A Review of the ALL-TEST IV PRO 2000 and SKF/Baker AWA II

Size: px
Start display at page:

Download "A Review of the ALL-TEST IV PRO 2000 and SKF/Baker AWA II"

Transcription

1 A Review of the ALL-TEST IV PRO 2000 and SKF/Baker AWA II Howard W Penrose, Ph.D., CMRP Vice President, Engineering and Reliability Services Dreisilker Electric Motors, Inc. Abstract: The importance of understanding the capabilities and limitations of the technologies for testing electric machines cannot be understated. Modern methods include both high and low voltage tests including insulation to ground, turn impulse testing, and motor circuit analysis. In this paper we will review several examples of the capabilities and limitations of both PD Surge, using an SKF Baker AWA II-6kV (AWA), and a Motor Circuit Analyzer, the ALL-TEST IV PRO 2000 (AT4). The comparison will include time to test, evaluation of the scope of test, and several examples of missed findings where other methods were able to detect the fault. In each case, the actual issues, if any, were unknown prior to the performance of each test. Note: We are looking to evaluate other test instruments such as the PdMA as part of this study. If you wish to lend us your PdMA tester for 3-4 weeks, please contact Dr. Penrose at hpenrose@dreisilker.com. Introduction For well over a century the primary methods for electricians to evaluate machines have been limited to insulation to ground testing, continuity and other similar tests. During the 1980s advanced test methods came onto the market that utilized both high voltage and low voltage methods to determine the condition of machines in the field. One method is based upon the surge comparison methodology which utilizes a tank circuit and a series of fast rise time pulses sent to a winding. The other utilizes very low voltage levels and higher frequencies along with bridge circuits to evaluate the condition of the windings. The high voltage test is exploring for insulation weakness while the low voltage test is exploring for insulation condition. In both cases, the technologies require a path to detect faults. During several weeks at the end of June, 2010, and the beginning of July, 2010, Dreisilker Electric Motors, Inc. was requested to review the capabilities of the AWA II-6kV system which weighs approximately 40 lbs. It was determined by Dreisilker Engineering to take the opportunity to review the AT4 and the AWA without representatives of either vendor participating. The results were interesting and provided important information on the accuracy of both technologies both in comparison and in capability. The live tests can be viewed on the MotorDoc channel of ( The tests were performed on relatively small electric motors of about ten horsepower, 480Vac, through to 19,000 horsepower, 13.2kV, including through over 1,000 feet of run. Each case was introduced into real world conditions without prior knowledge of the actual conditions of the machines. One 8000 horsepower electric motor made for an interesting case study and will be included in this paper. The results of this paper led the investigators to a greater understanding as to the need for training and experience in each of the technologies they use. Inexperienced technicians tend to rely too much on exact results which can end with unfortunate conclusions. It will also be noted that several of the case studies presented indicate the failure of the technology(s) to detect specific faults within their advertised capability. ANY technology that claims that this proves their technology superior had obviously not been subjected to the rigors of this analysis and cannot make such claims. In effect, buyer beware of such tactics (and we would be happy to put them through the same rigors and comparisons). It is noted by the investigators that each of the technologies evaluated in this paper have performed admirably in the field for over two decades.

2 Overheated Windings During the testing that was being performed, a great number of motors, with a few of them shown in the YouTube videos, were tested both assembled and disassembled. The purpose of this paper is to identify where things were missed and to evaluate the reasons why. The first evaluation that was missed was a submersible pump. Both the AT4 and AWA were used with the full range of both instruments (abbreviated for YouTube, the PI was not performed with the AWA, just the DA). The AWA was set for resistance, 500Vdc insulation resistance and DA, a high potential test of 2000 Vdc, and a surge test at 2000 Volts. The value for the high potential and surge tests should have been: Eq. 1: DC High Potential (used winding) ( 2(480V ) V ) *1.7 *.65 = 2, 166V Eq. 2: Surge Test (new winding) ( 2(480) V ) = 1, 960V The values used were the default values of the AWA. The submersible was tested with the default 480 Vac machine values built into the AWA, including the Dielectric Absorption (DA). The findings can be found as Attachment A of this white paper. The AT4 was also utilized and all of the tests performed were satisfactory. The motor was disassembled and the stator inspected. The AT4 and AWA had detected rather low insulation readings which changed as the leads were moved. The submersible had been installed and the cable fouled and damaged. It was then energized. Upon disassembly of the pump, it was determined that the winding had overheated as the ties broke on the windings. The insulation, in general, looked to be in good condition other than the overheating (Figure 1). The low insulation resistance related to the leads was due to the insulation on the leads deteriorating. The low insulation resistance detected a potential problem; the additional work identified the issue. Figure 1: Overheated Winding The conclusion was that experience is still required even while using advanced testing equipment. Without the experience to hunt down the cause for the odd insulation resistance readings, the unit might have passed and been put back into service as both technologies passed the winding based upon automated (software) analysis. Understanding the presented data allowed the technician to focus in on the fault hp 13.2 kv Machine Another project involved reviewing the condition of two large 13.2 kv machines. One at 19,000 horsepower synchronous and one 8,000 horsepower induction that had tripped off line. The unit available for initial testing was the 6kV AWA unit at close to 40 pounds and requiring a 100 foot extension cord. The other unit was the ALL-TEST IV PRO Table 1: AT4 Pro 19000hp Data T1-T2 T1-T3 T2-T3 Resistance Impedance Inductance Fi I/F The AT4 was used from the disconnect approximately 250 yards away with results

3 showing in Table 1 for the 19,000 horsepower motor. The AWA was used with the resistance, insulation resistance, and polarization index being used from the disconnect. It required disconnection at the motor (the lightning arrestors and surge arrestors were disconnected for all testing) to perform the high potential test and surge test. Figure 2: Surge Test hp The motor was pulled from service and disassembled for evaluation. It was immediately apparent that one winding had blown and had impacted the coil immediately across. It was also apparent that the sole reason why the fault was detected with insulation resistance and capacitance testing was carbon dust and conductive contaminants on the surface of the conductors. If there had been any break, the fault would not have been detected even with four wire Kelvin technology. Figure 3: Actual Fault Image A phase to phase insulation resistance test was also performed with the neutral open and a phase to phase capacitance test was performed with the ATIV. Based upon the success of all of the testing, it was determined that this motor could be started, and was, successfully. The 8000hp machine was evaluated at the motor. The surge test passed at 6,000 Volts, the insulation resistance and PI tests passed, the step voltage high potential test passed, and the ATIV test passed (Table 2). Table 2: ATIV Test 8000 hp T1-T2 T1-T3 T2-T3 Resistance Impedance Inductance Fi I/F Figure 4: Image Inside Faulted Coil The capacitance readings using the ATIV identified an issue and the insulation resistance test between A phase and B phase tripped on overcurrent at 3250 Vdc. As only these tests identified a fault, a second high voltage insulation resistance test was performed with a different meter. It also failed at over 3200 Vdc.

4 During the investigation, it was noted that the machine and coil passed a surge test at 22,700 V. The fault was in the first two turns of the first coil of Phase A. What surprised the investigators was that resistance, AWA, surge, and AT4 should have identified this fault even at the test voltages used. It was also noted that when the carbon and contaminants were brushed away from the coils that the insulation resistance and capacitance between phases was excellent. Single Phased Motor During a field analysis of an electronic soft start, an electric motor was found to have a good insulation to ground, good ohm readings and continuity, and passed a surge comparison test. The AT4 was used and the results showed as in Table 3, which shows a turn to turn short and overheated windings. Table 3: AT4 Blower Motor Evaluation T1-T2 T1-T3 T2-T3 Resistance Impedance Inductance Fi I/F Figure 5: Stator Condition As shown in Figure 5, one coil group was burned in the motor. Conclusion As noted in Electrical Motor Diagnostics: 2 nd Edition, no one test method can be relied upon to detect all faults. There is also a high risk of missing faults if the operator does not have a full understanding of the technologies used and equipment that is being tested. It is equally important to note when a single component of a suite of tests performed identifies a potential fault that additional investigation is necessary. The experienced technician needs to use his senses and knowledge as a tool as much as the test equipment available. This is particularly important as 20% or more of electric machines are pulled for repair or replacement that have no problems to begin with. Even worse is when parts are swapped in an effort to plug and play a solution to a problem when equipment is down. These issues occur a majority of the time, especially when the technician does not trust himself or his technology. Bibliography Penrose, Howard W, Ph.D., CMRP, Electrical Motor Diagnostics: 2 nd Edition, SUCCESS by DESIGN, Connecticut, About the Author Howard W Penrose, Ph.D., CMRP is the Vice President of Engineering and Reliability Services for Dreisilker, the Web Editor-in-Chief of the IEEE Dielectrics and Electrical Insulation Society, the Director of Membership for the Society for Maintenance and Reliability Professionals (SMRP) and serves on the Board of Directors for the Autism Society of Illinois. He has won five consecutive UAW and General Motors People Make Quality Happen Awards ( ) for energy, conservation, production, and motor management programs developed for GM facilities globally and is an SMRP Certified Maintenance and Reliability Professional (CMRP). Dr. Penrose is the author of the Axiom Business Book Award (2008 Bronze and 2009 Bronze) winning Physical Asset Management for the Executive (Caution: Do Not Read This If You Are on an Airplane), and the 2008 Foreword Book of the Year Finalist textbook, Electrical Motor Diagnostics: 2 nd Edition. Dr. Penrose may be contacted by at hpenrose@dreisilker.com.

5 Nameplate Information Location DEM Winding Building Incoming Model Manufacturer FAIRBANKS MORSE Serial Number HP/KW 25 Volts-Rating 460 Volts-Operating 460 Amps-Rating 32 Amps-Operating 32 Insulation F Enclosure SUB RPM 1760 Service Factor 1.15 Frame Freq-Hz 60 LR Code LR Amps 0 NEMA Design b Max Amb C 40 NEMA nom eff 0 Duty Cycle cont Manuf's Type Manuf Dt Cd Description Place holder MotorID. After adding valid motors, delete this one

6 Nameplate Information Location DEM Winding Building Incoming Model Manufacturer FAIRBANKS MORSE Serial Number HP/KW 25 Volts-Rating 460 Volts-Operating 460 Amps-Rating 32 Amps-Operating 32 Insulation F Enclosure SUB RPM 1760 Service Factor 1.15 Frame Freq-Hz 60 LR Code LR Amps 0 NEMA Design b Max Amb C 40 NEMA nom eff 0 Duty Cycle cont Manuf's Type Manuf Dt Cd Description Place holder MotorID. After adding valid motors, delete this one Application Information Test Date/Time 6/29/ :13:14 PM Test ID 480V w/rotor<100hp Repair/Job # StepV Tested By Tested For Room # MCC Location DEM Winding Building Incoming Use % Load Vert/Horiz Starter Starts/24Hrs Rewind Dt Install Dt Basic Dt Volts Amps Volts Amps Volts Amps Tester Type AWA4_6kV_4Wire Tester SN Tester ID PP30 SN 0 Cal Date 09/01/2009 Next Cal Date 09/01/2010

7 Results Summary Test ID: Nameplate Information Location DEM Winding Building Incoming Model Manufacturer FAIRBANKS MORSE Serial Number HP/KW 25 Volts-Rating 460 Volts-Operating 460 Amps-Rating 32 Amps-Operating 32 Insulation F Enclosure SUB RPM 1760 Service Factor 1.15 Frame Freq-Hz 60 LR Code LR Amps 0 NEMA Design b Max Amb C 40 NEMA nom eff 0 Duty Cycle cont Manuf's Type Manuf Dt Cd Description Place holder MotorID. After adding valid motors, delete this one 480V w/rotor<100hp StepV Test Date/Time 6/29/ :13:14 PM Repair/Job # Tested By Tested For Room # MCC Location DEM Winding Building Incoming Temp Status Tested PI Status PASS Temp 26.7 C 80.0 F Volts (V) 500 Resist Status PASS DA Ratio 1.0 L1-L2 (Ohms) Corr: PI Ratio DA Only L2-L3 (Ohms) Corr: HiPot PASS L3-L1 (Ohms) Corr: Volts (V) 2000 Max Delta R % 0.083% Current(µA) Coil 1 (Ohms) Corr: Resist (Mohm) 167 At 40 C 66 Coil 2 (Ohms) Corr: Surge Status PASS Coil 3 (Ohms) Corr: Peak Volt(V) L Megohm Status PASS Peak Volt(V) L Volts (V) 500 Peak Volt(V) L Current(µA) 2.50 Max P-P EAR% 3.2%,3.3%,3.1% Resist (Mohm) 200 At 40 C 79 EAR 1-2,2-3,3-1 No Test

8 DA/PI Test Date/Time 6/29/ :13:14 PM Voltage (V) 500 DA Ratio 1.0 PI Ratio DA Only PI Status PASS Time (Min) Current(µA) Megohms 0: : : : : : : :

9 Surge: Nested Waveforms Test Date/Time 6/29/ :13:14 PM Surge Status PASS Lead Peak Voltage (V) PP EAR Status Max P-P EAR% PASS 3.2% PASS 3.3% PASS 3.1%

10 Pulse-to-Pulse EAR Test Date/Time 6/29/ :13:14 PM Surge Status PASS Lead Peak Voltage (V) PP EAR Status Max P-P EAR% PASS 3.2% PASS 3.3% PASS 3.1%

11 Surge Phase-to-Phase Comparison Test Date/Time 6/29/ :13:14 PM Surge Status PASS Compare Peak Voltage (V) LL EAR Status L-L EAR% No Test 15% No Test 11% No Test 24%

A Novel Approach to Electrical Signature Analysis

A Novel Approach to Electrical Signature Analysis A Novel Approach to Electrical Signature Analysis Howard W Penrose, Ph.D., CMRP Vice President, Engineering and Reliability Services Dreisilker Electric Motors, Inc. Abstract: Electrical Signature Analysis

More information

THE ELECTROM itig II MOTOR TESTER AND WINDING ANALYZER

THE ELECTROM itig II MOTOR TESTER AND WINDING ANALYZER THE ELECTROM itig II MOTOR TESTER AND WINDING ANALYZER EASY TO USE TESTER THAT FINDS MORE FAULTS. The state of the art Electrom itig II provides a wide range of tests to analyze the condition of insulation

More information

THE ELECTROM itig II MOTOR TESTER AND WINDING ANALYZER

THE ELECTROM itig II MOTOR TESTER AND WINDING ANALYZER THE ELECTROM itig II MOTOR TESTER AND WINDING ANALYZER AUTOMATED, SAFE, AND EASY TO USE TESTER. HIGH AND LOW VOLTAGE TESTS IN A LIGHTWEIGHT PACKAGE. The state of the art Electrom itig II provides a wide

More information

The Multi-Technology Approach to Motor Diagnostics

The Multi-Technology Approach to Motor Diagnostics The Multi-Technology Approach to Motor Diagnostics Howard W. Penrose, Ph.D. For: ALL-TEST Pro Old Saybrook, CT Introduction There has been a persistent misconception that there is a magic bullet, in the

More information

Application of Electrical Signature Analysis. Howard W Penrose, Ph.D., CMRP President, SUCCESS by DESIGN

Application of Electrical Signature Analysis. Howard W Penrose, Ph.D., CMRP President, SUCCESS by DESIGN Application of Electrical Signature Analysis Howard W Penrose, Ph.D., CMRP President, SUCCESS by DESIGN Introduction Over the past months we have covered traditional and modern methods of testing electric

More information

Direct Current Motor Electrical Evaluation Using Motor Circuit Analysis

Direct Current Motor Electrical Evaluation Using Motor Circuit Analysis Direct Current Motor Electrical Evaluation Using Motor Circuit Analysis Introduction Howard W. Penrose, Ph.D BJM Corp, ALL-TEST Division Old Saybrook, CT Electrical testing of Direct Current (DC) electric

More information

CASE STUDIES IN ONLINE AND OFFLINE MOTOR ANALYSIS

CASE STUDIES IN ONLINE AND OFFLINE MOTOR ANALYSIS CASE STUDIES IN ONLINE AND OFFLINE MOTOR ANALYSIS David L. McKinnon, PdMA Corporation, Member, IEEE Abstract In this paper we present three case studies using online and offline motor analysis to prevent

More information

The NEW itig II Winding and Motor Analyzer A revolution in automated, safe, and comprehensive high and low voltage tests all in a lightweight

The NEW itig II Winding and Motor Analyzer A revolution in automated, safe, and comprehensive high and low voltage tests all in a lightweight The NEW itig II Winding and Motor Analyzer A revolution in automated, safe, and comprehensive high and low voltage tests all in a lightweight package. The Electrom itig II offers a comprehensive range

More information

Case Studies in On-Line and Off-Line Motor Analysis

Case Studies in On-Line and Off-Line Motor Analysis Case Studies in On-Line and Off-Line Motor Analysis Feature by David L. McKinnon PdMA Corporation I. Introduction Current signature analysis (CSA) has become the standard for detecting broken rotor bars

More information

Electrical Motor Diagnostics Applications for Motors and Generators

Electrical Motor Diagnostics Applications for Motors and Generators Speaker BIO President MotorDoc LLC; VP MotorSight Corp; Treasurer SMRP; Web Editor in Chief IEEE DEIS; Managing Partner 2XL Powerlifting LLC Electrical Machinery and related systems condition, energy,

More information

The Basics of Insulation Testing

The Basics of Insulation Testing The Basics of Insulation Testing Feature by Jim Gregorec IDEAL Industries, Inc. What Is Insulation Testing? In a perfect world, all the electrical current sent along a conductive wire would reach its intended

More information

IMPORTANCE OF INSULATION RESISTANCE

IMPORTANCE OF INSULATION RESISTANCE IMPORTANCE OF INSULATION RESISTANCE What is Good Insulation? Every electric wire in your plant whether it s in a motor, generator, cable, switch, transformer, etc., is carefully covered with some form

More information

SKF Static Motor Analyzer Baker DX Series

SKF Static Motor Analyzer Baker DX Series SKF Static Motor Analyzer Baker DX Series Quick Reference Guide Part number: 71-031 EN V1 SKF Static Motor Analyzer Baker DX Series Quick Reference Guide For use with 4 kv, 6 kv, 6 kv high output (HO),

More information

Pulse Width Modulated Motor Drive Fault Detection Using Electrical Signature Analysis

Pulse Width Modulated Motor Drive Fault Detection Using Electrical Signature Analysis Pulse Width Modulated Motor Drive Fault Detection Using Electrical Signature Analysis By ALL-TEST Pro, LLC & EMA Inc. Industry s use of Motor Drives for AC motors continues to grow and the Pulse-Width

More information

Insulation Resistance Testing

Insulation Resistance Testing Testing Application Note Introduction detailed information on leakage resistance testers can currents and resistance tests see be used to determine the integ- the following sections: What Is & Leakrity

More information

Knowledge Is Power SM Apparatus Maintenance and Power Management for Energy Delivery. Application of EMI Diagnostics to Hydro Generators

Knowledge Is Power SM Apparatus Maintenance and Power Management for Energy Delivery. Application of EMI Diagnostics to Hydro Generators Knowledge Is Power SM Apparatus Maintenance and Power Management for Energy Delivery Application of EMI Diagnostics to Hydro Generators James Timperley Doble Global Power Services Columbus, Ohio jtimperley@doble.com

More information

Insulation resistance testing

Insulation resistance testing Insulation resistance testing Application Note Introduction Insulation resistance testers can be used to determine the integrity of windings or cables in motors, transformers, switchgear, and electrical

More information

Electronically Commutated (EC) Motor Control with Solo, Select and Sync PWM Boards

Electronically Commutated (EC) Motor Control with Solo, Select and Sync PWM Boards Electronically Commutated (EC) Motor Control with Solo, Select and Sync PWM Boards The Solo, Select and Sync PWM boards provide a pulse-width modulated (PWM) signal to the EC motor to control fan speed.

More information

ELECTRICIAN S THEORY EXAMINATION 20 November 2010 QUESTION AND ANSWER BOOKLET

ELECTRICIAN S THEORY EXAMINATION 20 November 2010 QUESTION AND ANSWER BOOKLET Candidate Code No. ET37 For Board Use Only Result Date Int Result Date Int ELECTRICIAN S THEORY EXAMINATION 20 November 2010 QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Time Allowed: Three

More information

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser, OMICRON electronics Corp. USA Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser,

More information

ELECTRICIAN S THEORY EXAMINATION 17 November 2012 QUESTION AND ANSWER BOOKLET

ELECTRICIAN S THEORY EXAMINATION 17 November 2012 QUESTION AND ANSWER BOOKLET Candidate Code No. ET43 For Board Use Only Result Date Int Result Date Int ELECTRICIAN S THEORY EXAMINATION 17 November 2012 QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Time Allowed: Three

More information

Insulation Testing. Distributor Training Program

Insulation Testing. Distributor Training Program Testing Distributor Training Program Testing Leaking current can cause a range of problems. Find out if poor insulation is the cause. resistance testers can be used to determine the integrity of windings

More information

The Reflective Wave Phenomena

The Reflective Wave Phenomena Application Note The Reflective Wave Phenomena Rev2.doc The Reflective Wave Phenomena Note to Specifiers This application note contains Cutler-Hammer s recommendations for the application of filters for

More information

ALL-TEST IV PRO. Very Easy To Use. Economical! MOTOR CIRCUIT ANALYZER PREDICTIVE MAINTENANCE QUALITY CONTROL TROUBLE SHOOTING

ALL-TEST IV PRO. Very Easy To Use. Economical! MOTOR CIRCUIT ANALYZER PREDICTIVE MAINTENANCE QUALITY CONTROL TROUBLE SHOOTING Serving the Industry Since 1983 ALL-TEST IV PRO TM MOTOR CIRCUIT ANALYZER PREDICTIVE MAINTENANCE QUALITY CONTROL TROUBLE SHOOTING LOOKING FOR TROUBLE? if so... YOU WILL FIND IT WITH THE ALL-TEST! Revolutionary

More information

BECAUSE MOTOR & GENERATOR FAILURE IS NOT AN OPTION USCG

BECAUSE MOTOR & GENERATOR FAILURE IS NOT AN OPTION USCG PRODUCT CATALOG M O T O R & G E N E R A T O R P R O T E C T I O N BECAUSE MOTOR & GENERATOR FAILURE IS NOT AN OPTION USCG Why Your Equipment Needs MEG-ALERT Protection 1 2 3 4 5 6 7 How can you be sure

More information

WAVEFORM CORRECTOR (WAVEFORM CORRECTORS) REPLACES SURGE PROTECTION DEVICES (SPD) PREVIOUSLY KNOWN AS (TVSS)

WAVEFORM CORRECTOR (WAVEFORM CORRECTORS) REPLACES SURGE PROTECTION DEVICES (SPD) PREVIOUSLY KNOWN AS (TVSS) WAVEFORM CORRECTOR (WAVEFORM CORRECTORS) REPLACES SURGE PROTECTION DEVICES (SPD) PREVIOUSLY KNOWN AS (TVSS) 1 PART 1: GENERAL This section describes materials and installation requirements for low voltage

More information

The Variable Threshold Neutral Isolator (VTNI)

The Variable Threshold Neutral Isolator (VTNI) The Variable Threshold Isolator (VTNI) Installation Instructions INTRODUCTION The is designed specifically for installation between the primary neutral of a power utility distribution system and the secondary

More information

Transformer Factory Testing

Transformer Factory Testing Transformer Factory Testing John J. Foschia Test Engineer John.Foschia@spx.com September 2018 Reasons for Testing Compliance with user specifications Assessment of quality and reliability Verification

More information

SECTION 1 INTRODUCTION

SECTION 1 INTRODUCTION Power PE Engineering Pro Guides Full Exam 80 exam difficulty level problems and detailed solutions Tests concepts not tested by other sample exams. Follows the exam outline and covers the main topics.

More information

ENERGY SAVINGS THROUGH POWER CONDITIONING WITH THE PowerGUARD SYSTEM

ENERGY SAVINGS THROUGH POWER CONDITIONING WITH THE PowerGUARD SYSTEM ENERGY SAVINGS THROUGH POWER CONDITIONING WITH THE PowerGUARD SYSTEM Abstract Efficient operation of the electrical system of any facility is essential to controlling operational costs while maximizing

More information

MIT415 Insulation tester

MIT415 Insulation tester MIT415 Insulation tester General features o 10V & 100V ESD testing o 25V, 50V, 250V & 500V additional ranges o Insulation testing up to 50Gohms (500V) o Continuity testing at 200mA or 20mA from 0.01ohms

More information

Substation Preventive Maintenance

Substation Preventive Maintenance Substation Preventive Maintenance PROVINCIAL ELECTRICITY AUTHORITY 1 Presentation Contents 1) A kind of substation 2) Electrical equipment details of AIS substation 3) Electrical equipment details of GIS

More information

SWF DV/DT Solutions Sinewave Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

SWF DV/DT Solutions Sinewave Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262) SWF DV/DT Solutions Sinewave Filters N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI 53051 P. (262) 754-3883 F. (262) 754-3993 www.apqpower.com Does your application use variable frequency drives for improved

More information

MODEL 421 Over/Under Motor Load Monitor

MODEL 421 Over/Under Motor Load Monitor MODEL 421 Over/Under Motor Load Monitor Monitors True Motor Power (volts x current x power factor) Detects Motor Overload or Underload Operates on 120 or, Single-phase or 3-phase Built-in Trip and Restart

More information

Impulse Testing as a Predictive Maintenance Tool

Impulse Testing as a Predictive Maintenance Tool Testing as a Predictive Maintenance Tool E. Wiedenbrug SM IEEE, G. Frey M IEEE, J. Wilson, M IEEE Baker Instrument Company engr@bakerinst.com Abstract: testing is an integral part of predictive maintenance

More information

SINGLE PHASE BUCK & BOOST TRANSFORMERS INSTRUCTION MANUAL

SINGLE PHASE BUCK & BOOST TRANSFORMERS INSTRUCTION MANUAL SINGLE PHASE INSTRUCTION MANUAL DIAGRAM D This manual applies to all single-phase buck & boost transformers sold by Larson Electronics. Please refer to the connection diagram on pages 4-6 for properly

More information

ENGINEERING DATA SUBMITTAL For the Interconnection of Generation System

ENGINEERING DATA SUBMITTAL For the Interconnection of Generation System WHO SHOULD FILE THIS SUBMITTAL: Anyone in the final stages of interconnecting a Generation System with Nodak Electric Cooperative, Inc. This submittal shall be completed and provided to Nodak Electric

More information

Variable Frequency Drive Packages with Harmonic Mitigation. Low Harmonic Drive Packages Engineered by Rockwell Automation

Variable Frequency Drive Packages with Harmonic Mitigation. Low Harmonic Drive Packages Engineered by Rockwell Automation Variable Frequency Drive Packages with Harmonic Mitigation Low Harmonic Drive Packages Engineered by Rockwell Automation What Do I Need to know About Harmonics? What are Harmonics? Harmonics are deviations

More information

CEU Certification Test Drive Road Show: TRM040-DrivesRoadShow-CEU

CEU Certification Test Drive Road Show: TRM040-DrivesRoadShow-CEU Taking the Certification Test Please record all answers on this answer sheet. The total number of points possible on this test is 35. A passing score is 80% or better (no more than 7 wrong). Returning

More information

Generator Exciter Replacement and Troubleshooting Efforts -- A Capstone Experience

Generator Exciter Replacement and Troubleshooting Efforts -- A Capstone Experience Generator Exciter Replacement and Troubleshooting Efforts -- A Capstone Experience M.M. A Rahman 1 and T. Petersen School of Engineering, Grand Valley State University, 301 W Futon Street Grand Rapids,

More information

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21 Chapter 1 Electrical Fundamentals Unit 1 Matter...3 Introduction...3 1.1 Matter...3 1.2 Atomic Theory...3 1.3 Law of Electrical Charges...4 1.4 Law of Atomic Charges...4 Negative Atomic Charge...4 Positive

More information

Preface...x Chapter 1 Electrical Fundamentals

Preface...x Chapter 1 Electrical Fundamentals Preface...x Chapter 1 Electrical Fundamentals Unit 1 Matter...3 Introduction...3 1.1 Matter...3 1.2 Atomic Theory...3 1.3 Law of Electrical Charges...4 1.4 Law of Atomic Charges...5 Negative Atomic Charge...5

More information

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers KNOW MORE ABOUT THE TRANSFORMERS Glossary Transformers Ambient temperature The existing temperature of the atmosphere surrounding a transformer installation. Ampere The practical unit of electric current.

More information

Industrial Electrician Level 3

Industrial Electrician Level 3 Industrial Electrician Level 3 Industrial Electrician Unit: C1 Industrial Electrical Code I Level: Three Duration: 77 hours Theory: Practical: 77 hours 0 hours Overview: This unit is designed to provide

More information

MIT510/2, MIT520/2 and MIT1020/2

MIT510/2, MIT520/2 and MIT1020/2 MIT510/2, MIT520/2 and MIT1020/2 Line supply or battery operated Digital/analog backlit display Measurement range to 15 TΩ (MIT510/2 and MIT520/2) and 35 TΩ (MIT1020/2) CAT IV 600 V safety rating Automatic

More information

TOSHIBA International Corp

TOSHIBA International Corp TOSHIBA International Corp GUIDE SPECIFICATIONS THREE PHASE UNINTERRUPTIBLE POWER SYSTEM TOSHIBA 4200FA 30 kva CT Internal Battery UPS GUIDE SPECIFICATIONS 1 (30 kva CT) 1.0 SCOPE 1.1 System This specification

More information

7. INSPECTION AND TEST PROCEDURES

7. INSPECTION AND TEST PROCEDURES 7.1 Switchgear and Switchboard Assemblies A. Visual and Mechanical Inspection 1. Compare equipment nameplate data with drawings and specifications. 2. Inspect physical and mechanical condition. 3. Inspect

More information

EVERGREEN EM INSTALLATION GUIDE

EVERGREEN EM INSTALLATION GUIDE EVERGREEN INSTALLATION GUIDE A Regal Brand Genteq s Evergreen is designed to replace O X13 ECM motors quickly and easily with no programming required. Evergreen provides the same comfort, lower utility

More information

Diagnostic testing of cast resin transformers

Diagnostic testing of cast resin transformers Paper of the Month Diagnostic testing of cast resin transformers Author Michael Krüger, OMICRON, Austria michael.krueger@omiconenergy.com Christoph Engelen, OMICRON, Austria christoph.engelen@omicronenergy.com

More information

Investi ations Into the Use of Temperature Detectors as # tator Winding Partial Discharge Detectors

Investi ations Into the Use of Temperature Detectors as # tator Winding Partial Discharge Detectors Conference Record of the 2006 IEEE International Symposium on Electrical Insulation Investi ations Into the Use of Temperature Detectors as # tator Winding Partial Discharge Detectors S.R. Campbell, G.C.

More information

Construction Electrician/Industrial Electrician/Power Electrician Common Core Level 2

Construction Electrician/Industrial Electrician/Power Electrician Common Core Level 2 Common Core Level 2 Unit: B1 Commercial Electrical Code Level: Two Duration: 60 hours Theory: Practical: 60 hours 0 hours Overview: This unit is designed to provide the apprentice with the knowledge about

More information

vacon 100 industrial vacon 100 flow vacon 100 hvac vacon 100 x ac drives du/dt filter technical guide

vacon 100 industrial vacon 100 flow vacon 100 hvac vacon 100 x ac drives du/dt filter technical guide vacon 100 industrial vacon 100 flow vacon 100 hvac vacon 100 x ac drives du/dt filter technical guide vacon 1 TABLE OF CONTENTS Document code: DPD01929A Date: 12.1.2017 1. Introduction... 2 1.1 Intended

More information

FIELD ELECTRICAL TESTING SPX TRANSFORMER SOLUTIONS, INC.

FIELD ELECTRICAL TESTING SPX TRANSFORMER SOLUTIONS, INC. Regional Technical Seminar FIELD ELECTRICAL TESTING SPX TRANSFORMER SOLUTIONS, INC. Field Electrical Testing Applications Key Purposes of Field Electrical Testing: Receiving inspection Acceptance testing/commissioning

More information

INDEX. PdMA PRODUCT SUPPORT MANUAL

INDEX. PdMA PRODUCT SUPPORT MANUAL % Current Imbalance, 6-58, 6-63 % FLA, 6-62 % Full Load Amps, 6-58, 6-62, 6-74 % Slip, 6-57 A About, 3-16 Absorption Current, 5-64 AC Assets, 7-14 AC EMAX Summary Report, 3-46 AC Induction, 5-7 Analysis,

More information

PKG-341-MLA-CBL System Diagram and Specifications

PKG-341-MLA-CBL System Diagram and Specifications PKG-341-MLA-CBL System Diagram and Specifications 600 34Y112S-LW8, MLA10641, Div by 16, 120VAC, Series 400 Included Components: 540 360 34Y112S-LW8-MS MLA10641 CBL-18AWG-04C-010-MS PWR-10EMC1 LIN-AA4254

More information

BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY FEATURES ADDITIONAL INFORMATION. FUNCTIONS AND FEATURES Pages 2-4. APPLICATIONS Page 2

BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY FEATURES ADDITIONAL INFORMATION. FUNCTIONS AND FEATURES Pages 2-4. APPLICATIONS Page 2 BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY The BE1-67N Ground Directional Overcurrent Relay provides ground fault protection for transmission and distribution lines by sensing the direction and magnitude

More information

Top-Innovator MotorAnalyzer 2. Multi-purpose testers for electric motors and windings. Made in Germany Expect more.

Top-Innovator MotorAnalyzer 2. Multi-purpose testers for electric motors and windings. Made in Germany Expect more. Top-Innovator 2014 MotorAnalyzer 2 Multi-purpose testers for electric motors and windings Made in Germany Expect more. EN Winding testers 1 The MotorAnalyzer 2 unbeatably versatile The all-purpose MotorAnalyzer

More information

+ 24V 3.3K - 1.5M. figure 01

+ 24V 3.3K - 1.5M. figure 01 ELECTRICITY ASSESSMENT 35 questions Revised: 08 Jul 2013 1. Which of the wire sizes listed below results in the least voltage drop in a circuit carrying 10 amps: a. 16 AWG b. 14 AWG c. 18 AWG d. 250 kcmil

More information

D7, DH7, DHR7, DR7 Series, Rated up to 50 Amps, 115/200 VAC, 400 Hz

D7, DH7, DHR7, DR7 Series, Rated up to 50 Amps, 115/200 VAC, 400 Hz Product Facts n 3PDT and 3PST NO n Gasket sealed or Hermetically sealed n Auxiliary contacts available n Meets many requirements of MIL-PRF-6106 115/200 VAC, 400 Hz See Part Number Table on Last Page Performance

More information

Conventional Paper-II-2011 Part-1A

Conventional Paper-II-2011 Part-1A Conventional Paper-II-2011 Part-1A 1(a) (b) (c) (d) (e) (f) (g) (h) The purpose of providing dummy coils in the armature of a DC machine is to: (A) Increase voltage induced (B) Decrease the armature resistance

More information

Fault Zone Analysis: Six Part Series on Identifying Motor Defects

Fault Zone Analysis: Six Part Series on Identifying Motor Defects Fault Zone Analysis: Six Part Series on Identifying Motor Defects Noah P. Bethel PdMA Corporation 5909C Hampton Oaks Parkway Tampa, FL 33610 Ph: 813-621-6463 Fax: 813-620-0206 Web: www.pdma.com E-mail:

More information

A cost effective, compact and reliable PWM drive for 1/4 through 1 HP DC applications

A cost effective, compact and reliable PWM drive for 1/4 through 1 HP DC applications A cost effective, compact and reliable PWM drive for 1/4 through 1 HP DC applications The Micro 100 Drives have been designed with a Pulse Width Modulated (PWM) regulator to produce clean DC current to

More information

Measuring Reflected Voltage Spikes in VFD Motor Applications

Measuring Reflected Voltage Spikes in VFD Motor Applications Keywords: VFD, ASD, impedance mismatch, high frequency, reflected voltage, spikes, over voltage, ringing, cable length, inverter rated motor, turn to turn voltage, electric motor testing, oscilloscope,

More information

State of North Dakota Engineering data submittal Page 1 For interconnection of distributed generation to Otter Tail Power Company

State of North Dakota Engineering data submittal Page 1 For interconnection of distributed generation to Otter Tail Power Company Engineering data submittal Page 1 WHO SHOULD FILE THIS SUBMITTAL : Anyone in the final stages of in terconnecting a Generation System with Otter Tail Power. This submittal shall be completed and provided

More information

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Furnish and install automatic transfer switches (ATS) with number of poles, amperage, voltage, and withstand

More information

APPENDIX B: Generation Interconnection Application Form

APPENDIX B: Generation Interconnection Application Form 2 APPENDIX B: Generation Interconnection Application Form WHO SHOULD FILE THIS APPLICATION: Anyone expressing interest to install generation which will interconnect with Xcel Energy (Local electric utility)

More information

Introduction. AC or DC? Insulation Current Flow (AC) 1. TECHNICAL BULLETIN 012a Principles of Insulation Testing. Page 1 of 10 January 9, 2002

Introduction. AC or DC? Insulation Current Flow (AC) 1. TECHNICAL BULLETIN 012a Principles of Insulation Testing. Page 1 of 10 January 9, 2002 Page 1 of 10 January 9, 2002 TECHNICAL BULLETIN 012a Principles of Insulation Testing Introduction Probably 80% of all testing performed in electrical power systems is related to the verification of insulation

More information

MODEL KBWD-15 Pulse Width Modulated (PWM)

MODEL KBWD-15 Pulse Width Modulated (PWM) MODEL KBWD-15 Pulse Width Modulated (PWM) DC MOTOR SPEED CONTROL WHISPER DRIVE INSTALLATION AND OPERATING INSTRUCTIONS See Safety Warning on Page 1 and Application Note Warning on Page 2 The information

More information

5-kV and 10-kV Insulation Resistance Testers. n CAT IV 600 V safety rating. n Line supply or battery operated

5-kV and 10-kV Insulation Resistance Testers. n CAT IV 600 V safety rating. n Line supply or battery operated n CAT IV 600 V safety rating n Line supply or battery operated n Noise rejection (3mA or 4mA rms@200v and above) for use in high voltage substations or switchyards n 5mA output current provides fast charging

More information

Challenges of Parallel Operations

Challenges of Parallel Operations GENLINK TM issimilar Pitch Limiter Key Features Inserts >40% impedance in neutral current circulating path Reduces neutral circulating current by >75% Adds

More information

Insulation resistance testing. A complete solution for every application.

Insulation resistance testing. A complete solution for every application. Insulation resistance testing A complete solution for every application. Why perform insulation testing? Safety The most important reason for testing insulation is to ensure public and personal safety.

More information

WHITE PAPER. Medium Voltage On-Site Generation Overview. BY MIKE KIRCHNER Technical Support Manager at Generac Power Systems

WHITE PAPER. Medium Voltage On-Site Generation Overview. BY MIKE KIRCHNER Technical Support Manager at Generac Power Systems WHITE PAPER Medium Voltage On-Site Generation Overview BY MIKE KIRCHNER Technical Support Manager at Generac Power Systems INTRODUCTION It seems that just about everyone is looking for more power. As our

More information

The InterNational Electrical Testing Association Journal. BY STEVE TURNER, Beckwith Electric Company, Inc.

The InterNational Electrical Testing Association Journal. BY STEVE TURNER, Beckwith Electric Company, Inc. The InterNational Electrical Testing Association Journal FEATURE PROTECTION GUIDE 64S Theory, Application, and Commissioning of Generator 100 Percent Stator Ground Fault Protection Using Low Frequency

More information

REK 510 Current injection device for earth-fault protection of a synchronous machine rotor. User s Manual

REK 510 Current injection device for earth-fault protection of a synchronous machine rotor. User s Manual REK 50 protection of a synchronous machine User s Manual REK 50 X 0 9 8 7 6 5 4 0 V 00 V 0 V 5 6 7 Ordering No: REK 50-AA Uau = 00/0 Vac Un = 48 V Serial No: fn = 50/60 Hz Uec = ma 600 Vdc MRS 75587-MUM

More information

Top wiring permanent magnet latching For non-motor loads, lighting, heating NEMA sizes to 300 A 2-, 3-, and 4-pole configurations

Top wiring permanent magnet latching For non-motor loads, lighting, heating NEMA sizes to 300 A 2-, 3-, and 4-pole configurations Bulletin LP NEMA AC Permanent Magnet-Latching Lighting Contactors Product Overview/Product Selection/Wiring Diagram A, -Pole Open Type without Enclosure Bulletin LP Top wiring permanent magnet latching

More information

CoolBLUE Inductive Absorbers NaLA Noise Line Absorbers

CoolBLUE Inductive Absorbers NaLA Noise Line Absorbers CoolBLUE Inductive Absorbers NaLA Noise Line Absorbers Motor Bearing Solution from MH&W International Corp. http://www.coolblue-mhw.com Variable Frequency Motor Drive Systems 1. What is the problem 2.

More information

PART 1 OWNER/APPLICANT INFORMATION

PART 1 OWNER/APPLICANT INFORMATION CALHOUN COUNTY ELECTRIC COOP. ASSN. Application for Operation of Customer-Owned Generation This application should be completed as soon as possible and returned to the Cooperative in order to begin processing

More information

AC/DC Clamp Meter. Owner's Manual. Model No Safety Operation Maintenance Español

AC/DC Clamp Meter. Owner's Manual. Model No Safety Operation Maintenance Español Owner's Manual AC/DC Clamp Meter Model No. 82369 CAUTION: Read, understand and follow Safety Rules and Operating Instructions in this manual before using this product. Safety Operation Maintenance Español

More information

MIT400 Series CAT IV Insulation Resistance and Continuity Testers

MIT400 Series CAT IV Insulation Resistance and Continuity Testers Insulation testing up to 1000 V and 200 GΩ Patented analog arc and dual digital display CAT IV 600 V rating TRMS & DC Voltage measurement Continuity testing at 200 ma or 20 ma down to 0.01 Pass/Fail limit

More information

INTELLIMETER REGISTER

INTELLIMETER REGISTER INTELLIMETER REGISTER MODEL RG2 INSTALLATION AND CONNECTIONS INSTALLATION MANUAL WARNING: Any work on or near energized metering equipment can present a danger of electrical shock. All work on these products

More information

Distribution/Substation Transformer

Distribution/Substation Transformer Distribution/Substation Transformer Type VFI, Vacuum Fault Interrupter Transformer Option Functional Specification Guide Functional specification for 15 kv, 25 kv, or 35 kv vacuum fault interrupter distribution/substation

More information

Owner/Customer Name: Mailing Address: City: County: State: Zip Code: Phone Number: Representative: Address: Fax Number:

Owner/Customer Name: Mailing Address: City: County: State: Zip Code: Phone Number: Representative:  Address: Fax Number: Interconnection of a Customer-Owned Renewable Generation System of Greater than 100 KW and Less than or Equal to 1 MW to the LCEC Electric Grid Tier 3 Application and Compliance Form Instructions: Complete

More information

Electrical Measurement Safety. Sponsored By:

Electrical Measurement Safety. Sponsored By: Electrical Measurement Safety Sponsored By: About the Viewer Panel Slides: Go to the Links tab at the top and click on the link to download the PDF of the slides If you re watching the archive version,

More information

Installation Guide. A Regal Brand. EvergreenCM ManPROOF _Fnl.indd 1

Installation Guide. A Regal Brand. EvergreenCM ManPROOF _Fnl.indd 1 Installation Guide A Regal Brand EvergreenCM ManPROOF 100713_Fnl.indd 1 In 1987 General Electric introduced ECM technology to the residential HVAC industry. This technology is predominantly used in variable

More information

TRANSFORMER OPERATIONAL PRINCIPLES, SELECTION & TROUBLESHOOTING

TRANSFORMER OPERATIONAL PRINCIPLES, SELECTION & TROUBLESHOOTING Training Title TRANSFORMER OPERATIONAL PRINCIPLES, SELECTION & TROUBLESHOOTING Training Duration 5 days Training Date Transformer Operational Principles, Selection & Troubleshooting 5 15 19 Nov $4,250

More information

ENOSERV 2014 Relay & Protection Training Conference Course Descriptions

ENOSERV 2014 Relay & Protection Training Conference Course Descriptions ENOSERV 2014 Relay & Protection Training Conference Course Descriptions Day 1 Generation Protection/Motor Bus Transfer Generator Protection: 4 hours This session highlights MV generator protection and

More information

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax :

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax : NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata - 700 032, Tel : 033 2477 3126; Fax : 033 2477 2403 www.ntplindia.com SPECIFICATION NTPL MAKE MICRO-CONTROLLER BASED AUTOMATIC 50KV/10A AC HIGH VOLTAGE

More information

VOTANO 100. Accurate and mobile voltage transformer testing and calibration system

VOTANO 100. Accurate and mobile voltage transformer testing and calibration system VOTANO 100 Accurate and mobile voltage transformer testing and calibration system Sophisticated testing of inductive and capacitive voltage transformers VOTANO 100: accuracy and portability At only 15

More information

Training Fees 3,300$ per participant including Materials/Handouts, Tea/Coffee Refreshments & International Buffet Lunch.

Training Fees 3,300$ per participant including Materials/Handouts, Tea/Coffee Refreshments & International Buffet Lunch. Training Title POWER TRANSFORMERS Training Duration 5 days Training Venue and Dates Power transformers 5 20-24 May $3,300 Abu Dhabi In any of the 5 star hotel. The exact venue will be informed soon. Training

More information

Safety through proper system Grounding and Ground Fault Protection

Safety through proper system Grounding and Ground Fault Protection Safety through proper system Grounding and Ground Fault Protection November 4 th, 2015 Presenter: Mr. John Nelson, PE, FIEEE, NEI Electric Power Engineering, Inc. Event to start shortly Scheduled time:

More information

DLVP A OPERATOR S MANUAL

DLVP A OPERATOR S MANUAL DLVP-50-300-3000A OPERATOR S MANUAL DYNALOAD DIVISION 36 NEWBURGH RD. HACKETTSTOWN, NJ 07840 PHONE (908) 850-5088 FAX (908) 908-0679 TABLE OF CONTENTS INTRODUCTION...3 SPECIFICATIONS...5 MODE SELECTOR

More information

Deploying Current Transformers in Applications Greater Than 200 A

Deploying Current Transformers in Applications Greater Than 200 A Deploying Current Transformers in Applications Greater Than 200 A Andrew Schaeffler Step-down Current Transformers (CTs) are common, and useful, in large motor applications. They provide isolation between

More information

MEGOHMMETER. User Manual

MEGOHMMETER. User Manual MEGOHMMETER 11 E N G L I S H User Manual Statement of Compliance Chauvin Arnoux, Inc. d.b.a. AEMC Instruments certifies that this instrument has been calibrated using standards and instruments traceable

More information

Upgrading Your Electrical Distribution System To Resistance Grounding

Upgrading Your Electrical Distribution System To Resistance Grounding Upgrading Your Electrical Distribution System To Resistance Grounding The term grounding is commonly used in the electrical industry to mean both equipment grounding and system grounding. Equipment grounding

More information

ANALYSIS OF A FLASHOVER OPERATION ON TWO 138KV TRANSMISSION LINES

ANALYSIS OF A FLASHOVER OPERATION ON TWO 138KV TRANSMISSION LINES ANALYSIS OF A FLASHOVER OPERATION ON TWO 138KV TRANSMISSION LINES Authors: Joe Perez, P.E.: SynchroGrid, College Station, Texas Hung Ming Chou, SynchroGrid, College Station, Texas Mike McMillan, Bryan

More information

SOUTH CENTRAL INDIANA REMC Application for Operation of Member-Owned Small Power Generation Systems

SOUTH CENTRAL INDIANA REMC Application for Operation of Member-Owned Small Power Generation Systems SOUTH CENTRAL INDIANA REMC Application for Operation of Member-Owned Small Power Generation Systems This application should be completed as soon as possible and returned to the Cooperative in order to

More information

Transformer Questions & Answers

Transformer Questions & Answers Transformer Questions & Answers. What is a transformer and how does it work? A transformer is an electrical apparatus designed to convert alternating current from one voltage to another. It can be designed

More information

TABLE OF CONTENT

TABLE OF CONTENT Page : 1 of 34 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia TABLE OF CONTENT SCOPE 3 REFERENCES

More information