1 SAUTER EY-modulo 4 PDS en Product Data Sheet EY-AS420 modu420: Automation station How energy efficiency is improved Integrated pulse counter to measure and optimise energy consumption. Integrated calendar function enables operation of the plant to be adapted to usage with minimal energy consumption. Areas of application Can be used for a wide variety of applications such as fan-coil, control of chilled beams, heating pumps, multispeed ventilation plants, energy measurement, cooling and heating systems, or roof-top units. Features Compact, freely programmable LON automation station Supports LonMark object types #0, #1, #3, #20020, #3300 and #20100 LonMark -certified as per Interoperability Guideline, Version 3.4 Lower housing can be separated so that terminals and electronics can be installed separately. Audio jack plug for rapid access to the LON network. LNS plug-in for rapid programming of the automation station Technical description 24 V~/= power supply Universal inputs and outputs can be configured via software 6 universal inputs 3 fuse-protected universal outputs 5 Triac outputs 2 scheduler objects TP/FT 10, 78 kbps Neuron 3150 processor Products Type EY-AS420F001 Description Compact automation station Technical data Electrical supply Permitted ambient conditions Power supply 24 V~ (50/60 Hz) ± 15% Operating temperature 0 70 C 24 V= ( V) Transport and storage temperature C Power consumption 12 VA max. Humidity 0 90% rh no condensation Inputs, outputs Universal inputs 6 Standards, guidelines and directives Resolution 16 bit analogue/digital Degree of protection IP 10 (EN 60529) Can be used as: Protection class III (EN ) Counters Potential-free contact Environmental class 3K3 (IEC 60721) Analogue input U/I/R CE conformity as per Temperature measurement NI1000, NTC, PT100, PT1000 EMC Directive 2004/108/EC EN Potentiometer R EN Universal outputs 3 Resolution 10 bit digital/analogue Installation Can be used as: Dimensions W H D (mm) Analogue output U/I Weight (kg) 0.35 Digital output 0-I Housing ABS PA-765A PWM max. 60 ma at 12 V= Triac outputs 5 Additional information up to 1 A Fitting instructions MV P Material declaration MD Dimension drawing Wiring diagram M11424 M11425 A10589 Accessories Type Description Manual operating panel EY-RU482F001 EY-RU481F001 EY-RU481F002 EY-RU481F003 ecos4 sensor FCU, display ecos4 sensor ecos4 sensor, occupancy ecos4 sensor, occupancy, setpoint 1/6

2 SAUTER EY-modulo 4 General functioning of the automation station The modu420 automation station (AS) is a microprocessorassisted, freely programmable controller used to control and regulate a varied range of HVAC applications on the basis of LON technology. The modu420 automation station uses the LonTalk communication protocol and is LonMark -certified if the sensor profile (number 1) is used for the relevant input objects and if the actuator profile (number 3) is used for the relevant output objects. The integrated operating programme can be programmed freely; it reads in the hardware and software addresses, processes the user programme, updates the outputs and handles the necessary communication with other stations in the network or with the management level. The user program can be loaded from any point in the LON network using SAUTER CASE LON Engine. The plugins can be used to programme or parameterize the controllers with the SAUTER CASE LON Engine network management tool or via any LNS-based software, according to choice. Engineering notes Installation and wiring The modu420 automation station can be fitted in an MCC using a top-hat rail (EN 60715). Wall-mounting is possible, using the fitting holes in the lower housing. It is possible to separate the upper and lower sections of the housing in order to install and connect the automation station. The plant devices are connected via screw terminals. The following conditions must be met: Cross-section conductors: LON network: of min mm² (AWG 18), max. 2 mm² (AWG 13), compliant with standards and national installation regulations. min mm² (AWG 22), twisted and unscreened Suitable network terminations (terminators) must be used for different network topologies. Failure to comply with the specified requirements may cause transmission errors between the controllers. The use of different cable cross-sections in one network section is not permitted. Detailed guidelines on planning and installing twisted-pair LonWorks networks have been published by the Echolon Corporation. Connections: LON network: 2 jack plugs, mono, 1/8" (3.5 mm) Earth terminals: 19 I/O terminals: 24 LS-MM terminals: 24 V~/= Room operating unit: 2 (SMRT +/- ) Hardware: The modu420 automation station comprises: Processor: Neuron 3150 ; 8 bit; 10 MHz Memory: Non-volatile 64 kb flash memory (APB application) Non-volatile 128 kb flash-chip (programme) Communication: LonTalk protocol Channel: TP/FT-10; 78 kbit/s Status indicators: Green LED: Power supply status and LON-TX Description of inputs and outputs The modu420 automation station has 6 universal inputs, 5 Triac outputs and 3 universal outputs on the hardware side. All the inputs and outputs must be configured via software. The input resolution is 16 bits and the output resolution is 10 bits. The inputs and outputs may be used as follows: Input: Temperature sensor: Potentiometer: Current: Digital: Pulse: Ni1000, NTC, Pt 10 k, 100 k 0 20 ma (4 20 ma) Dry contact Dry contact 500 ms min. ON/OFF Output: Current: 0 20 ma Voltage: 0 10 V= Digital: 0/12 V=, (I/O) PWM Triac: PWM, on/off, floating 1 A max The sampling period for the inputs is 1 s if they are configured as current, voltage, potentiometer or temperature inputs, and 500 ms for configuration as digital or pulse inputs. The UIx inputs can take a maximum load of 24 V. 2/6

3 EY-AS420 Technical specifications of inputs and outputs Temperature measurement (Ni1000, NTC, Pt) The Ni/Pt1000 sensors are connected using the two-wire method between one of the input terminals for a universal input (UI01 UI06) and an earth terminal. In case of an Ni/NTC/Pt connection, the inputs do not require calibration and can be used directly. The connected sensor type and the desired offset input are chosen in the software. Ni1000 Accuracy: ± 0.5 C Circuit: Period duration Value Short-circuit/ override *) < 5 s > 5 s > 15 s Override = on Override = off Input = Open: NTC type 2, 10 k Accuracy: ± 0.5 C NTC type 3, 10 k Accuracy: ± 0.5 C Circuit: Period duration Value Short-circuit/ override *) < 5 s > 5 s > 15 s Override = on Override = off Input = Open: PT1000, 1 k Accuracy: ± 1 C PT100, 100 k Range: C Accuracy: ± 1 C Circuit: Period duration Value Short-circuit/ override *) < 5 s > 5 s > 15 s Override = on Override = off Input = Open: *) If the input is short-circuited, this may be interpreted as an override, i.e. the relevant control loop is switched from "unoccupied" status to the "occupied/override" operating mode. Potentiometer measurement (Pot) It is possible to use the input in combination with a potentiometer if a 10 k or 100 k resistance is used. For configuration purposes, the resistance value can be limited and scaled to any desired value range in C. A potentiometer is connected between an input terminal of a universal input (UI01 UI06) and the associated earth terminal. The measurement accuracy is ± 0.5%. Current measurement (I) The current to be measured is connected to the input terminals of the universal inputs (UI01 UI06) between UIx and earth. The signal must be potential-free. In order to use the current input on the modu420 automation station, either a supply of current to the sensor or a parallel input-sensor supply is required. A 249 resistance must also be connected in parallel with the input. The input is defined as a 0 20 ma input by default. To adapt the input to 4 20 ma, the minimum value must be configured as 4 ma in the software. Voltage measurement (U) The universal inputs (UI01 UI06) are used to measure voltage. The voltage input has a range of 0 10 V. The connection is made to an input and the associated earth terminal. The voltage signal must be potential-free. The input can be adapted to different ranges via software. Parameters "min.", "max." or "offset" are available for this purpose. Digital inputs All universal inputs (UI01 UI06) can be used as digital inputs and must be connected to earth. Type of inputs: Pulse counters: Potential-free contacts, connected to earth Opto-coupler Transistor (open collector) 500 ms on/off Digital inputs (DI) Digital information is connected between the input terminals (UI01 UI06) and earth. The station applies a voltage of approx. 13 V to the terminal. In normal cases (NORMAL) this corresponds to INACTIVE (bit=0) for an open contact. When a contact is closed it is ACTIVE (bit=1) and 0 V is applied, whereby the current flow equates to approx. 1 ma. For each input, it is possible to define the "on" and "off" values individually, as well as the direction of operation (normal or reverse). Pulse counter at digital input (CI with DI) Counter inputs for potential-free contacts, opto-couplers or transistors with an open collector can be connected to the digital inputs. The maximum time that can be measured between the ON and OFF values for the input must be at least 500 ms. Pulses are measured on the rising and falling flanks. The values for this purpose can be adjusted individually. The combination of the two values is evaluated as a pulse. Digital output (DO) All the universal outputs (UO01 UO03) can be configured as digital outputs. A discrete output signal is issued: 0 V= for OFF and 12 V= for ON. If a relay is triggered via the universal output, a diode (1N400x family) must be connected to the connection terminals in parallel. This protects the output against voltage peaks when the relay cuts out. If the universal outputs are configured as PWM outputs, the period duration can be set between 2 s and 15 min. The period duration can be set between 0 and 100% of the "on" duration. Loading capacity of the output: max. 60 ma at 12 V= Max. load 200 The output is fitted with a self-resetting fuse. Maximum power load: 60 ma at 60 C 100 ma at 100 C The output is written immediately if the programmed value changes. However, this does not take place more quickly than the programme cycle time. It is not advisable to connect a relay to the output in PWM mode. 3/6

4 EY-AS420 Voltage output (U) The universal outputs (UO01 UO03) can be configured as voltage outputs, via the software. The output voltage is measured between the relevant output terminal and an earth terminal (UOx, Com). Type of output: 0(2)...10 V= approx. 60 ma to earth Triac outputs 5 x digital Triac max. 1.0 A for 24 V~ at Tmax 40 C Triac max A for 24 V~ at Tmax 70 C One earth per output The Triac outputs can be configured as PWM, digital (on/off) or 3- point outputs, according to choice. For use as a 3-point output, it is mandatory to use two adjacent outputs. Time programme and calendar A maximum of two independent time programmes can be configured in the AS programme. This is done via a plug-in. Each time programme supports up to 6 events per day of the week. In addition, 4 special days with up to 6 events each can be configured per time programme. Behaviour on switching off or in case of a mains failure All the programme parameters are stored in the flash memory to secure them against failures. When the station is reconnected to the power supply, the user programme is started as normal. LED displays The automation station has 3 LED displays on the front to signal operating statuses and network communication. The three LEDs on the left, arranged vertically, indicate the following statuses: LED name Display Description Permanently on Normal mode Permanently off APB file missing (AS has no application loaded) SERVICE Flashing AS in operation; LED flashes depending on execution of the programme Flashing slowly (1 s on/1 s off) AS is not configured Flashing quickly (0.3 s on/1 s off) Watchdog time-out; application is faulty. RX/TX Flickers irregularly AS is sending and/or receiving data LEDs O01 O08 signal the operating status of the universal outputs depending on the specific configuration. Output configuration Analogue output (0 10 V) Digital output PWM Display 0 V = off 10 V = on 0 V = off 10 V = on 0V = off 12 V = on Programming and parameterisation of the automation station Commissioning the automation station To commission the automation station, it must be connected to the LON network. Sauter CASE LON Engine can be used to commission the automation station. To do this, call up the Commission Device function, select the appropriate image (.abp file) and then press the Service Pin on the automation station. If an incorrect.apb file is loaded, the neuron chip may be destroyed and the automation station will become unusable. Network variables The controller software supports all structured SNVTs and UNVTs of 1 and 2 bytes in length. 17 NVIs and 17 NVOs (with changeable types and lengths) are available. 5 additional NVIs are available as possible bindings, as fan inputs. In this case, 3 NVIs can be used (supporting up to 80 NVs) in combined minimum, maximum, total or average function, and 2 NVIs in maximum or minimum function. User programme To create the user programme, a graphic programming interface is available in which individual function blocks are combined to form complex programmes. For this purpose, the modu420 automation station supports the use of up to 16 independent PID loops and 2 schedules. Once functions have been created within the programming environment, it is possible to store them for further use in the form of one's own user modules. The software supports the following types of function block (functions): Comparators (=,, <, >, ) constant and variable (types: numerical and enumeration), customer-specific function blocks, function blocks of a general nature (min, max, limit, etc.), HVAC (optimum start/stop, enthalpy calculation, dew-point calculation, etc.), logic functions (and, or, switch, multiplexer, etc.), mathematical functions (+, -, *, /, sum, root, etc.), SNVT conversion, time functions (timer, schedule, etc.) and VAV functions. A value range of 24 bits (± ) is available for integers. Up to 10 values can be stored permanently so that they are not lost after a reset. The two schedulers have simply configurable weekly, daily and vacation planners. Special events can quickly be added or deleted. Seven weekly templates and six configurable events can be set per day for each scheduler. 4/6

5 EY-AS420 Functional profile nvirequest SNVT_obj_request nvifilereq SNVT_file_req nvifilepos SNVT_file_pos Mandatory Network Variables Node Object #0 nvostatus SNVT_obj_status Optional Network Variables nvofilestat SNVT_file_status nvifp_xx (xx=09-12) Manufacturer Network Variables Manufacturer Network Variables Fan-In Support nvifp_xx (xx=13-14) (Hisel & Lowsel) nvofp_xx (xx=07-17) 6x Optional Configuration Properties Device Major Version (SCPTdevMajVer) Device Minor Version (SCPTdevMinVer) Location (SCPTlocation) Manufacturer Configuration Properties Hardware Information (UCPThardwareInfo) Mandatory Network Variables Hardware Input Open-Loop Sensor #1 Optional Configuration Properties Maximum Send Time (SCPTMaxSendTime) Minimum Send Time (SCPTMinSendTime) Manufacturer Configuration Properties nvofp_xx nvifp_xx (xx=15-17) nvimodify UNVT_modify_internal_val (Hisel, Lowsel, Sum & Average) Free Programmable Internal Points FreeProg Object Type #20100 nvovn1_7 UNVT_Internal_var_1to7 nvovn8_14 UNVT_Internal_var_8to14 nvovn15_21 UNVT_Internal_var_15to21 nvovn22_28 UNVT_Internal_var_22to28 nvovn29_35 UNVT_Internal_var_29to35 nvove1_27 UNVT_Internal_var_1to27 nvohwi1_6 UNVT_hardware_input_1to6 nvosmi1_5 UNVT_sm_Input_1to5 nvowri1_14 UNVT_wr_Input_1to14 nvohwo1_8 UNVT_hardware_output_1to8 8x nvifp_xx xx=01to06 Mandatory Network Variables Hardware Output Open-Loop Actuator #3 Optional Configuration Properties Maximum Receive Time (SCPTmaxRcvTime) Manufacturer Configuration Properties Valid Output Signal Type (UCPTvalidOutputSignalType) Configuration Properties nvofp Configuration Properties: Update Rate (SCPTupdateRate) Default Output (SNVT_tod_event) nvifp Configuration Properties: Maximum Receive Time (SCPTmaxRcvTime) Manufacturer Configuration Properties: Object Major Version (SCPTobjMajVer) Object Minor Version (SCPTobjMinVer) Minimum Send Time (SCPTminSendTime) Maximum Send Time (SCPTmaxSendTime) Associated File Index (UCPTassociatedFileIndex) ncicn1_7 (UNVT_Internal_const_1to7) ncicn8_14 (UNVT_Internal_const_8to14) ncicn15_21 (UNVT_Internal_const_15to21) ncicn22_28 (UNVT_Internal_const_22to28) ncicn29_35 (UNVT_Internal_const_29to35) ncice1_31 (UNVT_Internal_const_1to31) xx=01to08 2x Scheduler Object Type #20020 Manufacturer Network Variables nvischedulex SNVT_tod_event nvoschedulex SNVT_tod_event Configuration Properties nvoschedule Configuration Properties: Update Rate (SCPTupdateRate) Default Output (SNVT_tod_event) nvischedule Configuration Properties: Maximum Receive Time (SCPTmaxRcvTime) Manufacturer Configuration Properties: Object Major Version (SCPTobjMajVer) Object Minor Version (SCPTobjMinVer) Associated File Index (UCPTassociatedFileIndex) x=1to2 5/6

6 Dimension drawing 144,8 50,8 108,0 12VDC Relay M11424 M ,4 57,2 Wiring diagram Triac DOx x-x Fuse AXT111F202 + Ext. Trafo 230 / 24 V Ls MM 24 V modu420 Outputs (Triac) Outputs (Universal) Service Power Inputs (Universal) ecounit 482 TX RX A10589a Fr. Sauter Ltd Im Surinam 55 CH-4016 Basle Tel Fax info@sauter-controls.com 6/ Printed in Switzerland

Fan-coil intelligent unitary controller

Fan-coil intelligent unitary controller SAUTER EY-modulo 4 PDS 94147 en Product Data Sheet EY-RC401 ecos401: Fan-coil intelligent unitary controller How energy efficiency is improved Demand-led control for fan-coil and chilled beams applications

More information

LONMARK Certified 14-Point Programmable Controller. Overview

LONMARK Certified 14-Point Programmable Controller. Overview LONMARK Certified 14-Point Programmable Controller Applications Meets the requirements of the following applications: Rooftop Units Fan Coil Units Heat Pump Units Unit Ventilators Small Air Handling Units

More information

LONMARK Certified 10-Point Programmable Controller. Overview

LONMARK Certified 10-Point Programmable Controller. Overview LONMARK Certified 10-Point Programmable Controller Applications Meets the requirements of the following applications: Fan Coil Units Heat Pump Units Unit Ventilators Chilled Ceilings Improves energy efficiency

More information

DDC volume flow controller

DDC volume flow controller SAUTER EY-modulo 4 PDS 94.120 en Product Data Sheet ecos415: DCC volume flow controller How energy efficiency is improved Demand-led control for air volume flows using efficient control strategies. Battery-free

More information

ECP-103 Series. ECP-103 Series. 10-Point Free Programmable Controller. Applications. Features

ECP-103 Series. ECP-103 Series. 10-Point Free Programmable Controller. Applications. Features ECP-103 Series 10-Point Free Programmable Controller Applications Control of terminal units such as VAV, FCU, UV and HPU as well as control for chilled ceiling applications. Control of many other types

More information

EY-EM 527: Remote I/O module, ecolink527

EY-EM 527: Remote I/O module, ecolink527 Product data sheet 94.078 EY-EM 527: Remote I/O module, ecolink527 How energy efficiency is improved Regulation, control, monitoring and optimisation of operational systems, e.g. room automation or HVAC

More information

ECP-400 Series. ECP-400 Series. 24-Point Free Programmable Controller. Applications. Features

ECP-400 Series. ECP-400 Series. 24-Point Free Programmable Controller. Applications. Features ECP-400 Series 24-Point Free Programmable Controller Applications Control of equipment such as: roof top units, multistage air handling units, chillers, boilers, pumps, cooling towers, lighting systems,

More information

EY-EM 522, 523: Remote I/O module, ecolink522, 523

EY-EM 522, 523: Remote I/O module, ecolink522, 523 Product data sheet 94.077 EY-EM 522, 523: Remote I/O module, ecolink522, 523 How energy efficiency is improved Regulation, control, monitoring and optimisation of operational systems, e.g. room automation

More information

EYL225: nova225, Compact automation station

EYL225: nova225, Compact automation station SAUTER EY3600 PDS 92.525 en Product Data Sheet EYL225 EYL225: nova225, Compact automation station The nova225 compact automation station can be connected with various outlying units, so-called field modules.

More information

ECL-VAV-N. Features & Benefits

ECL-VAV-N. Features & Benefits D a t a s h e e t ECL-VAV-N Overview The ECL-VAV-N controller is a microprocessorbased programmable variable air volume (VAV) controller designed to control any variable air volume box. This controller

More information

ECB-103 BACnet B-ASC 10-Point Programmable Controllers

ECB-103 BACnet B-ASC 10-Point Programmable Controllers D a t a s h e e t BACnet B-ASC 10-Point Programmable Controllers Overview The is a microprocessor-based programmable controller designed to control terminal units such as fan coil unit, heat pump unit,

More information

NRT 105: Electronic fan-coil controller, equiflex

NRT 105: Electronic fan-coil controller, equiflex Product data sheet 4.04 R 105: Electronic fan-coil controller, equiflex How energy efficiency is improved ECO Meter for displaying the current energy consumption and digital input for the change-over between

More information

EYK220: nova220, Compact automation station with BACnet interface

EYK220: nova220, Compact automation station with BACnet interface SAUTER EY3600 PDS 92.450 en Product Data Sheet EYK220 EYK220: nova220, Compact automation station with BACnet interface This EYK220 is the compact nova220 units of the EY3600 system family equipped with

More information

Control solutions Biofloor

Control solutions Biofloor MR24 Central radio controller 24V Connect COMAP offers the Connect control system as part of its underfloor heating and cooling solution. Composed of a central radio control module (MR24), wireless digital

More information

Lonbox PIO4014 Users Manual

Lonbox PIO4014 Users Manual PROLON CONTROL SYSTEMS Herstedvesterstraede 56 DK-2620 Albertslund Denmark Tlf.: (+45) 43668060 Fax.: (+45) 43668061 e-mail: info@prolon.dk Internet: www.prolon.dk Lonbox PIO4014 Users Manual PIO4014 energy

More information

SRC-110 Series Zone Controllers with Modbus RTU

SRC-110 Series Zone Controllers with Modbus RTU Product sheet CT2.142 Type SRC-110-MOD SRC-110 Series Zone Controllers with Modbus RTU The SRC-110 series controllers have been designed for zone heating and cooling control. The controllers have 3 analogue

More information

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency echnical data sheet GR24A--R Communicative Retrofit rotary actuator for rotary valves and butterfly valves Nominal torque 40 Nm Nominal voltage AC/DC 24 V Control Modulating DC (0)2...10 V Variable Position

More information

CONTA-ELECTRONICS. Converter Units

CONTA-ELECTRONICS. Converter Units CONTA-ELECTRONICS Whether for manufacturing, electrical machine and plant instrumentation, control engineering, power distribution, building automation, or process engineering it is always important to

More information

NRT 300: Electronic air-conditioning controller, heating/cooling, equiflex

NRT 300: Electronic air-conditioning controller, heating/cooling, equiflex roduct data sheet 43.019 NR 300: Electronic air-conditioning controller, heating/cooling, equiflex ow energy efficiency is improved ey directly on device for individual changeover between presence and

More information

DUAL 4-20 MA NETWORK BRIDGE. Voltage. Regulator. Neuron CPU. Ohm Sense Resistor. Model 1400A Block

DUAL 4-20 MA NETWORK BRIDGE. Voltage. Regulator. Neuron CPU. Ohm Sense Resistor. Model 1400A Block NEUROLOGIC RESEARCH CORPORATION MODEL 1400A DUAL 4-20 MA NETWORK BRIDGE Instantly integrate any standard sensor into the LONWORKS digital network. Supports loop and self powered sensors. Electronics are

More information

XIOC technology and networking modules

XIOC technology and networking modules / XIO XIO digitale and analog input/output modules XIO technology and networking modules XIO the compact I/O and much more XIO are local expansion modules for direct connection to all Xontrol controllers.

More information

92.450/1. EYK 220: nova220, Compact automation station with BACnet interface. Sauter Systems

92.450/1. EYK 220: nova220, Compact automation station with BACnet interface. Sauter Systems 92.450/1 EYK 220: nova220, Compact automation station with BACnet interface This EYK 220 is the compact nova220 units of the EY3600 system family equipped with a BACnet communication card (EYK 300). This

More information

FX10 Standard Programmable Electronic controller for HVAC and refrigeration applications. Features and Benefits

FX10 Standard Programmable Electronic controller for HVAC and refrigeration applications. Features and Benefits Slim Object Platform Catalogue Product Bulletin FX10 Issue Date 0 00 FX10 Standard Programmable Electronic controller for HVAC and refrigeration applications I ntroduction The FX10 is a high performance,

More information

Sensor Plug-In Description / Documentation

Sensor Plug-In Description / Documentation Sensor Plug-In LONWORKS UK24LON LonTal ka b Open Loop Sensor Object # 1 MFT-H SNVTtempp MP-Com. 0V 24V Y U/MP Power 0V 24V n.c. z.b. Regelgerät nvi..(name) SNVTtempp Pt1000 T ~ AC 24 V DC 24 V Weitere

More information

VFSC9 ELECTRONIC SPEED CONTROLLER. Mounting and operating instructions

VFSC9 ELECTRONIC SPEED CONTROLLER. Mounting and operating instructions ELECTRONIC SPEED CONTROLLER Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 5 WIRING

More information

Power amplifier for thermic valve actuators

Power amplifier for thermic valve actuators 9 Power amplifier for thermic valve actuators For controllers with an AC V output signal The power amplifier is used to allow the connection of additional valve actuators to controllers with an AC V output

More information

Electro Controls. Input-Output Modules WattsIndustries.co.uk

Electro Controls. Input-Output Modules WattsIndustries.co.uk Electro Controls Input-Output Modules - 2017 WattsIndustries.co.uk Input-Output Modules Section 08 B.M.S INPUT - OUTPUT MODULES SINGLE AND ADJUSTABLE RELAY ESRM.. Volt free contacts DIN RAIL mounted relay

More information

High-quality digital indicator for panel mounting Model DI35-M, with multi-function input Model DI35-D, with two inputs for standard signals

High-quality digital indicator for panel mounting Model DI35-M, with multi-function input Model DI35-D, with two inputs for standard signals Accessories High-quality digital indicator for panel mounting Model DI35-M, with multi-function input Model DI35-D, with two inputs for standard signals WIKA data sheet AC 80.03 Applications Machine building

More information

Analogue temperature controllers

Analogue temperature controllers Analogue temperature controllers CT8A Input by J-K thermo-couple or by thermo-resistance Pt 00 (-wire) regulation modes : ON/OFF or proportional derivative selected by wiring Relay output Specifications

More information

PolyGard Digital Transmitter DGC DT-02

PolyGard Digital Transmitter DGC DT-02 PolyGard Digital Transmitter DGC DT-02 Description LON interoperable digital gas transmitter to monitor toxic and combustible gases and vapors in the ambient air. The complete monitoring and alarm tripping

More information

Viconics VT76x7 Series Rooftop Unit Controllers Engineering Guide Specification

Viconics VT76x7 Series Rooftop Unit Controllers Engineering Guide Specification Viconics VT76x7 Series Rooftop Unit Controllers Engineering Guide Specification General The VT76x7 series is designed for single-stage and multi-stage control of heating/cooling equipment such as rooftop

More information

EQJW145. Content: 1 General. 2. Indicators and operating controls 3. Putting into service (by a technician) 4. How to operate (user)

EQJW145. Content: 1 General. 2. Indicators and operating controls 3. Putting into service (by a technician) 4. How to operate (user) SAUER equitherm Electronic heating controller 1) Valid from soft version 09 Content: General 2. Indicators and operating controls 3. Putting into service (by a technician) 4. How to operate (user) en Quick

More information

43.019/1. NRT 300: Electronic controller for air-conditioning (heating/cooling) Sauter Components

43.019/1. NRT 300: Electronic controller for air-conditioning (heating/cooling) Sauter Components 43.09/ NR 300: Electronic controller for air-conditioning (heating/cooling) For fixed-value control (I control, continuous) in air-conditioning systems, for residential and business premises. Used with

More information

Electronic Step Controller

Electronic Step Controller 4 915 Electronic Step Controller, Adjustable switch-on delay (typically used to prevent current surges on startup and after a power failure) Adjustable switch-on points Adjustable switching differential

More information

Radiocontrol F. Floor Heating Controller Radio control system for floor heating

Radiocontrol F. Floor Heating Controller Radio control system for floor heating Radiocontrol F Floor Heating Controller Radio control system for floor heating IMI HEIMEIER / Floor Heating Control / Radiocontrol F Radiocontrol F The Radiocontrol F radio control system for controlling

More information

LON I/O Module DR-N MCU4-AC Art. no.: MTN881811

LON I/O Module DR-N MCU4-AC Art. no.: MTN881811 Art. no.: MTN881811 User Manual LON I/O Module DR-N MCU4-AC Art. no.: MTN881811 Directory Directory... 1 1.... 2 2. Function... 2 3. Mounting... 3 4. Remarks... 3 5. Technical Data... 4 6. Application

More information

QFM21... Duct sensors. Symaro. for relative humidity and temperature

QFM21... Duct sensors. Symaro. for relative humidity and temperature 1 864 1864P01 Symaro Duct sensors for relative humidity and temperature QFM21... Operating voltage AC 24 V / DC 13.5...35 V Signal output DC 0...10 V / 4 20 ma for relative humidity Signal output DC 0...10

More information

Thermostat P. Thermostats Electronic room thermostat with clock for thermal actuators

Thermostat P. Thermostats Electronic room thermostat with clock for thermal actuators Thermostat P Thermostats Electronic room thermostat with clock for thermal actuators IMI HEIMEIER / Thermostats & Actuators / Thermostat P Thermostat P The Thermostat P room temperature controller is used

More information

Data Acquisition Modules/ Distributed IO Modules

Data Acquisition Modules/ Distributed IO Modules User Manual Data Acquisition Modules/ Distributed IO Modules Future Design Controls, Inc. 7524 West 98 th Place / P.O. Box 1196 Bridgeview, IL 60455 888.751.5444 - Office: 888.307.8014 - Fax 866.342.5332

More information

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency echnical data sheet LR24A-KNX Communicative rotary actuator for ball valves Nominal torque 5 Nm Nominal voltage AC/DC 24 V Control modulating Conversion of sensor signals Communication via KNX (S-Mode)

More information

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency echnical data sheet SVK24A--PC Communicative globe valve actuator with emergency control function for 2-way and 3-way globe valves Actuating force 1500 N Nominal voltage AC/DC 24 V Control modulating,

More information

Functional description "BIU-2ILT"

Functional description BIU-2ILT Cécile PAULME AEG Functional description "BIU-2ILT" TABLE OF CONTENTS 1. INTRODUCTION 3 2. ELECTRONIC PRODUCT FORM 4 2.1 Product description...4 2.2 Physical installation...5 2.3 Technical specifications...6

More information

Compact room automation stations, BACnet MS/TP, AC 24 V

Compact room automation stations, BACnet MS/TP, AC 24 V Desigo Room Automation Compact room automation stations, BACnet MS/TP, AC 24 V DXR2.M11.., DXR2.M12P.., DXR2.M12PX.., DXR2.M18.. For building with increased demands placed on functionality and flexibility

More information

Gateway EnOcean/LonWorks

Gateway EnOcean/LonWorks s 1 661 1661P01, 1661P02 DESIGO RXC Gateway EnOcean/LonWorks For use with: DESIGO RXC Devices / systems with LONWORKS communication RXZ95.1/LON Wireless receiver with LONWORKS interface FTT10A Evaluation

More information

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency echnical data sheet GM24A--P Communicative damper actuator for adjusting dampers in technical building installations Air damper size up to approx. 8 m² Nominal torque 4 Nm Nominal voltage AC/DC 24 V Control

More information

FTT-10A Free Topology Twisted Pair Transceiver Model 50051

FTT-10A Free Topology Twisted Pair Transceiver Model 50051 FTT-10A Free Topology Twisted Pair Transceiver Model 50051 Description The FTT-10A Free Topology Twisted Pair Transceiver provides a simple, cost-effective method of adding a LONWORKS transceiver to any

More information

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency echnical data sheet Communicative damper actuator for adjusting dampers in technical building installations Air damper size up to approx. m² Nominal torque 5 Nm Nominal voltage AC/DC 24 V Control Modulating

More information

NetBiter I/O Extender 4RO 6RTD 8DIO - DAIO User Manual Revision 1.00

NetBiter I/O Extender 4RO 6RTD 8DIO - DAIO User Manual Revision 1.00 NetBiter I/O Extender 4RO 6RTD 8DIO DAIO User Manual Revision 1.00 IntelliCom Innovation AB Linjegatan 3D SE302 50 Halmstad SWEDEN Phone +46 35 18 21 70 Fax +46 35 18 21 99 email info@intellicom.se www

More information

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency echnical data sheet LH24A-00 Communicative linear actuator adjusting dampers and slide valves in technical building installations Air damper size up to approx. m² Actuating force 50 N Nominal voltage AC/DC

More information

ELECTRONIC THERMOSTAT: T920

ELECTRONIC THERMOSTAT: T920 μnistδt ELECTRONIC THERMOSTAT: T One analog output DESCRIPTION The T series thermostats are microcomputer-based, proportional and integral (PI) devices with one analog 0 to 0 output. They can be used with

More information

Sauter Components

Sauter Components R 44.488/ QRK 0: Heating controller Used in conjunction with temperature detectors (Ni000) and appropriate control valves for heating and domestic-hot-water control (with various configurations), mainly

More information

21 VA (l max 20 5 ms) Connection Cable 1 m, 4 x 0.75 mm 2 Functional data Factory settings Variable Setting Torque Inhibiting torque

21 VA (l max 20 5 ms) Connection Cable 1 m, 4 x 0.75 mm 2 Functional data Factory settings Variable Setting Torque Inhibiting torque echnical data sheet GK4A- Communicative SuperCap rotary actuator with emergency setting function and extended functionalities for adjusting air dampers in ventilation and air-conditioning systems for building

More information

Excel 10 W7761A Remote Input/Output Device

Excel 10 W7761A Remote Input/Output Device Excel 0 W776A Remote Input/Output Device INSTALLATION INSTRUCTIONS PRODUCT DESCRIPTION The W776A Remote Input/Output (RIO) Device is a Free Topology Transceiver (FTT) LonMark compliant device in the Excel

More information

PLC-K506 Series FEATURES DESCRIPTION FEATURES

PLC-K506 Series FEATURES DESCRIPTION FEATURES FEATURES Two High Speed Counters Two Pulse Train Outputs Two Pulse Width Modulation Outputs Inputs 10 Outputs 1 RS232 Port 2 RS485 Ports Supports Modbus RTU Protocol Communicate With Up to 32 Devices DESCRIPTION

More information

Manual triggering of the adaption by pressing the «Adaption» button or with the PC-Tool

Manual triggering of the adaption by pressing the «Adaption» button or with the PC-Tool echnical data sheet SMA--P Multifunctional damper actuator for adjusting air dampers in ventilation and air-conditioning systems for building services installations For air dampers up to approx. m orque

More information

Functional data Factory settings Variable Settings

Functional data Factory settings Variable Settings echnical data sheet Rotary actuator RF-MF(-O) Multifunctional rotary actuator with emergency control for and 3 way control ball valve orque Nm Nominal voltage AC/DC V Control: Modulating DC... V or variable

More information

11 VA Connection Cable 1 m, 4 x 0.75 mm 2 Functional data Factory settings Variable Setting Torque (nominal torque) Motor Spring return

11 VA Connection Cable 1 m, 4 x 0.75 mm 2 Functional data Factory settings Variable Setting Torque (nominal torque) Motor Spring return echnical data sheet SF24A- Communicative spring return actuator with emergency function for adjusting air dampers in ventilation and air conditioning systems in buildings For air dampers up to approx.

More information

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency echnical data sheet LR24A-KNX Communicative rotary actuator for ball valves Nominal torque 5 Nm Nominal voltage AC/DC 24 V Conversion of sensor signals echnical data Electrical data Nominal voltage AC/DC

More information

Intelligent Compact Controller

Intelligent Compact Controller TCY-T0121 Intelligent Compact Controller Features Temperature control for 2-pipe, 4-pipe HVAC systems. Temperature range from 40 to 140 C. 1 independent PI and On/Off control loop to control temperature.

More information

Outside Temperature Sensors

Outside Temperature Sensors 1 814 1814P01 Symaro Outside Temperature Sensors QAC31 Active sensors for acquiring the outside temperature Operating voltage AC 24 V or DC 13535 V Signal output DC 010 V or 420 ma Use The QAC31 outside

More information

Wireless multizone receiver RDE-MZ6

Wireless multizone receiver RDE-MZ6 s 1 428 Wireless multizone receiver RDE-MZ6 for floor heating / zone heating systems Mains-powered RDE-MZ6 multizone wireless receiver (AC 230 V) DIN rail mounting 2-position control with On/Off output

More information

SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS

SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS ELECTRICAL ENGINEERING DIVISION Distribution Network Department SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS ELA T150.2 en SRA 2250/6 Resistor specification The SRA 2250/6 Resistor is intended to increase

More information

R7L-YV2. DC VOLTAGE OUTPUT MODULE, 2 points MODEL BEFORE USE... POINTS OF CAUTION COMPONENT IDENTIFICATION INSTRUCTION MANUAL R7L-YV2

R7L-YV2. DC VOLTAGE OUTPUT MODULE, 2 points MODEL BEFORE USE... POINTS OF CAUTION COMPONENT IDENTIFICATION INSTRUCTION MANUAL R7L-YV2 INSTRUCTION MANUAL DC VOLTAGE OUTPUT MODULE, 2 points MODEL R7L-YV2 BEFORE USE... Thank you for choosing M-System. Before use, please check contents of the package you received as outlined below. If you

More information

Technical Information itemp TMT180

Technical Information itemp TMT180 TI00088R/09/EN/14.16 71315611 Technical Information itemp TMT180 Temperature head transmitter for resistance thermometers Pt100 Configurable using a PC, for installation in a terminal head, form B Application

More information

High-quality digital indicator for panel mounting Model DI35-M, with multi-function input Model DI35-D, with two inputs for standard signals

High-quality digital indicator for panel mounting Model DI35-M, with multi-function input Model DI35-D, with two inputs for standard signals Accessories Highquality digital indicator for panel mounting Model DI35M, with multifunction input Model DI35D, with two inputs for standard signals WIKA data sheet AC 80.03 Applications Machine building

More information

n FRONT PANEL CONFIGURATIONS

n FRONT PANEL CONFIGURATIONS INSTRUCTION MANUAL VALVE POSITIONER (for LonWorks; built-in SSR) MODEL MEXL MEXL BEFORE USE... Thank you for choosing M-System. Before use, check the contents of the package you received as outlined below.

More information

KNC-PLC-K506 Series FEATURES DESCRIPTION FEATURES

KNC-PLC-K506 Series FEATURES DESCRIPTION FEATURES FEATURES Two High Speed Counters Two Pulse Train Outputs Two Pulse Width Modulation Outputs Inputs 10 Outputs 1 RS232 Port 2 RS485 Ports Supports Modbus RTU Protocol Communicate with up to 32 devices DESCRIPTION

More information

control & display PROGRAMMABLE SENSOR CONTROLLER COMPLETE VERSATILITY OF SENSOR MANAGEMENT & DATA COMMUNICATIONS

control & display PROGRAMMABLE SENSOR CONTROLLER COMPLETE VERSATILITY OF SENSOR MANAGEMENT & DATA COMMUNICATIONS S E N S O R S PROGRAMMABLE SENSOR CONTROLLER TX9044 COMPLETE VERSATILITY OF SENSOR MANAGEMENT & DATA COMMUNICATIONS Analogue sensors, temperature devices, frequency inputs and digital sensors direct fingertip

More information

US2, US4, US6 Electronic step controllers

US2, US4, US6 Electronic step controllers 4 98 US, US4, Electronic step controllers The electronic step controllers are used in linear mode to switch devices (pumps, compressors, humidifiers and fans etc.) on and off in stages. Switch-on time

More information

Gateway EnOcean/LonWorks

Gateway EnOcean/LonWorks s 1 661 1661P01, 1661P02 DESIGO RXC Gateway EnOcean/LonWorks For use with: DESIGO RXC Devices / systems with LONWORKS communication RXZ95.1/LON Wireless receiver with LONWORKS interface FTT10A Evaluation

More information

HV / MV / LV electrical network quality analyzers Class A. Communication port: local, modem, integrated Ethernet, multi-point

HV / MV / LV electrical network quality analyzers Class A. Communication port: local, modem, integrated Ethernet, multi-point 2010 MAP Range HV / MV / LV electrical network quality analyzers Class A > Network quality Analyzers PRODUCT ADVANTAGES COMPLIANT with the EN 61000-4-30 standard, Class A DETECTION of the fault LOCATION

More information

ERV-M ELECTRONIC FAN SPEED CONTROLLER. Mounting and operating instructions

ERV-M ELECTRONIC FAN SPEED CONTROLLER. Mounting and operating instructions ELECTRONIC FAN SPEED CONTROLLER Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 5

More information

The universal input/output device is a DIN rail mounted device. It is connected to the EIB via a bus connecting terminal.

The universal input/output device is a DIN rail mounted device. It is connected to the EIB via a bus connecting terminal. , GH Q631 0026 R0111 SK 0097 B97 The universal input/output device is a DIN rail mounted device. It is connected to the EIB via a bus connecting terminal. The device has 32 freely programmable inputs/outputs,

More information

Room Temperature Controllers. for heating and cooling systems

Room Temperature Controllers. for heating and cooling systems 3 041 RCU10 RCU101 Room Temperature Controllers for heating and cooling systems RCU10 Choice of two-position or modulating PI control ON / OFF or PWM outputs for heating and cooling Operating modes: normal

More information

Room Sensors. for relative humidity and temperature

Room Sensors. for relative humidity and temperature 1 857 1857P01 Room Sensors for relative humidity and temperature QFA20 Operating voltage AC 24 V or DC 13535 V Signal output DC 010 V for relative humidity Signal output DC 010 V or LG-Ni 1000 or T1 for

More information

Room Sensors. In ventilating and air conditioning plants to acquire relative humidity and temperature in rooms. Humidity measuring range

Room Sensors. In ventilating and air conditioning plants to acquire relative humidity and temperature in rooms. Humidity measuring range 1 857 1857P01 Room Sensors for relative humidity and temperature QFA20 Use Operating voltage AC 24 V or DC 13535 V Signal output DC 010 V for relative humidity Signal output DC 010 V or LG-Ni 1000 or T1

More information

R7420B. MicroniK 100 HONEYWELL TEMPERATURE CONTROLLER PRODUCT DATA GENERAL FEATURES

R7420B. MicroniK 100 HONEYWELL TEMPERATURE CONTROLLER PRODUCT DATA GENERAL FEATURES HONEYWELL MicroniK 1 R742B TEMPERATURE CONTROLLER GENERAL PRODUCT DATA The temperature controller R742B uses direct digital control technology to provide a more accurate and efficient operation of heating,

More information

Controller for the Implementation of a Central or Decentralized Electrohydraulic System

Controller for the Implementation of a Central or Decentralized Electrohydraulic System EFX 1624m Electronic Controller Programmed with Eaton CONTROL F(x) Software to IEC 61131-3 Standard 2nd CAN interface for gateway function according to SAE J1939 Supply voltage 10...32V DC Technical Data

More information

Room Temperature Controllers. for heating and cooling systems

Room Temperature Controllers. for heating and cooling systems 3 048 RCU15 Room Temperature Controllers for heating and cooling systems RCU15 Choice of two-position or modulating PI control ON / OFF or PWM outputs for heating and cooling Control depending on room-

More information

Technical data. Safety notes. T3-LR24A-SR en v Subject to changes 1 / 2

Technical data. Safety notes.  T3-LR24A-SR en v Subject to changes 1 / 2 echnical data sheet LR4A-SR Modulating rotary actuator for and -way control ball valves orque Nm Nominal voltage AC/DC 4 V Control: Modulating DC... V Position feedback: DC... V echnical data Safety notes

More information

Netbiter IO Extender 4RO 6RTD 8DIO DAIO 8AIV 8AIIS

Netbiter IO Extender 4RO 6RTD 8DIO DAIO 8AIV 8AIIS USER MANUAL Netbiter IO Extender 4RO 6RTD 8DIO DAIO 8AIV 8AIIS Doc ID: HMSI-27-228 Version: 2.0 HALMSTAD CHICAGO KARLSRUHE TOKYO BEIJING MILANO MULHOUSE COVENTRY PUNE COPENHAGEN RAVENSBURG HMS Industrial

More information

NRT 107: Room- and supply-temperature controller, equiflex

NRT 107: Room- and supply-temperature controller, equiflex Product data sheet 43.036 NR 107: Room- and supply-temperature controller, equiflex Ho energy efficiency is improved Analogue input for shifting the setpoint depending on the outside temperature, and integrated

More information

Room sensors. In ventilating and air conditioning plants to acquire relative humidity and temperature in rooms. Humidity measuring range

Room sensors. In ventilating and air conditioning plants to acquire relative humidity and temperature in rooms. Humidity measuring range 1 857 1857P01 QFA20 Room sensors For relative humidity and temperature QFA20 Operating voltage AC 24 V or DC 13.5 35 V Signal output DC 0...10 V for relative humidity Signal output DC 0...10 V or LG-Ni

More information

STR-LCF. Security Advice Caution. Notes on Disposal. Electronic Fan Coil Thermostat (Flush mounting) Datasheet. Application

STR-LCF. Security Advice Caution. Notes on Disposal. Electronic Fan Coil Thermostat (Flush mounting) Datasheet. Application STR-LCF Electronic Fan Coil Thermostat (Flush mounting) Datasheet Subject to technical alteration Issue date: 28.2.217 Application The fan coil room thermostat has been designed for individual control

More information

Overview of types. Technical data

Overview of types. Technical data echnical data sheet SHA-.. Multifunctional linear actuators for adjusting air dampers and slide valves in ventilation and air-conditioning systems for building services installations For air control dampers

More information

Self-learning Room Temperature Controller Receiver

Self-learning Room Temperature Controller Receiver 2 265 REV23RF REV-R.02/1 REV23RF/SE Self-learning Room emperature Controller Receiver Consisting of controller (with integrated radio transmitter) and receiver (switching unit with relay outputs) REV23RF

More information

PHOENIX CONTACT - 03/2007

PHOENIX CONTACT - 03/2007 Inline Function Terminal for Pulse Width Modulation and Frequency Modulation N AUTOMATIONWORX Data Sheet 6920_en_01 1 Description PHOENIX CONTACT - 03/2007 $ ' ) The terminal is designed for use within

More information

Differential pressure sensors

Differential pressure sensors 1 912 1912P02 QBM64/ 1912P01 QBM63/ Differential pressure sensors for air and non-aggressive gases, with a diaphragm sensing element QBM63/ QBM64/ With choice of pressure-linear or extracting-the-root

More information

em4 local - Robust Specific characteristics Part number

em4 local - Robust Specific characteristics Part number em4 em4 local em4 local Very compact and easy to program nanoplc Save time in designing your application using the most intuitive graphical function block language of the market Measure accurately your

More information

LX Scheduler. Installation Instructions LX-SCHEDL-0. Mounting. Applications. North American Emissions Compliance. Installation

LX Scheduler. Installation Instructions LX-SCHEDL-0. Mounting. Applications. North American Emissions Compliance. Installation LX Scheduler Installation Instructions LX-SCHEDL-0 Code No. LIT-12011573 Issued April 28, 2014 Supersedes August 7, 2009 Applications The LX Scheduler controller features network-ready scheduling and a

More information

QUINT-PS/ 3AC/24DC/10

QUINT-PS/ 3AC/24DC/10 Primary-switched power supply with SFB technology, 3 AC, output current 10 A INTERFACE Data sheet 103131_en_01 1 Description PHOENIX CONTACT - 09/2009 Features QUINT POWER power supply units Maximum system

More information

J IPC IGBT power converter

J IPC IGBT power converter M. K. JUCHHEIM GmbH & Co Delivery address:mackenrodtstraße 14, 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: +49 661 60 03-0 Fax: +49 661 60 03-6 07 E-mail: mail@jumo.net Internet: www.jumo.net

More information

UniStream Uni-I/O Modules

UniStream Uni-I/O Modules UniStream Uni-I/O Modules Technical Specifications UIS-WCB1 This guide provides specifications for Unitronics Uni-I/O Wide module UIS-WCB1. This module comprises: 10 Digital inputs, 24VDC, sink/source,

More information

Electronic Air / Fuel Ratio Control System

Electronic Air / Fuel Ratio Control System 7 871 ISO 9001 Electronic Air / Fuel Ratio Control System RVW20... Electronic control unit - for use with modulating single- and dual-fuel burners - with extended functionality for mechanical air / fuel

More information

PROMUX Distributed MODBUS I/O Modules Catalog and Design Guide

PROMUX Distributed MODBUS I/O Modules Catalog and Design Guide PROMUX Distributed MODBUS I/O Modules Catalog and Design Guide 14/11/2006 V10 P.O.Box 24 Stanfield 3613 SOUTH AFRICA Tel: +27 (031) 7028033 Fax: +27 (031) 7028041 Email: proconel@proconel.com Web: www.proconel.com

More information

Compact room automation stations, BACnet/IP, AC 24 V

Compact room automation stations, BACnet/IP, AC 24 V Desigo Room Automation Compact room automation stations, BACnet/IP, AC 24 V DXR2.E12P.., DXR2.E12PX.., DXR2.E18.. For building with increased demands placed on functionality and flexibility in Room Automation

More information

Software Description SRCN_HWL_9_1_03 for SRC 04 FTT and SRC 65 FTT

Software Description SRCN_HWL_9_1_03 for SRC 04 FTT and SRC 65 FTT Software Description SRCN_HWL_9_1_03 for SRC 04 FTT and SRC 65 FTT 1 Overview The application enables the receipt and evaluation of max. nine EnOcean wireless sensors. The following sensor types are supported:

More information

DIN 22.5/17.5 Size Lineup of A Wide Range of Measuring and Monitoring Relays. Model Number Structure

DIN 22.5/17.5 Size Lineup of A Wide Range of Measuring and Monitoring Relays. Model Number Structure New Product News Measuring & Monitoring Relays K8AK/K8DS Series DIN 22.5/17.5 Size Lineup of A Wide Range of Measuring and Monitoring Relays Compact 22.5 mm and 17.5 mm housings Resistant to high-frequency

More information

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W ADC5000 SERIES AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications 60W, 125W and 250 W Input voltage 230/115 VAC voltages 12, 24, 36 or 48 VDC Statistical MTBF >3 000

More information

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency echnical data sheet NM24A- Communicative damper actuator for adjusting dampers in technical building installations Air damper size up to approx. 2 m² Nominal torque Nm Nominal voltage AC/DC 24 V Control

More information