1 Contents Data Sheet DS7U Rev. 9 FSM Electromagnetic Flowmeter The all-purpose flowmeter for conductive fluids Function Electromagnetic flowmeters can be used to accurately measure the flowrate of liquids, slurries, pastes and sludges with an electrical conductivity of at least μs/cm (opt. /. μs/cm). Applications The system is specially designed to measure liquids in the pulp & paper and food & beverage industries. It can be used to measure fast changing processes, two phase liquids, continuous and pulsating flows (piston pump application). Benefits Digital signal processing (DSP) and zero stability ensure long-term stability and accuracy in both flow directions. Enhanced diagnostic functions and monitoring of coil and electrode circuits as well as magnetic field for increased operational stability. Verification via fingerprint. Key features Pressure equipment designed acc. to PED Directive 97/ EC Meter size DN DN (/... ) Accuracy < ±.% of rate (> DN ) Fluid temperature - C ( F) (opt. C [6 F]) Hygienic certification: A, EHEDG Liners, PFA, PTFE, ETFE, hard or soft rubber, ceramic carbide Standardized installation lengths for DIN, ASME B6. or JIS B-K flanges AC / DC supply power

2 Data Sheet Electromagnetic Flowmeter FSM Electromagnetic Flowmeter FSM DS7U Contents Overview of flowmeter sensor and transmitter designs... General information.... Measuring accuracy.... Grounding.... Installation Requirements.... Flowmeter Sizes, Pressure Ratings, Flow Range...7. Flowrate nomograph...9 Model SEF.... Specifications.... Dimensions.... Ordering information... Model SE_.... Specifications.... Dimensions.... Ordering information... Mounting accessories.... Ordering information Wafer Accessories (Table H)... 6 Transmitter Specifications Inputs/outputs Digital communication Electrical connections Connection examples for peripherals (incl. HART) Dimensions Ordering information FXC flowmeter sensor simulator Installation set for " pipe installation in field-mount housing...67

3 Electromagnetic Flowmeter FSM DS7U Overview of flowmeter sensor and transmitter designs Housing Material Alu. Housing, Series Stainless Steel Housing, Series DN... (/... 6") DN... (/... / ) DN... (... ") DN... (/... /") ) ) DN... (/... ") DN... (... ") G G- DN... (... ) G9 ) ) Fixed Flange Fixed Flange Wafer type Variable Connections Flowmeter sensor Model number SEF SEF SEW SE_* Measured value error.% of rate (> DN ) DN PN DN PN DN PN DN PN * Wafer type Flange DIN /EN Flange ASME B6. / B6.7 JIS B-K /... " / CL CL / CL CL/JIS / CL/JIS CL/JIS (/... / ) S Pipe connection, (, ) 6 S DIN 6, ( /, ) S Weld stubs DIN Weld stubs DIN 6 / ISO 7 Weld stubs ISO 7 / SMS - - (/... / ), (, ) 6, ( /, ) - - (/... / ), (, ) 6, ( /, ) - - (... / ), (, ) 6, ( /, ) - - (/... ) 6, ( /, ) Tri-clamp DIN 676 / ASME BPE External threads ISO / - - (/... ) 6 E DIN 999 /" sanitary connectors - - (/.../ ) B Lining Hard/soft rubber, ceramic PEEK, Torlon (< DN ) carbide, PTFE, PFA, PFA (vacuum-tight) PFA (> DN ) ETFE, other Conductivity Electrodes Process Connection Material Degree of protection acc. to EN 69 Fluid temperature µs/cm (optional /. µs/cm) Stainless steel.7 (6 Ti),.9 (9 L), Hastelloy B-/C-, platinum-iridium, tantalum, titanium - Steel, stainless steel G / / R R R Q / J Q / J Q / J P / X P / X P / X T/K T/K > DN : Stainless steel. (6 L) < DN :.7 (6 Ti), PVC, POM IP 6 / IP 67 / IP 6 IP 6 / IP 67 / IP 6 IP 6 / IP 67 / IP / C F / 6 F -... C F -... C F -... C F Approvals Hygienic and sterile requirements - CIP/SIP-enabled A, EHEDG, CIP/SIP-enabled Pressure Equipment Directive 97//EC Conformity assessment in accordance with category III, fluid group CRN (Canadian Reg. Number) On request Transmitter Model number S Supply power V AC, V AC/DC Current output /... ma, /... ma Impulse output active ( V), optocoupler ( ma) Ext. zero return yes Ext. totalizer reset yes Forward/reverse flow metering yes Communication HART protocol, PROFIBUS PA, FOUNDATION Fieldbus Pipe empty detection std. yes, DN or higher and µs/cm Self-monitoring, extended diagnostic functions yes, expanded diagnostic functions / fingerprint only in connection with flowmeters SE, SEF and SEF for DN or higher On-site display/totalization yes Density correction yes, manual entry (totalize and display in mass units) Degree of protection acc. to EN 69 IP 6 / IP 67, NEMA X G Housing field-mount housing ) Weld stubs ) Tri-clamp ) Threaded pipe connection ) External threads

4 Electromagnetic Flowmeter FSM DS7U Change from one to two columns General information. Measuring accuracy.. Reference conditionsper EN 9 Fluid temperature Ambient temperature Power supply C (6 F) ± K C (6 F) ± K Line voltage as per name plate U N ± % Installation conditions Upstream > x DN straight section Downstream > x DN straight section DN = Flowmeter sensor size Warm-up phase min.. Maximum measuring error Pulse output DN... DN (/... /"): ± % of measured value, ±. Q maxdn DN... DN (/... "): Q >. Q maxdn ±.% of measured value Q <. Q maxdn ±. Q maxdn Q maxdn = maximum flowrate for the flowmeter size m/s Analog output effects Same as pulse output plus ±.% of rate ±. ma 6, %, %, %. Grounding The grounding of the flowmeter sensor is essential for both safety reasons, and to ensure trouble-free operation of the electromagnetic flowmeter. The ground screws on the flowmeter sensor are to be brought to ground potential. For technical reasons, this potential should be identical to the potential of the metering fluid, if possible. For plastic or insulated lined pipelines, the fluid is grounded by installing ground plates. When there are stray potentials present in the pipeline, we recommend installing a ground plate on both ends of the flowmeter sensor. To comply with the EMC and Low Voltage Directives, the connection box/ transmitter must be grounded in addition to the meter tube of the flowmeter sensor.. Installation Requirements The device measures the flowrate in both directions. Forward flow is the factory setting, as shown in Fig.. Fig. The following items must be observed:.. Electrode axis Electrode axis () as level as possible or rotated max.. max. G99 Y, %, % DN... (/.../ ), % DN..., % (/... ) 6 m/s 6,, 9,7 6,, ft/s X G6 Fig. Y Accuracy ± of rate X Flow velocity v Fig. G

5 Electromagnetic Flowmeter FSM.. In- and outlet pipe sections The metering principle is independent of the flow profile as long as standing eddies do not extend into the metering section, such as may occur after double elbows (), in the event of tangential inflow, or where half-open gate valves are located upstream of the flowmeter sensor. In such cases, measures must be put in place to normalize the flow profile. Do not install fittings, manifolds, valves, etc., directly in front of the flowmeter sensor (). Butterfly valves must be installed so that the valve plate does not extend into the flowmeter sensor. Valves or other turn-off components should be installed in the outlet pipe section (). Experience has shown that, in most installations, straight inlet sections x DN long and straight outlet sections x DN long are sufficient (DN = nominal diameter of the sensor Fig. ). For test stands, the reference conditions of x DN straight inlet and x DN straight outlet must be provided, in accordance with EN 9 / ISO 9. Fig... Vertical connections xdn xdn G9 Vertical installation for measuring abrasive fluids, preferably with flow in upward direction... Free inlet or outlet DS7U For a free outflow, do not install flowmeter at the highest point in the pipeline, since measuring tube may empty, creating bubbles (). For free inflow/outflow, provide an invert, to ensure that the pipeline is always full (). Fig Strongly contaminated fluids G96 For strongly contaminated fluids, a bypass connection according to the figure is recommended so that operation of the system can continue to run without interruption the during the mechanical cleaning. Fig...7 Installation in the vicinity of pumps G97 For flowmeter sensors that are installed near pumps or other vibration-causing fixtures, the use of mechanical vibration control components is mandatory. Fig... Horizontal connections The measuring tube must always be full. Provide for a slight incline of the connection for degassing. G9 Fig. 9 G9 Fig. 6 G9

6 Electromagnetic Flowmeter FSM DS7U.. Installing the high temperature design The high temperature design allows for complete thermal insulation of the sensor. The pipeline and sensor must be insulated after installing the unit according to the following illustration. Nomograph for pressure drop determinations For adaptor with α/ = Fig. Insulation G Installation in pipelines with larger nominal diameter Determine the resulting pressure loss when using reduction pieces ():. Calculate the diameter ratio d/d.. Determine the flow velocity based on the flow range nomograph (Fig. ).. Read the pressure drop on the Y-axis in Fig.. D d Fig. Fig. d Inside diameter of the flowmeter v Flow velocity [m/s] Δp Pressure loss [mbar] D Inside diameter of the pipeline G99 6

7 wei Electromagnetic Flowmeter FSM DS7U Change from one to two columns. Flowmeter Sizes, Pressure Ratings, Flow Range Meter size DN Standard pressure rating PN Min. flow velocity measuring range. m/s Max. flow velocity measuring range m/s. / /6 /..6. l/min l/min l/min l/min l/min l/min / / /.. l/min l/min l/min.9.. l/min l/min l/min.6.. /6 / / / l/min l/min l/min l/min..6.. l/min l/min l/min l/min / / l/min l/min l/min l/min l/min l/min / 6 9 m /h m /h m /h 6 6 m /h m /h m /h m /h m /h m /h 9 6 m /h m /h m /h /6 /6 /6 9 m /h m /h m /h 96 m /h m /h m /h /6 /6 /6 6 m /h m /h m /h m /h m /h m /h m /h m /h m /h m /h m /h m /h m /h m /h m /h m /h 9 7 m /h m /h

8 Electromagnetic Flowmeter FSM DS7U Change from one to two columns Flange design and pressure rating Nominal diameter (/ / )... (/... ") ( /") ( /") (") 6 ( /") (") (") (") (6") Flange ) Material PN PED /" sanitary DIN ASME JIS DIN ASME JIS DIN ASME JIS DIN ASME Stainless steel.7 (6 Ti) or POM, brass, PVC Stainless steel or steel Stainless steel or steel Stainless steel or steel Stainless steel or steel bar, 6, bar ) CL, CL, CL6 ) bar bar CL, CL bar, 6, bar CL, CL, CL6 bar, 6, bar CL, CL, CL6 JIS bar DIN Stainless steel or 6,, 6, steel bar ASME CL, CL, CL6 JIS bar DIN Stainless steel or, 6, bar ASME steel CL, CL, CL6 JIS bar DIN Stainless steel or 6,, 6, steel bar ASME CL, CL, CL6 JIS bar DIN Stainless steel or 6,, 6, steel bar ASME CL, CL JIS bar DIN Stainless steel or 6,, 6, steel bar ASME JIS ASME CL, CL, CL6 bar CL SEP Sec. Para. Conformity assessment in accordance with category III, module B + D, fluid group Nominal diameter (") (") (") JIS... 6 DIN (... ") ASME JIS 7... DIN (... ) ASME Flange ) Material PN PED DIN Stainless steel or, 6,,, steel 6, bar ASME CL, CL, CL6 JIS bar DIN Stainless steel or, 6,, steel bar ASME CL, CL JIS bar DIN Stainless steel or, 6,, steel bar ASME CL, CL Stainless steel or steel Stainless steel or steel bar, 6, bar CL, CL bar, 6, bar CL ) Connecting dimensions for flange acc. to DIN / EN9- or ASME or JIS. ) PN6, PN only for nominal diameters DN and DN. ) CL6 only for nominal diameters DN and DN. Conformity assessment in accordance with category III, module B + D, fluid group Other meter sizes, pressure stages and temperature classes are available upon request.

9 Electromagnetic Flowmeter FSM. Flowrate nomograph The volume flowrate is a function of the flow velocity and the diameter of the flowmeter. The flowrate nomograph indicates the flowrate range for a specific flowmeter nominal diameter and which flowmeter nominal diameters are suitable for a specific flowrate. l/min m /h DN DN DN 6 DN DN DN DN DN DN DN DN DN 6 DN DN DN DN. DN l/s l/min m /h ,,6, DN DN 9 DN DN 7 DN 6 DN DN DN DN DN DN DN DN DN 6 m/s DS7U l/s Fig. : Flowrate nomograph DN... DN (... ") G6 Example: Flowrate = 7 m /h (max. value = range end value). Sensor nominal diameters DN... DN 6 (/... /") are suitable for a flow velocity of.... m/s.,,6, 6 m/s Fig. : Flowrate nomograph DN... DN (/... ") Example G 9

10 Electromagnetic Flowmeter FSM DS7U Change from one to two columns Model SEF. Specifications Change from one to two columns Temperature graph Fig. : 6 G Fluid temperature as function of ambient temperature Ambient temperature C Fluid temperature C Standard flange (steel): Hard/soft rubber max. 9 / 6 C (9... F) Stainless steel flange Standard flange (steel): PTFE / PFA / ETFE max. C (66 F) 6 High temperature: Thick PTFE / PFA max. C (6 F) Max. allowable cleaning temperature PTFE-, PFA-design CIP cleaning Liner Flowmeter sensor T max t max Min T amb. Steam cleaning PTFE, PFA C ( F) 6 C (77 F) Wet cleaning PTFE, PFA C ( F) 6 C (77 F) If the ambient temperature is > C, then the difference must be subtracted from the max. cleaning temperature. T max - Δ C.Δ C = (T amb. - C) Weight See "Dimensions" Min. permissible pressure as a function of fluid temperature Lining Nominal diameter DN Hard rubber (/ ) Soft rubber ( ) PTFE 6 (/ ) Thick PTFE hightemperature design ( ) ( ) ( ) PFA (/ ) P Operation mbar abs at T Operating < 9 C (9 F) < 6 C ( F) < C (6 F) < C ( F) < C (66 F) < C (6 F) < C (6 F) < C (6 F) < C (66 F) < C (6 F) ETFE... (... ) < C (66 F) Ceramic < C (76 F) carbide ( ) Flowmeter sensor material Parts Standard Others Lining PTFE, PFA, hard rubber, soft rubber, ETFE Ceramic carbide Signal and ground electrode for - Hard rubber - Soft rubber - PTFE, PFA, ETFE Grounding plate Protection plate Stainless steel.7 (6 Ti) Hastelloy C- (.6) Stainless steel.7 (6 Ti) Stainless steel.7 (6 Ti) Hastelloy B- (.6), Hastelloy C- (.6), Titanium, tantalum, Platinumiridium, Stainless steel.9 (9 L) Stainless steel.7 (6 Ti) Hastelloy B- (.6), Titanium, tantalum, Platinumiridium, Stainless steel.9 (9 L) On request On request Process connection material Parts Standard Others Flange DN... DN Stainless steel ) (/... / ) DN... DN Galvanized steel ) Stainless (/... ) steel ) DN... DN (... ) Painted steel ) Housing DN... (/... ) DN... DN (... ) Terminal box Meter tube Dual-shell casing, cast aluminum, painted, paint coat, µm thick, RAL 9 Welded steel design, painted, paint coat, µm thick, RAL 9 Al alloy, painted, µm dick, frame: dark gray, RAL 7 Cover: light gray, RAL 9 Stainless steel. () cable gland used Polyamide The process connections are made of one of the materials listed below: ). (),.7,. (6L). (6L),. ().7 (6Ti), ASTM A F, ASTM A FL, ASTM A F6L, ASTM A F, ASTM A F6TI, ASTM A F6, CrNi9, CrNi, Cr7NiMo, Cr7NiMo, CrNi9Ti, CrNiMoTi ).,.6,.7,., ASTM A, QA, #, 6Mn

11 Electromagnetic Flowmeter FSM DS7U Storage temperature C (-... F) PS [bar] PS [PSI] 9. Degree of protection acc. to EN 69 IP 6 / IP 67 IP 6 (option) 9 PN.. 6. Pipeline vibration according to EN Transmitter - In the range of Hz, max. deflection. mm Flowmeter sensor - In the range of Hz, max. deflection. mm - In the range of Hz, max. acceleration g Designs The flanged flowmeters comply with the installation lengths specified in VDI / VDE 6, ISO 9 or according to DVGW (process sheet W, design WP; ISO 6 short) PN 6 PN PN PN 6 PN 6 7 TS Fig. 6: Stainless steel DIN flange up to DN 6 (") [ C] [ F] G9 Material load Limits for allowable fluid temperature (TS) and allowable pressure (PS) are a function of the liner and flange material used (see the factory tag and name plate of the unit). Temperature limits Lining Flange material Hard rubber Soft rubber PTFE / ETFE Thick PTFE / PFA Ceramic carbide Steel Stainless steel Steel Stainless steel Steel Stainless steel Steel Stainless steel Steel Stainless steel Min. temper ature - C ( F) - C ( F) - C ( F) - C ( F) - C ( F) - C (- F) - C ( F) - C (- F) - C ( F) - C (- F) Max. temperature Standard High temperatur e 9 C (9 F) 9 C (9 F) 6 C ( F) 6 C ( F) C (66 F) C (66 F) C (66 F) C (66 F) C (76 F) C (76 F) C (6 F) C (6 F) - - PS [bar] CL6 CL CL 6 7 TS Fig. 7: Stainless steel ASME flange up to DN (6") (CL/); up to DN (") (CL); up to DN (") (CL 6) PS [bar] PN PN 6 PN PN PN 6 PN 7 TS 9 9 Fig. : DIN flange SS to DN 6 ( ) 66 PS [PSI] [ C] [ F] G9 PS [PSI] [ C] [ F] G

12 Electromagnetic Flowmeter FSM DS7U PS [bar] CL CL PS [psi] [ C] [ F] TS G Fig. 9: Steel ASME flange up to DN (6") (CL/); up to DN (") (CL) JIS K-B Flange Nominal size DN (¼ 6 ) (¼ 6 ) Material PN TS PS [bar] Stainless steel - + C (- +6 F) Steel - + C ( 66 F) PS [bar] 7 6 DN 7 PN 6 PS [psi] DN 9 PN 6 DN PN 6 7. DN PN DN 9 PN. DN PN DN 7 PN 6. 7 DN PN [ C] TS [ F] G9 Fig. : Stainless steel DIN flange, DN 7... DN (... ") PS [bar] DN 7 PN 6 DN 9 PN 6 DN PN 6 DN PN 6 PS [psi] DN 9 PN 6. DN PN 7 DN 7 PN. 6 DN PN [ C] TS [ F] G Fig. : DIN flange steel, DN 7... DN (... )

13 Electromagnetic Flowmeter FSM DS7U Change from one to two columns. Dimensions.. Model SEF Flange DN (/ ) (.6) (.) C D F E Fig. : Dimensions in mm (inch) Cable gland M x. or NPT Flange in acc. with DIN/EN 9- A L* Dimensions [mm] DN PN ) D L ) ) F ) C E ) A Approx. weight [kg]... ) Tolerance L: + / - mm G977 Dimensions [inch] DN (inch) PN ) D L ) ) F ) C E ) A Approx. weight [lb]... ) (/... /6) (/) (/) (/) () ( /) ( /) () ( /) () () () Tolerance L: + / -. inch

14 Electromagnetic Flowmeter FSM DS7U Flange in acc. with ASME B6. CL Dimensions [mm] CL ISO 9 ISO 9 Approx. weight [kg] DN Inch D L ) ) D L ) ) F ) C E ) A... /... /6 6) / 6) / / / / / / / Tolerance L: + / - mm Dimensions [inch] CL CL ISO 9 ISO 9 Approx. weight [lb] DN Inch D L ) ) D L ) ) F ) C E ) A... /... /6 6) / 6) / / / / / / / 7.7 Tolerance L: + / -. inch ) Other pressure ratings available on request. ) If a grounding plate is installed (attached to one side of the flange), this increases dimension L as follows: DN... by mm. inch); DN by mm (.97 inch). ) If protection plates are installed (attached to both sides of the flange), this increases dimension L as follows: DN... by 6 mm (.6 inch; DN by mm (.9 inch). ) Depending on the device design, the dimensions change according to the following table. Device design Dimension E, F Standard temperature design High temperature version +7 mm (+ inch) ) Connection flange DN 6) Connection flange /" 7) Connecting dimensions in acc. with EN 9-. For DN 6, PN 6 in acc. with EN 9-, please order PN.

15 Electromagnetic Flowmeter FSM DS7U.. Flange DN (6 ") (.6) (.) C D E F A L* G97 Fig. : Dimensions in mm (inch) Cable gland M x. or NPT Flange in acc. with DIN/EN 9- Dimensions [mm] DN PN ) D L ) ) F ) C E ) A Approx. weight [kg] Tolerance L: DN... + / - mm, DN... + / - mm Dimensions [inch] DN PN ) D L ) ) F ) C E ) A Approx. weight [lb] (6) () () () Tolerance L: DN... + / -. inch, DN... + / -.97 inch

16 Electromagnetic Flowmeter FSM DS7U Flange in acc. with ASME B6. CL Dimensions [mm] CL ISO 9 ISO 9 Approx. weight [kg] DN Inch D L ) ) D L ) ) F ) C E ) A / 7 / / 7 7 / Tolerance L: DN... + / - mm, DN... + / - mm Dimensions [inch] CL CL ISO 9 ISO 9 Approx. weight [lb] DN Inch D L ) ) D L ) ) F ) C E ) A / / / / 6. Tolerance L: DN... + / -. inch, DN... + / -.97 inch ) Other pressure ratings available on request. ) If a grounding plate is installed (attached to one side of the flange), this increases dimension L by mm (.97 inch). ) If protection plates are installed (attached to both sides of the flange), this increases dimension L by mm (.9 inch). ) Depending on the device design, the dimensions change according to the following table. Device design Dimension E, F Standard temperature design High temperature version +7 mm (+ inch) 6

17 Electromagnetic Flowmeter FSM DS7U.. Flange DN (6 ") C F E A Fig. : Cable gland M x. or NPT Flange in acc. with DIN/EN 9- L* Dimensions [mm] DN PN ) D L ) ) F C E A Approx. weight [kg] Tolerance L: DN + / - mm, DN / - mm Dimensions [inch] DN (inch) PN ) D L ) ) F C E A Approx. weight [lb] () (6) () () () () (6) () Tolerance L: DN + / -.97 inch, DN / -.9 inch D G979 7

18 Electromagnetic Flowmeter FSM DS7U Flange up to DN 6 (") in acc. with ASME B6., flange DN 7... (... ") in acc. with ASME B6.7, Series B CL Dimensions [mm] Installation length Approx. weight [kg] DN Inch D L ) ) F C E A Tolerance L: DN... + / - mm, DN / - mm Dimensions [inch] CL Installation length Approx. weight [lb] DN Inch D L ) ) F C E A Tolerance L: DN... + / -.97 inch, DN / -.9 inch ) Other pressure ratings available on request. ) If a grounding plate is installed (attached to one side of the flange), this increases dimension L as follows: DN... 6 um mm (.97 inch). ) If protection plates are installed (attached to both sides of the flange), this increases dimension L as follows: DN... 6 by mm (.9 inch).

19 Electromagnetic Flowmeter FSM DS7U.. Flange DN... (/... "), high-pressure versions PN 6 and PN (.6) (.) C D F E Fig. : Dimensions in mm (inch) Cable gland M x. or NPT A L* G977 Flange in acc. with DIN 66 (PN 6) and DIN 67 (PN ) Dimensions [mm (inch)] / [kg (lb)] DN PN D L ) ) F ) C E ) A Approx. weight (.) (.6) (6.6) (.) (.96) (.) (7.6) (.) (.6) (6.6) (.) (.96) (.) (.) (6.69) (.) (6.) (.6) (.) (.) (6.6) (7.9) (.) (6.7) (.) (.7) (.) (.66) (7.6) (.) (6.7) (.) (.7) (.) (.7) (.7) (.99) (7.) (.) (.9) (.9) (.7) 7 (.66) (.99) (7.) (.) (.9) (.9) (6.) 6 7 (.6) (.9) (7.) (.) (.9) (.9) (.9) 7 (9.6) (.9) (7.) (.) (.9) (.9) (.9) (9.) (.7) (7.7) (.) (6.77) (.9) (9.) (.) (.7) (7.7) (.) (6.77) (.9) (79.7) Continued on next page 9

20 Electromagnetic Flowmeter FSM DS7U Continued Dimensions [mm (inch)] DN PN D L ) ) F ) C E ) A 6 9 (.6) (7.7) (.7) (.) (7.7) (.9) (.) (7.7) (.7) (.) (7.7) (.9) (.) (7.7) (.) (.7) (9.) (6.) (.9) (7.7) (.) (.7) (9.) (6.) 6 7 (6.) (9.69) (.) (6.69) (.) (7.7) 7 (6.9) (9.69) (.) (6.69) (.) (7.7) Tolerance L: + / - mm (+ / -. inch) ) If a grounding plate is installed (attached to one side of the flange), this increases dimension L as follows: DN... by mm (. inch), DN and above by mm (.97 inch). ) If protection plates are installed (attached to both sides of the flange), this increases dimension L as follows: DN... by 6 mm (.6 inch), DN and above by mm (.9 inch). ) Depending on the device design, the dimensions change according to the following table. Device design Dimension E, F Standard temperature design High temperature version +7 mm (+ inch)

21 Electromagnetic Flowmeter FSM DS7U.. Flange DN... (/... "), high-pressure version CL 6 (.6) (.) C D F E Fig. 6: Dimensions in mm (inch) Cable gland M x. or NPT A L* G977 Flange in acc. with ASME B6., CL 6 Dimensions [mm (inch)] / [kg (lb)] DN PN ) D L ) ) F ) C E ) A Approx. weight (½) CL (.7) (.6) (6.6) (.) (.96) (.). () CL (.) (.6) (6.6) (.) (.96) (.). ( ½) CL (6.) (.) (6.) (.6) (.) (.). () CL (6.) (.) (6.7) (.) (.7) (.).66 6 ( ½) CL (7.) (.99) (7.) (.) (.9) (.9) 9.6 () CL 6 7 (.) (.9) (7.) (.) (.9) (.9).7 () CL (.7) (.7) (7.7) (.) (6.77) (.9) 97. () CL 6 On request () (7.7) (.7) (.) (7.7) (.9) (6) CL On request () (7.7) (.) (.7) (9.) (6.) () CL 6 7 On request (6.) (9.69) (.) (6.69) (.) (7.7) Tolerance L: + / - mm (+ / -. inch) ) If a grounding plate is installed (attached to one side of the flange), this increases dimension L as follows: DN... by mm (. inch), DN and above by mm (.97 inch). ) If protection plates are installed (attached to both sides of the flange), this increases dimension L as follows: DN... by 6 mm (.6 inch), DN and above by mm (.9 inch). ) Depending on the device design, the dimensions change according to the following table. Device design Dimension E, F Standard temperature design High temperature version +7 mm (+ inch)

22 Electromagnetic Flowmeter FSM DS7U. Ordering information Information on A conformity: If A conformity is desired, please order model SE Welded Flange, Liner Material Thick-PTFE / PTFE / PFA / ETFE Main order number Add. order no. Version number XX Electromagnetic Flowmeter SEF- X X X X X X X X X X X X X X X X X X X X X X XX FSM Liner Material / Meter Size PFA / DN (/ in.) P PFA / DN (/ in.) P PFA / DN 6 (/ in.) P 6 PFA / DN (/6 in.) P PFA / DN (/ in.) P PFA / DN (/ in.) P PFA / DN (/ in.) P PFA / DN ( in.) P PFA / DN (-/ in.) P PFA / DN (-/ in.) P PFA / DN ( in.) P PFA / DN 6 (-/ in.) P 6 PFA / DN ( in.) P PFA / DN ( in.) P H PFA / DN ( in.) P Q PFA / DN (6 in.) P F PFA / DN ( in.) P H PTFE / DN (/ in.) T PTFE / DN (/ in.) T PTFE / DN (/ in.) T PTFE / DN ( in.) T PTFE / DN (-/ in.) T PTFE / DN (-/ in.) T PTFE / DN ( in.) T PTFE / DN 6 (-/ in.) T 6 PTFE / DN ( in.) T PTFE / DN ( in.) T H PTFE / DN ( in.) T Q PTFE / DN (6 in.) T F PTFE / DN ( in.) T H PTFE / DN ( in.) T F PTFE / DN ( in.) T H PTFE / DN ( in.) T F PTFE / DN (6 in.) T H PTFE / DN ( in.) T F PTFE / DN ( in.) T H PTFE / DN 6 ( in.) T 6 H Thick PTFE / DN ( in.) F Thick PTFE / DN (-/ in.) F Thick PTFE / DN (-/ in.) F Thick PTFE / DN ( in.) F Thick PTFE / DN 6 (-/ in.) F 6 Thick PTFE / DN ( in.) F Thick PTFE / DN ( in.) F H Thick PTFE / DN ( in.) F Q Thick PTFE / DN (6 in.) F F Thick PTFE / DN ( in.) F H Thick PTFE / DN ( in.) F F Thick PTFE / DN ( in.) F H ETFE / DN ( in.) E ETFE / DN (-/ in.) E ETFE / DN (-/ in.) E ETFE / DN ( in.) E ETFE / DN 6 (-/ in.) E 6 Continued on next page

23 Electromagnetic Flowmeter FSM DS7U Main order number Add. order no. Version number XX Electromagnetic Flowmeter SEF- X X X X X X X X X X X X X X X X X X X X X X XX FSM Liner Material / Meter Size ETFE / DN ( in.) E ETFE / DN ( in.) E H ETFE / DN ( in.) E Q ETFE / DN (6 in.) E F ETFE / DN ( in.) E H ETFE / DN ( in.) E F ETFE / DN ( in.) E H ETFE / DN ( in.) E F ETFE / DN (6 in.) E H ETFE / DN ( in.) E F ETFE / DN ( in.) E H ETFE / DN 6 ( in.) E 6 H ETFE / DN 7 ( in.) E 7 H ETFE / DN ( in.) E H ETFE / DN 9 (6 in.) E 9 H ETFE / DN ( in.) E T Others / DN (/ in.) Z Others / DN (/ in.) Z Others / DN 6 (/ in.) Z 6 Others / DN (/6 in.) Z Others / DN (/ in.) Z Others / DN (/ in.) Z Others / DN (/ in.) Z Others / DN ( in.) Z Others / DN (-/ in.) Z Others / DN (-/ in.) Z Others / DN ( in.) Z Others / DN 6 (-/ in.) Z 6 Others / DN ( in.) Z Others / DN ( in.) Z H Others / DN ( in.) Z Q Others / DN (6 in.) Z F Others / DN ( in.) Z H Others / DN ( in.) Z F Others / DN ( in.) Z H Others / DN ( in.) Z F Others / DN (6 in.) Z H Others / DN ( in.) Z F Others / DN ( in.) Z H Others / DN 6 ( in.) Z 6 H Measuring Electrodes Material / Grounding Electrodes Hastelloy C- (.6) / Without H Hastelloy B- (.6) / Without B AISI 6Ti SST (.7) / Without S Titanium / Without M Tantalum / Without T AISI 9L SST (.9) / Without F Platinum-Iridium / Without P Nickel / Without ) U Double Layer/ Without ) C Tungsten-Carbide / Without ) K Continued on next page ) >= DN ( in.) ) Basic material Hastelloy C

24 Electromagnetic Flowmeter FSM DS7U Main order number Add. order no. Version number XX Electromagnetic Flowmeter FSM SEF- X X X X X X X X X X X X X X X X X X X X X X XX Measuring Electrodes Material / Grounding Electrodes Hastelloy C- (.6) / With ) O Hastelloy B- (.6) / With ) N AISI 6Ti SST (.7) / With ) E Titanium / With ) I Tantalum / With ) Q AISI 9L SST (.9) / With ) R Platinum-Iridium / With ) G Nickel / With ) V Double Layer / With ) D Pressure Rating PN, ISO lay length C PN 6, ISO lay length 6) D PN, ISO lay length E PN, ISO lay length 7) F JIS K, ISO lay length ) K ASME CL, ISO lay length R ASME CL, ISO lay length 9) S Others Z Material of Process Connection Steel ) Stainless steel ) Accessories Without A Protection rings AISI 6Ti SST (.7) ) B Grounding ring AISI 6Ti SST (.7) ) C Others Z Temperature Range Standard design (<= C [66 F]) S High temperature design (<= C [6 F]) ) H Certificates PED Standard A Material certificate. acc. EN with pressure test ) D AD Pressure test AD G Inspection certificate. acc. EN F Calibration Certificates Standard A Fingerprint saved at factory ) F Type of Protection / Cable Entry IP 67 / Thread for screw-type conduit fitting M x. IP 67 / Thread for screw-type conduit fitting NPT / in. IP 6 / Thread for screw-type conduit fitting M x. 6) 7 IP 6 / Cable connected and connection box potted Continued on next page ) Grounding electrodes <= DN (6 in.) ) >= DN ( in.) / Grounding electrodes <= DN (6 in.) ) Basic material Hastelloy C / Grounding electrodes <= DN (6 in.) 6) DN 6 (-/ in.) / PN 6 with connection dimensions acc. EN 9-: Please order PN 7) Standard for DN... DN (/... in.) ) <= DN ( in.) 9) <= DN 6 ( in.) ) >= DN (/ in. ) Standard for DN... DN (/... / in.), option from DN (/ in.) ) Protection rings mounted on both sides and ground rings mounted on one side to flange. Material SST.7 (6Ti). Not available with grounding electrodes ) only with Thick-PTFE/PFA >= DN ( in.) ) Material certificate for meter tube and flanges ) > DN (/6 in.) 6) Sealing compound (optional): DBU

25 Electromagnetic Flowmeter FSM DS7U Main order number Add. order no. Version number XX Electromagnetic Flowmeter SEF- X X X X X X X X X X X X X X X X X X X X X X XX FSM Design Without pre-amplifier 7) With pre-amplifier type A ) With pre-amplifier type B 9) Name Plate Language / Type German / Adhesive foil G English / Adhesive foil E French / Adhesive foil F German / Stainless steel J English / Stainless steel K French / Stainless steel L Design Level (Specified by ABB) x Lay Length Short, acc. ISO 9 A Electrode Design Standard Conical head, AISI 9L SST (.9) ) Swedish design, Hastelloy C- (.6) ) Signal Cable Length Without cable m (6 ft) m ( ft) m (66 ft) m (99 ft) m ( ft) m (6 ft) 6 m (9 ft) 6 7 m ( ft) 7 m (6 ft) 9 m (9 ft) 9 m ( ft) m ( ft) m (9 ft) 7 m (7 ft) 7 m (66 ft) Excitation Cable Length Without cable m (6 ft) m ( ft) m (66 ft) m (99 ft) m ( ft) m (6 ft) 6 m (9 ft) 6 7 m ( ft) 7 m (6 ft) 9 m (9 ft) 9 m ( ft) m ( ft) m (9 ft) 7 m (7 ft) 7 m (66 ft) Continued on next page 7) From DN (/ in.) >= μs/cm ) Standard up to DN (/6 in.) >= μs/cm,option > DN (/6 in.) >= μs/cm and lay length max. m (66 ft) 9) Option up to DN (/6 in.) >= µs/cm, > DN (/6 in.) >=. µs/cm and lay length max. m (66 ft) ) For application e.g. with high fat contents ) DN... DN (... in.), for pulp applications with high resin contents

26 Electromagnetic Flowmeter FSM DS7U Main order number Add. order no. Version number XX Electromagnetic Flowmeter FSM SEF- X X X X X X X X X X X X X X X X X X X X X X XX Calibration Points (Standard) VK Point Standard Calibration VC Witnessed Calibration, Calibration Points ) VE Point Calibration acc. DKD ) VD Language of Documentation German M English M Russian MB Language package Western Europe / Scandinavia (Languages DE, EN, DA, ES, FR, IT, NL, PT, FI, SV) ME Language package Eastern Europe (Languages DE, EL, CS, ET, LV, LT, HU, PL, SK, SL, RO, BG) MW Others MZ Other Usage Certifications Russia, Metrological and GOST-R Certificate CG Kazakhstan, Metrological and GOST-K Certificate CG Ukraine, Metrological Certificate CG Belarus, Metrological Certificate CG6 ) Only available with FSM-S External Converter 6

27 Electromagnetic Flowmeter FSM Festflansch, Auskleidung Hartgummi, Weichgummi, Ceramic Carbide Main order number DS7U Add. order no. Version number XX Electromagnetic Flowmeter SEF- X X X X X X X X X X X X X X X X X X X X X X XX FSM Liner Material / Meter Size Hard Rubber / DN (/ in.) H Hard Rubber / DN (/ in.) H Hard Rubber / DN ( in.) H Hard Rubber / DN (-/ in.) H Hard Rubber / DN (-/ in.) H Hard Rubber / DN ( in.) H Hard Rubber / DN 6 (-/ in.) H 6 Hard Rubber / DN ( in.) H Hard Rubber / DN ( in.) H H Hard Rubber / DN ( in.) H Q Hard Rubber / DN (6 in.) H F Hard Rubber / DN ( in.) H H Hard Rubber / DN ( in.) H F Hard Rubber / DN ( in.) H H Hard Rubber / DN ( in.) H F Hard Rubber / DN (6 in.) H H Hard Rubber / DN ( in.) H F Hard Rubber / DN ( in.) H H Hard Rubber / DN 6 ( in.) H 6 H Hard Rubber / DN 7 ( in.) H 7 H Hard Rubber / DN ( in.) H H Hard Rubber / DN 9 (6 in.) H 9 H Hard Rubber / DN ( in.) H T Soft Rubber / DN ( in.) S Soft Rubber / DN 6 (-/ in.) S 6 Soft Rubber / DN ( in.) S Soft Rubber / DN ( in.) S H Soft Rubber / DN ( in.) S Q Soft Rubber / DN (6 in.) S F Soft Rubber / DN ( in.) S H Soft Rubber / DN ( in.) S F Soft Rubber / DN ( in.) S H Soft Rubber / DN ( in.) S F Soft Rubber / DN (6 in.) S H Soft Rubber / DN ( in.) S F Soft Rubber / DN ( in.) S H Soft Rubber / DN 6 ( in.) S 6 H Soft Rubber / DN 7 ( in.) S 7 H Soft Rubber / DN ( in.) S H Soft Rubber / DN 9 (6 in.) S 9 H Soft Rubber / DN ( in.) S T Ceramic-Carbide / DN ( in.) ) C Ceramic-Carbide / DN (-/ in.) ) C Ceramic-Carbide / DN (-/ in.) ) C Ceramic-Carbide / DN ( in.) ) C Ceramic-Carbide / DN 6 (-/ in.) ) C 6 Ceramic-Carbide / DN ( in.) ) C Ceramic-Carbide / DN ( in.) ) C H Ceramic-Carbide / DN ( in.) ) C Q Ceramic-Carbide / DN (6 in.) ) C F Ceramic-Carbide / DN ( in.) ) C H Ceramic-Carbide / DN ( in.) ) C F Ceramic-Carbide / DN ( in.) ) C H Ceramic-Carbide / DN ( in.) ) C F Continued on next page ) Nur mit Wolfram-Karbid Elektroden / Schutzscheiben beidseitig am Flansch befestigt. Material.7 (6Ti) 7

28 Electromagnetic Flowmeter FSM DS7U Main order number Add. order no. Version number XX Electromagnetic Flowmeter SEF- X X X X X X X X X X X X X X X X X X X X X X XX FSM Liner Material / Meter Size Ceramic-Carbide/ DN (6 in.) ) C H Ceramic-Carbide/ DN ( in.) ) C F Ceramic-Carbide/ DN ( in.) ) C H Ceramic-Carbide/ DN 6 ( in.) ) C 6 H Ceramic-Carbide/ DN 7 ( in.) ) C 7 H Ceramic-Carbide/ DN ( in.) ) C H Ceramic-Carbide/ DN 9 (6 in.) ) C 9 H Ceramic-Carbide/ DN ( in.) ) C T Others / DN (/ in.) Z Others / DN (/ in.) Z Others / DN ( in.) Z Others / DN (-/ in.) Z Others / DN (-/ in.) Z Others / DN ( in.) Z Others / DN 6 (-/ in.) Z 6 Others / DN ( in.) Z Others / DN ( in.) Z H Others / DN ( in.) Z Q Others / DN (6 in.) Z F Others / DN ( in.) Z H Others / DN ( in.) Z F Others / DN ( in.) Z H Others / DN ( in.) Z F Others / DN (6 in.) Z H Others / DN ( in.) Z F Others / DN ( in.) Z H Others / DN 6 ( in.) Z 6 H Others / DN 7 ( in.) Z 7 H Others / DN ( in.) Z H Others / DN 9 (6 in.) Z 9 H Others / DN ( in.) Z T Measuring Electrodes Material / Grounding Electrodes AISI 6Ti SST (.7) / Without S Hastelloy C- (.6) / Without H Hastelloy B- (.6) / Without B Titanium / Without M Tantalum / Without T AISI 9L SST (.9) / Without F Platinum-Iridium / Without P Nickel / Without ) U Double Layer / Without ) C Tungsten-Carbide / Without ) K Continued on next page ) With Tungsten Carbide Electrode only / Protection rings mounted on both sides to flange. Material.7 (6Ti) ) >= DN ( in.) ) Basic material Hastelloy C

29 Electromagnetic Flowmeter FSM DS7U Main order number Add. order no. Version number XX Electromagnetic Flowmeter FSM SEF- X X X X X X X X X X X X X X X X X X X X X X XX Measuring Electrodes Material / Grounding Electrodes Hastelloy C- (.6) / With ) O Hastelloy B- (.6) / With ) N AISI 6Ti SST (.7) / With ) E Titanium / With ) I Tantalum / With ) Q AISI 9L SST (.9) / With ) R Platinum-Iridium / With ) G Nickel / With ) V Double Layer / With 6) D Pressure Rating PN, ISO laid length C PN 6, ISO laid length 7) D PN, ISO laid length E PN, ISO laid length ) F PN 6 9) G PN 9) H JIS K, ISO laid length ) K ASME CL, ISO laid length R ASME CL, ISO laid length ) S ASME CL 6 9) T Others Z Material of Process Connection Steel ) Stainless steel ) Accessories Without A Others Z Temperature Range Standard design S Certificates PED Standard A Material certificate. acc. EN with pressure test ) D AD Pressure test AD G Inspection certificate. acc. EN F Calibration Certificates Standard A Fingerprint saved at factory ) F Type of Protection / Cable Entry IP 67 / Thread for screw-type conduit fitting M x. IP 67 / Thread for screw-type conduit fitting NPT / in. IP 6 / Thread for screw-type conduit fitting M x. 6) 7 IP 6 / Cable connected and connection box potted Continued on next page ) Grounding electrodes <= DN (6 in.) ) >= DN ( in) / Grounding electrodes <= DN (6 in.) 6) Basic material Hastelloy C / Grounding electrodes <= DN (6 in.) 7) DN 6 (-/ in.) / PN 6 with connection dimensions acc. EN 9-: Please order PN ) Standard for DN... DN (/... in.) 9) <= DN ( in.) / Hardrubber only ) <= DN ( in.) ) <= DN 6 ( in.) ) >= DN (/ in.) ) Standard for DN... DN (/... / in.), option from DN (/ in.) ) Material certificate for meter tube and flanges ) > DN (/6 inch) 6) Sealing compound (optional): DBU 9

30 Electromagnetic Flowmeter FSM DS7U Main order number Add. order no. Version number XX Electromagnetic Flowmeter SEF- X X X X X X X X X X X X X X X X X X X X X X XX FSM Design Without pre-amplifier 7) With pre-amplifier type A ) With pre-amplifier type B 9) Name Plate Language / Type German / Adhesive foil G English / Adhesive foil E French / Adhesive foil F German / Stainless steel J English / Stainless steel K French / Stainless steel L Design Level (Specified by ABB) x Laid Length Short, acc. ISO 9 A Electrode Design Standard Conical head, AISI 9L SST (.9) ) Signal Cable Length Without cable m (6 ft) m ( ft) m (66 ft) m (99 ft) m ( ft) m (6 ft) 6 m (9 ft) 6 7 m ( ft) 7 m (6 ft) 9 m (9 ft) 9 m ( ft) m ( ft) m (9 ft) 7 m (7 ft) 7 m (66 ft) Excitation Cable Length Without cable m (6 ft) m ( ft) m (66 ft) m (99 ft) m ( ft) m (6 ft) 6 m (9 ft) 6 7 m ( ft) 7 m (6 ft) 9 m (9 ft) 9 m ( ft) m ( ft) m (9 ft) 7 m (7 ft) 7 m (66 ft) Continued on next page 7) >= μs/cm ) Option >= μs/cm and lay length max. m (66 ft) 9) Option >=. µs/cm and lay length max. m (66 ft) ) For application e.g. with high fat contents

31 Electromagnetic Flowmeter FSM DS7U Main order number Add. order no. Version number XX Electromagnetic Flowmeter FSM SEF- X X X X X X X X X X X X X X X X X X X X X X XX Calibration Points (Standard) VK Point Standard Calibration VC Witnessed Calibration, Calibration Points ) VE Point Calibration acc. DKD ) VD Language of Documentation German M English M Russian MB Language package Western Europe / Scandinavia (Languages DE, EN, DA, ES, FR, IT, NL, PT, FI, SV) ME Language package Eastern Europe (Languages DE, EL, CS, ET, LV, LT, HU, PL, SK, SL, RO, BG) MW Others MZ Other Usage Certifications Russia, Metrological and GOST-R Certificate CG Kazakhstan, Metrological and GOST-K Certificate CG Ukraine, Metrological Certificate CG Belarus, Metrological Certificate CG6 ) Only available with FSM-S External Converter

32 Electromagnetic Flowmeter FSM DS7U Model SE_. Specifications Change from one to two columns Minimum Allowable Absolute Pressure Lining Nominal diameter DN PFA (/ ) Peek/Torlon (/ / ) P Operation mbar abs at T Operating ) C C (66 F) C ( F) ) Higher temperatures are allowed for CIP / SIP cleaning for limited time periods, see the table titled "Max. allowable cleaning temperature". Maximum Allowable Cleaning Temperature CIP cleaning Lining T max T max Minutes Steam cleaning PFA / Peek C ( F) Wet cleaning PFA / Peek / Torlon C ( F) T amb. 6 C (77 F) 6 C (77 F) If the ambient temperature is > C (77 F), then the difference must be subtracted from the max. cleaning temperature. T max Δ C, Δ C = (T amb - C) Maximum Allowable Temperature Shock Lining Temp Shock max. Temp. Diff. C Temp. gradient C/min PFA Any Any Peek, Torlon Any Any Maximum allowable ambient temperature as function of fluid temperature T amb. C ( F) - Fig. 7: DN... DN 6 () () - 9 (9) (F) - DN... DN () () - (-) Temperature graph The flowmeter sensor must not be isolated. (66) G T Measuring C ( F) Fluid temperature DN DN (/... /") - C (... F), max. allowable cleaning temperature, see table. Flowmeter material Lining Electrode material Electrode design PFA, Peek, Torlon Standard Others Standard Others Hast.-C Hast.-B Flat head Pointed (.6) (.6), head (.9.9 ( DN ) [9 L] (9 L),.9 for pipe.7 (9 L) conn. and (6 Ti), Tri-Clamp) Titanium, tantalum, Platinumiridium /" sanitary connectors always with grounding electrodes in material for signal electrodes, standard. Process connection material Process connection Standard Option Flange Stainless steel.7 On rqst. (6 Ti) Wafer type None Weld stubs Stainless steel. On rqst. (6 L) Threaded pipe Stainless steel. On rqst. connection (6 L) Tri-Clamp Stainless steel. On rqst. (6 L) External threads Stainless steel. (6 L) On rqst. /" sanitary connectors Terminal box - without/with preamplifier, type A - with preamplifier, type B Stainless steel.7 (6 Ti) Stainless steel. () Al alloy, painted, paint coat frame: dark gray, RAL 7 cover: light gray, RAL 9 POM, brass, PVC Meter tube Stainless steel. () cable gland used Polyamide PVDF Flowmeter sensor housing Stainless steel. () Gasket material (internal) Process Standard Option connection Wafer type None Weld stubs Threaded pipe connection Tri-Clamp External threads /" sanitary connectors Flat gaskets EPDM (Ethylene- Propylene) with FDA approval, silicone with FDA approval (CIPresistant, no oils or grease) PTFE Silicon (resistant to oil, grease) Silicon with FDA approval (optional, resistant to oils and grease) PTFE with FDA approval (DN... ) Viton (only in combination with PVC process connection)

33 Electromagnetic Flowmeter FSM DS7U Storage temperature - 7 C (-... F) Degree of protection acc. to EN 69 IP 67 IP 6 (option) JIS B-K wafer type Meter size DN (¼ ) Material PN TS PS [bar]. (6 L),. (6 L),. () - C (- 66 F) Pipeline vibration according to EN Transmitter - In the range of Hz, max. deflection. mm Flowmeter sensor - In the range of Hz, max. deflection. mm - In the range of Hz, max. acceleration g Materialload for meters with variable process connections / wafer type SE DN... DN (/... ") Process Nominal connection diameter Liner PFA DN Wafer type (/ ) 6 ( / ) Weld stubs (/ / ) ; (, ) 6, Threaded pipe connection conforming to DIN Tri-Clamp conforming to DIN 676 Tri-Clamp in acc. with ASME BPE External threads ISO /" sanitary connectors ( / ) (/ / ) ; (, ) 6, ( / ) (/ ) 6 ( / )... (/... ) (/ (/ / ) PS max [bar] TS min - C (- F) - C (- F) - C (- F) - C (- F) - C (- F) 6 - C (- F) - C ( F) TS max C (66 F) C (66 F) C (66 F) C ( F) C (66 F) C (66 F) C ( F) Material load for flange model SEF Lining: PFA PS [bar] PN PS [psi] PN PN PN *) [ C] *) [ F] TS Fig. : DIN flange, stainless steel.7 (6 Ti) up to DN (") Liner PFA PS [bar] CL CL PS [psi] *) [ C] *) [ F] TS Fig. 9: ASME flange, stainless steel.7 (6 Ti) up to DN (") 7. G G Material load for flange model SEW Lining: PFA wafer type PS [bar] PS [psi] 6.. PN /CL 7.. PN *) [ C] *) [ F] Fig. PN 6/CL PN TS G *) For CIP / SIP cleaning, higher temperatures are permitted for limited time periods; refer to the table titled "Maximum permissible cleaning temperature".

34 Electromagnetic Flowmeter FSM DS7U Change from one to two columns. Dimensions.. Model SEF Stainless steel housing, flange acc. to DIN / EN 9-, DN... DN ; ASME B6., /... /" (,9) (,) (,6) F E Ød ØD F E G G 7 (,) Ød A L b k D G9 Fig. : Dimensions in mm (inch) Cable gland M x. or NPT Number of holes N Flange dimensions acc. to DIN / EN, liner PFA Weight DN PN mm approx. kg L ) A D k d d b E F G... ) , DN PN inch Approx. lb L ) A D k d d b E F G... ) , , ) If a grounding plate is required, L + mm (."), material upon request. With grounding plates (protection plates) L + 6 mm (."), material upon request. ) Connecting dimensions acc. to EN9- ) Connection flange DN (/") ) Connection flange /"

35 Electromagnetic Flowmeter FSM DS7U Flange dimensions acc. to ASME B6., liner PFA Weight Inch PN mm approx. kg L ) A D k d d b E F G /... /6 ) / ), / / CL / / /... /6 ) / ), / / CL / / Inch PN inch Approx. lb L ) A D k d d b E F G /... /6 ) / ), / / CL / / /... /6 ) / ), / / CL / / ) If a grounding plate is required, L + mm (."), material upon request. With grounding plates (protection plates) L + 6 mm (."), material upon request. ) Connecting dimensions acc. to EN9- ) Connection flange DN (/") ) Connection flange /"

36 Electromagnetic Flowmeter FSM DS7U Stainless steel housing, flange acc. to DIN / EN 9-, DN... DN ; ASME B6.,... " (,) (,6) d E E G 7 (,) G Ød ØD A L b G Fig. : Dimensions in mm (inch) Cable gland M x. or NPT Number of holes N Flange dimensions acc. to DIN / EN, liner PFA Weight DN PN mm approx. kg L ) A D k d d N b E G ) inch DN PN Approx. lb L ) A D k d d N b E G ) ) If a grounding plate is required, L + mm (."), material upon request. With grounding plates (protection plates) L + 6 mm (."), material upon request. ) For DN 6/PN 6 acc. to EN 9- please order PN

37 Electromagnetic Flowmeter FSM DS7U Flange dimensions acc. to ASME B6., liner PFA Weight Inch PN mm approx. kg L ) A D k d d N b E G / CL / CL Inch PN inch Approx. lb L ) A D k d d N b E G / CL / CL ) If a grounding plate is required, L + mm (."), material upon request. With grounding plates (protection plates) L + 6 mm (."), material upon request. 7

38 Electromagnetic Flowmeter FSM DS7U.. Model SEW Stainless steel housing, wafer type DN... DN (/... ") DN... DN (/... ½") (,) (,6) F E G 7 (,) A ØDi ØC ØD J DN... DN (/... /6 ) 7 (,6) B A* L x Ø, (, ) C ØDi Ø.6 G DN... DN (... ") (,) (,6) F ØDi ØC ØD E G 7 (,) A* L G9 Fig. : Dimensions in mm (inch) Cable gland Pg. or NPT Pattern for axial holes Hole pattern Mounting bracket (optional)

39 Electromagnetic Flowmeter FSM DS7U Wafer type dimensions Weight DN (inch) PN mm approx. L ) A* A B C ØC ØDi ØD E F G J kg (/) (/) 6 (/) (/6) , (/) (/)... CL (/) CL , JIS () , ( /) , ( /) , () , 6 ( /) , () CL JIS , () , DN (inch) PN inch Approx. L ) lb A* A B C ØC ØDi ØD E F G J (/) (/)..6 6 (/) (/6) (/) (/)... CL.9..6 (/) CL JIS () ( /) ( /) () ( /) () CL JIS () ) Installation lengths with ground plates L + mm (.") Mounting bracket (optional) With mounting bracket, combined height + 7 mm (.6") DN... DN (/... ½"), +. mm (.") DN... DN (... "). 9

40 Electromagnetic Flowmeter FSM DS7U.. Model SE_ Variable process connection DN... DN (/... ½") (,9) (,) (,) (,6) G F E 7 (,) A ØD x Ø. (,) 7 (,6) B C G DN... DN (... ") (,9) (,) (,) (,6) 7 (,) 6 G E (,) F, (,) ØD Fig. : Dimensions in mm (inch) Cable gland Pg. or NPT Pattern for axial holes Mounting bracket (optional) x Ø. B DN 6... ( /... ) xø. C DN () Hole pattern L Pipe 6 Number of holes N G

41 Electromagnetic Flowmeter FSM DS7U DN (inch) Variable process connection mm A ØD B C E F G L Pipe N... (/... /) Weight appr. kg ) (/) (/) () ( /) ( /) () ( /) 6 6. () () DN (inch) inch A ØD B C E F G L Pipe N... (/... /) (/) (/) () ( /) ( /) () ( /) appr. lb ) () () ) For process connection weights see page Mounting bracket (optional) With mounting bracket, combined height +7 mm (.6") DN... DN (/... ½"), +. mm (.") DN... DN (... ").

42 Electromagnetic Flowmeter FSM DS7U.. Adapter for variable process connections DN... DN (/... ") L L Di Da R Di Da a Fig. Weld stubs Threaded pipe connection DIN L Tri-Clamp External threads L G7 Weld stubs Weight mm DN (inch) ISO 7 DIN SMS DIN 6 ISO 7 kg Ø Di Ø Da Ø Di Ø Da Series Ø Di Ø Da Ø Di Ø Da Ø Di Ø Da Series L... (/... /) (/) (/) () ( /) ( /) () ( /) () () inch DN (inch) ISO 7 DIN SMS DIN 6 ISO 7 lb Ø Di Ø Da Ø Di Ø Da Series Ø Di Ø Da Ø Di Ø Da Ø Di Ø Da Series L... (/... /) (/) (/) () ( /) ( /) () ( /) () ()

43 Electromagnetic Flowmeter FSM DS7U Threaded pipe connection Tri-Clamp DIN DIN 676 ASME BPE DN (inch) mm mm mm Weight Weight Weight Rd. thd. L /kg Ø Di Ø Da Series L /kg Tri-Clamp Ø Di Ø Da L kg... (/... /) x /" /" 9... (/) x /" /".7.. (/) x /6" "...7 () x /6" "... ( /) x /6" ( /) 6 x /6" 7... /" () 7 x /6" " ( /) 96 x /6" /" () x /" " () x /" " inch inch inch DN (inch) Weight Weight Weight Rd. thd. L /lb Ø Di Ø Da Series L /lb Tri-Clamp Ø Di Ø Da L lb... (/... /) x /" /" (/) x /" /" (/) x /6" " () x /6" " ( /) x /6" ( /) 6 x /6" /" () 7 x /6" " ( /) 96 x /6" /" () x /" " () x /" " External threads ISO / DIN 999, tapered Weight DN (inch) mm R a L kg... (/... /) /" 9. (/) /" 9. (/) /" 6. () " 79. DN (inch) inch R a L lb... (/... /) /".7.7. (/) /".7.7. (/) /" () "

44 Electromagnetic Flowmeter FSM DS7U.. Model SEB /" sanitary connectors, DN... DN (/... /") C D E F A B (,9) (,9) (,7) (,7) Fig. 6: Dimensions in mm (inch) Gaskets Connecting dimensions for gland G /" internal thread 6 (,) x Ø. 6 (,6) (,7) 9 (,) (,9) (,) 69 (,7) Cable gland Pg. or NPT Mounting bracket, standard G6 Important The flowmeter sensor is equipped as standard with grounding electrodes in the same material as the measuring electrodes. The flowmeter sensor can only be operated on S transmitters with software version B. or higher. Preamplifier A B C D E F Without / type A 9 (.6) 7 (.79) 6 (.) (.7) (.) (.6) Type B (.9) 6 (.) 6 (6.) 7 (.79) (.9) 7 (.7) Process Connection DN PN Weight kg /" sanitary connectors )... (/... /"). (. lb) ) For hose 6 x mm

45 Electromagnetic Flowmeter FSM DS7U. Ordering information Welded Flange, Liner Material PFA Main order number Add. order no. Version number XX Electromagnetic Flowmeter SEF- X X X X X X X X X X X X X X X X X X X X X X XX FSM Process Connection Welded flange DIN / ASME F Liner Material / Meter Size PFA / DN (/ in.) P PFA / DN (/ in.) P PFA / DN 6 (/ in.) P 6 PFA / DN (/6 in.) P PFA / DN (/ in.) P PFA / DN (/ in.) P PFA / DN (/ in.) P PFA / DN ( in.) P PFA / DN (-/ in.) P PFA / DN (-/ in.) P PFA / DN ( in.) P PFA / DN 6 (-/ in.) P 6 PFA / DN ( in.) P PFA / DN ( in.) P H Measuring Electrodes Material / Grounding Electrodes Hastelloy C- (.6) / Without H Hastelloy B- (.6) / Without B AISI 6Ti SST (.7) / Without S Titanium / Without M Tantalum / Without T AISI 9L SST (.9) / Without ) F Platinum-Iridium / Without P Hastelloy C- (.6) / With O Hastelloy B- (.6) / With N AISI 6Ti SST (.7) / With E Titanium / With I Tantalum / With Q AISI 9L SST (.9) / With ) R Platinum-Iridium / With G Pressure Rating PN 6 ) D PN F ASME CL P ASME CL Q Material of Process Connection AISI 6Ti SST (.7) Accessories Without A Protection rings AISI 6Ti SST (.7) ) B Grounding ring AISI 6Ti SST (.7) ) C Temperature Range Standard design (<= C [66 F]) S Certificates PED Standard A Material certificate. acc. EN with ) D pressure test AD Pressure test AD G Inspection certificate. acc. EN F Calibration Certificates Standard A Fingerprint saved at factory ) F Continued on next page ) For food and beverage applications ) DN 6 (-/ in.) / PN 6 with connection dimensions acc. EN 9-: Please order PN ) Protection rings mounted on both sides and ground rings mounted on one side to flange. Material SST.7 (6Ti) ) Material certificate for meter tube and flanges ) > DN (/ in.)

46 Electromagnetic Flowmeter FSM DS7U Main order number Add. order no. Variantenstelle XX Electromagnetic Flowmeter FSM SEF- X X X X X X X X X X X X X X X X X X X X X X XX Type of Protection / Cable Entry IP 67 / Thread for screw-type conduit fitting M x. IP 67 / Thread for screw-type conduit fitting NPT / in. IP 6 / Thread for screw-type conduit fitting M x. 6) 7 IP 6 / Cable connected and connection box potted Design Without pre-amplifier 7) With pre-amplifier type A ) With pre-amplifier type B 9) Name Plate Language / Type German / Adhesive foil G English / Adhesive foil E French / Adhesive foil F German / Stainless steel J English / Stainless steel K French / Stainless steel L Design Level (Specified by ABB) x Electrode Design Standard Conical head, AISI 9L SST (.9) ) Signal Cable Length Without cable m (6 ft) m ( ft) m (66 ft) m (99 ft) m ( ft) m (6 ft) 6 m (9 ft) 6 7 m ( ft) 7 m (6 ft) 9 m (9 ft) 9 m ( ft) m ( ft) m (9 ft) 7 m (7 ft) 7 m (66 ft) Excitation Cable Length Without cable m (6 ft) m ( ft) m (66 ft) m (99 ft) m ( ft) m (6 ft) 6 m (9 ft) 6 7 m ( ft) 7 m (6 ft) 9 m (9 ft) 9 m ( ft) m ( ft) m (9 ft) 7 m (7 ft) 7 m (66 ft) Continued on next page 6) Sealing compound (optional): DBU 7) From DN (/ in.) >= μs/cm ) Standard up to DN (/6 in.) >= μs/cm, > DN (/6 in.) >= μs/cm and lay length max. m (66 ft) 9) Option: Up to DN (/6 in.) >= µs/cm, > DN (/6 in.) >=. µs/cm and lay length max. m (66 ft) ) For application e.g. with high fat contents 6

47 Electromagnetic Flowmeter FSM DS7U Main order number Add. order no. Variantenstelle XX Electromagnetic Flowmeter SEF- X X X X X X X X X X X X X X X X X X X X X X XX FSM Calibration Points (Standard) VK Point Standard Calibration VC Witnessed Calibration, Calibration Points ) VE Point Calibration acc. DKD ) VD Language of Documentation German M English M Russian MB Language package Western Europe / Scandinavia (Languages DE, EN, DA, ES, FR, IT, NL, PT, FI, SV) ME Language package Eastern Europe (Languages DE, EL, CS, ET, LV, LT, HU, PL, SK, SL, RO, BG) MW Others MZ Other Usage Certifications Russia, Metrological and GOST-R Certificate CG Kazakhstan, Metrological and GOST-K Certificate CG Ukraine, Metrological Certificate CG Belarus, Metrological Certificate CG6 ) Only available with FSM-S External Converter 7

48 Electromagnetic Flowmeter FSM DS7U Wafer Type / / in. Sanitary Connection / Variable Process Connections, Liner Material Torlon, PEEK, PFA Main order number Add. order no. Version number XX Electromagnetic Flowmeter SE- X X X X X X X X X X X X X X X X X X X X X X X XX FSM Process Connection Wafer type W Weld stubs DIN R Weld stubs DIN 6 Q Weld stubs ISO 7 J Weld stubs SMS X Without adapter ) V Weld stubs ISO 7 P Pipe connection DIN S Tri-Clamp DIN 676 T Tri-Clamp ASME BPE K Male thread ISO / DIN 999 E conical / in. Pipe thread B Liner Material / Meter Size PEEK / DN (/ in.) K PEEK / DN, (/7 in.) K S PEEK / DN (/ in.) K Torlon / DN (/ in.) N Torlon / DN, (/7 in.) N S Torlon / DN (/ in.) N PFA / DN (/ in.) P PFA / DN (/ in.) P PFA / DN 6 (/ in.) P 6 PFA / DN (/6 in.) P PFA / DN (/ in.) P PFA / DN (/ in.) P PFA / DN (/ in.) P PFA / DN ( in.) P PFA / DN (-/ in.) P PFA / DN (-/ in.) P PFA / DN ( in.) P PFA / DN 6 (-/ in.) P 6 PFA / DN ( in.) P PFA / DN ( in.) P H Measuring Electrodes Material / Grounding Electrodes Hastelloy C- (.6) / Without H Hastelloy B- (.6) / Without B AISI 6Ti SST (.7) / Without S Titanium / Without M Tantalum / Without T AISI 9L SST (.9) / Without ) F Platinum-Iridium / Without P Hastelloy C- (.6) / With O Hastelloy B- (.6) / With N AISI 6Ti SST (.7) / With E Titanium / With I Tantalum / With Q AISI 9L SST (.9) / With ) R Platinum-Iridium / With G Pressure Rating PN C PN 6 D PN F ASME CL P ASME CL Q Continued on next page ) Spare sensor, for replacement only ) For food and beverage applications

49 Electromagnetic Flowmeter FSM DS7U Main order number Add. order no. Version number XX Electromagnetic Flowmeter FSM SE- X X X X X X X X X X X X X X X X X X X X X X X XX Material of Process Connection Without AISI 6Ti SST (.7) ) AISI 6L SST (.) PVC ) 7 POM ) Accessories Without 6) A With fastening element 7) C Temperature Range Standard design (<= C [66 F]) (DN... DN : max. S C [ F]) Certificates PED Standard A Material certificate. acc. EN with pressure test ) D AD Pressure test AD G Inspection certificate. acc. EN F Calibration Certificates Standard A Fingerprint saved at factory 9) F Type of Protection / Cable Entry IP 67 / Thread for screw-type conduit fitting M x. IP 67 / Thread for screw-type conduit fitting NPT / in. IP 6 / Thread for screw-type conduit fitting M x. ) 7 IP 6 / Cable connected and connection box potted Design Without pre-amplifier ) With pre-amplifier type A ) With pre-amplifier type B ) Name Plate Language / Type German / Adhesive foil G English / Adhesive foil E French / Adhesive foil F German / Stainless steel J English / Stainless steel K French / Stainless steel L Design Level (Specified by ABB) x Electrode Design Standard Conical head, AISI 9L SST ) (.9) Continued on next page ) Standard at / in. pipe thread and welded flange ) DN... DN (/... / in.) see Gasket ) DN... DN (/... / in.) 6) > DN (/ in.) 7) No A conformity ) Certificate for meter tube and adapter => DN (/ in.) 9) > DN (/ in.) ) Sealing compound optional: DBU ) From DN (/ in.) >= μs/cm ) Standard up to DN (/6 in.) >= μs/cm, option > DN (/6 in.) >= μs/cm and lay length max. m (66 ft) ) Option: Up to DN (/6 in.) >= µs/cm, > DN (/6 in.) >=. µs/cm and lay length max. m (66 ft) ) For application e.g. with high fat contents 9

50 Electromagnetic Flowmeter FSM DS7U Main order number Add. order no. Version number XX Electromagnetic Flowmeter SE- X X X X X X X X X X X X X X X X X X X X X X X XX FSM Gasket Material Without A EPDM (with FDA certificate) E Silicone (with FDA certificate) S PTFE ) T Viton 6) V Signal Cable Length Without cable m (6 ft) m ( ft) m (66 ft) m (99 ft) m ( ft) m (6 ft) 6 m (9 ft) 6 7 m ( ft) 7 m (6 ft) 9 m (9 ft) 9 m ( ft) m ( ft) m (9 ft) 7 m (7 ft) 7 m (66 ft) Excitation Cable Length Without cable m (6 ft) m ( ft) m (66 ft) m (99 ft) m ( ft) m (6 ft) 6 m (9 ft) 6 7 m ( ft) 7 m (6 ft) 9 m (9 ft) 9 m ( ft) m ( ft) m (9 ft) 7 m (7 ft) 7 m (66 ft) Continued on next page ) Only DN... DN (/... / in.) 6) Only DN... DN (/... / in.) and PVC process connection

51 Electromagnetic Flowmeter FSM DS7U Main order number Add. order no. Version number XX Electromagnetic Flowmeter FSM SE- X X X X X X X X X X X X X X X X X X X X X X X XX Calibration Points (Standard) VK Point Standard Calibration VC Witnessed Calibration, Calibration Points 7) VE Point Calibration acc. DKD 7) VD Language of Documentation German M English M Russian MB Language package Western Europe / Scandinavia (Languages DE, EN, DA, ES, FR, IT, NL, PT, FI, SV) ME Language package Eastern Europe (Languages DE, EL, CS, ET, LV, LT, HU, PL, SK, SL, RO, BG) MW Others MZ Other Usage Certifications Russia, Metrological and GOST-R Certificate CG Kazakhstan, Metrological and GOST-K Certificate CG Ukraine, Metrological Certificate CG Belarus, Metrological Certificate CG6 7) Only available with FSM-S External Converter

52 Electromagnetic Flowmeter FSM DS7U Mounting accessories Change from one to two columns Wafer type accessories The following accessories are available based on meter size and pressure rating: Bolts, nuts, lockwashers. Gaskets are not included in the accessories. For order information, see page. Weld connections For flowmeters with welded connections, welding adapters are available. For order information, see page.

53 Electromagnetic Flowmeter FSM DS7U Change from one to two columns. Ordering information Wafer type Accessories (Table H) Wafer type Accessories Description Nominal size Nominal pressure rating Order number FX / FSM Wafer type Accessories DN... DN (/... / in.) PN... PN D6L6U ASME CL D6L6U ASME CL D6L6U Welding adapter DN (/ in.) PN... PN D6L6U ASME CL D6L66U ASME CL D6L66U6 DN (/ in.) PN... PN D6L67U ASME CL D6L67U ASME CL D6L67U6 DN ( in.) PN... PN D6L6U ASME CL D6L6U ASME CL D6L6U6 DN (-/ in.) PN... PN D6L69U ASME CL D6L69U ASME CL D6L69U6 DN (-/ in.) PN... PN D6L7U ASME CL D6L7U ASME CL D6L7U6 DN ( in.) PN... PN D6L96U ASME CL D6L96U ASME CL D6L96U6 DN 6 (-/ in.) PN... PN 6 D6L97U PN... PN D6L97U9 ASME CL D6L97U ASME CL D6L97U DN ( in.) PN... PN D6L9U ASME CL D6L9U9 ASME CL D6L9U DN ( in.) PN... PN 6 D6L99U7 PN... PN D6L99U ASME CL D6L99U9 Material Nominal size Order number Stainless steel AISI (.) DN... DN (/... / in.) DC7U DN (/ in.) DC7U DN (/ in.) DC7U DN ( in.) DN (-/ in.) DN (-/ in.) DN ( in.) DN 6 (-/ in.) DN ( in.) DN ( in) DC7U DC7U DC7U DCU DC6U9 DC96U DC9U The adapter is a tool for sensors that feature weld stubs as the process connection type. It enables these weld stubs to be welded into the pipeline in a coplanar manner.

54 Change from one to two columns Electromagnetic Flowmeter FSM DS7U 6 Transmitter 6. Specifications Design Field-mount housing made of cast aluminum per DIN 7, painted. Paint coat thickness µm. Lower section (RAL 7), upper section (RAL 9). See dimensions on page 6. Weight, approx.. kg. Electrical connections Cable entry M x., NPT, PF with adapter (upon request), screw terminals Damping (τ) Configurable for.7... s. Fig. 7: Transmitter FSM-S Measuring range Minimum conductivity Repeatability (measurement period = s) Response time Supply power Power consumption Ambient temperature Storage temperature G Any flow range whose % value corresponds to a flow velocity between. m/s and m/s can be selected. µs/cm standard DN... (/... ) µs/cm with preamplifier DN... (/... /6 ) µs/cm with preamplifier DN... (/... ). µs/cm with preamplifier DN... (/... ) DN... (/... /"): ± (. % of measured value +. % of Q maxdn ) DN... (/... "): ± (. % of measured value +. % of Q maxdn ) τ = 7 ms ( %) "Fast" mode τ = ms ( %) "Standard" mode/piston pump U =... V, / 6 Hz U rat =... V, / 6 Hz /6 Hz ± 6% V AC,..... V DC, ripple % S VA (flowmeter sensor including transmitter) C (-... F) -... C ( F) Relative humidity Acc. to IEC 66-- classification of environmental conditions, natural factors, temperature and air humidity. No effect under the following conditions: Temperature in range from... C (77... F) and a relative humidity of %. Vibration Acc. to IEC (/9), grouping of devices according to table C for general industry applications. No additional effect on the following levels of vibration. Frequency:... Hz; amplitude max.. mm. Low flow cutoff Configurable for... % of end value range Signal cable Max. cable length between flowmeter sensor and transmitter is: m for the standard design and versions with automatic zero return, from DN (/") and from µs/cm. m for designs with preamplifier. A m signal cable is included with each flowmeter. If a longer cable is required, see the order information for the flowmeter sensor on page,. Magnet coil supply cable Is required to connect the flowmeter sensor to the transmitter. For EMC reasons, the -wire cable is shielded. A m cable is included with each flowmeter. If a longer cable is required, see the order information for the flowmeter sensor on page,. Forward/reverse flow metering Flow direction is indicated by direction arrows in the display and over the contact for external signaling. The contact output can also transmit this information. Display -line, illuminated graphic display. To improve readability, the flow information can be displayed on two lines with larger characters. This allows the individual flowrate and output values to be displayed. Nonswitching dot-matrix display with max. x 6 characters. A plaintext diagnostic display opens automatically when the system detects an error. An alarm condition can also be signaled via contact output. Data backup Via FRAM (ferroelectric non-volatile random access memory) all data is stored for a period of years (even without supply power) at shutoff or during a power outage. Additional security is provided by a serial FRAM installed in the transmitter and on the external connection board in which the parameter settings and process information are stored. This makes it easy to replace a transmitter without reconfiguration by simply uploading the stored data from the external FRAM to the new transmitter. Flow totalization The flow is totalized in engineering units. The limits for the pulse factor are configurable and depend on the measuring range (Qmax) as well as the totalizer units selected. The limits are a min. (.6 Hz) and max. pulse frequency ( KHz). Totalizer values for the forward and reverse flow directions can be displayed simultaneously by selecting the "Display" menu item. Degree of protection acc. to EN 69 IP 67 for field-mount housing and NEMA X

55 Electromagnetic Flowmeter FSM DS7U Parameter adjustment The display supports several languages (German, English, French, Finnish, Swedish, Italian, Spanish, Dutch or Turkish), and information can be entered using the three keys in the dialog or via a communication interface with PC, HART protocol, PROFIBUS or FOUNDATION Fieldbus. The magnet stick can also be used to configure the flowmeter with the front door closed. Position the magnet stick over the magnet icons on the display cover. Alarm signals A max-min alarm can be used with the transmitter. The alarm limits can be set between... % of the flow range. When the flowrate is outside the alarm limits, an error message is displayed in the upper line and a contact is triggered. The contact output can also transmit this information. Wiring error Monitoring of magnet coil or electrode circuits for short circuits or wire breaks. Upgrades The transmitter with all its functions can also be used with older model electromagnetic flowmeters. The appropriate model number must be selected during parameter setting of the transmitter. It is also possible to use the transmitter with model D flowmeters. A special FRAM (Cs = %, Cz = %) is required when updating an older model (see order information for transmitter) and applies for meter sizes DN... DN (/... ") in low voltage design only. Isolation of input/output The current output, pulse output, contact input and contact output are electrically isolated from the input circuit and from each other. Extended diagnostic functions Recorded parameters/fingerprints Cyclical ( s... 7 days) or manual acquisition of parameters. The data records are stored in the transmitter FRAM (with time stamp / operating hours counter). A maximum of records can be stored. When the eleventh record is stored, the oldest data record is overwritten automatically. Magnet coil circuit Electrode circuit AC voltage AC DC resistance (primary value for temperature) Temperature Insulation resistance (ground) DAC value (primary value for coil current) Magnetic linearity Electrode voltage E (primary value for electrode balance) Electrode voltage E (primary value for electrode balance) Electrode balance Quality (signal-to-noise ratio) The parameters can be checked for min.-max. errors. If the value is above or below the specified limit, a diagnostic error or warning, depending on the configuration, is triggered. The fingerprint database integrated in the transmitter allows you to compare the values at the time of factory calibration or commissioning with the currently recorded values. Users can store up to three different fingerprint data records (commissioning, product, product) in the fingerprint database. The default fingerprint (optional) cannot be overwritten. Detectable error states Monitoring of... Detection of... Coil current / coil Changes in the driver or coil circuit. voltage / DAC value Coil resistance Changes in coil circuit, e.g., fine short. Coil temperature Risk of overheating due to fluid. Coil insulation resistance Linearity of magnetic circuit Signal quality (signalto-noise ratio) Electrode balance Problems with the coil insulation. Can be caused, e.g., by dampness in the flowmeter sensor or in the connection box. External magn. field interference on the EMF, resulting in loss of accuracy. Changes in fluid, e.g., gas bubbles, increased / reduced amount of solids. Distorted flow profile, e.g., due to improper installation. Detect interference in electrode circuit, e.g., failure of electrode due to insulating coating or a collapsed liner (vacuum shock). Backward compatibility The transmitter is suitable for connecting to flowmeter sensors over years old. Occasionally, an adapter board may be required (for details, see the FSM operating instructions). The following flowmeter sensors are supported: DS, DSF, DSF, DS (A-E), DI, D, D6, D7

56 Electromagnetic Flowmeter FSM DS7U 6. Inputs/outputs DC output (terminals, ) The following functions can be selected in the software:... ma load 6 Ω... ma load 6 Ω... ma load Ω... ma load Ω Contact output (terminals, ) The following functions can be selected in the software: Forward/reverse flow direction signal Flowrate alarm (max. or min.) General alarm Empty pipe The contact output can be configured as normally open or normally closed. Optocoupler "closed" "open" V U CEL V, ma I CEL ma 6 V U CEH V, ma I CEH ma Scaled pulse output (terminals, ) Maximum totalizer frequency khz. Pulse factor per engineering unit from.... / unit selectable in the software. The pulse width is configurable from.... The version (active, passive) can be changed via jumpers. Active Voltage pulse V rectangular Load Ω Pulse width ms, max. pulse frequency Hz, Load Ω Pulse width. ms, max. pulse frequency: khz. Passive Optocoupler "closed": "open": V U CEL V, ma I CEL ma 6 V U CEH V, ma I CEH ma Contact input (terminals /) Passive based on normally open contact (closed). The following functions can be selected in the software: External output signal switch-off When the meter tube empties the output signals can be turned off. DC output, e.g., ma or / ma, depending on current output configuration. External totalizer reset For totalizer overflows displayed internally and pulse counters for both flow directions. External system zero position Starts the external zero adjustment. To run a zero adjustment, the metering tube must be full and flowrate must be zero. The adjustment lasts approx. minute. Design passive (optocoupler) "ON": 6 V U KL V "OFF" V U KL V Ri: kω 6. Digital communication The transmitter has the following options for digital communication: 6.. HART protocol The unit is registered with the HART Communication Foundation. Fig. HART protocol Configuration Transmission Max. signal amplitude Current output load Cable Max. cable length Baud rate Display Directly on the device Software DAT Asset Vision Basic (+ HART-DTM) FSK modulation on current output... ma acc. to Bell standard. ma ss Min. Ω, max. = 6 Ω AWG twisted m baud Log. : Hz Log. : Hz For additional information, see the separate interface description. System integration In conjunction with the DTM (Device Type Manager) available for the device (software version B. and higher), communication (configuration, parameterization) can occur with the corresponding framework applications according to FDT. (DAT Asset Vision Basic). Other tool/system integrations (e.g., Emerson AMS/Siemens S7) are available upon request. A free of charge version of the DAT Asset Vision Basic framework application for HART or PROFIBUS is available upon request. The required DTMs are contained on the DAT Asset Vision Basic DVD or in the DTM Library. They can also be downloaded from PROFIBUS PA protocol The interface conforms to Profile. (PROFIBUS standard, EN 7, DIN 9 [PRO9]). PROFIBUS PA ID no.: x7c Alternative standard ID no.: x97 or x97 Configuration Directly on the device Software DAT Asset Vision Basic (+ PROFIBUS PA-DTM) Transmission signal Acc. to IEC 6- Cable Shielded, twisted cable (acc. to IEC 6-, types A or B are preferred) 6

57 Electromagnetic Flowmeter FSM DS7U PROFIBUS DP PROFIBUS PA H-Bus A PA+ PA- PA+ PA- PA+ PA- A = Segment coupler (incl. bus supply and termination) Fig. 9: Example for PROFIBUS PA interface connection F G 6.. FOUNDATION Fieldbus (FF) FF interface Compliant with FF standard 9/9 and FF 9/9 Interoperability test IT 7 (ITK.6) campaign no. Manufacturer ID x Device ID x7 Configuration Directly on the device Via services integrated in the system National configurator Transmission signal Acc. to IEC 6- Bus topology Tree and / or line structure Bus termination: passive at both ends of the main bus line (RC element R = Ω, C = µf) Voltage / current consumption Average current consumption: ma In the event of an error, the integrated FDE function (=Fault Disconnection Electronic) integrated in the device is ensures that the current consumption can rise to a maximum of ma. The upper current limit is restricted electronically. The voltage on the bus line must lie in the range of 9... V DC. Bus address In the case of devices with a PROFIBUS PA interface, check the bus address prior to commissioning. If no specifications exist to the contrary, the address is set to 6. During commissioning, the address must be set to a valid value in the range.... System integration Use of PROFIBUS PA profile B, B. ensures interoperability and interchangeability of units. Interoperability means that devices from different manufacturers can be physically connected to a bus and are communication-ready. The devices can be interchanged without having to reconfigure the process control system. To support interchangeability, three different GSD files (equipment master data) are provided, which can be integrated in the system. For additional information, see the separate interface description. The manufacturer-specific GSD file ABB_7C can be downloaded from The standard GSD files PA97xx.gsd can be downloaded from Ethernet HSE-Bus B FOUNDATION Fieldbus H FF+ FF- FF+ FF- FF+ FF- F G B = Linking device (incl. bus supply and termination) Fig. : Example for FOUNDATION Fieldbus interface connection Bus topology Tree and / or line structure Bus termination: passive at both ends of the main bus line (RC element R = Ω, C = µf) Voltage / current consumption Average current consumption: ma In the event of an error, the integrated FDE function (=Fault Disconnection Electronic) integrated in the device is ensures that the current consumption can rise to a maximum of ma. Upper current limit: electronically restricted. The voltage on the bus line must lie in the range of 9... V DC. Bus address The bus address is automatically assigned or can be set in the system manually. Addresses are detected using a unique combination of manufacturer ID, device ID, and device serial number. System integration The following are required: DD (Device Description) file, which includes the device description. The CFF (Common File Format) file is required for engineering the segment. Engineering can be performed online or offline. For additional information, see the separate interface description. The files required for operation can be downloaded from 7

58 Electromagnetic Flowmeter FSM DS7U Change from one to two columns 6. Electrical connections Standard DN... DN (/... ") S transmitter (wall mount housing) S S M M - + N L SE S S A 6 M M SE Flowmeter sensor G9 Fig. : Connection diagram: Flowmeter sensor standard DN... DN (/... ") Functional ground (busbar) Pulse output ) Contact input ) Contact output ) Current output ) 6 Magnet coil cable: shielded x mm CE Typ 7 TEC 7 ABB order no. D7D7U, m included in shipment, standard 7 Supply power Low voltage:... V AC, terminals L, N, Low voltage: V AC; Low voltage:..... V DC Low voltage: Terminals +, -, Frequency: 7 Hz f Hz; Hz supply power Frequency: 6 Hz f 6 Hz; 6 Hz supply power Steel shielding 9 Aluminum foil Yellow Shield Blue Red White Shielded signal cable: ABB order no. D7DU, m included in shipment ) See the section "Connection examples for peripherals" in the operating instructions and/or on the data sheet Comment: We recommend that shielded output cables be used with the shields connected to the functional ground at one end.

59 Electromagnetic Flowmeter FSM DS7U with preamplifier DN... DN (/... ") S transmitter (wall mount housing) U+ U M M - + N L SE U+ U- A 6 M M SE Flowmeter sensor G96 Fig. : Connection diagram: Flowmeter sensor with preamplifier DN... DN (/... "), transmitter field-mount housing Functional ground (busbar) Pulse output ) Contact input ) Contact output ) Current output ) 6 Magnet coil cable: shielded x mm CE Typ 7 TEC 7 ABB order no. D7D7U, m included in shipment, standard 7 Supply power Low voltage:... V AC, terminals L, N, Low voltage: V AC; Low voltage:..... V DC Low voltage: Terminals +, -, Frequency: 7 Hz f Hz; Hz supply power Frequency: 6 Hz f 6 Hz; 6 Hz supply power Steel shielding 9 Aluminum foil Yellow Shield Blue Red White Shielded signal cable: ABB order no. D7DU, m, included in shipment 6 With preamplifier (always with DN... DN [/... /6"]) ) See the section "Connection examples for peripherals" in the operating instructions and/or on the data sheet Comment: We recommend that shielded output cables be used with the shields connected to the functional ground at one end. Important If the flowmeter sensor is equipped with a preamplifier for low conductivity or in nominal diameter DN... DN (/... /6"), the shieldings of the signal wires must be connected to terminals U+ and U- on both the flowmeter sensor and the transmitter. 9

60 Electromagnetic Flowmeter FSM DS7U Retrofitting for model D: DN... DN (/... ); model DI and DSA-E: DN... DN (... ) S transmitter (wall mount housing) V S S M M N L SE 6 7 L N Flowmeter sensor G Fig. : Flowmeter sensor standard DN... DN (/... "), transmitter field-mount housing Functional ground (busbar) Pulse output ) Contact input ) Contact output ) Current output ) 6 Supply power Low voltage:... V AC, terminals L, N, Frequency: 7 Hz f Hz; Hz supply power Frequency: 6 Hz f 6 Hz; 6 Hz supply power 7 Shielded signal cable: Use ABB order no. D7DU or incorporate in existing wiring Reference cable: Only for connection to model D Terminals: close 6,7 and the hook switch S9 9 Magnet coil supply: Magnet coil supply via supply power Connection board: D6AU ) See the section "Connection examples" in the operating instructions and/or on the data sheet Comment: We recommend that shielded output cables be used with the shields connected to the functional ground at one end. 6

61 Electromagnetic Flowmeter FSM DS7U DN... DN (/... ") with PROFIBUS PA / FOUNDATION Fieldbus S transmitter (wall mount housing) 6 6 c b FF+ FF- U+ U- PA+ PA- a S S M M - + N L 7 9 SE S S A 6 M M SE SE U+ U- A 6 Flowmeter sensor M M SE 6 G97 Fig. : Connection diagram: transmitter SF with PROFIBUS PA / FOUNDATION Fieldbus Functional ground (busbar) Contact output (see the section "Connection examples for peripherals" in the operating instructions and/or on the data sheet) Digital communication a: PROFIBUS PA design according to IEC 6- (Profile.) a: U = 9... V, I = ma (normal operation) a: U = 9... V, I = ma (in the event of error/fde) a: Terminals: 97/9, PA+/PA- a: (see the section "Connecting via M plug" in the operating a: instructions and/or on the data sheet) b: FOUNDATION Fieldbus design conforming to IEC 6- a: U = 9... V, I = ma (normal operation) a: U = 9... V, I = ma (in the event of error/fde) a: Terminals: 97/9, FF+/FF- a: (see the section "Connecting via M plug" in the operating a: instructions and/or on the data sheet) c: Bus termination with installed bus termination a: components with hook switches closed Magnet coil cable: shielded x mm CE Typ 7 TEC 7 ABB order no. D7D7U, m included in shipment, standard Supply power Low voltage:... V AC, terminals L, N, Low voltage: V AC; Low voltage:..... V DC Low voltage: Terminals +, -, Frequency: 7 Hz f Hz; Hz supply power Frequency: 6 Hz f 6 Hz; 6 Hz supply power 6 Shielded signal cable: Power supply for flowmeter sensor with preamplifier Terminals U+, U- instead of S and S in standard unit 7 Steel shielding Aluminum foil 9 Yellow Shield Blue Red White Shielded signal cable: ABB order no. D7DU, m, included in shipment Without preamplifier 6 With preamplifier (always with DN... DN [/... /6"]) Comment: We recommend that shielded output cables be used with the shields connected to the functional ground at one end. Important If the flowmeter sensor is equipped with a preamplifier for low conductivity or in nominal diameter DN... DN (/... /6"), the shieldings of the signal wires must be connected to terminals U+ and U- on both the flowmeter sensor and the transmitter. 6

62 Electromagnetic Flowmeter FSM DS7U 6. Connection examples for peripherals (incl. HART) Current output /... ma /... ma I E I = internal E = external + - Current output: Function: G selectable in software Active /... ma ( Ω RB 6 Ω) /... ma ( Ω RB Ω) (with HART only... ma) Terminals:, Fig. : Current output active with/without HART protocol (... ma) Contact output I E +U R B * V VDC Note Horn and alarm light are shown only as examples. Other suitable devices such as bells, sirens, buzzers, etc., can also be used. * U R CE B I CE G Contact output: Function: selectable in software Passive "closed" V U CEL V, ma I CEL ma "open" 6 V U CEH V, ma I CEH ma Terminals:, Fig. 6: Contact output for system monitoring, Max.-Min. alarm for empty tube or forward/reverse signal Contact input I E R i +6...VDC V G Contact input: Function: selectable in software Passive "On" 6 V U KL V "Off" V U KL V Ri = kω Terminals:, Fig. 7: Contact input for external totalizer reset and external zero return 6

63 Electromagnetic Flowmeter FSM DS7U Pulse output Pulse output active Pulse output, passive, optocoupler I E R * B V DC - * R B U CE I CE G7 Function: fmax: fmin: Setting range: active/passive, selectable via jumper (see "Commissioning" in operating instructions) khz,.6 Hz Pulses/unit, pulse width (observe dynamic limits) Active: Ω Load < kω Pulse width ms, max. pulse frequency Hz, Ω Load < kω Pulse width. ms, max. pulse frequency: khz Passive: "closed": V UC EL V, ma I CEL ma "open": 6 V U CEH V, ma I CEH ma Terminals:, Fig. : Pulse output, active and passive, optocoupler PROFIBUS PA / FOUNDATION Fieldbus I E I E The resistance R and capacitor C form the bus termination. They must be installed when the device is connected to the end of the PA- FF- entire bus cable. 9 9 R = Ω; C = µf R R PA+ FF+ PROFIBUS PA C C FOUNDATION Fieldbus I = Internal G E = external Fig. 9 6

64 Electromagnetic Flowmeter FSM DS7U Bus termination for S transmitter To terminate the bus if the instrument is at the end of the bus cable, the termination components in the S transmitter can be used. To do so, close both hook switches in the connection area of the transmitter. Important If the transmitter plug-in module is removed, bus termination is also canceled. U+ S S U M M Connection board for field housing unit Hook switches for bus termination must be closed G9 Fig. Connection via M plug (for PROFIBUS PA only) As an option, the bus can also be connected via an M plug instead of the cable gland (see order information for device). The device can be shipped completely prewired. For information about suitable connectors (type EPG) and other accessories, refer to the data sheet /6.6. DE. Pin assignment (Front view showing pin insert and pins) PIN = PA+ PIN = nc PIN = PA- PIN = shield G Fig. 6

65 Electromagnetic Flowmeter FSM DS7U 6.6 Dimensions 6.6. Transmitter housing and mounting arrangements (.9) 9 (7.79) 9,7 (.) 67 (6.7) Ø7 (.7), (.7) 6 (.) 9 (9.) 66 (.9) (.9) (.9), (.) M x, min. 6 (.) min.7 (6.) G7 Fig. : (Dimensions in mm) Field mount housing with window Cable connector M x. Mounting holes for pipe mounting set for a pipe installation; mounting set upon request (order no. 6B9U7) Protection class IP 67 6

66 Electromagnetic Flowmeter FSM DS7U 6.7 Ordering information Accuracy.% of rate Main order number Add. order no. Version number XX FSM-S External Converter S- X X X X X X X X X X X XX Housing Field housing (cable gland M x.) A Field housing (cable gland / in. NPT) B Power Supply... V AC G V AC / V DC K Display Magnetic stick operation and display illuminated A Input / Output Options Current output active + Pulse output active + ) Contact input + Contact output Current output active + Pulse output active + Contact input + Contact output + HART Current output active + Pulse output passive + ) Contact input + Contact output Current output active + Pulse output passive + Contact input + Contact output + HART Contact output + PROFIBUS PA 7 Contact output + FOUNDATION Fieldbus Contact output + PROFIBUS PA with M plug Others 9 9 Application Extended diagnostics For Flowmeter Sensor SE_, SE_ ) DS_, DS_, DS, DI (>= DN ) [ in.]), D, D, D Certificates Standard Name Plate Language / Type German / Adhesive foil G English / Adhesive foil E French / Adhesive foil F German / Stainless steel J English / Stainless steel K French / Stainless steel L Design Level / Software Level (Specified by ABB) X X Language of Documentation German English Russian Language package Western Europe / Scandinavia (Languages DE, EN, DA, ES, FR, IT, NL, PT, FI, SV) Language package Eastern Europe (Languages DE, EL, CS, ET, LV, LT, HU, PL, SK, SL, RO, BG) Others Other Usage Certifications Russia, Metrological and GOST-R Certificate Kazakhstan, Metrological and GOST-K Certificate Ukraine, Metrological Certificate Belarus, Metrological Certificate M M MB ME MW MZ CG CG CG CG6 ) Not with low voltage power supply (code K) ) The external FRAM is in the terminal box of the associated flowmeter sensor on delivery ) In this variant, the external FRAM already is plugged into the converter with the values Cz = % and Cs = %. 66

67 Electromagnetic Flowmeter FSM DS7U 6. FXC flowmeter sensor simulator Main order number Version number FXC flowmeter sensor simulator XC X X X X X Flow signal setting None (adapter only) -digit switch in, increments Power supply Without (adapter only) With Schuko plug... V AC / 6 Hz With mm plug... V AC / DC With US plug... V AC / 6 Hz Additional equipment Without Adapter for converter type FXE-E, FXM-XM, FXF-DF Adapter plate for converter FSM-S Adapter plate for converter FET 6 Design level (specified by ABB) * Name plate German English French 6.9 Installation set for " pipe installation in field-mount housing Abb. : Part number: KXFL G79 67

FSM4000 Electromagnetic Flowmeter. Measurement made easy. The all-purpose flowmeter for conductive fluids

FSM4000 Electromagnetic Flowmeter. Measurement made easy. The all-purpose flowmeter for conductive fluids Conten ts Data Sheet D8S7U Rev. FSM Electromagnetic Flowmeter Measurement made easy The all-purpose flowmeter for conductive fluids Function Electromagnetic flowmeters can be used to accurately measure

More information

Electromagnetic Flowmeter FXE4000 (COPA-XE/MAG-XE)

Electromagnetic Flowmeter FXE4000 (COPA-XE/MAG-XE) Contents Data Sheet D184S75U2 Electromagnetic Flowmeter FXE4 (COP-XE/MG-XE) The Electromagnetic Flowmeter (EMF) can be used to accurately measure the flowrate of liquids which have an electrical conductivity

More information

ABB MEASUREMENT & ANALYTICS DATA SHEET. HygienicMaster FEH630 Electromagnetic flowmeter

ABB MEASUREMENT & ANALYTICS DATA SHEET. HygienicMaster FEH630 Electromagnetic flowmeter ABB MEASUREMENT & ANALYTICS DATA SHEET HygienicMaster FEH630 Electromagnetic flowmeter 2 HYGIENICMASTER FEH630 ELECTROMAGNETIC FLOWMETER DS/FEH630-EN REV. C Measurement made easy The clean choice for all

More information

Flow Measurement SITRANS F M

Flow Measurement SITRANS F M Overview Mode of operation The flow measuring principle is based on Faraday s law of electromagnetic induction according to which the sensor converts the flow into an electrical voltage proportional to

More information

JUMO flowtrans MAG S01

JUMO flowtrans MAG S01 Phone: +49 661 6003-0 Fax: +49 661 6003-607 Internet: www.jumo.net Fax: +44 1279 635262 sales@jumo.co.uk Fax: 315-437-5860 info.us@jumo.net Page 1/57 JUMO flowtrans MAG S01 Electromagnetic flowmeter for

More information

www. otech.com.sg EFS801 ELECTROMAGNETIC FLOWMETER

www. otech.com.sg EFS801 ELECTROMAGNETIC FLOWMETER www. otech.com.sg EFS801 ELECTROMAGNETIC FLOWMETER 1 www. otech.com.sg EFS801 - CFT181/RFT201 ELECTROMAGNETIC FLOWMETER Accurate, Reliable and Stable Flow Measurement. Measuring Principle The measuring

More information

Flow Measurement SITRANS F M

Flow Measurement SITRANS F M Overview Mode of operation The flow measuring principle is based on Faraday s law of electromagnetic induction according to which the sensor converts the flow into an electrical voltage proportional to

More information

OPTIFLUX 5000 Technical Datasheet

OPTIFLUX 5000 Technical Datasheet OPTIFLUX 5000 Technical Datasheet Electromagnetic flowmeter in flanged version Exceptional long-term stability and accuracy For highly aggressive and abrasive fluids Fully vacuum-resistant with high-tech

More information

OPTIFLUX 5000 Technical Datasheet

OPTIFLUX 5000 Technical Datasheet OPTIFLUX 5000 Technical Datasheet Electromagnetic flowmeter in flanged version Exceptional long-term stability and accuracy For highly aggressive and abrasive fluids Fully vacuum-resistant with high-tech

More information

Flow Measurement SITRANS F M. Flow sensor MAG /49. Overview

Flow Measurement SITRANS F M. Flow sensor MAG /49. Overview Siemens AG 2010 Flow Measurement Overview Mode of operation The flow measuring principle is based on Faraday s law of electromagnetic induction according to which the sensor converts the flow into an electrical

More information

SITRANS F flowmeters SITRANS F M. Flow sensor MAG /48 Siemens FI Overview

SITRANS F flowmeters SITRANS F M. Flow sensor MAG /48 Siemens FI Overview Siemens AG 2009 Overview Integration The complete flowmeter consists of a flow sensor and an associated transmitter MAG 5000, 6000 or 6000 I. The flexible communication concept USM II simplifies integration

More information

HygienicMaster FEH500 Electromagnetic Flowmeter. A first-class choice for all hygienic applications

HygienicMaster FEH500 Electromagnetic Flowmeter. A first-class choice for all hygienic applications Change from one to two columns Data Sheet HygienicMaster FEH500 Electromagnetic Flowmeter A first-class choice for all hygienic applications Intuitive operation Softkey-based functionality Easy Set-up

More information

ProcessMaster FEP500 Electromagnetic Flowmeter. The process industry's first choice. Maximum measuring accuracy Maximum measuring error: 0.

ProcessMaster FEP500 Electromagnetic Flowmeter. The process industry's first choice. Maximum measuring accuracy Maximum measuring error: 0. Change from one to two columns Data Sheet Rev. B ProcessMaster FEP500 Electromagnetic Flowmeter The process industry's first choice Intuitive operation Softkey-based functionality Easy Set-up function

More information

CoriolisMaster FCB330, FCB350, FCH330, FCH350 Coriolis mass flowmeter

CoriolisMaster FCB330, FCB350, FCH330, FCH350 Coriolis mass flowmeter Data Sheet DS/FCB300/FCH300-EN Rev. H CoriolisMaster FCB330, FCB350, FCH330, FCH350 Coriolis mass flowmeter 4-wire compact device For flow measurement of liquids and gases Measurement made easy CoriolisMaster

More information

ProcessMaster FEP300 Electromagnetic Flowmeter. The process industry's first choice

ProcessMaster FEP300 Electromagnetic Flowmeter. The process industry's first choice Change from one to two columns Data Sheet Rev. F ProcessMaster FEP300 Electromagnetic Flowmeter The process industry's first choice Intuitive operation Softkey-based functionality Easy Set-up function

More information

Mass Flowmeter CoriolisMaster FCM2000

Mass Flowmeter CoriolisMaster FCM2000 Contents Data Sheet Mass Flowmeter CoriolisMaster FCM2000 Coriolis Mass Flowmeters are used for high precision measurement of mass flow and density. The fluid need not be electrically conductive. No moving

More information

Mass Flowmeter CoriolisMaster FCM2000

Mass Flowmeter CoriolisMaster FCM2000 Contents Data Sheet Mass Flowmeter CoriolisMaster FCM2000 Coriolis Mass Flowmeters are used for high precision measurement of mass flow and density. The fluid need not be electrically conductive. No moving

More information

Flow Measurement SITRANS F M. Transmitter TRANSMAG 2 with sensor 911/E 4/101. Overview

Flow Measurement SITRANS F M. Transmitter TRANSMAG 2 with sensor 911/E 4/101. Overview Siemens AG 2010 Flow Measurement Overview Design The complete flowmeter consists of a flow sensor and an associated transmitter from the TRANSMAG 2 for pulsed alternating field. These are available as

More information

ProcessMaster FEP300 Electromagnetic flowmeter. The process industry's first choice

ProcessMaster FEP300 Electromagnetic flowmeter. The process industry's first choice Change from one to two columns Data Sheet Rev. I ProcessMaster FEP300 Electromagnetic flowmeter The process industry's first choice One solution for all your needs The versatile product tailored to meet

More information

JUMO flowtrans MAG H01

JUMO flowtrans MAG H01 sales@jumo.co.uk info.us@jumo.net Page 1/50 JUMO flowtrans MAG H01 Electromagnetic flowmeter for hygienic applications Brief description The electromagnetic flowmeter JUMO flowtrans MAG H01 was specially

More information

Electromagnetic Flow Transmitter

Electromagnetic Flow Transmitter Electromagnetic Flow Transmitter Sensor in solid state technology Working as a transmitter and/or as an On/Off controller Automatic-calibration of full scale: Teach-In Clean in place (CIP) Type can be

More information

FLOMID FX Electromagnetic Flowmeter

FLOMID FX Electromagnetic Flowmeter FLOMID FX Electromagnetic Flowmeter Working pressure manufacturing according to PED 97/23/CE (Lloyd s Register Certificate Nº 031) Introduction Modular design in two versions: Compact, sensor and electronics

More information

ABB FCB330 FCH350 Mass Flowmeter datasheet

ABB FCB330 FCH350 Mass Flowmeter datasheet ABB FCB330 FCH350 Mass Flowmeter datasheet http://www.manuallib.com/abb/fcb330-fch350-mass-flowmeter-datasheet.html State of the art transmitter Easy handling Data safety due to unique sensor memory concept

More information

Electromagnetic Flow Measuring System Two-wire, loop-powered PROline promag 23 H

Electromagnetic Flow Measuring System Two-wire, loop-powered PROline promag 23 H Technical Information TI 051D/06/en 50097004 Electromagnetic Flow Measuring System Two-wire, loop-powered PROline promag 23 H Flow measurement in hygiene, food and beverage or process applications Features

More information

ABB Measurement & Analytics. FSM4000 The electromagnetic flowmeter of choice For critical applications in a wide range of industries

ABB Measurement & Analytics. FSM4000 The electromagnetic flowmeter of choice For critical applications in a wide range of industries ABB Measurement & Analytics FSM4000 The electromagnetic flowmeter of choice For critical applications in a wide range of industries 2 FSM4000 The electromagnetic flowmeter of choice Electromagnetic flow

More information

TIDALFLUX 2300 F Technical Datasheet

TIDALFLUX 2300 F Technical Datasheet Technical Datasheet Electromagnetic flow sensor for partially filled pipes Measurement in partially filled pipes up to DN1600 / 64" Patented, non-contact level measurement Measurement possible down to

More information

SITRANS F flowmeters. SITRANS F System information MAGFLO electromagnetic flowmeters 4/9

SITRANS F flowmeters. SITRANS F System information MAGFLO electromagnetic flowmeters 4/9 Overview MAGFLO family MAGFLO electromagnetic are designed for measuring the flow of electrically conductive mediums. The patented MAGFLO Verificator guarantees accurate measurement and simple verification.

More information

INSERTION paddle wheel flowmeter for continuous flow measurement

INSERTION paddle wheel flowmeter for continuous flow measurement INSERTION paddle wheel flowmeter for continuous flow measurement Economic integration in pipe systems without any additional piping 3-wire frequency pulse version to directly interface with PLC s (both

More information

Magnetic-inductive flow meter. PITe / UMF2. Technical Datasheet. Maintenance-free Nearly no pressure drop Robust design Easy installation and start-up

Magnetic-inductive flow meter. PITe / UMF2. Technical Datasheet. Maintenance-free Nearly no pressure drop Robust design Easy installation and start-up Magnetic-inductive flow meter Technical Datasheet PITe / UMF2 Maintenance-free Nearly no pressure drop Robust design Easy installation and start-up Subject to change without notice 1 Function An electrically

More information

SITRANS F flowmeters. SITRANS F M System information MAGFLO electromagnetic flowmeters. 4/18 Siemens FI

SITRANS F flowmeters. SITRANS F M System information MAGFLO electromagnetic flowmeters. 4/18 Siemens FI Function All are based on Faraday s law of induction: U M = B v d k U M = Measured voltage induced in the medium perpendicular to the magnetic field and the flow direction. The voltage is tapped at two

More information

OPTIFLUX 1000 Technical Datasheet

OPTIFLUX 1000 Technical Datasheet OPTIFLUX 1000 Technical Datasheet Electromagnetic flow sensor in sandwich design Lightweight and compact Excellent price performance ratio Quick and easy to install The documentation is only complete when

More information

Ambient Conditions. Operating Conditions. Pressure

Ambient Conditions. Operating Conditions. Pressure Temperature Relative Humidity -20 C +75 C 0% 100 RH to 65 C non condensing 86 106 bar 4.0MPa (DN10 DN80) 1.6MPa (DN100 DN150) 1.0MPa (DN200 DN1000) Remote version < 80 C (rubber coating) Compact version

More information

CoriolisMaster FCB330, FCB350 Coriolis Mass Flowmeter. 4-wire compact device For flow measurement of liquids and gases

CoriolisMaster FCB330, FCB350 Coriolis Mass Flowmeter. 4-wire compact device For flow measurement of liquids and gases Data Sheet DS/FCB300-EN Rev. C CoriolisMaster FCB330, FCB350 Coriolis Mass Flowmeter 4-wire compact device For flow measurement of liquids and gases CoriolisMaster simply fits! The ideal NAMUR Standard

More information

Magnetic-Inductive flow Meter fmi

Magnetic-Inductive flow Meter fmi 1 Product information fmi-c, fmi-r f o o d P H A R M A Magnetic-Inductive flow Meter fmi Application/Specified usage Magnetic-inductive flowmeter for the measurement of flow rate and volume in food and

More information

4/11. Overview. Easier service Transmitter replacement requires no programming. SENSORPROM automatically updates all settings after initialization.

4/11. Overview. Easier service Transmitter replacement requires no programming. SENSORPROM automatically updates all settings after initialization. Overview family are designed for measuring the flow of electrically conductive mediums. Benefits Easier commissioning of 5000, 6000, 6000 I All pulsed DC feature a unique SENSORPROM memory unit which stores

More information

SITRANS F flowmeters SITRANS F US SONOCAL /184 Siemens FI

SITRANS F flowmeters SITRANS F US SONOCAL /184 Siemens FI Overview Integration The flowmeter pulse output is often used as input for heat calculators. The range of meters enables optimum measurement of energy consumption. The analog output is used to inform the

More information

INLINE flowmeter for continuous flow measurement

INLINE flowmeter for continuous flow measurement INLINE flowmeter for continuous flow measurement Economic integration in pipe systems without any additional piping 3-wire frequency pulse version to directly interface with PLC s (both PNP and NPN) Connection

More information

SITRANS F flowmeters SITRANS F M. Transmitter Transmag 2 with sensor 911/E 4/77. Overview

SITRANS F flowmeters SITRANS F M. Transmitter Transmag 2 with sensor 911/E 4/77. Overview Overview Design The complete flowmeter consists of a flow sensor and an associated transmitter from the Transmag 2 for pulsed alternating field. These are available as remote and compact versions ( 911/E

More information

INLINE flowmeter for continuous flow measurement

INLINE flowmeter for continuous flow measurement INLINE flowmeter for continuous flow measurement Economic integration in pipe systems without any additional piping 3-wire frequency pulse version to directly interface with PLC s (both PNP and NPN) Connection

More information

Technical Information Proline Promag 10P

Technical Information Proline Promag 10P TI00094D/06/EN/13.17 71385977 Products Solutions Services Technical Information Electromagnetic flowmeter Flow measurement of liquids in chemical or process applications Application Electromagnetic flowmeter

More information

Electro-Magnetic Flowmeters COPA-XE

Electro-Magnetic Flowmeters COPA-XE Data Sheet Electro-Magnetic Flowmeters COPA-XE 10DX4311 Flowmeter system utilizes a smart microprocessor converter System accuracy of ± 0.5% of rate Field configurable via integral pushbuttons, eliminates

More information

ABB MEASUREMENT & ANALYTICS DATA SHEET. CoriolisMaster FCB400, FCH400 Coriolis mass flowmeter

ABB MEASUREMENT & ANALYTICS DATA SHEET. CoriolisMaster FCB400, FCH400 Coriolis mass flowmeter ABB MEASUREMENT & ANALYTICS DATA SHEET CoriolisMaster FCB400, FCH400 Coriolis mass flowmeter 2 CORIOLISMASTER FCB400, FCH400 CORIOLIS MASS FLOWMETER DS/FCB400/FCH400-EN REV. F Measurement made easy High-precision

More information

Electromagnetic Flowmeter FSM4000

Electromagnetic Flowmeter FSM4000 Operating Instruction D184B14U2 Electromagnetic Flowmeter FSM4 Valid for software versions C.1 and higher Model FSM4-SE41F FSM4-SE21 FSM4-SE21F FSM4-S4 Contents Blinder Text Electromagnetic Flowmeter FSM4

More information

SITRANS F flowmeters. SITRANS F M System information MAGFLO electromagnetic flowmeters 4/11

SITRANS F flowmeters. SITRANS F M System information MAGFLO electromagnetic flowmeters 4/11 Overview family are designed for measuring the flow of electrically conductive mediums. Benefits System information FLO Easier to commission for 5000, 6000, 6000 I All FLO pulsed DC feature a unique SENSORPROM

More information

INLINE flowmeter for continuous flow measurement

INLINE flowmeter for continuous flow measurement INLINE flowmeter for continuous flow measurement Economic integration in pipe systems without any additional piping 3-wire frequency pulse version to directly interface with PLC s (both PNP and NPN) Connection

More information

SITRANS F flowmeters. SITRANS F M System information MAGFLO electromagnetic flowmeters 4/11

SITRANS F flowmeters. SITRANS F M System information MAGFLO electromagnetic flowmeters 4/11 Overview family are designed for measuring the flow of electrically conductive mediums. Benefits SITRANS F flowmeters System information FLO Easier to commission All FLO feature a unique SENSORPROM memory

More information

Technical Information Smartec CLD18

Technical Information Smartec CLD18 TI01080C/07/EN/02.14 71264779 Products Solutions Services Technical Information Smartec CLD18 Compact inductive conductivity measurement for the food and beverage industry Application Compact measuring

More information

Digital inductive conductivity transmitter

Digital inductive conductivity transmitter Digital inductive conductivity transmitter Optimal solution for conductivity measurements in difficult fluids (polluted, dirty,...) PEEK/PPA version for CIP applications Large range of process connections

More information

Electromagnetic flowmeters and switches DWM 1000/2000

Electromagnetic flowmeters and switches DWM 1000/2000 KROHNE 10/2000 D 20 DW10 02 E GR Electromagnetic flowmeters and switches DWM 1000/2000 Variable area flowmeters Vortex flowmeters Flow controllers Electromagnetic flowmeters Ultrasonic flowmeters Mass

More information

Electromagnetic Flowmeter FSM4000

Electromagnetic Flowmeter FSM4000 Operating Instruction D184B14U2 Electromagnetic Flowmeter FSM4 Valid for software versions C.1 and higher Model FSM4-SE41F FSM4-SE21 FSM4-SE21F FSM4-S4 Contents Blinder Text Electromagnetic Flowmeter FSM4

More information

OPTIMASS 1000 Technical Datasheet

OPTIMASS 1000 Technical Datasheet OPTIMASS 1000 Technical Datasheet Sensor for mass flow First choice for universal applications Best price-performance ratio A wide range of options available with no restrictions The documentation is only

More information

Electromagnetic Flow Measuring System Two-wire, loop-powered PROline promag 23 P

Electromagnetic Flow Measuring System Two-wire, loop-powered PROline promag 23 P Technical Information TI 049D/06/en 50097005 Electromagnetic Flow Measuring System Two-wire, loop-powered PROline promag 23 P Flow rate measurement in chemical or process applications Features and benefits

More information

Digital flow ELEMENT transmitter for continuous flow measurement

Digital flow ELEMENT transmitter for continuous flow measurement ELEMENT Transmitter Digital flow ELEMENT transmitter for continuous flow measurement Type can be combined with... PN10, DN15 to DN400 fluidic process connection Programmable outputs : one or two transistor

More information

Technical Information Smartec CLD18

Technical Information Smartec CLD18 TI01080C/07/EN/01.12 71195835 Products Solutions Services Technical Information Smartec CLD18 Compact inductive conductivity measurement for the food and beverage industry Application The compact measuring

More information

BATCHFLUX and BATCHCONTROL

BATCHFLUX and BATCHCONTROL KROHNE 04/2001 D 31 BATC 02 E GR/PRINTO BATCHFLUX and volumetric batching and dosing with electromagnetic flowmeters A new era in volumetric batching!!! Optimum sanitary design Ceramic measuring tube Only

More information

BATCHFLUX 5500 C Technical Datasheet

BATCHFLUX 5500 C Technical Datasheet BATCHFLUX 5500 C Technical Datasheet Electromagnetic flowmeter for volumetric filling machines High-stability ceramic measuring tube, therefore extremely long-term stability Optimum hygienic design Only

More information

KMS305W. ManuFlo Page 1 MANU ELECTRONICS PTY LTD Flow Measurement Products. Electromagnetic Wafer Flowmeters with S300 display

KMS305W. ManuFlo Page 1 MANU ELECTRONICS PTY LTD Flow Measurement Products. Electromagnetic Wafer Flowmeters with S300 display Electromagnetic Wafer Flowmeters with S300 display for corrosive chemicals/acids & slurries (sizes: 2.5mm to 100mm) 0BFEATURES: For aggressive chemicals, slurries, oxides, grouts & dosing applications

More information

FLOWave SAW-Flowmeter

FLOWave SAW-Flowmeter SAW-Flowmeter No parts in the measurement tube 28-04 Conform to hygienic requirements Ideal for low conductivity or non conductive liquids Digital communication Type 8098 can be combined with... Compact,

More information

WATERFLUX 3070 Technical Datasheet

WATERFLUX 3070 Technical Datasheet WATERFLUX 3070 Technical Datasheet Engineered and manufactured for the water and wastewater industry Highly accurate measurement with extremely short in- and outlet lengths Battery operated, stand alone

More information

Type F-20-3A Sanitary Pressure Transmitter NEMA 4X with Integral Junction Box

Type F-20-3A Sanitary Pressure Transmitter NEMA 4X with Integral Junction Box Type F-20-3A Sanitary Pressure Transmitter NEMA 4X with Integral Junction Box Applications Food and beverage industry Pharmaceutical industry Biotechnology industry Cosmetic industry Special Features Meets

More information

Technical Information Smartec CLD18

Technical Information Smartec CLD18 TI01080C/07/EN/03.16 71314717 Products Solutions Services Technical Information Smartec CLD18 Compact inductive conductivity measurement for the food and beverage industry Application Compact measuring

More information

KFS. Flap-type flow meter. Design and range of application

KFS. Flap-type flow meter. Design and range of application Design and range of application The measuring device operates largely independent of viscosity and is suitable for indicating the flow rate of water, acids, alkaline solutions and gases. Every device is

More information

Digital flow ELEMENT transmitter for continuous flow measurement

Digital flow ELEMENT transmitter for continuous flow measurement Digital flow ELEMENT transmitter for continuous flow measurement Type 8036 can be combined with... DN06 to DN65 fluidic process connection Programmable outputs : one or two transistor output(s) and single

More information

ProcessMaster FEP610, HygienicMaster FEH610 Electromagnetic flowmeter

ProcessMaster FEP610, HygienicMaster FEH610 Electromagnetic flowmeter Operating Instruction OI/FEP610/FEH610-EN Rev. A ProcessMaster FEP610, HygienicMaster FEH610 Electromagnetic flowmeter Measurement made easy Short product description Electromagnetic flowmeter can measure

More information

Rosemount Specifications. Product Data Sheet , Rev BA February 2009 PERFORMANCE SPECIFICATIONS

Rosemount Specifications. Product Data Sheet , Rev BA February 2009 PERFORMANCE SPECIFICATIONS Rosemount 2051 Product Data Sheet PERFORMANCE SPECIFICATIONS Specifications For zero based spans, reference conditions, silicone oil fill, SST materials, Coplanar flange () or 1 /2 in. - 14 NPT () process

More information

Magnetic Flowmeter Systems

Magnetic Flowmeter Systems Series 8700 Magnetic Flowmeter Systems THE 8700 SERIES... Model 8712 C/U - Easiest to use local operator interface and works with any manufacturer s flowtubes Model 8712H/8707 High-Signal System - Pulsed

More information

Condumax W CLS19. Technical Information. Conductivity sensors Two-electrode sensors with cell constants k = 0.01 cm 1 or k = 0.

Condumax W CLS19. Technical Information. Conductivity sensors Two-electrode sensors with cell constants k = 0.01 cm 1 or k = 0. Technical Information Condumax W CLS9 Conductivity sensors Two-electrode sensors with cell constants k = 0.0 cm or k = 0. cm Application Measurement in pure and ultrapure water: Monitoring ion exchangers

More information

Digital flowmeter for continuous flow measurement

Digital flowmeter for continuous flow measurement 8025 Flowmeter INSERTION Digital flowmeter for continuous flow measurement Compact or remote version for DN06 to DN400, PN10 Displays both flow rate and volume (with two totalizers) On site calibration

More information

Abridged Specifications: 10DS3111E/A Sensor with 50SM1000 Transmitter

Abridged Specifications: 10DS3111E/A Sensor with 50SM1000 Transmitter Abridged Specifications: E/A Sensor with 50SM1000 Transmitter The E/A flanged sensors and 50SM1000 transmitters are AC magnetic flowmeters. These systems are recommended noisy slurries, applications involving

More information

Proline Promag 10P. Technical Information. Electromagnetic Flow Measuring System Flow measurement of liquids in chemical or process applications

Proline Promag 10P. Technical Information. Electromagnetic Flow Measuring System Flow measurement of liquids in chemical or process applications Technical Information Proline Promag 10P Electromagnetic Flow Measuring System Flow measurement of liquids in chemical or process applications Application Electromagnetic flowmeter for bidirectional measurement

More information

Pressure transmitter For sanitary applications Model SA-11

Pressure transmitter For sanitary applications Model SA-11 Electronic pressure measurement Pressure transmitter For sanitary applications Model SA-11 WIKA data sheet PE 81.80 for further approvals see page 8 Applications For gases, compressed air, vapour, liquids,

More information

The transducer component converts the measured signal and displays the actual value.

The transducer component converts the measured signal and displays the actual value. Digital inductive conductivity transmitter System Integration Provides low Total Cost of Ownership PEEK/PPA version for CIP applications TEACH IN and SIMULATION Function Approval PVDF Version PEEK Version

More information

RADAR TRANSMITTERS BLISSFLEX 1100 SELECTION GUIDE. The characters of the order code have been described below

RADAR TRANSMITTERS BLISSFLEX 1100 SELECTION GUIDE. The characters of the order code have been described below BLISSFLEX 1100 The characters of the order code have been described below BA25 4 BLISSFLEX 1100 C 2-wire loop-powered 4...20 ma Guided Radar (TDR) level meter: -50...+100 C and -1...16 barg / -58...212

More information

Electromagnetic Flow Measuring System promag 33

Electromagnetic Flow Measuring System promag 33 Technical Information TI 07D/06/en No. 50063743 Electromagnetic Flow Measuring System promag 33 Flexible System Wide choice of materials for process connections and measuring tube linings, compatible to

More information

Digital conductivity transmitter

Digital conductivity transmitter Digital conductivity transmitter Compact version with integrated conductivity electrodes Remote version with seperated transmitter for short (15 ft.) or long (1500 ft.) distance Commissioning is easy due

More information

Proline Promag 55S. Technical Information

Proline Promag 55S. Technical Information Technical Information Proline Promag 55S Electromagnetic Flow Measuring System Flow rate measurement of liquids with solids content or inhomogeneous liquids Application Electromagnetic flowmeter for bidirectional

More information

Digital flowmeter for continuous flow measurement

Digital flowmeter for continuous flow measurement 8025 Flowmeter INSERTION Digital flowmeter for continuous flow measurement Compact or remote version for DN06 to DN400, PN10 Displays both flow rate and volume (with two totalizers) On site calibration

More information

Flow Switch - 2 programmable thresholds. Stand Alone (Battery) - Battery powered, - 2 totalizers display, - Local flow display,

Flow Switch - 2 programmable thresholds. Stand Alone (Battery) - Battery powered, - 2 totalizers display, - Local flow display, DN 15 - DN 50; PN Advantages / Benefits Easy System integration by Easy LINK provides low cost of ownership Easy commissioning due to multi-language, menu-guided operation TEACH-IN: automatic calibration

More information

Rosemount 8700 Series. Magnetic Flowmeter Systems. Rosemount 8700 Series. Product Data Sheet , Rev NB Catalog

Rosemount 8700 Series. Magnetic Flowmeter Systems. Rosemount 8700 Series. Product Data Sheet , Rev NB Catalog Magnetic Flowmeter Systems THE 8700 SERIES... Rosemount 8712 HART Transmitter - available with Device Diagnostics to improve reliability and performance. Provides quick setup with easy-to-use local operator

More information

Coriolis Massflowmeter

Coriolis Massflowmeter Coriolis Massflowmeter for liquids and gas measuring monitoring analysing Measuring range: 0-0.8 kg / h 0-65 000 kg / h water Accuracy: ± 0.1 of reading ±zero-point stability (liquids) pmax: PN40 tmax:

More information

Technical Information Memosens CLS82D

Technical Information Memosens CLS82D TI01188C/07/EN/03.16 71318348 Products Solutions Services Technical Information Memosens CLS82D Hygienic conductivity sensors, digital with Memosens technology, cell constant k = 0.57 cm -1 Application

More information

In-Line Resistance Thermometers Model TR25

In-Line Resistance Thermometers Model TR25 Electrical Temperature Measurement In-Line Resistance Thermometers Model TR25 WIKA Data Sheet TE 60.25 Applications Food and beverage industry, dairies, drink dispensers and bottling plants, breweries

More information

SM-10. Features. Variable Area Flowmeter with Sight Glass for Small Flow Volumes. Description: Application: / Indication without power supply

SM-10. Features. Variable Area Flowmeter with Sight Glass for Small Flow Volumes. Description: Application: / Indication without power supply SM-10 Variable Area Flowmeter with Sight Glass for Small Flow Volumes Description: Features / Indication without power supply The SM-10 series of flowmeters operates according to the proven variable area

More information

Electromagnetic Flow Measuring System promag 35

Electromagnetic Flow Measuring System promag 35 Technical Information TI 035D/06/en No. 50075884 Electromagnetic Flow Measuring System promag 35 Applications Promag 35 S solves complex flow problems and is used to measure fluids with a high solids content,

More information

Design and applications

Design and applications Design and applications The measuring device operates largely independent of viscosity and is suitable for indicating the flow rate of water, acids, alkaline solutions and gases. Every device is calibrated

More information

Advanced instrumentation solutions crafted with highest precision

Advanced instrumentation solutions crafted with highest precision www.adeptfluidyne.com Advanced instrumentation solutions crafted with highest precision perpendicular to both the liquid flow direction and the electromagnetic field direction. The voltage sensed by the

More information

Resistance thermometers for process technology

Resistance thermometers for process technology Data Sheet 90.2820 Page 1/8 Resistance thermometers for process technology for temperatures from -200 to +600 C with protection tubes in stainless steel, titanium, tantalum, Iconel and Hastelloy available

More information

FXF2000 (COPA-XF) Electromagnetic Flowmeter. All in one -Flowmeter. With pulsed DC field excitation in a compact design

FXF2000 (COPA-XF) Electromagnetic Flowmeter. All in one -Flowmeter. With pulsed DC field excitation in a compact design Data Sheet DS07U0 Rev. 0 FXF000 (COPA-XF) Electromagnetic Flowmeter All in one -Flowmeter With pulsed DC field excitation in a compact design Function Electromagnetic flowmeter can be used to accurately

More information

Digital flow transmitter for continuous flow measurement

Digital flow transmitter for continuous flow measurement Digital flow transmitter for continuous flow measurement Compact or remote version for DN 06 to 400, PN10 Shows both flow rate and volume (with two totalizers) Automatic-calibration: TEACH-IN Simulation:

More information

UFM 800 W, C Ultrasonic flowmeter for water and wastewater

UFM 800 W, C Ultrasonic flowmeter for water and wastewater KROHNE 08/2000 7.02343.21.00 GR/PRINTO, C Ultrasonic flowmeter for water and wastewater...with weld-in sensors for metal pipelines...withbuilt-on or built-in sensors for open channels Variable area flowmeters

More information

IFC 010 Signal Converter

IFC 010 Signal Converter KROHNE 04/2003 7.02347.22.00 GR Signal Converter for electromagnetic flowmeters Easy to install Low-cost signal converter, measuring error < 0.5% of the measured value Easy user-friendly operation Self-monitoring

More information

Condumax CLS15 and CLS15D

Condumax CLS15 and CLS15D Technical Information Condumax CLS15 and CLS15D Conductivity sensors, analog or digital with Memosens technology, Cell constant k = 0.01 cm -1 or k = 0.1 cm -1 Application Measurement in pure and ultrapure

More information

Condumax W CLS15 and CLS15D

Condumax W CLS15 and CLS15D Technical Information Condumax W CLS15 and CLS15D Conductivity sensors, analog or digital with Memosens technology, Cell constant k = 0.01 cm -1 or k = 0.1 cm -1 Application Measurement in pure and ultrapure

More information

Indumax CLS50/CLS50D. Technical Information

Indumax CLS50/CLS50D. Technical Information Technical Information Indumax CLS50/CLS50D Inductive conductivity sensor for standard, hazardous and high-temperature applications, analog or digital with Memosens protocol Application Indumax CLS50/CLS50D

More information

Magnetic Inductive Flowmeter

Magnetic Inductive Flowmeter Magnetic Inductive Flowmeter for conductivity liquids measuring monitoring analysing Measuring range: up to 10 m/s Accuracy: ±1.5% of reading ±0.5% full scale pmax: PN40 tmax: -40 +150 C Connection: flange

More information

OPTIFLUX 2000 Technical Datasheet

OPTIFLUX 2000 Technical Datasheet OPTIFLUX 2000 Technical Datasheet Electromagnetic flow sensor For all water and wastewater applications Wide range of approvals for potable water Robust, fully welded construction The documentation is

More information

J Series induq VMZ MAGNETIC INDUCTIVE FLOW SENSORS. DB_Magnetic_Inductive_Flow_Sensors 05/2016

J Series induq VMZ MAGNETIC INDUCTIVE FLOW SENSORS. DB_Magnetic_Inductive_Flow_Sensors 05/2016 J Series induq VMM J Series induq VMI J Series induq VMZ MAGNETIC INDUCTIVE FLOW SENSORS J DB_Magnetic_Inductive_Flow_Sensors 5/216 67 Magnetic inductive flow sensors Principle of operation The smart flow

More information

KMS502F. ManuFlo Page 1 MANU ELECTRONICS PTY LTD Flow Measurement Products. Electromagnetic Flanged Flowmeters FEATURES: (sizes: 25mm to 200mm)

KMS502F. ManuFlo Page 1 MANU ELECTRONICS PTY LTD Flow Measurement Products. Electromagnetic Flanged Flowmeters FEATURES: (sizes: 25mm to 200mm) KMS502F Electromagnetic Flanged Flowmeters (sizes: 25mm to 200mm) FEATURES: For all your water applications including batching. Flanged connection suites ANSI 150lb flanges. Unsurpassed accuracy to ±0.5%

More information

Type PLC Fitting. Valve for Continuous control. Diaphragm valve. Output

Type PLC Fitting. Valve for Continuous control. Diaphragm valve. Output Digital Inductive conductivity transmitter Optimal solution for conductivity measurements in difficult fluids (polluted, dirty,...) PEEK/PPA version for CIP applications Large range of process connections

More information

Condumax W CLS19. Technical Information. Conductivity sensors Two-electrode sensors with cell constants k = 0.01 cm 1 or k = 0.

Condumax W CLS19. Technical Information. Conductivity sensors Two-electrode sensors with cell constants k = 0.01 cm 1 or k = 0. Technical Information Condumax W CLS9 Conductivity sensors Two-electrode sensors with cell constants k = 0.0 cm or k = 0. cm Application Measurement in pure and ultrapure water: Monitoring ion exchangers

More information