EXPERIMENTAL INVESTIGATION OF A TRANSIENT INDUCED VOLTAGE TO AN OVERHEAD CONTROL CABLE FROM A GROUNDING CIRCUIT

Size: px
Start display at page:

Download "EXPERIMENTAL INVESTIGATION OF A TRANSIENT INDUCED VOLTAGE TO AN OVERHEAD CONTROL CABLE FROM A GROUNDING CIRCUIT"

Transcription

1 EXPERIMENTAL INVESTIGATION OF A TRANSIENT INDUCED VOLTAGE TO AN OVERHEAD CONTROL CABLE FROM A GROUNDING CIRCUIT Akihiro AMETANI, Tomomi OKUMURA, Naoto NAGAOKA, Nobutaka, MORI Doshisha University - Japan aametani@mail.doshisha.ac.jp 1. Introduction and sheath voltages and currents are summarized in Table 1. Electromagnetic disturbance of low voltage control circuits in generator stations and substations and of consumer electronic/digital circuits are becoming a significant problem as a number of electronic/digital circuits composed of sensitive semiconductors have been adopted. In fact, a few disturbances have been experienced in Japan [1-3]. During last 10 years more than 300 disturbances in the control circuits in the power stations and substations are informed, and about 70% is estimated due to lightning. Among the 220 cases, 104 cases are of the voltage class 66-77kV, 45 cases/ kv, 14 cases above 154kV, and 57 cases the voltage class unknown. The incoming path of a lightning surge causing the disturbances has been investigated in the hydraulic generator stations and substations, and the result indicates two dominant paths : (1) via VTs and CTs, (2) via grounding systems due to arrester operation in a main circuit and etc. It is statistically found that more than 20% of the lightning surges are coming through the grounding systems, and another 20% through VTs and CTs. The present paper carries out an experimental investigation of a transient voltage and current of an overhead control cable induced from a single grounding conductor, i.e. a counterpoise, when a lightning current flows into the grounding conductor probably by an arrester operation. The transient voltages and currents on the cable core and sheath are measured under various termination of the cable. 500Ω PG 10m 4m 3D-2V 0.3m 1 node m 2m Fig. 1 Experimental setup 0.1m 1m 2. Experimental setup (a) Transient voltage Fig. 1 illustrates an experimental setup. A naked Cu conductor (counterpoise) with the radius of 1cm is buried underneath the earth surface at the depth of 30cm with the total length of 4m. A coaxial single core cable (3D2V) with the length of 2m is suspended above the earth surface at the height of 10cm. A pulse generator (PG) is connected to one end of the counterpoise through a resistance 500Ω via a lead wire of 10m. When measuring a sheath voltage, one terminal of an oscilloscope is connected to a voltage reference line with the length of 60m of which the other end is grounded independently from the counterpoise. Terminating conditions of the both ends of the overhead cable core and sheath are changed as summarized in Table 1. For examples, the sheath ends are either connected (ON) / disconnected (OFF) to the counterpoise or independently grounded (IG) from the counterpoise. The core ends are either open-circuited or connected through a matching resistance to the sheath. Measured results of core (b) Transient current Fig. 2 Measured results of transient voltage and current waveforms along a counterpoise DOS_Ametani_A1 Session 2 Paper No 4-1 -

2 case No. sheath to counterpoise core - to - sheath resistance[ Ω ] 3. Measured Results and Discussions 3.1 Voltage and Current along Counterpoise Fig. 2 shows measured results of transient voltages and currents along a counterpoise. Wave propagation characteristics along a counterpoise have been discussed in detail in reference [4]. 3.2 Sheath Ends Open-Circuited Fig.3 shows measured results of transient voltage and current waveforms on the cable core ( core to sheath ) and sheath ( to voltage reference wire ) in the case of the sheath both ends being open-circuited (OFF, OFF). (a) is the core to sheath voltage at the receiving end, (b) the sheath receiving-end voltage and (c) the sheath current in case11. It is clear in Fig. 3(a) that the core voltage is nearly the same as the sheath voltage at the receiving ends. The maximum difference is less than 2V as observed in Table 1 independently from the core termination. The phenomenon is readily explained by a traveling wave theory. Define the surge impedance matrices between nodes 0 to 1, 1 to 2 and 2 to right in Fig.1 as [Z 1 ] and [Z 2 ] respectively. Then, the refraction coefficients λ 1f from the left to the right at the node 1 is given in the following equation[5]. [λ 1f ] = 2 [Z 2 ] ( [Z 1 ] + [Z 2 ] ) -1 (1) Z g 0 0 where [Z 1 ] = 0 R1c 0, 0 0 R1s Zg [Z 2 ] = Zc Zm (2) Zm Zs Table 1 Experimental conditions and measured results max. core to sheath voltage [V] max. sheath voltage to reference wire [V] and Z g : self surge impedance of a counterpoise Z c : self surge impedance of a cable core Z s : self surge impedance of a cable sheath Z m : mutual impedance between a core and a sheath Z n : mutual impedance between a counterpoise and a cable R 1c, R 1s : terminating impedance of a core and a sheath at node 1 When the both ends of the cable core and sheath are open-circuited, the terminating impedances are difined by : R 1c = R 1s = infinite ( ) (3) Substituting the above condition into eq. (1), the following refraction coefficient matrix is obtained [5] [λ 1f ] = Z n / Z g 0 0 (4) Z n / Z g 0 0 The above equation indicates that the sending-end voltages on the core and the sheath are the same. When the core sending end is short-circuited to the sheath, the refraction coefficient matrix [λ 1s ] is defined in the following equation [6]. 1 [λ 1s ] = 2( Z T Z ) T 1 U + 1' 2 t (5) Z g 0 where [ Z 1 '] =, [T ] = : rotation matrix (6) and subscript t for a transposed matrix. Then, the refraction coefficient is given in the following 2 2 matrix. 1 0 [λ 1s ] = Z n / Z g 0 core Max. current [A] send receive R 1c R 2c send receive send receive send receive send receive 11 OFF OFF OFF OFF ON OFF ON OFF ON OFF ON OFF OFF ON OFF ON OFF ON OFF ON ON ON ON ON ON ON ON ON independent grounding sheath (7) DOS_Ametani_A1 Session 2 Paper No 4-2 -

3 (a) Core to sheath voltage at the receiving end Z 0 = at f = 10MHz (8) Thus, the transient induced voltage to the cable is estimated to be about 30% of the counterpoise voltage. The maximum counterpoise voltage being about 120V in Fig. 2, the cable voltage is evaluated roughly to be 30V which is smaller than the measured result in Fig. 3(b). The discrepancy is estimated due to a direct induction from the current lead wire. The sheath current in Fig. 3(c) is quite oscillatory, similarly to the core-to-sheath voltage in Fig. 3(a). The high frequency component is estimated due to multiple reflection of the coaxial and the earth-return modes of propagation (coaxial v 1 = 195m / µ s, earth 236 m / µ s ) at the cable ends. On the contrary, the sheath voltage shows a rather smooth waveshape, similarly to the counterpoise voltage. The propagation velocity on the counterpoise is measured to be about 100 m / µ s, which gives a dominant transient frequency = 1/ 4τ 6.3MHz, or one cycle T = 160ns. f g g 3.3 Sheath Sending-End Connected to Counterpoise (b) Sheath voltage at the receiving end (c) Sheath current in Case 11 Fig.3 Transient voltage waveform on a cable in Case 1i It is observed from eq. (4) and (7) that the core voltage is the same as the sheath voltage at the sending end independently from the open and the short circuit of the core and the sheath, and is given as ( Z n / Z g ) E0, where E 0 is a traveling-wave voltage incoming to node 1 along the counterpoise. The sending end voltage V g of the counterpoise is given by E 0 as in eq.(7), if no circuit is connected to the cable sending end. The characteristic impedances calculated by the Cable Parameters of the ATP-EMTP[7] are given in eq.(8) at 10MHz. Fig.4 shows transient sheath voltages when the sending end of the cable sheath is short-circuited to the counterpoise at the node 1 in Fig. 1, i.e. Case 2i in Table 1. The receiving end of the sheath is open-circuited. It is observed that the sheath voltage at the sending end is similar to that of the counterpoise voltage at the node 1 in Fig. 2(a). The receiving-end voltage is attenuated at the wavefront and the oscillatory waveform becomes distinct. The sheath current in Fig. 4(c) is less oscillatory than that in Case 11, Fig. 3(c) and the peak current at the sending end is nearly twice of Case 11. The node 1 voltage is analytically determined in the same manner as that in Sec.3.2. The sheath voltage is the same as the counterpoise voltage because those are short circuited. The voltage is roughly given by : g s ( Z Z ) V = V = E 2 V c (9) 0 2Z s / g + where E 0 : traveling-wave voltage incoming to node 1 along the counterpoise Applying the characteristic impedances in eq.(8), V g = V s V c ( 10 /11) E 0 With E0 50V at the node 1 in Fig. 2(a), the above equation gives the following result. V g = V s V c 45.5V The value agrees well with the measured results in Table 1. It should be noted that the sheath voltage in Case 2i is greater than that in Case 1i. s DOS_Ametani_A1 Session 2 Paper No 4-3 -

4 same, except the (a) Sending end (a) Sending end (b) Receiving end (b) Receiving end (c) Sheath current in Case 21 Fig.4 Transient sheath voltages in Case 2i 3.4 Sheath Receiving-End Connected to Counterpoise Fig.5 shows transient voltages in the case of the sheath receiving end being short-circuited to the counterpoise at node 2 (Case 3i). The maximum voltage is smaller in Case 3i than in Case 2i as observed in Table 1. Fig. 5(c) shows the voltage difference between the counterpoise and the sheath at the sending end. The counterpoise voltage is composed of Fig. 5(a) and (c), and becomes similar to that in Fig. 2(a). 3.5 Both Ends of Sheath Connected to Counterpoise Fig.6 shows transient voltages and current waveforms on the cable sheath in Case 4i. It is clear that the sending-end voltage waveform in Fig. 6(a) is nearly the (c) Voltage difference between the counterpoise and the sheath Fig.5 Transient sheath voltages in Case3i maximum value, as that in Fig. 4(a) in the case of the sheath sending end short-circuited to the counterpoise. The receiving-end voltage in Fig. 6(b) is similar to Fig. 5(b) except the initial part. As a result, the maximum sheath voltage is the smaller in Case 4i than that in Cases 2i and 3i as observed in Table 1, and this agrees with the conventional practice of the both ends of a cable sheath to be short-circuited to a counterpoise. Currents waveforms in Fig. 6(c) are quite different from those in Cases 1i to 3i which are highly oscillatory. The peak value of the current is far greater in Fig. 6(c). The reason is simply due a closed circuit composed of the sheath and the counterpoise. DOS_Ametani_A1 Session 2 Paper No 4-4 -

5 is (a) Sending end (a) Core-to-sheath voltage at the receiving end (b) Receiving end (b) Sheath voltage at the sending end (c) Current in Case 41 Fig.6 Transient sheath voltage and current waveforms in Case 4i (c) Sheath voltage at the receiving end 3.6 Sheath Grounded Independently from Counterpoise A transient voltage and current induced to a control cable from a counterpoise is desired as small as possible from the viewpoint of the insulation and the electromagnetic immunity of the control circuit in a power station and a substation. To achieve this, the paper investigates an independent grounding (Case 5i in Table 1) of the cable sheath from the counterpoise. The cable sheath is grounded at the both ends to a buried vertical rod apart by 2m from the counterpoise. Fig.7 shows measured results of transient voltage and current waveforms. (a) is the core-to-sheath voltage at the receiving end. A maximum voltage difference between the core and the sheath is observed to be less than 1.5V, which (d) Sheath current in Case 51 Fig.7 Transient voltage and current waveforms in Case 5i (independent grounding) DOS_Ametani_A1 Session 2 Paper No 4-5 -

6 similar to those in the Cases 1i to 4i in Table 1. Fig.7(b) and (c) are the sheath voltages at the sending and the receiving ends respectively. A comparison with the sheath voltage waveforms in Case 1i to 4i (Figs. 3 to 6) indicates that there is no fast rise of the voltage at the wavefront, and the maximum sheath voltage in Case 5i is less than 15.5V, while it reaches about 36V in Case 1i, 52.5V in Case 2i, 48V in Case 3i and 47V in Case 4i. Thus, it is clear that the maximum sheath voltage is reduced to 1/3 of that in the cases of the cable sheath being connected to the counterpoise. Fig. 7(d) shows the sheath current in Case 51. The sheath current is observed to be similar to that in Fig. 3(c), Case11 in the beginning, and to be far smaller than that in Fig. 6(c), Case 41. [4] A. Ametani, et.al. : Basic investigation of wave propagation characteristics on an underground naked conductor, Proceedings of ICEE 02, Jeju (Korea), pp , 2002 [5] A. Ametani : Distributed-Parameter Circuit Theory, Corona Pub.Co. (Tokyo), [6] N. Nagaoka and A. Ametani, Transient calculations on crossbonded cables, IEEE Trans., vol.pas-102, pp , 1983 [7] A. Ametani : Cable Parameters Rule Book, B.P.A Conclusions The paper has investigated experimentally transient voltages and currents on an overhead cable induced from a counterpoise, representing an induced voltage and current on a control cable in a power station and a substation. Based on the investigation, the following remarks have been obtained. (1) No significant voltage difference appears between the cable core and the sheath. (2) The sheath voltage is smaller in the case of the sheath being open-circuited, i.e. not connected to a counterpoise, than that in the case of the sheath connected to the counterpoise. (3) When a cable sheath is connected to a counterpoise, the sheath voltage becomes the smallest and the sheath current is the largest in the case of the both ends connected to the counterpoise. The sheath voltage is the largest in the case of the sending end connected to the counterpoise. (4) The sheath voltage is far smaller in the case of the sheath being grounded independently from the counterpoise than that in the case of the sheath connected to the counterpoise. Thus, the independent grounding of a control cable could be an effective means to reduce the transient overvoltage on a control cable in a power station and a substation, unless a voltage difference between the independent grounding and the counterpoise (or mesh) dose not cause a problem. References [1] T. Hasegawa, et.al., A fact-finding analysis of lightning disturbances and substations, IEE of Japan, Annual Meeting Records, Paper 1218, 1992 [2] Technologies of Countermeasures against Surges on Protection Relay and Control Systems, Report of Japanese ETRA, vol.57, No.3, Jan.2002 [3] T. Sonoda, et.al., An experimental study on surges induced from grounding grid to low-voltage control circuits, IEE of Japan, Research Meeting, Paper HV , 2001 DOS_Ametani_A1 Session 2 Paper No 4-6 -

Derivation of Theoretical Formulas of Sequence Currents on Underground Cable System

Derivation of Theoretical Formulas of Sequence Currents on Underground Cable System Derivation of Theoretical Formulas of Sequence Currents on Underground Cable System Teruo Ohno, Akihiro Ametani, Claus Leth Bak Abstract-- A reliable operation of a cable system necessitates an accurate

More information

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models International Journal of Electrical & Computer Sciences IJECS-IJENS Vol:15 No:03 39 Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models Shen-Wen Hsiao, Shen-Jen

More information

Experimental and Analytical Studies of Lightning Overvoltages in Wind Turbine Generation Systems

Experimental and Analytical Studies of Lightning Overvoltages in Wind Turbine Generation Systems Experimental and Analytical Studies of Lightning Overvoltages in Wind Turbine Generation Systems K. Yamamoto, T. Noda, S. Yokoyama, A. Ametani Abstract-- This paper presents the results of the experimental

More information

Simulation of Lightning Transients on 110 kv overhead-cable transmission line using ATP-EMTP

Simulation of Lightning Transients on 110 kv overhead-cable transmission line using ATP-EMTP Simulation of Lightning Transients on 110 kv overhead-cable transmission line using ATP-EMTP Kresimir Fekete 1, Srete Nikolovski 2, Goran Knezević 3, Marinko Stojkov 4, Zoran Kovač 5 # Power System Department,

More information

Lightning Overvoltages on Low Voltage Circuit Caused by Ground Potential Rise

Lightning Overvoltages on Low Voltage Circuit Caused by Ground Potential Rise Lightning Overvoltages on Low Voltage Circuit Caused by Ground Potential Rise S. Sekioka, K. Aiba, S. Okabe Abstract-- The lightning overvoltages incoming from an overhead line such as a power distribution

More information

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers Voltage (kv) Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers Li-Ming Zhou, Senior Member, IEEE and Steven Boggs, Fellow, IEEE Abstract: The high frequency attenuation

More information

Measurements for validation of high voltage underground cable modelling

Measurements for validation of high voltage underground cable modelling Measurements for validation of high voltage underground cable modelling Unnur Stella Gudmundsdottir, Claus Leth Bak, Wojciech T. Wiechowski, Kim Søgaard, Martin Randrup Knardrupgård Abstract-- This paper

More information

A Study on Lightning Overvoltage Characteristics of Grounding Systems in Underground Distribution Power Cables

A Study on Lightning Overvoltage Characteristics of Grounding Systems in Underground Distribution Power Cables J Electr Eng Technol Vol. 9, No. 2: 628-634, 2014 http://dx.doi.org/10.5370/jeet.2014.9.2.628 ISSN(Print) 1975-0102 ISSN(Online) 2093-7423 A Study on Lightning Overvoltage Characteristics of Grounding

More information

Accurate Modeling of Core-Type Distribution Transformers for Electromagnetic Transient Studies

Accurate Modeling of Core-Type Distribution Transformers for Electromagnetic Transient Studies IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 17, NO. 4, OCTOBER 2002 969 Accurate Modeling of Core-Type Distribution Transformers for Electromagnetic Transient Studies Taku Noda, Member, IEEE, Hiroshi Nakamoto,

More information

Lab 1: Pulse Propagation and Dispersion

Lab 1: Pulse Propagation and Dispersion ab 1: Pulse Propagation and Dispersion NAME NAME NAME Introduction: In this experiment you will observe reflection and transmission of incident pulses as they propagate down a coaxial transmission line

More information

Published in: Proceedings of the International Conference on Power Systems Transients (IPST 2009)

Published in: Proceedings of the International Conference on Power Systems Transients (IPST 2009) Aalborg Universitet Measurements for validation of high voltage underground cable modelling Bak, Claus Leth; Gudmundsdottir, Unnur Stella; Wiechowski, Wojciech Tomasz; Søgaard, Kim; Knardrupgård, Martin

More information

Modeling for the Calculation of Overvoltages Stressing the Electronic Equipment of High Voltage Substations due to Lightning

Modeling for the Calculation of Overvoltages Stressing the Electronic Equipment of High Voltage Substations due to Lightning Modeling for the Calculation of Overvoltages Stressing the Electronic Equipment of High Voltage Substations due to Lightning M. PSALIDAS, D. AGORIS, E. PYRGIOTI, C. KARAGIAΝNOPOULOS High Voltage Laboratory,

More information

Parameters Affecting the Back Flashover across the Overhead Transmission Line Insulator Caused by Lightning

Parameters Affecting the Back Flashover across the Overhead Transmission Line Insulator Caused by Lightning Proceedings of the 14 th International Middle East Power Systems Conference (MEPCON 10), Cairo University, Egypt, December 19-21, 2010, Paper ID 111. Parameters Affecting the Back Flashover across the

More information

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS TRANSFORMER IN GRID When surge arres t ers are installed close to a power transformer, they provide protection against lightning overvoltage ABSTRACT The aim of this research article is to determine the

More information

Cross-bonding cable and box model based on pulse reflection measurement

Cross-bonding cable and box model based on pulse reflection measurement Published in IET Science, Measurement and Technology Received on 20th December 2013 Revised on 4th June 2014 Accepted on 13th June 2014 ISSN 1751-8822 Cross-bonding cable and box model based on pulse reflection

More information

Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System

Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 17, NO. 2, APRIL 2002 569 Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System Li-Ming Zhou, Senior Member, IEEE,

More information

LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION

LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION Andreas SUMPER sumper@citcea.upc.es Antoni SUDRIÀ sudria@citcea.upc.es Samuel GALCERAN galceran@citcea.upc.es Joan RULL rull@citcea.upc.es

More information

Accuracy of Lightning Surge Analysis of Tower Surge Response

Accuracy of Lightning Surge Analysis of Tower Surge Response Accuracy of ightning Surge Analysis of Tower Surge esponse Naoki Itamoto, Hironao Kawamura, Kazuo Shinjo, Hideki Motoyama, Masaru Ishii Abstract--This paper presents a comparison between the measured and

More information

Proposal of double voltage transmission line pulse generator using four coaxial cables

Proposal of double voltage transmission line pulse generator using four coaxial cables Proposal of double voltage transmission line pulse generator using four coaxial cables Hitoshi Kijima, Koji Ochi Abstract In order to carry out the simulation of an electrical noise, a pulse generator

More information

Simplified Approach to Calculate the Back Flashover Voltage of Shielded H.V. Transmission Line Towers

Simplified Approach to Calculate the Back Flashover Voltage of Shielded H.V. Transmission Line Towers Proceedings of the 14 th International Middle East Power Systems Conference (MEPCON 1), Cairo University, Egypt, December 19-1, 1, Paper ID 1. Simplified Approach to Calculate the Back Flashover Voltage

More information

The Analysis Results of Lightning Overvoltages by EMTP for Lightning Protection Design of 500 kv Substation

The Analysis Results of Lightning Overvoltages by EMTP for Lightning Protection Design of 500 kv Substation The Analysis Results of Lightning Overvoltages by EMTP for Lightning Protection Design of 500 kv Substation J. W. Woo, J. S. Kwak, H. J. Ju, H. H. Lee, J. D. Moon Abstract--To meet increasing power demand,

More information

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 BONDING METHODS

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 BONDING METHODS 1.0 SCOPE 2.0 BONDING METHODS 2.1 Introduction 2.2 Design 2.3 Single-Point Bonding 2.4 Cross Bonding 2.5 Sheath Sectionalizing Joints 2.6 Sheath Standing Voltage 2.7 Sheath Voltage at Through Fault 2.8

More information

VFTO STUDIES DUO TO THE SWITCHING OPERATION IN GIS 132KV SUBSTATION AND EFFECTIVE FACTORS IN REDUCING THESE OVER VOLTAGES

VFTO STUDIES DUO TO THE SWITCHING OPERATION IN GIS 132KV SUBSTATION AND EFFECTIVE FACTORS IN REDUCING THESE OVER VOLTAGES VFTO STUDIES DUO TO THE SWITCHING OPERATION IN GIS 132KV SUBSTATION AND EFFECTIVE FACTORS IN REDUCING THESE OVER VOLTAGES Shohreh Monshizadeh Islamic Azad University South Tehran Branch (IAU), Tehran,

More information

Switching Restrikes in HVAC Cable Lines and Hybrid HVAC Cable/OHL Lines

Switching Restrikes in HVAC Cable Lines and Hybrid HVAC Cable/OHL Lines Switching Restrikes in HVAC Cable Lines and Hybrid HVAC Cable/OHL Lines F. Faria da Silva, Claus L. Bak, Per B. Holst Abstract--The disconnection of HV underground cables may, if unsuccessful, originate

More information

2000 Mathematics Subject Classification: 68Uxx/Subject Classification for Computer Science. 281, 242.2

2000 Mathematics Subject Classification: 68Uxx/Subject Classification for Computer Science. 281, 242.2 ACTA UNIVERSITATIS APULENSIS Special Issue SIMULATION OF LIGHTNING OVERVOLTAGES WITH ATP-EMTP AND PSCAD/EMTDC Violeta Chiş, Cristina Băla and Mihaela-Daciana Crăciun Abstract. Currently, several offline

More information

Transmission Line Transient Overvoltages (Travelling Waves on Power Systems)

Transmission Line Transient Overvoltages (Travelling Waves on Power Systems) Transmission Line Transient Overvoltages (Travelling Waves on Power Systems) The establishment of a potential difference between the conductors of an overhead transmission line is accompanied by the production

More information

GIS Disconnector Switching Operation VFTO Study

GIS Disconnector Switching Operation VFTO Study GIS Disconnector Switching Operation VFTO Study Mariusz Stosur, Marcin Szewczyk, Wojciech Piasecki, Marek Florkowski, Marek Fulczyk ABB Corporate Research Center in Krakow Starowislna 13A, 31-038 Krakow,

More information

Aalborg Universitet. Ground Loop Impedance of Long EHV Cable Lines Ohno, Teruo; Bak, Claus Leth; Sørensen, Thomas K.

Aalborg Universitet. Ground Loop Impedance of Long EHV Cable Lines Ohno, Teruo; Bak, Claus Leth; Sørensen, Thomas K. Aalborg Universitet Ground Loop Impedance of Long EHV Cable Lines Ohno, Teruo; Bak, Claus Leth; Sørensen, Thomas K. Published in: Proceedings of Western Protective Relay Conference Publication date: Document

More information

Measurement of Surge Propagation in Induction Machines

Measurement of Surge Propagation in Induction Machines Measurement of Surge Propagation in Induction Machines T. Humiston, Student Member, IEEE Department of Electrical and Computer Engineering Clarkson University Potsdam, NY 3699 P. Pillay, Senior Member,

More information

EMC Philosophy applied to Design the Grounding Systems for Gas Insulation Switchgear (GIS) Indoor Substation

EMC Philosophy applied to Design the Grounding Systems for Gas Insulation Switchgear (GIS) Indoor Substation EMC Philosophy applied to Design the Grounding Systems for Gas Insulation Switchgear (GIS) Indoor Substation Marcos Telló Department of Electrical Engineering Pontifical Catholic University of Rio Grande

More information

A Study of Lightning Surge on Underground Cables in a Cable Connection Station

A Study of Lightning Surge on Underground Cables in a Cable Connection Station Proceedings of the 6th WSEAS International Conference on Instrumentation, Measurement, Circuits & Systems, Hangzhou, China, April 1517, 2007 198 A Study of Lightning Surge on Under Cables in a Cable Connection

More information

Power Quality. Case Study. Conrad Bottu Laborelec January 2008

Power Quality. Case Study. Conrad Bottu Laborelec January 2008 Case Study Electromagnetic compatibility (EMC) study Breakdown of low voltage electronic equipment in a 25 kv substation Conrad Bottu Laborelec January 2008 Power Quality Power Quality 1 Introduction Description

More information

Experimental Study and Circuit Analysis Model of Lightning Isolation Transformer for Railway Signal System

Experimental Study and Circuit Analysis Model of Lightning Isolation Transformer for Railway Signal System 214 International Conference on Lightning Protection (ICLP), Shanghai, China Experimental Study and Circuit Analysis Model of Lightning Isolation Transformer for Railway Signal System Shunichi Yanagawa

More information

Maximum Lightning Overvoltage along a Cable due to Shielding Failure

Maximum Lightning Overvoltage along a Cable due to Shielding Failure Maximum Lightning Overvoltage along a Cable due to Shielding Failure Thor Henriksen Abstract--This paper analyzes the maximum lightning overvoltage due to shielding failure along a cable inserted in an

More information

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS M. Kondalu, Dr. P.S. Subramanyam Electrical & Electronics Engineering, JNT University. Hyderabad. Joginpally B.R. Engineering

More information

A Simple Simulation Model for Analyzing Very Fast Transient Overvoltage in Gas Insulated Switchgear

A Simple Simulation Model for Analyzing Very Fast Transient Overvoltage in Gas Insulated Switchgear A Simple Simulation Model for Analyzing Very Fast Transient Overvoltage in Gas Insulated Switchgear Nguyen Nhat Nam Abstract The paper presents an simple model based on ATP-EMTP software to analyze very

More information

ABSTRACT 1 INTRODUCTION

ABSTRACT 1 INTRODUCTION ELECTROMAGNETIC ANALYSIS OF WIND TURBINE GROUNDING SYSTEMS Maria Lorentzou*, Ian Cotton**, Nikos Hatziargyriou*, Nick Jenkins** * National Technical University of Athens, 42 Patission Street, 1682 Athens,

More information

ABSTRACTS of SESSION 6

ABSTRACTS of SESSION 6 ABSTRACTS of SESSION 6 Paper n 1 Lightning protection of overhead 35 kv lines by antenna-module long flashover arresters Abstract: A long-flashover arrester (LFA) of a new antenna-module type is suggested

More information

Simulation Study on Transient Performance of Lightning Over-voltage of Transmission Lines

Simulation Study on Transient Performance of Lightning Over-voltage of Transmission Lines 7th Asia-Pacific International Conference on Lightning, November 1-4, 2011, Chengdu, China Simulation Study on Transient Performance of Lightning Over-voltage of Transmission Lines Zihui Zhao, Dong Dang,

More information

GIS Instrument Transformers: EMC Conformity Tests for a Reliable Operation in an Upgraded Substation

GIS Instrument Transformers: EMC Conformity Tests for a Reliable Operation in an Upgraded Substation GIS Instrument Transformers: EMC Conformity Tests for a Reliable Operation in an Upgraded Substation W. Buesch 1) G. Palmieri M.Miesch J. Marmonier O. Chuniaud ALSTOM LTD 1) ALSTOM LTD High Voltage Equipment

More information

Influence Of Lightning Strike Location On The Induced Voltage On a Nearby Overhead Line

Influence Of Lightning Strike Location On The Induced Voltage On a Nearby Overhead Line NATIONAL POWER SYSTEMS CONFERENCE NPSC22 563 Influence Of Lightning Strike Location On The Induced Voltage On a Nearby Overhead Line P. Durai Kannu and M. Joy Thomas Abstract This paper analyses the voltages

More information

Lumped Network Model of a Resistive Type High T c fault current limiter for transient investigations

Lumped Network Model of a Resistive Type High T c fault current limiter for transient investigations Lumped Network Model of a Resistive Type High T c fault current limiter for transient investigations Ricard Petranovic and Amir M. Miri Universität Karlsruhe, Institut für Elektroenergiesysteme und Hochspannungstechnik,

More information

OVERVOLTAGE MEASUREMENTS RELATED TO LIGHTNING- DETECTION SYSTEMS IN NORWAY

OVERVOLTAGE MEASUREMENTS RELATED TO LIGHTNING- DETECTION SYSTEMS IN NORWAY 3p.3 OVERVOTAGE MEASUREMENTS REATED TO IGHTNING- DETECTION SYSTEMS IN NORWAY H. K. Høidalen F. Dahlslett hans.hoidalen@elkraft.ntnu.no Norwegian University of Science and Technology Norway frank.dahlslett@energy.sintef.no

More information

Frequency Domain Transient Analysis of Resonant Behavior for Different HV Overhead Line and Underground Cable Configurations

Frequency Domain Transient Analysis of Resonant Behavior for Different HV Overhead Line and Underground Cable Configurations Frequency Domain Transient nalysis of Resonant ehavior for Different HV Overhead Line and Underground able onfigurations L. Wu, P... F. Wouters, E. F. Steennis bstract Electrical resonant behavior in a

More information

Fast Front Transients in Transformer Connected to Gas Insulated Substations: (White+Black) Box Models and TDSF Monitoring

Fast Front Transients in Transformer Connected to Gas Insulated Substations: (White+Black) Box Models and TDSF Monitoring Fast Front Transients in Transformer Connected to Gas Insulated Substations: (White+Black) Box Models and TDSF Monitoring Luis ROUCO 1, Xose M. LÓPEZ-FERNÁNDEZ 2, 3, Casimiro ALVAREZ-MARIÑO 3 and Hugo

More information

SWITCHING OVERVOLTAGES IN A 400-KV CABLE SYSTEM

SWITCHING OVERVOLTAGES IN A 400-KV CABLE SYSTEM SWITCHING OVERVOLTAGES IN A 4-KV CABLE SYSTEM Mustafa Kizilcay University of Siegen Siegen, Germany kizilcay@uni-siegen.de Abstract This paper deals with the computation of switching overvoltages in a

More information

X International Symposium on Lightning Protection

X International Symposium on Lightning Protection X International Symposium on Lightning Protection 9 th -13 th November, 2009 Curitiba, Brazil LIGHTNING SURGES TRANSFERRED TO THE SECONDARY OF DISTRIBUTION TRANSFORMERS DUE TO DIRECT STRIKES ON MV LINES,

More information

Lightning performance of a HV/MV substation

Lightning performance of a HV/MV substation Lightning performance of a HV/MV substation MAHMUD TAINBA, LAMBOS EKONOMOU Department of Electrical and Electronic Engineering City University London Northampton Square, London EC1V HB United Kingdom emails:

More information

Understanding Design, Installation, and Testing Methods That Promote Substation IED Resiliency for High-Altitude Electromagnetic Pulse Events

Understanding Design, Installation, and Testing Methods That Promote Substation IED Resiliency for High-Altitude Electromagnetic Pulse Events Understanding Design, Installation, and Testing Methods That Promote Substation IED Resiliency for High-Altitude Electromagnetic Pulse Events Tim Minteer, Travis Mooney, Sharla Artz, and David E. Whitehead

More information

The relationship between operating maintenance and lightning overvoltage in distribution networks based on PSCAD/EMTDC

The relationship between operating maintenance and lightning overvoltage in distribution networks based on PSCAD/EMTDC The relationship between operating maintenance and lightning overvoltage in distribution networks based on PSCAD/EMTDC Xiaojun Chena *, Wenjie Zhengb, Shu Huangc, Hui Chend Electric Power Research Institute

More information

A Reflectometer for Cable Fault Location with Multiple Pulse Reflection Method

A Reflectometer for Cable Fault Location with Multiple Pulse Reflection Method 2014 by IFSA Publishing, S. L. http://www.sensorsportal.com A Reflectometer for Cable Fault Location with Multiple Pulse Reflection Method Zheng Gongming Electronics & Information School, Yangtze University,

More information

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages Session Four: ractical Insulation Co-ordination Session Four: ractical Insulation Co-ordination for Lightning Induced Overvoltages Jason Mayer Technical Director, Energy Services, Aurecon Introduction

More information

Exercises. 6 Exercises

Exercises. 6 Exercises 6 Exercises The following five computer exercises accompany the course. Alternative Transients Program (ATP-EMTP) will be used to compute electrical transients. First electrical network should be created

More information

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE Z.Liu, B.T.Phung, T.R.Blackburn and R.E.James School of Electrical Engineering and Telecommuniications University of New South Wales

More information

Propagation of Intersheath Modes on Underground Cables

Propagation of Intersheath Modes on Underground Cables Propagation of Intersheath Modes on Underground Cables I. Lafaia, Y. Yamamoto, A. Ametani, J. Mahseredjian, M.. Correia de Barros, I. Koçar, A. Naud Abstract his paper investigates wave propagation and

More information

SUPPRESSION METHODS FOR VERY FAST TRANSIENT OVER- VOLTAGES ON EQUIPMENT OF GIS

SUPPRESSION METHODS FOR VERY FAST TRANSIENT OVER- VOLTAGES ON EQUIPMENT OF GIS SUPPRESSION METHODS FOR VERY FAST TRANSIENT OVER- VOLTAGES ON EQUIPMENT OF GIS A.Raghu Ram 1, P.Swaraj 2 1,2 Associate Professor, PG Scholar, Department of Electrical and Electronics Engineering, JNTUH

More information

Prediction of Transient Transfer Functions at Cable-Transformer Interfaces

Prediction of Transient Transfer Functions at Cable-Transformer Interfaces 1 Prediction of Transient Transfer Functions at Cable-Transformer Interfaces Joe Y. Zhou, Member, IEEE and Steven A. Boggs, Fellow, IEEE Joe Zhou participated in this work while completing his Ph.D. at

More information

Analysis of Overvoltage and its Mitigation in Long Cable PWM Drives using Distributed-Parameter Representation

Analysis of Overvoltage and its Mitigation in Long Cable PWM Drives using Distributed-Parameter Representation Analysis of Overvoltage and its Mitigation in Long Cable PWM Drives using Distributed-Parameter Representation Thiago F. L. Milagres, Alessandro F. Moreira, Wallace C. Boaventura Departamento de Engenharia

More information

Power Quality and Reliablity Centre

Power Quality and Reliablity Centre Technical Note No. 8 April 2005 Power Quality and Reliablity Centre TRANSIENT OVERVOLTAGES ON THE ELECTRICITY SUPPLY NETWORK CLASSIFICATION, CAUSES AND PROPAGATION This Technical Note presents an overview

More information

Investigation on the Performance of Different Lightning Protection System Designs

Investigation on the Performance of Different Lightning Protection System Designs IX- Investigation on the Performance of Different Lightning Protection System Designs Nicholaos Kokkinos, ELEMKO SA, Ian Cotton, University of Manchester Abstract-- In this paper different lightning protection

More information

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017 Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017 NAME: LOCATION: 1. The primitive self-inductance per foot of length

More information

Modeling insulation in high-voltage substations

Modeling insulation in high-voltage substations 38 ABB REVIEW DESIGNED FOR SAFETY DESIGNED FOR SAFETY Modeling insulation in high-voltage substations The goal of insulation coordination is to determine the dielectric strength of transformers and other

More information

ATP SIMULATION OF FARADAY CAGE FOR THE ANALYSIS OF LIGHTNING SURGES

ATP SIMULATION OF FARADAY CAGE FOR THE ANALYSIS OF LIGHTNING SURGES ATP SIMULATION OF FARADAY CAGE FOR THE ANALYSIS OF LIGHTNING SURGES Mehmet Salih Mamis Cemal Keles 1 Muslum Arkan 1 Ramazan Kaya 2 Inonu University, Turkey 1 Inonu University, Engineering Faculty, Electrical

More information

Fatima Michael college of Engineering and Technology

Fatima Michael college of Engineering and Technology Fatima Michael college of Engineering and Technology DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE2303 TRANSMISSION AND DISTRIBUTION SEM: V Question bank UNIT I INTRODUCTION 1. What is the electric

More information

Analyzing and Modeling the Lightning Transient Effects of 400 KV Single Circuit Transmission Lines

Analyzing and Modeling the Lightning Transient Effects of 400 KV Single Circuit Transmission Lines International Journal of Science and Engineering Investigations vol. 2, issue 19, August 2013 ISSN: 2251-8843 Analyzing and Modeling the Lightning Transient Effects of 400 KV Single Circuit Transmission

More information

Lightning transient analysis in wind turbine blades

Lightning transient analysis in wind turbine blades Downloaded from orbit.dtu.dk on: Aug 15, 2018 Lightning transient analysis in wind turbine blades Candela Garolera, Anna; Holbøll, Joachim; Madsen, Søren Find Published in: Proceedings of International

More information

(i) Determine the admittance parameters of the network of Fig 1 (f) and draw its - equivalent circuit.

(i) Determine the admittance parameters of the network of Fig 1 (f) and draw its - equivalent circuit. I.E.S-(Conv.)-1995 ELECTRONICS AND TELECOMMUNICATION ENGINEERING PAPER - I Some useful data: Electron charge: 1.6 10 19 Coulomb Free space permeability: 4 10 7 H/m Free space permittivity: 8.85 pf/m Velocity

More information

EE 340 Transmission Lines. Spring 2012

EE 340 Transmission Lines. Spring 2012 EE 340 Transmission Lines Spring 2012 Physical Characteristics Overhead lines An overhead transmission line usually consists of three conductors or bundles of conductors containing the three phases of

More information

Conventional Paper-II-2011 Part-1A

Conventional Paper-II-2011 Part-1A Conventional Paper-II-2011 Part-1A 1(a) (b) (c) (d) (e) (f) (g) (h) The purpose of providing dummy coils in the armature of a DC machine is to: (A) Increase voltage induced (B) Decrease the armature resistance

More information

Lightning overvoltage and protection of power substations

Lightning overvoltage and protection of power substations Lightning overvoltage and protection of power substations Mahmud Trainba 1, Christos A. Christodoulou 2, Vasiliki Vita 1,2, Lambros Ekonomou 1,2 1 Department of Electrical and Electronic Engineering, City,

More information

PRELIMINARIES. Generators and loads are connected together through transmission lines transporting electric power from one place to another.

PRELIMINARIES. Generators and loads are connected together through transmission lines transporting electric power from one place to another. TRANSMISSION LINES PRELIMINARIES Generators and loads are connected together through transmission lines transporting electric power from one place to another. Transmission line must, therefore, take power

More information

IEEE Power Engineering Society 2001 Winter Meeting Columbus, OH. Panel Session. Data for Modeling System Transients

IEEE Power Engineering Society 2001 Winter Meeting Columbus, OH. Panel Session. Data for Modeling System Transients IEEE Power Engineering Society 2001 Winter Meeting Columbus, OH Panel Session Data for Modeling System Transients Parameters for Modeling Transmission Lines and Transformers in Transient Studies Bruce

More information

Experimental Study on Lightning Surge Response of 500kV Transmission Tower with Overhead Lines

Experimental Study on Lightning Surge Response of 500kV Transmission Tower with Overhead Lines Experimental Study on Lightning Surge Response of 500kV Transmission Tower with Overhead Lines H. Motoyama, CRIEPI, Japan motoyama@criepi.denken.or.jp Y. Kinoshita, Chube Electric Power Co., Inc., Japan

More information

Back-flashover Investigation of HV Transmission Lines Using Transient Modeling of the Grounding Systems

Back-flashover Investigation of HV Transmission Lines Using Transient Modeling of the Grounding Systems Back-flashover Investigation of HV Transmission Lines Using Transient Modeling of the Grounding Systems F. Amanifard* and N. Ramezani** Abstract: The article presents the transients analysis of the substation

More information

Analysis of lightning performance of 132KV transmission line by application of surge arresters

Analysis of lightning performance of 132KV transmission line by application of surge arresters Analysis of lightning performance of 132KV transmission line by application of surge arresters S. Mohajer yami *, A. Shayegani akmal, A.Mohseni, A.Majzoobi High Voltage Institute,Tehran University,Iran

More information

Modeling of long High Voltage AC Underground Cables

Modeling of long High Voltage AC Underground Cables Modeling of long High Voltage AC Underground Cables U. S. Gudmundsdottir, C. L. Bak and W. T. Wiechowski ABSTRACT HIS paper presents the work and findings of a PhD T project focused on accurate high frequency

More information

MODELLING OF BROADBAND POWERLINE COMMUNICATION CHANNELS

MODELLING OF BROADBAND POWERLINE COMMUNICATION CHANNELS Vol.2(4) December 2 SOUTH AFRICAN INSTITUTE OF ELECTRICAL ENGINEERS 7 MODELLING OF BROADBAND POWERLINE COMMUNICATION CHANNELS C.T. Mulangu, T.J. Afullo and N.M. Ijumba School of Electrical, Electronic

More information

A Special Ferro-resonance Phenomena on 3-phase 66kV VT-generation of 20Hz zero sequence continuous voltage

A Special Ferro-resonance Phenomena on 3-phase 66kV VT-generation of 20Hz zero sequence continuous voltage A Special Ferro-resonance Phenomena on 3-phase 66kV VT-generation of Hz zero sequence continuous voltage S. Nishiwaki, T. Nakamura, Y.Miyazaki Abstract When an one line grounding fault in a transmission

More information

Chapter 1. Overvoltage Surges and their Effects

Chapter 1. Overvoltage Surges and their Effects Chapter 1 Overvoltage Surges and their Effects 1.1 Introduction Power equipment are often exposed to short duration impulse voltages of high amplitude produced by lightning or switching transients. These

More information

Electric Stresses on Surge Arrester Insulation under Standard and

Electric Stresses on Surge Arrester Insulation under Standard and Chapter 5 Electric Stresses on Surge Arrester Insulation under Standard and Non-standard Impulse Voltages 5.1 Introduction Metal oxide surge arresters are used to protect medium and high voltage systems

More information

Distance Protection of Cross-Bonded Transmission Cable-Systems

Distance Protection of Cross-Bonded Transmission Cable-Systems Downloaded from vbn.aau.dk on: April 19, 2019 Aalborg Universitet Distance Protection of Cross-Bonded Transmission Cable-Systems Bak, Claus Leth; F. Jensen, Christian Published in: Proceedings of the 12th

More information

SURGE PROPAGATION AND PROTECTION OF UNDERGROUND DISTRIBUTION CABLES

SURGE PROPAGATION AND PROTECTION OF UNDERGROUND DISTRIBUTION CABLES SURGE PROPAGATION AND PROTECTION OF UNDERGROUND DISTRIBUTION CABLES Jae-bong LEE, Korea Electric Power Research Institute(KEPRI), (Korea), jbonglee@kepco.co.kr Ju-yong KIM, Korea Electric Power Research

More information

Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment

Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment Christian Suttner*, Stefan Tenbohlen Institute of Power Transmission and High Voltage Technology (IEH), University of

More information

Analysis of Electromagnetic Transients in Secondary Circuits due to Disconnector Switching in 400 kv Air-Insulated Substation

Analysis of Electromagnetic Transients in Secondary Circuits due to Disconnector Switching in 400 kv Air-Insulated Substation Analysis of Electromagnetic Transients in Secondary Circuits due to Switching in 400 k Air-Insulated Substation I. Uglešić, B. Filipović-Grčić,. Milardić, D. Filipović-Grčić Abstract-- The paper describes

More information

Calculation of Transients at Different Distances in a Single Phase 220KV Gas insulated Substation

Calculation of Transients at Different Distances in a Single Phase 220KV Gas insulated Substation Calculation of Transients at Different Distances in a Single Phase 220KV Gas insulated Substation M. Kondalu1, Dr. P.S. Subramanyam2 Electrical & Electronics Engineering, JNT University. Hyderabad. 1 Kondalu_m@yahoo.com

More information

The Potential Gradient of Ground Surface according to Shapes of Mesh Grid Grounding Electrode using Reduced Scale Model

The Potential Gradient of Ground Surface according to Shapes of Mesh Grid Grounding Electrode using Reduced Scale Model Paper The Potential Gradient of Ground Surface according to Shapes of Mesh Grid Grounding Electrode using Reduced Scale Model Chung-Seog Choi Hyang-Kon Kim Hyoung-Jun Gil Woon-Ki Han Ki-Yeon Lee Member

More information

Pre location: Impulse-Current-Method (ICE)

Pre location: Impulse-Current-Method (ICE) 1 ICE (Impulse current method three phased 2 1.1 Ionisation delay time 2 1.2 DIRECT MODE 2 1.3 Output impedance of the generator 2 Surge generator as impulse source 3 High voltage test set as impulse source

More information

3.003 Lab 3 Part A. Measurement of Speed of Light

3.003 Lab 3 Part A. Measurement of Speed of Light 3.003 Lab 3 Part A. Measurement of Speed of Light Objective: To measure the speed of light in free space Experimental Apparatus: Feb. 18, 2010 Due Mar. 2, 2010 Components: 1 Laser, 4 mirrors, 1 beam splitter

More information

A MODEL TO SIMULATE EM SWITCHING TRANSIENTS IN ELECTRIC POWER DISTRIBUTION SUBSTATIONS

A MODEL TO SIMULATE EM SWITCHING TRANSIENTS IN ELECTRIC POWER DISTRIBUTION SUBSTATIONS A MODEL TO SIMULATE EM SWITCHING TRANSIENTS IN ELECTRIC POWER DISTRIBUTION SUBSTATIONS G. Ala, P. Buccheri, M. Inzerillo Dipartimento di Ingegneria Elettrica - Universitˆ di Palermo Viale delle Scienze,

More information

UNTIL now, little research has been published on field

UNTIL now, little research has been published on field Online Fault Location on AC Cables in Underground Transmission Systems using Sheath Currents C.F. Jensen, O.M.K.K. Nanayakkara, A. D. Rajapakse, U.S. Gudmundsdottir, and C.L. Bak Abstract This paper studies

More information

WAVELET TRANSFORM ANALYSIS OF PARTIAL DISCHARGE SIGNALS. B.T. Phung, Z. Liu, T.R. Blackburn and R.E. James

WAVELET TRANSFORM ANALYSIS OF PARTIAL DISCHARGE SIGNALS. B.T. Phung, Z. Liu, T.R. Blackburn and R.E. James WAVELET TRANSFORM ANALYSIS OF PARTIAL DISCHARGE SIGNALS B.T. Phung, Z. Liu, T.R. Blackburn and R.E. James School of Electrical Engineering and Telecommunications University of New South Wales, Australia

More information

Modelling electromagnetic field coupling from an ESD gun to an IC

Modelling electromagnetic field coupling from an ESD gun to an IC Modelling electromagnetic field coupling from an ESD gun to an IC Ji Zhang #1, Daryl G Beetner #2, Richard Moseley *3, Scott Herrin *4 and David Pommerenke #5 # EMC Laboratory, Missouri University of Science

More information

Coupling modes. Véronique Beauvois, Ir Copyright 2015 Véronique Beauvois, ULg

Coupling modes. Véronique Beauvois, Ir Copyright 2015 Véronique Beauvois, ULg Coupling modes Véronique Beauvois, Ir. 2015-2016 General problem in EMC = a trilogy Parameters Amplitude Spectrum Source (disturbing) propagation Coupling modes Victim (disturbed) lightning electrostatic

More information

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY 9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor

More information

Modeling Ferroresonance Phenomena on Voltage Transformer (VT)

Modeling Ferroresonance Phenomena on Voltage Transformer (VT) Modeling Ferroresonance Phenomena on Voltage Transformer (VT) Mohammad Tolou Askari Department of Electrical Faculty of Engineering Universiti Putra Malaysia 43400 UPM Serdang, Selangor, Malaysia Abstract

More information

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES 23 CHAPTER 2 v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES 2.1 INTRODUCTION For reliable design of power system, proper insulation coordination among the power system equipment is necessary. Insulation

More information

Sources of transient electromagnetic disturbance in medium voltage switchgear

Sources of transient electromagnetic disturbance in medium voltage switchgear Sources of transient electromagnetic disturbance in medium voltage switchgear Dennis Burger, Stefan Tenbohlen, Wolfgang Köhler University of Stuttgart Stuttgart, Germany dennis.burger@ieh.uni-stuttgart.de

More information

Analysis of Collided Signal Waveform on the Long Transmission Line of UART-CSMA/CD Control Network

Analysis of Collided Signal Waveform on the Long Transmission Line of UART-CSMA/CD Control Network PIERS ONLINE, VOL. 5, NO. 2, 2009 171 Analysis of Collided Signal Waveform on the Long Transmission Line of UART-CSMA/CD Control Network Chuzo Ninagawa 1 and Yasumitsu Miyazaki 2 1 Mitsubishi Heavy Industries,

More information

Experiment No. 6 Pre-Lab Transmission Lines and Time Domain Reflectometry

Experiment No. 6 Pre-Lab Transmission Lines and Time Domain Reflectometry Experiment No. 6 Pre-Lab Transmission Lines and Time Domain Reflectometry The Pre-Labs are informational and although they follow the procedures in the experiment, they are to be completed outside of the

More information

Pulse Transmission and Cable Properties ================================

Pulse Transmission and Cable Properties ================================ PHYS 4211 Fall 2005 Last edit: October 2, 2006 T.E. Coan Pulse Transmission and Cable Properties ================================ GOAL To understand how voltage and current pulses are transmitted along

More information