Practical measurements and IEC/EN rise and fall time during short-circuits at different places of a supply installation
|
|
- Eleanor Sparks
- 5 years ago
- Views:
Transcription
1 Practical measurements and IEC/EN rise and fall time during short-circuits at different places of a supply installation The relating standards: IEC/EN IEC/EN The part IEC/EN of the international IEC/EN 61 series standards defines test methods for immunity testing and test levels for voltage drops, short interruptions and voltage variations. The standard is applicable for devices intended to be connected to the public low power distribution network. The generation of voltage drops the IEC/EN specifies and requires a voltage source with a rise- and fall-time of 1-5µs at 1 load. At a nominal voltage of 23V this means: 23V eff /µs up to 46V eff /µs (=325V/µs up to 65V/µs). The basics about the arising, the effects, remedial actions measuring methods and measurement results of devices to be tested according to IEC/EN are defined in the IEC/TR Ed. 1.. The disturbances are described as phenomena Fig. 1: Equivalent circuit for voltage drops acc. to IEC/EN appearing on public low voltage supply networks and having influence on devices connected to this public grid. This document shall demonstrate, that practically the riseand fall-times of the supply voltage are in the range of 15µs (as described in the IEC/EN in the chapter A2: requirements of the voltage source). One of the main reasons for voltage dips and short interruptions on the public supply network are electric shortcircuits occurring on any point of the supplying grid. Output voltage at no load: ± 5% of the residual voltage value Voltage change with load at the output of the generator: 1% output, A to 16A 8% output, A to 2A 7% output, A to 23A 4% output, A to 4A Output current capability: 16Arms per phase at Urated. The generator must be able to deliver: Peak inrush current capability: Not to be limited by the generator 2A at 8% Urated.for 5s 23A at 7% Urated. for 3s 4A at 4% Urated. for 3s Max. 1A for 25-6V mains Max. 5A for 2-24V mains Max. 25A for 1-12V mains Generator loaded with 1 resistive load Between 1µs and 5µs Generator loaded with 1 resistive load Instantaneous peak overshoot/ undershoot of the actual voltage Voltage rise (and fall) time tr (and tf) during abrupt change Phase shifting: -36 Phase relationship of voltage dips and <± 1 interruptions with the power frequency Zero crossing control of the generator: ± 1 Output impedance Predominatly resistive < (,4+j,25) Even during transitions Table 1: Requirements of the testing voltage source acc. to IEC/EN page 1 of 9 pages
2 In electrical systems short circuits cannot be avoided at all. The amplitude of a voltage drop depends on the distance between monitoring point, short-circuit point and supplying source. This relation is shown in Fig. 2. To meet the practical values described in the technical report IEC/TR the requirements of the testing voltage source of the IEC/EN are well defined in table 1. The theoretical values for riseand fall-time can be calculated by simulation software. For this simulation the parameters for the cable length must be calculated. The definition of the equivalent circuit was given as a short circuit at the load, at the local grid entry point and within the local grid. Fig. 2: Equivalent circuit diagram for short circuit in the supply line The base impedance for the simulation is the mains reference impedance defined in the IEC/EN with,4+j,25 Ohm. The simulation performed the characteristic of a resistive load with 16A nominal current at a nearby (2m) occurring short circuit (with a cable diameter 1,5mm²). The rise- and fall-times of the supplying voltage at short circuit are shown in Fig. 3. And Fig. 4. In Fig. 4 (higher resolution in the time base) the fall-time of the supplying voltage can be seen in a range of 5µs. To verify the simulated values with the rise- and fall-time of the reality several practical measurements have been performed. The measurement results were then compared with the simulation results. Fig. 3: Voltage characteristic during simulation (1ms/DIV) Fig. 4: Voltage characteristic during simulation (5µs/DIV) page 2 of 9 pages
3 PRACTICAL SHORT CIRCUIT MEASUREMENTS To investigate the real occurring rise- and fall-times several practical measurements have been performed. The electrical installation of an existing building was provided. At two points of the installation a laboratory bench was set up. The installation of the building can be described with the following equivalent circuit diagram which was verified through a practical measurement of the installation of the building: Real vermessenes Netz: Teilstück Teilstück 1 Teilstück 2 L18 R26 L2 R28 L21 R29 L24 R uH 8m 5.375uH 18m uH 59m uH 831m V4 VOFF = VAMPL = 325 FREQ = 5 C12 V+.5n C n C16 3.5n V+ C17 3.3u V- V- L19 R uH 69m C14 C15.5n 2.5n 2 L uH L uH 1 1 R32 R3 46m R33 R31 243m 1.531k 1.312k U4 TCLOSE = 15m TTRAN = 1n Abzweig 1 (Labortischgruppe1) Abzweig 2 (Labortischgruppe2) Fig. 5: Equivalent circuit of the building installation The equivalent circuit shows three parts of the installation ( Teilstück -2 ) and the two workbench connections ( Abzweig 1/2"). The input voltage source is an ideal source with 23V nominal voltage at 5Hz. The parts Teilstück 1, Teilstück 2 and Teilstück 3 are representing three parts of the current bar. The workbenches are connected with a supply cable with a length of 5m. Different EUT s were connected to the end of Teilstück 2 with a supply cable of 35m length. The inductive and capacitive parameters of the cabling system were determined using the technical report Simulation of short circuit on different places and influences on rise time of Mr.Lutz, Fa. EMC Partner AG as follows: L 1.75 µh m C.75 µh m The serial impedances of the single cable parts were calculated through loading and measuring the voltage drop over the cable length. page 3 of 9 pages
4 Practical measurement 1: Short circuit between without load fall-time approx. /µs fall-time approx. 3V/µs fall-time approx. 3V/µs Fig. 6: Voltage curve at short circuit measurement 1 (5ms/DIV) 15V Resolution 1µs/DIV 5V -V -5V - -15V 2.97ms 2.98ms 2.99ms 2.1ms 2.11ms 2.12ms 2.13ms 2.14ms 2.15ms 2.16ms 2.17ms V(R35:2,R32:1) V(R33:2,R33:1) Fig. 7: Voltage curve at short circuit measurement 1 (1µs/DIV) 15V Resolution 5µs/DIV 5V -V -5V - -15V 2.8ms 2.1ms 2.12ms 2.14ms 2.16ms 2.18ms 2.2ms 2.22ms 2.24ms 2.26ms 2.28ms 2.3ms V(R35:2,R32:1) V(R33:2,R33:1) Fig. 8: Voltage curve at short circuit measurement 1 (5µs/DIV) page 4 of 9 pages
5 Practical measurement 2: Short circuit between with 6W rectifier load u1 n fall-time approx. 3V/µs fall-time approx. 6V/µs fall-time approx. 35V/µs t1 n1 1 3 t2 n2 1 3 t3 n3 1 3 Fig. 9: Voltage curve at short circuit measurement 2 (5ms/DIV) page 5 of 9 pages
6 Practical measurement 3: Short circuit between with,1uf//268 load fall-time approx. 3V/µs fall-time approx. 8V/µs fall-time approx. 65V/µs u1 n t1 n1 1 3 t2 n2 1 3 t3 n3 1 3 Fig. 1: Voltage curve at short circuit measurement 3 (5ms/DIV) 4V 3V Resolution,5µs/DIV V ms 3.798ms 3.8ms 3.82ms 3.84ms 3.86ms 3.88ms 3.81ms 3.812ms 3.814ms 3.816ms V(R37:2,R32:1) V(R33:2,R33:1) 4V Fig. 11: Voltage curve at short circuit measurement 3 (,5µs/DIV) 3V Resolution 5µs/DIV V ms 3.8ms 3.82ms 3.84ms 3.86ms 3.88ms 3.9ms 3.92ms 3.94ms 3.96ms 3.98ms 4.ms V(R37:2,R32:1) V(R33:2,R33:1) Fig. 12: Voltage curve at short circuit measurement 3 (5µs/DIV) page 6 of 9 pages
7 Practical measurement 4: Short circuit between with 1uF in series 16,5 load fall-time approx. 2V/µs fall-time approx. 4V/µs V t2 n2 1 6 t3 n3 1 6 Fig. 13: Voltage curve at short circuit measurement 4 (5ms/DIV) 3V Resolution,5µs/DIV 25V 15V 5V V 3.794ms 3.796ms 3.798ms 3.8ms 3.82ms 3.84ms 3.86ms 3.88ms 3.81ms 3.812ms 3.814ms V(C17:2,R36:1) V(R33:2,R33:1) 35V Fig. 14: Voltage curve at short circuit measurement 4 (,5µs/DIV) 3V Resolution 5µs/DIV 25V 15V 5V V 3.78ms 3.8ms 3.82ms 3.84ms 3.86ms 3.88ms 3.9ms 3.92ms 3.94ms 3.96ms 3.98ms 4.ms V(C17:2,R36:1) V(R33:2,R33:1) Fig. 15: Voltage curve at short circuit measurement 4 (5µs/DIV) page 7 of 9 pages
8 Practical measurement 5: Short circuit between with,1uf in series 16,5 load fall-time approx. 2V/µs fall-time approx. 4V/µs V t2 n2 1 6 t3 n3 1 6 Fig. 16: Voltage curve at short circuit measurement 5 (5ms/DIV) 3V Resolution,2µs/DIV V ms 3.8ms 3.81ms 3.82ms 3.83ms 3.84ms 3.85ms 3.86ms 3.87ms 3.88ms 3.89ms V(C17:2,R36:1) V(R33:2,R33:1) 4V Fig. 17: Voltage curve at short circuit measurement 5 (,2µs/DIV) 3V Resolution 5µs/DIV V ms 3.8ms 3.82ms 3.84ms 3.86ms 3.88ms 3.9ms 3.92ms 3.94ms 3.96ms 3.98ms 4.ms V(C17:2,R36:1) V(R33:2,R33:1) Fig. 18: Voltage curve at short circuit measurement 5 (5µs/DIV) page 8 of 9 pages
9 Practical measurement 6: Short circuit between L1 and N fall-time approx. 1V/µs fall-time approx. 18V/µs fall-time approx. 15V/µs u1 n t1 n1 1 3 t2 n2 1 3 t3 n3 1 3 Fig. 19: Voltage curve at short circuit measurement 6 (5ms/DIV) Practical measurement 7: Short circuit between L1 and L2 with,1uf//268 load fall-time approx. /µs fall-time approx. 3V/µs fall-time approx. 3V/µs u1 n t1 n1 1 3 t2 n2 1 3 t3 n3 1 3 Fig. 2: Voltage curve at short circuit measurement 7 (5ms/DIV) CONCLUSION: These practical measurements are showing clearly: 1. The nearer the short-circuit appears, so much faster are rise- and fall-times. 2. Directly at the short circuit rise- and fall-times are faster than 1us. 3. Depending on the load and the distance to the short-circuit different rise- and fall-times can be measured, but all of them are between 1-5us. In comparison between simulation and measurement data we can see, that simulation and reality are very close together. The definitions given in the IEC/EN of the preferred voltage source are very important to perform realistic test cycles. Spitzenberger & Spies 216 all data are subject to change page 9 of 9 pages
PAS series of 4-Quadrant Amplifiers
PAS series of 4Quadrant Amplifiers THE REAL 4QUADRANT AMPLIFIER The relating standards: IEC/EN 6132 IEC/EN 6133 IEC/EN 61311 IEC/EN 61312 IEC/EN 614611 IEC/EN 6122 IEC/EN 6144 IEC/EN 6145 IEC/EN 6148 IEC/EN
More informationVoltage Transient Emission Test
Manual For Operation AN 200 Series Voltage Transient Emission Test AN 200 AN 200B The AN 200 is used to evaluate automotive electrical and electronic components for conducted emissions of transients along
More informationAdvanced Test Equipment Rentals ATEC (2832)
Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) 1 MIG Tester Type MIG2000-6 Technical Specification E-MIG2000-6 revised: 07. May 2009 1 MIG Tester Type MIG2000-6 1
More informationEV series of AC voltage amplifiers
EV series of AC voltage amplifiers Wide frequency range AC power amplifier system The applications: - Component testing - Measuring equipment testing - Ignition pulse testing (lighting equipment) High
More informationECE 2274 Pre-Lab for Experiment # 4 Diode Basics and a Rectifier Completed Prior to Coming to Lab
Part I I-V Characteristic Curve ECE 2274 Pre-Lab for Experiment # 4 Diode Basics and a Rectifier Completed Prior to Coming to Lab 1. Construct the circuit shown in figure 4-1. Using a DC Sweep, simulate
More informationETSI EN V2.1.2 ( )
EN 300 132-2 V2.1.2 (2003-09) European Standard (Telecommunications series) Environmental Engineering (EE); Power supply interface at the input to telecommunications equipment; Part 2: Operated by direct
More informationBROADBAND LINEAR AMPLIFIER Model F1020 (models F10A and F20A combined)
BROADBAND LINEAR AMPLIFIER Model F1020 (models F10A and F20A combined) HIGH VOLTAGE FIXED GAIN BROADBAND ±100V 185mA/±150V 150mA 10x/20x DC to ca 1 MHz HIGH SLEW RATE LOW OUTPUT IMPEDANCE 300 V/µs
More informationIEC Electrical fast transient / Burst immunity test
CONDUCTED RF EQUIPMENT POWER AMPLIFIERS IEC 61000-4-4 Electrical fast transient / Burst immunity test IEC 61000-4-4 Electrical fast transient / Burst immunity test Markus Fuhrer Phenomenom open a contact
More informationAPS series of 4-quadrant amplifiers
APS series of 4-quadrant amplifiers 4-QUADRANT VOLTAGE / CURRENT AMPLIFIER Fig. 1: 4-quadrant amplifier APS 1000 NEW: Constant current mode The adjustable and desired output current is automatically regulated
More informationLow Frequency Measuring System
Emission Measurements Low Frequency Measuring System Brief Overview of Phenomena............... 2 Applicable Standards................... 3 Test System Overview.................. 4 Generator Specifications.................
More informationPart 1: General. Part 3: Mechanical loads Part 4: Climatic loads Part 5: Chemical loads
ISO 16750-2 (2012) at a glance Road vehicles. Environmental conditions and testing for electrical and electronic equipment Part 2: Electrical loads The relating standards: ISO 16750-2 (2003) ISO 16750-2
More informationEmerging Standards for EMC Emissions & Immunity
Emerging Standards for EMC Emissions & Immunity Requirements for Industrial, Scientific, Medical & Information Technology Equipment CE Marking requirements are the path to increased market access Powerful
More informationPower Electronics. Exercise: Circuit Feedback
Lehrstuhl für Elektrische Antriebssysteme und Leistungselektronik Technische Universität München Prof Dr-Ing Ralph Kennel Aricsstr 21 Email: eat@eitumde Tel: +49 (0)89 289-28358 D-80333 München Internet:
More informationInsulation Test System
Component Tests Insulation Test System Brief Overview of Phenomena............... 2 Applicable Standards................... 3 Test System Overview.................. 3 Generator Specifications.................
More informationEMC standards. Presented by: Karim Loukil & Kaïs Siala
Training Course on Conformity and Interoperability on Type Approval testing for Mobile Terminals, Homologation Procedures and Market Surveillance, Tunis-Tunisia, from 20 to 24 April 2015 EMC standards
More informationHigh-Voltage Isolation Amplifiers / Shunt Isolators. VariTrans P 29000
High-Voltage Isolation Amplifiers / Shunt Isolators VariTrans P 29000 Compact high-voltage isolators with safe galvanic isolation, VariPower broad-range power supply and genuine calibrated range selection.
More informationImmunity Test System RIS 3000 / RIS 6000 acc. to IEC/EN
Description The setup of a radiated immunity test system can be done in the conventional way with many separate instruments or in a more comfortable and less risky way with our new EMC control unit, type
More informationDUAL CHANNEL BROADBAND LINEAR AMPLIFIER Model A800D
DUAL CHANNEL BROADBAND LINEAR AMPLIFIER Model A800D HIGH VOLTAGE FIXED GAIN BROADBAND 800Vpp 60mA 100x DC to ca 200 khz LOW OUTPUT IMPEDANCE HIGH SLEW RATE
More informationTechnical Specification
LARGEST RANGE OF IMPULSE TESTERS UP TO 100KV/100KA Technical Specification No. E-MIG0603IN2.doc revised: 20.October 2004 1 MIG Tester Type MIG0603IN2 1 MIG Tester Type MIG0603IN2 1 1.1 Introduction 1 2
More informationProduct Specification
MODEL NO. WP507F12 This power supply is a small footprint, AC input power supply. This power supply is capable of supplying 400 watts of output power into 5 DC output voltages. 1.0 INPUT REQUIREMENTS 1.1
More informationDC/DC Converter URA_ZP-6WR3 & URB_ZP-6WR3 Series
/ Converter FEATURES 6W,Ultra wide input, isolated & regulated dual/ single output, DIP package, - converter CB Patent Protection RoHS Wide range of input voltage (4:1) Efficiency up to 88% No-load power
More informationTHE MODULAR SOLUTION FOR 6 KV APPLICATIONS
THE MODULAR SOLUTION FOR 6 KV APPLICATIONS Teseq s new NSG 3060 conducted immunity generator takes the proven, user-friendly design of the highly successful Modula series to a new level. This innovative
More informationCB Patent Protection RoHS
3W, Ultra wide input isolated & regulated single output DC/DC converter Selection Guide Certification Part No. -- URB2403MT-3WR3 Input Voltage (VDC) Output Efficiency 2 Nominal Output Voltage Output Current
More informationCHAPTER-IV EXPERIMENTAL AND SIMULATION PROGRAM
49 CHAPTER-IV EXPERIMENTAL AND SIMULATION PROGRAM 4.0 INTRODUCTION This chapter covers in detail the experimental set up of proposed Z source Matrix (ZSMC) based UPFC and compares with a lab scale model
More informationCombination Wave Test System
Immunity Tests Combination Wave Test System Brief Overview of Phenomena............... 2 Applicable Standards................... 3 Test System Overview.................. 4 Generator Specifications.................
More information08/07/2015
17.5 mm - 1 Solid State Relay 0.7A MUS2 Part number 88827004 Multi-function or mono-function Multi-range Multi-voltage Screw or spring terminals LED status indicator (relay version) Possibility of external
More informationLVA 4-Quadrant Amplifier 1000
LVA 4-Quadrant Amplifier 1 AUTOMOTIVE SUPPLY SIMULATION AT IT S BEST The relating standards: ISO 7637-2/-3 ISO 167-2 ISO 21848 LV 124 VDA 32 (LV 148) SAE J 1113-11 BMW GS 92 BMW GS 924-2-2 BMW GS 926 Ford
More informationEMC TEST REPORT For MPP SOLAR INC Inverter/ Charger Model Number : PIP 4048HS
EMC-E20130903E EMC TEST REPORT For MPP SOLAR INC Inverter/ Charger Model Number : PIP 4048HS Prepared for : MPP SOLAR INC Address : 4F, NO. 50-1, SECTION 1, HSIN-SHENG S. RD. TAIPEI, TAIWAN Prepared by
More informationFEATURES. Nominal Output Voltage and Current(Vo/Io) Max. Capacitive Load (uf) 5V/200mA LS01-15B09SS(-F) 9V/111mA
W, AC/DC converter FEATURES Ultra wide input voltage range: 85-305VAC/70-430VDC AC and DC dual-use (input from the same terminal) Compact size, High power density Output short circuit, over-current protection
More informationAS SERIES (2.00 x 1.6 Package) Up to 20 Watt DC-DC Converter
PRODUCT OVERVIEW The AS series offer up to 20 watts of output power in standard 2.00 x 1.60 x 0.45 inches packages. This series features high efficiency and 1500 Volts of DC isolation. The AS series provides
More informationvia cable Route of signal interferences Shielding against radiation
1. Introduction In the vicinity of electronics and control systems, there is often high powered equipment and cabling. In these situations it is possible that electronic circuits can be affected by these
More information1. General Instructions 2 2. Safety 2 3. Lamp Starting Test Instrument LSTI 5 3
1. General Instructions 2 2. Safety 2 3. Lamp Starting Test Instrument LSTI 5 3 3.1. Components and Connections of the Front Panel (Fig. 1) 5 3.2. Connection of the Rear Panel (Fig. 2) 7 3.3. Operation
More informationImmunity Testing for the CE Mark
Immunity Testing for the CE Mark Summary The European Union (EU) currently has 25 member countries with 2 additional countries to be added in 2007. The total population at that time will be nearly a half
More informationLVA 4-Quadrant Amplifier 5000
LVA 4-Quadrant Amplifier 5 AUTOMOTIVE SUPPLY SIMULATION AT IT S BEST Example: LVA 1 Front panel Extremely low harmonic distortion - even under very non-linear load conditions Very fast slew rate > 2V/µs
More informationAN003. Basic Terms Used for DC Power Supplies. Elaborated by: Marco Geri (R&D Manager - NEXTYS SA.)
AN003 Elaborated by: Marco Geri (R&D Manager - NEXTYS SA.) Rev.1.0 Page 1/5 1 Introduction DC (Direct Current) power supplies are used in various applications related to automation, telecom, industry,
More informationApplication Note. Application for Precision Impedance Meters in a Standards Laboratory. Required Capabilities for Precision Measurements
Application for Precision Impedance Meters in a Standards Laboratory The IET Labs 1689 Precision RLC Digibridge, which measures resistance, capacitance and inductance, has found wide acceptance in production
More informationBROADBAND'LINEAR'AMPLIFIER Model&F10AD
BROADBAND'LINEAR'AMPLIFIER Model&F10AD DUAL'CHANNEL & HIGH&VOLTAGE& FIXED&GAIN& BROADBAND & ±100V&185mA& 10x& DC&to&ca&1&MHz & HIGH&SLEW&RATE& LOW&OUTPUT&IMPEDANCE & 400&V/µs&
More informationCompliance. Safety Approvals USA Canada Europe. Isolation: General. Dimensions. AC Input CN1 Output CN2 Optional CN3. Weight
IEC 1-1-2 4th Edition Compliant BF (Body Floating) Rated Class II Construction for Home Health Care Applications Class I With Functional Ground Connection 3 x 5 Footprint ua @ 264VAC Earth Leakage Current
More informationIntroduction EMC. Filter parameters. Definition of EMC / EMI. X-Capacitor. Sources of EMI. Coupling mechanism. Y-Capacitor.
Introduction to EMC Schurter has over 75 years experience in the electronics and electrical industries, developing and manufacturing components that ensure a clean and safe supply of power. Schurter provides
More informationTEST REPORT DIN V VDE V :2006 Automatic disconnecting device
age 1 of 23 TEST REORT Automatic disconnecting device Report Reference No...: GZ10080033-1 Date of issue...: August 18, 2010 Total number of pages... 23 pages Testing Laboratory...: Address...: Tested
More informationCircuit breakers for direct current applications
Circuit breakers for direct current applications Complementary technical information schneider-electric.com Complementary technical information Circuit breakers for direct current applications Contents
More informationElectromagnetic compatibility Guidance and manufacturer s declaration DIN EN :2007 (IEC :2007)
Compressor set Equipment Under Test (EUT) Type 028 Type 047 Type 052 Type 085 Electromagnetic compatibility Guidance and manufacturer s declaration DIN EN 60601-1-2:2007 (IEC 60601-1-2:2007) 2017 PARI
More informationType CP-S, CP-C & CP-A Switch mode
Switch mode power CP-S, CP-C & CP-A Switch mode Characteristics CP-S and CP-C range Output current 5 A, 10 A and 20 A Integrated power reserve of up to 50 % 5 A and 10 A devices with pluggable connecting
More informationETSI EN V2.2.1 ( )
EN 300 132-2 V2.2.1 (2007-05) European Standard (Telecommunications series) Environmental Engineering (EE); Power supply interface at the input to telecommunications equipment; Part 2: Operated by direct
More informationKOLLMORGEN. Motion Technologies Group. EMC Installation and Application Guidelines for BDS4/5 Goldline Series MB4000H Issue 3
KOLLMORGEN Motion Technologies Group EMC Installation and Application Guidelines for BDS4/5 Goldline Series MB4000H Issue 3 CONTENTS DOCUMENT HISTORY 1 DECLARATION OF CONFORMITY 1 1. INTRODUCTION 2 2.
More information05/09/2012
17.5 mm EMER8 Part number 88829198 Multifunction or mono-function Multi-range (7 ranges) Multi-voltage or single voltage Screw terminals LED status indicator (1 voltage present LED, 1 timer ON LED) Option
More informationTopology: Active Clamp Forward Device: UCC2897A Unless otherwise mentioned the measurements were done with about 2A output current.
1 Startup... 2 2 Shutdown... 4 3 Efficiency... 6 4 Load Regulation... 7 5 Line Regulation... 8 6 Output Ripple Voltage... 9 7 Input Ripple Voltage... 10 8 Load Transients... 11 9 Control Loop Frequency
More informationPRODUCT OVERVIEW. APPLICATIONS: Distributed Power Architectures Mobile telecommunication Industrial applications Battery operated equipment
FEATURES Industry Standard 24-Pin DIP package 15Watts Isolated Output 4:1 Input Range Regulated Outputs Up to 90 % Efficiency Low No Load Power Consumption -40 C to +85 C industrial temperature range Negative
More informationRegulatory authority use EMC PARTNER's HAR1000 to enforce Harmonic and Flicker CE requirements in Germany
Emission Measurements Regulatory authority use EMC PARTNER's HAR1000 to enforce Harmonic and Flicker CE requirements in Germany Martin Lutz, Reto Casanova, Nicholas Wright Contents 1. Introduction... 2
More informationUNIVERSITY OF TECHNOLOGY, JAMAICA School of Engineering -
UNIVERSITY OF TECHNOLOGY, JAMAICA School of Engineering - Electrical Engineering Science Laboratory Manual Table of Contents Safety Rules and Operating Procedures... 3 Troubleshooting Hints... 4 Experiment
More informationURA_(X)D-10WR2& URB_(X)D-10WR2 Series 10W,ULTRA-WIDE INPUT ISOLATED& REGULATED DUAL/SINGLE OUTPUT DIP PACKAGING, DC-DC CONVERTER
URA_(X)D-0WR& URB_(X)D-0WR Series 0W,ULTRA-WIDE INPUT ISOLATED& REGULATED DUAL/SINGLE OUTPUT DIP PACKAGING, - CONVERTER Patent Protection RoHS PART NUMBER SYSTEM URB405(X)D-0WR Rated Power Package Style
More informationTechnical Specification
LARGEST RANGE OF IMPULSE TESTERS UP TO 100KV/100KA Technical Specification E-MIG1203CWG revised: 22. June 2003 1 MIG Tester Type MIG1203CWG 1 MIG Tester Type MIG1203CWG 1 1.1 Introduction 1 2 General 2
More informationVRA_LD-15WR2 & VRB_LD-15WR2 SERIES 15W,WIDE INPUT, ISOLATED & REGULATED DUAL/SINGLE OUTPUT DC-DC CONVERTER
VRA_LD-5WR & VRB_LD-5WR SERIES 5W,WIDE INPUT, ISOLATED & REGULATED DUAL/SINGLE OUTPUT - CONVERTER PART NUMBER SYSTEM VRB5LD-5WR SELECTION GUIDE Model Number Rated Power Package Style Output Voltage Input
More informationSafety EMC Environment Quality assurance Secretary: Klaus-Peter Bretz
77/457/CD COMMITTEE DRAFT (CD) IEC/TC or SC: 77 Title of TC/SC: Electromagnetic Compatibility Also of interest to the following committees CISPR H Proposed horizontal standard Project number IEC 61000-6-2
More informationInsulation Test System
Component Tests Insulation Test System Brief Overview of Phenomena............... 2 Applicable Standards................... 3 Test System Overview.................. 3 Generator Specifications.................
More informationABB DRIVES Technical guide No. 6 Guide to harmonics with AC drives
ABB DRIVES Technical guide No. 6 Guide to harmonics with AC drives 2 TECHNICAL GUIDE NO. 6 GUIDE TO HARMONICS WITH AC DRIVES Guide to harmonics This guide is part of ABB s technical guide series, describing
More informationURA_(X)D-10WR2& URB_(X)D-10WR2 Series 10W,ULTRA-WIDE INPUT ISOLATED& REGULATED DUAL/SINGLE OUTPUT DIP PACKAGING, DC-DC CONVERTER
URA_(X)D-WR& URB_(X)D-WR Series W,ULTRA-WIDE INPUT ISOLATED& REGULATED DUAL/SINGLE OUTPUT DIP PACKAGING, - CONVERTER Patent Protection RoHS PART NUMBER SYSTEM URB5(X)D-WR Rated Power Package Style No CTRL
More informationInstallation and Operational Instructions for ROBA -multiswitch Type 019._00.2
Guidelines on the Declaration of Conformity A conformity evaluation has been carried out for the product in terms of the EU Low Voltage Directive 2014/35/ EU and the Electromagnetic Compatibility (EMC)
More informationVRA_LD-20WR2 & VRB_LD-20WR2 SERIES 20W,WIDE INPUT, ISOLATED & REGULATED DUAL/SINGLE OUTPUT DC-DC CONVERTER
VRA_LD-WR & VRB_LD-WR SERIES W,WIDE INPUT, ISOLATED & REGULATED DUAL/SINGLE OUTPUT - CONVERTER Patent Protection RoHS PART NUMBER SYSTEM VRB5LD-WR SELECTION GUIDE Model Number Rated Power Package Style
More information9 to 36 Vdc and 18 to 75 Vdc input, 3.3 to 15 Vdc Single Output, 40W. Features
PXF40xxWSxx Single Output DC/DC Converter 9 to 36 Vdc and 18 to 75 Vdc input, 3.3 to 15 Vdc Single Output, 40W Features Single output current up to 10A 40 watts maximum output power 4:1 ultra wide input
More informationUNIVERSITY OF TECHNOLOGY, JAMAICA SCHOOL OF ENGENEERING. Electrical Engineering Science. Laboratory Manual
UNIVERSITY OF TECHNOLOGY, JAMAICA SCHOOL OF ENGENEERING Electrical Engineering Science Laboratory Manual Table of Contents Experiment #1 OHM S LAW... 3 Experiment # 2 SERIES AND PARALLEL CIRCUITS... 8
More informationVaristor Testing. Introduction. Measurement of Varistor Characteristics [1] Application Note January 1998 AN9773.
Varistor Testing Application Note January 1998 AN9773 Introduction This note details the common tests of varistor parameters and describes suitable test methods using simplified test circuits. All tests
More informationSpecification for Conducted Emission Test
1 of 10 1. EMI Receiver Frequency range 9kHz 7.0 GHz Measurement time per frequency 10 µs to 100 s time sweep, span = 0 Hz - 1 µs to 16000 s Sweep time in steps of 5 % frequency sweep, span 10 Hz - 2.5
More informationAA SERIES (1 x 1 Package) Up to 10 Watt DC-DC Converter
FEATURES Industry standard footprint (1 inch X 1 inch) Regulated Outputs, Fixed Switching Frequency Up to 87 % Efficiency Low No Load Power Consumption Designed for use without tantalum capacitors -40
More informationCaution - leakage currents! Leakage currents in fault-current protected environments
Caution - leakage currents! Leakage currents in fault-current protected environments Herbert Blum Product Manager EMC > General situation > Leakage current vs. fault current > Leakage currents from frequency
More informationError vs. Uncertainty Historical Perspective
1 Error vs. Uncertainty Historical Perspective Jim McBride Chairman PSIM Committee Vice-Chairman HVTT Subcommittee IEEE PES SPDC Fall 2017 Clearwater, FL Discussions on Uncertainty PSIM - HVTT Subcommittee
More informationTraining Course on Conformity and Interoperability, Tunis-Tunisia, from 14 to 18 December EMC standards
Training Course on Conformity and Interoperability, Tunis-Tunisia, from 14 to 18 December 2015 EMC standards Presented by: Karim Loukil & Kaïs Siala Kaim.wakil@cert.mincom.tn Kais.siala@cert.mincom.tn
More informationExamples Paper 3B3/4 DC-AC Inverters, Resonant Converter Circuits. dc to ac converters
Straightforward questions are marked! Tripos standard questions are marked * Examples Paper 3B3/4 DC-AC Inverters, Resonant Converter Circuits dc to ac converters! 1. A three-phase bridge converter using
More informationTraining Course on Conformity and Interoperability, Tunis-Tunisia, from 11 to 15 April EMC standards
Training Course on Conformity and Interoperability, Tunis-Tunisia, from 11 to 15 April 2016 EMC standards Presented by: Karim Loukil & Kaïs Siala Karim.wakil@cert.mincom.tn Kais.siala@cert.mincom.tn Page
More informationFEATURES. Nominal Output Voltage and Current(Vo/Io) Max. Capacitive Load (uf) LS03-15B03SR2S(-F)* 1.98W 3.3V/600mA LS03-15B05SR2S(-F)
3W, AC/DC converter CB RoHS FEATURES Ultra wide input voltage range: 85-305VAC/70-430VDC Output short circuit, over-current protection High efficiency, high power density Low power consumption, green power
More informationSelf Oscillating 25W CFL Lamp Circuit
APPLICATION NOTE Self Oscillating 25W CFL Lamp Circuit TP97036.2/F5.5 Abstract A description is given of a self oscillating CFL circuit (demo board PR39922), which is able to drive a standard Osram Dulux
More informationOne-day Conference 18 March Power Supply, EMC and Signalling, in Railway Systems
One-day Conference 18 March 2017 Power Supply, EMC and Signalling, in Railway Systems EMC Management and Related Technical Aspects in Railway Systems By Dr Peter S W LEUNG http://www.ee.cityu.edu.hk/~pswleung/
More informationCERTIFICATE OF CALIBRATION
CERTIFICATE OF CALIBRATION Issued by: Pico Technology Ltd. Certificate Number: 9999 of: James House, Colmworth Business Park, St. Neots, Cambridgeshire, Signature: PE19 8YP UNITED KINGDOM Tel: +44 (0)
More informationPXD30-xxWS-xx-Single Output DC/DC Converters
PXD30-xxWS-xx-Single Output DC/DC Converters 9 to 36 Vdc and 18 to 75 Vdc input, 1.5 to 15 Vdc Single Output, 30W Applications Wireless Network Telecom / Datacom Industry Control System Measurement Semiconductor
More informationA PROTOCOL TO TEST THE SENSITIVITY OF LIGHTING EQUIPMENT TO VOLTAGE FLUCTUATIONS
A PROTOCOL TO TEST THE SENSITIVITY OF LIGHTING EQUIPMENT TO VOLTAGE FLUCTUATIONS José Julio GUTIERREZ Pierre BEECKMAN Izaskun AZCARATE University of the Basque Country Philips Innovation Services University
More informationDC/DC Converter URE_P-6WR3 & URF_P-6WR3 Series
DC/DC Converter 6W,Ultra wide input isolated & regulated dual/single FEATURES output, DIP package, DC/DC converter Wide input voltage range (4:1) High efficiency up to 88% No-load power consumption as
More informationConducted Immunity Testing
EMC PARTNER COMPLETE TEST SOLUTIONS FOR Conducted Immunity Testing This document has been optimized for electronic media Accredited Calibration Quality at EMC PARTNER is based on an ISO 9001 management
More informationECE 2006 University of Minnesota Duluth Lab 11. AC Circuits
1. Objective AC Circuits In this lab, the student will study sinusoidal voltages and currents in order to understand frequency, period, effective value, instantaneous power and average power. Also, the
More informationSAMPLE: EXPERIMENT 2 Series RLC Circuit / Bode Plot
SAMPLE: EXPERIMENT 2 Series RLC Circuit / Bode Plot ---------------------------------------------------------------------------------------------------- This experiment is an excerpt from: Electric Experiments
More informationFlexRay Communications System. Physical Layer Common mode Choke EMC Evaluation Specification. Version 2.1
FlexRay Communications System Physical Layer Common mode Choke EMC Evaluation Specification Version 2.1 Disclaimer DISCLAIMER This specification as released by the FlexRay Consortium is intended for the
More informationLVA series of 4-Quadrant amplifiers
LVA series of 4-Quadrant amplifiers AUTOMOTIVE SUPPLY SIMULATION AT IT S BEST LVA 1 Front panel Extremely low harmonic distortion - even under very non-linear load conditions Very fast slew rate > 2V/µs
More informationCP-T range Product group picture
Product group picture /1 ABB Catalog Electronic Products and Relays 1/1 2CDC 110 00 C09 Table of contents CP-T range Product group picture /1 Table of contents /2 Benefits and advantages / Ordering details
More informationInstallation and Operational Instructions for ROBA -switch Type 017._00.2
OBA -switch Type 017._00.2 Guidelines on the Declaration of Conformity A conformity evaluation has been carried out for the product in terms of the EC Low Voltage Directive 2014/35/ EC and the EMC Directive
More informationHigh Current Amplifier
High Current Amplifier - Introduction High Current Amplifier High current amplifier is often a very useful piece of instrument to have in the lab. It is very handy for increasing the current driving capability
More informationUncertainties of immunity measurements
Uncertainties of immunity measurements DTI-NMSPU project R2.2b1 Annex A Description of the circuit model (conducted immunity) Annex A Description of the circuit model (conducted immunity) Annex A Description
More informationPQ Monitoring Standards
Characterization of Power Quality Events Charles Perry, EPRI Chair, Task Force for PQ Characterization E. R. Randy Collins, Clemson University Chair, Working Group for Monitoring Electric Power Quality
More informationECE 2274 Diode Basics and a Rectifier Completed Prior to Coming to Lab
ECE 2274 Diode Basics and a Rectifier Completed Prior to Coming to Lab Perlab: Part I I-V Characteristic Curve for the 1. Construct the circuit shown in figure 1. Using a DC Sweep, simulate in LTspice
More informationELEC 0017: ELECTROMAGNETIC COMPATIBILITY LABORATORY SESSIONS
Academic Year 2015-2016 ELEC 0017: ELECTROMAGNETIC COMPATIBILITY LABORATORY SESSIONS V. BEAUVOIS P. BEERTEN C. GEUZAINE 1 CONTENTS: EMC laboratory session 1: EMC tests of a commercial Christmas LED light
More informationAC/DC Converter LD20-26Bxx Series
20W, AC/DC converter RoHS FEATURES Ultra wide input voltage range: 90-528VAC/100-745VDC Regulated output, Low ripple & noise Operating temperature range: -40 to +70 Output short circuit, over-current,
More informationEMC Seminar Series All about EMC Testing and Measurement Seminar 1
EMC Seminar Series All about EMC Testing and Measurement Seminar 1 Introduction to EMC Conducted Immunity Jeffrey Tsang Organized by : Department of Electronic Engineering 1 Basic Immunity Standards: IEC
More informationSTRATO 70W LED P DESCRIPTION KEY FEATURES APPLICATIONS AND BENEFITS MODEL CODING AND OUTPUT RATINGS TRC ELECTRONICS, INC
STRATO 70W LED P S DESCRIPTION STRATO switch mode driver technology is designed to generate one constant voltage output from a wide range AC input. The size and performance of these products make them
More informationETSI EN V2.5.1 ( )
EN 300 132-2 V2.5.1 (2016-10) EUROPEAN STANDARD Environmental Engineering (EE); Power supply interface at the input to telecommunications and datacom (ICT) equipment; Part 2: Operated by -48 V direct current
More informationXR1 Rotor Earth Fault Relay. Manual XR1 (Revision C)
XR1 Rotor Earth Fault Relay Manual XR1 (Revision C) Woodward Manual XR1 (EN) Woodward Governor Company reserves the right to update any portion of this publication at any time. Information provided by
More informationAC/DC Converter LS01-15BXXSS Series
1W, AC/DC converter RoHS Model marking with number, such as 0105 means FEATURES Input voltage range: 85-264VAC/-0VDC Over current protection and short circuit protection High, high power density Low power
More informationMEASUREMENT OF VOLTAGE INSTABILITIES CAUSED BY INVERTERS IN WEAK GRIDS
MEASUREMENT OF VOLTAGE INSTABILITIES CAUSED BY INVERTERS IN WEAK GRIDS Michael Höckel Andreas Gut Michel Arnal BFH Switzerland BFH Switzerland BKW Switzerland michael.hoekel@bfh.ch andreas.gut@bfh.ch michel.arnal@bkw.ch
More informationDC/DC Converter URA_YMD-10WR3 & URB_YMD-10WR3 Series
10W, Ultra wide input isolated & regulated dual/single output,dip packaging, DC-DC converter CB Patent Protection RoHS FEATURES Ultra wide input voltage range (4:1) High efficiency up to 88% No-load power
More informationTitle. Description. Date 16 th August, Revision 1.1 RD W Telecoms DC/DC PSU Input : 37Vdc to 60Vdc Output : 32V/10A
Title Description RD008 320W Telecoms DC/DC PSU Input : 37Vdc to 60Vdc Output : 32V/10A Date 16 th August, 2007 Revision 1.1 WWW.ConverterTechnology.CO.UK RD008 320W Push-Pull Converter August 16, 2007
More informationTypes of EMC measures
Training Course on Conformity and Interoperability on Type Approval testing for Mobile Terminals, Homologation Procedures and Market Surveillance, Tunis-Tunisia, from 20 to 24 April 2015 EMC standards
More informationSchottky Barrier Rectifiers
Schottky Barrier Rectifiers FEATURES Guardring for overvoltage protection Very small conduction losses Extremely fast switching Low forward voltage drop DO-204AL (DO-4) High frequency operation Solder
More informationDA45C USB-PD. Product Descriptions. 45 Watts
DA45C USB-PD 45 Watts AC-DC Adapter Page 1 Total Power: 45 Watts Input Voltage: 100-240Vac # of Outputs: Single Output Voltages: 5, 9V, 15V & 20Vdc (Changeable) Main Features Small Size 58L x 40.2W x 27H
More information