Protection against unacceptable voltages in railway systems

Size: px
Start display at page:

Download "Protection against unacceptable voltages in railway systems"

Transcription

1 Bernhard Richter*, Alexander Bernhard*, Nick Milutinovic** SUMMERY Based on the system voltages for AC and DC railway systems the required voltage ratings for modern gapless MO surge arresters are given. The origin of overvoltages occurring in railway systems are explained, and some typical figures are presented. VDV Recommendation 525 gives a protection concept for railway systems with U n = 600 V and U n = 750 V DC, including requirements for MO arresters. This protection concept is becoming common praxis in other DC railway systems as well, e.g. in 1500 V DC and 3000 V DC systems. The described concept provides protection of equipment against overvoltages originating from lightning and switching. For the protection against dangerous touch voltages low voltage limiters are used. These devices, generally based on gap technology, have the disadvantage of short-circuiting when stressed with impulses due to lightning. To overcome this problem a new hybrid voltage limiter, a combination of MOsurge arrester and low voltage limiter was developed and introduced. Tests with LVLs prove that these devices go in short-circuit conditions after the first impulse stress. LVLs with claimed lightning resistance withstand impulse stresses originated by lightning phenomena. Anyhow, the discharge voltage is changing after applied impulse stresses, being then in some cases out of the declared tolerances. The hybrid voltage limiter HVL turns out to be the only device that protects against overvoltages and touch voltages and provides reliable and safe protection. 1 INTRODUCTION Overvoltages in electrical supply networks of AC and DC railway networks result from the effects of lightning strokes and switching actions and cannot be avoided. Furthermore, the power supply of electrical railways is endangered by direct or nearby lightning. Considering additional the safety aspects for people (touch voltages) in railway systems, one has to deal with three aspects: direct or nearby lightning, induced voltages, and unacceptable voltages due to failures in the system (e.g. breaking of overhead line). Depending on the insulation of the rails against earth, different aspects have to be considered for a general protection concept. A new device, combining protection against overvoltages and touch voltages is introduced. 2 VOLTAGES IN RAILWAY SYSTEMS 2.1 System Voltages The supply voltages for railway networks are given in the European Standard EN : Railway applications Supply voltages of traction systems. In the following some definitions and values are given, which are necessary for the dimensioning of the MO-surge arresters and the protection concept in general. Nominal voltage U n : the designated value for a system. Highest permanent voltage U max1 : the maximum value of the voltage likely to be present indefinitely. Highest non-permanent voltage U max2 : the maximum value of the voltage likely to be present for maximum of 5 min. Table 1 gives the voltage values for the relevant DC and AC systems. U n in V, DC U max1 in V, DC U max2 in V, DC U n in V, AC U max1 in V, AC Table 1 U max2 in V, AC The values in Table 1 for U max2 can become 800

2 V in the 600 V system, and 1000 V in the 750 V system in case of regenerative breaking. The AC values are given in rms values. The system with U n =15 kv has a power frequency of f=16,7 Hz, the system with U n =25 kv a power frequency of f=50 Hz. 2.2 Overvoltages The dimensions (height, insulators, etc.) of overhead AC and DC power supply systems in railway networks are somewhat similar to medium voltage (MV) distribution networks. Therefore, with respect to overvoltages in AC and DC power supply systems the same considerations as for MV systems may be used for an estimation of the occurring stresses. The expected number of direct and indirect lightning events depends on the exposure of the line and on the screening provided by nearby objects such as trees, buildings, towers, etc. Overvoltages due to direct and indirect lightning strikes are characterized by complex and very different wave shapes. Overvoltages due to a direct strike have an overall wave shape similar to that of the incident lightning current, the fast rising portion being superimposed with several spikes which are due to insulation breakdown. Induced overvoltages are characterized by pulse width significantly shorter than the channel-base current of the lightning and their wave shape is strongly affected by the ground electrical conductivity Overvoltages due to direct lightning A lightning striking a phase conductor injects current waves in both directions. The corresponding voltage equals half of the current multiplied by the line characteristic impedance, which is about 400 Ω. Since more than 90% of the strokes have a peak current of at least 10 ka, the overvoltage will exceed 2 MV for 90% of the strokes. These voltages are far above the lightning withstand of the line. For this reason flashovers between phase and earth will occur. Depending on the type of pole and the earthing conditions this voltage can still reach values up to the MV range Lightning-induced overvoltages A cloud-to-ground lightning flash generates a transient electromagnetic field which can induce overvoltages of significant magnitudes on overhead power lines in the vicinity. The return stroke of the lightning discharge is considered to be the major responsible for the induced voltages, because the highest di/dt in the lightning channel occurs during this phase. The analysis and calculation of lightning-induced overvoltages require the use of elaborate models. The complexity of these models calls for an implementation into computer codes because they require a numerical integration of the relevant equations. For more details see for instance, where the different models are described and the influencing lightning parameters (peak value of the current and steepness di/dt) are explained. Table 2 gives typical parameters for induced overvoltages (calculated values, considering the point of flash in 50 m distance from the line, adopted from [1]) First stroke I peak = 30 ka Subsequent stroke I peak = 12 ka U peak (kv) du/dt max (kv/µs) Front time (µs) 2,8 0,8 Time to half value (µs) Table 2 5,8 1,7 For illustrating the influence of the peak value of the current the following examples for induced overvoltages U peak are given (considering a constant di/dt of 40 ka/µs) I peak U peak 4,6 ka 28 kv 12 ka 66 kv 30 ka 133 kv For a constant current peak value of I peak = 12 ka the steepness di/dt of the current influences the peak value U peak of the induced voltage as follows. di/dt U peak 12 ka/µs 50 kv 40 ka/µs 66 kv 120 ka/µs 72 kv

3 2.3 Touch Voltages The earthing concepts for AC and DC railway systems are different. In AC systems the rails are directly connected with all metallic parts along the rails, e.g. the poles, and the common earth. In DC systems the rails are isolated against the earth to avoid stray currents. Especially in DC systems dangerous potential differences can occur due to normal train service, and especially in case of failures like broken overhead lines or derailed pantographs. All this leads to endangering of persons and has to be avoided by the use of low voltage limiters. The acceptable values for touch voltages U t and admissible voltages U c1 are given in different standards, for instance in EN :1997 [2]. The acceptable touch voltages U t are depending on the time duration. The longer the time, the lower the value. The touch voltages depend on the impedance of the human body, the resistance of the shoes etc., and therefore it is complicated to estimate exact values for all cases. As long as the effects of AC and DC currents are somewhat different in the human body, the values for the touch voltages are a bit different for AC and DC. In the time range of t=0,02 s the touch voltages can be up to U t =940 V, for t=0,5 s the voltage is U t = 395 V (for DC systems), and for t=1 s and longer time durations the voltage has to be in any case below 80 V or even 25 V depending on the degree of safety required. 3 PROTECTIVE DEVICES 3.1 MO Surge Arresters The wish to increase the reliability and safety of the arresters, and correspondingly of the energy supply, brought about the development of the arresters with polymeric housing in the middle of the eighth decade of the last century. Silicon, as an insulating material with excellent properties, especially under severe pollution conditions, is used in the high voltage area since about 35 years. Due to the various possibilities of application in very difficult electrical, mechanical and environmental conditions special designs are increasingly recognized globally, especially in medium voltage systems and for specific applications as for instance DC systems. When designing arresters for different network voltages, three main characteristics are to be considered: the highest continuous voltage that arises in the network, the protection level, and the energy absorption capability of the arrester. The strong voltage fluctuations in the railway systems make it necessary to lay the maximum continuous operating voltage U c of the MOarrester above the highest continuous voltage U max1 of the system. The highest non-permanent voltage U max2 of the system can appear for 5 min, but it is not known how often and in which time intervals this can happen. As long as the modern MO-surge arresters have very favourable protection levels combined with a high energy absorption capability, it is possible to lay the MO-arresters continuous operating voltage U c equal or higher to U max2, so that follows U c U max2. It follows for the system voltages acc. to Table 1: U n = 600 V => U c 800 V U n = 750 V => U c 1000 V U n = 1500 V => U n = 3000 V => U c 1950 V U c 3900 V U n = 15 kv => U c 18 kv U n = 25 kv => U c 29 kv MO surge arresters for AC application AC networks with 15 kv, 16,7 Hz. With the SBB and other Swiss Railways MO surge arresters with U c =18 kv are used on electrical locomotives and in overhead lines. Due to safety aspects completely in silicon moulded MO surge arresters with line discharge class 3 are used for the overhead lines, and line discharge class 4 for the use on locomotives. The German DB adopted a coordination concept with the locomotive BRE 101, which is used in the interregional trains, and installs on the roof of the locomotive a MO surge arrester with U c =18 kv and in the locomotive one with U c =20 kv. Again, the arrester on the roof of the locomotive is of line discharge class 4, the one in the locomotive has a lower line discharge class. AC networks with 25 kv, 50 Hz. MO surge arresters with U c =29 kv to U c =31 kv are used in the German National Railways (DB). With modern E-locomotives the high voltage from the collector is brought into the inner part of the locomotive through a cable, and this requires again a coordination of the MO arresters on the locomotive and in the locomotive. On the roof of the locomotive are two arresters with U c =29 kv and line discharge class 4 are installed, at each pantograph one, and in the locomotive an

4 arrester with U c =31 kv and a lower line discharge class in front of the main power breaker. The ratio U p /U c can be chosen 3, as long as the thermal stability of the MO-arrester in the system is not endangered. A ratio U p /U c >3 is not acceptable. Most of the modern MO-surge arresters on the market to be used as A1-arresters have a lower protection level than the here proposed 3,0 kv, for instance U p =2,4 kv. It should be taken advantage of the better protection level when choosing an A1-arrester. Fig.2 shows examples of A1- and A2-arresters. Fig. 1: MO surge arrester type POLIM-H 18 N on the roof of a locomotive (left) MO surge arresters for DC application DC networks of 600 V and 750 V. In [3] a protection concept for DC railway systems with a nominal voltage U n =600 V and U n =750 V, and the requirements for MO-surge arresters to be used, are proposed. The protection concept defines two arresters according to their place of installation and their application, a type A1, between the overhead line, or the feeder-line, and the return line (may be the rail), and a type A2 between the return line (rail) and the so called station earth (equipotential bar). The details of this concept are given in the following chapters. Requirements on A1-arresters: - Maximum continuous operating voltage U c 1,0 kv - Protection level U p 3,0 kv - Nominal current I n (8/20 µs) 10 ka - Rectangular current, 2 ms I rw 1200 A - Short circuit current 20 ka Requirements on A2-arresters: - Maximum continuous operating voltage 120 V U c 300 V - Protection level 360 V U p 900 V - Nominal current I n (8/20 µs) 10 ka - Rectangular current, 2 ms I rw 1200 A - Short circuit current 20 ka Fig. 2: A1-arrester with U c =1,0 kv (left) and A2- arrester with U c =0,29 kv (middle). Both the arresters are completely moulded in silicon. On the right a HVL is shown. 3.2 Low Voltage Limiters In order to avoid stray currents in DC railway systems it is common practise not to have a direct earthing of the rails, as far as possible. In case of a broken overhead line (falling down of the conductor) an unacceptable high touch voltage may occur. Normal train service may also produce a voltage rise of unacceptably high values. In such cases personal protection is given by the use of low voltage limiters (LVL). Basically, LVLs consist of two opposite copper electrodes, insulated from each other, which produce a remaining short-circuit (by melting together) after energy absorption beyond a specified maximum value. The insulation is implemented by a ring of insulating material. Alternatively a gas discharge tube is used to provide insulation and to ensure a certain degree of protection against surges in addition. LVLs produce a short-circuit between the two potentials whenever an unacceptable touch voltage occurs. The short-circuit persists because virtually all LVLs existing in the market are not reversible once after being in shortcircuit condition. Low voltage limiters, installed in substations and along the rails, are stressed with surges originated by lightning.

5 3.3 Hybrid Voltage Limiter HVL 120-0,3 The HVL can be considered a fully reversible low voltage limiter with very high energy handling capability, combining the required personal protection against touch voltages with the protection of electrical equipment against lightning overvoltages. The HVL is made up from a metal oxide (MO) resistor in parallel to two thyristors in anti-parallel configuration. The MO resistor functions as a surge arrester and limits lightning and switching overvoltages (time range between some microseconds to some hundred microseconds). The thyristors short-circuit potential rises of the rail and provide protection against dangerous touch voltages (time range app. 400 µs up to minutes). The MO-resistor in the HVL is of the same diameter and the same electrical characteristics as the MO-resistor in the A1-arrester. Therefore, by combining an A1-arrester with a HVL an optimised protection can be achieved. This protection concept can be used in overhead lines and in substations as well, just by replacing the A2-arrester by a HVL. Figure 2 shows a HVL with accessories as well as examples of A1 and A2 arresters. U U I MO-resistor no trigger Triggerelektronik trigger unit thyristor triggered antiparallel thyristors overvoltage protection protection against touch voltages Fig. 3: Hybrid voltage limiter type HVL. Figure 3 shows on the top the principle circuitry of the HVL, in the middle the lightning currents and corresponding overvoltages, handled by the MO resistor, and at the bottom the potential rises of longer duration, which lead to triggering of the thyristors. The failure current is then commutated to the thyristors and the voltage is virtually zero. Fig. 4: Hybrid voltage limiter of type HVL, practical installation 4 PROTECTION CONCEPT A protection concept for railway systems, especially for DC systems, has to consider the protection of equipment (against overvoltages) and the protection of persons (against touch voltages) in the same time. Of great importance is the safety aspect in public places, as for instances train stations, rail crossings, etc.. Based on the VDV publication 525 [3] a protection concept for DC railway systems is discussed which considers the overvoltage protection of the supply lines against the return line (generally the rail) and the protection of the return line against the station earth. The protection against touch voltages is included in this concept. In [3] a protection concept for DC railway systems with U n = 600 V and 750 V is proposed, as already mentioned. This concept considers the protection of overhead lines and substations. 4.1 Protection Measures On The Overhead Lines It is recommended to install gapless arresters for outdoor use at each service entrance, at the end of feeding sections, and at the coupling point as well as at points of power demand (e.g. for point heaters). For track sections with frequent lightning strokes, for instance at bridges or free overland routes additional arresters are

6 advisable. These arresters are called A1- arresters and should fulfil the electrical requirements as given in chapter Figure 5 shows the principle arrangement. Power demand isolated rails (open ballast). The remaining potential on the pole may lead to touch voltages of unacceptable value. The remaining of the failure voltage can be avoided with the installation of a second arrester. It is proposed to install a type A2-arrester as used in the substations, between the earthing terminal and the rail. A hybrid voltage limiter (see chapter 3) could be used alternatively to the A2-arrester, as it is shown in Figure 7. Feeder lines Fig. 5: Installation of A1-arresters along the track with reference to VDV Recommendation 525 [3]. b The arresters should be installed at the level of the overhead line and connected in the shortest possible way with insulated conductors. In case the rails are isolated against earth in open ballast (to avoid stray currents) it is recommended to connect the A1-arrester to a separate earth connection with a resistance less or equal than 10 Ω. In case the rails are in closed ballast not isolated against the earth, the A1-arrester is to be connected via an insulated connector directly to the rail. Figure 6 shows the two possibilities. a c l vom Unterwerk Fig. 6: Connection of the A1-arrester to the separate FFF earth termination (left), and to the rail (right). a: insulated cable to earth termination, b: insulated cable to rail, c: feeder line from substation. b c Fig. 7: Connection of an A2-arrester, or alternatively a hybrid voltage limiter, between the earth terminal and the rail in case of isolated rails. b: insulated cable. It has to be pointed out, that the installation of a hybrid voltage limiter is the better solution in all respects. Due to the limited protection distance arresters are protecting only a distance of some meters. This means that the arresters generally have to be as close as possible to the equipment they have to protect. The connections should be as straight and short as possible. Due to the length of the earth connection a remarkable inductive voltage drop will occur along the earth connection, which has to be added to the residual voltage of the arrester. The additional voltage drop can be calculated with the equation u(t) = L di/dt. For a straight connection L can be roughly estimated with 1 µh/m. In the very rare cases of an overload of the A1- arrester a current of some 10 A would flow against earth, which would not be detected as a failure current by the protection relays in case of 4.2 Protection Measures For Substations Arresters installed along the track can protect only the equipment in the vicinity, and not electronic or other equipment in the substations.

7 Feeder lines Speiseleitungen vehicles and directly connected to the pantograph. The arresters have to fulfil the same requirements as the A1-arresters on the poles of the overhead lines. Special mechanical requirements as shock and vibration resistance have to be fulfilled in addition. Safety aspects, as explosion resistant design and the use of inflammable materials have to be considered. Figure 9 shows a practical installation. L1 L2 L3 A1 A1 Return line Rückleiter A2 A2 PB PAS R E R E;UW Fig. 8: Protection of a DC substation with A1- and A2-arresters. PB: potential bonding bar, R E : earthing resistance. For the protection of the DC-substations it is proposed to install A1-arresters directly at the breakers in the substation between the feeder line and the return line (rail). Additional an A2- arrester should be installed between the return line (rail) and the equipotential bonding bar. The A2-arrester reduces overvoltages travelling along the rail, originated by lightning, and protects against potential rise of the rail against the earth of the building. The use of A1- and A2- arresters in the substations is nowadays essential, because electronics are more and more used. Nowadays A1- and A2-arresters are on the market, which are adapted to the special requirements of DC railway systems. Figure 8 shows the principle of the substation protection. Alternative to the A2-arresters hybrid voltage limiters can be installed as well. This should be done in general, if besides the overvoltage protection, personal protection against touch voltages is required. 4.3 Protection Of Traction Vehicles It is state of the art to protect the cable bushings and the equipment downstream with arresters of type A1, installed on the roof of the traction Fig. 9: A1-arrester installed on the roof of a traction vehicle at the base of the pantograph. 5 CONCLUSION Modern MO surge arresters with silicon housing have been adapted to the special requirements in AC and DC railway systems. The installation of AC and DC MO surge arresters in substations, overhead lines and on locomotives is state of the art and worldwide practice. Coordination concepts and newly developed hybrid voltage limiters allow new protection concepts. 6 REFERENCES [1] Cigré Technical Brochure 287: Protection of MV and LV networks against lightning Part 1: Common Topics. Cigré JWG C4.4.02, 2005 [2] EN :1997 Railway applications Fixed installations Part 1: Protective provisions relating to electrical safety and earthing. [3] VDV Recommendation /06: Protection of DC Traction Power Supply Systems in case of a Lightning Strike. Association of German Transport Undertakings (VDV), Köln.

8

Transformers connected via a cable Overvoltage protection

Transformers connected via a cable Overvoltage protection A P P L I C AT I O N N OT E 2. 1 Transformers connected via a cable Overvoltage protection The APPLICATION NOTES (AN) are intended to be used in conjunction with the APPLICATION GUIDELINES Overvoltage

More information

OVERVOLTAGE PROTECTION. Dimensioning, testing and application of metal oxide surge arresters in low-voltage power distribution systems

OVERVOLTAGE PROTECTION. Dimensioning, testing and application of metal oxide surge arresters in low-voltage power distribution systems PPLICATION GUIDELINES OVERVOLTAGE PROTECTION Dimensioning, testing and application of metal oxide surge arresters in low-voltage power distribution systems Foreword Up until 1998 no international standards

More information

TECHNICAL NOTE 2.0. Overvoltages origin and magnitudes Overvoltage protection

TECHNICAL NOTE 2.0. Overvoltages origin and magnitudes Overvoltage protection ECHNICAL NOE 2.0 Overvoltages origin and magnitudes Overvoltage protection he ECHNICAL NOES (N) are intended to be used in conjunction with the APPLICAION GIDELINES Overvoltage protection Metaloxide surge

More information

ABSTRACTS of SESSION 6

ABSTRACTS of SESSION 6 ABSTRACTS of SESSION 6 Paper n 1 Lightning protection of overhead 35 kv lines by antenna-module long flashover arresters Abstract: A long-flashover arrester (LFA) of a new antenna-module type is suggested

More information

High voltage engineering

High voltage engineering High voltage engineering Overvoltages power frequency switching surges lightning surges Overvoltage protection earth wires spark gaps surge arresters Insulation coordination Overvoltages power frequency

More information

Coordination of surge arresters in DC 3 kv railway traction system field tests

Coordination of surge arresters in DC 3 kv railway traction system field tests Coordination of surge arresters in DC 3 kv railway traction system field tests Miroslaw Zielenkiewicz Tomasz Maksimowicz Center of Protection against Overvoltages and Electromagnetic Interferences RST

More information

Lightning performance of a HV/MV substation

Lightning performance of a HV/MV substation Lightning performance of a HV/MV substation MAHMUD TAINBA, LAMBOS EKONOMOU Department of Electrical and Electronic Engineering City University London Northampton Square, London EC1V HB United Kingdom emails:

More information

7P Series - Surge Protection Device (SPD) Features 7P P P

7P Series - Surge Protection Device (SPD) Features 7P P P Features 7P.09.1.255.0100 7P.01.8.260.1025 7P.02.8.260.1025 SPD Type 1+2 Surge arrester range - single phase system / three phase system Surge arresters suitable in low-voltage applications in order to

More information

2007 DEHN + SÖHNE / protected by ISO EXFS / 5392

2007 DEHN + SÖHNE / protected by ISO EXFS / 5392 2007 DEHN + SÖHNE / protected by ISO 16016 EXFS 100 11.12.07 / 5392 Ex Isolating Spark Gaps EXFS 100 (923 100) and EXFS 100 KU (923 101) 2007 DEHN + SÖHNE / protected by ISO 16016 Ex isolating spark gap

More information

LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION

LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION Andreas SUMPER sumper@citcea.upc.es Antoni SUDRIÀ sudria@citcea.upc.es Samuel GALCERAN galceran@citcea.upc.es Joan RULL rull@citcea.upc.es

More information

Energy Division. Bowthorpe LV/MV Surge Arresters

Energy Division. Bowthorpe LV/MV Surge Arresters Energy Division Bowthorpe LV/MV Surge Arresters Bowthorpe EMP LV/MV surge arresters OCP, Open Cage Polymeric series Bowthorpe pioneered the development of polymeric housed surge arresters in the early

More information

Insulation Co-ordination For HVDC Station

Insulation Co-ordination For HVDC Station Insulation Co-ordination For HVDC Station Insulation Co-ordination Definitions As per IEC 60071 Insulation Coordination is defined as selection of dielectric strength of equipment in relation to the operating

More information

A Case Study on Selection and Application of Lightning Arrester and Designing its Suitable Grounding Grid

A Case Study on Selection and Application of Lightning Arrester and Designing its Suitable Grounding Grid A Case Study on Selection and Application of Lightning Arrester and Designing its Suitable Grounding Grid 1 Arpan K. Rathod, 2 Chaitanya H. Madhekar Students Electrical Engineering, VJTI, Mumbai, India

More information

Lightning transient analysis in wind turbine blades

Lightning transient analysis in wind turbine blades Downloaded from orbit.dtu.dk on: Aug 15, 2018 Lightning transient analysis in wind turbine blades Candela Garolera, Anna; Holbøll, Joachim; Madsen, Søren Find Published in: Proceedings of International

More information

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS TRANSFORMER IN GRID When surge arres t ers are installed close to a power transformer, they provide protection against lightning overvoltage ABSTRACT The aim of this research article is to determine the

More information

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY 9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor

More information

Utility System Lightning Protection

Utility System Lightning Protection Utility System Lightning Protection Many power quality problems stem from lightning. Not only can the high-voltage impulses damage load equipment, but the temporary fault that follows a lightning strike

More information

Overvoltage Protection of Light Railway Transportation Systems

Overvoltage Protection of Light Railway Transportation Systems Overvoltage Protection of Light Railway Transportation Systems F. Delfino, R. Procopio, Student Member, IEEE, and M. Rossi, Student Member, IEEE Abstract In this paper the behavior of the power supply

More information

APPLICATION GUIDELINES. Overvoltage protection Metal-oxide surge arresters in medium-voltage systems

APPLICATION GUIDELINES. Overvoltage protection Metal-oxide surge arresters in medium-voltage systems APPLICATION GUIDELINES Overvoltage protection Metal-oxide surge arresters in medium-voltage systems First published November 1994 2nd revised edition: September 1995 3rd revised edition: May 1999 4th revised

More information

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS 29 th International Conference on Lightning Protection 23 rd 26 th June 2008 Uppsala, Sweden PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS Ivo Uglešić Viktor Milardić Božidar

More information

Power Quality and Reliablity Centre

Power Quality and Reliablity Centre Technical Note No. 8 April 2005 Power Quality and Reliablity Centre TRANSIENT OVERVOLTAGES ON THE ELECTRICITY SUPPLY NETWORK CLASSIFICATION, CAUSES AND PROPAGATION This Technical Note presents an overview

More information

Selection of MO surge arresters Overvoltage protection

Selection of MO surge arresters Overvoltage protection A P P L I C AT I O N N OT E 1. 1 Selection of MO surge arresters Overvoltage protection The APPLICATION NOTES (AN) are intended to be used in conjunction with the APPLICATION GUIDELINES Overvoltage protection

More information

CHOICE OF MV FEEDER BIL TO MAXIMIZE QOS AND MINIMIZE EQUIPMENT FAILURE

CHOICE OF MV FEEDER BIL TO MAXIMIZE QOS AND MINIMIZE EQUIPMENT FAILURE CHOICE OF MV FEEDER BIL TO MAXIMIZE QOS AND MINIMIZE EQUIPMENT FAILURE Willem DIRKSE VAN SCHALKWYK ESKOM - South Africa vschalwj@eskom.co.za ABSTRACT A high BIL (300 kv) on a MV feeder ensures that no

More information

HIGH VOLTAGE Insulation Coordination

HIGH VOLTAGE Insulation Coordination HIGH VOLTAGE Insulation Coordination Assistant Professor Suna BOLAT KRÖGER Eastern Mediterranean University Department of Electric & Electronic Engineering Insulation coordination The term Insulation Co-ordination

More information

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT Claus NEUMANN Darmstadt University of Technology Germany claus.neumann@amprion.net Klaus WINTER Swedish Neutral

More information

Lightning Protection of Distribution Substations by Using Metal Oxide Gapless Surge Arresters Connected in Parallel

Lightning Protection of Distribution Substations by Using Metal Oxide Gapless Surge Arresters Connected in Parallel International Journal of Power and Energy Research, Vol. 1, No. 1, April 2017 https://dx.doi.org/10.22606/ijper.2017.11001 1 Lightning Protection of Distribution Substations by Using Metal Oxide Gapless

More information

Computer Based Model for Design Selection of Lightning Arrester for 132/33kV Substation

Computer Based Model for Design Selection of Lightning Arrester for 132/33kV Substation IOSR Journal of Engineering (IOSRJEN) ISSN (e): 2250-3021, ISSN (p): 2278-8719 Vol. 04, Issue 05 (May. 2014), V2 PP 32-36 www.iosrjen.org Computer Based Model for Design Selection of Lightning Arrester

More information

Modeling insulation in high-voltage substations

Modeling insulation in high-voltage substations 38 ABB REVIEW DESIGNED FOR SAFETY DESIGNED FOR SAFETY Modeling insulation in high-voltage substations The goal of insulation coordination is to determine the dielectric strength of transformers and other

More information

Earthing of Electrical Devices and Safety

Earthing of Electrical Devices and Safety Earthing of Electrical Devices and Safety JOŽE PIHLER Faculty of Electrical Engineering and Computer Sciences University of Maribor Smetanova 17, 2000 Maribor SLOVENIA joze.pihler@um.si Abstract: - This

More information

X International Symposium on Lightning Protection

X International Symposium on Lightning Protection X International Symposium on Lightning Protection 9 th -13 th November, 2009 Curitiba, Brazil LIGHTNING SURGES TRANSFERRED TO THE SECONDARY OF DISTRIBUTION TRANSFORMERS DUE TO DIRECT STRIKES ON MV LINES,

More information

Tab 8 Surge Arresters

Tab 8 Surge Arresters s en em Tab 8 Surge Arresters Si Distribution System Engineering Course Unit 10 2017 Industry Inc., All Rights Reserved Surge Arresters The main protective devices against system transient overvoltages.

More information

6. Internal lightning protection

6. Internal lightning protection 6. Internal lightning protection 6.1 Equipotential bonding for metal installations Equipotential bonding according to IEC 60364-4- 41 and IEC 60364-5-54 Equipotential bonding is required for all newly

More information

2 Grounding of power supply system neutral

2 Grounding of power supply system neutral 2 Grounding of power supply system neutral 2.1 Introduction As we had seen in the previous chapter, grounding of supply system neutral fulfills two important functions. 1. It provides a reference for the

More information

Generation of Sub-nanosecond Pulses

Generation of Sub-nanosecond Pulses Chapter - 6 Generation of Sub-nanosecond Pulses 6.1 Introduction principle of peaking circuit In certain applications like high power microwaves (HPM), pulsed laser drivers, etc., very fast rise times

More information

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP IJSTE - International Journal of Science Technology & Engineering Volume 3 Issue 2 August 216 ISSN (online): 2349-784X Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

More information

Hazard of Induced Overvoltage to Power Distribution Lines Jiang Jun, Zhao Rui, Chen Jingyang, Tian Hua, Han Lin

Hazard of Induced Overvoltage to Power Distribution Lines Jiang Jun, Zhao Rui, Chen Jingyang, Tian Hua, Han Lin 4th International Conference on Machinery, Materials and Computing Technology (ICMMCT 2016) Hazard of Induced Overvoltage to Power Distribution Lines Jiang Jun, Zhao Rui, Chen Jingyang, Tian Hua, Han Lin

More information

IMP/007/011 - Code of Practice for the Application of Lightning Protection

IMP/007/011 - Code of Practice for the Application of Lightning Protection Version 1.1 of Issue Aug 2006 Page 1 of 11 IMP/007/011 - Code of Practice for the Application of Lightning Protection 1.0 Purpose The purpose of this document is to ensure the company achieves its requirements

More information

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS M. Kondalu, Dr. P.S. Subramanyam Electrical & Electronics Engineering, JNT University. Hyderabad. Joginpally B.R. Engineering

More information

Our experience. Our products

Our experience. Our products Our experience With 20 years know-how in the field of Medium Voltage network protection, DERVASIL designs and manufactures lightning arresters with zinc oxide varistors and synthetic housings. Our products

More information

Lightning overvoltage and protection of power substations

Lightning overvoltage and protection of power substations Lightning overvoltage and protection of power substations Mahmud Trainba 1, Christos A. Christodoulou 2, Vasiliki Vita 1,2, Lambros Ekonomou 1,2 1 Department of Electrical and Electronic Engineering, City,

More information

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E.

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E. Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E. HP Critical Facility Services delivered by EYP MCF What is VOLTAGE? Difference of Electric Potential

More information

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers Voltage (kv) Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers Li-Ming Zhou, Senior Member, IEEE and Steven Boggs, Fellow, IEEE Abstract: The high frequency attenuation

More information

PRACTICAL GUIDE. Low-voltage power systems Protection against overvoltages

PRACTICAL GUIDE. Low-voltage power systems Protection against overvoltages PRACTICAL GUIDE Low-voltage power systems Protection against overvoltages Introduction Overvoltage Since the 1960s, the purely technical term EMC (electromagnetic compatibility) has become a term comprising

More information

Simplified Approach to Calculate the Back Flashover Voltage of Shielded H.V. Transmission Line Towers

Simplified Approach to Calculate the Back Flashover Voltage of Shielded H.V. Transmission Line Towers Proceedings of the 14 th International Middle East Power Systems Conference (MEPCON 1), Cairo University, Egypt, December 19-1, 1, Paper ID 1. Simplified Approach to Calculate the Back Flashover Voltage

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Current transducer ITC 2000-S/SP2 N = 2000 A For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Features Bipolar and insulated

More information

Insulation Test System

Insulation Test System Component Tests Insulation Test System Brief Overview of Phenomena............... 2 Applicable Standards................... 3 Test System Overview.................. 3 Generator Specifications.................

More information

Technical Requirements for Resistibility of Telecommunications Equipment to. Overvoltage and Overcurrent

Technical Requirements for Resistibility of Telecommunications Equipment to. Overvoltage and Overcurrent Technical Requirements for Resistibility of Telecommunications Equipment to Overvoltage and Overcurrent TR NO.189001 Edition 3 1st, April, 2018 Nippon Telegraph and Telephone Corporation Notice This document

More information

I -limiter The world s fastest switching device

I -limiter The world s fastest switching device I S -limiter 2 I S -limiter The world s fastest switching device Reduces substation cost Solves short-circuit problems in new substations and substation extensions Optimum solution for interconnection

More information

Analysis of lightning performance of 132KV transmission line by application of surge arresters

Analysis of lightning performance of 132KV transmission line by application of surge arresters Analysis of lightning performance of 132KV transmission line by application of surge arresters S. Mohajer yami *, A. Shayegani akmal, A.Mohseni, A.Majzoobi High Voltage Institute,Tehran University,Iran

More information

Effect of Surge Arrester on Overhead Transmission Lines as Shield against Over Voltage

Effect of Surge Arrester on Overhead Transmission Lines as Shield against Over Voltage Effect of Surge Arrester on Overhead Transmission Lines as Shield against Over Voltage Swati Agrawal Assistant Professor, MATS University, Raipur (C.G) Abstract: This paper describes the usage of surge

More information

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01 SEC DISTRIBUTION GROUNDING STANDARD SDCS-03 Part-II Rev.01 SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING Rev. 01 This specification is property of SEC

More information

APPLICATION OF LONG FLASHOVER ARRESTERS FOR IMPROVEMENT OF LIGHTNING PROTECTION AND OPERATING VOLTAGE RELIABILITY OF DISTRIBUTION LINES

APPLICATION OF LONG FLASHOVER ARRESTERS FOR IMPROVEMENT OF LIGHTNING PROTECTION AND OPERATING VOLTAGE RELIABILITY OF DISTRIBUTION LINES APPLICATION OF LONG FLASHOVER ARRESTERS FOR IMPROVEMENT OF LIGHTNING PROTECTION AND OPERATING VOLTAGE RELIABILITY OF DISTRIBUTION LINES G. V. Podporkin, V. E. Pilshikov, A. D. Sivaev Streamer Electric

More information

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 Nkosinathi Buthelezi Senior Consultant: Power Transformers and Reactors Presentation Content Standardization of Power

More information

Cable Protection against Earth Potential Rise due to Lightning on a Nearby Tall Object

Cable Protection against Earth Potential Rise due to Lightning on a Nearby Tall Object Cable Protection against Earth Potential Rise due to Lightning on a Nearby Tall Object U. S. Gudmundsdottir, C. F. Mieritz Abstract-- When a lightning discharge strikes a tall object, the lightning current

More information

I P. /dt. di p V S Applications. Standards 1) IEC : 2007; IEC : ) IEC : 2016; IEC : 2017

I P. /dt. di p V S Applications. Standards 1) IEC : 2007; IEC : ) IEC : 2016; IEC : 2017 Ref: ART-B22-D70, ART-B22-D125, ART-B22-D175, ART-B22-D300 Flexible clip-around Rogowski coil for the electronic measurement of AC current with galvanic separation between the primary circuit (power) and

More information

VBS TBS KTS BSS LFS UFS

VBS TBS KTS BSS LFS UFS VBS TBS KTS BSS LFS UFS TBS. Surge protection systems Order information and technical data Protection and isolating spark gaps Protection spark gap or isolating spark gap? Isolating spark gaps Protection

More information

The Role of the Grounding System in Electronics Lightning Protection

The Role of the Grounding System in Electronics Lightning Protection ILPS 2016 - International Lightning Protection Symposium April 21-22, 2016 Porto Portugal The Role of the Grounding System in Electronics Lightning Protection Roberto Menna Barreto SEFTIM Brazil Rio de

More information

ABSTRACT 1 INTRODUCTION

ABSTRACT 1 INTRODUCTION ELECTROMAGNETIC ANALYSIS OF WIND TURBINE GROUNDING SYSTEMS Maria Lorentzou*, Ian Cotton**, Nikos Hatziargyriou*, Nick Jenkins** * National Technical University of Athens, 42 Patission Street, 1682 Athens,

More information

Parameters Affecting the Back Flashover across the Overhead Transmission Line Insulator Caused by Lightning

Parameters Affecting the Back Flashover across the Overhead Transmission Line Insulator Caused by Lightning Proceedings of the 14 th International Middle East Power Systems Conference (MEPCON 10), Cairo University, Egypt, December 19-21, 2010, Paper ID 111. Parameters Affecting the Back Flashover across the

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Current Transducer LF 1010-S/SPA5 I P N = 1000 A For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Features Bipolar and

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Current Transducer ITL 4000-S I PN = 4000 A For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. I > 0 P Features Closed

More information

Maximum Lightning Overvoltage along a Cable due to Shielding Failure

Maximum Lightning Overvoltage along a Cable due to Shielding Failure Maximum Lightning Overvoltage along a Cable due to Shielding Failure Thor Henriksen Abstract--This paper analyzes the maximum lightning overvoltage due to shielding failure along a cable inserted in an

More information

Technical Requirements for Resistibility of Telecommunications Equipment to. Overvoltage and Overcurrent

Technical Requirements for Resistibility of Telecommunications Equipment to. Overvoltage and Overcurrent Technical Requirements for Resistibility of Telecommunications Equipment to Overvoltage and Overcurrent TR NO.189001 Edition 2.1 1st, April, 2015 Nippon Telegraph and Telephone Corporation Notice This

More information

Precautions to be considered for use of surge arresters tested according to Class 1 of IEC

Precautions to be considered for use of surge arresters tested according to Class 1 of IEC DATA SHEET No. 1 December 2000 Issued by the French Lightning Protection Association Precautions to be considered for use of surge arresters tested according to Class 1 of IEC 61643-1 Foreword: The protection

More information

Prepared by Mick Maytum

Prepared by Mick Maytum IEC Technical Committee 109: Standards on insulation co-ordination for low-voltage equipment Warning Prepared by Mick Maytum mjmaytum@gmail.com The document content is of a general nature only and is not

More information

Electricity Supply to Africa and Developing Economies. Challenges and opportunities. Technology solutions and innovations for developing economies

Electricity Supply to Africa and Developing Economies. Challenges and opportunities. Technology solutions and innovations for developing economies Electricity Supply to Africa and Developing Economies. Challenges and opportunities. Technology solutions and innovations for developing economies Magnetic induced currents and voltages on earthed lines

More information

TECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES

TECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION October 2014 TECHNICAL DESCRIPTION 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES I. SCOPE This

More information

Secondary Arresters. Figure 1. Type L secondary surge arrester rated 175 Vac, 125 Vdc.

Secondary Arresters. Figure 1. Type L secondary surge arrester rated 175 Vac, 125 Vdc. Surge Arresters Secondary Arresters and Protective Gaps Electrical Apparatus 235-10 GENERAL INFORMATION The necessity of providing surge arrester protection on low-voltage circuits is fundamentally the

More information

Chapter 1. Overvoltage Surges and their Effects

Chapter 1. Overvoltage Surges and their Effects Chapter 1 Overvoltage Surges and their Effects 1.1 Introduction Power equipment are often exposed to short duration impulse voltages of high amplitude produced by lightning or switching transients. These

More information

WIRELESS INSULATOR POLLUTION MONITORING SYSTEM

WIRELESS INSULATOR POLLUTION MONITORING SYSTEM SYSTEM OVERVIEW Pollution monitoring of high voltage insulators in electrical power transmission and distribution systems, switchyards and substations is essential in order to minimise the risk of power

More information

PANIMALAR ENGINEERING COLLEGE Department of Electrical and Electronics Engineering

PANIMALAR ENGINEERING COLLEGE Department of Electrical and Electronics Engineering PANIMALAR ENGINEERING COLLEGE Department of Electrical and Electronics Engineering 1. Write some applications of high voltage? High Voltage Engineering 2 mark Question with answers Unit I Overvoltages

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary circuit and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary circuit and the secondary circuit. Current Transducer CTSR 0.6-TP/SP2 I PRN = 600 ma For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary circuit and the secondary circuit. Features

More information

SIOV metal oxide varistors

SIOV metal oxide varistors SIOV metal oxide varistors Application notes Date: January 2018 EPCOS AG 2018. Reproduction, publication and dissemination of this publication, enclosures hereto and the information contained therein without

More information

Investigation on the Performance of Different Lightning Protection System Designs

Investigation on the Performance of Different Lightning Protection System Designs IX- Investigation on the Performance of Different Lightning Protection System Designs Nicholaos Kokkinos, ELEMKO SA, Ian Cotton, University of Manchester Abstract-- In this paper different lightning protection

More information

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages Session Four: ractical Insulation Co-ordination Session Four: ractical Insulation Co-ordination for Lightning Induced Overvoltages Jason Mayer Technical Director, Energy Services, Aurecon Introduction

More information

EMC Philosophy applied to Design the Grounding Systems for Gas Insulation Switchgear (GIS) Indoor Substation

EMC Philosophy applied to Design the Grounding Systems for Gas Insulation Switchgear (GIS) Indoor Substation EMC Philosophy applied to Design the Grounding Systems for Gas Insulation Switchgear (GIS) Indoor Substation Marcos Telló Department of Electrical Engineering Pontifical Catholic University of Rio Grande

More information

I P. /dt. di p V S+ Applications. Standards. 1) IEC ed1.0: 2007; IEC : ed1.0: 2012

I P. /dt. di p V S+ Applications. Standards. 1) IEC ed1.0: 2007; IEC : ed1.0: 2012 Ref: ART-B22-D70, ART-B22-D125, ART-B22-D175 Flexible clip-around Rogowski coil for the electronic measurement of AC current with galvanic separation between the primary circuit (power) and the secondary

More information

Lightning Overvoltages on Low Voltage Circuit Caused by Ground Potential Rise

Lightning Overvoltages on Low Voltage Circuit Caused by Ground Potential Rise Lightning Overvoltages on Low Voltage Circuit Caused by Ground Potential Rise S. Sekioka, K. Aiba, S. Okabe Abstract-- The lightning overvoltages incoming from an overhead line such as a power distribution

More information

The relationship between operating maintenance and lightning overvoltage in distribution networks based on PSCAD/EMTDC

The relationship between operating maintenance and lightning overvoltage in distribution networks based on PSCAD/EMTDC The relationship between operating maintenance and lightning overvoltage in distribution networks based on PSCAD/EMTDC Xiaojun Chena *, Wenjie Zhengb, Shu Huangc, Hui Chend Electric Power Research Institute

More information

Insulation Test System

Insulation Test System Component Tests Insulation Test System Brief Overview of Phenomena............... 2 Applicable Standards................... 3 Test System Overview.................. 3 Generator Specifications.................

More information

AMENDMENT NO. 1 SEPTEMBER IS (Part 1) : 2001/IEC (1991) SURGE ARRESTORS

AMENDMENT NO. 1 SEPTEMBER IS (Part 1) : 2001/IEC (1991) SURGE ARRESTORS AMENDMENT NO. 1 SEPTEMBER 2011 TO IS 15086 (Part 1) : 2001/IEC 60099-1 (1991) SURGE ARRESTORS PART 1 NON-LINEAR RESISTOR TYPE GAPPED SURGE ARRESTORS FOR a.c. SYSTEMS (The Amendment was originally published

More information

Power Quality. Case Study. Conrad Bottu Laborelec January 2008

Power Quality. Case Study. Conrad Bottu Laborelec January 2008 Case Study Electromagnetic compatibility (EMC) study Breakdown of low voltage electronic equipment in a 25 kv substation Conrad Bottu Laborelec January 2008 Power Quality Power Quality 1 Introduction Description

More information

Isolating Spark Gaps. Isolating spark gaps at an additional earth ring conductor. Isolating spark gaps for Ex zones

Isolating Spark Gaps. Isolating spark gaps at an additional earth ring conductor. Isolating spark gaps for Ex zones Isolating Spark Gaps Isolating spark gaps at an additional earth ring conductor Isolating spark gaps for Ex zones 187 Protective Spark Gaps For use at roof supports for overhead lines For indirect connection

More information

SPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS

SPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS -1- INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION June 2013 SPECIFICATION No 150 kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS I. SCOPE This specification

More information

In order to minimise distribution (11 and 22 kv) feeder breaker

In order to minimise distribution (11 and 22 kv) feeder breaker Lightning protection for equipment on MV feeders By WJD van Schalkwyk and M du Preez, Eskom This article presents the influence of lightning on MV feeders supplying small power users (400/230 V) with focus

More information

Distribution Transformer Random Transient Suppression using Diode Bridge T-type LC Reactor

Distribution Transformer Random Transient Suppression using Diode Bridge T-type LC Reactor Distribution Transformer Random Transient Suppression using Diode Bridge T-type LC Reactor Leong Bee Keoh 1, Mohd Wazir Mustafa 1, Sazali P. Abdul Karim 2, 1 University of Technology Malaysia, Power Department,

More information

A Study on Lightning Overvoltage Characteristics of Grounding Systems in Underground Distribution Power Cables

A Study on Lightning Overvoltage Characteristics of Grounding Systems in Underground Distribution Power Cables J Electr Eng Technol Vol. 9, No. 2: 628-634, 2014 http://dx.doi.org/10.5370/jeet.2014.9.2.628 ISSN(Print) 1975-0102 ISSN(Online) 2093-7423 A Study on Lightning Overvoltage Characteristics of Grounding

More information

Fixed Series Compensation

Fixed Series Compensation Fixed Series Compensation High-reliable turnkey services for fixed series compensation NR Electric Corporation The Fixed Series Compensation (FSC) solution is composed of NR's PCS-9570 FSC control and

More information

Simulation of Lightning Transients on 110 kv overhead-cable transmission line using ATP-EMTP

Simulation of Lightning Transients on 110 kv overhead-cable transmission line using ATP-EMTP Simulation of Lightning Transients on 110 kv overhead-cable transmission line using ATP-EMTP Kresimir Fekete 1, Srete Nikolovski 2, Goran Knezević 3, Marinko Stojkov 4, Zoran Kovač 5 # Power System Department,

More information

Current Transducer CTSR 1-P = 1A

Current Transducer CTSR 1-P = 1A Current Transducer CTSR 1-P I PRN = 1A For the electronic measurement of current: DC, AC, pulsed..., with galvanic isolation between the primary (high power) and the secondary circuit (electronic circuit).

More information

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models International Journal of Electrical & Computer Sciences IJECS-IJENS Vol:15 No:03 39 Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models Shen-Wen Hsiao, Shen-Jen

More information

PMT/UMT(275) Power Gap Description and Use Application Note

PMT/UMT(275) Power Gap Description and Use Application Note Application Note Introduction The PMT(275)/UMT(275) Series has been designed for use in applications where a rugged miniature sized surge arrester is needed capable of high speed of response. This Power

More information

(2) New Standard IEEE P (3) Core : (4) Windings :

(2) New Standard IEEE P (3) Core : (4) Windings : (d) Electrical characteristics (such as short-circuit withstand, commutating reactance, more number of windings, etc); (e) Longer life expectancy; (f) Energy efficiency; (g) more demanding environment.

More information

TECHNICAL SPECIFICATION

TECHNICAL SPECIFICATION TECHNICAL SPECIFICATION IEC TS 60071-5 First edition 2002-06 Insulation co-ordination Part 5: Procedures for high-voltage direct current (HVDC) converter stations Coordination de l isolement - Partie 5:

More information

Modeling of overhead transmission lines with line surge arresters for lightning overvoltages. Poland

Modeling of overhead transmission lines with line surge arresters for lightning overvoltages. Poland Application of Line Surge Arresters in Power Distribution and Transmission Systems COLLOQUIUM Cavtat 2008 Modeling of overhead transmission lines with line surge arresters for lightning overvoltages M.

More information

RESULTS OF EXPERIMENTAL HIGH CURRENT IMPULSE 4/10 s OF METAL OXIDE VARISTORS ZINC IN THE HIGH VOLTAGE 220KV SURGE ARRESTER

RESULTS OF EXPERIMENTAL HIGH CURRENT IMPULSE 4/10 s OF METAL OXIDE VARISTORS ZINC IN THE HIGH VOLTAGE 220KV SURGE ARRESTER RESULTS OF EXPERIMENTAL HIGH CURRENT IMPULSE 4/10 s OF METAL OXIDE VARISTORS ZINC IN THE HIGH VOLTAGE 220KV SURGE ARRESTER PhD. Nguyen Huu Kien National Key Laboratory for High Voltage Techniques - Institute

More information

Electric Stresses on Surge Arrester Insulation under Standard and

Electric Stresses on Surge Arrester Insulation under Standard and Chapter 5 Electric Stresses on Surge Arrester Insulation under Standard and Non-standard Impulse Voltages 5.1 Introduction Metal oxide surge arresters are used to protect medium and high voltage systems

More information

V P N. Voltage transducer DVM 2000-B = 2000 V

V P N. Voltage transducer DVM 2000-B = 2000 V Voltage transducer DVM 2-B V P N = 2 V For the electronic measurement of voltage: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Features Bipolar and insulated

More information

V P N. Voltage transducer DVM 4200 = 4200 V

V P N. Voltage transducer DVM 4200 = 4200 V Voltage transducer DVM 42 N = 42 V For the electronic measurement of voltage: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Features Bipolar and insulated measurement

More information

Insulation Coordination Fundamentals Where Arrester and Insulator Characteristics Meet

Insulation Coordination Fundamentals Where Arrester and Insulator Characteristics Meet ArresterWorks Insulation Coordination Fundamentals Where Arrester and Insulator Characteristics Meet 6/23/2012 Jonathan Woodworth Transient overvoltages are a fact of life on power systems. Arresters can

More information