Damcles 2404i Inputs 1 8 Each blue terminal is shared by tw inputs. POWER 12V supply (+U / GND) ETHERNET Link & Activity Inputs 17 24 Each blue terminal is shared by tw inputs. Cnfiguratin Default: DIP1= Off DIP2= Off RS-232 Serial prt cnfiguratin, temperature sensr POWER 12V supply (+U / GND) Outputs: relays 1 4, each utput has a NO (Nrmally Open) and a NC (Nrmally Clsed) relay cntact. Inputs 9 16 Each blue terminal is shared by tw inputs. Output Off IN9 IN10 NO NC Output On IN9 = 1 (On) IN10 = 0 (Off) NO NC
1) Cnnecting the cables Turn the unit upside dwn and write dwn its MAC address that is printed n the label. Set the switches: DIP1=Off, DIP2=Off, remaining DIP switches d nt matter. Cnnect the unit t the Ethernet (with a patch cable t a switch, crss-ver cable t a PC), RJ-45 prt. Plug the pwer adapter int a mains utlet and cnnect it t the Damcles pwer cnnectr. The green POWER LED lights up. If the Ethernet cnnectin wrks prperly, the LINK LED lights up after a shrt while, and then flashes whenever data are transferred (activity indicatin). 2) Cnfiguring the IP address UDP Cnfig UDP Cnfig utility rt directry f the supplied CD (Windws and Linux versins). Available fr dwnlad at www.hwgrup.cm Sftware > UDP Cnfig. Click the icn t launch UDP Cnfig. The prgram autmatically lks fr cnnected devices. T search fr devices, click the Find Devices icn. The prgram searches fr devices in yur lcal netwrk. Individual Pseidn units are identified by their MAC addresses (printed n the label at the bttm side f the unit). Duble-click a MAC address t pen a basic cnfiguratin dialg. Cnfigure netwrk parameters IP address / HTTP prt (80 by default) Netwrk mask Gateway IP address fr yur netwrk Device name (ptinal) Click the Apply Changes buttn t save the settings. Ntes: T reset the device t factry defaults, tggle DIP1 several times within 5 secnds after pwer-up. N cnfiguratin changes can be stred while DIP2=On. T change the IP address, set DIP2=Off.
3) Cnfiguring the IP address UDP Cnfig The UDP Cnfig utility is lcated in the rt flder f the CD, r it is available fr dwnlad at www.hw-grup.cm. Run UDP Cnfig. The prgram autmatically searches fr cnnected devices. Duble click The prgram lks fr devices n yur lcal netwrk. T identify a particular Damcles unit, lk at the MAC address n the label at the bttm f the unit. Duble-click a MAC address t pen a basic cnfiguratin dialg. Set the IP address HTTP Prt Netwrk mask Gateway IP address Device name (ptinal) Cautin: If yu dn t knw these details r are nt sure, please cntact yur netwrk administratr. Click the Apply Changes buttn t save yur changes. Nte: Alternatively, yu may use the fllwing utilities t cnfigure the IP address: UDP Cnfig fr Linux Hercules utility (/Hercules.exe) (UDP Setup r serial prt terminal)
RS-232 serial prt (any terminal prgram, 9600 8N1, DIP1=ON, restart) 4) WWW interface f the device T pen the WWW interface f the device: Enter the IP address int a web brwser Click the IP address in UDP Cnfig Click the underlined IP address in UDP SETUP The WWW page displays current status f inputs and utputs. Click the Graphic Flash SETUP link t pen the graphical cnfiguratin interface (Flash Setup). Device IP address Overview f dry cntact inputs Output states, names and unique IDs Device name Detailed cnfiguratin in Flash Setup Descriptin f the values.xml file Descriptin f SNMP structures in the MIB / OID list
5) Flash SETUP T pen the FLASH interface, FLASH supprt needs t be installed n yur PC. If the cmputer is cnnected t the Internet, the needed plug-in is dwnladed autmatically. Flash Setup allws yu t: Cntrl utputs Assign names t inputs and utputs and their states Watch current sensr readings (refreshed autmatically at predefined intervals) Set SNMP parameters (Cmmunity names & rights), define target IPs fr SNMP traps that are sent upn alarm Set device name, passwrd, and secure IP address range and mre...
6) Sending e-mail Alarms and e-mail alerting Damcles supprts alerts t changes n ne particular input Single Alarm, as well as alerts t a certain input cmbinatin Grup Alarm. Alarm state (On r Off) t be ntified by sending an e-mail r SNMP Trap can be cnfigured fr each individual input. >> Inputs tab, green Single Alarm clumn. Each individual Alarm needs t be activated >> Inputs tab, Enable clumn. Fr each Alarm, a target destinatin needs t be set. Fur SNMP Trap targets (named A, B, C, D) and tw e-mail targets (named E, F) are available >> Alarms tab, SNMP r E-mail clumn. Destinatins A thrugh D (fr SNMP) and E, F fr e-mail need t be cnfigured and enabled. Testing e-mail T send an e-mail directly frm the device, check the fllwing settings. Gateway IP address >> Setup tab, Netwrk Settings pane, Gateway field. DNS server settings >> Setup tab, Netwrk Settings pane, DNS fields. SMTP server settings >> Email & SNMP tab, Email Settings pane. Send a test e-mail t verify crrect peratin >> Email & SNMP tab, Email Settings pane.
7) Cntrlling inputs / utputs with custm SW M2M prtcls Yur custm sftware can use SNMP, XML r Mdbus/TCP prtcls t cntrl utputs. PsDamIO Fr simple utput cntrl using the cmmand line, the HWg PsDamIO utility can be used. PsDamIO uplads a XML file with the requested utput states t a specified IP address. The utility is available fr Windws and Linux, including surce cde, as a part f ur HWg-SDK (available fr dwnlad at ur website). PD Trigger T react t alarms and t cntrl utputs, the PD Trigger applicatin can be used. It reacts t incming Alarm alerts by, fr instance, activating a netwrked relay. (Available fr dwnlad at ur website.) Nte: Unauthrized changes f utput states can be prevented by requiring a passwrd r cnfiguring a range f allwed IP addresses, r cmpletely denied by switching DIP 2 t ON. When DIP 2 is ON, utput states cannt be changed.
CapTemp Sftware fr cllecting and analyzing sensrs readings in fd prcessing and ther industries. CapTemp and MnTemp is a pair f utilities t mnitr prductin prcesses. The prgrams can supervise all sensrs by (temperature and humidity sensrs, cntacts, etc) as well as sensrs by ther manufacturers. CapTemp lgs the readings int an internal database, displays several mst recent nes, and prcesses cnditins and alarms. Alerts t readings within an alarm range are sent by e- mail, r by SMS via a GSM mdem cnnected t the PC. MnTemp subsequently prcesses data stred in the database, generates graphic reprts, histgrams, and ISO r HACCP quality assurance prtcls. CapTemp supprts Pseidn, Damcles and I/O Cntrller prducts Alarm alerts are sent by e-mail r SMS (GSM mdem) Well-designed graphical envirnment Supprts cnditins and rules fr simple cntrl tasks Evaluatin versin functins fr 21 days withut restrictins
Technical specificatins Ethernet: RJ45 10BASE-T/10 Mbit/s 24 digital inputs: Shared terminal fr every tw inputs 4 digital utputs: Relay cntact utputs, each utput cntrls a NO and a NC cntact Prt 1: RS-232 (DB9M cnnectr), device cnfiguratin, temperature sensr cnnectin Cnfiguratin DIP switches DIP1 = On activates Serial SETUP mde (9600 8N1) Restres factry defaults when 5x tggled within 5 secnds after pwer up DIP2 = On prevents changes in the cnfiguratin Device features Alarming when a reading threshld is exceeded Remte mnitring f input states and temperature sensr Pulse cunter fr every input Remte utput cntrl Lcal utput cntrl with Alarm cnditins (Grup 1 and Grup 2) Pwer supply: +12V / 250 ma Dimensins: 116 x 179 x 46 [mm] LED indicatrs: Pwer, LINK, STATUS, ALARM 60 12-24V IN1 IN2 IN3 IN4 IN5 IN6 IN7 IN8 IN17 IN18 IN19 IN19 IN20 +U GND NC1 NO1 NC2 NO2 31 IN1 IN2 IN3 IN4 IN5 IN6 IN7 IN9 IN10 IN11 IN12 IN13 IN14 IN15 IN16 IN8 IN17 IN18 IN19 IN20 OUT1 OUT2 Damcles 2404i IN21 IN22 IN23 IN24 OUT3 OUT4 STATUS ALARM LINK POWER ON 1 2 SECURITY SETUP 1 30 NOT USED IN9 IN10 IN11 IN12 IN13 IN14 IN15 IN16 IN21 IN22 IN23 IN24 +U GND NO3 NC3 NO4 NC4 Cmmn grund fr a pair f inputs IN1.. IN24 Inputs I1 thrugh I24, cnnected against a cmmn grund () +U +12 t 24 VDC supply GND Pwer supply grund, cnnected t the cmmn grunds NO, NC, Electrically islated relay utputs
Ethernet prt + Interface RJ45 (10BASE-T) 10 Mbps r 10/100 Mbps netwrk cmpatible + Supprted prtcls IP: ARP, TCP/IP (HTTP, Mdbus ver TCP), UDP/IP (SNMP) + SNMP cmpatibility Ver:1.00 cmpatible, sme parts f the ver 2.0 implemented Serial prt 1 DB9M - RS-232 + Cnnectr Cannn 9 male (DB9M) + Pinut Standard IBM PC - DB9M (RxD,TxD,RTS,CTS, GND) + Usage Serial setup, 9600 8N1 Temperature sensr (max 1 sensr) + Max. distance Up t 2m Digital Inputs + Input type 24 Cntact Input (Ready t Dry cntact r Wet cntact) + Islatin Optislated (1kV) + Wet cntact Lgic 0: 0-3V / Lgic 1: 5-30V + Input current Min current 4mA, max current 50 ma + Pulse cunter Each Digital input, min pulse width 100 ms Pwer vilatin memry fr all input cunters + Max. distance Up t 30m Digital Outputs + Output type 4 Relay cntacts (NC, NO every utput) + Max. lad up t 4A/24V + State Pwer up state (NO state memry) LED Status indicatrs + POWER Green - pwer OK + LINK & Activity Green - Ethernet cnnectivity + Alarm & RS-232 Setup Red - blinking - Device is in the RS-232 Setup mde DIP SWITCH cnfiguratin ON = RS-232 Setup mde ver Prt 1 (RS-232 mde nly) OFF = Run mde + DIP1 - RS--232 Setup mde Lad defaults: Tggle 3 times during first 5 secnds after device pwer-up t lad default settings. ON = Security mde - remte cnfiguratin disabled + DIP2 - Security OFF = Nn-Security mde - remte cnfiguratin enabled + DIP3-8 Nt used Physical parameters + Vltage requirements 12-24 V/ 600 ma DC + Pwer cnnectin - caxial pwer cnnectr (barrel, inner 2.5 mm uter 16.3 mm) - cnnect pwer directly t the terminal bard (pin 15,16 and 65, 66) + Dimensins / Weight 116 x 179 x 46 [mm] / 500 g + Temperature -10 C t 60 C
Mechanical dimensins
DO Outputs Each utput cntrls tw independent relay cntacts: ne Nrmally Open cntact (NO, pen when the pwer is ff and after startup), and ne Nrmally Clsed cntact (NC, clsed when the pwer is ff and after startup). Bth cntacts ale electrically islated; hence, tw separate devices (ne cnnected t the NO terminals, the ther t the NC terminals) can be cnnected t a single utput. Cntact state (clsed / pen) is indicated by the crrespnding LED. NO NC The picture shws an example f cnnecting a 12V light bulb, pwered frm the same surce as the unit and cntrlled by the Nrmally Open cntact f utput N. 4. NO 29 30 Pwer +U GND 12V Pwer DI Inputs Digital inputs can be cnnected t external vltage, r t dry cntacts (using the recmmended wiring). The inputs are electrically islated frm the device supply vltage, unless the same supply is used t cntrl them. Uncnnected inputs read as 0 (Off). Discnnected sensr detectin: Nne, discnnected sensr reads as O (Off). Activated inputs read as 1 (On), maximum resistance is given by the switching current and driving vltage. Fr a 12V supply, the resistance must be less than 3kΩ. Fr a 24V supply, the resistance must be less than 7kΩ. Maximum wiring length: 50 m Supprted sensrs: Any cntact withut external vltage (dry cntact) Plling perid: 800 ms Range f sensr IDs: Inputs use IDs frm 1 t 24 Sensr names: An input can be named using up t 12 characters State names: Input state (On and Off) can be named with up t 6 characters (e.g. Fuel Tank 14 Full / Empty )
Dry cntact I7 52 - I8 51-55 Driving an input against the supply vltage I7 48 - +U Pwer GND 64 63 + - 12V Pwer
Updating the firmware ver the WEB Uplad the firmware in a.hwg file ver http t http://x.x.x.x/uplad/. Cnnectin prblems etc. must be avided during file transfer. If the update fails, uplad the firmware ver RS-232. Firmware in the.hwg frmat is available at ur website, r n the supplied CD. TIP Fr a cmplete descriptin f the Flash Setup user interface and fr further details, see the detailed manual fr the Damcles line f prducts.