo or reversible

More information

Absolute Encoders Multiturn

Absolute Encoders Multiturn Absolute Encoders Multiturn Functional Safety, optical The absolute multiturn encoders Sendix 5863 SIL and 5883 SIL are perfectly suited for use in safety-related applications up to SIL3 according to DIN

More information

Contents. Safety Information and Precautions Product Information Operation Panel (Keypad & Display) Quick Setup...

Contents. Safety Information and Precautions Product Information Operation Panel (Keypad & Display) Quick Setup... Contents Safety Information and Precautions...2 1. Product Information...4 1.1 Nameplate and Designation Rule... 4 1.2 General Specifications... 5 1.3 Environment... 9 2 Wiring... 10 2.1 Typical System

More information

QUICK GUIDE PUMP CONTROL. Frequency inverter for pump control and HVAC applications. Date Version 22/09/

QUICK GUIDE PUMP CONTROL. Frequency inverter for pump control and HVAC applications. Date Version 22/09/ QUICK GUIDE PUMP CONTROL Frequency inverter for pump control and HVAC applications Date Version 22/9/9 1..8 Version Details Date Written Checked Approved 1..3 English Translation from Spanish J. M. Ibáñez

More information

MTY (81)

MTY (81) This manual describes the option "d" of the SMT-BD1 amplifier: Master/slave electronic gearing. The general information about the digital amplifier commissioning are described in the standard SMT-BD1 manual.

More information

Brushed DC Motor Microcontroller PWM Speed Control with Optical Encoder and H-Bridge

Brushed DC Motor Microcontroller PWM Speed Control with Optical Encoder and H-Bridge Brushed DC Motor Microcontroller PWM Speed Control with Optical Encoder and H-Bridge L298 Full H-Bridge HEF4071B OR Gate Brushed DC Motor with Optical Encoder & Load Inertia Flyback Diodes Arduino Microcontroller

More information

3. Be aware of the ambient temperature. Use the unit within the specified ambient temperature only.

3. Be aware of the ambient temperature. Use the unit within the specified ambient temperature only. This document is a short guide to how to connect, do the configuration and start the unit in the easiest way. Refer to the Instruction Manual IMAE-01, appropriate revision of Axpert-Eazy Series AC Drive

More information

SX (400 V) System configuration

SX (400 V) System configuration ~ ~ SX (400 V) High performance Vector Control IP54 full range. Compact design & Robustness Built-in Filter according to C3 Class Built-in Fuses (From 200 kw) Safety according EN13849-1 and EN62061 standards

More information

SAFETY INSTRUCTIONS WARNING

SAFETY INSTRUCTIONS WARNING Important User Information Thank you for purchasing LS Variable Frequency Drives! SAFETY INSTRUCTIONS Always follow safety instructions to prevent accidents and potential hazards from occurring. In this

More information

QUICK GUIDE PUMP CONTROL. High performance Compact Inverter. Date Version 22/09/

QUICK GUIDE PUMP CONTROL. High performance Compact Inverter. Date Version 22/09/ QUICK GUIDE PUMP CONTROL High performance Compact Inverter Date Version 22/9/29 1..3 Version Details Date Written Checked Approved 1.. Draft J. M. Ibáñez J. Català 1..1 Second Version 17/9/29 J. M. Ibáñez

More information

Single-phase or three phase AC220V (-15% ~ +10%) 50 ~ 60Hz

Single-phase or three phase AC220V (-15% ~ +10%) 50 ~ 60Hz KT270-H Servo Drive Features: The use of DSP ( digital signal processor ) chip, greatly accelerating the speed of data acquisition and processing, the motor running with good performance. Application of

More information

Integrated Servo Motor UCS57

Integrated Servo Motor UCS57 Integrated Servo Motor Introduction is a new generation of high performance digital integrated servo drive motor, which is a series of low voltage AC servo products integrated with AC servo motor and drive

More information

VF-nC1 Adjustable Speed Drive Engineering Specification

VF-nC1 Adjustable Speed Drive Engineering Specification PART 1 - GENERAL 1.0 Scope This specification shall cover Toshiba VF-nC1 AC Variable Frequency Drives, 6 pulse for 100V single-phase 0.1 to 0.75kW, 200V single-phase 0.2 to 2.2kW and 200V threephase 0.1

More information

CHAPTER 8 SUMMARY OF PARAMETER SETTINGS

CHAPTER 8 SUMMARY OF PARAMETER SETTINGS CHAPTER 8 SUMMARY OF PARAMETER SETTINGS VFD-S Series!: The parameter can be set during operation, *: Twice the value for 460V class. Group 0 User Parameters Parameters Explanation s 0-00 Identity Code

More information

Absolute Encoders - Singleturn

Absolute Encoders - Singleturn The Sendix 5 and Sendix 7 singleturn encoders with SSI or BiSS-C interface and optical sensor technology can achieve a resolution of max. 7 bits. These encoders are also available with an optional SinCos

More information