Mass Flowmeter CoriolisMaster FCM2000

Save this PDF as:
 WORD  PNG  TXT  JPG

Size: px
Start display at page:

Download "Mass Flowmeter CoriolisMaster FCM2000"

Transcription

1 Contents Data Sheet Mass Flowmeter CoriolisMaster FCM2000 Coriolis Mass Flowmeters are used for high precision measurement of mass flow and density. The fluid need not be electrically conductive. No moving parts, no wear, no maintenance Ex design acc. to ATEX / FM [USA] Transmitter with DSP technology - The latest digital filter technology assures detection of even the weakest sensor signals Operate using a magnet stick without opening the housing Simultaneous measurement of mass flow, volume flow, density, temperature and concentration Type-tested acc. to NAMUR Options: - Expanded density calibration with temperature compensation - Pressure-resistant housing - EHEDG-certified - Concentration measurement P R O F I PROCESS FIELD BUS B U S 4-wire Compact Design Digital Signal Processor Transmitter Technology

2 Contents Overview of flowmeter and transmitter designs...3. ATEX and IECEx device overview FM device overview (PID: 30526) General information Installation Requirements Model FCM2000-MC Specifications Dimensions Ordering information Model FCM2000-MS Specifications Dimensions Ordering information Transmitter Specifications Concentration measurement DensiMass Inputs/outputs Digital Communication Electrical connections Dimensions Ordering information Ex relevant specifications Questionnaire

3 Overview of flowmeter and transmitter designs MC2 MS2 G0036 Standard Hygienic (EHEDG) Standard Flowmeter sensor Model number MC2 MC2 _ 3 MS2 DN PN DN PN DN PN Flange DIN 250/EN /5 40/00 Flange ASME B6.5 /2... 6" CL CL 600 /2" CL CL 600 Threaded pipe connection DN 5... DN 00 (/2... 4") DN DN 80 (3/4... 3") DN 0 (3/8") conforming to DIN 85 Tri-Clamp DIN (ISO 2852) DN 5... DN 00 (/2... 4") DIN (ISO 2852) DN DN 80 (3/4... 3") DIN (ISO 2852) DN 0 (3/8") Aseptic flange DIN DN 5... DN 00 (/2... 4") DN DN 80 (3/4... 3") "G" threaded pipe connection /4" NPT threaded pipe connection /4" Accuracy of mass flowrate 0. %/0.5 %/0.25 %/0.4" 0. %/0.5 %/0.25 %/0.4" 0.5 %/0.25 %/0.4" Accuracy of density kg/l, 0.00 kg/l kg/l, 0.00 kg/l 0.0 kg/l Accuracy of temperature K K K Materials in contact with fluid Stainless steel Hastelloy C-4 Stainless steel.4435 (36L) Stainless steel.4435 (36L), Hastelloy C-22 Protection class acc. to EN IP 67 IP 67 IP Fluid temperature (see Section 3/4 of the data sheet, Section 0 of the operating instructions) C ( F) C ( F) C ( F) Approvals Explosion protection conforming to ATEX, IEC (KEM 08 ATEX 050X/05X), (IECEx KEM X) FM explosion protection (PID: 30526) Other approvals for potentially explosive areas Hygienic and sterile requirements Transmitter Zone 0//2 Dust-ignition-proof Zone 0//2 Dust-ignition-proof G0044 Zone (ATEX only) Class I Div. Class I Div. 2 Class I Div. Class I Div. 2 Please contact our sales Please contact our sales Please contact our sales organization organization organization FDA FDA, EHEDG FDA Model number ME2_/MC23, MC27 ME2_ Housing Separate, field-mount housing/compact housing Separate, field-mount housing Cable length Up to 50 m (64 ft.); 300 m (984 ft.) on request 5, 0, 20, or 50 m (6, 32, 65, or 64 ft.) Supply power V AC, 24 V AC/DC Current output Active: 0/ ma or passive: ma Current output 2 Passive: ma Pulse output Active (non-ignition-proof) or passive Ext. output switch-off Yes Ext. totalizer reset Yes Forward/reverse flow metering Yes Communication HART protocol, PROFIBUS PA, FOUNDATION Fieldbus Pipe empty detection Yes, based on preconfigured density alarm < 0.5 kg/l Self-monitoring, diagnostics Yes On-site display/totalization Yes Field optimized flow/density Yes Protection class acc. to EN ME2: IP 65/67, NEMA 4X MC : IP 67, NEMA 4X G0035 3

4 . ATEX and IECEx device overview Standard/Non-Ex Zone 2/2, 22 Zone /2 Type MC23 A, U MC23 M, N MC27 B, E. Compact design Standard/non-Ex Ex Zone 2/2, 22 Ex Zone /2 Type ME2 A, U MC2 A, U ME26 B, E MC26 B, E 2. Separate design Transmitter and flowmeter sensor Standard/non-Ex Ex Zone /2 Type ME2 A, U MC2 M, N MC26 B, E 3. Separate design Transmitter Standard/non-Ex Flowmeter sensor Ex Zone /2 Ex Zone 2/2, 22 Type ME22 A, U... MS2 A, U ME27/28 B, E MS26 B, E 4. Separate design (small nominal sizes) Transmitter and flowmeter sensor Standard/non-Ex Ex Zone 2/2, 22 Ex Zone /2 Type ME24/25 A, U... MS26 B, E 5. Separate design (small nominal sizes) Transmitter Standard/non-Ex Ex Zone 2/2, 22 Flowmeter sensor Ex Zone /2 G00387 Fig. : FCM2000 overview 4

5 .2 FM device overview (PID: 30526) FM installation Class I, Div. /Div. 2 Class I, Div. Area, Zone Class I, Div. 2 Area, Zone 2 General purpose / Safe Area MC27C MC23O MC23T ME2T MC2T ME2O ME2T MC2O G00332 Fig. 2 5

6 2 General information Change from one to two columns The FCM2000 is ABB's economical and uncomplicated mass flowmeter, featuring the new DSP transmitter, either integrated in the flowmeter or mounted separately from it. The compact unit reduces installation and cabling expenditure. Flowrate information can be viewed directly at the meter site and the meter can be installed in systems in an even more space-saving manner than is currently possible. The FCM2000 operates according to the Coriolis principle. The design offers the following benefits: Space-saving, rugged design. Wide flow measuring range; meter size "S" (DN.5 [/6"]) to meter size "L" (DN 50 [6"]). Variety of process connection options. Two separate current outputs for measuring mass or volume flowrate, density, or temperature, as well as one pulse output. Contact inputs and outputs. HART protocol, PROFIBUS PA, FOUNDATION Fieldbus. Ex approval: The user can select the "i" or "e" type of protection for the output circuits; the type chosen will depend on the circuits which are connected. The type of protection can be changed after installation has been completed. The contact outputs can be configured as NAMUR outputs by the user. Permissible fluid temperature up to 200 C (392 F), CIP-enabled Illuminated, 2-line display with data entered using a magnet stick and without opening the housing. Certified acc. to EHEDG. Mass transmitter with digital signal processor (DSP) The transmitter for the FCM2000 incorporates a digital signal processor (DSP) that enables high-precision mass flow and density measurements to be made. The Coriolis sensor signals are immediately converted into digital data without any intermediate analog steps. Excellent long-term stability and reliability together with fast signal processing are achieved with the new DSP transmitter. Self-diagnostic functions for the flowmeter sensor and the transmitter, in combination with absolute zero stability, are benefits you can count on to ensure accurate measurements are taken. The FCM2000 transmitter is particularly well suited for use in the following cases: When mass flowrate is to be metered to the highest degree of accuracy. When the fluid density is to be determined. When the components of a recipe are to be mixed together. When metering non-conductive fluids or highly viscous, solidloaded liquids, for example. In batch filling systems. 2. Installation Requirements 2.. General information Change from one to two columns Inspection Before installing the flowmeter sensor, check for physical damage due to possible improper handling during shipment. All claims for damage are to be made promptly to the shipper. Installation Requirements / System Sizing Information The FCM2000 is suitable for both indoor and outdoor installations. The standard instrument meets the requirements of Protection Class IP 67. The primary is bidirectional and can be installed in any orientation. It is important to ensure that the meter pipes are always completely filled with fluid. The corrosion resistance of the fluid wetted materials must be evaluated. The following points are to be considered during installation: The preferred flow direction is indicated by the arrow on the flowmeter sensor. Flow in this direction will be indicated as positive (a forward/reverse flow calibration is available as on option). Installation position The FCM2000 operates in any orientation. The optimal installation orientation is vertical with the flow upwards. Supports In order to support the weight of the flowmeter sensor and to ensure reliable measurements when adverse external effects exist (e. g., vibrations), the primary should be installed in rigid pipelines. Two supports or hangers should be installed symmetrically and stress free in close proximity to the in- and outlet process connections. Shut Off Devices To conduct a system zero adjustment, shut off devices are required in the pipeline: - in horizontal installation at the outlet, - in vertical installation at the inlet. When possible, shut off devices should be installed both up- and downstream from the flowmeter sensor. Inlet Straight Sections The mass meter does not require any flow conditioning inlet straight sections. Care should be exercised to ensure that any valves, gates, sight glasses, etc., do not cavitate and are not set into vibration by the flowmeter sensor. 6

7 System Design Information The presence of gas bubbles in the fluid can result in erroneous measurements, particularly in the density measurement. Therefore the flowmeter sensor should not be installed at the highest point in the system. Advantageous are installations in low pipeline sections, e. g., at the bottom of a U-section in the pipeline (invert). Long drop lines downstream from the flowmeter sensor should be avoided to prevent the meter tube from draining. Installation should be performed as stress free as possible. The flowmeter sensor should not come in contact with any other objects. Attachments to the housing are not permissible. When the cross-section of the connecting pipeline is larger than the flowmeter sensor size, suitable standard reducers should be installed. If strong vibrations exist in the pipeline, they should be damped using elastic pipeline elements. The damping devices must be installed beyond the supported flowmeter section and outside of the section between the shut off devices. The direct connection of flexible elements to the flowmeter sensor should be avoided. Care should be exercised to ensure that any dissolved gases, which may be present in many liquids, do not outgas. The back pressure at the outlet should be at least 0.2 bar (2,9 psi). Ensure that operation below the vapor pressure cannot occur when a vacuum exists in the meter tube. The flowmeter sensor should not be installed in the vicinity of strong electromagnetic fields, e. g., near motors, pumps, transformers etc. When operating more than one meter in one or multiple interconnected pipelines, the flowmeter primaries should be spaced distant from each other or the pipelines should be decoupled to prevent cross talk. Request information about special installation conditions for meter size "L". Zero balance In order to adjust the zero under operating conditions, it must be possible to reduce the flowrate "ZERO" while the meter tube remains completely filled. A bypass line is optimal when the process cannot be shut down. It is important for accurate measurements that during the zero adjustment there are no gas bubbles in the flowmeter sensor. It is also important that the pressure and temperature in the meter tube be the same as those which exists during operation. B A G003 Fig. 3: Vibrations G0036 Fig. 4: Zero point adjustment with bypass line 7

8 2..2 Installation notes for FCM2000-MC2 Horizontal Installations, Self Draining Vertical installation position The optimal installation orientation is a vertical installation with an upward flow as shown in Fig. 5. This has the advantage that any solids contained in the fluid will settle downward and any gas bubbles will move upward out of the meter tube when the flowrate is zero. Additionally, it is easy to drain the meter tube. Deposits can thereby be avoided. G00304 Fig. 7: Horizontal Installations, Self Draining, α 2-4 Installation in a Drop Line The installation recommendation shown in Fig. 8 is only permissible if a pipeline reduction or orifice with a smaller cross-section can be installed to prevent the flowmeter sensor from partially draining during the measurements. Fig. 5: G00302 Vertical installation position, self-draining (flow upwards) Horizontal Installation Orientations Fig. 6: Horizontal Installation Orientations G G00305 Fig. 8: Installation in a Drop Line Supply reservoir 2 Flowmeter sensor 3 Orifice/pipe constriction 4 Valve 5 Product reservoir 8

9 Difficult Installation Conditions The accumulation of air or gas bubbles in the meter pipe can lead to increased inaccuracies. Fig. Fig. 9 shows critical installation conditions. Installations at the highest point in the pipeline (Figure A) can result in the formation of air pockets which can lead to appreciable inaccuracies. Another difficult installation condition is immediately upstream of a free discharge (Figure B) in a drop line. A 2..3 Installation notes FCM2000-MS2 Installing the flowmeter sensor DN.5 (/6 ) Horizontal installation is recommended. If vertical installation is required, a flow direction from below to above is recommended for better elimination of air bubbles. In order for air to be removed from the flowmeter sensor, the flow speed in the flowmeter sensor must be at least m/s. If the fluid contains solid particles, especially in conjunction with too little flow, a level installation location of the flowmeter sensor and positioning of the input flange completely on top is recommended so that the particles can be more easily flushed out. In order to avoid a partial emptying of the flowmeter sensor, a sufficient back pressure must be present at the unit (min bar/( psi)). Install the flowmeter sensor in a vibration-free manner to a wall or a steel frame. Position the flowmeter sensor at a low location in the system in order to avoid a negative pressure in the flowmeter sensor, that could lead to air or gas separation in the fluid. Ensure that the flowmeter sensor is not run empty (in the normal operation) as this can lead to inaccurate measurements. Horizontal B G00307 Fig. 9: Difficult Installation Conditions G00306 Vertical Important: Check whether the coordination flowmeter sensor and transmitter is correct. Compatible devices have the same end numbers, e. g., X00 and Y00 or X002 and Y002, on the type plate. Pressure losses The pressure losses, at the operating conditions, depends on the fluid and the actual flow. To calculate the pressure loss, the design program CD-CALC is provided. Fig. 0 G

10 High temperature version In the high temperature design the multi-connection plug is separated from the sensor housing by a pipe. Thereby the plug can still be accessed even when the sensor is insulated. - Angle multi-connection plug, vertical A specific orientation of the connection box is not prescribed for vertical installations, although the rotation of the sensor may not exceed the value shown. ± 90 ± 45 G00374 Fig. : Installation DN.5 (/6 ) vertical G0037 Important If there are large differences between the fluid and ambient temperature the sensor must be insulated, to prevent two phase flow and accuracy effects. This is especially important for low flowrates. The sensor must always be completely filled with homogeneous liquid or a single phase gas, otherwise the accuracy could be adversely affected. For air/gas in volatile fluids horizontal installations are recommended. Fig. 4: Angle multi-connection plug vertical Installing flowmeter sensor DN3/DN6 (/0 / /4") A horizontal installation position is recommended for light flow, since air bubbles are easier to remove in this position. If the liquid is volatile or contains solid particles, vertical installation is not recommended. Horizontal - + The mounting bracket included with the shipment should always be used. The bracket should be secured to a wall or a steel framework (vibration free and mechanically stable). 0mm Vertical G mm (0,08 ) G00372 Fig. 2: Installation DN.5 (/6 ) horizontal Angle multi-connection plug, horizontal To achieve optimum performance, the multi-connection plug is to be installed as shown in the figure. The multi-connection plug can be rotated within the angle noted. + ±5 ±5 G00373 Fig. 3: Angle multi-connection plug horizontal Fig. 5 G0030 0

11 Change from one to two columns Mass Flowmeter CoriolisMaster FCM2000 Change from one to two columns 3 Model FCM2000-MC2 3. Specifications Operating temperature effect Less than ± % of Q max / K Reproducibility of flowrate at rates > 5 % of Q max 0.0 % of flow rate for nom. deviation ± 0. % 0.5 % of flow rate for nom. deviation ± 0.25 % and 0.4 % Measuring range for density kg/dm 3 Fig. 6: FCM2000-MC2 flowmeter sensor Nominal sizes "E" (DN 20); "F" (DN 25); "G" (DN 40); "H" (DN 50); "I" (DN 65); "J" (DN 80); "K" (DN 00); "L" (DN 50) Measuring ranges for flowrate Nominal size Max. measuring range [Q max ] in [kg/min] "E" DN 20 (3/4") "F" DN 25 (") "G" DN 40 ( /2") "H" DN 50 (2") "I" DN 65 (2 0...,890 /2") "J" DN 80 (3") ,460 "K" DN 00 (4") ,60 "L" DN 50 (6") 0...,000 G0036 Measured value deviation for density Standard calibration ± 5 g/l Expanded density calibration ± g/l For separate designs, the signal cable is already calibrated and may not be either shortened or lengthened subsequently. The transmitter is calibrated accordingly and may not be changed. Reproducibility of density ± 0. g/l Measured value deviation for temperature C ( F) < C (33.8 F) For the precise temperatures for units with Ex approval, refer to the "Ex relevant specifications" section. If the ambient temperature is below -20 C (-4 F), additional flowrate, density, and temperature deviations are to be expected. Protection class: IP 65/IP 67, NEMA 4X Measured value deviation for flowrate DN 20 (3/4") to DN 65 (.5") (sizes "E", "F", "G", "H", "I") ± 0.4 % of flow rate % of Q max ± 0.25 % of flow rate % of Q max ± 0.5 % of flow rate % of Q max ± 0. % of flow rate % of Q max (not for size "E") (deviation from rate + zero error) Measured value deviation for flowrate DN 80 (3") and DN 00 (4") (sizes "J", "K") ± 0.4 % of flow rate % of Q max ± 0.25 % of flow rate % of Q max ± 0. % of flow rate % of Q max ± 0.5 % v. M % v. Q max (deviation from rate + zero error) Measured value deviation for flowrate DN 50 (6") (size "L") ± 0.4 % of flow rate ± 0.05 % of Q max ± 0.25 % of flow rate ± 0.05 % of Q max ± 0.5 % of flow rate ± 0.05 % of Q max ± 0. % of flow rate ± 0.05 % of Q max

12 3.. Reference conditions Calibration fluid Water 25 C (77 F) (+ 5 K/- 5 K) Pressure bar ( psi) Ambient temperature 25 C (77 F) (+ 0 K/- 5 K) Supply power Line voltage as per name plate U N ± % Warm-up phase 30 minutes Installation according to this specification No visible gas phase, no external mechanical or hydraulic disturbances, particularly cavitation Output calibration Pulse output Effect of the analog output on the measurement accuracy Similar to pulse output ± 0. % of measured value 3..2 Materials and additional specifications Flowmeter sensor materials Parts in contact with fluid Stainless steel.457/.4308 (36Ti/CF8) Stainless steel.4435/36l Hastelloy C-4/2.460 With flowmeter sensor material.4435 cert. acc. to EHEDG Option: Manufactured acc. to NACE MR075 (ISO 556) Housing Stainless steel.430/.4308 (304/CF8) Process connections Flange DIN/ASME Tri-clamp DIN (ISO 2852) - DN 5... DN 50 (/2... 2"): series 3 - DN DN 00 (2 /2... 4"): series Threaded pipe connection conforming to DIN 85 The max. permissible operating pressure is determined by the respective process connection, the fluid temperature, the screws, and the gasket material. Pressure rating PN 6, PN 40, PN 00 (up to DN 80 [3"]) CI 50, CI 300, CI 600 (up to DN 80 [3"]) Housing as protective device (optional) Max. 40 bar (580 psi) Pressure Equipment Directive 97/23/EC Conformity assessment in accordance with Category III, fluid group, gas Take into consideration the corrosion resistance of the meter tube materials as regards the measuring fluid. EHEDG-approved unit versions The appropriate installation conditions must be observed in order to achieve an installation that complies with hygiene requirements. The process connection/gasket combination created by the operator is particularly important too. Therefore, to ensure that the installation complies with hygiene requirements, only parts that conform to EHEDG stipulations (EHEDG Position Paper "Hygienic Process connections to use with hygienic components and equipment") may be used. Transmitter materials Housing Alloy casting, varnished Mid-section: RAL 702 Cover: RAL 9002 Paint coat: µm thickness Fluid temperature Standard: C ( F) The relevant ambient temperatures for use in a potentially explosive area can be found in the corresponding chapter. Ambient temperature C ( F); opt C ( F) The relevant ambient temperatures for use in a potentially explosive area can be found in the corresponding chapter. 2

13 Material load for process connections Process connection Threaded pipe connection conforming to DIN 85 Tri-Clamp conforming to DIN Nominal size DN (/2... /2") (2... 4") (/2... 2") (2 /2... 4") PS max [bar] TS max [ C] TS min [ C] Pressure [mbar] E F G H I J K L Material load curves for flanged units Pressure [bar] PN PN PN PN Pressure [psi] 0, G0034 Mass flowrate [kg/min] Fig. 9: Pressure loss curve FCM2000-MC2; measured with water, viscosity mpa s Viscosity range Max. dyn. viscosity: Pas (=,000 mpas =,000 cp) At higher viscosities, please contact our ABB representatives [ C] [ F] 0 G0032 Temperature Fig. 7: DIN flange SS.457 to DN 50 (6") CI Pressure [bar] CI CI Pressure [bar] [ C] [ F] Temperature C Fig. 8: ASME flange SS.457 to DN 50 (6") 0 G0033 3

14 Change from one to two columns Mass Flowmeter CoriolisMaster FCM Dimensions 3.2. Design MC2 Remote design, flanged construction "E" to "F", DIN/ASME 80 (3,5) 80 (3,5) ØA F G B L -5 2 G00339 Fig. 20: Dimensions in mm (inch) Flange DIN 2635 / ASME / ISO 7005 (connecting dimensions for ASME flanges acc. to ASME B6.5 (ANSI)) 2 Flow direction Meter size DN Process connection DIN 2635 PN 40 DN 5 (/2 ) 693 (27.28) 598 (23.54) DN 25 ( ) 698 (27.48) DN 20 (3/4 ) 758 (29.84) 658 (25.9) DN 40 ( /2 ) 808 (3.8) E (20) DN 20 (3/4 ) F (25) DN 25 ( ) All dimensions in mm (inch) DIN 2636 PN (27.76) DIN 2637 PN (27.76) 735 (28.94) 735 (28.94) 693 (27.28) 840 (33.07) 693 (27.28) 840 (33.07) L -5 G F B Ø A ASME CL (27.87) 68 (24.33) 728 (28.66) 778 (30.63) 688 (27.09) 838 (32.99) ASME CL (28.27) 628 (24.72) 738 (29.06) 788 (3.02) 698 (27.48) 855 (33.66) ASME CL (28.74) 645 (25.39) 753 (29.65) 802 (3.57) 70 (27.95) 868 (34.7) DIN form A ) 672 (26.46) 583 (22.95) 683 (26.89) 743 (29.25) 643 (25.3) 786 (30.94) 358 (4.09) 358 (4.09) 27 (5.00) 27 (5.00) 66 (2.60) 66 (2.60) 89 (3.50) 89 (3.50) Weight kg (lb) 5 (33.) 5 (33.) 6 (35.3) 6 (35.3) 6 (35.3) 9 (4.9) ) Antiseptic grooved flange DIN 864-2, form A, for pipes acc. to DIN 866 4

15 Remote design, flanged construction "G" to "L", DIN/ASME 80 (3,5) 80 (3,5) A G F 2 B L -5 G00340 Fig. 2: Dimensions in mm (inch) Flange DIN 2635 / ASME B6.5 / ISO 7005 (connecting dimensions for ASME flanges acc. to ASME B6.5 (ANSI)) 2 Flow direction 5

16 Meter size DN Process connection DIN 2633 DIN 2635 DIN 2636 DIN 2637 PN 6 PN 40 PN 64 PN 00 DN 25 ( ) G (40) DN 40 ( /2 ) DN 50 (2 ) DN 40 ( /2 ) H (50) DN 50 (2 ) I (65) J (80) DN 65 (2 /2 ) DN 50 (2 ) DN 65 (2 /2 ) DN 80 (3 ) DN 65 (2 /2 ) DN 80 (3 ) DN 00 (4 ) DN 80 (3 ) K (00) DN 00 (4 ) DN 50 (6 ) L (50) DN 50 (6 ) All dimensions in mm (inch) 450 (57.09) 450 (57.09) 736 (68.35) 2000 (78.74) 879 (34.6) 780 (30.7) 940 (37.0) 045 (4.4) 940 (37.0) 00 (43.3) 220 (48.03) 00 (43.3) 220 (48.03) 330 (52.36) 220 (48.03) 480 (58.27) 640 (64.57) 480 (58.27) 776 (69.92) 2040 (80.3) 94 (35.98) 83 (32.0) 967 (38.07) 078 (42.44) 967 (38.07) 32 (44.57) 248 (49.3) 32 (44.57) 248 (49.3) 362 (53.62) 248 (49.3) 494 (58.82) 668 (65.67) 494 (58.82) 86 (7.50) 2080 (8.89) 94 (35.98) 83 (32.0) 979 (38.54) 078 (42.44) 979 (38.54) 48 (45.20) 259 (49.57) 48 (45.20) 260 (49.6) 378 (54.25) 260 (49.6) 530 (60.24) 680 (66.4) 530 (60.24) L -5 G F B A ASME CL (35.83) 80 (3.89) 970 (38.9) 075 (42.32) 970 (38.9) 28 (47.95) 250 (49.2) 28 (47.95) 240 (48.82) 365 (53.74) 240 (48.82) 500 (59.06) 660 (65.35) 500 (59.06) ASME ASME DIN CL 300 CL 600 form A ) 922 (36.30) 825 (32.48) 980 (38.58) 090 (42.9) 980 (38.58) 228 (48.35) 260 (49.6) 228 (48.35) 260 (49.6) 375 (54.3) 260 (49.6) 520 (59.84) 680 (66.4) 520 (59.84) (7.0) (7.89) (8.50) (82.28) 932 (36.69) 843 (33.9) 00 (39.4) 08 (43.62) 00 (39.4) 248 (49.3) 28 (50.43) 249 (49.7) 282 (50.47) 396 (54.96) 282 (50.47) 568 (6.73) 702 (67.0) 568 (6.73) 864 (34.02) 76 (29.96) 98 (36.4) 025 (40.35) 98 (36.4) 08 (42.56) 97 (47.3) 08 (42.56) 200 (47.24) 30 (5.57) 200 (47.24) 463 (57.60) 68 (63.70) 463 (57.60) 374 (4.72) 403 (5.87) 429 (6.89) 456 (7.95) 500 (9.69) 63 (24.3) 29 (5.08) 48 (5.83) 64 (6.46) 86 (7.32) 25 (8.46) 285 (.22) 64 (2.52) 80 (3.5) 97 (3.82) 08 (4.25) 3 (5.6) 90 (7.48) 90 (3.54) 0 (4.33) Wt. kg (lb) 20 (44.) 22 (48.5) 23 (50.7) 32 (70.5) 34 (75.0) 38 (83.8) 43 (94.8) (5.2) (05.8) 50 (0.2) 56 (23.5) (5.5) (27.9) 69 (52.) (6.69) (85.2) 9 (200.6) 20 (264.6) (9.84) (529.) ) Antiseptic grooved flange DIN 864-2, form A, for pipes acc. to DIN 866 6

17 Dimensions, remote design, food industry fitting "E" to "F", DIN (3,5) 80 (3,5) R G F A B L -5 2 g G0034 Fig. 22: Dmensions in mm (inch) Food industry fitting acc. to DIN 85 (threaded connector) 2 Flow direction Meter Size DN Process connection L -5 g G F B Ø A R Weight kg (lb) DN 5 / /2" Rd 34 x /8 672 (26.46) 4 (0.6) 52 (5.98) "E" (20) DN 20 / 3/4" Rd 44 x /6 583 (22.95) 6 (0.24) 358 (4.09) 27 (5.00) 66 (2.60) 89 (3.50) 02 (4.02) 3 (28.7) DN 25 / " Rd 52 x /6 683 (26.89) 7 (0.28) 52 (5.98) DN 20 / 3/4" Rd 44 x /6 743 (29.25) 6 (0.24) 62 (6.38) "F" (25) DN 25 / " Rd 52 x /6 643 (25.3) 7 (0.28) 358 (4.09) 27 (5.00) 66 (2.60) 89 (3.50) 2 (4.4) 4 (30.9) DN 40 / /2" Rd 65 x /6 786 (30.94) 7 (0.28) 85 (7.28) All dimensions in mm (inch) If this connection is supplied with an EHEDG-certified device, the device nominal sizes must correspond with the connection nominal sizes! 7

18 Remote design, food industry fitting "G" to "K", DIN (3,5) 80 (3,5) R F G A B L -5 2 L g G00342 Fig. 23: Dimensions in mm (inch) Food industry fitting acc. to DIN 85 (threaded connector) 2 Flow direction Meter Size DN Process connection L -5 g G F B A R Weight kg (lb) DN 25 / (") Rd 52 x /6 864 (34.02) 7 (0.28) 28 (8.58) 6 (35.3) G (40) DN 40 / ( /2") Rd 65 x /6 76 (29.96) 7 (0.28) 374 (4.72) 29 (5.08) 64 (2.52) 90 (3.54) 64 (6.46) 8 (39.7) DN 50 / (2") Rd 78 x /6 98 (36.4) 7 (0.28) 24 (9.49) 9 (4.9) DN 40 / ( /2") Rd 65 x /6 025 (40.35) 7 (0.28) 233 (9.7) 28 (6.7) H (50) DN 50 / (2") Rd 78 x /6 98 (36.4) 7 (0.28) 403 (5.87) 48 (5.83) 80 (3.5) 0 (4.33) 77 (6.97) 30 (66.) DN 65 / (2 /2") Rd 95 x /6 08 (42.56) 8 (0.3) 254 (0.00) 34 (75.0) DN 50 / (2") Rd 78 x /6 97 (47.3) 7 (0.28) 29 (.46) 40 (88.2) I (65) DN 65 / (2 /2") Rd 95 x /6 08 (42.56) 8 (0.3) 429 (6.89) 64 (6.46) 97 (3.82) 30 (5.2) 227 (8.94) 44 (97.0) DN 80 / (3") Rd 0 x /4 200 (47.24) 8 (0.3) 28 (.06) 47 (03.6) DN 65 / (2 /2") Rd 95 x /6 30 (5.57) 8 (0.3) 39 (2.56) 54 (9.0) J (80) DN 80 / (3") Rd 0 x /4 205 (47.44) 8 (0.3) 456 (7.95) 86 (7.32) 08 (4.25) 40 (5.5) 258 (0.6) 56 (23.5) DN 00 / (4") Rd 30 x /4 463 (57.60) 0 (0.39) 38 (5.00) 60 (32.3) K (00) DN 80 / (3") Rd 0 x /4 68 (63.70) 8 (0.3) 40 (5.79) 82 (80.8) DN 00 / (4") Rd 30 x /4 463 (57.60) 0 (0.39) 500 (9.69) 25 (8.46) 3 (5.6) 70 (6.69) 34 (2.36) 86 (89.6) All dimensions in mm (inch) If this connection is supplied with an EHEDG-certified device, the device nominal sizes must correspond with the connection nominal sizes! 8

19 Remote design, tri-clamp "E" to "F", DIN (ISO 2852) 80 (3,5) 80 (3,5) R ØA G F B L -5 G00343 Fig. 24: Flow direction Dimensions in mm (inch) Meter Size DN Process connection L -5 G F B Ø A R Weight kg (lb) DN 5 (/2) 656 (25.83) 40 (5.5) 2 (26.5) E (20) DN 20 (3/4 ) DIN (22.09) 358 (4.09) 27 (5.00) 66 (2.60) 89 (3.50) 92 (3.62) DN 25 ( ) 66 (26.02) 42 (5.59) DN 20 (3/4 ) 72 (28.39) 52 (5.98) F (25) DN 25 ( ) DIN (24.45) 358 (4.09) 27 (5.00) 66 (2.60) 89 (3.50) 02 (4.02) DN 40 ( /2 ) 773 (30.43) 80 (7.09) All dimensions in mm (inch) 3 (28.7) If this connection is supplied with an EHEDG-certified device, the device nominal sizes must correspond with the connection nominal sizes! 9

20 Remote design, tri-clamp "G" to "K", DIN (ISO 2852) 80 (3,5) 80 (3,5) R F A G B L -5 G00344 Fig. 25: Flow direction Dimensions in mm (inch) Meter Size DN Process connection fitting L -5 ± 3 G F B A R Weight kg (lb) DN 25 ( ) 842 (33.5) 242 (9.53) 7 (37.5) G (40) DN 40 ( /2 ) 748 (29.45) 374 (4.72) 29 (5.08) 64 (2.52) 90 (3.54) 95 (7.68) 7 (37.5) DN 50 (2 ) 93 (35.94) 278 (0.94) 8 (39.7) DN 40 ( /2 ) 02 (39.84) 275 (0.83) 27 (59.5) H (50) DN 50 (2 ) 93 (35.94) 403 (5.87) 48 (5.83) 80 (3.5) 0 (4.33) 225 (8.86) 26 (57.3) DN 65 (2 /2 ) 073 (42.24) 305 (2.0) 27 (59.5) DN 50 (2 ) 92 (46.93) 335 (3.9) 36 (79.4) I (65) DN 65 (2 /2 ) 073 (42.24) 429 (6.89) 64 (6.46) 97 (3.82) 30 (5.2) 275 (0.83) 37 (8.6) DN 80 (3 ) 80 (46.46) 328 (2.9) 38 (83.8) DN 65 (2 /2 ) 302 (5.26) 378 (4.88) 45 (99.2) J (80) DN 80 (3 ) 80 (46.46) 456 (7.95) 86 (7.32) 08 (4.25) 40 (5.5) 296 (.65) 44 (97.0) DN 00 (4 ) 448 (57.0) 430 (6.93) 46 (0.4) K (00) DN 80 (3 ) 598 (62.9) 500 (9.69) 25 (8.46) 3 (5.6) 70 (6.69) 440 (7.32) 7 (56.5) DN 00 (4 ) 448 (57.0) 365 (4.37) 69 (52.) All dimensions in mm (inch) If this connection is supplied with an EHEDG-certified device, the device nominal sizes must correspond with the connection nominal sizes! 20

21 3.2.2 Design MC23 / MC26 / MC27 compact design or remote Ex design Flanged construction "E" to "F", DIN/ASME 200 (7,87) 80 (3,5) F Ø 34 (5,27) G ØA 2 B L -5 G00333 Fig. 26: Dimensions in mm (inch) Flange DIN 2635 / ASME B6.5 / ISO 7005 (connecting dimensions for ASME flanges acc. to ASME B6.5 (ANSI)) 2 Flow direction Meter Size DN A F B G Process L -5 connection DN MC23 MC26/ MC27 DIN 2635 PN 40 DIN 2636 PN 64 DIN 2637 PN 00 ASME CL 50 ASME CL 300 ASME CL 600 DIN form A ) Weight kg (lb) 20 ( E ) 25 ( F ) 89 (3.50) 89 (3.50) 27 (5) 27 (5) 66 (2.60) 66 (2.60) 470 (8.50) 470 (8.50) 494 (9.45) 494 (9.45) 5 (/2 ) 20 (3/4 ) 25 ( ) 20 (3/4 ) 25 ( ) 40 ( /2 ) 693 (27.28) 598 (23.54) 698 (27.48) 758 (29.84) 658 (25.9) 808 (3.8) 705 (27.76) 705 (27.76) 708 (27.87) 68 (24.33) 735 (28.94) 735 (28.94) 728 (28.66) 778 (30.63) 693 (27.28) 840 (33.07) 693 (27.28) 840 (33.07) 688 (27.09) 838 (32.99) 78 (28.27) 628 (24.72) 738 (29.06) 788 (3.02) 698 (27.48) 855 (33.66) 730 (28.74) 645 (25.39) 753 (29.65) 802 (3.57) 70 (27.95) 868 (34.7) 672 (26.46) 583 (22.95) 683 (26.89) 743 (29.25) 643 (25.3) 786 (30.94) All dimensions in mm (inch) ) Antiseptic grooved flange DIN 864-2, form A, for pipes acc. to DIN 866 2

22 Flanged construction "G" to "L", DIN/ASME 200 (7,87) 80 (3,5) F A G Ø 34 (5,27) 2 B L -5 G00334 Fig. 27: Dimensions in mm (inch) Flange DIN 2635 / ASME B6.5 / ISO 7005 (connecting dimensions for ASME flanges acc. to ASME B6.5 (ANSI)) 2 Flow direction 22

23 Meter Size DN 40 ( G ) 50 ( H ) 65 ( I ) 80 ( J ) 00 ( K ) 50 ( L ) A F B G Process L -5 conn. MC23 MC26/ DIN 2633 DIN 2635 DIN 2636DIN 2637 ASME ASME ASME DN MC27 PN 6 PN 40 PN 64 PN 00 CL 50 CL 300 CL (3.54) 0 (4.33) 30 (5.2) 40 (5.5) 70 (6.69) 250 (9.84) 29 (5.08) 48 (5.83) 64 (6.46) 86 (7.32) 25 (8.46) All dimensions in mm (inch) (2.52) (9.3) (3.5) (20.28) (3.82) (2.30) (4.25) (22.36) 3 62 (5.6) (24.09) (.22) (7.48) (28.54) 5 (20.2) 540 (2.26) 566 (22.28) 593 (23.35) 637 (25.08) 750 (29.53) 25 ( ) 40 ( /2 ) 50 (2 ) 40 ( /2 ) 50 (2 ) 65 (2 /2 ) 50 (2 ) 65 (2 /2 ) 80 (3 ) 65 (2 /2 ) 80 (3 ) 00 (4 ) 80 (3 ) 00 (4 ) 50 (6 ) 50 (6 ) ) Antiseptic grooved flange DIN 864-2, form A, for pipes acc. to DIN (57.09) 450 (57.09) 736 (68.35) 2000 (78.74) 879 (34.6) 780 (30.7) 940 (37.0) 045 (4.4) 940 (37.0) 00 (43.3) 220 (48.03) 00 (43.3) 220 (48.03) 330 (52.36) 220 (48.03) 480 (58.27) 640 (64.57) 480 (58.27) 776 (69.92) 2040 (80.3) 94 (35.98) 83 (32.0) 967 (38.07) 078 (42.44) 967 (38.07) 32 (44.57) 248 (49.3) 32 (44.57) 248 (49.3) 362 (53.62) 248 (49.3) 494 (58.82) 668 (65.67) 494 (58.82) 86 (7.50) 2080 (8.89) 94 (35.98) 83 (32.0) 979 (38.54) 078 (42.44) 979 (38.54) 48 (45.20) 259 (49.57) 48 (45.20) 260 (49.6) 378 (54.25) 260 (49.6) 530 (60.24) 680 (66.4) 530 (60.24) 90 (35.83) 80 (3.89) 970 (38.9) 075 (42.32) 970 (38.9) 28 (47.95) 250 (49.2) 28 (47.95) 240 (48.82) 365 (53.74) 240 (48.82) 500 (59.06) 660 (65.35) 500 (59.06) (36.30) (36.69) (32.48) (33.9) (38.58) (39.4) (42.9) (43.62) (38.58) (39.4) (48.35) (49.3) (49.6) (50.43) (48.35) (49.7) (49.6) (50.47) (54.3) (54.96) (49.6) (50.47) (59.84) (6.73) (66.4) (67.0) (59.84) (6.73) (7.0) (7.89) (8.50) (82.28) DIN form A ) 864 (34.02) 76 (29.96) 98 (36.4) 025 (40.35) 98 (36.4) 08 (42.56) 97 (47.3) 08 (42.56) 200 (47.24) 30 (5.57) 200 (47.24) 463 (57.60) 68 (63.70) 463 (57.60) Weight kg (lb) 2 (46.3) 23 (50.7) 24 (52.9) 33 (72.8) 35 (77.2) 39 (86.0) 44 (97.0) 49 (08.0) 5 (2.4) 57 (25.7) 59 (30.) 70 (54.3) 85 (87.4) 92 (202.8) 20 (264.6) 240 (529.) 23

24 Food industry fitting "E" to "F", DIN (7,87) 80 (3,5) Ø 34 (5,27) G ØA F 2 B L -5 G00336 Fig. 28: Dimensions in mm (inch) Food industry fitting acc. to DIN 85 (threaded connector) 2 Flow direction Meter Size A F B G Process connection L -5 DN MC23 MC26 / MC27 DN DIN 85 5 (/2 ) 672 (26.46) 20 ( E ) 89 (3.50) 27 (5.00) 66 (2.60) 470 (8.50) 494 (9.45) 20 (3/4 ) 583 (22.95) 25 ( ) 683 (26.89) 20 (3/4 ) 743 (29.25) 25 ( F ) 89 (3.50) 27 (5.00) 66 (2.60) 470 (8.50) 494 (9.45) 25 ( ) 643 (25.3) 40 ( /2 ) 786 (30.94) Weight appr. kg (lb) 4 (30.9) 5 (33.) All dimensions in mm (inch) If this connection is supplied with an EHEDG-certified device, the device nominal sizes must correspond with the connection nominal sizes! 24

25 Food industry fitting "G" to "K", DIN (7,87) 80 (3,5) Ø 34 (5,27) G R F 2 g B L -5 L G00335 Fig. 29: Dimensions in mm (inch) Food industry fitting acc. to DIN 85 (threaded connector) 2 Flow Direction Meter Size DN 40 ( G ) 50 ( H ) 65 ( I ) 80 ( J ) 00 ( K ) A F B G Process L -5 g M R connection MC23 MC26/ DN MC27 90 (3.54) 0 (4.33) 30 (5.2) 40 (5.5) 70 (6.69) 29 (5.08) 48 (5.83) 64 (6.46) 86 (7.32) 25 (8.46) All dimensions in mm (inch) 64 (2.52) 80 (3.5) 97 (3.82) 08 (4.25) 3 (5.6) 486 (9.3) 55 (20.28) 54 (2.30) 568 (22.36) 62 (24.09) Weight appr kg (lb) 25 ( ) 864 (34.02) 7 (0.28) Rd 52 x /6 28 (8.58) 2 (46.3) 5 (20.2) 40 ( /2 ) 6 (29.96) 7 (0.28) Rd 65 x /6 64 (6.46) 23 (50.7) 50 (2 ) 98 (36.4) 7 (0.28) Rd 78 x /6 24 (9.49) 24 (52.9) 40 ( /2 ) 025 (40.35) 7 (0.28) Rd 65 x /6 233 (9.7) 33 (72.8) 540 (2.26) 50 (2 ) 98 (36.4) 7 (0.28) Rd 78 x /6 77 (6.97) 35 (77.2) 65 (2 /2 ) 08 (42.56) 8 (0.3) Rd 95 x /6 254 (0.00) 39 (86.0) 50 (2 ) 97 (47.3) 7 (0.28) Rd 78 x /6 29 (.46) 44 (97.0) 566 (22.28) 65 (2 /2 ) 08 (42.56) 8 (0.3) Rd 95 x /6 227 (8.94) 48 (05.8) 80 (3 ) 200 (47.24) 8 (0.3) Rd 0 x /4 28 (.06) 5 (2.4) 65 (2 /2 ) 30 (5.57) 8 (0.3) Rd 95 x /6 39 (2.56) 57 (25.7) 593 (23.35) 80 (3 ) 200 (47.24) 8 (0.3) Rd 0 x /4 258 (0.6) 59 (30.) 00 (4 ) 463 (57.60) 0 (0.39) Rd 30 x /4 38 (5.00) 70 (54.3) (3 ) 68 (63.70) 8 (0.3) Rd 0 x /4 40 (5.79) 85 (87.4) (25.08) 00 (4 ) 463 (57.60) 0 (0.39) Rd 30 x /4 34 (2.36) 92 (202.8) If this connection is supplied with an EHEDG-certified device, the device nominal sizes must correspond with the connection nominal sizes! 25

26 Tri-clamp "E" to "F", DIN (ISO 2852) 200 (7,87) 80 (3,5) R ØA G Ø 34 (5,27) F B L -5 G00338 Fig. 30: Flow direction Dimensions in mm (inch) A F B G Process L -5 R Meter Size connection DN MC23 MC26/ DN MC27 5 (/2 ) 656 (25.83) 40 (5.5) 20 ( E ) 89 (3.50) 27 (5.00) 66 (2.60) 470 (8.50) 494 (9.45) 20 (3/4 ) 56 (22.09) 92 (3.62) 25 ( ) 66 (26.02) 42 (5.59) 20 (3/4 ) 72 (28.39) 52 (5.98) 25 ( F ) 89 (3.50) 27 (5.00) 66 (2.60) 470 (8.50) 494 (9.45) 25 ( ) 62 (24.45) 02 (4.02) 40 ( /2 ) 773 (30.43) 80 (7.09) All dimensions in mm (inch) Weight appr kg (lb) 4 (30.9) 5 (33.) If this connection is supplied with an EHEDG-certified device, the device nominal sizes must correspond with the connection nominal sizes! 26

27 Tri-clamp "G" to "K", DIN (ISO 2852) 200 (7,87) 80 (3,5) G R F ØA Ø 34 (5,27) B L -5 G00337 Fig. 3: Flow direction Dimensions in mm (inch) A F B G Process L -5 R Meter Size connection DN MC23 MC26/ DN MC27 40 ( G ) 90 (3.54) 29 (5.08) 64 (2.52) 486 (9.3) 5 (20.2) 50 ( H ) 0 (4.33) 48 (5.83) 80 (3.5) 55 (20.28) 540 (2.26) 65 ( I ) 30 (5.2) 64 (6.46) 97 (3.82) 54 (2.30) 566 (22.28) 80 ( J ) 40 (5.5) 86 (7.32) 08 (4.25) 568 (22.36) 593 (23.35) 00 ( K ) 70 (6.69) 25 (8.46) 3 (5.6) 62 (24.09) 637 (25.08) All dimensions in mm (inch) Weight appr kg (lb) 25 ( ) 842 (33.5) 242 (9.53) 7 (37.5) 40 ( /2 ) 748 (29.45) 95 (7.68) 7 (37.5) 50 (2 ) 93 (35.94) 278 (0.94) 8 (39.7) 40 ( /2 ) 02 (39.84) 275 (0.83) 27 (59.5) 50 (2 ) 93 (35.94) 225 (8.86) 26 (57.3) 65 (2 /2 ) 073 (42.24) 305 (2.0) 27 (59.5) 50 (2 ) 92 (46.93) 335 (3.9) 36 (79.4) 65 (2 /2 ) 073 (42.24) 275 (0.83) 37 (8.6) 80 (3 ) 80 (46.46) 328 (2.9) 38 (83.8) 65 (2 /2 ) 302 (5.26) 378 (4.88) 45 (99.2) 80 (3 ) 80 (46.46) 296 (.65) 44 (97.0) 00 (4 ) 448 (57.0) 430 (6.93) 46 (0.4) 80 (3 ) 598 (62.9) 440 (7.32) 7 (56.5) 00 (4 ) 448 (57.0) 365 (4.37) 69 (52.) If this connection is supplied with an EHEDG-certified device, the device nominal sizes must correspond with the connection nominal sizes! 27

28 3.3 Ordering information Separate sensor and compact version, DN 5... DN 50 (/2... 6") Main order number Version number CoriolisMaster mass flowmeter FCM2000 MC2 X X X X X X X X X X X X X X X X X Design Remote design Compact (integral) design 3 Ex, remote design, ATEX, FM Class I, Div. 4) 6 Ex, compact (integral) design, ATEX, FM Class I, Div. 7 Explosion Protection / Connection / Ambient Temperature None / M20 x.5 / Standard A None / NPT /2 in. / Standard T None/cable gland M20 x.5/extended C ( F) 5) U None / M20 x.5 / Extended C ( F) 5) X ATEX Zone / M20 x.5 / Standard 3) B ATEX Zone 2 / M20 x.5 / Standard 6) M ATEX / M20 x.5 / Extended C ( F) 3) E ATEX Zone 2 / M20 x.5 / Extended C ( F) 5) N FM Class I, Div., Zone / NPT /2 in. / Standard 3) C FM Class I, Div. 2, Zone 2 / NPT /2 in. / Standard O FM Class I, Div., Zone / NPT /2 in. / Extended C ( F) 3) Y FM Class I, Div. 2, Zone 2 / NPT /2 in. / Extended C ( F) 5) V CSA Class I, Div., Zone / NPT /2 in. / Standard 7) D CSA Class I, Div. 2, Zone 2 / NPT /2 in. / Standard 6) P CSA Class I, Div., Zone / NPT /2 in. / Extended C ( F) 3) Q CSA Class I, Div. 2, Zone 2 / NPT /2 in. / Extended C ( F) 5) W Certificates Standard Material certificate 3. acc. to EN Material certificate acc. to EN Pressure test per AD Pressure test per AD Certificate NACE material 5 Certificate NACE + Pressure test 6 Tube Material AISI 36Ti SST (.457) AISI 36L SST (.4435) EHEDG design 8) 3 Hastelloy C-4 (2.460) 2) 4 Measuring Range / Meter Size / DN Nominal kg/min ( lbs/min) / ''E'' / DN 20 (3/4 in.) E kg/min ( lbs/min) / ''F'' / DN 25 ( in.) F kg/min ( lbs/min) / ''G'' / DN 40 (-/2 in.) G kg/min ( lbs/min) / ''H'' / DN 50 (2 in.) H kg/min ( lbs/min) / ''I'' / DN 65 (2-/2 in.) I kg/min ( lbs/min) / ''J'' / DN 80 (3 in.) J kg/min ( lbs/min) / ''K'' / DN 00 (4 in.) K kg/min ( lbs/min) / ''L'' / DN 50 (6 in.) L Continued on next page 28

29 Main order number Version number CoriolisMaster mass flowmeter FCM2000 MC2 X X X X X X X X X X X X X X X X X Process Connection Size DN 5 (/2 in.) 9) 5 DN 20 (3/4 in.) 9) 2 0 DN 25 ( in.) 9) 2 5 DN 40 ( /2 in.) 9) 4 0 DN 50 (2 in.) 9) 5 0 DN 65 (2 /2 in.) 9) 6 5 DN 80 (3 in.) 9) 8 0 DN 00 (4 in.) 9) H DN 50 (6 in.) 9) F Process Connection Flange DIN PN 6 D Flange DIN PN 40 F Flange DIN PN 64 G Flange DIN PN 00 0) H Flange ASME CL 50 P Flange ASME CL 300 Q Flange ASME CL 600 ) R Aseptic Flange acc. to DIN Form A for tubes acc. to DIN 866 N Tri-Clamp acc. to DIN ) U Pipe connection acc. to DIN 85 0) V 29

30 Main order number Version number CoriolisMaster mass flowmeter FCM2000 MC2 X X X X X X X X X X X X X X X X X Housing (sensor) Standard Housing as secondary containment 40 bar (565 psi) 0) 2 Heating / Cooling Without Calibration Flow forward +/ % of flow rate / density (+/- 5 g/l) A Flow forward +/ % of flow rate / density (+/- 5 g/l) B Flow forward +/- 0.5 % of flow rate / density (+/- 5 g/l) C Flow forward +/- 0. % of flow rate / density (+/- 5 g/l) 2) M Flow forward +/ % of flow rate / density (+/- g/l) 0) D Flow forward +/ % of flow rate / density (+/- g/l) 0) E Flow forward +/- 0.5 % of flow rate / density (+/- g/l) 0) F Flow forward +/- 0. % of flow rate / density (+/- g/l) 2) N Flow forward / reverse +/ % of flow rate / density (+/- 5 /l) G Flow forward / reverse +/ % of flow rate / density (+/- 5 /l) H Flow forward / reverse +/- 0.5 % of flow rate / density (+/- 5 /l) I Flow forward / reverse +/- 0. % of flow rate / density (+/- 5 g/l) 2) O Flow forward / reverse +/ % of flow rate / density (+/- /l) 0) J Flow forward / reverse +/ % of flow rate / density (+/- /l) 0) K Flow forward / reverse +/- 0.5 % of flow rate / density (+/- /l) 0) L Flow forward / reverse +/- 0. % of flow rate / density (+/- g/l) 2) P Name Plate / Documentation German G English E Design level (Specified by ABB) X Operating Mode / Software Version Not selected (for remote design only) X Standard software (mass and density measurement) A Standard software plus Concentration calculation (DensiMass) C Outputs Current output I (active), Current output II (passive) + Pulse output (active) [Ex not possible] ) A Current output I (active), Current output II (passive) + Pulse output (passive) B Current output I (passive), Current output II (passive) + Pulse output (passive) 3) D Not selected / Fieldbus / Remote X Communication Not selected (for remote design only) X Without 0 HART protocol PROFIBUS PA 3 FOUNDATION Fieldbus 5 PROFIBUS PA with M2 plug 7 Power Supply Not selected (for remote design only) X High voltage V AC G Low voltage 24 V AC / DC K Accessories FCM2000-MC2 Signal Cable (Price per Meter) D73D46U0 ) Not for size ``L`` (DN 50 [6 in.]). Size ``K`` (DN 00 [4 in.]) on request 2) Not for size ``L`` (DN 50 [6 in.]) or "E" (DN 20 [3/4 in.]) 3) Only for MC27 4) With transmitter ME2- for Non-hazardous area. FM, CSA in preparation 5) Only for MC23 6) Only for MC2 / MC23 7) Only for MC27 / MC26 8) Only with process connection DIN 85 or Tri-Clamp and size ``E``... ``J`` 9) For available combinations, see data sheet 0) Not for size ``L`` (DN 50 [6 in.]) ) Not for MC27 2) Only DIN PN 40 / ASME CL 50 and size ``E``... ``K`` 30

31 Change from one to two columns Mass Flowmeter CoriolisMaster FCM Model FCM2000-MS2 4. Specifications Supply power Line voltage as per name plate U N ± % Warm-up phase 30 minutes Installation according to this specification No visible gas phase No external mechanical or hydraulic disturbances, particularly cavitation G0035 Output calibration Pulse output Fig. 32: FCM2000-MS2 flowmeter sensor Nominal sizes "S" (DN.5); "T" (DN 3); "U" (DN 6) Measuring ranges for flowrate Nominal size Max. measuring range [Q max ] in [kg/h] "S" DN.5 (/6") "T" DN 3 (/0") "U" DN 6 (/4") Protection class: IP 65 Measured value deviation for flowrate ± 0.4 % of flow rate ± 0.02 % of Q max ± 0.25 % of flow rate ± 0.02 % of Q max ± 0.5 % of flow rate ± 0.0 % of Q max (deviation from rate + zero error) Reproducibility of flowrate 0. % of flow rate for nom. deviation ± 0.5 % 0.5 % of flow rate for nom. deviation ± 0.25 % and 0.4 % Measuring range for density kg/dm 3 Measured value deviation for density Standard calibration ± 0 g/l Temperature range C ( F) Expanded density calibration available upon request Measured value deviation for temperature C ( F) < C (33.8 F) Effect of the analog output on the measurement accuracy Similar to pulse output ± 0. % of measured value Materials and additional specifications Sensor materials Parts in contact with fluid.4435/36l Housing.4404 Fluid temperature Standard: C ( F): DN 3 (/0"), DN 6 (/4") C ( F): DN.5 (/6") C ( F): DN.5 (/6") (optional) For information about the design for operation in potentially explosive areas, refer to the corresponding chapter. Ambient temperature C ( F) For information about the design for operation in potentially explosive areas, refer to the corresponding chapter. Process connections G/4" ISO 228- /4" NPT ASME B.20 Flange DIN/ASME for DN 6 (/4") Threaded pipe connection conforming to DIN 85 for DN 6 (/4") Tri-Clamp conforming to DIN (ISO 2852) for DN 6 (/4") The max. permissible operating pressure is determined by the respective process connection, the fluid temperature, the screws, and the gasket material. Pressure rating Flange PN 40, PN 00, Cl 50, Cl 600 Thread G /4", /4" NPT, PN PN 40 (for each option) Reference conditions Calibration fluid Water 25 C (77 F) (+ 5 K/- 5 K) Pressure bar ( psi) Installation For more detailed instructions regarding installation, refer to the operating instructions. Ambient temperature 25 C (77 F) (+ 0 K/- 5 K) 3

32 Mass Flowmeter CoriolisMaster FCM2000 Pressure loss curves 00 Viscosity [cst] Viscosity [cst] P [bar],0 P [bar],0 0, 0,0 0, 0 70 [kg/h] G0037 0, [kg/h] G0038 Fig. 33: Pressure losses MS2, DN.5 (/6") Fig. 35: Pressure losses MS2, DN 6 (/4") Viscosity [cst] P [bar],0 0, [kg/h] G0038 Fig. 34: Pressure losses MS2, DN 3 (/0") 32

33 Change from one to two columns Mass Flowmeter CoriolisMaster FCM Dimensions 4.2. Design MS2 Remote design DN 3... DN 6 (/0... /4 ) L3 L L2 88 (3,46) B D D D H (3,03) D L D 5 L L 7,5 (0,68) G00345 Size T = DN 3 (/0 ) Size U = DN 6 (/4 ) Fig. 36: Dimensions in mm (inch) 33

34 Nom. size DN Connections Type Pressure PN Size Threaded connector ISO 228/-G /4 3 (/0 ) Threaded connection ANSI/ASME B.20.-/4" NPT Flange DIN (/4 ) Flange DIN 2637 Flange DIN 2635 Flange DIN 2637 Flange ANSI / ASME B 6.5 Flange ANSI / ASME B 6.5 Flange ANSI / ASME B 6.5 Flange ANSI / ASME B 6.5 Screwed connection DIN 85 Screwed connection DIN 85 Tri-clamp, DIN (ISO 2852) Clamp, ISO 2853 Threaded connector ISO 228/-G /4 Threaded connection ANSI/ ASME B.20.-/4" NPT Threaded connection ISO 228/-G /4 Threaded connection ANSI/ ASME B.20.-/4" NPT Measurements in mm (inch) 00 /4 00 / (64) (64) DN 0 DN 0 DN 5 DN 5 Class 50 /2 L L2 L3 H B D D2 D3 D4 D (5.75) (.02) (2.44) (2.36) (5.75) (.02) (2.44) (2.36) (22.05) (.02) (2.44) (22.83) (.02) (2.44) (25.2) (.02) (2.44) (25.75) (.02) (2.44) (24.57) (5.35) (2.44) Class 600 / (25.43) (5.35) (2.44) Class 50 3/ (26.38) (5.35) (2.44) Class 600 3/ (27.28) (5.35) (2.44) 40 DN (20.94) (5.35) (2.44) 40 DN (22.44) (5.35) (2.44) mm (22.44) (5.35) (2.44) mm (22.56) (5.35) (2.44) 00 / (22.3) (5.35) (2.44) 00 / (22.3) (5.35) (2.44) EN.4435 PN /4 EN PN 40 (22.3) (5.35) (2.44) EN.4435 PN /4 EN PN 40 (22.3) (5.35) (2.44) 40 (.57) 40 (.57) 40 (.57) 40 (.57) 40 (.57) 40 (.57) 40 (.57) 40 (.57) 40 (.57) 40 (.57) 40 (.57) 40 (.57) 40 (.57) 40 (.57) 40 (.57) 40 (.57) (0.47) 2 (0.47) 2 (0.47) 2 (0.47) 2 (0.47) 2 (0.47) 2 (0.47) 2 (0.47) 2 (0.47) 2 (0.47) 2 (0.47) 2 (0.47) 2 (0.47) 2 (0.47) 2 (0.47) 2 (0.47) (0.84) (4.09) (0.84) (4.09) 7.0 (0.67) 7.0 (0.67) 7.0 (0.67) 7.0 (0.67) 7.0 (0.67) 7.0 (0.67) 7.0 (0.67) 7.0 (0.67) 7.0 (0.67) 7.0 (0.67) 7.0 (0.67) 7.0 (0.67) 7.0 (0.67) 7.0 (0.67) 7.0 (0.67) 7.0 (0.67) 04 (4.09) 04 (4.09) 04 (4.09) 04 (4.09) 04 (4.09) 04 (4.09) 04 (4.09) 04 (4.09) 04 (4.09) 04 (4.09) 04 (4.09) 04 (4.09) 04 (4.09) 04 (4.09) 04 (4.09) 04 (4.09) 90.0 (3.54) 88.9 (3.50) 60.0 (2.36) 60.5 (2.38) 4.0 (0.55) 5.7 (0.62) Weight appr. kg (lb) 4 (8.8) 8 (7.6) 34

35 Remote design, DN.5 (/6 ) 20 (,8) 46 (0,47) 86 (3,38) 52 (5,98) Ø29 (5,07) 78 (3,07) 64,5 (2,53) Ø57 (2,24) 4 (0,6) 20 (4,72) 0 (0,39) 5 (0,59) 2 (0,47) NV2 5 (0,59) 2 (0,47) NV2 /4 NPT G /4 Ø8,8 (0,74) Ø8,8 (0,74) Ø24 (0,94) Ø24 (0,94) Ø9 (0,35) /4 NPT ANSI/ASME B G /4 ISO 228/ 20 (0,78) 00 (3,93) 25 (0,98) G00346 Fig. 37: Dimensions in mm (inch) 35

36 4.3 Ordering information Separate sensor, DN.5... DN 6 (/0... /4") Main order number Version number CoriolisMaster mass flowmeter FCM2000 MS2 X X X X X X X X X X X X X Design Remote design Ex, remote design, ATEX 6 Application Standard A ATEX Zone / M20 x.5 / Standard B Certificates Standard EN Pressure Test 3 Tube Material AISI 36L SST (.4435) 3 Hastelloy C-22 (2.4602) 4 Measuring Range kg/h ( lbs/h), DN.5 (/6 in.) S kg/h ( lbs/h), DN 3 (/0 in.) T kg/h ( lbs/h), DN 6 (/4 in.) U Temperature Version Max. 25 C (257 F) (only DN.5 [/6 in.]) Max. 80 C (356 F) (DN 3 and DN 6 [/0 and /4 in.]) 2 Process Connection G /4 in. ISO 228- A /4 in. NPT ANSI / ASME B.20. B Flange EN092- DN 0 / PN 40 C Flange EN092- DN 5 / PN 40 P Flange EN092- DN 0 / PN 00 Q Flange EN092- DN 5 / PN 00 R Flange /2 in. / Class 50 (only DN 6 [/4 in.]) I Flange 3/4 in. / Class 50 U Flange /2 in. / Class 600 V Flange 3/4 in. / Class 600 W DN 0 acc. to DIN 85 / PN 40 (only DN 6 [/4 in.]) M DN 5 acc. to DIN 85 / PN 40 (only DN 6 [/4 in.]) N Tri-Clamp 25 mm ISO 2852 / PN 6 J Pressure Rating Standard PN 230 (36L) 2 PN 350 (HC22) 3 PN 365 (HC22) 4 PN PN 40 6 Heating / Cooling Without 0 With DN 5 flange heating connection With /2 in. ASME flange heating connection 2 Continued on next page 36

37 Main order number Version number CoriolisMaster mass flowmeter FCM2000 MS2 X X X X X X X X X X X X X Calibration 0.40 % / 0 g/l forward flow A 0.25 % / 0 g/l forward flow B 0.5 % / 0 g/l forward flow C 0.40 % / 0 g/l forward / reverse flow G 0.25 % / 0 g/l forward / reverse flow H 0.5 % / 0 g/l forward / reverse flow I Name plate German G English E Design level (Specified by ABB) X Signal Cable 5 m (6 ft.) ) 0 m (33 ft.) ) 2 25 m (82 ft.) ) 3 50 m (60 ft.) ) 4 ) With plug at Sensor 37

38 Change from one to two columns Mass Flowmeter CoriolisMaster FCM Transmitter 5. Specifications Display The graphic display has 2 lines and features an LED backlight. Both lines are freely configurable to display the mass flowrate, volume flowrate, density, or temperature. Flow count, 7-digit with overflow counter and physical unit for mass or volume. Ex approval FM, ME2O Nonincendive Class I, II, III Division 2, Groups A, B, C, D, F, G/T6 Ta = 60 C, NEMA 4X NS G00320 Fig. 38: FCM2000-ME2 transmitter, field-mount housing Measuring range Freely configurable between 0.0 Q max and Q max N S N S Protection class IP 65/IP 67, NEMA 4X NS G0032 Electrical connections Cable gland M20 x.5 or /2" NPT Max. signal cable length for separate design 50 m (longer lengths available upon request) Fig. 39 Points for inserting the magnet stick Supply power Supply voltage V AC (tolerance -5 % and +0 %), Hz V AC, Hz V DC Ripple: 5 % Power consumption S 25 VA Response time As jump function % (corr. to 5 τ) s Ambient temperature C ( F), optional C ( F) At operation below -20 C (-4 F), the display can no longer be read and the electronic unit should be operated with as few vibrations as possible. Complete operational reliability is achieved at temperatures above -20 C (-4 F). Design Field-mount housing and compact transmitter unit as alloy casting, varnished Mid-section: RAL 702, dark gray Cover: RAL 9002, light gray Paint coat: µm thickness Forward/reverse flow metering Signals are shown on the display by direction arrows and by the optocoupler for ext. signaling. 38

CoriolisMaster FCB330, FCB350, FCH330, FCH350 Coriolis mass flowmeter

CoriolisMaster FCB330, FCB350, FCH330, FCH350 Coriolis mass flowmeter Data Sheet DS/FCB300/FCH300-EN Rev. H CoriolisMaster FCB330, FCB350, FCH330, FCH350 Coriolis mass flowmeter 4-wire compact device For flow measurement of liquids and gases Measurement made easy CoriolisMaster

More information

OPTIMASS 1000 Technical Datasheet

OPTIMASS 1000 Technical Datasheet OPTIMASS 1000 Technical Datasheet Sensor for mass flow First choice for universal applications Best price-performance ratio A wide range of options available with no restrictions The documentation is only

More information

TMU. Coriolis Mass Flow Meter. for liquids and gas

TMU. Coriolis Mass Flow Meter. for liquids and gas Coriolis Mass Flow Meter for liquids and gas measuring monitoring analysing TMU S5 OO Measuring range: 0-60 kg/h 0-2200 t/h water OO Accuracy: ± 0.1% of reading ±zero point stability (from liquids up to

More information

Coriolis Massflowmeter

Coriolis Massflowmeter Coriolis Massflowmeter for liquids and gas measuring monitoring analysing Measuring range: 0-60 kg/h 0-60 000 kg/h water Accuracy: ±0,15 of reading ±zero-point stability pmax: PN40 tmax: -40 +180 C Connection:

More information

Accuracy: ± 0.1 % of reading ±zero point stability (from liquids up to TMU-x040) Material: (316 L) / (316 Ti)/ Hastelloy C-22

Accuracy: ± 0.1 % of reading ±zero point stability (from liquids up to TMU-x040) Material: (316 L) / (316 Ti)/ Hastelloy C-22 Coriolis Massflowmeter for liquids and gas measuring monitoring analysing TMU S5 Measuring range: 0-60 kg/h 0-2200 t/h water Accuracy: ± 0.1 % of reading ±zero point stability (from liquids up to TMU-x040)

More information

Coriolis Mass Flow Meter Model TM

Coriolis Mass Flow Meter Model TM Coriolis Mass Flow Meter for liquids and gas measuring monitoring analysing TM S5 Measuring range: 0-0.8 kg / h 0-65000 kg / h water Accuracy: ± 0.1 of reading ± zero-point stability (liquids) p max :

More information

Coriolis Massflowmeter

Coriolis Massflowmeter Coriolis Massflowmeter for liquids and gas measuring monitoring analysing Measuring range: 0-60 kg/h 0-60 000 kg/h water Accuracy: ±0,15 of reading ±zero-point stability pmax: PN40 tmax: -40 +180 C Connection:

More information

4/111. Overview. Benefits Greater flexibility Wide product program Uniform sensor interface enabling "plug & play" for all transmitters

4/111. Overview. Benefits Greater flexibility Wide product program Uniform sensor interface enabling plug & play for all transmitters Siemens AG 2008 Overview coriolis mass flowmeters are designed for measurement of a variety of liquids and gases. The meter is a multi parameter device offering accurate measurement of mass flow, volume

More information

Flow Measurement SITRANS F M

Flow Measurement SITRANS F M Overview Mode of operation The flow measuring principle is based on Faraday s law of electromagnetic induction according to which the sensor converts the flow into an electrical voltage proportional to

More information

VortexMaster FSV430, FSV450 Vortex flowmeter

VortexMaster FSV430, FSV450 Vortex flowmeter Data Sheet DS/FSV430/450-EN Rev. F VortexMaster FSV430, FSV450 Vortex flowmeter Reliable measurement of liquids, gases and steam in volume, mass or energy units Measurement made easy ABB common look and

More information

Full Metal Variable Area Flowmeter and Counter Model BGF

Full Metal Variable Area Flowmeter and Counter Model BGF Full Metal Variable Area Flowmeter and Counter for horizontal and vertical mounting measuring monitoring analysing BGF OO Measuring range: 10-100... 6000-60000 l/h water 0.3-3.0... 170-1700 m³/h air (20

More information

VortexMaster FSV430, FSV450 Vortex flowmeter

VortexMaster FSV430, FSV450 Vortex flowmeter Data Sheet DS/FSV430/450-EN Rev. D VortexMaster FSV430, FSV450 Vortex flowmeter Two-wire vortex flowmeter for measurement of the flow of gas, vapor and liquid Measurement made easy Intuitive operation

More information

Rosemount Specifications. Product Data Sheet , Rev BA February 2009 PERFORMANCE SPECIFICATIONS

Rosemount Specifications. Product Data Sheet , Rev BA February 2009 PERFORMANCE SPECIFICATIONS Rosemount 2051 Product Data Sheet PERFORMANCE SPECIFICATIONS Specifications For zero based spans, reference conditions, silicone oil fill, SST materials, Coplanar flange () or 1 /2 in. - 14 NPT () process

More information

Dosimass. Technical Information. Coriolis Mass Flow Measuring System For filling applications

Dosimass. Technical Information. Coriolis Mass Flow Measuring System For filling applications Technical Information Coriolis Mass Flow Measuring System For filling applications Application Suitable for use as a mass or volume flowmeter for filling applications. Liquids with the most diverse properties

More information

TME. Coriolis Massflowmeter. for liquids and gases kg/h kg/h water. p max. : PN40 t max : C

TME. Coriolis Massflowmeter. for liquids and gases kg/h kg/h water. p max. : PN40 t max : C Coriolis Massflowmeter for liquids and gases measuring monitoring analysing TME OMeasuring O range: 0-60 kg/h 0-60000 kg/h water O O Accuracy: ±0.15 of reading ± zero-point stability OO p max : PN40 t

More information

ProcessMaster FEP500 Electromagnetic Flowmeter. The process industry's first choice. Maximum measuring accuracy Maximum measuring error: 0.

ProcessMaster FEP500 Electromagnetic Flowmeter. The process industry's first choice. Maximum measuring accuracy Maximum measuring error: 0. Change from one to two columns Data Sheet Rev. B ProcessMaster FEP500 Electromagnetic Flowmeter The process industry's first choice Intuitive operation Softkey-based functionality Easy Set-up function

More information

Digital inductive conductivity transmitter

Digital inductive conductivity transmitter Digital inductive conductivity transmitter Optimal solution for conductivity measurements in difficult fluids (polluted, dirty,...) PEEK/PPA version for CIP applications Large range of process connections

More information

Glass-fibre-reinforced polycarbonate. Dead zone Adaptive or fixed from % 1.5 s adjustable. 20 ms. 60 ms. 60 ms. Approx. 1.

Glass-fibre-reinforced polycarbonate. Dead zone Adaptive or fixed from % 1.5 s adjustable. 20 ms. 60 ms. 60 ms. Approx. 1. General data Mounting On linear actuators On quarter turn actuators ARCA-integrated or to VDI/VDE 3847-1 or IEC 534-6 (NAMUR) Range of stroke: 3... 130 mm Integrated to VDI/VDE 3847-2 or VDI/VDE 3845 Angle

More information

ProcessMaster FEP300 Electromagnetic Flowmeter. The process industry's first choice

ProcessMaster FEP300 Electromagnetic Flowmeter. The process industry's first choice Change from one to two columns Data Sheet Rev. F ProcessMaster FEP300 Electromagnetic Flowmeter The process industry's first choice Intuitive operation Softkey-based functionality Easy Set-up function

More information

Technical Information Memosens CLS82D

Technical Information Memosens CLS82D TI01188C/07/EN/03.16 71318348 Products Solutions Services Technical Information Memosens CLS82D Hygienic conductivity sensors, digital with Memosens technology, cell constant k = 0.57 cm -1 Application

More information

Electromagnetic Flowmeter FXE4000 (COPA-XE/MAG-XE)

Electromagnetic Flowmeter FXE4000 (COPA-XE/MAG-XE) Contents Data Sheet D184S75U2 Electromagnetic Flowmeter FXE4 (COP-XE/MG-XE) The Electromagnetic Flowmeter (EMF) can be used to accurately measure the flowrate of liquids which have an electrical conductivity

More information

Technical Information Condumax CLS21D/CLS21

Technical Information Condumax CLS21D/CLS21 TI00085C/07/EN/14.14 71268310 Products Solutions Services Technical Information Condumax CLS21D/CLS21 Conductivity sensors, analog or digital with Memosens technology Cell constant k = 1.0 cm 1 Application

More information

Condumax CLS15 and CLS15D

Condumax CLS15 and CLS15D Technical Information Condumax CLS15 and CLS15D Conductivity sensors, analog or digital with Memosens technology, Cell constant k = 0.01 cm -1 or k = 0.1 cm -1 Application Measurement in pure and ultrapure

More information

SwirlMaster FSS430, FSS450 Swirl flowmeter

SwirlMaster FSS430, FSS450 Swirl flowmeter Data Sheet DS/FSS430/450-EN Rev. E SwirlMaster FSS430, FSS450 Swirl flowmeter Reliable measurement of liquids, gases and steam in volume, mass or energy units Measurement made easy Compact, space-saving

More information

FV4000, FS4000 Vortex Flowmeter / Swirl Flowmeter. 2-wire Compact Design Digital Signal Processor Converter Technology

FV4000, FS4000 Vortex Flowmeter / Swirl Flowmeter. 2-wire Compact Design Digital Signal Processor Converter Technology Contents Data Sheet Rev. 10 FV4000, FS4000 Vortex Flowmeter / Swirl Flowmeter 2-wire Compact Design Digital Signal Processor Converter Technology For metering liquids, gases and steam FV4000 Vortex flowmeter

More information

Proline Promass 80/83 H, I

Proline Promass 80/83 H, I Technical Information Proline Promass 80/83 H, I Coriolis Mass Flow Measuring System The single-tube system with a fit-and-forget design: easy to clean hygienic does not harm the material being measured

More information

MJK Expert 700 / 800 / 900 / 1100 / 2100 MJK Expert 1400 / 3400

MJK Expert 700 / 800 / 900 / 1100 / 2100 MJK Expert 1400 / 3400 Data Sheet MJK Expert 700 / 800 / 900 / 1100 / 2100 MJK Expert 1400 / 3400 Submersible Hydrostatic s Rugged and versatile We reserve the right to continuously improve our products and make any change in

More information

2-Wire. Level Gauge BM 702

2-Wire. Level Gauge BM 702 KROHNE 09/2001 7.02323.22.00 GR/PRINTO Level Gauge 2-Wire Level-Radar 2-Wire The first and only FMCW Radar Level Gauge with 2-wire technology The non-contact alternative to ageing technologies Maintenance-free

More information

PhD Inline Vortex. Performance Specifications Accuracy. Operating Specifications

PhD Inline Vortex. Performance Specifications Accuracy. Operating Specifications Description The Vortex PhD vortex shedding flowmeter measures process fluid flow by detecting the frequency at which vortices are shed from an obstruction in the process fluid line (the bluff body). A

More information

Level gauges Series LT Level indicator, switch and transmitter for liquids

Level gauges Series LT Level indicator, switch and transmitter for liquids Level gauges Series LT Level indicator, switch and transmitter for liquids Simple construction Resistant under extreme temperature and pressure conditions No risk of leakage Excellent chemical resistance

More information

SITRANS F flowmeters. SITRANS F M System information MAGFLO electromagnetic flowmeters 4/11

SITRANS F flowmeters. SITRANS F M System information MAGFLO electromagnetic flowmeters 4/11 Overview family are designed for measuring the flow of electrically conductive mediums. Benefits SITRANS F flowmeters System information FLO Easier to commission All FLO feature a unique SENSORPROM memory

More information

SATRON VB Pressure Transmitter

SATRON VB Pressure Transmitter SATRON VB pressure transmitter belongs to the series V transmitters. SATRON VB is userfriendly, through the ball valve mounted transmitter which is used for 04 kpa... 03 MPa ranges. The transmitter communicates

More information

RCM DIRECT READING FLOWMETER

RCM DIRECT READING FLOWMETER RCM DIRECT READING FLOWMETER Flow Pressure Level Temperature measurement monitoring control Special Features Compact Design Easy to Install For Horizontal or Vertical Pipes Rugged Construction Accuracy:

More information

Digital flow transmitter for continuous flow measurement

Digital flow transmitter for continuous flow measurement Digital flow transmitter for continuous flow measurement Compact or remote version for DN 06 to 400, PN10 Shows both flow rate and volume (with two totalizers) Automatic-calibration: TEACH-IN Simulation:

More information

ECHOTEL 915 series. 2 Wire, current shift Ultrasonic level switch. Worldwide level and flow solutions DESCRIPTION. Compact and universal level switch

ECHOTEL 915 series. 2 Wire, current shift Ultrasonic level switch. Worldwide level and flow solutions DESCRIPTION. Compact and universal level switch ECHOTEL 915 series 2 Wire, current shift Ultrasonic level switch DESCRIPTION Echotel 915 series ultrasonic level controls are 2 wire (24 V DC) integral units which utilize pulsed wave technology to detect

More information

Proline Promass 80H, 83H

Proline Promass 80H, 83H Technical Information Proline Promass 80H, 83H Coriolis Mass Flow Measuring System The single-tube system with a "fit-and-forget" design: does not harm the material being measured chemical-resistant materials

More information

SALES SERVICE +358 (0)

SALES SERVICE +358 (0) SALES SERVICE +358 (0)17 262 3555 info@econosto.fi ADCATROL ELECTRO-PNEUMATIC POSITIONERS PE 986 (ATEX) DESCRIPTION The ADCATROL PE986 positioner requires an input signal of 4 20 ma for proportional control

More information

Condumax W CLS19. Technical Information. Conductivity sensors Two-electrode sensors with cell constants k = 0.01 cm 1 or k = 0.

Condumax W CLS19. Technical Information. Conductivity sensors Two-electrode sensors with cell constants k = 0.01 cm 1 or k = 0. Technical Information Condumax W CLS9 Conductivity sensors Two-electrode sensors with cell constants k = 0.0 cm or k = 0. cm Application Measurement in pure and ultrapure water: Monitoring ion exchangers

More information

Digital conductivity transmitter

Digital conductivity transmitter Digital conductivity transmitter Compact version with integrated conductivity electrodes Remote version with seperated transmitter for short (15 ft.) or long (1500 ft.) distance Commissioning is easy due

More information

BGF. Full Metal Variable Area Flow Meter and Counter. for horizontal and vertical mounting. Special versions up to 600 bar

BGF. Full Metal Variable Area Flow Meter and Counter. for horizontal and vertical mounting. Special versions up to 600 bar Full Metal Variable rea Flow Meter and Counter for horizontal and vertical mounting measuring monitoring analysing BGF Special versions up to 600 bar S2 Measuring range: 10-100... 4000-40000 l/h water

More information

VortexMaster FSV430, FSV450 SwirlMaster FSS430, FSS450 Vortex and Swirl flowmeter

VortexMaster FSV430, FSV450 SwirlMaster FSS430, FSS450 Vortex and Swirl flowmeter Commissioning and safety instruction CI/FSV/FSS/430/450-EN Rev. G VortexMaster FSV430, FSV450 SwirlMaster FSS430, FSS450 Vortex and Swirl flowmeter Measurement made easy Change from one to two columns

More information

Technical Information Proline Promass 80E, 83E

Technical Information Proline Promass 80E, 83E TI61D/6/EN/15.15 71281945 Products Solutions Services Technical Information Proline Promass 8E, 83E Coriolis flowmeter The flowmeter for minimized cost of ownership with extended transmitter functionality

More information

LST100 Ultrasonic level transmitter for upstream oil and gas

LST100 Ultrasonic level transmitter for upstream oil and gas Data sheet DS/LST100-EN LST100 Ultrasonic level transmitter for upstream oil and gas Accurately track and measure the most expensive consumable on your site chemicals. Measurement made easy Features Keep

More information

Digital Input Output Module for Zone 2 Series 9470/33

Digital Input Output Module for Zone 2 Series 9470/33 www.stahl.de > 16 channels can be adjusted in pairs as digital input or output > Intrinsically safe inputs/outputs Ex ia > For contacts, NAMUR proximity switches and low-power solenoid valves > Up to 8

More information

prosonic T FMU230, FMU231

prosonic T FMU230, FMU231 Technical Information prosonic T FMU230, FMU231 Ultrasonic Level Measurement Compact transmitters for non-contact level measurement of fluids and coarse bulk materials Application The compact transmitters

More information

Liquiphant T FTL20H. Technical Information

Liquiphant T FTL20H. Technical Information Technical Information Liquiphant T FTL0H Level limit switch Level limit switch for liquids in the foodstuff industry, compact design, housing made of corrosion-resistant stainless steel Application The

More information

General Specifications

General Specifications General Specifications YTA70 Temperature Transmitter The YTA70 is the highly accurate temperature transmitter that accepts Thermocouple, RTD, ohms or DC millivolts inputs and converts it to a to 0 ma DC

More information

Process Automation. Sensors and Systems: Level Sensors Level Switches Overfill Prevention Pressure Sensors Temperature Sensors

Process Automation. Sensors and Systems:  Level Sensors Level Switches Overfill Prevention Pressure Sensors Temperature Sensors Process Automation Accurate Level Sensors Level Switches Overfill Prevention Pressure Sensors Temperature Sensors Flexible Sensors and Systems: www.fafnir.com Reliable FAFNIR Sensors and Systems Reliable,

More information

Inductive conductivity measurement mypro CLM 431 / CLD 431 inductive

Inductive conductivity measurement mypro CLM 431 / CLD 431 inductive Technical Information TI 195C/07/en No. 51500053 Inductive conductivity measurement mypro CLM 431 / CLD 431 inductive Two-wire transmitter for inductive measurement of conductivity in Ex and non-ex areas

More information

Level Plus. Magnetostrictive Liquid-Level Sensors with Temposonics Technology. M-Series Model MR Transmitter with Analog Output.

Level Plus. Magnetostrictive Liquid-Level Sensors with Temposonics Technology. M-Series Model MR Transmitter with Analog Output. Level Plus Magnetostrictive Liquid-Level Sensors with Temposonics Technology M-Series Model MR Transmitter with Analog Output Data Sheet SENSORS Document Part Number 550677 Revision K FEATURES 4 to 20

More information

Brooks Models SLAMf50, SLAMf51, SLAMf53 Mass Flow Controllers and Models SLAMf60, SLAMf61, SLAMf63 Mass Flow Meters

Brooks Models SLAMf50, SLAMf51, SLAMf53 Mass Flow Controllers and Models SLAMf60, SLAMf61, SLAMf63 Mass Flow Meters Data Sheet Brooks Industrial Brooks Digital Series Digital MFC's and MFM's Brooks Models SLAMf50, SLAMf51, SLAMf53 Mass Flow Controllers and Models SLAMf60, SLAMf61, SLAMf63 Mass Flow Meters General Features:

More information

Proline Prosonic Flow B 200

Proline Prosonic Flow B 200 Technical Information Proline Prosonic Flow B 200 Ultrasonic flow measuring system The device for accurate, reliable biogas measurement under variable process conditions Application Reliable measurement

More information

Digital Input Output Module 24 V for Ex n Zone 2 Series 9472/35

Digital Input Output Module 24 V for Ex n Zone 2 Series 9472/35 www.stahl.de > 16 channels can be adjusted in pairs as digital inputs or outputs > Suitable for NAMUR proximity switches, 3-wire PNP proximity switches, contacts and solenoid valves (24 V / 0.5 A). > Up

More information

Intrinsically safe pressure transmitter For applications in hazardous areas Models IS-20-S, IS-21-S, IS-20-F, IS-21-F

Intrinsically safe pressure transmitter For applications in hazardous areas Models IS-20-S, IS-21-S, IS-20-F, IS-21-F Replacement product: Model IS-3 Electronic pressure measurement Intrinsically safe pressure transmitter For applications in hazardous areas Models IS-20-S, IS-21-S, IS-20-F, IS-21-F WIKA data sheet PE

More information

Size : Connection End : Min Temperature : Max Temperature : Materials : Cast iron body

Size : Connection End : Min Temperature : Max Temperature : Materials : Cast iron body Size : Connection End : Min Temperature : Max Temperature : DN 50 to 200 Flanged R.F. PN10/16 0 C ( for cold water type ) + 90 C (for hot water type ) Max Pressure : 16 Bars Specifications : Horizontal

More information

DMH. Magnetic Inductive Flowmeter. for Conductive Fluids

DMH. Magnetic Inductive Flowmeter. for Conductive Fluids Magnetic Inductive Flowmeter for Conductive Fluids measuring monitoring analyzing DMH Measuring Range: 0.29...26.4 to 431.6 43,333 GPM Accuracy: ± 0.3% of Reading ± 0.01% x Q max p max : 580 PSI t max

More information

Technologies, Solutions and Applications. Magnetic Level Indication and Bridle Measurements

Technologies, Solutions and Applications. Magnetic Level Indication and Bridle Measurements Technologies, Solutions and Applications Magnetic Level Indication and Bridle Measurements Magnetic Level Indicators and Bridles VEGA is dedicated to offering complete magnetic level indication and engineered

More information

Condumax W CLS15 and CLS15D

Condumax W CLS15 and CLS15D Technical Information Condumax W CLS15 and CLS15D Conductivity sensors, analog or digital with Memosens technology, Cell constant k = 0.01 cm -1 or k = 0.1 cm -1 Application Measurement in pure and ultrapure

More information

Inductive Conductivity Meter ILM

Inductive Conductivity Meter ILM 1 Product Information ILM-2 ILM-3 Inductive Conductivity Meter ILM f o o d Application / Specified Usage Authorizations Inductive measurement of the specific conductivity of liquid media in the range of

More information

ProcessMaster, HygienicMaster FEX300, FEX500

ProcessMaster, HygienicMaster FEX300, FEX500 SM/FEX300/FEX500/FM/CSA-EN ProcessMaster, HygienicMaster FEX300, FEX500 FM / cfm Div. 1, Div. 2 Safety information for electrical equipment for potentially explosive areas in accordance with Factory Mutual

More information

Pressure transmitter For general industrial applications Model A-10

Pressure transmitter For general industrial applications Model A-10 Electronic pressure measurement Pressure transmitter For general industrial applications Model A-10 WIKA data sheet PE 81.60 for further approvals see page 9 Applications Machine building Shipbuilding

More information

Level Switch Catalogue

Level Switch Catalogue Level Switch Catalogue 2 www.besta.ch 3 Table of contents Worldwide in use Trimod Besta Level Switches 4 Worldwide approved Approvals 5 Quality for your safety Modular flexibility Mounting combinations

More information

AT200 External Mount Magnetostrictive Level Transmitter

AT200 External Mount Magnetostrictive Level Transmitter Data sheet DS/AT200-EN Rev. W AT200 External Mount Magnetostrictive Level Transmitter High accuracy liquid level and interface level detection K-TEK Level Products Measurement made easy Features Certified

More information

SITRANS F flowmeters. SITRANS F R Rotary-piston meters Accessory modules 4/431. Overview. Siemens AG 2009

SITRANS F flowmeters. SITRANS F R Rotary-piston meters Accessory modules 4/431. Overview. Siemens AG 2009 Siemens AG 2009 SITRANS F flowmeters Rotary-piston meters Accessory modules Accessory modules For quantity measurements in conjunction with electromechanical and electronic pulse counters As transmitter

More information

Intrinsically safe pressure transmitter For applications in hazardous areas Models IS-20-S, IS-21-S, IS-20-F, IS-21-F

Intrinsically safe pressure transmitter For applications in hazardous areas Models IS-20-S, IS-21-S, IS-20-F, IS-21-F Replacement product: Model IS-3 Electronic pressure measurement Intrinsically safe pressure transmitter For applications in hazardous areas Models IS-20-S, IS-21-S, IS-20-F, IS-21-F WIKA data sheet PE

More information

ph or ORP Transmitter

ph or ORP Transmitter ph or ORP Transmitter Programmable outputs: two transistor and single or dual analog 4-20 ma (Process + Temp) Removable backlighted display Universal process connection Compatible with 120 mm ph/ ORP probes

More information

Resistance Thermometers Model Series TR7X0, Sheathed Design

Resistance Thermometers Model Series TR7X0, Sheathed Design Electrical Temperature Measurement Resistance Thermometers Model Series TR7X0, Sheathed Design WIKA Data Sheet TE 60.40 Applications T Suitable for all industrial and laboratory applications Special Features

More information

PTG series Smart Pressure Transmitter

PTG series Smart Pressure Transmitter No. SS2-PTG300-0100 PTG series Smart Pressure Transmitter Model PTG71 / PTG72 OVERVIEW The Smart Pressure Transmitter model PTG is a high- performance, highly reliable gauge pressure transmitter. Based

More information

SVM 3000 PLUS Smart Vortex Flowmeter Specification and Application Data. 37-VM Rev /98

SVM 3000 PLUS Smart Vortex Flowmeter Specification and Application Data. 37-VM Rev /98 SVM 3000 PLUS Smart Vortex Flowmeter Specification and Application Data 37VM2901 Rev. 2.1 10/98 Copyright, Notices, and Trademarks Printed in U.S.A. Copyright 1998 by Honeywell Inc. Revision 2.1 10/98

More information

Vortex Meter VTX2. P e

Vortex Meter VTX2. P e VTX2 P 408.003e Contents Vortex meter VTX2, the new generation Page 3 Principle of measurement Page 3 Applications Page 4 Design Page 5 Table of measurement ranges Page 5 Specifications Page 6 Vortex meter

More information

Flow Measurement SITRANS F US Inline

Flow Measurement SITRANS F US Inline Flowmeter SITRANS FUS80 standard Overview Design The -path design of SITRANS FUS80 ensures maximum accuracy under short inlet conditions. The flowmeter consists of a flow sensor pipe, 4 transducers/transducer

More information

ph or ORP Transmitter

ph or ORP Transmitter ph or ORP Transmitter Programmable outputs: two transistor and single or dual analog 4-20 ma (Process + Temp) Removable backlighted display Universal process connection Compatible with 120 mm ph/ ORP probes

More information

Operating Instructions for Level Switch Tuning Fork Principal. Model: NWS

Operating Instructions for Level Switch Tuning Fork Principal. Model: NWS Operating Instructions for Level Switch Tuning Fork Principal Model: NWS 1. Contents 1. Contents... 2 2. Note... 3 3. Instrument Inspection... 3 4. Regulation Use... 3 5. Operating Principle... 4 6. Use

More information

Pressure and level transmitter PASCAL CV LEVEL,

Pressure and level transmitter PASCAL CV LEVEL, Pressure and level transmitter PASCAL CV LEVEL, temperature compensation by LTC-technology,Type series CV311. L Features Modular pressure and level transmitter temperature compensation up to 0.1 mbar /

More information

MFC 400 Technical Datasheet

MFC 400 Technical Datasheet MFC 400 Technical Datasheet Signal converter for mass flowmeters High performance signal converter for all applications Stable in multi-phase applications due to synthesised drive High developed diagnostic

More information

A New Generation Of Pressure Transmitters -AII V5. ECNO : 610e

A New Generation Of Pressure Transmitters -AII V5. ECNO : 610e A New Generation Of Pressure Transmitters -AII V5 ECNO : 610e A New Transmitter at the edge of Technology As a leader in the field of measurement, Fuji Electric has an installed base of more than 1 000

More information

Clamp-on ultrasonic flowmeters have six product families: max. 2% solids

Clamp-on ultrasonic flowmeters have six product families: max. 2% solids System info and selection guide Ultrasonic flowmeters Overview Siemens offers two types of ultrasonic flowmeters, wetted flowmeters and clamp-on flowmeters. This offers the end user the maximum flexibility

More information

SITRANS P measuring instruments for pressure

SITRANS P measuring instruments for pressure Overview Siemens AG 009 SITRANS P300 and DS III series with PMC connection Technical description Benefits High quality and long life High reliability even under etreme chemical and mechanical loads, e.g.

More information

SMARTPAT PH 1590 Technical Datasheet

SMARTPAT PH 1590 Technical Datasheet SMARTPAT PH 1590 Technical Datasheet Digital ph sensor for the water industry 2-wire loop powered sensor with integrated transmitter technology Special sensor design for all-purpose applications Low maintenance

More information

Soliphant T FTM20, FTM21

Soliphant T FTM20, FTM21 Technical Information Soliphant T FTM20, FTM21 Level limit switch Robust vibration limit switch for bulk solids, also for dust incendive hazardous areas Application Soliphant T is a robust level limit

More information

Pharma Temperature Sensor G3/8"

Pharma Temperature Sensor G3/8 1 Product Information TFP-58P, -68P, -168P, -188P Pharma Temperature Sensor G3/8" P H A R M A Application / Specified Usage Aseptic temperature measurement, inline, high precise and fast without product

More information

Ultrasonic Liquid Level Transmitters

Ultrasonic Liquid Level Transmitters Product Data Sheet Ultrasonic Liquid Level Transmitters Non-contacting measurement with no moving parts Integral LCD and push-buttons as standard for on-site programming Continuous measurement of level

More information

Expert 1400 / Expert 3400 Submersible Hydrostatic Level Transmitters

Expert 1400 / Expert 3400 Submersible Hydrostatic Level Transmitters Expert 1400 / Expert 3400 Submersible Hydrostatic Level Transmitters ll 2G EEx ia llc T6 As our products are continuously improved, we reserve the right to make any change in the stated specifications

More information

Single-Channel Safety Barriers Series 9001

Single-Channel Safety Barriers Series 9001 Single-Channel Safety Barriers Series 9001 > Broad product range for all standard applications in the world of automation > Flexible and space saving single and dual channel versions available > Time saving

More information

Advancements in Clamp-on Ultrasonic Flow Measurements Biosolids Workshop December 1 st 2016

Advancements in Clamp-on Ultrasonic Flow Measurements Biosolids Workshop December 1 st 2016 Advancements in Clamp-on Ultrasonic Flow Measurements 2016 Biosolids Workshop December 1 st 2016 Market Leader in Clamp-On Ultrasonic Flowmeters with >50,000 instruments sold Background Information Extraordinary

More information

Ceramax CPS341D. Technical Information

Ceramax CPS341D. Technical Information Technical Information Ceramax CPS341D Electrode with ph sensitive enamel and digital Memosens technology Meets highest demands of measuring accuracy, pressure, temperature, sterility and durability Application

More information

SITRANS LR 300: High Performance Radar for Level Measurement

SITRANS LR 300: High Performance Radar for Level Measurement SITRANS LR 300: High Performance Radar for Level Measurement Reliable Measurement In Extreme Conditions SITRANS LR 300 delivers high performance level measurement at an affordable price for the chemical,

More information

OEM pressure transmitter For mobile working machines Model MH-3

OEM pressure transmitter For mobile working machines Model MH-3 Electronic pressure measurement OEM pressure transmitter For mobile working machines Model MH-3 WIKA Data sheet PE 81.59 Applications Load monitoring Load moment limitation Hydraulic drive control Special

More information

AT9000 Advanced Transmitter Gauge Pressure Transmitters In-line model

AT9000 Advanced Transmitter Gauge Pressure Transmitters In-line model No. SS2-GTX00G-0600 AT9000 Advanced Transmitter Gauge Pressure Transmitters In-line model OVERVIEW AT9000 Advanced Transmitter is a microprocessor-based smart transmitter that features high performance

More information

Technical Information Indumax CLS50D/CLS50

Technical Information Indumax CLS50D/CLS50 TI00182C/07/EN/16.15 71280313 Products Solutions Services Technical Information Indumax CLS50D/CLS50 Inductive conductivity sensor for standard, Ex and high-temperature applications Digital sensor with

More information

BATCHFLUX 5500 C Handbook

BATCHFLUX 5500 C Handbook BATCHFLUX 5500 C Handbook Electromagnetic flowmeter for volumetric filling machines KROHNE : IMPRINT ::::::::::::::::::::::::::::::::::::::: All rights reserved. It is prohibited to reproduce this documentation,

More information

TF 02 / TF 02-Ex. Head mounted temperature transmitters, FOUNDATION Fieldbus (H1), Pt 100 (RTD), thermocouples, 1 or 2 independent channels

TF 02 / TF 02-Ex. Head mounted temperature transmitters, FOUNDATION Fieldbus (H1), Pt 100 (RTD), thermocouples, 1 or 2 independent channels TF 0 / TF 0-Ex Head mounted temperature transmitters, FOUNDATION Fieldbus (H), Pt 00 (RTD), thermocouples, or independent channels 0/-8.5 EN Input Resistance thermometer (,, wire circuit) Thermocouples

More information

Isolating Repeater Input Series 9163

Isolating Repeater Input Series 9163 > For 4-wire HART transmitters and voltage sources > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > For use up to SIL 2 (IEC 61508) > High accuracy www.stahl.de

More information

Conductive conductivity measurement mypro CLM 431 / CLD 431 conductive

Conductive conductivity measurement mypro CLM 431 / CLD 431 conductive Technical Information TI 202C/07/en No. 51500563 Conductive conductivity measurement mypro CLM 431 / CLD 431 conductive Two-wire transmitter for conductive measurement of conductivity and specific resistance

More information

VortexMaster FSV430, FSV450 SwirlMaster FSS430, FSS450 Vortex and Swirl flowmeter

VortexMaster FSV430, FSV450 SwirlMaster FSS430, FSS450 Vortex and Swirl flowmeter Operating Instruction OI/FSV/FSS/430/450-EN Rev. D VortexMaster FSV430, FSV450 SwirlMaster FSS430, FSS450 Vortex and Swirl flowmeter Measurement made easy Change from one to two columns Short product description

More information

Fieldbus Isolating Repeater Series 9185/11

Fieldbus Isolating Repeater Series 9185/11 www.stahl.de > For operation of the intrinsically safe Profibus DP (RS-485 IS to PNO standard) > Intrinsically safe fieldbus RS-422, RS-485 [Ex ib] IIC > Galvanic isolation between RS-422 / RS-485, RS-232,

More information

SolidFlow 2.0. Solid mass flow measurement. Product Information. SWR engineering Messtechnik GmbH enveatm a trademark of Environnement S.

SolidFlow 2.0. Solid mass flow measurement. Product Information. SWR engineering Messtechnik GmbH enveatm a trademark of Environnement S. EN SolidFlow.0 Product Information Solid mass flow measurement SWR engineering Messtechnik GmbH enveatm a trademark of Environnement S.A Group Use SolidFlow.0 has been specially developed for measuring

More information

Technical Information Proline Promag L 400

Technical Information Proline Promag L 400 TI01045D/06/EN/06.16 71314353 Products Solutions Services Technical Information Proline Promag L 400 Electromagnetic flowmeter The flowmeter with an integrated web server and weight-optimized sensor Application

More information

Proline Prowirl 72F, 72W, 73F, 73W

Proline Prowirl 72F, 72W, 73F, 73W Technical Information Proline Prowirl 72F, 72W, 73F, 73W Vortex Flow Measuring System Reliable flow measurement of gas, steam and liquids Application For the universal measurement of the volume flow of

More information