OPTIVENT ULTRA VAV damper CONTROL UNIT FOR MODBUS 227VMZ-MB

Size: px
Start display at page:

Download "OPTIVENT ULTRA VAV damper CONTROL UNIT FOR MODBUS 227VMZ-MB"

Transcription

1 OPTIVENT ULTRA VAV damper CONTROL UNIT FOR MODBUS 227VMZ-MB

2 2 OPTIVENT ULTRA OPTIVENT ULTRA WITH COMPACT CONTROLLER FOR MODBUS 227VMZ-MB OPTIVENT ULTRA is a complete VAV unit consisting of a Modbus actuator, ultrasound based measuring sensor for pressure-independent control and user interface with 3-digit display which enables monitoring of the air flow and setting up values without external equipment. The controller can be operated via Modbus or with analogue signal, which is set to a standard value of - V on delivery. To change operating range to 2 - V see Setting the values, quick reference guide. The controller can also be force controlled via closing contacts (timer, presence detector, etc.) to override the set min or max air flow. It is also possible to use the controller with a CAV function. Modbus is wired according to 2-wire RS-485 rules. There can be up to 28 devices on one bus (Modbus load /4.) The wiring should be done using a twisted pair cable, such as Datajamak 2x(2+)x.24. The signal grounds of all devices on the same bus should be connected together. The bus should form a daisy chain, with the cable running from one device to the next without branches (max. branch length m). The maximum bus length is 8 m. The bus should be terminated at both ends using 2 Ω resistors. Master D R CONNECTION DIAGRAM Actuators are provided with color coded and numbered wires ( m). BU 2 BN S 3 BK Y/Z 4 GY 24 VAC/DC Supply U /2- VDC Control A WH B WH D D RS 485 /2- VDC Feedback (,5 ma) WIRING Modbus = BU = Blue 2 = BN = Brown 3 = BK = Black 4 = GY = Grey A = WH = White B = WH = White Lenght: mm Strand cross section: 4 x,75 mm2 2 x,38 mm2 Observe polarity on secondary of transformers. All common and signal ( ) must be connected in line. Incorrect polarity can cause controller damage or operation error. Provide overload protection for line voltage and disconnect as required. Consider voltage drops when connecting multiply actuators in parallel. Always use a separate transformer when controller power is full-wave rectified. Controller and actuators must have separate transformers for paralleled multi-actuator application. LT D R Slave Balanced Pair Slave n D D The bus cable should be connected to wires A and B in the same way at every device on the bus. The terminating resistors at both ends of the bus should be connected between wires A and B. If necessary to eliminate interference, the shield of the twisted pair cable can be connected to protective ground. The connection should be made only at one end of the shield, for example always to the cable coming from the controller. MODBUS FACTORY SETTINGS D R Transmission mode RTU Address Transfer rate 92 bps Data bits 8 Parity Even Stop bits Delay ms Response time ms + delay

3 OPTIVENT ULTRA 3 USER INTERFACE 3 Note: Setting or not setting the intermediate position Vbtw has no effect on the operation of the actuator when - / 2- VDC control voltage is used. Vbtw is activated only when forced control signal is used. FUNCTIONS, DETAILED DESCRIPTION 2 On the cover of the actuator there are two selectors, value selector () and function selector (2). Also there is the 3-digit display (3) to show selected functions, values and units. SETTING THE VALUES, QUICKREFERENCE GUIDE. Select air flow unit: Dot on upper-right or lower-right corner of display indicates which units that are used, l/s or m3/h. If there is need of change, turn the function selector until it points to Flow. Then turn the value selector until dot on display toggles to other position. After the selection the display flashes three dashes (- - -) twice for indication that new setting is stored. 2. Setting up Vmax: Turn the function selector until it points to Vmax. Then turn the value selector until desired air flow is shown on display. After the selection the display flashes twice for indication that new Vmax setting is stored. 3. Setting up Vmin: Turn the function selector until it points to Vmin. Then turn the value selector until desired air flow is shown on display. After the selection the display flashes twice for indication that new Vmin setting is stored. 4. Select input signal range: Turn the function selector until it points to Mode. Currently valid range is shown on display, -n for -V range or 2-n for 2-V range. If there is need of change, turn the value selector until desired value is shown on display. After the selection the new range is saved and the display flashes twice for indication. 5. Setting up Modbus address: Turn the function selector until it points to Adr. Then turn the value selector to select the desired address (-247). 6. Setting up Installation parameter: Turn function selector until it points to Inst. Then turn the value selector until desired parameter is shown in display. After the selection the display flashes for indication that new value is stored. Turn the function selector to Flow after the settings is set.. Value selector The value selector allows the changing of values. The position of the arrow shows the value set. The changes are displayed as soon as the selector is moved ± from its position. 2. Function Selector The function selector allows choosing the function depending on its position. If there is no function selected the display will show three dashes(- - -). Flow Shows the actual flow in selected units, m3 /h or l/s. This display matches with the feedback signal U. The display starts flashing if the servomotor hits an end stop before matching actual to reference flow. An overflow (air speed higher than 5 m/s) is indicated in the display by a small circle, see section Display. Turning the value selector allows unit selection. The appropriate dot on display is toggled as indicator. Dot on upper-right corner of display: unit of flow used is l/s. Dot on lower-right corner of display: unit of flow used is m3/h. Vmin Allows to set the desired minimum flow for the external reference signal Y=V/2V by turning the value selector. Selected value is shown on display in m 3 /h or l/s. Vbtw Enables the setting of desired intermediate position flow for the external forced control signal (negative rectified half wave from 24VAC supply) by turning the value selector. Selected value is shown on display in m3/h or l/s.

4 4 OPTIVENT ULTRA Vmax Allows to set the desired maximum flow for the external reference signal Y=V by turning the value selector. Selected value is shown on display in m3/h or l/s. Test Opens the diagnose menu. All outside input signals on Y are neglected and the controller only operates according to the selected override function. All override functions are disabled after a time-out of hours. The display toggles after the selection of the function between the actual flow (8s showing time) and the function (2s showing time). OFF-mode toggles with Y- signal. Selecting another function will disable the Diag function and set it automatically to OFF. Turning the value selector allows Diag function selection. The appropriate symbols on display are toggled as indicator. rst Activate calibration and self-diagnostic for the sensor. Shows the actual duct size e.g. size DN25 is shown as d2. Showing the software version. After 3s showing the display shows off again. Mode Allows to set the input signal range ( V or 2 V) by turning the value selector. The feedback signal range of U corresponds to Y. op(en) opens the damper -n... signal range is -V. cl(ose) closes the damper 2-n... signal range is 2-V. Hi(gh) forces the actuator to V max Lo(w) forces the actuator to V min Adr Selecting the Modbus address. Inst. Set installation parameter for short safety distance installations. Default value is. on Test mode is switched on. The actuator stays in the current position. off Test mode is switched off. The actuator starts controlling according to external signal Y. This signal Y shall be shown in the range of x - V

5 OPTIVENT ULTRA 5 INPUT SIGNALS (ANALOG) Note that control signals are ignored if Modbus control is activated (see register no 23). The input signal Y allows to control the VAV actuator according to the selected mode of operation. In mode VDC the input signal Y matches to the following flows: Vact = Vmin + Y. (Vmax - Vmin) VDC and the flows match to Y = VDC as (Vmin) and Y = VDC as (Vmax) Vact - Vmin Y = VDC. Vmax - Vmin In mode 2 VDC the input signal Y matches to the following flows: Y-2VDC Vact = Vmin +. 8VDC (Vmax - Vmin) OUTPUT SIGNALS (ANALOG) In mode VDC the output signal U matches to the following flows: Vact U = VDC. where Vnom is size dependent nominal flow and to calculate the actual flow Vact from the feedback signal U: Vact =. U Vnom VDC In mode 2 VDC the output signal U matches to the following flows: Vact U = 2VDC + (VDC. and to calculate the actual flow Vact from the feedback signal U: Vact = Vnom Vnom. U VDC Vnom and the flows match to Y = 2VDC as (Vmin) and Y = VDC as (Vmax) Vact - Vmin Y = 2VDC + 8VDC. Vmax - Vmin Mode 2 VDC includes special feature to close damper with input signal Y = VDC. See also Fig. Reference Signal Y.. V max Air volume flow. V min V Nom. Y... V ref = (V max V min ) + V min.. Y 2... V ref = (V max V min ) + V 8 min. Vmin See also Fig 2. Actual air volume flow U. V Nom (%) Air volume flow.. V act = V Nom Mode... VDC U Mode 2... VDC. V min (Apparat) 2 Actual air volume flow U Fig. 2. Actual air volume flow U.. V act = V Nom U 2 8 Control range VDC (Device) 2 Reference signal Y Fig. Reference Signal Y VDC

6 6 OPTIVENT ULTRA WIRING A B A B 24 VAC 24 VDC ~ 24 VAC ~ 24 VDC +... V 2... V... V 2... V Operating voltage Control signal Feedback signal Modbus RS485 blue (BU) brown (BN) black (BK) grey (GY) white (WH) The following wiring solutions are possible: Parallel control M M BU BN BK GY WH WH A B BU BN BK GY WH WH A B.../2... V DC 24 V AC/DC Modbus RS485 Master-slave (same sizes) M M Vmin = Vmax = Vnom BU BN BK GY WH WH BU BN BK GY WH WH A B A B.../2... V DC 24 V AC/DC Modbus RS485

7 OPTIVENT ULTRA 7 WIRING (CONT.) EMSF control EMSF UL(S,D)A - V 2- V - V 2- V p M GT-MB 227VMZ-MB BU BN GY WH WH BU BN BK GY WH WH 2 4 A B A B 24 V AC/DC ~ Modbus RS Vmax S (GT) = Vmax (227VMZ) Vmin (227VMZ) = CAV constant air volume Vmax = Vmin = Setpoint BU BN BK GY M WH WH A B 24 V AC/DC Modbus RS485

8 8 OPTIVENT ULTRA FORCED CONTROLS Note that control signals are ignored if Modbus control is activated (see register no 23). The controller can be force controlled to following positions via closing contacts (see fig. 3): (Close) Y= connected to ground conductor of 24 VAC supply (only with mode 2- VDC) (Vmin) Y= disconnected (Vbtw) Y= neg. rectified half wave from 24VAC supply (Vmax) Y= full wave from 24VAC supply (Open) Y= pos. rectified half wave from 24VAC supply ~ Y/ U Z 227VM BU BN BK GY N47 Fig. 3. Forced control alternatives Vmin Vbtw Vmax Open CLOSE Y U A B AC 24 V DC 24 V + ~ DC...V DC 2...V DC...V DC 2...V SETTING THE CONTROLLER TO A CONSTANT AIR FLOW The controller can be set to a constant air flow neglecting all analog inputs Y. This functionality can be used as an advanced diagnostic function. To activate this function Vmax needs to be set to. The Diag dot in the display appears and the controller uses Vmin as the constant air flow to control to. Use Vmin function to set desired constant air flow. SETTING THE CONTROLLER TO A CONSTANT AIR FLOW The display (3) uses 7-segment numbers in full 3-digits. Additional signs include a small circle, three square dots and two rectangular slashes. The square dots are used with the externally printed text to visualize certain functions or units (m 3/h, l/s). It is meant to denote the unit of the value shown in the display. In the shown case it could be m 3 /h, l/s or activated Diag (diagnostic function). The rectangular slashes are used to define the thousand separators. See following examples: l/s l/s l/s l/s 25 l/s

9 OPTIVENT ULTRA 9 STATUS MESSAGES The actuator and the sensor self-monitor the status. In normal operation the sensor indicates air speed by green LEDs. All malfunctions are indicated with red LEDs and error message on the actuators display. LED number 5 is the LED closest the actuator. During the issue it is possible to drive manually the actuator to fully closed or fully open. In case of issue, contact Fläkt Woods technical support and inform the error message to get further assistant. Note that not all status messages are presented in the table below Note: The unit have a calendar based self testing procedure. During this procedure the blade of the damper will be closed for about 3 seconds. The procedure can be turned off by setting value of register 54 to. However, Fläkt Woods recommends that the procedure is kept activated at all times. With ULDA only messages on actuator s display is visible. Status message LED indication (sensor) Message on actuator display Action if message appears Cable between the sensor and the actuator not connected - ce Fatal error Red LED 4 lights continuously Er or Err Check that cable is connected and there are no visible damages. Contact Fläkt Woods technical support. Err: the actuator needs to be changed Er: the damper needs to be changed Low air speed ( less than.5 m/s) Green LED blinks - - Air speed.5 m/s 3 m/s Green LED lights continuously - - Air speed 3 m/s 6 m/s Green LED and 2 lights continuously - - Air speed 6 m/s 9 m/s Green LED, 2 and 3 lights continuously - - Air speed 9 m/s 2 m/s Green LED, 2, 3, and 4 lights continuously - - Air speed 2 m/s 5 m/s Green LED, 2, 3, 4 and 5 lights continuously - - High air speed (more than 5 m/s) All Green LED blinks - - Damper controlling - Dot indicating unit of the flow flashes Setpoint is not reached - Display starts flashing If the blade is not fully open, damper is stucked. Contact technical support If the blade is fully open, air flow is not sufficient The actuator is finding mechanical limits - Adp or Ref Initialization process on-going - Cal Normal operation after powering up. Will go automatically away after about minute Normal operation after powering up. Will go automatically away after about minute

10 OPTIVENT ULTRA TECHNICAL DATA Power supply Over voltage Power consumption Input signal 24 VAC/VDC ± 2%, 5/6 Hz Up to 4 VDC, max. 5 sec. 4 VA/5Nm Proportional to [V min...v max ] - / 2 - VDC, or - 2 / 4-2 ma with 5 Ω resistor and override controls With the pointer at Vnom, a delay can be set: Some master devices require a delay when switching from transmission mode to reception mode. This response delay is added to 3.5 characters at the end of the message. The delay time is adjustable in steps of 3 ms, the maximum being 765 ms. With the pointer at Mode, the actual position 255 ( %) is shown. The pointer at Test = on, start adaption. Vmax, Vbtw, Vmin are not in use. With the pointer at Flow, the main menu is displayed again. Input impedance Feedback signal Permissible ambient - working temperature - storage temperature - humidity >5 kω - / 2 - VDC proportional to air volume flow 5 C to 5 C -2 C to 8 C 5-95% RH, non-condensing MODBUS SETTINGS The address can be selected from the range 247. With the function selector in the adr position, select the desired address using the value selector. Hardware settings can be changed by setting the function selector to adr and then turning the value selector until the parameter 2in is displayed. This opens up a sub- menu, which is indicated by a small circle on the display. Navigating the Modbus sub-menu With the pointer at adr, hardware settings can be made as shown in the tables below. Display number EE- PROM-value Baudrate Parity Stop bits 96 none even odd Modbus frame address funktion code byte byte N*byte data CRC end 2byte (CRC_Lbyte, CRC_Hbyte 3,5 char Function codes function code name description 3h read hold. register device parameter/ actual values read (integer/float) 6h write single register device parameter single word write The data types, that are used of each register can be found in the parameter tables. CHAR is a 8 bit integer value. The CHAR value use the lbyte of a word register. BYTE is a 8 bit integer value. The BYTE value use the lbyte of a word register. WORD is a 6 bit integer value. The WORD value use the lbyte and the hbyte of a word register (except as explicitly noted otherwise). CRC: according to Modbus over serial line specification and implementation guide v.2. End: message frames are separated by a silent interval of at least 3,5 character time none even odd none even odd 9 96 none 92 none none Note: Fläkt Woods recommends the use of settings -9.

11 OPTIVENT ULTRA MODBUS REGISTRERS Operation values Number Name Address Data type Value range Read/write Description Default Shows/sets Setpoint [%] Setpoint WORD... r/w...% matches on Vmin and Vmax % = Vmin % = Vmax The register is read only, if register 22 = or 3 Sets Override - 2 Override control WORD...4 r/w No override open 2 close 3 Vmin 4 Vmax 5 Vbetween Shows Device ID 4 Device ID 3 WORD...7 r 5 Relative position 4 WORD... r standard actuator 2 VAV 3 fire damper 4 GUAC VAV 5 GUAC CM 6 GT 7 PICB Shows Relative position [%] Absolute position 5 WORD r Shows Absolute position [ ] - 7 Relative flow 6 WORD... r Shows flow [%] - 8 Absolute flow 7 WORD r Shows flow [l/s, m^3/h] - 9 Sensor value 8 WORD... r Analog output Word... r/w Shows value of input signal [mv]... Sets analog output [mv]... see register Temperature 2 Signed word r [ C] -5,

12 2 OPTIVENT ULTRA Service values The values are used only when commissioning the damper or monitoring status. Do not write values constantly to the Service registers Number Name Address Data type Value range Read/write Description Default 4 Software version 3 WORD r Shows software version - 5 Service information 4 WORD r 6 Min value relative 5 WORD... r/w 7 Max value relative 6 WORD... r/w 9 Bus fail position 8 WORD r/w Shows status of the actuator, see status register table Sets Vmin value [%]....% Sets Vmax value [%]....% Sets the actuator position when no communication on bus within 2 seconds no bus monitoring at timeout position close 2 at timeout position open - 9 Between value relative 8 WORD... r/w Sets Vbtw value [%]...% 5 2 Between value absolute 9 WORD... r/w Sets Vbetween value [l/s, m^3/h] Size depended 2 Min value absolute 2 WORD... r/w Sets Min value [l/s, m^3/h] 22 Max value absolute 2 WORD... r/w Sets Max [l/s, m^3/h] Size depended Sets referencing signal and analog output mode Value of the register Setpoint mode Value of Output signal U 23 Setpoint signal mode and mode of analog output 22 WORD...3 r/w Setpoint from analog input Y Setpoint is written to register Actual flow (2)...V Actual flow (2)...V 2 Setpoint is written to register Value written to register 3 Setpoint from analog input Y Value written to register 3 Modbus address 3 WORD -247 r/w Sets device address 32 Sensor status 3 WORD r Shows status of the sensor, see sensor status register table - 33 Installation parameter 32 WORD 5-5 r/w Sets inst. parameter 22 Flow unit 2 WORD.. r/w = l/s, = m^3/h 542 Self testing 54 WORD.. r/w =self monitoring on, = self monitoring off

13 OPTIVENT ULTRA Modbus communication parameter 568 BYTE...8 r/w Sets Modbus communication settings, see Modbus settings table. Note that stored value starts from Mode register 769 WORD r Shows override status, see Mode register-table - Status register (4) The status register makes possible to monitor a health of the actuator. bit Description If bit is = Everything ok = Memory corrupted = Everything ok = Memory corrupted = Everything ok = Password shielded memory open = Everything ok = Password shielded memory open = Everything ok = Fatal error = Everything ok = The actuator has detected a mechanical block or is at end position. = Normal operation = Seepage flow detected = Normal operation = Issue with motor = The actuator is at normal operation range = The actuator has reached the end position. The actuator needs to be changed The actuator needs to be changed Contact Fläkt Woods technical support. Do not restart or power off the actuator. Contact Fläkt Woods technical support. Do not restart or power off the actuator. The actuator needs to be changed Check that bit 2 is not. If bits 5 and 2 are, the actuator has reached an end position. Check that nothing is preventing the actuator to move. Use the test functions to check if the actuator can move to opposite direction. The actuator drives to closed position. Check that there is an air flow in the duct. Contact Fläkt Woods technical support If override Open or Closed is not selected, check that the air flow to the actuator is sufficient Sensor status (3) The status register makes possible to monitor status of the sensor. bit Description If bit is Operation status Normal operation Communication status Communication between the actuator and sensor not working normally 2 Low air speed Air speed less than.5 m/s 3 High air speed Air speed more than 5 m/s 4 Used internally - 5 Status of factory calibration Factory calibration ok 6 Status bit Contact Fläkt Woods technical support. 7 Status bit Contact Fläkt Woods technical support. 8 Status bit Contact Fläkt Woods technical support. 9 Status bit Contact Fläkt Woods technical support.

14 4 OPTIVENT ULTRA Mode register (769) The status register makes possible to check settings of the actuator and monitor active overrides. bit Description If bit is = -V mode selected = 2-V mode selected = Setpoint from analog input Y = Setpoint is written to register To change see Setting up the mode in Quick reference Section To change see register 22 2 = Override CLOSED active - 3 = Override OPEN active - 4 = Override VBetween active - 5 = Override VMax active = Normal control direction = Opposite control direction = Normal operation = Motor off Contact Fläkt Woods technical support. Contact Fläkt Woods technical support. 8 = Override VMin active - 9 = Negative rectified half-wave connected to Y Forced control Vbetween active = positive rectified half-wave connected to Y Forced control Open active = Full-wave connected to Y Forced control Vmax active 2 = Y disconnected or Y signal is (2) V The actuator keeps Vmin flow 3 = Y signal is V The actuator keeps Vmax flow 4 = Y signal connected to ground in 2-V mode The actuator goes to closed position

15 OPTIVENT ULTRA 5

16 FG_DC_56GB_ULSA_ULDA_CO_289_R Copyright 28 FläktGroup ULSA, ULDA 56 FläktGroup is the European market leader for smart and energy efficient Indoor Air and Critical Air solutions to support every application area. We offer our customers innovative technologies, high quality and outstanding performance supported by more than a century of accumulated industry experience. The widest product range in the market, and strong market presence in 65 countries worldwide, guarantee that we are always by your side, ready to deliver Excellence in Solutions. PRODUCT FUNCTIONS BY FLÄKTGROUP Air Treatment Air Movement Air Diffusion Air Distribution Air Filtration Air Management & ATD s Air Conditioning & Heating Controls Service» Learn more on or contact one of our offices

Specification GRUNER YSP 227C

Specification GRUNER YSP 227C Specification 227CM & CMX Written by: Dillinger Kevin Issue 1 Date: 26.03.2013 14:11:00 Side 1 of 35 TOC Seite 1. Additional information... 3 1.1. Preamble... 3 1.2. Version... 3 2. General Description...

More information

REACTa. Installation Commissioning Maintenance Installation circular version Legend to figures 3-5: Min. 500 mm. Min.

REACTa. Installation Commissioning Maintenance Installation circular version Legend to figures 3-5: Min. 500 mm. Min. a Installation Commissioning Maintenance 20180125 Installation ir flow measuring of requires a straight section of duct before the unit (in air flow direction), according to installation figures. Modbus

More information

Modbus communication module for TCX2: AEX-MOD

Modbus communication module for TCX2: AEX-MOD Modbus communication module for TCX2: Communication Specification TCX2 is factory installed in TCX2 series controllers with -MOD suffix, and is also available separately upon request for customer installation

More information

VAV-Compact. Contents. Modbus General Notes 2 Modbus Register Overview 3 Modbus Register Description 4

VAV-Compact. Contents. Modbus General Notes 2 Modbus Register Overview 3 Modbus Register Description 4 Modbus-Register Description VAV-Compact VAV-Compact Contents Modbus General Notes 2 Modbus Register Overview 3 Modbus Register Description 4 www.belimo.com Modbus-Register VAV-Compact en v.0 05.208 Subject

More information

Functional data Factory settings Variable Settings

Functional data Factory settings Variable Settings echnical data sheet Rotary actuator RF-MF(-O) Multifunctional rotary actuator with emergency control for and 3 way control ball valve orque Nm Nominal voltage AC/DC V Control: Modulating DC... V or variable

More information

Multi-channel DC power digital isolation transducer manual CE-AD81-34MN3-0.5

Multi-channel DC power digital isolation transducer manual CE-AD81-34MN3-0.5 Multi-channel DC power digital isolation transducer manual CE-AD81-34MN3-0.5 1 Overview The main function of this product is to centralized measurement convert multi-channel standard DC transmission signal

More information

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency echnical data sheet LR24A-KNX Communicative rotary actuator for ball valves Nominal torque 5 Nm Nominal voltage AC/DC 24 V Control modulating Conversion of sensor signals Communication via KNX (S-Mode)

More information

[ ] kvs theor.: Theoretical kvs value for pressure drop calculation. Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

[ ] kvs theor.: Theoretical kvs value for pressure drop calculation. Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency echnical data sheet EP..R+MOD Communicative characterised control valve with sensor-operated flow control, 2-way, internal thread (EPIV) Nominal voltage AC/DC 24 V Control communicative For closed cold

More information

Brief description. Type overview

Brief description. Type overview echnical data sheet VAV-Compact KNX A pressure sensor, digital VAV controller and damper actuator all in one, providing a VAV-Compact solution with a communications capability for pressureindependent VAV

More information

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency echnical data sheet GR24A--R Communicative Retrofit rotary actuator for rotary valves and butterfly valves Nominal torque 40 Nm Nominal voltage AC/DC 24 V Control Modulating DC (0)2...10 V Variable Position

More information

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency echnical data sheet LR24A-KNX Communicative rotary actuator for ball valves Nominal torque 5 Nm Nominal voltage AC/DC 24 V Conversion of sensor signals echnical data Electrical data Nominal voltage AC/DC

More information

Overview of types. Technical data

Overview of types. Technical data echnical data sheet SHA-.. Multifunctional linear actuators for adjusting air dampers and slide valves in ventilation and air-conditioning systems for building services installations For air control dampers

More information

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency echnical data sheet GM24A--P Communicative damper actuator for adjusting dampers in technical building installations Air damper size up to approx. 8 m² Nominal torque 4 Nm Nominal voltage AC/DC 24 V Control

More information

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency echnical data sheet Communicative damper actuator for adjusting dampers in technical building installations Air damper size up to approx. m² Nominal torque 5 Nm Nominal voltage AC/DC 24 V Control Modulating

More information

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency echnical data sheet LH24A-00 Communicative linear actuator adjusting dampers and slide valves in technical building installations Air damper size up to approx. m² Actuating force 50 N Nominal voltage AC/DC

More information

WIRELESS MODBUS GATEWAY WGW410

WIRELESS MODBUS GATEWAY WGW410 WIRELESS MODBUS GATEWAY WGW410 The Tekon Wireless Modbus Gateway WGW410 is specifically designed to meet the most rigorous requirements of operation in the industrial process environments. Due to their

More information

Manual triggering of the adaption by pressing the «Adaption» button or with the PC-Tool

Manual triggering of the adaption by pressing the «Adaption» button or with the PC-Tool echnical data sheet SMA--P Multifunctional damper actuator for adjusting air dampers in ventilation and air-conditioning systems for building services installations For air dampers up to approx. m orque

More information

Servomotor for butterfly valves VF, VFH. delta-elektrogas.com EE157-01/16

Servomotor for butterfly valves VF, VFH. delta-elektrogas.com EE157-01/16 MZ Servomotor for butterfly valves VF, VFH delta-elektrogas.com EE157-01/16 MZ Servomotor Contents Description.... 2 Features........ 2 Functioning and application..... 3 Technical specifications......

More information

ma/bcd Converter Model MFC-201 ma/bcd The MFC-201 ma/bcd Converter is a device designed to convert a DC current signal into BCD (8421) signals.

ma/bcd Converter Model MFC-201 ma/bcd The MFC-201 ma/bcd Converter is a device designed to convert a DC current signal into BCD (8421) signals. 1 Definition ma/bcd Converter Model MFC-201 ma/bcd The MFC-201 ma/bcd Converter is a device designed to convert a DC current signal into BCD (8421) signals. 2 Operating Principle An electronic circuit

More information

21 VA (l max 20 5 ms) Connection Cable 1 m, 4 x 0.75 mm 2 Functional data Factory settings Variable Setting Torque Inhibiting torque

21 VA (l max 20 5 ms) Connection Cable 1 m, 4 x 0.75 mm 2 Functional data Factory settings Variable Setting Torque Inhibiting torque echnical data sheet GK4A- Communicative SuperCap rotary actuator with emergency setting function and extended functionalities for adjusting air dampers in ventilation and air-conditioning systems for building

More information

11 VA Connection Cable 1 m, 4 x 0.75 mm 2 Functional data Factory settings Variable Setting Torque (nominal torque) Motor Spring return

11 VA Connection Cable 1 m, 4 x 0.75 mm 2 Functional data Factory settings Variable Setting Torque (nominal torque) Motor Spring return echnical data sheet SF24A- Communicative spring return actuator with emergency function for adjusting air dampers in ventilation and air conditioning systems in buildings For air dampers up to approx.

More information

VFSC9 ELECTRONIC SPEED CONTROLLER. Mounting and operating instructions

VFSC9 ELECTRONIC SPEED CONTROLLER. Mounting and operating instructions ELECTRONIC SPEED CONTROLLER Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 5 WIRING

More information

current transformers or VAC secondary voltage from our SIGNAL CONVERTERS Selection Chart

current transformers or VAC secondary voltage from our SIGNAL CONVERTERS Selection Chart NK Technologies ADC series signal converters use sensor outputs (4 0 ma, 0 5 and 0 10 VDC) and convert these to digital RS485 outputs. The CTC series accept either 5 A secondary current from Analog to

More information

ELECTRONIC THERMOSTAT: T920

ELECTRONIC THERMOSTAT: T920 μnistδt ELECTRONIC THERMOSTAT: T One analog output DESCRIPTION The T series thermostats are microcomputer-based, proportional and integral (PI) devices with one analog 0 to 0 output. They can be used with

More information

269 Troubleshooting Guide 11/4/98 1

269 Troubleshooting Guide 11/4/98 1 269 Troubleshooting Guide 11/4/98 1 Table of Contents Phase currents 3 Communications. 6 RTDs.. 9 Ground Fault Currents... 13 Output Relays. 15 Analog Output 17 Switch Inputs...18 11/4/98 2 Phase Currents

More information

Data Acquisition Modules/ Distributed IO Modules

Data Acquisition Modules/ Distributed IO Modules User Manual Data Acquisition Modules/ Distributed IO Modules Future Design Controls, Inc. 7524 West 98 th Place / P.O. Box 1196 Bridgeview, IL 60455 888.751.5444 - Office: 888.307.8014 - Fax 866.342.5332

More information

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency echnical data sheet NM24A- Communicative damper actuator for adjusting dampers in technical building installations Air damper size up to approx. 2 m² Nominal torque Nm Nominal voltage AC/DC 24 V Control

More information

GUIDE SPECIFICATIONS CONTROLS SPECIFICATIONS AND CONTROL POINT DATA MAP GENERAL DESCRIPTION

GUIDE SPECIFICATIONS CONTROLS SPECIFICATIONS AND CONTROL POINT DATA MAP GENERAL DESCRIPTION GUIDE SPECIFICATIONS 256920-UGS-A-0506 Simplicity Intelli-Comfort Optional Control in 3-25 Ton Packaged Units GENERAL DESCRIPTION CONTROLS SPECIFICATIONS AND CONTROL POINT DATA MAP Equipment with Simplicity

More information

ioselect Z-NET Z-4RTD 4 Channel RTD Input Module

ioselect Z-NET Z-4RTD 4 Channel RTD Input Module 4 Channel nput Module : PT00, PT000, PT500 & N00: 2, 3 & 4 wire 500 V solation, 6-way Modbus Communications Adjustable Sampling Time Accuracy to 0.2 C Configuration and Setup Software EC 63 Flexible Power

More information

ERV-M ELECTRONIC FAN SPEED CONTROLLER. Mounting and operating instructions

ERV-M ELECTRONIC FAN SPEED CONTROLLER. Mounting and operating instructions ELECTRONIC FAN SPEED CONTROLLER Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 5

More information

Series Valve Temperature Controller. Instruction Sheet

Series Valve Temperature Controller. Instruction Sheet 2013/10/03 Series Valve Temperature Controller Instruction Sheet Thank you very much for choosing Delta DTV series valve temperature controller. Please read this instruction sheet before using your DTV

More information

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency echnical data sheet SVK24A--PC Communicative globe valve actuator with emergency control function for 2-way and 3-way globe valves Actuating force 1500 N Nominal voltage AC/DC 24 V Control modulating,

More information

Ultrasonic Multiplexer OPMUX v12.0

Ultrasonic Multiplexer OPMUX v12.0 Przedsiębiorstwo Badawczo-Produkcyjne OPTEL Sp. z o.o. ul. Morelowskiego 30 PL-52-429 Wrocław tel.: +48 (071) 329 68 54 fax.: +48 (071) 329 68 52 e-mail: optel@optel.pl www.optel.eu Ultrasonic Multiplexer

More information

MICRO-CONTROLLER X (48 48 mm)

MICRO-CONTROLLER X (48 48 mm) PX series digital temperature controller MICRO-CONTROLLER X ( mm) DATA SHEET PXG PXG is a compact size temperature controller of front panel size mm. To cope with any of versatile uses as a temperature

More information

Air Water Actuators xm(c)24a-mod xr24a-mod xv(k)24a-mod xf24a-mod xrf24a-mod

Air Water Actuators xm(c)24a-mod xr24a-mod xv(k)24a-mod xf24a-mod xrf24a-mod Modbus-Register Description Air Water Air Water Actuators xm(c)24a-mod xr24a-mod xv(k)24a-mod xf24a-mod xrf24a-mod Contents Modbus General Notes 2 Modbus Register Overview 3 Modbus Register Description

More information

NX Series Inverters. HVAC Pocket Programming Guide

NX Series Inverters. HVAC Pocket Programming Guide NX Series Inverters HVAC Pocket Programming Guide HVAC Pocket Programming Guide HVAC Pocket Programming Guide / Contents This guide provides a single reference document for the user of NXL HVAC (product

More information

MV110-8AS. Analog input module 8 channel. User guide

MV110-8AS. Analog input module 8 channel. User guide MV110-8AS Analog input module 8 channel User guide MV110-8AS_2016.12_0226_EN All rights reserved Subject to technical changes and misprints Contents 1 Description... 2 1.1 Function... 2 1.2 RS485 network...

More information

BAS Integration Manual

BAS Integration Manual Snow Melting Control 680 Introduction BAS Integration Manual Snow Melting 680_B 10/15 Replaces: 04/15 The Snow Melting Control 680 can communicate with a Building Automation System (BAS) using either BACnet

More information

Excellent low-cost Process & Temperature Controllers

Excellent low-cost Process & Temperature Controllers C22 C62 C82 C83 Excellent low-cost Process & Temperature Controllers C72 C42 R22 01. High Quality LCD Display 02. High Accuracy 18 Bit A-D Input and 15 Bit D-A Output 03. The Fast Sampling Rate in 200

More information

BusWorks 900EN Series Modbus TCP/IP 10/100M Industrial Ethernet I/O Modules

BusWorks 900EN Series Modbus TCP/IP 10/100M Industrial Ethernet I/O Modules BusWorks 900EN Series Modbus TCP/IP 10/100M Industrial Ethernet I/O Modules Six Differential Current Inputs Six Differential Voltage Inputs USER S MANUAL ACROMAG INCORPORATED Tel: (248) 295-0880 30765

More information

IO-DIM4 4-Channel, Digital to Analogue Converters

IO-DIM4 4-Channel, Digital to Analogue Converters Page 1 of 5 IO-DIM4 4-Channel, Digital to Analogue Converters Features: Benefits: Input status indication Calibrated output DIN Rail mounting Expands controller input capacity Fault finding LED indication

More information

SRC-110 Series Zone Controllers with Modbus RTU

SRC-110 Series Zone Controllers with Modbus RTU Product sheet CT2.142 Type SRC-110-MOD SRC-110 Series Zone Controllers with Modbus RTU The SRC-110 series controllers have been designed for zone heating and cooling control. The controllers have 3 analogue

More information

HD 48V01T... HD 4977T...

HD 48V01T... HD 4977T... RH-26 HD 4807T HD 4907T HD 48V07T HD 4901T... HD 4801T... HD 4917T... HD 48V01T... HD 4977T... HD 4817T... HD 48V17T... HD 4877T... HD 48V77T... HD 4807T, HD 48V07T, HD 48S07T, HD 4801T..., HD 48V01T...,

More information

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency echnical data sheet LM24A-KNX Communicative damper actuator for adjusting dampers in technical building installations Nominal torque 5 Nm Nominal voltage AC/DC 24 V Conversion of sensor signals echnical

More information

RSMFX-2R MULTIFUNCTIONAL

RSMFX-2R MULTIFUNCTIONAL Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAMS 5 WIRING AND

More information

isma-b-w0202 Modbus User Manual GC5 Sp. z o.o. Poland, Warsaw

isma-b-w0202 Modbus User Manual GC5 Sp. z o.o. Poland, Warsaw isma-b-w0202 isma-b-w0202 Modbus User Manual GC5 Sp. z o.o. Poland, Warsaw www.gc5.com 1. Introduction... 4 2. Safety rules... 4 3. Technical specifications... 5 4. Dimension... 6 5. LED Indication...

More information

MULTIFUNCTION GRAPHICAL UNIT MGU 800

MULTIFUNCTION GRAPHICAL UNIT MGU 800 MULTIFUNCTION GRAPHICAL UNIT MGU 800 For display, recording and evaluation of process instruments signals (level, temperature, pressure, etc.) 3.5" TFT display, multi-language menu Variety of possible

More information

CONTROL Room. Room product for Swegon s WISE system for demand-controlled ventilation. Quick facts Room control against temperature, CO 2

CONTROL Room. Room product for Swegon s WISE system for demand-controlled ventilation. Quick facts Room control against temperature, CO 2 Room product for Swegon s WISE system for demand-controlled ventilation Quick facts Room control against temperature, CO 2, content, etc. Static pressure and flow measurement Position-independent Shut-off-capable

More information

Installation of VAV-Compact Retrofit with ZDMS-..

Installation of VAV-Compact Retrofit with ZDMS-.. Installation of VAV-Compact Retrofit with ZDMS-.. LMVAX-D3-MP NMVAX-D3-MP ZDMS-.. VAV-Compact Retrofit for utilisation of existing VAV devices made by various manufacturers. for various air velocities

More information

PROCESS & TEMPERATURE CONTROLLERS

PROCESS & TEMPERATURE CONTROLLERS PROCESS & TEMPERATURE CONTROLLERS NOVA PD54 Series Thermocouple, RTD, & Process Inputs High Accuracy Auto-Tuning PID Heating & Cooling Models Universal Power Supply 1-24 VAC Up to 3 Relays & 2 Analog Outputs

More information

INTRODUCTION. T hank you for your HB8215/HB8216 loadcell indicator purchase. The HB8215 and HB8216 are the best choice for industrial weighing

INTRODUCTION. T hank you for your HB8215/HB8216 loadcell indicator purchase. The HB8215 and HB8216 are the best choice for industrial weighing INTRODUCTION T hank you for your HB8215/HB8216 loadcell indicator purchase. The HB8215 and HB8216 are the best choice for industrial weighing application requiring quality, performance and economy. Please

More information

EY-EM 527: Remote I/O module, ecolink527

EY-EM 527: Remote I/O module, ecolink527 Product data sheet 94.078 EY-EM 527: Remote I/O module, ecolink527 How energy efficiency is improved Regulation, control, monitoring and optimisation of operational systems, e.g. room automation or HVAC

More information

TLE ANALOG WEIGHT TRANSMITTER 4 20 ma, 0 20 ma, 0 10 V, 0 5 V, V, -5 5 V

TLE ANALOG WEIGHT TRANSMITTER 4 20 ma, 0 20 ma, 0 10 V, 0 5 V, V, -5 5 V Installation and User Manual version 1.00 TLE ANALOG WEIGHT TRANSMITTER 4 20 ma, 0 20 ma, 0 10 V, 0 5 V, -10 10 V, -5 5 V 2014/30/EU EN55022:2010 EN61000-6-2:2005 EN61000-6-4:2007 SYSTEM IDENTIFICATION

More information

RI-D440. Three Phase easywire Multifunction DIN Rail Energy Meter. Telephone : +44 (0) Displayed Parameters

RI-D440. Three Phase easywire Multifunction DIN Rail Energy Meter. Telephone : +44 (0) Displayed Parameters RI-D440 Three Phase easywire Multifunction DIN Rail Energy Meter Four module DIN rail mounted Energy pulse LED 330mV Input from easywire CTs (or -/1A and -/5A current transformer input with TAS-SCTEWA

More information

8000 SERIES PRECISION MULTIMETER VERIFICATION AND ADJUSTMENT GUIDE

8000 SERIES PRECISION MULTIMETER VERIFICATION AND ADJUSTMENT GUIDE 8000 SERIES PRECISION MULTIMETER VERIFICATION AND ADJUSTMENT GUIDE TRANSMILLE LTD. Version 1.1 : Apr 2015 TABLE OF CONTENTS PREPARING FOR CALIBRATION... 4 INTRODUCTION... 4 CALIBRATION INTERVAL SELECTION...

More information

High Performance Process & Temperature Controllers

High Performance Process & Temperature Controllers C22 C62 C82 C83 High Performance Process & Temperature Controllers C72 C42 R22 01. Multi Color LCD Display 02. High Accuracy 18 Bit A-D Input and 15 Bit D-A Output 03. 200 msec Sampling Rate 04. True Universal

More information

Electro Controls. Input-Output Modules WattsIndustries.co.uk

Electro Controls. Input-Output Modules WattsIndustries.co.uk Electro Controls Input-Output Modules - 2017 WattsIndustries.co.uk Input-Output Modules Section 08 B.M.S INPUT - OUTPUT MODULES SINGLE AND ADJUSTABLE RELAY ESRM.. Volt free contacts DIN RAIL mounted relay

More information

HC-220 PID Controller

HC-220 PID Controller HC-220 PID Controller Operation and Maintenance Manual The information contained in this manual was current at the time of printing. The most current versions of all Hydro Instruments manuals can be found

More information

Single Channel Loop Detector

Single Channel Loop Detector Single Channel Loop Detector Model LD120T Series The LD120T is a series of single channel inductive loop detectors. The use of microprocessor and surface mount technology enables a large number of functions

More information

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency echnical data sheet SHK24A-MF Parameterisable linear SuperCap actuator with emergency control function and extended functionalities for adjusting dampers and slide valves in technical building installations

More information

Earth Leakage Monitoring System IsoBase IsoHub IsoOut

Earth Leakage Monitoring System IsoBase IsoHub IsoOut 2014 11 21 Earth Leakage Monitoring System IsoBase IsoHub IsoOut User Manual Due to our policy of continual improvement, specifications may change without prior notice Page 2 (34) Contents Earth Leakage

More information

STANDARD WIRING DIAGRAMS FOR SMART MODEL 20

STANDARD WIRING DIAGRAMS FOR SMART MODEL 20 CODING SYSTEM FOR AV ACTUATOR WIRING DIAGRAMS There are 3 elements to the wiring codes used in AVA electric actuators: WIRING CODE 1 3 Wire system, single pole double throw, switching the live SPDT 2 3

More information

April 1994 UCM-420A. Setpoint Controller. Operating and Installation Instructions

April 1994 UCM-420A. Setpoint Controller. Operating and Installation Instructions April TM UCM-A Setpoint Controller Operating and Installation Instructions A LARGE number of applications in a SMALL package... REMOTE SETPOINT CONTROLLER LOCAL SETPOINT CONTROLLER - ma SIGNAL GENERATOR

More information

Position Indicator model MFC-300/IP. Technical Manual. Licht

Position Indicator model MFC-300/IP. Technical Manual. Licht Position Indicator model MFC-300/IP Technical Manual Licht Contents 1 Introduction 2 2 Front panel indication 3 3 Error indication 4 4 Manual commands 5 5 Configuration 6 5.1 Parameter reset 6 6 Programmable

More information

745 Transformer Protection System Communications Guide

745 Transformer Protection System Communications Guide Digital Energy Multilin 745 Transformer Protection System Communications Guide 745 revision: 5.20 GE publication code: GEK-106636E GE Multilin part number: 1601-0162-A6 Copyright 2010 GE Multilin GE Multilin

More information

maxon document number:

maxon document number: maxon document number: 791272-04 1 Table of contents... 2 2 Table of figures... 3 3 Introduction... 4 4 How to use this guide... 4 5 Safety Instructions... 5 6 Performance Data... 6 6.1 Motor data... 6

More information

Room Controller Thermostat

Room Controller Thermostat ºF / º VAV Thermostat with BAnet ommunication Port Technical Data Inputs Room ontroller Thermostat TROB24T4XYZ1 3 Analog input universal (0-10 Vdc or thermistor or digital input dry contact) 2 Analog outputs

More information

Temperature Controller model MFC-301/T-Dry. Version for Dry Transformers and Motors. Technical Manual. Licht

Temperature Controller model MFC-301/T-Dry. Version for Dry Transformers and Motors. Technical Manual. Licht Temperature Controller model MFC-301/T-Dry Version for Dry Transformers and Motors Technical Manual Licht Contents 1 Introduction 2 2 Operating principle 3 2.1 General principle 3 2.2 RTD operation 3 3

More information

DC Current Transducers

DC Current Transducers Current Transducers are designed to provide an analog current reading for monitoring, data logging and panel meter applications. NK Technologies current transducers offer a choice of 5 VDC, 1 VDC or ma

More information

MicroManager. Torque Mode CTCW/Loadcell Control. Instruction Manual MM3000-CTCW

MicroManager. Torque Mode CTCW/Loadcell Control. Instruction Manual MM3000-CTCW MicroManager Torque Mode CTCW/Loadcell Control Instruction Manual MM3000-CTCW Table of Contents 1. General Description... 5 2. Specifications... 5 2.1 Electrical... 5 2.2 Physical... 6 3. Installation...

More information

Senseair S8 Commercial

Senseair S8 Commercial Product Specification Senseair S8 Commercial Miniature infrared CO 2 sensor module 1 (8) Item Senseair S8 Commercial Article No. 004-0-0010, 004-0-0075 Target gas CO 2 Operating Principle Non-dispersive

More information

Wireless Analog Output Modules

Wireless Analog Output Modules Overview and Product Identification Wireless Analog s Analog s receive data from a BAPI 418 MHz receiver or 900 MHz receiver through a four-wire RS 485 bus. Up to 127 different Analog s can be connected

More information

DC1010/DC1020/DC1030/DC1040/Compact type DIGITAL CONTROLLERS Specification

DC1010/DC1020/DC1030/DC1040/Compact type DIGITAL CONTROLLERS Specification 01 May 20 30-10-10--EN Page 1 of DC1010/DC1020/DC1030/DC1040/Compact type DIGITAL CONTROLLERS Specification Overview The DC1000 Series are microprocessorbased controllers designed with a high degree of

More information

Energy Meters for DIN Rail Mounting Electric energy meter WS0101, WS0102,WS1102 WS0301, WS0302,WS1302

Energy Meters for DIN Rail Mounting Electric energy meter WS0101, WS0102,WS1102 WS0301, WS0302,WS1302 Energy Meters for DIN Rail Mounting Electric energy meter WS0101, WS0102,WS1102 WS0301, WS0302,WS1302 Direct connection up to 65 A (WSx10x) Connection with current transformer (WSx30x) Industrial or meters

More information

Programming restrictions when operating SM 331; AI 8 x RTD with PROFIBUS masters which only support DPV0.

Programming restrictions when operating SM 331; AI 8 x RTD with PROFIBUS masters which only support DPV0. 6.9 Analog input module SM 331; AI 8 x RTD; (6ES7331-7PF01-0AB0) Cycle time extension due to wire-break monitoring The wire-break monitoring software function of the module is available in all operating

More information

PLA 33. Power line analyzer. User and service manual. version 2.4

PLA 33. Power line analyzer. User and service manual. version 2.4 PLA 33 Power line analyzer User and service manual version 2.4 Content. Front control panel and terminal plate...3 7.2.2. System frequency setting...0 2. Device description...4 7.2.3. Password protection...0

More information

Table of Contents. Proximity Sensors. IEC Limit Switches. Encoders. Current Sensors. Section 17

Table of Contents. Proximity Sensors. IEC Limit Switches. Encoders. Current Sensors. Section 17 Proximity Section 17 Table of Contents............ 21 2 Application Guide........................ 21 3 ACT Series Transducers......... 21 4 ACTR Series Transducers........ 21 6 ACS150 Series Switches..................

More information

Technical data. Parameterisable damper actuator in the

Technical data. Parameterisable damper actuator in the echnical data sheet Parameterisable damper actuator in the IP66 protective housing for or adjusting ad usting air dampers in industrial plants and in technical building installations For air dampers up

More information

IP1 Datasheet PWM OUTPUT WITH SINGLE CHANNEL ADC MODULE FEATURES DESCRIPTION CONNECTOR DETAILS

IP1 Datasheet PWM OUTPUT WITH SINGLE CHANNEL ADC MODULE FEATURES DESCRIPTION CONNECTOR DETAILS PWM OUTPUT WITH SINGLE CHANNEL ADC MODULE FEATURES 1 PWM Output (3.3V) 0 Hz 1 khz Single Channel 3.3V 12-bit ADC input for voltage sensing Optional automated PWM adjustment based on input voltage for standalone

More information

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency echnical data sheet SM24A--P Communicative damper actuator for adjusting dampers in technical building installations Air damper size up to approx. 4 m² Nominal torque 2 Nm Nominal voltage AC/DC 24 V Control

More information

GB QUICK GUIDE FOR THE CONFIGURATION OF VARIABLE SPEED DRIVES

GB QUICK GUIDE FOR THE CONFIGURATION OF VARIABLE SPEED DRIVES GB QUICK GUIDE FOR THE CONFIGURATION OF VARIABLE SPEED DRIVES LOVATO ELECTRIC S.P.A. 24020 GORLE (BERGAMO) ITALIA VIA DON E. MAZZA, 12 TEL. 035 4282111 FAX (Nazionale): 035 4282200 FAX (International):

More information

BU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on supply lines for medical locations ISOLTESTER-DIG-RZ/RS/PLUS

BU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on supply lines for medical locations ISOLTESTER-DIG-RZ/RS/PLUS INSTRUCTION MANUAL BU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on supply lines for medical locations ISOLTESTER-DIG-RZ/RS/PLUS 1/23 More information than that reported

More information

Manual triggering of the adaption by pressing the «Adaption» button or with the PC-Tool

Manual triggering of the adaption by pressing the «Adaption» button or with the PC-Tool echnical data sheet LMA-MF-P Multifunctional damper actuator for operating air control dampers in ventilation and air-conditioning systems for building services installations For air dampers up to approx.

More information

Digital Panel Meters DC/AC Current and Voltage Indicator/Controller Type LDM40

Digital Panel Meters DC/AC Current and Voltage Indicator/Controller Type LDM40 Digital Panel Meters Current and Voltage Indicator/Controller Type LDM40 Multi-input instrument 4-DGT LED 0.1% RDG basic accuracy TRMS AC current and voltage measurements AC/DC current measurements: selectable

More information

sw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS

sw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS INSTRUCTIONS MANUAL IM831-U v0.92 HRI-R40W sw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS INDEX: GENERAL TYPES ACESSORIES AND OPTIONS

More information

APPENDIX APPENDIX A 1

APPENDIX APPENDIX A 1 A 1 SPECIFICATIONS Ratings Supply voltage 100 to 240 VAC, 50/60 Hz 24 VAC, 50/60 Hz/24 VDC Operating voltage range 85 to 110% of rated supply voltage Power consumption 7VA 4VA/2.5W Sensor input Thermocouple

More information

Analogue temperature controllers

Analogue temperature controllers Analogue temperature controllers CT8A Input by J-K thermo-couple or by thermo-resistance Pt 00 (-wire) regulation modes : ON/OFF or proportional derivative selected by wiring Relay output Specifications

More information

Mars-Energo. Volt/mA Calibrator CALMAR-S. User s manual Edition 3.1

Mars-Energo. Volt/mA Calibrator CALMAR-S. User s manual Edition 3.1 Mars-Energo Volt/mA Calibrator CALMAR-S User s manual Edition 3.1 Manufacturer: OOO NPP Mars-Energo Address: V.O. 13 Line, 6-8, office 41H, Saint-Petersburg, Russia, 199034 2017 MARS-ENERGO Table of contents

More information

METERSUK. SmartLink D Y N A M i T E. EM415 MOD Series. User Manual KEY FEATURES INDEX 3. TECHNICAL DESCRIPTION. Single Phase Metering

METERSUK. SmartLink D Y N A M i T E. EM415 MOD Series. User Manual KEY FEATURES INDEX 3. TECHNICAL DESCRIPTION. Single Phase Metering METERSUK LTD s a l e s @ m e t e r s. c o. u k 0 1 5 2 4 5 5 5 9 2 9 Series Smart Energy Meter KEY FEATURES Single Phase Metering Single phase metering 4 din modules, Standard DIN rail Format (DIN43880)

More information

Digital electronic module 4DO DC24V/2A HF (6ES7132-4BD30-0AB0) SIMATIC

Digital electronic module 4DO DC24V/2A HF (6ES7132-4BD30-0AB0) SIMATIC Digital electronic module 4DO DC24V/2A HF (6ES7132-4BD30-0AB0) SIMATIC Properties 1 Parameters 2 Diagnostics 3 ET 200S distributed I/O Digital electronic module 4DO DC24V/2A HF (6ES7132-4BD30-0AB0) Manual

More information

AC Current Transducers

AC Current Transducers Current Transducers are designed to provide an analog signal proportional to the AC current for monitoring, data logging and panel meter applications. NK Technologies current transducers offer a choice

More information

DTAP. universal programmable controller. Универсален програмируем контролер

DTAP. universal programmable controller. Универсален програмируем контролер dtap DTAP Универсален програмируем контролер universal programmable controller The DTAPG universal programmable controller provides a temperature and/or an analog input (0-10 VDC/0-20 ma/pwm) and a user-defined

More information

micro Technical Manual

micro Technical Manual GB micro opos 4 Positioning system Progr. version M001B110 Technical Manual Servo unit micropos 4 Contents 1. Introduction... 1 1.1. General... 1 1.2. System survey... 2 1.3. Master... 3 Modbus RTU or

More information

I-7088, I-7088D, M-7088 and M-7088D User Manual

I-7088, I-7088D, M-7088 and M-7088D User Manual I-7088, I-7088D, M-7088 and M-7088D User Manual I-7000 New Features 1. Internal Self Tuner 2. Multiple Baud Rates 3. Multiple Data Formats 4. Internal Dual WatchDog 5. True Distributed Control 6. High

More information

Signet 9900 Transmitter

Signet 9900 Transmitter Signet 9900 Transmitter Member of the SmartPro Family of Instruments Features Field Mount Multi-Parameter input selection Large auto-sensing backlit display with at a glance visibility Dial-type digital

More information

BACnet- MS/TP COMMUNICATION V

BACnet- MS/TP COMMUNICATION V - MS/TP COMMUNICATION V1.00.08.17 11.1 Introduction The VFD can be controlled and monitored through the BACnet MS/TP protocol over an RS-485 connection. The VFD operates as an MS/TP master device, which

More information

Introduction. Specifications LF620,LF622. Field Intelligent Device Series Electromagnetic Flowmeter Converter

Introduction. Specifications LF620,LF622. Field Intelligent Device Series Electromagnetic Flowmeter Converter Field Intelligent Device Series Electromagnetic Flowmeter Converter LF620,LF622 Introduction Combined with a multi-functional converter LF620 (combined type) or LF622 (separate type) equipped with its

More information

SolarEdge Feed-in Limitation Application Note

SolarEdge Feed-in Limitation Application Note SolarEdge Feed-in Limitation Application Note Version 1.0 Disclaimers Disclaimers Important Notice Copyright SolarEdge Inc. All rights reserved. No part of this document may be reproduced, stored in a

More information

N1040i Indicator. UNIVERSAL INDICATOR INSTRUCTIONS MANUAL V1.0x D PRESENTATION FEATURES

N1040i Indicator. UNIVERSAL INDICATOR INSTRUCTIONS MANUAL V1.0x D PRESENTATION FEATURES UNIVERSAL INDICATOR INSTRUCTIONS MANUAL V1.0x D PRESENTATION N1040i is a quite versatile process indicator. With a wide list of input types - thermocouples, thermo-resistance, voltage and current the N1040i

More information

The DO8332 module is equipped with eight outputs for 1-wire connections. The rated output current is 2 A.

The DO8332 module is equipped with eight outputs for 1-wire connections. The rated output current is 2 A. 1.1 DO8332 1.1.1 General information The DO8332 module is equipped with eight outputs for 1-wire connections. The rated output current is 2 A. The output supply is fed directly to the module. An additional

More information