Application for A Sub-harmonic Protection Relay. ERLPhase Power Technologies
|
|
- Isaac Patterson
- 5 years ago
- Views:
Transcription
1 Application for A Sub-harmonic Protection Relay ERLPhase Power Technologies 1
2 Outline Introduction System Event at Xcel Energy Event Analysis Microprocessor based relay hardware architecture Sub harmonic detection process Principle of sub harmonic detection Operations/Minute detector Results and discussions Conclusions 2
3 Introduction Wind power based generation is growing rapidly throughout the world Since wind farms are generally located far away from the load centers series compensation is used for economical reasons Sub Synchronous Resonance (SSR) is a well known phenomena in series compensated system and many mitigation techniques exist 3
4 Introduction.. Sub harmonic oscillations due to wind generation interaction (controls/system) impose new challenges to today s electrical grid. An event on Xcel Energy grid involving the interconnection between a wind generator and a series compensated transmission system lead to the development of a protection relay to detect frequencies in the range of 5 HZ to 25 HZ, later expanded to 40Hz, to provide back up protection to special protection schemes installed around the series compensated line. 4
5 Introduction... Sub harmonics is defined as the harmonic frequency below the system frequency (60 Hz or 50 Hz) Natural frequency of series compensated transmission system is defined by f n = f sys X c /X TOT Where, Note: f n = natural frequency (Hz) f sys = system frequency (60 Hz or 50 Hz) X c = series capacitor reactance X TOT = sum of all the system inductive reactance (transmission line, transformer, generator sub transient reactance For compensation between 20% to 80%, f n < 60 Hz which is sub synchronous frequency 5
6 Introduction. System electrical dynamics current voltage Generator electromagnetic dynamics Electrical self excitation or Induction generator effect (IGE) 6
7 Introduction.. SSCI Sub Synchronous Control Instability Interaction Between Power Electronics Devices (Wind Turbine, HVDC, SVC etc.) and Series Compensated Transmission System. Power Electronic Devices Control Signals Series Compensated Transmission System 7
8 Introduction... System electrical dynamics Current Voltage Generator electromagnetic dynamics Electromagnetic torque Shaft speed Turbine mechanical dynamics Torsional interaction Mechanical torque Capacitor fault induced voltage Current Generator electromagnetic dynamics Electromagnetic torque Turbine mechanical dynamics Mechanical Torque Amplifications 8
9 System Single Line Diagram 9
10 Event Description 10
11 Event Description 11
12 Event Description 12
13 Event Description 13
14 Event Description 14
15 System Event 1- Breaker 1 & 2 opened for regular system switching procedure 2- CT1,CT2, and W start feeding radially through series capacitor 345 kv To the System To the System Line kv W - Wind generators as a single unit CT1, CT2 - Combustion turbine generators 15 MW (20% of total generation) 45 MVA 3- Tripped the CT generator unit 15
16 Event Analysis 9 Hz & 13 Hz dominant sub harmonics High speed recording of 3 phase currents captured by the DFR 16
17 Event Analysis Slow speed (swing ) recording of one of the phases 17
18 Studies and Conclusions Radial connection of generation to the system would lead to sub synchronous frequency oscillation. Study was conducted to determine the impact of series capacitors installation on existing generators in the region. The study concluded that only the combustion turbines and the wind farm at Lakefield generation were impacted. Special Protection Scheme (SPS) was needed to bypass the capacitor under some system configuration. 18
19 Effect of Series Capacitors On Combustion Turbine The study concluded that the CT generator units are stable under base (normal) condition but with some potential for SSR under N-1 contingency. Since conclusion depended heavily on the actual mode shape of the turbine-generators and damping due to load, it was decided to determine the load damping and mode shape through actual measurement on one of the units. 19
20 On Wind Farms Effect of Series Capacitors Study concluded that the wind farm will be affected by what is known as SSR induction generation effect. In the case of Xcel Energy, it was determined that this can be mitigated by bypassing the series capacitor on loss of LFD-LAJ line. In addition, a study performed by Xcel Energy also concluded that failure to bypass should be backed up by suitable SSR protection that can recognize the electrical instability and trip the wind farm as a last resort. 20
21 Special Protection Scheme A special protection scheme was designed to bypass the series capacitor for the following conditions: At Lakefield Generation substation: Any relay operation on the LFD-LAJ line Breaker configuration at Lakefield Generation that leads to radial connection of wind farm or CT Generators At Lakefield Junction substation Any relay operation on LAJ-LFD line Any configuration of breakers at Lakefield Junction that leads to opening of the line towards Lakefield Generation. 21
22 Special Protection Scheme 22
23 Second Event Analysis Phase currents of wind generators connected to the system during the second switching event had sub synchronous frequencies even when the series capacitor was not in service. The conclusion was to develop a back up protection device to detect sustained oscillations. 23
24 Need for Backup Protection for Wind Farm None available at that time to detect sub synchronous frequencies. Specification/Requirement: Ability to detect any frequencies from 5-25 HZ with 1 HZ resolution. Set points based on nominal, fundamental and THD frequency ratio. Set points based on individual current or voltage input as well as summation of more than one current input. 24
25 Is this the only event that ever occurred? There was an event in Reference NERC Lesson Learned Sub-Synchronous Interaction between Series-Compensated Transmission Lines and Generation. Published July 26, Synchronous_Interaction.pdf 25
26 Description of the 2009 Event 26
27 NERC Conclusiones 27
28 4000 Series Large LCD allows for better metering display. Navigation controls allows for and easy experience through maintenance, service and view menus. Programmed target LEDs provides tripping information facilitating crew personnel. Fast processor and hardware platform. Optical ports ready for IEC Goose. Unique front panel USB and Ethernet ports provide easy and fast access to settings and set up.
29 S-PRO Sub-Harmonic Protection
30 S-PRO Sub-Harmonic Protection Inputs and Outputs 4 sets of 3-Phase CT inputs (<0.25 VA) 5 A RMS nominal (1 Amp nominal version available) 15 A RMS - maximum continuous 100 A for 1 second - maximum full scale without distortion 400 A for 1 second - maximum thermal rating 2 sets of 3-Phase VT inputs (<0.15 VA) 69 V RMS - nominal 138 V RMS maximum continuous 207 V RMS for 10 seconds - maximum thermal rating 9 digital inputs, externally wetted 14 programmable output contacts, plus 1 relay inoperative output
31 S-PRO Sub-Harmonic Protection Rear Connections 3U Unit 4U Unit - Future
32 Protection S-PRO Sub-Harmonic Protection Sub-Harmonic Detector Frequency Range 5 25 Hz Fundamental Frequency Protection functions IEEE devices 27, 50LS, 59 Ring bus capability ProLogic 24 control logic statements 8 setting groups with setting group logic
33 Sub Harmonic Detection Trip or Alarm: = max (f2, f3, f4, f5, f6, f7) > Lset 52
34 Operations/Minute Detection Return 53
35 Sub Harmonic Detection Logic Diagram 56
36 Results and discussions 62
37 Calculating Relay Settings Current response to sub-synchronous resonance 63
38 Calculating Relay Settings Sub-harmonic magnitudes (RMS). Return 64
39 Sub-Harmonic Current Nominal Ratio Calculated by taking the highest sub-harmonic current observed for the 5Hz - 40Hz divided by the nominal input current setting (1A or 5A). Sub-harmonic current levels can vary depending on the topology of the power system and the type of event. It is recommended that different contingencies be considered. In the case under consideration, the highest sub-harmonic current observed during the event was the 11th harmonic with a magnitude of 172 primary amps with a current transformer ratio of 400:1. The relay current inputs were 5A inputs. 65
40 Sub-Harmonic Current Nominal Ratio Applying the nominal ratio setting, we have the following: Set nominal ratio > 6% 66
41 Sub-Harmonic Current Fundamental Ratio Calculated by taking the highest sub-harmonic current between 5Hz - 40Hz divided by the fundamental current value (50Hz or 60 Hz). This ratio is calculated as follows: The fundamental current observed in the record was 1300 primary amps with a current transformer ratio of 400:1. The fundamental ratio then becomes: Set fundamental ratio > 10% 67
42 Total Sub-harmonic Distortion This setting takes into account every sub-harmonic from 5Hz - 40Hz by taking the square root of the sub-harmonics currents squared. The record in slide 40 shows a captured value of total subharmonic distortion (TSHD) between 160% and 165%. A TSHD setting greater than 100% would be appropriate. 68
43 Operations per Minute Due to nuisance cases, and as shown in slide 32 an operations per minute setting should be applied. For this case, a minimum of 30 op/min is required for any of the other sub-harmonic settings to take effect. 69
44 Sub-Harmonic Voltage Nominal Ratio Calculated by taking the highest sub-harmonic voltage value seen in the 5Hz 40Hz frequency range divided by the secondary nominal voltage level 69V For the case under consideration, the 11th sub-harmonic had the highest magnitude. Using the PT ratio of 3000:1, the nominal ratio is: Nominal ratio = 3% Set > 2% 70
45 Sub-Harmonic Voltage Fundamental Ratio Calculated by taking the highest sub-harmonic voltage value and dividing it by the fundamental voltage value. This ratio is calculated as follows: Nominal ratio = 3% Set > 2% 71
46 Overcurrent and Overvoltage Overcurrent and Overvoltage Setting for the fundamental shall be determined by means of a power system study that should reveal the current and voltage levels that may appear in the system during an event. The overcurrent settings shall be coordinated with the other overcurrent relays being used to protect the transmission line. The overvoltage settings shall be coordinated with the regional reliability center requirements and the minimum insulation requirements for the equipment. 72
47 Conclusions The event captured at the Xcel Energy Utility lead to the development of a new microprocessor based sub harmonic protection technique. With the increase use of wind generators feeding HV and EHV utility networks, it is necessary to ensure that sub harmonic oscillations are monitored, and that the electrical grid is protected from any resulting detrimental effects. 73
48 Conclusions.. The performance of the sub-harmonic protection technique was successfully tested using a Real Time Digital Simulator (RTDS) The tests demonstrated that the solution is capable of performing reliably the following functions: Nominal sub-harmonic detection Fundamental sub-harmonic detection Total sub-harmonic detection Operations/Minute detection 74
49 Conclusions... Digital fault recorders can be used to capture osciollography files that can be analyzed to determine levels of sub-harmonics during a SSR event Using graphical tools similar to those shown in this presentation, protection and control engineers can easily determine appropriate relay settings for subharmonic protection relays There are also software tools that can be used to simulate the power system to determine possible SSR phenomena for various power system topologies 75
Mitigation & Protection of Sub-Synchronous Controller Interactions (SSCI) in DFIG Wind Turbine Systems
Mitigation & Protection of Sub-Synchronous Controller Interactions (SSCI) in DFIG Wind Turbine Systems Krish Narendra, P.hD. CTO ERL Protection, Automation, Control & Smart Grid ERLPhase Power Technologies
More informationProtection for Sub SSTI Conditions Using an Industrial Sub-harmonic Relay
Relay Conference 2018 Protection for Sub SSTI Conditions Using an Industrial Sub-harmonic Relay R. Midence ERLPhase Power Technologies Winnipeg, MB Canada 1 Outline Sub Synchronous Torsional Interactions
More informationWind and Solar (PV) Sub harmonic Interactions with Power Systems
I PCGRID Workshop - 2017 Wind and Solar (PV) Sub harmonic Interactions with Power Systems Dr. Krish Narendra Chief Technology Officer ERLPhase Protection, Automation, Control & Smart Grid ERLPhase Power
More informationCommissioning Process and Acceptance Test of a Sub-harmonic Protection Relay
Commissioning Process and Acceptance Test of a Sub-harmonic Protection Relay K. Narendra, R. Midence, A. Oliveira, N. Perera, N. Zhang - ERLPhase Power Technologies Ltd Abstract Numerous technical papers
More informationA New Subsynchronous Oscillation (SSO) Relay for Renewable Generation and Series Compensated Transmission Systems
21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2015 Grid of the Future Symposium A New Subsynchronous Oscillation (SSO) Relay for Renewable Generation and Series Compensated
More informationPlanners Perspective on Series Compensated Transmission Lines
TOGETHER WE DELIVER Planners Perspective on Series Compensated Transmission Lines Kenneth A. Donohoo, PE Director, System Planning Distribution and Transmission kenneth.donohoo@oncor.com Oncor Electric
More informationCOMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR)
7 February 2018 RM Zavadil COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR) Brief Overview of Sub-Synchronous Resonance Series
More informationUse of a Sub Harmonic Protection Relay to Detect SSO Conditions Associated with Type-III Windfarms and Series Compensated Transmission Systems
21, rue d Artois, F-75008 PARIS 095 DUBLIN 2017 http : //www.cigre.org Use of a Sub Harmonic Protection Relay to Detect SSO Conditions Associated with Type-III Windfarms and Series Compensated Transmission
More informationUNDERSTANDING SUB-HARMONICS
UNDERSTANDING SUB-HARMONICS Joe Perez, P.E., SynchroGrid, College Station, TX 77845, jperez@synchrogrid.com Introduction: Over the years, engineers have employed fundamental principles of electrical engineering
More informationABB Inc. April 1, 2016 Slide 1
Galina S. Antonova, ABB Inc., i-pcgrid Workshop - 2016 Combining subsynchronous oscillations detection and synchrophasor measurements to increase power system stability April 1, 2016 Slide 1 Sub synchronous
More informationUProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy
UProtection Requirements Ufor a Large scale Wind Park Shyam Musunuri Siemens Energy Abstract: In the past wind power plants typically had a small power rating when compared to the strength of the connected
More informationFixed Series Compensation
Fixed Series Compensation High-reliable turnkey services for fixed series compensation NR Electric Corporation The Fixed Series Compensation (FSC) solution is composed of NR's PCS-9570 FSC control and
More informationArtificial Island Open Window Concerns re: Dominion Proposal 1A
Artificial Island Open Window Concerns re: Dominion Proposal 1A Esam A. Khadr Michael Kayes Robert Pollock Donald Shoup Managing Director PSE&G Electric Delivery Planning Director PSE&G Delivery Projects
More informationELEMENTS OF FACTS CONTROLLERS
1 ELEMENTS OF FACTS CONTROLLERS Rajiv K. Varma Associate Professor Hydro One Chair in Power Systems Engineering University of Western Ontario London, ON, CANADA rkvarma@uwo.ca POWER SYSTEMS - Where are
More informationISSUES OF SYSTEM AND CONTROL INTERACTIONS IN ELECTRIC POWER SYSTEMS
ISSUES OF SYSTEM AND CONTROL INTERACTIONS IN ELECTRIC POWER SYSTEMS INDO-US Workshop October 2009, I.I.T. Kanpur INTRODUCTION Electric Power Systems are very large, spread over a wide geographical area
More informationDigital Fault Recorder Deployment at HVDC Converter Stations
Digital Fault Recorder Deployment at HVDC Converter Stations On line continuous monitoring at HVDC Converter Stations is an important asset in determining overall system performance and an essential diagnostic
More informationA Comprehensive Approach for Sub-Synchronous Resonance Screening Analysis Using Frequency scanning Technique
A Comprehensive Approach Sub-Synchronous Resonance Screening Analysis Using Frequency scanning Technique Mahmoud Elfayoumy 1, Member, IEEE, and Carlos Grande Moran 2, Senior Member, IEEE Abstract: The
More informationPower systems Protection course
Al-Balqa Applied University Power systems Protection course Department of Electrical Energy Engineering 1 Part 5 Relays 2 3 Relay Is a device which receive a signal from the power system thought CT and
More informationCatastrophic Relay Misoperations and Successful Relay Operation
Catastrophic Relay Misoperations and Successful Relay Operation Steve Turner (Beckwith Electric Co., Inc.) Introduction This paper provides detailed technical analysis of several catastrophic relay misoperations
More informationPRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75
PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion
More informationAppendix S: PROTECTION ALTERNATIVES FOR VARIOUS GENERATOR CONFIGURATIONS
Appendix S: PROTECTION ALTERNATIVES FOR VARIOUS GENERATOR CONFIGURATIONS S1. Standard Interconnection Methods with Typical Circuit Configuration for Single or Multiple Units Note: The protection requirements
More informationECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control
ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control Spring 2014 Instructor: Kai Sun 1 References Saadat s Chapters 12.6 ~12.7 Kundur s Sections
More informationGPM. Field and Stator Ground Fault Protection Modules. Instruction Manual AF1. GE Grid Solutions
GE Grid Solutions GPM Field and Stator Ground Fault Protection Modules Instruction Manual Product version: 2.0x GE publication code: 1601-0256-AF1 (GEK-113231D) 1601-0256-AF1 Copyright 2017 GE Multilin
More informationAdvanced Applications of Multifunction Digital Generator Protection
Advanced Applications of Multifunction Digital Generator Protection Charles J. Mozina Beckwith Electric Company 6190-118th Avenue North Largo, FL 33773-3724 U.S.A. Abstract: The protection of generators
More informationPRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76
PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion
More informationNTG MULTIFUNCTON GENERATOR PROTECTION RELAY. NTG-Slide
NTG MULTIFUNCTON GENERATOR PROTECTION RELAY 1 NTG Digital protection relay that integrates a number of functions required r for the protection of generators. It is used in power stations from gas, steam,
More informationN. TEST TEST DESCRIPTION
Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy meters and transducers Primary injection testing capabilities
More informationNERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell
Power Plant and Transmission System Protection Coordination Phase Distance (21) and Voltage-Controlled or Voltage-Restrained Overcurrent Protection (51V) NERC Protection Coordination Webinar Series June
More informationUsing a Multiple Analog Input Distance Relay as a DFR
Using a Multiple Analog Input Distance Relay as a DFR Dennis Denison Senior Transmission Specialist Entergy Rich Hunt, M.S., P.E. Senior Field Application Engineer NxtPhase T&D Corporation Presented at
More informationPower Plant and Transmission System Protection Coordination Fundamentals
Power Plant and Transmission System Protection Coordination Fundamentals NERC Protection Coordination Webinar Series June 2, 2010 Jon Gardell Agenda 2 Objective Introduction to Protection Generator and
More informationFerroresonance Conditions Associated With a 13 kv Voltage Regulator During Back-feed Conditions
Ferroresonance Conditions Associated With a Voltage Regulator During Back-feed Conditions D. Shoup, J. Paserba, A. Mannarino Abstract-- This paper describes ferroresonance conditions for a feeder circuit
More informationITC Holdings Planning Criteria Below 100 kv. Category: Planning. Eff. Date/Rev. # 12/09/
ITC Holdings Planning Criteria Below 100 kv * Category: Planning Type: Policy Eff. Date/Rev. # 12/09/2015 000 Contents 1. Goal... 2 2. Steady State Voltage & Thermal Loading Criteria... 2 2.1. System Loading...
More informationIntegration of Wind Generation into Weak Grids
Integration of Wind Generation into Weak Grids Jason MacDowell GE Energy Consulting NERC ERSTF Atlanta, GA December 10-11, 2014 Outline Conventional and Power Electronic (PE) Sources Stability limitations
More informationBUS2000 Busbar Differential Protection System
BUS2000 Busbar Differential Protection System Differential overcurrent system with percentage restraint protection 1 Typical Busbar Arrangements Single Busbar Double Busbar with Coupler Breaker and a Half
More informationCapacitor protection relay
Capacitor Protection Relay FEATURES Capacitor unbalance protection Line current unbalance protection Overvoltage protection Overheating protection Ground fault protection Overcurrent protection Undercurrent
More informationEH2741 Communication and Control in Electric Power Systems Lecture 2
KTH ROYAL INSTITUTE OF TECHNOLOGY EH2741 Communication and Control in Electric Power Systems Lecture 2 Lars Nordström larsno@kth.se Course map Outline Transmission Grids vs Distribution grids Primary Equipment
More informationCoil Products Beginnings 1960 State of the Art. Customer partnership around the globe. Continuous innovation since 1900
Coil Products Coil Products Customer partnership around the globe More than 250,000 coil products delivered to more than 170 countries. More than 60 years of operational experience. 35,000 in Europe 13,000
More informationMVCT. Megger VT & CT Analyzer. MVCT Megger VT & CT Analyzer
MVCT Ability to test both VT and CT Easy to use one-button automated test plans Industry leading test duration using patented simultaneous tap measurements Smallest and lightest unit on the market CT Kneepoints
More informationTransient stability improvement by using shunt FACT device (STATCOM) with Reference Voltage Compensation (RVC) control scheme
I J E E E C International Journal of Electrical, Electronics ISSN No. (Online) : 2277-2626 and Computer Engineering 2(1): 7-12(2013) Transient stability improvement by using shunt FACT device (STATCOM)
More informationPower System Protection Where Are We Today?
1 Power System Protection Where Are We Today? Meliha B. Selak Power System Protection & Control IEEE PES Distinguished Lecturer Program Preceding IEEE PES Vice President for Chapters melihas@ieee.org PES
More informationNotes 1: Introduction to Distribution Systems
Notes 1: Introduction to Distribution Systems 1.0 Introduction Power systems are comprised of 3 basic electrical subsystems. Generation subsystem Transmission subsystem Distribution subsystem The subtransmission
More informationCOPYRIGHTED MATERIAL. Index
Index Note: Bold italic type refers to entries in the Table of Contents, refers to a Standard Title and Reference number and # refers to a specific standard within the buff book 91, 40, 48* 100, 8, 22*,
More informationDetecting and Managing Geomagnetically Induced Currents With Relays
Detecting and Managing Geomagnetically Induced Currents With Relays Copyright SEL 2013 Transformer Relay Connections Voltage Current Control RTDs Transformer Protective Relay Measures differential current
More informationGrid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017
Grid codes and wind farm interconnections CNY Engineering Expo Syracuse, NY November 13, 2017 Purposes of grid codes Grid codes are designed to ensure stable operating conditions and to coordinate the
More informationOPEN-PHASE DETECTION TECHNIQUES FOR CRITICAL STANDBY SUPPLIES
OPEN-PHASE DETECTION TECHNIQUES FOR CRITICAL STANDBY SUPPLIES U AJMAL, GE Grid Solutions UK Ltd, usman.ajmal@ge.com S SUBRAMANIAN, GE Grid Solutions UK Ltd, sankara.subramanian@ge.com H Ha GE Grid Solutions
More informationNERC Requirements for Setting Load-Dependent Power Plant Protection: PRC-025-1
NERC Requirements for Setting Load-Dependent Power Plant Protection: PRC-025-1 Charles J. Mozina, Consultant Beckwith Electric Co., Inc. www.beckwithelectric.com I. Introduction During the 2003 blackout,
More informationJoe Warner, Electric Power Industry Conference (EPIC), November 15, 2016 Advances in Grid Equipment Transmission Shunt Compensation
Joe Warner, Electric Power Industry Conference (EPIC), November 15, 2016 Advances in Grid Equipment Transmission Shunt Compensation Slide 1 Excerpt from the BoA BoA: Book of Acronyms MSC/MSR: Mechanically
More informationISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements
Applicability 1(1) Section 502.1 applies to the ISO, and subject to the provisions of subsections 1(2), (3) and (4) to any: (a) a new wind aggregated generating facility to be connected to the transmission
More informationGrid Impact of Neutral Blocking for GIC Protection:
Report submitted to EMPRIMUS - Critical Infrastructure Protection Grid Impact of Neutral Blocking for GIC Protection: Impact of neutral grounding capacitors on network resonance Prepared By: Athula Rajapakse
More informationIDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)
IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: IDAHO POWER COMPANY Designated Contact Person: Jeremiah Creason Address: 1221 W. Idaho Street, Boise ID 83702 Telephone
More informationBus Protection Fundamentals
Bus Protection Fundamentals Terrence Smith GE Grid Solutions 2017 Texas A&M Protective Relay Conference Bus Protection Requirements High bus fault currents due to large number of circuits connected: CT
More informationTECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR SMALL GENERATION INTERCONNECTIONS
TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR SMALL GENERATION INTERCONNECTIONS Puget Sound Energy, Inc. PSE-ET-160.60 October 30, 2007 TABLE OF CONTENTS 1. INTRODUCTION...1 1.1 GENERAL
More informationPOWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.
POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. This document may be subject to changes. Contact ARTECHE to confirm the characteristics and availability of the products
More informationGeneration Interconnection Requirements at Voltages 34.5 kv and Below
Generation Interconnection Requirements at Voltages 34.5 kv and Below 2005 March GENERATION INTERCONNECTION REQUIREMENTS AT 34.5 KV AND BELOW PAGE 1 OF 36 TABLE OF CONTENTS 1. INTRODUCTION 5 1.1. Intent
More informationGenerator Protection GENERATOR CONTROL AND PROTECTION
Generator Protection Generator Protection Introduction Device Numbers Symmetrical Components Fault Current Behavior Generator Grounding Stator Phase Fault (87G) Field Ground Fault (64F) Stator Ground Fault
More informationNew Methods to Mitigate Distribution System Harmonics
Alberta Power Industry Consortium 214 Power & Energy Innovation Forum New Methods to Mitigate Distribution System Harmonics By Wilsun Xu Power Disturbance & Signaling Research Lab November 5, 214 Outline
More informationSolidGround TM grid stability and harmonics mitigation system Geomagnetic Storm Induced Current (GIC) and Electromagnetic Pulse (EMP) protection
SolidGround TM grid stability and harmonics mitigation system Geomagnetic Storm Induced Current (GIC) and Electromagnetic Pulse (EMP) protection SolidGround TM GIC grid stability and harmonics mitigation
More information10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY
9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor
More informationSystem Protection and Control Subcommittee
Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),
More informationKončar TMS - Bushing monitoring
Končar TMS - Bushing monitoring Many recent studies have shown that bushing failure is one of the most common causes of transformer failure. Thus need for bushing diagnostic and monitoring system has risen.
More informationTransformer Protection
Transformer Protection Transformer Protection Outline Fuses Protection Example Overcurrent Protection Differential Relaying Current Matching Phase Shift Compensation Tap Changing Under Load Magnetizing
More informationArvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India
e t International Journal on Emerging Technologies 4(1): 10-16(2013) ISSN No. (Print) : 0975-8364 ISSN No. (Online) : 2249-3255 Control of Synchronous Generator Excitation and Rotor Angle Stability by
More informationQUESTIONNAIRE for Wind Farm Power Stations only
TRANSMISSION SYSTEM OPERATOR QUESTIONNAIRE for Wind Farm Power Stations only To be submitted by the Generation Licensees together with the Application for Connection Certificate according to IEC 61400-21
More informationISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements
Division 502 Technical Applicability 1(1) Section 502.1 applies to: Expedited Filing Draft August 22, 2017 the legal owner of an aggregated generating facility directly connected to the transmission system
More informationSystem Protection Schemes in Power Network based on New Principles
System Protection Schemes in Power Network based on New Principles Daniel Karlsson, ABB Automation Products AB S-721 59 Västerås, SWDN daniel.h.karlsson@se.abb.com Abstract This report describes how a
More informationPeteris Spels, ABB Inc., WMEA, November 18, 2011 HARMONICS. ABB Group December 14, 2011 Slide 1
Peteris Spels, ABB Inc., WMEA, November 18, 2011 HARMONICS December 14, 2011 Slide 1 Agenda Harmonics: What they are? Where do they come from? Why bother? Regulations How to detect? How to avoid? Summary
More informationN. TEST TEST DESCRIPTION
Multi function system for testing substation equipment such as: current, voltage and power transformers, over-current protection relays, energy meters and transducers Primary injection testing capabilities
More informationElectric Power Quality: Voltage Sags Momentary Interruptions
Slide 1 Electric Power Quality: Voltage Sags Momentary Interruptions Ward Jewell Wichita State University ward.jewell@wichita.edu Slide 2 Power Quality Events Voltage sags Outages/interruptions Voltage
More informationIOCL Electrical Engineering Technical Paper
IOCL Electrical Engineering Technical Paper 1. Which one of the following statements is NOT TRUE for a continuous time causal and stable LTI system? (A) All the poles of the system must lie on the left
More informationESB National Grid Transmission Planning Criteria
ESB National Grid Transmission Planning Criteria 1 General Principles 1.1 Objective The specific function of transmission planning is to ensure the co-ordinated development of a reliable, efficient, and
More informationSECTION LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED
SECTION 16280 LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED PART 1 - GENERAL 1.1 SUMMARY This specification defines the requirements for active harmonic filter systems in order to meet IEEE-519-2014
More informationNERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell
Power Plant and Transmission System Protection Coordination GSU Phase Overcurrent (51T), GSU Ground Overcurrent (51TG), and Breaker Failure (50BF) Protection NERC Protection Coordination Webinar Series
More informationProtection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin
Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com 1 Protection Fundamentals By John Levine 2 Introductions Tools Outline Enervista Launchpad
More informationSTRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS
1 STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS Z. GAJIĆ S. HOLST D. BONMANN D. BAARS ABB AB, SA Products ABB AB, SA Products ABB AG, Transformers ELEQ bv Sweden Sweden Germany Netherlands zoran.gajic@se.abb.com
More informationTECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR INTERCONNECTION OF GENERATION FACILITIES NOT SUBJECT TO FERC JURISDICTION
TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR INTERCONNECTION OF GENERATION FACILITIES NOT SUBJECT TO FERC JURISDICTION Document 9022 Puget Sound Energy, Inc. PSE-TC-160.70 December
More informationFerroresonance Experience in UK: Simulations and Measurements
Ferroresonance Experience in UK: Simulations and Measurements Zia Emin BSc MSc PhD AMIEE zia.emin@uk.ngrid.com Yu Kwong Tong PhD CEng MIEE kwong.tong@uk.ngrid.com National Grid Company Kelvin Avenue, Surrey
More informationAORC Technical meeting 2014
http : //www.cigre.org B4-112 AORC Technical meeting 214 HVDC Circuit Breakers for HVDC Grid Applications K. Tahata, S. Ka, S. Tokoyoda, K. Kamei, K. Kikuchi, D. Yoshida, Y. Kono, R. Yamamoto, H. Ito Mitsubishi
More informationSEL-311C TRANSMISSION PROTECTION SYSTEM
SEL-3C TRANSMISSION PROTECTION SYSTEM ADVANCED TRANSMISSION LINE PROTECTION, AUTOMATION, AND CONTROL Bus ANSI NUMBERS/ACRONYMS AND FUNCTIONS 52 3 3 2 P G 8 O U 27 68 50BF 67 P G Q 50 P G Q 59 P G Q 5 P
More informationNERC Protection Coordination Webinar Series July 15, Jon Gardell
Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),
More informationProtection of Electrical Networks. Christophe Prévé
Protection of Electrical Networks Christophe Prévé This Page Intentionally Left Blank Protection of Electrical Networks This Page Intentionally Left Blank Protection of Electrical Networks Christophe Prévé
More informationPhase Angle Monitoring:
Phase Angle Monitoring: Industry Experience Following the 2011 Pacific Southwest Outage Recommendation 27 Ryan D. Quint, PhD, PE NERC SMS Coordinator NASPI Work Group Meeting October 2016 Background Purpose:
More informationCHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS
86 CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 5.1 POWER QUALITY IMPROVEMENT This chapter deals with the harmonic elimination in Power System by adopting various methods. Due to the
More informationLevel 6 Graduate Diploma in Engineering Electrical Energy Systems
9210-114 Level 6 Graduate Diploma in Engineering Electrical Energy Systems Sample Paper You should have the following for this examination one answer book non-programmable calculator pen, pencil, ruler,
More informationA short introduction to Protection and Automation Philosophy
Training Center A short introduction to Protection and Automation Philosophy Philippe Goossens & Cédric Moors Training Center Contents Definitions and basic concepts Differential and distance protection
More informationPower System Stability. Course Notes PART-1
PHILADELPHIA UNIVERSITY ELECTRICAL ENGINEERING DEPARTMENT Power System Stability Course Notes PART-1 Dr. A.Professor Mohammed Tawfeeq Al-Zuhairi September 2012 1 Power System Stability Introduction Dr.Mohammed
More informationPower Plant and Transmission System Protection Coordination of-field (40) and Out-of. of-step Protection (78)
Power Plant and Transmission System Protection Coordination Loss-of of-field (40) and Out-of of-step Protection (78) System Protection and Control Subcommittee Protection Coordination Workshop Phoenix,
More informationPJM Manual 07:: PJM Protection Standards Revision: 2 Effective Date: July 1, 2016
PJM Manual 07:: PJM Protection Standards Revision: 2 Effective Date: July 1, 2016 Prepared by System Planning Division Transmission Planning Department PJM 2016 Table of Contents Table of Contents Approval...6
More informationA Direct Power Controlled and Series Compensated EHV Transmission Line
A Direct Power Controlled and Series Compensated EHV Transmission Line Andrew Dodson, IEEE Student Member, University of Arkansas, amdodson@uark.edu Roy McCann, IEEE Member, University of Arkansas, rmccann@uark.edu
More informationSSE Offices, Glasgow and Teleconference
DRAFT Minutes Name NETS SQSS Sub-Synchronous Oscillations (SSO) Workgroup Number 3 Date of 28 November 2014 Time 10:00 14:00 Location SSE Offices, Glasgow and Teleconference Attendees Name Role Initials
More informationSequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network
Preface p. iii Introduction and General Philosophies p. 1 Introduction p. 1 Classification of Relays p. 1 Analog/Digital/Numerical p. 2 Protective Relaying Systems and Their Design p. 2 Design Criteria
More informationT/3000 T/3000. Substation Maintenance and Commissioning Test Equipment
T/3000 Substation Maintenance and Commissioning Test Equipment MULTI FUNCTION SYSTEM FOR TESTING SUBSTATION EQUIPMENT SUCH AS: CURRENT, VOLTAGE AND POWER TRANSFORMERS, ALL TYPE OF PROTECTION RELAYS, ENERGY
More informationPower Plant and Transmission System Protection Coordination
Technical Reference Document Power Plant and Transmission System Protection Coordination NERC System Protection and Control Subcommittee Revision 1 July 2010 Table of Contents 1. Introduction... 1 1.1.
More informationHarmonic Design Considerations for Wind Farms
Harmonic Design Considerations for Wind Farms To Ensure Grid Code Compliance Liam Breathnach Power System Studies Group ESB International Agenda Introduction Harmonic Theory and Concepts Grid Code Requirements
More informationCapstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web:
Phone: (818) 734-5300 Fax: (818) 734-5320 Web: www.capstoneturbine.com Technical Reference Capstone MicroTurbine Electrical Installation 410009 Rev F (October 2013) Page 1 of 31 Capstone Turbine Corporation
More informationSystem Protection and Control Subcommittee
Power Plant and Transmission System Protection Coordination Volts Per Hertz (24), Undervoltage (27), Overvoltage (59), and Under/Overfrequency (81) Protection System Protection and Control Subcommittee
More information1
Guidelines and Technical Basis Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive
More informationConsiderations for the Application of Thyristor Controlled Series Capacitors to Radial Power Distribution Circuits
1 Considerations for the Application of Thyristor Controlled Series Capacitors to Radial Power Distribution Circuits M. N. Moschakis, E. A. Leonidaki, Student Member, IEEE, N. D. Hatziargyriou, Senior
More informationAutomated Fault Detection With PQ Monitors
Automated Fault Detection With PQ Monitors Theo Laughner, PE Sr. Program Manager of Power Quality Acknowledgements: Anthony Murphy, PE October 12, 2015 Background Case Studies (5) Needs Tools Conclusion
More informationBabak Enayati National Grid Thursday, April 17
2014 IEEE PES Transmission & Distribution Conference & Exposition Impacts of the Distribution System Renewable Energy Resources on the Power System Protection Babak Enayati National Grid Thursday, April
More informationELECTRICAL POWER ENGINEERING
Introduction This trainer has been designed to provide students with a fully comprehensive knowledge in Electrical Power Engineering systems. The trainer is composed of a set of modules for the simulation
More information