Document ID: PRELIMINARY VERSION

Size: px
Start display at page:

Download "Document ID: PRELIMINARY VERSION"

Transcription

1 Directional residual overcurrent protection function block description Document ID: PRELIMINARY VERSION

2 User s manual version information Version Date Modification Compiled by Preliminary Preliminary version, without technical information Petri Technical information added Petri New Fig. 1-2 added Petri PRELIMINARY VERSION 2/12

3 CONTENTS 1 function Application Mode of operation Structure of the directional residual overcurrent protection algorithm Enabling the directional decision (Comparison ) Calculation of the vector angle (FI calculation) Directional decision (DIRST) Non-directional residual overcurrent protection function (TOC51N) Technical summary Technical data Summary of the parameters Summary of the generated output signals Summary of the input signals The function block PRELIMINARY VERSION 3/12

4 1 function 1.1 Application The main application area of the directional residual overcurrent protection function is l earthfault protection. 1.2 Mode of operation The inputs of the function are the Fourier basic harmonic components of the zero sequence current and those of the zero sequence voltage. The block of the directional decision generates a signal of TRUE value if the UN=3Uo zero sequence voltage and the IN=-3Io current is sufficient for directional decision, and the angle difference between the vectors is within the preset range. This decision enables the output start and trip signal of an overcurrent protection function block (TOC51N). Note: the position of the vectors in Figure 1-1 indicates a forward fault, i.e., the location of the earth fault is on the protected line (the positive direction of the current is from the busbar to the line). jx +R0A Z -R0A Fi RCA R Figure 1-1 The directional decision (setting on the impedance plane) jim 3Io (180-FI) U Uphase Re Un=3Uo Figure 1-2 The directional decision (injected vectors on the complex plane) PRELIMINARY VERSION 4/12

5 1.3 Structure of the directional residual overcurrent protection algorithm Fig.1-2 shows the structure of the directional residual overcurrent protection (TOC51N) algorithm. UNFour TOC 67N AND INFour FI OK φ DIRST OR DIR_OK TOC 51N Signals Parameters Signals Direction=NonDir Figure 1-3 Structure of the residual directional overcurrent protection algorithm The inputs are the RMS value of the fundamental Fourier component of the residual current (IN=3Io), the RMS value of the fundamental Fourier component of the residual voltage (UN=3Uo), parameters, status signals. The outputs are the binary output status signals. The software modules of the residual directional overcurrent protection function: Comparison These modules decide if the RMS values of the fundamental Fourier component of the residual current and voltage are above the limits needed for correct directional decision. FI calculation This module calculates the vector angle between the residual voltage and the residual current. DIRST The directional decision. TOC51N Non-directional residual overcurrent protection function. The following description explains the details of the individual components. PRELIMINARY VERSION 5/12

6 1.3.1 Enabling the directional decision (Comparison ) These modules decide if the RMS values of the fundamental Fourier component of the residual current and voltage are above the limits needed for correct directional decision. Integer parameters Parameter name Title Unit Min Max Step Default The threshold value for the 3Uo zero sequence voltage, below which no directionality is possible. % of the rated voltage of the voltage transformer input. TOC67N_UoMin_IPar_ Uo min % The threshold value for the 3Io zero sequence current, below which no operation is possible. % of the rated current of the current transformer input. TOC67N_IoMin_IPar_ Io min % Table 1-1 The integer parameters for enabling the directional decision The input signals are the RMS values of the fundamental Fourier component of the residual current and voltage. The internal output status signal for enabling the directional decision is true if both the residual voltage and the residual current is above the preset limits Calculation of the vector angle (FI calculation) This module calculates the phase angle between the residual voltage and the residual current. The reference signal is the residual voltage according to Figure 1-1. The input signals are the fundamental Fourier components of the residual current and voltage. The internal output signal is the calculated phase angle Directional decision (DIRST) This module decides if the phase angle between the residual voltage and the residual current is within the limit range defined by the preset parameter. The operation of this function is explained in Figure 1-1. The input signals are The enabling status signal from the Comparison modules in AND relationship. The calculated phase angle between the residual voltage and the residual current. Parameters. The internal output signal is the decision if the direction is OK, which is TRUE if the phase angle between the residual voltage and the residual current is within the limit range defined by the preset parameter OR if non-directional operation is selected by the preset parameter TOC67N_Dir_EPar_ (Direction=NonDir). PRELIMINARY VERSION 6/12

7 Enumerated parameters Parameter name Title Selection range Default Directionality of the function TOC67N_Dir_EPar_ Direction NonDir,Forward,Backward* Forward *The forward direction is defined by the RCA characteristic angle (See Tables 1-4 below). Tables 1-2 The enumerated parameters of the directional decision Integer parameters Parameter name Title Unit Min Max Step Default Operating angle (See Figure 1-1) TOC67N_ROA_IPar_ Operating Angle deg Characteristic angle (See Figure 1-1) TOC67N_RCA_IPar_ Characteristic Angle deg Table 1-3 Integer parameters of the directional decision Non-directional residual overcurrent protection function (TOC51N) This module is equivalent to the TOC51N function block described in a separate document. Summary of the parameters: Enumerated parameters Parameter name Title Selection range Default Operating characteristic selection of the TOC51N module Off,DefiniteTime,IEC Inv,IEC VeryInv,IEC ExtInv,IEC LongInv,ANSI TOC67N_Oper_EPar_ Operation Inv,ANSI ModInv,ANSI VeryInv,ANSI ExtInv,ANSI LongInv,ANSI LongVeryInv,ANSI LongExtInv DefiniteTime Tables 1-4 The enumerated parameters of the TOC51N function block Integer parameters Parameter name Title Unit Min Max Step Default Start current of the inverse characteristics (TOC51N module) TOC67N_StCurr_IPar_ Start current % Table 1-5 Integer parameters of the TOC51N function block Float parameters Parameter name Title Unit Min Max Digits Default Time multiplier of the inverse characteristics (TOC51N module) TOC67N_Multip_FPar_ Time Mult sec Table 1-6 Float parameters of the TOC51N function block PRELIMINARY VERSION 7/12

8 Timer parameters Parameter name Title Unit Min Max Step Default Minimal time delay for the inverse characteristics (TOC 51N module): TOC67N_MinDel_TPar Min. Time msec _ Definite time delay for the inverse characteristics (TOC 51N module): TOC67N_DefDel_TPar Definite Time msec _ Reset time delay for the inverse characteristics (TOC 51N module): TOC67N_Reset_TPar_ Reset Time msec Table 1-7 Timer parameters of the TOC51N function block The output status signals of the TOC51N function block are identical with those of the TOC67N function: Binary status signal Title Explanation TOC67N_GenSt_GrI_ Start General start signal of the function TOC67N_GenTr_GrI_ Trip General trip command of the function Table 1-8 The binary output status signals of the TOC51N function block PRELIMINARY VERSION 8/12

9 1.4 Technical summary Technical data Function Effective range* Accuracy* Definite time characteristics Operating characteristic accuracy Definite time <2% Reset ratio 0.95 Operate time accuracy At Time delay 100 ms <30 ms At Time delay>100 ms <3 ms Reset time ms Inverse time characteristics Operating characteristic accuracy Inverse time, according to parameter selection <2% Reset ratio 0.95 Operate time accuracy <30 ms ms Reset time Or according to reset characteristics Directional characteristics Angular accuracy <3 Table 1-9 Technical data of the directional residual overcurrent protection function PRELIMINARY VERSION 9/12

10 1.4.2 Summary of the parameters Enumerated parameters Parameter name Title Selection range Default Directionality of the function TOC67N_Dir_EPar_ Direction NonDir,Forward,Backward Forward Operating characteristic selection of the TOC51N module Off,DefiniteTime,IEC Inv,IEC VeryInv,IEC ExtInv,IEC LongInv,ANSI Inv,ANSI TOC67N_Oper_EPar_ Operation ModInv,ANSI VeryInv,ANSI ExtInv,ANSI LongInv,ANSI LongVeryInv,ANSI LongExtInv DefiniteTime Table 1-10 The enumerated parameters of the directional residual overcurrent protection function Integer parameters Parameter name Title Unit Min Max Step Default The threshold value for the 3Uo zero sequence voltage, below which no directionality is possible. % of the rated voltage of the voltage transformer input. TOC67N_UoMin_IPar_ Uo min % The threshold value for the 3Io zero sequence current, below which no operation is possible. % of the rated current of the current transformer input. TOC67N_IoMin_IPar_ Io min % Operating angle (See Figure 1-1) TOC67N_ROA_IPar_ Operating Angle deg Characteristic angle (See Figure 1-1) TOC67N_RCA_IPar_ Characteristic Angle deg Start current of the inverse characteristics (TOC51N module) TOC67N_StCurr_IPar_ Start current % Table 1-11 Integer parameters of the directional residual overcurrent protection function PRELIMINARY VERSION 10/12

11 Float parameters Parameter name Title Unit Min Max Digits Default Time multiplier of the inverse characteristics (TOC51N module) TOC67N_Multip_FPar_ Time Mult sec Table 1-12 Float parameters of the directional residual overcurrent protection function Timer parameters Parameter name Title Unit Min Max Step Default Minimal time delay for the inverse characteristics (TOC 51N module): TOC67N_MinDel_TPar_ Min. Time msec Definite time delay for the inverse characteristics (TOC 51N module): TOC67N_DefDel_TPar_ Definite Time msec Reset time delay for the inverse characteristics (TOC 51N module): TOC67N_Reset_TPar_ Reset Time msec Table 1-13 Timer parameters of the directional residual overcurrent protection function Summary of the generated output signals Binary status signal Title Explanation TOC67N_GenSt_GrI_ Start General start signal of the function TOC67N_GenTr_GrI_ Trip General trip command of the function Table 1-14 The binary output status signals of the directional residual overcurrent protection function Summary of the input signals Binary status signals The directional residual overcurrent protection function has a binary input status signal. The conditions are defined by the user applying the graphic equation editor. Binary status signal Title Explanation TOC67N_Blk_GrO_ Block Blocking input status signal Table 1-15 The binary input signal of the directional residual overcurrent protection function PRELIMINARY VERSION 11/12

12 1.4.5 The function block The function block of the residual directional overcurrent protection function is shown in Figure 1-4. This block shows all binary input and output status signals that are applicable in the graphic equation editor. Figure 1-4 The function block of the residual overcurrent protection function The names of the input and output signals are parts of the Binary status signal names listed in Table 1-14 and Table 1-15 above. PRELIMINARY VERSION 12/12

Directional three-phase overcurrent protection function block description

Directional three-phase overcurrent protection function block description Directional three-phase overcurrent protection function block description Document ID: PRELIMINARY VERSION Budapest, October 2009 User s manual version information Version Date Modification Compiled by

More information

Residual instantaneous overcurrent protection function block description

Residual instantaneous overcurrent protection function block description Residual instantaneous overcurrent block description Document ID: PRELIMINARY VERSION User s manual version information Version Date Modification Compiled by Preliminary 30.10.2009. Preliminary version,

More information

Three-phase instantaneous overcurrent protection function block description

Three-phase instantaneous overcurrent protection function block description Three-phase instantaneous overcurrent protection block description Document ID: PRELIMINARY VERSION User s manual version information Version Date Modification Compiled by Preliminary 30.10.2009 Preliminary

More information

Restricted earth-fault protection function block description

Restricted earth-fault protection function block description function block description Document ID: PRELIMINARY VERSION User s manual version information Version Date Modification Compiled by Preliminary 30.10.2009. Preliminary version, without technical information

More information

Capacitor overvoltage protection function

Capacitor overvoltage protection function Budapest, May 2018. User s manual version information Version Date Modification Compiled by 1.0 2012-10-10 First edition Gyula Poka Kornel Petri 1.1 2018-05-30 Minor corrections Erdős VERSION 1.1 2/5 Capacitor

More information

DTIVA-F1 configuration description

DTIVA-F1 configuration description DTIVA-F1 configuration description Document ID: PRELIMINARY VERSION Budapest, July 2010 Microener - 49 rue de l'université 93160 Noisy le Grand France - +33 (0)1 48 15 09 09 - info@microener.com User s

More information

INSTRUCTION MANUAL. AQ F3x0 Feeder protection IED

INSTRUCTION MANUAL. AQ F3x0 Feeder protection IED INSTRUCTION MANUAL AQ F3x0 Feeder protection IED Instruction manual AQ F3x0 Feeder protection IED 2 (173) Revision 1.00 Date November 2010 Changes - The first revision. Revision 1.01 Date January 2011

More information

Centralized busbar differential and breaker failure protection function

Centralized busbar differential and breaker failure protection function Centralized busbar differential and breaker failure protection function Budapest, December 2015 Centralized busbar differential and breaker failure protection function Protecta provides two different types

More information

Overexcitation protection function block description

Overexcitation protection function block description unction block description Document ID: PRELIMIARY VERSIO ser s manual version inormation Version Date Modiication Compiled by Preliminary 24.11.2009. Preliminary version, without technical inormation Petri

More information

High speed bus transfer function block description Operation Manual

High speed bus transfer function block description Operation Manual Operation anual FDE Rev.A Page 2 sur 27 User s manual version information Version Date odification Compiled by Version 1.0 30.06.2016. First edition Kiss - Petri A 15/06/2017 Change cover and diffusion

More information

Distributed busbar differential protection function and breaker failure protection

Distributed busbar differential protection function and breaker failure protection Distributed busbar differential protection function and breaker failure protection Document ID: PP-13-21321 Budapest, September 2016. Distributed busbar differential protection function and breaker failure

More information

Automatic reclosing function for high voltage networks

Automatic reclosing function for high voltage networks Automatic reclosing function for high voltage networks Budapest, December 2010. Automatic reclosing function for high voltage networks The HV automatic reclosing function for high voltage networks can

More information

INSTRUCTION MANUAL. AQ L3x7 Line protection IED

INSTRUCTION MANUAL. AQ L3x7 Line protection IED INSTRUCTION MANUAL AQ L3x7 Line protection IED Instruction manual AQ L3x7 Line Protection IED 2 (210) Revision 1.00 Date November 2010 Changes - The first revision. Revision 1.01 Date January 2011 Changes

More information

Directional Elements in L-PRO 4000

Directional Elements in L-PRO 4000 Directional Elements in L-PRO 4000 ERLPhase Power Technologies Ltd. All Rights Reserved. 1 Objectives This Technical Note clarifies: 1. Directional Elements used in L-PRO 4000: A. Default Directional Element

More information

Extensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network

Extensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network Copyright 2017 ABB. All rights reserved. 1. Introduction Many distribution networks around the world have limited earth-fault current by a resistor located in the LV winding neutral point of for example

More information

function block description to the differential protection and restricted earth-fault protection functions for autotransformers

function block description to the differential protection and restricted earth-fault protection functions for autotransformers Circuit Application breaker guide control function block description to the differential protection and restricted earth-fault protection functions for autotransformers Document ID: Budapest, PRELIMINARY

More information

www. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay

www. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay Transformer Differential Relay The MD3T Transformer Differential Relay is a member of Cooper Power Systems Edison line of microprocessor based protective relays. The MD3T relay offers the following functions:

More information

High-Tech Range. C&S Protection & Control Ltd. MRI1- Digital multifunctional relay for overcurrent protection SELECT/RESET I P I Q I> ENTER CHAR I>

High-Tech Range. C&S Protection & Control Ltd. MRI1- Digital multifunctional relay for overcurrent protection SELECT/RESET I P I Q I> ENTER CHAR I> High-Tech Range MRI1- Digital multifunctional relay for overcurrent protection L1 L2 L3 E I P I Q RS SELECT/RESET + t > I> ENTER CHAR I> U E > t I> TRIP t IE> I>> >> t IE>> t I>> PHASE EARTH 1I MRI1-IRER

More information

ELECTRICAL VARIABLE ANALYZER RELAY EVAR

ELECTRICAL VARIABLE ANALYZER RELAY EVAR ELECTRICAL VARIABLE ANALYZER RELAY EVAR 1 ORION ITALIA SERIES MODBUS PROTOCOL. The ORION ITALIA SERIES implement a subset of the AEG Modicon Modbus serial communication standard. Many devices support this

More information

The three zone distance protection, Z(1,2,3)RW is intended for systems.

The three zone distance protection, Z(1,2,3)RW is intended for systems. Page 1 Revision: - Issued: December 2002 Data subject to change without notice )HDWXUHV Intended for single or two-phase railway systems (16 2/3, 50 or 60 Hz) Full scheme distance protection, where each

More information

Multimeter 500CVD21 RTU500 series

Multimeter 500CVD21 RTU500 series Remote Terminal Units - Data sheet Multimeter 500CVD21 RTU500 series CT/VT interface with 4 voltage and 24 current inputs for direct monitoring of 3/4 wire 0 300 V AC (line to earth), 0...500 V AC (phase

More information

Overcurrent Elements

Overcurrent Elements Exercise Objectives Hands-On Relay Testing Session Overcurrent Elements After completing this exercise, you should be able to do the following: Identify overcurrent element settings. Determine effective

More information

OVERCURRENT PROTECTION RELAY GRD110

OVERCURRENT PROTECTION RELAY GRD110 INSTRUCTION MANUAL OVERCURRENT PROTECTION RELAY GRD110 TOSHIBA Corporation 2002 All Rights Reserved. ( Ver. 3.1) Safety Precautions Before using this product, please read this chapter carefully. 1 This

More information

Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines

Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines Dhanashree Kotkar 1, N. B. Wagh 2 1 M.Tech.Research Scholar, PEPS, SDCOE, Wardha(M.S.),India

More information

UV3 _ Three-Phase Undervoltage Protection Low-Set Stage (UV3Low) High-Set Stage (UV3High)

UV3 _ Three-Phase Undervoltage Protection Low-Set Stage (UV3Low) High-Set Stage (UV3High) 1MRS752333-MUM Issued 10/1997 Version: H/23.06.2005 Data subject to change without notice Three-Phase Undervoltage Protection Low-Set Stage (UV3Low) High-Set Stage (UV3High) Contents 1. Introduction...

More information

POWER SYSTEM ANALYSIS TADP 641 SETTING EXAMPLE FOR OVERCURRENT RELAYS

POWER SYSTEM ANALYSIS TADP 641 SETTING EXAMPLE FOR OVERCURRENT RELAYS POWER SYSTEM ANALYSIS TADP 641 SETTING EXAMPLE FOR OVERCURRENT RELAYS Juan Manuel Gers, PhD Example - Single Line Example 1 - Data Calculate the following: 1. The three phase short circuit levels on busbars

More information

Table 1 Various IRD models and their associated time/current characteristics Time/Current Characteristics. Definite Time Moderately Inverse Time

Table 1 Various IRD models and their associated time/current characteristics Time/Current Characteristics. Definite Time Moderately Inverse Time IRD SCOPE This test procedure covers the testing and maintenance of Westinghouse IRD relays. The Westinghouse Protective Relay Division was purchased by ABB, and new relays carry the ABB label. Refer to

More information

INSTRUCTION MANUAL. AQ F210 Feeder Protection IED

INSTRUCTION MANUAL. AQ F210 Feeder Protection IED INSTRUCTION MANUAL AQ F210 Feeder Protection IED Instruction manual AQ F210 Feeder Protection IED 2 (298) Revision 1.00 Date 8.4.2013 Changes - The first revision for AQ-F210 IED. Revision 1.01 Date 22.11.2013

More information

200ADM-P. Current Injection System with Phase Shift A 3.000s 2.000A 50.00Hz 0.0. Features

200ADM-P. Current Injection System with Phase Shift A 3.000s 2.000A 50.00Hz 0.0. Features CT ratio Power Harmonics ac+dc 200ADM-P Current Injection System with Phase Shift Features 0-200A output current True RMS metering with 1 cycle capture Variable auxiliary AC voltage/current output with

More information

Data. Dr Murari Mohan Saha ABB AB. KTH/EH2740 Lecture 3. Data Acquisition Block. Logic. Measurement. S/H and A/D Converter. signal conditioner

Data. Dr Murari Mohan Saha ABB AB. KTH/EH2740 Lecture 3. Data Acquisition Block. Logic. Measurement. S/H and A/D Converter. signal conditioner Digital Protective Relay Dr Murari Mohan Saha ABB AB KTH/EH2740 Lecture 3 Introduction to Modern Power System Protection A digital protective relay is an industrial microprocessor system operating in real

More information

Teleprotection function

Teleprotection function eleprotection function Budapest, July 2011. eleprotection function eleprotection function he non-unit protection functions, generally distance protection, can have two, three or even more zones available.

More information

AQ F201 Overcurrent and Earthfault

AQ F201 Overcurrent and Earthfault INSTRUCTION MANUAL AQ F201 Overcurrent and Earthfault Relay Instruction manual AQ F201 Overcurrent and Earth-fault Relay 2 (198) Revision 1.00 Date 8.1.2013 Changes - The first revision for AQ-F201 Revision

More information

No. SSIEC-SEW SHINSUNG. Solid Insulation Eco Load Break Switch (SILO) SILO SERIES 15kV, 27kV 400A, 630A

No. SSIEC-SEW SHINSUNG. Solid Insulation Eco Load Break Switch (SILO) SILO SERIES 15kV, 27kV 400A, 630A SHINSUNG Solid Insulation Eco Load Break Switch (SILO) SILO SERIES 15kV, 27kV 400A, 630A Enhanced Self Healing System General SILO is 3 phase, solid insulated load break switch (LBS) and vacuum interruption

More information

Transformer protection IED RET 670

Transformer protection IED RET 670 Gunnar Stranne Transformer protection IED RET 670 Santiago Septiembre 5, 2006 1 Transformer protection IED RET670 2 Introduction features and applications Differential protection functions Restricted Earth

More information

SIEMENS PSS SINCAL Platform 10.5 Update 6

SIEMENS PSS SINCAL Platform 10.5 Update 6 General Information This update can exclusively be used for the PSS SINCAL Platform 10.5. It can't be used with other product versions! Procedure for Installation with Update Wizard Close all running PSS

More information

AutoBench 1.1. software benchmark data book.

AutoBench 1.1. software benchmark data book. AutoBench 1.1 software benchmark data book Table of Contents Angle to Time Conversion...2 Basic Integer and Floating Point...4 Bit Manipulation...5 Cache Buster...6 CAN Remote Data Request...7 Fast Fourier

More information

AQ T216 Transformer Protection IED

AQ T216 Transformer Protection IED INSTRUCTION MANUAL AQ T216 Transformer Protection IED Instruction manual AQ T216 Transformer Protection IED 2 (325) Revision 1.00 Date 8.7.2013 Changes - The first revision for AQ-T216 IED. Revision 1.01

More information

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment T/3000 Substation Maintenance and Commissioning Test Equipment MULTI FUNCTION SYSTEM FOR TESTING SUBSTATION EQUIPMENT SUCH AS: CURRENT, VOLTAGE AND POWER TRANSFORMERS, ALL TYPE OF PROTECTION RELAYS, ENERGY

More information

CableTroll 2410 PN: /03. User Manual

CableTroll 2410 PN: /03. User Manual CableTroll 2410 PN: 01-2410- 02/03 User Manual UG CT 2410-RMU February 2010 This document describes the installation and configuration of the RMU Fault Indicator Product no: 01-2410- 02/03 Rev. 0.1 (21.01.09)

More information

BUS2000 Busbar Differential Protection System

BUS2000 Busbar Differential Protection System BUS2000 Busbar Differential Protection System Differential overcurrent system with percentage restraint protection 1 Typical Busbar Arrangements Single Busbar Double Busbar with Coupler Breaker and a Half

More information

NO WARRANTIES OF ANY KIND ARE IMPLIED ON THE INFORMATION CONTAINED IN THIS DOCUMENT.

NO WARRANTIES OF ANY KIND ARE IMPLIED ON THE INFORMATION CONTAINED IN THIS DOCUMENT. MODBUS/BECO2200-M3425A Communication Data Base for M-3425A Integrated Protection System Device I.D. = 150 Specifications presented herein are thought to be accurate at the time of publication but are subject

More information

SIPROTEC. Multi-Functional Generator Protection Relay 7UM61. Preface. Contents. Introduction 1. Functions 2. Mounting and Commissioning 3

SIPROTEC. Multi-Functional Generator Protection Relay 7UM61. Preface. Contents. Introduction 1. Functions 2. Mounting and Commissioning 3 Preface SIPROTEC Multi-Functional Generator Protection Relay 7UM61 V4.1 Manual Contents Introduction 1 Functions 2 Mounting and Commissioning 3 Technical Data 4 Appendix Literature Glossary A Index C53000-G1176-C127-4

More information

Creating Retinotopic Mapping Stimuli - 1

Creating Retinotopic Mapping Stimuli - 1 Creating Retinotopic Mapping Stimuli This tutorial shows how to create angular and eccentricity stimuli for the retinotopic mapping of the visual cortex. It also demonstrates how to wait for an input trigger

More information

Inrush3 Three-Phase Transformer Inrush and Motor Start-Up Current Detector

Inrush3 Three-Phase Transformer Inrush and Motor Start-Up Current Detector 1MRS752306-MUM Issued: 10/1997 Version: G/23.6.2005 Data subject to change without notice Three-Phase Transformer Inrush and Motor Start-Up Current Detector Contents 1. Introduction... 2 1.1 Features...

More information

C.A Complete electrical network analysis at the tips of your fingers! Power Quality Monitor. Keeping up with the standards

C.A Complete electrical network analysis at the tips of your fingers! Power Quality Monitor. Keeping up with the standards Keeping up with the standards C.A 8352 Power Quality Monitor Complete electrical network analysis at the tips of your fingers! All measurements for complete analysis: powers, harmonics, flicker, symmetry,

More information

PSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2)

PSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2) 1MRS752324-MUM Issued: 3/2000 Version: D/23.06.2005 Data subject to change without notice PSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2) Contents 1. Introduction... 2 1.1

More information

Numerical Multi-Function Motor Protection Relay RHO 3. Operation & Maintenance Instruction Manual

Numerical Multi-Function Motor Protection Relay RHO 3. Operation & Maintenance Instruction Manual Numerical Multi-Function Motor Protection Relay RHO 3 Operation & Maintenance Instruction Manual RHO MANUAL Contents Section Page Description of operation 4 2 Performance specification 20 3 Relay settings

More information

MotStart Three-phase Start-Up Supervision for Motors

MotStart Three-phase Start-Up Supervision for Motors 1MRS752307-MUM Issued: 10/1998 Version: F/23.06.2005 Data subject to change without notice MotStart Three-phase Start-Up Supervision for Motors Contents 1. Introduction... 2 1.1 Features... 2 1.2 Application...

More information

g GE POWER MANAGEMENT

g GE POWER MANAGEMENT 745 FREQUENTLY ASKED QUESTIONS 1 I get a communication error with the relay when I try to store a setpoint. This error can occur for several different reasons. First of all, verify that the address is

More information

Reducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems

Reducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems Reducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems Alexander Apostolov AREVA T&D Automation I. INTRODUCTION The electric utilities industry is going through significant

More information

Advanced Test Equipment Rentals ATEC (2832)

Advanced Test Equipment Rentals ATEC (2832) Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) The toolbox for substation 3-phase testing Three currents and four voltages Stand-alone functionality Rugged and reliable

More information

ASHIDA Numerical 3OC + 1EF Protection Relay

ASHIDA Numerical 3OC + 1EF Protection Relay PROTH. ERR L5 PKP FAULT DT REC LOCK BF L6 L7 CLOSE TRIP ADR 241B Protection Features : 4 Element (3 Phase + EF + Sensitive EF) Over current IDMT/DMT with instant trip. Programmable (Non- Volatile) Setting

More information

NTG MULTIFUNCTON GENERATOR PROTECTION RELAY. NTG-Slide

NTG MULTIFUNCTON GENERATOR PROTECTION RELAY. NTG-Slide NTG MULTIFUNCTON GENERATOR PROTECTION RELAY 1 NTG Digital protection relay that integrates a number of functions required r for the protection of generators. It is used in power stations from gas, steam,

More information

Protection and control. Sepam range Sepam 2000 Metering and protection functions

Protection and control. Sepam range Sepam 2000 Metering and protection functions Protection and control Sepam range Sepam 2 Metering and protection functions Contents chapter / page metering functions 1/1 protection functions 2/1 appendix 3/1 Notation c Sepam 2 may include several

More information

css Custom Silicon Solutions, Inc.

css Custom Silicon Solutions, Inc. css Custom Silicon Solutions, Inc. GENERAL PART DESCRIPTION The is a micropower version of the popular timer IC. It features an operating current under µa and a minimum supply voltage of., making it ideal

More information

Protection and control VIP300. Technical manual

Protection and control VIP300. Technical manual Protection and control VIP300 Technical manual contents 1. presentation of the VIP300...3 2. use and settings...4 3. choice of sensors and operating ranges...9 4. connection scheme...10 5. assembly...11

More information

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements User s Guide General Most faults in power systems can be detected by applying

More information

RISH PQM. Power Quality Monitor. Preliminary Datasheet subject to change without notice. Individual Harmonics measurement upto 56th Harmonics

RISH PQM. Power Quality Monitor. Preliminary Datasheet subject to change without notice. Individual Harmonics measurement upto 56th Harmonics Power Quality Monitor Individual Harmonics measurement upto 56th Harmonics True representation of Voltage & Current waveforms. Phasor Representation of All 3 phases for system analysis Real Time Clock

More information

FUJI Inverter. Standard Specifications

FUJI Inverter. Standard Specifications FUJI Inverter o Standard Specifications Norminal applied motor The rated output of a general-purpose motor, stated in kw. That is used as a standard motor. Rated capacity The rating of an output capacity,

More information

SVERKER 900 Relay and Substation Test System

SVERKER 900 Relay and Substation Test System SVERKER 900 The toolbox for substation 3-phase testing Three currents and four voltages Stand-alone functionality Rugged and reliable for field use Generation of 900 V and 105 A in single phase mode Secondary

More information

U I. Time Overcurrent Relays. Basic equation. More or less approximates thermal fuse. » Allow coordination with fuses 9/24/2018 ECE525.

U I. Time Overcurrent Relays. Basic equation. More or less approximates thermal fuse. » Allow coordination with fuses 9/24/2018 ECE525. Time Overcurrent Relays More or less approximates thermal fuse» Allow coordination with fuses Direction of Current nduced Torque Restraining Spring Reset Position Time Dial Setting Disk Basic equation

More information

TECO F510 Inverter. Quick Start Guide. Step 1. Supply & Motor connection

TECO F510 Inverter. Quick Start Guide. Step 1. Supply & Motor connection Quick Start Guide TECO F510 Inverter This guide is to assist you in installing and running the inverter and verify that it is functioning correctly for it s main and basic features. For detailed information

More information

SPAA 341 C. Feeder Protection Relay. User s manual and Technical description SPAA 341 C. U aux V ~ V. f n. t 2 > [ s ] 0 I 0 >> Trip

SPAA 341 C. Feeder Protection Relay. User s manual and Technical description SPAA 341 C. U aux V ~ V. f n. t 2 > [ s ] 0 I 0 >> Trip SPAA C Feeder Protection Relay User s manual and Technical description f n = 0Hz 0Hz I n = A A ( I ) I n = A A ( I 0B ) I n = 0,A A ( I 0 ) U n = 00V 0V 0V ( ) U 0 I > I I L I L I L I o IRF Uo I o ϕ U

More information

A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG

A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG CHAPTER 3 3.1 INTRODUCTION In plain radial feeders, the non-directional relays are used as they operate when

More information

Setting Generic Distance Relay UTP-100#WPSC1. in the. Computer-Aided Protection Engineering System (CAPE)

Setting Generic Distance Relay UTP-100#WPSC1. in the. Computer-Aided Protection Engineering System (CAPE) Setting Generic Distance Relay UTP-100#WPSC1 in the Computer-Aided Protection Engineering System (CAPE) Prepared for CAPE Users' Group August 6, 1998 Revised August 24, 1998 Electrocon International, Inc.

More information

A NEW DIFFERENTIAL PROTECTION ALGORITHM BASED ON RISING RATE VARIATION OF SECOND HARMONIC CURRENT *

A NEW DIFFERENTIAL PROTECTION ALGORITHM BASED ON RISING RATE VARIATION OF SECOND HARMONIC CURRENT * Iranian Journal of Science & Technology, Transaction B, Engineering, Vol. 30, No. B6, pp 643-654 Printed in The Islamic Republic of Iran, 2006 Shiraz University A NEW DIFFERENTIAL PROTECTION ALGORITHM

More information

Replacement solution

Replacement solution Replacement solution for the ABB DPU2000R protection and control relay Specification File, Revision, Date (Pages) Replacement Relay Specification_ABB DPU2000R_0.doc, Revision 0, August 2, 2013 (37) Table

More information

Multifunction Protection and Switchgear Control Unit REF 542plus Protection Manual

Multifunction Protection and Switchgear Control Unit REF 542plus Protection Manual Multifunction Protection and Switchgear Control Unit REF 542plus Document ID: 1MRS755860 Issued: 2016-06-27 Revision: F Product version: 3.0 Copyright 2016 ABB. All rights reserved Copyright This document

More information

SOFTWARE DEFINED RADIO IMPLEMENTATION IN 3GPP SYSTEMS

SOFTWARE DEFINED RADIO IMPLEMENTATION IN 3GPP SYSTEMS SOFTWARE DEFINED RADIO IMPLEMENTATION IN 3GPP SYSTEMS R. Janani, A. Manikandan and V. Venkataramanan Arunai College of Engineering, Thiruvannamalai, India E-Mail: jananisaraswathi@gmail.com ABSTRACT Radio

More information

15P0161B1 - DCREG for Applications to Electromagnets - SW Rev. D3.09 R.03 - Updated 01/04/04

15P0161B1 - DCREG for Applications to Electromagnets - SW Rev. D3.09 R.03 - Updated 01/04/04 POWER CONNECTIONS AND DCREG PROTECTING DEVICES DCREG thyristor converter can be used to power very inductive loads, such as electromagnets. Applications problems due to this type of load that can be compared

More information

Unit-II----Analysis of HVDC Converters

Unit-II----Analysis of HVDC Converters Unit-II----Analysis of HVDC Converters Introduction: HVDC converters converts AC to DC and transfer the DC power, then DC is again converted to AC by using inverter station. HVDC system mainly consists

More information

Relion 605 series. Self-Powered Feeder Protection REJ603 Application manual

Relion 605 series. Self-Powered Feeder Protection REJ603 Application manual Relion 605 series Relion 605 series Relion 605 series Self-Powered Feeder Protection REJ603 Application manual Document ID: 1MDU07206-YN 6 2 4 This document and parts thereof must not be reproduced or

More information

DPX³ 250 Electronic 4P - ModbusTable LGR EN v1.01.xls

DPX³ 250 Electronic 4P - ModbusTable LGR EN v1.01.xls GENERAL MODBUS TABLE ORGANIZATION Starting of the Group s Starting of the Group s System Version (Release) System Version (Build) Group Name (Text) Group Code Group Complexity Group Version 1638 000 01

More information

Protective Relays Digitrip 3000

Protective Relays Digitrip 3000 New Information Technical Data Effective: May 1999 Page 1 Applications Provides reliable 3-phase and ground overcurrent protection for all voltage levels. Primary feeder circuit protection Primary transformer

More information

3. (a) List out the advantages and disadvantages of HRC fuse (b) Explain fuse Characteristics in detail. [8+8]

3. (a) List out the advantages and disadvantages of HRC fuse (b) Explain fuse Characteristics in detail. [8+8] Code No: RR320205 Set No. 1 1. (a) Explain about Bewley s Lattice diagrams and also mention the uses of these diagrams. [6+2] (b) A line of surge impedance of 400 ohms is charged from a battery of constant

More information

TESTING PROCEDURE for SEL 311L DISTANCE and DIFFERENTIAL RELAY

TESTING PROCEDURE for SEL 311L DISTANCE and DIFFERENTIAL RELAY 1 TESTING PROCEDURE for SEL 311L DISTANCE and DIFFERENTIAL RELAY 2 CONTENTS 1. Launching COMMUNICATION and GETTING Setting Parameters from RELAY 2. MEASUREMENT 3. DIFFERENTIAL TEST 4. OVERCURRENT TEST

More information

1 INTRODUCTION 1.1 PRODUCT DESCRIPTION

1 INTRODUCTION 1.1 PRODUCT DESCRIPTION GEK-00682D INTRODUCTION INTRODUCTION. PRODUCT DESCRIPTION The MDP Digital Time Overcurrent Relay is a digital, microprocessor based, nondirectional overcurrent relay that protects against phase-to-phase

More information

NEW DESIGN OF GROUND FAULT PROTECTION

NEW DESIGN OF GROUND FAULT PROTECTION NEW DESIGN OF GROUND FAULT PROTECTION J. Blumschein*, Y. Yelgin* *SIEMENS AG, Germany, email: joerg.blumschein@siemens.com Keywords: Ground fault protection, directional element, faulted phase selection

More information

SYNCHRONISING AND VOLTAGE SELECTION

SYNCHRONISING AND VOLTAGE SELECTION SYNCHRONISING AND VOLTAGE SELECTION This document is for Relevant Electrical Standards document only. Disclaimer NGG and NGET or their agents, servants or contractors do not accept any liability for any

More information

PC/104 THREE CHANNEL DIGITAL TO. PC/104 THREE CHANNEL DIGITAL to SYNCHRO/RESOLVER CONVERTER

PC/104 THREE CHANNEL DIGITAL TO. PC/104 THREE CHANNEL DIGITAL to SYNCHRO/RESOLVER CONVERTER Model 73DS2 PC/104 THREE CHANNEL DIGITAL TO SYNCHRO/RESOLVER CONVERTER PC/104 THREE CHANNEL DIGITAL to SYNCHRO/RESOLVER CONVERTER 1.2 VA, 16 BIT RESOLUTION; 0.0167 ACCURACY; Built-In SELF TEST With OPTIONAL

More information

www. ElectricalPartManuals. com Generator Differential Relay MD32G Rotating Machine Differential Relay

www. ElectricalPartManuals. com Generator Differential Relay MD32G Rotating Machine Differential Relay Generator Differential Relay The MD3G Rotating Machine Differential Relay is a member of Cooper Power Systems Edison line of microprocessor based protective relays. The MD3G relay offers the following

More information

Modbus communication module for TCX2: AEX-MOD

Modbus communication module for TCX2: AEX-MOD Modbus communication module for TCX2: Communication Specification TCX2 is factory installed in TCX2 series controllers with -MOD suffix, and is also available separately upon request for customer installation

More information

INSTRUCTION MANUAL TRANSFORMER PROTECTION RELAY GRT100 - B

INSTRUCTION MANUAL TRANSFORMER PROTECTION RELAY GRT100 - B INSTRUCTION MANUAL TRANSFORMER PROTECTION RELAY GRT00 - B Toshiba Energy Systems & Solutions Corporation 207 All Rights Reserved. ( Ver. 3.) Safety Precautions Before using this product, be sure to read

More information

MRI3 - Digital multifunctional relay for overcurrent protection

MRI3 - Digital multifunctional relay for overcurrent protection MRI3 - Digital multifunctional relay for overcurrent protection Contents 1 Introduction and application 2 Features and characteristics 3 Design 3.1 Connections 3.1.1 Analog input circuits 3.1.2 Output

More information

DIRECTIONAL PROTECTION

DIRECTIONAL PROTECTION UNIVERSITY OF LJUBLJANA FACULTY OF ELECTRICAL ENGINEERING DIRECTIONAL PROTECTION Seminar work in the course Distribution and industrial networks Mentor: Prof. Grega Bizjak Author: Amar Zejnilović Ljubljana,

More information

APPLICATION OF MULTI-FREQUENCY ADMITTANCE-BASED FAULT PASSAGE INDICATION IN PRACTICAL COMPENSATED MV-NETWORK

APPLICATION OF MULTI-FREQUENCY ADMITTANCE-BASED FAULT PASSAGE INDICATION IN PRACTICAL COMPENSATED MV-NETWORK 24 th International Conference on Electricity Distribution Glasgow, 2-5 June 27 Paper 967 APPLICATION OF MULTI-FREQUENC ADMITTANCE-BASED FAULT PASSAGE INDICATION IN PRACTICAL COMPENSATED MV-NETWORK Janne

More information

GB QUICK GUIDE FOR THE CONFIGURATION OF VARIABLE SPEED DRIVES

GB QUICK GUIDE FOR THE CONFIGURATION OF VARIABLE SPEED DRIVES GB QUICK GUIDE FOR THE CONFIGURATION OF VARIABLE SPEED DRIVES LOVATO ELECTRIC S.P.A. 24020 GORLE (BERGAMO) ITALIA VIA DON E. MAZZA, 12 TEL. 035 4282111 FAX (Nazionale): 035 4282200 FAX (International):

More information

SPAS 348 C. Feeder Protection Relay. User s manual and Technical description SPAS 348 C V ~ V. t 2 > [ s ] f n = 50Hz 60Hz

SPAS 348 C. Feeder Protection Relay. User s manual and Technical description SPAS 348 C V ~ V. t 2 > [ s ] f n = 50Hz 60Hz SPAS 8 C Feeder Protection Relay User s manual and Technical description f n = 50Hz 60Hz I n = A 5A ( I ) I n = 0,A A ( I 0 ) U n 00V...0V ( U ) U n = 00V/0V/0V ( U 0 ) 5 I > I L U I L U IRF B I > I L

More information

Discrete Fourier Transform (DFT)

Discrete Fourier Transform (DFT) Amplitude Amplitude Discrete Fourier Transform (DFT) DFT transforms the time domain signal samples to the frequency domain components. DFT Signal Spectrum Time Frequency DFT is often used to do frequency

More information

H8238/MCM MODBUS POINT MAP

H8238/MCM MODBUS POINT MAP H8238/MCM MODBUS POINT MAP F O R M A T Int Float R/W NV Description 1 257/258 R/W NV Energy Consumption, kwh, Low-word integer 2 259/260 R/W NV Energy Consumption, kwh, High-word integer Both 257/258 and

More information

Protection Scheme for Energy Storage Systems Operating in Island or Grid Connected Modes

Protection Scheme for Energy Storage Systems Operating in Island or Grid Connected Modes 24 th International Conference on Electricity Distribution Glasgow, 12-15 June 217 Paper 182 Protection Scheme for Energy Storage Systems Operating in Island or Grid Connected Modes Andre NEVES Bernardo

More information

PQVO3Sd Short duration voltage variations

PQVO3Sd Short duration voltage variations 1MRS755448 Issued: 6/2005 Version: A/08.07.2005 PQVO3Sd Short duration voltage variations Data subject to change without notice Contents 1. Introduction... 3 1.1 Features... 3 1.2 Short duration voltage

More information

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime Issued: 5.06.999 Status: 5.06.999 Version: B/09..00 Data subject to change without notice Features Overvoltage and undervoltage protection Single- or three-phase operation High-set overvoltage stage with

More information

Electronics Design Laboratory Lecture #4. ECEN 2270 Electronics Design Laboratory

Electronics Design Laboratory Lecture #4. ECEN 2270 Electronics Design Laboratory Electronics Design Laboratory Lecture #4 Electronics Design Laboratory 1 Part A Experiment 2 Robot DC Motor Measure DC motor characteristics Develop a Spice circuit model for the DC motor and determine

More information

Voltage Source Converter Modelling

Voltage Source Converter Modelling Voltage Source Converter Modelling Introduction The AC/DC converters in Ipsa represent either voltage source converters (VSC) or line commutated converters (LCC). A single converter component is used to

More information

Protection relay software models in interaction with power system simulators

Protection relay software models in interaction with power system simulators Protection relay software models in interaction with power system simulators Ivan Goran Kuliš *, Ante Marušić ** and Goran Leci * * Končar-Power Plant and Electric Traction Engineering, Zagreb, Croatia

More information

ALI UMAIR DETECTION ALGORITHM FOR THE CROSS COUNTRY EARTH FAULTS IN MEDIUM VOLTAGE NETWORK

ALI UMAIR DETECTION ALGORITHM FOR THE CROSS COUNTRY EARTH FAULTS IN MEDIUM VOLTAGE NETWORK ALI UMAIR DETECTION ALGORITHM FOR THE CROSS COUNTRY EARTH FAULTS IN MEDIUM VOLTAGE NETWORK Masters of Science Thesis Examiner: Professor Pertti Järventausta and Dr Tech. Ari Nikander Examiner and topic

More information

INSTRUCTIONS FOR THE COMMISSIONING AND MAINTENANCE OF DIGITAL GENERATOR PROTECTION 3 I - PRINCIPLES AND APPLICATIONS 4 on 5 6 7 Figure 5 - Inverse time curve (N1) 8 9 1 0 1 1 1 2 1 3 All relays are delivered

More information

BACnet- MS/TP COMMUNICATION V

BACnet- MS/TP COMMUNICATION V - MS/TP COMMUNICATION V1.00.08.17 11.1 Introduction The VFD can be controlled and monitored through the BACnet MS/TP protocol over an RS-485 connection. The VFD operates as an MS/TP master device, which

More information

HPVFP High Performance Full Function Vector Frequency Inverter

HPVFP High Performance Full Function Vector Frequency Inverter Advanced User Manual HPVFP High Performance Full Function Vector Frequency Inverter HP VER 1.00 1. HPVFP Parameter Set Overview...3 1.1. About this section...3 1.2. Parameter Structure Overview...3 1.3.

More information