SOCOMEC - Réf.: A

Size: px
Start display at page:

Download "SOCOMEC - Réf.: A"

Transcription

1 34

2 THE ATyS RAGE The ATyS family proposes a complete motorised changeover range including electrical and mechanical interlocking. Manual operation is always possible on all the products in case of emergency. The electric command is realised via a motorised module, electronically driven by types of logic: Remote controlled: ATyS 3 products are controlled by volt free contacts allowing the switch to be driven in, 0 or position. These contacts can come from an external control logic. Automatic control: AtyS 6 products integrate all controls, timers and relays required to realise a ormal/ Emergency application. ATyS 6e and 6m versions also integrate the remote controlled feature. The motorised and control modules can easily be replaced without disconnecting the power cables. ATyS 3s ATyS 3e ATyS 6s ATyS 6e ATyS 6m ATyS C30 ATyS C0 MOTORISED CHAGEOVER Dual power supply Integrated control relay Control relay for changeover Metering Com option Communication option I/ O option inputs/ outputs option Remote interfaces ATyS D0 & D0 > This instruction manual applies to following products: Control relay ATyS C0/C30 > Following products are delivered with their own instruction manual: ATyS 3s ATyS 3e, 6s, 6e ATyS 6m Remote interfaces ATyS D0 & D0 35

3 GEERAL PRESETATIO ATyS C0/C30 Product introduction Product introduction ATYS C0 LCD Control terminals Modular frame ATYS 446 A Voltage sensing and power supply terminals Keypad ATYS C30 LCD Control terminals Modular frame ATYS 445 A RJ45 terminal Voltage sensing and power supply terminals Keypad 36

4 ISTALLATIO ATyS C0/C30 Mounting Dimensions Characteristics Mounting > Mounting rail DI Dimensions ,5 ATYS 437 A ATYS 436 A Characteristics > IP IP and class II on front face > Operation Temperature: -0 C to +60 C Humidity: 80% at 55 C 95% at 40 C 37

5 COECTIOS ATyS C0/C30 Control circuits Electrical operation Control circuits 400 Vac (P-P) APPLICATIO WITH EUTRAL CODUCTOR SWITCHIG TYPE TECHOLOGY Configure the type of control logic in impulse mode (see chapter). LOAD L L L3 L L L3 F F F, F Fuse protection 30 Vac 5 A DPS Ph Power 30 Vac Double Power Supply option Control I II 0 C CA CA0 CA I I GE O DC-*DC+* OLY O ATyS C30 ATyS D0 or D0 remote interface Cable RJ45 8/8 03 L3 04 L 05 L 06 L 03 L3 05 ATYS 46 A GB * Only on DC versions. Maximum control cables lenght = 0 m. In case of longer distance, insert control relays. Remote interfaces maximum connection cable (RJ45) = 3 m. 38

6 COECTIOS Control circuits 400 Vac (P-P) APPLICATIO WITH EUTRAL CODUCTOR COTACTOR TYPE TECHOLOGY Configure the type of control logic in contactor (see chapter). LOAD L L L3 L L L3 F F K K K K F, F Fuse protection 30 Vac 5 A I II O O I I GE DC-*DC+* OLY O ATyS C30 ATyS D0 or D0 remote interface Cable RJ45 8/8 03 L3 04 L 05 L 06 L 03 L3 05 ATYS 438 A GB * Only on DC versions. Maximum control cables lenght = 0 m. In case of longer distance, insert control relays. Remote interfaces maximum connection cable (RJ45) = 3 m. 39

7 COECTIOS ATyS C0/C30 Control circuits Electrical operation Control circuits 400 Vac (P-P) APPLICATIO WITH EUTRAL CODUCTOR CIRCUIT BREAKER TYPE ELECTRICAL ITERLOCKIG VIA EXTERAL COTROL RELAYS Configure the type of control logic in contactor (see chapter). LOAD L L L3 L L L3 F F POS closing POS opening POS closing POS opening AUXILIARY COTACT BRE. BRE. F, F Fuse protection 30 Vac 5 A K K K K I II O O I I GE DC-* DC+* OLY O ATyS C30 ATyS D0 or D0 remote interface Cable RJ45 8/8 03 L3 04 L 05 L 06 L 03 L3 05 ATYS 439 A GB * Only on DC versions. Maximum control cables lenght = 0 m. In case of longer distance, insert control relays. Remote interfaces maximum connection cable (RJ45) = 3 m. 40

8 COECTIOS Control circuits 400 Vac (P-P) APPLICATIO WITH EUTRAL CODUCTOR CIRCUIT BREAKER TYPE ELECTRICAL ITERLOCKIG OT ITEGRATED Configure the type of control logic in contactor (see chapter). This drawing is not including the electrical interlock. LOAD L L L3 L L L3 F BREAKER F Closing Opening F, F Fuse protection 30 Vac 5 A BREAKER Closing Opening I I GE DC-* DC+* OLY O ATyS C30 ATyS D0 or D0 remote interface Cable RJ45 8/8 03 L3 04 L 05 L 06 L 03 L3 05 ATYS 440 A GB * Only on DC versions. Maximum control cables lenght = 0 m. In case of longer distance, insert control relays. Remote interfaces maximum connection cable (RJ45) = 3 m. 4

9 COECTIOS ATyS C0/C30 Control circuits Electrical operation Control circuits Denomination Terminals Description Characteristics Recommended section Power supply (03) eutral 440 V ac (phase-phase).5 mm Source L3 (04) Phase 3 maximum L (05) Phase 54 V ac (phase neutre) L (06) Phase maximum Power supply L (03) Phase 400 V ac (phase-phase).5 mm Source L3 (05) Phase 3 maximum Power supply DC () DC- Power supply 0 V From 9 V dc to 30 V dc.5 mm Vdc, 4Vdc DC+ Power supply +V dc Genset () 3 Genset start/stop relay - stable positions Dry contact.5 mm start signal 4 Programmable state - factory setting = O, close to start 5A AC/50 V Control 3 Impulse mode: order to close source 5 A AC/50 V (impulse, 4 Contactor mode: order to close contactor source contactor Breaker mode: order to close breaker source and breaker 33 Impulse mode: order to close source 5 A AC/50 V.5 mm mode to 34 Contactor mode: order to close contactor source programm) Breaker mode: order to open breaker source 43 Impulse mode: order to close position 0 5 A AC/50 V.5 mm 44 Contactor mode: programmable relay O Breaker mode: order to close breaker source 53 Impulse mode: programmable relay O 5 A AC/50 V.5 mm 54 Contactor mode: programmable relay O Breaker mode: order to open breaker source Information 30 Auxiliary contact information position CA Do not connect to.5 mm auxiliary 30 Auxiliary contact information position 0 CA0 any power supply contacts 303 Auxiliary contact information position CA Programmable 304 Programmable input Do not connect to.5 mm Inputs 305 Programmable input any power supply Common 36 Specifique voltage supply Do not connect to.5 mm input Common terminals 30 to 30 any power supply Remote interface RJ Remote interface ATyS D0 or D0 Maximum connection RJ45 8/8 connection cable 3 m () Only on DC version () Refer to programming, Setup, to modify relay state. 4

10 COECTIOS Electrical operation POWER SUPPLY ATyS C0/ C30 integrate power inputs (04-06, 03-05), and consider the available soure to keep the product operational. Product supplied when voltage on terminals 00 Vac For the DC version, these is only one power supply input (DC-, DC+). ATYS 444 A GB AUT position priority power source backup power source product O : terminals : terminals

11 OPERATIO ATyS C0/C30 Presentation Operational modes Operation Visualisation Automatic sequences Presentation The product allows: sources control, automatic transfer control in AUT mode, parameters configuration, voltage and frequency metering, system state display, alarm or fault indication, FAULT led Led is on when product is faulty. Disconnect power supplies to reset LCD 7 digits + 4 pointers POWER led Green led is on when product is powered RJ45 connection* RJ45 terminal for ATyS D0 or D0. If connected, the LCD is off Sources state - Led is on: source = OK - Led is off: source is not available Keypad Escape LCD & leds test Operations avigation Validation ATYS 47 A GB Switch state green leds: - switch I state - switch II state Operational modes - Automatic sequence simulator (test on load) - Genset remote start (test off load) - Changeover switch position control (local or remote) * only on ATyS C30. SOFTWARE VERSIO Displayed after reset. (3 minutes power off action to allow reset). ATYS 48 A GB Version number 44

12 OPERATIO Operational modes VISUALISATIO Measured values & parametered timers display. Always accessible without code. OPERATIO Test sequences. Password access (code 4000). PROGRAMMIG Parameters configuration. Password access (code 000 from factory). The manual mode is to programme on an input. Available functions, switching gear on mode Code Operation Code Visualisation Operation Test off load Available functions, switching gear on AUT mode Code Operation Code Visualisation Operation Test off load Test on load Loss of main source sequence Main s return sequence PHASES ROTATIO COTROL Function available only on source in case of 3BL, 4BL and 4BL network. If a fault is detected, the source availability is not indicated. V V OK OK ATYS 9 A V3 V ATYS 44 A V V3 45

13 OPERATIO ATyS C0/C30 Presentation Operational modes Operation Visualisation Automatic sequences This mode allows product parameters configuration Always accessible in mode (when programmed on an input) Always accessible in AUT mode, changeover switch on priority source, priority source being available ot accessible when test off load, test on load functions are active or during automatic sequence. Parameters requiring programming before use: type of network nominal voltage nominal frequency control logic number of auxiliary contact. > avigation in the menus or Parameters access: Press up, down, left & right push buttons + + Parametermodification: press left & right push button to access the parameter to modify Press up and down push buttons to modify the parameter and validate Return to main menu: press ESC push button Value is only modified after validation > access > exit Step : press and hold for 5 s validation push button Press and hold for 5 s validation push button Step : enter code (factory code = 000) using navigation push buttons Step 3: press validation push button 46

14 OPERATIO PROGRAMMIG MEU ARCHITECTURE Setup Voltage Frequency Timer I/ O ESC ESC ESC ESC ESC Type of network Phase-Phase nominal voltage ominal frequency Genset start signal state etwork priority selection: or Manuel retransfer Impulse, breaker or contactor logic umber of auxiliary contact Return on position 0 -> Return on position 0 -> umber of permutation counter Reset etwork over voltage threshold etwork over voltage threshold hysteresis etwork under voltage threshold etwork under voltage threshold hysteresis etwork over voltage threshold etwork over voltage threshold hysteresis etwork under voltage threshold etwork under voltage threshold hysteresis etwork over frequency threshold etwork over frequency threshold hysteresis etwork under frequency threshold etwork under frequency threshold hysteresis etwork over frequency threshold etwork over frequency threshold hysteresis etwork under frequency threshold etwork under frequency threshold hysteresis Main Failure Timer Delay on Transfer Timer O main failure Timer Main Return Timer O main Return Timer Cool Down Timer Option Input (variable selection) Option Input (contact state selection) Option Input (variable selection) Option Input (contact state selection) Output * Output * Load shedding timer** code modification * Availability of output functions depending on control logic selection (impulse, breaker or contactor logic) ** Displayed if LS variable has been selected. 47

15 OPERATIO ATyS C0/C30 Presentation Operational modes Operation Visualisation Automatic sequences PARAMETER MODIFICATIO > Example: Modify network nominal voltage from 400 to 30 V. Press to access first digit (blinking) Press X to display (blinking) Press to access second digit (blinking) Press 3X to display 3 (blinking) Press to validate ATI 074 A 48

16 OPERATIO PARAMETERS CHARACTERISTICS > Menu Setup LCD Denomination Definition Setting Default range values Type of network* etwork nominal voltage umber of active conductors of controlled network (refer to annexes) Phase-eutral voltage for BL & 4BL Phase-Phase voltage for others BL, BL, BL, 3BL, 4BL, 4 BL from 00 V to 400 V 4BL 400 V etwork nominal frequency Genset start signal state etwork nominal frequency 50 Hz or 60 Hz 50 Hz ormally opened or closed O or C O etwork priority selection Keypad selection ( or ) Also possible via external contact using option or ( or ) ( ) Manual Retransfer Activation of the feature Yes or o o Type of control logic selection Impulse, contactor or breaker Imp, con, bre Con umber of auxiliary contact Depending on the number if available auxiliary contacts (switch, contactor, breaker) 0,, 3 Parameter, return in position 0 Parameter return in position 0 umber of permutation counter Reset code modification Allows to go to position 0 in case of loss (contactor type) Yes or o o Allows to go to position 0 in case of loss (contactor type) Yes or o o Allows source -> source automatic sequences Yes or o o counter reset Possible to change the programming code from 0000 to * Refer to annexes. 49

17 OPERATIO ATyS C0/C30 Presentation Operational modes Operation Visualisation Automatic sequences > Volt Menu Threshold detection starts from the loss of source or source return sequence. % Controlled value (voltages) Over voltage threshold (ou) 00 Over voltage hysteresys threshold (ouh) Available source t Under voltage hysteresys threshold (uuh) ATYS 43 A GB Under voltage threshold (uu) LCD Denomination/ Definition Setting Default range values etwork over voltage threshold From 0 to 0% etwork over voltage threshold hysteresis From 0 to 9% (< ou) etwork under voltage threshold From 80 to 98% etwork under voltage threshold hysteresis From 8 to 99% (> uo) etwork over voltage threshold From 0 to 0% etwork over voltage threshold hysteresis From 0 to 9% (< ou) etwork under voltage threshold From 80 to 98% etwork under voltage threshold hysteresis From 8 to 99% (> uu) 5% 0% 85% 95% 5% 0% 85% 95% Values definition: % of nominal values Hysteresis values range is limited by thresholds values. 50

18 OPERATIO > Frequency Menu Threshold detection starts from the loss of source or source return sequence. % Controlled value (frequency) Over frequency threshold (ou) 00 ATYS 86 A GB Over frequency hysteresys threshold (ouh) Available source t Under frequency hysteresys threshold (uuh) Under frequency threshold (uu) LCD Denomination/ Definition Setting Default range values etwork over frequency threshold From 0 to 0% etwork over frequency threshold hysteresis From 00.5 to 9.5% (< of) etwork under frequency threshold From 80 to 99% etwork under frequency threshold hysteresis From 80.5 to 99.5% (> uf) etwork over frequency threshold From 0 to 0% etwork over frequency threshold hysteresis From 00.5 to 9.5% (< of) etwork under frequency threshold From 80 to 99% etwork under frequency threshold hysteresis From 80.5 to 99.5% (> uf) 05% 03% 95% 97% 05% 03% 95% 97% Values definition: % of nominal values Hysteresis values range is limited by thresholds values. 5

19 OPERATIO ATyS C0/C30 Presentation Operational modes Operation Visualisation Automatic sequences > Menu Timer LCD Denomination Definition Setting Default range values Main Failure Timer Delay on transfer Timer O Main failure Timer Main return Timer O main return Timer Cool down Timer Delays priority network failure detection Standby network stability validation before transfer Rest in O position when transferring from main network to secondary network Main network stability validation before re-transfer Rest in O position when re-transferring from standby network to main network Allows generator cooling down period after load s retransfer from standby source (generator) to Main source from 0 to 60 s from 0 to 60 s from 0 to 0 s from 0 to 30 min from 0 to 0 s 5 s 5 s 5 s min 5 s from 0 to 30 min 4 min 5

20 OPERATIO > Inputs/Outputs Menu Output relays are O type (construction) and can not be configured as C. Input state can be configured: C or O. LCD Denomination/Definition Setting range Default values Input Ft, Ft, Ft3, Ft4, Pri, Mtf,/ / SA, MA, CtS, tol, tfl, EJP State input O, C, / O Input Ft, Ft, Ft3, Ft4, Pri, Mtf,/ / SA, MA, CtS, tol, tfl, EJP State input O, C, / O Output SA, SA, LS, / / Output SA, SA, LS, / / 53

21 OPERATIO ATyS C0/C30 Presentation Operational modes Operation Visualisation Automatic sequences > Inputs/Outputs Menu Inputs Variable Description Ft Fault input. The fault led is blinking as soon as the input is active and Ft is displayed on LCD. Reset when the input is de-activated Ft Fault input. The fault led is blinking as soon as the input is active and Ft is displayed on LCD. Reset when the input is de-activated Ft3 Fault input 3. The fault led is blinking as soon as the input is active and Ft3 is displayed on LCD. The transfer switch is immediately driven in 0 position. Keypad action (Esc) necessary to Reset the fault Ft4 Fault input 4. The fault led is blinking as soon as the input is active and Ft4 is displayed on LCD. The transfer switch is immediately driven in 0 position. Keypad action (Esc) necessary to Reset the fault Pri Priority network selection. etwork has priority when input is not activated. etwork has priority if input is active Mtf Remote manuel re-transfer. Feature identical to manual retransfer on keypad. Re-transfer from priority network to backup network is allowed from input activation ( s front). The Mtf variable in the setup menu must be selected (Yes) to allow input recognition SA Information source available (Genset) used instead of voltage/frequency measurement from ATyS (inhibited when SA is selected) Man Information transfer system in manual mode All automatic commands (+ test on load) are inhibited as soon as the input is activated CtS Remote transfer control. Possible to initiate transfer from priority source to backup source before DTT ends. If DTT is set to its maximum value (60s), the transfer is initiated as soon as the input is activated ( s front) tol Remote test on load. Started from input activation. Re-transfer is blocked until input de-activation tfl Remote test off load Started from input activation (remote genset start/stop) EJP EJP cycle inputs are automatically affected to EJP input for EJP advice, to start generator input to transfer on emergency source Retransfer is activated when input dissapears This information is the only considered in case of option configuration. variable Pri is then inhibited. EJP advice (input ) EJP transfer (input ) Start generator CDT CDT DTT ATYS 44 A GB Source Source OMF OMR OMF OMR 54

22 OPERATIO > Inputs/Outputs Menu Outputs Variable SA SA LS Description Source available. Output activated as soon as source is considered available (similar to front led source ) Source available. Output activated as soon as source is considered available (similar to front led source ) Load shedding relay. LS timer corresponds to time available to disconnect the shed loads. The relay is activated before permutation on standby network according to LS timer. The relay is de-activated after retransfer on mains network and LS timer countdown In case of LS function selection, it is required to configure associated LS timer. Output Function Default Value Setting range For LS: For LS: SA, SA, LS, / 0 to 60 s ( DTT)* 3 s * In case of DTT variable configuration below LS, LS will be automatically set to DTT value. Example: LS configuration (output relay Ou, 3 seconds): The load shedding can t be used with the priority network (priority source = source ). In this case, LS output is not valid. ATYS 69 A Load shedding cycle DTT timer LS timer Priority source - emergency source transfer Emergency source - priority source transfer LS timer Position II (emergency) AC activation LS relay Activation ATYS 334 A GB LS AC II Load shedding output The output is de-activated in case of loss of power. It may then be required to put in parrallel with the load shedding ouptut relay, position auxiliary contact. This would avoid taking back the load in case of loss of emergency source in emergency position. 55

23 OPERATIO ATyS C0/C30 Presentation Operational modes Operation Visualisation Automatic sequences Operation PRESETATIO This mode allows in manual mode (not padlocked) to start a test off load. In automatic mode, it allows to start a test, on or off load. Enter operation mode: Exit operation mode: Step : press and hold the TEST push button for 5 s Press and hold for 5 s TEST push button Step : enter the operation code (CE) using navigation push buttons (code 4000) Step 3: press validation push button avigate in operation mode: Press TEST push button to access different features Press validation push button to activate required function OPERATIO MODE ARCHITECTURE Enter: press 5 seconds Led test on load is blinking Yes, press validation Led TEST O LOAD is fixed TEST O LOAD Loss of priority source sequence o, press TEST Led test off load is blinking Yes, press validation Led TEST OFF LOAD is fixed TEST OFF LOAD Genset start sequence o, press TEST ATYS 43 A GB Exit: press 5 seconds 56

24 Control relay ATyS OPERATIO Operation TEST OFF LOAD (ACCESSIBLE I AUT/ MODES) It can be activated from: operation mode ATyS D0 interface programming input (TFL) if selected. This test is made for applications where emergency source is typically a genset (priority source must be source ). This test can only be activated, in automatic mode, changeover switch in position, source available. > Description This mode will start and stop remote by genset operation without load transfer The test is not possible during an automatic sequence start Gen Gen? Yes Stop Gen? o Validate > Keypad activation After operation mode access, press mode push button to make a test with the load led blinking and validate to start the sequence. ATI 087 B GB Gen stopped TEST O LOAD (ACCESSIBLE I AUT MODE) It is activated from: operation mode ATyS D0 interface programming input (TOL) if selected. Automatic cycle keeps priority. > Description: This test simulates a loss of priority source situation. The sequence generates load transfer from priority source to emergency source after backup source start up operation (in case of genset). The return sequence always keeps manual re transfer feature activated (from priority source availability). All timers are counted down. The product automatically returns to Visualisation mode after complete test sequence. The test is only possible in automatic mode, the changeover switch in a priority source position, priority source being available. > Keypad activation After operation mode access, press mode push button to make test on load led blinking and validate to start a cycle. > Keypad and remote Manual retransfer to validate on keypad. In retransfer sequence from emergency source to priority source, the MRT count down is set to 0 seconds (maximum), unless a lower value has been programmed. > Remote activation via specific input It is also possible to start a test on load remotely with the programming input TOL if selected. The cycle is started from contacts closure. The re-transfer is initiated from contacts opening. The re-transfer from emergency source to priority source is blocked and only authorized after manuel retransfer validation (keypad activation) or terminals opening. Start gen relay is closed if source priority. has 57

25 OPERATIO ATyS C0/C30 Presentation Operational modes Operation Visualisation Automatic sequences Visualisation PRESETATIO This mode allows parameters to be displayed independently from mode / AUT (if programmed on input) switch position o code required to access parameters visualisation Without any action during 5 seconds on the keypad, the LCD displays voltage available on active network. In case of changeover switch on 0 position, priority network voltage is displayed. avigation in visualisation mode: Press up and bottom push buttons to access required parameter Press left and right push buttons to navigate in the different menus 58

26 OPERATIO Visualisation VISUALISATIO MODE ARCHITECTURE MEUS Metering Timers Counter Phase-neutral voltage V Main Failure Timer Priority source -> network Emergency source transfer counter Phase-neutral voltage V network Delay on Transfer Timer Phase-neutral voltage V3 network O Main Failure Timer etwork frequency Main Return Timer Phase-phase U network O Main Return Timer Phase-phase U3 network Cool Down Timer Phase-phase U3 network Load shedding* Phase-neutral voltage V network Phase-phase U3 network etwork frequency * If selected. All values indicated might not be available according to programmed network. Refer to annexes. 59

27 OPERATIO ATyS C0/C30 Presentation Operational modes Operation Visualisation Automatic sequences Automatic sequences MAUAL MODE/ AUTOMATIC MODE > Manual mode - Automatic mode permutation/power supply reappearance As soon as the selector switch is switched to automatic, the automatic mode is active Voltages and frequencies are verified to define new stable position of the changeover switch The same table can be taken into account after complete power supply loss (the product must be completely discharged to reset = 3 minutes.) > ew stable position of the changeover switch Refer to timer menus for MFT, MRT or DTT timers definition. Changeover switch Sources availability ew position initial position Priority source Priority source available, Priority source emergency source available or unavailable Priority source Priority source unavailable for MFT time period, Emergency source. If emergency source emergency source available or unavailable unavailable start emergency source first and wait for DTT timer period before transfer Emergency source Emergency source available, Emergency source priority source unavailable Emergency source Emergency source available, Priority source priority source available for MRT time period Emergency source Emergency source not available, Priority source priority source available Position 0 Priority source available, Available source to count down MRT before emergency source unavailable transfer to priority source Position 0 Priority source available, Priority source emergency source unavailable Position 0 Priority source unavailable, Emergency source emergency source available Position 0 Priority source unavailable, o action (because no supply). emergency source unavailable When supply becomes available change to priority source or emergency source The switch transfers to new stable position as soon as the keyswitch is turned from Manual to Automatic mode or as soon as Power comes back. 60 LOSS OF PRIORITY SOURCE AUTOMATIC SEQUECE This sequence is started as soon as the switch is in automatic mode and in priority position (position I - source ). source is available transfer switch is in position I source is available or unavailable > Available source Source being within programmed voltage and frequency settings, phases rotation being correct. > Specific feature: remote transfer control It is possible to transfer from main source to emergency source before DTT finishes up. If it is setup to its maximum values (60s), it is possible to allow transfer with CTS option if selected.

28 OPERATIO Automatic sequences > Sequence description Example: position I = priority source ( ) position II = emergency source type Genset ( ) Automatic mode Loss of mains? Loss of main? o Yes MFT = 0 Count down MFT Main comes back before MFT ends? Start Genset Genset start up Reset MFT Emergency source available? Yes o o Stop gen Yes Priority source? Reset DTT o Gen fails Count down DTT = 0 o CTS =? Yes Yes OMF 0? o Transfer I > 0 Count down OMF OMF = 0 Transfer 0 > I Transfer I > II Transfer I > I I ATYS 443 A GB Go to priority source return automatic sequence 6

29 OPERATIO ATyS C0/C30 Presentation Operational modes Operation Visualisation Automatic sequences Automatic sequences RETUR TO PRIORITY SOURCE This sequence is activated as soon as the changeover switch is in automatic mode and in emergency position (position II): the priority source is not available > Specific feature: manual re-transfer When priority source comes back, it can be required not to automatically retransfer and wait for more adequate moment. It is possible, validating manual retransfer feature (refer to programming), to block the re-transfer. It is initiated from: validation push button localy or on ATyS D0 via a programming input if MTF option is selected. ATYS 43 B the changeover switch is in emergency position (ex: genset) the emergency source is available. Manual retransfer = validation press Or optional input activation, feature Mtf > Sequence description Priority source unavailable Generator running (emergency source) & Switch in position II Main s return Priority source return? Yes o Manual re-transfer Yes Loss of priority source? Count down MRT MRT = 0 o Reset MRT Priority source lost again before MRT times out? Mode semi-auto activated? (Mtf) Yes o Yes Validation Yes OMR 0? o Transfer II > 0 Count Down OMR OMR = 0 Transfer 0 > I Transfer II > I To loss of priority source sequence Reset CDT Count Down CDT Transfer II > I Loss of priority source CDT = 0 Stop generator position Back to priority source control ATYS 55 A GB 6

30 TROUBLESHOOTIG GUIDE ATyS C0/C30 STATE Electrical operation is not working Product is faulty (fault is active) FT, FT, FT3, FT4 Source available led is never active when available The changeover switch does not transfer after loss of main ACTIO Verify voltage applied on terminals 00 Vac to 440 Vac or 9 Vdc to 30 Vdc for DC version Verify state of input MA if selected Disconnect power supply to try to reset the fault In case of programming inputs FT or FT, verify if external fault is not active. If the external fault disappear it acquit the fault In case of programming inputs FT3 or FT4, verify if external fault is not active. The fault must be validated (valid push button) to be acquitted Press test lamp to verify led is operational (push 5 seconds) Verify nominal preset values (voltage and frequency) Verify voltage and frequency thresholds Verify phases sequence Verify state of input MA, if selected Verify emergency source is available (ex: genset is started) Verify voltage applied on terminals Test on load and off load Verify password to access test (4000) can not be activated from keypad Verify state of input MA, if selected The changeover switch does not re-transfer after main's return Verify MRT is counted down Verify state of input MA if selected Verify manual retransfer feature is not active (press validation to allow retransfer) Retransfer has been realised but Verfiy CDT is counted down emergency source in still running (did not stop) Verify Start Gen output relay command, terminals 3-4 (disconnect connector if required) Electrical operation not according to commands Verify control logic (impulse, breaker or contactor mode) The product is in faulty position Error LCD Err XXXX Verify the number of AC in the setup menu. It must be in conformity with the number of AC connected Verify the switch position Send the product back to the manufacturer 63

31 AEXES ATyS C0/C30 etworks analysis and connections ATyS etworks analysis TYPES OF ETWORKS > Three phases network with neutral - 4BL > Two phases network (with midpoint) - BL ATYS 73 A GB Source 3 Load Source 3 ATYS 74 A GB Source Source 3 3 Load > Phase-Phase network without neutral - BL Source Source > Single phase network with neutral (phase-neutral) - BL Source Source 3 3 ATYS 75 A GB Load ATYS 76 A GB Load > Three phases network without neutral - 3BL > Three phases network with neutral on source Single phase network with neutral on source - 4 BL ATYS 77 A GB Source 3 Load 3 Source ATYS 78 A GB Source 3 Load Source Only single phase loads. 64

32 AEXES and connections ATyS C30 ATyS integrates all identified networks in his programm. It is necessary to verify this parameter before use. THREE PHASES SESIG O SOURCE - SIGLE PHASE SESIG O SOURCE Prog. ATyS Source (active connectors) 3 phases phase phase phase 3 phases 3 phases 4 wires 3 wires wires wire 3 wires 4BL BL BL BL 3BL 4BL Source (active connectors) Sensing parameters available Source Source U, U3, U3, U, U, U3 U3 U, U3, U3 U3 U3 U3 U U U, U3, U3 U3 U, U, U3 U Controls Source U, U3, U3 U, U3, U3 U3 U U, U3, U3 U, U, U3 Source U3 U3 U3 U U3 U Example Un = 40 V Source U = U3 = U3 = 40 V U3 = 40 V U3 = 40 V U = 40 V U = U3 = U3 = 40 V U = U = U3 = 40 V Source 40 V 40 V 40 V 40 V 40 V 40 V 65

33

34

35 SOCOMEC - Ref.: 53 4 A - 04/05 QUAT OT 3i HEAD OFFICE SOCOMEC GROUP SWITCHIG PROTECTIO & UPS S.A. capital R.C. Strasbourg B B.P. 0 - Rue de Westhouse - F-6735 Benfeld Cedex - FRACE SALES MAAGEMET DIVISIO SOCOMEC 95, rue Pierre Grange 943 Fontenay-sous-Bois Cedex Tél Fax This document is not a contract. SOCOMEC reserves the right to modify features without prior notice in view of continued improvement.

CONTROLLER ATyS C20/C30

CONTROLLER ATyS C20/C30 COTROLLER ATyS C0/C30 otice d utilisation - Operating instructions F GB MAKE YOUR BUSIESS SAFE SOCOMEC GROUP SWITCHIG PROTECTIO & UPS F Sommaire LA GAMME ATyS 3 PRÉSETATIO GÉÉRALE 4 Présentation des produits

More information

ATS-I USER MANUAL. Tecnoelettra srl Dal Via Vioni Dimo, S.Rocco di Guastalla (RE)

ATS-I USER MANUAL. Tecnoelettra srl Dal Via Vioni Dimo, S.Rocco di Guastalla (RE) USER MANUAL ATS-I Tel.+39.0522.832004 P1/17 ATS-I User manual Fax.+39.0522.832012 Tecnoelettra_EN.doc P.1/17 Index General description...3 Electrical specifics...3 Device operative logic...4 Manual mode...4

More information

ATyS M 6e Operating instructions GB

ATyS M 6e Operating instructions GB ATyS M 6e Operating instructions GB GENERAL SAFETY INSTRUCTIONS This manual provides instructions on safety, connections and operation of the ATYS source switchgear system. This system must always be installed

More information

DIRIS A40/A41 RS485 PROFIBUS DP COM. Operating instructions. PROFIBUS Certification

DIRIS A40/A41 RS485 PROFIBUS DP COM. Operating instructions. PROFIBUS Certification DIRIS A40/A41 RS485 PROFIBUS DP Operating instructions F GB D I NL E P ON 1 COM PROFIBUS Certification SOCOMEC GROUP SWITCHING PROTECTION & UPS Systèmes de Coupure et de Protection Industrial Switching

More information

DIRIS A40/A41 RS485 PROFIBUS DP. Operating instructions F GB D I NL E P. SOCOMEC GROUP switching PROTECTION & ups

DIRIS A40/A41 RS485 PROFIBUS DP. Operating instructions F GB D I NL E P. SOCOMEC GROUP switching PROTECTION & ups DIRIS A40/A41 RS485 PROFIBUS DP Operating instructions F GB D I NL E P SOCOMEC GROUP switching PROTECTION & ups 2 DIRIS A20 - Réf. : 536 182 A GB 876_786_A_gb.indd 2 3/04/09 10:50:47 GB Contents PRELIMINARY

More information

DIRIS Ap RS485 JBUS/MODBUS COM. Systèmes de Coupure et de Protection Industrial Switching and Protection Systems ON 1

DIRIS Ap RS485 JBUS/MODBUS COM. Systèmes de Coupure et de Protection Industrial Switching and Protection Systems ON 1 DIRIS Ap RS485 JBUS/MODBUS F GB ON 1 D COM I NL E P Systèmes de Coupure et de Protection Industrial Switching and Protection Systems PRELIMINARY OPERATIONS NB: For personnel and product safety please read

More information

Installation and Operating Instructions. Power IT Power Factor Controller RVC

Installation and Operating Instructions. Power IT Power Factor Controller RVC Installation and Operating Instructions Power IT Power Factor Controller RVC Table of contents Page 1. Read this first... 3 About this Instruction Manual... 3 Safety... 3 Electromagnetic compatibility...

More information

PRELIMINARY DATA SHEET. RI-F300 Series. easywire Single and Three Phase Multifunction Energy Meter (MID Certified) MID

PRELIMINARY DATA SHEET. RI-F300 Series. easywire Single and Three Phase Multifunction Energy Meter (MID Certified) MID RIF300 Series easywire Single and Three Phase Multifunction Energy Meter (MID Certified) DI 96 panel mounted 330mV Input from easywire CTs (or /1A and /5A current transformer input with TASSCTEWA module)

More information

RI-D440. Three Phase easywire Multifunction DIN Rail Energy Meter. Telephone : +44 (0) Displayed Parameters

RI-D440. Three Phase easywire Multifunction DIN Rail Energy Meter. Telephone : +44 (0) Displayed Parameters RI-D440 Three Phase easywire Multifunction DIN Rail Energy Meter Four module DIN rail mounted Energy pulse LED 330mV Input from easywire CTs (or -/1A and -/5A current transformer input with TAS-SCTEWA

More information

Technical Datasheet. True RMS Digital Protection Relay. Line Monitoring Relay

Technical Datasheet. True RMS Digital Protection Relay. Line Monitoring Relay Technical Datasheet RELAY-1 RELAY-2 k V Hz RESET ABH TEST True RMS Measurement True RMS Digital Protection V/Hz is used to protect against Over Voltage, Under Voltage, Phase Unbalance, Phase Sequence detection,

More information

PRELIMINARY DATA SHEET. RI-F400 Series. easywire Single and Three Phase Multifunction Energy Meter

PRELIMINARY DATA SHEET. RI-F400 Series. easywire Single and Three Phase Multifunction Energy Meter Telephone : 44 (0) 1245 428500 PRELIMIARY DATA SHEET RIF400 Series easywire Single and Three Phase Multifunction Energy Meter DI 96 panel mounted 330mV Input from easywire CTs (or /1A and /5A current transformer

More information

Technical Datasheet. True RMS Digital Protection Relay. Voltage Protection Relay

Technical Datasheet. True RMS Digital Protection Relay. Voltage Protection Relay Technical Datasheet RELAY-1 RISHABH k V RESET True RMS Digital Protection Relay RELAY-2 TEST True RMS Measurement RISH Relay V is used to protect against Over Voltage, Under Voltage, Phase Sequence detection,

More information

TCS2P125. Automatic Transfer Switch Control Unit for 1 Phase System Operation Manual

TCS2P125. Automatic Transfer Switch Control Unit for 1 Phase System Operation Manual TCS2P125 Automatic Transfer Switch Control Unit for 1 Phase System Operation Manual Single Phase 2P 125 Amp Rated Voltage 250 Vac Patent Number : U.S. Pat. No. 7,557,683 KUTAI ELECTRONICS INDUSTRY CO.,

More information

T 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers

T 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers Secondary Injection Relay Test Set Designed for testing relays and transducers Microprocessor controlled With phase angle shifter Frequency generator Test results and settings are saved into local memory

More information

Microprocessor Control Board Set Up Procedures (OR PLC)

Microprocessor Control Board Set Up Procedures (OR PLC) Microprocessor Control Board Set Up Procedures (OR-00 PLC) SWITCHES/PUSHBUTTONS Push Buttons at display SW Enter button SW Back button SW Down SW UP Back light on/off switch Rotary switches on main board

More information

Relay. Technical Datasheet. True RMS Digital Protection Relay. Line Monitoring Relay

Relay. Technical Datasheet. True RMS Digital Protection Relay. Line Monitoring Relay Line Monitoring Technical Datasheet RISH RELAY-1 RELAY-2 RISHABH k V Hz True RMS Digital Protection RISH V/Hz is used to protect against Over Voltage, Under Voltage, Phase Unbalance, Phase Sequence detection,

More information

RI-F200 Series. Single and Three Phase Multifunction Energy Meter. Telephone : +44 (0) Displayed Parameters

RI-F200 Series. Single and Three Phase Multifunction Energy Meter. Telephone : +44 (0) Displayed Parameters RI-F200 Series Single and Three Phase Multifunction Energy Meter DIN 96 panel mounted -/1A or -/5A current transformer input Single phase or three phase network compatible Programmable voltage and current

More information

ATS-01 Ver1.2 AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL

ATS-01 Ver1.2 AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL ATS-01 Ver1.2 AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL Headquarters : No.3, Lane 201, Chien Fu ST., Chyan Jenn Dist., Kaohsiung, TAIWAN Tel : + 886-7-8121771 Fax : + 886-7-8121775 URL :

More information

RETROFITTING. Motor Protection Relay. Two mountings are available, Flush Rear Connection (EDPAR) or Projecting Rear Connection (SDPAR).

RETROFITTING. Motor Protection Relay. Two mountings are available, Flush Rear Connection (EDPAR) or Projecting Rear Connection (SDPAR). RETROFITTING Motor Protection Relay NPM800R (R2 case) and NPM800RE (R3 case) are dedicated to the refurbishment of 7000 series (R2 and R3 cases) of CEE relays providing the protection of medium voltage

More information

CROSS Chassis from 160 A to 450 A

CROSS Chassis from 160 A to 450 A CROSS Chassis from 160 A to 450 A STS CATALOGUE Important note! The technical data enclosed is for general information. Please note that the operating instructions and references indicated on the products

More information

English RACON SERIES II RADIO CONTROL SERVICE MANUAL

English RACON SERIES II RADIO CONTROL SERVICE MANUAL English 22.2.2007 RACON SERIES II RADIO CONTROL SERVICE MANUAL Read the instructions supplied with the product before installation and commissioning. Keep the instructions in a safe place for future reference.

More information

MID. RI-F300 Series. easywire Single and Three Phase Multifunction Energy Meter (MID Certified) MID

MID. RI-F300 Series. easywire Single and Three Phase Multifunction Energy Meter (MID Certified) MID Telephone : 44 (0) 1245 428500 RIF300 Series MID easywire Single and Three Phase Multifunction Energy Meter (MID Certified) DI 96 panel mounted 1A Input from easywire CTs Single phase or three phase network

More information

PRELIMINARY DATA SHEET RI-D140. Three Phase Multifunction DIN Rail Energy Meter (MID Certified) MID

PRELIMINARY DATA SHEET RI-D140. Three Phase Multifunction DIN Rail Energy Meter (MID Certified) MID RI-D140 Three Phase Multifunction DIN Rail Energy Meter (MID Certified) Four module DIN rail mounted Energy pulse LED True RMS measurement Cost effective and accurate Modbus communication -/1A or -/5A

More information

TD 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers

TD 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers Secondary Injection Relay Test Set Designed for testing relays and transducers Two current outputs to test differential relays Convertible current and voltage generator With phase angle shifter Frequency

More information

NX Series Inverters. HVAC Pocket Programming Guide

NX Series Inverters. HVAC Pocket Programming Guide NX Series Inverters HVAC Pocket Programming Guide HVAC Pocket Programming Guide HVAC Pocket Programming Guide / Contents This guide provides a single reference document for the user of NXL HVAC (product

More information

INSTRUCTIONS MANUAL DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS HRI-R40W

INSTRUCTIONS MANUAL DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS HRI-R40W Page 2 / 16 INDEX: GENERAL TYPES ACESSORIES AND OPTIONS INSTALLATION WIRING DIAGRAMS CONNECTING TERMINALS DIAGRAMS WIRING DIAGRAM DESCRIPTION WORKING DESCRIPTION AND KEYBOARD WORKING DESCRIPTION AND PROGRAMMING

More information

SDMO. Changeover switch VERSO 200

SDMO. Changeover switch VERSO 200 User guide SDMO Changeover switch VERSO 200 V 1.1a 13/11/2013 33502029301_0_1 Summary 1 - Safety guidelines for installation and operation... 4 2 - Installation of the source changeover switch... 5 2.1

More information

PRODUCT LEAFLET AUGIER-BOX. Remote Monitoring Unit for Street Lighting /07/2011

PRODUCT LEAFLET AUGIER-BOX. Remote Monitoring Unit for Street Lighting /07/2011 PRODUCT LEAFLET AUGIER-BOX Remote Monitoring Unit for Street Lighting 1 60 11432-04/07/2011 Put a TECHNICIAN in each street lighting cabinet, and control them 24H per day! The Augier-Box Programmable Logic

More information

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Furnish and install automatic transfer switches (ATS) with number of poles, amperage, voltage, and withstand

More information

Low Voltage Products. Enclosed Third Harmonic Filter THF and THF star Enclosed units. Brochure THFS1GB 03_04 1SCC330003C0201

Low Voltage Products. Enclosed Third Harmonic Filter THF and THF star Enclosed units. Brochure THFS1GB 03_04 1SCC330003C0201 Low Voltage Products Enclosed Third Harmonic Filter and star Enclosed units Brochure S1GB 3_4 1SCC333C21 The Third Harmonic - a Growing Problem Today's electrical networks and plants are under much more

More information

Monicon International Co., Ltd ATS 100 ATS 100 Controller User Manual

Monicon International Co., Ltd ATS 100 ATS 100 Controller User Manual ATS 100 Controller User Manual Web Site:http://www.monicon.com.tw E-mail:sales@monicon.com.tw 1 Introduction ATS 100, automatic transfer switch controller, is a sophisticated module with high quality-price

More information

sw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS

sw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS INSTRUCTIONS MANUAL IM831-U v0.92 HRI-R40W sw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS INDEX: GENERAL TYPES ACESSORIES AND OPTIONS

More information

CS-200. PORTABLE TRAFFIC LIGHT CONTROLLER (Software 1.05) OPERATION AND SERVICE MANUAL

CS-200. PORTABLE TRAFFIC LIGHT CONTROLLER (Software 1.05) OPERATION AND SERVICE MANUAL CS-200 PORTABLE TRAFFIC LIGHT CONTROLLER (Software 1.05) OPERATION AND SERVICE MANUAL CS-200 Operation and Service Manual Page 2 Manufactured by: LINCAST INTERNATIONAL PTY. LTD. 2/3 Sir Laurence Drive

More information

CONTROL MANUAL. Dry-Pic 09PE - 09VE

CONTROL MANUAL. Dry-Pic 09PE - 09VE CONTROL MANUAL Dry-Pic 09PE - 09VE Translation of the original document 003, 04.01 EN CONTENTS PAGE 1 - IMPORTANT RECOMMENDATIONS 1.1 Power supply 1. Electronic board specifications 1.3 Caution 1.4 Earth

More information

Digital Multifunction Instrument - Rish Master 3440

Digital Multifunction Instrument - Rish Master 3440 Application Rish Master 3440 measures important electrical parameters in 3 phase and single phase etwork & replaces the multiple analog panel meters. It measures electrical parameters like AC current,

More information

Technical description MT24. User manual WARNING GENERAL INSTRUCTIONS GENERAL DESCRIPTION

Technical description MT24. User manual WARNING GENERAL INSTRUCTIONS GENERAL DESCRIPTION WARIG The equipment makes a compact set of the switchboard. Just this set is safe from the point of electrical shock. Therefore do not use other power supplies or circuits than mentioned in this direction

More information

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax :

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax : NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata - 700 032, Tel : 033 2477 3126; Fax : 033 2477 2403 www.ntplindia.com SPECIFICATION NTPL MAKE MICRO-CONTROLLER BASED AUTOMATIC 50KV/10A AC HIGH VOLTAGE

More information

vacon 100 flow ac drives application manual

vacon 100 flow ac drives application manual vacon 100 flow ac drives application manual PREFACE VACON 3 PREFACE Document ID: DPD01083D Date: 15.10.2014 Software version: FW0159V010 ABOUT THIS MANUAL This manual is copyright of Vacon Plc. All Rights

More information

BU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on supply lines for medical locations ISOLTESTER-DIG-RZ/RS/PLUS

BU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on supply lines for medical locations ISOLTESTER-DIG-RZ/RS/PLUS INSTRUCTION MANUAL BU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on supply lines for medical locations ISOLTESTER-DIG-RZ/RS/PLUS 1/23 More information than that reported

More information

These parameters are available only on EMC-D3b-485 model and readable only by RS485 interface.

These parameters are available only on EMC-D3b-485 model and readable only by RS485 interface. ISTRUCTIO MAUAL IM450-U v3.1 -D3b -D3b-485 EERGY MULTIFUCTIO COUTER AVAILABLE MODELS -D3b: 3-phase energy counter with 7+1 digit display. 1 digital input and two digital pulse output for kwhr and kvarhr.

More information

TECO F510 Inverter. Quick Start Guide. Step 1. Supply & Motor connection

TECO F510 Inverter. Quick Start Guide. Step 1. Supply & Motor connection Quick Start Guide TECO F510 Inverter This guide is to assist you in installing and running the inverter and verify that it is functioning correctly for it s main and basic features. For detailed information

More information

FAST SAMPLING CONVERTER

FAST SAMPLING CONVERTER FAST SAMPLING CONVERTER ML4-F1 HIGH SAMPLING RATE CONVERTER (UP TO 400 SAMPLES/SECOND) Warranty conditions are available on this website: www.isomag.eu only in English version INDEX TECHNICAL DATA... 3

More information

AEROCONNECT 1B NA C Control manual

AEROCONNECT 1B NA C Control manual AEROCONNECT 1B NA 11.3 C 03-01 Control manual EN CONTENTS PAGE 1 - IMPORTANT RECOMMENDATIONS 1.1 Power supply 1. Electronic board specifications 1.3 Caution 1.4 Earth 1. Sensor connections 1.6 Communication

More information

Energy counting and measurement

Energy counting and measurement Energy counting In the current context of research of energy saving, counting of consumption become unavoidable. Hager offers new residential and tertiary solutions, to better control energy consumption.

More information

INSTRUCTION MANUAL. Power Factor Controller - 12 steps Model A12 NOKIAN CAPACITORS. Power Factor Controller A12

INSTRUCTION MANUAL. Power Factor Controller - 12 steps Model A12 NOKIAN CAPACITORS. Power Factor Controller A12 INSTRUCTION MANUAL Power Factor Controller - 12 steps Model A12 NOKIAN CAPACITORS Power Factor Controller A12 1. CONTENTS 1. CONTENTS 1 2. FEATURES 2 3. INSTALLATION, CONNECTION AND APPLYING POWER 2 4.

More information

Technical Data Sheets

Technical Data Sheets GE Consumer & Industrial Power Protection Technical Data Sheets Digital Energy Uninterruptible Power Supply SG Series 80 100 120 kva 400 Vac CE Series 0 Date of issue: 01.11.2007 SGSE_080_UPS_GE_01a SGSE_100-120_UPS_GE_01a

More information

vacon 100 flow ac drives application manual

vacon 100 flow ac drives application manual vacon 100 flow ac drives application manual vacon 1 TABLE OF CONTENTS Document: DPD01083A Version release date: 16.11.12 Corresponds to software package FW0159V121106.vcx 1. Vacon 100 FLOW - Quick Startup

More information

SECTION AUTOMATIC TRANSFER SWITCH

SECTION AUTOMATIC TRANSFER SWITCH SECTION 26 36 23 PART 1 - GENERAL 1.1 THE REQUIREMENT A. Furnish and install automatic transfer switches (ATS) with number of poles, amperage, voltage, withstand and close-on ratings as shown on the plans.

More information

Remote Maintenance Box, RMB

Remote Maintenance Box, RMB OPERATOR S MANUAL Remote Maintenance Box, RMB Warnings and legal information Operating procedure Voltage measurement Document no.: 4189340730B SW version AGC 3.40.0 or later and AGC 4.00.0 or later Table

More information

DESIGNER S REFERENCE HANDBOOK

DESIGNER S REFERENCE HANDBOOK DESIGNER S REFERENCE HANDBOOK Generator Paralleling Controller GPC-3/GPC-3 Gas/GPC-3 Hydro Functional description Modes and sequences General product information PID controller DEIF A/S Frisenborgvej 33

More information

Mounting Instructions / Manual MV1171

Mounting Instructions / Manual MV1171 Mounting Instructions / Manual MV1171 POWER FACTOR Controller ESTAmat MH-N Vishay Electronic GmbH ESTA Capacitors Division Revision: 19-April-2011 Hofmark-Aich-Strasse 36 84030 Landshut, Germany Phone

More information

IPS INTELLIGENT PUMP STARTER. Integrated Tru-power electronic motor and pump protection

IPS INTELLIGENT PUMP STARTER. Integrated Tru-power electronic motor and pump protection IPS INTELLIGENT PUMP STARTER With TM Smartstart Ø & Ø, 0/60 Hz, 20~600 VAC, /~00HP Integrated electronic pump protection overload Power metering and data logging options Motor Protection Key dealer yr.

More information

ZHUHAI PILOT TECHNOLOGY CO., LTD.

ZHUHAI PILOT TECHNOLOGY CO., LTD. SPM32 Multifunctional Power Meter SPM32 Multifunction Power Meter Installation & Operation Manual V1.0 ZHUHAI PILOT TECHNOLOGY CO., LTD. Danger and warning! This device can be installed only by professionals.

More information

DIRIS A40 DIRIS A41. Functions. Conformity to standards. Applications. Energy management DIRIS A40. Network analysis

DIRIS A40 DIRIS A41. Functions. Conformity to standards. Applications. Energy management DIRIS A40. Network analysis diris_561_b_3_x_cat 1 1. Backlit LCD display. 2. Direct access key for currents and setup wiring correction. 3. Direct access key for voltages and frequency. 4. Direct access key for active, reactive,

More information

BATCHMATE 1500 Batch Control Computer Technical Bulletin

BATCHMATE 1500 Batch Control Computer Technical Bulletin TS-5(C) BATCHMATE 5 Batch Control Computer Technical Bulletin DESCRIPTION The BATCHMATE features an 8 digit.55-in. alphanumeric LED display. The pulse input model will accept up to 2, pulses per second

More information

LINETRAXX VMD460-NA. Network and system protection (NS protection) for monitoring the power feed-in of power generation systems

LINETRAXX VMD460-NA. Network and system protection (NS protection) for monitoring the power feed-in of power generation systems LIETRAXX -A etwork and system protection (S protection) for monitoring the power feed-in of power generation systems -A_D00001_01_D_XXE/09.2015 LIETRAXX -A etwork and system protection (S protection) for

More information

NZ7. NZ7 Automatic Transfer Switching Equipment. 2. Type designation. 1. General. 3. Operation conditions N Z 7- /

NZ7. NZ7 Automatic Transfer Switching Equipment. 2. Type designation. 1. General. 3. Operation conditions N Z 7- / Z7 2. Type designation Z 7- / Transfer mode without code: Users can set the matter : self-throwing and self-reset (power network to power network) S: self-throwing and not self-reset (power network to

More information

Temperature Controller model MFC-301/T-Dry. Version for Dry Transformers and Motors. Technical Manual. Licht

Temperature Controller model MFC-301/T-Dry. Version for Dry Transformers and Motors. Technical Manual. Licht Temperature Controller model MFC-301/T-Dry Version for Dry Transformers and Motors Technical Manual Licht Contents 1 Introduction 2 2 Operating principle 3 2.1 General principle 3 2.2 RTD operation 3 3

More information

Rotational speed controller

Rotational speed controller Model number Features Rotational speed monitoring up to khz pre-select value with relay output and LED indicator Multi-range power pack -, -, -wire and NAMUR sensors as well as rotary encoder connectable

More information

MW3105 DIGITAL CLAMP MULTIMETER

MW3105 DIGITAL CLAMP MULTIMETER MW3105 DIGITAL CLAMP MULTIMETER 2 M MW3105 A 01 INTRODUCTION 1.1 - Unpacking and inspection Upon removing your new Digital Clamp Meter from its packing, you should have the following items: 1. Digital

More information

ALPTEC POWER FACTOR CONTROLLER

ALPTEC POWER FACTOR CONTROLLER ALPTEC POWER FACTOR CONTROLLER ALPTEC3 ALPTEC5 ALPTEC7 ALPTEC12 0 REF : 2008-ALPTEC3.5.7.12-01-ANG CONTENTS I GENERAL INFORMATION. 2 II WAYS TO SET UP THE CONTROLLER.. 4 III OPERATING MODE..6 IV ADVANCED

More information

Section 16621A - AUTOMATIC TRANSFER SWITCH. Part 1 General

Section 16621A - AUTOMATIC TRANSFER SWITCH. Part 1 General Section 16621A - AUTOMATIC TRANSFER SWITCH Part 1 General 1.01 One 600 Amp, 3 Phase, 480 Volt Automatic Transfer Switch (ATS) shall be provided with gasketed enclosure. The ATS shall consist of an inherently

More information

WARRANTY. Long Range Systems, LLC, 20 Canal St, Suite 4N, Franklin, NH 03235

WARRANTY. Long Range Systems, LLC, 20 Canal St, Suite 4N, Franklin, NH 03235 WARRANTY Long Range Systems, Inc. warrants the trap release product against any defects that are due to faulty material or workmanship for a one-year period after the original date of consumer purchase.

More information

DIRIS A40/A41 ETHERNET. Operating instructions F GB D I NL E P

DIRIS A40/A41 ETHERNET. Operating instructions F GB D I NL E P DIRIS A40/A41 ETHERNET Operating instructions F GB D I NL E P 2 DIRIS A40/A41 - Ref.: 536 181 B GB GB Contents PRELIMINARY OPERATIONS 4 GENERAL INFORMATION 4 INSTALLATION 5 CONNECTION 5 VISUAL DIAGNOSTIC

More information

T 1000 PLUS Secondary Injection Relay Test Set

T 1000 PLUS Secondary Injection Relay Test Set Secondary Injection Relay Test Set Designed for testing relays and transducers Microprocessor controlled With phase angle shifter Frequency generator Test results and settings are saved into local memory

More information

Smart-house Dimmer Power dimmer up to 500W Type SH2D500W230

Smart-house Dimmer Power dimmer up to 500W Type SH2D500W230 Smart-house Dimmer Power dimmer up to 500W Type SH2D500W230 Universal dimmer switch for R, L, C up to 500W and LED loads Automatic load detection for L, R, C loads Integrated heat sink for temperature

More information

T 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers

T 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers Secondary Injection Relay Test Set Designed for testing relays and transducers Microprocessor controlled With phase angle shifter Frequency generator High power outputs Large graphical display Compact

More information

itl impulse relays IEC/EN itls: IEC/EN itls b Allows remote indication of its operating state (open/closed)

itl impulse relays IEC/EN itls: IEC/EN itls b Allows remote indication of its operating state (open/closed) DB123399 DB116619 Country approval pictograms itl, itli, itls, itlc, itlm IEC/EN 60669-2-2 itls: IEC/EN 60947-5-1 Impulse relays B106126-34 B106128-34 itl b The impulse relays are used to control, by means

More information

Viconics VT76x7 Series Rooftop Unit Controllers Engineering Guide Specification

Viconics VT76x7 Series Rooftop Unit Controllers Engineering Guide Specification Viconics VT76x7 Series Rooftop Unit Controllers Engineering Guide Specification General The VT76x7 series is designed for single-stage and multi-stage control of heating/cooling equipment such as rooftop

More information

3 PHASE ENERGY ELECTRONIC METERS MKT & MKT2. (Code to ) INSTRUCTION MANUAL ( M / 00 A ) (c) CIRCUTOR S.A.

3 PHASE ENERGY ELECTRONIC METERS MKT & MKT2. (Code to ) INSTRUCTION MANUAL ( M / 00 A ) (c) CIRCUTOR S.A. 3 PHASE ENERGY ELECTRONIC METERS MKT & MKT2 (Code 7 71 071 to 7 71 083) INSTRUCTION MANUAL ( M 981 200 / 00 A ) (c) CIRCUTOR S.A. ----- MKT- MKT2 - ELECTRONIC METERS -------- M-981 200 --- Page Nº 2 3

More information

Analogue temperature controllers

Analogue temperature controllers Analogue temperature controllers CT8A Input by J-K thermo-couple or by thermo-resistance Pt 00 (-wire) regulation modes : ON/OFF or proportional derivative selected by wiring Relay output Specifications

More information

SUPPLY NETWORK ANALYZER. CVMk SERIES. CVMk-4C SERIES INSTRUCTION MANUAL. ( M / 00 B - Manual 1 / 2 ) (c) CIRCUTOR S.A.

SUPPLY NETWORK ANALYZER. CVMk SERIES. CVMk-4C SERIES INSTRUCTION MANUAL. ( M / 00 B - Manual 1 / 2 ) (c) CIRCUTOR S.A. SUPPLY NETWORK ANALYZER CVMk SERIES & CVMk-4C SERIES INSTRUCTION MANUAL ( M 981 171 / 00 B - Manual 1 / 2 ) (c) CIRCUTOR S.A. ----- Supply network analyzer CVMk and CVMk-ITF ------ Manual 1 / 2 --- Page

More information

Technical Data Sheet. Uninterruptible Power Supply On-line VH Series UPS. Critical Power UL / 208V

Technical Data Sheet. Uninterruptible Power Supply On-line VH Series UPS. Critical Power UL / 208V Technical Data Sheet Uninterruptible Power Supply On-line VH Series UPS 2000-3000 UL / 208V GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850

More information

Eltek TU GenII GD900A Energy monitor (multidrop NDRail350) transmitter user instructions

Eltek TU GenII GD900A Energy monitor (multidrop NDRail350) transmitter user instructions Eltek TU1043 - GenII GD900A Energy monitor (multidrop NDRail350) transmitter user instructions System configuration diagram GD900A NDRail350 AC supply 240V nominal RS485 AC AC AC For 1 x three phase load

More information

PROCESS & TEMPERATURE CONTROLLERS

PROCESS & TEMPERATURE CONTROLLERS PROCESS & TEMPERATURE CONTROLLERS NOVA PD54 Series Thermocouple, RTD, & Process Inputs High Accuracy Auto-Tuning PID Heating & Cooling Models Universal Power Supply 1-24 VAC Up to 3 Relays & 2 Analog Outputs

More information

AC CURRENT GENERATOR POC-6000 (current from 0 to 1000 ARMS)

AC CURRENT GENERATOR POC-6000 (current from 0 to 1000 ARMS) AC CURRENT GENERATOR PERFORMANCES Wide range of current 50 db dynamic range Signal-to-noise ratio: 80 db open loop protection Stability < 0,1% Very low THD distortion < 0,3% External synchronization Build-up

More information

EIB/KNX Switch Actuators. User manual

EIB/KNX Switch Actuators. User manual EIB/KNX Switch Actuators User manual IT KNT 004 IT KNT 012 Tel.: +34943627988 E-mail: knx@dinuy.com Web: www.dinuy.com Contents 1. Introduction --------------------------------------------------------------------------------------------------------------

More information

C-Band Redundant LNA Systems

C-Band Redundant LNA Systems C-Band Redundant LNA Systems LRC-1000 Series Introduction Redundant LNA systems minimize system downtime due to LNA failure by providing a spare LNA and an automatic means of switching to the spare upon

More information

Power IT LV Active Filters PQFI PQFM PQFK. The ABB comprehensive solution for active filtering of harmonics

Power IT LV Active Filters PQFI PQFM PQFK. The ABB comprehensive solution for active filtering of harmonics Power IT LV Active Filters PQFI PQFM PQFK The ABB comprehensive solution for active filtering of harmonics Harmonics and Power Quality Power Quality relates to the amplitude, frequency and distortion of

More information

High Performance Process & Temperature Controllers

High Performance Process & Temperature Controllers C22 C62 C82 C83 High Performance Process & Temperature Controllers C72 C42 R22 01. Multi Color LCD Display 02. High Accuracy 18 Bit A-D Input and 15 Bit D-A Output 03. 200 msec Sampling Rate 04. True Universal

More information

XUA1 AC Voltage and phase balance relay. (August 1996) Manual XUA1 (Revision New)

XUA1 AC Voltage and phase balance relay. (August 1996) Manual XUA1 (Revision New) XUA1 AC Voltage and phase balance relay (August 1996) Manual XUA1 (Revision New) Woodward Manual XUA1 GB Woodward Governor Company reserves the right to update any portion of this publication at any time.

More information

Product Data Sheet. Models 1022/1025/1029C/1032/3629B 3629B. Models 1022/1025/1032. Model 1029C. Model 3629B. Phase Angle Power Control

Product Data Sheet. Models 1022/1025/1029C/1032/3629B 3629B. Models 1022/1025/1032. Model 1029C. Model 3629B. Phase Angle Power Control s 1022/1025/1029C/1032/3629B 3629B Product Data Sheet s 1022/1025/1032 Single phase power controllers Current ratings from 10 to 70 Amps 1022-0 to 5VDC or pot input 1025-4 to 20 ma signal 1032 Current

More information

X-Band Redundant LNA Systems

X-Band Redundant LNA Systems X-Band Redundant LNA Systems LRX-1000 Series Introduction Redundant LNA systems minimize system downtime due to LNA failure by providing a spare LNA and an automatic means of switching to the spare upon

More information

WRM-10 TM TRANSFORMER WINDING RESISTANCE METER

WRM-10 TM TRANSFORMER WINDING RESISTANCE METER WRM-10 TM TRANSFORMER WINDING RESISTANCE METER USER S MANUAL Vanguard Instruments Company, Inc. 1520 S. Hellman Ave. Ontario, California 91761, USA TEL: (909) 923-9390 FAX: (909) 923-9391 June 2009 Revision

More information

THYFREC-VT210S 400V System 37 to 315kW (C/T) 400V System 45 to 370kW (V/T) QUICK START GUIDE

THYFREC-VT210S 400V System 37 to 315kW (C/T) 400V System 45 to 370kW (V/T) QUICK START GUIDE MEIDEN AC SPEED CONTROL EQUIPMENT THYFREC-VT210S 400V System 37 to 315kW (C/T) 400V System 45 to 370kW (V/T) QUICK START GUIDE NOTICE 1. Read this manual thoroughly before using the VT210S, and store in

More information

Commissioning Instructions Rev. 03

Commissioning Instructions Rev. 03 Power Factor regulator BLR-CM-T/RT L1 L2 L3 Einspeisung Supply Last Load BLR-CM-T + - Triggereingang/ Triggerinput BEL-TSXX N PE L1 L2 L3 Einspeisung Supply Last Load BLR-CM-RT + - Triggereingang/ Triggerinput

More information

Excellent low-cost Process & Temperature Controllers

Excellent low-cost Process & Temperature Controllers C22 C62 C82 C83 Excellent low-cost Process & Temperature Controllers C72 C42 R22 01. High Quality LCD Display 02. High Accuracy 18 Bit A-D Input and 15 Bit D-A Output 03. The Fast Sampling Rate in 200

More information

Position Indicator model MFC-300/IP. Technical Manual. Licht

Position Indicator model MFC-300/IP. Technical Manual. Licht Position Indicator model MFC-300/IP Technical Manual Licht Contents 1 Introduction 2 2 Front panel indication 3 3 Error indication 4 4 Manual commands 5 5 Configuration 6 5.1 Parameter reset 6 6 Programmable

More information

Product Catalog PRODUCT CATALOG. Power supply system & test equipment

Product Catalog PRODUCT CATALOG. Power supply system & test equipment Product Catalog PRODUCT CATALOG 2018 2018 Power supply system & test equipment. 138/79, Moo 2 Tambon Ban Klang, Amphoe Mueang Pathumthani, Pathumthani Province 12000, Thailand. Tel: +66 21475048-9 Fax:

More information

The universal input/output device is a DIN rail mounted device. It is connected to the EIB via a bus connecting terminal.

The universal input/output device is a DIN rail mounted device. It is connected to the EIB via a bus connecting terminal. , GH Q631 0026 R0111 SK 0097 B97 The universal input/output device is a DIN rail mounted device. It is connected to the EIB via a bus connecting terminal. The device has 32 freely programmable inputs/outputs,

More information

APPLICATION: The heart of the system is a DSR 100 Digital Static Regulator used in conjunction with standard SCR based rectifier bridges.

APPLICATION: The heart of the system is a DSR 100 Digital Static Regulator used in conjunction with standard SCR based rectifier bridges. APPLICATION: Basler Electric offers a New Line of digitally controlled brush (static) or brushless excitation systems designed for use with existing Hydro, Gas as well as Diesel driven generators requiring

More information

COUNTIS E27/E28 Three-phase energy meter Direct - 80 A Ethernet

COUNTIS E27/E28 Three-phase energy meter Direct - 80 A Ethernet INSTRUCTION MANUAL COUNTIS E27/E28 Three-phase energy meter Direct - 80 A Ethernet EN countis e27 countis e28 - mid www.socomec.com/ en/countis-e2x EN Contents 1. Documentation.... 3 2. Hazards and warnings...

More information

S11 Adjustable Speed Drive Engineering Specification

S11 Adjustable Speed Drive Engineering Specification PART 1 - GENERAL 1.0 Scope This specification shall cover Toshiba S11 AC Variable Frequency Drives, 6 pulse for 3- phase 200-240VAC, 380-500VAC and single phase 200V to 240VAC. 1.1 References A. National

More information

ISOMETER IRDH575. Approvals

ISOMETER IRDH575. Approvals Insulation monitoring device for unearthed AC, DC and AC/DC systems (IT systems) with control and display function for EDS insulation fault location systems IRDH575_D00089_02_D_XXEN/09.2018 Insulation

More information

COUNTIS E25/E26 Three-phase active energy meter 63A direct M-BUS

COUNTIS E25/E26 Three-phase active energy meter 63A direct M-BUS COUNTIS E25/E26 Three-phase active energy meter 63A direct M-BUS Operating instructions EN Contents 1. Documentation...3 2. Danger and warning...3 2.1. Risk of electrocution, burns or explosion...3 2.2.

More information

MULTI POWER TRANSDUCER MODEL LSMT4

MULTI POWER TRANSDUCER MODEL LSMT4 ISTRUCTIO MAUAL MULTI POWER TRASDUCER MODEL LSMT4 BEFORE USE... Thank you for choosing M-System. Before use, please check contents of the package you received as outlined below. If you have any problems

More information

Table 6.1 Fault Code List Code indication (Note 3)

Table 6.1 Fault Code List Code indication (Note 3) 62 Table 6.1 Fault List UA801 UA802 UA803 UA804 UA805 UA806 UA807 UA808 UA810 UA812 UA813 UA814 UA815 UA817 UA821 AC VOLTAGE OUT OF RANGE AC FREQUENCY OUT OF RANGE AC PHASE ROTATION ERROR OPE. OVER OVER

More information

Monitoring Relays True RMS 3-Phase, 3-Phase+N, Multifunction Types DPC01, PPC01

Monitoring Relays True RMS 3-Phase, 3-Phase+N, Multifunction Types DPC01, PPC01 Monitoring Relays rue RMS 3-Phase, 3-Phase+, Multifunction ypes DPC01, PPC01 DPC01 Product Description 3-phase or 3-phase+neutral line voltage monitoring relay for phase sequence, phase loss, asymmetry,

More information

FCR 06, FCR 12. Power factor correction controller. User and service manual

FCR 06, FCR 12. Power factor correction controller. User and service manual FCR 06, FCR 12 Power factor correction controller User and service manual version 2.3 Czech Republic Czech Republic 1 Content 1. Control and signal elements... 3 2. Device description... 4 3. Instruction

More information

Data Sheet. Earth Leakage Relay RISH ELR/ELR+/ELR VI/ELR VI(NE) A V RISH ELR VI. Record. Digital Protection Relay RESET TEST ENTER

Data Sheet. Earth Leakage Relay RISH ELR/ELR+/ELR VI/ELR VI(NE) A V RISH ELR VI. Record. Digital Protection Relay RESET TEST ENTER ata Sheet arth eakage Relay RISH R/R+/R VI/R VI() RISH R VI 8.8. 8. 8. V R-1 R-2 igital Protection Relay K RST TST TR nalyze ata Sheet arth eakage Relay RISH R RISH arth eakage Relay is used to etect and

More information