Application of GridEye for Grid Analytics
|
|
- Juliet Henderson
- 5 years ago
- Views:
Transcription
1 Application of GridEye for Grid Analytics This document provides a use case for the application of GridEye for the monitoring of low voltage grids. GridEye modules primarily measure the electrical quantities and process the measurements using the distributed intelligence on every module. Thus, only useful data for the system operators and/or endcustomers are communicated and stored. In this way, the high communication costs and big data issues are avoided. GridEye monitoring is an efficient and scalable approach for providing observability in low voltage grids and ensuring its secure operation. This functionality of GridEye is not only useful for the grids with PV production, but it is also a valuable tool for understanding the current and voltage levels, and balanced operation of three phases systems. Various analysis using the temporal profiles and statistics are accessible through the GridEye interfaces. The transmitted data is used for monitoring and visualization purposes through a dedicated interface. Author: Omid Alizadeh-Mousavi Date: March 8th, 2017 DEPsys SA 1
2 1. INTRODUCTION OF THE USE CASE AND GRIDEYE INSTALLATION The grid topology of the use case and the installations of GridEye modules are shown in Figure 1. The electricity consumptions in the grid are mainly residential and agricultural. Moreover, there are PV installations at three locations shown by G1, G2 and G3. In this use case, the GridEye modules are used for the monitoring of electric quantities. It is worth noting that the monitoring request can be from system operators and/or from end-customers. In this use case, the local distribution system operator is interested in monitoring and optimal control of the shown grid as well as the monitoring and optimization of the energy consumptions and productions of a private end-customer. For this private customer in node 104, shown within the dashed line, an additional GridEye module is installed. The installations of GridEye modules at the MV/LV transformer as well as on distribution cabinets are demonstrated in Figure ANALYSIS OF MONITORING DATA The GridEye measurements are used to analyze the voltages, currents, power flows, and loadings in the transformer and the low voltage grid. The temporal profiles and statistics of the measurements are used for the detailed analysis of the devices Transformer daily loading The profiles and distributions of the transformer loading for a winter and a summer day are shown in Figure 3. The distribution of transformer loading Figure 3-a and Figure 3-b) illustrate the number of hours that the transformer is operated at each loading level. The temporal profile of the active, reactive, and apparent powers of the transformer are illustrated in Figure 3-c and Figure 3-d). During the winter day, the transformer is loaded between 30% and 110% of its nominal capacity (i.e. 250 kva). The observed overloading is for a short period of time and it is due to consumption peak around 19:00 as illustrated in Figure 3-c. Therefore, the transformer overloading can be an issue for the system operator, specifically if additional consumption is planned to be added to the transformer. Figure 1. The use case grid and the installations of GridEye modules. During the summer day, the transformer is loaded between 0% and 80% of its nominal capacity which is lower than the winter loading. The highest loading level in the summer day is due to PV production as a) Distribution cabinet c) MV/LV transformer b) Rogowski coils for the current measurements at transformer LV d) PV power plant Figure 2. Installation of GridEye modules 2
3 Winter day Summer day a) distribution of transformer loading b) distribution of transformer loading c) temporal profile of transformer powers d) temporal profile of transformer powers Figure 3. Distribution and temporal profile of transformer loading for a winter day (a and c) and a summer day (b and d). Sunny day Cloudy day a) temporal profile of voltage temporal profile of voltage b) c) temporal profile of current d) temporal profile of current Figure 4. Temporal profile of transformer s voltage and current for a sunny day (a and c) and a cloudy day (b and d). 3
4 indicated in Figure 3-d. Therefore, the production of the existing PV installations does not cause transformer overloading. However, the impact of additional PV installations on the transformer loading should be taken into consideration Transformer daily voltage and current variations The temporal profile of the transformer s voltage and current for a sunny and a cloudy day are shown in Figure 4 and the dynamics of voltage and current variations are analyzed. The period with negative currents, indicated in Figure 4-c and Figure 4-d, corresponds to the instances where production is higher than consumption. It is worth noting that for these two days, the maximum current production does not deviate from the nominal current of the transformer (i.e. 362 A). During the days with PV production, in general, the voltage profile follows the current profile. In other words, the increase of PV power injection (i.e. larger negative current) results in the increase of the voltage level. During the sunny day, the highest voltage level (i.e. 246V) is observed around 13:30 that corresponds to the instance with the highest PV production. Furthermore, the observed voltage steps at 6:00 and 9:00, specified in Figure 4-a, are due to the change of a tap-changer in MV grid, since there are no current variations at these instances. During the cloudy day, the large voltage variations are observed because of the large variations of the PVs productions. The current variation during the day reaches 470 A (from 130 A consumption to 340 A production) and the largest current step is approximately 300 A within a 2- minutes period. Similarly, the voltage variation during the day reaches 10 V and the largest voltage step is 4 V over 2- minutes. Here, the utilized measurement data has 2- minutes time interval. In this case, measurements with lower time intervals are needed to capture the voltage variations using shorter time steps. It also emphasizes the importance of power quality measurements October 2016) is shown in Figure 5, Figure 6, and Figure 7, respectively. In these figures, every data point represents the daily average of the electrical quantities. The transformer s loading, shown in Figure 5, is lower during the summer months and the higher loading levels occur during the winter months. The higher PV productions during the summer months results in the negative power flows from LV to MV grid for almost 4-5 months. The current profiles, shown in Figure 6, follow the active power profile and have negative values during the summer months. It is worth noting that the neutral current does not vary in different months that the level of balanced operation of the grid does not change over the seasons. The voltage profiles, shown in Figure 7, follow the PV production and have higher values during the summer months. Figure 5. Daily average profile of transformer active, reactive, and apparent powers for 18 months. Figure 6. Daily average profile of transformer currents for 18 months Yearly statistics Transformer power, current, and voltage average daily dynamics The temporal profile of transformer s powers, currents, and voltages for 18 months of measurements (April Figure 7. Daily average profile of transformer voltages for 18 months. 4
5 Transformer current and voltage weekly dynamics The temporal profile of transformer s currents and voltages for 18 months of measurements (April 2015 October 2016) is shown in Figure 8 and Figure 9, respectively. In these figures, average, minimum, and maximum values of the currents and voltages for every week is represented by a data point. In Figure 8, it is observed that the current variation is higher during the summer weeks due to higher PV production. In the consumption side, the maximum current exceeds the nominal current in a winter week. In the production side, the maximum current reaches the values close to the nominal current. It is also observed that the neutral current and the imbalance between three phases is low. In Figure 9, it is observed that the voltages in winter are lower than in summer because of the relatively weak transformer (i.e. 250 kva) Distribution of transformer loading The distribution of the transformer apparent power for one year is shown in Figure 10-top. It demonstrates the number of hours that the transformer is operated at every loading level. Although the transformer is mostly operated in average loading levels, the loadings between 90% and 110% are observed for almost 5 hours during the year. Therefore, the risk of transformer overloading should be considered in its operation and specifically in planning studies. The distribution of the transformer active power for the same period of time is shown in Figure 10-middle. The active power distribution contains the direction of power flow in addition to the loading level. It is observed that the transformer is operated more on the consumption side (i.e. positive power flow) and that a 100% loading level is reached for less than an hour. Thus, the impact of the increase of the LV grid consumption on the transformer loading level should be considered. Although the transformer is operated for less number of hours on the production side (i.e. negative power flow), it is interesting to mention that 90% loading on the production side is experienced for almost two hours. This observation emphasizes that additional PV installations in the LV grid can result in overloading on the production side. The distribution of the transformer reactive power for the same period of time is shown in Figure 10-bottom. It is observed that the transformer s reactive power is less than 20% of its nominal capacity for more than 98% of the time period. The low reactive power loading of the transformer indicates that in the LV grid the active power losses is low and the power factor is high. This information is important for the system operator and the end-customer specifically if the endconsumers are charged for the reactive power. Moreover, the transformer is operated for 99% and 1% of the time in the inductive and capacitive loadings that respectively correspond to the positive and negative reactive power flows. In the inductive side, the transformer is loaded between 20% and 50% of the nominal capacity for 140 hours. Figure 8. Weekly mean, minimum, and maximum profiles of transformer currents for 18 months. This observation justifies the need for the optimal voltage control in this use case. From a planning point of view, further PV installations at these nodes, without voltage control, will definitely result in overvoltage issues. Figure 9. Weekly mean, minimum, and maximumprofiles of transformer voltages for 18 months. 5
6 Figure 10. Distribution of transformer loading for one year, apparent, active, and reactive powers Distribution of voltages and currents throughout the grid The distribution of the three phase voltages at the transformer and several grid nodes are shown in Figure 11. The voltage distributions demonstrate the number of hours that each node is operated at every voltage level. The first observation is that the voltages across all nodes are within the acceptable limits (230 ± 10%) during the whole year. Nevertheless, the voltages at node 101 and 102 reach to the maximum allowed voltage level (i.e. 253V) which is due to the PV installations at these two nodes. The high voltage levels at these nodes require paying particular attention to ensuring the secure operation of the grid. Figure 11.Three phase voltage distributions at several nodes of the gridover one year. 6
7 loading reaches to 20%. The cable is mostly used on the consumption side. There is small PV production at node 102 that results in a small negative loading. Although from the loading perspective, this cable has a large margin and additional PV installations can be considered at node 102, the additional PV installations can cause overvoltage issues. Therefore, a holistic planning analysis should simultaneously consider both the voltage and current aspects. Figure 12.Three phase and neutral current distributions at the transformer and several cables of the grid over one year. The distribution of three phases and neutral currents for the transformer and several cables over one year are shown in Figure 12. The current distributions show the number of hours that the transformer or the cables are operated at every loading level while the direction of current flow is preserved (i.e. positive for consumption and negative for production). The loading level of the transformer and the cables are determined by dividing the value of currents by their nominal current values. The transformer is mostly used on the consumption side and the maximum consumption current goes above 100% of its nominal current. Although the transformer is operated for less period on the production side, its maximum current on the production side reaches up to 90% because of PV productions. The overloading of the transformer should be studied in the case of additional consumption and PV installations. The cable is often used on the consumption side. However, the highest loading level (i.e. -52%) is reached on the production side which is because of the PV installations at node 101 and 102. The cable is mostly used on the consumption side. The maximum loading levels on the production and consumption sides are observed at -25% and 48%, respectively. The production part is due to the PV installations at node 104 and the consumption part includes the loads at node 104, 105, and 106. The cable and the cable are only operated on the consumption side because there are no PV productions at nodes 103 and 106. These two cables are only slightly loaded as their maximum Furthermore, the voltage and current distributions provide important information about the balanced operation of the three phases. This information can be used for improving the operation and planning of the distribution grids. In the case of unbalanced loading of three phases, the distribution of the voltages and currents of the phases are shifted to left/right with respect to each other and the distribution of the neutral current shows higher values. In this use case, it is observed that the voltages and currents of three phases have similar distributions and the neutral currents are not significant. These observations denote a balanced operation of the three phases. For more information please contact: DEPsys SA Route du Verney 20B 1070 Puidoux, Switzerland Phone : Omid Alizadeh-Mousavi R&D Director omid.mousavi@depsys.ch Antony Pinto Electrical Engineer antony.pinto@depsys.ch Joël Jaton Chief Technology Officer joel.jaton@depsys.ch 7
NEW APPROACH TO REGULATE LOW VOLTAGE DISTRIBUTION NETWORK
NEW APPROACH TO REGULATE LOW VOLTAGE DISTRIBUTION NETWORK Yves CHOLLOT Philippe DESCHAMPS Arthur JOURDAN SCHNEIDER ELECTRIC France SCHNEIDER ELECTRIC France SCHNEIDER ELECTRIC France yves.chollot@schneider-electric.com
More informationEN50160 Report: Station 28 Puidoux Accepted Week 12 20/03/ /03/2017
EN50160 Report: Station 28 Puidoux Accepted 2017 Week 12 20/03/2017 27/03/2017 Date : 28 march 2017 INTRODUCTION This report covers the time period between Monday, March 20, 2017, 12:00:00 to Monday, March
More informationUNBALANCED CURRENT BASED TARRIF
UNBALANCED CURRENT BASED TARRIF Hossein ARGHAVANI Tehran Electricity Distribution (TBTB) Co.-Iran hosein.argavani@gmail.com ABSTRACT The voltage ¤t unbalance are serious power quality problems with
More informationHVDC CAPACITOR COMMUTATED CONVERTERS IN WEAK NETWORKS GUNNAR PERSSON, VICTOR F LESCALE, ALF PERSSON ABB AB, HVDC SWEDEN
HVDC CAPACITOR COMMUTATED CONVERTERS IN WEAK NETWORKS GUNNAR PERSSON, VICTOR F LESCALE, ALF PERSSON ABB AB, HVDC SWEDEN Summary Capacitor Commutated Converters (CCC) were introduced to the HVDC market
More informationPOWER QUALITY IMPACTS AND MITIGATION OF DISTRIBUTED SOLAR POWER
POWER QUALITY IMPACTS AND MITIGATION OF DISTRIBUTED SOLAR POWER Presented by Ric Austria, Principal at Pterra Consulting to the IEEE San Francisco Chapter Feb 17, 2016 California Public Utilities Commission,
More informationRecommendations for Harmonic and Power Measurements in Electrical Networks
Recommendations for Harmonic and Power Measurements in Electrical Networks Analysis implementation and reporting requirements regarding grid power quality and equipment loads Power Capacitor Division Recommendations
More informationTechnical Information Requirement for MV Transformers and Transformer for Internal Power Supply for SUNNY CENTRAL
Technical Information Requirement for MV Transformers and Transformer for Internal Power Supply for SUNNY CENTRAL ENGLISH SC_Trafo-TI-en-66 Version 6.6 Table of Contents SMA Solar Technology AG Table of
More informationEmbedded Generation Connection Application Form
Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed
More informationLV DC DISTRIBUTION NETWORK WITH DISTRIBUTED ENERGY RESOURCES: ANALYSIS OF POSSIBLE STRUCTURES
LV DC DISTRIBUTION NETWORK WITH DISTRIBUTED ENERGY RESOURCES: ANALYSIS OF POSSIBLE STRUCTURES Alessandro AGUSTONI Enrico BORIOLI Morris BRENNA * Giuseppe SIMIOLI Enrico TIRONI * Giovanni UBEZIO * Politecnico
More informationVOLTAGE CONTROL STRATEGY IN WEAK DISTRIBUTION NETWORKS WITH HYBRIDS GENERATION SYSTEMS
VOLTAGE CONTROL STRATEGY IN WEAK DISTRIBUTION NETWORKS WITH HYBRIDS GENERATION SYSTEMS Marcelo CASSIN Empresa Provincial de la Energía de Santa Fe Argentina mcassin@epe.santafe.gov.ar ABSTRACT In radial
More informationEmbedded Generation Connection Application Form
Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed
More informationDISTRIBUTED MODEL-FREE CONTROL OF PHOTOVOLTAIC UNITS FOR MITIGATING OVERVOLTAGES IN LOW-VOLTAGE NETWORKS
DISTRIBUTED MODEL-FREE CONTROL OF PHOTOVOLTAIC UNITS FOR MITIGATING OVERVOLTAGES IN LOW-VOLTAGE NETWORKS Petros Aristidou Frédéric Olivier Maria Emilia Hervas University of Liège, Belgium, University of
More informationReactive power control strategies for UNIFLEX-PM Converter
Reactive power control strategies for UNIFLEX-PM Converter S. Pipolo, S. Bifaretti, V. Bonaiuto Dept. of Industrial Engineering University of Rome Tor Vergata Rome, Italy Abstract- The paper presents various
More informationTechnical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks
2014 Technical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks This document specifies the technical requirement for connecting sspv to the low voltage distribution
More informationTechnical Information Requirement for MV Transformers and Transformer for Internal Power Supply for SUNNY CENTRAL
Technical Information Requirement for MV Transformers and Transformer for Internal Power Supply for SUNNY CENTRAL ENGLISH SC_Trafo-TI-en-65 Version 6.5 Table of Contents SMA Solar Technology AG Table of
More informationImpact Assessment Generator Form
Impact Assessment Generator Form This connection impact assessment form provides information for the Connection Assessment and Connection Cost Estimate. Date: (dd/mm/yyyy) Consultant/Developer Name: Project
More informationModeling and Validation of an Unbalanced LV Network Using Smart Meter and SCADA Inputs
Modeling and Validation of an Unbalanced LV Network Using Smart Meter and SCADA Inputs Derek C. Jayasuriya, Max Rankin, Terry Jones SP AusNet Melbourne, Australia Julian de Hoog, Doreen Thomas, Iven Mareels
More informationASSESSMENT OF HARMONIC DISTORTION LEVELS IN LV NETWORKS WITH INCREASING PENETRATION LEVELS OF INVERTER CONNECTED EMBEDDED GENERATION
ASSESSMENT OF HARMONIC DISTORTION LEVELS IN LV NETWORKS WITH INCREASING PENETRATION LEVELS OF INVERTER CONNECTED EMBEDDED GENERATION Adam DYŚKO, Graeme M. BRT, James R. McDONALD niversity of Strathclyde
More informationDC utilization of existing LVAC distribution cables
DC utilization of existing LVAC distribution cables D. Antoniou, A. Tzimas and S. M. Rowland The University of Manchester School of Electrical and Electronic Engineering M13 9PL, UK Abstract Low Voltage
More informationEmbedded Generation Connection Application Form
Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed
More informationCHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS
84 CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS 4.1 INTRODUCTION Now a days, the growth of digital economy implies a widespread use of electronic equipment not only in the industrial
More informationCHAPTER 3 DEVELOPMENT OF DISTRIBUTION SIMULATION PACKAGE FOR LOAD ANALYSIS OF LV NETWORK
78 CHAPTER 3 DEVELOPMENT OF DISTRIBUTION SIMULATION PACKAGE FOR LOAD ANALYSIS OF LV NETWORK 3.1 INTRODUCTION Distribution loads vary in response to temperature, time of the day, day of the week and other
More informationHarmonic Planning Levels for Australian Distribution Systems
Abstract Harmonic Planning Levels for Australian Distribution Systems V.J. Gosbell 1, V.W. Smith 1, D. Robinson 1 and W. Miller 2 1 Integral Energy Power Quality Centre, University of Wollongong 2 Standards
More informationDietrich Bonmann, ABB Monselice Transformer Days, May 5, 2010 Optimized AC transmission solutions with phase-shifting transformers and shunt reactors
Dietrich Bonmann, ABB Monselice Transformer Days, May 5, 2010 Optimized AC transmission solutions with phase-shifting transformers and shunt reactors May 11, 2010 Slide 1 Why phase-shifting transformers
More informationLandis+Gyr S650 Smart Grid Terminal. a smart grid innovation
Landis+Gyr S650 Smart Grid Terminal a smart grid innovation 2 Emerging challenges in the distribution system. Utilities, both DNOs and DSOs, are facing growing challenges due to quick changes happening
More informationVOLTAGE QUALITY PROVISION IN LOW VOLTAGE NETWORKS WITH HIGH PENETRATION OF RENEWABLE PRODUCTION
VOLTAGE QUALITY PROVISION IN LOW VOLTAGE NETWORKS WITH HIGH PENETRATION OF RENEWABLE PRODUCTION ABSTRACT Anže VILMAN Elektro Gorenjska, d.d. Slovenia anze.vilman@elektro-gorenjska.si Distribution system
More informationINVESTIGATING THE BENEFITS OF MESHING REAL UK LV NETWORKS
INVESTIGATING THE BENEFITS OF MESHING REAL UK LV NETWORKS Muhammed S. AYDIN Alejandro NAVARRO Espinosa Luis F. OCHOA The University of Manchester UK The University of Manchester UK The University of Manchester
More informationVOLTAGE CONTROL IN MEDIUM VOLTAGE LINES WITH HIGH PENETRATION OF DISTRIBUTED GENERATION
21, rue d Artois, F-75008 PARIS CIGRE US National Committee http: //www.cigre.org 2013 Grid of the Future Symposium VOLTAGE CONTROL IN MEDIUM VOLTAGE LINES WITH HIGH PENETRATION OF DISTRIBUTED GENERATION
More informationSouthern Company Power Quality Policy
Southern Company Power Quality Policy Alabama Power Georgia Power Gulf Power Mississippi Power i Table of Contents: Southern Company Power Quality Policy SCOPE AND PURPOSE... 1 DEFINITIONS... 2 I. HARMONICS...
More informationPower Flow Redistribution in Croatian Power System Network using Phase- Shifting Transformer
Power Flow Redistribution in Croatian Power System Network using Phase- Shifting Transformer Ivica Pavić Faculty of Electrical Engineering and Computing Zagreb, CROATIA Sejid Tešnjak Faculty of Electrical
More informationSmart Energy & Power Quality Solutions. UMG 96RM Universal measurement instrument (EN 50160, IEEE 519, ITIC)
Smart Energy & Power Quality Solutions UMG 96RM Universal measurement instrument (EN 50160, IEEE 519, ITIC) UMG 96RM UMG 96RM Universal measurement instrument Unrivalled in its class The UMG 96RM is a
More informationPower Quality in High Density Residential Distribution Grids
Power Quality in High Density Residential Distribution Grids Gustav R. Krüger, Raj M. Naidoo Abstract Research in the field of power quality challenges in distribution grids is gaining a strong foothold.
More informationTripping of circuit breakers in PV installations due to zero sequence field impedance
Tripping of circuit breakers in PV installations due to zero sequence field impedance B. Verhelst 1,2, C. Debruyne 1,2, J. Desmet 1,2 1 dept. Electrical Engineering - Lemcko HoWest Kortrijk, Belgium bart.verhelst@howest.be
More informationGRIDBOX AN OPEN PLATFORM FOR MONITORING AND ACTIVE CONTROL OF DISTRIBUTION GRIDS
GRIDBOX AN OPEN PLATFORM FOR MONITORING AND ACTIVE CONTROL OF DISTRIBUTION GRIDS Marco MANGANI Dr. Florian KIENZLE Marc EISENREICH ewz Switzerland ewz Switzerland BKW Switzerland marco.mangani@ewz.ch florian.kienzle@ewz.ch
More informationEuropean Utility Week 2014 Amsterdam. Case Study Power Network 2030 Stettlen
European Utility Week 2014 Amsterdam Case Study Power Network 2030 Stettlen Oliver Krone Head of Smart Grid Engineering BKW Energie AG - Switzerland 5 November 2014 Agenda BKW Group and Activities Motivation
More informationVoltage Level Management of Low Voltage Radial Distribution Networks with High Penetration of Rooftop PV Systems
Voltage Level Management of Low Voltage Radial Distribution Networks with High Penetration of Rooftop PV Systems Piyadanai Pachanapan and Surachet Kanprachar Abstract The increasing of rooftop photovoltaic
More informationAdvanced Test Equipment Rentals ATEC (2832) CP RC. Resonance circuit for GIS testing
Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) CP RC Resonance circuit for GIS testing A new approach to testing gas-insulated switchgear Testing gas-insulated switchgear
More informationUser Guide for the Calculators Version 0.9
User Guide for the Calculators Version 0.9 Last Update: Nov 2 nd 2008 By: Shahin Farahani Copyright 2008, Shahin Farahani. All rights reserved. You may download a copy of this calculator for your personal
More informationHarmonic distortion analysis on the MV and LV distribution networks: problems, influencing factors and possible solutions
Harmonic distortion analysis on the MV and LV distribution networks: problems, influencing factors and possible solutions Fernando Bastião and Humberto Jorge Department of Electrical Engineering and Computers
More information2 METHODOLOGY. The method of reactive power compensation, proposed in this research is suitable
2 METHODOLOGY 2.1 BASE LOAD REACTIVE POWER REQUIREMENT The method of reactive power compensation, proposed in this research is suitable to meet the base reactive power requirement of the network. The base
More informationElectric Power Quality Monitoring and Analysis at a Tri-generation Plant under Development
Electric Power Quality Monitoring and Analysis at a Tri-generation Plant under Development IOANA PISICĂ, LAURENŢIU CONSTANTIN LIPAN, PETRU POSTOLACHE, CORNEL TOADER Department of Power Systems University
More informationImpact of Distributed Generation on Voltage Regulation by ULTC Transformer using Various Existing Methods
Proceedings of the th WSEAS International Conference on Power Systems, Beijing, China, September -, 200 Impact of Distributed Generation on Voltage Regulation by ULTC Transformer using Various Existing
More informationPower Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss
Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss Siemens AG, EV NP3 P.O. Box 3220 91050 Erlangen, Germany e-mail: Michael.Weinhold@erls04.siemens.de
More informationRequirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH
Requirements for Offshore Grid Connections in the Grid of TenneT TSO GmbH Bernecker Straße 70, 95448 Bayreuth Updated: 5th October 2010 1/10 Requirements for Offshore Grid Connections in the Grid of TenneT
More informationProject acronym: Multi-island
Technical report for The Experimental investigation on the performance characteristics of anti-islanding techniques in the prospect of high PV penetration level Project acronym: Multi-island USER PROJECT
More informationThe Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller
The Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller This paper deals with the general problem of utilizing of renewable energy sources to generate electric
More informationENERGY SAVING WITH OPTIMIZATION OF VOLTAGE AND CURRENT QUALITY
ENERGY SAVING WITH OPTIMIZATION OF VOLTAGE AND CURRENT QUALITY Approximation based on the know-how of SEMAN S.A. The non-linear nature of modern electric loads makes the reception of measures for the confrontation
More informationISSN Vol.03,Issue.07, August-2015, Pages:
WWW.IJITECH.ORG ISSN 2321-8665 Vol.03,Issue.07, August-2015, Pages:1276-1281 Comparison of an Active and Hybrid Power Filter Devices THAKKALAPELLI JEEVITHA 1, A. SURESH KUMAR 2 1 PG Scholar, Dept of EEE,
More informationVoltage Unbalance Reduction in Low Voltage Feeders by Dynamic Switching of Residential Customers among Three Phases
Voltage Unbalance Reduction in Low Voltage Feeders by Dynamic Switching of Residential Customers among Three Phases Farhad Shahnia, Peter Wolfs and Arindam Ghosh 3 Centre of Smart Grid and Sustainable
More informationRISK MANAGEMENT IN A LOW VOLTAGE NETWORK ON SAFETY ISSUES FROM ASSET MANAGEMENT PERSPECTIVE
RISK MANAGEMENT IN A LOW VOLTAGE NETWORK ON SAFETY ISSUES FROM ASSET MANAGEMENT PERSPECTIVE Sharmistha BHATTACHARYYA Endinet The Netherlands sharmirb@yahoo.com Thijs van DAEL Endinet The Netherlands thijs.van.dael@endinet.nl
More informationTechnical Information Installation Requirements for TRANSFORMER COMPACT STATION 500SC-JP/630SC-JP/800SC-JP
Technical Information Installation Requirements for TRANSFORMER COMPACT STATION 500SC-JP/630SC-JP/800SC-JP The Transformer Compact Station is the ideal link between a central inverter of the Sunny Central
More informationEH27401 Communication and Control in Electric Power Systems Lecture 2. Lars Nordström
EH27401 Communication and Control in Electric Power Systems Lecture 2 Lars Nordström larsn@ics.kth.se 1 Course map 2 Outline 1. Power System Topologies Transmission Grids vs Distribution grids Radial grids
More informationUnderstanding LV Network Voltage Distribution- UK Smart Grid Demonstration Experience
Understanding LV Network Voltage Distribution- UK Smart Grid Demonstration Experience Chen Zhao, Chenghong Gu, Ran Li, Furong Li Dept. of Electronic & Electrical Eng. University of Bath, Bath, BA2 7AY,
More informationA Methodology for the Efficient Application of Controlled Switching to Current Interruption Cases in High-Voltage Networks
A Methodology for the Efficient Application of Controlled Switching to Current Interruption Cases in High-Voltage Networks C. D. TSIREKIS Hellenic Transmission System Operator Kastoros 72, Piraeus GREECE
More informationGRID CODE COMPATIBLE PROTECTION SCHEME FOR SMART GRIDS
GRID CODE COMPATIBLE PROTECTION SCHEME FOR SMART GRIDS Hannu LAAKSONEN ABB Oy Finland hannu.laaksonen@fi.abb.com ABSTRACT Medium-voltage (MV) network short-circuit protection operation time delays have
More informationShunt Reactors. Global Top Energy, Machinery & Plant Solution Provider
Shunt Reactors Global Top Energy, Machinery & Plant Solution Provider Our Business Brief introduction of Hyosung Power & Industrial Systems PG While Hyosung is an established name for world-class electrical
More informationPower Quality Monitoring and Power Metering Tutorial
Power Quality Monitoring and Power Metering Tutorial Power generation and transmission today are accomplished using three phase alternatingcurrent. To understand electrical power quality monitoring and
More informationHarmonic Distortion Evaluations
Harmonic Distortion Evaluations Harmonic currents produced by nonlinear loads can interact adversely with the utility supply system. The interaction often gives rise to voltage and current harmonic distortion
More informationSingle-Phase Transformation Review
Single-Phase Transformation Review S T U D E N T M A N U A L March 2, 2005 2 STUDENT TRAINING MANUAL Prerequisites: None Objectives: Given the Construction Standards manual and a formula sheet, you will
More informationHARDWARE BASED CHARACTERISATION OF LV INVERTER FAULT RESPONSE
HARDWARE BASED CHARACTERISATION OF LV INVERTER FAULT RESPONSE Ibrahim ABDULHADI Federico COFFELE Power Networks Demonstration Centre - UK ibrahim.f.abdulhadi@strath.ac.uk federico.coffele@strath.ac.uk
More informationNetwork Monitoring and Visibility Summary
Network Monitoring and Visibility Summary This article reviews the shortfalls in legacy monitoring and what will be needed to manage the changing nature of the distribution network. This includes a particular
More informationCompany Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System
Company Directive STANDARD TECHNIQUE: SD7F/2 Determination of Short Circuit Duty for Switchgear on the WPD Distribution System Policy Summary This document provides guidance on calculation of fault levels
More informationT e l N o : F a x N o : E m a i l : a i s h c m c - m e. c o m w w w. c m c - m e.
EE179: Electrical Fault Analysis: Causes, Detection & Remedies EE179 Rev.001 CMCT COURSE OUTLINE Page 1 of 5 Training Description: It is essential to know the Short Circuit Current and KVA that the system
More informationAlternative Coupling Method for Immunity Testing of Power Grid Protection Equipment
Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment Christian Suttner*, Stefan Tenbohlen Institute of Power Transmission and High Voltage Technology (IEH), University of
More informationDynamic Grid Edge Control
Dynamic Grid Edge Control Visibility, Action & Analytics at the Grid Edge to Maximize Grid Modernization Benefits The existence of greater volatility at the grid edge creates a set of problems that require
More informationELECTRICAL POWER ENGINEERING
Introduction This trainer has been designed to provide students with a fully comprehensive knowledge in Electrical Power Engineering systems. The trainer is composed of a set of modules for the simulation
More informationMV Network Operation Issues and Elimination of Phase Voltage Unbalance
Transactions on Electrical Engineering, Vol. 6 (2017), No. 3 72 MV Network Operation Issues and Elimination of Phase Voltage Unbalance František Žák Analyst and Lecturer of the distribution network operation,
More informationTransactions on Information and Communications Technologies vol 16, 1996 WIT Press, ISSN
An expert system for teaching voltage control in power systems M. Negnevitsky & T. L. Le Department of Electrical & Electronic Engineering University of Tasmania GPO Box 252C Hobart, Tasmania 7001, Australia
More informationEFFECTS OF IONOSPHERIC SMALL-SCALE STRUCTURES ON GNSS
EFFECTS OF IONOSPHERIC SMALL-SCALE STRUCTURES ON GNSS G. Wautelet, S. Lejeune, R. Warnant Royal Meteorological Institute of Belgium, Avenue Circulaire 3 B-8 Brussels (Belgium) e-mail: gilles.wautelet@oma.be
More informationRealisation of the galvanic isolation in customer-end DC to AC inverters for the LVDC distribution
Realisation of the galvanic isolation in customer-end DC to AC inverters for the LVDC distribution Background: The electric distribution network in Finland has normally voltage levels of 20 kv and 400
More informationStudy on Reactive Automatic Compensation System Design
Available online at www.sciencedirect.com Physics Procedia 24 (2012) 211 216 2012 International Conference on Applied Physics and Industrial Engineering Study on Reactive Automatic Compensation System
More informationVoltage Sags Evaluating Methods, Power Quality and Voltage Sags Assessment regarding Voltage Dip Immunity of Equipment
s Evaluating Methods, Power Quality and s Assessment regarding Voltage Dip Immunity of Equipment ANTON BELÁŇ, MARTIN LIŠKA, BORIS CINTULA, ŽANETA ELESCHOVÁ Institute of Power and Applied Electrical Engineering
More informationHigh Voltage DC Transmission Prof. Dr. S. N. Singh Department of Electrical Engineering Indian Institute of Technology, Kanpur
High Voltage DC Transmission Prof. Dr. S. N. Singh Department of Electrical Engineering Indian Institute of Technology, Kanpur Module No. # 01 Lecture No. # 02 Comparison of HVAC and HVDC Systems Welcome
More informationHamdy Faramawy Senior Application Specialist ABB Sweden
Design, Engineering and Application of New Firm Capacity Control System (FCCS) Mohammed Y. Tageldin, MSc. MIET Senior Protection Systems Engineer ABB United Kingdom mohammed.tageldin@gb.abb.com Hamdy Faramawy
More informationSensor Accuracy and Data Management Issues
8/2/21 1 Sensor Accuracy and Data Management Issues Panel on Experiences and System Requirements for Power Quality Data Analytics 1PESGM912 Jan Meyer Robert Stiegler Etienne Gasch Max Domagk Technische
More informationSystem Requirements for Wind Farms and Distributed Generation. Giuseppe Di Marzio
ystem Requirements for Wind Farms and Distributed Generation Giuseppe Di Marzio giuseppe.di.marzio@elraft.ntnu.no 1 Contents Grid interconnection schemes Power quality requirements Fault Level considerations
More informationMultimeter 500CVD21 RTU500 series
Remote Terminal Units - Data sheet Multimeter 500CVD21 RTU500 series CT/VT interface with 4 voltage and 24 current inputs for direct monitoring of 3/4 wire 0 300 V AC (line to earth), 0...500 V AC (phase
More informationDETERMINING THE HARMONIC NETWORK IMPEDANCE MAINLY FOR PLANNING PURPOSES IN LOW VOLTAGE SYSTEMS
DETEMINING THE HAMONIC NETWOK IMPEDANCE MAINLY FO PLANNING PUPOSES IN LOW VOLTAGE SYSTEMS F. Otto W. upf G.Winkler J. Meyer DEWAG Stadtwerke Dresden GmbH PF 273 8 Dresden (Germany) Tel: +49 35 86 472 Fa:
More informationEL-AC Electronic Load
s are power electronics devices that behave as an electrical load. While most electronic loads are dissipative, CINERGIA offers a comprehensive range of, and & full 4Q and full regenerative electronic
More informationAEL-TI-01. Analysis of Three-phase Power Lines Application INTRODUCTION. Configuration example of AEL-TI with AEL-TI-01 application included
Engineering and Technical Teaching Equipment Analysis of Three-phase Power Lines Application AEL-TI-01 Configuration example of AEL-TI with AEL-TI-01 application included INTRODUCTION Power line is a structure
More informationShunt Reactor Switching
Shunt Reactor Switching Dielectric stresses produced by circuit-breakers to shunt reactors. Presentation made during the IEEE Transformers Committee meeting, Amsterdam, Netherlands, April 2001 Presented
More informationESB National Grid Transmission Planning Criteria
ESB National Grid Transmission Planning Criteria 1 General Principles 1.1 Objective The specific function of transmission planning is to ensure the co-ordinated development of a reliable, efficient, and
More information, ,54 A
AEB5EN2 Ground fault Example Power line 22 kv has the partial capacity to the ground 4,3.0 F/km. Decide whether ground fault currents compensation is required if the line length is 30 km. We calculate
More informationFACILITY RATINGS METHOD TABLE OF CONTENTS
FACILITY RATINGS METHOD TABLE OF CONTENTS 1.0 PURPOSE... 2 2.0 SCOPE... 3 3.0 COMPLIANCE... 4 4.0 DEFINITIONS... 5 5.0 RESPONSIBILITIES... 7 6.0 PROCEDURE... 8 6.4 Generating Equipment Ratings... 9 6.5
More informationProtection of MV Converters in the Grid: The Case of MV/LV Solid-State Transformers
2017 IEEE IEEE Journal of Emerging and Selected Topics in Power Electronics, Vol. 5, No. 1, pp. 393-408, March 2017 Protection of MV Converters in the Grid: The Case of MV/LV Solid-State Transformers T.
More informationShortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller
Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer Anura Perera, Paul Keller System Operator - Eskom Transmission Introduction During the design phase of
More informationDistribution Network Voltage Unbalance Control under High Penetration of Single-Phase Photovoltaic Microgeneration
Distribution Network Voltage Unbalance Control under High Penetration of Single-Phase Photovoltaic Microgeneration Youcef Bot, Ahmed Allali, Mouloud Denai University of Khemis Miliana, Algeria LDDEE, Laboratory,
More informationAC Power Instructor Notes
Chapter 7: AC Power Instructor Notes Chapter 7 surveys important aspects of electric power. Coverage of Chapter 7 can take place immediately following Chapter 4, or as part of a later course on energy
More informationMEASUREMENT CAMPAIGN AND ASSESSMENT OF THE QUALITY OF SUPPLY IN RES AND DG FACILITIES IN SPAIN
MEASUREMENT CAMPAIGN AND ASSESSMENT OF THE QUALITY OF SUPPLY IN RES AND DG FACILITIES IN SPAIN Eugenio PEREA*, Eduardo ZABALA*, J. Emilio RODRÍGUEZ*, Asier GIL DE MURO*, Hugo GAGO * * * Fundación LABEIN,
More informationALI UMAIR DETECTION ALGORITHM FOR THE CROSS COUNTRY EARTH FAULTS IN MEDIUM VOLTAGE NETWORK
ALI UMAIR DETECTION ALGORITHM FOR THE CROSS COUNTRY EARTH FAULTS IN MEDIUM VOLTAGE NETWORK Masters of Science Thesis Examiner: Professor Pertti Järventausta and Dr Tech. Ari Nikander Examiner and topic
More informationIroning out resonance
Ironing out resonance Ferroresonance prevention in MV voltage transformers Wojciech Piasecki, Marek Florkowski, Marek Fulczyk, Pentti Mahonen, Mariusz Luto, Wieslaw Nowak, Otto Preiss Every engineer knows
More informationImplementation Guidelines CGMES v2.4.15
15 March 2016 This document provides implementation guidelines for Suppliers and TSOs on the ENTSO-E Common Grid Model Exchange Standard (CGMES) version 2.4.15. The clarifications provided in this document
More informationThe Influence of Voltage Flicker for the Wind Generator upon Distribution System
The Influence of Voltage Flicker for the Wind Generator upon Distribution System Jin-Lung Guan, Jyh-Cherng Gu, Ming-Ta Yang, Hsin-Hung Chang, Chun-Wei Huang, and Shao-Yu Huang Digital Open Science Index,
More informationFerroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy
Ferroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy W. Piasecki, M. Stosur, T. Kuczek, M. Kuniewski, R. Javora Abstract-- Evaluation
More informationAPPLICATIONS DATA SHEET. Product: Single Phase AC/DC Power Meter QI-POWER-485
APPLICATIONS DATA SHEET Product: Single Phase AC/DC Power Meter QI-POWER-485 Renewable energy: 1. PV String Monitoring: the QI-POWER-485 measures DC current up to 50 A and DC voltage up to 1000 V, with
More informationA cost effective hybrid HVDC transmission system with high performance in DC line fault handling
2, rue d Artois, F-758 PARIS B4-7 CIGRE 28 http : //www.cigre.org A cost effective hybrid HVDC transmission system with high performance in DC line fault handling Mats Andersson, Xiaobo ang and ing-jiang
More informationFuture. Ready. SM. Using Meters as Distribution Sensors for Capacitor Bank Monitoring. White Paper
White Paper Using Meters as Distribution Sensors for Capacitor Bank Monitoring The role capacitor banks play in maintaining power quality varies by utility. But regardless of how capacitors are deployed,
More informationLow Voltage Grid Monitoring
Smart Grid Gotland Subproject Power Quality Low Voltage Grid Monitoring EUW Amsterdam 2017-10-04 Why monitor the low voltage grid? Power outages have so far been identified only by customers, not acceptable
More informationPOWER NETWORK MEASUREMENTS Analysers, Multimeters & Transducers
POWER NETWORK MEASUREMENTS Analysers, Multimeters & Transducers Measurements of electrical energy and 1 or network parameters belong to the LUMEL s main competence area. We offer in the scope of devices
More informationChapter L Power factor correction and harmonic filtering
Chapter L Power factor correction and 1 2 3 4 5 6 7 8 9 10 Contents Reactive energy and power factor 1.1 The nature of reactive energy L2 1.2 Equipment and appliances requiring reactive energy L2 1.3 The
More information