LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION
|
|
- Loreen Palmer
- 6 years ago
- Views:
Transcription
1 LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION Andreas SUMPER sumper@citcea.upc.es Antoni SUDRIÀ sudria@citcea.upc.es Samuel GALCERAN galceran@citcea.upc.es Joan RULL rull@citcea.upc.es Daniel BERNADÓ Dirección de Explotación y Calidad de Suministro Calidad de la Explotación FECSA-ENDESA-Spain dbernado@fecsa.es Beatriz RAFOLS Dirección de Explotación y Calidad de Suministro Calidad de la Explotación FECSA-ENDESA-Spain brafols@fecsa.es 1 INTRODUCTION The main source of transient overvoltages on utility systems is lightning flashes, which cause important transient overvoltages. The consequences of these transient overvoltages, as well known, are insulation stress, short interruptions, voltage dips due to tripping, and finally, long interruptions due to permanent faults. This results in power quality problems for the customer and damage or lifetime reduction of the substation equipment. In order to protect the substation equipment from the overvoltages it is necessary to apply surge arresters. For the right application of surge arresters it is also necessary to study the interaction between the arresters and the other station equipment and the power line. In the following paper we will discuss a realised case study of a 220kV / 25 kv substation in semi-rural area in the north-east of Spain. At fist, the statistical data of power interruptions are analyzed to discover potential for improvements and, at last, the results of one of the realised simulation are shown in the second part of this article. 2 GENERAL 2.1 Typical network configuration The typical configuration of a substation in the northeastern region of Spain is represented in figure 1. The studied substation is connected to the transportation network by two 220 kv lines. There are two levels of distribution voltages, namely 66 kv and 25 kv rated voltage. The 66 kv distribution network serves to supply a local chemical industry by cable, and in this case, it will not be part of the study. The 25 kv distribution network is used to supply the semirural area nearby the substation by cable and is followed by an overhead line (figure 2). In this figure we can observe that the substation is connected to 8 distribution lines by an underground cable, which connects the substation with a disconnector (cable section 2). The length of this section is between 20 and 45 meters. The length of the cable connection between the disconnector and the overhead line (cable section 1) reaches between 35 and 263 meters. The poles supporting the overhead line are usually made of steel with a medium ground impedance of 12 Ω. The 25 kv level is used in this region in general for the distribution, which is not a standard rated voltage established by the IEC. This means that the equipment used in 25 kv substations and lines has to be the highest voltage for the equipment U m of 36 kv (1 kv BIL), which means an overinsulation of the equipment in relationship with the rated voltage. Furthermore, the switching events of two capacitor banks with each 5,4 MVA should be considered. In this case, the transient overvoltages due to capacitor switching were determinated by numerical simulation and are not considered as critical. 220 kv 0/60/40 MVA 66 kv 25 kv 25 kv Figure 1: Configuration of the studied substation Figure 2: Configuration of the studied 25 kv line 2.2 Lightning as origin of transient overvoltage As mentioned, lightning is the main source of transient overvoltages. Due to the lack of shielding, the overvoltages can be divided into overvoltages due Lines 40 MVA 5,4 MVA 5,4 MVA kv Cable Sect. 1 Cable Sect. 2 Substation 3 CEA_Sumper_A1 Session 2 Paper No 2-1 -
2 to direct lightning and overvoltage due to indirect lightning. According to [1] the number of direct strokes per year can be evaluated by the following formula: N d = K N ( b +,5 H where: g ) 1 (1) N g is the ground flash density H is the average height of the line b is the horizontal distance between the outside conductors K o is the orographic coefficient The expected number of direct strokes for the studied lines (N g = 1,8; H = 5m; b = 2m and K o = 1,8) is 12,02 per year and 0 km. The average lightning current in year 1999 was 16,6 A. The expected number of induced lightning overvoltages higher than a given value U (kv) is shown in the following formula [1]: ( 1 c) Ni = 0,19 3,5 + 2,5 Log N g H (2) U where c is the coupling factor (for unshielded lines c = 0) and the parameters N g and H are the same as in formula (1). For our studied line the number of induced lightning overvoltages which exceed the lightning insulation level (BIL) of 1 kv, are,36 strikes per year and 0 km. The total flashover rate is 22,38 flashovers for the studied line, if shielding by nearby objects is not considered. 3 OVERVOLTAGES AND POWER QUALITY Overvoltages have a great influence on the quality of supply. On one hand, the direct influence of transient overvoltages stresses insulation and can lead to equipment damage. On the other hand, permanent faults, caused by transient overvoltages, are the main origin of interruptions. Short interruptions are mainly caused by breaker tripping (breaker opens for minimum 20 cycles and recloses) to clear earth faults. Sensitive equipment will almost surely trip during this type of interruption. Long interruptions are mainly caused by the earth faults, which are not clearable by breaker tripping, or insulation faults and damage to MV equipment. 3,75 Figure 3 shows the power interruptions per line and year which are caused by lightning. It is clearly seen that lines like Line A, are more affected by a higher number of interruptions than lines like Line M, which can be explained by the constructive differences (the lines M and N are the only line with shielding cables). On the other hand, due to the statistical likelihood of lightning flashes, lines like line A have a high fluctuation between the four studied years Line A Line B Line C Line D Line E Line F Line G Line H Line I Line J Line K Line L Line M Line N Line O Figure 3: Power quality events due to lightning in the studied MV network in north eastern Spain. In figure 4 the percentage of interruptions, with reference to the duration of interruption, in the period from 1999 to 2002 is shown. It can be seen that the number of interruption decreases with the duration of the interruption. The same conclusion is valid for in figure 5, which presents the interrupted transformer in relation with the duration of interruption. Depending on the connected power and number of consumers the interrupted power can vary strongly, which is evidenced by the second bars in figure 4 and 5. % of total interruptions,00% 60,00%,00% 40,00%,00% 20,00%,00% 0,00% Interruptions due to lightning Duration in min. Figure 4: Number of events due to lightning Statisical data In the next section, statistical data about power interruption MV network which is connected to the substation is analysed. The data was collected by the system SGI (Sistema de Gestión de Incidencias) and refers exclusively to the MV network caused by lightning events from the year 1999 to CEA_Sumper_A1 Session 2 Paper No 2-2 -
3 Transformer Power Power interruptions due to lightning At last we can analyze the effects of transient overvoltages on long interruptions and the type of failure which caused the long term interruption. (figure 8). The main types of failure are caused by the intermediate protection, and in the case of a permanent short circuit fault, the main feeder breaker disconnects the line [4]. Nearby 26% of the failures are caused by insulation failures of apparatus Duration in min Figure 5: Transformer power of interruptions due to lightning Interruptions with durations of shorter than three minutes, after EN 160 [3], are defined as short interruption and interruptions longer than three minutes are considered as long interruptions. After this division, it is seen that 44,6 % of all interruptions in the studied network are short interruptions and 56.4% are long interruptions (see figure 6). Long interruptions effects 11,3% Insulation Failure 26,4% 47,2% 15,1% Main Breaker Interruption Intermediate Protections Without Failure or no Defect Localized Figure 8: Relationship between short term interruptions and long term interruptions in the investigated network. 44,6% Percentage of the type of interruption due to lightning ,4% Long interruptions Short interruptions Figure 6: Relationship between short interruptions and long interruptions in the investigated network. Figure 7 presents the long interruptions in the studied network. The number of interruptions, like in figure 4, decreases to the duration as the interruption increases. % of total interruptions 25,00% 20,00% 15,00%,00% 5,00% 0,00% Long interruptions due to lightning Duration in min. Figure 7: Relationship between short term interruptions and long term interruptions in the investigated network. 3.2 Conclusion from the statistics An overvoltage disturbance leads to an intervention by the power system protection, which in nonredundant networks, like radial MV networks, causes an interruption for a number of customers. To reduce the duration of interruption, fuse saving is applied, which means that the main breaker is working with fast tripping. Permanent faults lead to main beaker or intermediate protection interruptions. Moreover, with 26,4 % long interruptions due to insulation faults, it is recommendable to revise methods to protect equipment (e.g. surge arrester) and the overvoltages proceeding from lightning events. 4 MIXED NETWORK AND SUBSTATION OVERVOLTAGE PROTECTION In our case it is necessary to improve the substation protection from overvoltages. On one hand, we have the possibility to protect the overhead line itself against lightning strikes. In some literature [2] overinsulation of a line, addition of shielding, or application of surge arrester on every pole are presented as methods of protection. All these methods entail high investments. On the other hand it is possible to protect only the susceptible apparatus with surge arresters, which is also the case in our substation. All substations, which are connected via a cable to an overhead line, are in danger with regard to possible overvoltages caused by lightning flashes. The studied substation is also connected to a mixed network with alternating parts, overhead lines, and cables. The overhead lines are unshielded and therefore at risk for lightning overvoltages. As is well known, the CEA_Sumper_A1 Session 2 Paper No 2-3 -
4 lightning overvoltages propagate in the network and can stress cable terminals and other apparatus connected to the cable and line. It is necessary take measures to protect the cable terminals and apparatus with surge arresters. 4.1 Configuration of the simulated network The main feeders of our substation with initial cable sections is shown in figure 9. The overhead line is connected at point 1 to a cable network, which consists of two cable sections. At point 2 the cable section 1 ends and is connected to an air disconnector (see figure ). The cable endings at point 1 and 2 are protected with a surge arrester. The second cable section stretches from point 2 to point 3 to the main breaker in the indoor substation. The cable sections at the studied substation vary from 35 m to 263 m. Overvoltages can cause damage to station apparatus at point 3 due to the reflected waves at the conjunctions. Therefore it is necessary to verify if the overvoltage protection of the two applied surge arresters is sufficient [5]. different lengths of cables. The EMTP is probably the most widely-used tool for the analysis of such transient and travelling waves. For the computation, the system was divided into suitable parts which were substituted by equivalent circuits. Analysis of the equivalent lumped-constants network is carried out by means of EMTP. Each branch (transformer, cable, transmission line) together with the lightning waveform constitute the input to EMTP of which the output is the transient waveform. The simulation was carried out with the following parameters: Overhead line: LINE CONSTANTS 3 phase, steel pole, surge impedance 0Ω, v= 3. 5 km/s; total length 5,5 km. Cable: XPLE cable; Saenger (General Cable); Size = 6 mm 2 ; R = Ω/km; C = 0,334 µf/km Surge arrester: Type ASEA 42XBD, used MODEL: Type 99 Lightning source: Type Heidler, 15 ka, distance to substation: 0,5 km The length of the cable sections are shown in table Line Line Cable Cable Figure 9: Circuit used to investigate overvoltages Figure : Air disconnector at point Simulation and simulation parameters To study the transient on high voltage lines and in underground cables and in substations, numerical computations with the well known Electromagnetic Transient Program (EMTP/ATP) were carried out for Line Cable section 1 Cable section 2 Line E-F 253 m m Line G-H 35 m 45 m Line I-J 263 m 38,5 m Line A-B 112 m 22 m Table 1: Cable section length used for the simulation 4.3 Simulation results The results of the simulations are represented in figures 11 to 14. The figures show the overvoltages in the points 1 to 3 during the application of a lightning surge with a lightning current of 15 ka at 0,5 km distance to the substation. Figure 12 shows the most inconvenient cable length proportion with 112m and 22 m in spite of the damping function of the first section of the cable. Mainly, the oscillating overvoltage at the end of the cable is caused by the steepness of the overvoltage in point 2. In figure 11, the proportion between the two cable sections is 253 to and it is clearly shown that the rising overvoltage in point 2 is less steep, which leads to lower magnitude of the overvoltage in point 3. In the four cases it was shown that the substation overvoltage protection is sufficient with the application of two surge arresters at point 1 and point 2. A third surge arrester at point 3 is not necessary. In all simulated cases, the overvoltage at every point at the cable network is under the limits of the basic insulation level (BIL) of 1 kv. CEA_Sumper_A1 Session 2 Paper No 2-4 -
5 Line E-F; Sect.1= 253m; Sect.2= m Lines A-B, Sect.1= 112 m; Sect.2= 22m [ms] [ms] 0. Figure 11: Simulated overvoltages on lines E-F Line G-H; Sect.1= 35 m; Sect.2= 45 m; [ms] 0. Figure 12: Simulated overvoltages on lines G-H Line I-J; Sect.1= 263m; Sect.2= 38,5m [ms] 0. Figure 13: Simulated overvoltages on lines I-J Figure 14: Simulated overvoltages on lines A-B 5 CONCLUSIONS At first, statistical data from power interruptions due to lightning events of the studied network was analyzed. Due to a high activity of lightning and the resulting overvoltages, an increased rate of insulation failures was detected. The medium voltage substation, which is connected via two cable sections to the overhead line, is protected against lightning surges by two surge arrester, installed at the begin and end of the first cable section. Based on what was found in the simulation, an overvoltage protection in the substation is not necessary. 6 REFERENCES [1] Porrino A. (Joint Cired/Cigre Working Group 05); Protection of MV and LV Network against Lightning. Part I: Basic Information; 14 th International Conference and Exhibition on Electricity Distribution, Part 1, Subject area 2: Disturbances and overvoltages; IEE Press; 1997; [2] Porrino A. (Joint Cired/Cigre Working Group 05); Protetion of MV and LV Network against Lightning. Part II: Application to MV Networks, 14 th International Conference and Exibition on Electricity Distribution, Part 1, Subject area 2: Disturbances and Overvoltages; IEE Press; 1997; [3] Bollen, M. H. J.; Understanding Power Quality, Voltage Sags and Interrumptuions; IEEE Press; 2000; IEEE New York; US, [4] Dugan, R. C.; McGranaghan F. M.; Beaty H. W.; Electrical Power System Quality; McGraw-Hill; 1996; New York; US, [5] Balzer G.; Overvoltage Protection for MV substations.; 14 th International Conference and Exibition on Electricity Distribution, Part 1, Subject area 2: Disturbances and overvoltages; IEE Press; 1997; CEA_Sumper_A1 Session 2 Paper No 2-5 -
High voltage engineering
High voltage engineering Overvoltages power frequency switching surges lightning surges Overvoltage protection earth wires spark gaps surge arresters Insulation coordination Overvoltages power frequency
More informationPREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS
29 th International Conference on Lightning Protection 23 rd 26 th June 2008 Uppsala, Sweden PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS Ivo Uglešić Viktor Milardić Božidar
More informationCHOICE OF MV FEEDER BIL TO MAXIMIZE QOS AND MINIMIZE EQUIPMENT FAILURE
CHOICE OF MV FEEDER BIL TO MAXIMIZE QOS AND MINIMIZE EQUIPMENT FAILURE Willem DIRKSE VAN SCHALKWYK ESKOM - South Africa vschalwj@eskom.co.za ABSTRACT A high BIL (300 kv) on a MV feeder ensures that no
More informationSession Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages
Session Four: ractical Insulation Co-ordination Session Four: ractical Insulation Co-ordination for Lightning Induced Overvoltages Jason Mayer Technical Director, Energy Services, Aurecon Introduction
More informationTECHNICAL NOTE 2.0. Overvoltages origin and magnitudes Overvoltage protection
ECHNICAL NOE 2.0 Overvoltages origin and magnitudes Overvoltage protection he ECHNICAL NOES (N) are intended to be used in conjunction with the APPLICAION GIDELINES Overvoltage protection Metaloxide surge
More informationUtility System Lightning Protection
Utility System Lightning Protection Many power quality problems stem from lightning. Not only can the high-voltage impulses damage load equipment, but the temporary fault that follows a lightning strike
More informationLightning overvoltage and protection of power substations
Lightning overvoltage and protection of power substations Mahmud Trainba 1, Christos A. Christodoulou 2, Vasiliki Vita 1,2, Lambros Ekonomou 1,2 1 Department of Electrical and Electronic Engineering, City,
More informationThe relationship between operating maintenance and lightning overvoltage in distribution networks based on PSCAD/EMTDC
The relationship between operating maintenance and lightning overvoltage in distribution networks based on PSCAD/EMTDC Xiaojun Chena *, Wenjie Zhengb, Shu Huangc, Hui Chend Electric Power Research Institute
More informationModeling insulation in high-voltage substations
38 ABB REVIEW DESIGNED FOR SAFETY DESIGNED FOR SAFETY Modeling insulation in high-voltage substations The goal of insulation coordination is to determine the dielectric strength of transformers and other
More informationParameters Affecting the Back Flashover across the Overhead Transmission Line Insulator Caused by Lightning
Proceedings of the 14 th International Middle East Power Systems Conference (MEPCON 10), Cairo University, Egypt, December 19-21, 2010, Paper ID 111. Parameters Affecting the Back Flashover across the
More informationA Study on Lightning Overvoltage Characteristics of Grounding Systems in Underground Distribution Power Cables
J Electr Eng Technol Vol. 9, No. 2: 628-634, 2014 http://dx.doi.org/10.5370/jeet.2014.9.2.628 ISSN(Print) 1975-0102 ISSN(Online) 2093-7423 A Study on Lightning Overvoltage Characteristics of Grounding
More informationTab 2 Voltage Stresses Switching Transients
Tab 2 Voltage Stresses Switching Transients Distribution System Engineering Course Unit 10 2017 Industry, Inc. All rights reserved. Transient Overvoltages Decay with time, usually within one or two cycles
More informationPower Quality and Reliablity Centre
Technical Note No. 8 April 2005 Power Quality and Reliablity Centre TRANSIENT OVERVOLTAGES ON THE ELECTRICITY SUPPLY NETWORK CLASSIFICATION, CAUSES AND PROPAGATION This Technical Note presents an overview
More informationX International Symposium on Lightning Protection
X International Symposium on Lightning Protection 9 th -13 th November, 2009 Curitiba, Brazil LIGHTNING SURGES TRANSFERRED TO THE SECONDARY OF DISTRIBUTION TRANSFORMERS DUE TO DIRECT STRIKES ON MV LINES,
More informationSimulation of Lightning Transients on 110 kv overhead-cable transmission line using ATP-EMTP
Simulation of Lightning Transients on 110 kv overhead-cable transmission line using ATP-EMTP Kresimir Fekete 1, Srete Nikolovski 2, Goran Knezević 3, Marinko Stojkov 4, Zoran Kovač 5 # Power System Department,
More informationSimulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models
International Journal of Electrical & Computer Sciences IJECS-IJENS Vol:15 No:03 39 Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models Shen-Wen Hsiao, Shen-Jen
More informationMV network design & devices selection EXERCISE BOOK
MV network design & devices selection EXERCISE BOOK EXERCISES 01 - MV substation architectures 02 - MV substation architectures 03 - Industrial C13-200 MV substation 04 - Max. distance between surge arrester
More informationLightning Flashover Rate of an Overhead Transmission Line Protected by Surge Arresters
IEEE PES General Meeting June 23-27, 27, 2007, Tampa Lightning Flashover Rate of an Overhead Transmission Line Protected by Surge Arresters Juan A. Martinez Univ. Politècnica Catalunya Barcelona, Spain
More informationProtection against unacceptable voltages in railway systems
Bernhard Richter*, Alexander Bernhard*, Nick Milutinovic** SUMMERY Based on the system voltages for AC and DC railway systems the required voltage ratings for modern gapless MO surge arresters are given.
More informationABSTRACTS of SESSION 6
ABSTRACTS of SESSION 6 Paper n 1 Lightning protection of overhead 35 kv lines by antenna-module long flashover arresters Abstract: A long-flashover arrester (LFA) of a new antenna-module type is suggested
More informationLightning performance of a HV/MV substation
Lightning performance of a HV/MV substation MAHMUD TAINBA, LAMBOS EKONOMOU Department of Electrical and Electronic Engineering City University London Northampton Square, London EC1V HB United Kingdom emails:
More informationGIS Disconnector Switching Operation VFTO Study
GIS Disconnector Switching Operation VFTO Study Mariusz Stosur, Marcin Szewczyk, Wojciech Piasecki, Marek Florkowski, Marek Fulczyk ABB Corporate Research Center in Krakow Starowislna 13A, 31-038 Krakow,
More informationABSTRACT 1.0 INTRODUCTION LIST OF SYMBOLS
Lightning protection of pole-mounted transformers and its applications in Sri Lanka Prof. J R Lucas* and D A J Nanayakkara # *University of Moratuwa, # Lanka Transformers Limited ABSTRACT This paper presents
More informationVFTO STUDIES DUO TO THE SWITCHING OPERATION IN GIS 132KV SUBSTATION AND EFFECTIVE FACTORS IN REDUCING THESE OVER VOLTAGES
VFTO STUDIES DUO TO THE SWITCHING OPERATION IN GIS 132KV SUBSTATION AND EFFECTIVE FACTORS IN REDUCING THESE OVER VOLTAGES Shohreh Monshizadeh Islamic Azad University South Tehran Branch (IAU), Tehran,
More informationEffect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System
IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 17, NO. 2, APRIL 2002 569 Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System Li-Ming Zhou, Senior Member, IEEE,
More informationG. KOEPPL Koeppl Power Experts Switzerland
PS3: Substation Design: New Solutions and Experiences Bus-Node Substation A Big Improvement in Short-Circuit and Switching Properties at Reduced Substation Costs G. KOEPPL Koeppl Power Experts Switzerland
More informationThe Many Uses of Transmission Line Arresters
Introduction It was not realized at the time, but the 1992 introduction of the polymer-housed transmission line arrester (TLA) was clearly a game changer in the practice of lightning protection of transmission
More informationOvervoltage Protection of Light Railway Transportation Systems
Overvoltage Protection of Light Railway Transportation Systems F. Delfino, R. Procopio, Student Member, IEEE, and M. Rossi, Student Member, IEEE Abstract In this paper the behavior of the power supply
More informationABSTRACT 1 INTRODUCTION
ELECTROMAGNETIC ANALYSIS OF WIND TURBINE GROUNDING SYSTEMS Maria Lorentzou*, Ian Cotton**, Nikos Hatziargyriou*, Nick Jenkins** * National Technical University of Athens, 42 Patission Street, 1682 Athens,
More informationEffect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers
Voltage (kv) Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers Li-Ming Zhou, Senior Member, IEEE and Steven Boggs, Fellow, IEEE Abstract: The high frequency attenuation
More informationModeling of overhead transmission lines with line surge arresters for lightning overvoltages. Poland
Application of Line Surge Arresters in Power Distribution and Transmission Systems COLLOQUIUM Cavtat 2008 Modeling of overhead transmission lines with line surge arresters for lightning overvoltages M.
More informationNotes 1: Introduction to Distribution Systems
Notes 1: Introduction to Distribution Systems 1.0 Introduction Power systems are comprised of 3 basic electrical subsystems. Generation subsystem Transmission subsystem Distribution subsystem The subtransmission
More informationIn order to minimise distribution (11 and 22 kv) feeder breaker
Lightning protection for equipment on MV feeders By WJD van Schalkwyk and M du Preez, Eskom This article presents the influence of lightning on MV feeders supplying small power users (400/230 V) with focus
More informationAnalysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP
IJSTE - International Journal of Science Technology & Engineering Volume 3 Issue 2 August 216 ISSN (online): 2349-784X Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP
More informationThe line-lightning performance and mitigation studies of shielded steelstructure
The line-lightning performance and mitigation studies of shielded steelstructure distribution lines ASNAWI MOHD BUSRAH, MALIK MOHAMAD Energy System Group TNB Research Sdn Bhd No 1, Lorong Ayer Hitam, 43000
More informationOvervoltage Protection
Overvoltage Protection S T U D E N T M A N U A L March 31, 2005 2 STUDENT TRAINING MANUAL Prerequisites: Single-Phase Transformer Load Checks Objectives: From memory, you will be able to describe the electrical
More informationVoltage Sag Mitigation by Neutral Grounding Resistance Application in Distribution System of Provincial Electricity Authority
Voltage Sag Mitigation by Neutral Grounding Resistance Application in Distribution System of Provincial Electricity Authority S. Songsiri * and S. Sirisumrannukul Abstract This paper presents an application
More informationInvestigation on the Performance of Different Lightning Protection System Designs
IX- Investigation on the Performance of Different Lightning Protection System Designs Nicholaos Kokkinos, ELEMKO SA, Ian Cotton, University of Manchester Abstract-- In this paper different lightning protection
More informationWhen surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS
TRANSFORMER IN GRID When surge arres t ers are installed close to a power transformer, they provide protection against lightning overvoltage ABSTRACT The aim of this research article is to determine the
More informationModeling for the Calculation of Overvoltages Stressing the Electronic Equipment of High Voltage Substations due to Lightning
Modeling for the Calculation of Overvoltages Stressing the Electronic Equipment of High Voltage Substations due to Lightning M. PSALIDAS, D. AGORIS, E. PYRGIOTI, C. KARAGIAΝNOPOULOS High Voltage Laboratory,
More informationAdjustable Speed Drives and Power Quality
Adjustable Speed Drives and Power Quality S. Galceran 1, M. Teixidó 2, A. Sumper 2, J. Casas 3, J. Sánchez 3 1 Department of Electrical Engineering E.T.S.E.I.B., UPC Av. Diagonal, 647, 08028 Barcelona
More informationInsulation Co-ordination For HVDC Station
Insulation Co-ordination For HVDC Station Insulation Co-ordination Definitions As per IEC 60071 Insulation Coordination is defined as selection of dielectric strength of equipment in relation to the operating
More informationLightning Protection of Distribution Substations by Using Metal Oxide Gapless Surge Arresters Connected in Parallel
International Journal of Power and Energy Research, Vol. 1, No. 1, April 2017 https://dx.doi.org/10.22606/ijper.2017.11001 1 Lightning Protection of Distribution Substations by Using Metal Oxide Gapless
More information2000 Mathematics Subject Classification: 68Uxx/Subject Classification for Computer Science. 281, 242.2
ACTA UNIVERSITATIS APULENSIS Special Issue SIMULATION OF LIGHTNING OVERVOLTAGES WITH ATP-EMTP AND PSCAD/EMTDC Violeta Chiş, Cristina Băla and Mihaela-Daciana Crăciun Abstract. Currently, several offline
More informationEXPERIMENTAL INVESTIGATION OF A TRANSIENT INDUCED VOLTAGE TO AN OVERHEAD CONTROL CABLE FROM A GROUNDING CIRCUIT
EXPERIMENTAL INVESTIGATION OF A TRANSIENT INDUCED VOLTAGE TO AN OVERHEAD CONTROL CABLE FROM A GROUNDING CIRCUIT Akihiro AMETANI, Tomomi OKUMURA, Naoto NAGAOKA, Nobutaka, MORI Doshisha University - Japan
More informationAnalysis of lightning performance of 132KV transmission line by application of surge arresters
Analysis of lightning performance of 132KV transmission line by application of surge arresters S. Mohajer yami *, A. Shayegani akmal, A.Mohseni, A.Majzoobi High Voltage Institute,Tehran University,Iran
More informationISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements
Division 502 Technical Applicability 1(1) Section 502.1 applies to: Expedited Filing Draft August 22, 2017 the legal owner of an aggregated generating facility directly connected to the transmission system
More informationEarthing of Electrical Devices and Safety
Earthing of Electrical Devices and Safety JOŽE PIHLER Faculty of Electrical Engineering and Computer Sciences University of Maribor Smetanova 17, 2000 Maribor SLOVENIA joze.pihler@um.si Abstract: - This
More informationCalculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS
Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS M. Kondalu, Dr. P.S. Subramanyam Electrical & Electronics Engineering, JNT University. Hyderabad. Joginpally B.R. Engineering
More informationTopic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017
Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017 NAME: LOCATION: 1. The primitive self-inductance per foot of length
More informationEffect of Surge Arrester on Overhead Transmission Lines as Shield against Over Voltage
Effect of Surge Arrester on Overhead Transmission Lines as Shield against Over Voltage Swati Agrawal Assistant Professor, MATS University, Raipur (C.G) Abstract: This paper describes the usage of surge
More informationRoadmap For Power Quality Standards Development
Roadmap For Power Quality Standards Development IEEE Power Quality Standards Coordinating Committee Authors: David B. Vannoy, P.E., Chair Mark F. McGranghan, Vice Chair S. Mark Halpin, Vice Chair D. Daniel
More informationRESEARCH ON CLASSIFICATION OF VOLTAGE SAG SOURCES BASED ON RECORDED EVENTS
24 th International Conference on Electricity Distribution Glasgow, 2-5 June 27 Paper 97 RESEARCH ON CLASSIFICATION OF VOLTAGE SAG SOURCES BASED ON RECORDED EVENTS Pengfei WEI Yonghai XU Yapen WU Chenyi
More informationAnalysis of current distribution among long-flashover arresters for 10 kv overhead line protection against direct lightning strikes
2014 International onference on Lightning Protection (ILP), Shanghai, hina nalysis of current distribution among long-flashover arresters for 10 kv overhead line protection against direct lightning strikes
More informationLightning Performance Improvement of 115 kv and 24 kv Circuits by External Ground in MEA s Distribution System
Lightning Performance Improvement of 115 kv and 24 kv Circuits by External Ground in MEA s Distribution System A. Phayomhom and S. Sirisumrannukul Abstract This paper presents the guidelines for preparing
More informationLightning transient analysis in wind turbine blades
Downloaded from orbit.dtu.dk on: Aug 15, 2018 Lightning transient analysis in wind turbine blades Candela Garolera, Anna; Holbøll, Joachim; Madsen, Søren Find Published in: Proceedings of International
More information10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY
9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor
More informationVoltage Sags Evaluating Methods, Power Quality and Voltage Sags Assessment regarding Voltage Dip Immunity of Equipment
s Evaluating Methods, Power Quality and s Assessment regarding Voltage Dip Immunity of Equipment ANTON BELÁŇ, MARTIN LIŠKA, BORIS CINTULA, ŽANETA ELESCHOVÁ Institute of Power and Applied Electrical Engineering
More informationSimulation of Short Circuit and Lightning Transients on 110 kv Overhead and Cable Transmission Lines Using ATP-EMTP
Simulation of Short Circuit and Lightning Transients on 110 kv Overhead and Cable Transmission Lines Using ATP-EMTP Predrag Maric 1, Srete Nikolovski 1, Laszlo Prikler 2 Kneza Trpimira 2B 1 Faculty of
More informationMaximum Lightning Overvoltage along a Cable due to Shielding Failure
Maximum Lightning Overvoltage along a Cable due to Shielding Failure Thor Henriksen Abstract--This paper analyzes the maximum lightning overvoltage due to shielding failure along a cable inserted in an
More informationSAFETY ASPECTS AND NOVEL TECHNICAL SOLUTIONS FOR EARTH FAULT MANAGEMENT IN MV ELECTRICITY DISTRIBUTION NETWORKS
SAFETY ASPECTS AND NOVEL TECHNICAL SOLUTIONS FOR EARTH FAULT MANAGEMENT IN MV ELECTRICITY DISTRIBUTION NETWORKS A. Nikander*, P. Järventausta* *Tampere University of Technology, Finland, ari.nikander@tut.fi,
More informationOverview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E.
Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E. HP Critical Facility Services delivered by EYP MCF What is VOLTAGE? Difference of Electric Potential
More informationLightning Overvoltages on Low Voltage Circuit Caused by Ground Potential Rise
Lightning Overvoltages on Low Voltage Circuit Caused by Ground Potential Rise S. Sekioka, K. Aiba, S. Okabe Abstract-- The lightning overvoltages incoming from an overhead line such as a power distribution
More informationLightning current field measurement on a transmission line, comparison with electromagnetic transient calculations
Lightning current field measurement on a transmission line, comparison with electromagnetic transient calculations A. Xemard, M. Mesic, T. Sadovic, D. Marin, S. Sadovic Abstract- A lightning experiment
More informationSWITCHING OVERVOLTAGES IN A 400-KV CABLE SYSTEM
SWITCHING OVERVOLTAGES IN A 4-KV CABLE SYSTEM Mustafa Kizilcay University of Siegen Siegen, Germany kizilcay@uni-siegen.de Abstract This paper deals with the computation of switching overvoltages in a
More informationMODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT
MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT Claus NEUMANN Darmstadt University of Technology Germany claus.neumann@amprion.net Klaus WINTER Swedish Neutral
More informationTransmission of Electrical Energy
Transmission of Electrical Energy Electrical energy is carries by conductors such as overhead transmission lines and underground cables. The conductors are usually aluminum cable steel reinforced (ACSR),
More informationFERRORESONANCE SIMULATION STUDIES USING EMTP
FERRORESONANCE SIMULATION STUDIES USING EMTP Jaya Bharati, R. S. Gorayan Department of Electrical Engineering Institute of Technology, BHU Varanasi, India jbharatiele@gmail.com, rsgorayan.eee@itbhu.ac.in
More informationSolving Customer Power Quality Problems Due to Voltage Magnification
PE-384-PWRD-0-11-1997 Solving Customer Power Quality Problems Due to Voltage Magnification R. A. Adams, Senior Member S. W. Middlekauff, Member Duke Power Company Charlotte, NC 28201 USA E. H. Camm, Member
More informationSimulation Study on Transient Performance of Lightning Over-voltage of Transmission Lines
7th Asia-Pacific International Conference on Lightning, November 1-4, 2011, Chengdu, China Simulation Study on Transient Performance of Lightning Over-voltage of Transmission Lines Zihui Zhao, Dong Dang,
More informationResearch Article A Simplified High Frequency Model of Interleaved Transformer Winding
Research Journal of Applied Sciences, Engineering and Technology 10(10): 1102-1107, 2015 DOI: 10.19026/rjaset.10.1879 ISSN: 2040-7459; e-issn: 2040-7467 2015 Maxwell Scientific Publication Corp. Submitted:
More informationIntroduce system protection relays like underfrequency relays, rate of change of frequency relays, reverse - power flow
Module 1 : Fundamentals of Power System Protection Lecture 3 : Protection Paradigms - System Protection Objectives In this lecture we will: Overview dynamics in power systems. Introduce system protection
More informationLevel 6 Graduate Diploma in Engineering Electrical Energy Systems
9210-114 Level 6 Graduate Diploma in Engineering Electrical Energy Systems Sample Paper You should have the following for this examination one answer book non-programmable calculator pen, pencil, ruler,
More informationTransmission Line Transient Overvoltages (Travelling Waves on Power Systems)
Transmission Line Transient Overvoltages (Travelling Waves on Power Systems) The establishment of a potential difference between the conductors of an overhead transmission line is accompanied by the production
More informationTowards a transient earth fault clearing scheme for medium voltage networks
Towards a transient earth fault clearing scheme for medium voltage networks by Jan Scholtz, Eskom This paper describes the design principles and physical implementation of an improved transient earth fault
More informationElectric Stresses on Surge Arrester Insulation under Standard and
Chapter 5 Electric Stresses on Surge Arrester Insulation under Standard and Non-standard Impulse Voltages 5.1 Introduction Metal oxide surge arresters are used to protect medium and high voltage systems
More informationProblems connected with Commissioning of Power Transformers
Problems connected with Commissioning of Power Transformers ABSTRACT P Ramachandran ABB India Ltd, Vadodara, India While commissioning large Power Transformers, certain abnormal phenomena were noticed.
More informationUniversity of Zagreb Faculty of Electrical Engineering and Computing
Journal of Energy VOLUME 64 2015 journal homepage: http://journalofenergy.com/ Viktor Milardić viktor.milardic@fer.hr Ivica Pavić ivica.pavic@fer.hr University of Zagreb Faculty of Electrical Engineering
More informationB2-301 IMPROVING DOUBLE CIRCUIT TRANSMISSION LINE RELIABILITY THROUGH LIGHTNING DESIGN
21, rue d'artois, F-7008 Paris http://www.cigre.org B2-301 Session 200 CIGRÉ IMPROVING DOUBLE CIRCUIT TRANSMISSION LINE RELIABILITY THROUGH LIGHTNING DESIGN J. A. (TONY) GILLESPIE & GLENN STAPLETON Powerlink
More informationRAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements
RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements User s Guide General Most faults in power systems can be detected by applying
More information2 Grounding of power supply system neutral
2 Grounding of power supply system neutral 2.1 Introduction As we had seen in the previous chapter, grounding of supply system neutral fulfills two important functions. 1. It provides a reference for the
More informationTHE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE
THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE Z.Liu, B.T.Phung, T.R.Blackburn and R.E.James School of Electrical Engineering and Telecommuniications University of New South Wales
More informationDEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING YEAR / SEM : IV / VII UNIT I OVER VOLTAGES IN ELECTRICAL POWER SYSTEMS 1. What
More informationCoordination of surge arresters in DC 3 kv railway traction system field tests
Coordination of surge arresters in DC 3 kv railway traction system field tests Miroslaw Zielenkiewicz Tomasz Maksimowicz Center of Protection against Overvoltages and Electromagnetic Interferences RST
More informationTransformers connected via a cable Overvoltage protection
A P P L I C AT I O N N OT E 2. 1 Transformers connected via a cable Overvoltage protection The APPLICATION NOTES (AN) are intended to be used in conjunction with the APPLICATION GUIDELINES Overvoltage
More informationOVERVOLTAGE PROTECTION. Dimensioning, testing and application of metal oxide surge arresters in low-voltage power distribution systems
PPLICATION GUIDELINES OVERVOLTAGE PROTECTION Dimensioning, testing and application of metal oxide surge arresters in low-voltage power distribution systems Foreword Up until 1998 no international standards
More informationThe Effect of Lightning Parameters on Induced Voltages Caused by Nearby Lightning on Overhead Distribution Conducting Line.
The Effect of Lightning Parameters on Induced Voltages Caused by Nearby Lightning on Overhead Distribution Conducting Line. J.O. Adepitan, Ph.D. 1 and Prof. E.O. Oladiran 2 1 Department of Physics and
More informationInsulation Coordination Fundamentals Where Arrester and Insulator Characteristics Meet
ArresterWorks Insulation Coordination Fundamentals Where Arrester and Insulator Characteristics Meet 6/23/2012 Jonathan Woodworth Transient overvoltages are a fact of life on power systems. Arresters can
More informationPOWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009
POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 Nkosinathi Buthelezi Senior Consultant: Power Transformers and Reactors Presentation Content Standardization of Power
More informationProtection of MV Converters in the Grid: The Case of MV/LV Solid-State Transformers
2017 IEEE IEEE Journal of Emerging and Selected Topics in Power Electronics, Vol. 5, No. 1, pp. 393-408, March 2017 Protection of MV Converters in the Grid: The Case of MV/LV Solid-State Transformers T.
More informationDIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY
DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY Dr. Karthik Reddy VENNA Hong URBANEK Nils ANGER Siemens AG Germany Siemens AG Germany Siemens AG Germany karthikreddy.venna@siemens.com
More informationEnergy Division. Bowthorpe LV/MV Surge Arresters
Energy Division Bowthorpe LV/MV Surge Arresters Bowthorpe EMP LV/MV surge arresters OCP, Open Cage Polymeric series Bowthorpe pioneered the development of polymeric housed surge arresters in the early
More informationTECHNICAL REPORT. Insulation co-ordination
TECHNICAL REPORT IEC TR 60071-4 First edition 2004-06 Insulation co-ordination Part 4: Computational guide to insulation co-ordination and modelling of electrical networks IEC 2004 Copyright - all rights
More informationIndex. b back-flashover 245 biomass 207 breakers 74 buchholz protection 235 busbar sectionalizer 193 business enterprises 18
331 Index a activity plan 318 agricultural enterprise 21 annual increase factor 12 annuity factor 44, 156 annuity method 38 ANSI code numbers 237 arrester, protection level 245 assessment of losses 38
More informationMAJOR ADVANCES IN MV/LV SUBSTATIONS. Th.Grima et JF.Faltermeier. Groupe CAHORS, France SUMMARY
MJOR DVNCES IN MV/LV SUSTTIONS Th.Grima et JF.Faltermeier Groupe CHORS, France SUMMRY Improvements on the reliability of the components of the network, combined with a well-considered policy of cost reduction
More informationPower Quality Basics. Presented by. Scott Peele PE
Power Quality Basics Presented by Scott Peele PE PQ Basics Terms and Definitions Surge, Sag, Swell, Momentary, etc. Measurements Causes of Events Possible Mitigation PQ Tool Questions Power Quality Measurement
More informationSensitivity Analysis of Maximum Overvoltage on Cables with Considering Forward and Backward Waves
Sensitivity Analysis of Maximum Overvoltage on Cables with Considering Forward and Backward Waves Hamed Touhidi 1,Mehdi Shafiee 2, Behrooz Vahidi 3, Seyed Hossein Hosseinian 4 1 Islamic Azad University,
More informationDigital Fault Recorder Deployment at HVDC Converter Stations
Digital Fault Recorder Deployment at HVDC Converter Stations On line continuous monitoring at HVDC Converter Stations is an important asset in determining overall system performance and an essential diagnostic
More informationComputation of Lightning Impulse Backflashover Outages Rates on High Voltage Transmission Lines
www.ijape.org International Journal of Automation and Power Engineering (IJAPE) Volume Issue, January DOI:./ijape... omputation of Lightning Impulse Backflashover Outages Rates on High Voltage Transmission
More informationEducation & Training
Distribution System Operator Certificate This program provides you with a proficient working knowledge in modern electric power distribution systems. These four classes are designed to walk students through
More information