INSTALLATION LOCATIONS: STRUCTURE 37 & 82 DETAIL A DETAIL B TYP OPGW DEADEND ASSEMBLY

Size: px
Start display at page:

Download "INSTALLATION LOCATIONS: STRUCTURE 37 & 82 DETAIL A DETAIL B TYP OPGW DEADEND ASSEMBLY"

Transcription

1 SEE DETAIL "A" SEE DETAIL "B" 25 INSTALLATION LOCATIONS: STRUCTURE 37 & POLE BANDING AS REQ'D SLACK DETAIL A UC Synergetic, 1601 South MoPac Expy. Building 2, Suite 425 Austin, TX INSTALL 12' ABOVE GROUND LEVEL 24 DETAIL B TYP OPGW DEADEND ASSEMBLY NOTE WHEN INSTALLING ON TANGENT STRUCTURES; THIS DETAIL REPLACES THE OPGW SUPPORT FRAMING

2 68 66 INSTALLATION LOCATIONS: STRUCTURE # 1, 128 & 345# POLE BANDING AS REQ'D SLACK INSTALL 12' ABOVE GROUND LEVEL UC Synergetic, 1601 South MoPac Expy. Building 2, Suite 425 Austin, TX 78746

3 UC Synergetic, 1601 South MoPac Expy. Building 2, Suite 425 Austin, TX 78746

4 UC Synergetic, 1601 South MoPac Expy. Building 2, Suite 425 Austin, TX 78746

5 UC Synergetic, 1601 South MoPac Expy. Building 2, Suite 425 Austin, TX 78746

6 UC Synergetic, 1601 South MoPac Expy. Building 2, Suite 425 Austin, TX 78746

7 UC Synergetic, 1601 South MoPac Expy. Building 2, Suite 425 Austin, TX 78746

8 UC Synergetic, 1601 South MoPac Expy. Building 2, Suite 425 Austin, TX 78746

9 UC Synergetic, 1601 South MoPac Expy. Building 2, Suite 425 Austin, TX 78746

10 UC SYNERGETIC, LLC Alvin DeVane Blvd., Suite 510 Austin, TX Date: 02/04/2016 Page: 1 of 3 Revision: AB Total Pages: 3 Pike Job. No.: Company: Project: Document No.: Document Title: WANZEK CONSTRUCTION INC. ODELL Wind Project TRLCAC01 CONDUCTOR AMPACITY CALCULATION Professional Engineer I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under laws of the state of Minnesota. Signature: Typed or Printed Name: Stuart R Akers Date: 2/4/2016 License Number: 52545

11 Conductor Ampacity Calculations Date:2/4/2016 Page 2 of 4 TABLE OF CONTENTS Page 1.0 Conductor Ampacity Study Attachment A Calculation of Conductor Operating Temperature... 3 REVISION AB Revision Description AsBuilt Rev. Date 02/04/2016 Project Manager Chris Ferrell Project Engineer Michael Bauer Project Administrator Quality Manager Stuart Akers This document contains proprietary information of UC Synergetic and is to be returned upon request. Its contents may not be copied, disclosed to third parties, or used for other than the express purpose for which it has been provided without the written consent of UC Synergetic.

12 Conductor Ampacity Calculations Date:02/04/2016 Page 3 of Conductor Ampacity Study 115kV 345kV Utilizing the IEEE Steady State Conductor Temperature calculator in PLS CADD, UC Synergetic (UCS) determined that, at a maximum current of Amps, and assuming an ambient temperature of 95 F, 2ft/s wind speed, and maximum solar heating, the resulting conductor temperature is 167 F, which is less than the specified maximum operating temperature of 175 F for 1272 ACSR Bittern (See Attachment A Calculation of Thermal Rating Conductor Temperature). Therefore, 1272 ACSR Bittern will have sufficient ampacity for the project. Utilizing the IEEE Steady State Conductor Temperature calculator in PLS CADD, UC Synergetic (UCS) determined that, at a maximum current of 524 Amps, and assuming an ambient temperature of 95 F, 2ft/s wind speed, and maximum solar heating, the resulting conductor temperature is 122F, which is less than the maximum operating temperature of 135 F for 795 ACSR Drake (See Attachment A Calculation of Thermal Rating Conductor Temperature). Therefore, 795 ACSR Drake will have sufficient ampacity for the project. 2.0 Attachment A Calculation of Conductor Operating Temperature 115kV IEEE Std method of calculation Air temperature is (deg F) Wind speed is 2.00 (ft/s) Angle between wind and conductor is 90 (deg) Conductor elevation above sea level is 1450 (ft) Conductor bearing is 90 (deg) (user specified bearing, may not be value producing maximum solar heating) Sun time is 14 hours (solar altitude is 75deg. and solar azimuth is 112 deg.) Conductor latitude is 44.0 (deg) Atmosphere is CLEAR Day of year is 172 (corresponds to June 21 in year 2014) (day of the year with most solar heating) Conductor description: 1272 kcmil 45/7 Strands BITTERN ACSR Adapted from 1970's Publicly Available Data Conductor diameter is 1.345(in) Conductor resistance is (Ohm/mile) at 77.0 (deg F) and (Ohm/mile) at (deg F) Emissivity is 0.5and solar absorptivity is 0.5 Solar heat input is (Watt/ft) (corresponds to Global Solar Radiation of (Watt/ft^2) which was calculated)

13 Conductor Ampacity Calculations Date:02/04/2016 Page 4 of 4 Radiation cooling is Convective cooling is (Watt/ft) (Watt/ft) Given a maximum conductor temperature of (deg F), The steadystate thermal rating is amperes 345kV IEEE Std method of calculation Air temperature is (deg F) Wind speed is 2.00 (ft/s) Angle between wind and conductor is 90 (deg) Conductor elevation above sea level is 1450 (ft) Conductor bearing is 90 (deg) (user specified bearing, may not be value producing maximum solar heating) Sun time is 11 hours (solar altitude is 66 deg. and solar azimuth is 144 deg.) Conductor latitude is 44.0 (deg) Atmosphere is CLEAR Day of year is 172 (corresponds to June 21 in year 2015) (user specified day, may not be day producing maximum solar heating) Conductor description: 795kcmil 26/7 Strands DRAKE ACSR Adapted from 1970's Publicly Available Data Conductor diameter is (in) Conductor resistance is (Ohm/mile) at 77.0 (deg F) and (Ohm/mile) at (deg F) Emissivity is 0.5and solar absorptivity is 0.5 Solar heat input is 4.435(Watt/ft) (corresponds to Global Solar Radiation of (Watt/ft^2) which was calculated) Radiation cooling is (Watt/ft) Convective cooling is (Watt/ft) Given a maximum conductor temperature of (deg F), The steadystate thermal rating is amperes

14 UC SYNERGETIC, LLC Alvin DeVane Blvd., Suite 510 Austin, TX Date: 02/04/2016 Page: 1 of 6 Revision: AB Total Pages: 6 Pike Job. No.: Company: WANZEK CONSTRUCTION INC. Project: ODELL Wind Project Document No.: TRLCCC01 Document Title: CORONA CALCULATION Professional Engineer I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under laws of the state of Minnesota. Signature: Typed or Printed Name: Stuart R Akers Date: 2/4/2016 License Number: 52545

15 Corona Calculations Date:02/04/2016 Page 2 of 7 TABLE OF CONTENTS Page 1.0 Attachment A Corona Design Calculations Attachment B Corona Analysis Comparison Calculations... 6 REVISION AB Revision Description AsBuilt Rev. Date 02/04/2016 Project Manager Chris Ferrell Project Engineer Michael Bauer Project Administrator Quality Manager Stuart Akers This document contains proprietary information of UC Synergetic and is to be returned upon request. Its contents may not be copied, disclosed to third parties, or used for other than the express purpose for which it has been provided without the written consent of UC Synergetic.

16 Corona Calculations Date:02/04/2016 Page 3 of Attachment A Corona Design Calculations kV Conductor795 ACSR Drake System Voltage Data V(pp) 345 kv, Nominal Phase to Phase Voltage of the System 5 Percent increase for maximum voltage Vm(pp) kv, Maximum Nominal Phase to Phase Voltage of System V(pg) kv, Phase to Ground Voltage, V during analysis A 1450 ft, Project Maximum Altitude Conductor Data Code Name Drake Type ACSR size 795 kcmil diameter in D 26 ft, distance between Phases n 2 number of conductors per bundle per phase s 18 in, distance between conductors of bundle h 26.8 ft, height of center of bus above ground T 110 F, Temperature of Air Conversion Formulas Used During the Calculations 1 in. = 2.54 cm for all calculations F=C*9/5+32 C=(F32)*5/9 1 ft = km Corona Onset Gradient Eo= m Eg*Da*{1+C/(Da* re) 1/2 } m Conductor Typical Irregularity Factor Eo Corona Onset gradient for differnet m Eg 21.1 kv/cm, An Empircal Constant C /cm, An Empircal Constant Da 0.90 is the relative air density re 7.96 cm, Conductor outside equivilent radius for a bundle Relative Air Density, Da Da=(P/Po)*(273+To)/(273+T) Da 0.90 is the relative air density T Temperature of Air To deg C P/Po 0.96 P/Po = 1A/10 A 0.44 km, Altitude

17 Corona Calculations Date:02/04/2016 Page 4 of 7 Average and Maximum voltage Gradients at the Surface of the Conductors Ea = V/(n*r*LN(2*he/re)) Em = Ea(he/(here)) Ea kv/cm, Average Voltage Gradient Em kv/cm, Maximum Voltage Gradient V kv, Line to Ground Voltage d 2.77 cm, conductor diameter h cm, Height of conductor center from ground D cm, phase to phase spacing Equivalent distance from center of bus toground plane for Three Phases he = (h*d)/((4h 2 + D 2 ) 1/2 ) he cm, Equivilent distance from center of bus to ground plane Equivalent Single conductor Radius for Bundled Conductors re = r(g*s/r) ((n1)/n) re 7.96 cm, Equivalent Single conductor Radius g 1 g = 1 if n<4 otherwise g= 1.12 r 1.39 cm, Conductor outside radius s cm, distance between conductors of bundle n 2 number of conductors per bundle per phase

18 Corona Calculations Date:02/04/2016 Page 5 of kv Conductor 1272 ACSR BITTERN System Voltage Data kv, Nominal Phase to Phase Voltage of V(pp) 115 the System 5 Percent increase for maximum voltage Vm(pp) kv, Maximum Nominal Phase to Phase Voltage of System V(pg) kv, Phase to Ground Voltage, V during analysis A 1450 ft, Project Maximum Altitude Conductor Data Code Name Bittern Type ACSR size 1272 kcmil diameter in D 21 ft, distance between Phases (maximum) n 1 number of conductors per bundle per phase s in, distance between conductors of bundle h 26.8 ft, height of center of bus above ground T 120 F, Temperature of Air Conversion Formulas Used During the Calculations 1 in. = 2.54 cm for all calculations F=C*9/5+32 C=(F32)*5/9 1 ft = km Corona Onset Gradient Eo= m Eg*Da*{1+C/(Da* re) 1/2 } m Conductor Typical Irregularity Factor Eo Corona Onset gradient for different m Eg 21.1 kv/cm, An Empirical Constant C /cm, An Empirical Constant Da 0.88 is the relative air density re 1.71 cm, Conductor outside equivalent radius for a bundle Relative Air Density, Da Da=(P/Po)*(273+To)/(273+T) Da 0.88 is the relative air density T Temperature of Air To deg C P/Po 0.96 P/Po = 1A/10 A 0.44 km, Altitude

19 Corona Calculations Date:02/04/2016 Page 6 of 7 Average and Maximum voltage Gradients at the Surface of the Conductors Ea = V/(n*r*LN(2*he/re)) Em = Ea(he/(here)) Ea 6.97 kv/cm, Average Voltage Gradient Em 7.01 kv/cm, Maximum Voltage Gradient V kv, Line to Ground Voltage d 3.42 cm, conductor diameter h cm, Height of conductor center from ground D cm, phase to phase spacing Equivalent distance from center of bus toground plane for Three Phases he he = (h*d)/((4h 2 + D 2 ) 1/2 ) cm, Equivalent distance from center of bus to ground plane Equivalent Single conductor Radius for Bundled Conductors re = r(g*s/r) ((n1)/n) re 1.71 cm, Equivalent Single conductor Radius g 1 g = 1 if n<4 other wise g= 1.12 r 1.71 cm, Conductor outside radius s 0.00 cm, distance between conductors of bundle n 1 number of conductors per bundle per phase 2.0 Attachment B Corona Analysis Comparison Calculations kV Conductor Corona Analysis Comparison of Em and EoValues of Various Conductor Configurations Em values Eocalculations, kv/cm ACSR Conductor Name Conductor Diameter kcmil Number of Conductors Em At At At in n kv/cm m= m= m= Drake Cardinal Bittern Bluebird Drake Cardinal Bittern Falcon Mockingbird Legend: If the Eo cell is red, Em>Eo and does not meet IEEE 605, 2008 requirements If cell is green Em<Eo, and meets IEEE 605, 2008 requirements

20 Corona Calculations Date:02/04/2016 Page 7 of kV Conductor Corona Analysis Comparison of Em and EoValues of Various Conductor Configurations Em values Eocalculations, kv/cm ACSR Conductor Name Conductor Diameter kcmil Number of Conductors Em At At At in n kv/cm m= m= m= Tern Cardinal Bittern Falcon Tern Cardinal Bittern Falcon Mockingbird Legend: If the Eo cell is red, Em>Eo and does not meet IEEE 605, 2008 requirements If cell is green Em<Eo, and meets IEEE 605, 2008 requirements

21 UC SYNERGETIC, LLC South Mopac Expy. Building 2, Suite 425 Austin, TX Date: 02/04/2016 Page: 1 of 13 Revision: AB Total Pages: 13 Pike Job. No.: Company: WANZEK CONSTRUCTION Inc. Project: ODELL Wind Project Document No.: TRLCDC01 Document Title: TRANSMISSION DESIGN CRITERIA WANZEK CONSTRUCTION Inc. ODELL WIND PROJECT 115/345 kv TRANSMISSION DESIGN CRITERIA Professional Engineer I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under laws of the state of Minnesota. Signature: Typed or Printed Name: Date: License Number:

22 UC SYNERGETIC, LLC South Mopac Expy. Building 2, Suite 425 Austin, TX Date: 02/04/2016 Page: 2 of 13 Revision: AB Total Pages: 13 Pike Job. No.: Company: WANZEK CONSTRUCTION Inc. Project: ODELL Wind Project Document No.: TRLCDC01 Document Title: TRANSMISSION DESIGN CRITERIA REVISION AB B C D E 0 Revision Description Initial Issue Rev. Date 2/4/16 Project Manager Chris Ferrell Project Engineer Stuart Akers Project Administrator Quality Manager Stuart Akers This document contains proprietary information of UC Synergetic and is to be returned upon request. Its contents may not be copied, disclosed to third parties, or used for other than the express purpose for which it has been provided without the written consent of UC Synergetic.

23 UC SYNERGETIC, LLC South Mopac Expy. Building 2, Suite 425 Austin, TX Date: 02/04/2016 Page: 3 of 13 Revision: AB Total Pages: 13 Pike Job. No.: Company: WANZEK CONSTRUCTION Inc. Project: ODELL Wind Project Document No.: TRLCDC01 Document Title: TRANSMISSION DESIGN CRITERIA TABLE OF CONTENTS 1.0 Project Overview Conductor and Overhead Ground Wire Data Design Criteria Summary Pole Design Parameters Clearance Load Cases Uplift Special Load Cases Stringing tables Elevation Vertical Ground Clearances Vertical Clearance to Railroads, Roads, Pedestrian/Restricted & Water Areas Vertical Clearance between conductors at supports of the same utility Conductor clearance in any direction Materials Insulators Conductor Selection OPGW Selection... 13

24 UC SYNERGETIC, LLC South Mopac Expy. Building 2, Suite 425 Austin, TX Date: 02/04/2016 Page: 4 of 13 Revision: AB Total Pages: 13 Pike Job. No.: Company: WANZEK CONSTRUCTION Inc. Project: ODELL Wind Project Document No.: TRLCDC01 Document Title: TRANSMISSION DESIGN CRITERIA 1.0 Project Overview The ODELL Wind Transmission Line project consists of approximately 8.5 miles of 115 kv singlecircuit transmission line that takes the 115kV wind energy to the 115/345 kv ProjectBuilt Substation. A 550 long, 345kV overhead circuit will be built to tiein to the substation. The transmission line will be designed with a single 1272 ACSR BI TERN conductor sized to carry 1057A and a bundled 795 ACSR DRAKE conductor sized to carry 371A, 24 Fiber optical ground wires (OPGW) and 7/16 E.H.S. guy wire. The line is designed for electrical loads of 200MW. All structures to be designed in accordance with this Design Criteria developed in accordance with NESC C22012 and to maintain power factor of 0.95 lagging to 0.95 loading at the POI. Structures types Wood Braced Post with a height range of and class H1H4 for the 115kV Transmission Line and Engineering Steel for the 115kV/345KV deadend and running angle structures with a height range of Basic Identification Data No. 1 Line Name Odell Wind Energy Project 2 Owner s Designation and Name ODELL Wind LLC. 3 Location Cottonwood, Jackson, Martin and Watonwon Counties, MN 4 Summary Prepared By Elena Tomadakis 5 Date December 19th, Revision No. E 7 Revision Prepared By Elena Tomadakis 8 Revision Date April 2 nd, 2015

25 UC SYNERGETIC, LLC South Mopac Expy. Building 2, Suite 425 Austin, TX Date: 02/04/2016 Page: 5 of 13 Revision: AB Total Pages: 13 Pike Job. No.: Company: WANZEK CONSTRUCTION Inc. Project: ODELL Wind Project Document No.: TRLCDC01 Document Title: TRANSMISSION DESIGN CRITERIA 1.2 General Information No. Classification Description 1 Owner ODELL Wind LLC. 2 Line Identification Odell Wind Energy Project 3 Plan and Profile Drawing TRLCPP01 thru TRLCPP09/ TRLCPP10 4 Voltage 115kV/345kV 5 Line Length 8.5 miles/ Structure Type Refer to TRLCSL01 7 Basic Structure Height Class Refer to TRLCSL01 through TRLCSL06 Refer to TRLCSL01 through TRLCSL06 a. Maximum Total Generation Capacity 200MW 1 00 Wind 2.0 MW per turbine 8 b. Maximum 115/345 KV Ampacity Required at Power Factor of A /371A 9 Average Spans Horizontal 115KV Horizontal 345KV 370 ft 550 ft

26 UC SYNERGETIC, LLC South Mopac Expy. Building 2, Suite 425 Austin, TX Date: 02/04/2016 Page: 6 of 13 Revision: AB Total Pages: 13 Pike Job. No.: Company: WANZEK CONSTRUCTION Inc. Project: ODELL Wind Project Document No.: TRLCDC01 Document Title: TRANSMISSION DESIGN CRITERIA 2.0 Conductor and Overhead Ground Wire Data No. 1 Line Conductor 115kV/345kV a. Size Description 115kV: 1272 ACSR 45/7 stranding 345kV:Bundled 795 ACSR 26/7stranding b. Diameter in in c. Weight lbs/ft lbs/ft. d. Design Tension 3,000 lbs 5,000 lbs e. Reduced Tension 2,000 lbs 1,000 lbs 2 Fiber Optical Overhead Ground Wire a. Size 24 Fibers b. Material OPGW c. Weight lbs/ft. d. Design Tension 1,500 3,500 e. Reduced Tension 1,000 lbs 1,000 lbs 3 7/16 E.H.S. Steel Overhead Ground Wire f. Size 7/16 H.S. 7strands g. Material Steel 0.36 dia (in) h. Weight lbs/ft 10,800 R.B.S. (lbs) i. Design Tension 4,000 lbs j. Reduced Tension 3.0 Design Criteria Summary Loading Requirements: o NESC C22012 Design Criteria: 1,000 lbs NESC C22012 (250B Heavy District) NESC C22012 (250B Heavy District)

27 UC SYNERGETIC, LLC South Mopac Expy. Building 2, Suite 425 Austin, TX Date: 02/04/2016 Page: 7 of 13 Revision: AB Total Pages: 13 Pike Job. No.: Company: WANZEK CONSTRUCTION Inc. Project: ODELL Wind Project Document No.: TRLCDC01 Document Title: TRANSMISSION DESIGN CRITERIA Row# Description/ Condition NESC Heavy (250B) Extreme Wind (250C) Extreme Ice/Wind (250D) Wind Velocity (mph) Wind Pressure (psf) Wire Ice Thickness (in) Wire Temp. (deg F) Weather Load Factor NESC Constant (lbs/ft) Uplift No Wind (SWING 1) Moderate Wind (SWING 2) Moderate Wind (SWING 3) GALLOPING (SWING 4) GALLOPING (SAG) Deg F Deg F Deg F Deg F Deg F Deg F o The overload factors associated with the above design criteria will be as follows, as per NESC C22012 Table 2531: Loading Case Vertical Wind Tension NESC Loading Zone

28 UC SYNERGETIC, LLC South Mopac Expy. Building 2, Suite 425 Austin, TX Date: 02/04/2016 Page: 8 of 13 Revision: AB Total Pages: 13 Pike Job. No.: Company: WANZEK CONSTRUCTION Inc. Project: ODELL Wind Project Document No.: TRLCDC01 Document Title: TRANSMISSION DESIGN CRITERIA NESC Extreme Wind NESC Extreme Ice with Concurrent Wind o Maximum Design Tension: Conductors limited to 60% RBS for NESC 250B Loads with safety factor of 1.0. Conductors limited to 80% RBS for NESC 250C and 250D Loads with safety factor of 1.0. All wires limited to initial unloaded tension limited to 35% RBS at 30 F (NESC 250B LLZ), or at 60 F with appropriately applied vibration control All wires limited to final unloaded tension limited to 25% RBS at 30 F (NESC 250B LLZ), or at 60 F with appropriately applied vibration control o Max Operating Temperature 115kV TL: 175 o F o Max Operating Temperature 345kV TL: 135 F o Construction NESC Grade B o Terminal and dead end angle structures, conductor attachment arms and arm connections shall be designed to limit damage and mitigate a cascading failure under loading associated with a broken single longitudinal transmission conductor or shield wire. 4.0 Pole Design Parameters Performance Criteria Total Deflection Total Rotation Nonrecoverable Deflection Nonrecoverable Rotation: 3 Inches 1 Degree 1 Inches 0.5 Degree 5.0 Clearance Load Cases a. Max Operating Temp 115kV: 175 o F b. Max Operating Temp 345kV: 135 F c. NESC Heavy Loading Zone: 0 o F, 4 psf wind, 0.5 ice

29 UC SYNERGETIC, LLC South Mopac Expy. Building 2, Suite 425 Austin, TX Date: 02/04/2016 Page: 9 of 13 Revision: AB Total Pages: 13 Pike Job. No.: Company: WANZEK CONSTRUCTION Inc. Project: ODELL Wind Project Document No.: TRLCDC01 Document Title: TRANSMISSION DESIGN CRITERIA d. Blow out: 6 psf wind, 60 deg F e. No wind: 0 psf wind, 60 deg F 6.0 Uplift a. Cold Case: 20 deg F b. Every Day: No wind, 60 deg F c. NESC Load case with vertical OCF = Special Load Cases a. Broken conductor: Tension of a broken phase conductor shall be modeled in PLS CADD to ensure one broken conductor of a two conductor bundle does not cause irreparable harm to the supporting pole. This shall be modeled by removing one conductor from either side of the conductor support attachments under everyday weather conditions (60 o F, no wind, no ice). b. Broken Over Head Static Wire (OHSW) or Optical Ground Wire (OPGW): Tension of a broken OHSW or OPGW conductor shall be modeled in PLS CADD to ensure a broken conductor does not cause irreparable harm to the supporting pole. This shall be modeled by removing one conductor from either side of the conductor support attachments under everyday weather conditions (60 o F, no wind, no ice). c. DeadEnd Structures: All deadend structures shall be designed to withstand the loads created by removing all the conductors on one side of the structure creating a single deadend or terminal deadend condition d. Weather Conditions and Overload Capacity Factors as shown below: Description Weather Overload Capacity Factors Loading Case Temp. Wind Ice Vertical Wind Tension Broken conductor 60 o F 0 psf No ice Broken OHSW or OPGW 60 o F 0 psf No ice Stringing tables a. Temperature: 0 F to 115 F listed utilizing 5 degree increments

30 UC SYNERGETIC, LLC South Mopac Expy. Building 2, Suite 425 Austin, TX Date: 02/04/2016 Page: 10 of 13 Revision: AB Total Pages: 13 Pike Job. No.: Company: WANZEK CONSTRUCTION Inc. Project: ODELL Wind Project Document No.: TRLCDC01 Document Title: TRANSMISSION DESIGN CRITERIA b. Spans per Plan and Profile drawings. Span increments will be determined after spotting is complete. UCS will either utilize a span increment of 10 feet or by actual span lengths depending on the number of spans required. 9.0 Elevation 1450 feet above Mean Sea Level 10.0 Vertical Ground Clearances 345 kv NESC minimum ground clearance 26 ft. Clearance based on phase to ground voltage. 115kV NESC minimum ground clearance 21.2 ft. Clearance based on phase to ground voltage Vertical Clearance to Railroads, Roads, Pedestrian/Restricted & Water Areas The vertical clearances (NESC without buffer) used in the design of the ODELL Wind Line are as follows. No. Description 345kV 115KV 1 Railroads Roads Pedestrian/Restricted Water Areas (Not suitable for sailing) Vertical Clearance between conductors at supports of the same utility Minimum vertical clearance at structure between conductors: 345 kv clearance per NESC C22012 Table 2355 = 16in+[0.4 in/kv*((345kv*1.1)/ 3)8.7kV] = in =8.3

31 UC SYNERGETIC, LLC South Mopac Expy. Building 2, Suite 425 Austin, TX Date: 02/04/2016 Page: 11 of 13 Revision: AB Total Pages: 13 Pike Job. No.: Company: WANZEK CONSTRUCTION Inc. Project: ODELL Wind Project Document No.: TRLCDC01 Document Title: TRANSMISSION DESIGN CRITERIA 115 kv clearance per NESC C22012 Table 2355 = 16in+[0.4 in/kv*((115kv*1.1)/ 3)8.7kV] = in = Conductor clearance in any direction Clearance in any direction from supply lines to surface of support arms (Phase to Ground): a. 345 kv NESC minimum clearance, per Rule 235E and Table 2356: [11in+0.2 in/kv*(345kv*1.1/ 3)50 kv)] = 44.8in =3.7 b. 115 kv NESC minimum clearance, per Rule 235E and Table 2356: [11in+0.2 in/kv*(115kv*1.1/ 3)50 kv)] =15.6in =1.3 Clearance from supply lines to Guys in any direction c. 345 kv NESC minimum clearance, per Rule 235E and Table 2356 = [16in+(0.25in/kV)*(345kV*1.1/ 3) 50 kv)] = 58.3 in=4.9 d. 115 kv NESC minimum clearance, per Rule 235E and Table 2356 = [16in+(0.25in/kV)*(115kV*1.1/ 3) 50 kv)] = 21.8 in=1.81 Clearance from OPGW to supply lines in any direction e. 345 kv NESC minimum clearance, per Rule 235E and Table 2356 =[29in+(0.4in/kV)*(345 kv*1.1/ 3)50 kv)] = 96.6 in = Materials a. NESC Grade B construction material safety factors i. Material strength factors from NESC 2012 Table 2611: 1. Rule 250B for metal and prestressed concrete structures, crossarms and braces: Rule 250B for wood structures and crossarms: Rule 250B for guy wires: Rule 250B for guy anchor and foundation: Rule 250C for wood structures and crossarms: Rule 250C for guy wires: 0.9

32 UC SYNERGETIC, LLC South Mopac Expy. Building 2, Suite 425 Austin, TX Date: 02/04/2016 Page: 12 of 13 Revision: AB Total Pages: 13 Pike Job. No.: Company: WANZEK CONSTRUCTION Inc. Project: ODELL Wind Project Document No.: TRLCDC01 Document Title: TRANSMISSION DESIGN CRITERIA 7. Rule 250C for guy anchor and foundation: Rule 277 for Insulators based on NESC 250B loads without Load Factors: a. Line Post Insulators: i. 40% Cantilever strength ii. 50% Tension and Compressive Strength b. Suspension type: 50% Combined mechanical and electrical strength b. Foundations: i. Designed based on the ODELL Project Geotechnical Report, utilizing MFAD or LPile. c. Structures: i. All structures shall be modeled using Method 4 modeling in PLSPOLE. ii. Structures shall be designed utilizing Wood Braced Post for tangent structures, and engineered steel for RA and DeadEnd structures Insulators a. Per NESC 2012 Table 2731 Insulation level requirements for 345 kv Suspension/Strain Insulators: i.nesc 2012 Table 2731 Rated dry flashover voltage of insulators: 830 kv. ii.insulator strengths shall be governed by NESC C22012 Table b. Per NESC 2012 Table 2731 Insulation level requirements for 115 kv Suspension/Strain Insulators: i. NESC 2012 Table 2731 Rated dry flashover voltage of insulators: 315 kv. ii. Insulator strengths shall be governed by NESC C22012 Table Conductor Selection A study was performed to confirm that single 1272 ACSR Bittern for the 115kV TL and 795 ACSR Drake for the 345kV TL met the requirements of the project. This study took into consideration corona effects; audible noise and conductor ampacity (Refer to TRLCCC01).

33 UC SYNERGETIC, LLC South Mopac Expy. Building 2, Suite 425 Austin, TX Date: 02/04/2016 Page: 13 of 13 Revision: AB Total Pages: 13 Pike Job. No.: Company: WANZEK CONSTRUCTION Inc. Project: ODELL Wind Project Document No.: TRLCDC01 Document Title: TRANSMISSION DESIGN CRITERIA 17.0 OPGW Selection UCS recommends using a SFPOC/SFSJJ10377 (24 Fiber) which can withstand a 96ka fault for 33.5 cycles for the 115KV TL and a SFPOC/SFSJJ10377 (24 Fiber) which can withstand a 96ka fault for 10.8 cycles for the 345kV TL.

34 UC SYNERGETIC, LLC Alvin DeVane Blvd., Suite 510 Austin, TX Date: 02/04/2016 Page: 1 of 3 Revision: AB Total Pages: 3 Pike Job. No.: Company: WANZEK CONSTRUCTION INC. Project: ODELL Wind Project Document No.: TRLCSC01 Document Title: SHIELD ANGLE CALCULATION Professional Engineer I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under laws of the state of Minnesota. Signature: Typed or Printed Name: Stuart R Akers Date: 2/4/2016 License Number: 52545

35 TD04.01:Overhead Transmission Line Steel Pole Specification Date:02/04/2016 Page 2 of 4 TABLE OF CONTENTS Page 1.0 Attachment A Shield Angle Calculation... 3 REVISION AB 1 2 Revision Description Asbuilt Rev. Date 02/04/2016 Project Manager Chris Ferrell Project Engineer Michael Bauer Project Administrator Quality Manager Stuart Akers This document contains proprietary information of UC Synergetic and is to be returned upon request. Its contents may not be copied, disclosed to third parties, or used for other than the express purpose for which it has been provided without the written consent of UC Synergetic.

36 Shield Angle Calculation Date:02/04/2016 Page 3 of 4 Attachment A Shield Angle calculation per EPRI Red Book 115kV

37 Shield Angle Calculation Date:02/04/2016 Page 4 of 4 345kV

38 UC SYNERGETIC, LLC Alvin DeVane Blvd., Suite 510 Austin, TX Date: 02/04/2016 Page: 1 of 3 Revision: AB Total Pages: 3 Pike Job. No.: Company: Project: Document No.: Document Title: WANZEK CONSTRUCTION INC. ODELL Wind Project TRLCTR01 CONDUCTOR THERMAL RATING CALCULATION Professional Engineer I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under laws of the state of Minnesota. Signature: Typed or Printed Name: Stuart R Akers Date: 2/4/2016 License Number: 52545

39 TD04.01:Overhead Transmission Line Steel Pole Specification Date:02/04/2016 Page 2 of 4 TABLE OF CONTENTS Page 1.0 Attachment A Calculation of Conductor Thermal rating... 3 REVISION AB Revision Description AsBuilt Rev. Date 02/04/2016 Project Manager Chris Ferrell Project Engineer Michael Bauer Project Administrator Quality Manager Stuart Akers This document contains proprietary information of UC Synergetic and is to be returned upon request. Its contents may not be copied, disclosed to third parties, or used for other than the express purpose for which it has been provided without the written consent of UC Synergetic.

40 Conductor Thermal Rating Date:02/04/2016 Page 3 of Attachment A Calculation of Conductor Thermal rating KV

41 Conductor Thermal Rating Date:02/04/2016 Page 4 of KV Cable File Name Voltage (kv) Calculation Method Cable Steady State Current (Amps) Number of Wires per Phase Current for each wire Cable Surface Temp (deg F) Cable Core Temp (deg F) Solar Radiation Method Global Solar Radiation Day of (Watt/ft^2) Year Line Azimuth (deg) Conductor Latitude (deg) Sun Time Atmosphere IEEE 795 ACSR "Dra ke" Standard Calculated Clear 10 Soil, Grass, Crops ACSR "Dra ke" IEEE Standard Calculated Clear 10 Soil, Grass, Crops ACSR "Dra ke" IEEE Standard Calculated Clear 10 Soil, Grass, Crops Radiation Percentage Increase Ground Type Air Temp (deg F) Wind Speed (ft/s) Global Wind Direction (deg) WindTo Conductor Angle (deg) Conductor Altitude (ft) Cable Emissivity Coefficient from File Cable Asorptivity Coefficient from File Cable Emissivity Coefficient for Calculation Cable Asorptivity Coefficient for Calculation

42 TRANSMISSION LINE SPECIFICATION TITLE: ODELL Conductor Specification REV.: AB VERIFICATION OF SPECIFICATION Anticipated Purchaser Specification Title Wanzek Construction, Inc. ODELL Conductor Specification Specification No. ODELL.SD01 Revision No. AB Revision Date: 02/04/2016 In accord with established procedures, the quality of this specification has been assured. Signatures below certify that the above specification was originated, reviewed, and approved as noted. Prepared By: Elena Tomadakis Date: 02/04/16 Checked By: Michael Bauer Date: 02/04/1 6 Approved By: Stuart Akers Date: 02/04/16 Revision Log: AB. AsBuilt Professional Engineer I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under laws of the state of Minnesota. Signature: Typed or Printed Name: Stuart R Akers Date: 2/4/2016 License Number: 52545

43 TRANSMISSION LINE SPECIFICATION TITLE: ODELLConductor Specification REV.: AB TABLE OF CONTENTS PAGE 1.0 GENERAL DESCRIPTION ORDERING INFORMATION PRODUCTS MATERIAL Conductor Tests and Test Report Packaging Package Marking Delivery Instructions Inquiries Regarding this Specification APPLICABLE CODES AND STANDARDS AMERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM) STANDARDS AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)...5

44 TRANSMISSION LINE SPECIFICATION TITLE: ODELLConductor Specification REV.: AB 1.0 GENERAL 1.1 DESCRIPTION This specification covers steel reinforced aluminum conductor for use as electrical conductor on the overhead transmission systems. 1.2 GENERAL DESIGN CRITERIA Kv Conductor Size: The 345kV conductor shall be bundled 795 ACSR DRAKE sized to carry 371A kV Conductor Size: The 115kV conductor shall be single 1272 ACSR BITTERN sized to carry 1057A. 1.3 ORDERING INFORMATION The conductor size expressed in circular mil area, the conductor stranding, the quantity of each size expressed in pounds, the surface finish if nonspecular, the number of reels, and the reel size will be stated in the Purchase Order and Table 1, Package Sizes. 2.0 PRODUCTS 2.1 MATERIAL Conductor a. All conductor furnished in accordance with this specification shall be Class AA as defined in ASTM B232 (Reference 3.1.1). b. Steel core wire shall be zinccoated with Class A coating and produced in accordance with ASTM B498 (Reference 3.1.2). c. The stranded steel core shall be produced in accordance with ASTM B500 (Reference 3.1.3). d. The complete conductor shall be produced in accordance with ASTM B232 (Reference 3.1.1), except that the total number of welds in the finished aluminum wires composing the conductor may not exceed three (3) welds per reel of conductor.

45 TRANSMISSION LINE SPECIFICATION TITLE: ODELLConductor Specification REV.: AB e. A nonspecular finish, when required, shall be produced in accordance with ANSI C7.69 (Reference 3.2.1). The nonspecular finished conductor shall have radio interference mechanical and electrical properties equal to that of the normal finished conductor. f. For the aluminum rod material, one rod source, one fabrication method, and one factory operating under essentially the same conditions shall be used for the entire quantity of each conductor size specified Tests and Test Report a. The number and type of tests to be performed during manufacture shall be in accordance with the requirements of ASTM B232, ASTM B498, and ASTM B500 (References 3.1.1, 3.1.2, and 3.1.3). b. Additional tests, when required, shall be stated in the Purchase Order. c. One copy of the complete results of all tests required in the applicable specifications shall be sent to the purchasing agent prior to the shipment of material. d. All test reports shall show the limits of acceptability, as defined in the appropriate specifications, for the test values reported Packaging a. The Owner s standard conductor sizes, reel lengths, and reel sizes are shown in Table 1. b. Conductor lengths are to be within minus zero (0) to 2% of the specified reel length and no random lengths will be accepted. c. Any exception to the reel sizes shown in Table 1 must be approved by OWNER prior to packaging. d. All reels are to be furnished with wood lagging. e. The conductor shall be tightly and uniformly spooled on the reel and the ends of the cable shall be secured to prevent loosening of the cable wraps during transit and handling Package Marking Package marking shall be in accordance with the requirements of ASTM B232 (Reference 3.1.1). In addition, the inside and outside package marking shall include the method of rod manufacture (rolled ingot or continuous cast), the surface finish if nonspecular.

46 TRANSMISSION LINE SPECIFICATION TITLE: ODELLConductor Specification REV.: AB Delivery Instructions Instructions for delivery and advance notification of shipment, if required, will be stated on the Purchase Order Inquiries Regarding this Specification Any questions regarding this specification should be directed to the purchasing agent. Conductor Size and Stranding 795 ACSR 26/7 Drake (345kV) 1272 ACSR 45/7 Bittern (115kV) Table 1: Package Size Code Name Total Length (ft) Reel Size Drake 4,800 6,940 Bittern 145,000 12, APPLICABLE CODES AND STANDARDS The following documents of the issue in effect on the date of material purchase form part of this specification. 3.1 American Society for Testing and Materials (ASTM) Standards ASTM B232, Standard Specification for ConcentricLayStranded Aluminum Conductors, Coated Steel Reinforced (ACSR) ASTM B498, Standard Specification for ZincCoated (Galvanized) Steel Core Wire for Use in Overhead Electrical Conductors ASTM B500, Standard Specification for Metallic Coated Stranded Steel Core for Use in Overhead Electrical Conductors 3.2 American National Standards Institute (ANSI) ANSI C7.69, Standard for NonSpecular Surface Finish on Bare Overhead Aluminum Conductors

47 TRANSMISSION LINE SPECIFICATION TITLE: ODELL OPGW Specification REV.: AB VERIFICATION OF SPECIFICATION Anticipated Purchaser Specification Title Wanzek Construction, Inc. ODELL OPGW Specification Specification No. ODELL.SD02 Revision No. AB Revision Date: 02/04/16 In accord with established procedures, the quality of this specification has been assured. Signatures below certify that the above specification was originated, reviewed, and approved as noted. Prepared By: Elena Tomadakis Date: 02/04/16 Checked By: Michael Bauer Date: 02/04/1 6 Approved By: Stuart Akers Date: 02/04/16 Revision Log: AB AsBuilt Professional Engineer I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under laws of the state of Minnesota. Signature: Typed or Printed Name: Stuart R Akers Date: 2/4/2016 License Number: 52545

48 TRANSMISSION LINE SPECIFICATION TITLE: ODELLOPGW Specification REV.: AB TABLE OF CONTENTS PAGE 1.0 ITEM SCOPE USE CABLE MANUFACTURER S SPECIFIC REQUIREMENTS FIBER OPTIC CABLE CONSTRUCTION OPTICAL FIBERS COMPOSITE CABLE Cable Construction Mechanical Parameters Temperature Requirements INSPECTION, TESTS, AND DOCUMENTATION MANUFACTURER DESIGN TESTS HARDWARE REQUIREMENTS APPLICABLE CODES AND STANDARDS... 7

49 TRANSMISSION LINE SPECIFICATION TITLE: ODELLOPGW Specification REV.: AB 1. ITEM This specification details the the Optical Ground Wire (OPGW) and hardware required for this project. 2. SCOPE 3. USE The project consists of a 200MW Wind Farm Plant located approximately 8 miles east of the Town of Windom, Minnesota, with land control in parts of Cottonwood, Jackson, Martin and Watonwon Counties; called the ODELL Wind Project The site elevation is approximately 1450ft AMSL and is subject to high 90mph winds This specification covers the requirements for the OPGW of the 115kV and 345kV Transmission Lines This specification sets forth the minimum functional and performance requirements for optical ground wire to be used on this project. The cable shall be designed for aerial installation on electric utility power lines and will occupy the standard overhead shield wire position located in the top position above the phase conductors. The cable shall serve dual functions as a ground wire and as a telecommunications cable designed for the highspeed transmission of voice, data, and video communications. If the supplier can recommend an alternate product that deviates from the base specification, the alternative should be provided in additional a response that meets the base specifications. 4. CABLE MANUFACTURER S SPECIFIC REQUIREMENTS The cable manufacturer shall have and submit proof at the time of the bid that demonstrates at least 10 continuous years of experience in manufacturing and engineering optical ground wire cable systems. The Cable Manufacturer shall be responsible for all phases of manufacturing, packaging, and the safe keeping of the fiberoptic cable while at their facility. Prior to shipping, the Cable Manufacturer shall test each optical fiber to verify conformance to the specification herein and the Optical Glass Fiber Manufacturer's specifications. Each of the optical fibers in each of the cable reels shall be completely tested with an Optical Time Domain Reflectometer (OTDR) at optical wavelengths specified on an endtoend basis. A printed hard

50 TRANSMISSION LINE SPECIFICATION TITLE: ODELLOPGW Specification REV.: AB copy of the final test data completed prior to shipment shall be attached in a waterproof envelope or pouch to each reel of cable provided. 5. FIBER OPTIC CABLE CONSTRUCTION The following Sections 0 and 0 set forth the desired construction details and minimum requirements of the optical ground wire. A detailed description of the cable that is proposed by the bidder shall be provided to the purchaser for evaluation at the time of the submittal of the bid. The information required for the cable shall be, as a minimum, the optical glass manufacturer, cable configuration, optical characteristics, mechanical specifications, and all other pertinent information required for an accurate evaluation. 5.1 OPTICAL FIBERS The physical design shall meet the loading requirements of this specification Splice and termination boxes shall be mounted 12 feet above the ground level or baseplate. Splice and termination boxes shall have provisions for locking or securing. Splice and termination boxes on deadends within the substation fence shall be mounted 4 feet above the baseplate Sufficient cable shall be stored at splice location to allow for the splice case to reach a splice trailer Cable lengths shall be selected to minimize splices. All splicing shall be fusion type performed by the supplier of the optical ground wire Attenuation Factorytest attenuation for each fiber on each reel shall be equal to, or less than the following: 1310nm 0.35 db/km (maximum individual fiber) 1550nm 0.22 db/km (maximum individual fiber) The installed attenuation requirements including splice loss are as follows: 1310nm 0.4dB/Km (maximum individual fiber) 1550nm 0.3 db/km ( maximum individual fiber)

51 TRANSMISSION LINE SPECIFICATION TITLE: ODELLOPGW Specification REV.: AB 5.2 COMPOSITE CABLE Cable Construction a. Number of Fibers: 24 fibers. b. OPGW Fault Current Capability: c. Anticipated Lengths a. 345kV to tie into Wood Hill Substation: New 345kV DE Structure to Woad Hill 115/345kV Substation: 750 b. Proposed Substation north of 570 th Ave. Proposed Substation to 115kV DE Structure north of 345kV DE Structure near of Wood Hill Substation: 48,230 c. Reel cut lengths to be determined upon verification of maximum anticipated reel sizes from manufacturer. d. The fibers shall be bundled in groups of 12 in distinctly identifiable optical units. e. The cable must be designed such that, when tensioned to 95% of the cable s rated breaking strength, the optical fibers exhibit no change in attenuation. Test results demonstrating this requirement are to be submitted with the bid. Onsite testing to validate the OPGW Manufacturer s claim will be performed according to the buyer s request. f. The optical units shall be helically stranded together. There shall be a means of tying off the optical units in the splice box, such as Kevlar yarn stranded with the units. g. The stranded optical units shall be isolated from direct contact with the metallic portion of the cable through the means of a heat barrier. h. The cable core shall be contained within a continuouslywelded aluminum pipe. The pipe must be hermetically sealed in order to ensure that moisture and UV light are not allowed to penetrate the optical units, thereby damaging the optical performance over the life of the cable. i. Aluminum alloy and/or aluminum clad steel wires shall be helicallystranded around the aluminum pipe to complete the construction.

52 TRANSMISSION LINE SPECIFICATION TITLE: ODELLOPGW Specification REV.: AB Mechanical / Electrical Parameters The following parameters are the minimum requirements. The bidder shall include with the bidder s proposal detailed specifications addressing each of the parameters listed in this section. 115KV: 345KV: Cable Weight: lb/ft [max] Rated Breaking Strength (RBS): 14,106 lb [min] Fault Current Rating: 96 ka 2 s minimum Cable Weight: lb/ft [max] Rated Breaking Strength (RBS): 14,106 lb [min] Fault Current Rating: 96 ka 2 s minimum Temperature Requirements Temperatures shall be as follows: Storage Temperature:50 C to +80 C Installation Temperature:40 C to +80 C Operating Temperature:40 C to +80 C 6. INSPECTION, TESTS, AND DOCUMENTATION 6.1 MANUFACTURER The manufacturer shall make adequate tests to determine that the items manufactured under these specifications conform in every respect with all requirements contained in this specification and that all nonconforming items be rejected from any shipment.

53 TRANSMISSION LINE SPECIFICATION TITLE: ODELLOPGW Specification REV.: AB 6.2 DESIGN TESTS All optical ground wire designs provided in accordance with this specification shall successfully pass testing according to IEEE 1138.Testing completed on a design similar to the one being quoted is acceptable if the design philosophy is provided to and understood by the customer. 7. HARDWARE REQUIREMENTS The bidder shall include pricing and engineering data for their recommended line hardware for installing the OPGW, including suspension units, dead ends, armor rods, tower bonding clamps, vibration dampers, and guide clamps. All hardware shall be approved by the OPGW vendor. 8. APPLICABLE CODES AND STANDARDS The cable shall conform to the latest revision of each of the following standards as well as any standards referred to therein. o Institute of Electrical and Electronics Engineers (IEEE) , Standard Construction of Composite Fiber Optic Overhead Ground Wire (OPGW) for Use on Electric UtilityPower Lines o American Society for Testing and Materials (ASTM) B398, Standard Specification for AluminumAlloy6201T81 Wire for Electrical Purposes o ASTM B415, Standard Specification for HardDrawn AluminumClad Steel Wire o ASTM B416, Standard Specification for ConcentricLayStranded AluminumClad Steel Conductors o ASTM B483, Standard Specification for Aluminum and AluminumAlloyDrawn Tube and Pipe for General Purpose Applications

54 TRANSMISSION LINE SPECIFICATION TITLE: ODELL Overhead Static Wire Specification REV.: AB VERIFICATION OF SPECIFICATION Anticipated Purchaser Specification Title Wanzek Construction, Inc. ODELL Overhead Static Wire Specification Specification No. ODELL.SD03 Revision No. AB Revision Date: 02/04/16 In accord with established procedures, the quality of this specification has been assured. Signatures below certify that the above specification was originated, reviewed, and approved as noted. Prepared By: Elena Tomadakis Date: 02/04/16 Checked By: Michael Bauer Date: 02/04/1 6 Approved By: Stuart Akers Date: 02/04/16 Revision Log: AB. AsBuilt Professional Engineer I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under laws of the state of Minnesota. Signature: Typed or Printed Name: Stuart R Akers Date: 2/4/2016 License Number: 52545

55 TRANSMISSION LINE SPECIFICATION TITLE: ODELL Overhead Static Wire Specification REV.: AB TABLE OF CONTENTS 1.0 Item Scope Purpose Conductor Manufacturer s Specific Requirements OHSW Inspection, Tests, and Documentation Packaging and Marking References...5 Page

56 TRANSMISSION LINE SPECIFICATION TITLE: ODELL Over Head Static Wire,OHSW Specification REV.: AB 1.0 Item Overhead Static Wire (OHSW). 2.0 Scope This document together with supplementary requirements and any other referenced documents contain the requirements of the Overhead Static Wire hereafter referred to as the OHSW. 3.0 Purpose This specification sets forth the minimum functional and performance requirements for phase OHSW to be used on this project. 4.0 Wire Manufacturer s Specific Requirements The OHSW Manufacturer shall have and submit proof at the time of the bid to demonstrate at least ten continuous years of experience manufacturing and engineering OHSW systems. The OHSW Manufacturer shall be responsible for all phases of manufacturing, packaging, and the safe keeping of the OHSW while at their facility. Prior to shipping, the OHSW Manufacturer shall test each lot to ensure the OHSW meets the Manufacturer's specifications. A printed hard copy of the final test data completed prior to shipment shall be attached in a waterproof envelope or pouch to each reel of OHSW provided. 5.0 OHSW The OHSW shall be seven strand 7/16 Extra High Strength, EHS, Steel cable with the following mechanical properties as described in and manufactured in accordance with ASTM A 363 and ASTM A 475. Conductor Size: 7/16 inch Stranding (Steel): 7 Total Area: in 2 Diameter: in Weight/1000 ft: 399 lbs Rated Strength: 20,800 lbs The OHSW shall be Class A concentriclaystranded. The outer layer of strands of the conductor shall have a righthand lay. 6.0 Inspection, Tests, and Documentation The tests specified in this section shall be performed in accordance with all applicable standards. The

FTMG kV Transmission Line Steel Pole Bid June 1, 2017 Response to Bidders Questions

FTMG kV Transmission Line Steel Pole Bid June 1, 2017 Response to Bidders Questions Company A Questions: (Responses in Red) 1. Page 23 of 23 in the Steel Specification shows a list of equipment cut sheets that we don t have. Will these be provided? Yes. 2. Page 16 of 23 in the Steel Specification,

More information

SECTION CHAIN LINK FENCING AND GATES AND SOFTBALL BACKSTOP

SECTION CHAIN LINK FENCING AND GATES AND SOFTBALL BACKSTOP 1 1 1 0 1 0 1 0 1 SECTION 1 1 CHAIN LINK FENCING AND GATES AND SOFTBALL BACKSTOP BASED ON DFD MASTER SPECIFICATION DATED /01/ P A R T 1 - G E N E R A L SCOPE The work under this section shall consist of

More information

012: 2015 CEB SPECIFICATION GALVANIZED STEEL WIRE (EXCEPT SHIELDING WIRE FOR TOWER LINE APPLICATION)

012: 2015 CEB SPECIFICATION GALVANIZED STEEL WIRE (EXCEPT SHIELDING WIRE FOR TOWER LINE APPLICATION) 012: 2015 CEB SPECIFICATION GALVANIZED STEEL WIRE (EXCEPT SHIELDING WIRE FOR TOWER LINE APPLICATION) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 8051 Fax: +94 11 232 5387 CONTENTS Page 1.0

More information

Technical and Economic Assessment of Upgrading a Double-circuit 63kV to a Single-circuit 230kV Transmission Line in Iran

Technical and Economic Assessment of Upgrading a Double-circuit 63kV to a Single-circuit 230kV Transmission Line in Iran Australian Journal of Basic and Applied Sciences, 5(1): 090-097, 011 ISSN 1991-8178 Technical and Economic Assessment of Upgrading a Double-circuit 63kV to a Single-circuit 30kV Transmission Line in Iran

More information

Project: # Solano Community College District

Project: # Solano Community College District ADDENDUM #02 Project: #16 007 Solano Community College District Horticulture Site Improvements Date: April 26, 2016 The following clarifications are provided based on questions received or changes in District

More information

TransPowr ACSR/TW Bare Overhead Conductor Trapezoidal Aluminum Conductor Steel-Reinforced Concentric-Lay-Stranded

TransPowr ACSR/TW Bare Overhead Conductor Trapezoidal Aluminum Conductor Steel-Reinforced Concentric-Lay-Stranded TransPowr Bare Overhead Conductor 18/7 20/7 21/7 22/7 36/7 36/19 38/19 39/19 64/19 Product Construction: Complete Conductor: TransPowr is a trapezoidal aluminum conductor steel-reinforced concentric-lay-stranded

More information

ROCHESTER PUBLIC UTILITIES FACILITY RATINGS METHODOLOGY FOR TRANSMISSION, SUBSTATION, & GENERATION EQUIPMENT

ROCHESTER PUBLIC UTILITIES FACILITY RATINGS METHODOLOGY FOR TRANSMISSION, SUBSTATION, & GENERATION EQUIPMENT ROCHESTER PUBLIC UTILITIES FACILITY RATINGS METHODOLOGY FOR TRANSMISSION, SUBSTATION, & GENERATION EQUIPMENT Page 1 of 8 The document describes the current methodology used for developing facility ratings

More information

Fatima Michael college of Engineering and Technology

Fatima Michael college of Engineering and Technology Fatima Michael college of Engineering and Technology DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE2303 TRANSMISSION AND DISTRIBUTION SEM: V Question bank UNIT I INTRODUCTION 1. What is the electric

More information

MidAmerican Energy Company 69 kv Facility Ratings Methodology

MidAmerican Energy Company 69 kv Facility Ratings Methodology MidAmerican Energy Company 69 kv Facility Ratings Methodology Version 1.0 Issued by: Luke Erichsen Reviewed by: Tom Mielnik Last Reviewed: 8/29/2012 1 1.0 Scope: This document provides MidAmerican Energy

More information

Coated Dead-end NOMENCLATURE GENERAL RECOMMENDATIONS

Coated Dead-end NOMENCLATURE GENERAL RECOMMENDATIONS NOMENCLATURE Crossover Marks: Indicate starting point for application. Gritted and Neoprene Dipped Legs: Grit is permanently embedded in a coating of neoprene. GENERAL RECOMMENDATIONS Coated Dead-ends:

More information

Testing. Material testing will be according to applicable AASHTO, ASTM or Department methods as specified.

Testing. Material testing will be according to applicable AASHTO, ASTM or Department methods as specified. 907.01 Section 907. FENCING MATERIALS 907.01 General Requirements. Materials for use in fencing property, right-of-way and other installations must comply with this section. 907.02 Testing. Material testing

More information

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868) WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868) THREE-PHASE SUBSURFACE UNDERGROUND COMMERCIAL DISTRIBUTION (UCD) TRANSFORMER NOTE: This "Guide" summarizes the opinions, recommendations, and practices

More information

SECTION BULLET- RESISTANT DOORS

SECTION BULLET- RESISTANT DOORS 1 SECTION 08 3950 BULLET- RESISTANT DOORS PART 1- GENERAL 1.01 SUMMARY A. This Section Includes: 1. Bullet- resistant steel door and frame systems. 2. Door hardware for bullet- resistant steel door and

More information

FACILITY RATINGS METHOD TABLE OF CONTENTS

FACILITY RATINGS METHOD TABLE OF CONTENTS FACILITY RATINGS METHOD TABLE OF CONTENTS 1.0 PURPOSE... 2 2.0 SCOPE... 3 3.0 COMPLIANCE... 4 4.0 DEFINITIONS... 5 5.0 RESPONSIBILITIES... 7 6.0 PROCEDURE... 8 6.4 Generating Equipment Ratings... 9 6.5

More information

MidAmerican Energy Company 100 kv and Above Facility Ratings Methodology

MidAmerican Energy Company 100 kv and Above Facility Ratings Methodology MidAmerican Energy Company 100 kv and Above Facility Ratings Methodology For NERC Standard FAC-008 and FAC-009 Issued by: Dan Custer Reviewed by: Tom Mielnik Version 2.7 1 1.0 Scope: This document provides

More information

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide MGM Transformer Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide MGM Transformer Company 5701 Smithway Street Commerce, CA 90040 www.mgmtransformer.com Phone: 323.726.0888

More information

Standards Update Notice (SUN) Issued: June 6, 2017

Standards Update Notice (SUN) Issued: June 6, 2017 Standard Information Standard Number: UL 758 Standard Name: Standard for Safety for Appliance Wiring Material Standard Edition and Issue Date: 3 rd Edition Dated May 2, 2014 Date of Revisions: 2 nd Ed.

More information

Hendrix Tap, Tie & Ground Wire

Hendrix Tap, Tie & Ground Wire Hendrix Tap, Tie & Ground Wire MADE IN U.S.A. 53 Old Wilton Road Milford, NH 03055-3119 603-673-2040 www.marmonutility.com A Marmon Wire & Cable/Berkshire Hathaway Company Tap Wire Description Hendrix

More information

Transmission Facilities Rating Methodology for Florida

Transmission Facilities Rating Methodology for Florida Document title Transmission Facilities Rating Methodology for Florida Document number EGR-TRMF-00001 Applies to: Transmission Engineering, Transmission System Operations, and Transmission Planning Duke

More information

features and benefits

features and benefits features and benefits Fully waterblocked loose tube, gel-free design Medium-density polyethylene jacket Figure-8 cable design Available in 62.5 µm, 50 µm, single-mode and hybrid versions Simple access

More information

11-SDMS-03 REV. 02 SPECIFICATIONS FOR

11-SDMS-03 REV. 02 SPECIFICATIONS FOR 11-SDMS-03 REV. 02 SPECIFICATIONS FOR XLPE INSULATED POWER CABLES FOR RATED VOLTAGES FROM 15 KV UP TO 36 KV (U m ) This specification is property of SEC and subject to change or modification without notice

More information

KINECTRICS NORTH AMERICA INC. TEST REPORT FOR 3M COMPANY TO COMPARE THE LIGHTNING PERFORMANCE OF ACCR TO ACSR CONDUCTORS

KINECTRICS NORTH AMERICA INC. TEST REPORT FOR 3M COMPANY TO COMPARE THE LIGHTNING PERFORMANCE OF ACCR TO ACSR CONDUCTORS To: Colin McCullough 3M Composite Conductor Program 2465 Lexington Ave. South Mendota Heights, MN 5512 USA KINECTRICS NORTH AMERICA INC. TEST REPORT FOR 3M COMPANY TO COMPARE THE LIGHTNING PERFORMANCE

More information

KANSAS DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION TO THE STANDARD SPECIFICATIONS, 1990 EDITION

KANSAS DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION TO THE STANDARD SPECIFICATIONS, 1990 EDITION Sheet 1 of 5 KANSAS DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION TO THE STANDARD SPECIFICATIONS, 1990 EDITION NOTE: This special provision is generally written in the imperative mood. The subject, "the

More information

SPECIFICATIONS FOR THE MANUFACTURE AND DESIGN OF PRECAST THREE SIDED ARCH STRUCTURES, WINGWALLS AND HEADWALLS

SPECIFICATIONS FOR THE MANUFACTURE AND DESIGN OF PRECAST THREE SIDED ARCH STRUCTURES, WINGWALLS AND HEADWALLS SPECIFICATIONS FOR THE MANUFACTURE AND DESIGN OF PRECAST THREE SIDED ARCH STRUCTURES, WINGWALLS AND HEADWALLS 1. DESCRIPTION THESE SPECIFICATIONS ARE FOR A PRECAST THREE SIDED ARCH STRUCTURE, HEADWALLS

More information

SPECIFICATION SS-140/9. 0.6/1 (1.2) kv CONTROL AND POWER UNDERGROUND CABLES WITH PVC OR XLPE INSULATION AND PVC JACKET

SPECIFICATION SS-140/9. 0.6/1 (1.2) kv CONTROL AND POWER UNDERGROUND CABLES WITH PVC OR XLPE INSULATION AND PVC JACKET INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION December 2016 SPECIFICATION 0.6/1 (1.2) kv CONTROL AND POWER UNDERGROUND CABLES WITH PVC OR XLPE INSULATION

More information

Aluminum-clad Steel Wire

Aluminum-clad Steel Wire AS Wire/GS Wire AS WIRE Aluminum-clad Steel Wire GS WIRE Galvanized Steel Wire Made in the U.S.A. Development of Aluminumclad Steel (AS) Wire Conex Cable, LLC, under the original name of Conex, started

More information

COMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD

COMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

PART MATERIALS. Section Fencing Materials. Description

PART MATERIALS. Section Fencing Materials. Description PART 03000 - MATERIALS Section 03010 - Fencing Materials Description 03010.00 Scope - This section consists of the test requirements, specifications and tolerances for barbed wire, woven wire and chain

More information

Appendix I. Applicant s Audible Noise and EMF Calculations

Appendix I. Applicant s Audible Noise and EMF Calculations Appendix I Applicant s Audible Noise and EMF Calculations Structure Type Predicted Intensity of Electric Fields (kv/m) at Maximum Operating Voltage Where Not Paralleling Existing Transmission Lines Line

More information

Optical Ground Wires (OPGW)

Optical Ground Wires (OPGW) Optical Ground Wires (OPGW) Presented by NSW (Norddeutsche Seekabelwerke GmbH) 4-Nov-13 / 1 NSW The Company Plant Overview 4-Nov-13 / 2 NSW Ground Wire History Our Experience Ground Wire Cables production

More information

GEOTEXTILE INS TALL ATION GUIDE

GEOTEXTILE INS TALL ATION GUIDE GEOTEXTILE INS TALL ATION GUIDE TITAN ENVIRONMENTAL CONTAINMENT TE NON WOVEN GEOTEXTILE Rev. May, 2016 Unloading & Storage: The geotextile shall be labeled, stored, and handled in accordance with ASTM

More information

EMMEGI ARCHITECTURAL FENCING MASTER SPECIFICATION SECTION METAL FENCING, GATES & RAILING SYSTEM PART 1 GENERAL

EMMEGI ARCHITECTURAL FENCING MASTER SPECIFICATION SECTION METAL FENCING, GATES & RAILING SYSTEM PART 1 GENERAL EMMEGI ARCHITECTURAL FENCING MASTER SPECIFICATION SECTION 05720 METAL FENCING, GATES & RAILING SYSTEM PART 1 GENERAL EMMEGI ARCHITECTURAL FENCING is a high quality steel fencing system comprised of a hybrid

More information

Roll No. :... Invigilator s Signature :.. CS/B.TECH(EE)/SEM-5/EE-502/ POWER SYSTEM-I. Time Allotted : 3 Hours Full Marks : 70

Roll No. :... Invigilator s Signature :.. CS/B.TECH(EE)/SEM-5/EE-502/ POWER SYSTEM-I. Time Allotted : 3 Hours Full Marks : 70 Name : Roll No. :.... Invigilator s Signature :.. CS/B.TECH(EE)/SEM-5/EE-502/2011-12 2011 POWER SYSTEM-I Time Allotted : 3 Hours Full Marks : 70 The figures in the margin indicate full marks. Candidates

More information

SECTION CABLE TRAYS FOR COMMUNICATIONS SYSTEMS

SECTION CABLE TRAYS FOR COMMUNICATIONS SYSTEMS SECTION 270536 - CABLE TRAYS FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

EZ-WRAP Side Tie NOMENCLATURE GENERAL RECOMMENDATIONS (440) EN-CA

EZ-WRAP Side Tie NOMENCLATURE GENERAL RECOMMENDATIONS (440) EN-CA NOMENCLATURE IDENTIFICATION TAPE TIE TUBE INSULATOR IDENTIFICATION MARK C NECK BLACK F NECK YELLOW J NECK GREEN Conductor Tie Tube: For bare conductor, each tie is furnished with a Tie Tube Component.

More information

Title: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS

Title: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS TABLE OF CONTENTS PAGE 1.0 SCOPE... 2 2.0 STANDARDS... 2 3.0 DESIGN REQUIREMENTS... 2 3.01 Service Conditions... 2 3.02 Ratings... 3 4.0 Sectionalizer Construction... 4 5.0 Mechanism... 6 6.0 Solid Dielectric

More information

Appendix 6-F: Electric and Magnetic Field Study Report

Appendix 6-F: Electric and Magnetic Field Study Report Draft Environmental Impact Statement Cricket Valley Energy Project Dover, NY Appendix 6-F: Electric and Magnetic Field Study Report ELECTRIC & MAGNETIC FIELDS (EMFs) STUDY REPORT For the CRICKET VALLEY

More information

TECHNICAL SPECIFICATION FOR 11KV, 3C x95mm mm 2 AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED)

TECHNICAL SPECIFICATION FOR 11KV, 3C x95mm mm 2 AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED) TECHNICAL SPECIFICATION FOR 11KV, 3C x95mm 2 + 80mm 2 AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED) 1. SCOPE This specification covers requirements of, 3C x95mm 2 +

More information

Transformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications

Transformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications Minnesota Power Systems Conference November 3 5, 2009 Earl Brown Heritage Center University of

More information

AEOLIAN VIBRATION TEST ON 1572 KCMIL BITTERN ACCC/TW CONDUCTOR FOR COMPOSITE TECHNOLOGY CORPORATION

AEOLIAN VIBRATION TEST ON 1572 KCMIL BITTERN ACCC/TW CONDUCTOR FOR COMPOSITE TECHNOLOGY CORPORATION To: Mr. Dave Bryant Composite Technology Corporation 2026 McGaw Avenue Irvine, CA 92614 USA AEOLIAN VIBRATION TEST ON 1572 KCMIL BITTERN ACCC/TW CONDUCTOR FOR COMPOSITE TECHNOLOGY CORPORATION Kinectrics

More information

Foundation Specifications for 5.6-Meter Modular Earth Station Antennas

Foundation Specifications for 5.6-Meter Modular Earth Station Antennas Installation Instructions Bulletin 237029 Foundation Specifications for 5.6-Meter Modular Earth Station Antennas Revision A Introduction This document specifies typical foundation characteristics, designs,

More information

6o ft (18.3 m) Southwest Windpower, Inc West Route 66 Flagstaff, Arizona USA Phone: Fax:

6o ft (18.3 m) Southwest Windpower, Inc West Route 66 Flagstaff, Arizona USA Phone: Fax: 6o ft (18.3 m) sectional MONOPOLE TOWER INSTALLATION MANUAL Southwest Windpower, Inc. 1801 West Route 66 Flagstaff, Arizona 86001 USA Phone: 928.779.9463 Fax: 928.779.1485 www.skystreamenergy.com 3-CMLT-1390-01

More information

Foundation Specifications for 7.6-Meter Modular Earth Station Antennas

Foundation Specifications for 7.6-Meter Modular Earth Station Antennas Installation Instructions Foundation Specifications for 7.6-Meter Modular Earth Station Antennas Bulletin 237186A Revision A Introduction This document specifies typical foundation characteristics, designs,

More information

Transmission Facilities Rating Methodology

Transmission Facilities Rating Methodology Document title Transmission Facilities Rating Methodology Document number EGR-TRMC-00009 Applies to: Transmission Engineering, Transmission System Operations, and Transmission Planning- Progress Energy

More information

SECTION CHAIN LINK FENCING

SECTION CHAIN LINK FENCING SECTION 32 31 13 CHAIN LINK FENCING PART 1 - GENERAL 1.01 SECTION INCLUDES A. The Work specified in this Section consists of furnishing and installing permanent chain link fences and gates in accordance

More information

COPPERCLAD STEEL WIRE. Dead Soft Annealed Jacketed High Strength. Extra High Strength Composite Conductors Guy Wire

COPPERCLAD STEEL WIRE. Dead Soft Annealed Jacketed High Strength. Extra High Strength Composite Conductors Guy Wire COPPERCLAD STEEL WIRE Dead Soft Annealed Jacketed High Strength Extra High Strength Composite Conductors Guy Wire Founded in 1984, AFL is an international manufacturer providing end-to-end solutions to

More information

A. Extent of structural precast concrete work is shown on drawings and in schedules.

A. Extent of structural precast concrete work is shown on drawings and in schedules. SECTION 03 41 00 - STRUCTURAL PRECAST CONCRETE PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 specification

More information

Installation Instructions for OPGW Bolted Dead End

Installation Instructions for OPGW Bolted Dead End INS-ACA015 OPGW Bolted Dead End Procedure 1. Disassemble dead end. Remove one bolt from the same side of each keeper. Loosen other bolts to permit conductor to be placed in the conductor groove. If keepers

More information

Distribution Tie. Distribution Tie NOMENCLATURE GENERAL RECOMMENDATIONS (440)

Distribution Tie. Distribution Tie NOMENCLATURE GENERAL RECOMMENDATIONS (440) Distribution (Overhead): Section 13 NOMENCLATURE Distribution Tie Tie Tube: Each tie is furnished with Tie Tube Component. The Tie Tube is detached and applied over the conductor. Tape: Shows catalog number,

More information

Standard Specification for Copper-Clad Steel Wire for Electronic Application 1

Standard Specification for Copper-Clad Steel Wire for Electronic Application 1 Designation: B 45 0 Standard Specification for Copper-Clad Steel Wire for Electronic Application 1 This standard is issued under the fixed designation B 45; the number immediately following the designation

More information

GURANTEED TECHNICAL PARTICULARS OF BACK CLAMP FOR LT CROSS ARM

GURANTEED TECHNICAL PARTICULARS OF BACK CLAMP FOR LT CROSS ARM Technical Specification of Back Clamp for LT Cross Arm (MS) Back clamp for LT Cross Arm made out of 50 x 6mm MS Flat suitable for 8m X 300 Kg PSC poles. After fabrication the cross arm shall be painted

More information

SELF DAMPING TEST ON 1020 KCMIL ACCC/TW CONDUCTOR FOR COMPOSITE TECHNOLOGY CORPORATION

SELF DAMPING TEST ON 1020 KCMIL ACCC/TW CONDUCTOR FOR COMPOSITE TECHNOLOGY CORPORATION To: Dave Bryant Composite Technology Corporation 2026 McGaw Avenue Irvine, CA 92614 USA SELF DAMPING TEST ON 1020 KCMIL ACCC/TW CONDUCTOR FOR COMPOSITE TECHNOLOGY CORPORATION Kinectrics North America Inc.

More information

DIVISION 11 EQUIPMENT SECTION PHOTO DARKROOM FUME EXHAUST VENT-HOODS

DIVISION 11 EQUIPMENT SECTION PHOTO DARKROOM FUME EXHAUST VENT-HOODS DIVISION 11 EQUIPMENT SECTION PHOTO DARKROOM FUME EXHAUST VENT-HOODS PART 1 GENERAL 1.01 Scope of Work A. Provide material, accessories, tools, equipment and labor as required for the complete fabrication

More information

1.8 METER SERIES 1184 ANTENNA SYSTEM

1.8 METER SERIES 1184 ANTENNA SYSTEM REVISION F January 10, 2002 ASSEMBLY MANUAL 1.8 METER SERIES 1184 ANTENNA SYSTEM PRODELIN CORPORATION 1500 Prodelin Drive Newton NC 28658 1.8 METER SERIES 1184 ANTENNA SYSTEM F Revised Address 1/10/02

More information

WAL-MART SUPERCENTER # ; Milwaukie, OR: SPECIFICATIONS. Revisions to Specification Fence

WAL-MART SUPERCENTER # ; Milwaukie, OR: SPECIFICATIONS. Revisions to Specification Fence MILWAUKIE OR #3144-00 ADDENDUM #5 NARRATIVE: 11-08-12 WAL-MART SUPERCENTER #3144-00; Milwaukie, OR: SPECIFICATIONS SPECIFICATIONS Revisions to Specification 02822 Fence Spec division 02822 has been revised

More information

Evaluation of In-Pavement Light Fixture Designs and Performance

Evaluation of In-Pavement Light Fixture Designs and Performance Evaluation of In-Pavement Light Fixture Designs and Performance Presented to: IES ALC Fall Technology Meeting By: Joseph Breen Date: Background In-Pavement Light Fixture Assemblies Utilize a Circle of

More information

MGVCL/MM/ /2082/11KV AB CABLE TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES

MGVCL/MM/ /2082/11KV AB CABLE TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES 1. Qualifying Requirement of AB Cable Manufacture/Supplier The manufacturer should have manufactured, successfully type tested

More information

REVISION #1. Section. fire alarm B. C. the hot. intent of. required. manufacturer. materials. C. Warranty

REVISION #1. Section. fire alarm B. C. the hot. intent of. required. manufacturer. materials. C. Warranty HOT AISLE CONTAINMENT SYSTEM (HACS) REVISION #1 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. B. C. Drawings and general provisions of the Contract, including General and Supplementary. Conditions apply to

More information

b. B aluminum and aluminum-alloy extruded bar, rod, wire, shape and tube

b. B aluminum and aluminum-alloy extruded bar, rod, wire, shape and tube MODEL 240I SECTION 08120 FLUSH ALUMINUM DOORS AND FRAMES PART I GENERAL 1.01 SCOPE OF WORK A. Furnish all labor, materials, equipment and incidentals required to deliver and install aluminum doors, frames,

More information

INTREPID Model 336 Digital Microwave Link

INTREPID Model 336 Digital Microwave Link Southwest Microwave, Inc. 9055 S. McKemy Street Tempe, Arizona 85284 USA +1(480) 783-0201 Fax +1(480) 783-0401 Product Specifications INTREPID Model 336 Digital Microwave Link Purpose of document This

More information

Howard Smart Transformer Specification Guide

Howard Smart Transformer Specification Guide Howard Smart Transformer Specification Guide General Requirements Overhead pole-type smart distribution transformers shall be single phase, 60 Hz, mineral-oil filled and self-cooled and shall conform as

More information

1.1_KV PVC insulated PVC sheathed multicore Aluminium Cable (armoured & unarmoured)

1.1_KV PVC insulated PVC sheathed multicore Aluminium Cable (armoured & unarmoured) WEST BENGAL STATE ELECTRICITY DISTRIBUTION COMPANY LIMITED (A Govt. of West Bengal Enterprise) Office of the Chief Engineer, Procurement & Contracts Department Vidyut Bhavan, 4 th. floor, Bidhannagar,

More information

II Design Criteria for Electrical Facilities Connected to the PJM 765 kv, 500 kv, 345 kv, 230 kv, 138 kv, 115 kv, & 69 kv Transmission Systems

II Design Criteria for Electrical Facilities Connected to the PJM 765 kv, 500 kv, 345 kv, 230 kv, 138 kv, 115 kv, & 69 kv Transmission Systems II Design Criteria for Electrical Facilities Connected to the PJM 765 kv, 500 kv, 345 kv, 230 kv, 138 kv, 115 kv, & 69 kv Transmission Systems These design criteria have been established to assure acceptable

More information

B. Shop Drawings: Include elevations, door edge details, frame profiles, metal thicknesses, preparations for hardware, and other details.

B. Shop Drawings: Include elevations, door edge details, frame profiles, metal thicknesses, preparations for hardware, and other details. SECTION 081113 - HOLLOW METAL DOORS AND FRAMES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Standard hollow metal doors and frames. 1.2 SUBMITTALS A. Product Data: For each type of product indicated.

More information

Technical Specification. for 1.1 KV Copper Control Cable

Technical Specification. for 1.1 KV Copper Control Cable WEST BENGAL STATE ELECTRICITY DISTRIBUTION COMPANY LIMITED (A Govt. of West Bengal Enterprise) Office of the Chief Engineer, Procurement & Contracts Department Vidyut Bhavan, 4 th. floor, Bidhannagar,

More information

SECTION STRUCTURAL STEEL. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION.

SECTION STRUCTURAL STEEL. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION. SECTION 051200 PART 1 GENERAL 1.01 GENERAL REQUIREMENTS A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION. B. Examine all conditions as they exist at the project prior to submitting

More information

RR-F-191/1D 14 May SUPERCEDING RR-F-191/1C July 22, 1981 FEDERAL SPECIFICATION SHEET

RR-F-191/1D 14 May SUPERCEDING RR-F-191/1C July 22, 1981 FEDERAL SPECIFICATION SHEET 14 May 1990 ----------- SUPERCEDING RR-F-191/1C July 22, 1981 FEDERAL SPECIFICATION SHEET FENCING, WIRE AND POST METAL (CHAIN-LINK FENCE FABRIC) (DETAIL SPECIFICATION) This Federal Specification is approved

More information

SECTION STEEL LIGHTING STANDARDS. 1. Electrical conduit and fittings; Section

SECTION STEEL LIGHTING STANDARDS. 1. Electrical conduit and fittings; Section 02760-1 of 5 SECTION 02760 STEEL LIGHTING STANDARDS 02760.01 GENERAL A. Description Steel lighting standards shall include, but not necessarily be limited to, furnishing and installing steel lighting poles,

More information

Bipole III Transmission Project

Bipole III Transmission Project Bipole III Transmission Project Clean Environment Commission Public Hearings Fall 2012 System Planning Ronald Mazur BP III Keewantinoow Limestone Kettle Kelsey Jenpeg Grand Rapids OVERVIEW Transmission

More information

MDOTProjectwise\Documents\Reference Documents\Traffic Reference\Statewide Special Details\Develop

MDOTProjectwise\Documents\Reference Documents\Traffic Reference\Statewide Special Details\Develop 500 460 MDOTProjectwise\Documents\Reference Documents\Traffic Reference\Statewide Special Details\Develop Check if Applicable TRAFFIC SIGNAL SPECIAL DETAILS INDEX/CHECKLIST *One completed checklist required

More information

MidAmerican Energy Company 100 kv and Above Facility Ratings Methodology

MidAmerican Energy Company 100 kv and Above Facility Ratings Methodology MidAmerican Energy Company 100 kv and Above Facility Ratings Methodology For NERC Standard FAC-008-3 Version 3.4 1 Contents 1. Scope... 3 2. Establishment and Communication of Facility Ratings:... 3 2.1.

More information

INTRODUCTION. General Design Criteria o (include charts from Section 2 of TSS) Functional Criteria o (from TSS section 3) Accessibility and Layout

INTRODUCTION. General Design Criteria o (include charts from Section 2 of TSS) Functional Criteria o (from TSS section 3) Accessibility and Layout Substation Subgroup Members: Please update the sections below you volunteered to review using the track changes option or highlight your changes. Once done, email your updated document to Scott Herb (SEHerb@pplweb.com)

More information

SECTION VI SCOPE OF WORK

SECTION VI SCOPE OF WORK SECTION VI SCOPE OF WORK Overhead Lines and Underground cables VI 5.2 - i TABLE OF CONTENTS 5.2 SCOPE OF WORKS... 1 5.2.1 General... 1 5.2.2 Factory Acceptance Test... 2 5.2.3 33KV Lines and Cables...

More information

Conductor Splice NOMENCLATURE GENERAL RECOMMENDATIONS (440)

Conductor Splice NOMENCLATURE GENERAL RECOMMENDATIONS (440) Conductor Splice NOMENCLATURE Sub-Sets: Individual rods assembled and gritted into groups (subsets), corresponding to tabular information appearing on catalog page. Center Mark: Establishes recommended

More information

NORMATIVE REFERENCES

NORMATIVE REFERENCES American National Standards Institute NORMATIVE REFERENCES ANSI C135.30 1988 (expired 1993) Zinc-Coated Ferrous Ground Rod Electrodes for Overhead or Underground Lines American Society for Testing and

More information

.84M Ku-Band Rx/O Antenna System

.84M Ku-Band Rx/O Antenna System 4096-644 Revision A May 9, 2003 ASSEMBLY MANUAL.84M Ku-Band Rx/O Antenna System PRODELIN CORPORATION 1500 PRODELIN DRIVE NEWTON, NC 28658 .84M Ku-Band Rx/O Antenna System A ORIGINAL RELEASE 5/9/2003 A.Hahn

More information

REPORT HOLDER: ISAIAH INDUSTRIES, INC. EVALUATION SUBJECT:

REPORT HOLDER: ISAIAH INDUSTRIES, INC. EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1360 Reissued 08/2018 This report is subject to renewal 08/2019. DIVISION: 07 00

More information

B. Shop Drawings: Include elevations, door edge details, frame profiles, metal thicknesses, preparations for hardware, and other details.

B. Shop Drawings: Include elevations, door edge details, frame profiles, metal thicknesses, preparations for hardware, and other details. SECTION 081113 - HOLLOW METAL DOORS AND FRAMES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Standard hollow metal doors and frames. 1.2 SUBMITTALS A. Product Data: For each type of product indicated.

More information

SECTION VI SCOPE OF WORK

SECTION VI SCOPE OF WORK SECTION VI SCOPE OF WORK Overhead Lines and Underground cables VI 5.2 - i TABLE OF CONTENTS 5.2 SCOPE OF WORKS... 1 5.2.1 General... 1 5.2.2 Factory Acceptance Test... 2 5.2.3 33KV Lines and Cables...

More information

For crossing under a railroad, contact the specific railroad company's engineering department.

For crossing under a railroad, contact the specific railroad company's engineering department. PAGE 330524-1 SECTION 330524 SPECIFIER: This section is for the underground installation of piping by directional drilling. When specifying this method of piping installation, care must be taken to ensure

More information

1.8 METER SERIES 1194 ANTENNA SYSTEM

1.8 METER SERIES 1194 ANTENNA SYSTEM January 14, 2002 REVISION G ASSEMBLY MANUAL 1.8 METER SERIES 1194 ANTENNA SYSTEM PRODELIN CORPORATION 1500 Prodelin Drive Newton NC 28658 1.8 METER SERIES 1194 ANTENNA SYSTEM G Revise Address 1/14/02 F

More information

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5 Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Energy & Water Services.2 UBC Building Operations 1.2 Description.1 UBC requirements for Substation Transformers. 2.0 MATERIAL AND DESIGN REQUIREMENTS

More information

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI GENERAL: The scope of this document is to provide instruction for the installation and testing of Medium Voltage, 3 Phase, Pad Mounted Transformers installed at the University of Missouri. Preferred transformers

More information

BSR A300 Part 3 Draft 1 Version 1, a

BSR A300 Part 3 Draft 1 Version 1, a Standards & Regulations Cabling and Bracing Standard Proposed Revision This is an excerpt from the draft version of the ANSI standard for supplemental support systems cabling and bracing used in tree care

More information

RUS Accepted NOMENCLATURE GENERAL RECOMMENDATIONS (440) EN-CA

RUS Accepted NOMENCLATURE GENERAL RECOMMENDATIONS (440) EN-CA NOMENCLATURE RUS Accepted Crossover Marks: Indicate starting point for application. Color Code and Length: Assist in identification of conductor size, corresponding to tabular information appearing on

More information

Determining Crossing Conductor Clearance Using Line-Mounted LiDAR. J. C. MCCALL, P. SPILLANE, K. LINDSEY Lindsey Manufacturing USA

Determining Crossing Conductor Clearance Using Line-Mounted LiDAR. J. C. MCCALL, P. SPILLANE, K. LINDSEY Lindsey Manufacturing USA 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2015 Grid of the Future Symposium Determining Crossing Conductor Clearance Using Line-Mounted LiDAR J. C. MCCALL, P. SPILLANE,

More information

CIR (Crush & Impact Resistant) VFD Power Cable

CIR (Crush & Impact Resistant) VFD Power Cable 37-2 CIRVFD CIR (Crush & Impact Resistant) VFD Power Cable Gexol Insulated Three Conductor 2kV Rated 90 C UL Listed as Type TC-ER Power Conductors (x3) Soft annealed flexible stranded tinned copper per

More information

50-SDMS-01 SPECIFICATIONS FOR

50-SDMS-01 SPECIFICATIONS FOR SPECIFICATIONS FOR CURRENT TRANSFORMERS UP TO 36 KV This specification is property of SEC and subject to change or modification without any notice C O N T E N T S CLAUSE TITLE PAGE NO. ------------ --------

More information

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 177 2012 Specification for Braided 75 Ω, Mini-Series Quad Shield Coaxial Cable for CMTS and SDI cables NOTICE

More information

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01 SEC DISTRIBUTION GROUNDING STANDARD SDCS-03 Part-II Rev.01 SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING Rev. 01 This specification is property of SEC

More information

Conductor Splice NOMENCLATURE GENERAL RECOMMENDATIONS (440) EN-CA

Conductor Splice NOMENCLATURE GENERAL RECOMMENDATIONS (440) EN-CA NOMENCLATURE Sub-Sets: Individual rods assembled and gritted into groups (subsets), corresponding to tabular information appearing on catalog page. Center Mark: Establishes recommended alignment of rods

More information

MIPSYCON GRID RESILIENCY. David Flaten Electric Distribution Standards November 10, 2015

MIPSYCON GRID RESILIENCY. David Flaten Electric Distribution Standards November 10, 2015 MIPSYCON GRID RESILIENCY David Flaten Electric Distribution Standards November 10, 2015 LINE TO SIMULATE TREES FALLING 3 miles long, 70 structures, 200 foot spans #4 Copper phase wires, #2 ACSR neutral

More information

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS SECTION 16461C - DRY TYPE TRANSFORMERS PART 1 - GENERAL 1.1 This section includes design and performance requirements for dry-type transformers rated for use on secondary distribution systems rated 600

More information

HOW TO BUILD A DEER OR ELK-PROOF FENCE. Saskatchewan Environment Resource Stewardship Branch 112 Research Drive Saskatoon, Saskatchewan S7K 2H6

HOW TO BUILD A DEER OR ELK-PROOF FENCE. Saskatchewan Environment Resource Stewardship Branch 112 Research Drive Saskatoon, Saskatchewan S7K 2H6 HOW TO BUILD A DEER OR ELK-PROOF FENCE Saskatchewan Environment Resource Stewardship Branch 112 Research Drive Saskatoon, Saskatchewan S7K 2H6 Revised March 2005 1 This information is intended to assist

More information

Slack Span Dead-end. Slack Span Dead-end GENERAL RECOMMENDATIONS NOMENCLATURE 14-23

Slack Span Dead-end. Slack Span Dead-end GENERAL RECOMMENDATIONS NOMENCLATURE 14-23 NOMENCLATURE Dead-end Material Helical Leg Section: Aluminum covered steel. An aluminum alloy version is available for corrosive environment. Contact PLP. Crossover Marks: Indicates starting point for

More information

Load Tables, Technical Data and Installation Instructions

Load Tables, Technical Data and Installation Instructions W22. W22. W22. W22. W22 W22.. Simpson Strong-Tie Fastening Systems Structural Wood-to-Wood Connections Including Ledgers Designed to provide an easy-to-install, high-strength alternative to through-bolting

More information

SECTION PANELBOARDS

SECTION PANELBOARDS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 24 16 PANELBOARDS SPEC WRITER NOTE: Delete between // --- // if not applicable to project. Also, delete any other item or paragraph not applicable in the section

More information

Kansas City Power & Light Company. Transmission Facility Rating Methodology

Kansas City Power & Light Company. Transmission Facility Rating Methodology Company Prepared by: KCP&L Transmission Planning December 6, 2017 Table of Contents 1. Purpose...4 2. Generator Rating Methodology...4 3....4 3.1. Equipment Rating Methodology...4 3.2. Items considered

More information

DOCUMENT ADDENDUM NO. 4. Issued to all Bidders: Date: October 14, Contract Name: Electrical Installation. Contract Number: C8410

DOCUMENT ADDENDUM NO. 4. Issued to all Bidders: Date: October 14, Contract Name: Electrical Installation. Contract Number: C8410 DOCUMENT 009104 - ADDENDUM NO. 4 Issued to all Bidders: Date: October 14, 2015 Contract Name: Electrical Installation Contract Number: C8410 This addendum forms a part of the Bid described above. The original

More information

STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENT 1073 PRECAST CONCRETE CERTIFICATION PROGRAM JULY 20, 2018

STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENT 1073 PRECAST CONCRETE CERTIFICATION PROGRAM JULY 20, 2018 STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENT 1073 PRECAST CONCRETE CERTIFICATION PROGRAM JULY 20, 2018 1073.01 Program Overview 1073.02 Qualification 1073.03 Documentation Phase 1073.04 Documentation

More information