Gate control mts2000/02 R2.8

Size: px
Start display at page:

Download "Gate control mts2000/02 R2.8"

Transcription

1 Control system Gate control mts2000/02 R2.8

2 I Table of contents 1 Conformities 1.1 Guidelines and standards CE mark General safety information 2.1 Explanation of symbols used to provide safety information Information regarding the safety information Permissible users Correct handling Basic information 3.1 Warranty and liability Purchaser obligation User obligation Correct use Improper use Instructions concerning EMC protection Description of product 4.1 Safety concept Safety equipment independent of the processor Monitored safety equipment Scope Overview of operating modes Interfaces for input elements Interfaces for output elements Structure Operating modes Impulse control as sequence control Impulse control, defined up down Single/dual lane feedback control with light control and automatic closing Special operating modes Manual mode Emergency control Functions Continuously open switch ("gatekeeper s switch") / external clock Weekly indexing clock Halt key The safety equipment Closing edge protection Stop in open + closed position (protection against anything being snagged and pulled in) Stop in closed position (passage protection) Process of re-opening after triggering during closing 4-10 meißner gate systems Gate control operating manual mts2000/02

3 Table of contents I Hold open time Extending the hold open time Shortening the hold open time Run time monitoring Technical data Electrical data Mains connection Stop switch Impulse sensor connections Interfaces for safety equipment Connection for potential-free contact Connection for lights Connection for drive Device protection Mechanical data Ambient conditions Assembly and installation 5.1 Safety information regarding assembly Fitting gate control mts2000/ Electrical connection Start-up and operation 6.1 Programming gate control mts2000/ Controls of gate control mts2000/ Hardware settings Function of keys Menu structure of operating software Language setting Program gate Service Operation Assembly instructions for weekly time switching clock mts2000/02 (not in standard version) Assembly Programming Operating instructions for radio mts2000/02 (not in standard version) Assembly Setting instructions Coding table Displays Maintenance & service 7.1 Troubleshooting tool Troubleshooting 7-1 Gate control operating manual mts2000/02 meißner gate systems

4 I Table of contents Testing Fault rectification Control PCB measurement points Regular testing Address of manufacturer 7-6 meißner gate systems Gate control operating manual mts2000/02

5

6 1 Conformities 1.1 Guidelines and standards Device name: Gate control mts2000/02 Guidelines and standards: EMC 89/336/EEC: European guideline regulation on the electromagnetic compatibility (EMC) of electrical equipment VDE 0100: Guidelines for setting up high power systems of up to 1000V VDE 0105: Operating high power systems EN 60204: Electrical systems with electronics operating equipment VDE 0160: Equipping high power systems and electric operating equipment VDE 0700: Safety of electrical devices for domestic consumption etc. BGVA2: Electrical systems and operating equipment BGR 232: Guidelines for power-assisted windows, doors and gates Note The gate control system has been produced and inspected (TÜV Bau und Betriebstechnik GmbH, corporate group for southern Germany in Filderstadt) in accordance with the standards and guidelines listed and was in perfect condition in terms of technical safety when leaving the factory. 1.2 CE mark Gate control mts2000/02 corresponds to the fundamental requirements of the relevant directive (EMC 89/336/EEC, dated 3 May 1989) of the Council of the European Union. Conformity has been proven and he corresponding documents (declaration) are archived by the manufacturer. meißner gate systems 1-1 Gate control operating manual mts2000/02

7 General safety information Explanation of symbols used to provide safety information The following symbols are used in these instructions for use to provide the user with safety information: This symbol identifies a direct threat of danger to the health or even life of people. Failure to follow these instructions can endanger life and limb, resulting in anything from serious damage to health to life-threatening injuries. This symbol identifies a risk of injury to the device user. This symbol identifies important instructions on correct use of the device. Failure to follow these instructions can result in malfunctions on the device. Note This symbol identifies tips for application and particularly useful information which will help you to make the most of all the device s functions. Liability exclusion: This symbol indicates that operator error or failure on the part of the operator to follow certain instructions can give rise to the manufacturer s liability cover being rendered null and void. Instructions for disposal: Ship used devices to an authorised recycling plant (separated into metals, plastics etc.) Information regarding the safety information The safety instructions in these instructions for use MUST be noted and followed. Gate control operating manual mts2000/ meißner gate systems

8 2 General safety information 2.2 Permissible users Only trained electricians may work on the electrical systems. They must assess the work assigned to them, recognise any sources of possible risk and be able to take appropriate safety measures. 2.3 Correct handling In order to keep the device in perfect condition from a technical safety standpoint and to be able to assure safe operation, the user undertakes to comply with the points listed in this operating manual. Operation of the control unit is only permitted while its covers and guards are all in position. Ensure that all gaskets and screw connections are properly secured. meißner gate systems 2-2 Gate control operating manual mts2000/02

9 Basic information Warranty and liability To be assured of success, warranty claims must be predicated on correct and appropriate operation and handling. The manufacturer provides an assurance that all parts are free of material and machining defects at the time of delivery. Liability exclusion: The manufacturer assumes no liability for damage which is caused by operating errors and/or failure to comply with the operating instructions or a failure to carry out maintenance or servicing. 3.2 Purchaser obligation The purchaser must ensure that users are trained in the operation and all safetyrelated aspects of gate control mts2000/02. A report should be produced by all training course attendees documenting the training they have received and this report should be kept on file. Liability exclusion: The manufacturer assumes no liability for damage resulting from any failure by the purchaser to comply with the purchaser s obligations. The purchaser undertakes to only allow trained groups of people to work with the device. The purchaser is also responsible for ensuring that the operating instructions for gate control mts2000/02 are available to the group of users when working with the device. 3.3 User obligation All users must confirm in writing to the purchaser that they have read and understood the safety information and operating instructions. If errors occur as a result of incorrect operations, the user will be deemed to have been responsible. 3.4 Correct use Gate control mts2000/02 is fitted in line with state-of-the-art technology and the recognised rules governing safety with technical equipment. Gate control mts2000/02 should only be used to activate gates which are driven using three-phase motors with reversal inhibit protection and limit switches or AC / DC motors with limit switches when in perfectly safe technical condition. Correct usage also includes: observing all instructions in the operating instructions Gate control operating manual mts2000/ meißner gate systems

10 3 Basic information 3.5 Improper use Incorrect or improper use of the device can put the life and limb of the user at risk, inflict injury on the user and damage the device and/or other material assets. Liability exclusion: The manufacturer assumes no liability for damage caused by improper use. 3.6 Instructions concerning EMC protection The controller has been manufactured and tested in accordance with the corresponding guidelines for EMC (see Section 1.2 CE marking). However, it is possible that mains voltage peaks (due to non-emc compatible loads, for example) may cause the processor to switch off. This procedure is intentional and in no way affects the controller s safety functions. The processor restarts automatically thereafter and the controller is set to Ready mode. The programme sequence can be restarted via the emission of a pulse. These voltage peaks can be suppressed on-site (e.g. by inserting a mains filter as close as possible to terminals 43 and 44, or by taking similar measures). meißner gate systems 3-2 Gate control operating manual mts2000/02

11 Description of product Safety concept Safety equipment independent of the processor All safety-related parts are incorporated in the safety chain (sensors and actuators) directly and independently of the microprocessor. The integrated microprocessor registers and reports from the results of the safety monitoring process, but is not able to influence the safety measures triggered with the exception of reversing the closing edge. The possibility of uncontrolled gate movement triggered by the microprocessor is therefore ruled out and is prohibited by the hardware Monitored safety equipment The evaluation of all safety equipment corresponds to the standard set by the mechanical engineering industry: 1. Before every gate movement, the gate s function is checked automatically. 2. If this function check produces an error, the system is shifted into error status (red light(s) flash(es), if fitted). 3. The gate system cannot be started if an error is present. Normal operations can only be continued once the cause of the error has been rectified. Gate control operating manual mts2000/ meißner gate systems

12 4 Description of product 4.2 Scope Gate control mts2000/02 can be used wherever a high degree of flexibility and complexity is needed. It is used to activate the gates, refer to Chapter 3.4 (Correct use) The operating modes are programmed via a removable display / keypad module Overview of operating modes Impulse control Single/dual lane feedback control with light control and automatic closing Manual mode (with safety functions) Emergency actuation (without safety functions) For more information, refer to Chap.4.4 Operating modes Interfaces for input elements The following external input elements can be connected up, e.g. as impulse sensors: one or two command radio with/without antenna (optional plug-in module) pushbuttons pull buttons key-operated keys continuously open switch ("gatekeeper s switch") Interfaces for output elements The following external output elements can be connected up to the gate control: external lighting for stairways and garages, activation for ventilation or fault message (contact is open in the event of a fault or fall in voltage) lights meißner gate systems 4-2 Gate control operating manual mts2000/02

13 Description of product Structure The gate control is housed in a robust industrial housing of safety class IP54 with the dimensions 250 x 160 x 127 mm. The function group consists of two PCBs: connection PCB control PCB removable display PCB with programming keys Firstly, release plug from connection X1, then remove PCB and bolts The operating and fault statuses appear on the LCD display on the control PCB. Fig. 4 1 Control PCB with controls Gate control operating manual mts2000/ meißner gate systems

14 4 Description of product Supply lines are guided into the housing via screw connections. Apertures which are not used must be sealed with blind plugs. meißner gate systems 4-4 Gate control operating manual mts2000/02

15 Description of product Operating modes Impulse control as sequence control Function: Opening and closing the gate system after activation taking the safety equipment and if necessary the pre-warning time setting into consideration. Details: impulse sequence Activation from either: internal + key radio triggers the following function: motion status of gate changes in the following sequence: OPEN STOP CLOSED STOP If the gate is in its upper or lower limit position, the STOP status is jumped Impulse control, defined up - down Function: 1. Opening and closing the gate system after activation taking the safety equipment and if necessary the pre-warning time set into consideration. Details: Activation from either: impulse for open impulse for close internal + / - keys radio 2 commands triggers the following function: the gate opens or closes. Gate control operating manual mts2000/ meißner gate systems

16 4 Description of product Single/dual lane feedback control with light control and automatic closing Function: 1. Opening the gate system after activation taking the safety equipment into consideration. 2. Closing the gate system once the hold open time and if necessary the prewarning time has lapsed taking the safety equipment into consideration. 3. Light control depending on the occurrence of signals at the inputs for impulse inside, impulse outside or two channel radio. Details: impulse inside Activation from either: impulse outside internal + / - key radio Note triggers the following function: the gate opens. The direction of travel is approved using lights depending on gate control activation (triggering from inside or outside). In the event of alternating activation (triggering from inside or outside) within the hold open time, the direction of travel is changed over using the lights after a pre-warning time which may be set if necessary. The gate shuts automatically once the hold open time and if necessary the prewarning time has lapsed. If selected, the superordinate special operating mode of continuously open (clock) is undertaken in preference to the single/dual lane feedback control with light control Special operating modes: Manual mode Note Function: Opening and closing the gate system taking the safety equipment into consideration. Details: The gate opens or closes for as long as the internal + or keys are pressed. This mode is used for start-up as well as other functions. meißner gate systems 4-6 Gate control operating manual mts2000/02

17 Description of product Emergency control Function: Opening and closing the gate system regardless of the control system s operating mode. Details: The gate opens or closes for as long as the emergency control switches connected up externally or internally are pressed (refer to Fig. 4-1 Control PCB with controls). These switches have a direct impact on the drive. The safety equipment fitted is bridged. Operations without the control PCB attached are possible using the external emergency control switches. For reasons associated with safety, the operator must be able to fully view the gate when pressing the emergency control switch. Care must be taken to ensure that emergency control does not cause damage to the gate and/or does not put people at risk. Note We would recommend using a key-operated switch as the external switch. Gate control operating manual mts2000/ meißner gate systems

18 4 Description of product 4.5 Functions Continuously open switch ("gatekeeper s switch") / external clock Any locking switch can be fitted on site as the continuously open switch. The continuously open function takes priority over all other operating functions; i.e. live processes are interrupted and the gate switches into continuously open mode Weekly indexing clock Function: Holding the gate open and closed at defined times of the day. Details: The weekly indexing clock (which can be retrofitted) controls up to 8 openingclosing cycles per day of the week. The switching times of the week days can be programmed individually or as a group. If the gate is opened, the traffic is control by the light functions. When the gate is closed, the single/dual lane feedback control system is operated by: Activation from either: impulse inside impulse outside internal + key radio Note For more information, please note the operating instructions for the clock, refer to Chapter 6.2 If selected, the superordinate special operating mode of continuously open (clock) is undertaken in preference to programming the weekly indexing clock Halt key A key with a make and break contact can be fitted on-site. The halt function takes preference over all other operating functions; i.e. live processes are interrupted. meißner gate systems 4-8 Gate control operating manual mts2000/02

19 Description of product The safety equipment Closing edge protection Function: Opening and/or reversing the gate once the safety equipment has been activated during the closing process. Details: When the main closing edge protection is triggered during the closing process, the gate either opens to its limit position or reverses for 1 sec. and remains in this position. When at 2 sec. before the lower limit position, only reversing is possible (preset). If the main closing edge is activated, the control system undertakes a total of 3 attempts to close before a fault is displayed. The fault status is reported by rapid fault flashing of the lights, if connected up (also refer to option for the re-opening process described in Chapter "Program gate" 6.1.3). The following can be connected up: optical system OS12 optical system OSE resistance strip R = 8.2 K Note The function of the closing edge protection is checked before every gate movement. Configuration is undertaken via jumper J1 on the control system PCB Stop in open + closed position (protection against anything being drawn in) Note Function: Stop after activation during opening and closing. Details: When triggered regardless of the gate status the gate system is shifted into stop mode. This fault status is reported by the lights fault flashing. Connections are available for one system protecting from anything being drawn in on both the inside and outside. For assembly arrangements, refer to Fig. 4-2 The function of this safety equipment is checked before every gate movement. Precondition: use of one-way light barriers (separate transmitter and receiver). A reflection light barrier can also be connected up but this does not comply with the safety rulings! Gate control operating manual mts2000/ meißner gate systems

20 4 Description of product Stop in closed position (passage protection) Process of re-opening after triggering during closing. During the closing process, the gate will open to its limit position if the passage protection is triggered. Note This applies to all operating modes Hold open time If the function is set to NO for "Reset hold open time via passage protection (also refer to option for "RESET O TIME VIA PP" in Chapter "Program gate" 6.1.4), the time expires despite the passage protection being triggered. Note This applies to the single lane and dual lane feedback control operating modes Extending the hold open time The hold open time is restarted by triggering the passage protection before the hold open time lapses after opening the gate and reaching the top limit position. The hold open time can be set to anything between 1 and 600 seconds. Note This applies to the single/dual lane feedback control operating modes. meißner gate systems 4-10 Gate control operating manual mts2000/02

21 Description of product Shortening the hold open time With the Hold open briefly function set (also refer to option for "Hold open briefly" in Chapter "Program gate" 6.1.3), the gate is held open longer for the period of the Hold open time brief set when the passage protection is triggered and before the hold open time lapses. The closing process is then initiated. The process is restarted when the gate is next driven through. Note This applies to the single/dual lane and dual lane feedback control operating modes Run time monitoring In addition to the hardware safety equipment, the control system is also fitted with software run time monitoring. If the gate does not reach a limit position as a result of the run time set, the system is transferred into error mode. In other words, red light(s) flash(es), if fitted and gate remains motionless. Gate control operating manual mts2000/ meißner gate systems

22 4 Description of product 4.7 Technical data Electrical data Mains connection Voltage supply (at terminals 43, 44) PE (protective conductor) Block of terminals on housing base Power consumption 230 VAC 230 V AC <15 W Stop switch Stop switch (terminals 1, 2) Halt key (terminals 3, 4) 24 V AC/ 1 A 24 V AC/ 1 A Impulse sensor connections Open key or inside impulse 24 V / 100 ma (key, potential-free contact at terminals 5, 6) Close key or outside impulse 24 V / 100 ma (key, potential-free contact at terminals 7, 8) Key for impulse sequence or switch for continuously open (external clock) 24 V / 100 ma (key, potential-free contact at terminals 9, 10) The line length of the impulse sensor should not exceed 15 m. Longer lines must if necessary be disconnected (e.g. potential-free activation of connection via a relay contact) Interfaces for safety equipment Closing edge protection 12 V / 8.2 kω optical (OSE) terminals 11, 12, 13 electro-mechanical (EMC) terminals 11, 12 Stop in closed position (light barrier, potential-free contact) 24 V / 100 ma Supply for transmitter terminals 16,17 Supply for receiver terminals 16,17 Switching output terminals 14,15 meißner gate systems 4-12 Gate control operating manual mts2000/02

23 Description of product 4 Stop in open + closed positions 1 (light barrier, potential-free contact) 24 V / 100 ma Supply for transmitter terminals 17, 21 Supply for receiver terminals 16, 17 Switching output terminals 19, 20 Stop in open + closed positions 2 (light barrier, potential-free contact) 24 V / 100 ma Supply for transmitter terminals 17, 24 Supply for receiver terminals 16, 17 Switching output terminals 22, Connection for potential-free contact e.g. bulb 230VAC / 2 A (at terminals 25, 26) Connection for lights Lights (bulb) (at terminals 29-34) Supply to lights (at terminals 27, 28) 230VAC / 2 A 230VAC / 2 A Connection for drive Drive close (relay) (at terminals 41, 42) Drive open (relay) (at terminals 40, 42) 230VAC / 4A 230VAC / 4A Device protection Type of protection IP Mechanical data Dimensions W x H x D Weight Installation position 160 mm x 250 mm x 127 mm 1800 g vertical Ambient conditions Temperature range 0-60 C Gate control operating manual mts2000/ meißner gate systems

24

25 Assembly and installation Safety information regarding assembly The control system may only be converted or modified once the agreement of the manufacturer has been sought. Always use genuine spare parts. Warranty cover ceases to apply if 3 rd party spare parts are used. When installing, starting up, maintaining and testing the control system, the always ensure compliance with applicable Health & Safety at Work regulations for the specific application must be noted. Amongst others, these rulings include: VDE 0100: Guidelines for setting up high power systems of up to 1000 V VDE 0105: Operating high-current electrical systems EN 60204: Electrical systems with electronic operating equipment VDE 0160: Equipping high power systems and electrical operating equipment VDE 0700: Safety of electrical devices for domestic consumption etc. BGV A2: BGR 232: Electrical systems and operating equipment Guidelines for power-assisted windows, doors and gates Gate control operating manual mts2000/ meißner gate systems

26 5 Assembly and installation 5.2 Fitting gate control mts2000/02 Select an assembly location for the gate control which ensures that the gate can be fully observed. Start-up and service work: For safety reasons, operators must be able to see the gate at all times while pressing the emergency stop switch. Prepare retaining bores for gate control housing (refer to Fig. 5-1 Housing dimensions of gate control). Screw on gate control cover and move cover to one side. Release retaining bolts of control board. Carefully and evenly withdraw board out of connection board. Move board to one side. Prevent static discharge on board! Only touch the edges of the board. Note ESD Directive. Drill holes depending on the quantity and size of lines in the housing. Insert PG screw connections in housing. Fit gate control housing to prepared point. Pull connection cable through PG screw connections and into housing. Attach cable to terminals according to Chapter 5.3, Electrical connection. Carefully attach control board to plug connections of connection board and use 3 screws to secure. Close and screw down cover. meißner gate systems 5-2 Gate control operating manual mts2000/02

27 Assembly and installation 5 Fig. 5-1 Housing dimensions of gate control Gate control operating manual mts2000/ meißner gate systems

28 5 Assembly and installation 5.3 Electrical connection The following diagram shows an overview of the connection board. Follow the references on the detailed diagrams. Connect the external inputs and outputs to gate control mts2000/02 as shown in these diagrams. Fig. 5-2 Connection boards of gate control mts2000/02 meißner gate systems 5-4 Gate control operating manual mts2000/02

29 Assembly and installation 5 Attach connections to connection board of gate control mts2000/02: 24 V connections 1) Gate control (controls) 2) Closing edge protection 3) Protection against anything being snagged or pulled in 230 V connections 1) 230 VAC connection 2) Lights, potential-free contact 3) Drive, mains supply Fig. 5-3 Impulse sensor Gate control operating manual mts2000/ meißner gate systems

30 5 Assembly and installation Fig. 5-4 Closing edge control meißner gate systems 5-6 Gate control operating manual mts2000/02

31 Assembly and installation 5 Fig. 5-5 Passage protection and protection against anything being snagged or pulled in, earthing 0 V Gate control operating manual mts2000/ meißner gate systems

32 5 Assembly and installation Fig. 5-6 Passage protection and protection against anything being snagged or pulled in, earthing 0 V meißner gate systems 5-8 Gate control operating manual mts2000/02

33 Assembly and installation 5 Fig. 5-7 Light connection and potential-free contact Gate control operating manual mts2000/ meißner gate systems

34 5 Assembly and installation Fig. 5-8 Emergency control and mains connection meißner gate systems 5-10 Gate control operating manual mts2000/02

35 Assembly and installation 5 Fig. 5-9 Drive Gate control operating manual mts2000/ meißner gate systems

36

37 Start-up and operation Programming gate control mts2000/02 To undertake programming, the gate control or gate system must be energised. Malfunctions cannot generally be ruled out at this time. Therefore cordon the gate system off from non-specialist staff. Ensure that you and your team have sufficient safety equipment. Energise the gate system: Switch on master switch and/or plug in connector Controls of gate control mts2000/02 Gate control mts2000/02 is programmed using 4 keys (refer to Fig. 4-1) on the control unit display board. The individual menu items of the control unit software are shown on the display. The keys are suppressed and have to be held down for around 1 second before they will respond Hardware settings (for more information, refer to Fig. 4-1) J1 Set according to the closing edge protection fitted J2 Apply jumper when system stop in open + closed position 1 is not connected up and/or no testing is needed (e.g. with reflection light barriers) J3 Apply jumper when system stop in open + closed position 2 is not connected up and/or no testing is needed (e.g. with reflection light barriers) For more information, also refer to Fig. 4-2 Gate control operating manual mts2000/ meißner gate systems

38 6 Start-up and operation Fig. 6-1 Removable display module with programming keys meißner gate systems 6-2 Gate control operating manual mts2000/02

39 Start-up and operation Function of keys Use key M to select a menu item. Use key P to select a parameter in the software for viewing and setting. Use the keys + and to increase or decrease by a specified step width the parameter selected. The value selected is entered by confirming the question Save? Menu structure of operating software Fig. 6-2 Menu levels of operating software for gate control mts2000/ Language setting The language is set on the display. For more information, refer to Chap Service, Language. Gate control operating manual mts2000/ meißner gate systems

40 6 Start-up and operation Program gate Here you will find information on the set values of the individual values for the Gate program menu item (refer to Fig. 6-2 Menu levels of operating software for gate control mts2000/02). Shown on LCD display Comments P R O G R A M G A T E P R E S S P P T O A B O R T P R E S S M T O C O N T I N U E P R E S S P P I N P U T S T A T U S ********* Stop in open + closed position 1 and 2 Stop Closing edge Stop in closed position Impulse open Impulse inside Impulse closed Impulse outside Continuously open externally or clock Impulse sequence open-stopclosed-stop Transmitter stop in open and closed position 1 functioning Transmitter stop in open and closed position 2 functioning * = Contact closed and/or functioning Assignment during operating mode for single or dual lanes Assignment during operating mode for impulse control P H A Z A R D F L A S H I N G / - 5 s Time between impulse emission and gate closing motion, red light flashes P meißner gate systems 6-4 Gate control operating manual mts2000/02

41 Start-up and operation 6 H O L D O P E N / s Time for which the gate remains open, not during impulse control P H O L D O P E N B R I E F / - o f f Only if light barrier is fitted for stop in closed position. Time after which the gate closes after passage, not during impulse control. P L I G H T A C T I V A T I O N F R O M O U T S I D E The potential-free contact closes during every impulse from inside or outside or inside+outside. Set impulse period using light period. If setting outside, impulse also during continuously open function. Only active if light activation is programmed in service. P R E - O P E N O P T I O N o n on: re-opens once closing edge has been activated off: revise once closing edge has been activated P L I G H T S D U R I N G C O N T O P E N O P T 0 Light times: Clearing phase = pre-warn time Green phase = hold open time P Only functions during one lane operating mode and continuously open, or clock mode. 0 = All lights off, green on request 1 = Autom. change, green inside and outside 2 = Green outside continuously, green inside on request 3 = Green inside continuously, green outside on request 4 = Red inside and outside, green on request R E D L I G H T G A T E C L O S E D O P T I O o f f on: red lights on when gate is closed. off: red lights off when gate is closed. P Gate control operating manual mts2000/ meißner gate systems

42 6 Start-up and operation H A Z A R D F L A S H I N G O P T I O N o n on: flashing when faults occur in operating process P R U N T I M E / s Time which the gate needs between limit positions when closing / opening. P C O N T I N U O U S L I G H T / - 1 s Impulse period of potential-free contact Only active if light activation is programmed in service. P S A V E? P H O L D D O W N Save settings --> hold down for 5 seconds, Reject changes --> press "M". P Press for 5 seconds S A V E? P S A V E D Save is acknowledged. P meißner gate systems 6-6 Gate control operating manual mts2000/02

43 Start-up and operation Service Here you will find information on the set values for the individual parameters of the Service menu item (refer to Fig. 6-2 Menu levels of the operating software for gate control mts2000/02). Use key M to select service menu Press and hold down + key, to do this press key P Shown on LCD display Comments S E R V I C E P S E R V I C E P R E S S M Only accessible to service fitters Hold down +, then press P + + P L A N G U A G E : G B + / - Use + / to select language P G A T E C Y C L E S 1 Counter for gate cycles, according to EN Chap (total cycle). P P R E S E T T I N G? Activate manufacturer presettings. Change: hold down + and, then press P P R E V E R S E T I M E / s Time after which the gate reopens when closing after closing edge or stop in closed position. P Gate control operating manual mts2000/ meißner gate systems

44 6 Start-up and operation O P E R A T I N G M O D E S I N G L E L A N E Operating modes available: Single lane with autom. closing. Dual lanes with autom. closing. Impulse control. P R E S E T O - T I M E V I A P P o n P on: hold open time reset when passage protection is activated. off: hold open time is not reset when passage protection is acti- vated (processed without interrupt) P O T. F R E E C O N T A C T L I G H T A C T I V A T I O N LIGHT ACTIVATION or FAULT MESSAGE can be selected. P S A V E? P H O L D D O W N Save settings --> hold down for 5 seconds, Reject changes --> press "M". P Press for 5 seconds S A V E? P S A V E D Save is acknowledged. P Operation Gate control mts2000/02 requires no operation. It is operated as part of the entire gate system using the controls connected to the system such as remote control, keys, continuously open switch. meißner gate systems 6-8 Gate control operating manual mts2000/02

45 Start-up and operation Assembly instructions for weekly time indexing clock mts2000/02 The clock (item 739) can be retrofitted Assembly 1. De-energise the system before assembly. 2. Attach clock to the intended connection point (refer to Fig. 4-1). 3. Re-energise system Programming In accordance with the programming instructions enclosed with the clock. Gate control operating manual mts2000/ meißner gate systems

46 6 Start-up and operation 6.3 Operating instructions for radio mts2000/02 The radio (item 91) can be retrofitted. The radio module is equipped with 2 channels, e.g. entrance and exit for one lane mode with automatic closing Assembly 1. De-energise the system before assembly. 2. Attach the radio plate to the intended connection point (refer to Fig. 4-1). The setting and display elements for the radio plate must face the inside of the housing. 3. The projectile antenna supplied should be in a vertical position. An external antenna (item 477) can be fitted if range problems are experienced. 4. Re-energise system Setting instructions 1. The setting on the 10-pin code switch must match that of the handheld transmitter. 2. The transmitter keys on the 4-pin code switch can be assigned channels, e.g. setting for one lane operations with automatic closing (entrance, exit). 1 = On 2 = Off 3 = On 4 = On meißner gate systems 6-10 Gate control operating manual mts2000/02

47 Start-up and operation Coding table Coding table Coding Left key Right key On Off On Off On Off On Off No function Channel 1 and 2 No function Channel 2 No function Channel 2 Channel 1 Channel 2 On Off On Off Channel 1 Channel 1 No function No function On Off On Off On Off No function Channel 1 No function Channel 1 Channel 2 Channel Displays Press left key, LED 1 lights up Press right key, LED 2 lights up Gate control operating manual mts2000/ meißner gate systems

48

49 Maintenance & service Troubleshooting tool The activities listed below may only be undertaken by specialists. Other people may cause damage to the device and injury to persons! Troubleshooting Troubleshooting is shown on the control system display Testing When an impulse is issued, testing of the stop in open + closed systems and closing edge protection is initiated. A system cannot be tested if ERROR TESTING appears on the control system display. The cause may e.g. be: - light barriers not aligned or not adjusted - light barrier receiver cannot be deactivated due to reflections - light barrier transmitter not connected to test output - light barrier receiver is affected by an external light (e.g. sun) - jumper J2 or J3 set - closing edge protection activated or defective - closing edge type incorrectly configured or not connected - consumers connected to terminals 21 or 24 when jumpers J2 and/or J3 are set Fault rectification Impact Gate not in end position Rectification Issue new command using keys or keyoperated switches etc. If nothing moves; call Service! Gate control operating manual mts2000/ meißner gate systems

50 7 Maintenance & service Control PCB measurement points Test specimen Measurement point 1 Mains connection Measurement points and values for control PCB, pins Measurement Measurement Measurement result Unit Condition Warning point 2 parameter Voltage +/- 230 VAC Mains voltage present 10% Emergency control, drive "CLOSED" Emergency control switch on PCB Resistance 0 Ohm CLOSED or external CLOSED emergency control switch pressed Emergency control switch on PCB Resistance infinite Ohm CLOSED or external CLOSED emergency control switch not pressed. No voltage at terminals 38 and 39 Emergency control, drive "OPEN" Emergency control switch on PCB Resistance 0 Ohm "OPEN" or external " OPEN" emergency control switch pressed Emergency control switch on PCB Resistance infinite Ohm " OPEN" or external " OPEN" emergency control switch not pressed. Outside green Resistance 0 Ohm Outside green light active 51 light 55 Resistance infinite Ohm Outside green light not active Outside red Resistance 0 Ohm Inside green light active 52 light 55 Resistance infinite Ohm Inside green light not active Inside green Resistance 0 Ohm Outside red light active 53 light 55 Resistance infinite Ohm Outside red light not active Resistance 0 Ohm Inside red light active Inside red light Resistance infinite Ohm Inside red light not active Resistance 0 Ohm Output active, contact closed Potential-free 58 contact 59 Resistance infinite Ohm Output inactive, contact opened No voltage at terminals 38 and 39 No voltage at terminals 27 and 28 No voltage at terminals 27 and 28 No voltage at terminals 27 and 28 No voltage at terminals 27 and 28 No voltage at terminals 25 and 26 Meißner gate systems 7-2 Gate control operating manual

51 Maintenance & service 7 Measurement points and values for control PCB, pins Test specimen Stop in open and closed positions 2 Stop in open and closed positions 2 Stop in open and closed positions 1 Control voltage Stop in closed position Auxiliary voltage for closing edge Closing edge as OSE Closing edge as EMC Continuously open and/or impulse sequence Measurem. Measurem. Measurem. point 1 point 2 parameter Voltage Measurem. result Unit Condition +/- 10% 24 VDC Transmitter for system 2 active Voltage 0 VDC Transmitter for system 2 inactive Voltage +/- 10% 24 VDC Voltage 0 VDC Transmitter for systems 1 and 2 active and receiver for systems 1 and 2 active (contacts closed) Transmitter for systems 1 or 2 inactive or receivers for systems 1 or 2 inactive (contacts open) Voltage +/- 10% 24 VDC Transmitter for system 1 active Voltage 0 VDC Transmitter for system 1 inactive Voltage +/- 10% 24 VDC Control system active Control system inactive or short Voltage 0 VDC circuit or ground/earth Voltage +/- 10% 24 VDC Voltage 0 VDC Voltage +/- 10% Voltage 0 VDC Voltage +/- 10% connection Transmitter for stop in closed position active and receiver active (contact closed) Transmitter for stop in closed position inactive or receiver inactive (contact open) 12 VDC Control system active 1,8 VDC Control system inactive or short circuit and/or ground/earth connection Closing edge active (not activated) Closing edge inactive (activated Voltage 0 VDC or conductor failure) Voltage Closing edge active (not 6 VDC +/- 10% activated) Voltage 10 VDC Closing edge activated Voltage 0 VDC Closing edge inactive, conductor failure Continuously open or impulse Voltage 24 VDC sequence activated (contact +/- 10% closed) Voltage 0 VDC Continuously open or impulse sequence not activated (contact open) Gate control operating manual mts2000/ meißner gate systems

52 7 7 Maintenance & service Measurement points and values for control PCB, pins Test specimen Impulse outside and/or closed impulse Impulse inside and/or open impulse Impulse for halt Measurem. Measurem. Measurem. Measurem. point 1 point 2 parameter result Voltage +/- 10% Unit 24 VDC Voltage 0 VDC Voltage +/- 10% 24 VDC Voltage 0 VDC Voltage +/- 10% 24 VDC Voltage 0 VDC Condition Impulse outside or closed impulse activated (contact closed) Impulse outside or closed impulse not activated (contact closed) Impulse inside or open impulse activated (contact closed) Impulse inside or open impulse not activated (contact closed) Impulse for halt and stop not activated (contact closed) Impulse for halt and stop activated (contact open) Meißner gate systems 7-4 Gate control operating manual mts2000/02

53 Maintenance & service Regular testing 1. Remove cover 2. Issue open impulse, gate runs into upper limit position 3. During single lane or dual lane operating mode, wait until the hold open and pre-warning time has expired. During impulse control operating mode, issue close command. 4. Status of LEDs during the test phase (also refer to Fig. 4-1). LED 1 LED 2 LED 3 LED 4 Before test Test stage Test stage Test stage Test stage After test Close housing again once test is complete. If result of testing is negative, shut down system and call service. Gate control operating manual mts2000/ meißner gate systems

54 7 7 Maintenance & service 7.3 Address of manufacturer Meißner GmbH Toranlagen Robert-Koch-Straße Kehl-Auenheim Germany Tel / Fax / info@meissner-gmbh.de Meißner gate systems 7-6 Gate control operating manual mts2000/02

Documentation. Content. Measurement and Control. Type: ELT-GP1. 1. Installation instructions 2. Data sheets 3. Declarations of conformity

Documentation. Content. Measurement and Control. Type: ELT-GP1. 1. Installation instructions 2. Data sheets 3. Declarations of conformity Documentation Measurement and Control Type: ELT-GP1 Content 1. Installation instructions 2. Data sheets 3. Declarations of conformity (Part No. 008Q520) eltherm GmbH Ernst-Heinkel-Str. 6-10 57299 Burbach

More information

EC5401B. B-Tronic EasyControl. Assembly and Operating Instructions. Wall/hand-held transmitter, 1-channel, bidirectional

EC5401B. B-Tronic EasyControl. Assembly and Operating Instructions. Wall/hand-held transmitter, 1-channel, bidirectional B-Tronic EasyControl EC5401B en Assembly and Operating Instructions Wall/hand-held transmitter, 1-channel, bidirectional Important information for: Fitters / Electricians / Users Please forward accordingly!

More information

Precipitation Monitor ,

Precipitation Monitor , THE WORLD OF WEATHER DATA - THE WORLD OF WEATHER DATA - THE WORLD OF WEATHER DATA Instruction for use 021197/11/09 Precipitation Monitor 5.4103.10.000, 5.4103.10.700 ADOLF THIES GmbH & Co. KG Hauptstraße

More information

Wireless Receiver E28Q Mounting and Operating Instructions (Original operating instructions)

Wireless Receiver E28Q Mounting and Operating Instructions (Original operating instructions) EN Wireless Receiver E28Q Wireless Receiver E28Q Mounting and Operating Instructions (Original operating instructions) Always read before initial operation! 28509900_E28Q_EN_2012-05-08.doc 1 / 12 1 Data

More information

Technical manual. Microstep driver SMC11. NANOTEC ELECTRONIC GmbH & Co. KG Gewerbestraße 11 D Landsham near Munich, Germany

Technical manual. Microstep driver SMC11. NANOTEC ELECTRONIC GmbH & Co. KG Gewerbestraße 11 D Landsham near Munich, Germany Technical manual Microstep driver NANOTEC ELECTRONIC GmbH & Co. KG Gewerbestraße 11 D-85652 Landsham near Munich, Germany Tel. +49 (0)89-900 686-0 Fax +49 (0)89-900 686-50 info@nanotec.de Editorial Editorial

More information

External brake resistor AX2090-BW5x

External brake resistor AX2090-BW5x Documentation External brake resistor AX2090-BW5x Accessories for Beckhoff servo drive AX5000 Version: Date: 1.3 2018-03-14 Table of content Table of content 1 Foreword... 5 1.1 Notes on the documentation...

More information

B-Tronic EasyControl EC5401B

B-Tronic EasyControl EC5401B B-Tronic EasyControl EC5401B en Assembly and Operating Instructions Wall/hand-held transmitter, 1-channel, bidirectional Important information for: Fitters / Electricians / Users Please forward accordingly!

More information

Mounting instruction and operating manual. Access Point (UK) HmIP-HAP-UK

Mounting instruction and operating manual. Access Point (UK) HmIP-HAP-UK Mounting instruction and operating manual Access Point (UK) HmIP-HAP-UK Package contents Quantity Description 1 Homematic IP Access Point (UK) 1 Plug-in mains adapter 1 Network cable 2 Screws 2 Plugs 1

More information

DT1100 xx xx xx PS. Isolators, Isolator / Power Supplies. Operating Instructions

DT1100 xx xx xx PS. Isolators, Isolator / Power Supplies. Operating Instructions Isolators, Isolator / Power Supplies Operating Instructions EN Contents 1. About this document...4 1.1. Function... 4 1.2. Target group... 4 1.3. Symbolism used... 4 2. For your safety...5 2.1. Authorized

More information

Instruction manual for STA 1 sectional door operator

Instruction manual for STA 1 sectional door operator Instruction manual for STA 1 sectional door operator Sectional door operator STA 1 / Rev. 0.3 1 GB 1. Contents 3. General safety instructions 1. Contents 2 2. Key to symbols 2 3. General safety instructions

More information

DT1100 E xx xx (PS) Galvanic Isolators. Operating Instructions

DT1100 E xx xx (PS) Galvanic Isolators. Operating Instructions DT1100 E xx xx (PS) Galvanic Isolators Operating Instructions Contents 1. About this document...4 1.1. Function... 4 1.2. Target group... 4 1.3. Symbolism used... 4 2. For your safety...5 2.1. Authorized

More information

Original operating instructions Fail-safe inductive sensor GG507S / / 2013

Original operating instructions Fail-safe inductive sensor GG507S / / 2013 Original operating instructions Fail-safe inductive sensor GG507S 80005283 / 00 05 / 2013 Contents 1 Preliminary note...3 1.1 Explanation of symbols...3 2 Safety instructions...4 2.1 Safety-related requirements

More information

Radio Control Installation and Operating Instructions System 4

Radio Control Installation and Operating Instructions System 4 Radio Control Installation and Operating Instructions System 4 P.O. Box 403, One Cedar Parkway, Jackson, WI 53037 Phone: 800-628-1909 Fax: 262-677-2058 Revision: April 19, 2012 Contents Introduction 3

More information

Operating Instructions. for. Controller SMS 150 / 151

Operating Instructions. for. Controller SMS 150 / 151 Operating Instructions for Controller SMS 150 / 151 Contents Controller SMS 150 / 151... 1 Contents... 2 Reserve... 2 1. Safety instructions for users... 3 2. Application... 4 3. Warnings... 5 4. Installation...

More information

Impulse system MPT 700. Manual Edition GB

Impulse system MPT 700. Manual Edition GB Impulse system MPT 700 Manual 6.2.2.2 Edition 10.10 GB 1 Introduction... 4 1.1 Version and model... 5 1.2 CE Mark... 7 2 Operation... 8 2.1 Controls... 8 2.1.1 Front panel... 8 2.1.2 Parameter display...

More information

INSTRUCTION MANUAL. IBRit - rf1 - usb PC - Station for wireless Data transmission. M e s s t e c h n i k. Messtechnik GmbH & Co.

INSTRUCTION MANUAL. IBRit - rf1 - usb PC - Station for wireless Data transmission. M e s s t e c h n i k. Messtechnik GmbH & Co. M e s s t e c h n i k INSTRUCTION MANUAL PC - Station for wireless Data transmission Document No. : D1F604 001 Version : April 2006 Copyright : IBR Messtechnik GmbH & Co. KG Contents 1. Introduction 1.1

More information

Installation and Operating Instructions. Power IT Power Factor Controller RVC

Installation and Operating Instructions. Power IT Power Factor Controller RVC Installation and Operating Instructions Power IT Power Factor Controller RVC Table of contents Page 1. Read this first... 3 About this Instruction Manual... 3 Safety... 3 Electromagnetic compatibility...

More information

IRIS \ IRIS-I QUICK SET-UP GUIDE STEP 1 INSTALL

IRIS \ IRIS-I QUICK SET-UP GUIDE STEP 1 INSTALL IRIS \ IRIS-I QUICK SET-UP GUIDE STEP 1 INSTALL Confirm contents of package: 1 sensor, 1 cable, 1 wide lens (default), 1 narrow lens, mounting template, User s Guide. Install the sensor at the desired

More information

Instruction manual for STA 1 sectional door operator

Instruction manual for STA 1 sectional door operator Instruction manual for STA 1 sectional door operator GB Sectional door operator STA 1 / Rev. 0.0 1 1. Contents 3. General safety instructions 1. Contents 2 2. Key to symbols 2 3. General safety instructions

More information

DB 112 B. Double Sheet Testing Unit TECHNICAL DESCRIPTION. en / We reserve the right to. make technical changes

DB 112 B. Double Sheet Testing Unit TECHNICAL DESCRIPTION. en / We reserve the right to. make technical changes en 03-2014/06 50126540 We reserve the right to make technical changes DB 112 B Double Sheet Testing Unit TECHNICAL DESCRIPTION 2014 Leuze electronic GmbH + Co. KG In der Braike 1 D-73277 Owen / Germany

More information

RADIOBAND 3G RB3 T868 RB3 R868 USER'S MANUAL

RADIOBAND 3G RB3 T868 RB3 R868 USER'S MANUAL RADIOBAND 3G RB3 T868 RB3 R868 USER'S MANUAL Index INTRODUCTION... 3 Operating... 3 Receiver RB3 R868... 4 Transmitter RB3 T868... 5 ASSEMBLY AND INSTALLATION... 6 1 Installation of the equipment... 6

More information

Radio receiver E17 2-channel, 27 MHz, 40MHz, or 433 MHz, 2 relay outputs. Operating voltage: 230 V/AC or 12 V or 24 V AC/DC available.

Radio receiver E17 2-channel, 27 MHz, 40MHz, or 433 MHz, 2 relay outputs. Operating voltage: 230 V/AC or 12 V or 24 V AC/DC available. Fig.: 230 V version Radio receiver E17 2-channel, 27 MHz, 40MHz, or 433 MHz, 2 relay outputs. Operating voltage: 230 V/AC or 12 V or 24 V AC/DC available. Installation, connection and programming instructions

More information

Installation and Operational Instructions for ROBA -switch Type 017._00.2

Installation and Operational Instructions for ROBA -switch Type 017._00.2 Manufacturer s Declaration This product is intended for installation in a machine or system, based on the machine directive 2006/42/EC. It is forbidden to start use of the product until the machine or

More information

NSD Safety Mat Controller Modules Both Modules are compliant to OSHA & ANSI Standards - EN ISO EN EN 81-1 EN NSD VDC

NSD Safety Mat Controller Modules Both Modules are compliant to OSHA & ANSI Standards - EN ISO EN EN 81-1 EN NSD VDC Datasheet NSD Safety Mat Controller Modules Both Modules are compliant to OSHA & ANSI Standards - EN ISO 13849-1 EN 62061 EN 81-1 EN 50156-1 Approvals NSD-3580 24 VDC NSD-3590 115 TO 230 VAC Technical

More information

TPM + Lenze ECS. Quick Startup Guide D Revision: 02

TPM + Lenze ECS. Quick Startup Guide D Revision: 02 4091-D012345 00 TPM + Lenze ECS Quick Startup Guide 4091-D032121 Revision: 02 Quick Startup Guide TPM + Revision history Revision Date Comment Chapter 01 27 th July 2012 First release All 02 27 th March

More information

Magnetic Inductive Flow Sensor induq

Magnetic Inductive Flow Sensor induq Operating manual (Translation) Operating manual... page 1-16 Magnetic Inductive Flow Sensor induq Series VMZ SIKA Ba_VMZ_en 10/2014. Please keep this operating manual for future reference. If the device

More information

AMERITRON RCS-12 AUTOMATIC ANTENNA SWITCH

AMERITRON RCS-12 AUTOMATIC ANTENNA SWITCH AMERITRON RCS-12 AUTOMATIC ANTENNA SWITCH INSTRUCTION MANUAL PLEASE READ THIS MANUAL BEFORE OPERATING THIS EQUIPMENT! 116 Willow Road Starkville, MS 39759 USA 662-323-8211 Version 3B Printed in U.S.A.

More information

English RACON SERIES II RADIO CONTROL SERVICE MANUAL

English RACON SERIES II RADIO CONTROL SERVICE MANUAL English 22.2.2007 RACON SERIES II RADIO CONTROL SERVICE MANUAL Read the instructions supplied with the product before installation and commissioning. Keep the instructions in a safe place for future reference.

More information

Installation and Operational Instructions for ROBA -switch Type 017._00.2

Installation and Operational Instructions for ROBA -switch Type 017._00.2 OBA -switch Type 017._00.2 Guidelines on the Declaration of Conformity A conformity evaluation has been carried out for the product in terms of the EC Low Voltage Directive 2014/35/ EC and the EMC Directive

More information

Precipition Sensor with analogue Intensity Output ,

Precipition Sensor with analogue Intensity Output , THE WORLD OF WEATHER DATA - THE WORLD OF WEATHER DATA - THE WORLD OF WEATHER DATA Instruction for use 021335/11/09 Precipition Sensor with analogue Intensity Output 5.4103.20.041, 5.4103.20.741 ADOLF THIES

More information

Operating instructions Fail-safe delay timer AZS About this document. Content

Operating instructions Fail-safe delay timer AZS About this document. Content 8 Appendix 8.1 Wiring example...4 8.2 Integral System Diagnostics (ISD)....5 9 EU Declaration of conformity Operating instructions.............pages 1 to 6 Original x.000 / 11.2017 / v.a. - 101126753-

More information

Operating Instructions

Operating Instructions Level and Pressure Operating Instructions VEGATOR 620, 621, 622 max. 0 10 min. 0 10 on VEGATOR 622! 6 7 8 9 10 11 12 13 14 in out Contents Contents Safety information... 2 Note Ex area... 2 1 Product description

More information

User Manual March 2008

User Manual March 2008 User Manual March 008 Motor Silent Gliss 900, 90, 90, 903 Motor Silent Gliss 9030, 903, 903, 9033 Usermanual Motors 90x_903x Page Copyright April 007 by Silent Gliss International Ltd., 3073 Gümligen/Berne

More information

Out 1 sin / cos 1Vpp. sin / cos 1Vpp. Out 3. sin / cos 1Vpp. Out 4 sin / cos 1Vpp. Interface type SV211 SinCos signal splitter with 4 SinCos outputs

Out 1 sin / cos 1Vpp. sin / cos 1Vpp. Out 3. sin / cos 1Vpp. Out 4 sin / cos 1Vpp. Interface type SV211 SinCos signal splitter with 4 SinCos outputs Operating Manual Out 1 sin / cos 1Vpp Input: sin / cos 1 Vpp Out 2 sin / cos 1Vpp Out 3 sin / cos 1Vpp SV 211 Out 4 sin / cos 1Vpp Interface type SV211 SinCos signal splitter with 4 SinCos outputs Product

More information

Level Switch NRS 2-50 NRS Original Installation Instructions English

Level Switch NRS 2-50 NRS Original Installation Instructions English Level Switch NRS 2-50 NRS 2-51 EN English Original Installation Instructions 819179-03 1 Contents Important Notes Page Usage for the intended purpose...4 Function...4 Safety note...4 Directives and Standards

More information

Awning control system GFM001. Installation and Operating Instructions

Awning control system GFM001. Installation and Operating Instructions Geiger-Funk Sunshade controls Awning control system for 230V drives GFM001 Installation and Operating Instructions for pre-coded systems Table of Contents 1 Introduction...3 2 Safety instructions...3 3

More information

OPERATION MANUAL ELECTRONIC FREQUENCY CONVERTER HFO-E

OPERATION MANUAL ELECTRONIC FREQUENCY CONVERTER HFO-E OPERATION MANUAL ELECTRONIC FREQUENCY CONVERTER HFO-E Lievers Holland PO Box 103 3640 AC Mijdrecht Tel: +31 (0)297-231900 Fax: +31 (0)297-231909 E-mail: info@lieversholland.nl - www.lieversholland.nl CONTENT

More information

Operating Instructions PROFITEST H+E TECH. Diagnostics Unit for Electric Charging Stations (Type 2 Connector Socket and Plug) /3.

Operating Instructions PROFITEST H+E TECH. Diagnostics Unit for Electric Charging Stations (Type 2 Connector Socket and Plug) /3. Diagnostics Unit for Electric Charging Stations (Type 2 Connector Socket and Plug) 3-349-878-03 1/3.16 Opening the Instrument / Repairs The instrument may only be opened by authorized, trained personnel

More information

RADIOBAND V3 Programming & Installation Manual

RADIOBAND V3 Programming & Installation Manual RADIOBAND V3 Programming & Installation Manual Radioband V3 User s Manual Introduction The RadioBand system is designed for Automatic Gates, Commercial and Domestic door applications where a safety edge

More information

DB 12 B. Double Sheet Testing Unit. Phone: Fax: Web: -

DB 12 B. Double Sheet Testing Unit. Phone: Fax: Web:  - DB 12 B Double Sheet Testing Unit GB 03-08/08 50104956 Table of contents 1 General information... 2 1.1 Explanation of symbols... 2 1.2 Declaration of conformity... 2 2 Safety notices... 3 2.1 Safety standards...

More information

Operating Instructions for Control CS 500

Operating Instructions for Control CS 500 Operating Instructions for Control CS 500 GB CS 500 Gate Controls / Rev.A 5.0 1 1. Contents 1. Contents 2 2. Information in this document 2 3. General safety instructions 3 4. Overview of products 4 5.

More information

OSMAC RDR Low-voltage Retrofit Kit

OSMAC RDR Low-voltage Retrofit Kit OSMAC RDR Low-voltage Retrofit Kit Part Number RDR0160LVN0 User s Guide Installation of the RDR (Radio Data Receiver) low-voltage unit will enable you to remotely operate your existing Vari-Time 4000 satellite

More information

GESTRA Steam Systems LRS English. Installation & Operating Instructions Conductivity Switch LRS 1-50

GESTRA Steam Systems LRS English. Installation & Operating Instructions Conductivity Switch LRS 1-50 GESTRA Steam Systems LRS 1-50 EN English Installation & Operating Instructions 819223-02 Conductivity Switch LRS 1-50 Contents Important notes Page Usage for the intended purpose...4 Function...4 Safety

More information

TR20A120 RE / 02.2012 DE EN FR NL IT ES PT Anleitung für Montage und Betrieb Funk-Codetaster FCT 10 BiSecur Instructions for fitting and operating Radio code switch FCT 10 BiSecur Instructions de montage

More information

Original operating instructions Fail-safe inductive sensor GM504S / / 2010

Original operating instructions Fail-safe inductive sensor GM504S / / 2010 Original operating instructions Fail-safe inductive sensor GM504S 704070 / 01 06 / 2010 Contents 1 Preliminary note 3 1.1 Explanation of symbols 3 2 Safety instructions 4 2.1 Safety-related requirements

More information

Brunata Optuna H Ultrasonic energy meter Type 775 Installation Guide Edition 1.2

Brunata Optuna H Ultrasonic energy meter Type 775 Installation Guide Edition 1.2 Ultrasonic energy meter Type 775 Installation Guide Edition 1.2 UK-QB101575 / 29.05.2012 Brunata a/s is a Danish owned company. We have more than 90 years of experience within developing and producing

More information

Digital Function Generator

Digital Function Generator Digital Function Generator 13654-99 PHYWE Systeme GmbH & Co. KG Robert-Bosch-Breite 10 37079 Göttingen Germany Tel. +49 (0) 551 604-0 Fax +49 (0) 551 604-107 E-mail info@phywe.de Operating Instructions

More information

ISOMETER IRDH575. Approvals

ISOMETER IRDH575. Approvals Insulation monitoring device for unearthed AC, DC and AC/DC systems (IT systems) with control and display function for EDS insulation fault location systems IRDH575_D00089_02_D_XXEN/09.2018 Insulation

More information

Documentation. Measurement and Control. Type: ELT-GP2

Documentation. Measurement and Control. Type: ELT-GP2 Documentation Measurement and Control Type: ELT-GP2 05.01.2018 K. Folkerts Content 1. Data sheet 2. Installation instructions 3. Declarations of conformity 05.01.2018 K. Folkerts 1 05.01.2018 K. Folkerts

More information

Current Loop Interface Module M 2025D

Current Loop Interface Module M 2025D CONTROLS Current Loop Interface Module M 2025D Current-to-Voltage Analog Converter used with the M 2001 Series Digital Tapchanger Control and M-2948 Tap Position Sensors to provide positive tap position

More information

A RANGE-STANDARD MODULAR VALIDATOR

A RANGE-STANDARD MODULAR VALIDATOR A RANGE-STANDARD MODULAR VALIDATOR Azkoyen 10042 UK 06-2004 1. INTRODUCTION AND DESCRIPTION OF COMPONENTS This Technical Manual contains the technical information related to the coin validators in the

More information

1800 Series Attachable Loop-Powered Digital Indicators Operating Manual

1800 Series Attachable Loop-Powered Digital Indicators Operating Manual 1800 Series Attachable Loop-Powered Digital Indicators Operating Manual 1010 West Bagley Road, Berea, Ohio 44017 P 440.243.0888 F 440.243.3472 www.noshok.com Index 1 INTRODUCTION 3 2 SAFETY REGULATIONS

More information

Operating Instructions. for. Controller SMS 160 / 161

Operating Instructions. for. Controller SMS 160 / 161 Operating Instructions for Controller SMS 160 / 161 Contents Controller SMS 160 / 161... 1 Contents... 2 Reserve... 2 1. Safety instructions for users... 3 2. Application... 4 3. Warnings... 5 4. Installation...

More information

Operating Instructions for Pressure Sensor with Ceramic Sensor Element. Model: SEN-9601

Operating Instructions for Pressure Sensor with Ceramic Sensor Element. Model: SEN-9601 Operating Instructions for Pressure Sensor with Ceramic Sensor Element Model: SEN-9601 We don t accept warranty and liability claims neither upon this publication nor in case of improper treatment of the

More information

COD GB / 1.0 RBAND/UMS - RBAND/CSM

COD GB / 1.0 RBAND/UMS - RBAND/CSM INTRODUCTION DESCRIPTION The RadioBand system is designed of Industrial, Commercial and Domestic door and gate applications where a safety edge is used. The system provides a wireless system replacing

More information

RMO500 M I C R O O H M M E T E R

RMO500 M I C R O O H M M E T E R M I C R O O H M M E T E R Reference Manual IBEKO POWER AB Sweden 2 IBEKO POWER AB Manual Version:. MV.01 IBEKO POWER AB 2003 This Reference Manual is a publication of IBEKO POWER AB, 18 125 Lidingö, Sweden.

More information

Installation & Operation Manual SAGA1-K Series Industrial Radio Remote Control

Installation & Operation Manual SAGA1-K Series Industrial Radio Remote Control Installation & Operation Manual SAGA1-K Series Industrial Radio Remote Control Gain Electronic Co. Ltd. Table Of Contents Safety Considerations ------------------------------------------------------------2

More information

Receiver Type /Version Factory No. Frequency. Transmitter Type /Version Factory No. Frequency

Receiver Type /Version Factory No. Frequency. Transmitter Type /Version Factory No. Frequency Receiver Type /Version Factory No. Frequency Transmitter Type /Version Factory No. Frequency 1. STANDARD SPECIFICATION Portable transmitter. Receiver with integrated mounting holes. Multi-pin connecting

More information

DeltaSol AX HE * * Differential temperature controller Manual for the specialised craftsman

DeltaSol AX HE * * Differential temperature controller Manual for the specialised craftsman DeltaSol X HE Differtial temperature controller Manual for the specialised craftsman Installation Operation Functions and options Troubleshooting *110633* 110633 Thank you for buying this RESOL product.

More information

! "! # $ % & ' ( ) " * % +, # # -. / ( ! " ! # $ % &

! ! # $ % & ' ( )  * % +, # # -. / ( !  ! # $ % & Manual HT55 2. General 2.1 Unpacking and inspecting The product must be inspected for possible shipping damage when it is unpacked. If damage is found then the freight carrier, railway company or postal

More information

TPM + power. Bosch Rexroth IndraDrive. Quick Startup Guide D Revision: 02

TPM + power. Bosch Rexroth IndraDrive. Quick Startup Guide D Revision: 02 4091-D021068 01 TPM + power Bosch Rexroth IndraDrive Quick Startup Guide 4091-D021074 Revision: 02 Quick Startup Guide TPM + power Revision history Revision Date Comment Chapter 01 08.07.2009 First release

More information

Original operating instructions Fail-safe inductive sensor GG507S

Original operating instructions Fail-safe inductive sensor GG507S Original operating instructions Fail-safe inductive sensor GG507S 80236827 / 00 09 / 2016 Contents 1 Preliminary note...3 1.1 Symbols used...3 1.2 Warning signs used...3 2 Safety instructions...4 2.1 Safety-related

More information

autotronic multitronic Radio transponder reader NB693N Installation and operation instructions

autotronic multitronic Radio transponder reader NB693N Installation and operation instructions WWW.FUHR.DE autotronic Radio transponder reader NB693N Installation and operation instructions These instructions are to be passed on by the fitter to the user. MBW23-GB/04.16-4 Inhalt 1 Applications...3

More information

Wireless wall transmitter, 1-gang with inscription space, Wireless wall transmitter, 3-gang with inscription space

Wireless wall transmitter, 1-gang with inscription space, Wireless wall transmitter, 3-gang with inscription space Wireless wall transmitter, 1-gang with inscription space Order No. : 5331.. Wireless wall Order No. : 5333.. Operating instructions 1 Safety instructions Electrical devices may only be mounted and connected

More information

Transmitter System USER S MANUAL. Light Series

Transmitter System USER S MANUAL. Light Series Transmitter System USER S MANUAL Light Series Follow the indications and warnings given by the machine producer regarding the machine controlled by the radio remote control. The information contained in

More information

Radio System Strobe Wizard Plus Freemask

Radio System Strobe Wizard Plus Freemask Radio System Strobe Wizard Plus Freemask User manual Translation of the original German user manual Doc. No.: 900.0509.00 Version: 09/2017 Contents Information about this manual and about the manufacturer...

More information

SUNNY BEAM REPEATER Transmission Range Increase for Sunny Beam

SUNNY BEAM REPEATER Transmission Range Increase for Sunny Beam SUNNY BEAM REPEATER Transmission Range Increase for Sunny Beam User Manual SBeamRep-BEN091911 98-0002611 Version 1.1 EN SMA Solar Technology AG Table of Contents Table of Contents 1 Notes on this Manual..............................

More information

Operating Instructions K-POWERgrip EWL Always on the safe site.

Operating Instructions K-POWERgrip EWL Always on the safe site. Operating Instructions K-POWERgrip EWL 4941. Always on the safe site. KaVo Elektrotechnisches Werk GmbH Wangener Straße 78 D-88299 Leutkirch A 1 User information...2 A 1.1 Meaning of the pictograms...2

More information

Installation and Operational Instructions for ROBA -multiswitch Type 019._00.2

Installation and Operational Instructions for ROBA -multiswitch Type 019._00.2 Guidelines on the Declaration of Conformity A conformity evaluation has been carried out for the product in terms of the EU Low Voltage Directive 2014/35/ EU and the Electromagnetic Compatibility (EMC)

More information

Seite 2 Standard-Empfänger. EN Operation Instructions

Seite 2 Standard-Empfänger. EN Operation Instructions sign lux DE Bedienungsanleitung Seite 2 Standard-Empfänger EN Operation Instructions Page 10 Standard receiver FR Mode d emploi Page 18 Récepteur standard NL Gebruiksaanwijzing Pagina 26 Standaard ontvanger

More information

Catalogue 1SFC en, Edition 3 November 2003 Supersedes Catalogue 1SFC en, Edition 2 November Arc Guard System TVOC

Catalogue 1SFC en, Edition 3 November 2003 Supersedes Catalogue 1SFC en, Edition 2 November Arc Guard System TVOC Catalogue 1SFC 266006-en, Edition 3 November 2003 Supersedes Catalogue 1SFC 266006-en, Edition 2 November 2000 Arc Guard System TVOC System units The two units of the are used as below: Approvals 1. with

More information

PU202 Level converter & encoder signal generator without potential separation

PU202 Level converter & encoder signal generator without potential separation Operating Manual PU202 Level converter & encoder signal generator without potential separation Product features: Converts HTL signals from 10 up to 30 V (A / B / Z) into the corresponding TTL / RS422 format

More information

WEL-200 O P E R A T I N G I N S T R U C T I O N S W I R E L E S S E D G E L I N K

WEL-200 O P E R A T I N G I N S T R U C T I O N S W I R E L E S S E D G E L I N K O P E R A T I N G I N S T R U C T I O N S WEL-200 TM W I R E L E S S E D G E L I N K 4564 Johnston Parkway, Cleveland, Ohio 44128 P. 800 426 9912 F. 216 518 9884 Sales Inquiries: salessupport@emxinc.com

More information

1. Function. Universal dimming actuator REG-K/2x230/ 300 W. Universal dimming actuator REG-K/230/ 500 W. Universal dimming actuator REG-K/230/ 1000 W

1. Function. Universal dimming actuator REG-K/2x230/ 300 W. Universal dimming actuator REG-K/230/ 500 W. Universal dimming actuator REG-K/230/ 1000 W L L N N on error RUN 1 2 3 4 KNX EIB 1 1 1 1 Chapter 9: Dimming actuators/control units Chapter 9:Dimming actuators/control unitsart. no.6493xxas of 10/079.2Universal dimming actuators Universal dimming

More information

Safety. Operating instructions Communications module ACM WAVE SYSTEM RF for gas meters with Absolute ENCODER AE2 with and without smart valve DANGER

Safety. Operating instructions Communications module ACM WAVE SYSTEM RF for gas meters with Absolute ENCODER AE2 with and without smart valve DANGER Edition 02.10 D GB NL SK www.docuthek.com Operating instructions ommunications module AM WAVE SYSTEM RF for gas meters with Absolute ENODER AE2 with and without smart valve Translation from the German

More information

ECM3 EARTH CONTINUITY RELAY

ECM3 EARTH CONTINUITY RELAY TECHNICAL DATASHEET ECM3 EARTH CONTINUITY RELAY Electrical Protection for Hard Rock Mines Application The ECM3 has been designed to provide earth continuity protection for cables containing pilot cores.

More information

USERS GUIDE EAGLE SMR MOTION SENSOR

USERS GUIDE EAGLE SMR MOTION SENSOR USERS GUIDE EAGLE SMR MOTION SENSOR DESCRIPTION The revolutionary Eagle SMR Motion Detector incorporates K-band technology combined with digital processing. These two technological capabilities assure

More information

Operating Manual * * Differential pressure transmitter. Table of Contents. 1 Safety guidelines. 1.1 General Information

Operating Manual * * Differential pressure transmitter. Table of Contents. 1 Safety guidelines. 1.1 General Information *09005137* BA_EN_DE50 Rev.A 11/12 *09005137* d e v e l o p i n g s o l u t i o n s DE50 Operating Manual Differential pressure transmitter Table of Contents 1 Safety guidelines 2 Application purpose 3

More information

Model 5100F. Advanced Test Equipment Rentals ATEC (2832) OWNER S MANUAL RF POWER AMPLIFIER

Model 5100F. Advanced Test Equipment Rentals ATEC (2832) OWNER S MANUAL RF POWER AMPLIFIER Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) OWNER S MANUAL Model 5100F RF POWER AMPLIFIER 0.8 2.5 GHz, 25 Watts Ophir RF 5300 Beethoven Street Los Angeles, CA 90066

More information

OPERATION MANUAL MOB 112

OPERATION MANUAL MOB 112 OPERATION MANUAL MOB 112 1 Contents 1 GENERAL... 4 1.1 Information regarding the operating instruction... 4 1.2 Limitation of liability... 4 1.3 Warranty... 5 2 TECHNICAL DATA... 6 2.1 Dimension... 6 2.2

More information

Built-in receiver module

Built-in receiver module TT2N Built-in receiver module 0682 EN - Instructions and warnings for the Fitter IT - Istruzioni ed avvertenze per l Installatore FR - Instructions et recommandations pour l Installateur ES - Instrucciones

More information

FACTORY AUTOMATION. MANUAL LC10-* Laying loops for Loop detector LC10-1 and LC10-2

FACTORY AUTOMATION. MANUAL LC10-* Laying loops for Loop detector LC10-1 and LC10-2 FACTORY AUTOMATION MANUAL LC10-* Laying loops for Loop detector LC10-1 and LC10-2 With regard to the supply of products, the current issue of the following document is applicable: The General Terms of

More information

Melt pressure Transmitter GREENLINE Type DTAI with Temperature element

Melt pressure Transmitter GREENLINE Type DTAI with Temperature element Melt pressure Transmitter GREENLINE Type DTAI with Temperature element Operation and Maintenance Manual English Mercury free NaK free Seite 1 / 9 Contents: 1. Introduction 2. Operating range and field

More information

Operator s Guide. Sequin Device. Version 1.3. Published by: ZSK Stickmaschinen GmbH - Dokumentation - D Krefeld-Gartenstadt

Operator s Guide. Sequin Device. Version 1.3. Published by: ZSK Stickmaschinen GmbH - Dokumentation - D Krefeld-Gartenstadt Operator s Guide Sequin Device Version 1.3 Published by: ZSK Stickmaschinen GmbH - Dokumentation - D-47800 Krefeld-Gartenstadt Magdeburger Str. 38 40 04 by ZSK, Printed in Germany Subject to change. 04

More information

HB-25 Motor Controller (#29144)

HB-25 Motor Controller (#29144) Web Site: www.parallax.com Forums: forums.parallax.com Sales: sales@parallax.com Technical: support@parallax.com Office: (916) 624-8333 Fax: (916) 624-8003 Sales: (888) 512-1024 Tech Support: (888) 997-8267

More information

TIG 250 AC-DC. POWER SOURCE art

TIG 250 AC-DC. POWER SOURCE art CEBORA S.p.A. 1 TIG 250 AC-DC POWER SOURCE art. 236.76 SERVICE MANUAL CEBORA S.p.A. 2 CONTENTS 1 - GENERAL INFORMATION... 3 1.1 - Introduction.... 3 1.2 - General service policy.... 3 1.3 - Safety information....

More information

Connection and installation manual. Induction loop detector ISD 4, ISD 4/2

Connection and installation manual. Induction loop detector ISD 4, ISD 4/2 Connection and installation manual Induction loop detector ISD 4, ISD 4/2 warning and safety notes These installation and operating instructions form an integral part of the product. They have been specifically

More information

English. Operating manual. Temperature measuring transducer MU125. Save for later reference. Company / brands of GHM

English. Operating manual. Temperature measuring transducer MU125.  Save for later reference. Company / brands of GHM English Operating manual Temperature measuring transducer MU125 Company / brands of GHM www.ghm-messtechnik.de Save for later reference. Table of contents Page 1. Intended use (areas of application)...

More information

Sentry Digital Timers

Sentry Digital Timers Sentry Digital Timers 0733s S4 Contents 1. Safety precautions 2. General rmation 3. DIN rail Installation 4. Display Layout. Programming 6. Technical Data 7. Guarantee 2 Safety precautions The connection

More information

AD-8100 & AD-8200 Servo Amplifiers

AD-8100 & AD-8200 Servo Amplifiers Instruction Manual IM-0607 AD-8100 & AD-8200 Servo Amplifiers Table of Contents General Information... 2 Basic Models... 3 Specifications... 3 Installation Wiring... 3 Setup & Calibration... 4-6 Troubleshooting

More information

Installation and Operating Instructions for Phase Demodulator Type _.2

Installation and Operating Instructions for Phase Demodulator Type _.2 Guidelines on the Declaration of Conformity A conformity evaluation has been carried out for the product in terms of the EU Low Voltage Directive 2014/35/EU and the Electromagnetic Compatibility (EMC)

More information

TETRIS 1000 High Impedance Active Probe. Instruction Manual

TETRIS 1000 High Impedance Active Probe. Instruction Manual TETRIS 1000 High Impedance Active Probe Instruction Manual Copyright 2015 PMK GmbH All rights reserved. Information in this publication supersedes that in all previously published material. Specifications

More information

CS-200. PORTABLE TRAFFIC LIGHT CONTROLLER (Software 1.05) OPERATION AND SERVICE MANUAL

CS-200. PORTABLE TRAFFIC LIGHT CONTROLLER (Software 1.05) OPERATION AND SERVICE MANUAL CS-200 PORTABLE TRAFFIC LIGHT CONTROLLER (Software 1.05) OPERATION AND SERVICE MANUAL CS-200 Operation and Service Manual Page 2 Manufactured by: LINCAST INTERNATIONAL PTY. LTD. 2/3 Sir Laurence Drive

More information

TC 34 MICROPROCESSOR-BASED DIGITAL ELECTRONIC PULSE COUNTER. OPERATING INSTRUCTIONS Vr. 02 (ENG) - cod.: ISTR-MTC34ENG02

TC 34 MICROPROCESSOR-BASED DIGITAL ELECTRONIC PULSE COUNTER. OPERATING INSTRUCTIONS Vr. 02 (ENG) - cod.: ISTR-MTC34ENG02 TC 34 MICROPROCESSOR-BASED DIGITAL ELECTRONIC PULSE COUNTER INDEX 1 INSTRUMENT DESCRIPTION 1.1 GENERAL DESCRIPTION 1.2 FRONT PANEL DESCRIPTION 2 PROGRAMMING 2.1 SET POINT PROGRAMMING 2.2 PARAMETERS PROGRAMMING

More information

Keyed latch. Cover. Service Outlet 115VAC, 15A. Plastic base. Unpack. Operator. the Operator

Keyed latch. Cover. Service Outlet 115VAC, 15A. Plastic base. Unpack. Operator. the Operator Service Outlet Quick Start Steps Keyed latch Cover 115VAC, 15A Plastic base Operator Unpack the Operator Site Planning and Operator Installation The illustrations and instructions presented in this guide

More information

RUNner RUNner+ EN Installation and Operating Instructions Serial number

RUNner RUNner+ EN Installation and Operating Instructions Serial number RUNner RUNner+ EN Installation and Operating Instructions 1-32 The programming of power values has been changed. The new procedure is described in the Programming run section in the Commissioning chapter!

More information

Safety light curtain to safeguard the hinge edge IMPORTANT NOTE

Safety light curtain to safeguard the hinge edge IMPORTANT NOTE Installation and Operation Manual CEDES MicroRay Safety light curtain to safeguard the hinge edge English EN 12978 EN 13849-1 IMPORTANT NOTE FOLLOW THE INSTRUCTIONS GIVEN IN THIS MANUAL CAREFULLY. FAILURE

More information

Industrial motor controller for brushed DC motors 12 VDC

Industrial motor controller for brushed DC motors 12 VDC Industrial motor controller for brushed DC motors 12 VDC Design for output currents up to 5 A Control with the following functions: - reversal of direction of rotation - rotational speed control (external)

More information

OPERATION MANUAL ELECTRONIC FREQUENCY CONVERTER HFO E

OPERATION MANUAL ELECTRONIC FREQUENCY CONVERTER HFO E OPERATION MANUAL ELECTRONIC FREQUENCY CONVERTER HFO E Lievers Holland Postbus 103 3640 AC Mijdrecht Tel: +31 (0)297 231900 Fax: +31 (0)297 231909 E mail: info@lieversholland.nl www.lieversholland.nl Operation

More information

Industrial motor controller for brushed DC motors 24 VDC

Industrial motor controller for brushed DC motors 24 VDC Industrial motor controller for brushed DC motors 24 VDC Design for output currents up to 5 A Control with the following functions: - reversal of direction of rotation - open-loop speed control (external)

More information