1 REGIONAL TRANSIT AUTHORITY PUBLIC NOTICE IFB Rail Expansion (Streetcar) Rampart Street Addendum IV Acknowledge receipt of this addendum in the bid submission. This addendum is a part of the Contract Documents and shall be included in the Contract Documents. Changes made by the addenda take precedence over information published at an earlier date. Questions received in writing: Q1. Technical Specifications F 3 discusses the need for opening a security lighting contract with Entergy for the use of temporary street lighting. After calling Mike S at Entergy there still remains to be questions. The following will be needed by Entergy in order to provide a proper quote. What type of light fixture is required or needed? Entergy offers many options and depending on the footcandles required by RTA would determine the type of fixture? A1. Per Section 02415, Part 3.05.F.1 the Contractor, NOT Entergy Electric, is to maintain the existing street lighting. Entergy is to provide and maintain electrical service and connections to existing Entergy facilities. Light fixture is to be acceptable to the owner, the City of New Orleans Department of Public Works (DPW). The Contractor is to provide light intensity equivalent to current street lighting. DPW has indicated that they typically require temporary installation to match the existing lighting wattage or as close as possible, on Rampart it s safe to use 100W, and identified a metal halide medium floodlight, catalog #F400ML SCWA provided by Lithonia Lighting, as an acceptable product. Q2. Entergy stated they needed permission granted by the RTA on the exact locations of the temporary poles/lights in order to install the lights in the neutral ground. Can you provide the exact locations and grant the permission needed in an addenda? A2. The Contractor, NOT Entergy Electric, is to maintain the existing street lighting. Entergy is to provide and maintain electrical service and connections to existing Entergy facilities. Exact locations are to be determined by the approved Contractor s work plan.

2 Q3. Is it RTAs intent for the Contractor to take down all of the historic lights on Rampart St one at a time or to have them remove 3 blocks at a time as the work progresses and has been restricted according to Technical Specs A 5? This will determine how many temporary lights will be needed at one time per the contract with Entergy. A3. Contractor is to establish his work program in order to maintain the Project Schedule. Q4. As per Paragraph 1.03 Sequence of Work, Specification Section 01010, Page 4, the Contractor shall be prepared with sufficient labor, equipment and materials to complete all of the work in the area of the Half Grand Union at the intersection of Canal St. and Rampart St. within the 28-day continuous period. However, as per Note No. 2 on Drawing B-TCP-102, Sheet 395 all work in Phase V, Canal St. /N. Rampart St. intersection, shall be completed within a 3 week closure period. Please clarify. A4. Please refer to Table SP-01-1 of Special Provisions. The Special Provisions duration supersedes the 3-week closure period defined in B-TCP-102 and the 28- day continues period noted in Technical Specifications. Q5. Reference: Casing pipe. 2a) As per Carrier & Casing Pipe Chart on Drawing B-UR-DET3, Sheet 66, for 8 DI carrier pipe, casing pipe shall be 20 steel x wall thickness. However, on Drawing B-UR-101RT (Sheet 27), on Drawing B-UR-102RT (Sheet 28), and on Drawing B-UR-105RT (Sheet 31) casing pipe for 8 DI carrier pipe is 16 steel. Please clarify which is correct. A5. Various casing sizes were required based on the amount of cover and other location specific conditions. The casing sizes called out on the relocation drawings (B-UR-100 & B-UR-200 series) should take precedent over the table listed on B-UR-DET3. Q6. As per Carrier & Casing Pipe Chart on Drawing B-UR-DET3 (Sheet 66), for 12 DI carrier pipe, casing pipe shall be 24 steel x wall thickness. However, on Drawing B-UR-104RT, Sheet 30, casing pipes for 12 DI carrier pipes are 20 steel. Please clarify which is correct. 2c) Carrier & Casing Pipe Chart on Drawing B-UR-DET3 (Sheet 66), exclude 10 DI carrier pipe, casing pipe size and casing wall thickness. Please provide missing information for 10 DI carrier pipe and please confirm that 16 casing for 10 water main line, as shown on Drawing B-UR-103RT (Sheet 29) is correct. 2d) Carrier & Casing Pipe Chart on Drawing B-UR-DET3 (Sheet 66), exclude 6 DI carrier pipe, casing pipe size and casing wall thickness. Please provide missing information for 6 DI carrier pipe, please confirm that 12

3 casing for 6 water main line, as shown on Drawing B-UR-1043RT (Sheet 30) is correct and please clarify under what bid item, payments for installation of 12 steel casing is to be included. A6. Various casing sizes were required based on the amount of cover and other location specific conditions. The casing sizes called out on the relocation drawings (B-UR-100 & B-UR-200 series) should take precedent over the table listed on B-UR-DET3. The 12 steel casing should be incorporated into Unit Price Bid Form, Ref. No A) Unit Price Bid Form: CHANGE Ref. No to read as follows: Steel Pipe Casing by Trenching (12" and 16"; 0.375" Thick) B) Unit Price Bid Form: CHANGE Ref. No QUANTITY to 456 LINEAR FOOT C) Specification Section 01025, Subpart : MODIFY first line to read as follows: Steel Pipe Casing by Trenching (12" and 16"; 0.375" Thick) will be measured Q7. Section 02215, Paragraph 1.01.C, Related Work Specified Elsewhere refer to Section Removal/Modification of Existing Structures. The bid documents include Section with this name: Removal of Existing Pavement and Miscellaneous Items. Please clarify. A7. Please refer to Section that contains information concerning Protection of Persons and Property which, among other contract documents, is pertinent to Section Q8. Demo Note No. 4 on Drawing B-P-101, Sheet 102 states: For utility relocations and removal see utility relocation plans. Utility relocations shown on demo sheets for reference only. a) Please explain how removal of traffic manholes and removal of traffic control box is shown on demolition plans, Drawing B-DEM-102 & B-DEM-103 (Sheets 87 & 88) but is not shown on utility relocation plan, Drawing B-UR-102RT & B-UR-103RT, Sheet 28 & 29. b) Please clarify under what bid item measurement and payment for this removal work shall be included. A8. a) Contract drawings are not intended to be repetitive; therefore, work associated with traffic manholes and traffic control boxes may not, necessarily, be contained in their entirety in other drawings.

4 b) There are several bid line items that contain work of this nature. Refer to Section for Measurement and Payment. Q9. As per note on Drawing B-UR-105RT, Sheet 31 existing 15 RCP must be removed and replaced beneath track bed and tie in to new MH & existing RCP using transition coupling at both ends. Please clarify under what bid item, measurement and payments for this work shall be included and please provide additional info on transition couplings. A9. As per section of Measurement & Payment in the project specifications payment shall include tie-ins, fittings Any additional costs for the transitional couplings should be included in the linear foot price for Reinforced Concrete Pipe Arch. Transition couplings shall meet S&WB and industry standards. Q10. Note on Drawing B-PP-203, Sheet 126 reads: Req d MHP1 STA drain to MHC1. Please clarify what is meant by this note as there is no connection between MHP1 and MHC1. A10. Note on Drawing B-PP-203, Sheet 126 should read: Req d MHP1 STA drain to track drain at STA Q11. Per technical specification section Measurement and payment, bid item Sawcutting is described to include all the full depth and 2 sawcut that is required for pavement removal per contract drawings. Also, bid item Pavement Restoration (Asphaltic Concrete) is described to include any labor and equipment for sawcutting as required. Please clarify the scope of sawcutting to be included in bid item A11. Item # should contain the primary sawcutting. Item # is meant to include incidental sawcutting associated with the scope of work defined in technical specification Section Q12. Typical sections at sheltered stops on drawings B-P-303 & B-P-314 calls for 8 Base Course LADOT Class II under the concrete slab. However, structural drawing B-S-042 calls for 6 compacted granular fill. Please clarify the thickness and type of material. A12. Drawing #B-S-042 should be modified. CHANGE all details from 6" COMPACTED GRANULAR FILL TO READ 8" BASE COURSE LADOT CLASS II 95% COMPACTION

5 Q13. Drawing B-PP-201, Sheet 124, Invert Elevation for req d track drain at STA is (-) However, on Drawing B-PP-401, Sheet 155, Invert Elevation is (-) 1.7. Please clarify. A13. Drawing B-PP-201, Sheet 124, Invert Elevation for req d track drain at STA should read (-)1.7 not (-) Q14. Reference: Manholes labeled MHC and MHP. a) Please clarify under what bid item, measurement and payment for manholes labeled MHC and MHP as shown on B-PP drawings is to be included? b) Please provide additional info including, but not limited to, standard drawings reference, details, etc. for MHC and MHP manholes. A14. The MHP and MHC are identified in several details in the drawings, including in the B-EC-XXX, B-TPC-XXX and B-TKC-XXX series of drawings. In the latter, these are described as track pit so as to distinguish their rectangular dimensions from circular manholes. Bid items for these are identified in Section Q15. On the Right Track Profile drawings (Sheet 136 through 139) and the Left Track Profile drawings (Sheet 150 through 154), the existing structures are shown bold compared with proposed track drain lines and structures. Some of the proposed structures are not shown at all or without invert elevations. However the existing structures are not labeled as required and it is unclear if these structures are part of scope of work of this project. Please clarify and provide all required information. A15. The provision of all track drain lines and track drain structures are part of the scope of work. By comparing the B-PP-XXX series of drawings with the utility B-U-XXX and B-UR-XXX series of drawings, the changes and/or improvements in those structures can be identified. Q16. There are numerous references to spare parts throughout the specs. These are not reflected in the quantities on the bid form. Can a line item for Spare Parts be added as an ALLOWANCE to the bid form in a new addenda? If not, can a list of the Spare Parts be released and a line item added to the Bid Form for Spare Parts? A16. No. A new Bid Form will not be added. The measurement and payment for the spare parts is to be considered incidental to the scope of work to which they are referenced.

6 Q17. Plan sheet The sheet is titled "House Connections - Sewer 1 of 3", but the information provided is for water service connections. Please provide the information for the sewer service connections. A17. This sheet is incorrectly labeled and should be changed to House Connections - Water 1 of 3. Q18. Plan sheets These sheets are titled "House Connections - Water 1 of 3, 2 of 3 and 3 of 3", but the information provided is for sewer service connections. Please provide the information for the water service connections. A18. The sheets are incorrectly labeled and should be changed to House Connections - Sewer 1 of 3, 2 of 3 and 3 of 3. Q19. Bid Item "Steel Pipe Casing by Trenching (32 ; Thick)" - I was not able to locate this size casing in the plans. Please provide the location(s) that this size casing is required. A19. The item is to be removed from the contract scope of work. A) Unit Price Bid Form: DELETE Ref. No B) Specification Section 01025, Subpart (page ): DELETE in its entirety Q20. Bid item "Reinforced Concrete Pipe Arch (15 Equiv.)" - I was not able to locate this size arch pipe in the drawings. Please provide the location(s) that this size arch pipe is required. A20. The item is to be removed from the contract scope of work. A) Unit Price Bid Form: DELETE Ref. No B) Specification Section 01025, Subpart (page ): DELETE in its entirety Q21. Bid item "Reinforced Concrete Pipe Arch (18 Equiv.)" - I was not able to locate this size arch pipe in the drawings. Please provide the location(s) that this size arch pipe is required. A21. The item is to be removed from the contract scope of work. A) Unit Price Bid Form: DELETE Ref. No B) Specification Section 01025, Subpart (page ): DELETE in its entirety

7 Q22. Bid item "Reinforced Concrete Pipe Arch (30 Equiv.)" - I was not able to locate this size arch pipe in the drawings. Please provide the location(s) that this size arch pipe is required. A22. The item is to be removed from the contract scope of work. A) Unit Price Bid Form: DELETE Ref. No B) Specification Section 01025, Subpart (page ): DELETE in its entirety Q23. 4" Gate Valve w/ MH at station , 11.02' LT shown on plan sheet 37 - Is the 4" gate valve w/ MH considered incidental to the 4" waterline or should a bid item be added? A23. This bid item is to be addressed by the following changes: A) Unit Price Bid Form: CHANGE Ref. No to read as follows: Furnish and Install New 4 and 8 Water Gate Valve B) Unit Price Bid Form: CHANGE Ref. No QUANTITY to 6 EACH C) Specification Section 01025, Subpart : MODIFY first line to read as follows: Furnish and Install New 4 and 8 Water Gate Valve will be measured Q24. Fire Hydrants shown on plan sheets 37 & 38 - Is the 6" gate valve incidental to the fire hydrant bid item or should a bid item be added? A24. The gate valve is part of Bid Item Q25. 4" waterlines shown on plan sheet 37 - The plan view calls for an 8" PVC casing, but the profile view calls for an 8" steel casing. Please specify casing material. Also, is the casing installation incidental to the 4" water line of should a bid item be added? A25. Provide 8 PVC casing. The work is incidental to Unit Price Bid Form, Ref. No Additionally, change the following: A) Unit Price Bid Form: CHANGE Ref. No QUANTITY to 168 LINEAR FOOT

8 Q26. Bid item "4 PVC New Water Main With Main Line Fittings" - The 4" water lines are shown on sheet 37 and are called out to be ductile iron, but the bid item description calls for PVC. Please specify the required material type for the 4" water line. A26. The 4 waterline is to be PVC. Q27. Plan sheet 48 - The plans callout for the removal & replacement of 30 linear feet of 15" RCP. Please provide a bid item for 15" RCP. A27. This bid item is to be addressed by the following changes: A) Unit Price Bid Form: CHANGE Ref. No to read as follows: Reinforced Concrete Pipe (15" and 18") B) Unit Price Bid Form: CHANGE Ref. No QUANTITY to 345 LINEAR FOOT C) Specification Section 01025, Subpart : MODIFY first line to read as follows: Reinforced Concrete Pipe (15" and 18") will be measured Q28. Bid item "Steel Pipe Casing by Trenching (20 ; Thick)" - I have taken off a quantity that is much less than the quantity shown. Please confirm the bid item quantity. A28. Modify the quantity as follows: A) Unit Price Bid Form: CHANGE Ref. No QUANTITY to 303 LINEAR FOOT Q29. Bid item "Reinforced Concrete Pipe Arch (24 Equiv.)" - I have taken off a quantity that is much less than the quantity shown. Please confirm the bid item quantity. A29. Modify the quantity as follows: A) Unit Price Bid Form: CHANGE Ref. No QUANTITY to 59 LINEAR FOOT

9 Q30. For insurance purposes, please provide an anticipated streetcar schedule for an estimated amount of daily traffic on the track. A30. The anticipated schedule for Rampart streetcar line has not been determined yet. The streetcar schedules for all other existing lines can be found at RTA s website under Maps & Schedules. Q31. The contract documents state that this project has an established SLDBE goal of 28.56%. The documents are silent on SLDBEs having to be certified by the bid date. Do companies that bid on this project have to be SLDBE certified by the bid date? As long as SLDBE certification is obtained before the work is performed, can the bidding entity's participation count towards the SLDBE goal? A31. All DBE firms participating on the project must be certified by the bid opening date. Q32. In regards to Specification Section 01025, Measurement and Payment, it lists Bid Item Replacement Water House Connection (5/8 ) (From Main to Meter). We could not find this item in the bidding documents, please provide location of this item. A32. This item is intended to be a draw down amount, since the exact quantity quantity of work performed, and documented by the Contractor. Refer to Drawing series B-STD-XXX for additional Sewerage and Water Board House connection standards and Drawing series B-REF-XXX for the approximate locations of these House connections, which will be required between Esplanade Avenue and St. Bernard Avenue. Q33. In regards to Specification Section 01025, Measurement and Payment, it lists Bid Item Replacement Water House Connection (3/4 ) (From Main to Meter). We could not find this item in the bidding documents, please provide location of this item. A33. This item is intended to be a draw down amount, since the exact quantity quantity of work performed, and documented by the Contractor. Refer to Drawing series B-STD-XXX for additional Sewerage and Water Board House connection standards and Drawing series B-REF-XXX for the approximate locations of these House connections, which will be required between Esplanade Avenue and St. Bernard Avenue.

10 Q34. In regards to Specification Section 01025, Measurement and Payment, it lists Bid Item Replacement Water House Connection (1 3/4 ) (From Main to Meter). We could not find this item in the bidding documents, please provide location of this item. A34. This item is intended to be a draw down amount, since the exact quantity quantity of work performed, and documented by the Contractor. Refer to Drawing series B-STD-XXX for additional Sewerage and Water Board House connection standards and Drawing series B-REF-XXX for the approximate locations of these House connections, which will be required between Esplanade Avenue and St. Bernard Avenue. Q35. In regards to Specification Section 01025, Measurement and Payment, it lists Bid Item Replacement Water House Connection (4 ) (From Main to Meter). We could not find this item in the bidding documents, please provide location of this item. A35. This item is intended to be a draw down amount, since the exact quantity quantity of work performed, and documented by the Contractor. Refer to Drawing series B-STD-XXX for additional Sewerage and Water Board House connection standards and Drawing series B-REF-XXX for the approximate locations of these House connections, which will be required between Esplanade Avenue and St. Bernard Avenue. Q36. In regards to Bid Item , 4 PVC New Water Main, per Specification Section the drawings indicate New Water Main as Ductile Iron. Please confirm material for the New Water Main. A36. Please refer to Question No. 26 Q37. In regards to Bid Item , 6 PVC New Water Main, per Specification Section the drawings indicate New Water Main as Ductile Iron. Please confirm material for the New Water Main. A37. The 6 water line will be PVC. The contractor is to use Ductile Iron for the 6 water line fittings, etc. as stated in the plans. Q38. In regards to Specification Section 01025, Measurement and Payment, it lists Bid Item Sewer House Connection from Main to Back of Curb. We could not find this item in the bidding documents, please provide location of this item.

11 A38. This item is intended to be a draw down amount, since the exact quantity quantity of work performed, and documented by the Contractor. Refer to Drawing series B-STD-XXX for additional Sewerage and Water Board House connection standards and Drawing series B-REF-XXX for the approximate locations of these House connections, which will be required between Esplanade Avenue and St. Bernard Avenue. Q39. In regards to Specification Section 01025, Measurement and Payment, it lists Bid Item Sewer House Connection beyond Back of Curb. We could not find this item in the bidding documents, please provide location of this item. A39. This item is intended to be a draw down amount, since the exact quantity quantity of work performed, and documented by the Contractor. Refer to Drawing series B-STD-XXX for additional Sewerage and Water Board House connection standards and Drawing series B-REF-XXX for the approximate locations of these House connections, which will be required between Esplanade Avenue and St. Bernard Avenue. Q40. In regards to Specification Section 01025, Measurement and Payment, it lists Bid Item Remove Abandoned Concrete Encased Utility Duct Banks. We could not find this item in the bidding documents, please provide location of this item. A40. This item is intended to be a draw down amount, since the exact quantity quantity of work performed, and documented by the Contractor. Q41. In regards to Specification Section 01025, Measurement and Payment, it lists Bid Item Remove Abandoned Gas Pipes/Conduits. We could not find this item in the bidding documents, please provide location of this item. A41. This item is intended to be a draw down amount, since the exact quantity quantity of work performed, and documented by the Contractor. Q42. In regards to Specification Section 01025, Measurement and Payment, it lists Bid Item Steel Pipe Casing by Trenching (20 ; Thick). We could not find this item in the bidding documents, please provide location of this item.

12 A42. The item is included in the pay items as well as on the plans (for example, drawing sheet 34). Also refer to Question No. 28. Q43. In regards to Specification Section 01025, Measurement and Payment, it lists Bid Item Steel Pipe Casing by Trenching (32 ; Thick). We could not find this item in the bidding documents, please provide location of this item. A43. Please refer to Question No. 19 Q44. In regards to Specification Section 01025, Measurement and Payment, it lists Bid Item Reinforced Concrete Pipe Arch (15 Equiv.). We could not find this item in the bidding documents, please provide location of this item. A44. Please refer to Question No. 20 Q45. In regards to Specification Section 01025, Measurement and Payment, it lists Bid Item Reinforced Concrete Pipe Arch (18 Equiv.). We could not find this item in the bidding documents, please provide location of this item. A45. Please refer to Question No. 21 Q46. In regards to Specification Section 01025, Measurement and Payment, it lists Bid Item Reinforced Concrete Pipe Arch (24 Equiv.). We could not find this item in the bidding documents, please provide location of this item. A46. The item is included in the pay items as well as on the plans (for example, drawing sheet 31). Note - also refer to Question No. 29. Q47. In regards to Specification Section 01025, Measurement and Payment, it lists Bid Item Reinforced Concrete Pipe Arch (30 Equiv.). We could not find this item in the bidding documents, please provide location of this item. A47. Please refer to Question No. 22 Q48. General Provisions Contractor shall bear the risk of loss until acceptance. In Addendum II, A8, RTA agreed that builder s risk would end at Substantial Completion but no change was made to amend Contractors risk of loss. Contractor cannot accept the uninsured risk of the work after Substantial Completion. Please clarify that Contractor s risk of loss will also end at Substantial Completion. A48. Please refer to Question No. 49 Q49. General Provisions 14.1, RTA may take possession of or use portions of the work with no relief to Contractor exception for the cost of repairs, rework or

13 renewals due to ordinary wear and tear. In Addendum II, A10, RTA agreed that builder s risk would end at Substantial Completion but there was no acknowledgement that builder s risk would not apply to work put to use. And, no change was made to amend Contractors risk of loss. Contractor cannot accept this uninsured risk. Please clarify so that, except to the extent of Contractor s negligence or the costs necessary to repair, replace or rectify defective material or workmanship, Contractor s risk of loss will end once RTA takes possession of or puts any work to use. A49. The Addendum II stated that Builder s Risk Insurance may end at Substantial completion, which will not be declared until all contract requirements are met in order for RTA to put the final product to use. Therefore Builder s Risk Insurance clearly doesn t apply to work that has been put to use. The Contractor s risk of loss will also end at Substantial Completion, with the exception of Contractor s negligence or the costs necessary to repair, replace or rectify defective material or workmanship. Q50. Curve B-207 has R=625 and shows restraining rail in sheet 177. The Restraining Rail Conditions chart on sheet 185 shows single guard rail for R<600. Please clarify. A50. Restraining Rail is not required on B-207. Q51. The restraining rail on curve B-406 will end 10 into the turnout at Station Should the restraining rail end before the PS? A51. Plans are correct as shown. The restraining rail is to end 10 beyond the PT of the curve, at STA [STA plus 10 ]. The casting for the Turnout begins at STA Note that DWG. #B-TKC-051 shows the casting for the turnout beginning at 5.75 (7-3 minus 18 ) prior to the curve PC location [also the PS], or at STA [PC STA minus 5.75 ]. As such, the restraining rail will not encroach into the turnout casting. Q52. Specification section states that restraining rail should extend 10 beyond the curve onto tangent track. The restraining rail on curves B-207, B208, and B109 appear to start/end 10 past the SC/CS. Is this correct? A52. The extension of the restraining rail limits is defined as the ST/TS point, which is the end of the spiraled curves. Therefore, the restraining rail limits are NOT a function of the position of the SC/CS points. Q53. How many existing insulated joints are to be removed in Bid Item , Remove Insulated Joints on Canal Street Line near Basin St E?

14 A53. There are a total of 4 insulated joints that are to be removed: 2 insulated joints with single running rail and 2 insulated joints with running rail and restraining rail. Q54. Specification 02461, paragraph 2.03 calls for 4500 psi silica fume concrete for the track slab and Specification 03300, paragraph 2.01 calls for 5000 psi structural sand-light weight concrete for the track slab. Which concrete specification is correct? A54. Specification 03300, Paragraph 2.01 is correct. Delete specification Section 02461, subparts 2.03.B, 2.03.C and 2.03.D. Q55. After encapsulation of the Half Grand Union trackwork and subsequent disassembly for transport to the installation site, will a qualified representative need to be present for re-application of encapsulation material at joints. A55. Yes, a qualified representative will need to be present for the re-application of encapsulation material at joints. Bidder is strongly advised to review and understand the special trackwork requirement, including Section 02458, Part Q56. Is the elastomeric grout as shown on sheet 241 required at the cross bonds which are installed prior to encapsulation on the special trackwork? A56. Yes, cross bonds must be encapsulated. Q.57. My company is very interested in providing pricing for the Radio Activated, GPS Based Traffic Signal Preemption and Priority Control System. The specifications are written around a specific product, but the specs afford others the ability to request approval of a substitute product. Information must be sent to the Construction Manager and the Design Manager, however there was no contact information (names, address nor phone numbers) provided so that one could submit documentation for approval. Could you please provide the names and contact information for both positions so that I can submit for approval? Thank you in advance for your help with this matter. A57. The Technical Specifications for this system must be followed and all requested requirements must be met in order to maintain compatibility with the existing DPW s infrastructure. RTA will review any requests for a variance or substitution submitted by the successful bidder after the Contract is fully executed and the Notice to Proceed is issued to the Contractor.

15 Justin Augustine Vice President - Transdev In service to the Regional Transit Authority

Valley Road Main Replacement

Valley Road Main Replacement Bonding Provided Construction Co., Construction, Construction, 5% 5% 5% 5% 5% 5% 5% acknowledged 2 - Bidder Acknowledges Receipt of Addendums there was only 1 Affadivit of Preferential Bidders Status not

More information

PART 4 STANDARD DRAWINGS FOR CONSTRUCTION

PART 4 STANDARD DRAWINGS FOR CONSTRUCTION 4.0. INTRODUCTION PART 4 STANDARD DRAWINGS FOR CONSTRUCTION In this document, Ivins City adopts the most recent edition (currently 2007), including all amendments, of the APWA Utah Chapter s Manual of

More information

MPA Project No. M495-C1 Refrigerated Container Storage Improvements Project Location: Conley Terminal, Boston, MA

MPA Project No. M495-C1 Refrigerated Container Storage Improvements Project Location: Conley Terminal, Boston, MA MPA Project No. M495-C1 Refrigerated Container Storage Improvements Project Location: Conley Terminal, Boston, MA RESPONSES TO QUESTIONS and/or RFI s Date: 11/29/2017 The attention of Contractors submitting

More information

HUSSEY GAY BELL SAVANNAH, GEORGIA

HUSSEY GAY BELL SAVANNAH, GEORGIA HUSSEY GAY BELL SAVANNAH, GEORGIA ------------------------------------------------------------------------------------------------------------ ADDENDUM NO. 3 TO THE CONTRACT DOCUMENTS AND TECHNICAL SPECIFICATIONS

More information

NEWTON COUNTY WATER AND SEWERAGE AUTHORITY RESIDENTIAL, COMMERCIAL, INSTITUTIONAL AND INDUSTRIAL SUBDIVISIONS CONSTRUCTION PLANS CHECK LIST

NEWTON COUNTY WATER AND SEWERAGE AUTHORITY RESIDENTIAL, COMMERCIAL, INSTITUTIONAL AND INDUSTRIAL SUBDIVISIONS CONSTRUCTION PLANS CHECK LIST NEWTON COUNTY WATER AND SEWERAGE AUTHORITY RESIDENTIAL, COMMERCIAL, INSTITUTIONAL AND INDUSTRIAL SUBDIVISIONS CONSTRUCTION PLANS CHECK LIST Project Name Checked By Date Designer Check List marks to be

More information

ADDENDUM NO. 3 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO COM.00030

ADDENDUM NO. 3 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO COM.00030 ADDENDUM NO. 3 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO. 2018-008-COM.00030 To: Prospective Bidders of Record Date: January 8, 2019 The following changes, additions, revisions, and/or deletions

More information

September 21, Mannik Smith Group 1771 North Dixie Highway Monroe, Michigan RE: LA Fitness City File No.: CVLP

September 21, Mannik Smith Group 1771 North Dixie Highway Monroe, Michigan RE: LA Fitness City File No.: CVLP CITY OF ANN ARBOR, MICHIGAN Public Services Area / Engineering 301 E. Huron Street, P.O. Box 8647 Ann Arbor, Michigan 48107 Phone (734) 794-6410 Fax (734) 994-1744 Web: www.a2gov.org Printed on recycled

More information

SECTION III SUBMITTALS AND APPROVALS

SECTION III SUBMITTALS AND APPROVALS SECTION III SUBMITTALS AND APPROVALS In order to expedite the approval process of new water distribution system and sanitary sewer collection system extensions, the Hilton Head No. 1 Public Service District

More information

CHARLES COUNTY GOVERNMENT ITB NO ST. MARK S PUMP STATION UPGRADE

CHARLES COUNTY GOVERNMENT ITB NO ST. MARK S PUMP STATION UPGRADE CHARLES COUNTY GOVERNMENT Department of Fiscal and Administrative Services Purchasing Division Telephone: 301-645-0656 August 30, 2016 ITB NO. 17-07 ST. MARK S PUMP STATION UPGRADE ADDENDUM NUMBER THREE

More information

SECTION III STANDARD DRAWINGS ROYSE CITY GENERAL CONSTRUCTION NOTES & DETAILS

SECTION III STANDARD DRAWINGS ROYSE CITY GENERAL CONSTRUCTION NOTES & DETAILS 9. STANDARD DETAILS SECTION III STANDARD DRAWINGS ROYSE CITY GENERAL CONSTRUCTION NOTES & DETAILS j:\clerical\royse city\1-4086 general services\168-tech const standards review\tcss manual\2018 tcss manual\sec-9a

More information

ADDENDUM #1. April 29, 2009

ADDENDUM #1. April 29, 2009 April 29, 2009 Re: HACC, Central Pennsylvania s Community College Midtown 1 CCTA Phase 2 Solicitation # 09-17 From: Eastern pcm, LLC Construction Manager HACC 212 Locust Street, Suite 604 Harrisburg, PA

More information

PORT OF ST. HELENS SCAPPOOSE INDUSTRIAL AIRPARK PARALLEL TAXIWAY B RELOCATON AIP PROJECT ADDENDUM NO. 1

PORT OF ST. HELENS SCAPPOOSE INDUSTRIAL AIRPARK PARALLEL TAXIWAY B RELOCATON AIP PROJECT ADDENDUM NO. 1 PORT OF ST. HELENS SCAPPOOSE INDUSTRIAL AIRPARK PARALLEL TAXIWAY B RELOCATON AIP PROJECT 3-41-0056-024-2018 ADDENDUM NO. 1 Addendum No. 1 hereby amends the contract documents and drawings for the Scappoose

More information

TOWN of LAKESHORE SITE PLAN CHECKLIST

TOWN of LAKESHORE SITE PLAN CHECKLIST TOWN of LAKESHORE SITE PLAN CHECKLIST Last Revised December 17, 2009 Project Name: Project Location: Date Submitted: Name Phone Number E-mail Address Owner: Contractor/ Engineer: ( ) ( ) Applicant: ( )

More information

CITY OF LA MARQUE CHAPTER GRAPHIC REQUIREMENTS CONSTRUCTION PLAN AND MISCELLANEOUS REQUIREMENTS

CITY OF LA MARQUE CHAPTER GRAPHIC REQUIREMENTS CONSTRUCTION PLAN AND MISCELLANEOUS REQUIREMENTS CITY OF LA MARQUE CHAPTER 2 -------------------------------------------- GRAPHIC REQUIREMENTS CONSTRUCTION PLAN AND MISCELLANEOUS REQUIREMENTS CHAPTER 2 ------------------------------------------------

More information

Renewable Water Resources Greenville, South Carolina. CONTRACT DOCUMENTS Reedy River Basin Sewer Tunnel ADDENDUM IV - CONTRACT REVISIONS.

Renewable Water Resources Greenville, South Carolina. CONTRACT DOCUMENTS Reedy River Basin Sewer Tunnel ADDENDUM IV - CONTRACT REVISIONS. Renewable Water Resources Greenville, South Carolina CONTRACT DOCUMENTS ADDENDUM IV - CONTRACT REVISIONS Prepared by Black & Veatch Corporation Greenville, South Carolina B&V Project No. 192263 October

More information

STANDARD BID ITEM NUMBERS

STANDARD BID ITEM NUMBERS 10701 TRAFFIC CONTROL LUMP SUM 10702 Traffic Control for Storm Sewer Installation LUMP SUM 10703 Traffic Control for Water Main Installation LUMP SUM 10704 Traffic Control for Sanitary Sewer Installation

More information

June 10, 2014 BOARD OF COUNTY COMMISSIONERS ORANGE COUNTY, FLORIDA

June 10, 2014 BOARD OF COUNTY COMMISSIONERS ORANGE COUNTY, FLORIDA June 10, 2014 BOARD OF COUNTY COMMISSIONERS ORANGE COUNTY, FLORIDA ADDENDUM NO. 5 BID NO. Y14-792 PH IFB EAST SERVICE AREA POTABLE WATER AND RECLAIMED WATER STORAGE AND REPUMP FACILITY BID OPENING: June

More information

November 16, 2017 BOARD OF COUNTY COMMISSIONERS ORANGE COUNTY, FLORIDA. Y CH / Addendum #6 SHERRY DRIVE BRIDGE REPLACEMENT

November 16, 2017 BOARD OF COUNTY COMMISSIONERS ORANGE COUNTY, FLORIDA. Y CH / Addendum #6 SHERRY DRIVE BRIDGE REPLACEMENT November 16, 2017 BOARD OF COUNTY COMMISSIONERS ORANGE COUNTY, FLORIDA Y18-703-CH / Addendum #6 SHERRY DRIVE BRIDGE REPLACEMENT REVISED BID OPENING DATE: DECEMBER 5, 2017 This addendum is hereby incorporated

More information

INVITATION FOR BID (IFB) IFB NO. GSWA

INVITATION FOR BID (IFB) IFB NO. GSWA INVITATION FOR BID (IFB) IFB NO. GSWA-005-16 AGAT AND MALOJLOJ RESIDENTIAL TRANSFER STATION IMPROVEME AND DEDEDO RESIDENTIAL TRANSFER STATION CLOSURE ADDENDUM NO. 6 September 22, 2016 ALL BIDDERS MUST

More information

December 31, 2015 A. THE BID OPENING DATE IS UNCHANGED. B. Questions, Additions, and Deletions

December 31, 2015 A. THE BID OPENING DATE IS UNCHANGED. B. Questions, Additions, and Deletions December 31, 2015 BOARD OF COUNTY COMMISSIONERS ORANGE COUNTY, FLORIDA Y16-721-MM / ADDENDUM No. 1 ORANGE COUNTY CONVENTION CENTER PHASE III VALENCIA BALLROOM RENOVATION Bid Opening Date: January 12, 2016

More information

UTILITY AND STREET CONSTRUCTION PLAN REQUIREMENTS SECTION 1

UTILITY AND STREET CONSTRUCTION PLAN REQUIREMENTS SECTION 1 UTILITY AND STREET CONSTRUCTION PLAN REQUIREMENTS SECTION 1 ENGINEERING STANDARDS FOR UTILITY AND STREET CONSTRUCTION PLANS MARCH 2014 CONSTRUCTION PLAN SHEET FORMAT REQUIREMENTS REPRODUCIBLE MYLAR 1.

More information

A. This section specifies procedural requirements for Shop Drawings, product data, samples, and other miscellaneous Work-related submittals.

A. This section specifies procedural requirements for Shop Drawings, product data, samples, and other miscellaneous Work-related submittals. SECTION 01300 PART 1 GENERAL 1.1 SECTION INCLUDES A. Description of Requirements B. Submittal Procedures C. Specific Submittal Requirements D. Action on Submittals E. Repetitive Review 1.2 DESCRIPTION

More information

SECTION 39 - MANHOLES TABLE OF CONTENTS

SECTION 39 - MANHOLES TABLE OF CONTENTS SECTION 39 - MANHOLES TABLE OF CONTENTS Section Page 39-1 GENERAL... 39.1 39-2 PRECAST CONCRETE MANHOLES... 39.1 39-2.01 Precast Concrete Sewer Manholes... 39.1 39-2.02 Precast Concrete Storm Drain Manholes...

More information

ACWWA DRAWING SUBMITTAL INFORMATION - UTILITY DRAWING REQUIREMENTS

ACWWA DRAWING SUBMITTAL INFORMATION - UTILITY DRAWING REQUIREMENTS ACWWA DRAWING SUBMITTAL INFORMATION - UTILITY DRAWING REQUIREMENTS Detailed construction drawings for system extensions shall be prepared for approval with a submittal to the Authority. All construction

More information

This addendum forms a part of the Contract Documents dated: August 10, 2012.

This addendum forms a part of the Contract Documents dated: August 10, 2012. Addendum # 1 Date Issued: August 28, 2012 Issued By: Project: Owner: Renker Eich Parks Architects 1609 Dr. Martin Luther King Street North St. Petersburg, Florida 33704 Ph# (727) 821-2986 Fax # (727) 896-4911

More information

September 6, 2018 CITY OF BERKELEY SHATTUCK RECONFIGURATION AND PEDESTRIAN SAFETY PROJECT SPECIFICATION NO C ADDENDUM NO.

September 6, 2018 CITY OF BERKELEY SHATTUCK RECONFIGURATION AND PEDESTRIAN SAFETY PROJECT SPECIFICATION NO C ADDENDUM NO. Department of Public Works Transportation Division September 6, 2018 CITY OF BERKELEY SHATTUCK RECONFIGURATION AND PEDESTRIAN SAFETY PROJECT SPECIFICATION NO. 17-11090-C ADDENDUM NO. 3 Dear Bidder: The

More information

3. The PAC (Permit Application Center) will notify the design professional of plan review results.

3. The PAC (Permit Application Center) will notify the design professional of plan review results. Planning and Development Dept. Infrastructure Division P.O. Box 11706, or 155 Johnston Street Rock Hill, South Carolina 29731-1706 Phone: 803-329-5515 FAX: 803-329-7228 www.cityofrockhill.com AS-BUILT

More information

SECTION CLOSEOUT SUBMITTALS SECTION CLOSEOUT SUBMITTALS

SECTION CLOSEOUT SUBMITTALS SECTION CLOSEOUT SUBMITTALS PART 1 GENERAL 1.01 SECTION INCLUDES A. Project Record Documents. B. Operation and Maintenance Manuals. C. Warranties and bonds. 1.02 RELATED REQUIREMENTS SECTION 01 78 00 A. Section 01 30 00 - Administrative

More information

WATER MAIN ALONG ENTRANCE TO ENCINO PS / HWY 281 TO ENCINO TANK Solicitation Number: CO Job No.:

WATER MAIN ALONG ENTRANCE TO ENCINO PS / HWY 281 TO ENCINO TANK Solicitation Number: CO Job No.: WATER MAIN ALONG ENTRANCE TO ENCINO PS / HWY 281 TO ENCINO TANK Solicitation Number: CO-00111 Job No.: 16-7003 To Respondent of Record: ADDENDUM 2 July 5, 2017 This addendum, applicable to work referenced

More information

SECTION SUBMITTAL PROCEDURES

SECTION SUBMITTAL PROCEDURES SECTION 01330 SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 DESCRIPTION A. Scope: 1. CONTRACTOR shall provide submittals in accordance with the General Conditions as modified by the Supplementary Conditions,

More information

Anticipated schedule, Page 2. Change the Contract Term from 635 Days to be 1,127 Days.

Anticipated schedule, Page 2. Change the Contract Term from 635 Days to be 1,127 Days. This addendum is hereby made part of the Request for Bid for the above-named project and shall be taken into consideration by all firms preparing a submittal on this project. Acknowledge receipt of this

More information

ADDENDUM NO. 02 July 31, 2012

ADDENDUM NO. 02 July 31, 2012 Post Point Wastewater Treatment Plant Improvements Owner: Engineer: GC/CM: City of Bellingham Carollo Engineers Mortenson Construction ADDENDUM NO. 02 July 31, 2012 THIS ADDENDUM MUST BE ACKNOWLEDGED ON

More information

Facility Services Subgroup Preface for Divisions 21` through 28

Facility Services Subgroup Preface for Divisions 21` through 28 Facility Services Subgroup Preface for Divisions 21` through 28 1.1 EXECUTIVE SUMMARY A. This document provides standards for the Consultants and Contractors producing mechanical and electrical design

More information

SAUSALITO-MARIN CITY SANITARY DISTRICT MISCELLANEOUS UPGRADES PROJECT. Addendum No. 2

SAUSALITO-MARIN CITY SANITARY DISTRICT MISCELLANEOUS UPGRADES PROJECT. Addendum No. 2 SAUSALITO-MARIN CITY SANITARY DISTRICT MISCELLANEOUS UPGRADES PROJECT Addendum No. 2 The following shall modify the Contract Documents. The work shall be accomplished in accordance with such modifications.

More information

2. What are the estimated volumes for the Residuum Harvesting See response to Question 1

2. What are the estimated volumes for the Residuum Harvesting See response to Question 1 No. Question Answer 1. What are the approximate earthwork quantities for this job? FBP approximate quantities will be provided via amendment with or before the CADD files. Contractor is still responsible

More information

SPECIFICATIONS FOR THE INSTALLATION OF CONDUIT SYSTEMS IN RESIDENTIAL SUBDIVISIONS. Notification of Completed Conduit Sections

SPECIFICATIONS FOR THE INSTALLATION OF CONDUIT SYSTEMS IN RESIDENTIAL SUBDIVISIONS. Notification of Completed Conduit Sections SPECIFICATIONS FOR THE INSTALLATION OF CONDUIT SYSTEMS IN RESIDENTIAL SUBDIVISIONS Section 1 Definitions 2 Scope of Work 3 Extent of Work 4 Inspection and Performance of Work 5 Trenching 6 Duct Installation

More information

ADDENDUM NO. 1 TO THE CONTRACT DOCUMENTS AND SPECIFICATIONS DATED JULY 2017 FLORIDA GOVERNMENTAL UTILITY AUTHORITY PROJECT NO.

ADDENDUM NO. 1 TO THE CONTRACT DOCUMENTS AND SPECIFICATIONS DATED JULY 2017 FLORIDA GOVERNMENTAL UTILITY AUTHORITY PROJECT NO. ADDENDUM NO. 1 TO THE CONTRACT DOCUMENTS AND SPECIFICATIONS DATED JULY 2017 FLORIDA GOVERNMENTAL UTILITY AUTHORITY PROJECT NO. PS 061 SEVEN SPRINGS WASTEWATER TREATMENT FACILITY IMPROVEMENTS PASCO COUNTY,

More information

Anne Arundel County Dept. of Inspections and Permits Water Sewer Plan Checklist

Anne Arundel County Dept. of Inspections and Permits Water Sewer Plan Checklist Project Name Project Number Engineer Plans are to be designed based on the standards set forth in the Anne Arundel County Design Manual Standards and Specifications, and all other manuals as stipulated

More information

Existing and proposed contours at 1-foot intervals. The fill and/or excavation quantities in cubic yards.

Existing and proposed contours at 1-foot intervals. The fill and/or excavation quantities in cubic yards. PLAN REQUIREMENTS The plans for street design shall conform to the requirements of Sections 3 and 4. The following requirements shall also be shown on the plans where applicable. Road and Storm Plans:

More information

List of Figures. List of Forms

List of Figures. List of Forms City of Columbia Engineering Regulations PART 1: SUBMISSION OF PLANS Table of Contents Paragraph Description Page No. 1.1 General 1-1 1.2 Engineer s Report 1-1 1.3 Plans 1-3 1.4 Revisions to Approved Plan

More information

Renewable Water Resources Greenville, South Carolina. CONTRACT DOCUMENTS Reedy River Basin Sewer Tunnel ADDENDUM III - CONTRACT REVISIONS.

Renewable Water Resources Greenville, South Carolina. CONTRACT DOCUMENTS Reedy River Basin Sewer Tunnel ADDENDUM III - CONTRACT REVISIONS. Renewable Water Resources Greenville, South Carolina CONTRACT DOCUMENTS ADDENDUM III - CONTRACT REVISIONS Prepared by Black & Veatch Corporation Greenville, South Carolina B&V Project No. 192263 September

More information

PROJECT TITLE PROJECT NO: CONTRACT TITLE UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA

PROJECT TITLE PROJECT NO: CONTRACT TITLE UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA SECTION 01 78 00 CLOSE-OUT SUBMITTALS PART 1 - GENERAL 1.1 GUARANTEES A. Compile and submit guarantees, bonds, and service and maintenance contracts specified in the individual B. Guarantees from Subcontractors

More information

MPA Project No. M545-C2 Project Title: New Berth 10 Project - Phase II Location: Conley Terminal, South Boston, Massachusetts

MPA Project No. M545-C2 Project Title: New Berth 10 Project - Phase II Location: Conley Terminal, South Boston, Massachusetts MPA Project No. M545-C2 Project Title: New Berth 10 Project - Phase II Location: Conley Terminal, South Boston, Massachusetts RESPONSES TO QUESTIONS and/or RFI s # 3 Date: 09/14/18 The attention of Contractors

More information

SECTION MANHOLES

SECTION MANHOLES SECTION 02601 MANHOLES PART 1 GENERAL 1.01 SCOPE OF WORK A. WORK required under this section consists of all materials, accessories, equipment, tools, and labor required to install precast concrete standard

More information

CHECKLIST PRELIMINARY SUBDIVISION AND PRELIMINARY SITE PLAN

CHECKLIST PRELIMINARY SUBDIVISION AND PRELIMINARY SITE PLAN N/A Waiver (1) Four (4) copies of application form. (2) Fifteen (15) copies of plan (3) Subdivision/site plan application fee & professional review escrow deposit (4) Variance application fee & professional

More information

DIVISION 1 - GENERAL REQUIREMENTS SECTION SUBMITTALS

DIVISION 1 - GENERAL REQUIREMENTS SECTION SUBMITTALS DIVISION 1 - GENERAL REQUIREMENTS SECTION 01300 - SUBMITTALS PART 1 - GENERAL 1.1 STIPULATIONS A. The section "Special Requirements" forms a part of this section by this reference thereto and shall have

More information

BRASELTON WATER AND WASTEWATER DEPARTMENT CONSTRUCTION PLAN REVIEW CHECKLIST May 2006

BRASELTON WATER AND WASTEWATER DEPARTMENT CONSTRUCTION PLAN REVIEW CHECKLIST May 2006 Project Name: BRASELTON WATER AND WASTEWATER DEPARTMENT CONSTRUCTION PLAN REVIEW CHECKLIST May 2006 Phase: Unit: # Lots: Development Type (residential, commercial, industrial, etc.) Braselton Project No.

More information

City of Waltham Purchasing Department Waltham, Massachusetts ADDENDUM NO. 2

City of Waltham Purchasing Department Waltham, Massachusetts ADDENDUM NO. 2 City of Waltham Purchasing Department Waltham, Massachusetts 02452 ADDENDUM NO. 2 Plans & Specifications for: Elsie Turner Field & Graverson Playground, Waltham, MA TO: ALL PLAN HOLDERS This Addendum No.

More information

RFP # CULVER CITYBUS: BUS SIGNAL PRIORITY SYSTEMS PROJECT Response to Questions

RFP # CULVER CITYBUS: BUS SIGNAL PRIORITY SYSTEMS PROJECT Response to Questions RFP #1587 - CULVER CITYBUS: BUS SIGNAL PRIORITY SYSTEMS PROJECT Response to Questions 1. Question: Spec requires connects to bitrans, are you going to modify the specs? Answer: City of Culver City s ATCS

More information

CITY AND COUNTY OF SAN FRANCISCO PUBLIC UTILITIES COMMISSION WASTEWATER ENTERPRISE

CITY AND COUNTY OF SAN FRANCISCO PUBLIC UTILITIES COMMISSION WASTEWATER ENTERPRISE San Francisco Water Power Sewer SOUTHEAST WATER POLLUTION CONTROL PLANT BUILDINGS 040, 041, 044, 060, 061, 062, 925, AND 960 MECHANICAL IMPROVEMENTS CONTRACT NO. WW-654 ADDENDUM NO. 3 Signatures: 9i;,.,,:.._\

More information

ROUTES: 65 SECTIONS: miles in length. THE FOLLOWING ITEMS AND APPROXIMATE QUANTITIES ARE INVOLVED:

ROUTES: 65 SECTIONS: miles in length. THE FOLLOWING ITEMS AND APPROXIMATE QUANTITIES ARE INVOLVED: ARKANSAS DEPARTMENT OF TRANSPORTATION CA0801 HWY. 110 - CLINTON (WIDENING) (S) FEDERAL AID PROJECT ACNHPP-0071(31) THE PURPOSE OF THIS PROJECT IS TO WIDEN HIGHWAY 65 IN VAN BUREN COUNTY. THIS PROJECT CONSISTS

More information

LOWNDES COUNTY ENGINEERING PLAN REVIEW CHECKLIST. Design Professional: Phone: Developer: Phone: 2 nd Submittal (No Fee)

LOWNDES COUNTY ENGINEERING PLAN REVIEW CHECKLIST. Design Professional: Phone: Developer: Phone: 2 nd Submittal (No Fee) MEMORANDUM MICHAEL B. FLETCHER, P.E. COUNTY ENGINEER 327 N. Ashley Street Valdosta, GA 31601 Telephone: (229) 671-2424 Fax: (229) 245-5299 mfletcher@lowndescounty.com LOWNDES COUNTY ENGINEERING PLAN REVIEW

More information

Section Meetings Section Material and Equipment. None Required

Section Meetings Section Material and Equipment. None Required January 2000 Page 1 of 8 PART 1 GENERAL 1.01 OTHER CONTRACT DOCUMENTS 1.02 DESCRIPTION OF WORK 1.03 RELATED WORK PART 2 PRODUCTS The General Conditions of the Contract, General Requirements and Supplemental

More information

Answer: Qualification statement should be provided with the bid.

Answer: Qualification statement should be provided with the bid. Little Diversified Architectural Consulting, Inc. 5815 Westpark Drive Charlotte, North Carolina 28217 Phone: 704-525-6350 Fax: 704-561-8700 Lincoln County Probation Renovation 208 N. Government Street

More information

.1 Applicability: These criteria shall be applied as follows:

.1 Applicability: These criteria shall be applied as follows: DESIGN CRITERIA DIVISION 4800 STREET LIGHTING 4801 GENERAL: These criteria shall be adhered to for the design of all publiclyfinanced or privately-financed traffic signal systems to be installed in the

More information

1. Land survey Work. 2. Civil and Structural engineering services.

1. Land survey Work. 2. Civil and Structural engineering services. SECTION 01050 FIELD ENGINEERING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division-1 Specification

More information

MPA Project No. M495-C1 Refrigerated Container Storage Improvements Project Location: Conley Terminal, Boston, MA

MPA Project No. M495-C1 Refrigerated Container Storage Improvements Project Location: Conley Terminal, Boston, MA MPA Project No. M495-C1 Refrigerated Container Storage Improvements Project Location: Conley Terminal, Boston, MA RESPONSES TO QUESTIONS and/or RFI s Date: 12/7/2017 The attention of Contractors submitting

More information

JEFFERSON LAB TECHNICAL ENGINEERING & DEVELOPMENT FACILITY (TEDF ONE) Newport News, Virginia

JEFFERSON LAB TECHNICAL ENGINEERING & DEVELOPMENT FACILITY (TEDF ONE) Newport News, Virginia BULLETIN NO. 6 TO THE PLANS AND SPECIFICATIONS FOR JEFFERSON LAB TECHNICAL ENGINEERING & DEVELOPMENT FACILITY (TEDF ONE) Newport News, Virginia EwingCole Architects.Engineers.Interior Designers.Planners

More information

ADDENDUM TO RFQ/P DOCUMENTS PROJECT # ADDENDUM: #01

ADDENDUM TO RFQ/P DOCUMENTS PROJECT # ADDENDUM: #01 ADDENDUM TO RFQ/P DOCUMENTS PROJECT #14-013 ADDENDUM: #01 Solano Community College District SCCD REQUEST FOR QUALIFICATIONS/PROPOSAL Project: HVAC & EMS Efficiency Project Implementation Date: 03/28/2014

More information

Clarifications in italics added July 2018

Clarifications in italics added July 2018 SECTION 10000 RECORD DRAWING CHECKLIST Clarifications in italics added July 2018 All entities who construct public infrastructure, private streets, private storm drain collection systems and travel lanes,

More information

TG Glazing Design-Build

TG Glazing Design-Build TG08.1 - Glazing Design-Build Question No. 0040 0041 0042 0043 Submission Date Question 7.14.2011 Is it acceptable to use 304 stainless in lieu of 316 where the material will be painted per 09 97 15? 7.14.2011

More information

Standard Specifications

Standard Specifications Standard Specifications PART 1.00 GENERAL 1.01 DECRIPTION SECTION 02620 PRECAST REINFORCED CONCRETE SANITARY MANHOLES A. Work included: The Contractor shall furnish all labor, materials, equipment, and

More information

SECTION G ESTIMATE OF QUANTITIES

SECTION G ESTIMATE OF QUANTITIES PROJECT STATE OF SOUTH DAKOTA NH 2115(45)87 SHEET G2 TOTAL SHEETS G27 SECTION G ESTIMATE OF QUANTITIES BID ITEM NUMBER ITEM QUANTITY UNIT 009E0010 Mobilization Lump Sum LS 560E0068 7'x3' Precast Concrete

More information

744 Kent Minh, Project Engineer

744 Kent Minh, Project Engineer San Francisco Water Power Sewer Senricos of the San Francisco Public Utilities Commis 'on SOUTHEAST WATER POLLUTION CONTROL PLANT BUILDINGS 040, 041, 044, 060, 061, 062, 925, AND 960 MECHANICAL IMPROVEMENTS

More information

WATER & SEWER CONSTRUCTION SITE PLAN DESIGN SUMMARY COMMERCIAL & RESIDENTIAL

WATER & SEWER CONSTRUCTION SITE PLAN DESIGN SUMMARY COMMERCIAL & RESIDENTIAL WATER & SEWER CONSTRUCTION SITE PLAN DESIGN SUMMARY COMMERCIAL & RESIDENTIAL This summary is not all inclusive of the requirements set forth by the York County Planning & Development Services, York County

More information

***************************************************************************** DRAFT UFGS- 01 XX XX (FEB 2014)

***************************************************************************** DRAFT UFGS- 01 XX XX (FEB 2014) DRAFT UFGS- 01 XX XX (FEB 2014) ------------------------ Drafting Activity: USACE UNIFIED FACILITIES GUIDE SPECIFICATION SECTION TABLE OF CONTENTS DIVISION 01 GENERAL REQUIREMENTS SECTION 01 XX XX (FEB

More information

SAN FRANCISCO UNIFIED SCHOOL DISTRICT 2011 PROPOSITION A BOND PROGRAM Miraloma ES & Sunnyside ES Green Schoolyard ADDENDUM NO. 1

SAN FRANCISCO UNIFIED SCHOOL DISTRICT 2011 PROPOSITION A BOND PROGRAM Miraloma ES & Sunnyside ES Green Schoolyard ADDENDUM NO. 1 SAN FRANCISCO UNIFIED SCHOOL DISTRICT 2011 PROPOSITION A BOND PROGRAM Miraloma ES & Sunnyside ES Green Schoolyard ADDENDUM NO. 1 PROJECT: Miraloma Elementary School DATE: March 24, 2016 175 Omar Way, SF,

More information

REVISION #1. Section. fire alarm B. C. the hot. intent of. required. manufacturer. materials. C. Warranty

REVISION #1. Section. fire alarm B. C. the hot. intent of. required. manufacturer. materials. C. Warranty HOT AISLE CONTAINMENT SYSTEM (HACS) REVISION #1 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. B. C. Drawings and general provisions of the Contract, including General and Supplementary. Conditions apply to

More information

B-PERMIT PLAN CHECK MANUAL

B-PERMIT PLAN CHECK MANUAL B-PERMIT PLAN CHECK MANUAL 5. SEWER PLANS Sewer Plans are usually submitted in conjunction with Street Plans to meet the requirements of conditions imposed on a Planning or Zoning action. In some cases

More information

INDEX OF SPECIFICATIONS SECTION F SPECIAL CONDITIONS DIVISION 1 - GENERAL REQUIREMENTS:

INDEX OF SPECIFICATIONS SECTION F SPECIAL CONDITIONS DIVISION 1 - GENERAL REQUIREMENTS: INDEX OF SPECIFICATIONS SECTION F SPECIAL CONDITIONS DIVISION 1 - GENERAL REQUIREMENTS: 013300 SUBMITTAL PROCEDURES 018116 CONSTRUCTION WASTE MANAGEMENT DIVISION 2 EXISTING CONDITIONS: 023000 EARTHWORK

More information

CITY OF TUMWATER 555 ISRAEL RD. SW, TUMWATER, WA (360)

CITY OF TUMWATER 555 ISRAEL RD. SW, TUMWATER, WA (360) CITY OF TUMWATER 555 ISRAEL RD. SW, TUMWATER, WA 98501 (360) 754-4180 Email: cdd@ci.tumwater.wa.us WATER-SEWER-STREET-STORM (IN CITY) Submittal Checklist TUM - RCVD BY DATE STAMP APPLICANT INFORMATION

More information

CITY OF LOMPOC DEVELOPMENT ASSISTANCE BROCHURE ENCROACHMENT PERMITS AND PUBLIC IMPROVEMENT PLANS

CITY OF LOMPOC DEVELOPMENT ASSISTANCE BROCHURE ENCROACHMENT PERMITS AND PUBLIC IMPROVEMENT PLANS CITY OF LOMPOC DEVELOPMENT ASSISTANCE BROCHURE E-10 ENCROACHMENT PERMITS AND PUBLIC IMPROVEMENT PLANS The City of Lompoc has determined that the Engineering Division should administer and issue Encroachment

More information

STREETSCAPE FEASIBILITY TERMS OF REFERENCE

STREETSCAPE FEASIBILITY TERMS OF REFERENCE Introduction STREETSCAPE FEASIBILITY TERMS OF REFERENCE As outlined in the Official Plan, Section 9, Build A Desirable Urban Form, Mississauga will transform the public realm to create a strong sense of

More information

Clarification # 1. Request for Tender T Sackville Cross Road Stormwater System Renewal

Clarification # 1. Request for Tender T Sackville Cross Road Stormwater System Renewal August 24, 206 Clarification # Request for Tender T30.206 Sackville Cross Road Storwater Syste Renewal To All Bidders of T30.206: Plse note: the following clarification is in response to questions received

More information

CITY OF BEVERLY HILLS Department of Public Works and Transportation Civil Engineering Division STREET/ALLEY IMPROVEMENT PLAN REVIEW CHECKLIST

CITY OF BEVERLY HILLS Department of Public Works and Transportation Civil Engineering Division STREET/ALLEY IMPROVEMENT PLAN REVIEW CHECKLIST CITY OF BEVERLY HILLS Department of Public Works and Transportation Civil ing Division STREET/ALLEY IMPROVEMENT PLAN REVIEW CHECKLIST The following checklist consists of the minimum requirements for preparation

More information

CHAPTER 29 PROJECT COMPLETION DOCUMENTS

CHAPTER 29 PROJECT COMPLETION DOCUMENTS CHAPTER 29 PROJECT COMPLETION DOCUMENTS PROJECT COMPLETION Upon completion of traffic control signal system and lighting projects, there are forms and checklists to ensure that the project is closed out

More information

ROWAN UNIVERSITY 201 MULLICA HILL ROAD GLASSBORO, NEW JERSEY 08028

ROWAN UNIVERSITY 201 MULLICA HILL ROAD GLASSBORO, NEW JERSEY 08028 THE CENTER FOR RESEARCH AND EDUCATION IN ADVANCED TRANSPORTATION ENGINEERING SYSTEMS (CREATEs) ISSUED FOR BID - CONTRACT - 02 201 MULLICA HILL ROAD GLASSBORO, NEW JERSEY 08028 ALL DIMENSIONS MUST BE VERIFIED

More information

East Central College

East Central College SECTION 013300 - SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

Survey Data and TOPO Checklist

Survey Data and TOPO Checklist Checklists Survey Data and TOPO Preliminary Plan Field Review Plans o Field Review Erosion Control Right-of-Way and Utility Meeting Plans Final Plan Field Review Plans Methods of Plan Markups Plan-in-Hand

More information

Attached is Addendum No. 2 to SEPTA Sealed Bid APES, Install DC Stinger Distribution System - SEPTA Fern Rock Car House.

Attached is Addendum No. 2 to SEPTA Sealed Bid APES, Install DC Stinger Distribution System - SEPTA Fern Rock Car House. Dear Sir/Madam: Attached is Addendum No. 2 to SEPTA Sealed Bid 17-00222-APES, Install DC Stinger Distribution System - SEPTA Fern Rock Car House. The Bid due date and time is changed from Thursday, Nov.

More information

SECTION SUBMITTALS PART 1 - GENERAL 1.01 RELATED DOCUMENTS

SECTION SUBMITTALS PART 1 - GENERAL 1.01 RELATED DOCUMENTS SECTION 01300 SUBMITTALS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and other Division-1 Specification Sections,

More information

Appendix C Construction Details

Appendix C Construction Details 7172 Kennedy Road Warrenton, Virginia 20187 Appendix C Construction Details November 2017 TABLE OF CONTENTS THRUST BLOCKS Anchorage for 11 1/4 o, 22 1/2 o & 45 o Upper Vertical Bends... AV 01 Buttresses

More information

SECTION OPERATION AND MAINTENANCE DATA

SECTION OPERATION AND MAINTENANCE DATA SECTION 01787 OPERATION AND MAINTENANCE DATA PART 1 GENERAL 1.01 SUMMARY A. Compile product data and related information appropriate for OWNER's maintenance and operation of products furnished under Contract.

More information

SECTION ADMINISTRATIVE REQUIREMENTS SECTION ADMINISTRATIVE REQUIREMENTS

SECTION ADMINISTRATIVE REQUIREMENTS SECTION ADMINISTRATIVE REQUIREMENTS PART 1 GENERAL 1.01 SECTION INCLUDES A. Project Coordination. B. Preconstruction meeting. C. Progress meetings. D. Preinstallation conferences. E. Requests for information (RFI). F. Coordination drawings.

More information

SECTION MANHOLES

SECTION MANHOLES SECTION 33 05 13 MANHOLES PART 1 GENERAL 1.01 SECTION INCLUDES A. CONTRACTOR shall furnish and install precast concrete manhole base, sections, adjusting rings, steps, and manhole ring and cover, complete.

More information

B.2 MAJOR SUBDIVISION PRELIMINARY PLAN CHECKLIST

B.2 MAJOR SUBDIVISION PRELIMINARY PLAN CHECKLIST B.2 MAJOR SUBDIVISION PRELIMINARY PLAN CHECKLIST YES* GENERAL SUBMISSION ITEMS Does the submission include: 1. Thirteen (13) copies of completed Application Form? 2. Thirteen (13) copies of the Preliminary

More information

CITY OF BEVERLY HILLS Department of Public Works and Transportation Civil Engineering Division STORM DRAIN IMPROVEMENT PLAN REVIEW CHECKLIST

CITY OF BEVERLY HILLS Department of Public Works and Transportation Civil Engineering Division STORM DRAIN IMPROVEMENT PLAN REVIEW CHECKLIST CITY OF BEVERLY HILLS Department of Public Works and Transportation Civil ing Division STORM DRAIN IMPROVEMENT PLAN REVIEW CHECKLIST The following checklist consists of the minimum requirements for preparation

More information

SECTION 100 PRELIMINARY CONSIDERATIONS & INSTRUCTIONS

SECTION 100 PRELIMINARY CONSIDERATIONS & INSTRUCTIONS SECTION 100 PRELIMINARY CONSIDERATIONS & INSTRUCTIONS 101 General 102 Submittal Requirements A. Initial Submittal B. Second Submittal 103 Plan Requirements A. Subdivisions B. Site Plans 104 Approval of

More information

RAIL PANEL AT TRANSITION SECTION PLAN - POST DETAIL PLAN - TUBE SPLICE. Colorado Department of Transportation. Staff Bridge Branch

RAIL PANEL AT TRANSITION SECTION PLAN - POST DETAIL PLAN - TUBE SPLICE. Colorado Department of Transportation. Staff Bridge Branch Limits of pay length for Bridge RailType 10M (For post spacing, see Dwg. No. B ) B60610 (Use with B60610A) 8 min. 1 max. 8 min. 1 max. 10 0 Max. 10 0 Max. post spacing 10 0 Max. 2 5 Post 1 x 1 slotted

More information

City of Beaumont. Public Works Engineering. Street Improvement Plan Checklist REV 4/18/16

City of Beaumont. Public Works Engineering. Street Improvement Plan Checklist REV 4/18/16 City of Beaumont Public Works Engineering Project Name: TR: Project No.: Date: Street Improvement Plan Checklist Chk A. All Sheets 1. 24" x 36" 2. Signed by the engineer-of-work 3. Marked with the contact

More information

SPECIFICATIONS FOR NEW UNDERGROUND RESIDENTIAL DISTRIBUTION SYSTEMS

SPECIFICATIONS FOR NEW UNDERGROUND RESIDENTIAL DISTRIBUTION SYSTEMS Page: 4-1 4.0 URD Process and Documentation Requirements 4.1 Process Steps The process of developing underground distribution facilities in a residential area consists of 10 major steps, which are summarized

More information

MSD STANDARD DRAWINGS LOUISVILLE AND JEFFERSON COUNTY METROPOLITAN SEWER DISTRICT 700 WEST LIBERTY STREET LOUISVILLE, KENTUCKY

MSD STANDARD DRAWINGS LOUISVILLE AND JEFFERSON COUNTY METROPOLITAN SEWER DISTRICT 700 WEST LIBERTY STREET LOUISVILLE, KENTUCKY MSD M etr o p olitan S e w e r Di s t r ict STANDARD DRAWINGS LOUISVILLE AND JEFFERSON COUNTY METROPOLITAN SEWER DISTRICT 700 WEST LIBERTY STREET LOUISVILLE, KENTUCKY 40203-1911 STANDARD DRAWINGS DIVISION

More information

Ecological Restoration Drafting & Design Guidelines

Ecological Restoration Drafting & Design Guidelines Ecological Restoration Drafting & Design Guidelines Version 2.0 July 2017 Philadelphia Water Ecological Restoration Drafting & Design Guidelines Table of Contents 1.0 INTRODUCTION...2 2.0 GENERAL PLAN

More information

REQUIREMENTS. for ENGINEERING SERVICES PUBLIC CONSTRUCTION PROJECTS

REQUIREMENTS. for ENGINEERING SERVICES PUBLIC CONSTRUCTION PROJECTS REQUIREMENTS for ENGINEERING SERVICES on PUBLIC CONSTRUCTION PROJECTS April, 2007 David W. Johnson Senior Engineer Design & Construction Requirements for Engineering Services on Public Construction Projects

More information

-and- (the Artist ) maquette means the drawing or model, prepared by the Artist, of the proposed Art Work;

-and- (the Artist ) maquette means the drawing or model, prepared by the Artist, of the proposed Art Work; THIS AGREEMENT made in triplicate this th day of, 200 BETWEEN: CITY OF OTTAWA (the City -and- (the Artist WHEREAS the Council of the former City of Ottawa, an old municipality as defined in the City of

More information

KC Water Rules and Regulations For Water Main Extensions and Relocations

KC Water Rules and Regulations For Water Main Extensions and Relocations KC Water Rules and Regulations For Water Main Extensions and Relocations MAY 2017 NOTE: Changes from 2016 are highlighted in yellow and appear on Pages 5, 8, 10-11, 13, and 15. Additional changes made

More information

Construction Specification for Watermain and Water Service Tracer Wire

Construction Specification for Watermain and Water Service Tracer Wire Engineering and Construction Services Division Standard Specifications for Sewers and Watermains TS 7.40 April 2013 for Watermain and Water Service Tracer Wire Table of Contents TS 7.40.01 SCOPE... 2 TS

More information

DESIGN GUIDELINES (SD) COUNTY OF ALAMEDA PUBLIC WORKS AGENCY 399 ELMHURST STREET HAYWARD, CA

DESIGN GUIDELINES (SD) COUNTY OF ALAMEDA PUBLIC WORKS AGENCY 399 ELMHURST STREET HAYWARD, CA DESIGN GUIDELINES (SD) COUNTY OF ALAMEDA PUBLIC WORKS AGENCY 399 ELMHURST STREET HAYWARD, CA 94544-1395 PUBLIC WORKS DESIGN GUIDELINES TABLE OF CONTENTS SD-100 SERIES SPECIAL DRAWINGS SD-100 8/1991 SILT

More information

City of Massillon Site Plan Checklist

City of Massillon Site Plan Checklist City of Massillon Site Plan Checklist The following information MUST be included with all Site Plans submitted for review and processing in order to constitute a complete Site Plan Package. Incomplete

More information

APPLICATION FORM FOR INFRASTRUCTURE NOC

APPLICATION FORM FOR INFRASTRUCTURE NOC APPLICATION FORM FOR INFRASTRUCTURE NOC Submission Type New Resubmission (Previous Reference No): Arch. Str. HVAC EHS Others Revision /Amendment (Infrastructure NOC Reference No): Arch. Str. HVAC EHS Others

More information