Operating Instructions. for. Controller SMS 160 / 161

Size: px
Start display at page:

Download "Operating Instructions. for. Controller SMS 160 / 161"

Transcription

1 Operating Instructions for Controller SMS 160 / 161

2 Contents Controller SMS 160 / Contents... 2 Reserve Safety instructions for users Application Warnings Installation Overview and dimensions Technical data Connection possibilities Starting Operating tips Repairs Troubleshooting Declaration of conformity Reserve General informations und data contained in this documentation can changed without announcement. Errors and omissions excepted. The users are committed to observe all applicably copyright laws. Without explicit permission in written form of the company RUG Regler und Gerätebau GmbH no part of this documentation may copied or communicate for any purposes, independently in which kind or with any instruments, electronically or mechanically, this happens. 2

3 1. Safety instructions for users These instructions contain the necessary information for the correct use of the products described. They are for use by technically qualified persons. Qualified personnel are those persons whose vocational training, experience and internal training and their knowledge of the relevant standards, regulations, accident prevention regulations and plant operating conditions has led the person responsible for operational safety to authorise them to carry out the necessary work, and are able to recognise and avoid potential risks (definition of skilled workers as per IEC 364). Risk information The following information serves not only the personal safety of the operating personnel but also the safety of the products described herein and appliances connected to them. DANGER! Highvoltage operations. Noncompliance can lead to death, serious injury or damage to property. Always disconnect the supply voltage before assembly or dismantling work, when replacing fuses or altering the structure. The relevant Accident Prevention and Safety at Work Regulations must be complied with at all times. Before commissioning, make sure that the appliance's nominal voltage conforms to the local mains voltage. EMERGENCY SWITCHES must remain operational in all working modes. Unlocking EMERGENCY SWITCHES must not lead to uncontrolled. Electrical connections must be covered at all times! After assembly, check all protective conductor systems for correct functioning! Proper use The appliance described here is an electrical device for use in feeder equipment or automation plant. The appliance has been planned for use in oscillation conveyors, in control and automation technology. 3

4 This appliance conforms to the relevant LowVoltage and EMC Guidelines. 2. Application The SMS 160/161 electronic controller is used for stepless control of inductive loads such as spiral conveyors, linear conveyors and hoppers. The controller works on the phase control system, the conveyor output is carried out by setting the magnet voltage via the setpoint potentiometer integrated in the casing cover, or via an externally applied analog setpoint voltage (010 V DC) or an externally connected current source (020mA DC) at the 6pole terminal strip on the board (selectable via jumper). The control curve of the setpoint value voltage can be restricted by means of two trimming potentiometers, Umin and Umax, on the board in such a way that the complete range of the setpoint value can always be used. The ignition impulses can be displaced infinitely in the range of the positive or negative mains voltage halfwave through the setpoint voltage adjustable with the setpoint, which then sets the voltagetime area of the output voltage is set. With feeder appliances with 50 Hz oscillation frequency both (positive and negative) mains voltage halfwaves are controlled, and with feeders with 25 Hz oscillation frequency only one mains voltage halfwave is controlled. The switchover between fullwave and halfwave mode is carried out as a standard with a sliding switch on the board (see Connection Possibilities). After the working voltage has been switched on the integrated variable softstart is started and guarantees smooth acceleration of the output voltage to the preset voltage value. This eliminates possible switching peaks. In addition, the softstart, and the softstop, become effective when the output voltage is switched on and off via the controller input for the level control system and serves to increase or decrease the conveyor output on a timecontrolled basis so that bulk material does not change its position. Both these times can be set separately. The controller inputs control the running time of the oscillation conveyor in such a way that unnecessary running time are avoided. Internal variable times (GAN and GAB) are used to turn the oscillation conveyor ON or OFF in dependency on the material level measured via a material sensor. The controller inputs enable the turn On and OFF of the controller load output through another system (SPS, initiator, sensor and other). The controller has an integrated power supply for +24VDC. A turn ON and OFF through a external +24VDC voltage is possible. The controller input takes affect to the ignition pulses. The controller makes 4 different forms of application available which can choose over switches (standard, hopper control, air blast delay and 2 speeds). A relay, working parallel to the conveyor, and a +24VDC transistor output for control function are integrated. Measurements of the output voltage (arithmetic value measurements) enable changes to the voltage to be registered immediately an compensated by means of a controller stage. This guarantees even running of the bulk material. 4

5 Miniature magnets can also be operated safely at the controller! Setting the ON and OFF time delay for the level controller The level of the material in the filling section is measured by the GAN and GAB trimmers. To increase the material backup downstream from the sensor, use the GAB trimmer to lengthen the controller's OFF delay time. Reduce the GAB time to reduce the backup of material. The GAN trimmer can now be used to determine the time that passes from when the last part of the material leaves the sensor position until the feeder appliance is switched on The diagram shows the time sequence in operations with the controller input low active: V GAN SA GAB SS X 0 0,110s 0,55s 0,110s 0,15s Output voltage t 1 0 Signal at control input t 3. Warnings!!! In the case of applications that require the oscillation conveyor to be switched ON and OFF constantly (e.g. dust switched off, hopper control system, etc.), the prescribed controller input must be used. If the load circuit is disconnected with a switch or a relay the controller may be damaged. If the controller is switched on, never insert or remove the plug at the vibration conveyor being operated. This can damage the appliance. Repair work must be carried out by qualified personnel only. We recommend that repairs are carried out on our premises. 5

6 4. Installation For mounting of the controller there is a hole and a long hole accessibly from the outside. These holes are separated from the interior of the housing. Mounting on a vibration free background. Please notice, the interior ribbon cables may not squeezed against the housing. When the ribbon cables are squeezed there can be a shortcircuit and the controller can be destroyed! 6

7 4.1 Overview and dimensions 7

8 4.2 Technical data Type SMS 160 / SMS 161 Mains voltage 230V AC / +10% / 115V AC / +10% Mains frequency 50Hz / 60Hz Output frequency 25Hz/50Hz / 30Hz/60Hz Output voltage V AC / V AC Setup to 200 VAC Output current 0,01 6 A AC Type of protection IP 54 at mounting hanging (fitting show down) Fuse 1 x 6,3 A F flink Ambient temperature C Setpoint Internal or external potentiometer 010VDC, 420mA Mains connection 2m with gated Schukoplug 90 Connection conveyor 2m witht Contact HA3BS plug Housing Albackground + AlStrand casting + Plastic cover Dimensions (l x b x h) ca. 175 x 80 x 94 mm Features: Oscillation frequency Controller input isolated Switching level HI: 6 24 VDC Switching level LO: 0 4 VDC Reversible +24 V DC / max. 50mA / PNP Opener mode: Output voltage 0 V with applied switching voltage of + 24 V DC Preset output voltage with applied switching of 0 V DC Outputs Relay Transistor output Twin timer (GAN/GAB) Softstart t1 Softstop t2 Mains voltage compensation (arithmetic measurement) Closer mode : Output voltage 0 V with applied switching voltage of 0 V DC Preset output voltage with applied switching voltage of + 24 V DC Twoway contact 230VAC/5A +24VDC / max. 50mA GAN turn ON delay : 010 seconds GAB turn OFF delay : 010 seconds ca sec. Variable ca sec. Variable Compensation of mains voltage fluctuations at output. With preset output voltage of e.g. 170 V AC a max. voltage change of 3,5 V AC arises, with changes of the input voltage from 230 V AC to 200 V AC or from 230 V AC to 260 V AC. Standards complied with DIN EN Part 1 Residential, commercial and trade and light industry, industry. DIN EN Part 2 Industry 8

9 4.3 Connection possibilities VDE

10 Connection conveyor Pin 1 Load Pin 2 Load Pin 3 NotConnected PE Protective earth Connection sensor / control input max.50ma / PNP Input 1 Pin VDC Pin 2 NotConnected Pin 3 ground Pin 4 Input 1 Input 2 terminal VDC terminal 24 Input 2 terminal 23 ground The +24VDC supply is isolated to 230VAC und +5VDC side of the CPU! Connection relay / transistoroutput Relay Pin 1 (Pin left/29) normally open/no Pin 2 (Pin middle/30) normally closed/nc Pin 3 (Pin right/31) change over/co Transistoroutput terminal 26 ground terminal 27 Output max. 50mA terminal VDC max. 50mA The +24VDC supply is isolated to 230VAC und +5VDC side of the CPU! 10

11 Programming DIP4 Dip 1,2 Nominal value setpoint 1 OFF OFF ON ON 2 OFF ON OFF ON. Internal External 420mA 010VDC Poti Poti Dip 3,4 Additional functions 3 OFF OFF ON ON 4 OFF ON OFF ON. Standard Blast air delay Hopper control 2 speeds Additional functions 11

12 Input 1 M12plug DIP8_4 GAN/GAB 1 Combination DIP8_6 / DIP8_7 Relay Terminal 29,30,31 Conveyor Input 2 Terminal 23,24,25 DIP8_5 GAN/GAB 2 Standard DIP4_3 = OFF DIP4_4 = OFF 24VDC Output Terminal 26,27,28 Input 1 M12plug Input 2 Terminal 23,24,25 DIP8_4 DIP8_5 GAN/GAB 1 Combination DIP8_6 / DIP8_7 Relay Terminal 29,30,31 Conveyor DIP8_8 Blast air delay DIP4_3 = OFF 24VDC Output Terminal 26,27,28 GAN/GAB 2 DIP4_4 = ON Input 1 M12plug Input 2 Terminal 23,24,25 DIP8_4 DIP8_5 GAN/GAB 1 GAN/GAB 2 Combination DIP8_6 / DIP8_7 Relay Terminal 29,30,31 Conveyor DIP8_8 OR Combination Hopper control DIP4_3 = ON DIP4_4 = OFF 24VDC Output Terminal 26,27,28 Input 1 M12plug DIP8_4 GAN/GAB 1 Relay Terminal 29,30,31 Conveyor Input 2 Terminal 23,24,25 DIP8_5 0 Nominal value setpoint via GAB 2 Speed conveyor 2 Speeds DIP4_3 = ON DIP4_4 = ON 1 Nominal value setpoint via setpointpotentiometer Programming DIP8 Dip 1 Frequency 50/25Hz OFF 50Hz ON 25Hz Dip 2 Setpoint fixed OFF Setpointpotentiometer active ON Setpointpotentiometer inactive Value fixed by switching Definition closer/opener can interpret also as invers/non invers Dip 3 Control OFF Output has reaction on control input and Closer/opener ON Output always ON, no reaction on control Input and closer/opener Dip 4 Input 1 12

13 OFF value opener ON value closer (input 1 inverted) Dip 5 Input 2 OFF value opener ON value closer (input 2 inverted) Dip 6,7 Combination form 6 OFF OFF ON ON 7 OFF ON OFF ON. OR AND HOLDUP Only E1 Dip 8 for hopper control and blast air delay OFF value opener ON value closer Combination form: OR Combination Signal 1 Signal 2 Output t AND Combination Signal 1 Signal 2 Output t Holdup Combination Signal 1 Signal 2 Output t 13

14 Values Umin Low limit of the output Umax High limit of the output SA SS Soft start Soft stop GAN 1 Turn ON delay input 1 GAB 1 Turn OFF delay input 1 GAN 2 Turn ON delay input 2 or Turn ON delay for blast air delay GAB 2 Turn OFF delay input 2 or Turn OFF delay for blast air delay or nominal value slow speed at 2 speeds Right rotary Min left limit stop Max right limit stop Setpoint for nominal value terminal 6 +5 VDC fur external potentiometer terminal 2 currentsetpoint 420mA terminal 5 voltagesetpoint 010 VDC or external potentiometer terminal 1 ground for currentsetpoint voltagesetpoint external potentiometer Jumper between AB > 010V DC or potentiometer between BC > 420mA DC Display LED SIGNAL LED lights if a potential over +6VDC is pending at input 1. LED Conveyor LED lights after delays and conveyor is running. 14

15 4.4 Starting 1. Before connecting the controller, check the working voltage and working frequency of the conveyor and compare them with the technical data for the controller. The output current of 6A should not be exceeded. 2. Depending on the working frequency of the conveyor, set the slide switch on the board: Fullwave operations 50/60 Hz Halfwave operations 25/30 Hz Check the programming on the board in dependence on the type of switching and set. Connect the conveyor to the controller. Insert the controller's plug into the mains. Switch the controller on. Set the required control range with the Umin and Umax potentiometers. 5. Operating tips Before switching on, check that the controller is correctly plugged into the conveyor. Switch the controller on with a mains switch. If required, adjust the setpoint until the vibration conveyor reaches the desired output. 6. Repairs Replacing fuse 15

16 1. Replace defective fuse with a 6,3 A F fuse. Fuse is available over fuseholder in the cover. 7. Troubleshooting Appliance not working Check the mains voltage, check the fuse and replace if necessary. Is the controller input set correctly, programming correct? No output from conveyor Check whether the correct oscillation frequency has been set, change setting where necessary. Check the mains frequency (50/60 Hz). The oscillation frequency and the mains voltage must agree. Umax trimmer set too low. Set Umax. Conveyor vibrates too much, magnet knocking (noises) Oscillation frequency setting incorrect. CAUTION! Magnet may have been destroyed by overheating or damaged mechanically by knocking. Umax trimmer set too high. Set Umax if necessary. Magnet heats up Magnet has incorrect mains voltage, check. Incorrect oscillation frequency set, change if necessary. Controller input not working Control voltage polarity reversal, check. Correct jumper for controller input? Check. 16

17 Declaration of conformity The company RUG Regler und Gerätebau GmbH KarlEhmannStr Göppingen hereby declares in its own responsibility that the product control appliance for oscillation conveyor systems with the type designation SMS 160/161 (incl. derivatives) to which this declaration refers conforms to the following standards Basic standards for transient emissions : DIN EN Teil 1 living quarters, business and trade area plus small companys Basic standards for interfernce resistancet : DIN EN Teil 2 Industrial in accordance to the appointments of the EC Directive 2004/108/EG. 17

Operating Instructions. for. Controller SMS 150 / 151

Operating Instructions. for. Controller SMS 150 / 151 Operating Instructions for Controller SMS 150 / 151 Contents Controller SMS 150 / 151... 1 Contents... 2 Reserve... 2 1. Safety instructions for users... 3 2. Application... 4 3. Warnings... 5 4. Installation...

More information

Frequency Controller SIGA (V6) Translation of operating and installation instructions

Frequency Controller SIGA (V6) Translation of operating and installation instructions Frequency Controller SIGA (V6) Translation of operating and installation instructions Copyright by Afag GmbH This operation instruction applies to: Typ Bestellnummer Frequency Controller SIGA (V6) 230

More information

Controllers for Vibratory Feeder Engineering REOVIB MTS 440/442. REO-USA, Inc. Thyristor controllers for vibratory feeders With digital settings

Controllers for Vibratory Feeder Engineering REOVIB MTS 440/442. REO-USA, Inc. Thyristor controllers for vibratory feeders With digital settings Operating Instructions REOVIB MTS 0/ Thyristor controllers for vibratory feeders With digital settings REO-USA, Inc 850 E 7th Street Indianapolis, IN 66 USA hone + (7) 899-95 ax + (7) 899-96 http://www.reo-usa.com

More information

FREQUENCY-CONVERTER MFR 600A / 1500A Version 2

FREQUENCY-CONVERTER MFR 600A / 1500A Version 2 Technical documentation for: FREQUENCY-CONVERTER MFR 600A / 1500A Version 2 Contents: 1. General description 2. Technical data 3. Function of the ramp generator 4. Electrical connection, examples for the

More information

Instruction Manual TABLE OF CONTENTS 1 PRINCIPLE OF OPERATION Limitations INSTALLATION Mains connection...

Instruction Manual TABLE OF CONTENTS 1 PRINCIPLE OF OPERATION Limitations INSTALLATION Mains connection... instrumentación para fluidos CI- pulse / ma Converter Instruction Manual TABLE OF CONTENTS PRINCIPLE OF OPERATION.... Limitations.... INSTALLATION.... Mains connection........ Input connection........

More information

Operating Manual * * Differential pressure transmitter. Table of Contents. 1 Safety guidelines. 1.1 General Information

Operating Manual * * Differential pressure transmitter. Table of Contents. 1 Safety guidelines. 1.1 General Information *09005137* BA_EN_DE50 Rev.A 11/12 *09005137* d e v e l o p i n g s o l u t i o n s DE50 Operating Manual Differential pressure transmitter Table of Contents 1 Safety guidelines 2 Application purpose 3

More information

Installation, Operation and Maintenance Instructions

Installation, Operation and Maintenance Instructions VM-7D Installation, Operation and Maintenance Instructions Unicon Controller -5 AmP Model NEMA 2 AND CHASSIS MOUNT 5 or 230 VOLT AC ERIEZ MAGNETICS HEADQUARTERS: 2200 ASBURY ROAD, ERIE, PA 6506 402 U.S.A.

More information

Installation, Operation and Maintenance Instructions

Installation, Operation and Maintenance Instructions VM-10A Installation, Operation and Maintenance Instructions N12- G & HW SERIES FREQUENCY CONTROLLERS 115/230VAC FOR 30, 40, 50 & 60HZ ELECTROMAGNETIC FEEDERS ERIEZ HEADQUARTERS: 2200 ASBURY ROAD, ERIE,

More information

Orbital GFI Inverter Series

Orbital GFI Inverter Series Orbital GFI Inverter Series Datasheet Key Features One, split or three phases and up to 25 kva Superior efficiency of 95% CAN Bus control and DAQ Power quality and EMC compliance in accordance with European

More information

Power supply CP-E 24/2.5

Power supply CP-E 24/2.5 2CDC 271 015 F0t06 a OUTPUT L+, L : terminals output b DC OK: terminal signalling output c INPUT L, N, PE: terminals input d OUTPUT OK: green LED output voltage OK e OUTPUT Adjust: potentiometer adjustment

More information

TVA 080 / 100 / 120 / 180 / 200 / 220 Isolation amplifier active

TVA 080 / 100 / 120 / 180 / 200 / 220 Isolation amplifier active Technical manual BA 0318 Signal converter Isolation amplifier active for galvanic isolation, conversion and adjustment of electrical standard signals Evaluable input signals Direct voltage 0...10V / 0...1V

More information

Power supply CP-E 24/0.75

Power supply CP-E 24/0.75 2CDC 271 016 F0t06 a OUTPUT L+, L : terminals output b INPUT L, N, PE: terminals input c LOW: red LED output voltage too low d OK: green LED output voltage OK e OUTPUT Adjust: rotary potentiometer output

More information

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W ADC5000 SERIES AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications 60W, 125W and 250 W Input voltage 230/115 VAC voltages 12, 24, 36 or 48 VDC Statistical MTBF >3 000

More information

SIMEAS-T. Operating Instructions Transducer without auxiliary power. 7KG6111 and 7KG6101. Operating Instructions

SIMEAS-T. Operating Instructions Transducer without auxiliary power. 7KG6111 and 7KG6101. Operating Instructions Operating Instructions SIMEAS-T s Operating Instructions Transducer without auxiliary power for alternating current for alternating voltage for alternating voltage with expanded end range 7KG6111 and 7KG6101

More information

TE200S Solid State Relays. Two-phase control of three-phase loads. User manual

TE200S Solid State Relays. Two-phase control of three-phase loads. User manual TE200S Solid State Relays Two-phase control of three-phase loads User manual Copyright Eurotherm Automation 1998 All rights reserved. All reproduction or transmission in any form or using any procedure

More information

FREQUENCY-CONVERTER MFR 600A

FREQUENCY-CONVERTER MFR 600A Technical documentation for: FREQUENCY-CVERTER MFR 600A Contents: 1. General description 2. Technical data 3. Function of the ramp generator 4. Electrical connection, examples for the control 5. Start

More information

Documentation. Content. Measurement and Control. Type: ELT-GP1. 1. Installation instructions 2. Data sheets 3. Declarations of conformity

Documentation. Content. Measurement and Control. Type: ELT-GP1. 1. Installation instructions 2. Data sheets 3. Declarations of conformity Documentation Measurement and Control Type: ELT-GP1 Content 1. Installation instructions 2. Data sheets 3. Declarations of conformity (Part No. 008Q520) eltherm GmbH Ernst-Heinkel-Str. 6-10 57299 Burbach

More information

Power supply CP-E 24/2.5

Power supply CP-E 24/2.5 2CDC 271 015 F0t06 a OUTPUT L+, L : terminals output b DC OK: terminal signalling output c INPUT L, N, PE: terminals input d OUTPUT OK: green LED output voltage OK e OUTPUT Adjust: potentiometer adjustment

More information

Installation and Operating Instructions for Phase Demodulator Type _.2

Installation and Operating Instructions for Phase Demodulator Type _.2 Guidelines on the Declaration of Conformity A conformity evaluation has been carried out for the product in terms of the EU Low Voltage Directive 2014/35/EU and the Electromagnetic Compatibility (EMC)

More information

Operating instructions Fail-safe delay timer AZS About this document. Content

Operating instructions Fail-safe delay timer AZS About this document. Content 8 Appendix 8.1 Wiring example...4 8.2 Integral System Diagnostics (ISD)....5 9 EU Declaration of conformity Operating instructions.............pages 1 to 6 Original x.000 / 11.2017 / v.a. - 101126753-

More information

Power supply CP-E 24/20.0

Power supply CP-E 24/20.0 2CDC 271 027 F0008 a OUTPUT L+, L+, L, L-: terminals output b INPUT L, N, PE: terminals input c 13-14: terminals - signalling contact d OUTPUT OK: green LED output voltage OK e OUTPUT LOW: red LED output

More information

Power supply CP-D 24/1.3

Power supply CP-D 24/1.3 2CDC 271 027 F0t07 a OUTPUT ++/ : terminals output Features Rated output voltage 24 V DC Output voltage adjustable via front face potentiometer OUTPUT Adjust Rated output current 1.3 A Rated output power

More information

Power supply CP-E 48/5.0 Primary switch mode power supply Data sheet

Power supply CP-E 48/5.0 Primary switch mode power supply Data sheet 2CDC 271 028 F0008 OUTPUT L+, L+, L-, L-: terminals - output Features Rated output voltage 48 V DC Output voltage adjustable via front-face rotary potentiometer OUTPUT Adjust Rated output current 5 A Rated

More information

Impulse system MPT 700. Manual Edition GB

Impulse system MPT 700. Manual Edition GB Impulse system MPT 700 Manual 6.2.2.2 Edition 10.10 GB 1 Introduction... 4 1.1 Version and model... 5 1.2 CE Mark... 7 2 Operation... 8 2.1 Controls... 8 2.1.1 Front panel... 8 2.1.2 Parameter display...

More information

Power supply CP-D 12/2.1

Power supply CP-D 12/2.1 2CDC 271 025 F0t07 a OUTPUT ++/ : terminals output Features Rated output voltage 12 V DC Output voltage adjustable via front face potentiometer OUTPUT Adjust Rated output current 2.1 A Rated output power

More information

Cable Identifying Generator LCI TX / LCI TX-440

Cable Identifying Generator LCI TX / LCI TX-440 Operation manual Cable Identifying Generator LCI TX / LCI TX-440 Mess- und Ortungstechnik Measuring and Locating Technologies Elektrizitätsnetze Power Networks Kommunikationsnetze Communication Networks

More information

PHOENIX CONTACT - 06/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

PHOENIX CONTACT - 06/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area. Primary-switched power supply with SFB technology, 1 AC, output current 20 A INTERFACE Data Sheet 103383_en_00 1 Description PHOENIX CONTACT - 06/2008 Features QUINT POWER power supply units highest system

More information

Power supply CP-E 12/10.0 Primary switch mode power supply Data sheet

Power supply CP-E 12/10.0 Primary switch mode power supply Data sheet 2CDC 271 024 F0008 OUTPUT L+, L+, L-, L-: terminals - output INPUT L, N, PE: terminals - input OUTPUT OK: green LED - output voltage OK OUTPUT LOW: red LED - output voltage too low OUTPUT Adjust: potentiometer

More information

Power supply CP-T 48/5.0 Primary switch mode power supply

Power supply CP-T 48/5.0 Primary switch mode power supply Data sheet Power supply CP-T 48/5.0 Primary switch mode power supply The CP-T range of three-phase power supply units is the youngest member of ABB s power supply family. In terms of design and functionality,

More information

Precipitation Monitor ,

Precipitation Monitor , THE WORLD OF WEATHER DATA - THE WORLD OF WEATHER DATA - THE WORLD OF WEATHER DATA Instruction for use 021197/11/09 Precipitation Monitor 5.4103.10.000, 5.4103.10.700 ADOLF THIES GmbH & Co. KG Hauptstraße

More information

Section 1, General information Introduction... 3 Description... 3 Specifications... 4 Wiring connections... 5

Section 1, General information Introduction... 3 Description... 3 Specifications... 4 Wiring connections... 5 LIST OF CONTENTS Section 1, General information Introduction... 3 Description... 3 Specifications... 4 Wiring connections... 5 Section 2, Calibration Calculations... 7 Calibration Procedure... 8 Section

More information

Instruction manual for STA 1 sectional door operator

Instruction manual for STA 1 sectional door operator Instruction manual for STA 1 sectional door operator Sectional door operator STA 1 / Rev. 0.3 1 GB 1. Contents 3. General safety instructions 1. Contents 2 2. Key to symbols 2 3. General safety instructions

More information

Power supply CP-T 24/10.0 Primary switch mode power supply

Power supply CP-T 24/10.0 Primary switch mode power supply Data sheet Power supply CP-T 24/10.0 Primary switch mode power supply The CP-T range of three-phase power supply units is the youngest member of ABB s power supply family. In terms of design and functionality,

More information

Switched mode power supply for DIN rail mounting type SMP21 DC24V/10A

Switched mode power supply for DIN rail mounting type SMP21 DC24V/10A Switched mode power supply for DIN rail mounting type SMP2 DC24V/0A Description Switched mode power supply for rail mounting, with independent change-over of input voltages (AC 5/20 V), integral passive

More information

Power supply CP-T 24/40.0 Primary switch mode power supply

Power supply CP-T 24/40.0 Primary switch mode power supply Data sheet Power supply CP-T 24/40.0 Primary switch mode power supply The CP-T range of three-phase power supply units is the youngest member of ABB s power supply family. In terms of design and functionality,

More information

MCR-SL-CUC Universal current transducer. Data sheet _en_05. 1 Description

MCR-SL-CUC Universal current transducer. Data sheet _en_05. 1 Description Universal current transducer Data sheet 104059_en_05 PHOENIX CONTACT 2011-03-09 1 Description MCR-SL-CUC-...-I and MCR-SL-CUC-...-U active current transducers convert DC, AC, and distorted currents into

More information

Parallel. Parallel. data transmission. Technical Information TR - ECE - TI - GB /05/2016

Parallel. Parallel. data transmission. Technical Information TR - ECE - TI - GB /05/2016 TR - ECE - TI - GB - 0054-01 04/05/2016 Parallel Parallel data transmission Technical Information TR-Electronic GmbH D-78647 Trossingen Eglishalde 6 Tel.: (0049) 07425/228-0 Fax: (0049) 07425/228-33 email:

More information

DT1100 xx xx xx PS. Isolators, Isolator / Power Supplies. Operating Instructions

DT1100 xx xx xx PS. Isolators, Isolator / Power Supplies. Operating Instructions Isolators, Isolator / Power Supplies Operating Instructions EN Contents 1. About this document...4 1.1. Function... 4 1.2. Target group... 4 1.3. Symbolism used... 4 2. For your safety...5 2.1. Authorized

More information

QUINT-PS AC/24DC/40

QUINT-PS AC/24DC/40 Power supply unit INTERFACE Data sheet 102315_en_02 1 Description PHOENIX CONTACT 2010-04-23 Features QUINT POWER power supply units for plant and special engineering reliably start heavy loads with high

More information

Power supply CP-T 48/20.0 Primary switch mode power supply

Power supply CP-T 48/20.0 Primary switch mode power supply Data sheet Power supply CP-T 48/20.0 Primary switch mode power supply The CP-T range of three-phase power supply units is the youngest member of ABB s power supply family. In terms of design and functionality,

More information

Process/Mini. English IMPORTANT NOTE. Installation and Operation Manual. General Purpose Light Curtain with 30 mm resolution

Process/Mini. English IMPORTANT NOTE. Installation and Operation Manual. General Purpose Light Curtain with 30 mm resolution Installation and Operation Manual Process/Mini General Purpose Light Curtain with 30 mm resolution English manufactured under ISO 9001: 2000 IMPORTANT NOTE FOLLOW THE INSTRUCTIONS GIVEN IN THIS MANUAL

More information

SCA-SS (70V, 10A)

SCA-SS (70V, 10A) Manual SCA-SS-70-10 V 2.3 01/04 page 1 SCA-SS-70-10 (70V, 10A) The servo-amplifier SCA-SS-70-10 is a powerful PWM-module for brushed DC motors with an output range up to 700 Watt. Six operation modes are

More information

QUINT-PS/ 3AC/24DC/10

QUINT-PS/ 3AC/24DC/10 Primary-switched power supply with SFB technology, 3 AC, output current 10 A INTERFACE Data sheet 103131_en_01 1 Description PHOENIX CONTACT - 09/2009 Features QUINT POWER power supply units Maximum system

More information

DT1100 E xx xx (PS) Galvanic Isolators. Operating Instructions

DT1100 E xx xx (PS) Galvanic Isolators. Operating Instructions DT1100 E xx xx (PS) Galvanic Isolators Operating Instructions Contents 1. About this document...4 1.1. Function... 4 1.2. Target group... 4 1.3. Symbolism used... 4 2. For your safety...5 2.1. Authorized

More information

MINI-PS AC/24DC/1.3

MINI-PS AC/24DC/1.3 Power supply unit INTERFACE Data sheet 102894_en_03 1 Description PHOENIX CONTACT 2015-11-17 Features MINI POWER power supplies for MCR technology In measurement and control technology (MCR), modular electronics

More information

Power supply CP-T 24/20.0 Primary switch mode power supply

Power supply CP-T 24/20.0 Primary switch mode power supply Data sheet Power supply CP-T 24/20.0 Primary switch mode power supply The CP-T range of three-phase power supply units is the youngest member of ABB s power supply family. In terms of design and functionality,

More information

English. Operating manual. Temperature measuring transducer MU125. Save for later reference. Company / brands of GHM

English. Operating manual. Temperature measuring transducer MU125.  Save for later reference. Company / brands of GHM English Operating manual Temperature measuring transducer MU125 Company / brands of GHM www.ghm-messtechnik.de Save for later reference. Table of contents Page 1. Intended use (areas of application)...

More information

User s Manual Current Probe. IM E 2nd Edition IM E

User s Manual Current Probe. IM E 2nd Edition IM E User s Manual 700937 Current Probe 2nd Edition Introduction Thank you for purchasing the 700937 Current Probe. This Instruction Manual contains useful information about the instrument s functions and operating

More information

DB 12 B. Double Sheet Testing Unit. Phone: Fax: Web: -

DB 12 B. Double Sheet Testing Unit. Phone: Fax: Web:  - DB 12 B Double Sheet Testing Unit GB 03-08/08 50104956 Table of contents 1 General information... 2 1.1 Explanation of symbols... 2 1.2 Declaration of conformity... 2 2 Safety notices... 3 2.1 Safety standards...

More information

PROXIMITY SENSOR TERMINOLOGY

PROXIMITY SENSOR TERMINOLOGY Never use this desk reference for installation or operation of equipment. Refer to manual for installation and operation instructions. The following descriptions refer to the European standard EN 60947-5-2.

More information

DB 112 B. Double Sheet Testing Unit TECHNICAL DESCRIPTION. en / We reserve the right to. make technical changes

DB 112 B. Double Sheet Testing Unit TECHNICAL DESCRIPTION. en / We reserve the right to. make technical changes en 03-2014/06 50126540 We reserve the right to make technical changes DB 112 B Double Sheet Testing Unit TECHNICAL DESCRIPTION 2014 Leuze electronic GmbH + Co. KG In der Braike 1 D-73277 Owen / Germany

More information

Operating Instructions

Operating Instructions Level and Pressure Operating Instructions VEGATOR 620, 621, 622 max. 0 10 min. 0 10 on VEGATOR 622! 6 7 8 9 10 11 12 13 14 in out Contents Contents Safety information... 2 Note Ex area... 2 1 Product description

More information

Electronic Air / Fuel Ratio Control System

Electronic Air / Fuel Ratio Control System 7 871 ISO 9001 Electronic Air / Fuel Ratio Control System RVW20... Electronic control unit - for use with modulating single- and dual-fuel burners - with extended functionality for mechanical air / fuel

More information

Precipition Sensor with analogue Intensity Output ,

Precipition Sensor with analogue Intensity Output , THE WORLD OF WEATHER DATA - THE WORLD OF WEATHER DATA - THE WORLD OF WEATHER DATA Instruction for use 021335/11/09 Precipition Sensor with analogue Intensity Output 5.4103.20.041, 5.4103.20.741 ADOLF THIES

More information

Manual SCA-SS V /02 page 1

Manual SCA-SS V /02 page 1 Manual SCA-SS-30-06 V 0.9 09/02 page 1 SCA-SS-30-06 (30V, 6A) The servo amplifier SCA-SS-30-06 is a powerful servo amplifier for brushed DC motors with an output range up to 150 Watt. These operation modes

More information

Installation and Operational Instructions for ROBA -multiswitch Type 019._00.2

Installation and Operational Instructions for ROBA -multiswitch Type 019._00.2 Guidelines on the Declaration of Conformity A conformity evaluation has been carried out for the product in terms of the EU Low Voltage Directive 2014/35/ EU and the Electromagnetic Compatibility (EMC)

More information

PHOENIX CONTACT - 05/2008. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area.

PHOENIX CONTACT - 05/2008. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area. Primary-switched power supply with SFB technology, 1 AC, output current 20 A INTERFACE Data Sheet 103129_en_01 PHOENIX CONTACT - 05/2008 1 Description QUINT POWER power supply units highest system availability

More information

Amplifier Series BASIC. Installation & Operations Manual

Amplifier Series BASIC. Installation & Operations Manual Amplifier Series BASIC Installation & Operations Manual Bittner-Audio 200 Power Amplifier Series BASIC Bittner - Audio September 200 200 Bittner-Audio. All Rights Reserved. Bittner-Audio reserves specification

More information

S1 Programming Chart Program Description S1 Switch Positions. Constant ON High/Low Track, WR

S1 Programming Chart Program Description S1 Switch Positions. Constant ON High/Low Track, WR RODIX INC. FEEDER CUBE FC90 Plus Series ADVANCED FEATURES Optional software features of the 24490 / 2449 circuit boards OVERVIEW: The FC90 Plus Series of feeder controls are built around the circuit boards

More information

DUAL OUTPUT AC CURRENT/VOLTAGE TRANSDUCER

DUAL OUTPUT AC CURRENT/VOLTAGE TRANSDUCER OPERATOR S MANUAL DUAL OUTPUT AC CURRENT/VOLTAGE TRANSDUCER Masibus Automation & Instrumentation Pvt. Ltd. B/30, GIDC Electronics Estate, Sector-25, Gandhinagar-382044, Gujarat, India Web Site: www..com

More information

QUINT-PS/ 1AC/24DC/20

QUINT-PS/ 1AC/24DC/20 Primary-switched power supply with SFB technology, 1 AC, output current 20 A INTERFACE Data sheet 103129_en_04 1 Description PHOENIX CONTACT - 02/2010 Features QUINT POWER power supply units Maximum system

More information

Service Instructions. The Conductor Controls. Conductor DC15-A, Enclosed Unit CH15-A, Open Chasis Unit

Service Instructions. The Conductor Controls. Conductor DC15-A, Enclosed Unit CH15-A, Open Chasis Unit Service Instructions The Conductor Controls Conductor DC15-A, Enclosed Unit CH15-A, Open Chasis Unit Table of Contents General Section Page Safety Instructions.. 4 Introduction 5 Inspection and Long-Term

More information

Installation and Operating Manual

Installation and Operating Manual GB Analog Weight Transmitter PS-1000 Installation and Operating Manual LIST OF CONTENTS Section 1, General information Introduction... 3 Description... 3 Specifications... 4 Wiring connections... 5 Section

More information

MATRIX INDUCTIVE LOOP CONTROL BOX

MATRIX INDUCTIVE LOOP CONTROL BOX EN MATRIX INDUCTIVE LOOP CTROL BOX MATRIX-S2-24: single loop with 2 to 24 V AC/DC power supply MATRIX-D2-24: double loop with 2 to 24 V AC/DC power supply MATRIX-S220: single loop with 220 to 240 V AC

More information

PRetrans Table of contents

PRetrans Table of contents HART TRANSPARENT REPEATER PRetrans 5106 Table of contents Warnings 16 Safety instructions 17 EC Declaration of Conformity 19 How to demount SYSTEM 5000 20 Application 21 Technical characteristics 21 Mounting

More information

Instruction manual for STA 1 sectional door operator

Instruction manual for STA 1 sectional door operator Instruction manual for STA 1 sectional door operator GB Sectional door operator STA 1 / Rev. 0.0 1 1. Contents 3. General safety instructions 1. Contents 2 2. Key to symbols 2 3. General safety instructions

More information

3B SCIENTIFIC PHYSICS

3B SCIENTIFIC PHYSICS 3B SCIENTIFIC PHYSICS Digital Multimeter E 1018832 Instruction sheet 12/16 SD/UD 1 probe 1a Finger guards 2 Measurement socket 10 A for current measurement in 10-A (positive) 3 Measurement socket COM (negative)

More information

Gate control mts2000/02 R2.8

Gate control mts2000/02 R2.8 Control system Gate control mts2000/02 R2.8 I Table of contents 1 Conformities 1.1 Guidelines and standards 1-1 1.2 CE mark 1-1 2 General safety information 2.1 Explanation of symbols used to provide safety

More information

INSTRUCTION MANUAL (ATEX / IECEx)

INSTRUCTION MANUAL (ATEX / IECEx) INSTRUCTION MANUAL (ATEX / IECEx) STExS1 & STExS2 Sounder For use in Flammable Gas and Dust Atmospheres 1) Warnings DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS PRESENT POTENTIAL ELECTROSTATIC CHARGING

More information

Power supply CP-D 24/4.2 Primary switch mode power supply

Power supply CP-D 24/4.2 Primary switch mode power supply Data sheet Power supply CP-D 24/4.2 Primary switch mode power supply The CP-D range of modular power supply units in MDRC design (modular DIN rail components) is ideally suited for installation in distribution

More information

DeltaSol AX HE * * Differential temperature controller Manual for the specialised craftsman

DeltaSol AX HE * * Differential temperature controller Manual for the specialised craftsman DeltaSol X HE Differtial temperature controller Manual for the specialised craftsman Installation Operation Functions and options Troubleshooting *110633* 110633 Thank you for buying this RESOL product.

More information

D.C. BRUSHLESS MOTORS DRIVE. BLD07-IT Service Manual

D.C. BRUSHLESS MOTORS DRIVE. BLD07-IT Service Manual D.C. BRUSHLESS MOTORS DRIVE BLD07-IT Service Manual INTECNO s.r.l. Via Caduti di Sabbiuno n. 9/E 40011 Anzola Emilia (BO) - Italy tel. 051.19985350 fax 051.19985360 www.intecno-srl.com INDEX Description

More information

Operating Instruction

Operating Instruction Level and Pressure Operating Instruction VEGASEL 643 6 5 + + 3 5 + + max. min. on VEGASEL 643 5 6 7 8 9 10 11 12 13 14 in out Contents Contents Safety information... 2 1 Product description 1.1 Function

More information

TC1028 series. Thyristor units. Control of single-phase resistive or inductive loads. User manual (300A to 500A rated units)

TC1028 series. Thyristor units. Control of single-phase resistive or inductive loads. User manual (300A to 500A rated units) TC1028 series Thyristor units Control of single-phase resistive or inductive loads User manual (300A to 500A rated units) Copyright Eurotherm Automation 1998 All rights reserved. All reproduction or transmission

More information

R180. AVRs. Installation and maintenance

R180. AVRs. Installation and maintenance This manual concerns the alternator AVR which you have just purchased. We wish to draw your attention to the contents of this maintenance manual. SAFETY MEASURES Before using your machine for the first

More information

Inductive sensor slot-type SI2-K08-AP7

Inductive sensor slot-type SI2-K08-AP7 SI2-K08-AP7 Slot sensor, height 8 mm Plastic, polypropylene Mechanical end stop, removable, for analog pointer instruments 3-wire DC, 10 30 VDC NO contact, PNP output Cable connection Wiring diagram Type

More information

PU202 Level converter & encoder signal generator without potential separation

PU202 Level converter & encoder signal generator without potential separation Operating Manual PU202 Level converter & encoder signal generator without potential separation Product features: Converts HTL signals from 10 up to 30 V (A / B / Z) into the corresponding TTL / RS422 format

More information

ERV-M ELECTRONIC FAN SPEED CONTROLLER. Mounting and operating instructions

ERV-M ELECTRONIC FAN SPEED CONTROLLER. Mounting and operating instructions ELECTRONIC FAN SPEED CONTROLLER Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 5

More information

Linear feeder HLF07-P / 12-P Translation of operating and installation instructions

Linear feeder HLF07-P / 12-P Translation of operating and installation instructions Linear feeder HLF07-P / 12-P Translation of operating and installation instructions Copyright by Afag GmbH This operation instruction applies to: Type Order number Linear feeder HLF07-P 230 V / 50 Hz 50162932

More information

3B SCIENTIFIC PHYSICS

3B SCIENTIFIC PHYSICS 3B SCIENTIFIC PHYSICS Analogue Multimeter Escola 100 1013527 Instruction sheet 12/15 SD/JS 1 Display with mirror scale 2 Slotted screw for zero calibration 3 Calibration trimmer for setting centre zero

More information

Flow Detection MDS Integral or Remote Housing. Installation and Operating Instructions

Flow Detection MDS Integral or Remote Housing. Installation and Operating Instructions Flow Detection MDS Integral or Remote Housing Solids - Chute and Conveyor 10.525 GHz Sender Receiver Installation and Operating Instructions Measurement Systems INTRODUCTION CONTENTS PROPRIETARY NOTICE

More information

Ametek, Inc. Rotron Technical Products Division. 100 East Erie St., Suite 200 Kent, Ohio User's Guide. Number Revision F

Ametek, Inc. Rotron Technical Products Division. 100 East Erie St., Suite 200 Kent, Ohio User's Guide. Number Revision F Ametek, Inc. Rotron Technical Products Division 100 East Erie St., Suite 200 Kent, Ohio 44240 User's 120 Volt, 800 Watt and 240 Volt, 1200 Watt Brushless Motor Drive Electronics 5.7" (145 mm) and 7.2"

More information

Proximity Sensor Terminology

Proximity Sensor Terminology The following descriptions refer to the European standard EN 60947-5-2. of 2007. The specifications given here are intended to be minimum performance values described by the standard. Alignment must not

More information

MINI MCR-SL-UI-f(-SP)

MINI MCR-SL-UI-f(-SP) Configurable Analog Frequency Transducer INTERFACE Data Sheet PHOENIX CONTACT - 02/2006 Description The configurable analog frequency transducer MINI MCR-SL-UI-f(-SP) is used to convert analog standard

More information

WEL-200 O P E R A T I N G I N S T R U C T I O N S W I R E L E S S E D G E L I N K

WEL-200 O P E R A T I N G I N S T R U C T I O N S W I R E L E S S E D G E L I N K O P E R A T I N G I N S T R U C T I O N S WEL-200 TM W I R E L E S S E D G E L I N K 4564 Johnston Parkway, Cleveland, Ohio 44128 P. 800 426 9912 F. 216 518 9884 Sales Inquiries: salessupport@emxinc.com

More information

Installation and Operational Instructions for ROBA -switch Type 017._00.2

Installation and Operational Instructions for ROBA -switch Type 017._00.2 OBA -switch Type 017._00.2 Guidelines on the Declaration of Conformity A conformity evaluation has been carried out for the product in terms of the EC Low Voltage Directive 2014/35/ EC and the EMC Directive

More information

Analog amplifier RA. RE Edition: Replaces:

Analog amplifier RA. RE Edition: Replaces: Analog amplifier RA RE 950 Edition: 08.05 Replaces: 0.006 For control of simple functions of electrohydraulic components Two power outputs (PWM) and one switching output Each output has a separately adjustable

More information

QUINT-PS/ 3AC/24DC/40

QUINT-PS/ 3AC/24DC/40 Primary-switched power supply unit with SFB technology, 3 AC, output current 40 A INTERFACE Data sheet 103133_en_00 1 Description PHOENIX CONTACT - 07/2009 Features QUINT POWER power supply units Maximum

More information

EY-EM 527: Remote I/O module, ecolink527

EY-EM 527: Remote I/O module, ecolink527 Product data sheet 94.078 EY-EM 527: Remote I/O module, ecolink527 How energy efficiency is improved Regulation, control, monitoring and optimisation of operational systems, e.g. room automation or HVAC

More information

User s Manual Current Probe. IM E 2nd Edition. Yokogawa Electric Corporation

User s Manual Current Probe. IM E 2nd Edition. Yokogawa Electric Corporation User s Manual 701930 Current Probe Yokogawa Electric Corporation 2nd Edition Foreword Revisions Thank you for purchasing the Current Probe (Model 701930). This instruction manual contains useful information

More information

User s Manual Current Probe. IM E 1st Edition. Yokogawa Electric Corporation

User s Manual Current Probe. IM E 1st Edition. Yokogawa Electric Corporation User s Manual 701932 Current Probe Yokogawa Electric Corporation 1st Edition Foreword Revisions Thank you for purchasing the 701932 Current Probe. This user's manual contains useful information about the

More information

Switched mode power supply for DIN rail mounting type SMP23 DC24V/40A

Switched mode power supply for DIN rail mounting type SMP23 DC24V/40A Switched mode power supply for DIN rail mounting type SMP DC4V/40A Description Switched mode power supply (SMP) for rail mounting, three-phase supply voltage, high efficiency, integral input filter and

More information

QUINT-PS-24DC/24DC/10

QUINT-PS-24DC/24DC/10 QUINT-PS-24/24/10 QUINT - converter, primary switched mode, input: 24 V, output: 24 V /10 A INTERFACE Data Sheet PHOENIX CONTACT - 02/2006 Description The QUINT - converter 24 V/10 A converts the voltage

More information

Copyright 2016 by Brüel & Kjær Vibro GmbH, D Darmstadt

Copyright 2016 by Brüel & Kjær Vibro GmbH, D Darmstadt All rights reserved No part of this technical documentation may be reproduced without prior written permission of Brüel & Kjær Vibro GmbH. Subject to change without prior notice. Copyright 06 by Brüel

More information

GESTRA Steam Systems LRS English. Installation & Operating Instructions Conductivity Switch LRS 1-50

GESTRA Steam Systems LRS English. Installation & Operating Instructions Conductivity Switch LRS 1-50 GESTRA Steam Systems LRS 1-50 EN English Installation & Operating Instructions 819223-02 Conductivity Switch LRS 1-50 Contents Important notes Page Usage for the intended purpose...4 Function...4 Safety

More information

Universal Controller

Universal Controller 7 863 Universal Controller POLYGYR RWF32... ISO 9001 RWF32... with casing ARG61.01 The RWF32... is a universal digital boiler temperature / pressure controller designed for use in oil- and / or gas-fired

More information

MINI-PS AC/2X15DC/1

MINI-PS AC/2X15DC/1 MII-PS-100-240AC/2X15DC/1 Power supply unit ITERFACE Data sheet 100299_en_04 1 Description PHOEIX COTACT - 2010-10-20 Features MII POWER is the extremely slim power supply unit with constructional widths

More information

Reactive Power Control Relay RM 2106 / 2112 Operating Instructions. FRAKO Kondensatoren- und Anlagenbau

Reactive Power Control Relay RM 2106 / 2112 Operating Instructions. FRAKO Kondensatoren- und Anlagenbau Reactive Power Control Relay RM 2106 / 2112 Operating Instructions FRAKO Kondensatoren- und Anlagenbau www.frako.com Figure 1 Front view a b c d e Display for active capacitor stages Display for inductive

More information

Technical Documentation

Technical Documentation Technical Documentation PROAM-21 Power amplifier for directional valves Grundlage der Funktionsbeschreibung und zur Prüfung der Module (keine Produktdokumentation). AMCA HYDRAULIC FLUID POWER B.V. P.O.BOX

More information

PD30CNB25xxPS. Photoelectrics, Background suppression reflective - PointSpot. Main features. Main functions. Description

PD30CNB25xxPS. Photoelectrics, Background suppression reflective - PointSpot. Main features. Main functions. Description Photoelectrics, Background suppression reflective - PointSpot Main features Miniature sensor range The visible red PointSpot light makes alignment very easy Range: 250 mm Sensitivity adjustment by potentiometer

More information