Končar TMS - Bushing monitoring

Size: px
Start display at page:

Download "Končar TMS - Bushing monitoring"

Transcription

1 Končar TMS - Bushing monitoring Many recent studies have shown that bushing failure is one of the most common causes of transformer failure. Thus need for bushing diagnostic and monitoring system has risen. Although, the offline diagnostic gives more accurate and precise insight in bushing insulation state, it is still not common practice for substation maintenance to perform such test very often. Main reason is that it demands transformer outage, well trained personnel and expensive equipment. Koncar TMS bushing monitoring provides insight in bushing insulation state while transformer is online. Developing fault inside bushing now can be detected in very early stage so proper action can be taken to save substation equipment and personnel. Powerful digital signal processor module enables precise measurement of bushing leakage current amplitude and phase angle. By measuring those parameters, relative dissipation factor change ( tan ) and relative capacitance change ( CC0 ) can be estimated. Key features: Bushing capacitance and tanδ monitoring High speed analog input channels Synchronous acquisition Digital signal processing Bushing adapters for various tap design Voltage RMS, Peak measurement Overvoltage detection Frequency and phase measurements

2 Koncar Electrical Engineering Institute Inc. System Architecture: Končar bushing monitoring system is modular system and comes in two versions. Basic system for 3 bushings On-line bushing capacitance and tanδ monitoring for 3 bushings (6 optional) Overvoltage detection Advanced algorithms and analysis tools Built-in additional 8 analog inputs for measuring load current, temperature, humidity, etc. Built-in additional 2 digital outputs for alarm signaling Expandable system up to 6 additional modules On-line bushing capacitance and tanδ monitoring for 3 bushings (optional up to 12 bushings) Overvoltage detection Advanced algorithms and analysis tools Built-in additional 8 analog inputs for measuring load current, temperature, humidity, etc. Built-in additional 2 digital outputs for alarm signaling Expandable system - analog input, analog output, digital input, digital output or RTD module can be added to create complete transformer monitoring system

3 Measurements methods: Končar Bushing monitoring can monitor bushings using 3 methods. Each method has its advantages and disadvantages. Method selection has to be based on measurement requirements, available conditions in substation and budget. Sum-of-phasors Advantages: Simple method Less cabling High sensitivity Disadvantages: Advantages: Network unbalance problems Bushing to Bushing comparison No network unbalance problems Monitors 6 bushings Disadvantages: More cabling Available only if 2 transformers are operating concurrently on same busbar Voltage transformer reference Advantages: Absolute measurement No network unbalance problems Disadvantages: More cabling VTs are usually placed far away from transformer and very often not available

4 How it works: Measuring path of the bushing monitoring system is shown on the figure below. Signal is coupled from test tap of bushing by tap adapter and measuring impedance. Measuring path provides safe connection to the earth, thus preventing appearance of dangerous voltage at the test tap. Several levels of voltage limiting devices are built-in test tap adapter, measuring impedance and TMS cubicle. TAP ADAPTERS Further, signal is connected to DSP (digital signal processor) which measures amplitude and phase angles related to the signals from other bushings or secondary terminal of voltage transformer. In sum-of-phasors method, resultant phasor is calculated from signals of 3 bushings. Changes in capacitance and tan are then calculated from resultant phasor. This technique provides very good sensitivity to changes of tan because relatively small changes in resistive component of leakage current cause big changes in resultant phasor. Bushing-to-bushing comparison method is used for monitoring of 6 bushings for 2 transformers that are operating concurrently on same busbar. While each set of bushing can be monitored independently using sum-of-phasors method, this method gives more information by comparing signals from pair of bushings that are operating on same lineto-earth voltage. Changes in bushing capacitance and tan are calculated from changes in phase angle and amplitudes ratio of leakage currents. If signal from secondary of voltage transformer is available, absolute value of capacitance and tan can be measured by definition. This method provides best results, but often it is not possible to use it because there are no available VTs in substation or they are too far from transformer.

5 Additionally, Koncar Bushing Monitoring can detect peak value of fast overvoltage (including 1.2/50 µs wave) that appears during switching of transformer or atmospheric discharges. During overvoltage event, very fast comparator detects that voltage is out of bounds and activates state-of-the-art peak detector circuit which samples the peak value of overvoltage. Both, positive and negative, peak values of overvoltage can be measured. Typical signal waveform is given below: This information is of great importance because insulation of transformer and bushing can be damaged during those events.

6 Technical specifications: Basic system 3 bushings General Power consumption 25 W Transient overvoltage protection up to 50 V Power supply interruption protection 5 ms Communication protocols: IEC , MODBUS/TCP Power requirements Power supply range Power consumption Physical characteristic Dimensions (HxWxD) Weight V 40 W 150x277x171 mm 1.5 kg Temperature range Operating temperature range -40 to +85 C (IEC 60571:2006, Class Tx) Storage temperature range -40 to +85 C Shock and vibration IEC 61373:2010, Category 1, Class B Electromagnetic compatibility This product meets requirements of the following standards: EN50155:2007 EN :2006 EN :2007 EN :2005 Digital outputs Number of channels 2 Relay type DPDT Min. switching load 100 ma at 12 V Maximum switching capacity AC 1 A at 250 VAC 1 A up to 50 V 0.4 A at 120 V Analog Input Module Number of channels 8 AD resolution 12 bits Frequency range Hz Update rate, all channels 1 ms Input type configurable current or voltage Current 0 30 ma Voltage ±30V Bushing voltage transducer Number of channels 3 Input voltage Vpp Monitored quantities Relative Capacitance change resolution 0.1% Dissipation Factor change resolution 0.05%

7 Technical specifications: Expandable system General Power consumption 25 W Transient overvoltage protection up to 50 V Power supply interruption protection 5 ms Communication protocols: IEC , MODBUS/TCP Power requirements Power supply range Power consumption Physical characteristic Dimensions (HxWxD) Weight V 50 W 150x439x171 mm 3 kg Temperature range Operating temperature range -40 to +85 C (IEC 60571:2006, Class Tx) Storage temperature range -40 to +85 C Shock and vibration IEC 61373:2010, Category 1, Class B Electromagnetic compatibility This product meets requirements of the following standards: EN50155:2007 EN :2006 EN :2007 EN :2005 Digital outputs Number of channels 2 Relay type DPDT Min. switching load 100 ma at 12 V Maximum switching capacity AC 1 A at 250 VAC 1 A up to 50 V 0.4 A at 120 V Analog Input Module Number of channels 8 AD resolution 12 bits Frequency range Hz Update rate, all channels 1 ms Input type configurable current or voltage Current 0 30 ma Voltage ±30V Digital Input Module Number of channels 32 Input range 0-30 V Input current 2.9 ma at 30 V Transient overvoltage 2500 V RMS Digital Output Module Number of channels 8 Relay Type SPDT Maximum switching capacity AC 1 A at 250 VAC 1 A up to 50 V 0.4 A at 120 V RTD module Number of channels 8 Type 4 wire RTD AD resolution 16 bits Update rate, all channels 0.56 s Excitation current 2 ma Data type Temperature ( C) or Resistance (Ω) Monitored quantities Relative Capacitance change resolution 0.1% Dissipation Factor change resolution 0.05%

8 Drawings: Basic system 3 bushings Expandable system with up to 8 additional modules

Fault indicator. Application. SPEF 3A2 C 1MRS MBG Issued: April 1999 Status: Updated Version: B/ Data subject to change without notice

Fault indicator. Application. SPEF 3A2 C 1MRS MBG Issued: April 1999 Status: Updated Version: B/ Data subject to change without notice Issued: April 1999 Status: Updated Version: B/08.11.200 Data subject to change without notice Features Versatile, multifunction line fault indicator for distribution networks Overcurrent, earth-fault and

More information

NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function.

NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function. REGULATION AUTOMATIC SYNCHRONIZER for GENERATOR NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function. NPRG870 adds

More information

NPRG860 NPRG870 REGULATION. Automatic Synchronizer for Generator

NPRG860 NPRG870 REGULATION. Automatic Synchronizer for Generator REGULATION Automatic Synchronizer for Generator NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function. NPRG870 adds

More information

HV / MV / LV electrical network quality analyzers Class A. Communication port: local, modem, integrated Ethernet, multi-point

HV / MV / LV electrical network quality analyzers Class A. Communication port: local, modem, integrated Ethernet, multi-point 2010 MAP Range HV / MV / LV electrical network quality analyzers Class A > Network quality Analyzers PRODUCT ADVANTAGES COMPLIANT with the EN 61000-4-30 standard, Class A DETECTION of the fault LOCATION

More information

ALP-UDR Universal Detection Relay user-defined protection, automation, and monitoring

ALP-UDR Universal Detection Relay user-defined protection, automation, and monitoring ALP-UDR Universal Detection Relay user-defined protection, automation, and monitoring The first Real-Time Protection and Automation platform that can be adapted to a wide variety of applications. While

More information

Specialists in HV and MV test and diagnostics. Testing in Substations

Specialists in HV and MV test and diagnostics. Testing in Substations Specialists in HV and MV test and diagnostics Testing in Substations Testing in Substations Testing in Substations At 4fores we specialize in the diagnosis and measurement of all types of existing technologies

More information

DIFFERENTIAL CURRENT GENERATOR «POCDIF» (AC/DC - 32A - 50V - 12 ranges)

DIFFERENTIAL CURRENT GENERATOR «POCDIF» (AC/DC - 32A - 50V - 12 ranges) PERFORMANCES 12 ranges of AC current from 16 ma to 128 A peak AC permanent current up to 26 ARMS Nine ranges of DC permanent current from 16 ma to 12 A DC current ± 6mA or ± 10 ma stackable to AC current

More information

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment T/3000 Substation Maintenance and Commissioning Test Equipment MULTI FUNCTION SYSTEM FOR TESTING SUBSTATION EQUIPMENT SUCH AS: CURRENT, VOLTAGE AND POWER TRANSFORMERS, ALL TYPE OF PROTECTION RELAYS, ENERGY

More information

Overcurrent Protection / 7SJ45

Overcurrent Protection / 7SJ45 Overcurrent Protection / SJ SIPROTEC easy SJ numerical overcurrent protection relay powered by CTs Fig. / Description SIPROTEC easy SJ numerical overcurrent protection relay powered by current transformers

More information

IN ELECTRICAL ENGINEERING - I C M E T CRAIOVA

IN ELECTRICAL ENGINEERING - I C M E T CRAIOVA Taking into account that power transformer is the major item of equipment in power systems, its correct operation is vital to system operation. It is well known that transformer failures are sometimes

More information

XR1 Rotor Earth Fault Relay. (May 2007) Manual XR1 (Revision New)

XR1 Rotor Earth Fault Relay. (May 2007) Manual XR1 (Revision New) XR1 Rotor Earth Fault Relay (May 2007) Manual XR1 (Revision New) Woodward Manual XR1 GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information provided

More information

DRTS 66 The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

DRTS 66 The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Manual

More information

I P. /dt. di p V S Applications. Standards 1) IEC : 2007; IEC : ) IEC : 2016; IEC : 2017

I P. /dt. di p V S Applications. Standards 1) IEC : 2007; IEC : ) IEC : 2016; IEC : 2017 Ref: ART-B22-D70, ART-B22-D125, ART-B22-D175, ART-B22-D300 Flexible clip-around Rogowski coil for the electronic measurement of AC current with galvanic separation between the primary circuit (power) and

More information

Monitoring Solutions For Power Transformers, Reactors, Bushings and Instrument Transformers

Monitoring Solutions For Power Transformers, Reactors, Bushings and Instrument Transformers in cooperation with Monitoring Solutions For Power Transformers, Reactors, Bushings and Instrument Transformers BZ-MS/1 pazifik power Complete Transformer Monitoring System (TMS) ZVCM-1001 Bushing Monitoring

More information

I P I OUT R L. Applications. Standards. N 52.D ; Page 1/8

I P I OUT R L. Applications. Standards. N 52.D ; Page 1/8 Ref: ATO-10-B225-D10/SP3 r = 10 A ATO series is a split core current transformer for the electronic measurement of AC waveform current with galvanic separation between the primary circuit (power) and the

More information

Appendix A: Specifications

Appendix A: Specifications All specifications apply to the TDS 200-Series Digital Oscilloscopes and a P2100 probe with the Attenuation switch set to 10X unless noted otherwise. To meet specifications, two conditions must first be

More information

1 INTRODUCTION ORDER CODE / INFORMATION

1 INTRODUCTION ORDER CODE / INFORMATION INTRODUCTION ORDER CODE / INFORMATION 269/269Plus * * * * * * 269/269Plus SV D/O.4 ORDER CODE / INFORMATION Motor management relay Standard version Drawout version Phase CT Ground CT (required for D/O

More information

Advanced Test Equipment Rentals ATEC (2832) CP RC. Resonance circuit for GIS testing

Advanced Test Equipment Rentals ATEC (2832) CP RC. Resonance circuit for GIS testing Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) CP RC Resonance circuit for GIS testing A new approach to testing gas-insulated switchgear Testing gas-insulated switchgear

More information

TRAX Transformer and Substation Test System

TRAX Transformer and Substation Test System Replaces need for multiple test sets Saves time by eliminating need for multiple instruments learning User-friendly interface reduces training and testing time Portable and compact system components for

More information

TRAX Transformer and Substation Test System

TRAX Transformer and Substation Test System TRAX Replaces need for multiple test sets Saves time by eliminating need for multiple instruments learning User-friendly interface reduces training and testing time Portable and compact system components

More information

N acquisitions, all channels simultaneously, N is selectable from 4, 16, 64, and 128 Inputs

N acquisitions, all channels simultaneously, N is selectable from 4, 16, 64, and 128 Inputs With compliments All specifications apply to the TDS 200-Series Digital Real-Time Oscilloscope with a P2100 probe with the Attenuation switch set to 10X unless noted otherwise. To meet specifications,

More information

08/07/2015

08/07/2015 17.5 mm - 1 Solid State Relay 0.7A MUS2 Part number 88827004 Multi-function or mono-function Multi-range Multi-voltage Screw or spring terminals LED status indicator (relay version) Possibility of external

More information

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime Issued: 5.06.999 Status: 5.06.999 Version: B/09..00 Data subject to change without notice Features Overvoltage and undervoltage protection Single- or three-phase operation High-set overvoltage stage with

More information

38 Series - Relay interface modules A. Features /

38 Series - Relay interface modules A. Features / Series - Relay interface modules 0.1-2 - 6-8 A Features 1 Pole - 6 A electromechanical relay interface modules, 6.2 mm wide. Ideal interface for PLC and electronic systems Sensitive DC coil or coil versions

More information

A DUMMIES GUIDE TO GROUND FAULT PROTECTION

A DUMMIES GUIDE TO GROUND FAULT PROTECTION A DUMMIES GUIDE TO GROUND FAULT PROTECTION A DUMMIES GUIDE TO GROUND FAULT PROTECTION What is Grounding? The term grounding is commonly used in the electrical industry to mean both equipment grounding

More information

A New Approach for Transformer Bushing Monitoring. Emilio Morales Technical Application Specialist Qualitrol

A New Approach for Transformer Bushing Monitoring. Emilio Morales Technical Application Specialist Qualitrol A New Approach for Transformer Bushing Monitoring Emilio Morales Technical Application Specialist Qualitrol Abstract Transformer bushings are one of the most critical components of a transformer. Up to

More information

AC/DC Current Probe GCP-100 QUICK START GUIDE ISO-9001 CERTIFIED MANUFACTURER

AC/DC Current Probe GCP-100 QUICK START GUIDE ISO-9001 CERTIFIED MANUFACTURER AC/DC Current Probe GCP-100 QUICK START GUIDE ISO-9001 CERTIFIED MANUFACTURER This manual contains proprietary information, which is protected by copyright. All rights are reserved. No part of this manual

More information

REK 510 Current injection device for earth-fault protection of a synchronous machine rotor. User s Manual

REK 510 Current injection device for earth-fault protection of a synchronous machine rotor. User s Manual REK 50 protection of a synchronous machine User s Manual REK 50 X 0 9 8 7 6 5 4 0 V 00 V 0 V 5 6 7 Ordering No: REK 50-AA Uau = 00/0 Vac Un = 48 V Serial No: fn = 50/60 Hz Uec = ma 600 Vdc MRS 75587-MUM

More information

XR1 Rotor Earth Fault Relay. Manual XR1 (Revision C)

XR1 Rotor Earth Fault Relay. Manual XR1 (Revision C) XR1 Rotor Earth Fault Relay Manual XR1 (Revision C) Woodward Manual XR1 (EN) Woodward Governor Company reserves the right to update any portion of this publication at any time. Information provided by

More information

D7F. Detects Changes in Machine. Vibration. Vibration Sensor with Linear Output or Manual Setting. Ordering Information

D7F. Detects Changes in Machine. Vibration. Vibration Sensor with Linear Output or Manual Setting. Ordering Information with Linear Output or Manual Setting Detects Changes in Machine ON/OFF output can be set and checked quickly and easily from the vibration level meter. waveforms can be checked using the AC monitor output.

More information

TRAX Transformer and Substation Test System

TRAX Transformer and Substation Test System TRAX Replaces need for multiple test sets Saves time by eliminating need for multiple instruments learning User-friendly interface reduces training and testing time Portable and compact system components

More information

BUS2000 Busbar Differential Protection System

BUS2000 Busbar Differential Protection System BUS2000 Busbar Differential Protection System Differential overcurrent system with percentage restraint protection 1 Typical Busbar Arrangements Single Busbar Double Busbar with Coupler Breaker and a Half

More information

SINEAX I 503 / SINEAX U 504 Transducer for AC current or AC voltage

SINEAX I 503 / SINEAX U 504 Transducer for AC current or AC voltage Application The transducers SINEAX I 503/U 504 (Figs. 1 and 2) are designed to convert a sinusoidal AC current or voltage into a load independent DC signal proportional to the measured value. This output

More information

Installation and Operating Instructions. Power IT Power Factor Controller RVC

Installation and Operating Instructions. Power IT Power Factor Controller RVC Installation and Operating Instructions Power IT Power Factor Controller RVC Table of contents Page 1. Read this first... 3 About this Instruction Manual... 3 Safety... 3 Electromagnetic compatibility...

More information

SPAE 010, 011 High Impedance Protection Relay

SPAE 010, 011 High Impedance Protection Relay SPAE 010, 011 High Impedance Protection Relay User s manual and Technical description f n = 50/60 Hz U n = 50 / 100 / 200 V 2 5 U REF > SPAE 010 0.8 U aux 0.6 1.0 RESET OK x 80... 265 V ~ _ 0.4 U > U n

More information

SIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay

SIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay Overcurrent Protection / 7SJ46 SIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay Function overview Fig. /11 Description The SIPROTEC easy 7SJ46 is a numerical overcurrent protection relay which

More information

MT 560/UMT TRANSDUCER & ANALYZER

MT 560/UMT TRANSDUCER & ANALYZER MT 560/UMT 560 - TRANSDUCER & ANALYZER USE The MT 560/UMT 560 multi transducer and analyzer is used for a permanent analysis of electricity supply quality in compliance with the SIST EN 50160 standard.

More information

8588A Reference Multimeter

8588A Reference Multimeter 8588A Reference Multimeter Product Specifications March 2019 Rev. A 2019 Fluke Corporation. All rights reserved. Specifications are subject to change without notice. All product names are trademarks of

More information

Ariadna CI MV & LV cable identifier

Ariadna CI MV & LV cable identifier Ariadna CI MV & LV cable identifier In electrical maintenance works, in order to cope with safety standards, it becomes necessary to identify de-energized cables unambiguously prior to its manipulation.

More information

Module 2 : Current and Voltage Transformers. Lecture 8 : Introduction to VT. Objectives. 8.1 Voltage Transformers 8.1.1Role of Tuning Reactor

Module 2 : Current and Voltage Transformers. Lecture 8 : Introduction to VT. Objectives. 8.1 Voltage Transformers 8.1.1Role of Tuning Reactor Module 2 : Current and Voltage Transformers Lecture 8 : Introduction to VT Objectives In this lecture we will learn the following: Derive the equivalent circuit of a CCVT. Application of CCVT in power

More information

Power systems Protection course

Power systems Protection course Al-Balqa Applied University Power systems Protection course Department of Electrical Energy Engineering 1 Part 5 Relays 2 3 Relay Is a device which receive a signal from the power system thought CT and

More information

I P. /dt. di p V S+ Applications. Standards. 1) IEC ed1.0: 2007; IEC : ed1.0: 2012

I P. /dt. di p V S+ Applications. Standards. 1) IEC ed1.0: 2007; IEC : ed1.0: 2012 Ref: ART-B22-D70, ART-B22-D125, ART-B22-D175 Flexible clip-around Rogowski coil for the electronic measurement of AC current with galvanic separation between the primary circuit (power) and the secondary

More information

Application for A Sub-harmonic Protection Relay. ERLPhase Power Technologies

Application for A Sub-harmonic Protection Relay. ERLPhase Power Technologies Application for A Sub-harmonic Protection Relay ERLPhase Power Technologies 1 Outline Introduction System Event at Xcel Energy Event Analysis Microprocessor based relay hardware architecture Sub harmonic

More information

Automatic Transformer Winding Analyser

Automatic Transformer Winding Analyser 2293 Automatic Transformer Winding Analyser The 2293 is an automatic winding analyser, optimized for three phase power and distribution transformer measurements. It uniquely combines winding resistance

More information

DM1200ID. Specification highlights Symbol Unit Min Typ Max. Applications: Features. Power measurement and power analysis

DM1200ID. Specification highlights Symbol Unit Min Typ Max. Applications: Features. Power measurement and power analysis Ultra-stable, high precision (ppm class) fluxgate technology DM Series current transducer for non-intrusive, isolated DC and AC current measurement up to 1500A Features Ø45mm aperture enabling large isolated

More information

DeltaV SIS Logic Solver

DeltaV SIS Logic Solver DeltaV SIS Process Safety System Product Data Sheet September 2017 DeltaV SIS Logic Solver World s first smart SIS Logic Solver Integrated, yet separate from the control system Easy compliance with IEC

More information

Autotransformer Condition Monitoring Systems

Autotransformer Condition Monitoring Systems Autotransformer Condition Monitoring Systems The Bidders shall offer separately the following systems of par.1 Integrated Condition Monitoring System and par.2 UHF PD Monitoring System. Two systems following

More information

Transformer differential protection

Transformer differential protection Transformer differential protection Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice (SE970883) Features Three phase differential protection with two, three, five or

More information

Earth fault protection for isolated neutral systems with frequency converters

Earth fault protection for isolated neutral systems with frequency converters Earth fault protection for isolated neutral systems with frequency converters Page Issued June 999 Changed since July 998 Data subject to change without notice (SE97089) Features Earth fault and flash-over

More information

PART NUMBERING SYSTEM

PART NUMBERING SYSTEM Plug-In Timer pins Multifunction or monofunction Compact body for space saving Wide time range (from 0. seconds to 0 days delay) niversal power supply (-0 Vz) or relay outputs (SPDT / Changeover) Protective

More information

RE17LLBM asymmetrical flashing relay s V AC - solid state output

RE17LLBM asymmetrical flashing relay s V AC - solid state output Characteristics asymmetrical flashing relay - 0.1..1 s - 24..240 V AC - solid state output Product availability : Non-Stock - Not normally stocked in distribution facility Price* : 75.00 USD Main Range

More information

Fixed Series Compensation

Fixed Series Compensation Fixed Series Compensation High-reliable turnkey services for fixed series compensation NR Electric Corporation The Fixed Series Compensation (FSC) solution is composed of NR's PCS-9570 FSC control and

More information

N. TEST TEST DESCRIPTION

N. TEST TEST DESCRIPTION Multi function system for testing substation equipment such as: current, voltage and power transformers, over-current protection relays, energy meters and transducers Primary injection testing capabilities

More information

DIFFERENTIAL CURRENT GENERATOR «POCDIF» (AC/DC - 32A - 50V - 12 ranges)

DIFFERENTIAL CURRENT GENERATOR «POCDIF» (AC/DC - 32A - 50V - 12 ranges) PERFORMANCES 12 ranges of AC current from 16 ma to 128 A peak AC permanent current up to 26 ARMS Nine ranges of DC permanent current from 16 ma to 12 A DC current ± 6mA or ± 10 ma stackable to AC current

More information

DS10000ULFS-10V/10kA

DS10000ULFS-10V/10kA Ultra-stable, high precision (ppm class) fluxgate technology DS Series current transducer for non-intrusive, isolated DC and AC current measurement up to 11kA Features Linearity error maximum +/- 7ppm

More information

SWT 3000 Teleprotection technical data siemens.com

SWT 3000 Teleprotection technical data siemens.com Power network telecommunication SWT 3000 Teleprotection technical data siemens.com Sustainable success for high-voltage power networks The SWT 3000 Teleprotection system has been the first choice for reliable

More information

Theta 20A / 20V. Technical Data Sheet. Special Features

Theta 20A / 20V. Technical Data Sheet. Special Features Technical Data Sheet Theta 20A / 20V Theta 20A / 20V is used to measure and convert AC Voltage or Current input into a load independent DC current or voltage output signal. Special Features Available in

More information

CP CU1. Coupling unit for line and ground testing

CP CU1. Coupling unit for line and ground testing CP CU1 Coupling unit for line and ground testing Line and ground test system CPC 100 The CPC 100 is a multifunctional test set for primary assets. When combined with the CP CU1 it covers the following

More information

IDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODEL:

IDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODEL: IDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODEL: 61-352 The Service Information provides the following information: Precautions and safety information Specifications Basic maintenance (cleaning, replacing

More information

Harmonic restraint earth fault or single-phase overcurrent protection

Harmonic restraint earth fault or single-phase overcurrent protection Harmonic restraint earth fault or single-phase overcurrent protection Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice (SE970885) Features Sensitive earth fault protection

More information

Maximum power. Nominal voltage. Operating temperature 0 to 50ºC. Humidity without condensation 5 95 % Contamination level 2 Current input features

Maximum power. Nominal voltage. Operating temperature 0 to 50ºC. Humidity without condensation 5 95 % Contamination level 2 Current input features s Features Portable power analyzer for three-phase and single-phase electrical networks with simultaneous measurement of leakage current, power quality and recording of transients. is the best tool for

More information

EN 50178, IEC

EN 50178, IEC Type: DF51 322 1K5 Article No.: 289107 Sales text """Frequency inverter DF51(1,5 kw; 230V) Ordering information Rated voltage U e V Max. rated operational current I e A 7.1 Rated power for motors at 230

More information

5069 Compact I/O Modules Specifications

5069 Compact I/O Modules Specifications Technical Data 5069 Compact I/O Modules Specifications Digital I/O Module Catalog Numbers 5069-IB16, 5069-IB16F, 5069-IB6F-3W, 5069-OB16, 5069-OB16F, 5069-OW4I, 5069-OX4I Analog I/O Module Catalog Numbers

More information

8558A 8 1/2 Digit Multimeter

8558A 8 1/2 Digit Multimeter 8558A 8 1/2 Digit Multimeter Product Specifications March 2019 Rev. A 2019 Fluke Corporation. All rights reserved. Specifications are subject to change without notice. All product names are trademarks

More information

Zelio Control Measurement Relays

Zelio Control Measurement Relays Selection Guide Application Voltage control Current control Functions 3-phase Single-phase and d.c. Integrated current transformer - Overvoltage and between phases - Overvoltage and between phases and

More information

N. TEST TEST DESCRIPTION

N. TEST TEST DESCRIPTION Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy meters and transducers Primary injection testing capabilities

More information

Residual Current Operated Circuit-Breakers (RCCBs)

Residual Current Operated Circuit-Breakers (RCCBs) Product Overview Residual Current Operated Circuit-Breakers (RCCBs) Residual current operated circuit-breakers Number of poles Rated current A Rated residual current ma MW Auxiliary contacts can be mounted

More information

C.A Complete electrical network analysis at the tips of your fingers! Power Quality Monitor. Keeping up with the standards

C.A Complete electrical network analysis at the tips of your fingers! Power Quality Monitor. Keeping up with the standards Keeping up with the standards C.A 8352 Power Quality Monitor Complete electrical network analysis at the tips of your fingers! All measurements for complete analysis: powers, harmonics, flicker, symmetry,

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Current Transducer ITL 4000-S I PN = 4000 A For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. I > 0 P Features Closed

More information

RE17RAMU on-delay timing relay - 1 s..100 h V AC - 1 OC

RE17RAMU on-delay timing relay - 1 s..100 h V AC - 1 OC Characteristics on-delay timing relay - 1 s..100 h - 24..240 V AC - 1 OC Main Range of product Product or component type Discrete output type Width Device short name Time delay type Time delay range Nominal

More information

Temperature Input Module for Zone 1 Series 9482/32

Temperature Input Module for Zone 1 Series 9482/32 www.stahl.de > 8 channels for temperature sensors > Intrinsically safe inputs Ex ia > For Pt-, Ni- and Cu-resistance temperature detectors according to DIN, IEC and GOST in 2-, 3- and 4-wire circuits >

More information

General Specifications

General Specifications General Specifications MODEL UT50L Limit Controller GS 5DD-0E Overview The UT50L is an FM approved limit controller that can be configured either as a high limit or as a low limit controller by a user.

More information

RE17RCMU off-delay timing relay - 1 s..100 h V AC - 1 OC

RE17RCMU off-delay timing relay - 1 s..100 h V AC - 1 OC Characteristics off-delay timing relay - 1 s..100 h - 24..240 V AC - 1 OC Main Range of product Product or component type Discrete output type Width Device short name Time delay type Time delay range Nominal

More information

QUINT-PS-24DC/24DC/10

QUINT-PS-24DC/24DC/10 QUINT-PS-24/24/10 QUINT - converter, primary switched mode, input: 24 V, output: 24 V /10 A INTERFACE Data Sheet PHOENIX CONTACT - 02/2006 Description The QUINT - converter 24 V/10 A converts the voltage

More information

Device Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L.

Device Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L. /9 TECHNICAL SPECIFICATIONS VOLTAGE LOW-POWER TRANSFORMER VS- Rev. Date Revision Description Prepared by Checked by Approved by 0 24/09/2 First issue A. Peretto L. Peretto 24/06/6 All text review E. Scala

More information

I Pr I P I OUT R L. Applications. Standards

I Pr I P I OUT R L. Applications. Standards Ref: ATO-XXX-B225-D10 I Pr = 10, 15, 16, 20, 30, 32, 50, 60, 63, 75 A ATO series is a split core current transformer for the electronic measurement of AC waveform current with galvanic separation between

More information

10/2 Product overview. 10/3 4AC3 0, 4AC3 1 bell transformers. 10/5 4AC AC3 6 transformers for permanent loads. 10/8 4AC2 4 power supply units

10/2 Product overview. 10/3 4AC3 0, 4AC3 1 bell transformers. 10/5 4AC AC3 6 transformers for permanent loads. 10/8 4AC2 4 power supply units BETA Switching Transformers, Bells and Socket Outlets /2 Product overview /3 4AC3 0, 4AC3 1 bell transformers /5 4AC3 4... 4AC3 transformers for permanent loads /8 4AC2 4 power supply units / 7LQ2 2 bells

More information

WIRELESS INSULATOR POLLUTION MONITORING SYSTEM

WIRELESS INSULATOR POLLUTION MONITORING SYSTEM SYSTEM OVERVIEW Pollution monitoring of high voltage insulators in electrical power transmission and distribution systems, switchyards and substations is essential in order to minimise the risk of power

More information

satech SynchroStar GPS 200 Series

satech SynchroStar GPS 200 Series satech SynchroStar GPS 200 Series KEY BENEFITS Designed with high quality oscillator OCXO the device is characterized by superior frequency stability and improved holdover performance that allows maintaining

More information

08/07/2015

08/07/2015 17.5 mm - 1 Relay 8A MUR1 Part number 88827105 Multi-function or mono-function Multi-range Multi-voltage Screw or spring terminals LED status indicator (relay version) Possibility of external load connection

More information

Time over/underfrequency relay with protection assemblies

Time over/underfrequency relay with protection assemblies Time over/underfrequency relay with protection assemblies RXFK 2H and RAFK 509 009-BEN Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice (SE970104) (SE970108) Features

More information

Fluke 83V and 87V Digital Multimeters

Fluke 83V and 87V Digital Multimeters Fluke 83V and 87V Digital Multimeters Detailed Specifications For all detailed specifications: is given as ±([% of reading] + [number of least significant digits]) at 18 C to 28 C, with relative humidity

More information

PCB MOUNT SOLID STATE RELAY ESR2 SERIES

PCB MOUNT SOLID STATE RELAY ESR2 SERIES PCB MOUNT SOLID STATE RELAY ESR2 SERIES E155181(R) FEATURES PCB Mount; Single in Line Package. Optically Isolated. Input LED Indicator. High dv/dt and High Blocking Voltage. Low Input Power Consumption,

More information

RIGOL. User s Guide. RP1000D Series High Voltage Differential Probe. Feb RIGOL Technologies, Inc

RIGOL. User s Guide. RP1000D Series High Voltage Differential Probe. Feb RIGOL Technologies, Inc User s Guide RP1000D Series High Voltage Differential Probe Feb. 2013 RIGOL Technologies, Inc Guaranty and Declaration Copyright 2012 RIGOL Technologies, Inc. All Rights Reserved. Trademark Information

More information

Current clamps for AC current

Current clamps for AC current Current clamps for AC current "C100" series The "C100" series is a range of thirteen transformer clamps with all the advantages of our old "C30" series clamps whilst incorporating considerable improvements,

More information

SINEAX U 553 Transducer for AC Voltage

SINEAX U 553 Transducer for AC Voltage With power supply RMS value measurement Carrying rail housing P/0 Application he transducer SINEAX U 55 (Fig. ) converts a sinusoidal or a distorted AC voltage into a load independent DC current or a load

More information

presentation contents application advantages

presentation contents application advantages presentation contents page presentation protection functional and connection schemes other connection schemes connection characteristics 9 installation 0 commissioning ordering information Sepam 00 is

More information

For ultra-high precision measurement of current: DC, AC, pulsed..., with galvanic separation between primary and secondary. Applications.

For ultra-high precision measurement of current: DC, AC, pulsed..., with galvanic separation between primary and secondary. Applications. Current Transducer IT 700-SB ULTRASTAB I PM = 700 A For ultra-high precision measurement of current: DC, AC, pulsed..., with galvanic separation between primary and secondary. Features ± 10 V voltage output

More information

Model Number Structure. Ordering Information. Solid-state Power OFF-delay Timer H3DE-H. Model Number Legend. List of Models

Model Number Structure. Ordering Information. Solid-state Power OFF-delay Timer H3DE-H. Model Number Legend. List of Models Solid-state Power OFF-delay Timer H3DE-H Timers Two delay-time models available. 0.1 to 12 seconds (S Series) 1 to 120 seconds (L Series) Covers wide range of supply voltage. Model Number Structure Model

More information

DRTS-6. DRTS-6 has been designed to test: DRTS-6. Advanced Protection Relay Test Set and Measurement System

DRTS-6. DRTS-6 has been designed to test: DRTS-6. Advanced Protection Relay Test Set and Measurement System DRTS-6 Advanced Protection Relay Test Set and Measurement System MULTI-TASKING EQUIPMENT DESIGNED FOR TESTING PROTECTION RELAYS, ENERGY METERS, TRANSDUCERS POWERFUL AND LIGHTWEIGHT HIGH ACCURACY: BETTER

More information

Measuring Transducer MT4xx series Programmable AC Current Transducer MT418

Measuring Transducer MT4xx series Programmable AC Current Transducer MT418 Measuring Transducer MT4xx series Programmable AC Current Transducer MT418 o RMS AC current or frequency measurements o Current auto range measurements up to 12 A o Frequency measurement range 16 400 Hz

More information

T108, GPS/GLONASS/BEIDOU Time Server

T108, GPS/GLONASS/BEIDOU Time Server T108, GPS/GLONASS/BEIDOU Time Server Galileo (Europe) and QZSS (Japan) ready NTP Time server / Multi-GNSS Primary Clock, with PoE and advanced I/O synchronization features. - Static applications - HEOL-T108:

More information

PLC-K506 Series FEATURES DESCRIPTION FEATURES

PLC-K506 Series FEATURES DESCRIPTION FEATURES FEATURES Two High Speed Counters Two Pulse Train Outputs Two Pulse Width Modulation Outputs Inputs 10 Outputs 1 RS232 Port 2 RS485 Ports Supports Modbus RTU Protocol Communicate With Up to 32 Devices DESCRIPTION

More information

AUTOMOTIVE CURRENT TRANSDUCER OPEN LOOP TECHNOLOGY HAH1DR 200-S

AUTOMOTIVE CURRENT TRANSDUCER OPEN LOOP TECHNOLOGY HAH1DR 200-S AUTOMOTIE CURRENT TRANSDUCER OPEN LOOP TECHNOLOGY HAHDR 2-S Introduction The HAHDR family is for the electronic measurement of DC, AC or pulsed currents in high power automotive applications with galvanic

More information

PART NUMBERING SYSTEM

PART NUMBERING SYSTEM Plug-In Timer 11 pins Multifunction or monofunction Compact body for space saving Wide time range (from 0.5 seconds to 10 days delay) Universal power supply (12-240 Vz) 1 or 2 relay outputs (SPDT / Changeover)

More information

CMC 256plus - protection relay test set and universal calibrator

CMC 256plus - protection relay test set and universal calibrator Technical Data - protection relay test set and universal calibrator The is the universal solution for testing old and new generation relays and calibrating all kinds of meters, PQ devices and transducers.

More information

MINI-PS AC/24DC/1.3

MINI-PS AC/24DC/1.3 Power supply unit INTERFACE Data sheet 102894_en_03 1 Description PHOENIX CONTACT 2015-11-17 Features MINI POWER power supplies for MCR technology In measurement and control technology (MCR), modular electronics

More information

For ultra-high precision measurement of current: DC, AC, pulsed..., with galvanic separation between primary and secondary. Applications.

For ultra-high precision measurement of current: DC, AC, pulsed..., with galvanic separation between primary and secondary. Applications. Current Transducer IT 700-S ULTRASTAB I PM = 700 A For ultra-high precision measurement of current: DC, AC, pulsed..., with galvanic separation between primary and secondary. Features Closed loop (compensated)

More information

High Performance Current Transducer ITL 900-T = A

High Performance Current Transducer ITL 900-T = A High Performance Current Transducer ITL 900-T For the electronic measurement of currents: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. I PM = 0... 900 A Electrical

More information

Transformer and generator time-overexcitation relay and protection assemblies RXLK 2H and RALK

Transformer and generator time-overexcitation relay and protection assemblies RXLK 2H and RALK Transformer and generator time-overexcitation relay and protection assemblies RXLK 2H and RALK (RXLK_2H.tif) RALK.psd Features Micro-processor based time-overexcitation relay with continuous settings for

More information