Partial Discharge Monitoring and Diagnosis of Power Generator

Size: px
Start display at page:

Download "Partial Discharge Monitoring and Diagnosis of Power Generator"

Transcription

1 Partial Discharge Monitoring and Diagnosis of Power Generator Gao Wensheng Institute of High Voltage & insulation tech. Electrical Eng. Dept., Tsinghua University

2 Currently preventive maintenance is widely used. But it is carried out off-line. The shortcoming is as follows: Be carried out at de-energized status. However, it is difficult for most power equipment to stop the operation in normal condition. Be carried out periodically. But it is still possible for power equipment to initiate fault during the testing intervals. -4-

3 Sometimes it is not necessary to make the test and maintenance of equipment between regular intervals. The waste is tremendous. The equipment condition when power is off does not reflect the insulating condition truly, thus the identifying accuracy will be influenced. In the traditional PD test, the test voltage possibly can create new fault in power generator. -5-

4 Condition Based Maintenance Insulating performance Condition monitoring Fault diagnosis Maintenance suggestion -6-

5 Partial Discharge Partial Discharge is a discharge in a gas-filled void or on a dielectric surface. Partial discharges are the major cause of progressive failures in HV insulation and have drastic effects on the ageing process of HV generator resulting in early breakdown. -7-

6 Partial discharge (PD) important phenomenon Generators / transformers large capacity Affect of faults much more serious Great attention operational reliability Insulation faults possess a great part -8-

7 Partial Discharge Monitoring A discharge monitoring system for successful early detection of power generator breakdown. It is an essential task in modern asset management of power system. -9-

8 Equipment On-line monitoring system of generator Standard pulse Generator A C 0 A Transformer Neutral B B C C CT 4 C 3 C 2 C 1 C 1 ~ C 3 : Capacitance CT 3 CT 2 CT CT 1 1 ~ CT 4 : Sensors -10-

9 Main Exciter Grnerator Subexciter Outlet Bushing IPB Factory Building Creeping Flange Creeping Flange Factory Building A - IPB C - IPB B - IPB CT Transformer CT Transformer CT Transformer Wall CT CT CT CT Wall CT CT -11-

10 Foundations of PD monitoring technologies 1. Noise rejection 2. PD type recognition 3. On-line diagnosis -12-

11 1. Noise rejection Partial Discharge in power equipment Electric charge moving Electromagnetic radiation Ultrasonic amply vibration PD current transducer UHF PD Sensor Ultrasonic PD Sensor PD monitoring system -13-

12 The difficulty of condition monitoring and fault diagnosis is to depress the strong electromagnetic interference on-site. The different hardware and software filters are used : High-pass filter based on Remez algorithm could be used to real-time suppress the periodical narrow-band noise. Wavelet de-nosing method could reduce background noises effectively. -14-

13 Noise rejection result (a) Original detection signal (b) Signal after de-noise -15-

14 Noise Rejection Method based on UHF 220 V T 1 T 2 T 3 R C x Antenna C C K z 1 C z 2 Tektronix TDS-684C C T -16-

15 In comparison with HF detection, the UHF detection method had favorable anti-interference characteristic but its disadvantage was unable to get the actual discharge quantity by calibration. Therefore a new method for the suppression of pulse-shaped noise was developed, this combined de-noising method based on the fusion of UHF and HF measurements so that fully utilized the favorable anti-interference in UHF measurement and calibrating ability in HF measurement. -17-

16 a. time window b. after extraction in time-domain -18-

17 2. PD type recognition Basis judgments criterion of fault is apparent quantity of PD and its developing trend. Furthermore, we need to know the fault types of PD sources for maintenance suggestions. -19-

18 Typically Partial Discharge insulation HV shield HV lead board HV float Ground Surface discharge Lead discharge Ground Ground Floating discharge conductor High resistance anti-corona layer low resistance anti-corona layer main insulation layer model bar -20-

19 PD current detection result -21-

20 The partial discharge waveform will be distorted after the propagation along the winding, Thus it is difficult to estimate the discharge intensity and to recognize the fault types. -22-

21 We obtained discharge fingerprints, which were represented by T-F spectrum and ϕ-q-n graphs. A fingerprint bank of typical discharges in power equipment was established. Wigner Ville T-F Spectrum ϕ -Q-N 3D distribution charts -23-

22 With the 3D distribution charts the fault patterns and severity could be recognized based on ANN. x 0 f(x) A f(x) B x 1 f(x) A f(x) B f(x) C y x 2 f(x) A f(x) S 1 S 2-24-

23 3. On-line diagnostic expert system for generators For the analysis of fault modes about generators, the fault tree analysis (FTA) method was developed. Diagnostic fault trees of each subsystem were obtained which could supply with the theoretical base for the production diagnostic rule-base. The automatic diagnostic mode and man-machine interactive diagnostic mode are used to evaluate the state of generators based on the knowledge-based system (KBS). -25-

24 Architecture of knowledge-based system ( KBS ) Visual Record Heuristic Knowledge Refining Knowledge Preventive Test Data KB PD Test Data Generator Document Routine Test Data Standards -26-

25 Expression of Knowledge Rule name: Stator Over-current Premise: (Current of Phase A Exceeding 1.2 times Rating Current with CF 1 =0.6) OR (Current of Phase B Exceeding 1.2 times Rating Current with CF 2 =0.6) OR (Current of Phase C Exceeding 1.2 times Rating Current with CF 3 =0.6) Conclusion: 1. Generator Over-load with CF 4 = Short Circuit or Vibration CF 5 =

26 Synthesis database system ( SDBS ) Historical Database Diagnostic Fact-base SDBS Dynamic Database Fault Case-base -28-

27 Fault diagnostic expert system ( FDES ) SCADA Runtime Data DAU Case-base Diagnostic Facts Historical Database Knowledge Base Inference Machine Management Module Result Diagnosis Dynamic Database Man-Machine Graphic User Intreface -29-

28 Virtual Electrical Hospital -30-

29 Further Work Developing an artificial intelligent system for comprehensive assessments to power generator. Based on the data collected from monitoring, power generators residual life could be assessed. Collect data from local monitoring units (RTU) and send the data to central control room using wireless technology. -31-

30 Supported by National Natural Science Foundation of Beijing (Project No ) and National Natural Science Foundation of China (Project No ) -32-

International Journal of Advance Engineering and Research Development. Comparison of Partial Discharge Detection Techniques of Transformer

International Journal of Advance Engineering and Research Development. Comparison of Partial Discharge Detection Techniques of Transformer Scientific Journal of Impact Factor(SJIF): 3.134 International Journal of Advance Engineering and Research Development Volume 2,Issue 7, July -2015 e-issn(o): 2348-4470 p-issn(p): 2348-6406 Comparison

More information

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology Condition Assessment of High Voltage Insulation in Power System Equipment R.E. James and Q. Su The Institution of Engineering and Technology Contents Preface xi 1 Introduction 1 1.1 Interconnection of

More information

PD Solutions. On-Line PD Measurement Devices

PD Solutions. On-Line PD Measurement Devices On-Line PD Measurement Devices 1. Longshot Device (see Figure 1) The measurement system applied is based around the wideband (0-400 MHz) HVPD- Longshot partial discharge test unit which utilizes a high-speed

More information

Open Access Application of Partial Discharge Online Monitoring Technology in ± 660kV Converter Transformer

Open Access Application of Partial Discharge Online Monitoring Technology in ± 660kV Converter Transformer Send Orders for Reprints to reprints@benthamscience.ae 784 The Open Automation and Control Systems Journal, 2015, 7, 784-791 Open Access Application of Partial Discharge Online Monitoring Technology in

More information

MONTRANO. Continuous monitoring system for power transformers

MONTRANO. Continuous monitoring system for power transformers MONTRANO Continuous monitoring system for power transformers Condition monitoring to extend transformer life Knowing the dielectric condition of insulation is vital Dielectric flashover of insulation in

More information

Suppression of Pulse Interference in Partial Discharge Measurement Based on Phase Correlation and Waveform Characteristics

Suppression of Pulse Interference in Partial Discharge Measurement Based on Phase Correlation and Waveform Characteristics Journal of Energy and Power Engineering 9 (215) 289-295 doi: 1.17265/1934-8975/215.3.8 D DAVID PUBLISHING Suppression of Pulse Interference in Partial Discharge Measurement Based on Phase Correlation and

More information

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge The University of New South Wales School of Electrical Engineering and Telecommunications High Voltage Systems ELEC9712 Appendix Partial Discharge Content Introduction Quantities measured Test circuits

More information

PD Diagnostic Applications and TechImp solutions

PD Diagnostic Applications and TechImp solutions PD Diagnostic Applications and TechImp solutions Condition Assessment Solutions for Electrical Systems. PD based innovative tools for the Condition Based Maintenance. MD-04.05.004 - rev. 00-29/08/2006

More information

Basics of Partial Discharge. Prepared for 2015 Phenix RSM Meeting January 2015

Basics of Partial Discharge. Prepared for 2015 Phenix RSM Meeting January 2015 Basics of Partial Discharge Prepared for 2015 Phenix RSM Meeting January 2015 Definitions and History Standard Definitions Fundamentally, what is a Partial Discharge An electric discharge which only partially

More information

PARTIAL DISCHARGE MEASUREMENTS ON GENERATORS USING A NOISE GATING SYSTEM

PARTIAL DISCHARGE MEASUREMENTS ON GENERATORS USING A NOISE GATING SYSTEM Abstract PARTIAL DISCHARGE MEASUREMENTS ON GENERATORS USING A NOISE GATING SYSTEM Q. SU Department of Electrical & Computer Systems Engineering Monash University, Clayton VIC 3168 Email: qi.su@eng.monash.edu.au

More information

OMICRON Seminar on Partial Discharge Diagnostics on HV Assets. January 30, 2018 Beirut, Lebanon

OMICRON Seminar on Partial Discharge Diagnostics on HV Assets. January 30, 2018 Beirut, Lebanon OMICRON Seminar on Partial Discharge Diagnostics on HV Assets January 30, 2018 Beirut, Lebanon Substation Asset Testing and Diagnosis LOW ACCURACY LEVEL HIGH Take better maintenance decisions through accurate

More information

TECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets

TECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets TECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets Who we are TECHIMP is one of the leading providers of Condition Assessment Services Data Acquisition and Test Equipment

More information

Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound

Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound Africa Utility Week Focus Day 2014 Substation Condition Monitoring Benefits of Ultrasound Agenda Review - Substation Condition Monitoring Electrical discharge Types and origin In switchgear Results/consequences

More information

TECHIMP Power Transformer Monitoring

TECHIMP Power Transformer Monitoring TECHIMP Power Transformer Monitoring Kontakt: Martin Hesse Techimp Germany GmbH i.g. E-Mail: mhesse@techimp.com Tel.: +49 5724 391 007 Mobil: +49 170 2364 735 PD Monitoring of Power Transformers Power

More information

THE POWER OF LIFE. WinTech Partial Discharge based Predictive Intelligence of insulation system to eliminate power failure risk.

THE POWER OF LIFE. WinTech Partial Discharge based Predictive Intelligence of insulation system to eliminate power failure risk. THE POWER OF LIFE WinTech Partial Discharge based Predictive Intelligence of insulation system to eliminate power failure risk. Mr. Neal Yang Pro.E.E. Engineer About Us The flaw of dielectric material

More information

The Generators and Electric Motor Monitoring and Diagnostics Systems

The Generators and Electric Motor Monitoring and Diagnostics Systems The Generators and Electric Motor Monitoring and Diagnostics Systems MDR and PGU-DM 1 The «MDR» - Motor Diagnostics Relay the Universal System for Insulation Monitoring in Electric Machines PD-Monitor

More information

Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets

Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets Abstract: For decades it has been recognized that partial discharge assessment is an excellent method

More information

Why partial discharge testing makes good sense

Why partial discharge testing makes good sense Why partial discharge testing makes good sense PD measurement and analysis have proven to be reliable for detecting defects in the insulation system of electrical assets before major damage or a breakdown

More information

ON-LINE PARTIAL DISCHARGE DETECTION ON TRANSFORMERS

ON-LINE PARTIAL DISCHARGE DETECTION ON TRANSFORMERS ON-LINE PARTIAL DISCHARGE DETECTION ON TRANSFORMERS Pantelis D. AGORIS 1, Sander MEIJER 1, Edward GULSKI 1, Johan J. SMIT 1, A. Jos L.M. KANTERS 2 1 Delft University of Technology - The Netherlands 2 TenneT

More information

PARTIAL DISCHARGE MEASUREMENT

PARTIAL DISCHARGE MEASUREMENT PARTIAL DISCHARGE MEASUREMENT Partial Discharges are small electrical sparks which occur predominantly at insulation imperfection. It is the phenomenon which occurs in the insulation on application of

More information

OMICRON Seminar on Substation Testing and Diagnosis. October 23, 2017 Dubai, United Arab Emirates. October 24, 2017 Abu Dhabi, United Arab Emirates

OMICRON Seminar on Substation Testing and Diagnosis. October 23, 2017 Dubai, United Arab Emirates. October 24, 2017 Abu Dhabi, United Arab Emirates OMICRON Seminar on Substation Testing and Diagnosis October 23, 2017 Dubai, United Arab Emirates October 24, 2017 Abu Dhabi, United Arab Emirates Time Optimized Substation Asset Testing and Diagnosis Agenda

More information

Software for Partial Discharge and Localization

Software for Partial Discharge and Localization 48 PIERS Proceedings, Taipei, March 25 28, 2013 Software for Partial Discharge and Localization M. Cap, P. Drexler, P. Fiala, and R. Myska Department of Theoretical and Experimental Electrical Engineering

More information

CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN

CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN 75 CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN 5.1 INTRODUCTION Partial Discharge (PD) detection is an important tool for monitoring insulation conditions in high voltage (HV) devices in power systems.

More information

The importance of partial discharge testing throughout the development and operation of power transformers

The importance of partial discharge testing throughout the development and operation of power transformers The importance of partial discharge testing throughout the development and operation of power transformers Ulrike Broniecki OMICRON Energy Solutions GmbH, Berlin Power transformers are exposed to intense

More information

Investigation of PD Detection on XLPE Cables

Investigation of PD Detection on XLPE Cables Investigation of PD Detection on XLPE Cables Hio Nam O, T.R. Blackburn and B.T. Phung School of Electrical Engineering and Telecommunications The University New South Wales, Australia Abstract- The insulation

More information

CONTINUOUS ON-LINE MONITORING OF PARTIAL DICHARGES IN HV DISTRIBUTION CABLES

CONTINUOUS ON-LINE MONITORING OF PARTIAL DICHARGES IN HV DISTRIBUTION CABLES CONTINUOUS ON-LINE MONITORING OF PARTIAL DICHARGES IN HV DISTRIBUTION CABLES Hao ZHANG, Transgrid, (Australia), hao.zhang@transgrid.com.au Zhao LIU, University of NSW, (Australia), z.liu@unsw.edu.au Toan

More information

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE Z.Liu, B.T.Phung, T.R.Blackburn and R.E.James School of Electrical Engineering and Telecommuniications University of New South Wales

More information

Doble Solutions for Partial Discharge. Greg Topjian Solutions Manager

Doble Solutions for Partial Discharge. Greg Topjian Solutions Manager Doble Solutions for Partial Discharge Greg Topjian Solutions Manager 617-393-3129 gtopjian@doble.com Why do we need to conduct PD measurements PD a major cause of early failure for HV insulation. Partial

More information

PARTIAL DISCHARGE MEASUREMENT AS A DIAGNOSTIC TOOL FOR CURRENT TRANSFORMER

PARTIAL DISCHARGE MEASUREMENT AS A DIAGNOSTIC TOOL FOR CURRENT TRANSFORMER PARTIAL DISCHARGE MEASUREMENT AS A DIAGNOSTIC TOOL FOR CURRENT TRANSFORMER N. R. Bhasme 1 and Bhushan Salokhe 2 1 Associate Prof., 2 M.E. Student, Dept. of Electrical Engg., Govt. College of Engineering

More information

Insulation State On-Line Monitoring and Running Management of Large Generator

Insulation State On-Line Monitoring and Running Management of Large Generator Energy and Power Engineering, 2010, 2, 203-207 doi:10.4236/epe.2010.23030 Published Online August 2010 (http://www.scirp.org/journal/epe) Insulation State On-Line Monitoring and Running Management of Large

More information

PARTIAL DISCHARGE DETECTION AND LOCATION IN TRANSFORMERS BY PERFORMING PARTIAL DISCHARGE TESTS IN OIL USING UHF SENSORS

PARTIAL DISCHARGE DETECTION AND LOCATION IN TRANSFORMERS BY PERFORMING PARTIAL DISCHARGE TESTS IN OIL USING UHF SENSORS PARTIAL DISCHARGE DETECTION AND LOCATION IN TRANSFORMERS BY PERFORMING PARTIAL DISCHARGE TESTS IN OIL USING UHF SENSORS by K.K.JEMBU KAILAS and W. ADITHYA KUMAR L&T CONSTRUCTION L&T CONSTRUCTION KKJK@LNTECC.COM

More information

Partial Discharge Detection of High Voltage Switchgear Using a Ultra High Frequency Sensor

Partial Discharge Detection of High Voltage Switchgear Using a Ultra High Frequency Sensor TRANSACTIONS ON ELECTRICAL AND ELECTRONIC MATERIALS Vol. 14, No. 4, pp. 211-215, August 25, 2013 Regular Paper pissn: 1229-7607 eissn: 2092-7592 DOI: http://dx.doi.org/10.4313/teem.2013.14.4.211 Partial

More information

Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl

Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May 26 2011 St Pete Beach, Fl HDW ELECTRONICS, INC. THE BEST IN CABLE FAULT LOCATING TECHNOLOGY by Henning Oetjen Frank

More information

Partial Discharge Measurements on 110kV Current Transformers. Case Study. Results

Partial Discharge Measurements on 110kV Current Transformers. Case Study. Results 2016 International Conference on Electrical Engineering and Automation (ICEEA 2016) ISBN: 978-1-60595-407-3 Partial Discharge Measurements on 110kV Current Transformers. Case Study. Results Cristian DAN

More information

ANSE VISUAL, developed within the

ANSE VISUAL, developed within the ANSE VISUAL Software to Analyze Substation Robustness ANSE VISUAL, developed within the Institutional Project 1724, is a tool to analyze the robustness of electrical substations. The software carries out

More information

Insulator Defect Detection Technology Research

Insulator Defect Detection Technology Research 3rd International Conference on Material, Mechanical and Manufacturing Engineering (IC3ME 2015) Insulator Defect Detection Technology Research Yang Gao 1,a*, Aoran Xu 1,b, Qun Ouyang 2,c, Liu Zhang 1,d,

More information

Diagnostic testing of cast resin transformers

Diagnostic testing of cast resin transformers Paper of the Month Diagnostic testing of cast resin transformers Author Michael Krüger, OMICRON, Austria michael.krueger@omiconenergy.com Christoph Engelen, OMICRON, Austria christoph.engelen@omicronenergy.com

More information

Practical aspects of PD localization for long length Power Cables

Practical aspects of PD localization for long length Power Cables Practical aspects of PD localization for long length Power Cables M. Wild, S. Tenbohlen University of Stuttgart Stuttgart, Germany manuel.wild@ieh.uni-stuttgart.de E. Gulski, R. Jongen onsite hv technology

More information

The Application of Partial Discharge Measurement and Location on CGIS

The Application of Partial Discharge Measurement and Location on CGIS International Journal on Electrical Engineering and Informatics Volume 4, Number 3, October 2012 The Application of Partial Discharge Measurement and Location on CGIS Min-Yen Chiu¹, Keng-Wei Liang¹, Chang-Hsing

More information

New Techniques for the Monitoring of Transformer Condition

New Techniques for the Monitoring of Transformer Condition New Techniques for the Monitoring of Transformer Condition Thomas Prevost OMICRON electronics USA IEEE T&D Conference Chicago, Illinois April 17, 2014 Agenda Monitoring Expectations & Needs Bushing Monitoring

More information

NETWORK INNOVATION COMPETITION ANGLE-DC PROJECT HOLISTIC CIRCUIT CONDITION MONITORING SYSTEM REPORT

NETWORK INNOVATION COMPETITION ANGLE-DC PROJECT HOLISTIC CIRCUIT CONDITION MONITORING SYSTEM REPORT NETWORK INNOVATION COMPETITION PROJECT HOLISTIC CIRCUIT CONDITION MONITORING SYSTEM REPORT NOVEMBER 17 Version: 1.0 Authored by: Andrew Moon Engineering Consultant and Project Manager Kevin Smith Lead

More information

Abstract. 1 Introduction

Abstract. 1 Introduction Using optical couplers to monitor the condition of electricity infrastructure S.G. Swingler, L. Hao, P.L. Lewin and D.J. Swaffield The Tony Davies High Voltage Laboratory, University of Southampton, Southampton

More information

ABB Power Products Service

ABB Power Products Service Raben Naidoo, Technology days, May 21-22th, 2014, Cape Town, South Africa, Enhanced availability of transformers via transformer remote monitoring - TEC ABB Power Products Service Why a session on availability?

More information

Application Note. Detection of Partial Discharge Using Ultrasound. Detection of Partial Discharge Using Ultrasound. Problem. iriss.

Application Note. Detection of Partial Discharge Using Ultrasound. Detection of Partial Discharge Using Ultrasound. Problem. iriss. Detection of Partial Discharge Using Ultrasound Problem In electrical systems, especially above 1,000 Volts, sufficient and properly maintained equipment insulation helps ensure equipment longevity. However,

More information

H V T E S T S O L U T I O N S PA RT N E RS F O R H V & E M C

H V T E S T S O L U T I O N S PA RT N E RS F O R H V & E M C H V T E S T S O L U T I O N S PA RT N E RS F O R H V & E M C S O L U T I O N S Y O U R S O U R C E F O R T O P Q U A L I T Y T E S T E Q U I P M E N T w w w. h v t e c h n o l o g i e s. c o m Company

More information

NOISE REDUCTION AND SOURCE RECOGNITION OF PARTIAL DISCHARGE SIGNALS IN GAS-INSULATED SUBSTATION

NOISE REDUCTION AND SOURCE RECOGNITION OF PARTIAL DISCHARGE SIGNALS IN GAS-INSULATED SUBSTATION NOISE REDUCTION AND SOURCE RECOGNITION OF PARTIAL DISCHARGE SIGNALS IN GAS-INSULATED SUBSTATION JIN JUN NATIONAL UNIVERSITY OF SINGAPORE 2005 NOISE REDUCTION AND SOURCE RECOGNITION OF PARTIAL DISCHARGE

More information

PARTIAL DISCHARGE DETECTION - AN OVERVIEW

PARTIAL DISCHARGE DETECTION - AN OVERVIEW PARTIAL DISCHARGE DETECTION - AN OVERVIEW 1 MR. N. J. PATEL, 2 PROF. K. K. DUDANI, 3 PROF. A. K. JOSHI 1 M.E. [Power System] P.G. Student, Department of Electrical Engineering, L. E. College of Engineering,

More information

IEEE Transactions on Power Delivery. 15(2) P.467-P

IEEE Transactions on Power Delivery. 15(2) P.467-P Title Author(s) Citation Detection of wide-band E-M signals emitted from partial discharge occurring in GIS using wavelet transform Kawada, Masatake; Tungkanawanich, Ampol; 河崎, 善一郎 ; 松浦, 虔士 IEEE Transactions

More information

Software System for Finding the Incipient Faults in Power Transformers

Software System for Finding the Incipient Faults in Power Transformers Software System for Finding the Incipient Faults in Power Transformers Nikolina Petkova Technical University of Sofia, Department of Theoretical Electrical Engineering, 1156 Sofia, Bulgaria Abstract In

More information

Further Experience in the Use of Existing RTDs in Windings of Motors and Generators for the Measurement of Partial Discharges

Further Experience in the Use of Existing RTDs in Windings of Motors and Generators for the Measurement of Partial Discharges Further Experience in the Use of Existing RDs in Windings of Motors and Generators for the Measurement of Partial Discharges Claude Kane Eaton Electrical Predicative Diagnostics 5421 Feltl Road Suite 190

More information

GENERATOR TESTING APPLICATION GUIDE. reliable. precision.

GENERATOR TESTING APPLICATION GUIDE.  reliable. precision. GENERATOR TESTING APPLICATION GUIDE www.haefely-hipotronics.com reliable. precision. 2 GENERATOR TESTING CONTENTS Product Line Overview 3 AC Hipot Testing 4 Partial Discharge Measurement 5 DC Hipot Testing

More information

SENSITIVITY ASPECTS OF ON-LINE PD DIAGNOSIS OF MV POWER CABLES

SENSITIVITY ASPECTS OF ON-LINE PD DIAGNOSIS OF MV POWER CABLES SENSITIVITY ASPECTS OF ON-LINE PD DIAGNOSIS OF MV POWER CABLES Frank WESTER, Edward GULSKI, Johan SMIT, Edwin GROOT*, Mark VAN VLIET* Delft University of Technology The Netherlands * NUON The Netherlands

More information

1409. Comparison study between acoustic and optical sensors for acoustic wave

1409. Comparison study between acoustic and optical sensors for acoustic wave 1409. Comparison study between acoustic and optical sensors for acoustic wave Malik Abdulrazzaq Alsaedi Department of Electrical, Faculty of Engineering, University of Misan, Amarah, Iraq E-mail: maliksaady@yahoo.com

More information

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento Sept. 22-24, 28, Florence, Italy EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS C. Ceretta, R. Gobbo, G. Pesavento Dept. of Electrical Engineering University of

More information

Maintenance & Diagnosis Strategies. for. High Voltage Substations

Maintenance & Diagnosis Strategies. for. High Voltage Substations Maintenance & Diagnosis Strategies for High Voltage Substations 1/ 52 Robin Fischer, 28 April 2004 Diagnosis of Substation Equipment Power Transformers Instrument Transformers Switch-Gears Breakers Coils

More information

EIE 528 Power System Operation & Control(2 Units)

EIE 528 Power System Operation & Control(2 Units) EIE 528 Power System Operation & Control(2 Units) Department of Electrical and Information Engineering Covenant University 1. EIE528 1.1. EIE 528 Power System Operation & Control(2 Units) Overview of power

More information

WAVELET TRANSFORM ANALYSIS OF PARTIAL DISCHARGE SIGNALS. B.T. Phung, Z. Liu, T.R. Blackburn and R.E. James

WAVELET TRANSFORM ANALYSIS OF PARTIAL DISCHARGE SIGNALS. B.T. Phung, Z. Liu, T.R. Blackburn and R.E. James WAVELET TRANSFORM ANALYSIS OF PARTIAL DISCHARGE SIGNALS B.T. Phung, Z. Liu, T.R. Blackburn and R.E. James School of Electrical Engineering and Telecommunications University of New South Wales, Australia

More information

WAVELET DE-NOISING AND ANALYSIS OF UHF PARTIAL DISCHARGES IN HIGH VOLTAGE POWER TRANSFORMER

WAVELET DE-NOISING AND ANALYSIS OF UHF PARTIAL DISCHARGES IN HIGH VOLTAGE POWER TRANSFORMER Volume, Issue 9, PP: - 9, FEB. WAVELET DE-NOISING AND ANALYSIS OF UHF PARTIAL DISCHARGES IN HIGH VOLTAGE POWER TRANSFORMER K V RAMPRASAD *. Professor, Dept of ECE, KALLAM HARANADHA REDDY INSTITUTE OF TECHNOLOGY,

More information

High Voltage Diagnostics Sarl 4, Rue de Lac CH 1897 Le Bouveret Switzerland

High Voltage Diagnostics Sarl 4, Rue de Lac CH 1897 Le Bouveret Switzerland High Voltage Diagnostics Sarl 4, Rue de Lac CH 1897 Le Bouveret Switzerland Company HV Diagnostics Sarl is a Swiss based company in the field of high voltage test equipment for cable testing and diagnosis.

More information

Design of Meander Antenna for UHF Partial Discharge Detection of Transformers

Design of Meander Antenna for UHF Partial Discharge Detection of Transformers Sensors & Transducers 204 by IFSA Publishing, S. L. http://www.sensorsportal.com Design of Meander Antenna for UHF Partial Discharge Detection of Transformers Mengjie Li, Chuangxin Guo, 2 Ziping Peng College

More information

USING DAMPED AC VOLTAGES

USING DAMPED AC VOLTAGES MODERN & TESTING DIAGNOSIS OF POWER CABLES USING DAMPED AC VOLTAGES BY EDWARD GULSKI AND ROGIER JONGEN, Onsite HV Solutions ag, Switzerland AND RALPH PATTERSON, Power Products & Solutions LLC, United States

More information

PD Testing Considerations for MV Plant Cables

PD Testing Considerations for MV Plant Cables PD Testing Considerations for MV Plant Cables Cable Testing Philosophy Damage Mistake Aging Repair Manufacturing Transportation Installation Operation Power frequency 50/60 Hz Power frequency 50/60 Hz

More information

LEVEL DEPENDENT WAVELET SELECTION FOR DENOISING OF PARTIAL DISCHARGE SIGNALS SIMULATED BY DEP AND DOP MODELS

LEVEL DEPENDENT WAVELET SELECTION FOR DENOISING OF PARTIAL DISCHARGE SIGNALS SIMULATED BY DEP AND DOP MODELS International Journal of Industrial Electronics and Electrical Engineering, ISSN: 47-698 Volume-, Issue-9, Sept.-014 LEVEL DEPENDENT WAVELET SELECTION FOR DENOISING OF PARTIAL DISCHARGE SIGNALS SIMULATED

More information

MPD 500. Partial Discharge Measuring System for Routine Test Applications

MPD 500. Partial Discharge Measuring System for Routine Test Applications MPD 500 Partial Discharge Measuring System for Routine Test Applications Partial Discharge Measurement The MPD 500 partial discharge measuring system has been specially designed for providing fast and

More information

Partial discharge diagnostics on very long and branched cable circuits

Partial discharge diagnostics on very long and branched cable circuits 11 Nordic Insulation Symposium Stockholm, June 11-13, 2001 Partial discharge diagnostics on very long and branched cable circuits Nico van Schaik, E. Fred Steennis, Wim Boone and Dick M. van Aartrijk KEMA

More information

On-Site Partial Discharge Monitoring using the differential LEMKE PROBE LDP-5 and its accessories

On-Site Partial Discharge Monitoring using the differential LEMKE PROBE LDP-5 and its accessories Workshop 2000, lexandria, Virginia, 13 & 14 September 2000 paper No.: 8 On-Site Partial Discharge Monitoring using the differential LEMKE PROE and its accessories Dirk Russwurm, HV Technologies, Inc. bstract

More information

PULSE-SEQUENCE ANALYSIS OF PARTIAL DISCHARGES IN POWER TRANSFORMERS

PULSE-SEQUENCE ANALYSIS OF PARTIAL DISCHARGES IN POWER TRANSFORMERS PULSE-SEQUENCE ANALYSIS OF PARTIAL DISCHARGES IN POWER TRANSFORMERS Anne Pfeffer 1*, Stefan Tenbohlen 1 and Stefan Kornhuber 2 1 Institute of Power Transmission and High Voltage Technology, Pfaffenwaldring

More information

A Survey of Sensor Technologies for Prognostics and Health Management of Electronic Systems

A Survey of Sensor Technologies for Prognostics and Health Management of Electronic Systems Applied Mechanics and Materials Submitted: 2014-06-06 ISSN: 1662-7482, Vols. 602-605, pp 2229-2232 Accepted: 2014-06-11 doi:10.4028/www.scientific.net/amm.602-605.2229 Online: 2014-08-11 2014 Trans Tech

More information

APPLICATIONS OF ACOUSTIC LOCALIZATION TO ONLINE POWER TRANSFORMERS

APPLICATIONS OF ACOUSTIC LOCALIZATION TO ONLINE POWER TRANSFORMERS APPLICATIONS OF ACOUSTIC LOCALIZATION TO ONLINE POWER TRANSFORMERS David Larochelle NDB Technologies Reasons leading to acoustic testing are different weather it is a manufacturing or field environment

More information

Partial Discharge Classification Using Novel Parameters and a Combined PCA and MLP Technique

Partial Discharge Classification Using Novel Parameters and a Combined PCA and MLP Technique Partial Discharge Classification Using Novel Parameters and a Combined PCA and MLP Technique C. Chang and Q. Su Center for Electrical Power Engineering Monash University, Clayton VIC 3168 Australia Abstract:

More information

PARTIAL DISCHARGE MEASUREMENT ON ROTATING MACHINES

PARTIAL DISCHARGE MEASUREMENT ON ROTATING MACHINES PARTIAL DISCHARGE MEASUREMENT ON ROTATING MACHINES Engr. IÑIGO V. ESCOPETE, JR. ITC Level 2 Certified Thermographer PHIL-NCB NDT-UT Level 2 Partial Discharge testing is a Condition Based Maintenance tool

More information

PD ANALYSIS OF GAS INSULATED MEDIUM VOLTAGE SWITCHGEAR DURING FACTORY ASSEMBLY AND SITE COMMISSIONING

PD ANALYSIS OF GAS INSULATED MEDIUM VOLTAGE SWITCHGEAR DURING FACTORY ASSEMBLY AND SITE COMMISSIONING PD ANALYSIS OF GAS INSULATED MEDIUM VOLTAGE SWITCHGEAR DURING FACTORY ASSEMBLY AND SITE COMMISSIONING Andreas F.X. WELSCH*, Siegfried A. RUHLAND* *AREVA Sachsenwerk GmbH - Germany andreas.welsch@areva-td.com

More information

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser, OMICRON electronics Corp. USA Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser,

More information

Knowledge Is Power SM Apparatus Maintenance and Power Management for Energy Delivery. Application of EMI Diagnostics to Hydro Generators

Knowledge Is Power SM Apparatus Maintenance and Power Management for Energy Delivery. Application of EMI Diagnostics to Hydro Generators Knowledge Is Power SM Apparatus Maintenance and Power Management for Energy Delivery Application of EMI Diagnostics to Hydro Generators James Timperley Doble Global Power Services Columbus, Ohio jtimperley@doble.com

More information

UHF PD-DIAGNOSIS AT HIGH VOLTAGE CABLE TERMINATIONS INTERNATIONAL CASE STUDIES

UHF PD-DIAGNOSIS AT HIGH VOLTAGE CABLE TERMINATIONS INTERNATIONAL CASE STUDIES UHF PD-DIAGNOSIS AT HIGH VOLTAGE CABLE TERMINATIONS INTERNATIONAL CASE STUDIES D. Götz*, H.T. Putter* *Megger Germany INTRODUCTION High voltage termintions are essential components in high voltage cable

More information

Extended analysis versus frequency of partial discharges phenomena, in support of quality assessment of insulating systems

Extended analysis versus frequency of partial discharges phenomena, in support of quality assessment of insulating systems Extended analysis versus frequency of partial discharges phenomena, in support of quality assessment of insulating systems Romeo C. Ciobanu, Cristina Schreiner, Ramona Burlacu, Cristina Bratescu Technical

More information

Characteristics of Insulation Diagnosis and Failure in Gas Turbine Generator Stator Windings

Characteristics of Insulation Diagnosis and Failure in Gas Turbine Generator Stator Windings J Electr Eng Technol Vol. 9, No. 1: 280-285, 2014 http://dx.doi.org/10.5370/jeet.2014.9.1.280 ISSN(Print) 1975-0102 ISSN(Online) 2093-7423 Characteristics of Insulation Diagnosis and Failure in Gas Turbine

More information

KEYWORDS On-line diagnostics, cable termination, partial discharge (PD), ultra-high frequency (UHF), sensitivity check.

KEYWORDS On-line diagnostics, cable termination, partial discharge (PD), ultra-high frequency (UHF), sensitivity check. 2, rue d Artois, F-758 PARIS B-2 CIGRE 28 http : //www.cigre.org Application of UHF method for on-line PD diagnostics of cable terminations T. KLEIN Pfisterer Kontaktsysteme GmbH Germany D. DENISSOV, W.

More information

On-line Monitoring System Based on Principle of Electro-acoustic Monitoring for Transformer Partial Discharge

On-line Monitoring System Based on Principle of Electro-acoustic Monitoring for Transformer Partial Discharge Sensors & Transducers 2014 by IFSA Publishing, S. L. http://www.sensorsportal.com On-line Monitoring System Based on Principle of Electro-acoustic Monitoring for Transformer Partial Discharge Guang Ya

More information

Output performance: Analogue output accuracy check. Pulse output accuracy check.

Output performance: Analogue output accuracy check. Pulse output accuracy check. An insight into the reasons for verification: Confidence in ongoing performance, regulatory requirements, maintaining process quality. Calibration: The comparison of measurement values delivered by a device

More information

Intelligent Monitoring Analysis System

Intelligent Monitoring Analysis System Wireless RH503 & RH550 Software MOS2000 Intelligent Monitoring Analysis System Remark: RH503 is the updated version of RH501 1. Product Introduction RH503 wireless transducer and RH550 wireless communication

More information

TD-106. HAEFELY HIPOTRONICS Technical Document. Partial Discharge Pulse Shape Analysis to Discriminate Near and Far End Failures for Cable Location

TD-106. HAEFELY HIPOTRONICS Technical Document. Partial Discharge Pulse Shape Analysis to Discriminate Near and Far End Failures for Cable Location HAEFELY HIPOTRONICS Technical Document Partial Discharge Pulse Shape Analysis to Discriminate Near and Far End Failures for Cable Location P. Treyer, P. Mraz, U. Hammer Haefely Hipotronics, Tettex Instruments

More information

Condition-based maintenance of power transformers Complete three-phase system Turns Ratio: Recovery Voltage: Winding Resistance:

Condition-based maintenance of power transformers Complete three-phase system Turns Ratio: Recovery Voltage: Winding Resistance: ETP SYSTEM Condition-based maintenance of power transformers The predictive and condition based maintenance is nowadays accepted as the most efficient solution to guarantee the proper operation of critical

More information

How to Use the Method of Multivariate Statistical Analysis Into the Equipment State Monitoring. Chunhua Yang

How to Use the Method of Multivariate Statistical Analysis Into the Equipment State Monitoring. Chunhua Yang 4th International Conference on Mechatronics, Materials, Chemistry and Computer Engineering (ICMMCCE 205) How to Use the Method of Multivariate Statistical Analysis Into the Equipment State Monitoring

More information

The R Portable Device for Partial Discharge Measurement and Analysis in High Voltage Equipment Insulation

The R Portable Device for Partial Discharge Measurement and Analysis in High Voltage Equipment Insulation The R2200 - Portable Device for Partial Discharge Measurement and Analysis in High Voltage Equipment Insulation DIMRUS Ltd. www.dimrus.ru 1 The R2200 Device is for Effective Partial Discharge (PD) Measurement

More information

ON-LINE PARTIAL DISCHARGE MEASUREMENT AND CONTROL

ON-LINE PARTIAL DISCHARGE MEASUREMENT AND CONTROL REPRINT 19TH INTERNATIONAL CONFERENCE AND EXHIBITION ON ELECTRICITY DISTRIBUTION REED MESSE WIEN CONGRESS CENTER, VIENNA MAY 21-24, 2007 ON-LINE PARTIAL DISCHARGE MEASUREMENT AND CONTROL Kristian Winter,

More information

NOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV

NOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV NOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV Paul P. SEITZ, Seitz Instruments AG, (Switzerland), pps@seitz-instruments.ch Ben QUAK, Seitz Instruments AG, (Switzerland),

More information

Electrical Equipment Condition Assessment

Electrical Equipment Condition Assessment Feature Electrical Equipment Condition Assessment Using On-Line Solid Insulation Sampling Importance of Electrical Insulation Electrical insulation plays a vital role in the design and operation of all

More information

Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables

Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables 21, rue d Artois, F-75008 PARIS AUCKLAND 2013 http : //www.cigre.org Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables Michael Krüger, Rene Hummel, Stefan Böhler, OMICRON Austria

More information

NOISE REDUCTION OF PARTIAL DISCHARGE SIGNALS USING LINEAR PREDICTION AND WAVELET TRANSFORM

NOISE REDUCTION OF PARTIAL DISCHARGE SIGNALS USING LINEAR PREDICTION AND WAVELET TRANSFORM NOISE REDUCTION OF PARTIAL DISCHARGE SIGNALS USING LINEAR PREDICTION AND WAVELET TRANSFORM Babak Badrzadeh and S.M.Shahrtash Department of electrical engineering Iran University of Science and Technology

More information

Frequency Spectrum Analysis of Electromagnetic Waves Radiated by

Frequency Spectrum Analysis of Electromagnetic Waves Radiated by Frequency Spectrum Analysis of Electromagnetic Waves Radiated by Electrical Discharges HYEON-KYU CHA, SUN-JAE KIM, DAE-WON PARK, GYUNG-SUK KIL Division of Electrical and Electronics Engineering Korea Maritime

More information

FRANEO 800. The next generation for a reliable core and winding diagnosis of power transformers

FRANEO 800. The next generation for a reliable core and winding diagnosis of power transformers FRANEO 800 The next generation for a reliable core and winding diagnosis of power transformers The next generation of power transfor Mechanical or electrical problems in power transformer windings, contacts

More information

NJ. ISBN (2017) , /URSIGASS

NJ. ISBN (2017) , /URSIGASS Jaber, A. and Lazaridis, P. and Saeed, B. and Mather, P. and Vieira, M. F. Q. and Atkinson, R. and Tachtatzis, C. and Iorkyase, E. and Judd, M. and Glover, I. A. (2017) Diagnostic potential of free-space

More information

Specialists in HV and MV test and diagnostics. Testing in Substations

Specialists in HV and MV test and diagnostics. Testing in Substations Specialists in HV and MV test and diagnostics Testing in Substations Testing in Substations Testing in Substations At 4fores we specialize in the diagnosis and measurement of all types of existing technologies

More information

Research on Transformer On-line Monitoring System of 500 kv Transformer Substation based on Vibration Method

Research on Transformer On-line Monitoring System of 500 kv Transformer Substation based on Vibration Method Sensors & Transducers 2013 by IFSA http://www.sensorsportal.com Research on On-line Monitoring System of 500 kv Substation based on Vibration Method 1 Wang Wen-Xing North China University of Water Resources

More information

Končar TMS - Bushing monitoring

Končar TMS - Bushing monitoring Končar TMS - Bushing monitoring Many recent studies have shown that bushing failure is one of the most common causes of transformer failure. Thus need for bushing diagnostic and monitoring system has risen.

More information

PHG 70 TD PD / PHG 80 TD PD

PHG 70 TD PD / PHG 80 TD PD PHG 70 TD PD / PHG 80 TD PD BAUR VLF test and diagnostics system Functions Universal test and diagnostics system flexible, modular, extendable Cutting-edge testing and diagnostics technology: VLF truesinus

More information

Advanced Diagnostic Testing Services. Provides detailed and reliable results

Advanced Diagnostic Testing Services. Provides detailed and reliable results Advanced Diagnostic Testing Services Provides detailed and reliable results Advanced Diagnostic Testing Services from the world s leading manufacturer of power transformers ABB leadership begins with our

More information

EVALUATION AND COMPARISON OF ON-LINE PD DETECTION METHODS FOR HIGH-VOLTAGE POWER CABLE

EVALUATION AND COMPARISON OF ON-LINE PD DETECTION METHODS FOR HIGH-VOLTAGE POWER CABLE EVALUATION AND COMPARISON OF ON-LINE PD DETECTION METHODS FOR HIGH-VOLTAGE POWER CABLE Ju-Chu Hsieh 1, Cheng-Chi Tai 1, Ching-Chau Su 1, Chien-Yi Chen 1, Ting-Cheng Huang 1, Yu-Hsun Lin 2 1 Department

More information