1 Earthing of Electrical Devices and Safety JOŽE PIHLER Faculty of Electrical Engineering and Computer Sciences University of Maribor Smetanova 17, 2000 Maribor SLOVENIA Abstract: - This paper presents the importance of electrical devices earthing for safety of qualified personnel responsible for operation and maintenance of electrical devices; humans and animals which incidentally approach electrical devices or individual parts of electrical installations. For designers and users it is important that they are acquainted with theoretical backgrounds and voltages that may appear on earthed structures, possible consequences of these voltages and measures for prevention of dangerous impacts on living creatures. The results of laboratory tests are shown some examples if these measures are not taken into account. Key-Words: - Electrical devices, earthing, touch voltage, step voltage, safety. 1 Introduction Electric power system is one of the most complex systems in the nature. This system has to operate all the time reliably and without interruptions. In addition to this it has to be safe for people responsible for operation and maintenance of electrical devices. Earthing systems play an important role both in operational security and in providing safety to people and other living creatures that incidentally approach power system devices. The earth electrode as the most important part of the earthing system plays an important role in power system design. Earthing can have a significant impact on overvoltages and insulation stress in electrical devices. It also directly determines the magnitudes of short-circuit currents. Overvoltages and potential rise on the earth electrode can also appear due to lightning strike to the overhead earth wire of a power line. A certain share of current flows through the line tower to the earth electrode. A reflective voltage surge or damage can occur on the insulator chain. Between the affected phase and the metal cross arm of the line tower earth fault occurs. The fault current depends on the network capacity. A damage of insulator chain units or a sparkover on their surface is also a possible cause of puncture of the insulator chain. In this case the short circuit current also flows through the line tower and the earth electrode to the ground. The established current field causes potential rise inside the potential funnel due to resistance of the earth electrode. A potential rise can also occur on the transmission tower structure due to increased resistance between the elements of the line tower truss. This resistance can increase due to the poor quality execution of corrosion protection of steel structure (hot-dip galvanisation) or due to the colour application to the joints between the elements of the line tower truss. Each occurrence of overvoltage or potential rise causes increased touch and step voltage. If their values exceed the maximum permitted values, they pose a direct threat to humans and animals. Therefore it is of utmost importance that power system designers are aware of the conditions that may appear in order to prepare adequate measures for mitigation of impacts of potential rise on the earthing systems. The primary purpose of this paper is to present some examples of laboratory tests if these measures are not taken into account. The second section of the paper gives an overview of voltages that can appear on earthing systems. The third section presents the basics of earth electrodes design. The fourth section brings an estimation of possible voltage drops and consequently potential rise on earthed structures of electrical devices. Given are results of measurements of ohmic resistance on steel structures of line towers, as well as some results of practical tests with short circuit currents. 2 Voltage that may appear on earthing systems A deviation of voltage conditions in the network from the designed values can occur due to several different reasons. In most cases short- or long-term ISBN:

2 overvoltages occur due to switching manipulations or due to atmospheric discharges. Another source of overvoltages or voltage deviations from the designed values can be faults in the network. In case of a fault in the network potentials and voltages that are significantly higher than the designed values can occur in various parts of the network. Overvoltage is defined as a voltage between different parts of the network or between individual parts of the network and the ground, which is higher than the nominal voltage prescribed by the standard IEC [1], taking into consideration ±10 % tolerance band. Overvoltages that occur in the network have internal (operational) or external (atmospheric) source. Overvoltages can be different; therefore they are described with certain characteristics: amplitude, waveform or front time, duration, probability of occurrence, etc. According to the IEC [2] standard overvoltages are with regard to the cause of occurrence and overvoltage waveform classified in the following main groups: Low frequency continuous and temporary overvoltages. These are power system frequency overvoltages. Sources of them are earth faults, outages of large consumer units, ferroresonance or any combination of them. Slow-front transient overvoltages. These are overvoltages that appear during switching manipulations of power system elements (e.g. switching on or off of power lines) or in case of interrupting earth fault or short circuit currents. Fast-front and very-fast-front transient overvoltages. These are overvoltages that appear in case of lightning strike to an overhead line. Lightning strike can occur as a direct strike to the overhead earth wire, direct strike to the phase conductor or a strike in the vicinity of the line. The selection and design of the earthing system have an important impact on the overvoltage magnitude and duration. The earthing system has an impact on overvoltage magnitude, operational characteristics of the network, safety of users and operators of power devices, as well as of animals that can be found in the immediate vicinity of any electric power system facilities. The design of earthing systems is an extremely important part of power system design, since it has a significant impact on transient overvoltages, insulation stress and safety. It also directly determines the order of magnitude of fault currents. With regard to the method of earthing we distinguish networks with insulated neutral point, networks with resonant earthing, indirectly earthed networks and effectively earthed networks. In addition to the above stated it is of extreme importance to earth metal structures of individual power system elements, such as line towers, to ensure adequate level of safety. An overvoltage can cause local rise of earth potential, which is the voltage between the earthing system and the remote reference earth. The earthing system is a locally limited system of electrically connected earth electrodes or earthing conductors and equipotential bonding conductors or in the same way operating metal parts, such as line tower legs, metal reinforcements in concrete, metal cable coatings, etc. The reference earth (remote earth) is that part of the earth that is outside the area of influence of the earthing system or the earth electrode, where there is no significant perceivable potential difference due to currents in the earth between any two points. Potential rise of the earthing system can also occur due to the current caused by a lightning strike. Potential rise of the earthing system and of the nearby earth above permitted values can cause injury or death of living creatures, either by direct contacts or indirectly. Important criteria that define hazard of potential rise are touch and step voltage. Touch voltage: A part of earth potential rise that is transferred through the human body between hand and foot (it is supposed that the horizontal difference from the exposed part of the device amounts to 1 m). Step voltage: A part of the earth potential rise that can be bridged by a 1 m long step, which means that current flows through the human body from one foot to another [3]. 3 Designing of earth electrodes Earth electrodes are the most important elements of earthing systems of electric power networks and devices. They represent an extremely important part of operation and protection system against hazardous voltages and currents for people and animals. They need to be designed in such a way that in case of an earth fault the potential of the earth electrode does not rise to the magnitude that would cause excessive touch and step voltage on the earth surface. The level of the voltage rise depends on the earth electrode resistance. This can be to the maximum possible extent reduced by the adequate allocation of earth electrodes. This is therefore the primary protection measure against excessive touch and step voltages. This measure is successfully implemented in earthing of substations where the adequate allocation of earth electrode enables ISBN:

3 management of electrical potential on the earth surface. To a certain extent this can also be implemented in earthing systems of a line tower, although this is not a sufficient condition for protection against excessive touch and step voltages. resistance is immediately next to the rod. The graph of surface potential distribution (in the actual 3D space this is a potential funnel) is given in Fig Soil resistivity The designing of earth electrodes is closely connected to the soil resistivity. Soil resistivity varies with regard to the soil composition in the case of the same humidity. Varying the soil humidity additionally changes the earth resistivity. Earth electrodes that are laid in the foundations of buildings have a good conductance with regard to the surrounding earth, since their resistance is practically independent of the soil humidity, which may be drastically reduced during dry periods. Characteristic properties of soil can significantly change up to the depth of 3 m, while in deeper layers the conditions are much more stable. Soil resistivity also changes during the year. 3.2 Earth electrodes Earth electrode is a conductor or a group of conductors that are in the immediate contact with the earth and ensure electrical connection with it. Very important is voltage drop between the earth electrode and the remote reference point in the earth potential of the earth electrode. A distance of 200 m is usually enough for setting the remote reference point. The current density near the earth electrode is high, but since the cross section of the earth increases rapidly with the distance, the current density at the distance of 200 m practically equals to zero. To facilitate the observation of developments let s assume that the earth resistance is much higher than the resistance of the metal rod and that the current density is constant. The picture is more transparent taking into assumption homogenous soil and constant earth resistivity in horizontal and vertical direction. In practical applications we use various types of earth electrodes: horizontal strip earth electrode vertical rod earth electrode, foundation earth electrode, circular plate type and other earth electrodes. When the current flows through a metal rod to the earth, the current flow lines distribute radially the available cross section increases. The highest Fig. 1. Potential distribution and potential funnel of a circular plate type electrode. It is important to achieve such a potential distribution that touch and step voltages never exceed values that are dangerous for human beings. 3.3 Dimensioning of earthing systems with regard to human safety The standard [3] defines requirements for design, installation and testing of earthing systems with the purpose to ensure their operation in all conditions and limit the values of touch and step voltages at an acceptable level. An earthing system should fulfil the following five requirements: a) ensure mechanical strength and corrosion resistance, b) withstand thermal load with the maximum computed fault currents, c) prevent damage of property and equipment, d) ensure safety of people from voltages occurring on the earthing system in the case of an earth fault, e) ensure adequate degree of reliability of overhead lines. The decisive parameters for designing an earthing system are: magnitude of fault current, duration of fault current, soil properties. People are threatened by the electric current passing through the human body. The publication IEC [4] gives instructions about the effects of current passing through the human body, depending on current magnitude and duration of current passing through the body. In practice it is easier to present this dependence with maximum permitted values of touch voltage. Maximum permitted touch ISBN:

4 voltage (potential difference) is the value that can be applied along the body between hand and foot that, depending on duration, does not cause permanent consequences for the human being. Each earth fault needs to be interrupted either automatically or manually. Therefore the duration of occurrence of touch voltages is not infinite. If the earthing system is fully compliant with the requirements regarding the touch voltage, it can be assumed that there will be no dangerous step voltages [3]. (joint b). These two joints were tested in the laboratory with the 16 current lasting for 1 s. The time diagrams of current and voltage drops are shown in Fig Assessment of possible voltage drop on earthed structures of electrical devices Earthing systems comprise, in addition to the so far discussed earth electrodes and soil resistivity, the actual earth resistance, composed of earthing conductor resistance, earth electrode resistance, contact resistance between the electrode and the surrounding soil and soil resistivity. Earthing conductor resistance is the resistance of connecting cable, overhead conductor or a part of the line tower structure. All these elements represent a conductor through which the fault current or lightning surge current will flow through the earth electrode to earth. Fig. 2. Consequences of current test 16, 1 s. 4.1 Occurrence of induced voltages and voltage drops due to poorly designed or executed earthing Lightning strikes or earth faults can cause large currents in the line tower truss. The current will in both cases cause: magnetic field that will in closed loops cause induced voltages; and voltage drop due to resistance on the joints in the line tower truss. The induced voltage and voltage drop can be higher than the maximum permitted values and may cause injuries to human beings and animals. 4.2 Current load of line tower joints The effect of poor contact on the connecting conductor to the earth electrode was analysed by setting the actual joining elements of the line tower as shown in Fig. 2. We put together two joints, where the first was composed of unpainted and painted element (joint a) with the tightening torque of 130 Nm. The second joint was composed of two painted elements, screwed with the same tightening torque of 130 Nm Fig. 3. Time diagrams of current and voltage drops on the joints. During the tests the screws melted (Fig. 2) and an electric arc appeared [5]. Sparkling metal parts flew several metres away. The joint was completely destroyed and lost all required mechanical properties. Voltage drop on the joints exceeded 100 V. The main reason for this was too large contact resistance of the joint. 4.3 Computation of equalisation currents through the earth wire or earthed phase conductors and estimation of voltage drop on poorly joined parts of the structure The occurrence of equalisation currents in the earth wire or in the earthed phase conductors can be ISBN:

5 caused by: a) short circuit on another circuit of the line that is in operation; or b) atmospheric discharges Short circuit Let s assume a double-circuit overhead line with one circuit being switched off and earthed due to maintenance and another being in operation and energized. In the case of a short circuit fault in the operating circuit we assume that the values of equalisation current will not exceed the values of short circuit currents on the line during operation. The values of these currents through the earthing system can only be lower due to the presence of contact resistances on the connection points. The current magnitude also significantly depends on the method of insulation of the network neutral point. The computed potential difference on the line tower amounts to: ΔU = I st R st = Ω = 4,6 kv, (1) where I st is the maximum short circuit current that can flow to earth and R st is the resistance of metal parts of the line tower, if they are painted. This voltage drop that could appear in the line tower is deadly for people and animals Atmospheric discharges Atmospheric discharges causes surge currents of 8/20 µs waveform that can reach amplitudes in the range from 2 to 270, which is up to now the highest recorded value. The average value of 25 is usually used in practice. Table 1 from the IEC standard [6] gives the frequency of lightning currents through a line tower of the overhead line equipped with an earth wire. The table confirms the values that actually occur in practice. If 20 is assumed as an average value of current flowing through the line tower, as given in Table 1, 80 % of all lightning strikes are encompassed. Table 1. Frequency of current magnitudes through a line tower of the overhead line equipped with an earth wire. Current I st through the tower up to Cumulative frequency of all lightning strikes % 90 % 95 % 98 % 99 % observations are needed to determine the actual distribution of lightning currents in an overhead line route. The equation (1) is used to calculate the potential difference on the line tower for 20 current: ΔU = I st R st = Ω = 5,8 kv. The calculation results shows that the potential rise is high above the permitted values. 5 Conclusion The purpose of the paper was to warn the designers of electric power systems against overvoltages that may appear on earthing systems of the electrical devices. By means of measurements the values of resistance between individual elements of steel structure of line tower was established. On the basis of the predicted possible values of short circuit currents the potential rise was calculated. It was much higher than the permitted values of touch voltage. The test performed with the short circuit current through the steel structure with a high contact resistance lead to damaging and destruction of the structure. References: [1] IEC standard voltages, IEC 60038, 2009/06. [2] Insulation co-ordination - Part 1: Definitions, principles and rules, IEC , [3] Overhead electrical lines exceeding AC 45 kv Part 1: General requirements Common specifications, EN , [4] Effect of current passing through human body Part I: General aspects, IEC TS , [5] Test report of ICEM-TC Laboratory, 12-Mlab- 162, Maribor [6] Overhead electrical lines exceeding AC 45 kv- Part 3-21: National Normative, Aspects (NNA) for Slovenia (based on S IST EN :2002), SIST EN , The values in Table 1 are used in absence of actual distribution of frequencies of lightning currents, obtained by modern systems for their localisation. Several years of ISBN:

Industrial and Commercial Power Systems Topic 7 EARTHING

Industrial and Commercial Power Systems Topic 7 EARTHING The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 7 EARTHING 1 INTRODUCTION Advantages of earthing (grounding): Limitation

More information

7P Series - Surge Protection Device (SPD) Features 7P P P

7P Series - Surge Protection Device (SPD) Features 7P P P Features 7P.09.1.255.0100 7P.01.8.260.1025 7P.02.8.260.1025 SPD Type 1+2 Surge arrester range - single phase system / three phase system Surge arresters suitable in low-voltage applications in order to

More information

AC Voltage- Pipeline Safety and Corrosion MEA 2015

AC Voltage- Pipeline Safety and Corrosion MEA 2015 AC Voltage- Pipeline Safety and Corrosion MEA 2015 WHAT ARE THE CONCERNS ASSOCIATED WITH AC VOLTAGES ON PIPELINES? AC concerns Induced AC Faults Lightning Capacitive coupling Safety Code Induced AC Corrosion

More information

Safety earthing. Sector Energy PTI NC. Copyright Siemens AG All rights reserved. Theodor Connor

Safety earthing. Sector Energy PTI NC. Copyright Siemens AG All rights reserved. Theodor Connor Safety earthing Sector Energy PTI NC Theodor Connor Copyright Siemens AG 2008. All rights reserved. Content Introduction Theoretical background Soil Analysis Design of earthing system Measurements on earthing

More information

ABSTRACT 1 INTRODUCTION

ABSTRACT 1 INTRODUCTION ELECTROMAGNETIC ANALYSIS OF WIND TURBINE GROUNDING SYSTEMS Maria Lorentzou*, Ian Cotton**, Nikos Hatziargyriou*, Nick Jenkins** * National Technical University of Athens, 42 Patission Street, 1682 Athens,

More information

Prepared by Mick Maytum

Prepared by Mick Maytum IEC Technical Committee 109: Standards on insulation co-ordination for low-voltage equipment Warning Prepared by Mick Maytum mjmaytum@gmail.com The document content is of a general nature only and is not

More information

2 Grounding of power supply system neutral

2 Grounding of power supply system neutral 2 Grounding of power supply system neutral 2.1 Introduction As we had seen in the previous chapter, grounding of supply system neutral fulfills two important functions. 1. It provides a reference for the

More information

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS 29 th International Conference on Lightning Protection 23 rd 26 th June 2008 Uppsala, Sweden PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS Ivo Uglešić Viktor Milardić Božidar

More information

ABSTRACTS of SESSION 6

ABSTRACTS of SESSION 6 ABSTRACTS of SESSION 6 Paper n 1 Lightning protection of overhead 35 kv lines by antenna-module long flashover arresters Abstract: A long-flashover arrester (LFA) of a new antenna-module type is suggested

More information

A Case Study on Selection and Application of Lightning Arrester and Designing its Suitable Grounding Grid

A Case Study on Selection and Application of Lightning Arrester and Designing its Suitable Grounding Grid A Case Study on Selection and Application of Lightning Arrester and Designing its Suitable Grounding Grid 1 Arpan K. Rathod, 2 Chaitanya H. Madhekar Students Electrical Engineering, VJTI, Mumbai, India

More information

EMC Philosophy applied to Design the Grounding Systems for Gas Insulation Switchgear (GIS) Indoor Substation

EMC Philosophy applied to Design the Grounding Systems for Gas Insulation Switchgear (GIS) Indoor Substation EMC Philosophy applied to Design the Grounding Systems for Gas Insulation Switchgear (GIS) Indoor Substation Marcos Telló Department of Electrical Engineering Pontifical Catholic University of Rio Grande

More information

Overvoltage Protection

Overvoltage Protection Overvoltage Protection S T U D E N T M A N U A L March 31, 2005 2 STUDENT TRAINING MANUAL Prerequisites: Single-Phase Transformer Load Checks Objectives: From memory, you will be able to describe the electrical

More information

HIGH VOLTAGE Insulation Coordination

HIGH VOLTAGE Insulation Coordination HIGH VOLTAGE Insulation Coordination Assistant Professor Suna BOLAT KRÖGER Eastern Mediterranean University Department of Electric & Electronic Engineering Insulation coordination The term Insulation Co-ordination

More information

Appendix B to Working on Exposed Energized Parts

Appendix B to Working on Exposed Energized Parts Working on Exposed Energized Parts. - 1910.269 App B Regulations (Standards - 29 CFR) - Table of Contents Part Number: 1910 Part Title: Occupational Safety and Health Standards Subpart: R Subpart Title:

More information

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01 SEC DISTRIBUTION GROUNDING STANDARD SDCS-03 Part-II Rev.01 SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING Rev. 01 This specification is property of SEC

More information

Field Instruction. Induced voltages can occur in overhead lines, underground cables, or in switchyards.

Field Instruction. Induced voltages can occur in overhead lines, underground cables, or in switchyards. 8.3 Induced Voltage Purpose The purpose of this instruction is to provide awareness of Electrostatic and Electromagnetic induced voltages and the method required to reduce or eliminate it. An induced voltage

More information

University of Zagreb Faculty of Electrical Engineering and Computing

University of Zagreb Faculty of Electrical Engineering and Computing Journal of Energy VOLUME 64 2015 journal homepage: http://journalofenergy.com/ Viktor Milardić viktor.milardic@fer.hr Ivica Pavić ivica.pavic@fer.hr University of Zagreb Faculty of Electrical Engineering

More information

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT Claus NEUMANN Darmstadt University of Technology Germany claus.neumann@amprion.net Klaus WINTER Swedish Neutral

More information

INTERNATIONAL TELECOMMUNICATION UNION SERIES K: PROTECTION AGAINST INTERFERENCE

INTERNATIONAL TELECOMMUNICATION UNION SERIES K: PROTECTION AGAINST INTERFERENCE INTERNATIONAL TELECOMMUNICATION UNION )454 + TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU (10/96) SERIES K: PROTECTION AGAINST INTERFERENCE 2ISK ASSESSMENT OF DAMAGES TO TELECOMMUNICATION SITES DUE

More information

Evaluating Step and Touch Potential Risks on Earthing Systems of High Voltage Cable Systems TP, THINUS DU PLESSIS ESKOM SOUTH AFRICA HJ, HARTMUT JAGAU

Evaluating Step and Touch Potential Risks on Earthing Systems of High Voltage Cable Systems TP, THINUS DU PLESSIS ESKOM SOUTH AFRICA HJ, HARTMUT JAGAU Technology solutions and innovations for developing economies Evaluating Step and Touch Potential Risks on Earthing Systems of High Voltage Cable Systems TP, THINUS DU PLESSIS ESKOM SOUTH AFRICA HJ, HARTMUT

More information

PRACTICAL PROBLEMS WITH SUBSTATION EARTHING

PRACTICAL PROBLEMS WITH SUBSTATION EARTHING 1 PRACTICAL PROBLEMS WITH SUBSTATION EARTHING Dr Hendri Geldenhuys Craig Clark Eskom Distribution Technology This paper considers the issues around substation sites where the soil resistivity is of particularly

More information

AMENDMENT NO. 1 SEPTEMBER IS (Part 1) : 2001/IEC (1991) SURGE ARRESTORS

AMENDMENT NO. 1 SEPTEMBER IS (Part 1) : 2001/IEC (1991) SURGE ARRESTORS AMENDMENT NO. 1 SEPTEMBER 2011 TO IS 15086 (Part 1) : 2001/IEC 60099-1 (1991) SURGE ARRESTORS PART 1 NON-LINEAR RESISTOR TYPE GAPPED SURGE ARRESTORS FOR a.c. SYSTEMS (The Amendment was originally published

More information

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT A. General In a hazardous location grounding of an electrical power system and bonding of enclosures of circuits and electrical equipment in the

More information

TECHNICAL NOTE 2.0. Overvoltages origin and magnitudes Overvoltage protection

TECHNICAL NOTE 2.0. Overvoltages origin and magnitudes Overvoltage protection ECHNICAL NOE 2.0 Overvoltages origin and magnitudes Overvoltage protection he ECHNICAL NOES (N) are intended to be used in conjunction with the APPLICAION GIDELINES Overvoltage protection Metaloxide surge

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements Division 502 Technical Applicability 1(1) Section 502.1 applies to: Expedited Filing Draft August 22, 2017 the legal owner of an aggregated generating facility directly connected to the transmission system

More information

Investigation on the Performance of Different Lightning Protection System Designs

Investigation on the Performance of Different Lightning Protection System Designs IX- Investigation on the Performance of Different Lightning Protection System Designs Nicholaos Kokkinos, ELEMKO SA, Ian Cotton, University of Manchester Abstract-- In this paper different lightning protection

More information

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING. Rev. 01

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING. Rev. 01 SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING Rev. 01 This specification is property of SEC and subject to change or modification without any notice

More information

High Voltage Pylon earth Measurements. Tycom (Pty) Ltd Frank Barnes Comtest (Pty) Ltd Presented by Gavin van Rooy

High Voltage Pylon earth Measurements. Tycom (Pty) Ltd Frank Barnes Comtest (Pty) Ltd Presented by Gavin van Rooy High Voltage Pylon earth Measurements Tycom (Pty) Ltd Frank Barnes Comtest (Pty) Ltd Presented by Gavin van Rooy Abstract The earth connection of high voltage electrical power line pylons is obviously

More information

Voltage Sags Evaluating Methods, Power Quality and Voltage Sags Assessment regarding Voltage Dip Immunity of Equipment

Voltage Sags Evaluating Methods, Power Quality and Voltage Sags Assessment regarding Voltage Dip Immunity of Equipment s Evaluating Methods, Power Quality and s Assessment regarding Voltage Dip Immunity of Equipment ANTON BELÁŇ, MARTIN LIŠKA, BORIS CINTULA, ŽANETA ELESCHOVÁ Institute of Power and Applied Electrical Engineering

More information

APPLICATION OF LONG FLASHOVER ARRESTERS FOR IMPROVEMENT OF LIGHTNING PROTECTION AND OPERATING VOLTAGE RELIABILITY OF DISTRIBUTION LINES

APPLICATION OF LONG FLASHOVER ARRESTERS FOR IMPROVEMENT OF LIGHTNING PROTECTION AND OPERATING VOLTAGE RELIABILITY OF DISTRIBUTION LINES APPLICATION OF LONG FLASHOVER ARRESTERS FOR IMPROVEMENT OF LIGHTNING PROTECTION AND OPERATING VOLTAGE RELIABILITY OF DISTRIBUTION LINES G. V. Podporkin, V. E. Pilshikov, A. D. Sivaev Streamer Electric

More information

Outdoor Installation 2: Lightning Protection and Grounding

Outdoor Installation 2: Lightning Protection and Grounding Outdoor Installation 2: Lightning Protection and Grounding Training materials for wireless trainers This one hour talk covers lightning protection, grounding techniques and problems, and electrolytic incompatibility.

More information

SAFETY ISSUES RELATED TO THE CONNECTION OF MV AND HV GROUNDING

SAFETY ISSUES RELATED TO THE CONNECTION OF MV AND HV GROUNDING SAFETY ISSUES RELATED TO THE CONNECTION OF MV AND HV GROUNDING Y. Rajotte J. Fortin G. Lessard Hydro-Québec, Canada Hydro-Québec, Canada Hydro-Québec, Canada e-mails: rajotte.yves@ireq.ca fortin.jacques@ireq.ca

More information

A DUMMIES GUIDE TO GROUND FAULT PROTECTION

A DUMMIES GUIDE TO GROUND FAULT PROTECTION A DUMMIES GUIDE TO GROUND FAULT PROTECTION A DUMMIES GUIDE TO GROUND FAULT PROTECTION What is Grounding? The term grounding is commonly used in the electrical industry to mean both equipment grounding

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Current Transducer LF 1010-S/SPA5 I P N = 1000 A For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Features Bipolar and

More information

6. Internal lightning protection

6. Internal lightning protection 6. Internal lightning protection 6.1 Equipotential bonding for metal installations Equipotential bonding according to IEC 60364-4- 41 and IEC 60364-5-54 Equipotential bonding is required for all newly

More information

EPR Safety Mat Modelling & Field Testing Summary Report

EPR Safety Mat Modelling & Field Testing Summary Report EPR Safety Mat Modelling & Field Testing Summary Report 15 April 2014 1. Purpose This document present a summary of the calculations and field testing used to prove the efficacy of the new EPR Safety Mat

More information

LIMITING THE DANGER OF ELECTRIC CURRENT SHOCK IN RELATION TO THE MEAN OF NEUTRAL POINT EARTHING IN THE MV NETWORKS

LIMITING THE DANGER OF ELECTRIC CURRENT SHOCK IN RELATION TO THE MEAN OF NEUTRAL POINT EARTHING IN THE MV NETWORKS LIMITING THE DANGER OF ELECTRIC CURRENT SHOCK IN RELATION TO THE MEAN OF NEUTRAL POINT EARTHING IN THE MV NETWORKS Witold Hoppel, Józef Lorenc!" ph.+48 61 8782279 - FAX + 48 61 8782280 Jerzy Andruszkiewicz

More information

Grounding for Power Quality

Grounding for Power Quality Presents Grounding for Power Quality Grounding for Power Quality NEC 250.53 states that ground resistance should be less than 25 ohms. Is this true? Grounding for Power Quality No! NEC 250.53 states

More information

Lightning overvoltage and protection of power substations

Lightning overvoltage and protection of power substations Lightning overvoltage and protection of power substations Mahmud Trainba 1, Christos A. Christodoulou 2, Vasiliki Vita 1,2, Lambros Ekonomou 1,2 1 Department of Electrical and Electronic Engineering, City,

More information

Cable Protection against Earth Potential Rise due to Lightning on a Nearby Tall Object

Cable Protection against Earth Potential Rise due to Lightning on a Nearby Tall Object Cable Protection against Earth Potential Rise due to Lightning on a Nearby Tall Object U. S. Gudmundsdottir, C. F. Mieritz Abstract-- When a lightning discharge strikes a tall object, the lightning current

More information

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models International Journal of Electrical & Computer Sciences IJECS-IJENS Vol:15 No:03 39 Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models Shen-Wen Hsiao, Shen-Jen

More information

G. KOEPPL Koeppl Power Experts Switzerland

G. KOEPPL Koeppl Power Experts Switzerland PS3: Substation Design: New Solutions and Experiences Bus-Node Substation A Big Improvement in Short-Circuit and Switching Properties at Reduced Substation Costs G. KOEPPL Koeppl Power Experts Switzerland

More information

Energy Division. Bowthorpe LV/MV Surge Arresters

Energy Division. Bowthorpe LV/MV Surge Arresters Energy Division Bowthorpe LV/MV Surge Arresters Bowthorpe EMP LV/MV surge arresters OCP, Open Cage Polymeric series Bowthorpe pioneered the development of polymeric housed surge arresters in the early

More information

CHAPTER 10 HIGH VOLTAGE TESTING OF ELECTRICAL APPARATUS

CHAPTER 10 HIGH VOLTAGE TESTING OF ELECTRICAL APPARATUS CHAPTER 10 HIGH VOLTAGE TESTING OF ELECTRICAL APPARATUS 1. Introduction 2. Classification of High Voltage Tests 3. Test Voltages 4. High Voltage Testing of Electrical Apparatus 1. INTRODUCTION Purpose

More information

kv AC substation

kv AC substation 132-400 kv AC substation Outdoor AC substations Earthing systems ETS-50-08-01, Rev. 0 technical standard Document no. 13/90592-127 ETS-50-08-01 v. 0 REVISION VIEW Document no.: 13/90592-127 Version Author

More information

Safety Issues Caused by High Earth Resistance and Identifying Them Using Instruments

Safety Issues Caused by High Earth Resistance and Identifying Them Using Instruments Safety Issues Caused by High Earth Resistance and Identifying Them Using Instruments Thomas Szollossy Senior Technical Support Engineer Power Quality Thailand PQSynergy 2017, Chiang Mai, Thailand Introduction

More information

Power Quality. Case Study. Conrad Bottu Laborelec January 2008

Power Quality. Case Study. Conrad Bottu Laborelec January 2008 Case Study Electromagnetic compatibility (EMC) study Breakdown of low voltage electronic equipment in a 25 kv substation Conrad Bottu Laborelec January 2008 Power Quality Power Quality 1 Introduction Description

More information

LIGHTNING EARTHING SYSTEM : A PRACTICAL GUIDE

LIGHTNING EARTHING SYSTEM : A PRACTICAL GUIDE International Lightning Protection Association 1 st Symposium Valencia Spain 24th 25th of November, 2011 LIGHTNING EARTHING SYSTEM : A PRACTICAL GUIDE Alain Rousseau SEFTIM (France) ABSTRACT To make a

More information

Installation and Operational Instructions for ROBA -switch Type 017._00.2

Installation and Operational Instructions for ROBA -switch Type 017._00.2 OBA -switch Type 017._00.2 Guidelines on the Declaration of Conformity A conformity evaluation has been carried out for the product in terms of the EC Low Voltage Directive 2014/35/ EC and the EMC Directive

More information

High Voltage Pylon Earth Measurements

High Voltage Pylon Earth Measurements High Voltage Pylon Earth Measurements Speaker: Gavin van Rooy Authors: Frank Barnes and Gavin van Rooy Tycom (Pty) Ltd PO Box 3546, Randburg, 2125, South Africa E-mail: frank@tycom.co.za Phone: 011 787

More information

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E.

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E. Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E. HP Critical Facility Services delivered by EYP MCF What is VOLTAGE? Difference of Electric Potential

More information

Insulation Co-ordination For HVDC Station

Insulation Co-ordination For HVDC Station Insulation Co-ordination For HVDC Station Insulation Co-ordination Definitions As per IEC 60071 Insulation Coordination is defined as selection of dielectric strength of equipment in relation to the operating

More information

2007 DEHN + SÖHNE / protected by ISO EXFS / 5392

2007 DEHN + SÖHNE / protected by ISO EXFS / 5392 2007 DEHN + SÖHNE / protected by ISO 16016 EXFS 100 11.12.07 / 5392 Ex Isolating Spark Gaps EXFS 100 (923 100) and EXFS 100 KU (923 101) 2007 DEHN + SÖHNE / protected by ISO 16016 Ex isolating spark gap

More information

Underground System Design TADP 547

Underground System Design TADP 547 Underground System Design TADP 547 Industry Standards, Specifications and Guides Presentation 6.4 Instructor: Frank Frentzas Industry Organizations Several professional organizations develop standards

More information

Education & Training

Education & Training Distribution System Operator Certificate This program provides you with a proficient working knowledge in modern electric power distribution systems. These four classes are designed to walk students through

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and secondary circuit. Current Transducer LF 510-S I P N = 500 A For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and secondary circuit. Features Bipolar and insulated

More information

Analysis of lightning performance of 132KV transmission line by application of surge arresters

Analysis of lightning performance of 132KV transmission line by application of surge arresters Analysis of lightning performance of 132KV transmission line by application of surge arresters S. Mohajer yami *, A. Shayegani akmal, A.Mohseni, A.Majzoobi High Voltage Institute,Tehran University,Iran

More information

Lightning performance of a HV/MV substation

Lightning performance of a HV/MV substation Lightning performance of a HV/MV substation MAHMUD TAINBA, LAMBOS EKONOMOU Department of Electrical and Electronic Engineering City University London Northampton Square, London EC1V HB United Kingdom emails:

More information

LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION

LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION Andreas SUMPER sumper@citcea.upc.es Antoni SUDRIÀ sudria@citcea.upc.es Samuel GALCERAN galceran@citcea.upc.es Joan RULL rull@citcea.upc.es

More information

Protection of Electrical Networks. Christophe Prévé

Protection of Electrical Networks. Christophe Prévé Protection of Electrical Networks Christophe Prévé This Page Intentionally Left Blank Protection of Electrical Networks This Page Intentionally Left Blank Protection of Electrical Networks Christophe Prévé

More information

GROUNDING. What is it? Al Lewey K7ABL. Disclaimer

GROUNDING. What is it? Al Lewey K7ABL. Disclaimer GROUNDING What is it? Al Lewey K7ABL Disclaimer Disclamier Mechanical Engineer with some electrical background My primary reference is References UP THE TOWER The Complete Guide to Tower Construction By

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Current Transducer IN 1000-S N = 1000 A For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Features Closed loop (compensated)

More information

Fixed Series Compensation

Fixed Series Compensation Fixed Series Compensation High-reliable turnkey services for fixed series compensation NR Electric Corporation The Fixed Series Compensation (FSC) solution is composed of NR's PCS-9570 FSC control and

More information

SAUDI STANDARD NO. SASO IEC : 2007 SWITCHES FOR HOUSEHOLD AND SIMILAR FIXED ELECTRICAL INSTALLATIONS

SAUDI STANDARD NO. SASO IEC : 2007 SWITCHES FOR HOUSEHOLD AND SIMILAR FIXED ELECTRICAL INSTALLATIONS SAUDI STANDARD NO. SASO IEC 60669-2-2: 2007 SWITCHES FOR HOUSEHOLD AND SIMILAR FIXED ELECTRICAL INSTALLATIONS Part 2-2: Particular requirements Electromagnetic remote-control switches (RCS) SAUDI ARABIAN

More information

CONTINUING EDUC ATION

CONTINUING EDUC ATION 3 CONTINUING EDUC ATION FOR WISCONSIN ELECTRICIANS 2017 NEC Article 250 2 Hours WISCONSIN CONTRACTORS INSTITUTE N16 W23217 Stone Ridge Drive Suite 290 Waukesha, WI 53188 262-409-4282 www.wcitraining.com

More information

Electric Stresses on Surge Arrester Insulation under Standard and

Electric Stresses on Surge Arrester Insulation under Standard and Chapter 5 Electric Stresses on Surge Arrester Insulation under Standard and Non-standard Impulse Voltages 5.1 Introduction Metal oxide surge arresters are used to protect medium and high voltage systems

More information

American Electrical Institute

American Electrical Institute American Electrical Institute Oregon Electricians Continuing Education Grounding & Bonding (Article 250) 4 Hours American Electrical Institute PO Box 31131 Spokane, WA 99223 www.aeitraining.com Article

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Current transducer LF 510-S I PN = 500 A For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Features Bipolar and insulated

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Current Transducer LF 2010-S/SPA7 I P N = 2000 A For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Features Bipolar and

More information

VBS TBS KTS BSS LFS UFS

VBS TBS KTS BSS LFS UFS VBS TBS KTS BSS LFS UFS TBS. Surge protection systems Order information and technical data Protection and isolating spark gaps Protection spark gap or isolating spark gap? Isolating spark gaps Protection

More information

Parameters Affecting the Back Flashover across the Overhead Transmission Line Insulator Caused by Lightning

Parameters Affecting the Back Flashover across the Overhead Transmission Line Insulator Caused by Lightning Proceedings of the 14 th International Middle East Power Systems Conference (MEPCON 10), Cairo University, Egypt, December 19-21, 2010, Paper ID 111. Parameters Affecting the Back Flashover across the

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Current transducer LF 210-S/SP3 I PN = 100 A For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Features Bipolar and insulated

More information

The Many Uses of Transmission Line Arresters

The Many Uses of Transmission Line Arresters Introduction It was not realized at the time, but the 1992 introduction of the polymer-housed transmission line arrester (TLA) was clearly a game changer in the practice of lightning protection of transmission

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Current transducer LF 1010-S/SPA2 I PN = 1000 A For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Features Bipolar and

More information

Isolating Spark Gaps. Isolating spark gaps at an additional earth ring conductor. Isolating spark gaps for Ex zones

Isolating Spark Gaps. Isolating spark gaps at an additional earth ring conductor. Isolating spark gaps for Ex zones Isolating Spark Gaps Isolating spark gaps at an additional earth ring conductor Isolating spark gaps for Ex zones 187 Protective Spark Gaps For use at roof supports for overhead lines For indirect connection

More information

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY 9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor

More information

WIRELESS INSULATOR POLLUTION MONITORING SYSTEM

WIRELESS INSULATOR POLLUTION MONITORING SYSTEM SYSTEM OVERVIEW Pollution monitoring of high voltage insulators in electrical power transmission and distribution systems, switchyards and substations is essential in order to minimise the risk of power

More information

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 BONDING METHODS

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 BONDING METHODS 1.0 SCOPE 2.0 BONDING METHODS 2.1 Introduction 2.2 Design 2.3 Single-Point Bonding 2.4 Cross Bonding 2.5 Sheath Sectionalizing Joints 2.6 Sheath Standing Voltage 2.7 Sheath Voltage at Through Fault 2.8

More information

The Role of the Grounding System in Electronics Lightning Protection

The Role of the Grounding System in Electronics Lightning Protection ILPS 2016 - International Lightning Protection Symposium April 21-22, 2016 Porto Portugal The Role of the Grounding System in Electronics Lightning Protection Roberto Menna Barreto SEFTIM Brazil Rio de

More information

MATEFU Insulation co-ordination and high voltage testing of fusion magnets

MATEFU Insulation co-ordination and high voltage testing of fusion magnets Stefan Fink: MATEFU Insulation co-ordination and high voltage testing of fusion magnets Le Chateau CEA Cadarache, France April 7th, 29 Insulation co-ordination Some principle considerations of HV testing

More information

TECHNICAL SPECIFICATION

TECHNICAL SPECIFICATION TECHNICAL SPECIFICATION IEC TS 60071-5 First edition 2002-06 Insulation co-ordination Part 5: Procedures for high-voltage direct current (HVDC) converter stations Coordination de l isolement - Partie 5:

More information

I P. /dt. di p V S Applications. Standards 1) IEC : 2007; IEC : ) IEC : 2016; IEC : 2017

I P. /dt. di p V S Applications. Standards 1) IEC : 2007; IEC : ) IEC : 2016; IEC : 2017 Ref: ART-B22-D70, ART-B22-D125, ART-B22-D175, ART-B22-D300 Flexible clip-around Rogowski coil for the electronic measurement of AC current with galvanic separation between the primary circuit (power) and

More information

Single Earthed Neutral and Multi Earthed Neutral. Single Earthed Neutral and Multi Earthed Neutral: Multi Grounded Neutral System (MEN):

Single Earthed Neutral and Multi Earthed Neutral. Single Earthed Neutral and Multi Earthed Neutral: Multi Grounded Neutral System (MEN): Single Earthed Neutral and Multi Earthed Neutral. SEPTEMBER 6, 2011 5 COMMENTS Single Earthed Neutral and Multi Earthed Neutral: In Distribution System Three Phase load is unbalance and non linear so The

More information

Need for grounding Codes and Standards for grounding Wind Turbine Generator grounding design Foundation + Horizontal Electrode grounding design

Need for grounding Codes and Standards for grounding Wind Turbine Generator grounding design Foundation + Horizontal Electrode grounding design IEEE PES Transmission and Distribution Conference 2008 Panel Session Large Wind Plant Collector Design Wind Farm Collector System Grounding by Steven W. Saylors, P.E. Chief Electrical Engineer Vestas Americas

More information

Section 6: System Grounding Bill Brown, P.E., Square D Engineering Services

Section 6: System Grounding Bill Brown, P.E., Square D Engineering Services Section 6: System Grounding Bill Brown, P.E., Square D Engineering Services Introduction The topic of system grounding is extremely important, as it affects the susceptibility of the system to voltage

More information

Webinar: An Effective Arc Flash Safety Program

Webinar: An Effective Arc Flash Safety Program Webinar: An Effective Arc Flash Safety Program Daleep Mohla September 10 th, 2015: 2pm ET Agenda Arc Flash Defined and Quantified NFPA 70E / CSA Z 462 - Recent Updates What is the ANSI Z10 Hierarchy of

More information

TECHNICAL REPORT. Insulation co-ordination

TECHNICAL REPORT. Insulation co-ordination TECHNICAL REPORT IEC TR 60071-4 First edition 2004-06 Insulation co-ordination Part 4: Computational guide to insulation co-ordination and modelling of electrical networks IEC 2004 Copyright - all rights

More information

Insulation Coordination Fundamentals Where Arrester and Insulator Characteristics Meet

Insulation Coordination Fundamentals Where Arrester and Insulator Characteristics Meet ArresterWorks Insulation Coordination Fundamentals Where Arrester and Insulator Characteristics Meet 6/23/2012 Jonathan Woodworth Transient overvoltages are a fact of life on power systems. Arresters can

More information

Protection against unacceptable voltages in railway systems

Protection against unacceptable voltages in railway systems Bernhard Richter*, Alexander Bernhard*, Nick Milutinovic** SUMMERY Based on the system voltages for AC and DC railway systems the required voltage ratings for modern gapless MO surge arresters are given.

More information

Coordination of surge arresters in DC 3 kv railway traction system field tests

Coordination of surge arresters in DC 3 kv railway traction system field tests Coordination of surge arresters in DC 3 kv railway traction system field tests Miroslaw Zielenkiewicz Tomasz Maksimowicz Center of Protection against Overvoltages and Electromagnetic Interferences RST

More information

Residual Current Operated Circuit-Breakers (RCCBs)

Residual Current Operated Circuit-Breakers (RCCBs) Product Overview Residual Current Operated Circuit-Breakers (RCCBs) Residual current operated circuit-breakers Number of poles Rated current A Rated residual current ma MW Auxiliary contacts can be mounted

More information

Installation and Operational Instructions for ROBA -multiswitch Type 019._00.2

Installation and Operational Instructions for ROBA -multiswitch Type 019._00.2 Guidelines on the Declaration of Conformity A conformity evaluation has been carried out for the product in terms of the EU Low Voltage Directive 2014/35/ EU and the Electromagnetic Compatibility (EMC)

More information

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS TRANSFORMER IN GRID When surge arres t ers are installed close to a power transformer, they provide protection against lightning overvoltage ABSTRACT The aim of this research article is to determine the

More information

Fault location on power cables. Fault location on power cables

Fault location on power cables. Fault location on power cables Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 1. Introduction Fault location on communication and power cables

More information

DSA150 Series. xxx Series. 150 Watts. AC-DC Power Supplies. Models & Ratings. Mechanical Details 3.92 (99.8) 2.18 (55.5) 4.92 (125.

DSA150 Series. xxx Series. 150 Watts.   AC-DC Power Supplies. Models & Ratings. Mechanical Details 3.92 (99.8) 2.18 (55.5) 4.92 (125. 15 Watts xxx Series Ultra Slim Design 15% Peak Load for 3 seconds Ambient Operation from -1 C to +7 C High Efficiency Selectable Overload Characteristic Selectable Remote Inhibit or Enable 3 Year Warranty

More information

POWER QUALITY AND SAFETY

POWER QUALITY AND SAFETY POWER QUALITY AND SAFETY Date : November 27, 2015 Venue : 40 th IIEE Annual National Convention and 3E XPO 2015 PRESENTATION OUTLINE Power Quality I. INTRODUCTION II. GRID CODE REQUIREMENTS III. ERC RESOLUTION

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Current Transducer LF 21-S/SPA2 I P N = 2 A For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Features Bipolar and insulated

More information

National Radio Astronomy Observatory Socorro, NM EVLA Memorandum 41 Lightning Protection for Fiber Optic Cable. T. Baldwin June 05, 2002

National Radio Astronomy Observatory Socorro, NM EVLA Memorandum 41 Lightning Protection for Fiber Optic Cable. T. Baldwin June 05, 2002 National Radio Astronomy Observatory Socorro, NM 87801 EVLA Memorandum 41 Lightning Protection for Fiber Optic Cable T. Baldwin June 05, 2002 Summary Double-armor triple-sheath fiber optic cable will be

More information

ABSTRACT 1.0 INTRODUCTION LIST OF SYMBOLS

ABSTRACT 1.0 INTRODUCTION LIST OF SYMBOLS Lightning protection of pole-mounted transformers and its applications in Sri Lanka Prof. J R Lucas* and D A J Nanayakkara # *University of Moratuwa, # Lanka Transformers Limited ABSTRACT This paper presents

More information

ECE 528 Understanding Power Quality

ECE 528 Understanding Power Quality ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-316-1520 (voice) 1 Today Wiring and grounding Why it s important References Terms and

More information