ATyS M 6e Operating instructions GB

Size: px
Start display at page:

Download "ATyS M 6e Operating instructions GB"

Transcription

1 ATyS M 6e Operating instructions GB

2 GENERAL SAFETY INSTRUCTIONS This manual provides instructions on safety, connections and operation of the ATYS source switchgear system. This system must always be installed and commissioned by qualified and approved personnel. This manual must be kept in a place so as to be available to anyone likely to need it. Maintenance and servicing operations must be performed by trained and authorised personnel. This system meets the European Directives governing this type of product. It has the CE marking. The information provided in this manual is subject to change, and is non-contractual. This product complies with the following standards: - IEC EN NBN EN BS EN IEC GB EN NBN EN BS EN VDE ATyS M 6e - Ref.: 55 4 B

3 INDEX GENERAL SAFETY INSTRUCTIONS INDEX INTRODUCTION General introduction The complete ATyS range ATyS M 6e and its versions Product presentation Supply types Optional accessories TECHNICAL SPECIFICATIONS Parallel pole set-up in single-phase: Environmental conditions INSTALLATION /400 V AC network configurations /0 V AC network configurations Product fitting Connection of control/command circuits Connection of power circuits Fitting of accessories Other functions Fitting in the SOCOMEC modular enclosure Operation Presentation of electronic module Programming Display Operating Manual mode Automatic mode Communication REPAIR GUIDE Repair check-list Repairing ATyS M 6e - Ref.: 55 4 B

4 . INTRODUCTION.. General introduction The ATyS M 6e is a quick-acting source inverter based on 4-pole switches controlled by an electronic device, which makes it an IEC compliant product. Thanks to the switch technology, manual operations are always possible so as to ensure source switchover regardless of the circumstances. The electronic module includes: Power sources status display. Voltage and frequency measurement display. Keypad programming of test and operating sequences. Manual control, locking and programming are directly accessible from the front panel of the device... The complete ATyS range 00 A 800 A ATyS s ATyS e ATyS 6e ATyS 6m 60 A 5 A ATyS M s ATyS M 6s ATyS M 6e 6 A () For ATyS M 6e, only on the version with communication. () Return to zero without external energy source. Motorised changeover switch Dual supply Built-in control relay Comm. Communication () Remote interface D0/D0 Tripping () P, Q, S, Pf measurement 4 ATyS M 6e - Ref.: 55 4 B

5 . INTRODUCTION.. ATyS M 6e and its versions The ATyS M 6e is available in two supply versions: 7/0 V AC and 0/400 V AC. It comes with and without RS485 communication..4. Product presentation This quick-acting source inversion solution incorporates: mechanically interlocked switches including an electronic control-command module. A quick-acting electric control unit enabling automatic or manual system operation. Bridging bars (accessory). 4 Electrical specifications compliant with product standards, and a version identification. 5 Changeover switch wiring identification. 6 Control connections. 7 An RJ45 connection for a remote interface D0 / D A connector for RS485 communication (MODBUS), for the version with communication. ATYSM 099 A Specifications and advantages: - Breaking: A source inversion system, completely built-in and interlocked, with high electrical performance and offering microprocessor control and monitoring. - Operation: A flexible operating mechanism allowing quick manoeuvres in automatic mode or locally in manual mode for emergency operations. Features a locking device. ATyS M 6e - Ref.: 55 4 B 5

6 . INTRODUCTION.5. Supply types The power supply of ATyS M 6e is required to be 0Vac +/- 0% at a frequency of 50 Hz or 60 Hz. Two models of the ATyS M 6e, 7/0 V AC and 0/400 V AC, have been developed, so as to meet all possible network configurations..5.. Product version identification method Vac Ph-N / 0 Vac Ph-Ph 7 Vac Ph-N / 0 Vac Ph-Ph Version 7/0 Vac Version 7/0 Vac U U U U U = Vac Hz U = Vac Hz ATYSM 67 A GB Vac Ph-N / 400 Vac Ph-Ph 0 Vac Ph-N / 400 Vac Ph-Ph Version 0/400 Vac Version 0/400 Vac U U U U U = Vac Hz U = Vac Hz ATYSM 67 A GB 6 ATyS M 6e - Ref.: 55 4 B

7 . INTRODUCTION.6. Optional accessories Auxiliary contact Each product can take up to auxiliary contact blocks. A block comprises NOC auxiliary contact (positions I, O and II). Ref.: Specifications: 50 V AC / 5 A maximum. ATYSM 08 A Bridging bars To provide common point on outgoing terminals. ATYSM 05 A R e f s a r e a v a i l a b l e : Rating 5A: and rating 60A: Remote interface D0/D0 - Use Dedicated to applications requiring the changeover switch to be fitted inside a cabinet. Product self-supplied via the connection lead with ATyS M. Maximum connection distance: m. - ATyS D0 For transferring source and changeover switch statuses to the cabinet front panel. Protection rating: IP. ATYS 564 C Ref. ATyS D0: Ref. ATyS D0: ATyS D0 In addition to the ATyS D0 interface functions, enables configuration, checking, tests and measurements display from a cabinet front panel. Protection rating: IP. ATYS 565 C - Door mounted holes, ø.5. Connected to ATyS M via a non-insulated RJ45 plug and straight lead. Connection cable for remote interface For connecting between a remote interface and the ATyS. RJ45 lead, m. ACCES 09 A Ref.: Voltage and power socket terminal This provides connection terminals for conductor crosssections.5 mm. The unipolar terminal can be fitted in cages without reducing their connection capacity. t for use on terminals with bridging bars fitted. ATYSM 06 A Ref.: parts/ref. Terminal shrouds Protection against direct contact with terminals or connecting parts. Advantages of terminal shroud: perforations enabling remote thermographic verification without dismantling. Possibility of sealing. ATYSM 07 A Ref.: parts/ref. Enclosure Fully dedicated to using an ATyS M, it provides easy access to a compact, enclosed source switchover solution. ATYSM 06 A Ref.: Extension unit Combined with the polycarbonate enclosure, the extension unit enables you to allocate additional space to the enclosure if you want to connect cables with cross-section 70 mm to the ATyS M. ATYSM 044 A Ref.: ATyS M 6e - Ref.: 55 4 B 7

8 . TECHNICAL SPECIFICATIONS Ratings 6 A 80 A 00 A 5 A 60 A Frequencies 50 & 60 Hz 50 & 60 Hz 50 & 60 Hz 50 & 60 Hz 50 & 60 Hz Thermal current Ith at 40 C (A) Thermal current Ith at 50 C (A) * 5 Assigned insulation voltage Ui (V) (Power circuit) Assigned transient voltage Uimp (kv) (Power circuit) Assigned insulation voltage Ui (V) (Auxiliary circuit) Assigned transient voltage Uimp (kv) (Auxiliary circuit) Other specifications at AC A / B 6/6 80/80 00/00 5/5 60/60 40 C: Currents assigned (A) AC A / B 6/6 80/80 00/00 5/5 5/60 IEC specifications at 45V AC. AC A / B 6/6 80/80 00/00 5/5 5/60 IEC specifications at 45V AC. AC B / ACB / ACB 6/6/6 80/80/80 80/00/00 80/5/5 80/60/60 Operating class Equipment class (According to IEC ) PC PC PC PC PC Maximum short-circuit current if using gg DIN fuses. Short-circuit operation Maximum short-circuit current (act. ka) Associated fuses (gg) Current peak value: Maintaining and closing operation (peak ka) Permissible short-term assigned current (act. ka) / 0 ms Switchover time I-II or II-I (ms) Switchover dead time at Un (ms) Consumption Mechanical specifications Connection cross-section I-O / O-I / II-O / O-II (ms) Peak current during switchover (A) Consumption in stabilised state (VA) Number of switchovers Minimum size (Cu mm ), flexible Maximum size (Cu mm ), flexible Maximum size (Cu mm²), rigid * Possibility of reaching 5 with bigger connection cross-sections. 8 ATyS M 6e - Ref.: 55 4 B

9 . TECHNICAL SPECIFICATIONS.. Parallel pole set-up in single-phase: Rating conversion table for use in single-phase, and two-by-two parallel pole set-up. (Max ambient temperature = 40 C). minal current strength in three-phase (A) minal current strength in single-phase ( poles in //) (A) Environmental conditions Humidity 80 % humidity without condensation at 55 C 95 % humidity without condensation at 40 C Temperature: C without de-rating C with de-rating Altitude: Max 000 m without de-rating Storage: year maximum ø mm IP rating: IP4 in the SOCOMEC polycarbonate modular enclosure (see chapter.8) IPx for non-enclosed modular product ATyS M 6e - Ref.: 55 4 B 9

10 . INSTALLATION U = Vac Hz.. 0/400 V AC network configurations... Voltage configurations Type Wiring Version 0/400 Vac V PH-PH Name Position of Network Network Neutral () U U U = Vac Hz Neutral on the left Neutral on the right Source Source Source N N N Load Load Source N 4NBL Left (setup: auto) Right (setup: auto) N L L L N L L L L L L N L L L N Source Load Source Source Source Load NBL Left (setup: auto) Right (setup: auto) L L L L L L L L L L L L Source Load Source Source N N N Load Source N BL Left (setup: auto) Right (setup: auto) N (N) (L) L N (N) (L) L L (L) (N) N L (L) (N) N Source Source Source N N N Load Load Source N 4 NBL Left (setup: auto) Right (setup: auto) N L L L N L L L L L L N L L L N Source Source Source N N N Load Load Source N 4 NBL Left (setup: auto) Right (setup: auto) N L L L N (L) (L) L L L L N L L (L) N () Position of neutral on the product The neutral position should be configured in the setup menu: - auto: neutral is detected upon initialisation - Neutral on left: neutral forced left - Neutral on right: neutral forced right 0 ATyS M 6e - Ref.: 55 4 B

11 . INSTALLATION Detections Neutral () Rotation () Balancing Monitoring/Display (4) Tripod Ntwk Ntwk Ntwk Ntwk Ntwk Ntwk Ntwk Ntwk Network Network V Ph-Ph V Ph-N V Ph-Ph V Ph-N Left Left YES Right Right YES ABC ACB ABC ACB ABC ACB ABC ACB YES YES YES YES readings readings readings readings N N Left Left YES Right Right YES ABC ACB ABC ACB ABC ACB ABC ACB YES YES YES YES readings 0 measurements readings 0 measurements EITHER EITHER EITHER EITHER EITHER EITHER EITHER EITHER 0 measurements measurement 0 measurements measurement N N Left Left YES Right Right YES ABC ACB EITHER YES readings readings ABC ACB EITHER YES 0 measurements measurement N N Left Left YES Right Right YES ABC ACB EITHER YES readings readings ABC ACB EITHER YES measurement 0 measurements N () yes: the product recognises whether the network neutral position is not the same as for network : an error message is then displayed FO - NEUTRAL no: the product does not recognise whether the network neutral position is different from network : the measurements may be incorrect EITHER: position undetermined () It is possible to configure the direction of phase rotation in the Setup menu: clockwise or anti-clockwise EITHER: the phase rotation is not controlled. (4) : voltage monitored ATyS M 6e - Ref.: 55 4 B

12 . INSTALLATION.. 7/0 V AC network configurations... Voltage configurations Type Wiring 0 Vac Version 7/0 Vac 00 40V PH-PH Name Neutral () Network Network U U U = Vac Hz Neutral on the left Neutral on the right Source Source Source N N N Load Load Source N 4 NBL Left (setup: auto) Right (setup: auto) N L L L N L L L L L L N L L L N V PH-PH Source Load Version 0/400 Vac Source Source Source Load NBL Left (setup: auto) Right (setup: auto) L L L L L L L L L L L L Source Source U = Vac Hz Source Source Load Load Source Source Source Load Load Source NBL BL Fixed left (setup: left) Fixed right (setup: right) Left (setup: auto) Right (setup: auto) M L L M L L L L M L L M (L) L L (L) (L) L L (L) (L) L L (L) (L) L L (L) Source Source Source N N N Load Load Source N 4 NBL Left (setup: auto) Right (setup: auto) N L L L (N) L L (L) L L L N (L) L L (N) () Position of neutral on the product The neutral position should be configured in the setup menu: - auto: neutral is detected upon initialisation - Neutral on left: neutral forced left - Neutral on right: neutral forced right ATyS M 6e - Ref.: 55 4 B

13 . INSTALLATION Detections Neutral () Rotation () Balancing Monitoring/Display (4) Tripod Ntwk Ntwk Ntwk Ntwk Ntwk Ntwk Ntwk Ntwk Network Network V Ph-Ph V Ph-N V Ph-Ph V Ph-N Left Left YES Right Right YES ABC ACB ABC ACB ABC ACB ABC ACB YES YES YES YES readings readings readings readings N N Left Left YES Right Right YES ABC ACB ABC ACB ABC ACB ABC ACB YES YES YES YES readings 0 measurements readings 0 measurements Left Left EITHER EITHER readings 0 measurements readings 0 measurements Right Right EITHER EITHER EITHER EITHER EITHER EITHER measurement 0 measurements measurement 0 measurements EITHER EITHER EITHER EITHER Left Left YES Right Right YES ABC ACB EITHER YES readings readings ABC ACB EITHER YES measurement 0 measurements N () yes: the product recognises whether the network neutral position is not the same as for network : an error message is then displayed FO - NEUTRAL no: the product does not recognise whether the network neutral position is different from network : the measurements may be incorrect EITHER: position undetermined () It is possible to configure the direction of phase rotation in the Setup menu: clockwise or anti-clockwise EITHER: the phase rotation is not controlled. (4) : voltage monitored ATyS M 6e - Ref.: 55 4 B

14 ATyS M 6e POWER CONTROL TEST OFF LOAD TEST ON LOAD ESC CLICK! ATyS M 6e CLICK!. INSTALLATION.. Product fitting Before fitting think about changing the locking configuration, if necessary. For locking in Positions I, II and 0, refer to section.6.5. Locking.- Accepted product orientations OK OK OK OK OK OK remote interface advised for these orientations ATYSM 046 A.- Dimensions.- Board-mounted AUT AUT 45 45,5 AUT AUT,5 MAX : ,5 ATYSM 047 B 6 x M6 lb-in,5 Nm ATYSM 047 B.-4 DIN rail mounted RAIL IEC 6075 ATyS M 6e AUT AUT Posidriv PZ 8,8 lb-in Nm Prevents movement on the DIN rail ATYS M 049 B 4 ATyS M 6e - Ref.: 55 4 B

15 . INSTALLATION.4. Connection of control/command circuits.4- Switch to manual mode before connecting the product. The product is delivered in position 0 and in auto mode, with the generator start signal contact closed. RS RJ A AC 50 Vac 4 Slotted head mm,97 lb-in 0,5 Nm / O O O G I I I 0,5 to,5 mm # 0 to # 4 AWG 0,5 to,5 mm # 0 to # 6 AWG 6 mm / 0,6 " ATYSM 44 A v Type Terminal no. Description Characteristics Recommended connection cross-section Inputs 07 Common point for inputs 08 I: configurable input Dry contact 09 I: configurable input Potential free 0.5 to.5 mm² 0 I: configurable input Output 4/44 O: configurable output Resistive load 5/54 O: configurable output A 0V DC 5A 0V AC 6/64 O: configurable output Pmax: 60W or 5VA 0.5 to.5 mm² 7/74 G: generator start order* Umax: 0V DC or 0V AC Remote interface connection RJ Remote interface ATyS D0/D0 Maximum separation m RJ45 8/8 Serial link RS485 connection RS 0: interconnection of cable shielding upstream and downstream of RS485 bus RS485 bus insulated. Only on version with 0.5 to.5 mm² : negative terminal of RS485 bus + : positive terminal of RS485 bus communication Auxiliary contact //4 Changeover switch in position I block (accessory) //4 Changeover switch in position II 50V AC 5A AC 0.5 to.5 mm² 0/0/04 Changeover switch in position 0 * Order also issued in manual mode. ATyS M 6e - Ref.: 55 4 B 5

16 . INSTALLATION.5. Connection of power circuits.5- Hexagonal Metric Allen size 4 44, lb-in 5,0 Nm It is essential to tighten all the 6 terminals (even those that are empty). 0 to 70 mm # 8 to # 00 AWG 6 to 50 mm # 0 to # 00 AWG 5 mm / 0,59 " ATYS M 45 A.6. Fitting of accessories.6.. Auxiliary contacts..6.-! 0,5 to,5 mm # 0 to # 4 AWG 0,5 to,5 mm # 0 to # 6 AWG 6 mm / 0,6 " Slotted head,0 mm 4,4 lb-in 0,5 Nm 0 mm 5 mm Posidriv PZ 8,8 lb-in Nm Posidriv PZ 8,8 lb-innm MAX ATYS M 05 A An auxiliary contact module comprises: one NO/NC changeover contact for each position (I-0-II). Use the screws supplied with the accessory. part/ref..6.. Voltage socket.6.- Slotted head,5 mm,97 lb-in 0,45 Nm This provides connection terminals for conductors with crosssection.5 mm². The unipolar terminals can be fitted in any of the cages without reducing the cage connection capacity. parts/ref. t for use on terminals with bridging bars fitted. 0,5 to,5 mm # 0 to # 4 AWG 0,5 to,0 mm # 0 to # 6 AWG 6 mm / 0,6 " ATYS M 46 A 6 ATyS M 6e - Ref.: 55 4 B

17 . INSTALLATION.6. Fitting of accessories (continued).6.. Bridging bars.6.- OK 0 to 70 mm # 8 to # 00 AWG 6 to 50 mm # 0 to # 00 AWG 5 mm / 0,59 " Hexagonal Metric Allen size 4 44, lb-in 5,0 Nm x 8 ATYS M 0 B Make sure that the bridging bars is fitted the right way round. There are two references available: one for ratings less than or equal to 5 A, and another for rating 60 A. part/ref Terminal shrouds.6.4- C K ATYS M 055 A parts/ref..7. Other functions.7.. Locking: configuration on standard product Enables locking in position 0 (factory configuration) or in position I, 0, II. It is necessary to make this adjustment before fitting the product in the cabinet or enclosure..7.-! Posidriv PZ STEP STEP STEP Posidriv PZ Posidriv PZ, lb-in 0,5 Nm X ATYS M 057 B ATyS M 6e - Ref.: 55 4 B 7

18 . INSTALLATION.7. Other functions (continued).7.. Sealable Auto-Man cover.7.- ATYS M 097 A.8. Fitting in the SOCOMEC modular enclosure.8.. Dimensions and mounting The enclosure must be wall-mounted using screws (not supplied). Recommended size: M6 50 mm (minimum). Weight: between 8 and 0 kg, depending on the accessories. ATYS M 70 A mm 5 mm (M6) z mm 75 mm (M6) Drilling plans for the cable-routing plate provided in appendix. ATYS M 64 A 9 mm ATYS M 65 A Only auxiliary contact block mountable 8 ATyS M 6e - Ref.: 55 4 B

19 . INSTALLATION.8. Fitting in the SOCOMEC modular enclosure (continued).8.. Connection Example: neutral on right Maximum cable size: 5 mm² ATYS M 60 A N N N /.8.. Ratings / cable cross-section table 6 A 00 A 5 A 60 A Min cable size Max cable size * 70* *With extension unit Extension unit.8.4- Enables you to allocate additional space to the enclosure. ATYS M 044 A ATYS M 6 A ATyS M 6e - Ref.: 55 4 B 9

20 4.. Presentation of electronic module Presentation of front panel: The LED signalling is only active when the product supply is on (supply LED lit) Operating and test modes AUT: green LED lit for AUTO mode active. yellow LEDs for the test on load and test off load which are linked to the test mode selection button so as to facilitate selection. yellow LED for the control function. The user may force the position of the switch. Lights test button Availability of sources green LEDs to indicate whether source and/or source are available (checking voltages and frequencies). - LED lit = source available. - LED off = source unavailable. : Lights test button in display mode. Mode button Test mode selection button. Position of the switch green LEDs - LED I lit = switch in position I - LED II lit = switch in position II yellow LED - LED lit = switch in position 0 POWER AUT ATyS M 6e CONTROL TEST OFF LOAD TEST ON LOAD ESC CLICK! AUT Power supply LED green LED - Always off: power supply off or software error if the other indicators are operational (LED and Screen). - Always lit: product power supply on. Fault summary LED red LED to indicate the status of the product control fault. Open and close the AUT/MAN cover to reset the fault. Manual mode : yellow LED for MANU mode active. Capacitor load indicator Loading the return to zero capacity. If the indicator flashes, the RETURN to 0 function is unavailable. Locking Option to isolate ( x 8mm max). Manual switching Insert the Allen key (5.0 mm) provided to switch manually. Manual operation is not possible when padlocked. AUT/MAN cover Open the cover to switch to manual mode. Close the cover to return to automatic mode. Open and close the cover to clear the faults. Switch position indicators Display of position I, 0, II. ATYS M 56 A GB 0 ATyS M 6e - Ref.: 55 4 B

21 4.. PROGRAMMING 4... General Information Software version The software version is displayed after the product has been switched on and only directly after it has been off for several minutes (enabling its capacitors to fully discharge). Product programming Programming mode can be entered from any operating mode (Auto/Man). Accessing programming Default code: 000 Browsing Press for s To modify the value of this digit To access the other digits Validate entry Exit programming Press the validate button for seconds. ATyS M 6e - Ref.: 55 4 B

22 4.. Programming (continued) 4... Programming mode Depending on the type of application managed (Network-Network or Network-genset), certain parameters in the SETUP menu may not be displayed. Configure parameters () () () () Configure voltage thresholds and hystereses Frequency thresholds and hystereses configuration Timer configuration Input - output configuration Communication configuration () () () () (5) (5) (5) (5) (5) ATyS M 6e - Ref.: 55 4 B

23 () Only accessible if the Setup menu variable "APP" is at "M-G", see Setup Menu () Only accessible if the Setup menu variable "APP" is at "M-M", see Setup Menu () Only accessible if one of the inputs is EON, see I/O Menu (4) Only accessible if one of the inputs is EOF, see I/O Menu (5) Only on the COMM version, see description in the option section (6) Only accessible if one of the outputs is LSC, see I/O Menu * UNL = Unlimited () () () () () (4) (4) (4) (6) The entry point for programming mode is the SETUP menu. Parameters must always be adjusted and verified for compliance with the application. The default values are loaded as standard. ATyS M 6e - Ref.: 55 4 B

24 4.. Programming (continued) 4... SETUP Menu Definition Adjustment range Default values NETWORK Network type NEUTRAL Position of neutral - AUTO: neutral position is set automatically upon every power-up - LEFT: neutral must be connected on the left, i.e. to terminal 7 of each switch ROT PH. (see next page) NOM. VOLT NOM. FREQ - RIGHT: neutral must be connected on the right, i.e. to terminal of each switch The phase rotation can be selected as clockwise (ACB) or anti-clockwise (ABC). It is also possible to just check for consistency of direction of rotation between sources (----).To do so the sources must be simultaneously present, for example during the initial wiring. minal phase-phase voltage. Except for BL and 4NBL networks, where it is nominal phase-neutral voltage. 4NBL/4NBL/ 4NBL/BL/NBL (0/400V version) 4NBL/NBL/NBL/ BL/4NBL (7/0V version) AUTO LEFT RIGHT ABC ACB --- from 80 to 480 V AC (0/400V version) from 80 to 80V AC (7/0V version) M-G* M-M* 4NBL AUTO V AC (0/400V version) 0V AC (7/0V version) Rated frequency 50 or 60 Hz 50 Hz APP Application type: - M-G: between a network and genset - M-M: between two networks M-G M-M M-G GS START Generator start signal output status at rest - NO: rmally Open NO NC NO - NC: rmally Closed PRIO TON In case of an On Load Test, if the source is no longer available you can - NO: exit the test and switch to source NO YES NO - YES: stay in position II. The MSR input has priority over this parameter PRIO EON The same as in External On Load, - NO: exit the test and switch to source NO YES NO - YES: stay in position II. The MSR input has priority over this parameter * M-G: network - genset application - M-M: network - network application = time delay present in M-G and/or M-M application 4 ATyS M 6e - Ref.: 55 4 B

25 Definition Adjustment range Default values M-G* M-M* PRIO NET This is for defining the priority network: - : network has priority - : network has priority 0-0: no network has priority: one is backing up the other. The PRI input has priority over this parameter RETRANS Automatic retransfer inhibited NO NO - NO: automatic retransfer to the priority source YES - YES: "valid" must be pressed to execute the return RETURN 0 () In case of source failure, the product automatically switches over to 0 (after a 0T or 0T time delay) NO YES NO - NO: the product remains in position if the source is lost - YES: this function is activated If there are sources down, the power reserve must be available to execute this function (see indicator on front panel) ND TRIP () This function makes it possible to wait for the power reserve to become available before exiting position 0 to adopt a source again. NO YES NO - NO: Return to the source without waiting for the reserve to be fully charged - YES: Wait for the reserve to be fully charged before returning to the source. A second trip will therefore be immediately available MOD AUT AUTO mode forced, in spite of cover not being closed. NO YES NO CNT RST Switchover counter reset (number of manoeuvres) Returns to NO after reset BACKLGHT The screen backlighting can be set to: - OFF: always off - ON: always lit - INT: lit during operating sequences and then turned off after 0 seconds' inactivity on the keypad NO YES OFF ON INT CODE P Modifying input code in Programming mode 0000 to 9999 CODE E Modifying input code in Operating mode 0000 to 9999 NO INT * M-G: network - genset application - M-M: network - network application = time delay present in M-G and/or M-M application () The RETURN to 0 function, upon the source voltage or source being lost, opens the switch (II=>0 or I=>0) of the source in question after a time delay (0T or 0T). For instance, this solution provides the possibility of opening the switch after a short-circuit. This also makes it possible to restart the genset after a fault, without being connected to the load. () The nd TRIP parameter is associated with the RETURN to 0 function, as the latter requires a power reserve for the changeover. So to execute a second trip, you need to wait for this power reserve to recharge. ATyS M 6e - Ref.: 55 4 B 5

26 4.. Programming (continued) 4... SETUP Menu (continued) Phase rotation check: this functionality verifies the consistency of phase rotation i.e. of the wiring prior to commissioning. Example If the parameter ROT PH = ABC: 4..- L (A) 4..- L (A) OK NON OK L (C) L (B) ATYS 9 B GB L (B) L (C) ATYS 0 B GB Display or depending on the non-compliant source. Rotation check on sources and. Function active on both sources with a 4NBL or NBL type network, and only on source with a 4NBL or 4NBL network (see network configurations). 6 ATyS M 6e - Ref.: 55 4 B

27 4.. Programming (continued) VOLT. LEVELS Menu Definition Adjustment range Default values OV U Source over-voltage detection (In percentage of the NOM. VOLT, Setup menu) 0-0% 5% OV U HYS Source over-voltage hysteresis (In percentage of the NOM. VOLT, Setup menu) 0-9% 0% UND.U Source under-voltage detection (In percentage of the NOM. VOLT, Setup menu) 60-98% 85% UND.U HYS Source under-voltage hysteresis (In percentage of the NOM. VOLT, Setup menu) 6-99% 95% UNB. U Source unbalance detection (see next paragraph) 00-0% 00% UNB. U HYS Hysteresis unbalance detection (see next paragraph) 0-9% 0% OV U Source over-voltage detection (In percentage of the NOM. VOLT, Setup menu) 0-0% 5% OV U HYS Source over-voltage hysteresis (In percentage of the NOM. VOLT, Setup menu) 0-9% 0% UND.U Source under-voltage detection (As percentage of NOM. VOLT, Setup menu) 60-98% 85% UND.U HYS Source under-voltage hysteresis (In percentage of the NOM. VOLT, Setup menu) 6-99% 95% UNB.U Source unbalance detection (see next paragraph) 00-0% 00% UNB.U HYS Hysteresis unbalance detection (see next paragraph) 0-9% 0% ATyS M 6e - Ref.: 55 4 B 7

28 4.. Programming (continued) VOLT. LEVELS Menu (continued) Over-voltage and under-voltage The thresholds and hystereses are defined as percentages of nominal voltage. The hystereses define return to normal levels following an under-voltage or over-voltage % Checked value (voltage) Upper threshold (ov. V) upper threshold hysteresis (ov. V Hys) 00 T lower threshold hysteresis (und. V Hys) Lower threshold (und. V) Source available ATYSM 68 A GB Voltage unbalance measurement U U N N U U U U Network balanced Network unbalanced The unbalance reading is derived from the formula below U nba = max ( U - U, U - U, U - U ) avg avg avg where U avg = U + U + U U avg Example of an unbalanced network: U = 5 V AC U = 400 V AC U = 70 V AC U avg = ( )/ = 74 V AC U nba = 6/74 = => Unbalance threshold rate 7% 8 ATyS M 6e - Ref.: 55 4 B

29 4.. Programming (continued) FREQ. LEVELS Menu The thresholds and hystereses are defined as percentages of nominal frequency. The hystereses define return to normal levels following an under-frequency or over-frequency % Checked value (frequency) Upper threshold (ov. F) upper threshold hysteresis (ov. F Hys) 00 T lower threshold hysteresis (und. F Hys) Lower threshold (und. F) Source available ATYSM 69 A GB Definition Adjustment range Default values OV F Source over-frequency detection (In percentage of the NOM. FREQ menu Setup) 0-0% 05% OV F HYS Source over-frequency hysteresis (In percentage of the NOM. FREQ menu Setup) % 0% UND.F Source under-frequency detection (In percentage of the NOM. FREQ menu Setup) 60-99% 95% UND.F HYS Source under-frequency hysteresis (In percentage of the NOM. FREQ menu Setup) % 97% OV. F Source over-frequency detection (In percentage of the NOM. FREQ menu Setup) 0% - 0 % 05% OV. F HYS Source over-frequency hysteresis (In percentage of the NOM. FREQ menu Setup) % 0% UND.F Source under-frequency detection (In percentage of the NOM. FREQ menu Setup) 60-99% 95% UND.F HYS Source under-frequency hysteresis (In percentage of the NOM. FREQ menu Setup) % 97% ATyS M 6e - Ref.: 55 4 B 9

30 4.. Programming (continued) TIMERS Menu Definition Adjustment range Default values M-G* M-M* FT Source loss time delay ( Failure Timer) When source disappears, FT is started. If source is restored before the end of FT, the switchover cycle is not engaged. from 0 to 60 secs second RT Source restoration time delay ( Return Timer) When source reappears, RT is started. At the end of RT, source is considered as present. If source disappears before the end of RT, the switchover is not executed. If the replacement source disappears during RT, the latter dynamically adopts the s setting value temporarily. from 0 to 600 secs 80 second 0T Return to zero time delay from source ( to 0 Timer) Only accessible if the parameter RETURN 0 is activated. Waiting time delay following source failure, before switchover to position 0. This time delay avoids opening directly to short-circuit. from 0 to 0 secs second FT Source loss time delay ( Failure Timer) If source disappears, FT is started. If source is restored before the end of FT, the switchover cycle is not engaged. from 0 to 60 secs second RT Source restoration time delay ( Return Timer) When source reappears, RT is started. At the end of RT, source is considered as present. If source disappears before the end of RT, the switchover is not executed. from 0 to 60 secs 5 second AT Stabilisation time delay ( Available Timer) Stabilisation time delay for voltage and frequency on Source. This time delay must be completed to enable transfer to Source from 0 to 60 secs 5 second CT Genset cooling time delay (source ) ( Cool Timer) Following a switchover sequence, and after returning to source, source (genset) is kept running for CT to enable it to cool down. from 0 to 600 secs 80 second 0T Return to zero time delay from source ( to 0 Timer) Only accessible if the Setup menu parameter RETURN 0 is activated. Waiting time delay following source failure, before switchover to position 0. This time delay avoids opening directly to short-circuit. from 0 to 0 secs 0 second * M-G: network - genset application - M-M: network-network application = timer present on M-G and/or M-M applications 0 ATyS M 6e - Ref.: 55 4 B

31 ST Genset starting timeout delay (source ) ( Start Timer) 0DT TOT TFT Time delay started at the same time as the starting request. If after ST source (genset) has not started, an error message is displayed: "FAIL START". Minimum electric dead time delay (0 Dead Timer) This is the minimum load supply down time, possibly set to zero, so as to enable residual voltages generated by the load (engine type) to disappear. "On Load Test" duration time delay (Test On Load Timer) This time delay defines the On Load Test time. It starts when the Test is initiated. The return to the network takes place at the end of TOT. "Off Load test" time delay (Test off Load Timer) This time delay defines the Off Load Test duration. from 0 to 600 secs from 0 to 0 secs UNL (unlimited)/lmt (from 0 to 800 secs) UNL (unlimited) / LMT (from 0 to 800 secs) 0 second M-G* M-M* second UNL UNL ET () "On Load external operation" request time delay (start) This time delay starts at the same time as the EON order. At the end of this time delay, switchover to source is executed. from 0 to 800 secs 5 second ET () "On Load external operation" request time delay (duration) This time delay defines the EON order time. UNL (unlimited)/lmt (from 0 to 800 secs) UNL ET () "On Load external operation" request time delay (End) This time delay is counted from the end of the EON order, and only after this time delay is the switchover to source executed. from 0 to 800 secs 5 second E5T () "Off load external operation" request time delay (start) This time delay starts at the same time as the EOF order. At the end of this time delay, the genset starting order is sent. from 0 to 800 secs 5 second E6T () "Off load external operation" request time delay (duration) This time delay defines the EOF order time. from 0 to 800 secs 600 second E7T () "Off load external operation" request time delay (end) This time delay is counted from the end of the EOF order, and only after this time delay will time delay CT start, before the genset is stopped. from 0 to 800 secs 5 second LST Load shedding time delay Load Shedding Timer This time delay corresponds to the time available to perform the load shedding operation. from 0 to 60 secs 4 second * M-G: network - genset application - M-M: network-network application = timer present on M-G and/or M-M applications (): these time delays are only accessible and configurable if at least one programmable input is configured with the variable EON (see I/0 menu) (): these time delays are only accessible and configurable if at least one programmable input is configured with the variable EOF (see I/0 menu) ATyS M 6e - Ref.: 55 4 B

32 4.. Programming (continued) I-O menu Variable Definition Adjustment range IN I Input see table on next page Default value / IN I Input status NO or NC IN Input see table on next page NO / IN Input status NO or NC IN Input see table on next page NO / IN Input status NO or NC Out Output see table on next page NO / Out Output see table on next page / Out Output see table on next page / ATyS M 6e - Ref.: 55 4 B

33 4.. Programming (continued) I-O menu Inputs / Outputs M-G Network/Genset M-M Network/Network M G M M Input functions Automatic operation inhibited INH On load test TON / Off load test TOF / Delayable external on load operation request EON / Delayable external off load operation request EOF / Forcing to source (genset) in TON and EON mode MSR / Source priority / PRI Confirms mains restoration Fault reset Source / source alarm AL AL AL AL Source / source fault FT FT FT FT Source / source external availability signal OA OA OA OA Stabilisation time delay bypass SS SS SS SS Position I / position II command PS PS PS PS Position 0 command Load shedding time delay bypass Output functions Source / source available SA SA SA SA One source available SCA Position I / position II auxiliary contact AC AC AC AC Position 0 auxiliary contact Load supplied by source / by source LO LO LO LO Load shedding command LSC Fault summary Product operational (no fault + product in Auto mode) Input copy Input copy Input copy RTC RST PS0 LSI AC0 FLT POP CP CP CP ATyS M 6e - Ref.: 55 4 B

34 4.. Programming (continued) I-O menu (continued) Inputs Automatic operation inhibited Automatic operation inhibited, operation the same as manual mode. All automatic INH commands will be inhibited. The gen start contact status does not change upon activation. On load test TON Activates on load test. Retransfer remains locked until contact is deactivated. Off load test TOF Activates off load test (genset started and stopped). External on load operation request, delayable Activates an operating cycle depending on time delays ET, ET, ET. These time delays have to be set EON in the TIMERS menu (operation: see graphs below). External off load operation request, delayable Activates "Start Gen" contact (genset starting) (source ) according to time delays E5T, E6T, E7T. These EOF time delays have to be set in the TIMERS menu (operation: the same as the input EON, without load switchover). Forcing to source (Genset) in TON and EON mode During an on load test or a delayable external on load operation request, validating the input enables you MSR to remain in back-up position in all circumstances (loss of this source), as long as the test is active. This input has priority over parameters PRIO TON and PRIO EON. Confirms return to priority source Remote manual transfer. Transfer back to source initiated upon the contact closing (one second front). RTC Same function as the variable "RETRANS" cleared with the keypad. This SETUP menu variable must also be at YES to validate operation by the input. Source priority Defines the priority source. PRI It is equivalent to, but with priority over, the SETUP menu parameter PRIO NET. Stabilisation time delay bypass (Time delay AT) Remote transfer check. It is possible to initiate the transfer from source to source (and vice versa) before the end of the time delay RT/RT/AT countdown, depending on the application SS / SS type. If the latter is set to its maximum value, it is possible to transfer by activating the contact (for a minimum of one second). Positions I, II and 0 command PS/PS/PS0 Source / source alarm Position I / position II / position 0 command. When the command disappears the product returns to automatic mode. The last command received has priority. Command 0 has priority over commands I and II. NB, switching to Pos I (Pos II) is only possible if source (source ) is present. Informs the user by flashing the fault LED and indicating F ALR - / F ALR - on the screen. This AL / AL message disappears along with the alarm Source / source fault Informs the user by flashing the fault LED and indicating F FLT - / F FLT - on the screen. Disappears after validation and reset (by activating RST input, opening and then closing the cover or via FT / FT RS485). Immediately shifts the changeover switch to position 0, without 0T or 0T time delay. NB, only works if the nd TRIP parameter is activated. Source / source external availability signal 0A / 0A Availability signal for source (source ). This input is used instead of the voltage and frequency measurement taken Fault reset RST Clears a fault Load shedding bypass LSI This input bypasses the LST time delay, (signal indicating correct load shedding). 4 ATyS M 6e - Ref.: 55 4 B

35 4.. Programming (continued) I-O menu (continued) Explanation of how EON works ET limited EON input Operation request ET ET ET Starting order contact CT? Starting time Pos II Pos I AT ATYSM A GB ET has priority over EON if ET is limited (not infinite) EON input Operation request ET ET ET Starting order contact CT Pos II Pos I Starting time? AT ATYSM 8 A GB EON has priority over ET if ET is unlimited EON input Operation request ET ET Starting order contact CT? Starting time Pos II Pos I AT ATYSM 4 A GB ATyS M 6e - Ref.: 55 4 B 5

36 4.. Programming (continued) I-O menu (continued) Outputs Source available SA /SA Source / Source available. Output activated (closed) if source / source is within the defined setting ranges (operation same as LED on front panel). At least one source available SCA Source or available. Output activated (closed) if at least one of the sources is within the defined settings ranges. Position auxiliary contact AC/AC/AC0 Outputs activated respectively when product is in position I / position II / position 0. Load supplied by source / by source LO / LO Indicates which source is supplying the load. Output LO / LO activated if the following conditions are simultaneously validated: position I / position II is closed and source / source is available (LO = AC and SA / LO = AC and SA) Load shedding command LSC Load shedding relay. Initiates a load shedding action before transfer to back-up source, and then reloading after restoration. Operation described below. Fault summary FLT Output activated (closed) if at least one fault (internal or transferred external) is activated. Product operational (no fault + product in Auto mode) POP Output activated (closed) if the product is deemed "operational" i.e. it is in AUT mode, the supply is present and no fault is detected. Input copy CP/CP/CP The output adopts the same status as input / input / input. Function same as relaying. 6 ATyS M 6e - Ref.: 55 4 B

37 4.. Programming (continued) I-O menu (continued) Explanation of how LSC works If the output LSC is selected, the associated time delay LST should be programmed (see Timers Menu) Scenario : LSI input inactive Genset voltage CT LSC output LST delay LST Pos I II I ATYSM 6 B GB Scenario : LSI input active Genset voltage CT LSC output LST delay LST LSI Pos I II I ATYSM 6 B GB ATyS M 6e - Ref.: 55 4 B 7

38 4.. Programming (continued) COMM Menu Variable Definition Adjustment range Default value Address Address of communicating device to 55 5 Speed Communication speed 400, , Stop bit, 9600 Parity bit NO, ODD, EVE NO Only available on version with Comm. Detailed explanation in chapter 4.9. Common 8 ATyS M 6e - Ref.: 55 4 B

39 4.. Display 4... Presentation Display mode is activated as soon as the device is switched on. It enables you to view the various parameters, regardless of the cover position or the activated mode. The switchover cycles have priority over display mode, and display the time delay countdowns as soon as they are activated. Any value available in this mode is kept on the screen once displayed for 5 secs. After this time, or following a switchover cycle, the screen returns to the source phase-phase voltages display ( st screen in this mode). Dynamic display of derived time delays has priority. The alarms status display also has priority. ATyS M 6e - Ref.: 55 4 B 9

40 4.. Display (continued) 4... Encoding principle Example Fault Source. 5 Password Source. Status message Fault message 0 Manual switching Duty cycle Under-voltage Fault Over-voltage Alarm Under-frequency Neutral wiring / Phase rotation mismatch 4 Over-frequency Capacitor back to 0 5 Phase unbalance Insufficient switchover power 6 Phase rotation Position not reached 4... Events list Message Definition Message Definition Manual switching Over-frequency on source Under-voltage on source Over-frequency on source Under-voltage on source Phase unbalance on source Over-voltage on source Phase unbalance on source Over-voltage on source Incorrect direction of rotation on source Under-frequency on source Incorrect direction of rotation on source Under-frequency on source 40 ATyS M 6e - Ref.: 55 4 B

41 4.. Display (continued) Error messages list Error message Definition Action Reset Duty cycle Limited number of manoeuvres in a defined period. Wait min. for the error message to disappear. Automatic Source / source neutral wiring mismatch The neutral on source is not wired on the same side as the neutral on source. Rewire one of the two sources. E.g.: both neutrals on the left, or both neutrals on the right. Open and then close the cover Source / source fault This fault only appears if input FT/ FT (see I-O Menu) and the parameter ND TRIP (see Setup Menu) are activated. Activation of this fault shifts the changeover switch to position 0. Resolve the external problem that caused activation of input FT/FT Open and then close the cover or activate the RST input, if configured (see I-O Menu) or via RS485. Alarm / Alarm This fault only appears if input AL/ AL is activated (see I-O Menu). Resolve the external problem that caused activation of input AL/AL. Once this is done, the error message will disappear automatically. Automatic Phase rotation fault on source / source The phase rotation does not correspond to the ROT PH. variable in the Setup menu. Either invert two phases on source / source, or change the status of the ROT PH. variable in the Setup menu, if both sources are faulty. Return to zero capacitor charging fault on source / source Recharging malfunction of capacitor associated with source / source. Provisional action: deactivate the RETURN 0 function in the Setup menu (Set to NO), or open the cover and manoeuvre manually. Then: contact your retailer. Insufficient switchover power on source / source The power is insufficient to leave position II/I. Lend the power (U,I) from source or for at least 0 secs, or open the cover and manoeuvre manually. Automatic Open then close the enclosure Open then close the enclosure Source / source position fault Following an electric or automatic order, position I / II is not reached. Provisional action: open the cover and manoeuvre manually. Then: contact your retailer. Change source status. Manual manoeuvre. Source starting timeout If the genset does not start after the ST delay, the message will be sent. Press the validation key. Check the genset. ATyS M 6e - Ref.: 55 4 B 4

42 4.4. Operating In operation the operator has the option of controlling switchover manually or electrically. Test modes are also available Test modes Press the test button TEST After 5 secs Test off load Code OK Test off load sequence End Code not OK Auto After 5 secs Test on load Code OK Test on load sequence End Code not OK After 5 secs Check Code OK Switch position I, 0, II check (PS, PS0, PS) End Code not OK Tests output ATYSM 50 A GB Off load test (M-G application only) This test is possible in automatic or manual mode. It can be considered as a manual genset starting order without switching over the load to the genset. Description - This mode enables you to test the genset without load transfer to the latter. - The genset is started and stopped as normal (via the "Start Gen" contact). - This test is always possible, except during a source loss sequence. - This test may be time-delayed (TOF). Activation - either via the operating menu, - or via communication (for version with COM), - or via the ATyS D0 interface, - or via the programmable input. Deactivation - either by changing the status of the control input - or by pressing the validation key on the keypad - or after a genset starting timeout - or at the end of the timer (if set) - or in case of genset shutdown upon fault 4 ATyS M 6e - Ref.: 55 4 B

43 4.4. Operating (continued) On load test (M-G application only) This test is only possible in automatic mode, it enables you to start the genset and simulate a complete transfer sequence. Description - The purpose of this sequence is to execute a load transfer to the genset to test it, while adhering to switchover conditions. - The time delays for validating the transfer conditions (TOT, ST, AT, 0DT, CT) are derived according to their configuration. - The mains restoration confirmation function is always active throughout an on load test (from the keypad). It enables transfer back to source in case of an unlimited on load test, or interrupts a time delayed on load test. Activation - either via the operating menu, - or via communication, - or via the ATyS D0 interface, - or via the programmable input. Deactivation - either by changing the status of the control input - or by pressing the validation key on the keypad - or after a genset starting timeout - or at the end of the timer (if set) - or in case of genset shutdown upon fault Changeover switch position I, 0 and II check (accessible in AUT mode) Description Changeover switch electrical position check: PS, PS0, PS. Activation - either via the operating menu. It will then be possible to force one of the positions I, O, II via the keypad, - or by via communication (for version with COM), - or via the ATyS D0 interface, - or via the programmable input. Deactivation - either via the Escape key - or by switching from Auto mode to Man. mode. The check takes priority over all functions. ATyS M 6e - Ref.: 55 4 B 4

44 4.5. Manual mode To access manual mode, open the cover or use the input INH. Once manual mode is active (cover open) it is possible: To access the programming and display menus. To lock the changeover switch. To manoeuvre the changeover switch using the handle. To start the genset via the off load test. As soon as manual mode is activated, all automatic actions are inhibited (except the starting order in case of mains loss). The same result is obtained if the INH input is active. The automatic cycle is relaunched seconds after the switch from MAN. to AUTO mode. During this time nothing happens, and the AUTO LED will be flashing. Manual mode PROGRAMMING Display Locking Changeover switching Manual Off load test Manual switching Use the handle situated on the front panel under the cover to manoeuvre the changeover switch. Check the changeover switch position on the indicator situated on the front panel before making any manoeuvre. From position I, turn anti-clockwise to get to position 0 From position 0, turn anti-clockwise to get to position II From position II, turn clockwise to get to position 0 From position 0, turn clockwise to get to position I ATYSM 09 A Do not force the product (Max 8 Nm). Do not leave the handle in automatic mode, if the AUT MODE variable is forced Locking Locking is only possible in manual mode (cover open). Locking is configurable in position 0 only (standard) or in all positions (I-0-II), prior to product fitting. Pull on the locking handle to enable isolation. Isolate by inserting a lock into the orifice provided for this purpose Reset 4 mm min /6 min 8 mm min 5/6 min ATYSM 094 A Operating fault reset Open and re-close the AUT/MAN cover Hardware Reset Insert a pointed tip into the orifice on the upper part of the product. ATYSM 09 A ATYSM 48 A 44 ATyS M 6e - Ref.: 55 4 B

SOCOMEC - Réf.: A

SOCOMEC - Réf.: A 34 THE ATyS RAGE The ATyS family proposes a complete motorised changeover range including electrical and mechanical interlocking. Manual operation is always possible on all the products in case of emergency.

More information

SDMO. Changeover switch VERSO 200

SDMO. Changeover switch VERSO 200 User guide SDMO Changeover switch VERSO 200 V 1.1a 13/11/2013 33502029301_0_1 Summary 1 - Safety guidelines for installation and operation... 4 2 - Installation of the source changeover switch... 5 2.1

More information

CROSS Chassis from 160 A to 450 A

CROSS Chassis from 160 A to 450 A CROSS Chassis from 160 A to 450 A STS CATALOGUE Important note! The technical data enclosed is for general information. Please note that the operating instructions and references indicated on the products

More information

sw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS

sw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS INSTRUCTIONS MANUAL IM831-U v0.92 HRI-R40W sw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS INDEX: GENERAL TYPES ACESSORIES AND OPTIONS

More information

INSTRUCTIONS MANUAL DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS HRI-R40W

INSTRUCTIONS MANUAL DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS HRI-R40W Page 2 / 16 INDEX: GENERAL TYPES ACESSORIES AND OPTIONS INSTALLATION WIRING DIAGRAMS CONNECTING TERMINALS DIAGRAMS WIRING DIAGRAM DESCRIPTION WORKING DESCRIPTION AND KEYBOARD WORKING DESCRIPTION AND PROGRAMMING

More information

BU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on supply lines for medical locations ISOLTESTER-DIG-RZ/RS/PLUS

BU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on supply lines for medical locations ISOLTESTER-DIG-RZ/RS/PLUS INSTRUCTION MANUAL BU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on supply lines for medical locations ISOLTESTER-DIG-RZ/RS/PLUS 1/23 More information than that reported

More information

CONTROLLER ATyS C20/C30

CONTROLLER ATyS C20/C30 COTROLLER ATyS C0/C30 otice d utilisation - Operating instructions F GB MAKE YOUR BUSIESS SAFE SOCOMEC GROUP SWITCHIG PROTECTIO & UPS F Sommaire LA GAMME ATyS 3 PRÉSETATIO GÉÉRALE 4 Présentation des produits

More information

RCMS460 and RCMS490 Series

RCMS460 and RCMS490 Series 4 T M RCMS460 and RCMS490 Series Digital Multi-Channel Ground Fault Monitor / Ground Fault Relay Grounded and High-Resistance Grounded AC/DC Systems Technical Bulletin NAE1042060 / 04.2013 BENDER Inc.

More information

AC/DC. Monitoring Technique. VARIMETER IMD Insulation monitor RN 5897/300

AC/DC. Monitoring Technique. VARIMETER IMD Insulation monitor RN 5897/300 Monitoring Technique VARIMETER IMD Insulation monitor RN 5897/300 0274214 Your Advantages For mobile generator sets according to DIN VDE 0100-551 Preventive fire and system protection Detection of symmetric

More information

ISOMETER IRDH575. Approvals

ISOMETER IRDH575. Approvals Insulation monitoring device for unearthed AC, DC and AC/DC systems (IT systems) with control and display function for EDS insulation fault location systems IRDH575_D00089_02_D_XXEN/09.2018 Insulation

More information

ATS-I USER MANUAL. Tecnoelettra srl Dal Via Vioni Dimo, S.Rocco di Guastalla (RE)

ATS-I USER MANUAL. Tecnoelettra srl Dal Via Vioni Dimo, S.Rocco di Guastalla (RE) USER MANUAL ATS-I Tel.+39.0522.832004 P1/17 ATS-I User manual Fax.+39.0522.832012 Tecnoelettra_EN.doc P.1/17 Index General description...3 Electrical specifics...3 Device operative logic...4 Manual mode...4

More information

10/2 Product overview. 10/3 4AC3 0, 4AC3 1 bell transformers. 10/5 4AC AC3 6 transformers for permanent loads. 10/8 4AC2 4 power supply units

10/2 Product overview. 10/3 4AC3 0, 4AC3 1 bell transformers. 10/5 4AC AC3 6 transformers for permanent loads. 10/8 4AC2 4 power supply units BETA Switching Transformers, Bells and Socket Outlets /2 Product overview /3 4AC3 0, 4AC3 1 bell transformers /5 4AC3 4... 4AC3 transformers for permanent loads /8 4AC2 4 power supply units / 7LQ2 2 bells

More information

ALPTEC POWER FACTOR CONTROLLER

ALPTEC POWER FACTOR CONTROLLER ALPTEC POWER FACTOR CONTROLLER ALPTEC3 ALPTEC5 ALPTEC7 ALPTEC12 0 REF : 2008-ALPTEC3.5.7.12-01-ANG CONTENTS I GENERAL INFORMATION. 2 II WAYS TO SET UP THE CONTROLLER.. 4 III OPERATING MODE..6 IV ADVANCED

More information

Earth Leakage Monitoring System IsoBase IsoHub IsoOut

Earth Leakage Monitoring System IsoBase IsoHub IsoOut 2014 11 21 Earth Leakage Monitoring System IsoBase IsoHub IsoOut User Manual Due to our policy of continual improvement, specifications may change without prior notice Page 2 (34) Contents Earth Leakage

More information

VFSC9 ELECTRONIC SPEED CONTROLLER. Mounting and operating instructions

VFSC9 ELECTRONIC SPEED CONTROLLER. Mounting and operating instructions ELECTRONIC SPEED CONTROLLER Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 5 WIRING

More information

Centrale de mesure Power Meter PM500 Merlin Gerin

Centrale de mesure Power Meter PM500 Merlin Gerin Notice d'installation et d'utilisation Installation and user manual Centrale de mesure Power Meter PM500 Merlin Gerin 059473_D Introduction and description Package contents c one PM500 power meter with

More information

Multifuncion Measuring Device, 4 mod. DIN, connection via CT, with RS485 port

Multifuncion Measuring Device, 4 mod. DIN, connection via CT, with RS485 port Viale Borri 231, 21100 Varese Italy Multifuncion Measuring Device, 4 mod. Contents Pages 1. Description Use... 2 2. Range... 2 3. Overall dimensions... 2 4. Preparation Connection... 2 5. General characteristics...

More information

Temperature Controller model MFC-301/T-Dry. Version for Dry Transformers and Motors. Technical Manual. Licht

Temperature Controller model MFC-301/T-Dry. Version for Dry Transformers and Motors. Technical Manual. Licht Temperature Controller model MFC-301/T-Dry Version for Dry Transformers and Motors Technical Manual Licht Contents 1 Introduction 2 2 Operating principle 3 2.1 General principle 3 2.2 RTD operation 3 3

More information

TOSHIBA International Corp

TOSHIBA International Corp TOSHIBA International Corp GUIDE SPECIFICATIONS THREE PHASE UNINTERRUPTIBLE POWER SYSTEM TOSHIBA 4200FA 30 kva CT Internal Battery UPS GUIDE SPECIFICATIONS 1 (30 kva CT) 1.0 SCOPE 1.1 System This specification

More information

ISOSCAN EDS460-DG. Insulation fault locator for DC IT systems with high system leakage capacitances

ISOSCAN EDS460-DG. Insulation fault locator for DC IT systems with high system leakage capacitances ISOSCAN Insulation fault locator for DC IT systems with high system leakage capacitances _D00108_00_D_XXEN/05.2015 ISOSCAN Insulation fault locator for DC IT systems with high system leakage capacitances

More information

AU INSTALLATION INSTRUCTIONS. Revision B1 Rapid City, SD, USA, 02/2010 II_201A-AU_B1

AU INSTALLATION INSTRUCTIONS. Revision B1 Rapid City, SD, USA, 02/2010 II_201A-AU_B1 INSTALLATION INSTRUCTIONS Revision B1 Rapid City, SD, USA, 02/2010 MODELS 201A-AU 201-575-AU II_201A-AU_B1 2880 North Plaza Drive, Rapid City, South Dakota 57702 (800) 843-8848 (605) 348-5580 fax (605)

More information

RETROFITTING. Motor Protection Relay. Two mountings are available, Flush Rear Connection (EDPAR) or Projecting Rear Connection (SDPAR).

RETROFITTING. Motor Protection Relay. Two mountings are available, Flush Rear Connection (EDPAR) or Projecting Rear Connection (SDPAR). RETROFITTING Motor Protection Relay NPM800R (R2 case) and NPM800RE (R3 case) are dedicated to the refurbishment of 7000 series (R2 and R3 cases) of CEE relays providing the protection of medium voltage

More information

Metaphase ULC-2. Technologies ULC. Metaphase. Technologies Version 7.X August 2015 USER MANUAL. metaphase-tech.com. pg. 1

Metaphase ULC-2. Technologies ULC. Metaphase. Technologies Version 7.X August 2015 USER MANUAL. metaphase-tech.com. pg. 1 ULC Version 7.X August 2015 USER MANUAL pg. 1 Overview Universal LED Controller () provides independent true constant-current or voltage control of two LED loads from 0.02 to 4 Amps continuous (DC) with

More information

INSTRUCTION MANUAL. Power Factor Controller - 12 steps Model A12 NOKIAN CAPACITORS. Power Factor Controller A12

INSTRUCTION MANUAL. Power Factor Controller - 12 steps Model A12 NOKIAN CAPACITORS. Power Factor Controller A12 INSTRUCTION MANUAL Power Factor Controller - 12 steps Model A12 NOKIAN CAPACITORS Power Factor Controller A12 1. CONTENTS 1. CONTENTS 1 2. FEATURES 2 3. INSTALLATION, CONNECTION AND APPLYING POWER 2 4.

More information

3 - Protection components Circuit-breakers

3 - Protection components Circuit-breakers Contents - Protection components Circuit-breakers for the motor protection Selection guide..............................................page /2 Thermal-magnetic motor circuit-breakers Selection guide..............................................page

More information

Protection relays and transformers

Protection relays and transformers NEW ZEALAND WWW.LPINZ.CO.NZ Unit 6/22 Moselle Ave, Henderson, Auckland, New Zealand PO Box 21-872, Henderson, Auckland, New Zealand Phone:+64 9 833 5749 Email:info@LPINZ.co.nz Web: www.lpinz.co.nz Protection

More information

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax:

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax: Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 65 35305 Grünberg Tel.: 06401 807-0 Fax: 06401 807-259 Insulation fault locator Insulation fault locator for DC IT systems with high system leakage capacitances

More information

PLA 33. Power line analyzer. User and service manual. version 2.4

PLA 33. Power line analyzer. User and service manual. version 2.4 PLA 33 Power line analyzer User and service manual version 2.4 Content. Front control panel and terminal plate...3 7.2.2. System frequency setting...0 2. Device description...4 7.2.3. Password protection...0

More information

Instruction. Actuator ICAD 600 / ICAD 900 / ICAD 1200 ICAD 600 ICAD 900 ICAD 1200 ICAD 600 ICAD 900. ICAD 1200 Fig. 2. Fig. 4

Instruction. Actuator ICAD 600 / ICAD 900 / ICAD 1200 ICAD 600 ICAD 900 ICAD 1200 ICAD 600 ICAD 900. ICAD 1200 Fig. 2. Fig. 4 Instruction 027R9796 027R9796 Actuator ICAD 600 / ICAD 900 / ICAD 1200 ICAD 600 ICAD 900 ICAD 1200 ICAD 600 ICAD 900 ICAD 1200 Fig. 1 Fig. 2 Note: When mounting the ICAD make sure to push ICAD down to

More information

XUA1 AC Voltage and phase balance relay. (August 1996) Manual XUA1 (Revision New)

XUA1 AC Voltage and phase balance relay. (August 1996) Manual XUA1 (Revision New) XUA1 AC Voltage and phase balance relay (August 1996) Manual XUA1 (Revision New) Woodward Manual XUA1 GB Woodward Governor Company reserves the right to update any portion of this publication at any time.

More information

Thermistor motor protection relays

Thermistor motor protection relays Thermistor motor protection relays Content Benefits and advantages... / 68 Selection table... / 68 Ordering details CM-MSE... / 69 CM-MSS... / 69 CM-MSN... / 7 PTC sensor C0... / 7 Technical data... /

More information

Multifuncion Measuring Device, 4 mod. DIN, connection via CT, with RS485 port

Multifuncion Measuring Device, 4 mod. DIN, connection via CT, with RS485 port 87045 LIMOGES Cedex Telephone : 05 55 06 87 87 Fax: 05 55 06 88 88 Multifuncion Measuring Device, 4 mod. Contents Pages 1. Description Use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation Connection...

More information

COUNTIS E27/E28 Three-phase energy meter Direct - 80 A Ethernet

COUNTIS E27/E28 Three-phase energy meter Direct - 80 A Ethernet INSTRUCTION MANUAL COUNTIS E27/E28 Three-phase energy meter Direct - 80 A Ethernet EN countis e27 countis e28 - mid www.socomec.com/ en/countis-e2x EN Contents 1. Documentation.... 3 2. Hazards and warnings...

More information

COUNTIS E23. Three-phase energy meter Direct - 80 A MODBUS. Instruction manual. en/countis-e2x

COUNTIS E23. Three-phase energy meter Direct - 80 A MODBUS. Instruction manual.   en/countis-e2x Instruction manual COUNTIS E23/E24 Three-phase energy meter Direct - 80 A MODBUS COUNTIS E23 COUNTIS E24 - MID www.socomec.com/ en/countis-e2x Contents 1. Documentation.... 3 2. Hazards and warnings...

More information

Protection and safety SQZ3 phase and sequence relay

Protection and safety SQZ3 phase and sequence relay SQZ3 phase and sequence relay Supply voltage [Vn] 400 V a.c. Frequency [Hz] 0/60 SQZ3 2CSC4001F0201 Contact type [A] 1 CO, 20 V, 10 A (cos =1) safety switching Minimum voltage adjustment trimmer [%] 100

More information

DIN 22.5/17.5 Size Lineup of A Wide Range of Measuring and Monitoring Relays. Model Number Structure

DIN 22.5/17.5 Size Lineup of A Wide Range of Measuring and Monitoring Relays. Model Number Structure New Product News Measuring & Monitoring Relays K8AK/K8DS Series DIN 22.5/17.5 Size Lineup of A Wide Range of Measuring and Monitoring Relays Compact 22.5 mm and 17.5 mm housings Resistant to high-frequency

More information

Metaphase ULC-2. Technologies ULC. Metaphase. Technologies Version 6.2 June 12, 2013 USER MANUAL. metaphase-tech.com. pg. 1

Metaphase ULC-2. Technologies ULC. Metaphase. Technologies Version 6.2 June 12, 2013 USER MANUAL. metaphase-tech.com. pg. 1 ULC Version 6.2 June 12, 2013 USER MANUAL pg. 1 Overview Universal LED Controller () provides independent true constant-current or voltage control of two LED loads from 0.02 to 4 Amps continuous (DC) with

More information

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax :

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax : NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata - 700 032, Tel : 033 2477 3126; Fax : 033 2477 2403 www.ntplindia.com SPECIFICATION NTPL MAKE MICRO-CONTROLLER BASED AUTOMATIC 50KV/10A AC HIGH VOLTAGE

More information

TAC ATV38, IP55. Variable Speed Drives for Asynchronous Motors. 3-phase. 380/460 V, Hz

TAC ATV38, IP55. Variable Speed Drives for Asynchronous Motors. 3-phase. 380/460 V, Hz TAC ATV8, IP55 Variable Speed Drives for Asynchronous Motors. -phase. 80/460 V, 50-60 Hz E-60-24 24 May 2004 ATV 8 IP55 drives are specifically designed for pump and fan applications powered by a three-phase

More information

ISOMETER iso685- -B. Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) Preliminary data sheet

ISOMETER iso685- -B. Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) Preliminary data sheet Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) Preliminary data sheet iso685-x-b_d00177_04_d_xxen/04.2018 Insulation monitoring device for unearthed AC, AC/DC and DC systems

More information

NX Series Inverters. HVAC Pocket Programming Guide

NX Series Inverters. HVAC Pocket Programming Guide NX Series Inverters HVAC Pocket Programming Guide HVAC Pocket Programming Guide HVAC Pocket Programming Guide / Contents This guide provides a single reference document for the user of NXL HVAC (product

More information

CONTROL MANUAL. Dry-Pic 09PE - 09VE

CONTROL MANUAL. Dry-Pic 09PE - 09VE CONTROL MANUAL Dry-Pic 09PE - 09VE Translation of the original document 003, 04.01 EN CONTENTS PAGE 1 - IMPORTANT RECOMMENDATIONS 1.1 Power supply 1. Electronic board specifications 1.3 Caution 1.4 Earth

More information

STEP-UPS/24DC/24DC/3. Uninterruptible power supply. Data sheet. 1 Description. Features

STEP-UPS/24DC/24DC/3. Uninterruptible power supply. Data sheet. 1 Description. Features Uninterruptible power supply Data sheet 105623_en_00 PHOENIX CTACT 2013-06-07 1 Description Uninterruptible power supply units continue to deliver power even in the event of mains breakdowns or failures.

More information

Installation and Operating Instructions. Power IT Power Factor Controller RVC

Installation and Operating Instructions. Power IT Power Factor Controller RVC Installation and Operating Instructions Power IT Power Factor Controller RVC Table of contents Page 1. Read this first... 3 About this Instruction Manual... 3 Safety... 3 Electromagnetic compatibility...

More information

INSTALLATION MANUAL. Model: Smart Analyzer Manufacturer: Smart Impulse. Power meter with consumption breakdown by use 03/12/13

INSTALLATION MANUAL. Model: Smart Analyzer Manufacturer: Smart Impulse. Power meter with consumption breakdown by use 03/12/13 INSTALLATION MANUAL Model: Smart Analyzer Manufacturer: Smart Impulse Power meter with consumption breakdown by use 03/12/13 Table of contents Table of contents... 2 1. Introduction... 3 2. Installation

More information

AC/DC. Monitoring Technique. VARIMETER IMD Insulation monitor RN 5897/020

AC/DC. Monitoring Technique. VARIMETER IMD Insulation monitor RN 5897/020 Monitoring Technique VARIMETER IMD Insulation monitor RN 5897/020 0277078 RN 5897/020 RP 5898 Product Description The insulation monitor RN 5897/020 of the VARIMETER IMD family provides best and up to

More information

ES-777-MV-P2_A1 03/01/10

ES-777-MV-P2_A1 03/01/10 ENGINEERING SPECIFICATION SYMCOM MODEL 777-MV-P2 Electronic Overload Relay PART 1 GENERAL 1.1 REFERENCES A. UL 508 Industrial Control Equipment Underwriters Laboratories B. IEC 60947 Low Voltage Switchgear

More information

02/11/2015

02/11/2015 Modem communication plug and play solutions GSM Part number 88970119 For remote control of your application Automatic notification of alarms via SMS (GSM Modem) / email or on a PC with M3 ALARM software.

More information

Catalog 200 Contactors up to 115 A Motor Starters up to 55 kw 03/2009

Catalog 200 Contactors up to 115 A Motor Starters up to 55 kw 03/2009 Catalog 00 Contactors up to 5 A Motor Starters up to 55 kw 03/009 Kraus & Naimer The development of the Blue Line rotary switch, contactor and motor starter product ranges is based on more than hundred

More information

Modular equipment. Presentation, standards. Standard contactors TeSys GC

Modular equipment. Presentation, standards. Standard contactors TeSys GC Presentation, standards Standard contactors TeSys GC Presentation TeSys GC contactors are designed for use in modular panels and enclosures. These contactors feature: b Easy installation v quick clip-on

More information

CS-200. PORTABLE TRAFFIC LIGHT CONTROLLER (Software 1.05) OPERATION AND SERVICE MANUAL

CS-200. PORTABLE TRAFFIC LIGHT CONTROLLER (Software 1.05) OPERATION AND SERVICE MANUAL CS-200 PORTABLE TRAFFIC LIGHT CONTROLLER (Software 1.05) OPERATION AND SERVICE MANUAL CS-200 Operation and Service Manual Page 2 Manufactured by: LINCAST INTERNATIONAL PTY. LTD. 2/3 Sir Laurence Drive

More information

Contents. Introduction and description Package contents Device identification PM Options... 80

Contents. Introduction and description Package contents Device identification PM Options... 80 Contents 1 Introduction and description Package contents... 77 Device identification... 77 2 Characteristics PM500... 78 Options... 80 3 Installation Front-panel cut-out... 82 Mounting... 82 4 Connections

More information

EIB/KNX Switch Actuators. User manual

EIB/KNX Switch Actuators. User manual EIB/KNX Switch Actuators User manual IT KNT 004 IT KNT 012 Tel.: +34943627988 E-mail: knx@dinuy.com Web: www.dinuy.com Contents 1. Introduction --------------------------------------------------------------------------------------------------------------

More information

90 ReStart AUTOMATIC RECLOSING DEVICES

90 ReStart AUTOMATIC RECLOSING DEVICES RESTART WITH AUTOTEST Technical data TYPE ReStart with Autotest 2P ReStart with Autotest PRO 2P ReStart with Autotest PRO 4P Electrical characteristics Standards: EN 50557, EN 61008-1 Distribution system:

More information

RI-F200 Series. Single and Three Phase Multifunction Energy Meter. Telephone : +44 (0) Displayed Parameters

RI-F200 Series. Single and Three Phase Multifunction Energy Meter. Telephone : +44 (0) Displayed Parameters RI-F200 Series Single and Three Phase Multifunction Energy Meter DIN 96 panel mounted -/1A or -/5A current transformer input Single phase or three phase network compatible Programmable voltage and current

More information

Siemens AG Allows easy and consistent configuration with one series of overload relays (for small to large loads)

Siemens AG Allows easy and consistent configuration with one series of overload relays (for small to large loads) Overview Features Benefits 3RU11 3RB20/3RB21 3RB22/3RB23 Sizes Are coordinated with the dimensions, connections S00...S3 S00... S12 S00... S12 and technical characteristics of the other devices in the

More information

3 PHASE ENERGY ELECTRONIC METERS MKT & MKT2. (Code to ) INSTRUCTION MANUAL ( M / 00 A ) (c) CIRCUTOR S.A.

3 PHASE ENERGY ELECTRONIC METERS MKT & MKT2. (Code to ) INSTRUCTION MANUAL ( M / 00 A ) (c) CIRCUTOR S.A. 3 PHASE ENERGY ELECTRONIC METERS MKT & MKT2 (Code 7 71 071 to 7 71 083) INSTRUCTION MANUAL ( M 981 200 / 00 A ) (c) CIRCUTOR S.A. ----- MKT- MKT2 - ELECTRONIC METERS -------- M-981 200 --- Page Nº 2 3

More information

Multifunction network analyzer Q15U Q96U2L - Q96U4... Q15E Q96E MCU - MCUH Programmable transducer MCUU

Multifunction network analyzer Q15U Q96U2L - Q96U4... Q15E Q96E MCU - MCUH Programmable transducer MCUU Multifunction network analyzer Q15U2... - Q96U2L - Q96U4... Q15E2... - Q96E2... - MCU - MCUH Programmable transducer MCUU OPERATING MANUAL Ipm0163.8 - Edition 06.09 Langer Messtechnik GmbH Soyerhofstrasse

More information

PRELIMINARY DATA SHEET RI-D140. Three Phase Multifunction DIN Rail Energy Meter (MID Certified) MID

PRELIMINARY DATA SHEET RI-D140. Three Phase Multifunction DIN Rail Energy Meter (MID Certified) MID RI-D140 Three Phase Multifunction DIN Rail Energy Meter (MID Certified) Four module DIN rail mounted Energy pulse LED True RMS measurement Cost effective and accurate Modbus communication -/1A or -/5A

More information

Single and Dual Preset Counters Hengstler signo 721 series

Single and Dual Preset Counters Hengstler signo 721 series Instruction Leaflet Issued September 1996 8847 Single and Dual Preset Counters Hengstler signo 721 series Operating instructions RS stock no. No. of presets Supply voltage range Type of output Hengstler

More information

ABB NEW. Multifunctional three-phase monitoring relays. CM-MPS.23 and CM-MPS.43 Data sheet. Features J. Approvals. Marks.

ABB NEW. Multifunctional three-phase monitoring relays. CM-MPS.23 and CM-MPS.43 Data sheet. Features J. Approvals. Marks. 2CDC 251 052 F0t08 CM-MPS.23 2CDC 251 053 F0t08 CM-MPS.43 - relay status, timing - fault message - fault message Adjustment of the tripping delay t V Adjustment of the threshold value for overvoltage 6

More information

XUA1 - AC Voltage and phase balance relay

XUA1 - AC Voltage and phase balance relay XUA1 - AC Voltage and phase balance relay Contents 1. Applications and features 2. Design 3. Function 3.1 Voltage supervision 3.2 Unbalanced voltage supervision 4. Operation and settings 4.1 Setting of

More information

(1,5 modules per pole)

(1,5 modules per pole) 87045 LIMOGES Cedex Telephone: +33 5 55 06 87 87 FAX: +33 5 55 06 88 88 DX 3 MCB 25kA 80A to 125A CONTENTS PAGES 1. Description - Use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...

More information

Analogue temperature controllers

Analogue temperature controllers Analogue temperature controllers CT8A Input by J-K thermo-couple or by thermo-resistance Pt 00 (-wire) regulation modes : ON/OFF or proportional derivative selected by wiring Relay output Specifications

More information

Power connections, minimum and maximum wiring capabilities, tightening torque

Power connections, minimum and maximum wiring capabilities, tightening torque Wiring - power terminals Power Observe the cable cross-sectional areas recommended in the standards. The soft starter must be grounded to conform to the regulations concerning leakage currents. If the

More information

Motorised unit Changeover switch installation and operation guide. Ref. 4257Z001 Rev. 05

Motorised unit Changeover switch installation and operation guide. Ref. 4257Z001 Rev. 05 Ref. 4257Z001 Rev. 05 Motorised unit Changeover switch installation and operation guide Edition September 2007 Index Please follow carefully the instructions included in this manual for a correct installation

More information

XR1 Rotor Earth Fault Relay. (May 2007) Manual XR1 (Revision New)

XR1 Rotor Earth Fault Relay. (May 2007) Manual XR1 (Revision New) XR1 Rotor Earth Fault Relay (May 2007) Manual XR1 (Revision New) Woodward Manual XR1 GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information provided

More information

EY-EM 527: Remote I/O module, ecolink527

EY-EM 527: Remote I/O module, ecolink527 Product data sheet 94.078 EY-EM 527: Remote I/O module, ecolink527 How energy efficiency is improved Regulation, control, monitoring and optimisation of operational systems, e.g. room automation or HVAC

More information

RISH EM 3490 SS Kilowatt Hour Energy Meter With Rs485 RISH EM 3490 SS. Application : Product Features: Indication: Pulse Indication:

RISH EM 3490 SS Kilowatt Hour Energy Meter With Rs485 RISH EM 3490 SS. Application : Product Features: Indication: Pulse Indication: Application : RISH Master 3490 SS is a 96mm x 96mm panel mounted kilowatt hour meter it measures active energy with class 1.0 accuracy having auto-resetting 8 digit seven segment LED counter. The unit

More information

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Furnish and install automatic transfer switches (ATS) with number of poles, amperage, voltage, and withstand

More information

Electronic Circuit Breaker ESS1 for System SVS1

Electronic Circuit Breaker ESS1 for System SVS1 Electronic Circuit Breaker for System SVS Description The electronic circuit breaker is designed to ensure selective disconnection of individual s in industrial systems which are powered by a DC 24 V switch

More information

3-phase meter with direct connection and pulse or Modbus RS485 output

3-phase meter with direct connection and pulse or Modbus RS485 output 87045 LIMOGES Cedex Telephone: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 3-phase meter with direct connection and CONTENTS PAGES 1. Description, usage... 1 2. Range... 1 3. Dimensions... 1 4. Positioning...

More information

Portable Appliance Testers. OmegaPAT MI 2140 BetaPAT MI 2141 User Manual Ver Code No

Portable Appliance Testers. OmegaPAT MI 2140 BetaPAT MI 2141 User Manual Ver Code No Portable Appliance Testers OmegaPAT MI 2140 BetaPAT MI 2141 User Manual Ver. 1.2. Code No. 20 750 684 Distributor: Producer: METREL d.d. Ljubljanska 77 SI-1354 Horjul E-mail: metrel@metrel.si http://www.metrel.si

More information

DIRIS A40/A41 RS485 PROFIBUS DP. Operating instructions F GB D I NL E P. SOCOMEC GROUP switching PROTECTION & ups

DIRIS A40/A41 RS485 PROFIBUS DP. Operating instructions F GB D I NL E P. SOCOMEC GROUP switching PROTECTION & ups DIRIS A40/A41 RS485 PROFIBUS DP Operating instructions F GB D I NL E P SOCOMEC GROUP switching PROTECTION & ups 2 DIRIS A20 - Réf. : 536 182 A GB 876_786_A_gb.indd 2 3/04/09 10:50:47 GB Contents PRELIMINARY

More information

PHOENIX CONTACT

PHOENIX CONTACT Electronic circuit breaker CLIPLINE Data sheet 102898_en_03 PHOENIX CONTACT 2010-12-17 1 Description The electronic circuit breaker can be used in applications that cover all aspects of the switched-mode

More information

12/2 Product overview. 12/3 7KT1 14, 7KT1 53 E-counters. 12/9 7KT1 11, 7KT1 12 digital measuring devices. 12/11 7KT1 0 analog measuring devices

12/2 Product overview. 12/3 7KT1 14, 7KT1 53 E-counters. 12/9 7KT1 11, 7KT1 12 digital measuring devices. 12/11 7KT1 0 analog measuring devices BETA Measuring /2 Product overview /3 7KT1 14, 7KT1 53 E-counters /9 7KT1 11, 7KT1 digital measuring devices /11 7KT1 0 analog measuring devices / 7KT5 8 time and pulse counters /14 7KT5 5, 7KT5 6 time

More information

CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. UL 508, CAN/CSA C22.2 No.14 GL GOST CB scheme CCC

CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. UL 508, CAN/CSA C22.2 No.14 GL GOST CB scheme CCC 2CDC 251 048 F0t08 CM-MPS.11 2CDC 251 049 F0t08 CM-MPS.21 Features Monitoring of three-phase mains for phase sequence (can be switched off), phase failure, over- and undervoltage as well as phase unbalance

More information

ISOMETER iso685- Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems)

ISOMETER iso685- Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) iso685-x_d00022_08_d_xxen/04.2018 Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) Product

More information

Electronic relays. Monitoring. Monitoring

Electronic relays. Monitoring. Monitoring Electronic relays Neither overload nor underload are particularly good for machines and installations in industrial applications. An unsteady power supply may lead to machine failure and, thus, expensive

More information

RI-D440. Three Phase easywire Multifunction DIN Rail Energy Meter. Telephone : +44 (0) Displayed Parameters

RI-D440. Three Phase easywire Multifunction DIN Rail Energy Meter. Telephone : +44 (0) Displayed Parameters RI-D440 Three Phase easywire Multifunction DIN Rail Energy Meter Four module DIN rail mounted Energy pulse LED 330mV Input from easywire CTs (or -/1A and -/5A current transformer input with TAS-SCTEWA

More information

Energy counting and measurement

Energy counting and measurement Energy counting In the current context of research of energy saving, counting of consumption become unavoidable. Hager offers new residential and tertiary solutions, to better control energy consumption.

More information

Computer-14d - xx - 144a

Computer-14d - xx - 144a POWER FACTOR REGULATOR Computer-14d - xx - 144a INSTRUCTION MANUAL ( M 981 602 / 98B ) (c) CIRCUTOR S.A. -------- POWER FACTOR REGULATOR COMPUTER- 14d --------- Page 2 1.- POWER FACTOR REGULATORS COMPUTER-14d-144a

More information

Capacitor Switching Contactors

Capacitor Switching Contactors Capacitor Switching D385E51 Technical catalogues and news under: www.benedict.at Motor-Starter Mini- Overload Relays Capacitor Switching Motor-Starters Modular Circuit Breakers M4-32T... up to 32A M4-32R..

More information

DIRIS A40/A41 RS485 PROFIBUS DP COM. Operating instructions. PROFIBUS Certification

DIRIS A40/A41 RS485 PROFIBUS DP COM. Operating instructions. PROFIBUS Certification DIRIS A40/A41 RS485 PROFIBUS DP Operating instructions F GB D I NL E P ON 1 COM PROFIBUS Certification SOCOMEC GROUP SWITCHING PROTECTION & UPS Systèmes de Coupure et de Protection Industrial Switching

More information

SUPPLY NETWORK ANALYZER CVM-96 SERIES

SUPPLY NETWORK ANALYZER CVM-96 SERIES SUPPLY NETWORK ANALYZER CVM-96 SERIES (Power Demand) INSTRUCTION MANUAL ( M 981 326 / 00B - GB) (c) CIRCUTOR S.A. ----- Supply network analyzer CVM-96 ------ User's manual --- Page No. 1 CVM-96 SUPPLY

More information

PHOENIX CONTACT - 03/2007

PHOENIX CONTACT - 03/2007 Inline Function Terminal for Pulse Width Modulation and Frequency Modulation N AUTOMATIONWORX Data Sheet 6920_en_01 1 Description PHOENIX CONTACT - 03/2007 $ ' ) The terminal is designed for use within

More information

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency echnical data sheet SVK24A--PC Communicative globe valve actuator with emergency control function for 2-way and 3-way globe valves Actuating force 1500 N Nominal voltage AC/DC 24 V Control modulating,

More information

NSD Safety Mat Controller Modules Both Modules are compliant to OSHA & ANSI Standards - EN ISO EN EN 81-1 EN NSD VDC

NSD Safety Mat Controller Modules Both Modules are compliant to OSHA & ANSI Standards - EN ISO EN EN 81-1 EN NSD VDC Datasheet NSD Safety Mat Controller Modules Both Modules are compliant to OSHA & ANSI Standards - EN ISO 13849-1 EN 62061 EN 81-1 EN 50156-1 Approvals NSD-3580 24 VDC NSD-3590 115 TO 230 VAC Technical

More information

XP2-R Power and reverse power relay. (January 2006) Manual XP2-R (Revision New)

XP2-R Power and reverse power relay. (January 2006) Manual XP2-R (Revision New) XP2-R Power and reverse power relay (January 2006) Manual XP2-R (Revision New) Woodward Manual XP2-R GB Woodward Governor Company reserves the right to update any portion of this publication at any time.

More information

02/11/2015

02/11/2015 Modem communication plug and play solutions GSM Part number 88970119 For remote control of your application Automatic notification of alarms via SMS (GSM Modem) / email or on a PC with M3 ALARM software.

More information

Actuator ICAD 600A / ICAD 600A-TS / ICAD 1200A

Actuator ICAD 600A / ICAD 600A-TS / ICAD 1200A Installation Guide Actuator ICAD 600A / ICAD 600A-TS / ICAD 1200A 027R9966 ICAD 600A ICAD 600A-TS ICAD 1200A 027R9966 ICAD 600A / ICAD 600A-TS ICAD 1200A Fig. 1 Fig. 2 Note: When mounting the ICAD make

More information

ENA33LCD. Power line analyzer. User and service manual. Obrezija 5 SI-1411 Izlake

ENA33LCD. Power line analyzer. User and service manual.   Obrezija 5 SI-1411 Izlake ENA33LCD Power line analyzer User and service manual version 2.9 (FW version 6.8 and newer) ETI, d.o.o. Obrezija 5 SI-1411 Izlake www.etigroup.eu/products-services 1. Front control panel and terminal plate

More information

English RACON SERIES II RADIO CONTROL SERVICE MANUAL

English RACON SERIES II RADIO CONTROL SERVICE MANUAL English 22.2.2007 RACON SERIES II RADIO CONTROL SERVICE MANUAL Read the instructions supplied with the product before installation and commissioning. Keep the instructions in a safe place for future reference.

More information

VSD Series II Variable Speed Micro Drives (VSM II) FS1 FS5

VSD Series II Variable Speed Micro Drives (VSM II) FS1 FS5 New Information Electric Current! Danger to Life! Only skilled or instructed persons may carry out the following operations. Variable Speed Micro Drives for Machinery Applications () VSxxx0_, VSxxx2x4_,

More information

Reactive Power Control Relay RM 2106 / 2112 Operating Instructions. FRAKO Kondensatoren- und Anlagenbau

Reactive Power Control Relay RM 2106 / 2112 Operating Instructions. FRAKO Kondensatoren- und Anlagenbau Reactive Power Control Relay RM 2106 / 2112 Operating Instructions FRAKO Kondensatoren- und Anlagenbau www.frako.com Figure 1 Front view a b c d e Display for active capacitor stages Display for inductive

More information

ISOLGUARD HIG97 version 4 insulation monitoring device

ISOLGUARD HIG97 version 4 insulation monitoring device ISOLGUARD HIG97 version 4 insulation monitoring device The HAKEL HIG97 version 4 insulation monitoring device, falling in the ISOLGUARD product range, is designed to monitor the insulation status of three-phase

More information

AEROCONNECT 1B NA C Control manual

AEROCONNECT 1B NA C Control manual AEROCONNECT 1B NA 11.3 C 03-01 Control manual EN CONTENTS PAGE 1 - IMPORTANT RECOMMENDATIONS 1.1 Power supply 1. Electronic board specifications 1.3 Caution 1.4 Earth 1. Sensor connections 1.6 Communication

More information

SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS

SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS ELECTRICAL ENGINEERING DIVISION Distribution Network Department SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS ELA T150.2 en SRA 2250/6 Resistor specification The SRA 2250/6 Resistor is intended to increase

More information

Original operating instructions Fail-safe inductive sensor GM504S / / 2010

Original operating instructions Fail-safe inductive sensor GM504S / / 2010 Original operating instructions Fail-safe inductive sensor GM504S 704070 / 01 06 / 2010 Contents 1 Preliminary note 3 1.1 Explanation of symbols 3 2 Safety instructions 4 2.1 Safety-related requirements

More information

ABB 1. Multifunctional three-phase monitoring relays. CM-MPN.52, CM-MPN.62 and CM-MPN.72 Data sheet. Features. Approvals. Marks.

ABB 1. Multifunctional three-phase monitoring relays. CM-MPN.52, CM-MPN.62 and CM-MPN.72 Data sheet. Features. Approvals. Marks. 2CDC 251 054 F0t08 CM-MPN.52 2CDC 251 055 F0t08 CM-MPN.62 2CDC 251 056 F0t08 CM-MPN.72 Features Monitoring of three-phase mains for phase sequence (can be switched off), phase failure, over- and undervoltage

More information