OPTIVENT ULTRA VAV damper CONTROL UNIT FOR MODBUS 227VMZ-MB
|
|
- Lora Merritt
- 5 years ago
- Views:
Transcription
1 OPTIVENT ULTRA VAV damper CONTROL UNIT FOR MODBUS 227VMZ-MB
2 2 OPTIVENT ULTRA OPTIVENT ULTRA WITH COMPACT CONTROLLER FOR MODBUS 227VMZ-MB OPTIVENT ULTRA is a complete VAV unit consisting of a Modbus actuator, ultrasound based measuring sensor for pressure-independent control and user interface with 3-digit display which enables monitoring of the air flow and setting up values without external equipment. The controller can be operated via Modbus or with analogue signal, which is set to a standard value of - V on delivery. To change operating range to 2 - V see Setting the values, quick reference guide. The controller can also be force controlled via closing contacts (timer, presence detector, etc.) to override the set min or max air flow. It is also possible to use the controller with a CAV function. Modbus is wired according to 2-wire RS-485 rules. There can be up to 28 devices on one bus (Modbus load /4.) The wiring should be done using a twisted pair cable, such as Datajamak 2x(2+)x.24. The signal grounds of all devices on the same bus should be connected together. The bus should form a daisy chain, with the cable running from one device to the next without branches (max. branch length m). The maximum bus length is 8 m. The bus should be terminated at both ends using 2 Ω resistors. Master D R CONNECTION DIAGRAM Actuators are provided with color coded and numbered wires ( m). BU 2 BN S 3 BK Y/Z 4 GY 24 VAC/DC Supply U /2- VDC Control A WH B WH D D RS 485 /2- VDC Feedback (,5 ma) WIRING Modbus = BU = Blue 2 = BN = Brown 3 = BK = Black 4 = GY = Grey A = WH = White B = WH = White Lenght: mm Strand cross section: 4 x,75 mm2 2 x,38 mm2 Observe polarity on secondary of transformers. All common and signal ( ) must be connected in line. Incorrect polarity can cause controller damage or operation error. Provide overload protection for line voltage and disconnect as required. Consider voltage drops when connecting multiply actuators in parallel. Always use a separate transformer when controller power is full-wave rectified. Controller and actuators must have separate transformers for paralleled multi-actuator application. LT D R Slave Balanced Pair Slave n D D The bus cable should be connected to wires A and B in the same way at every device on the bus. The terminating resistors at both ends of the bus should be connected between wires A and B. If necessary to eliminate interference, the shield of the twisted pair cable can be connected to protective ground. The connection should be made only at one end of the shield, for example always to the cable coming from the controller. MODBUS FACTORY SETTINGS D R Transmission mode RTU Address Transfer rate 92 bps Data bits 8 Parity Even Stop bits Delay ms Response time ms + delay
3 OPTIVENT ULTRA 3 USER INTERFACE 3 Note: Setting or not setting the intermediate position Vbtw has no effect on the operation of the actuator when - / 2- VDC control voltage is used. Vbtw is activated only when forced control signal is used. FUNCTIONS, DETAILED DESCRIPTION 2 On the cover of the actuator there are two selectors, value selector () and function selector (2). Also there is the 3-digit display (3) to show selected functions, values and units. SETTING THE VALUES, QUICKREFERENCE GUIDE. Select air flow unit: Dot on upper-right or lower-right corner of display indicates which units that are used, l/s or m3/h. If there is need of change, turn the function selector until it points to Flow. Then turn the value selector until dot on display toggles to other position. After the selection the display flashes three dashes (- - -) twice for indication that new setting is stored. 2. Setting up Vmax: Turn the function selector until it points to Vmax. Then turn the value selector until desired air flow is shown on display. After the selection the display flashes twice for indication that new Vmax setting is stored. 3. Setting up Vmin: Turn the function selector until it points to Vmin. Then turn the value selector until desired air flow is shown on display. After the selection the display flashes twice for indication that new Vmin setting is stored. 4. Select input signal range: Turn the function selector until it points to Mode. Currently valid range is shown on display, -n for -V range or 2-n for 2-V range. If there is need of change, turn the value selector until desired value is shown on display. After the selection the new range is saved and the display flashes twice for indication. 5. Setting up Modbus address: Turn the function selector until it points to Adr. Then turn the value selector to select the desired address (-247). 6. Setting up Installation parameter: Turn function selector until it points to Inst. Then turn the value selector until desired parameter is shown in display. After the selection the display flashes for indication that new value is stored. Turn the function selector to Flow after the settings is set.. Value selector The value selector allows the changing of values. The position of the arrow shows the value set. The changes are displayed as soon as the selector is moved ± from its position. 2. Function Selector The function selector allows choosing the function depending on its position. If there is no function selected the display will show three dashes(- - -). Flow Shows the actual flow in selected units, m3 /h or l/s. This display matches with the feedback signal U. The display starts flashing if the servomotor hits an end stop before matching actual to reference flow. An overflow (air speed higher than 5 m/s) is indicated in the display by a small circle, see section Display. Turning the value selector allows unit selection. The appropriate dot on display is toggled as indicator. Dot on upper-right corner of display: unit of flow used is l/s. Dot on lower-right corner of display: unit of flow used is m3/h. Vmin Allows to set the desired minimum flow for the external reference signal Y=V/2V by turning the value selector. Selected value is shown on display in m 3 /h or l/s. Vbtw Enables the setting of desired intermediate position flow for the external forced control signal (negative rectified half wave from 24VAC supply) by turning the value selector. Selected value is shown on display in m3/h or l/s.
4 4 OPTIVENT ULTRA Vmax Allows to set the desired maximum flow for the external reference signal Y=V by turning the value selector. Selected value is shown on display in m3/h or l/s. Test Opens the diagnose menu. All outside input signals on Y are neglected and the controller only operates according to the selected override function. All override functions are disabled after a time-out of hours. The display toggles after the selection of the function between the actual flow (8s showing time) and the function (2s showing time). OFF-mode toggles with Y- signal. Selecting another function will disable the Diag function and set it automatically to OFF. Turning the value selector allows Diag function selection. The appropriate symbols on display are toggled as indicator. rst Activate calibration and self-diagnostic for the sensor. Shows the actual duct size e.g. size DN25 is shown as d2. Showing the software version. After 3s showing the display shows off again. Mode Allows to set the input signal range ( V or 2 V) by turning the value selector. The feedback signal range of U corresponds to Y. op(en) opens the damper -n... signal range is -V. cl(ose) closes the damper 2-n... signal range is 2-V. Hi(gh) forces the actuator to V max Lo(w) forces the actuator to V min Adr Selecting the Modbus address. Inst. Set installation parameter for short safety distance installations. Default value is. on Test mode is switched on. The actuator stays in the current position. off Test mode is switched off. The actuator starts controlling according to external signal Y. This signal Y shall be shown in the range of x - V
5 OPTIVENT ULTRA 5 INPUT SIGNALS (ANALOG) Note that control signals are ignored if Modbus control is activated (see register no 23). The input signal Y allows to control the VAV actuator according to the selected mode of operation. In mode VDC the input signal Y matches to the following flows: Vact = Vmin + Y. (Vmax - Vmin) VDC and the flows match to Y = VDC as (Vmin) and Y = VDC as (Vmax) Vact - Vmin Y = VDC. Vmax - Vmin In mode 2 VDC the input signal Y matches to the following flows: Y-2VDC Vact = Vmin +. 8VDC (Vmax - Vmin) OUTPUT SIGNALS (ANALOG) In mode VDC the output signal U matches to the following flows: Vact U = VDC. where Vnom is size dependent nominal flow and to calculate the actual flow Vact from the feedback signal U: Vact =. U Vnom VDC In mode 2 VDC the output signal U matches to the following flows: Vact U = 2VDC + (VDC. and to calculate the actual flow Vact from the feedback signal U: Vact = Vnom Vnom. U VDC Vnom and the flows match to Y = 2VDC as (Vmin) and Y = VDC as (Vmax) Vact - Vmin Y = 2VDC + 8VDC. Vmax - Vmin Mode 2 VDC includes special feature to close damper with input signal Y = VDC. See also Fig. Reference Signal Y.. V max Air volume flow. V min V Nom. Y... V ref = (V max V min ) + V min.. Y 2... V ref = (V max V min ) + V 8 min. Vmin See also Fig 2. Actual air volume flow U. V Nom (%) Air volume flow.. V act = V Nom Mode... VDC U Mode 2... VDC. V min (Apparat) 2 Actual air volume flow U Fig. 2. Actual air volume flow U.. V act = V Nom U 2 8 Control range VDC (Device) 2 Reference signal Y Fig. Reference Signal Y VDC
6 6 OPTIVENT ULTRA WIRING A B A B 24 VAC 24 VDC ~ 24 VAC ~ 24 VDC +... V 2... V... V 2... V Operating voltage Control signal Feedback signal Modbus RS485 blue (BU) brown (BN) black (BK) grey (GY) white (WH) The following wiring solutions are possible: Parallel control M M BU BN BK GY WH WH A B BU BN BK GY WH WH A B.../2... V DC 24 V AC/DC Modbus RS485 Master-slave (same sizes) M M Vmin = Vmax = Vnom BU BN BK GY WH WH BU BN BK GY WH WH A B A B.../2... V DC 24 V AC/DC Modbus RS485
7 OPTIVENT ULTRA 7 WIRING (CONT.) EMSF control EMSF UL(S,D)A - V 2- V - V 2- V p M GT-MB 227VMZ-MB BU BN GY WH WH BU BN BK GY WH WH 2 4 A B A B 24 V AC/DC ~ Modbus RS Vmax S (GT) = Vmax (227VMZ) Vmin (227VMZ) = CAV constant air volume Vmax = Vmin = Setpoint BU BN BK GY M WH WH A B 24 V AC/DC Modbus RS485
8 8 OPTIVENT ULTRA FORCED CONTROLS Note that control signals are ignored if Modbus control is activated (see register no 23). The controller can be force controlled to following positions via closing contacts (see fig. 3): (Close) Y= connected to ground conductor of 24 VAC supply (only with mode 2- VDC) (Vmin) Y= disconnected (Vbtw) Y= neg. rectified half wave from 24VAC supply (Vmax) Y= full wave from 24VAC supply (Open) Y= pos. rectified half wave from 24VAC supply ~ Y/ U Z 227VM BU BN BK GY N47 Fig. 3. Forced control alternatives Vmin Vbtw Vmax Open CLOSE Y U A B AC 24 V DC 24 V + ~ DC...V DC 2...V DC...V DC 2...V SETTING THE CONTROLLER TO A CONSTANT AIR FLOW The controller can be set to a constant air flow neglecting all analog inputs Y. This functionality can be used as an advanced diagnostic function. To activate this function Vmax needs to be set to. The Diag dot in the display appears and the controller uses Vmin as the constant air flow to control to. Use Vmin function to set desired constant air flow. SETTING THE CONTROLLER TO A CONSTANT AIR FLOW The display (3) uses 7-segment numbers in full 3-digits. Additional signs include a small circle, three square dots and two rectangular slashes. The square dots are used with the externally printed text to visualize certain functions or units (m 3/h, l/s). It is meant to denote the unit of the value shown in the display. In the shown case it could be m 3 /h, l/s or activated Diag (diagnostic function). The rectangular slashes are used to define the thousand separators. See following examples: l/s l/s l/s l/s 25 l/s
9 OPTIVENT ULTRA 9 STATUS MESSAGES The actuator and the sensor self-monitor the status. In normal operation the sensor indicates air speed by green LEDs. All malfunctions are indicated with red LEDs and error message on the actuators display. LED number 5 is the LED closest the actuator. During the issue it is possible to drive manually the actuator to fully closed or fully open. In case of issue, contact Fläkt Woods technical support and inform the error message to get further assistant. Note that not all status messages are presented in the table below Note: The unit have a calendar based self testing procedure. During this procedure the blade of the damper will be closed for about 3 seconds. The procedure can be turned off by setting value of register 54 to. However, Fläkt Woods recommends that the procedure is kept activated at all times. With ULDA only messages on actuator s display is visible. Status message LED indication (sensor) Message on actuator display Action if message appears Cable between the sensor and the actuator not connected - ce Fatal error Red LED 4 lights continuously Er or Err Check that cable is connected and there are no visible damages. Contact Fläkt Woods technical support. Err: the actuator needs to be changed Er: the damper needs to be changed Low air speed ( less than.5 m/s) Green LED blinks - - Air speed.5 m/s 3 m/s Green LED lights continuously - - Air speed 3 m/s 6 m/s Green LED and 2 lights continuously - - Air speed 6 m/s 9 m/s Green LED, 2 and 3 lights continuously - - Air speed 9 m/s 2 m/s Green LED, 2, 3, and 4 lights continuously - - Air speed 2 m/s 5 m/s Green LED, 2, 3, 4 and 5 lights continuously - - High air speed (more than 5 m/s) All Green LED blinks - - Damper controlling - Dot indicating unit of the flow flashes Setpoint is not reached - Display starts flashing If the blade is not fully open, damper is stucked. Contact technical support If the blade is fully open, air flow is not sufficient The actuator is finding mechanical limits - Adp or Ref Initialization process on-going - Cal Normal operation after powering up. Will go automatically away after about minute Normal operation after powering up. Will go automatically away after about minute
10 OPTIVENT ULTRA TECHNICAL DATA Power supply Over voltage Power consumption Input signal 24 VAC/VDC ± 2%, 5/6 Hz Up to 4 VDC, max. 5 sec. 4 VA/5Nm Proportional to [V min...v max ] - / 2 - VDC, or - 2 / 4-2 ma with 5 Ω resistor and override controls With the pointer at Vnom, a delay can be set: Some master devices require a delay when switching from transmission mode to reception mode. This response delay is added to 3.5 characters at the end of the message. The delay time is adjustable in steps of 3 ms, the maximum being 765 ms. With the pointer at Mode, the actual position 255 ( %) is shown. The pointer at Test = on, start adaption. Vmax, Vbtw, Vmin are not in use. With the pointer at Flow, the main menu is displayed again. Input impedance Feedback signal Permissible ambient - working temperature - storage temperature - humidity >5 kω - / 2 - VDC proportional to air volume flow 5 C to 5 C -2 C to 8 C 5-95% RH, non-condensing MODBUS SETTINGS The address can be selected from the range 247. With the function selector in the adr position, select the desired address using the value selector. Hardware settings can be changed by setting the function selector to adr and then turning the value selector until the parameter 2in is displayed. This opens up a sub- menu, which is indicated by a small circle on the display. Navigating the Modbus sub-menu With the pointer at adr, hardware settings can be made as shown in the tables below. Display number EE- PROM-value Baudrate Parity Stop bits 96 none even odd Modbus frame address funktion code byte byte N*byte data CRC end 2byte (CRC_Lbyte, CRC_Hbyte 3,5 char Function codes function code name description 3h read hold. register device parameter/ actual values read (integer/float) 6h write single register device parameter single word write The data types, that are used of each register can be found in the parameter tables. CHAR is a 8 bit integer value. The CHAR value use the lbyte of a word register. BYTE is a 8 bit integer value. The BYTE value use the lbyte of a word register. WORD is a 6 bit integer value. The WORD value use the lbyte and the hbyte of a word register (except as explicitly noted otherwise). CRC: according to Modbus over serial line specification and implementation guide v.2. End: message frames are separated by a silent interval of at least 3,5 character time none even odd none even odd 9 96 none 92 none none Note: Fläkt Woods recommends the use of settings -9.
11 OPTIVENT ULTRA MODBUS REGISTRERS Operation values Number Name Address Data type Value range Read/write Description Default Shows/sets Setpoint [%] Setpoint WORD... r/w...% matches on Vmin and Vmax % = Vmin % = Vmax The register is read only, if register 22 = or 3 Sets Override - 2 Override control WORD...4 r/w No override open 2 close 3 Vmin 4 Vmax 5 Vbetween Shows Device ID 4 Device ID 3 WORD...7 r 5 Relative position 4 WORD... r standard actuator 2 VAV 3 fire damper 4 GUAC VAV 5 GUAC CM 6 GT 7 PICB Shows Relative position [%] Absolute position 5 WORD r Shows Absolute position [ ] - 7 Relative flow 6 WORD... r Shows flow [%] - 8 Absolute flow 7 WORD r Shows flow [l/s, m^3/h] - 9 Sensor value 8 WORD... r Analog output Word... r/w Shows value of input signal [mv]... Sets analog output [mv]... see register Temperature 2 Signed word r [ C] -5,
12 2 OPTIVENT ULTRA Service values The values are used only when commissioning the damper or monitoring status. Do not write values constantly to the Service registers Number Name Address Data type Value range Read/write Description Default 4 Software version 3 WORD r Shows software version - 5 Service information 4 WORD r 6 Min value relative 5 WORD... r/w 7 Max value relative 6 WORD... r/w 9 Bus fail position 8 WORD r/w Shows status of the actuator, see status register table Sets Vmin value [%]....% Sets Vmax value [%]....% Sets the actuator position when no communication on bus within 2 seconds no bus monitoring at timeout position close 2 at timeout position open - 9 Between value relative 8 WORD... r/w Sets Vbtw value [%]...% 5 2 Between value absolute 9 WORD... r/w Sets Vbetween value [l/s, m^3/h] Size depended 2 Min value absolute 2 WORD... r/w Sets Min value [l/s, m^3/h] 22 Max value absolute 2 WORD... r/w Sets Max [l/s, m^3/h] Size depended Sets referencing signal and analog output mode Value of the register Setpoint mode Value of Output signal U 23 Setpoint signal mode and mode of analog output 22 WORD...3 r/w Setpoint from analog input Y Setpoint is written to register Actual flow (2)...V Actual flow (2)...V 2 Setpoint is written to register Value written to register 3 Setpoint from analog input Y Value written to register 3 Modbus address 3 WORD -247 r/w Sets device address 32 Sensor status 3 WORD r Shows status of the sensor, see sensor status register table - 33 Installation parameter 32 WORD 5-5 r/w Sets inst. parameter 22 Flow unit 2 WORD.. r/w = l/s, = m^3/h 542 Self testing 54 WORD.. r/w =self monitoring on, = self monitoring off
13 OPTIVENT ULTRA Modbus communication parameter 568 BYTE...8 r/w Sets Modbus communication settings, see Modbus settings table. Note that stored value starts from Mode register 769 WORD r Shows override status, see Mode register-table - Status register (4) The status register makes possible to monitor a health of the actuator. bit Description If bit is = Everything ok = Memory corrupted = Everything ok = Memory corrupted = Everything ok = Password shielded memory open = Everything ok = Password shielded memory open = Everything ok = Fatal error = Everything ok = The actuator has detected a mechanical block or is at end position. = Normal operation = Seepage flow detected = Normal operation = Issue with motor = The actuator is at normal operation range = The actuator has reached the end position. The actuator needs to be changed The actuator needs to be changed Contact Fläkt Woods technical support. Do not restart or power off the actuator. Contact Fläkt Woods technical support. Do not restart or power off the actuator. The actuator needs to be changed Check that bit 2 is not. If bits 5 and 2 are, the actuator has reached an end position. Check that nothing is preventing the actuator to move. Use the test functions to check if the actuator can move to opposite direction. The actuator drives to closed position. Check that there is an air flow in the duct. Contact Fläkt Woods technical support If override Open or Closed is not selected, check that the air flow to the actuator is sufficient Sensor status (3) The status register makes possible to monitor status of the sensor. bit Description If bit is Operation status Normal operation Communication status Communication between the actuator and sensor not working normally 2 Low air speed Air speed less than.5 m/s 3 High air speed Air speed more than 5 m/s 4 Used internally - 5 Status of factory calibration Factory calibration ok 6 Status bit Contact Fläkt Woods technical support. 7 Status bit Contact Fläkt Woods technical support. 8 Status bit Contact Fläkt Woods technical support. 9 Status bit Contact Fläkt Woods technical support.
14 4 OPTIVENT ULTRA Mode register (769) The status register makes possible to check settings of the actuator and monitor active overrides. bit Description If bit is = -V mode selected = 2-V mode selected = Setpoint from analog input Y = Setpoint is written to register To change see Setting up the mode in Quick reference Section To change see register 22 2 = Override CLOSED active - 3 = Override OPEN active - 4 = Override VBetween active - 5 = Override VMax active = Normal control direction = Opposite control direction = Normal operation = Motor off Contact Fläkt Woods technical support. Contact Fläkt Woods technical support. 8 = Override VMin active - 9 = Negative rectified half-wave connected to Y Forced control Vbetween active = positive rectified half-wave connected to Y Forced control Open active = Full-wave connected to Y Forced control Vmax active 2 = Y disconnected or Y signal is (2) V The actuator keeps Vmin flow 3 = Y signal is V The actuator keeps Vmax flow 4 = Y signal connected to ground in 2-V mode The actuator goes to closed position
15 OPTIVENT ULTRA 5
16 FG_DC_56GB_ULSA_ULDA_CO_289_R Copyright 28 FläktGroup ULSA, ULDA 56 FläktGroup is the European market leader for smart and energy efficient Indoor Air and Critical Air solutions to support every application area. We offer our customers innovative technologies, high quality and outstanding performance supported by more than a century of accumulated industry experience. The widest product range in the market, and strong market presence in 65 countries worldwide, guarantee that we are always by your side, ready to deliver Excellence in Solutions. PRODUCT FUNCTIONS BY FLÄKTGROUP Air Treatment Air Movement Air Diffusion Air Distribution Air Filtration Air Management & ATD s Air Conditioning & Heating Controls Service» Learn more on or contact one of our offices
Specification GRUNER YSP 227C
Specification 227CM & CMX Written by: Dillinger Kevin Issue 1 Date: 26.03.2013 14:11:00 Side 1 of 35 TOC Seite 1. Additional information... 3 1.1. Preamble... 3 1.2. Version... 3 2. General Description...
More informationREACTa. Installation Commissioning Maintenance Installation circular version Legend to figures 3-5: Min. 500 mm. Min.
a Installation Commissioning Maintenance 20180125 Installation ir flow measuring of requires a straight section of duct before the unit (in air flow direction), according to installation figures. Modbus
More informationModbus communication module for TCX2: AEX-MOD
Modbus communication module for TCX2: Communication Specification TCX2 is factory installed in TCX2 series controllers with -MOD suffix, and is also available separately upon request for customer installation
More informationVAV-Compact. Contents. Modbus General Notes 2 Modbus Register Overview 3 Modbus Register Description 4
Modbus-Register Description VAV-Compact VAV-Compact Contents Modbus General Notes 2 Modbus Register Overview 3 Modbus Register Description 4 www.belimo.com Modbus-Register VAV-Compact en v.0 05.208 Subject
More informationFunctional data Factory settings Variable Settings
echnical data sheet Rotary actuator RF-MF(-O) Multifunctional rotary actuator with emergency control for and 3 way control ball valve orque Nm Nominal voltage AC/DC V Control: Modulating DC... V or variable
More informationMulti-channel DC power digital isolation transducer manual CE-AD81-34MN3-0.5
Multi-channel DC power digital isolation transducer manual CE-AD81-34MN3-0.5 1 Overview The main function of this product is to centralized measurement convert multi-channel standard DC transmission signal
More informationElectrical data Nominal voltage AC/DC 24 V Nominal voltage frequency
echnical data sheet LR24A-KNX Communicative rotary actuator for ball valves Nominal torque 5 Nm Nominal voltage AC/DC 24 V Control modulating Conversion of sensor signals Communication via KNX (S-Mode)
More information[ ] kvs theor.: Theoretical kvs value for pressure drop calculation. Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency
echnical data sheet EP..R+MOD Communicative characterised control valve with sensor-operated flow control, 2-way, internal thread (EPIV) Nominal voltage AC/DC 24 V Control communicative For closed cold
More informationBrief description. Type overview
echnical data sheet VAV-Compact KNX A pressure sensor, digital VAV controller and damper actuator all in one, providing a VAV-Compact solution with a communications capability for pressureindependent VAV
More informationElectrical data Nominal voltage AC/DC 24 V Nominal voltage frequency
echnical data sheet GR24A--R Communicative Retrofit rotary actuator for rotary valves and butterfly valves Nominal torque 40 Nm Nominal voltage AC/DC 24 V Control Modulating DC (0)2...10 V Variable Position
More informationElectrical data Nominal voltage AC/DC 24 V Nominal voltage frequency
echnical data sheet LR24A-KNX Communicative rotary actuator for ball valves Nominal torque 5 Nm Nominal voltage AC/DC 24 V Conversion of sensor signals echnical data Electrical data Nominal voltage AC/DC
More informationOverview of types. Technical data
echnical data sheet SHA-.. Multifunctional linear actuators for adjusting air dampers and slide valves in ventilation and air-conditioning systems for building services installations For air control dampers
More informationElectrical data Nominal voltage AC/DC 24 V Nominal voltage frequency
echnical data sheet GM24A--P Communicative damper actuator for adjusting dampers in technical building installations Air damper size up to approx. 8 m² Nominal torque 4 Nm Nominal voltage AC/DC 24 V Control
More informationElectrical data Nominal voltage AC/DC 24 V Nominal voltage frequency
echnical data sheet Communicative damper actuator for adjusting dampers in technical building installations Air damper size up to approx. m² Nominal torque 5 Nm Nominal voltage AC/DC 24 V Control Modulating
More informationElectrical data Nominal voltage AC/DC 24 V Nominal voltage frequency
echnical data sheet LH24A-00 Communicative linear actuator adjusting dampers and slide valves in technical building installations Air damper size up to approx. m² Actuating force 50 N Nominal voltage AC/DC
More informationWIRELESS MODBUS GATEWAY WGW410
WIRELESS MODBUS GATEWAY WGW410 The Tekon Wireless Modbus Gateway WGW410 is specifically designed to meet the most rigorous requirements of operation in the industrial process environments. Due to their
More informationManual triggering of the adaption by pressing the «Adaption» button or with the PC-Tool
echnical data sheet SMA--P Multifunctional damper actuator for adjusting air dampers in ventilation and air-conditioning systems for building services installations For air dampers up to approx. m orque
More informationServomotor for butterfly valves VF, VFH. delta-elektrogas.com EE157-01/16
MZ Servomotor for butterfly valves VF, VFH delta-elektrogas.com EE157-01/16 MZ Servomotor Contents Description.... 2 Features........ 2 Functioning and application..... 3 Technical specifications......
More informationma/bcd Converter Model MFC-201 ma/bcd The MFC-201 ma/bcd Converter is a device designed to convert a DC current signal into BCD (8421) signals.
1 Definition ma/bcd Converter Model MFC-201 ma/bcd The MFC-201 ma/bcd Converter is a device designed to convert a DC current signal into BCD (8421) signals. 2 Operating Principle An electronic circuit
More information21 VA (l max 20 5 ms) Connection Cable 1 m, 4 x 0.75 mm 2 Functional data Factory settings Variable Setting Torque Inhibiting torque
echnical data sheet GK4A- Communicative SuperCap rotary actuator with emergency setting function and extended functionalities for adjusting air dampers in ventilation and air-conditioning systems for building
More information11 VA Connection Cable 1 m, 4 x 0.75 mm 2 Functional data Factory settings Variable Setting Torque (nominal torque) Motor Spring return
echnical data sheet SF24A- Communicative spring return actuator with emergency function for adjusting air dampers in ventilation and air conditioning systems in buildings For air dampers up to approx.
More informationVFSC9 ELECTRONIC SPEED CONTROLLER. Mounting and operating instructions
ELECTRONIC SPEED CONTROLLER Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 5 WIRING
More informationcurrent transformers or VAC secondary voltage from our SIGNAL CONVERTERS Selection Chart
NK Technologies ADC series signal converters use sensor outputs (4 0 ma, 0 5 and 0 10 VDC) and convert these to digital RS485 outputs. The CTC series accept either 5 A secondary current from Analog to
More informationELECTRONIC THERMOSTAT: T920
μnistδt ELECTRONIC THERMOSTAT: T One analog output DESCRIPTION The T series thermostats are microcomputer-based, proportional and integral (PI) devices with one analog 0 to 0 output. They can be used with
More information269 Troubleshooting Guide 11/4/98 1
269 Troubleshooting Guide 11/4/98 1 Table of Contents Phase currents 3 Communications. 6 RTDs.. 9 Ground Fault Currents... 13 Output Relays. 15 Analog Output 17 Switch Inputs...18 11/4/98 2 Phase Currents
More informationData Acquisition Modules/ Distributed IO Modules
User Manual Data Acquisition Modules/ Distributed IO Modules Future Design Controls, Inc. 7524 West 98 th Place / P.O. Box 1196 Bridgeview, IL 60455 888.751.5444 - Office: 888.307.8014 - Fax 866.342.5332
More informationElectrical data Nominal voltage AC/DC 24 V Nominal voltage frequency
echnical data sheet NM24A- Communicative damper actuator for adjusting dampers in technical building installations Air damper size up to approx. 2 m² Nominal torque Nm Nominal voltage AC/DC 24 V Control
More informationGUIDE SPECIFICATIONS CONTROLS SPECIFICATIONS AND CONTROL POINT DATA MAP GENERAL DESCRIPTION
GUIDE SPECIFICATIONS 256920-UGS-A-0506 Simplicity Intelli-Comfort Optional Control in 3-25 Ton Packaged Units GENERAL DESCRIPTION CONTROLS SPECIFICATIONS AND CONTROL POINT DATA MAP Equipment with Simplicity
More informationioselect Z-NET Z-4RTD 4 Channel RTD Input Module
4 Channel nput Module : PT00, PT000, PT500 & N00: 2, 3 & 4 wire 500 V solation, 6-way Modbus Communications Adjustable Sampling Time Accuracy to 0.2 C Configuration and Setup Software EC 63 Flexible Power
More informationERV-M ELECTRONIC FAN SPEED CONTROLLER. Mounting and operating instructions
ELECTRONIC FAN SPEED CONTROLLER Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 5
More informationSeries Valve Temperature Controller. Instruction Sheet
2013/10/03 Series Valve Temperature Controller Instruction Sheet Thank you very much for choosing Delta DTV series valve temperature controller. Please read this instruction sheet before using your DTV
More informationElectrical data Nominal voltage AC/DC 24 V Nominal voltage frequency
echnical data sheet SVK24A--PC Communicative globe valve actuator with emergency control function for 2-way and 3-way globe valves Actuating force 1500 N Nominal voltage AC/DC 24 V Control modulating,
More informationUltrasonic Multiplexer OPMUX v12.0
Przedsiębiorstwo Badawczo-Produkcyjne OPTEL Sp. z o.o. ul. Morelowskiego 30 PL-52-429 Wrocław tel.: +48 (071) 329 68 54 fax.: +48 (071) 329 68 52 e-mail: optel@optel.pl www.optel.eu Ultrasonic Multiplexer
More informationMICRO-CONTROLLER X (48 48 mm)
PX series digital temperature controller MICRO-CONTROLLER X ( mm) DATA SHEET PXG PXG is a compact size temperature controller of front panel size mm. To cope with any of versatile uses as a temperature
More informationAir Water Actuators xm(c)24a-mod xr24a-mod xv(k)24a-mod xf24a-mod xrf24a-mod
Modbus-Register Description Air Water Air Water Actuators xm(c)24a-mod xr24a-mod xv(k)24a-mod xf24a-mod xrf24a-mod Contents Modbus General Notes 2 Modbus Register Overview 3 Modbus Register Description
More informationNX Series Inverters. HVAC Pocket Programming Guide
NX Series Inverters HVAC Pocket Programming Guide HVAC Pocket Programming Guide HVAC Pocket Programming Guide / Contents This guide provides a single reference document for the user of NXL HVAC (product
More informationMV110-8AS. Analog input module 8 channel. User guide
MV110-8AS Analog input module 8 channel User guide MV110-8AS_2016.12_0226_EN All rights reserved Subject to technical changes and misprints Contents 1 Description... 2 1.1 Function... 2 1.2 RS485 network...
More informationBAS Integration Manual
Snow Melting Control 680 Introduction BAS Integration Manual Snow Melting 680_B 10/15 Replaces: 04/15 The Snow Melting Control 680 can communicate with a Building Automation System (BAS) using either BACnet
More informationExcellent low-cost Process & Temperature Controllers
C22 C62 C82 C83 Excellent low-cost Process & Temperature Controllers C72 C42 R22 01. High Quality LCD Display 02. High Accuracy 18 Bit A-D Input and 15 Bit D-A Output 03. The Fast Sampling Rate in 200
More informationBusWorks 900EN Series Modbus TCP/IP 10/100M Industrial Ethernet I/O Modules
BusWorks 900EN Series Modbus TCP/IP 10/100M Industrial Ethernet I/O Modules Six Differential Current Inputs Six Differential Voltage Inputs USER S MANUAL ACROMAG INCORPORATED Tel: (248) 295-0880 30765
More informationIO-DIM4 4-Channel, Digital to Analogue Converters
Page 1 of 5 IO-DIM4 4-Channel, Digital to Analogue Converters Features: Benefits: Input status indication Calibrated output DIN Rail mounting Expands controller input capacity Fault finding LED indication
More informationSRC-110 Series Zone Controllers with Modbus RTU
Product sheet CT2.142 Type SRC-110-MOD SRC-110 Series Zone Controllers with Modbus RTU The SRC-110 series controllers have been designed for zone heating and cooling control. The controllers have 3 analogue
More informationHD 48V01T... HD 4977T...
RH-26 HD 4807T HD 4907T HD 48V07T HD 4901T... HD 4801T... HD 4917T... HD 48V01T... HD 4977T... HD 4817T... HD 48V17T... HD 4877T... HD 48V77T... HD 4807T, HD 48V07T, HD 48S07T, HD 4801T..., HD 48V01T...,
More informationElectrical data Nominal voltage AC/DC 24 V Nominal voltage frequency
echnical data sheet LM24A-KNX Communicative damper actuator for adjusting dampers in technical building installations Nominal torque 5 Nm Nominal voltage AC/DC 24 V Conversion of sensor signals echnical
More informationRSMFX-2R MULTIFUNCTIONAL
Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAMS 5 WIRING AND
More informationisma-b-w0202 Modbus User Manual GC5 Sp. z o.o. Poland, Warsaw
isma-b-w0202 isma-b-w0202 Modbus User Manual GC5 Sp. z o.o. Poland, Warsaw www.gc5.com 1. Introduction... 4 2. Safety rules... 4 3. Technical specifications... 5 4. Dimension... 6 5. LED Indication...
More informationMULTIFUNCTION GRAPHICAL UNIT MGU 800
MULTIFUNCTION GRAPHICAL UNIT MGU 800 For display, recording and evaluation of process instruments signals (level, temperature, pressure, etc.) 3.5" TFT display, multi-language menu Variety of possible
More informationCONTROL Room. Room product for Swegon s WISE system for demand-controlled ventilation. Quick facts Room control against temperature, CO 2
Room product for Swegon s WISE system for demand-controlled ventilation Quick facts Room control against temperature, CO 2, content, etc. Static pressure and flow measurement Position-independent Shut-off-capable
More informationInstallation of VAV-Compact Retrofit with ZDMS-..
Installation of VAV-Compact Retrofit with ZDMS-.. LMVAX-D3-MP NMVAX-D3-MP ZDMS-.. VAV-Compact Retrofit for utilisation of existing VAV devices made by various manufacturers. for various air velocities
More informationPROCESS & TEMPERATURE CONTROLLERS
PROCESS & TEMPERATURE CONTROLLERS NOVA PD54 Series Thermocouple, RTD, & Process Inputs High Accuracy Auto-Tuning PID Heating & Cooling Models Universal Power Supply 1-24 VAC Up to 3 Relays & 2 Analog Outputs
More informationINTRODUCTION. T hank you for your HB8215/HB8216 loadcell indicator purchase. The HB8215 and HB8216 are the best choice for industrial weighing
INTRODUCTION T hank you for your HB8215/HB8216 loadcell indicator purchase. The HB8215 and HB8216 are the best choice for industrial weighing application requiring quality, performance and economy. Please
More informationEY-EM 527: Remote I/O module, ecolink527
Product data sheet 94.078 EY-EM 527: Remote I/O module, ecolink527 How energy efficiency is improved Regulation, control, monitoring and optimisation of operational systems, e.g. room automation or HVAC
More informationTLE ANALOG WEIGHT TRANSMITTER 4 20 ma, 0 20 ma, 0 10 V, 0 5 V, V, -5 5 V
Installation and User Manual version 1.00 TLE ANALOG WEIGHT TRANSMITTER 4 20 ma, 0 20 ma, 0 10 V, 0 5 V, -10 10 V, -5 5 V 2014/30/EU EN55022:2010 EN61000-6-2:2005 EN61000-6-4:2007 SYSTEM IDENTIFICATION
More informationRI-D440. Three Phase easywire Multifunction DIN Rail Energy Meter. Telephone : +44 (0) Displayed Parameters
RI-D440 Three Phase easywire Multifunction DIN Rail Energy Meter Four module DIN rail mounted Energy pulse LED 330mV Input from easywire CTs (or -/1A and -/5A current transformer input with TAS-SCTEWA
More information8000 SERIES PRECISION MULTIMETER VERIFICATION AND ADJUSTMENT GUIDE
8000 SERIES PRECISION MULTIMETER VERIFICATION AND ADJUSTMENT GUIDE TRANSMILLE LTD. Version 1.1 : Apr 2015 TABLE OF CONTENTS PREPARING FOR CALIBRATION... 4 INTRODUCTION... 4 CALIBRATION INTERVAL SELECTION...
More informationHigh Performance Process & Temperature Controllers
C22 C62 C82 C83 High Performance Process & Temperature Controllers C72 C42 R22 01. Multi Color LCD Display 02. High Accuracy 18 Bit A-D Input and 15 Bit D-A Output 03. 200 msec Sampling Rate 04. True Universal
More informationElectro Controls. Input-Output Modules WattsIndustries.co.uk
Electro Controls Input-Output Modules - 2017 WattsIndustries.co.uk Input-Output Modules Section 08 B.M.S INPUT - OUTPUT MODULES SINGLE AND ADJUSTABLE RELAY ESRM.. Volt free contacts DIN RAIL mounted relay
More informationHC-220 PID Controller
HC-220 PID Controller Operation and Maintenance Manual The information contained in this manual was current at the time of printing. The most current versions of all Hydro Instruments manuals can be found
More informationSingle Channel Loop Detector
Single Channel Loop Detector Model LD120T Series The LD120T is a series of single channel inductive loop detectors. The use of microprocessor and surface mount technology enables a large number of functions
More informationElectrical data Nominal voltage AC/DC 24 V Nominal voltage frequency
echnical data sheet SHK24A-MF Parameterisable linear SuperCap actuator with emergency control function and extended functionalities for adjusting dampers and slide valves in technical building installations
More informationEarth Leakage Monitoring System IsoBase IsoHub IsoOut
2014 11 21 Earth Leakage Monitoring System IsoBase IsoHub IsoOut User Manual Due to our policy of continual improvement, specifications may change without prior notice Page 2 (34) Contents Earth Leakage
More informationSTANDARD WIRING DIAGRAMS FOR SMART MODEL 20
CODING SYSTEM FOR AV ACTUATOR WIRING DIAGRAMS There are 3 elements to the wiring codes used in AVA electric actuators: WIRING CODE 1 3 Wire system, single pole double throw, switching the live SPDT 2 3
More informationApril 1994 UCM-420A. Setpoint Controller. Operating and Installation Instructions
April TM UCM-A Setpoint Controller Operating and Installation Instructions A LARGE number of applications in a SMALL package... REMOTE SETPOINT CONTROLLER LOCAL SETPOINT CONTROLLER - ma SIGNAL GENERATOR
More informationPosition Indicator model MFC-300/IP. Technical Manual. Licht
Position Indicator model MFC-300/IP Technical Manual Licht Contents 1 Introduction 2 2 Front panel indication 3 3 Error indication 4 4 Manual commands 5 5 Configuration 6 5.1 Parameter reset 6 6 Programmable
More information745 Transformer Protection System Communications Guide
Digital Energy Multilin 745 Transformer Protection System Communications Guide 745 revision: 5.20 GE publication code: GEK-106636E GE Multilin part number: 1601-0162-A6 Copyright 2010 GE Multilin GE Multilin
More informationmaxon document number:
maxon document number: 791272-04 1 Table of contents... 2 2 Table of figures... 3 3 Introduction... 4 4 How to use this guide... 4 5 Safety Instructions... 5 6 Performance Data... 6 6.1 Motor data... 6
More informationRoom Controller Thermostat
ºF / º VAV Thermostat with BAnet ommunication Port Technical Data Inputs Room ontroller Thermostat TROB24T4XYZ1 3 Analog input universal (0-10 Vdc or thermistor or digital input dry contact) 2 Analog outputs
More informationTemperature Controller model MFC-301/T-Dry. Version for Dry Transformers and Motors. Technical Manual. Licht
Temperature Controller model MFC-301/T-Dry Version for Dry Transformers and Motors Technical Manual Licht Contents 1 Introduction 2 2 Operating principle 3 2.1 General principle 3 2.2 RTD operation 3 3
More informationDC Current Transducers
Current Transducers are designed to provide an analog current reading for monitoring, data logging and panel meter applications. NK Technologies current transducers offer a choice of 5 VDC, 1 VDC or ma
More informationMicroManager. Torque Mode CTCW/Loadcell Control. Instruction Manual MM3000-CTCW
MicroManager Torque Mode CTCW/Loadcell Control Instruction Manual MM3000-CTCW Table of Contents 1. General Description... 5 2. Specifications... 5 2.1 Electrical... 5 2.2 Physical... 6 3. Installation...
More informationSenseair S8 Commercial
Product Specification Senseair S8 Commercial Miniature infrared CO 2 sensor module 1 (8) Item Senseair S8 Commercial Article No. 004-0-0010, 004-0-0075 Target gas CO 2 Operating Principle Non-dispersive
More informationWireless Analog Output Modules
Overview and Product Identification Wireless Analog s Analog s receive data from a BAPI 418 MHz receiver or 900 MHz receiver through a four-wire RS 485 bus. Up to 127 different Analog s can be connected
More informationDC1010/DC1020/DC1030/DC1040/Compact type DIGITAL CONTROLLERS Specification
01 May 20 30-10-10--EN Page 1 of DC1010/DC1020/DC1030/DC1040/Compact type DIGITAL CONTROLLERS Specification Overview The DC1000 Series are microprocessorbased controllers designed with a high degree of
More informationEnergy Meters for DIN Rail Mounting Electric energy meter WS0101, WS0102,WS1102 WS0301, WS0302,WS1302
Energy Meters for DIN Rail Mounting Electric energy meter WS0101, WS0102,WS1102 WS0301, WS0302,WS1302 Direct connection up to 65 A (WSx10x) Connection with current transformer (WSx30x) Industrial or meters
More informationProgramming restrictions when operating SM 331; AI 8 x RTD with PROFIBUS masters which only support DPV0.
6.9 Analog input module SM 331; AI 8 x RTD; (6ES7331-7PF01-0AB0) Cycle time extension due to wire-break monitoring The wire-break monitoring software function of the module is available in all operating
More informationPLA 33. Power line analyzer. User and service manual. version 2.4
PLA 33 Power line analyzer User and service manual version 2.4 Content. Front control panel and terminal plate...3 7.2.2. System frequency setting...0 2. Device description...4 7.2.3. Password protection...0
More informationTable of Contents. Proximity Sensors. IEC Limit Switches. Encoders. Current Sensors. Section 17
Proximity Section 17 Table of Contents............ 21 2 Application Guide........................ 21 3 ACT Series Transducers......... 21 4 ACTR Series Transducers........ 21 6 ACS150 Series Switches..................
More informationTechnical data. Parameterisable damper actuator in the
echnical data sheet Parameterisable damper actuator in the IP66 protective housing for or adjusting ad usting air dampers in industrial plants and in technical building installations For air dampers up
More informationIP1 Datasheet PWM OUTPUT WITH SINGLE CHANNEL ADC MODULE FEATURES DESCRIPTION CONNECTOR DETAILS
PWM OUTPUT WITH SINGLE CHANNEL ADC MODULE FEATURES 1 PWM Output (3.3V) 0 Hz 1 khz Single Channel 3.3V 12-bit ADC input for voltage sensing Optional automated PWM adjustment based on input voltage for standalone
More informationElectrical data Nominal voltage AC/DC 24 V Nominal voltage frequency
echnical data sheet SM24A--P Communicative damper actuator for adjusting dampers in technical building installations Air damper size up to approx. 4 m² Nominal torque 2 Nm Nominal voltage AC/DC 24 V Control
More informationGB QUICK GUIDE FOR THE CONFIGURATION OF VARIABLE SPEED DRIVES
GB QUICK GUIDE FOR THE CONFIGURATION OF VARIABLE SPEED DRIVES LOVATO ELECTRIC S.P.A. 24020 GORLE (BERGAMO) ITALIA VIA DON E. MAZZA, 12 TEL. 035 4282111 FAX (Nazionale): 035 4282200 FAX (International):
More informationBU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on supply lines for medical locations ISOLTESTER-DIG-RZ/RS/PLUS
INSTRUCTION MANUAL BU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on supply lines for medical locations ISOLTESTER-DIG-RZ/RS/PLUS 1/23 More information than that reported
More informationManual triggering of the adaption by pressing the «Adaption» button or with the PC-Tool
echnical data sheet LMA-MF-P Multifunctional damper actuator for operating air control dampers in ventilation and air-conditioning systems for building services installations For air dampers up to approx.
More informationDigital Panel Meters DC/AC Current and Voltage Indicator/Controller Type LDM40
Digital Panel Meters Current and Voltage Indicator/Controller Type LDM40 Multi-input instrument 4-DGT LED 0.1% RDG basic accuracy TRMS AC current and voltage measurements AC/DC current measurements: selectable
More informationsw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS
INSTRUCTIONS MANUAL IM831-U v0.92 HRI-R40W sw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS INDEX: GENERAL TYPES ACESSORIES AND OPTIONS
More informationAPPENDIX APPENDIX A 1
A 1 SPECIFICATIONS Ratings Supply voltage 100 to 240 VAC, 50/60 Hz 24 VAC, 50/60 Hz/24 VDC Operating voltage range 85 to 110% of rated supply voltage Power consumption 7VA 4VA/2.5W Sensor input Thermocouple
More informationAnalogue temperature controllers
Analogue temperature controllers CT8A Input by J-K thermo-couple or by thermo-resistance Pt 00 (-wire) regulation modes : ON/OFF or proportional derivative selected by wiring Relay output Specifications
More informationMars-Energo. Volt/mA Calibrator CALMAR-S. User s manual Edition 3.1
Mars-Energo Volt/mA Calibrator CALMAR-S User s manual Edition 3.1 Manufacturer: OOO NPP Mars-Energo Address: V.O. 13 Line, 6-8, office 41H, Saint-Petersburg, Russia, 199034 2017 MARS-ENERGO Table of contents
More informationMETERSUK. SmartLink D Y N A M i T E. EM415 MOD Series. User Manual KEY FEATURES INDEX 3. TECHNICAL DESCRIPTION. Single Phase Metering
METERSUK LTD s a l e s @ m e t e r s. c o. u k 0 1 5 2 4 5 5 5 9 2 9 Series Smart Energy Meter KEY FEATURES Single Phase Metering Single phase metering 4 din modules, Standard DIN rail Format (DIN43880)
More informationDigital electronic module 4DO DC24V/2A HF (6ES7132-4BD30-0AB0) SIMATIC
Digital electronic module 4DO DC24V/2A HF (6ES7132-4BD30-0AB0) SIMATIC Properties 1 Parameters 2 Diagnostics 3 ET 200S distributed I/O Digital electronic module 4DO DC24V/2A HF (6ES7132-4BD30-0AB0) Manual
More informationAC Current Transducers
Current Transducers are designed to provide an analog signal proportional to the AC current for monitoring, data logging and panel meter applications. NK Technologies current transducers offer a choice
More informationDTAP. universal programmable controller. Универсален програмируем контролер
dtap DTAP Универсален програмируем контролер universal programmable controller The DTAPG universal programmable controller provides a temperature and/or an analog input (0-10 VDC/0-20 ma/pwm) and a user-defined
More informationmicro Technical Manual
GB micro opos 4 Positioning system Progr. version M001B110 Technical Manual Servo unit micropos 4 Contents 1. Introduction... 1 1.1. General... 1 1.2. System survey... 2 1.3. Master... 3 Modbus RTU or
More informationI-7088, I-7088D, M-7088 and M-7088D User Manual
I-7088, I-7088D, M-7088 and M-7088D User Manual I-7000 New Features 1. Internal Self Tuner 2. Multiple Baud Rates 3. Multiple Data Formats 4. Internal Dual WatchDog 5. True Distributed Control 6. High
More informationSignet 9900 Transmitter
Signet 9900 Transmitter Member of the SmartPro Family of Instruments Features Field Mount Multi-Parameter input selection Large auto-sensing backlit display with at a glance visibility Dial-type digital
More informationBACnet- MS/TP COMMUNICATION V
- MS/TP COMMUNICATION V1.00.08.17 11.1 Introduction The VFD can be controlled and monitored through the BACnet MS/TP protocol over an RS-485 connection. The VFD operates as an MS/TP master device, which
More informationIntroduction. Specifications LF620,LF622. Field Intelligent Device Series Electromagnetic Flowmeter Converter
Field Intelligent Device Series Electromagnetic Flowmeter Converter LF620,LF622 Introduction Combined with a multi-functional converter LF620 (combined type) or LF622 (separate type) equipped with its
More informationSolarEdge Feed-in Limitation Application Note
SolarEdge Feed-in Limitation Application Note Version 1.0 Disclaimers Disclaimers Important Notice Copyright SolarEdge Inc. All rights reserved. No part of this document may be reproduced, stored in a
More informationN1040i Indicator. UNIVERSAL INDICATOR INSTRUCTIONS MANUAL V1.0x D PRESENTATION FEATURES
UNIVERSAL INDICATOR INSTRUCTIONS MANUAL V1.0x D PRESENTATION N1040i is a quite versatile process indicator. With a wide list of input types - thermocouples, thermo-resistance, voltage and current the N1040i
More informationThe DO8332 module is equipped with eight outputs for 1-wire connections. The rated output current is 2 A.
1.1 DO8332 1.1.1 General information The DO8332 module is equipped with eight outputs for 1-wire connections. The rated output current is 2 A. The output supply is fed directly to the module. An additional
More information