Maintenance Hole Structures Technical Addendum Background

Size: px
Start display at page:

Download "Maintenance Hole Structures Technical Addendum Background"

Transcription

1 Maintenance Hole Structures Technical Addendum Technical Addendum Number: SEWL TA SEW 01 Revision B MRWA edition version 1.0 of WSAA Sewerage Code WSA Background Construction validation activities carried out in 2011 identified a number of constructed shallow cast in situ Maintenance Hole structures that did not meet the Design and Construction requirements outlined in the MRWA edition of the WSAA Sewerage Code WSA These installations presented occupational health and safety hazards due to the incorrect design and installation of shaft, cone and neck increments. Technical Addendum SEWL TA SEW 01 Revision A was published to address this issue and other general Maintenance Hole matters to clarify South East Water s requirements. Following a recent review of the existing WITS Standard drawings and Sewer Code requirements, this updated technical addendum clarifies South East Water s requirements for the design and construction of maintenance holes.

2 Changes to the Sewerage Code Requirements 1. South East Water has re introduced a set of drawings, including some former Water Industry Technical Standard (WITS) Drawings. These drawings take precedent over the equivalent Standard Drawings provided in the MRWA edition of the WSAA Sewerage Code. The following table summarises the drawings that have been re introduced. Drawing Revision Name Comments and Purpose SCH.021 B Maintenance Hole Landings, Stepirons & Landing Planks SCH.031 B Cast In Situ Maintenance Holes Flat Top SCH.032 B Cast In Situ Maintenance Holes Conical Top SCH.033 B Cast In Situ Maintenance Holes Truncated Top SCH.034 B Shallow Maintenance Holes SEW B Water Seal Arrangements Twin Maintenance Hole System The Sewerage Code does not currently include a drawing with details for landings and portable standing planks. This drawing also provides details for step irons in addition to those shown on the current standard drawing SEW 1307 V. These drawings replace SEW 1301 V. The Designer is required to specify the type of each maintenance hole on the design drawings. Drawing SCH.032 includes a table of maintenance hole types and depth ranges, which is to be used as a guide for selecting appropriate maintenance hole types. Details for construction joints between the base and shaft have also been included. The Sewerage Code does not currently include drawings with details for shallow maintenance holes. Use of these maintenance holes is subject to prior South East Water approval. Revises SEW 1411 to include additional details for twin maintenance hole water seals (also referred to as gas check maintenance holes ). WITS Standard Drawings SCH.021 Rev B, SCH.031 Rev B, SCH.032 Rev B, SCH 033 Rev B, SCH.034 Rev B and SEW 1411 SE WATER REV2.1 B have been attached to the end of this Technical Addendum. In accordance with these drawing changes, the following changes are being applied to the MRWA edition of the WSAA Sewerage Code WSA : Clause 6.1, item (a) will be replaced with Maintenance Holes (MHs), which are applicable to all sewer sizes and allow personnel and equipment access to the sewer system. (Refer to Standard Drawings SEW 1300 V, SEW 1302 V, SEW 1303 V, SEW 1304 V, SEW 1305 V, SEW 1306 V, SEW 1307 V, SEW 1308 V, SEW 1309 V, SEW 1313 V, SCH.021 Rev B, SCH.031 Rev B, SCH.032 Rev B, SCH 033 Rev B and SCH.034 Rev B. SEWL TA SEW 01 Rev B Page 2 of 3 Issued 15 June 2012

3 Clause 6.6.2, final paragraph will be replaced with Special construction details are shown on Standard Drawings SEW 1309 and SEW 1313 V. WITS Standard Drawing SCH.031 Rev B can be used in conjunction with Standard Drawing SEW 1309 V for larger diameter MH installations. Clause 7.3.2, final sentence is replaced with Default detailed design requirements for water seals in sewers and gas check MHs are shown in Standard Drawing SEW 1411 SE WATER REV2.1 B and SEW 1409 V. Clause includes new items (j) and (k): (j) The Designer must specify each Maintenance Hole type (eg conical, truncated, flat top, precast), and whether they are cast in situ (CI) or precast (P), on the Maintenance Hole Schedule (refer 9.2.6). (k) A base layout must be shown for MHs where there are three or more incoming sewers, two or more drops, angles of deflection greater than 90 degrees, unusual configurations of incoming sewers, or sewers are offset from the centre of the MH. 2. Other Maintenance Hole Technical Addendum changes being applied to the MRWA edition of the WSAA Sewerage Code WSA are as follows: a) Protective coatings: Clause 4.7.2, last sentence is to be replaced with South East Water requires the application of an approved lining or protective coating on all new Maintenance Hole (MH) structures on sewers DN450, Gas check MHs, Pressure sewer/rising main discharge MHs, Sewage Pumping station wet well/ valve pit chambers, and other specific structures as directed. b) Connection of 10 or more units: Clause 5.5.2, last sentence will be replaced with Where 10 or more units/apartments are to be connected to the sewer system, this must be done via a Maintenance Hole. c) Cast in situ cover slabs: Clause (a) is to be replaced with Poured in situ MH comprising a poured base, channels and walls with a poured or precast concrete cover slab; d) Structural calculations for deep MHs: Clause includes a new paragraph: For Maintenance Holes >6.0metres in depth, structural calculations and a design layout must be prepared and submitted to South East Water for auditing purposes. e) Specification of step irons and ladders: Clause 6.6.8, third sentence and dot points are to be replaced with Stainless steel/plastic encapsulated step irons or stainless steel/grp ladders must be specified for all Maintenance Holes located on sewers DN450, within or downstream of industrial developments, and the downstream chamber of a Gas check MH. f) Retrofitted landings: Clause includes a new paragraph: Where it is necessary to retrofit a landing in an existing MH, the designer is required to obtain Water Agency approval, submit structural calculations, and show full design details and construction methodology on the design drawings. Retrofitted concrete landings will not be permitted. Further Information This revision of the Maintenance Hole Structures Technical Addendum will take immediate effect on: All South East Water Land Development sewerage projects that have not completed lodgement of the Design Verification Form and Design drawing documentation via the SWIFT application. All South East Water Capital Works branch sewer and reticulation pipeline projects currently under detail design phase. If you have any further enquiries or suggestions regarding any of the information outlined in this Technical Addendum, please e mail Mr Colin Paxman at colin.paxman@sewl.com.au SEWL TA SEW 01 Rev B Page 3 of 3 Issued 15 June 2012

4

5

6

7

8

9

LAND DEVELOPMENT - SURVEY MANUAL 01

LAND DEVELOPMENT - SURVEY MANUAL 01 2012 Central Highlands Water All rights reserved. This publication is protected by copyright and is provided under licence. No part of this publication may be reproduced, distributed, transmitted, stored

More information

Anti-Trust Statement

Anti-Trust Statement Anti-Trust Statement http://www.concrete-pipe.org/ A joint effort of the Texas Concrete Pipe Association and the Texas Department of Transportation What brought this about? The TxDOT organization consists

More information

STANDARD AND EXAMPLE DRAWINGS

STANDARD AND EXAMPLE DRAWINGS STANDARD AND EXAMPLE DRAWINGS DRAWING ISSUE TITLE GENERAL CA01-1-1 E EXAMPLE CATCHMENT PLAN - DESIGN BASIS CA01-1-2 D EXAMPLE PRESSURE MAIN CHARACTERISTIC CURVE CA01-1-3-1 B TYPE 10, 40 AND 90 PUMPING

More information

MANHOLES PART I: GENERAL. A. Precast Concrete Manholes

MANHOLES PART I: GENERAL. A. Precast Concrete Manholes MANHOLES PART I: GENERAL A. Precast Concrete Manholes 1) Manholes shall be made of precast concrete sections of which the top section shall be eccentric or flat slab top. The bottom section shall be a

More information

Pipe Product Catalog Table of Contents

Pipe Product Catalog Table of Contents Pipe Product Catalog Table of Contents Section A: Drawing #: Page Description A1 Reinforced Concrete Pipe A3 Storm Manhole Sizing Chart (48" - 96") A3.1 Storm Manhole Sizing Chart (108" - 144") A4 48"

More information

SAUSALITO-MARIN CITY SANITARY DISTRICT MISCELLANEOUS UPGRADES PROJECT. Addendum No. 2

SAUSALITO-MARIN CITY SANITARY DISTRICT MISCELLANEOUS UPGRADES PROJECT. Addendum No. 2 SAUSALITO-MARIN CITY SANITARY DISTRICT MISCELLANEOUS UPGRADES PROJECT Addendum No. 2 The following shall modify the Contract Documents. The work shall be accomplished in accordance with such modifications.

More information

SECTION MANHOLES

SECTION MANHOLES SECTION 02601 MANHOLES PART 1 GENERAL 1.01 SCOPE OF WORK A. WORK required under this section consists of all materials, accessories, equipment, tools, and labor required to install precast concrete standard

More information

INSTALLATION INSTRUCTIONS. March 2016 FOR FURTHER QUESTIONS, PLEASE CALL

INSTALLATION INSTRUCTIONS. March 2016 FOR FURTHER QUESTIONS, PLEASE CALL March 2016 INSTALLATION INSTRUCTIONS FOR FURTHER QUESTIONS, PLEASE CALL 775 440 2025 JENSEN WATER RESOURCES 521 Dunn Circle, Sparks, NV 89431 JensenPumps.com Figure 1: This illustration shows a complete

More information

CONSULTANT ACCREDITATION SCHEME SEWER DESIGN

CONSULTANT ACCREDITATION SCHEME SEWER DESIGN CONSULTANT ACCREDITATION SCHEME SEWER DESIGN DRAWING CRITERIA AND CHECKLIST Produced by SA Water Corporation Asset Management Group June 2013 Land Developer Agreements Contact Information Details Sharyn

More information

This specification describes the minimum requirements for service water piping systems (ie: cooling water, process water, etc.), located on surface.

This specification describes the minimum requirements for service water piping systems (ie: cooling water, process water, etc.), located on surface. SPEC-3500 1/9 1.0 PURPOSE This specification describes the minimum requirements for service water piping systems (ie: cooling water, process water, etc.), located on surface. Note: This specification does

More information

CONSTRUCTION SPECIFICATION FOR MAINTENANCE HOLE, CATCH BASIN, DITCH INLET, AND VALVE CHAMBER INSTALLATION

CONSTRUCTION SPECIFICATION FOR MAINTENANCE HOLE, CATCH BASIN, DITCH INLET, AND VALVE CHAMBER INSTALLATION ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS 407 NOVEMBER 2013 CONSTRUCTION SPECIFICATION FOR MAINTENANCE HOLE, CATCH BASIN, DITCH INLET, AND VALVE CHAMBER INSTALLATION TABLE OF CONTENTS 407.01

More information

Stormwater Solutions. Jacopa Penstocks. Key Features & Benefits: How We Create Value:

Stormwater Solutions. Jacopa Penstocks. Key Features & Benefits: How We Create Value: Key Features & Benefits: Suitable for Sewerage systems Suitable for Surface water systems Suitable for the control of Watercourses How We Create Value: Can provide a level of Flow control Provides high

More information

NEWTON COUNTY WATER AND SEWERAGE AUTHORITY RESIDENTIAL, COMMERCIAL, INSTITUTIONAL AND INDUSTRIAL SUBDIVISIONS CONSTRUCTION PLANS CHECK LIST

NEWTON COUNTY WATER AND SEWERAGE AUTHORITY RESIDENTIAL, COMMERCIAL, INSTITUTIONAL AND INDUSTRIAL SUBDIVISIONS CONSTRUCTION PLANS CHECK LIST NEWTON COUNTY WATER AND SEWERAGE AUTHORITY RESIDENTIAL, COMMERCIAL, INSTITUTIONAL AND INDUSTRIAL SUBDIVISIONS CONSTRUCTION PLANS CHECK LIST Project Name Checked By Date Designer Check List marks to be

More information

REGISTRATION EXAMINATION, JUNE 2008 DRAINLAYING ANSWER SCHEDULE

REGISTRATION EXAMINATION, JUNE 2008 DRAINLAYING ANSWER SCHEDULE No. 9197 REGISTRATION EXAMINATION, JUNE 2008 DRAINLAYING ANSWER SCHEDULE Plumbers, Gasfitters and Drainlayers oard, 2008. All rights reserved. No part of this publication may be reproduced by any means

More information

PRESSURE SEWER CODE OF AUSTRALIA AGENCY REQUIREMENTS PART 1 - DESIGN

PRESSURE SEWER CODE OF AUSTRALIA AGENCY REQUIREMENTS PART 1 - DESIGN PRESSURE SEWER CODE OF AUSTRALIA AGENCY REQUIREMENTS PART 1 - DESIGN Clause Description Requirement Supporting Document 1.5 Planning and Design In addition, SA Water s requirements for the initial Pt1

More information

MAINTENANCE HOLES, CATCH BASINS AND DITCH INLETS - MTC FORM 407 INDEX

MAINTENANCE HOLES, CATCH BASINS AND DITCH INLETS - MTC FORM 407 INDEX 407-1 - MAINTENANCE HOLES, CATCH BASINS AND DITCH INLETS - MTC FORM 407 INDEX 407-1.1 GENERAL Tender Items Specifications Standard Drawings 407-1.1.1 Frame and Grate Selection 407-1.1.2 Selection of Structure

More information

ADDENDUM NO. 3 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO COM.00030

ADDENDUM NO. 3 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO COM.00030 ADDENDUM NO. 3 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO. 2018-008-COM.00030 To: Prospective Bidders of Record Date: January 8, 2019 The following changes, additions, revisions, and/or deletions

More information

HUSSEY GAY BELL SAVANNAH, GEORGIA

HUSSEY GAY BELL SAVANNAH, GEORGIA HUSSEY GAY BELL SAVANNAH, GEORGIA ------------------------------------------------------------------------------------------------------------ ADDENDUM NO. 3 TO THE CONTRACT DOCUMENTS AND TECHNICAL SPECIFICATIONS

More information

Capricorn Municipal Development Guidelines MEETING POST AMALGAMATION MINUTES

Capricorn Municipal Development Guidelines MEETING POST AMALGAMATION MINUTES Venue: Rockhampton Regional Council Gracemere Office Date and Time: Wednesday 3 rd September 2008 (Lunch will be provided) Attendees: Apologies - Chris Hegarty (), Adam Van Nunen (), ckone (FRW), Greg

More information

This specification describes the minimum requirements for piping systems for the following service:

This specification describes the minimum requirements for piping systems for the following service: SPEC-3004 1/7 1.0 APPLICATION This specification describes the minimum requirements for piping systems for the following service: Service Water Design Conditions Operating Conditions 10 PSIG @ 33 o F to

More information

SECTION PRECAST CONCRETE SECTIONAL MANHOLES

SECTION PRECAST CONCRETE SECTIONAL MANHOLES SECTION 02545 PRECAST CONCRETE SECTIONAL MANHOLES PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Precast reinforced concrete cylindrical sectional manholes, complete with openings, inserts, hardware,

More information

This specification describes the minimum requirements for piping systems for the following service:

This specification describes the minimum requirements for piping systems for the following service: 201/11/2 1/9 1.0 APPLICATION This specification describes the minimum requirements for piping systems for the following service: Underground Service Water Note: This specification does not apply to piping

More information

How to provide as constructed information and interpretation of sewer plans

How to provide as constructed information and interpretation of sewer plans How to provide as constructed information and interpretation of sewer plans Contents Contents Providing and interpreting as constructed sewer plans... 1 1 Sewer Junction Cut Ins and As Constructed... 3

More information

Engineering and Construction Services Division Construction Drawings for Sewers and Watermains. T No. Revision T No. Revision Remarks All T drawings

Engineering and Construction Services Division Construction Drawings for Sewers and Watermains. T No. Revision T No. Revision Remarks All T drawings Engineering and Construction Services Division Construction Drawings for Sewers and Watermains Revision No. 8 April All T drawings New title block for each drawing is now standardized. Revision numbers

More information

CS3 represents manufacturers of products for use in the municipal waterworks industry.

CS3 represents manufacturers of products for use in the municipal waterworks industry. Brian Drexel & Rob Grier WWW.CS3WATERWORKS.COM Established in 2000, CS3 Waterworks is a Florida Based company with offices in Orange Springs Florida and Savannah Georgia. CS3 represents manufacturers of

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCESA / NASA UFGS-33 34 13 (April 2008) -------------------------- Preparing Activity: USACE Superseding UFGS-33 34 13 (April 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS References

More information

The Manitoba Water Services Board SECTION Standard Construction Specifications September 2013 Page 1 of 8

The Manitoba Water Services Board SECTION Standard Construction Specifications September 2013 Page 1 of 8 September 2013 Page 1 of 8 Part 1 General 1.1 DESCRIPTION OF WORK.1 The work described herein shall consist of the construction of air release chambers, flushout chambers, valve chambers, meter chambers

More information

Standard Specifications

Standard Specifications Standard Specifications PART 1.00 GENERAL 1.01 DECRIPTION SECTION 02620 PRECAST REINFORCED CONCRETE SANITARY MANHOLES A. Work included: The Contractor shall furnish all labor, materials, equipment, and

More information

This specification describes the minimum requirements for piping systems for the following service:

This specification describes the minimum requirements for piping systems for the following service: SPEC-3501 1/ 1.0 APPLICATION This specification describes the minimum requirements for piping systems for the following service: Instrument Air Design Conditions 150 PSIG @ 180 F Operating Conditions 125

More information

Page 1 of 12 Second Revision No. 5-NFPA 12-2014 [ Section No. 2.3.4 ] 2.3.4 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C 700, West Conshohocken, PA 19428-2959. ASTM A53, Standard

More information

ADDENDUM NO. 1 TO THE CONTRACT DOCUMENTS AND SPECIFICATIONS DATED JULY 2017 FLORIDA GOVERNMENTAL UTILITY AUTHORITY PROJECT NO.

ADDENDUM NO. 1 TO THE CONTRACT DOCUMENTS AND SPECIFICATIONS DATED JULY 2017 FLORIDA GOVERNMENTAL UTILITY AUTHORITY PROJECT NO. ADDENDUM NO. 1 TO THE CONTRACT DOCUMENTS AND SPECIFICATIONS DATED JULY 2017 FLORIDA GOVERNMENTAL UTILITY AUTHORITY PROJECT NO. PS 061 SEVEN SPRINGS WASTEWATER TREATMENT FACILITY IMPROVEMENTS PASCO COUNTY,

More information

STS 903 WORK AS CONSTRUCTED INFORMATION

STS 903 WORK AS CONSTRUCTED INFORMATION Hunter Water Corporation A.B.N. 46 228 513 446 Standard Technical Specification for: STS 903 WORK AS CONSTRUCTED INFORMATION This standard technical specification (STS) was developed by Hunter Water Corporation

More information

CONCRETE MANHOLES.

CONCRETE MANHOLES. CONCRETE CONCRETE SHAW PIPE produces circular, precast, concrete manholes in diameters 1050mmØ through 3000mmØ. Precast, concrete manholes are most frequently used for pipeline and sewer entry and are

More information

This specification describes the minimum requirements for piping systems for the following service:

This specification describes the minimum requirements for piping systems for the following service: 201/01/13 1/ 1.0 APPLICATION This specification describes the minimum requirements for piping systems for the following service: Service Air Design Conditions Operating Conditions Blast Air (see Note 1)

More information

MH Table of Contents Standard Title/Scope Page Table of Contents SCE Public

MH Table of Contents Standard Title/Scope Page Table of Contents SCE Public MH Table of Contents Standard Title/Scope MH 300 MH 310 MH 318 MH 320 MH 325 MH 330 MH 335 MH 340 MH 350 Manholes Requirements MH 300.1 Manholes Requirements...........................................

More information

SEWERAGE CODE OF AUSTRALIA AGENCY REQUIREMENTS PART 1 - DESIGN

SEWERAGE CODE OF AUSTRALIA AGENCY REQUIREMENTS PART 1 - DESIGN Clause Description Requirement SEWERAGE CODE OF AUSTRALIA AGENCY REQUIREMENTS PART 1 - DESIGN Supporting Document 4.2.2 Design Accuracy Design levels and distances to be in accordance with SA Water requirements:-

More information

ISSUE MODIF. ORDER NO. WEEK ISSUE MODIF. ORDER NO. WEEK ISSUE MODIF. ORDER NO. WEEK 01 SME SME SME

ISSUE MODIF. ORDER NO. WEEK ISSUE MODIF. ORDER NO. WEEK ISSUE MODIF. ORDER NO. WEEK 01 SME SME SME 1. Summary The still pipe used with Rosemount 5900 LPG/LNG antenna is not supplied by RTR, but is to be manufactured by the customer according to the RTR drawing D9240041-910 or D7000001-466. Additional

More information

SECTION 39 - MANHOLES TABLE OF CONTENTS

SECTION 39 - MANHOLES TABLE OF CONTENTS SECTION 39 - MANHOLES TABLE OF CONTENTS Section Page 39-1 GENERAL... 39.1 39-2 PRECAST CONCRETE MANHOLES... 39.1 39-2.01 Precast Concrete Sewer Manholes... 39.1 39-2.02 Precast Concrete Storm Drain Manholes...

More information

IOWA CITY WASTEWATER TREATMENT PLANT RELOCATION PROJECT NORTH PLANT SALVAGE AND DEMOLITION PHASE CITY OF IOWA CITY FEBRUARY, 2015

IOWA CITY WASTEWATER TREATMENT PLANT RELOCATION PROJECT NORTH PLANT SALVAGE AND DEMOLITION PHASE CITY OF IOWA CITY FEBRUARY, 2015 IOWA CITY WASTEWATER TREATMENT PLANT RELOCATION PROJECT No Record Drawing Comments by Veit for this Sheet! FOR FEBRUARY, 2015 VEIT Record Drawings Demolition Project Manager: Jason Mueller Demolition Superintendent:

More information

SECTION MANHOLES

SECTION MANHOLES SECTION 33 05 13 MANHOLES PART 1 GENERAL 1.01 SECTION INCLUDES A. CONTRACTOR shall furnish and install precast concrete manhole base, sections, adjusting rings, steps, and manhole ring and cover, complete.

More information

Introduction. Classifications of piping: Industrial. Residential (i.e., plumbing) Carries liquids and gases used in the manufacture of products

Introduction. Classifications of piping: Industrial. Residential (i.e., plumbing) Carries liquids and gases used in the manufacture of products Plumbing Plans Introduction Classifications of piping: Industrial Carries liquids and gases used in the manufacture of products Residential (i.e., plumbing) Carries fresh water, gas, liquid, solid waste

More information

ADDENDUM 4 BID OPPORTUNITY NO

ADDENDUM 4 BID OPPORTUNITY NO ` Corporate Finance Department Materials Management Branch ADDENDUM 4 BID OPPORTUNITY NO. 74-2005 Page 1 of 8 NEWPCC SECONDARY EFFLUENT UV DISINFECTION FACILITY URGENT PLEASE FORWARD THIS DOCUMENT TO WHOEVER

More information

DE027: X-mas Tree & Wellhead Operations, Maintenance & Testing

DE027: X-mas Tree & Wellhead Operations, Maintenance & Testing DE027: X-mas Tree & Wellhead Operations, Maintenance & Testing DE027 Rev.001 CMCT COURSE OUTLINE Page 1 of 5 Training Description: Wellhead and x-mas tree is the main equipment for oil production, water

More information

FORTRESS BOTTOM PLATE ANCHORS. Product. Scope. Building Regulations. Appraisal No. 687 [2017]

FORTRESS BOTTOM PLATE ANCHORS. Product. Scope. Building Regulations. Appraisal No. 687 [2017] FORTRESS BOTTOM PLATE This Appraisal replaces BRANZ Appraisal No. 687 (2010) BRANZ Appraisals Technical Assessments of products for building and construction. Manufacturing Suppliers Limited 560 Rosebank

More information

Manholes Table of Contents

Manholes Table of Contents Standard MH 300 Title Manholes Requirements MH 300.1 Manholes Requirements Manholes Table of Contents Underground Structures Standards MH 310 MH 318 MH 320 MH 325 MH 330 MH 335 MH 340 MH 350 Precast Tub-Type

More information

STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENT 1073 PRECAST CONCRETE CERTIFICATION PROGRAM JULY 20, 2018

STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENT 1073 PRECAST CONCRETE CERTIFICATION PROGRAM JULY 20, 2018 STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENT 1073 PRECAST CONCRETE CERTIFICATION PROGRAM JULY 20, 2018 1073.01 Program Overview 1073.02 Qualification 1073.03 Documentation Phase 1073.04 Documentation

More information

Grease Interceptor Design Checklist

Grease Interceptor Design Checklist CHECKLIST C2 Revised 5/2/2016 Grease Interceptor Design Checklist Public Works DISCLAIMER - This checklist is provided to Consulting Engineers for the express purpose of assisting them in compiling private

More information

Anne Arundel County Dept. of Inspections and Permits Water Sewer Plan Checklist

Anne Arundel County Dept. of Inspections and Permits Water Sewer Plan Checklist Project Name Project Number Engineer Plans are to be designed based on the standards set forth in the Anne Arundel County Design Manual Standards and Specifications, and all other manuals as stipulated

More information

SECTION 8: DRAINAGE, SEWER AND WATER SUPPLY NETWORKS

SECTION 8: DRAINAGE, SEWER AND WATER SUPPLY NETWORKS UDNP Standard Specifications SECTION 8: DRAINAGE, SEWER AND WATER SUPPLY NETWORKS 8.01 - Page i UDNP Standard Specifications SECTION 8: DRAINAGE, SEWER AND WATER SUPPLY NETWORKS Table of Contents SECTION

More information

Advancements in Clamp-on Ultrasonic Flow Measurements Biosolids Workshop December 1 st 2016

Advancements in Clamp-on Ultrasonic Flow Measurements Biosolids Workshop December 1 st 2016 Advancements in Clamp-on Ultrasonic Flow Measurements 2016 Biosolids Workshop December 1 st 2016 Market Leader in Clamp-On Ultrasonic Flowmeters with >50,000 instruments sold Background Information Extraordinary

More information

TOWN of LAKESHORE SITE PLAN CHECKLIST

TOWN of LAKESHORE SITE PLAN CHECKLIST TOWN of LAKESHORE SITE PLAN CHECKLIST Last Revised December 17, 2009 Project Name: Project Location: Date Submitted: Name Phone Number E-mail Address Owner: Contractor/ Engineer: ( ) ( ) Applicant: ( )

More information

Appendix C Construction Details

Appendix C Construction Details 7172 Kennedy Road Warrenton, Virginia 20187 Appendix C Construction Details November 2017 TABLE OF CONTENTS THRUST BLOCKS Anchorage for 11 1/4 o, 22 1/2 o & 45 o Upper Vertical Bends... AV 01 Buttresses

More information

SECTION III SUBMITTALS AND APPROVALS

SECTION III SUBMITTALS AND APPROVALS SECTION III SUBMITTALS AND APPROVALS In order to expedite the approval process of new water distribution system and sanitary sewer collection system extensions, the Hilton Head No. 1 Public Service District

More information

Cooke Precast Concrete

Cooke Precast Concrete Cooke Precast Concrete ACCESS COVERS History Cooke Precast Concrete Pty. Ltd. commenced business in September 1996, with a staff combining together bringing many decades of knowledge and experience within

More information

4 T V H A D A A

4 T V H A D A A 4 T V H 0 0 8 6 A D 0 0 0 A A 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Name All of units Outline Function Outdoor unit installation manual 1 Outdoor unit user manual 1 Be sure to deliver it to the customer

More information

RELINER INSIDE DROP SYSTEM SPECIFICATIONS

RELINER INSIDE DROP SYSTEM SPECIFICATIONS 1. PRODUCT NAME RELINER INSIDE DROP SYSTEM U.S. Patent 6074130 Canadian Patent # 2269565 All RELINER Products are proudly made in the U.S.A. 2. MANUFACTURER RELINER /Duran Inc. 53 Mount Archer Rd. Lyme

More information

ERRATA AND REVISIONS to the CANADIAN PLUMBING CODE

ERRATA AND REVISIONS to the CANADIAN PLUMBING CODE NATONAL RESEARCH COUNCL OF CANADA ASSOCATE COMMTTEE ON THE NATONAL BULDNG CODE ERRATA AND REVSONS to the CANADAN PLUMBNG CODE 1970 (ncorporating changes from Change Series No.2 to the National Building

More information

Public Works City of Lebanon, Tennessee; Department of Public Works

Public Works City of Lebanon, Tennessee; Department of Public Works SECTION 1 GENERAL 1. DEFINITIONS Public Works City of Lebanon, Tennessee; Department of Public Works City City of Lebanon, Wilson County, Tennessee City Engineer Employed by the City of Lebanon, Registered

More information

SOUTH AFRICAN NATIONAL STANDARD

SOUTH AFRICAN NATIONAL STANDARD ISBN 978-0-626-27370-5 SOUTH AFRICAN NATIONAL STANDARD Precast concrete manhole sections and components Published by SABS Standards Division 1 Dr Lategan Road Groenkloof Private Bag X191 Pretoria 0001

More information

Utility Structures. Utility vaults, trenches, transformer pads Electrical Pole Bases and switching cubicles

Utility Structures. Utility vaults, trenches, transformer pads Electrical Pole Bases and switching cubicles Utility Structures Utility vaults, trenches, transformer pads Electrical Pole Bases and switching cubicles PRODUCT GUIDE & TECHNICAL REFERENCE MANUAL Providing the right solutions. UTILITY STRUCTURES Perfect

More information

KANSAS DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION TO THE STANDARD SPECIFICATIONS, 1990 EDITION

KANSAS DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION TO THE STANDARD SPECIFICATIONS, 1990 EDITION Sheet 1 of 5 KANSAS DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION TO THE STANDARD SPECIFICATIONS, 1990 EDITION NOTE: This special provision is generally written in the imperative mood. The subject, "the

More information

MEDIUM DUTY CAST IRON SLIDE GATES SERIES 20-10C

MEDIUM DUTY CAST IRON SLIDE GATES SERIES 20-10C MEDIUM DUTY CAST IRON SLIDE GATES SERIES 20-10C Revised October 2007 Armtec reserves the right to alter designs. General The Armtec Sluice Gate is a quality and highly economical gate for a variety of

More information

City of Vaughan Engineering Department DESIGN STANDARD DRAWINGS

City of Vaughan Engineering Department DESIGN STANDARD DRAWINGS City of Vaughan Engineering Department DESIGN STANDARD DRAWINGS March 2004 STANDARD DRAWINGS Partners With The Environment March 2004 FORWARD The March 2004 version of the City of Vaughan Design Standard

More information

Design submission using DTC or Engineering Certified solution.

Design submission using DTC or Engineering Certified solution. Work Instruction Design submission using DTC or Engineering Certified solution. 1. Overview 1.1. Objective This work instruction provides the process that the Water Servicing Coordinator (WSC) is to follow

More information

C-M TMR Products Index

C-M TMR Products Index C-M TMR Products Index TMR Dwg. No. Grate/Frames 9x6 Dwg. AS3996 Recessed Road Gully Units Dwg. 1443, 1444 Protruded Road Gully Units Dwg. 1443, 1444 1220 Road Gully Units Dwg. 1459 7x4 Road Gully Units

More information

NORTH CAROLINA DEPARTMENT OF HEALTH AND HUMAN SERVICES DIVISION OF PUBLIC HEALTH ENVIRONMENTAL HEALTH SECTION ON-SITE WATER PROTECTION BRANCH

NORTH CAROLINA DEPARTMENT OF HEALTH AND HUMAN SERVICES DIVISION OF PUBLIC HEALTH ENVIRONMENTAL HEALTH SECTION ON-SITE WATER PROTECTION BRANCH NORTH CAROLINA DEPARTMENT OF HEALTH AND HUMAN SERVICES DIVISION OF PUBLIC HEALTH ENVIRONMENTAL HEALTH SECTION ON-SITE WATER PROTECTION BRANCH SEPTIC/PUMP TANK RISER ASSEMBLIES APPROVAL Septic/Pump Tank

More information

Section XV - PER, Design, and Construction Submittal Requirements

Section XV - PER, Design, and Construction Submittal Requirements Section XV - PER, Design, and Construction Submittal Requirements A. Introduction - In an effort to reduce paper and to further implement the Oracle Unifier Project Management System, the Engineering Department

More information

The Isolator/Surge Protector (ISP)

The Isolator/Surge Protector (ISP) The Isolator/Surge Protector (ISP) Technical Literature INTRODUCTION The Isolator/Surge Protector (ISP) is a solid-state device with logic-controlled circuitry which simultaneously provides isolation and

More information

ASSET INFORMATION SPECIFICATION

ASSET INFORMATION SPECIFICATION SEQ Water Supply and Sewerage Design & Construction Code (SEQ WS&S D&C Code) ASSET INFORMATION SPECIFICATION October 2015 This document contains inmation which is proprietary to the SEQ service and may

More information

ABOUT INLAND. Tannis Karklin, E.I.T Technical Sales and Marketing

ABOUT INLAND. Tannis Karklin, E.I.T Technical Sales and Marketing ABOUT INLAND Inland roots in the Winnipeg area date back to the early 960 s. Over time, through a number of mergers and acquisitions Inland Pipe is now part of the Lehigh Hanson group in North America

More information

Construction Specification for Watermain and Water Service Tracer Wire

Construction Specification for Watermain and Water Service Tracer Wire Engineering and Construction Services Division Standard Specifications for Sewers and Watermains TS 7.40 April 2013 for Watermain and Water Service Tracer Wire Table of Contents TS 7.40.01 SCOPE... 2 TS

More information

Please remove and replace the entire Table of Contents, Section A to Section J and all Appendices.

Please remove and replace the entire Table of Contents, Section A to Section J and all Appendices. Please remove and replace the entire Table of Contents, Section A to Section J and all Appendices. The following is a list of changes to the Design Criteria: 1. A2.01 General Note 4 Utility Coordination

More information

9/17/90 (rev.) STATE OF MINNESOTA HINNESOTA DEPARTMENT OF HEALTH

9/17/90 (rev.) STATE OF MINNESOTA HINNESOTA DEPARTMENT OF HEALTH This document is made available electronically by the Minnesota Legislative Reference Library as part of an ongoing digital archiving project. http://www.leg.state.mn.us/lrl/sonar/sonar.asp 9/17/90 (rev.)

More information

shawprecastsolutions.com BEBO Arch Systems PRODUCT GUIDE & TECHNICAL REFERENCE MANUAL Providing the right solutions.

shawprecastsolutions.com BEBO Arch Systems PRODUCT GUIDE & TECHNICAL REFERENCE MANUAL Providing the right solutions. shawprecastsolutions.com BEBO Arch Systems PRODUCT GUIDE & TECHNICAL REFERENCE MANUAL Providing the right solutions. BEBO ARCH SYSTEMS BEBO ARCH units are high quality, low maintenance precast structures

More information

Advancements in Clamp-on Ultrasonic Flow Measurements. Ohio Section AWWA SE District Fall Meeting September 1 st 2017

Advancements in Clamp-on Ultrasonic Flow Measurements. Ohio Section AWWA SE District Fall Meeting September 1 st 2017 Advancements in Clamp-on Ultrasonic Flow Measurements Ohio Section AWWA SE District Fall Meeting September 1 st 2017 About Us - Providing Measurement instrumentation and data collection since 1984 - State

More information

Design Deliverables. Summary. A. Expectations for Design Deliverables:

Design Deliverables. Summary. A. Expectations for Design Deliverables: Design Deliverables Summary A. Expectations for Design Deliverables: The Design Team is obligated to advance and deliver the project with a professional manner and standard of care that meets the expectations

More information

SYARIKAT BEKALAN AIR SELANGOR SDN BHD

SYARIKAT BEKALAN AIR SELANGOR SDN BHD NOTE : 1. FOR LEGEND, ABBREVIATION AND GENERAL NOTES SEE DRG. NO. SYA / STD / 001. 2. ALL DIMENSIONS ARE IN mm UNLESS OTHERWISE STATED. 3. ACTUAL LENGTH OF PE COMMUNICATION PIPES SHALL BE DETERMINED ON

More information

June 10, 2014 BOARD OF COUNTY COMMISSIONERS ORANGE COUNTY, FLORIDA

June 10, 2014 BOARD OF COUNTY COMMISSIONERS ORANGE COUNTY, FLORIDA June 10, 2014 BOARD OF COUNTY COMMISSIONERS ORANGE COUNTY, FLORIDA ADDENDUM NO. 5 BID NO. Y14-792 PH IFB EAST SERVICE AREA POTABLE WATER AND RECLAIMED WATER STORAGE AND REPUMP FACILITY BID OPENING: June

More information

ASSET MAP USER GUIDE NOVEMBER 2017

ASSET MAP USER GUIDE NOVEMBER 2017 ASSET MAP USER GUIDE NOVEMBER 2017 1. Asset Map Functionality 3 1.1 Navigating the Map Display 3 1.2 Map Tools 5 1.2.1 Query Tool 6 1.3 Additional Tools 7 1.3.1 Measurements 7 1.3.2 Map Selection 7 1.3.3

More information

SECTION EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING

SECTION EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING SECTION 230516 - EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

Government Of Newfoundland & Labrador Municipal Water, Sewer And Roads Master Construction Specifications

Government Of Newfoundland & Labrador Municipal Water, Sewer And Roads Master Construction Specifications PAGE NO. : 1 OF 4 Revision Date: July 2009 STANDARD DRAWINGS TABLE OF CONTENTS DRAWING # DESCRIPTION 0030............ Work Adjacent to Roadway 0040............ Work at the Edge of Roadway 0050............

More information

Guidelines for Choosing and Installing Radar in Stilling Wells and Bypass Chambers

Guidelines for Choosing and Installing Radar in Stilling Wells and Bypass Chambers 84-3-424, Rev BA May 29 Rosemount Radar Transmitters Guidelines for Choosing and Installing Radar in Stilling Wells and Bypass Chambers INTRODUCTION This document provides a guideline for choosing and

More information

Size : Connection Ends : Min Temperature : Max Temperature : Materials : Cast iron body

Size : Connection Ends : Min Temperature : Max Temperature : Materials : Cast iron body Size : Connection Ends : Min Temperature : Max Temperature : DN 50 to 200 Flanged ISO PN 10/16 ( ISO PN16 for DN200 ) 0 C + 50 C Max Pressure : 16 Bars Specifications : Tangential type Dry dial Magnetic

More information

Oil-Water Separator Design Checklist

Oil-Water Separator Design Checklist CHECKLIST C3 Revised 5/2/2016 Oil-Water Separator Design Checklist DISCLAIMER - This checklist is provided to Consulting Engineers for the express purpose of assisting them in compiling private oil-water

More information

DIVISION APPROVED MATERIAL LIST AND STANDARD DETAILS

DIVISION APPROVED MATERIAL LIST AND STANDARD DETAILS DIVISION 400 - APPROVED MATERIAL LIST AND STANDARD DETAILS Section 403 - STANDARD DETAILS TABLE OF CONTENTS DIVISION 400, Section 403 - STANDARD DETAILS SECTION DETAIL NOS. Application Table 403-1 I. Concrete

More information

Thermoplastic Valves Sewer Disconnect

Thermoplastic Valves Sewer Disconnect Sewer onnect Spears Sewer onnect functions as both cleanout and disconnect device, plus helps prevent sewage backup during hurricanes and floods. Complete unit consists of body and plunger (sold separately

More information

connecting the world PDF compression, OCR, web optimization using a watermarked evaluation copy of CVISION PDFCompressor

connecting the world PDF compression, OCR, web optimization using a watermarked evaluation copy of CVISION PDFCompressor C O N S T R U C T I O N I W I N D E N E R G Y I T U N N E L L I N G I R A I L I O E M connecting the world the tunnelling market Tunnelling is a key facet of infrastructure development particularly where

More information

OPTIFLUX 5000 Technical Datasheet

OPTIFLUX 5000 Technical Datasheet OPTIFLUX 5000 Technical Datasheet Electromagnetic flowmeter in flanged version Exceptional long-term stability and accuracy For highly aggressive and abrasive fluids Fully vacuum-resistant with high-tech

More information

DESIGN GUIDELINES (SD) COUNTY OF ALAMEDA PUBLIC WORKS AGENCY 399 ELMHURST STREET HAYWARD, CA

DESIGN GUIDELINES (SD) COUNTY OF ALAMEDA PUBLIC WORKS AGENCY 399 ELMHURST STREET HAYWARD, CA DESIGN GUIDELINES (SD) COUNTY OF ALAMEDA PUBLIC WORKS AGENCY 399 ELMHURST STREET HAYWARD, CA 94544-1395 PUBLIC WORKS DESIGN GUIDELINES TABLE OF CONTENTS SD-100 SERIES SPECIAL DRAWINGS SD-100 8/1991 SILT

More information

BOX CULVERTS DRAINAGE & WATER MANAGEMENT. v2.1

BOX CULVERTS DRAINAGE & WATER MANAGEMENT. v2.1 BOX CULVERTS DRAINAGE & WATER MANAGEMENT v2.1 FPMCCANN.CO.UK Magherafelt UddingSton Alnwick Designed and manufactured in accordance with all current design specifications and relevant standards, FP McCann

More information

ADDENDUM No. 1. ITB No Northside Interceptor Condition Assessment. Due: February 1, 2018 at 10:00 A.M. (Local Time)

ADDENDUM No. 1. ITB No Northside Interceptor Condition Assessment. Due: February 1, 2018 at 10:00 A.M. (Local Time) ADDENDUM No. 1 ITB No. 4521 Northside Interceptor Condition Assessment Due: February 1, 2018 at 10:00 A.M. (Local Time) The following changes, additions, and/or deletions shall be made to the Invitation

More information

SECTION TRACER WIRE FOR NONMETALLIC PIPE

SECTION TRACER WIRE FOR NONMETALLIC PIPE PART 1 GENERAL 1.1 DESCRIPTION A. The CONTRACTOR shall furnish and install a conductive tracer wire with all buried plastic water mains, services and appurtenances in accordance with the Water Utilities

More information

TO WHOM IT MAY CONCERN:

TO WHOM IT MAY CONCERN: TO WHOM IT MAY CONCERN: A lot of questions are asked throughout the year as to when a building permit is required. This list may help identify some of the instances when a permit would be required: Permit

More information

REGIONAL TRANSIT AUTHORITY PUBLIC NOTICE. IFB Rail Expansion (Streetcar) Rampart Street. Addendum IV

REGIONAL TRANSIT AUTHORITY PUBLIC NOTICE. IFB Rail Expansion (Streetcar) Rampart Street. Addendum IV REGIONAL TRANSIT AUTHORITY PUBLIC NOTICE IFB 2014-014 Rail Expansion (Streetcar) Rampart Street Addendum IV Acknowledge receipt of this addendum in the bid submission. This addendum is a part of the Contract

More information

Petroleum Safety Levy Methodology. Decision Paper

Petroleum Safety Levy Methodology. Decision Paper Petroleum Safety Levy Methodology Decision Paper DOCUMENT TYPE: REFERENCE: Decision Paper CER/14/429 DATE PUBLISHED: 7 th August 2014 VERSION 3.0 The Commission for Energy Regulation, The Exchange, Belgard

More information

L1702D-SW-PL-01 STORM LINES - PLANS (1 OF 3) L1702D-WW-PL-03 SEWER LINES - PLANS (3 OF 3) L1702D-SW-PL-02 STORM LINES - PLANS (2 OF 3)

L1702D-SW-PL-01 STORM LINES - PLANS (1 OF 3) L1702D-WW-PL-03 SEWER LINES - PLANS (3 OF 3) L1702D-SW-PL-02 STORM LINES - PLANS (2 OF 3) GENERAL DWG Nb. DRAWING TITLE L1702D-LOD- LIST OF DRAWINGS L1702D-GN- GENERAL & L1702D-WW-GNL-01 SEWER LINES - GENERAL LAYOUT L1702D-WW-KPL-01 SEWER LINES - GENERAL KEY PLAN L1702D-SW-GNL-01 STORM LINES

More information

.1 Materials and installation for steel piping, valves and fittings for hydronic systems in building services piping..2 Related Sections.

.1 Materials and installation for steel piping, valves and fittings for hydronic systems in building services piping..2 Related Sections. Issued 2006/08/01 Section 15183 Hydronic Systems: Steel Page 1 of 6 PART 1 GENERAL 1.1 SUMMARY.1 Section Includes..1 Materials and installation for steel piping, valves and fittings for hydronic systems

More information

EKSPAN. Standard F Series Bearings. Description. Bearing types F series bearings are available in three forms - Typical 21F details.

EKSPAN. Standard F Series Bearings. Description. Bearing types F series bearings are available in three forms - Typical 21F details. Standard F Series Bearings Description F Series is a range of structural bearings for locating structures. They are designed to react only horizontal loads. Fixed and guided bearings are available as standards

More information

REQUEST FOR BIDS WELL #4 ABANDONMENT

REQUEST FOR BIDS WELL #4 ABANDONMENT REQUEST FOR BIDS WELL #4 ABANDONMENT Department of Public Services 1015 S Lincoln Avenue Three Rivers, MI 49093 (269) 273-1845 Table of Contents Well #4 Abandonment... 8 Performance Bids... 8 I. Instructions...

More information

Special Provision No. 904S14 October OPSS 904, January 1995, Construction Specification for Concrete Structures, is amended as follows:

Special Provision No. 904S14 October OPSS 904, January 1995, Construction Specification for Concrete Structures, is amended as follows: DOWELS INTO CONCRETE Item No. Special Provision No. 904S14 October 2005 OPSS 904, January 1995, Construction Specification for Concrete Structures, is amended as follows: 904.02 REFERENCES Section 904.02

More information