1 On-line partial discharge monitoring of statorwindings : comparison of different sensors Pemen, A.J.M.; Leeuw, de, W.; van der Laan, P.C.T. Published in: Proceedings of the 1th International Symposium on High Voltage Engineering, volume 4, Montreal, Quebec, Canada, August 1997 Published: 1/1/1997 Document Version Publisher s PDF, also known as Version of Record (includes final page, issue and volume numbers) Please check the document version of this publication: A submitted manuscript is the author's version of the article upon submission and before peer-review. There can be important differences between the submitted version and the official published version of record. People interested in the research are advised to contact the author for the final version of the publication, or visit the DOI to the publisher's website. The final author version and the galley proof are versions of the publication after peer review. The final published version features the final layout of the paper including the volume, issue and page numbers. Link to publication General rights Copyright and moral rights for the publications made accessible in the public portal are retained by the authors and/or other copyright owners and it is a condition of accessing publications that users recognise and abide by the legal requirements associated with these rights. Users may download and print one copy of any publication from the public portal for the purpose of private study or research. You may not further distribute the material or use it for any profit-making activity or commercial gain You may freely distribute the URL identifying the publication in the public portal? Take down policy If you believe that this document breaches copyright please contact us providing details, and we will remove access to the work immediately and investigate your claim. Download date: 2. Aug. 218
2 ISH '97
3 describe the measurement technique, by means of an example of a measurement on a 65 MW turbine generator. 2. Measurement technique Unfortunately, for the monitoring of pd's during regular operation, standard pd-detectors can not be used. The main reason for this is the presence of many sources of EM-disturbances in a power plant. Standard pd-detectors operate in a frequency range < 1 MHz. Within this range large interference is caused by the rotor excitation. In [1] we show that this problem can be solved by using a tunable narrow-bandwidth filter as a front-end for a standard detector. The filter is tuned to a frequency where partial discharges dominate and no interference is present. Our experience is that the best results are obtained at tuning-frequencies between 1 and 3 MHz. As a tunable narrow-bandwidth filter we use a spectrumanalyser in the "zero-span" mode. The output of the spectrumanalyser is connected to a modem pd-detector (Haefely TE571). This detector provides a digital registration of all pd quantities, such as the discharge magnitude, the time of occurrence as related to the 5 Hz voltage, the instantaneous inception voltage, the discharge energy and the quadratic rate. The results can be shown in many ways, as 2 and 3D patterns or pulse-height histograms. Also the detector has built in tools for recognition and classification of pd patterns [2]. Figure 1 shows a result measured in phase " 1" of the 65 MW generator "Hemweg-8". During the measurement the generator was operating at full load. The spectrum analyser is tuned to 2 MHz. The figure shows the phase resolved distributions HQmax (the maximum discharge magitude), HQn (the mean discharge magnitude) and H,. (the number of discharges). After calculating and storing a 'fingerprint' of 29 statistical parameters, the measurement can be classified. This means that the result is correlated with a database, which can contain fingerprints of: (i) earlier measurements on the same generator, (ii) measurements on similar generators, (iii) known defects and (iv) known ageing states. Figure 2 gives the classification of the measurement in Fig.I ("KWARTAAL 4/FASE 1") with reference to an earlier measurement on the same generator ("KWARTAAL 3/FASE 1 "). The correlation between the two measurements is nearly 1 %, which means that the discharge pattern has not changed. 3. Comparison of different sensors An important part of a pd measuring system is the sensor. For the measurements in the previous Section we used Rogowski-coils, installed around the high-voltage terminals of the generator. Besides Rogowski-coils, we developed capacitive sensors that are housed inside a standard support-insulator of the isolate-12hase-hus (ipb) (Fig.3). Both sensors are described in [4] and have a good sensitivity, bandwidth, EMC-properties and can easily be installed. Recently, we installed capacitive sensors in the new 165 MW turbine generator "Roca-3 ". For each phase, two sensors are installed, one at the generator side and one at the step-up transformer side. Besides the capacitive sensors, in each phase two other capacitors were available: "ring" capacitors and overvoltage capacitors. The "ring" capacitors are shown in Fig.3c. A metal ring (35 cm. wide) is installed inside the ipb. The ring is isolated from the metal ipb and connected to a N-connector. The overvoltage capacitors are installed inside the enclosure of the generator-circuit-breaker (Fig.4a). The equivalent circuit for all three sensor types is given in Fig.4b. The capacitance values are given in Table 1. Table 1 values for the three sensor types sensor Cl C2 R capacitive sensor 25 pf 1 pf 5 ring capacitor 16 pf 182 pf 5 overvoltage capacitor 132 nf 8 µf 5 (s) (b) (c) Fig.3 (a) Isolated phase-bus (ipb), with (b) a capacitive sensor inside a support insulator, and (c) a nng -capacitor inside the ipb (a) Enclosure of the generator-circuit-breaker Overvoltage capacitor (b) j_ :~tg Fig.4 (a) Overvoltage capacitor house inside the coaxial enclosure of the generator-circuit-breaker, and (b) equivalent circuit for capacitive sensors
4 Figure 5 gives the frequency spectra as recorded in phase W, with a capacitive sensor, a ring capacitor and a overvoltage capacitor. It is clear that the capacitive sensor has the best sensitivity, while the sensitivity of the overvoltage capacitor is the lowest. The spectra show several peaks caused by partial discharges. These peaks are a result of resonances in the statorwinding or reflections of the signal in the ipb. Preferably, for discharge measurements the spectrum analyser is tuned to one of these peaks and an important question is to which peak. To find the best tuning frequency, for each sensor a serie of zero-span measurements is done. Measurements are done at 3 different tuning frequencies (from 1 to 7 MHz, with an interval of 2 MHz) and the signal level at these tuning frequencies is recorded during several cycles of the 5 Hz voltage. The best results for phase U are given in Fig.6. For all sensors the best tuning frequency is 1 or 12 MHz. At these frequencies, the sensors have the largest sensitivity and no interference is recorded. As can be seen, the capacitive sensor at the generator side Cg has the largest sensitivity, but also the other sensor types give good results. -5 E' Cx:i ~-6 l S? -7-8 : ;~ - - capacitive sensor -- 'ring' sensor ovsrvoltage capacitor frequency (MHz) Fig.5 Frequency spectra as measured in phase W of generator #Roca-3 #, by means of J different sensors 6 G ~ -2 (.) 2 ~ -2 toot -1~=[ =======~. _.,,...,.,., 2 4 time (ns) Fig.7 Waveshapes of a partial discharge in phase V of generator # Roca-3 #' measured simultaneous with 4 different sensors Figure 7 gives the waveshapes of a partial discharge in phase V, measured simultaneously with all 4 sensors in this phase. From the transit times.1tl and.1t2 it is seen that this signal comes from the generator. In case of a discharge in the step-up transformer, the signal would first show up at sensor Ct. So installing 2 or more sensors in one phase enables the localisation of a discharge. The transit time.1tl is 42 ns (or 12.7 m) and corresponds with the distance between the capacitive sensor at the generator side Cg and the overvoltage capacitor OV-C. The transit time.1t2 is 44 ns (or 13.3 m) and corresponds with the distance between the overvoltage capacitor OV-C and the capacitive sensor at the step-up transformer side Ct. The distance between the ring capacitor and the capacitive sensor at the generator side Cg is 3 cm, and the corresponding transit time of 1 ns cannot be seen in Fig. 7. As with the spectrumanalyser measurements, the capacitive sensor at the generator side Cg gives the largest signal. This signal of about 25 m V can easily be detected with a digital oscilloscope. However, the signals from the ring capacitor and the overvoltage capacitor have an amplitude of about 2 m V and already show bit-noise. These amplitudes are close to the limit of what can be detected with an oscilloscope. This shows a great advantage of the spectrumanalyser: a much larger sensitivity so that small signals can be detected reliably. T 4. Discussion The results in the previous section show that, although the capacitive sensors have the largest sensitivity, all three sensor types can be used for on-line partial discharge measurements. The measurements can be done with a spectrumanalyser tuned to a frequency where partial discharges
5 dominate and less interference is present. This interference has two ways of distorting a measurement: (i) by coupling into the measuring system, and (ii) by coupling into the statorwinding. Coupling into the measuring system must be avoided by state of the art EMC measures [7]. For the measurements in the previous section, all sensor types have good EMC-properties and are shielded by the ipb or by the enclosure of the generator-circuit-breaker. All connectors and coax-cables have a low transferimpedance and the recording equipment is installed in an EMC-cabinet. Coupling of interference into the statorwinding causes 'legitimate' signals at the sensors, but can be rejected by tuning to the correct frequency. This tuning technique is not effective when interference couples into the measuring system, as we noticed during measurements on turbine generator "Claus-B". Here the overvoltage capacitors are installed in cabinets outside the ipb, and have long leads to the ipb and the grounding. system of the plant. A magnetic flux <I> can couple into the large loop (about 6 m 2 ) formed. This magnetic flux <I> can be a restilt from any source and results in an interference voltage v. = -d<i>/dt. Figure 8 gives the results for measurements in phase U of generator "Claus-B", for tuning frequencies of 1, 2 and 3 MHz. At all frequencies (also at 12 other tuning frequencies between 5 and 4 MHz) interference is recorded. However, off-line measurements show large discharge levels upto 5 nc. The discharges are caused by cracks in the endwindings. The cracks are a result of vibrations of the end-windings due to loose blockings. After consulting the manufacturer it was decided to rewind the generator. Surprisingly, the on-line measurements gave no indications for the presence of large partial discharges, since interference dominated the measurements. This proves that it is very important to suppress interference as much as possible, preferably by good EMC-measures. The use of a tunable narrow-bandwidth filter (or signal processing) in itself are not enough to reject interference and can only be used for further improvement. 5. Conclusions Several sensor types (capacitive sensors, overvoltage capacitors and "ring" capacitors) were used for partial discharge measurements on a 165 MW turbine generator. The discharges were recorded with a standard pd-detector, preceeded by a tunable narrow-bandwidth filter. The filter is tuned to a frequency where discharges dominate and less interference is present. All three sensor types give good results at tuning frequencies of 1 or 12 MHz; the best sensitivity is obtained with capacitive sensors. Good EMC-measures are of major importance for online pd-measurements. On-line measurements on poorly installed (from an EMC point of view) overvoltage capacitors of a 58 MW generator only showed interference, while off-line measurements showed large discharges of >5 nc time (ms) Fig.8 On-line measurement with a over-voltage capacitor, installed outside the isolated-phase-bus of the 58 MW turbine generator "Claus-B" Acknowledgements: this research was undertaken at request of the Dutch electric supply companies. The authors gratefully acknowledge the cooperation of EPON, EPZ, EZH and UNA. The contribution of the working group "Generator railsystemen'' is very much appreciated. References (1) A.J.M. Pemen, P.C.T. van der Laan: "Pitfalls of pd measurements on statorwindings of turbine generators", 7th DMMA, Bath, UK, September 1996, pp (2) E. Guiski: "Digital analysis of partial discharges", IEEE Trans.on Dielectrics and Electrical Insulation, Vol.2, No.5, October 1995, pp (3] H.G. Sedding, S.R. Campbell. G.C. Stone, G.S. Klempner: "A new on-line partial discharge test for turbine generators", IEEE Trans.on Energy Conversion, Vol.6, No.I, December 1991, pp [4] A.J.M. Pemen, P.C.T. van der Laan, P.T.M. Vaessen: "Sensors for pd monitoring of turbo generators", 28th UPEC, Staffordshire, UK, September 1993, pp [5] J.E. Timperley: "Incipient fault identification through neutral rf monitoring of large rotating machines", IEEE Trans.PAS, Vol.PAS-12, No.3, March 1983, pp (6) P. Grunewald, J. Weidner: "Possibilities and experience with off- and on-line diagnosis of turbine generator stator winding insulation", 1994 CIGRE Session, paper 11-26, Paris, 1994 [7] P.C.T. van der Laan, A.P.J. van Deursen: "Protection of electronics in high power installations; theory, guidelines and demonstrations", CIGRE Symposium on EMC, Lausanne 1993, paper 6-8 Adresses of authors KEMA Transmission & Distribution P.O. Box 935, 68 ET Arnhem, The Netherlands phone fax Eindhoven Univ. of Technology, High-Voltage & EMC group P.O. Box 513, 56 MB Eindhoven, The Netherlands phone , fax
Directional Sensing for Online PD Monitoring of MV Cables Wagenaars, P.; van der Wielen, P.C.J.M.; Wouters, P.A.A.F.; Steennis, E.F.
Directional Sensing for Online PD Monitoring of MV Cables Wagenaars, P.; van der Wielen, P.C.J.M.; Wouters, P.A.A.F.; Steennis, E.F. Published in: Nordic Insulation Symposium, Nord-IS 05 Published: 01/01/2005
More informationPropagation of partial discharge signals in stator windings of turbine generators Pemen, A.J.M.; van der Laan, P.C.T.; Leeuw, de, W.
Propagation of partial discharge signals in stator windings of turbine generators Pemen, A.J.M.; van der Laan, P.C.T.; Leeuw, de, W. Published in: IEEE Transactions on Energy Conversion DOI: 10.1109/TEC.2005.847949
More informationPARTIAL DISCHARGE MEASUREMENTS ON GENERATORS USING A NOISE GATING SYSTEM
Abstract PARTIAL DISCHARGE MEASUREMENTS ON GENERATORS USING A NOISE GATING SYSTEM Q. SU Department of Electrical & Computer Systems Engineering Monash University, Clayton VIC 3168 Email: qi.su@eng.monash.edu.au
More informationIRIS POWER TGA-B. Periodic Online Partial Discharge Monitoring Instrument for Turbine Generators and Motors
IRIS POWER TGA-B Periodic Online Partial Discharge Monitoring Instrument for Turbine Generators and Motors We have not found another test method that produces as much decision support data for generator
More informationDocument Version Publisher s PDF, also known as Version of Record (includes final page, issue and volume numbers)
Noise figure and S-parameter measurement setups for on-wafer differential 60GHz circuits Sakian Dezfuli, P.; Janssen, E.J.G.; Essing, J.A.J.; Mahmoudi, R.; van Roermund, A.H.M. Published in: Proceedings
More informationKnowledge Is Power SM Apparatus Maintenance and Power Management for Energy Delivery. Application of EMI Diagnostics to Hydro Generators
Knowledge Is Power SM Apparatus Maintenance and Power Management for Energy Delivery Application of EMI Diagnostics to Hydro Generators James Timperley Doble Global Power Services Columbus, Ohio jtimperley@doble.com
More informationRelative Ability of UHF Antenna and VHF Capacitor Methods to Detect Partial Discharge in Turbine Generator Stator Windings
IEEE Transactions on Dielectrics and Electrical Insulation Vol. 22, No. 6; December 215 369 Relative Ability of UHF Antenna and VHF Capacitor Methods to Detect Partial Discharge in Turbine Generator Stator
More informationA 13.56MHz RFID system based on organic transponders
A 13.56MHz RFID system based on organic transponders Cantatore, E.; Geuns, T.C.T.; Gruijthuijsen, A.F.A.; Gelinck, G.H.; Drews, S.; Leeuw, de, D.M. Published in: Proceedings of the IEEE International Solid-State
More informationDBR based passively mode-locked 1.5m semiconductor laser with 9 nm tuning range Moskalenko, V.; Williams, K.A.; Bente, E.A.J.M.
DBR based passively mode-locked 1.5m semiconductor laser with 9 nm tuning range Moskalenko, V.; Williams, K.A.; Bente, E.A.J.M. Published in: Proceedings of the 20th Annual Symposium of the IEEE Photonics
More informationInvesti ations Into the Use of Temperature Detectors as # tator Winding Partial Discharge Detectors
Conference Record of the 2006 IEEE International Symposium on Electrical Insulation Investi ations Into the Use of Temperature Detectors as # tator Winding Partial Discharge Detectors S.R. Campbell, G.C.
More informationOn-chip antenna integration for single-chip millimeterwave FMCW radars Adela, B.B.; Pual, P.T.M; Smolders, A.B.
On-chip antenna integration for single-chip millimeterwave FMCW radars Adela, B.B.; Pual, P.T.M; Smolders, A.B. Published in: Proceedings of the 2015 9th European Conference on Antennas and Propagation
More informationPlanar circularly symmetric EBG's to improve the isolation of array elements Llombart, N.; Neto, A.; Gerini, G.; de Maagt, P.J.I.
Planar circularly symmetric EBG's to improve the isolation of array elements Llombart, N.; Neto, A.; Gerini, G.; de Maagt, P.J.I. Published in: Proceedings of the 2005 IEEE Antennas and Propagation Society
More informationStrathprints Institutional Repository
Strathprints Institutional Repository Given, M and Mason, Ronald and Judd, Martin and Mcglone, Phillip and Timoshkin, Igor and Wilson, Mark () Comparison between RF and electrical signals from the partial
More informationDocument Version Publisher s PDF, also known as Version of Record (includes final page, issue and volume numbers)
A 2V Iductorless Receiver Front-End for Multi-Standard Wireless Applications Vidojkovic, V; Sanduleanu, MAT; van der Tang, JD; Baltus, PGM; van Roermund, AHM Published in: IEEE Radio and Wireless Symposium,
More informationPressure estimation in vacuum circuit breakers
Pressure estimation in vacuum circuit breakers Damstra, G.C.; Smeets, R.P.P.; Poulussen, H.B.F. Published in: EEE Transactions on Dielectrics and Electrical nsulation DO: 10.1109/94.388240 Published: 01/01/1995
More informationPartial discharge diagnostics on very long and branched cable circuits
11 Nordic Insulation Symposium Stockholm, June 11-13, 2001 Partial discharge diagnostics on very long and branched cable circuits Nico van Schaik, E. Fred Steennis, Wim Boone and Dick M. van Aartrijk KEMA
More informationResonances in Collection Grids of Offshore Wind Farms
Downloaded from orbit.dtu.dk on: Dec 20, 2017 Resonances in Collection Grids of Offshore Wind Farms Holdyk, Andrzej Publication date: 2013 Link back to DTU Orbit Citation (APA): Holdyk, A. (2013). Resonances
More informationIRIS POWER PDTracII. Continuous On-line Partial Discharge Monitoring for Motors, Generators, Dry Type Transformers, and Air-Insulated Switchgear.
IRIS POWER PDTracII Continuous On-line Partial Discharge Monitoring for Motors, Generators, Dry Type Transformers, and Air-Insulated Switchgear. We have not found another test method that produces as much
More informationThe University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge
The University of New South Wales School of Electrical Engineering and Telecommunications High Voltage Systems ELEC9712 Appendix Partial Discharge Content Introduction Quantities measured Test circuits
More informationNon resonant slots for wide band 1D scanning arrays
Non resonant slots for wide band 1D scanning arrays Bruni, S.; Neto, A.; Maci, S.; Gerini, G. Published in: Proceedings of 2005 IEEE Antennas and Propagation Society International Symposium, 3-8 July 2005,
More informationCMOS based terahertz instrumentation for imaging and spectroscopy Matters - Kammerer, M.
CMOS based terahertz instrumentation for imaging and spectroscopy Matters - Kammerer, M. Published in: Proceedings of the International conference on Technology and instrumentation in particle physics
More informationIRIS POWER PDTracII. Continuous On-line Partial Discharge Monitoring for Motors, Generators, Dry Type Transformers, and Air-Insulated Switchgear.
IRIS POWER PDTracII Continuous On-line Partial Discharge Monitoring for Motors, Generators, Dry Type Transformers, and Air-Insulated Switchgear. We have not found another test method that produces as much
More informationA novel output transformer based highly linear RF-DAC architecture Bechthum, E.; Radulov, G.I.; Briaire, J.; Geelen, G.; van Roermund, A.H.M.
A novel output transformer based highly linear RF-DAC architecture Bechthum, E.; Radulov, G.I.; Briaire, J.; Geelen, G.; van Roermund, A.H.M. Published in: Proceedings of the 2st European Conference on
More informationVoltage dip detection with half cycle window RMS values and aggregation of short events Qin, Y.; Ye, G.; Cuk, V.; Cobben, J.F.G.
Voltage dip detection with half cycle window RMS values and aggregation of short events Qin, Y.; Ye, G.; Cuk, V.; Cobben, J.F.G. Published in: Renewable Energy & Power Quality Journal DOI:.484/repqj.5
More informationA NOVEL APPROACH TO PARTIAL DISCHARGE MONITORING
A NOVEL APPROACH TO PARTIAL DISCHARGE MONITORING Dr. Simon Higgins Sustainability Division Eskom SOC Ltd (South Africa) Mr. André Tétreault Tests & Diagnostics Division VibroSystM, Inc. (Canada) ABSTRACT
More informationPROPAGATION OF PARTIAL DISCHARGE AND NOISE PULSES IN TURBINE GENERATORS
PROPAGATION OF PARTIAL DISCHARGE AND NOISE PULSES IN TURBINE GENERATORS M. Henriksen, Technical University of Denmark, DK-2800 Lyngby, Denmark G.C. Stone, M. Kurtz, Ontario Hydro, 800 Kipling Avenue, Toronto,
More informationTwo octaves bandwidth passive balun for the eleven feed for reflector antennas Zamanifekri, A.; Yang, J.
Two octaves bandwidth passive balun for the eleven feed for reflector antennas Zamanifekri, A.; Yang, J. Published in: Proceedings of 2010 IEEE International Symposium on Antennas and Propagation, Toronto,
More informationSystem grounding of wind farm medium voltage cable grids
Downloaded from orbit.dtu.dk on: Apr 23, 2018 System grounding of wind farm medium voltage cable grids Hansen, Peter; Østergaard, Jacob; Christiansen, Jan S. Published in: NWPC 2007 Publication date: 2007
More informationPartial Discharge Monitoring and Diagnosis of Power Generator
Partial Discharge Monitoring and Diagnosis of Power Generator Gao Wensheng Institute of High Voltage & insulation tech. Electrical Eng. Dept., Tsinghua University Wsgao@tsinghua.edu.cn Currently preventive
More informationPartial discharge trends in medium voltage cables measured while in-service with PDOL Cuppen, A.N.; Steennis, E.F.; van der Wielen, P.C.J.M.
Partial discharge trends in medium voltage cables measured while in-service with PDOL Cuppen, A.N.; Steennis, E.F.; van der Wielen, P.C.J.M. Published in: Proceedings of the IEEE PES Transmission and Distribution
More informationCharacteristics of Insulation Diagnosis and Failure in Gas Turbine Generator Stator Windings
J Electr Eng Technol Vol. 9, No. 1: 280-285, 2014 http://dx.doi.org/10.5370/jeet.2014.9.1.280 ISSN(Print) 1975-0102 ISSN(Online) 2093-7423 Characteristics of Insulation Diagnosis and Failure in Gas Turbine
More informationEFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento
Sept. 22-24, 28, Florence, Italy EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS C. Ceretta, R. Gobbo, G. Pesavento Dept. of Electrical Engineering University of
More informationPD Solutions. On-Line PD Measurement Devices
On-Line PD Measurement Devices 1. Longshot Device (see Figure 1) The measurement system applied is based around the wideband (0-400 MHz) HVPD- Longshot partial discharge test unit which utilizes a high-speed
More informationA multi-band single-loop PLL frequency synthesizer with dynamically-controlled switched tuning VCO Samuel, A.M.; Pineda de Gyvez, J.
A multi-band single-loop PLL frequency synthesizer with dynamically-controlled switched tuning VCO Samuel, A.M.; Pineda de Gyvez, J. Published in: Proceedings of the 43rd IEEE Midwest Symposium on Circuits
More informationThe Game Experience Questionnaire
The Game Experience Questionnaire IJsselsteijn, W.A.; de Kort, Y.A.W.; Poels, K. Published: 01/01/2013 Document Version Publisher s PDF, also known as Version of Record (includes final page, issue and
More informationDocument Version Publisher s PDF, also known as Version of Record (includes final page, issue and volume numbers)
A 40 GHz, broadband, highly linear amplifier, employing T-coil bandwith extension technique Cheema, H.M.; Mahmoudi, R.; Sanduleanu, M.A.T.; van Roermund, A.H.M. Published in: IEEE Radio Frequency Integrated
More informationIEEE (2016) (2016). IEEE.,
Corr, Edward and Siew, W. H. and Zhao, Weijia (16) Long term testing and analysis of dielectric samples under DC excitation. In: IEEE Electrical Insulation Conference (16). IEEE., This version is available
More informationAalborg Universitet. MEMS Tunable Antennas to Address LTE 600 MHz-bands Barrio, Samantha Caporal Del; Morris, Art; Pedersen, Gert F.
Aalborg Universitet MEMS Tunable Antennas to Address LTE 6 MHz-bands Barrio, Samantha Caporal Del; Morris, Art; Pedersen, Gert F. Published in: 9th European Conference on Antennas and Propagation (EuCAP),
More informationNJ. ISBN (2017) , /URSIGASS
Jaber, A. and Lazaridis, P. and Saeed, B. and Mather, P. and Vieira, M. F. Q. and Atkinson, R. and Tachtatzis, C. and Iorkyase, E. and Judd, M. and Glover, I. A. (2017) Diagnostic potential of free-space
More informationObjective Methods to Interpret Partial-Discharge Data on Rotating-Machine Stator Windings
Objective Methods to Interpret Partial-Discharge Data on Rotating-Machine Stator Windings Greg C. Stone, Fellow, IEEE, and Vicki Warren, Member, IEEE From IEEE Transactions on Industry Applications Vol.
More informationCalibration of current-steering D/A Converters
Calibration of current-steering D/A Converters Citation for published version (APA): Radulov,. I., Quinn, P. J., Hegt, J. A., & Roermund, van, A. H. M. (2009). Calibration of current-steering D/A Converters.
More informationA 100MHz CMOS wideband IF amplifier
A 100MHz CMOS wideband IF amplifier Sjöland, Henrik; Mattisson, Sven Published in: IEEE Journal of Solid-State Circuits DOI: 10.1109/4.663569 1998 Link to publication Citation for published version (APA):
More informationPropagation of Partial Discharge and Noise Pulses in Turbine Generators
Downloaded from orbit.dtu.dk on: Jul 10, 2018 Propagation of Partial Discharge and Noise Pulses in Turbine Generators Henriksen, Mogens; Stone, G. C.; Kurtz, M. Published in: I E E E Transactions on Energy
More informationRegarding RF Isolation for small Enclosures
Regarding RF Isolation for small Enclosures IEEE electromagnetic society and IEEE standard board has published standards for measuring the shielding effectiveness (SE) of chambers. The measurement methods
More informationPublished in: Proceedings of the 20th Annual Symposium of the IEEE Photonics Benelux Chapter, November 2015, Brussels, Belgium
A Si3N4 optical ring resonator true time delay for optically-assisted satellite radio beamforming Tessema, N.M.; Cao, Z.; van Zantvoort, J.H.C.; Tangdiongga, E.; Koonen, A.M.J. Published in: Proceedings
More informationThe half-bridge SiC-MOSFET switching cell : implementation in a three phase motor drive Baskurt, F.; Boynov, K.; Lomonova, E.
The half-bridge SiC-MOSFET switching cell : implementation in a three phase motor drive Baskurt, F.; Boynov, K.; Lomonova, E. Published: 01/01/2017 Document Version Accepted manuscript including changes
More informationExtended analysis versus frequency of partial discharges phenomena, in support of quality assessment of insulating systems
Extended analysis versus frequency of partial discharges phenomena, in support of quality assessment of insulating systems Romeo C. Ciobanu, Cristina Schreiner, Ramona Burlacu, Cristina Bratescu Technical
More informationThe current distribution on the feeding probe in an air filled rectangular microstrip antenna
Downloaded from orbit.dtu.dk on: Mar 28, 2019 The current distribution on the feeding probe in an air filled rectangular microstrip antenna Brown, K Published in: Antennas and Propagation Society International
More informationTrees, vegetation, buildings etc.
EMC Measurements Test Site Locations Open Area (Field) Test Site Obstruction Free Trees, vegetation, buildings etc. Chamber or Screened Room Smaller Equipments Attenuate external fields (about 100dB) External
More informationDiagnostic testing of cast resin transformers
Paper of the Month Diagnostic testing of cast resin transformers Author Michael Krüger, OMICRON, Austria michael.krueger@omiconenergy.com Christoph Engelen, OMICRON, Austria christoph.engelen@omicronenergy.com
More informationA1-209 EXPERIENCES IN IDENTIFICATION OF PARTIAL DISCHARGE PATTERNS IN LARGE HYDROGENERATORS
21, rue d'artois, F-75008 Paris http://www.cigre.org A1-209 Session 2004 CIGRÉ EXPERIENCES IN IDENTIFICATION OF PARTIAL DISCHARGE PATTERNS IN LARGE HYDROGENERATORS CARLOS AZUAJE* WILLIAM TORRES C.V.G.
More informationCONTINUOUS ON-LINE SYSTEM FOR PARTIAL DISCHARGE MONITORING FOR HA1 AT CHE ROBEŞTI
U.P.B. Sci. Bull., Series D, Vol. 77, Iss. 4, 2015 ISSN 1454-2358 CONTINUOUS ON-LINE SYSTEM FOR PARTIAL DISCHARGE MONITORING FOR HA1 AT CHE ROBEŞTI Laurenţiu-Florian ION 1, Apolodor GHEORGHIU 2 A proper
More informationIEC Electrical fast transient / Burst immunity test
CONDUCTED RF EQUIPMENT POWER AMPLIFIERS IEC 61000-4-4 Electrical fast transient / Burst immunity test IEC 61000-4-4 Electrical fast transient / Burst immunity test Markus Fuhrer Phenomenom open a contact
More informationMeasurement and Analysis for Switchmode Power Design
Measurement and Analysis for Switchmode Power Design Switched Mode Power Supply Measurements AC Input Power measurements Safe operating area Harmonics and compliance Efficiency Switching Transistor Losses
More informationMEDIUM & HIGH VOLTAGE
MEDIUM & HIGH VOLTAGE TESTING EQUIPMENT VOLTAGE WITHSTAND SGM Series Resonant Systems The SGM series are used for generating high AC voltages at a fixed frequency (mainly 50 or 60 Hz) by means of an excited
More informationSIMULATION of EMC PERFORMANCE of GRID CONNECTED PV INVERTERS
SIMULATION of EMC PERFORMANCE of GRID CONNECTED PV INVERTERS Qin Jiang School of Communications & Informatics Victoria University P.O. Box 14428, Melbourne City MC 8001 Australia Email: jq@sci.vu.edu.au
More informationInharmonicity of wound guitar strings
Inharmonicity of wound guitar strings Houtsma, A.J.M. Published in: Journal of Guitar Acoustics Published: 01/01/1982 Document Version Publisher s PDF, also known as Version of Record (includes final page,
More informationTHE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE
THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE Z.Liu, B.T.Phung, T.R.Blackburn and R.E.James School of Electrical Engineering and Telecommuniications University of New South Wales
More informationCHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN
75 CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN 5.1 INTRODUCTION Partial Discharge (PD) detection is an important tool for monitoring insulation conditions in high voltage (HV) devices in power systems.
More informationA Waveguide Transverse Broad Wall Slot Radiating Between Baffles
Downloaded from orbit.dtu.dk on: Aug 25, 2018 A Waveguide Transverse Broad Wall Slot Radiating Between Baffles Dich, Mikael; Rengarajan, S.R. Published in: Proc. of IEEE Antenna and Propagation Society
More informationDevelopment of methods for numerical error correction of machine tools : interim report no. 2 Spaan, H.A.M.; Schellekens, P.H.J.
Development of methods for numerical error correction of machine tools : interim report no. 2 Spaan, H.A.M.; Schellekens, P.H.J. Published: 01/01/1990 Document Version Publisher s PDF, also known as Version
More informationSENSITIVITY ASPECTS OF ON-LINE PD DIAGNOSIS OF MV POWER CABLES
SENSITIVITY ASPECTS OF ON-LINE PD DIAGNOSIS OF MV POWER CABLES Frank WESTER, Edward GULSKI, Johan SMIT, Edwin GROOT*, Mark VAN VLIET* Delft University of Technology The Netherlands * NUON The Netherlands
More informationCompact microstrip bandpass filter with tunable notch
Downloaded from orbit.dtu.dk on: Feb 16, 2018 Compact microstrip bandpass filter with tunable notch Christensen, Silas; Zhurbenko, Vitaliy; Johansen, Tom Keinicke Published in: Proceedings of 2014 20th
More informationUnderstanding and Optimizing Electromagnetic Compatibility in Switchmode Power Supplies
Understanding and Optimizing Electromagnetic Compatibility in Switchmode Power Supplies 1 Definitions EMI = Electro Magnetic Interference EMC = Electro Magnetic Compatibility (No EMI) Three Components
More informationPulsed corona for breaking up air bubbles in water
Pulsed corona for breaking up air bubbles in water van Heesch, E.J.M.; Lemmens, R.H.P.; Franken, B.F.C.; Ptasinski, K.J.; Geurts, F.L.S. Published in: IEEE Transactions on Dielectrics and Electrical Insulation
More informationCONDITION MONITORING OF MEDIUM VOLTAGE ELECTRICAL CABLES BY MEANS OF PARTIAL DISCHARGE MEASUREMENTS
136 CONDITION MONITORING OF MEDIUM VOLTAGE ELECTRICAL CABLES BY MEANS OF PARTIAL DISCHARGE MEASUREMENTS H. van Jaarsveldt* and R. Gouws** School of Electrical, Electronic and Computer Engineering, North-West
More informationLeaky-wave slot array antenna fed by a dual reflector system Ettorre, M.; Neto, A.; Gerini, G.; Maci, S.
Leaky-wave slot array antenna fed by a dual reflector system Ettorre, M.; Neto, A.; Gerini, G.; Maci, S. Published in: Proceedings of IEEE Antennas and Propagation Society International Symposium, 2008,
More informationCharacteristic mode based pattern reconfigurable antenna for mobile handset
Characteristic mode based pattern reconfigurable antenna for mobile handset Li, Hui; Ma, Rui; Chountalas, John; Lau, Buon Kiong Published in: European Conference on Antennas and Propagation (EuCAP), 2015
More informationPORTABLE PARTIAL DISCHARGE MONITORING INSTRUMENT
PORTBLE PRTIL ISCHRGE MONITORING INSTRUMENT Periodic Online Monitoring of Partial ischarges on motors, generators, switchgear, isolated phase bus and dry type transformers. MOTORS TURBO GENERTORS HYRO
More informationElectromagnetic Compatibility
Electromagnetic Compatibility Introduction to EMC International Standards Measurement Setups Emissions Applications for Switch-Mode Power Supplies Filters 1 What is EMC? A system is electromagnetic compatible
More informationA Literature Review: PD Signal Propagation in Stator Windings, and its effect on PD Calibration.
A Literature Review: PD Signal Propagation in Stator Windings, and its effect on PD Calibration. Nathaniel Taylor, ETK, KTH February 2008 Contents 1 Background Details 2 1.1 Background to PD measurement................................
More informationExperimental modal analysis of an automobile tire under static load
Experimental modal analysis of an automobile tire under static load Citation for published version (APA): Pieters, R. S. (2007). Experimental modal analysis of an automobile tire under static load. (DCT
More informationRTD as a Valuable Tool in Partial Discharge Measurements on Rotating Machines
RTD as a Valuable Tool in Partial Discharge Measurements on Rotating Machines Z. Berler, I. Blokhintsev, A. Golubev, G. Paoletti, A. Romashkov Cutler Hammer Predictive Diagnostics Abstract: This paper
More informationEMI Filters Demystified. By William R. Bill Limburg February 21, 2018 Phoenix Chapter, IEEE EMC Society
EMI Filters Demystified By William R. Bill Limburg February 21, 2018 Phoenix Chapter, IEEE EMC Society An EMI Filter Defined An EMI filter is a network designed to prevent unwanted electrical conducted
More informationSlot waveguide microring modulator on InP membrane
Andreou, S.; Millan Mejia, A.J.; Smit, M.K.; van der Tol, J.J.G.M. Published in: Proceedings of the 20th Annual Symposium of the IEEE Photonics Benelux Chapter, 26-27 November 2015, Brussels, Belgium Published:
More informationSoftware for Partial Discharge and Localization
48 PIERS Proceedings, Taipei, March 25 28, 2013 Software for Partial Discharge and Localization M. Cap, P. Drexler, P. Fiala, and R. Myska Department of Theoretical and Experimental Electrical Engineering
More informationHeavy-Duty High-Repetition-Rate Generators
IEEE TRANSACTIONS ON PLASMA SCIENCE, VOL. 30, NO. 5, OCTOBER 2002 1627 Heavy-Duty High-Repetition-Rate Generators E. J. M. van Heesch, K. Yan, and A. J. M. Pemen, Member, IEEE Abstract We present our recent
More informationLightning transient analysis in wind turbine blades
Downloaded from orbit.dtu.dk on: Aug 15, 2018 Lightning transient analysis in wind turbine blades Candela Garolera, Anna; Holbøll, Joachim; Madsen, Søren Find Published in: Proceedings of International
More informationSensors for in-flight lightning detection on aircraft
Sensors for in-flight lightning detection on aircraft Stelmashuk, V.; van Deursen, A.P.J.; Webster, M. Published in: Electromagnetic Compatibility - EMC Europe, 2008 International Symposium, 8-12 Sept.
More informationGENERATOR TESTING APPLICATION GUIDE. reliable. precision.
GENERATOR TESTING APPLICATION GUIDE www.haefely-hipotronics.com reliable. precision. 2 GENERATOR TESTING CONTENTS Product Line Overview 3 AC Hipot Testing 4 Partial Discharge Measurement 5 DC Hipot Testing
More informationFurther Experience in the Use of Existing RTDs in Windings of Motors and Generators for the Measurement of Partial Discharges
Further Experience in the Use of Existing RDs in Windings of Motors and Generators for the Measurement of Partial Discharges Claude Kane Eaton Electrical Predicative Diagnostics 5421 Feltl Road Suite 190
More informationAalborg Universitet. Linderum Electricity Quality - Measurements and Analysis Silva, Filipe Miguel Faria da; Bak, Claus Leth. Publication date: 2013
Aalborg Universitet Linderum Electricity Quality - Measurements and Analysis Silva, Filipe Miguel Faria da; Bak, Claus Leth Publication date: 3 Document Version Publisher's PDF, also known as Version of
More informationA triple-mode continuous-time sigma delta modulator with switched-capacitor feedback DAC for a GSM- EDGE/CDMA2000/UMTS Receiver van Veldhoven, R.H.M.
A triple-mode continuous-time sigma delta modulator with switched-capacitor feedback DAC for a GSM- EDGE/CDMA2000/UMTS Receiver van Veldhoven, R.H.M. Published in: IEEE Journal of Solid-State Circuits
More informationDistance Protection of Cross-Bonded Transmission Cable-Systems
Downloaded from vbn.aau.dk on: April 19, 2019 Aalborg Universitet Distance Protection of Cross-Bonded Transmission Cable-Systems Bak, Claus Leth; F. Jensen, Christian Published in: Proceedings of the 12th
More informationPublished in: Proceedings of the 10th International Conference on Power Quality and Utilization (EPQU 2009), Lodz, Poland
Harmonic current interaction at a low voltage customer's installations Bhattacharyya, S.; Myrzik, J.M.A.; Kling, W.L.; Cobben, J.F.G.; Casteren, van, J. Published in: Proceedings of the 10th International
More informationStudy of High Voltage AC Underground Cable Systems Silva, Filipe Miguel Faria da; Bak, Claus Leth; Wiechowski, Wojciech T.
Aalborg Universitet Study of High Voltage AC Underground Cable Systems Silva, Filipe Miguel Faria da; Bak, Claus Leth; Wiechowski, Wojciech T. Published in: Proceedings of the Danish PhD Seminar on Detailed
More informationDocument Version Publisher s PDF, also known as Version of Record (includes final page, issue and volume numbers)
Effect of cable load impedance on coupling schemes for MV power line communication Wouters, P.A.A.F.; van der Wielen, P.C.J.M.; Veen, J.; Wagenaars, P.; Steennis, E.F. Published in: IEEE Transactions on
More informationELECTROMAGNETIC COMPATIBILITY HANDBOOK 1. Chapter 8: Cable Modeling
ELECTROMAGNETIC COMPATIBILITY HANDBOOK 1 Chapter 8: Cable Modeling Related to the topic in section 8.14, sometimes when an RF transmitter is connected to an unbalanced antenna fed against earth ground
More informationSelf-Resonant Electrically Small Loop Antennas for Hearing-Aids Application
Downloaded from orbit.dtu.dk on: Jul 5, 218 Self-Resonant Electrically Small Loop Antennas for Hearing-Aids Application Zhang, Jiaying; Breinbjerg, Olav Published in: EuCAP 21 Publication date: 21 Link
More informationPARTIAL DISCHARGE MEASUREMENT ON ROTATING MACHINES
PARTIAL DISCHARGE MEASUREMENT ON ROTATING MACHINES Engr. IÑIGO V. ESCOPETE, JR. ITC Level 2 Certified Thermographer PHIL-NCB NDT-UT Level 2 Partial Discharge testing is a Condition Based Maintenance tool
More informationIJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 04, 2014 ISSN (online):
IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 04, 2014 ISSN (online): 2321-0613 Conditioning Monitoring of Transformer Using Sweep Frequency Response for Winding Deformation
More informationFlexible AC current probes
Flexible AC current probes Making use of the principle of Rogowski coils, the MiniFLEX models are flexible sensors offering a wide dynamic range for measuring AC intensities and viewing high-speed current
More informationPERMANENT ON-LINE MONITORING OF MV POWER CABLES BASED ON PARTIAL DISCHARGE DETECTION AND LOCALISATION AN UPDATE
PERMANENT ON-LINE MONITORING OF MV POWER CABLES BASED ON PARTIAL DISCHARGE DETECTION AND LOCALISATION AN UPDATE Fred STEENNIS, KEMA, (the Netherlands), fred.steennis@kema.com Peter VAN DER WIELEN, KEMA,
More informationSignal and Noise Measurement Techniques Using Magnetic Field Probes
Signal and Noise Measurement Techniques Using Magnetic Field Probes Abstract: Magnetic loops have long been used by EMC personnel to sniff out sources of emissions in circuits and equipment. Additional
More informationThis is an author-deposited version published in : Eprints ID : 18192
Open Archive TOULOUSE Archive Ouverte (OATAO) OATAO is an open access repository that collects the work of Toulouse researchers and makes it freely available over the web where possible. This is an author-deposited
More informationTECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets
TECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets Who we are TECHIMP is one of the leading providers of Condition Assessment Services Data Acquisition and Test Equipment
More informationBeyond the switch: explicit and implicit interaction with light Aliakseyeu, D.; Meerbeek, B.W.; Mason, J.; Lucero, A.; Ozcelebi, T.; Pihlajaniemi, H.
Beyond the switch: explicit and implicit interaction with light Aliakseyeu, D.; Meerbeek, B.W.; Mason, J.; Lucero, A.; Ozcelebi, T.; Pihlajaniemi, H. Published in: 8th Nordic Conference on Human-Computer
More informationElectrical Power Engineering Group, School of Electronics and Computer Science, University of Southampton, Highfield, Southampton, SO17 1BJ, UK 2
Tsinghua University, Beijing, China, August 5-9, 5 G-3 Application of Superluminescent Light Emitting Diode to Electrooptic Modulator Based PD Continuous On-line Monitoring System Y Tian *, P L Lewin,
More informationCMOS Current-mode Operational Amplifier
Downloaded from orbit.dtu.dk on: Aug 17, 2018 CMOS Current-mode Operational Amplifier Kaulberg, Thomas Published in: Proceedings of the 18th European Solid-State Circuits Conference Publication date: 1992
More informationLog-periodic dipole antenna with low cross-polarization
Downloaded from orbit.dtu.dk on: Feb 13, 2018 Log-periodic dipole antenna with low cross-polarization Pivnenko, Sergey Published in: Proceedings of the European Conference on Antennas and Propagation Link
More information