ZS8.4 Air-insulated medium voltage switchgear
|
|
- Janice Dorsey
- 5 years ago
- Views:
Transcription
1 ZS8.4 Air-insulated medium voltage switchgear
2 Power products from ABB Future-proof solutions ABB provides utility, industrial and commercial customers with safe, reliable and smart technologies for the distribution of electricity. This extensive global offering includes distribution automation products, switching, limiting, measuring and sensing devices, switchgear, modular substation packages and related services. ABB offers innovative and fully-integrated compact medium voltage switchgear concepts that enable customers operating in today s increasingly competitive demanding markets to receive the maximum return on investment in their vital network assets. Air-insulated switchpanels from ABB ABB s ZS8.4 range is designed to provide maximum flexibility and the highest possible safety for circuit-breaker systems or switch-disconnector installations, using either conventional instrument transformers or modern sensor technology. Developed to meet the specific needs of medium voltage switchgear users in every respect, ZS8.4 delivers perfect power distribution. A strong solution for every market Customers throughout Europe rely on ABB s ZS8.4 family of air-insulated switchgear to provide the ideal, flexible solution for virtually any application. 2 ZS8.4 Air-insulated medium voltage switchgear
3 Simply universal Flexible safe economical The main scope of application for ZS8.4 switchgear has, in recent years, shifted increasingly to the primary distribution level with circuit-breakers. It is an independent product line targeted at the interface between secondary and primary distribution level. The majority of ZS8.4 installations are for industrial customers, however it is also specified for power supply and municipal services applications. In a wide range of situations, including metros, shopping malls, manufacturing facilities and offices ZS8.4 with vacuum circuitbreaker, switch-disconnector or vacuum contactor is the costeffective route to ensuring a safe and reliable power supply. Today there is an installed base of more than ZS8.4- panels in Central Europe, Asia and the Gulf States, with the majority found in Germany. ZS8.4 combines mature, well-established switchgear technology with modern manufacturing processes to deliver the optimum costeffective solution. ABB s ongoing product development process has resulted in the addition of a contactor panel as well as panels with expanded automatic protection against accidental contact. ZS8.4 Air-insulated medium voltage switchgear 3
4 Details in focus With comprehensive interlocks and integrated protection against accidental contact with the busbars, ZS8.4 offers a unique safety concept. For example, mutual interlocking of the devices practically precludes maloperation. Maintenance-free switching devices and the sealed encapsulation ensure permanently reliable operation. 4 ZS8.4 Air-insulated medium voltage switchgear
5 Automatic protection against accidental contact: By shutter in panels with tee-off partitioning, and by sliding plate in panels without tee-off partitioning. Three function areas are mutually partitioned - low voltage area, busbar area and MV area with circuit-breaker area, switch-disconnector area, contactor area and cable termination area. ZS8.4 Air-insulated medium voltage switchgear 5
6 Details in focus The optimal solution: - Vacuum circuit-breaker - Switch-disconnector - Vacuum contactor - Earthing switch The safety and availability of the ZS8.4 switchgear are further enhanced by use of the tee-off partitioning which protects the busbar area in case of internal faults in the device and cable termination areas. Rod-type switch-disconnector type C4 - High breaking and making capacity - Reliable arc quenching by combining the air blasting and the hard gas principle - Low maintenance - Capable of switching capacitive currents under earth fault conditions 6 ZS8.4 Air-insulated medium voltage switchgear
7 Circuit-breaker (VD4 / VM1) - VD4 minimum-maintenance - VM1 maintenance-free - High availability - High number of operating cycles - Very compact dimensions - Poles sealed for lifetime Vacuum contactor - Up to switching operations - Actuator with permanent magnets - Maintenance-free - Specific vacuum arcing chambers ZS8.4 Air-insulated medium voltage switchgear 7
8 Peripherals Protection and control with 615 series relay - Circuit-breaker control at the protection unit - Comprehensive feeder protection function from feeder protection REF 615 to pilot-wire differential relay RED615, further devices - 11 user-programmable LEDs - Up to 17 binary inputs and 12 binary outputs - Interlocking function - Three-channel arc protection against personnel injury - IEC communication with GOOSE or conventional messaging - Practical withdrawable component - Optimal solution for ZS8.4 for manually driven earthing switch and cut-off Controlling and operation - Combined protection and control device, e.g. REF542 plus - Conventional control engineering as desired for - Electromechanical bar position indication - Illuminated LED bar position indication - Customer specified multifunction device Protection relaying - Multifunctional protection of DMT by differential protection up to distance protection - Discrete protection units, e.g. REF610 8 ZS8.4 Air-insulated medium voltage switchgear
9 Current and voltage metering - Voltage transformer for permanent mounting or withdrawable component with lock and release device - Dimensions in accordance with DIN restricted type - Electrical characteristics in accordance with IEC-standards Sensors are short-circuit proof and insensitive to ferroresonance and to DC-component Link to control and protection system - The link available to a superimposed control and protection system depends on the kind of protection and control device Combined sensor or current transformer The uniform box frame can be equipped with a combined sensor consisting of a Rogowski coil and a potentiometer-type resistor, with current transformer cores or combination of Rogowski coil and potentiometer. ZS8.4 Air-insulated medium voltage switchgear 9
10 Peripherals Delivery - Complete panels - Are factory-checked - Transport units are individual panels - For crane or fork-lift truck Erection - Easy and fast erection - Suitable height of switchgear room from 2.40 metres - LSC 2A / PI panels from 2.70 metres - LSC 2A + LSC 2B / PM panels from 2.70 metres - Panels LSC 2A / PI + PM and LSC 2B / PM with pressure release duct from 2.40 metres - Installation to the frame or to the intermediate plate - Easy erection of the panels by simple busbar connections - Cable termination with standard sealing end Commissioning - Must be performed by trained specialists - Door interlock can be cancelled, for instance for visual inspection Inspection and servicing - Must be by trained personnel in accordance with safety regulations to DIN/VDE and of professional associations having liability for industrial safety and insurance. - The inspection and servicing intervals for some of the equipment/components are determined by fixed criteria such as switching frequency. The length of the intervals may depend on the different modes of operation in individual cases, such as the degree of loading, and also environmental influences Over the past 40 years, ABB has developed an outstanding reputation for the design and construction of air-insulated switchgear. The ZS8.4 switchgear series has built on this reputation to establish a leading position in the global market. 10 ZS8.4 Air-insulated medium voltage switchgear
11 Loss of service continuity LSC 2A, Partition class PI Circuit-breaker panel B Circuit-breaker area C Cable termination area 2 Circuit-breaker VM1/VD4 3 Automatic sliding plate 5 Current transformer 6 Voltage transformer 7 Installation contacts 8 Bay control and protection unit REF542 plus 10 Capacitive voltage indication Circuit-breaker panel - bus sectionaliser panel B Circuit-breaker area C Tie bus area 2 Circuit-breaker VM1/VD4 3 Automatic sliding plate 5 Current transformer 6 Tie bus 7 Installation contacts 8 Bay control and protection unit REF542 plus 10 Capacitive voltage indication Switch-disconnector panel B Switch-disconnector area C Cable termination area Switch-disconnector panel with fuse B Switch-disconnector area C Cable termination area 2 Switch-disconnector C4 3 Automatic sliding plate 2 Switch-disconnector C4 3 Automatic sliding plate 11 Fuse ZS8.4 Air-insulated medium voltage switchgear 11
12 Loss of service continuity LSC 2A, Partition class PI Switch-disconnector - bus sectionaliser panel B Switch-disconnector area C Tie bus area 1.2 Tie bus 2 Switch-disconnector C4 3 Automatic sliding plate Riser panel C Transformer area 1.2 Tie bus 5 Current transformer 6 Voltage transformer Operating availability LSC 2A, Partition class PI - Dimension U r l k Height Width Depth kv ka mm mm mm *) **) 2100 *) **) 2100 *) *) Low voltage compartment h = 730 mm --> h = 2100 mm **) Low voltage compartment h = 530 mm + cover h = 200 mm --> h = 2100 mm only CB-panels, SD-panels 17.5 kv/20 ka and 24 kv/16 ka! When the earthing switch is closed, the automatic sliding plate moves between the isolating contact of the circuitbreaker to guarantee protection against contact between live parts and the busbar area. Partition class PI metal-enclosed medium-voltage switchgear with one or additional non-metallic intermediate walls and/or shutter between accessible compartments and parts of the main circuit, which are energized. 12 ZS8.4 Air-insulated medium voltage switchgear
13 Loss of service continuity LSC 2A, Partition class PM Circuit-breaker panel B Circuit-breaker area C Cable termination area Contactor panel B Vacuum contactor area C Cable termination area 2 Circuit-breaker VM1/VD4 3 Automatic shutter 5 Current transformer 6 Voltage transformer 7 Installation contacts 8 Bay control and protection unit REF542 plus 9 Isolating tulip / tee-off partitioning 10 Capacitive voltage indication 2 Vacuum contactor 3 Automatic shutter 5 Current transformer 6 Voltage transformer 7 Installation contacts 8 Bay control and protection unit REF542 plus 9 Isolating tulip/tee-off partitioning 10 Capacitive voltage indication Switch-disconnector panel B Switch-disconnector area C Cable termination area D Low voltage area 2.1 Moveable isolating contact 2.2 Switch-disconnector 3 Automatic shutter Switch-disconnector panel with fuse B Switch-disconnector area C Cable termination area D Low voltage area 2.1 Moveable isolating contact 2.2 Switch-disconnector 3 Automatic shutter 11 Fuse ZS8.4 Air-insulated medium voltage switchgear 13
14 Loss of service continuity LSC 2A, Partition class PM Circuit-breaker - bus sectionaliser panel B Circuit-breaker area C Tie bus area 1.2 Tie bus 2 Circuit-breaker VM1/VD4 3 Automatic shutter 7 Installation contacts 8 Bay control and protection unit REF542 plus 9 Isolating tulip/tee-off partitioning 10 Capacitive voltage indication Riser panel C Transformer area 1.2 Tie bus 5 Current transformer 6 Voltage transformer Operating availability LSC 2A, partition class PM - Dimension U r l k Height Width Depth kv ka mm mm mm *) **) 2300 *) **) 2300 *) *) Low voltage compartment h = 730 mm + arc guide plate h = 200 mm --> h = 2300 mm Low voltage compartment h = 530 mm + arc guide plate h = 400 mm --> h = 2300 mm **) only CB-panels, for SD-panels plese see page 19 Moving the circuit-breaker on the withdrawable component into the test/disconnected position swings the automatic shutter in front of the isolating tulips and establishes protection against contact with the busbar area. This partition provides effective protection of the busbar compartment in the case of an arc fault in the cable/switching device compartment. Partition class PM metal-enclosed medium-voltage switchgear with one or additional metallic intermediate walls and/or shutter between accessible compartments and parts of the main circuit, which are energized. 14 ZS8.4 Air-insulated medium voltage switchgear
15 Loss of service continuity LSC 2B, Partition class PM Circuit-breaker panel B Circuit-breaker area C Cable termination area 2 Circuit-breaker VM1/VD4 3 Automatic sliding plate 5 Current transformer 6 Voltage transformer 7 Installation contacts 8 Bay control and protection unit REF542 plus 9 Isolating tulip / tee-off partition 10 Capacitive indication 3D-view-circuit-breaker panel Contactor panel (LSC 2A) B Vacuum contactor area C Cable termination area 2 Vacuum contactor 3 Automatic shutter 5 Current transformer 6 Voltage transformer 7 Installation contacts 9 Isolating tulip / tee-off partition 10 Capacitive indication Switch-disconnector panel with fuse (LSC 2A) B Switch-disconnector area C Cable termination area 2.1 Moveable isolating contact 2.2 Switch-disconnector 3 Automatic shutter 11 Fuse ZS8.4 Air-insulated medium voltage switchgear 15
16 Loss of service continuity LSC 2B, Partition class PM Circuit-breaker - bus sectionaliser panel B Circuit-breaker area C Tie bus area 1.2 Tie bus 2 Circuit-breaker VM1/VD4 3 Automatic sliding plate 5 Current transformer 7 Installation contacts 8 Bay controller and protection unit REF542 plus 9 Isolating tulip / tee-off partitioning 10 Capacitive indication Riser panel C Transformer area 1.2 Tie bus 5 Current transformer 6 Voltage transformer Operating availability LSC 2B, Partition class PM - Dimension U r l k Height Width Depth kv ka mm mm mm *) *) Low voltage compartment h = 730 mm + arc guide plate h = 200 mm --> h = 2300 mm Low voltage compartment h = 530 mm + arc guide plate h = 400 mm --> h = 2300 mm Moving the circuit-breaker withdrawable component into the test/disconnected position swings the automatic shutter in front of the isolating tulips and establishes protection against contact with the busbar area. The busbar area partition provides effective protection of the busbar compartment in the case of an arc fault in the cable/ switching device compartment. The busbar compartment is separated by a withdrawable metal partition from the switching device/cable termination compartment behind the front door. The shutter is withdrawable for cable installation. Protection against contact is realized in 3 areas: busbar area circuit-breaker area transformer/cable termination area 16 ZS8.4 Air-insulated medium voltage switchgear
17 Special panel solutions and top-mounted boxes Duplex-circuit-breaker panel Fig. 24 kv Special panels and top-mounted boxes - Dimension U r l k Height Width Depth kv ka mm mm mm 12 ***) *) ***) 25 **) 2300 *) *) Low voltage compartment h = 730 mm + arc guide plate h = 200 mm --> h = 2300 mm Low voltage compartment h = 530 mm + arc guide plate h = 400 mm --> h = 2300 mm **) 24 kv switchgear modified for 12 kv! ***) only CB-panels, for SD-panels plese see page 19 Top-mounted box 12/24 kv with earthing switch Switch-disconnector panel Partition class PI with fuse, current and voltage transformer for energy metering measuring Top-mounted box 12/24 kv with voltage transformer ZS8.4 Air-insulated medium voltage switchgear 17
18 ZS8.4 Air-insulated medium voltage switchgear ZS8.4 Successfully deployed for these customers - University hospital Frankfurt - E.ON Hanse - EnviaM - TAL - Opel - RWE - V&M Düsseldorf - University Hannover - Containerterminal Burchardkai - Degussa AG - SW Eberbach - Spitzke AG - Nexans SuperConductors GmbH - University hospital Freiburg - SW Heidelberg - MES - Bashneft, Russia - KIMA - Grona - Water power station Elze-Berkhof - University hospital Essen - Fair Cologne - Benteler Stahl - SW Munich - E.ON Avacon AG - Stuttgart SSB - Airport Navoi - REPOWER Systems 18 ZS8.4 Air-insulated medium voltage switchgear
19 Technical data Circuit-breaker panels, contactor panels and corresponding switch-disconnector panels Rated voltage U r kv Highest operating voltage kv Rated power frequency withstand voltage U d kv Rated lightning impulse withstand voltage U p kv Rated frequency f r Hz 50/60 50/60 50/60 Rated current, busbars I r A Rated current, feeder Switch-disconnector panel I r A 630 1) 630 1) 630 2) Contactor panel A 3) 5) 220 Circuit-breaker panel A Rated peak withstand current I p ka ) 63 8) Rated short time current 3 s I k ka 16/20/25 16/20/25 7) 16/20/25 7) Rated load breaking current of the switch-disconnector A Rated short-circuit making current of the switch-disconnector ka ) Rated short-circuit breaking current of the circuit-breaker ka Rated short-circuit making current of the circuit-breaker ka Rated operating sequence O s - CO - 15 s - CO O s - CO - 15 s - CO O s - CO - 15 s - CO Total break time ms Operating time ms Degree of protection of the switchgear IP4X IP4X IP4X of the compartments to one another IP2X IP2X IP2X Ambient temperature Maximum C h-mean value C Minimum C Site altitude m Height of cable connection: mm ) ) ) 1000 A available on request 2) 800 A available on request 3) Rated current at max. fuse size 400 A (SIBA) 6 kv 4) Cable connection height depends on panel type 5) Max. service voltage 7,2 kv 6) 17.5 kv switch-disconnector panel up to 50 ka 7) 17.5 kv switch-disconnector panel only 20 ka / 24 kv switch-disconnector panel 20 ka or 25 ka for switch-disconnector with fuse (max. fuse size 40 A) 8) 24 kv switch-disconnector panel 50 ka or 63 ka for switch disconnector with fuse (max. fuse size 40A) ZS8.4 Air-insulated medium voltage switchgear 19
20 Contact us Your sales contact: More product information: 1VLC Rev. B, en - Brochure (ZS8.4) (gs) The data and illustrations are not binding. We reserve the right to make changes without notice in the course of technical development of the product. Copyright 2018 ABB. All rights reserved.
Gas-Insulated Medium-Voltage Switchgear siemens.com/8dab12
8DB 12 blue GIS Gas-Insulated Medium-Voltage Switchgear siemens.com/8dab12 Features Gas-insulated switchgear (GIS) type 8D/B has been an integral part of the medium-voltage portfolio at Siemens for more
More informationSwitchgear Type 8DJH for Secondary Distribution Systems up to 24 kv, Gas-Insulated
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kv, Gas-Insulated Medium-Voltage Switchgear Catalog HA 40.2 2009 Answers for energy. -HA40-111.eps -HA40-110.eps -HA40-109.eps -HA40-112.eps
More informationSwitchgear Type SIMOSEC up to 24 kv, Air-insulated, Extendable
Switchgear Type SIMOSEC up to 4 kv, Air-insulated, Extendable Medium-Voltage Switchgear Catalog HA 41.1 0 Answers for energy. R-HA41-055 eps R-HA41-08 eps Contents Application Typical uses Pages Application,
More informationVI 3 - i TABLE OF CONTENTS
VI 3 - i TABLE OF CONTENTS 3 PROJECT SPECIFIC DATA... 1 3.1 DEFINITIONS... 1 3.1.1 Design Data, High and Medium Voltage... 1 3.1.2 Design Data, Low Voltage Equipment... 2 3.1.3 Phase Relationship... 3
More informationA compact, integrated solution for medium voltage connection, transformer and low voltage distribution
Low to medium voltage distribution M2L integrated power distribution system A compact, integrated solution for medium voltage connection, transformer and low voltage distribution Turnkey solution medium
More informationSchedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK
2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK PO Box 25876 Safat 13119 Kuwait Contact: Mr Atul Madhukar Vaidya Tel: +965 1822600 Fax: +965 24761963 E-Mail: factory@ahleiasg.com Website:
More informationI -limiter The world s fastest switching device
I S -limiter 2 I S -limiter The world s fastest switching device Reduces substation cost Solves short-circuit problems in new substations and substation extensions Optimum solution for interconnection
More informationTitle: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS
TABLE OF CONTENTS PAGE 1.0 SCOPE... 2 2.0 STANDARDS... 2 3.0 DESIGN REQUIREMENTS... 2 3.01 Service Conditions... 2 3.02 Ratings... 3 4.0 Sectionalizer Construction... 4 5.0 Mechanism... 6 6.0 Solid Dielectric
More informationCatalogue 1SFC en, Edition 3 November 2003 Supersedes Catalogue 1SFC en, Edition 2 November Arc Guard System TVOC
Catalogue 1SFC 266006-en, Edition 3 November 2003 Supersedes Catalogue 1SFC 266006-en, Edition 2 November 2000 Arc Guard System TVOC System units The two units of the are used as below: Approvals 1. with
More information10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY
9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor
More informationTECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES
INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION October 2014 TECHNICAL DESCRIPTION 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES I. SCOPE This
More informationTechnical catalogue. Emax Low voltage air circuit-breakers. Hotline:
Technical catalogue Emax Low voltage air circuit-breakers www.alobitanbd.com Hotline: 01711548558 PAGE : 02 The new Emax have received innumerable international certifications and approval by the major
More informationMEDIUM VOLTAGE COMPACT STARTER TYPE KAE
MEDIUM VOLTAGE COMPACT STARTER TYPE KAE up to 5 MW up to 17,5 kv up to 400 A Mocotech presents the compact motor starter t ype KAE with integrated autotransformer, switches, control and many more advantages.
More informationLa protection sélective des réseaux électriques
La protection sélective des réseaux électriques ULG 21. 11. 2012 The T&D grids Generation Transmission Distribution Industry The electricity network ensure an efficient supply of energy High Voltage Transformers
More informationStandards for MV switchgear rated for arc flash protection
Standards for MV switchgear rated for arc flash protection by Bryan Johnson, ABB Switchgear standards historically considered the electrical capability of switchgear with little regard to the effects of
More informationSubstation Preventive Maintenance
Substation Preventive Maintenance PROVINCIAL ELECTRICITY AUTHORITY 1 Presentation Contents 1) A kind of substation 2) Electrical equipment details of AIS substation 3) Electrical equipment details of GIS
More information11/0 IZM circuit-breakers, IN switch-disconnectors
11/0 IZM circuit-breakers, IN switch-disconnectors Contents IZM circuit-breakers, IN switch-disconnectors 11/1 from 630 A 6300 A Page Description 11/2 Technical overview 11/4 Overview of functions for
More information20 - Arc Guard Systems
Arc Guard Index Arc Guard - Arc Guard Arc Guard...1 -.14 Selection Arc Guard System, description...6...2...2 Description,...1 Description,...1 Description, with detectors...4 Description,...5 Detectors
More informationProtection of Electrical Networks. Christophe Prévé
Protection of Electrical Networks Christophe Prévé This Page Intentionally Left Blank Protection of Electrical Networks This Page Intentionally Left Blank Protection of Electrical Networks Christophe Prévé
More informationKEVCY 24 RE1; KEVCY 24 RF1 Indoor combined sensor; Indoor voltage sensor
Medium Voltage Product KEVCY 24 RE1; KEVCY 24 RF1 Indoor combined sensor; Indoor voltage sensor Parameters for Application Unit Value Rated primary current of application A up to 630 Rated primary voltage
More informationMV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer
PART 1: GENERAL 1.01 Transformer A. This section includes liquid filled, pad mounted distribution transformers with primary voltage of 12kV or 4.16kV (The University will determine primary voltage), with
More informationInstrument transformers for indoor applications. Product overview. Instrument transformers for indoor applications.
Instrument transformers for indoor applications Product overview Instrument transformers for indoor applications Product overview 2 I N S T R U M E N T T R A N S F O R M E R S F O R I N D O O R A P P L
More informationMV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING
Training Title MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Duration 5 days Training Date MV, HV and EHV Switchgear Testing & Commissioning 5 21 25 Sep $3,750 Dubai, UAE In any of the 5 star
More informationHigh voltage shunt capacitor banks HIGH VOLTAGE COMPENSATION AND HARMONIC FILTERING PRODUCTS
High voltage shunt capacitor banks Alstom Grid high voltage shunt capacitor bank offering is divided in: By bank construction HV open rack capacitor banks HV enclosed capacitor banks By bank design HV
More informationLV/MV/HV CIRCUIT BREAKERS (SWITCH GEAR) DESIGN, INSPECTION, MAINTENANCE, REPAIR & TROUBLESHOOTING
Training Title LV/MV/HV CIRCUIT BREAKERS (SWITCH GEAR) DESIGN, INSPECTION, MAINTENANCE, REPAIR & TROUBLESHOOTING Training Duration 5 days Training Venue and Dates LV/MV/HV Circuit Breakers (Switchgear):
More informationNeutral Earthing. For permanent or temporary neutral earthing in HV systems
Neutral Earthing Resistors RESISTORS For permanent or temporary neutral earthing in HV systems For continuous or temporary low-resistance neutral grounding in medium voltage systems Neutral point connection
More informationNOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS
NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS Ljubomir KOJOVIC Cooper Power Systems - U.S.A. Lkojovic@cooperpower.com INTRODUCTION In steel facilities that use Electric Arc Furnaces (EAFs) to manufacture
More informationDocuments and Addresses
Report No.: 14-041-MS Sheet: 2 Documents and Addresses Accreditation The Prüffeld der Schaltwerke, Berlin has been approved by the DAkkS (German accreditation body) according to EN ISO/IEC 17025 for tests
More informationExcitation Systems THYRIPART. Compound-Excitation System for Synchronous Generators. Power Generation
Excitation Systems Compound-Excitation System for Synchronous Generators Power Generation Operating Characteristics Load dependent Short circuit supporting Low voltage gradient dv/dt Black start capability
More informationLow voltage switchgear
Low voltage switchgear Sivacon S8 and 8PT Withdrawable core structure designed for demanding applications and international markets. SAT8 PU0 Main exchange system for demanding fixed output, industrial
More informationHamdy Faramawy Senior Application Specialist ABB Sweden
Design, Engineering and Application of New Firm Capacity Control System (FCCS) Mohammed Y. Tageldin, MSc. MIET Senior Protection Systems Engineer ABB United Kingdom mohammed.tageldin@gb.abb.com Hamdy Faramawy
More informationMINISTRY OF ELECTRICITY
MINISTRY OF ELECTRICITY IRAQ SUPERGRID PROJECTS 400/132 KV GIS SUBSTATIONS VOLUME 3 TECHNICAL SCHEDULES JANUARY 2007 LIST OF REVISIONS 1 2 3 4 5 Current Rev. Date 19.11.04 18.03.05 Aug 05 Oct 05 Jan 07
More informationFault indicator. Application. SPEF 3A2 C 1MRS MBG Issued: April 1999 Status: Updated Version: B/ Data subject to change without notice
Issued: April 1999 Status: Updated Version: B/08.11.200 Data subject to change without notice Features Versatile, multifunction line fault indicator for distribution networks Overcurrent, earth-fault and
More information2.7. IT system floor-standing distribution cabinet Series -IPS-F/EDS
Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 65 35305 Grünberg Tel.: 0640 807-0 Fax: 0640 807-259 IT system floor-standing distribution cabinet Series -IPS-F/EDS for supplying power to medical locations
More informationPRODUCT FOR HIGH VOLTAGE APPLICATION. Current transformers for Gasinsulated. Instructions for installation, use and maintenance
PRODUCT FOR HIGH VOLTAGE APPLICATION Current transformers for Gasinsulated switchgear type ELK Instructions for installation, use and maintenance 2 CURRENT TRANSFORMERS FOR GAS-INSULATED SWITCHGEAR TYPE
More informationCompany main topic [ Product ] TracFeed GR. English. Diode Rectifiers. Made in Germany
Company main topic [ Product ] TracFeed GR English Diode Rectifiers Made in Germany 2 Reliable traction power supply with rectifiers from Rail power Systems Application Rectifiers with natural air cooling
More informationAdvanced Test Equipment Rentals ATEC (2832) CP RC. Resonance circuit for GIS testing
Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) CP RC Resonance circuit for GIS testing A new approach to testing gas-insulated switchgear Testing gas-insulated switchgear
More informationMedium Voltage Products. KECA 80 C85 Indoor current sensor
Medium Voltage Products KECA 80 C85 Indoor current sensor Parameters for Application Value Rated primary current of application up to 2 500 A Sensor Parameters Value Highest voltage for equipment, U m
More informationThis webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB
This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB Relion. Thinking beyond the box. Designed to seamlessly consolidate functions, Relion relays
More informationEI HIGH VOLTAGE INSULATION TESTING POLICY
Network(s): Summary: ENGINEERING INSTRUCTION EI 09-0001 HIGH VOLTAGE INSULATION TESTING POLICY EPN, LPN, SPN This engineering instruction details the policy for the on-site insulation testing of new and
More informationComplex Solution for the Distribution Substation REF 542plus. Application and Setting Guide
Complex Solution for the Distribution Substation REF 542plus 1MRS756412 Complex Solution for the Distribution Substation REF 542plus Copyrights The information in this document is subject to change without
More informationExcitation Systems. Service Generators SIPOL. Transistorized Excitation Systems for Synchronous Generators. Power Generation
Excitation Systems Service Generators Transistorized Excitation Systems for Synchronous Generators Power Generation Operating Characteristics High availability Reliability Digital control facilities Very
More informationELECTRICAL POWER ENGINEERING
Introduction This trainer has been designed to provide students with a fully comprehensive knowledge in Electrical Power Engineering systems. The trainer is composed of a set of modules for the simulation
More informationMedium-voltage in-phase regulator system Energy Management
Medium-voltage in-phase regulator system Energy Management Challenges Distributed power generation can have an enormous impact on grid performance. The challenge of equalizing voltage fluctuations is especially
More informationRelion 605 series Self-Powered Feeder Protection REJ603 Product Guide
Relion 605 series Relion 605 series Self-Powered Feeder Protection Product Guide Contents 1 Description...3 2 Protection functions...3 3 Application...4 4 Self-supervision...4 5 Inputs and outputs...4
More informationFDM Medium Voltage Controller
1-1 LMR PLUS Product Description For over 50 years, EATON Corporation has been the industry leader in Medium Voltage Motor Control. The FDM Medium Voltage Fire Pump Controller is based on the AMPGARD controller
More informationMotor-protective circuit-breaker, 3p, Ir=40-50A, screw connection. Product range PKZM4 motor protective circuit-breakers up to 65 A
DATASHEET - PKZM4-50 Delivery program Motor-protective circuit-breaker, 3p, Ir=40-50A, screw connection Part no. PKZM4-50 Catalog No. 222355 Eaton Catalog No. XTPR050DC1NL EL-Nummer 0004355161 (Norway)
More informationExcitation Systems RG3 - T4. Transistorized Excitation Systems for Synchronous Generators. Power Generation
Excitation Systems RG3 - T4 Transistorized Excitation Systems for Synchronous Generators Power Generation Operating Characteristics Reliability High availability Digital control facilities Very good control
More informationECP HV INSULATION TESTING
Document Number: ECP 11-0006 Network(s): Summary: All ENGINEERING COMMISSIONING PROCEDURE ECP 11-0006 HV INSULATION TESTING This standard details the policy for the on-site insulation testing of new and
More informationCause, Effect & Mitigation Strategies
WSU HANDS ON RELAY SCHOOL 2019 Arc Flash Fault Cause, Effect & Mitigation Strategies Joe Xavier, Technical Manager West Region Arc Flash Fault - Agenda What is an Arc Flash? Why and when does Arc Flash
More informationELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER
Approval Amendment Record Approval Date Version Description 03/05/2017 1 Initial issue PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 1 of 13 Table of Contents 1. Purpose...
More informationSPTS 1 - Ratings and General Requirements for Plant, Equipment and Apparatus for The ScottishPower System and Connection Points to it.
1. SCOPE The requirements of this document apply to all Plant, Equipment and Apparatus that are part of, or are Directly connected to, the Company network. Requirements contained herein may be modified
More informationINTEGRATED TRANSMISSION PLAN Glossary
INTEGRATED TRANSMISSION PLAN Glossary SEPTEMBER 2017 GLOSSARY Term AC ACM asset health and asset health index (AHI) automatic underfrequency load shedding (AUFLS) availability bus cable capacitor bank
More informationELECTRICAL POWER TRANSMISSION TRAINER
ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER This training system has been designed to provide the students with a fully comprehensive knowledge in Electrical Power Engineering
More informationPowered by technology...driven by service CURRENT TRANSFORMERS. Multifunction Meters. Transducers & Isolators. Temperature Controllers
Multifunction Meters Transducers & Isolators Temperature Controllers Converters & Recorders Digital Panel Meters CURRENT TRANSFORMERS Current Transformers Analogue Panel Meters Shunts Digital Multimeters
More informationPower transformers. Shunt reactors Proven history for future success
Power transformers Shunt reactors Proven history for future success Shunt reactors an investment for today and for the future 2 Shunt reactors Improving power quality and reducing transmission costs Shunt
More informationDescription Basic devices with positive operation contacts. Standards IEC/EN 60947, EN , VDE 0660, UL, CSA
Contactor relay, 2N/O+2N/C, AC Part no. DILA-22(24V60HZ) Catalog No. 276390 Eaton Catalog No. XTRE10B22B6 Delivery program Product range DILA relays Application Contactor relays Description Basic devices
More informationDATASHEET - ETR4-70-A. Delivery program. Timing relay, 2W, 0.05s-100h, multi-function, VAC/DC, potentiometer connection
DATASHEET - ETR4-70-A Delivery program Timing relay, 2W, 0.05s-100h, multi-function, 24-240VAC/DC, potentiometer connection Part no. ETR4-70-A Catalog No. 031888 Eaton Catalog No. XTTR6A100H70B EL-Nummer
More informationTesting of 400 kv GIS
Testing of 400 kv GIS Robert le Roux, Dermot Dorgan, Brian Perry ESB International - Ireland Paper 028 1 Introduction The 400 kv transmission is designed for critical periods of low loading. Due to critical
More informationPOWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.
POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. This document may be subject to changes. Contact ARTECHE to confirm the characteristics and availability of the products
More informationEH27401 Communication and Control in Electric Power Systems Lecture 2. Lars Nordström
EH27401 Communication and Control in Electric Power Systems Lecture 2 Lars Nordström larsn@ics.kth.se 1 Course map 2 Outline 1. Power System Topologies Transmission Grids vs Distribution grids Radial grids
More informationI P. /dt. di p V S+ Applications. Standards. 1) IEC ed1.0: 2007; IEC : ed1.0: 2012
Ref: ART-B22-D70, ART-B22-D125, ART-B22-D175 Flexible clip-around Rogowski coil for the electronic measurement of AC current with galvanic separation between the primary circuit (power) and the secondary
More informationInternational Surveys on Circuit-Breaker Reliability Data for Substation and System Studies
IEEE TRANSACTIONS ON POWER DELIVERY 1 International Surveys on Circuit-Breaker Reliability Data for Substation and System Studies Anton Janssen, Member, IEEE, Dirk Makareinis, and Carl-Ejnar Sölver Abstract
More informationMFAC. Grid Solutions. High Impedance Differential Relay. MFAC Types. Key Benefits. Application. Description. Imagination at work
GE Grid Solutions MFAC High Impedance Differential Relay MFAC relays provide high speed differential protection for various types of power systems plants including generators, reactors, busbars, motors
More informationDATASHEET - ETR4-51-A. Delivery program. Technical data General. Timing relay, star-delta, 50 ms, 1W, 3-60s, VAC/DC
DATASHEET - ETR4-51-A Timing relay, star-delta, 50 ms, 1W, 3-60s, 24-240VAC/DC Part no. ETR4-51-A Catalog No. 031884 Eaton Catalog No. XTTR6A60S51B EL-Nummer 0004133308 (Norway) Delivery program Product
More informationI P. /dt. di p V S Applications. Standards 1) IEC : 2007; IEC : ) IEC : 2016; IEC : 2017
Ref: ART-B22-D70, ART-B22-D125, ART-B22-D175, ART-B22-D300 Flexible clip-around Rogowski coil for the electronic measurement of AC current with galvanic separation between the primary circuit (power) and
More informationSECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL
PART I: GENERAL 1.01 Wiring Devices A. This section of the standard includes design requirements for wiring connections, including receptacles and switches to equipment specified in other sections. a.
More informationEE030: Circuit Breaker & Switchgears Inspection, Maintenance, Design, Repair & Troubleshooting
EE030: Circuit Breaker & Switchgears Inspection, Maintenance, Design, Repair & Troubleshooting EE030 Rev.001 CMCT COURSE OUTLINE Page 1 of 6 Training Description: This course is designed to update participants
More informationDMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)
DELHI METRO RAIL CORPORATION LIMITED DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW) SPECIFICATION NO. DMES- 0005/ DMRC-E-TR-TRANSF-05 SPECIFICATIONS FOR THREE PHASE 33 kv/415 V AUXILIARY Issued on: Date
More informationCentral Inverter SUNNY CENTRAL 200 / 250 / 250HE / 350
Central Inverter SUNNY CENTRAL 200 / 250 / 250HE / 350 Installation Guide SC20_25_35-IEN094521 98-4004821 Version 2.1 EN SMA Solar Technology AG Table of Contents Table of Contents 1 Notes on this Manual..............................
More informationECP HV INSULATION TESTING
Document Number: ECP 11-0006 Network(s): Summary: ENGINEERING COMMISSIONING PROCEDURE EPN, LPN, SPN ECP 11-0006 HV INSULATION TESTING This standard details the policy for the on-site insulation testing
More informationAmpgard The name motor applications rely on
Medium-voltage motor control The name motor applications rely on Oil and gas Mining Water/wastewater Pulp and paper Utility A legacy of reliability for more than 4 decades 1950 1960 1970 1980* 1990 2000
More informationABB CUSTOMER WORLD, MARCH 13-16, 2017 Sensors in Critical Applications Ron Pate, Product Manager, Instrument Transformers and Sensors
ABB CUSTOMER WORLD, MARCH 13-16, 2017 Sensors in Critical Applications 050511 Ron Pate, Product Manager, Instrument Transformers and Sensors Sensors in Critical Applications Presentation code 050511 Speakers
More informationA Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment
International Research Journal of Engineering and Technology (IRJET) eissn: 23 0056 Volume: 04 Issue: 02 Feb 2017 www.irjet.net pissn: 072 A Review Comprehension: Guideline for Testing of HV, EHV and UHV
More informationNumbering System for Protective Devices, Control and Indication Devices for Power Systems
Appendix C Numbering System for Protective Devices, Control and Indication Devices for Power Systems C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS The requirements
More informationNo. SSIEC-PRC SHINSUNG. Polymer Recloser SIREC SERIES 15kV, 27kV, 38kV 400A, 630A, 800A
No. SSIEC-PRC-00803-1 SHINSUNG Polymer Recloser SIREC SERIES 15kV, 27kV, 38kV 400A, 630A, 800A Introduction SIREC(Solid Insulated Recloser) is designed for outdoor application with lightweight, longlife,
More informationContactors. Series C137, C163, C164, C165 Single pole contactors for battery voltages Catalogue B60.en
Contactors Series C7, C6, C6, C65 Single pole contactors for battery voltages Catalogue B.en Contactors for battery voltages C7, C6, C6, C65 Series With its proven line of C7 through C65 Series contactors
More informationCatalog 200 Contactors up to 115 A Motor Starters up to 55 kw 03/2009
Catalog 00 Contactors up to 5 A Motor Starters up to 55 kw 03/009 Kraus & Naimer The development of the Blue Line rotary switch, contactor and motor starter product ranges is based on more than hundred
More informationStabilized Differential Relay SPAD 346. Product Guide
Issued: July 1998 Status: Updated Version: D/21.03.2006 Data subject to change without notice Features Integrated three-phase differential relay, three-phase overcurrent relay and multiconfigurable earth-fault
More informationSwitching Devices Contactors and Contactor Assemblies for Switching Motors
Switching Devices Contactors and Contactor Assemblies for Switching Motors groups 41B, 41H / Introduction Power contactors for switching motors /5 General data /11 SIRIUS RT10 contactors, -pole,... 50
More information1/23/2003. Sensor presentation
1/23/2003 Sensor presentation Product Scope A Sensor is a device intended to transmit a signal corresponding to the primary current or voltage to the secondary equipment. Power IT Sensors are typically
More informationQUINT-PS/ 3AC/24DC/10
Primary-switched power supply with SFB technology, 3 AC, output current 10 A INTERFACE Data sheet 103131_en_01 1 Description PHOENIX CONTACT - 09/2009 Features QUINT POWER power supply units Maximum system
More informationPower Frequency Withstand Voltage On-site testing of 400 kv GIS
Power Frequency Withstand Voltage On-site testing of 400 kv GIS D. Anaraki Ardakani, A. Omidkhoda, M. Solati High Voltage Engineering Center ACECR Tehran, Iran Da_ardakani@yahoo.com Paper Reference Number:
More informationInstructions Contact numbers to EN Coil terminal markings to EN Integrated diode-resistor combination Coil rating 2.
Delivery program Contactor relay, 2N/O+2N/C, DC current Part no. DILER-22-G(24VDC) Catalog No. 010042 Eaton Catalog No. XTRM10A22TD EL-Nummer 4130354 (Norway) Product range DILER Mini-contactors Application
More informationElectronic timer CT-SDS.22 Star-delta change-over with 2 n/o contacts Data sheet
CDC 0 F0t07 Features Rated control supply voltage -8 V DC, -0 V AC Single-function timer with star-delta change-over One device includes 7 time ranges (0.0 s - 0 min) n/o contacts LEDs for status indication
More informationA3-102 PCB ROGOWSKI COILS HIGH PRECISION LOW POWER SENSORS. Ljubomir A. Kojovic * Cooper Power Systems USA
21, rue d'artois, F-758 Paris http://www.cigre.org A3-12 Session 24 CIGRÉ PCB ROGOWSKI COILS HIGH PRECISION LOW POWER SENSORS Ljubomir A. Kojovic * Cooper Power Systems USA Summary-This paper presents
More informationMedium voltage products. Field Application Support Analysis and calculations in Medium-Voltage electrical networks
Medium voltage products Field Application Support Analysis and calculations in Medium-Voltage electrical networks Concept The electrical installation of an industrial site is a complex structure. Analyzing
More informationHow to maximize reliability using an alternative distribution system for critical loads
White Paper WP024001EN How to maximize reliability using an alternative distribution system for critical loads Executive summary The electric power industry has several different distribution topologies
More informationElectronic timer CT-MVS.23 Multifunctional with 2 c/o (SPDT) contacts
Data sheet Electronic timer CT-MVS.23 Multifunctional with 2 c/o (SPDT) contacts The CT-MVS.23 is a multifunctional electronic timer from the CT-S range. It provides 11 timing functions and 10 time ranges.
More informationPower supply CP-T 48/20.0 Primary switch mode power supply
Data sheet Power supply CP-T 48/20.0 Primary switch mode power supply The CP-T range of three-phase power supply units is the youngest member of ABB s power supply family. In terms of design and functionality,
More informationOnsite Mobile AC High Voltage Test System
TSGMF(T) series Onsite Mobile AC High Voltage Test System Onsite mobile AC high voltage test systems are used for withstand voltage testing, partial discharge measurement, tan delta measurement to instrument
More informationEnergy a core sector at Siemens
Energy a core sector at Siemens Healthcare Sector Energy Sector Industry Sector Siemens Energy Sector Answers for energy supply Energy Products and Solutions - in 6 Divisions Oil & Gas Fossil Power Generation
More informationMichigan State University Construction Standards SWITCHBOARDS, PANELBOARDS, AND CONTROL CENTERS PAGE
PAGE 262400-1 SECTION 262400 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationDescription Basic devices with positive operation contacts. Standards IEC/EN 60947, EN , VDE 0660, UL, CSA
DATASHEET - DILA-22(230V50HZ,240V60HZ) Delivery program Contactor relay, 2N/O+2N/C, AC Part no. DILA-22(230V50HZ,240V60HZ) Catalog No. 276399 Eaton Catalog No. XTRE10B22F EL-Nummer 0004130208 (Norway)
More informationCEYLON ELECTRICITY BOARD SRI LANKA. Procurement of Plant
CEYLON ELECTRICITY BOARD SRI LANKA GREEN POWER DEVELOPMENT AND ENERGY EFFICIENCY IMPROVEMENT INVESTMENT PROGRAMME (TRANCHE 2) PACKAGE 2: LOT A MANNAR NADUKUDA TRANSMISSION DEVELOPMENT (ADB LOAN NO: 47037-SRI)
More informationUBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5
Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Energy & Water Services.2 UBC Building Operations 1.2 Description.1 UBC requirements for Substation Transformers. 2.0 MATERIAL AND DESIGN REQUIREMENTS
More informationSensor Technology. Applications for medium voltage
Sensor Technology Applications for medium voltage Contents Introduction to sensor technology... 3 Sensors versus instrument transformers... 6 Advantages for builders and users of switchgear... 7 The impact
More informationThe NOVA Recloser shall be designed and tested in accordance with the following standards as applicable:
Reclosers NOVA Three-Phase Recloser Functional Specification Guide Functional specification for NOVA three-phase recloser 1. Scope This specification describes the features and ratings of the NOVA recloser.
More informationKEVA B Indoor voltage sensor
Medium Voltage Products KEVA B Indoor voltage sensor Parameters for Application Unit Value Rated primary voltage of application kv up to 24 Sensor Parameters Unit Value Rated primary voltage, U pn Highest
More informationTS RES - OUTSTANDING ISSUES
TS RES - OUTSTANDING ISSUES This document has been officially issued as DRAFT until the following outstanding issues have been resolved. At that time the document will be officially reissued as the next
More information