ANALYSIS OF HARMONIC DISTORTION LEVELS ON A DISTRIBUTION NETWORK
|
|
- Abel Lawrence
- 6 years ago
- Views:
Transcription
1 Presented in AUPEC 7, Pert, Western Australia, 9- December, 7 ANALYSIS OF HARMONIC DISTORTION LEVELS ON A DISTRIBUTION NETWORK Glenn Nicolson - Manukau Institute of Tecnology, Auckland, New Zealand Professor Vic Gosbell, University of Wollongong, Australia Asok Parsotam, Vector Ltd, Auckland, New Zealand Abstract It is generally acknowledged tat armonic distortion levels on distribution networks are slowly but steadily increasing due to te proliferation of non-linear loads. Wile customer complaints relating to armonic distortion levels are relatively uncommon, and measured levels of armonic distortion are typically well witin te limits specified by national regulations and international standards, te increasing trend may mean tat more active management by utilities will soon be required. Effective management of armonic distortion levels will require knowledge not only of te level of disturbance, but also of ow te disturbance levels vary wit time, location, and te connected load. Accepted metods of assessing armonic levels tat rely on (typically 95%) cumulative probability statistics are inadequate for tis level of insigt. In tis paper voltage total armonic distortion levels (THD v ) from a distribution network power quality survey are analysed in terms of variation wit time, te relationsip of te measured THD v levels to system load and te pysical caracteristics of te monitored sites.. Introduction Harmonic distortion levels are seldom te source of complaints from network customers. After issues of network reliability, most customer complaints arise from discrete power quality disturbances suc as sort-term interruptions, voltage sags or swells, and voltage fluctuations tat cause ligt flicker. Wile armonic distortion may not cause suc immediate and easily-observed impacts, it can cause some equipment to malfunction, and does result in additional power losses in bot customer and network equipment []. It is generally accepted tat te proliferation of nonlinear loads is leading to a slow but steady increase in armonic distortion levels on networks. Even if present levels of armonic distortion are considered to be well witin acceptable levels, tis situation may well cange if te increasing trend continues. Management of armonic distortion levels will be assisted by knowledge of ow distortion levels vary bot in place and in time. Use of cumulative probability statistics calculated over te survey period do not give sufficient information for tis purpose. Tis paper will describe te analysis of armonic distortion levels recorded as part of a continuous power quality survey on a New Zealand distribution network. Measured levels of voltage total armonic distortion ave been analysed wit regard to bot variation over time and also te load caracteristics of te monitored. Reasons for tis study Te data on wic tis paper is based is taken from a continuous PQ monitoring programme carried out by Vector (NZ) Ltd. Vector ave been actively involved in routine PQ monitoring since 999 and now ave over 3 PQ monitors installed in te Auckland network, including 3 monitors connected to te kv bus in zone substations. It is te data from tese zone substations tat is analysed in tis paper. An earlier study [] analysed variation in THD v levels across te 3 monitored sites. For te purpose of tis study, te sites were grouped according to weter te predominant nature of te connected load was commercial, industrial or residential. Te survey consisted of two commercial sites, eigt industrial sites, and tree residential sites. 95% cumulative probability statistics were calculated for te purpose of reporting te THD v levels at eac It was found tat THD v levels were lowest at commercial sites, followed by industrial sites, wit residential sites igest. Tis seemed counter-intuitive, as it could be expected tat industrial sites would ave a muc iger proportion of non-linear loads tan residential sites. One of te outcomes of te earlier study was identifying te need for furter investigation into armonic distortion levels on te network. 3 Analysis of THD v data In tis paper, THD v data from te 3 monitored sites as been analysed, covering te period of te mont of June 4. Te objective of te analysis was to identify any time-varying trends in THD v levels, and also to identify any relationsip between te THD v and te predominant load type and load magnitude. Te steps in analysing te THD v data for eac site were: 86
2 Presented in AUPEC 7, Pert, Western Australia, 9- December, 7 Plot te THD v measurements against time in order to identify any trends wit regard to time (ref. Section 4). Compare te THD v plot wit te trend for site load current for te corresponding period (ref. Section 4). Calculate te correlation coefficient between THD v and load current (ref. Section 4). Investigate te relationsip between THD v and armonic current levels over te survey period (ref. Section 4.4). Compare te time trends for te site against all oter sites (ref. Section 5). Load Current Victoria June 4: THD vs Load Current Scattergrap THD (%) 4 THDv time series and load current analysis results 4. Commercial sites Te plot of THD v levels against time clearly identified bot daily and weekly cycles of variation. Te plot for one of te commercial sites is sown in Fig.. THDv(%) Victoria June 4 THDv Jun- : Jun- 6:3 Jun-3 3: Jun-4 9:3 Jun-6 : Jun-7 8:3 Jun-8 5: Jun-9 :3 Jun- 4: Jun- :3 Jun-3 7: Jun-4 3:3 Jun-6 6: Jun-7 :3 Jun-8 9: Jun- :3 Jun- 8: Jun- 4:3 Jun-3 : Jun-5 3:3 Jun-6 : Jun-7 6:3 Jun-8 3: Jun-3 5:3 Figure : Montly THD v trend for a commercial On a daily basis, THD v levels peak between te ours of midnigt and 5: a.m., and are fairly constant during tis time at around %. Daily minium THD v levels occur between te ours of 7: a.m. and 5:45 p.m. (at around.5%), and tis coincides wit commercial ours of business and te period of maximum load current. On a weekly scale, weekends (June 5-6, -3, 9- and 6-7) typically experience lower maximum levels and iger minimum levels of THD v. A scatter plot of THD v and load current was used to compare measured THD v levels against corresponding levels of load current for te same period. Tis plot is sown in Fig.. Fig.: Scatter plot of load current against THD v for a commercial Fig. suggests tat a negative correlation exists between load current and THD v. Using te data analysis tools in Microsoft Excel, te correlation coefficient was calculated to be.79 for te mont of June. Very similar results were obtained from te oter commercial site, te only significant difference being te magnitude of te THD v measurements. 4. Industrial Sites Data from eigt industrial sites was analysed in tis study. It is wort noting tat wile tese eigt sites are all considered to ave a predominantly industrial load, some sites are more industrial tan oters (i.e. some sites consist of a mix of industrial, commercial and residential load). Determining wat may be considered representative trends across te eigt sites is furter complicated by te fact tat at tree of te industrial sites, THD v levels are recorded ourly as opposed to te 5-minute recordings at te oter five industrial sites. Despite tese limitations, some trends were still found to be consistent across te eigt industrial sites. Fig.3 sows te THD v trend for wat can be considered a typical THDv(%) Bairds June 4 THDv Jun- : Jun- 3:45 Jun- 3:3 Jun-3 3:5 Jun-4 3: Jun-5 :45 Jun-6 :3 Jun-7 :5 Jun-8 : Jun-9 :45 Jun-3 3: Jun-4 :45 Jun-5 :3 Jun-6 :5 Jun-7 : Jun-8 :45 Jun-9 :3 Jun- :5 Jun- : Jun- :45 Jun-3 :3 Jun-4 :5 Jun-5 : Jun-6 9:45 Jun-7 9:3 Jun-8 9:5 Jun-9 9: Jun-3 8:45 Fig.3: Montly THD v trend for an industrial Te daily and weekly variation in THD v levels typical of industrial sites can be seen in Fig.3. For te site sown, THD v levels peak between 8: p.m. and midnigt. For all industrial sites, THD v levels peak during te nigt-time ours. At some sites tis peak occurs before midnigt, wile at oter sites te peak 87
3 Presented in AUPEC 7, Pert, Western Australia, 9- December, 7 occurs between midnigt and 5: a.m. Fig.3 also sows a clear weekly trend in THD v levels, wit iger levels being recorded on weekends. Tis is true for most of te industrial sites, and coincides wit periods of lower load current. Te relationsip between measured THD v levels and load current was assessed using a scatter plot. Te scatter plot corresponding to te THD v data from Fig.3 is sown in Fig.4. Load Current Bairds June 4 THDv - I Scattergrap THDv (%) Fig.4: Scatter plot of load current against THD v for an industrial As for te commercial sites, te scatter plot suggests a negative relationsip between THD v levels and load current. For te example industrial site, te correlation coefficient was calculated to be.53. All industrial sites displayed a negative correlation coefficient between THD v levels and load current, wit te coefficients ranging between.34 to.86 Across te eigt industrial sites, te range of peak THD v levels recorded was between.5% to 3%. 4.3 Residential Sites Te Vector power quality survey included data from tree residential sites. Cyclic variation of THD v levels on bot daily and weekly timescales was clearly apparent. Fig.5 sows te variation in THD v levels for one of te residential sites for te survey period. THDv(%) Takanini June 4 THDv Jun- : Jun- :45 Jun-3 5:3 Jun-4 8:5 Jun-5 : Jun-6 3:45 Jun-7 6:3 Jun-8 :3 Jun- :5 Jun- 3: Jun- 5:45 Jun-3 8:3 Jun-4 :5 Jun-5 4: Jun-6 6:45 Jun-7 9:3 Jun-8 :5 Jun- : Jun- 3:45 Jun- 6:3 Jun-3 9:5 Jun-4 : Jun-5 4:45 Jun-6 7:3 Jun-7 :5 Jun-8 3: Jun-3 :45 Fig.5: Montly THD v trend for a residential For te residential sites, THD v levels typically peak eac day between te ours of 7:3 p.m. and :3 a.m. Witin tis range, most daily THD v peaks occur around :3 p.m. Daily minimum THD v levels typically occur between te ours of 6:3 a.m. and 9: a.m., wic coincides wit te morning peak in load current. During te late afternoon-early evening load current peak, THD v levels also sow a marked decrease. On a weekly time scale, two of te tree sites sowed a clear weekly pattern, wit maximum THD v levels for te week being recorded on eiter Saturday or Sunday. For te tird residential site, te weekly pattern was less clear, but again many of te weekly peak levels occurred on Saturdays or Sundays. Te relationsip between THD v levels and load current is less clear for residential sites tan it is for commercial and industrial sites. For te example residential site sown in Fig.5, a strong negative correlation between THD v and load current was evident for te mont of June, as can be seen from te scatter plot in Fig.6. For tis site, te correlation coefficient was calculated to be.8. Load Current Tkanini June 4: THD vs Load Current Scattergrap Fig.6: Scatter plot of load current against THD v for a residential For te oter two residential sites, te THD v -load current correlation coefficients were. and.54 (i.e. bot positive). 4.4 Relationsip between THD v and armonic current levels Given tat te presence of armonic voltages on te network is te result of te flow of armonic currents, tis raises te question of ow do te armonic voltage levels relate to measured levels of armonic currents. Te only armonic current data available from eac site are te 5-minute averages of current THD for eac pase. Te usefulness of current THD for comparing values at different sites or at different times is limited, as eac measurement is divided by a different value of fundamental current as te load varies. A more useful value for comparison purposes is te magnitude of te distorting current. Wit data for bot average load current and current THD, te magnitude of te total distorting current can be calculated. Current THD is calculated as: THDv 88
4 Presented in AUPEC 7, Pert, Western Australia, 9- December, 7 I THDi = I were I I () = total distorting current = fundamental currrent and so te total distorting current can be calculated as armonic current I ave been plotted togeter. Te trend for an example site is sown in Fig.7, clearly illustrating te similarity in variation of THD v and total armonic current. Fig.7: THD v and armonic current I for a sample Bairds June 4 THDv & Harmonic Current I/ V THD mean I = THDi I () For te purpose of tis calculation, only te average rms value of load current (rater tan te fundamental) is available, but given tat I = I + I (3) rms THDv & I/ Harm Current I/ it can be sown tat te magnitude of te total distorting current can be calculated by: I Irms THD = + THD i i (4) Te relationsip between THD v and te total distorting current I as been analysed wit te aim of determining weter te source of tis disturbance is armonic load currents flowing downstream of te monitored site, or weter it originates from upstream of te monitored To analyse te relationsip, te correlation coefficient between THD v and total distorting load current I as been calculated for eac Te results are given in Table. Site THDv I Correlation Coefficient Commercial Quay.88 Victoria -.4 Industrial Bairds. 55 Carbine.9 Greenmount.7 McNab. 48 Otara.43 Rockfield.76 Rosebank.9 Wiri.9 Residential Howick.4 Manurewa.75 Takanini.87 Table : Correlation between THD v and d istorting load current I. Te results in Table sow tat all sites except one sow eiter a moderate or strong positive correlation between THD v and total distorting current. Tis suggests tat te voltage distortion levels present at te zone substations are likely due to distorting load currents downstream from te substation. It also indicates tat te variation in armonic current magnitude varies wit time in a similar manner to voltage distortion. To ceck tis, trends in THD v and.5 Jun- : Jun- 9:45 Jun- 5:3 Jun-3 :5 Jun-4 7: Jun-5 :45 Jun-5 :3 Jun-6 8:5 Jun-7 4: Jun-8 9:45 Jun-9 5:3 Jun-3 :45 Jun-3 :3 Jun-4 8:5 Jun-5 4: Jun-6 9:45 Jun-7 5:3 Jun-8 :5 Jun-8 : Jun-9 6:45 Jun- :3 Jun- 8:5 Jun- 4: Jun- 3:45 Jun-3 9:3 Jun-4 5:5 Jun-5 : Jun-6 6:45 Jun-7 :3 Jun-7 :5 Jun-8 8: Jun-9 3:45 Jun-3 9:3 5. Summary of results From comparison of te results from te tree site categories, it is clear tat tere are significant differences in te patterns of THD v variation, and tat tese differences can be attributed to bot predom inant load type, and te pattern of load current variation. Tere are also aspects of THD v variation tat are common across all sites. 5. THD v variation wit time Te first comparison tat can be made is between te times at wic peak THD v levels occur for eac Table sows te typical times of daily peak THD v levels for t e surveyed sites. Te saded areas indicate te range of times of daily peak THD v levels. Te range of peak times is defined as range of times of day during wic te daily maximum value of THD v occurs over te one-mont survey period. 6:-8: 8:-: :-: :-4: 4:-6: 6:-8: 8:-: :-: :-: :-: :-4: 4:-6: Quay Victoria Bairds Carbine Greenmount McNab Otara Rockfield Rosebank Wiri Howick Manurewa Takanini = commerc ial = industrial = residential Table : comparison of THD v peak tim es. 89
5 Presented in AUPEC 7, Pert, Western Australia, 9- December, 7 Te two zone substations supplying predominantly commercial load bot exibited ve ry similar patterns of variation of T HD v and load current. THD v levels peak between midnigt and 5: a. m., and fall to low levels during business ours wen load current is ig. Te diurnal variation in THD v levels is around %. Overall, THD v levels for te two commercial substations are lower tan for industrial or residential substations. Te average 95% cumulative probability value of THD v across te two sites for te mont of June was.44%. THD v levels at zone substations supplying predominantly industrial loads likewise peak at nigt and are generally iger on weekends, and tis coincides wit periods of reduced load current. Tere is some variation across te eigt substations in te time during te nigt at wic peak THD v levels occur. For most sites te peak occurs between 8: p.m. and midnigt (similar to a residential site) wile at one site te peak occurs between midnigt and 5: a.m. Te average diurnal variation in THD v levels at industrial sites is.6%, similar to tat for commercial sites. Te average 95% cumulative probability value of THD v across te eigt sites was.94%, sligtly iger tan tat for te commercial sites. THD v levels at te zone substations supplying predominantly residential load also tend to peak mostly during nigt-time ours. For two of te residential substations, THD v tends to peak between te ours of 8:3 p.m. and midnigt. Te one residential substation were THD v levels peak after midnigt also as a load current pattern tat suggests tat tis residential site as a significant commercial or industrial load component. Te average diurnal range in THD v levels for te residential substations is.3%, larger tan te range for eiter commercial or industrial sites. Te average 95% cumulative probability value of THD v across te tree residential sites was.58%, significantly iger tan te comparable values for bot commercial and industrial sites. Tis reaffirms te findings of [] tat THD v levels at residential sites are typically iger tan tose experienced at commercial or industrial sites. 5. THD v variation wit Load Current Te second comparison tat can be made between te sites is te relationsip between variation in THD v levels and daily and weekly variations in load current. Te correlation coefficient between THD v and load current for eac site is given in Table 3. Te two commercial sites sow a strong negative correlation between THD v and load current. Likewise, all industrial sites sow a negative correlation between THD v and load current. Te strengt of tis correlation varies between sites, and tis is likely due to variation in te degree to wic te load is purely industrial or combined wit some commercial or residential load. Te most interesting feature of Table 3 is tat two substations display a positive correlation between THD v and load current, and bot of tese substations are supplying predominantly residential load. Site THDv Load Current Correlation Coefficient Commercial Quay -.8 Victoria -.79 Industrial Bairds -.53 Carbine -.38 Greenmount -.86 McNab -.34 Otara -.39 Rockfield -.3 Rosebank Wiri -.6 Residential Howick +.54 Manurewa +. Takanini -.8 Table 3: Correlation coeffi cients for THD v against load current. Te daily and weekly cycles of variation in voltage armonic levels ave been observ ed and documented previously in a number of publications, and mention of tis aspect of armonic variation can be found in textbooks on power quality [3], [4]. In [3], a plot of fift armonic voltage against time over a one-week period sows strong similarity wit Fig.5 in tis paper. In [3], it is stated tat te peak voltage armonic levels can be attributed to user beaviour, and in particular te use of televisions. Wile tis may seem a plausible explanation for suc variation on a residential feeder, it does not explain te postmidnigt peak in voltage armonic levels tat occur at commercial and industrial sites. Additionally, at two of te residential sites included in tis study, THD v levels typically peak at between : p.m. and :3 p.m., wereas it would be expected tat te peak time for television watcing would be between te ours of 7: p.m. and : p.m. ( prime time ). In [5] it is concluded tat varying levels of television use ave a surprisingly low impact on armonic voltage levels. It maybe tat relatively iger levels of THD v are experienced during tese periods of low load because of te effective damping effect on armonic distortion tat occurs during periods of iger load current. In [4], it is stated tat iger levels of triplen armonic currents are commonly observed during te early morning ours wen te load is low, and tat tis is due to transformer excitation current. Tis explanation is questionable given tat transformer excitation current is typically muc less tan % of rated full load current. It also does not explain te variation in THD v levels observed in tis survey on a 9
6 Presented in AUPEC 7, Pert, Western Australia, 9- December, 7 MV network, as triplen armonics do not propagate back into te delta-connected MV distribution network. A possible explanation for te negative correlation between load current and THD v levels observed at most sites is armonic cancellation by te mixing of non-linear single pase and tree pase loads, as described in [6]. It as been found tat mixing single and tree pase loads can result in reduced THD v, te reason being tat te 5 t and 7 t armonic currents of single and tree pase loads are often in counter- pase resulting in at least partial cancellation. It could be suggested tat voltage armonic distortion is not a problem on te network due to te low levels recorded. Typical 95% cumulative probability values across all sites are in te vicinity of % to 3%. Tere is clearly no issue of non-conformance to national or international armonics standards. International standard AS/NZS [7] specifies a compatibility level of 8% for armonic voltages in MV power systems. Te requirements of te New Zealand Electricity Regulations [8] only relate to measurement of voltage armonic distortion levels at te point of common coupling, and so are not generally applicable to armonic levels on an MV distribution network. Te negative correlation between load current and THD v levels as possible implications for te management and regulation of armonic levels on distribution networks. If te igest levels of distortion occur in te middle of te nigt wen connected load is ligt, tis would suggest tat te impact on most customers (and network equipment) will be minimal. It also raises te question as to weter te application of cumulative probability statistics to specify acceptable armonic levels on distribution networks is appropriate. 6. Conclusions Voltage total armonic distortion levels (THD v ) from a variety of monitored sites on a MV distribution network ave been analysed in terms of variation wit time, predominant load type, and level of load current. It as been found tat for commercial and industrial sites, tere is a consistent negative correlation between THD v levels and load current. For te tree residential sites surveyed, two of te sites ad a positive correlation between THD v and load current. Te remaining site ad a negative correlation between THD v and load current, but tis site also displayed some load caracteristics more typical of a commercial or industrial site rater tan a residential Typical cyclic patterns of variation of THD v ave been identified for eac of te tree main load categories. For all sites, peak THD v levels typically occur at nigt, but weter te peak occurs during te late nigt or in te early morning ours depends on te predominant load type. Weekly patterns of THD v variation were also identified, wit iger levels occurring at weekends. Te findings of tis study cast doubt on previously accepted explanations for iger armonic levels at nigt or early morning. Te effects of television use, transformer excitation current, and te levels of triplen armonics do not satisfactorily explain tis penomena. Furter researc is required into te source(s) of tis armonic disturbance. Te assessing and reporting of armonic levels on MV distribution networks by use of cumulative probability statistics appears to be inappropriate, given tat te igest levels of armonic disturbance occur during periods of low load and wen risk to equipment is lower tan at times of iger load. ACKNOWLEDGEMENTS Te autors would like to acknowledge te support of Vector Ltd (NZ) for allowing access to network power quality data and for supporting tis project. REFERENCES [] Integral Energy Power Quality & Reliability Centre Tecnical Note 3: Harmonic Distortion in te Electric Supply System, Marc, [] Nicolson G, Gosbell V, Parsotam A, Te Influence of Site Pysical Caracteristics on Power Quality Performance, Proc. AUPEC 6, December 6, Melbourne Australia. [3] Sclabbac J., Blume D., Stepanblome T., Voltage Quality in Electrical Power Systems, IEE, London. [4] Dugan R., McGranagan M., Beaty H., Electrical Power Systems Quality, McGraw- Hill, New York, ISBN [5] Browne N., Perera S., Ribeiro P.F., Harmonic Levels and Television Events presented at IEEE PES General Meeting, 4-8 June 7, Tampa Florida, USA [6] Hansen S., Nielsen P., Blaabjerg F., Harmonic Cancellation by Mixing Nonlinear Single-Pase and Tree-Pase Loads, IEEE Transactions on Industry Applications, Jan pg.5-59 [7] AS/NZS 6.3.6: Limits Assessment of emission limits for distorting loads in MV and HV power systems. [8] New Zealand Electricity Regulations 997, s_997.pdf 9
A REVIEW OF THE NEW AUSTRALIAN HARMONICS STANDARD AS/NZS
A REVIEW OF THE NEW AUSTRALIAN HARMONICS STANDARD AS/NZS 61000.3.6 Abstract V. J. Gosbell 1, P. Muttik 2 and D.K. Geddey 3 1 University of Wollongong, 2 Alstom, 3 Transgrid v.gosbell@uow.edu.au Harmonics
More informationAbstract 1. INTRODUCTION
Allocating armonic emission to MV customers in long feeder systems V.J. Gosbell and D. Robinson Integral nergy Power Quality Centre University of Wollongong Abstract Previous work as attempted to find
More informationDYNAMIC BEAM FORMING USING CHIRP SIGNALS
BeBeC-018-D04 DYNAMIC BEAM FORMING USING CHIRP SIGNALS Stuart Bradley 1, Lily Panton 1 and Matew Legg 1 Pysics Department, University of Auckland 38 Princes Street, 1010, Auckland, New Zealand Scool of
More informationResearch on harmonic analysis and Simulation of grid connected synchronous motor Jian Huang1,a, Bingyang Luo2,b
5t nternational Conference on Environment, Materials, Cemistry and Power Electronics (EMCPE 06) Researc on armonic analysis and Simulation of grid connected syncronous motor Jian Huang,a, Bingyang Luo,b
More informationOn the relation between radiated and conducted RF emission tests
Presented at te 3 t International Zuric Symposium on Electromagnetic Compatibility, February 999. On te relation between radiated and conducted RF emission tests S. B. Worm Pilips Researc Eindoven, te
More informationEnergy Savings with an Energy Star Compliant Harmonic Mitigating Transformer
Energy Savings wit an Energy Star Compliant Harmonic Mitigating Transformer Tony Hoevenaars, P.Eng, Vice President Mirus International Inc. Te United States Environmental Protection Agency s Energy Star
More informationAnalysis of High Neutral Currents and Harmonic Impacts on Losses and Capacities of Distribution Transformers
roceedings of te World Congress on Engineering 06 Vol I WCE 06, June 9 - July, 06, London, U.K. Analysis of Hig Neutral Currents and Harmonic Impacts on Losses and Capacities of Distribution Transformers
More informationInvestigation of data reporting techniques and analysis of continuous power quality data in the Vector distribution network
University of Wollongong Research Online University of Wollongong Thesis Collection 1954-2016 University of Wollongong Thesis Collections 2006 Investigation of data reporting techniques and analysis of
More informationPower Quality Issues, Problems and Related Standards Avinash Panwar1,ASSISTANT PROFESSOR, MADHAV UNIVERSITY ABU ROAD INDIA
Power Quality Issues, Problems and Related Standards Avinas Panwar1,ASSISTANT PROFESSOR, MADHAV UNIVERSITY ABU ROAD INDIA 1 apanwar84@gmail.com, Summary: Te growt in power electronics as impacted many
More informationLoading transformers with non sinusoidal currents
LES00070-ZB rev. Loading transformers wit non sinusoidal currents K Factor Loading transformers wit non sinusoidal currents... Interpretation / example... 6 Copyrigt 007 ABB, All rigts reserved. LES00070-ZB
More informationA Filtering Scheme for Reducing Harmonics Penetration into Transmission Systems (V1.0)
A Filtering Sceme for Reducing Harmonics Penetration into Systems (V.) J. W. Hagge, Senior Member, IEEE, and L. L. Grigsby, Fellow, IEEE Abstract--Tis paper presents a novel sceme to reduce armonics penetration
More informationUnit 5 Waveguides P a g e 1
Unit 5 Waveguides P a g e Syllabus: Introduction, wave equation in Cartesian coordinates, Rectangular waveguide, TE, TM, TEM waves in rectangular guides, wave impedance, losses in wave guide, introduction
More informationON THE USE OF MULTI-HARMONIC LEAST-SQUARES FITTING FOR THD ESTIMATION IN POWER QUALITY ANALYSIS
Metrol. Meas. Syst., Vol. XIX (2012), No. 2, pp. 295-306. METROLOGY AND MEASUREMENT SYSTEMS Index 330930, ISSN 0860-8229 www.metrology.pg.gda.pl ON THE USE OF MULTI-HARMONIC LEAST-SQUARES FITTING FOR THD
More informationPower Quality Analysis Using An Adaptive Decomposition Structure
Power Quality Analysis Using An Adaptive Decomposition Structure Doğan Gökan Ece 1 and Ömer Nezi Gerek 1 (1) Dept. of Electrical and Elctronics Engineering, Anadolu University, Scool of Engineering and
More informationCalculation of Antenna Pattern Influence on Radiated Emission Measurement Uncertainty
Calculation of Antenna Pattern Influence on Radiated Emission Measurement Uncertainty Alexander Kriz Business Unit RF-Engineering Austrian Researc Centers GmbH - ARC A-444 Seibersdorf, Austria alexander.kriz@arcs.ac.at
More informationJurnal Teknologi HYBRID ACTIVE POWER FILTER METHOD IN FREQUENCY DOMAIN FOR QUALITY IMPROVEMENT IN VARIABLE FREQUENCY DRIVE APPLICATIONS.
Jurnal Tenologi HYBRID ACTIVE POWER FILTER METHOD IN FREQUENCY DOMAIN FOR QUALITY IMPROVEMENT IN VARIABLE FREQUENCY DRIVE APPLICATIONS Min Hoang Hac Le, Kim-An Nguyen 2*, Viet Hung Ngo 3 R&D project, PowerMore
More informationENGINEERING RECOMMENDATION G5/5
ENGINEERING RECOMMENDATION G5/5 EMISSION LIMITS FOR HARMONIC VOLTAGE DISTORTION AND THE CONNECTION OF NON-LINEAR AND RESONANT EQUIPMENT TO TRANSMISSION SYSTEMS AND DISTRIBUTION NETWORKS IN THE UNITED KINGDOM
More informationGrid Filter Design for a Multi-Megawatt Medium-Voltage Voltage Source Inverter
Grid Filter Design for a Multi-Megawatt Medium-Voltage Voltage Source Inverter A.A. Rockill, Grad. Student Member, IEEE, Marco Liserre, Senior Member, IEEE, Remus Teodorescu, Member, IEEE and Pedro Rodriguez,
More informationON TWO-PLANE BALANCING OF SYMMETRIC ROTORS
Proceedings of ME Turbo Expo 0 GT0 June -5, 0, openagen, Denmark GT0-6806 ON TO-PLNE BLNING OF YMMETRI ROTOR Jon J. Yu, P.D. GE Energy 63 Bently Parkway out Minden, Nevada 8943 U Pone: (775) 5-5 E-mail:
More informationA Guide for the Assessment and Mitigation of Bleed, Gloss Change, and Mold in Inkjet Prints During High-humidity Conditions
A Guide for te Assessment and Mitigation of Bleed, Gloss Cange, and Mold in Inkjet Prints During Hig-umidity Conditions Jennifer Burger; University of Rocester and Daniel Burge; Image Permanence Institute,
More informationSchool of Electrical and Computer Engineering, Cornell University. ECE 303: Electromagnetic Fields and Waves. Fall 2007
Scool of Electrical and Computer Engineering, Cornell University ECE 303: Electromagnetic Fields and Waves Fall 007 Homework 11 Due on Nov. 9, 007 by 5:00 PM Reading Assignments: i) Review te lecture notes.
More information5.3 Sum and Difference Identities
SECTION 5.3 Sum and Difference Identities 21 5.3 Sum and Difference Identities Wat you ll learn about Cosine of a Difference Cosine of a Sum Sine of a Difference or Sum Tangent of a Difference or Sum Verifying
More informationPublished in: Proceedings of 8th Annual IEEE Energy Conversion Congress & Exposition (ECCE 2016)
Aalborg Universitet A Multi-Pulse Front-End Rectifier System wit Electronic Pase-Sifting for Harmonic Mitigation in Motor Drive Applications Zare, Firuz; Davari, Pooya; Blaabjerg, Frede Publised in: Proceedings
More informationIndirect Measurement
exploration Georgia Performance Standards M6G1.c, M6A2.c, M6A2.g Te eigts of very tall structures can be measured indirectly using similar figures and proportions. Tis metod is called indirect measurement.
More informationOptimal DG Placement and Sizing in Distribution System for Loss and THD Reduction
International Journal of Electronic and Electrical Engineering. ISSN 0974-2174 Volume 5, Number 3 (2012), pp. 227-237 International Researc Publication House ttp://www.irpouse.com Optimal Placement and
More informationLOADING OF TRANSFORMERS BEYOND NAMEPLATE RATING
LOADING OF TRANSFORMERS BEYOND NAMEPLATE RATING by K. B. M. I. Perera and J. R. Lucas Abstract Te application of a load in excess of nameplate ratings, and/or an ambient temperature iger tan designed of
More informationChannel Estimation Filter Using Sinc-Interpolation for UTRA FDD Downlink
{ Cannel Estimation Filter Using Sinc-Interpolation for UTA FDD Downlink KLAUS KNOCHE, JÜGEN INAS and KAL-DIK KAMMEYE Department of Communications Engineering, FB- University of Bremen P.O. Box 33 4 4,
More informationAalborg Universitet. Published in: IET Power Electronics. DOI (link to publication from Publisher): /iet-pel Publication date: 2018
Aalborg Universitet Load-Independent Harmonic Mitigation in SCR-Fed Tree-Pase Multiple Adjustable Speed Drive Systems wit Deliberately Dispatced Firing Angles Yang, Yongeng; Davari, Pooya; Blaabjerg, Frede;
More informationEffect of Harmonics on Distribution Transformer Losses and Capacity
nternational Journal of Engineering Tecnology Science and Researc SSN 394 3386 June 017 Effect of Harmonics on Distribution Transformer Losses and Capacity Jaspreet Sing Sanjeev Sing Amanpreet Sing unjab
More informationHarmonic Distortion Contribution for the Transmission Loss Allocation in Deregulated Energy Market: A New Scheme for Industry Consumer
J Electr Eng Tecnol Vol. 9, o.?: 74-?, 04 ttp://dx.doi.org/0.5370/jeet.04.9.6.74 ISS(Print) 975-00 ISS(Online) 093-743 Harmonic Distortion Contribution for te Transmission Loss Allocation in Deregulated
More informationLecture-3 Amplitude Modulation: Single Side Band (SSB) Modulation
Lecture-3 Amplitude Modulation: Single Side Band (SSB) Modulation 3.0 Introduction. 3.1 Baseband Signal SSB Modulation. 3.1.1 Frequency Domain Description. 3.1. Time Domain Description. 3. Single Tone
More informationON THE IMPACT OF RESIDUAL CFO IN UL MU-MIMO
ON THE IMPACT O RESIDUAL CO IN UL MU-MIMO eng Jiang, Ron Porat, and Tu Nguyen WLAN Group of Broadcom Corporation, San Diego, CA, USA {fjiang, rporat, tun}@broadcom.com ABSTRACT Uplink multiuser MIMO (UL
More informationCOMPUTATION OF THE NETWORK HARMONIC IMPEDANCE WITH CHIRP-Z TRANSFORM
METROLOGY AND MEASUREMENT SYSTEMS Index 330930, ISSN 0860-8229 www.metrology.pg.gda.pl COMPUTATION OF THE NETWORK HARMONIC IMPEDANCE WITH CHIRP-Z TRANSFORM Krzysztof Duda, Dariusz Borkowski, Andrzej Bień
More informationFINAL REPORT FOR NCHRP 20-7 (364)
FINAL REPORT FOR NCHRP 20-7 (364) Revisions of AASHTO PP 74 Test Metod for Optical sizing and Sape Determination of Glass Beads Utilized in Traffic Marings August 2017 TRANSPORTATION RESEARCH BOARD NAS-NRC
More informationModelling and Control of Gene Regulatory Networks for Perturbation Mitigation
Tis article as been accepted for publication in a future issue of tis journal, but as not been fully edited. Content may cange prior to final publication. Citation information: DOI.9/TCBB.., IEEE/ACM IEEE/ACM
More informationHarmonic Survey of an MV Distribution System. V. Gosbell, D. Mannix, D. Robinson & S. Perera University of Wollongong
Harmonic Survey of an MV Distribution System V. Gosbell, D. Mannix, D. Robinson & S. Perera University of Wollongong Abstract The harmonic survey of a medium voltage distribution system involves three
More informationBinary Search Tree (Part 2 The AVL-tree)
Yufei Tao ITEE University of Queensland We ave already learned a static version of te BST. In tis lecture, we will make te structure dynamic, namely, allowing it to support updates (i.e., insertions and
More informationCAPACITY OF MULTIPLE ACCESS CHANNELS WITH CORRELATED JAMMING
CAPACITY OF MULTIPLE ACCESS CHANNELS WITH CORRELATED JAMMING Sabnam Safiee and Sennur Ulukus Department of Electrical and Computer Engineering University of Maryland College Park, MD ABSTRACT We investigate
More informationCoupling of twin rectangular supersonic jets
J. Fluid Mec. (1998), vol. 54, pp. 12 146. Printed in te United Kingdom c 1998 Cambridge University Press 12 Coupling of twin rectangular supersonic jets By GANESH RAMAN 1 AND RAY TAGHAVI 2 1 NYMA, Inc.,
More informationModelling Capture Behaviour in IEEE Radio Modems
Modelling Capture Beaviour in IEEE 80211 Radio Modems Cristoper Ware, Joe Cicaro, Tadeusz Wysocki cris@titruoweduau 20t February Abstract In tis paper we investigate te performance of common capture models
More informationA Study of Grounding Grid Characteristics with Conductive Concrete
A Study of Grounding Grid Caracteristics wit Conductive Concrete Cun-Yao Lee and Siang-Ren Wang Abstract e purpose of tis paper is to improve electromagnetic caracteristics on grounding grid by applying
More informationDistribution Transformer Losses Evaluation under Non-Linear Load
Distribution Transformer Losses Evaluation under Non-Linear Load *Dalila M.S., Kalid M. N. and Md Sa M. Centre of Electrical Energy System, Faculty of Electrical Engineering, Universiti Teknologi Malaysia,
More informationMethodology To Analyze Driver Decision Environment During Signal Change Intervals: Application of Fuzzy Set Theory
TRANSPORTATON RESEARCH RECORD 1368 49 Metodology To Analyze Driver Decision Environment During Signal Cange ntervals: Application of Fuzzy Set Teory SHNYA KKUCH AND JEFFREY R. REGNER During a signal cange
More informationOverview of MIMO Radio Channels
Helsinki University of Tecnology S.72.333 Postgraduate Course in Radio Communications Overview of MIMO Radio Cannels 18, May 2004 Suiyan Geng gsuiyan@cc.ut.fi Outline I. Introduction II. III. IV. Caracteristics
More informationImage Feature Extraction and Recognition of Abstractionism and Realism Style of Indonesian Paintings
Image Feature Extraction and Recognition of Abstractionism and Realism Style of Indonesian Paintings Tieta Antaresti R P and Aniati Murni Arymurty Faculty of Computer Science University of Indonesia Depok
More informationPunctured Binary Turbo-Codes with Optimized Performance
Punctured Binary Turbo-odes wit Optimized Performance I. atzigeorgiou, M. R. D. Rodrigues, I. J. Wassell Laboratory for ommunication Engineering omputer Laboratory, University of ambridge {ic1, mrdr, iw}@cam.ac.uk
More informationEstimation of Dielectric Constant for Various Standard Materials using Microstrip Ring Resonator
Journal of Science and Tecnology, Vol. 9 No. 3 (017) p. 55-59 Estimation of Dielectric Constant for Various Standard Materials using Microstrip Ring Resonator Pek Jin Low 1, Famiruddin Esa 1*, Kok Yeow
More informationMachine Vision System for Automatic Weeding Strategy in Oil Palm Plantation using Image Filtering Technique
Macine Vision System for Automatic Weeding Strategy in Oil Palm Plantation using Image Filtering Tecnique Kamarul Hawari Gazali, Mod. Marzuki Mustafa, and Aini Hussain Abstract Macine vision is an application
More informationHarmonic Levels and Television Events
1 Harmonic Levels and Television Events N. Browne, Member, IEEE, S. Perera, Member, IEEE, P.F Ribeiro, Fellow, IEEE. Abstract This paper investigates the impact on the harmonic levels of changes in television
More informationOptimal Multiobjective Design of Hybrid Active Power Filters Considering a Distorted Environment
Optimal Multiobjective Design of Hybrid Active Power Filters Considering a Distorted Environment Abstract Te development of new passive, active and ybrid filtering tecniques is important, and te issues
More informationHarmonic Distortion Contribution for the Transmission Loss Allocation in Deregulated Energy Market: A New Scheme for Industry Consumer
J Electr Eng Tecnol.05;0(): -7 ttp://dx.doi.org/0.5370/jeet.05.0..00 ISS(Print) 975-00 ISS(Online) 093-743 Harmonic Distortion Contribution for te Transmission Loss Allocation in Deregulated Energy Market:
More informationCompatibility and Safety Volume for Electromagnetic Exposure Limits in Shared Sites for 2G and 3G Wireless Communications
Compatibility and Safety Volume for Electromagnetic Exposure imits in Sared Sites for G and 3G Wireless Communications Rogelio Jiménez Jiménez*, Diego Ortega abajos*, Florentino Jiménez **, Rafael Herradón**
More informationIMAGE ILLUMINATION (4F 2 OR 4F 2 +1?)
IMAGE ILLUMINATION ( OR +?) BACKGROUND Publications abound wit two differing expressions for calculating image illumination, te amount of radiation tat transfers from an object troug an optical system
More informationImage Reconstruction Based On Bayer And Implementation On FPGA Sun Chen 1, a, Duan Xiaofeng 2, b and Wu Qijing 3, c
2nd International Worksop on Materials Engineering and Computer Sciences (IWMECS 2015) Image Reconstruction Based On Bayer And Implementation On FPGA Sun Cen 1, a, Duan Xiaofeng 2, b and Wu Qijing 3, c
More informationDimensions. Model Number. Features DAD15-8P/35. Optical data coupler
Dimensions Sensitivity adjuster 56 4 45 76 65 4 5 M6 5.5.7 0. 40. 4. 4. 5.5 4. 5.8 Model Number Optical data coupler Features 8 bit parallel data transfer Very large angle of divergence Can be connected
More informationHarmonic distortion analysis on the MV and LV distribution networks: problems, influencing factors and possible solutions
Harmonic distortion analysis on the MV and LV distribution networks: problems, influencing factors and possible solutions Fernando Bastião and Humberto Jorge Department of Electrical Engineering and Computers
More informationThis study concerns the use of machine learning based
Modern AI for games: RoboCode Jon Lau Nielsen (jlni@itu.dk), Benjamin Fedder Jensen (bfje@itu.dk) Abstract Te study concerns te use of neuroevolution, neural networks and reinforcement learning in te creation
More informationSample Survey and Sampling Methods
Sample Survey and Sampling Metods Course unit ECON 53115 MA/MSSc in Economics Dr. WM Semasinge Dept. of Economics Tere are several important concepts relating to te sample survey and sampling metods. Population:
More informationFrancesc Casanellas C. Sant Ramon, Aiguafreda - Spain NATURAL PERSPECTIVE
Francesc Casanellas C. Sant Ramon, 5 08591 Aiguafreda - Spain +34 677 00 00 00 francesc@casanellas.com - www.casanellas.com NATURAL PERSPECTIVE Introduction Te first studies on perspective were made in
More informationComparative Study on Different Dual-Band HIS Structures
ISSN (Print) : 232 3765 International Journal of Advanced Researc in Electrical, (An ISO 3297: 27 Certified Organization) Vol. 4, Issue 1, January 215 Comparative Study on Different Dual-Band HIS Structures
More informationPerformance analysis and comparison of m x n zero forcing and MMSE equalizer based receiver for mimo wireless channel
Songklanakarin J. Sci. Tecnol. 33 (3), 335-340, May - Jun. 0 ttp://www.sjst.psu.ac.t Original Article Performance analysis and comparison of m x n zero forcing and MMSE equalizer based receiver for mimo
More information3D Hole Inspection Using Lens with High Field Curvature
10.1515/msr-2015-0008 MEASUREMENT SCIENCE REVIEW, Volume 15, No. 1, 2015 3D Hole Inspection Using Lens wit Hig Field Curvature Petr Zavyalov Tecnological Design Institute of Scientific Instrument Engineering,
More informationEffects of Harmonic Pollution on Three-Phase Electrical Motors
t nternational Conference on Electrical and Electronics Engineering (CEEE-7) Oct. -, 07 Bali (ndonesia) Effects of Harmonic Pollution on Tree-Pase Electrical Motors Eleonora. Darie, Emanuel. Darie Abstract
More informationCharacteristics of power quality disturbances in Australia: voltage harmonics
University of Wollongong Research Online Faculty of Engineering and Information Sciences - Papers: Part A Faculty of Engineering and Information Sciences 2013 Characteristics of power quality disturbances
More informationDimensions. Model Number. Features DAD15-8P-R Optical data coupler
Dimensions 56 Sensitivity adjuster Mounting bracket OMH-DAD0 45 0. 76 65 4 5 5 M6.7 65.5 ø 5. 5 (4x) 5.5 6 5.8 40. 7 4. Model Number 4. 4. 5.5 Optical data coupler Features 8 bit parallel data transfer
More informationGENERALLY, the power loss in the winding of an
INTL JOURNAL OF ELECTRONICS AND TELECOMMUNICATIONS, 00, VOL. 6, NO., PP. 7-6 Manuscript received July 0, 00: revised September, 00. DOI: 0.78/v077-00-00- Foil Winding Resistance and Power Loss in Individual
More informationPerformance Analysis for LTE Wireless Communication
IOP Conference Series: Materials Science and Engineering PAPER OPEN ACCESS Performance Analysis for LTE Wireless Communication To cite tis article: S Tolat and T C Tiong 2015 IOP Conf. Ser.: Mater. Sci.
More informationAssessing network compliance for power quality performance
University of Wollongong Research Online Faculty of Engineering and Information Sciences - Papers: Part A Faculty of Engineering and Information Sciences 214 Assessing network compliance for power quality
More informationModeling and Characterization of Leakage Inductances for Transformer Winding Fault Studies
Modeling and Caracterization of Leakage Inductances for ransformer Winding Fault Studies Luís M.R. Oliveira 1,3 and A.J. Marques Cardoso,3 1 Instituto Superior de Engenaria, Universidade do Algarve, Faro,
More informationDamping Algorithm based on Phasor Estimation
Damping Algoritm based on Pasor Estimation Lennart Ängquist, Non-member IEEE ABB Power Systems AB S-7 64 Västerås, Sweden Abstract: Te paper describes a new metod to generate te reactance reference for
More informationOPTI-502 Optical Design and Instrumentation I John E. Greivenkamp Homework Set 5 Fall, 2018
Homework Set 5 all, 2018 Assigned: 9/26/18 Lecture 11 Due: 10/3/18 Lecture 13 Midterm Exam: Wednesday October 24 (Lecture 19) 5-1) Te following combination of tin lenses in air is in a telepoto configuration:
More informationDesign of Electrical Parameter Measurement System for Three Phase AC Motor Based on STM32
Sensors & Transducers 2014 by IFSA Publising, S. L. ttp://www.sensorsportal.com Design of Electrical Parameter Measurement System for Tree Pase AC Motor Based on STM32 Haiong Xiao, Jiming Luo, Scool of
More informationEvaluation Model of Microblog Information Confidence Based on BP Neural Network
Evaluation Model of Microblog Information Confidence Based on BP Neural Network Yuguang Ye Quanzou Normal University; Quanzou, 36, Cina Abstract: As te carrier of social media, microblog as become an important
More informationGrade 10 Mathematics: Question Paper 2
Matematics(NSC)/Grade 10/ P2 6 Exemplar Grade 10 Matematics: Question Paper 2 MRKS: 100 TIME: 2 ours QUESTION 1 1.1 Give te co-coordinates of, te new co-ordinates ofte point (-2; 5) if: 1.1.1 It is reflected
More informationELEC 546 Lecture #9. Orthogonal Frequency Division Multiplexing (OFDM): Basic OFDM System
ELEC 546 Lecture #9 Ortogonal Frequency Division Multiplexing (OFDM): Basic OFDM System Outline Motivations Diagonalization of Vector Cannels Transmission of one OFDM Symbol Transmission of sequence of
More informationSELF-TAPPING SCREWS AS REINFORCEMENTS IN BEAM SUPPORTS. I Bejtka H J Blaß. Lehrstuhl für Ingenieurholzbau und Baukonstruktionen Universität Karlsruhe
CIB-W18/39-7-2 INTERNATIONAL COUNCIL FOR RESEARCH AND INNOVATION IN BUILDING AND CONSTRUCTION WORKING COMMISSION W18 - TIMBER STRUCTURES SELF-TAPPING SCREWS AS REINFORCEMENTS IN BEAM SUPPORTS I Bejtka
More informationPerformance Evaluation of Limited Feedback Schemes for 3D Beamforming in LTE-Advanced System
Performance Evaluation of Limited Feedback Scemes for 3D Beamforming in LTE-Advanced System Sang-Lim Ju, Young-Jae Kim, and Won-Ho Jeong Department of Radio and Communication Engineering Cungbuk National
More informationThe deterministic EPQ with partial backordering: A new approach
Omega 37 (009) 64 636 www.elsevier.com/locate/omega Te deterministic EPQ wit partial backordering: A new approac David W. Pentico a, Mattew J. Drake a,, Carl Toews b a Scool of Business Administration,
More informationMIMO-based Jamming Resilient Communication in Wireless Networks
MIMO-based Jamming Resilient Communication in Wireless Networks Qiben Yan Huaceng Zeng Tingting Jiang Ming Li Wening Lou Y. Tomas Hou Virginia Polytecnic Institute and State University, VA, USA Uta State
More informationResearch on Three-level Rectifier Neutral-Point Voltage Balance. Control in Traction Power Supply System of High. Speed Train
Researc on Tree-level Rectifier Neutral-Point Voltage Balance Control in Traction Power Supply System of Hig Speed Train LU XIAO-JUAN, WANG XIN-JU, GUO QI, LI SHU-YUAN Scool of Automation and Electric
More informationEnhanced HARQ Technique Using Self-Interference Cancellation Coding (SICC)
MITUBIHI ELECTRIC REEARCH LABORATORIE ttp://www.merl.com Enanced HARQ Tecnique Using elf-interference Cancellation Coding (ICC) Wataru Matsumoto, Tosiyuki Kuze, igeru Ucida, Yosida Hideo, Pilip Orlik,
More informationAn Efficient Handoff Scheme Using a Minimum Residual Time First Scheme
An Efficient Handoff Sceme Using a Minimum Residual Time First Sceme Bilal Owaidat Rola Kassem and Hamza Issa Abstract Wen a mobile station (MS) wit an ongoing call is about to leave a cell te base station
More informationNo-Reference Image Quality Assessment Based on Localized Gradient Statistics: Application to JPEG and JPEG2000
No-Reference Image Quality Assessment Based on Localized Gradient Statistics: Application to JPEG and JPEG2000 Hantao Liu* a, Judit Redi b, Hani Alers a, Rodolfo Zunino b, Ingrid Heynderickx a,c a Department
More informationPOWER QUALITY MONITORING - PLANT INVESTIGATIONS
Technical Note No. 5 January 2002 POWER QUALITY MONITORING - PLANT INVESTIGATIONS This Technical Note discusses power quality monitoring, what features are required in a power quality monitor and how it
More informationThis is a repository copy of PWM Harmonic Signature Based Islanding Detection for a Single-Phase Inverter with PWM Frequency Hopping.
Tis is a repository copy of PWM Harmonic Signature Based Islanding Detection for a Single-Pase Inverter wit PWM Frequency Hopping. Wite Rose Researc Online URL for tis paper: ttp://eprints.witerose.ac.uk/110053/
More informationThe investment casting process can produce
T E C H N I C L U P T E esigning for Investment Castings Te investment casting process can prouce almost any sape from almost any alloy. s wit all processes, owever, esigning for te process can lower cost
More informationAnalysis of Rectangular Notch Antenna for Dual-Band Operation
Engineering, 00,, 9-96 doi:0.436/eng.00.0 Publised Online February 00 (ttp://www.scirp.org/journal/eng). Analysis of Rectangular Notc Antenna for Dual-Band Operation Abstract Rajes Kumar Viswakarma, Sanjay
More informationModeling and performance evaluations of Alamouti technique in a single frequency network
Tormos et al. EURASIP Journal on Wireless Communications and Networking 2013, 2013:78 RESEARCH Open Access Modeling and performance evaluations of Alamouti tecnique in a single frequency network for DVB-T2
More informationClosed-Form Optimality Characterization of Network-Assisted Device-to-Device Communications
Closed-Form Optimality Caracterization of Network-Assisted Device-to-Device Communications Serve Salmasi,EmilBjörnson, Slimane Ben Slimane,andMérouane Debba Department of Communication Systems, Scool of
More informationOn the Downlink Capacity of WCDMA Systems with Transmit Diversity
On te Downlink Capacity of WCDMA Systems wit ransmit Diversity Vaibav Sing, Oya Yilmaz, Jialing Wang, Kartigeyan Reddy, and S. Ben Slimane Radio Communication Systems Department of Signals, Sensors, and
More informationUpdate on the Australian National Network PQ Survey
Update on the Australian National Network PQ Survey Vic Gosbell 1, Sean Elphick 1, Robert Barr 2 1 Integral Energy Power Quality and Reliability Centre, University of Wollongong 2 Electric Power Consulting
More informationLINEAR IRRADIATION TYPE UV-LED UNIT. Concentration of optical technology
LINEAR IRRADIATION TYPE U-LED UNIT Concentration of optical tecnology LINEAR IRRADIATION TYPE U-LED UNIT Offering U-LED ligt sources wit a cluster of potonics tecnology Te LC-L5G U-LED ligt sources ave
More informationFOURIER ANALYSIS OF A SINGLE-PHASE FULL BRIDGE RECTIFIER USING MATLAB
-774 FOURIER ANALYSIS OF A SINGLE-PHASE FULL BRIDGE RECTIFIER USING MATLAB Bruno Osorno California Sate University Nortridge 8 Nordoff St Nortridge CA 933 Email: bruno@ecs.csun.edu Pone: (88)677-3956 Abstract
More informationComparative Analysis of CDMA Based Wireless Communication under Radio Propagation Environment
Comparative Analysis of CDMA Based Wireless Communication under Radio Propagation Environment Md. Rezaul Hoque Kan Department of EEE, CUET, Cittagong- 4349, Banglades. soagiut@yaoo.com A H M Razibul Islam
More informationSpectrum Sharing with Multi-hop Relaying
Spectrum Saring wit Multi-op Relaying Yong XIAO and Guoan Bi Scool of Electrical and Electronic Engineering Nanyang Tecnological University, Singapore Email: xiao001 and egbi@ntu.edu.sg Abstract Spectrum
More informationA new SAIFI based voltage sag index
University of Wollongong Research Online Faculty of Engineering - Papers (Archive) Faculty of Engineering and Information Sciences 28 A new SAIFI based voltage sag index Robert A. Barr University of Wollongong,
More informationHarmonics and Flicker Levels at a Sub- Transmission Substation: A Measurement Experience
University of Wollongong Research Online Faculty of Informatics - Papers (Archive) Faculty of Engineering and Information Sciences 2003 Harmonics and Flicker Levels at a Sub- Transmission Substation: A
More informationMulti-Objectivity for Brain-Behavior Evolution of a Physically-Embodied Organism
Multi-Objectivity for Brain-Beavior Evolution of a Pysically-Embodied Organism Jason Teo and Hussein A. Abbass Artificial Life and Adaptive Robotics (A.L.A.R.) Lab, Scool of Computer Science, University
More informationPublication V by author
Publication V Jyrki T. J. Penttinen. 2008. DVB H coverage estimation in igly populated urban area. In: Te 58t Annual IEEE Broadcast Symposium (ABS 2008. Alexandria, VA, USA. 15 17 October 2008. IEEE Broadcast
More informationGenetic Algorithm for Wireless Sensor Network With Localization Based Techniques
International Journal of Scientific and Researc Publications, Volume, Issue 9, September 201 1 Genetic Algoritm for Wireless Sensor Network Wit Localization Based Tecniques * Kapil Uraiya, ** Dilip Kumar
More information