Breaker Pole Discrepancy Function

Size: px
Start display at page:

Download "Breaker Pole Discrepancy Function"

Transcription

1 Breaker Pole Discrepancy Function

2 SIPROTEC 5 Application SIPROTEC 5 Application APN-031, Edition 2 Content Introduction Overview Circuit breaker switching state Pole discrepancy signal CFC Logic Timer Setting Logic with Phase Selective Close AND Open Conclusion... 8 APN Edition 2

3 1 SIPROTEC 5 Application 1.1 Introduction This application note describes a simple method to obtain a breaker pole discrepancy alarm using SIPROTEC 5. Additionally, the SIPROTEC 5 device manuals as well the DIGSI 5 help function should be consulted for further details. 1.2 Overview In most circuit breaker applications, the pole discrepancy function is part of the circuit breaker. Where breakers can be tripped single pole, the protection and auto re-close function ensure that a circuit breaker never ends in a single pole open state. Some applications however demand a circuit breaker pole discrepancy function in the protection relay. Such a pole discrepancy function is based purely on the status of the auxiliary contacts. This application note describes how this can be implemented with SIPROTEC 5 using standard functions included in the device. 1.3 Circuit breaker switching state The breaker switching state is obtained via binary inputs. There are a number of alternatives for the application of the auxiliary contacts: Figure 1: Typical routing of binary inputs for circuit breaker auxiliary contacts With the routing shown in Figure 1 above, the circuit breaker auxiliary contacts can, with good reliability, indicate both the open and closed state of the circuit breaker. For this example the external connection shown in Figure 2 below is required. For the application of the pole discrepancy function as described in this document, the 3 phase selective auxiliary contact signals, Position 1-pole phsx, must be applied in the closed high (CH) configuration because the logic will evaluate the phase selective CLOSED-Status. The 3-phase status, for example the Position 3-pole, which is routed as OH in Figure 1, is not required and may be left out. Under Heading 1.7 Logic with Phase Selective Close AND Open a further variant for the Pole Discrepancy Function is provided. This requires 6 binary inputs and replicates the classic discrete logic. Edition 2 3 APN-031

4 SIPROTEC 5 Applikation Ph A Ph B Ph C Ph A Ph B Ph C + DC CB SIPROTEC 5 FG CB BI1 3 pole Open High BI2 1 pole phsa Close High BI3 1 pole phsb Close High BI4 1 pole phsc Close High Figure 2: Connection of auxiliary contacts with phase selective Close High status The following state indications are available for the Circuit Breaker. Figure 3: Indication of circuit breaker state (the phase selective closed state is used in the logic) The signals that will be used for the pole discrepancy function are the phase selective closed state. In Figure 3 above this is the highlighted Position 1-pole phsa/closed for phase A. These states are indicated as soon as the state of the auxiliary contact for the respective phase shows that the pole is closed or not open. APN Edition 2

5 1.4 Pole discrepancy signal SIPROTEC 5 Application A user defined signal and time delay must be introduced for this purpose. From the library first add the Chart Setting Integer and rename it to Pole Disc, Timer ms. In the next step drag and drop the SPS into the new function and rename it PD alarm. Figure 4: Add user defined objects The new signal PD alarm is the pole discrepancy alarm. It may be routed to the required destinations now or later. Edition 2 5 APN-031

6 SIPROTEC 5 Applikation 1.5 CFC Logic For the pole discrepancy alarm the following logic is applied via a CFC chart. The chart is applied as Event Triggered CFC : Figure 5: CFC chart with pole discrepancy logic (Phase Selective Closed Status) The input to the timer will only be a high state when both the 3 input NOR gate and AND gate have a zero at their outputs. This happens when the Closed State is not the same in all three phases. Based on the three inputs used for the phase selective status as shown in Figure 2, this is the pole discrepancy state that will be alarmed when the set time expires. 1.6 Timer Setting The pole discrepancy time is set in ms in the user defined chart setting timer applied under heading 1.4 above. A setting of 1200 ms is applied as shown in the screen shot below: Figure 6: Setting of pole discrepancy timer APN Edition 2

7 1.7 Logic with Phase Selective Close AND Open SIPROTEC 5 Application The classic pole discrepancy function was implemented using 6 breaker auxiliary contacts in the configuration shown in Figure 7 below: Ph A Ph B Ph C Ph A Ph B Ph C + DC CB Pole Dicrepancy BI1 Timer Figure 7: Typical connection of discrete Pole Discrepancy Logic If the 6 auxiliary contacts shown in Figure 7 are connected to the SIPROTEC5 device a different logic should be implemented to achieve the same response as from the discreet logic shown in Figure 7 (Figure 9). Ph A Ph B Ph C Ph A Ph B Ph C + DC CB BI1 SIPROTEC 5 FG CB 1 pole phsa Close High BI2 1 pole phsb Close High BI3 1 pole phsc Close High BI4 1 pole phsa Open High BI5 1 pole phsb Open High BI6 1 pole phsc Open High Figure 8: Connection of auxiliary contacts with phase selective Close High AND Open High status To replicate the pole discrepancy logic as shown in Figure 7 with the connection to SIPROTEC5 as shown in Figure 8 the following logic must be applied: Edition 2 7 APN-031

8 SIPROTEC 5 Applikation Figure 9: CFC chart with pole discrepancy logic (Phase Selective Closed AND Open Status) With the CFC chart in Figure 9, the output of the two 3-input OR gates will both be high only when at least one of the normally open and one of the normally closed auxiliary contacts is closed (compare with Figure 7). The AND gate will then only trigger the timer when this pole discrepancy condition is present. 1.8 Conclusion The application note shows how the standard functions in the device can be applied to derive additional functions such as a Pole Discrepancy Alarm. Note that the logic must be selected according to the manner in which the Breaker Status is obtained. APN Edition 2

9 SIPROTEC 5 Application Edition 2 9 APN-031

10 Published by Siemens AG 2016 Energy Management Division Digital Grid Automation Products Humboldtstr Nuremberg, Germany For more information, please contact our Customer Support Center. Tel.: Fax: (Charges depending on provider) Siemens. Subject to changes and errors. The information given in this document only contains general descriptions and/or performance features which may not always specifically reflect those described, or which may undergo modification in the course of further development of the products. The requested performance features are binding only when they are expressly agreed upon in the concluded contract. For all products using security features of OpenSSL, the following shall apply: This product includes software developed by the OpenSSL Project for use in the OpenSSL Toolkit. ( ) This product includes cryptographic software written by Eric Young (eay@cryptsoft.com ) This product includes software written by Tim Hudson (tjh@cryptsoft.com) This product includes software developed by Bodo Moeller. APN Edition 2

Ground fault supervision of 4 feeders with 7SJ82 or 7SJ85 with 4x I, 4x V

Ground fault supervision of 4 feeders with 7SJ82 or 7SJ85 with 4x I, 4x V with 7SJ82 or 7SJ85 with 4x I, 4x V SIP5-APN-029, Edition 1 www.siemens.com/protection SIPROTEC 5 Application Note with 7SJ82 or 7SJ85 with 4x I, 4x V SIP5-APN-029, Edition 1 Content 1 with 7SJ82 or 7SJ85

More information

Impedance protection on power transformer.

Impedance protection on power transformer. Impedance protection on power transformer www.siemens.com/siprotec5 SIPROTEC 5 Application Impedance Protection on Power Transformer APN-045, Edition 1 Content 1...3 1.1 Introduction...3 1.2 Application

More information

Line protection with transformer in the protection zone

Line protection with transformer in the protection zone Line protection with transformer in the protection zone www.siemens.com/siprotec5 Three-end line protection with transformer in the protection range SIPROTEC 5 Application Three-end line protection with

More information

Acquisition of transformer tap positions via an analog measurement transformer

Acquisition of transformer tap positions via an analog measurement transformer Acquisition of transformer tap positions via SIP5-APN-038, Edition 2 www.siemens.com/protection SIPROTEC 5 Application Note Acquisition of transformer tap positions via SIP5-APN-038, Edition 1 Content

More information

SIPROTEC 5 Application Note

SIPROTEC 5 Application Note www.siemens.com/protection SIPROTEC 5 Application Note SIP5-APN-004: Answers for infrastructure and cities. SIPROTEC 5 - Application: SIP5-APN-004 Content 1 3 1.1 Summary 3 1.2 Introduction 3 1.3 Definitions:

More information

SIPROTEC 5 Application Note

SIPROTEC 5 Application Note www.siemens.com/protection SIPROTEC 5 Application Note SIP5-APN-015: Answers for infrastructure and cities. SIPROTEC 5 - Application: SIP5-APN-015 Content 1 Application 3 1.1 Introduction 3 1.2 Overview

More information

SIPROTEC 5 Application. SIP5-APN-025-en: 7UT8 Autotransformer bank with 2 sets of CT inside the delta connection of the compensation side

SIPROTEC 5 Application. SIP5-APN-025-en: 7UT8 Autotransformer bank with 2 sets of CT inside the delta connection of the compensation side www.siemens.com/protection SIPROTEC 5 Application SIP5-APN-025-en: 7UT8 Autotransformer bank with 2 sets of CT in the delta connection of the compensation Answers for infrastructure and cities. Autotransformer

More information

Fast fault location in medium-voltage cable and overhead line networks siemens.com/short-circuit-indicator

Fast fault location in medium-voltage cable and overhead line networks siemens.com/short-circuit-indicator SICAM short-circuit indicators Fast fault location in medium-voltage cable and overhead line networks siemens.com/short-circuit-indicator SICAM short-circuit indicators for cable and overhead line networks:

More information

Load Shedding (7RW80)

Load Shedding (7RW80) September 2011 Page 1 of 8 (7RW80) 1.0 INTRODUCTION Under normal conditions the generation and demand of power is balanced. If the demand exceeds the power generation, the frequency drops down. This can

More information

SIPROTEC. Multi-Functional Generator Protection Relay 7UM61. Preface. Contents. Introduction 1. Functions 2. Mounting and Commissioning 3

SIPROTEC. Multi-Functional Generator Protection Relay 7UM61. Preface. Contents. Introduction 1. Functions 2. Mounting and Commissioning 3 Preface SIPROTEC Multi-Functional Generator Protection Relay 7UM61 V4.1 Manual Contents Introduction 1 Functions 2 Mounting and Commissioning 3 Technical Data 4 Appendix Literature Glossary A Index C53000-G1176-C127-4

More information

SIPROTEC. Power Supply Transfer Device 7VU68. Preface. Table of contents. Data of the PROFIBUS-DP messages 1. Standard mappings

SIPROTEC. Power Supply Transfer Device 7VU68. Preface. Table of contents. Data of the PROFIBUS-DP messages 1. Standard mappings Preface SIPROTEC Power Supply Transfer Device Table of contents Data of the PROFIBUS-DP messages 1 Standard mappings 3-1 2 Index 7VU68 Communication module PROFIBUS-DP Bus mapping Edition: April. 2014

More information

Automatic reclosing function for high voltage networks

Automatic reclosing function for high voltage networks Automatic reclosing function for high voltage networks Budapest, December 2010. Automatic reclosing function for high voltage networks The HV automatic reclosing function for high voltage networks can

More information

Enhance operational efficiency with Advanced Process Control (APC) Integration of APC in SIMATIC PCS 7 SIMATIC PCS 7. Answers for industry.

Enhance operational efficiency with Advanced Process Control (APC) Integration of APC in SIMATIC PCS 7 SIMATIC PCS 7. Answers for industry. Enhance operational efficiency with Advanced Control (APC) Integration of APC in SIMATIC PCS 7 SIMATIC PCS 7 Answers for industry. Modern closed-loop control systems in the process industry In today s

More information

SIPROTEC Protection Technology. The Basis for Highest Availability of Supply

SIPROTEC Protection Technology. The Basis for Highest Availability of Supply SIPROTEC Protection Technology The Basis for Highest Availability of Supply Unrestricted Siemens AG 2016 www.siemens.com/ Objectives of this Brochure Objective The following examples give an overview of

More information

MAINTENANCE MANUAL 1B170K17 FOUR SHOT AUTO RECLOSE RELAY

MAINTENANCE MANUAL 1B170K17 FOUR SHOT AUTO RECLOSE RELAY Sheet 1 of 9 MAINTENANCE MANUAL 1B170K17 FOUR SHOT AUTO RECLOSE RELAY The Maintenance Manual is to be read in conunction with Product/Test Manual Sheet 2 of 9 INDEX 1. FULL DESCRIPTION OF OPERATION 1.1

More information

REB500 TESTING PROCEDURES

REB500 TESTING PROCEDURES Activate HMI 500/REBWIN ver 6.10 or 7.xx. The following screen will appear. Check out the Read Only box & type the password System. Click ok. Connect the black communication cable from the Com port until

More information

SWT 3000 Teleprotection technical data siemens.com

SWT 3000 Teleprotection technical data siemens.com Power network telecommunication SWT 3000 Teleprotection technical data siemens.com Sustainable success for high-voltage power networks The SWT 3000 Teleprotection system has been the first choice for reliable

More information

No. 139 Jinghai Third Road, BDA, Beijing, China, Office TEL. +86 (10) Website

No. 139 Jinghai Third Road, BDA, Beijing, China, Office TEL. +86 (10) Website PONOVO POWER CO., LTD No. 139 Jinghai Third Road, BDA, Beijing, China, 100176 Office TEL. +86 (10) 5908 9666 E-Mail Info@relaytest.com Website www.relaytest.com T1000 Series Universal Tester VERSION: DATE:

More information

Application of Low-Impedance 7SS601 Busbar Differential Protection

Application of Low-Impedance 7SS601 Busbar Differential Protection Application of Low-Impedance 7SS601 Busbar Differential Protection 1. Introduction Utilities have to supply power to their customers with highest reliability and minimum down time. System disturbances,

More information

Circuit Breakers. Excerpt from Master Catalogue. Circuit Breakers. Specifically For You

Circuit Breakers. Excerpt from Master Catalogue. Circuit Breakers. Specifically For You Circuit Breakers Excerpt from Master Catalogue Circuit Breakers Specifically For You Hydraulic-magnetic technology ensures reduced nuisance tripping with temperature variance Always holds 00% rated current

More information

Overcurrent Protection / 7SJ45

Overcurrent Protection / 7SJ45 Overcurrent Protection / SJ SIPROTEC easy SJ numerical overcurrent protection relay powered by CTs Fig. / Description SIPROTEC easy SJ numerical overcurrent protection relay powered by current transformers

More information

SIPROTEC 5 V1.1 Distance Protection, Line Differential Protection and Breaker Management for 1-Pole and 3-Pole Tripping 7SA87, 7SD87, 7SL87, 7VK87

SIPROTEC 5 V1.1 Distance Protection, Line Differential Protection and Breaker Management for 1-Pole and 3-Pole Tripping 7SA87, 7SD87, 7SL87, 7VK87 SIPROTEC 5 V1.1 Distance Protection, Line Differential Protection and Breaker Management for 1-Pole and 3-Pole Tripping 7SA87, 7SD87, 7SL87, 7VK87 Technical Data Extract from manual C53000-G5040-C011-2,

More information

Handling of select-before-execute command. Connections for internal or external synchro-check. Signals for blocking and interlocking of operation

Handling of select-before-execute command. Connections for internal or external synchro-check. Signals for blocking and interlocking of operation Page 1 Issued: December 2000 Status: New Data subject to change without notice Features Part of the apparatus control function Handling of select-before-execute command Connections for internal or external

More information

Texas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event

Texas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event Texas Reliability Entity Event Analysis Event: May 8, 2011 Loss of Multiple Elements Category 1a Event Texas Reliability Entity July 2011 Page 1 of 10 Table of Contents Executive Summary... 3 I. Event

More information

DPX³ 250 Electronic 4P - ModbusTable LGR EN v1.01.xls

DPX³ 250 Electronic 4P - ModbusTable LGR EN v1.01.xls GENERAL MODBUS TABLE ORGANIZATION Starting of the Group s Starting of the Group s System Version (Release) System Version (Build) Group Name (Text) Group Code Group Complexity Group Version 1638 000 01

More information

UPON ACHIEVEMENT OF THE USUAL FUNCTIONS OF TIME WITH PS-3 PLC KLÖCKNER- MOELLER

UPON ACHIEVEMENT OF THE USUAL FUNCTIONS OF TIME WITH PS-3 PLC KLÖCKNER- MOELLER UPON ACHIEVEMENT OF THE USUAL FUNCTIONS OF TIME WITH PS-3 PLC KLÖCKNER- MOELLER Iosif Popa, Assoc. Prof. PhD. Eng., Faculty of Engineering Hunedoara, Politehnica University Timişoara Gabriel Nicolae Popa,,

More information

2015 Relay School Bus Protection Mike Kockott March, 2015

2015 Relay School Bus Protection Mike Kockott March, 2015 2015 Relay School Bus Protection Mike Kockott March, 2015 History of Bus Protection Circulating current differential (1900s) High impedance differential (1940s) Percentage restrained differential (1960s)

More information

GA A23281 EXTENDING DIII D NEUTRAL BEAM MODULATED OPERATIONS WITH A CAMAC BASED TOTAL ON TIME INTERLOCK

GA A23281 EXTENDING DIII D NEUTRAL BEAM MODULATED OPERATIONS WITH A CAMAC BASED TOTAL ON TIME INTERLOCK GA A23281 EXTENDING DIII D NEUTRAL BEAM MODULATED OPERATIONS WITH A CAMAC BASED TOTAL ON TIME INTERLOCK by D.S. BAGGEST, J.D. BROESCH, and J.C. PHILLIPS NOVEMBER 1999 DISCLAIMER This report was prepared

More information

TRAINING Learning and Training application on site. QUALIFYING Evaluation of quiz Knowledge Validation To learn required skills

TRAINING Learning and Training application on site. QUALIFYING Evaluation of quiz Knowledge Validation To learn required skills FIRST LOGIC Substation Automation Training Proficiency development training programme Client-precise. Excellence through certification on your requirements. First Logic substation automation institute

More information

A B. 1 (a) (i) Fig shows the symbol for a circuit component. Fig Name this component. ... [1]

A B. 1 (a) (i) Fig shows the symbol for a circuit component. Fig Name this component. ... [1] (a) (i) Fig.. shows the symbol for a circuit component. Fig.. Name this component.... [] (ii) In the space below, draw the symbol for a NOT gate. (b) Fig..2 shows a digital circuit. [] C D E Fig..2 Complete

More information

Totally Integrated Power SIVACON 8PS LDM busbar trunking system siemens.com/ldm-system

Totally Integrated Power SIVACON 8PS LDM busbar trunking system siemens.com/ldm-system Safe and efficient power transmission in wind turbines Totally Integrated Power SIVACON 8PS LDM busbar trunking system siemens.com/ldm-system Contents Totally Integrated Power 2 SIVACON 8PS busbar trunking

More information

Sicat Master. Engineering of overhead contact line systems. siemens.com/rail-electrification

Sicat Master. Engineering of overhead contact line systems. siemens.com/rail-electrification Sicat Master Engineering of overhead contact line systems siemens.com/rail-electrification When engineering overhead contact lines for mass transit and main line railways, we combine the calculations of

More information

Transformer protection IED RET 670

Transformer protection IED RET 670 Gunnar Stranne Transformer protection IED RET 670 Santiago Septiembre 5, 2006 1 Transformer protection IED RET670 2 Introduction features and applications Differential protection functions Restricted Earth

More information

easygen-2000 Series Genset Control

easygen-2000 Series Genset Control 37429 easygen-2000 Series Genset Control Application Software Version 1.xxxx Manual 37429 WARNING Read this entire manual and all other publications pertaining to the work to be performed before installing,

More information

High speed bus transfer function block description Operation Manual

High speed bus transfer function block description Operation Manual Operation anual FDE Rev.A Page 2 sur 27 User s manual version information Version Date odification Compiled by Version 1.0 30.06.2016. First edition Kiss - Petri A 15/06/2017 Change cover and diffusion

More information

BCP56H series. 80 V, 1 A NPN medium power transistors

BCP56H series. 80 V, 1 A NPN medium power transistors SOT223 8 V, A NPN medium power transistors Rev. 23 November 26 Product data sheet. Product profile. General description NPN medium power transistors in a medium power SOT223 (SC-73) Surface-Mounted Device

More information

Complex Solution for the Distribution Substation REF 542plus. Application and Setting Guide

Complex Solution for the Distribution Substation REF 542plus. Application and Setting Guide Complex Solution for the Distribution Substation REF 542plus 1MRS756412 Complex Solution for the Distribution Substation REF 542plus Copyrights The information in this document is subject to change without

More information

AN2581 Application note

AN2581 Application note AN2581 Application note STM32F10xxx TIM application examples Introduction This application note is intended to provide practical application examples of the STM32F10xxx TIMx peripheral use. This document,

More information

SIPROTEC 5 V1.1 High-Voltage Bay Control Unit 6MD85/86. Technical Data. Extract from manual C53000-G5040-C015-1, chapter 11.

SIPROTEC 5 V1.1 High-Voltage Bay Control Unit 6MD85/86. Technical Data. Extract from manual C53000-G5040-C015-1, chapter 11. SIPROTEC 5 V1.1 High-Voltage Bay Control Unit 6MD85/86 Technical Data Extract from manual C53000-G5040-C015-1, chapter 11 Energy Automation NOTE For your own safety, please observe the warnings and safety

More information

Safe and efficient power transmission in wind turbines

Safe and efficient power transmission in wind turbines Totally Integrated Power SIVACON 8PS Safe and efficient power transmission in wind turbines LDM busbar trunking system www.siemens.com/busbar Contents Totally Integrated Power 2 SIVACON 8PS busbar trunking

More information

Easy Connect connection between SINUMERIK and a robot

Easy Connect connection between SINUMERIK and a robot Application description 10/2015 connection between SINUMERIK and a robot SINUMERIK 828D, SW 4.5 SP3 https://support.industry.siemens.com/cs/ww/en/view/109478437 Warranty and liability Warranty and liability

More information

AND8056/D. Control Solution using Logic, Analog Switches, and Discrete Semiconductor Devices for Reversing a One-Phase Motor APPLICATION NOTE

AND8056/D. Control Solution using Logic, Analog Switches, and Discrete Semiconductor Devices for Reversing a One-Phase Motor APPLICATION NOTE Control Solution using Logic, Analog Switches, and Discrete Semiconductor Devices for Reversing a One-Phase Motor Littelfuse.com APPLICATION NOTE INTRODUCTION In the huge variety of the AC motors, one

More information

200ADM-P. Current Injection System with Phase Shift A 3.000s 2.000A 50.00Hz 0.0. Features

200ADM-P. Current Injection System with Phase Shift A 3.000s 2.000A 50.00Hz 0.0. Features CT ratio Power Harmonics ac+dc 200ADM-P Current Injection System with Phase Shift Features 0-200A output current True RMS metering with 1 cycle capture Variable auxiliary AC voltage/current output with

More information

SIPROTEC Feeder Automation Controller 7SC80

SIPROTEC Feeder Automation Controller 7SC80 Preface SIPROTEC Feeder Automation Controller 7SC80 Contents DNP3 TCP Device Profile 1 Point Lists 2 Index Communication Module DNP3 TCP Bus Mapping/Point Lists C53000-L2040-C353-2 NOTE For your own safety,

More information

AN3332 Application note

AN3332 Application note Application note Generating PWM signals using STM8S-DISCOVERY Application overview This application user manual provides a short description of how to use the Timer 2 peripheral (TIM2) to generate three

More information

Drive System Application

Drive System Application Drive System Application Energy-saving mode with MICROMASTER 440 and SINAMICS Application description for MICROMASTER 440 and SINAMICS Warranty, liability and support Note The Application Examples are

More information

Product Data Sheet. Models 1022/1025/1029C/1032/3629B 3629B. Models 1022/1025/1032. Model 1029C. Model 3629B. Phase Angle Power Control

Product Data Sheet. Models 1022/1025/1029C/1032/3629B 3629B. Models 1022/1025/1032. Model 1029C. Model 3629B. Phase Angle Power Control s 1022/1025/1029C/1032/3629B 3629B Product Data Sheet s 1022/1025/1032 Single phase power controllers Current ratings from 10 to 70 Amps 1022-0 to 5VDC or pot input 1025-4 to 20 ma signal 1032 Current

More information

V7.50 and higher Low-Impedance Busbar Protection 7SS85

V7.50 and higher Low-Impedance Busbar Protection 7SS85 SIPROTEC 5 V7.50 and higher Low-Impedance Busbar Protection 7SS85 Technical Data Extract from manual C53000-G5040-C019-7 chapter 11 Energy Automation i NOTE For your own safety, observe the warnings and

More information

Universal Controller

Universal Controller Universal Controller Overview and Configuration Manual Overview... 1 About this Manual... 1 Introduction... 5 Hardware Overview... 5 Software Overview... 7 Interpreting Flow Diagrams... 8 Foreign Language

More information

Siemens AG New portfolio for reliable personnel, material and fire protection

Siemens AG New portfolio for reliable personnel, material and fire protection s Siemens AG 2016 SENTRON 5SV9 Compact RCBOs New portfolio for reliable personnel, material and fire protection Reliable personnel/ investment protection This combination of residual current operated circuit

More information

Stabilized Differential Relay SPAD 346. Product Guide

Stabilized Differential Relay SPAD 346. Product Guide Issued: July 1998 Status: Updated Version: D/21.03.2006 Data subject to change without notice Features Integrated three-phase differential relay, three-phase overcurrent relay and multiconfigurable earth-fault

More information

IRRIGATION 810-3R RECEIVER GUIDE

IRRIGATION 810-3R RECEIVER GUIDE IRRIGATION 810-3R RECEIVER GUIDE Pg. 2 HOT SHOT OVERVIEW 3 RECEIVER FUNCTION SWITCH SETTINGS 4 RECEIVER INDICATOR LIGHTS 4 SUPERVISION FEATURE 5 RECEIVER HOOKUP TO ENGINE DRIVEN WELL 6 RECEIVER HOOKUP

More information

Hex non-inverting precision Schmitt-trigger

Hex non-inverting precision Schmitt-trigger Rev. 4 26 November 2015 Product data sheet 1. General description The is a hex buffer with precision Schmitt-trigger inputs. The precisely defined trigger levels are lying in a window between 0.55 V CC

More information

74LV32A. 1. General description. 2. Features and benefits. 3. Ordering information. Quad 2-input OR gate

74LV32A. 1. General description. 2. Features and benefits. 3. Ordering information. Quad 2-input OR gate Rev. 1 19 December 2018 Product data sheet 1. General description 2. Features and benefits 3. Ordering information Table 1. Ordering information Type number Package The is a quad 2-input OR gate. Inputs

More information

Overview/Applications

Overview/Applications Overview/Applications Page SIPROTEC Relay Families /3 Typical Protection Schemes /17 Protection Coordination /39 / Siemens SIP Edition No. 6 Overview SIPROTEC Relay Families Solutions for today s and future

More information

SIPROTEC Compact 7SJ80 V4.6 Overcurrent Time Protection

SIPROTEC Compact 7SJ80 V4.6 Overcurrent Time Protection SIPROTEC Compact 7SJ80 V4.6 Overcurrent Time Protection Technical Data Extract from manual E50417-G1140-C343-A4, chapter 4 Energy Automation Note For safety purposes, please note instructions and warnings

More information

Introduction to PLCs

Introduction to PLCs Introduction to PLCs Introduction to PLCs Jay F. Hooper Carolina Academic Press Durham, North Carolina Copyright 2005 Jay F. Hooper All Rights Reserved Library of Congress Cataloging-in-Publication Data

More information

TN034 - Geo-Fencing with the SkyRouter TN November, Geo-Fencing with the SkyRouter (TN034)

TN034 - Geo-Fencing with the SkyRouter TN November, Geo-Fencing with the SkyRouter (TN034) 1. Applicability Geo-Fencing with the SkyRouter (TN034) All 4200, 4400, and 4550 models with required firmware upgrade. For the 4200/440 the required firmware is 4.02.02.07 or 6.00.01.00 or newer and for

More information

Excitation Systems RG3 - T4. Transistorized Excitation Systems for Synchronous Generators. Power Generation

Excitation Systems RG3 - T4. Transistorized Excitation Systems for Synchronous Generators. Power Generation Excitation Systems RG3 - T4 Transistorized Excitation Systems for Synchronous Generators Power Generation Operating Characteristics Reliability High availability Digital control facilities Very good control

More information

Gas-Insulated Medium-Voltage Switchgear siemens.com/8dab12

Gas-Insulated Medium-Voltage Switchgear siemens.com/8dab12 8DB 12 blue GIS Gas-Insulated Medium-Voltage Switchgear siemens.com/8dab12 Features Gas-insulated switchgear (GIS) type 8D/B has been an integral part of the medium-voltage portfolio at Siemens for more

More information

Repair & Retrofit new life for old transformers. Repair and retrofitting through TLM Transformer Lifecycle Management. Answers for energy.

Repair & Retrofit new life for old transformers. Repair and retrofitting through TLM Transformer Lifecycle Management. Answers for energy. Repair & Retrofit new life for old transformers Repair and retrofitting through TLM Transformer Lifecycle Management Answers for energy. Repair & Retrofit new life for old transformers The challenge: Transformers

More information

MTS. Stationary Meter Test Systems. - Source Systems - Amplifiers - Reference Meters - Error Calculators - Scanning Heads - Transformers

MTS. Stationary Meter Test Systems. - Source Systems - Amplifiers - Reference Meters - Error Calculators - Scanning Heads - Transformers MTS Stationary Meter Test Systems - Source Systems - Amplifiers - Reference Meters - Error Calculators - Scanning Heads - Transformers Design of a Standard System Design of an Advanced System Our Competence

More information

8253 functions ( General overview )

8253 functions ( General overview ) What are these? The Intel 8253 and 8254 are Programmable Interval Timers (PITs), which perform timing and counting functions. They are found in all IBM PC compatibles. 82C54 which is a superset of the

More information

Differential Protection Optimal differential protection for phase shifter transformers and special transformers

Differential Protection Optimal differential protection for phase shifter transformers and special transformers Differential Protection Optimal differential protection for phase shifter transformers and special transformers Due to the energy transition, a demand for renewable energy sources integration into power

More information

Distributed busbar protection REB500 Technical Manual

Distributed busbar protection REB500 Technical Manual Block diagram of BFP Substation Automation Products Technical Manual Document ID: 1MRK 505 350-UEN Issued: March 2016 Revision: A Product version: 8.2 Copyright 2016 ABB. All rights reserved Copyright

More information

V7.50 and higher Distance Protection, Line Differential Protection and Breaker Management for 1-Pole and 3-Pole Tripping 7SA87, 7SD87, 7SL87, 7VK87

V7.50 and higher Distance Protection, Line Differential Protection and Breaker Management for 1-Pole and 3-Pole Tripping 7SA87, 7SD87, 7SL87, 7VK87 SIPROTEC 5 V7.50 and higher Distance Protection, Line Differential Protection and Breaker Management for 1-Pole and 3-Pole Tripping 7SA87, 7SD87, 7SL87, 7VK87 Technical Data Extract from manual C53000-G5040-C011-9,

More information

Substation Automation Products. Distributed busbar protection REB500 Technical Manual

Substation Automation Products. Distributed busbar protection REB500 Technical Manual Substation Automation Products Technical Manual Document ID: 1MRK 505 296-UEN Issued: May 2015 Revision: - Product version: 8.10 Copyright 2015 ABB. All rights reserved Copyright This document and parts

More information

PMXB360ENEA. Relay driver Power management in automotive and industrial applications LED driver DC-to-DC converter

PMXB360ENEA. Relay driver Power management in automotive and industrial applications LED driver DC-to-DC converter 6 September 23 Product data sheet. General description N-channel enhancement mode Field-Effect Transistor (FET) in a leadless ultra small DFND-3 (SOT25) Surface-Mounted Device (SMD) plastic package using

More information

Relay driver Power management in automotive and industrial applications LED driver DC-to-DC converter

Relay driver Power management in automotive and industrial applications LED driver DC-to-DC converter 5 July 28 Product data sheet. General description N-channel enhancement mode Field-Effect Transistor (FET) in a leadless ultra small DFND-3 (SOT25) Surface-Mounted Device (SMD) plastic package using Trench

More information

Appendix S: PROTECTION ALTERNATIVES FOR VARIOUS GENERATOR CONFIGURATIONS

Appendix S: PROTECTION ALTERNATIVES FOR VARIOUS GENERATOR CONFIGURATIONS Appendix S: PROTECTION ALTERNATIVES FOR VARIOUS GENERATOR CONFIGURATIONS S1. Standard Interconnection Methods with Typical Circuit Configuration for Single or Multiple Units Note: The protection requirements

More information

EPSITRON Electronic Circuit Breakers Compact and Precise ECBs for DC Circuits

EPSITRON Electronic Circuit Breakers Compact and Precise ECBs for DC Circuits EPSITRON Electronic Circuit Breakers Compact and Precise ECBs for DC Circuits WHY SECONDARY-SIDE FUSE PROTECTION? On the secondary side, switchedmode power supplies provide DC voltage to control circuit

More information

80 V, 1 A NPN medium power transistors. Type number Package PNP complement Nexperia JEITA JEDEC BCP56T SOT223 SC-73 - BCP53T

80 V, 1 A NPN medium power transistors. Type number Package PNP complement Nexperia JEITA JEDEC BCP56T SOT223 SC-73 - BCP53T 8 V, A NPN medium power transistors Rev. 5 July 26 Product data sheet. Product profile. General description NPN medium power transistors in a medium power SOT223 (SC-73) Surface-Mounted Device (SMD) plastic

More information

BC857XQA series. 45 V, 100 ma PNP general-purpose transistors

BC857XQA series. 45 V, 100 ma PNP general-purpose transistors 45 V, 100 ma PNP general-purpose transistors Rev. 1 26 August 2015 Product data sheet 1. Product profile 1.1 General description PNP general-purpose transistors in a leadless ultra small DFN1010D-3 (SOT1215)

More information

PDTC143/114/124/144EQA series

PDTC143/114/124/144EQA series PDTC43/4/24/44EQA series s Rev. 30 October 205 Product data sheet. Product profile. General description 00 ma NPN Resistor-Equipped Transistor (RET) family in a leadless ultra small DFN00D-3 (SOT25) Surface-Mounted

More information

Analog Inputs and Outputs

Analog Inputs and Outputs Analog Inputs and Outputs PLCs must also work with continuous or analog signals. Typical analog signals are 0-10 VDC or 4-20 ma. Analog signals are used to represent changing values such as speed, temperature,

More information

PDTC143X/123J/143Z/114YQA series

PDTC143X/123J/143Z/114YQA series PDTC43X/23J/43Z/4YQA series 50 V, 0 ma NPN resistor-equipped transistors Rev. 30 October 205 Product data sheet. Product profile. General description 0 ma NPN Resistor-Equipped Transistor (RET) family

More information

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy Reyrolle Protection Devices 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Description Additional Options Solkor

More information

VARIMETER. Residual current monitor (RCM) Insulation monitoring device (IMD) Insulation fault detection system (EDS) Our experience. Your safety.

VARIMETER. Residual current monitor (RCM) Insulation monitoring device (IMD) Insulation fault detection system (EDS) Our experience. Your safety. VARIMETER Residual current monitor (RCM) Insulation monitoring device (IMD) Insulation fault detection system (EDS) Our experience. Your safety. Residual current and insulation monitoring Maximum availability,

More information

Data. Dr Murari Mohan Saha ABB AB. KTH/EH2740 Lecture 3. Data Acquisition Block. Logic. Measurement. S/H and A/D Converter. signal conditioner

Data. Dr Murari Mohan Saha ABB AB. KTH/EH2740 Lecture 3. Data Acquisition Block. Logic. Measurement. S/H and A/D Converter. signal conditioner Digital Protective Relay Dr Murari Mohan Saha ABB AB KTH/EH2740 Lecture 3 Introduction to Modern Power System Protection A digital protective relay is an industrial microprocessor system operating in real

More information

74AHC1G79; 74AHCT1G79

74AHC1G79; 74AHCT1G79 Rev. 6 23 September 2014 Product data sheet 1. General description 2. Features and benefits 3. Ordering information 74AHC1G79 and 74AHCT1G79 are high-speed Si-gate CMOS devices. They provide a single positive-edge

More information

RETROFITTING. Motor Protection Relay. Two mountings are available, Flush Rear Connection (EDPAR) or Projecting Rear Connection (SDPAR).

RETROFITTING. Motor Protection Relay. Two mountings are available, Flush Rear Connection (EDPAR) or Projecting Rear Connection (SDPAR). RETROFITTING Motor Protection Relay NPM800R (R2 case) and NPM800RE (R3 case) are dedicated to the refurbishment of 7000 series (R2 and R3 cases) of CEE relays providing the protection of medium voltage

More information

SIPROTEC 5 Generator Protection 7UM85. V7.50 and higher. Technichal Data. Extract from manual C53000-G5040-C027-3, chapter 11.

SIPROTEC 5 Generator Protection 7UM85. V7.50 and higher. Technichal Data. Extract from manual C53000-G5040-C027-3, chapter 11. SIPROTEC 5 Generator Protection 7UM85 V7.50 and higher Technichal Data Extract from manual C53000-G5040-C027-3, chapter 11 Energy Automation i NOTE For your own safety, observe the warnings and safety

More information

Low-power configurable multiple function gate

Low-power configurable multiple function gate Rev. 8 7 December 2016 Product data sheet 1. General description The provides configurable multiple functions. The output state is determined by eight patterns of 3-bit input. The user can choose the logic

More information

FIB / FIC. r with Overcurrent Protection (RCBO) Doepke. » effi cient. » reliable. » fl exible. » future-oriented

FIB / FIC. r with Overcurrent Protection (RCBO) Doepke. » effi cient. » reliable. » fl exible. » future-oriented Doepke The experts in residual current protection technology Residual Current Circuit-Breakers it- r with Overcurrent Protection (RCBO) FIB / FIC» effi cient» reliable» fl exible» future-oriented Doepke

More information

BC817K series. 1 Product profile. 45 V, 500 ma NPN general-purpose transistors. 1.1 General description. 1.2 Features and benefits. 1.

BC817K series. 1 Product profile. 45 V, 500 ma NPN general-purpose transistors. 1.1 General description. 1.2 Features and benefits. 1. 45 V, 5 ma NPN general-purpose transistors Rev. 2 6 March 28 Product data sheet Product profile. General description NPN general-purpose transistors in a small SOT23 (TO-236AB) Surface-Mounted Device (SMD)

More information

RMV-122D, RMV-132D ANSI

RMV-122D, RMV-132D ANSI DATA SHEET Voltage relays, RMV-112D, RMV-122D, RMV-132D ANSI codes 27/59, 59, 27 Under-voltage/over-voltage 3-phase measurement LED indication of fault condition Timer-controlled tripping LED indication

More information

ATS-01 Ver1.2 AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL

ATS-01 Ver1.2 AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL ATS-01 Ver1.2 AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL Headquarters : No.3, Lane 201, Chien Fu ST., Chyan Jenn Dist., Kaohsiung, TAIWAN Tel : + 886-7-8121771 Fax : + 886-7-8121775 URL :

More information

TEAMS Competition 2014

TEAMS Competition 2014 TEAMS Competition 2014 Engineering Digital Relays for Smart Electrical Grids Introduction W hen people talk about the national power grid, they are actually describing three power grids that are connected

More information

Embedded Generation Information Package

Embedded Generation Information Package Embedded Generation Information Package Remote Monitoring (RM) Remote Shutdown (RS) Prepared by: Station Design and Standards Embedded Generation Revision: 1.6 December 2015 Page 1 of 10 1. Background:

More information

HEF4002B. 1. General description. 2. Features and benefits. 3. Ordering information. 4. Functional diagram. Dual 4-input NOR gate

HEF4002B. 1. General description. 2. Features and benefits. 3. Ordering information. 4. Functional diagram. Dual 4-input NOR gate Rev. 4 17 October 2016 Product data sheet 1. General description 2. Features and benefits 3. Ordering information The is a dual 4-input NOR gate. The outputs are fully buffered for highest noise immunity

More information

Excitation Systems THYRIPART. Compound-Excitation System for Synchronous Generators. Power Generation

Excitation Systems THYRIPART. Compound-Excitation System for Synchronous Generators. Power Generation Excitation Systems Compound-Excitation System for Synchronous Generators Power Generation Operating Characteristics Load dependent Short circuit supporting Low voltage gradient dv/dt Black start capability

More information

74AHC1G79-Q100; 74AHCT1G79-Q100

74AHC1G79-Q100; 74AHCT1G79-Q100 74AHC1G79-Q100; 74AHCT1G79-Q100 Rev. 2 23 September 2014 Product data sheet 1. General description 74AHC1G79-Q100 and 74AHCT1G79-Q100 are high-speed Si-gate CMOS devices. They provide a single positive-edge

More information

Table 1. Quick reference data Symbol Parameter Conditions Min Typ Max Unit V RRM. half sine wave; T sp 112 C; Fig A

Table 1. Quick reference data Symbol Parameter Conditions Min Typ Max Unit V RRM. half sine wave; T sp 112 C; Fig A 4 September 8 Product data sheet. General description Planar passivated with sensitive gate in a SOT3 (SC-73) surface mountable plastic package. These devices are intended to be interfaced directly to

More information

ROTATIONAL TUBE CUTTER ROTUCUT. High speed for more productivity

ROTATIONAL TUBE CUTTER ROTUCUT. High speed for more productivity ROTATIONAL TUBE CUTTER ROTUCUT High speed for more productivity HIGH-PERFORMANCE CUTTER Optimal cutting results with shearing and sawing From raw tube to finished tube, the SMS group supplies everything

More information

NEW DESIGN OF GROUND FAULT PROTECTION

NEW DESIGN OF GROUND FAULT PROTECTION NEW DESIGN OF GROUND FAULT PROTECTION J. Blumschein*, Y. Yelgin* *SIEMENS AG, Germany, email: joerg.blumschein@siemens.com Keywords: Ground fault protection, directional element, faulted phase selection

More information

SIPROTEC. Multifunction protection with control 7SJ61 / 7SJ62 / 7SJ64. Preface. Table of Contents. Notes to SIPROTEC objects 1

SIPROTEC. Multifunction protection with control 7SJ61 / 7SJ62 / 7SJ64. Preface. Table of Contents. Notes to SIPROTEC objects 1 SIPROTEC Multifunction protection with control 7SJ61 / 7SJ62 / 7SJ64 Preface Table of Contents Notes to SIPROTEC objects 1 IEC 60870-5-103 Interoperability 2 Point List 3 Glossary Index Communication module

More information

X80 Activator. User's Manual. Version 1.1.

X80 Activator. User's Manual. Version 1.1. X80 Activator User's Manual Version 1.1 www.buckeyecam.com Table of Contents 1. Warnings... 3 2. Overview... 4 3. Getting Started... 5 4. Using the Activate Button... 7 5. Wiring... 8 6. Specifications...

More information

CEQA Exempt Referral Staff Approval Permit

CEQA Exempt Referral Staff Approval Permit DEPARTMENT OF PLANNING AND COMMNITY DEVELOPMENT 00 0 TH Street, Suite 3400, Modesto, CA 95354 Planning Phone: (209) 525-6330 Fax: (209) 525-59 uilding Phone: (209) 525-6557 Fax: (209) 525-7759 Date: November

More information

BUK A. Low conduction losses due to low on-state resistance Q101 compliant Suitable for logic level gate drive sources

BUK A. Low conduction losses due to low on-state resistance Q101 compliant Suitable for logic level gate drive sources 9 March 2 Product data sheet. General description Logic level N-channel enhancement mode Field-Effect Transistor (FET) in a plastic package using TrenchMOS technology. This product has been designed and

More information

AN TEA1892 GreenChip synchronous rectifier controller. Document information

AN TEA1892 GreenChip synchronous rectifier controller. Document information Rev. 1 9 April 2014 Application note Document information Info Keywords Abstract Content GreenChip, TEA1892TS, TEA1892ATS, Synchronous Rectifier (SR) driver, high-efficiency The TEA1892TS is a member of

More information