1 SIGNET ph/orp Transmitter D-4/0 English CAUTION! Remove power to unit before wiring input and output connections. Follow instructions carefully to avoid personal injury. Contents. Installation. Specifications. Electrical Connections 4. Menu Functions ph/orp 0.0 ph 5.0 C. Installation ProcessPro transmitters are available in two styles: panel mount and field mount. The panel mount is supplied with the necessary hardware to install the transmitter. This manual includes complete panel mounting instructions. Field mounting requires a separate mounting kit. The Universal kit enables the transmitter to be installed virtually anywhere. Detailed instructions for field installation options are included with the Universal kit.. Panel Installation. The panel mount transmitter is designed for installation using a /4 DIN Punch. For manual panel cutout, an adhesive template is provided as an installation guide. Recommended clearance on all sides between instruments is inch.. Place gasket on instrument, and install in panel.. Slide mounting bracket over back of instrument until quick-clips snap into latches on side of instrument. 4. To remove, secure instrument temporarily with tape from front or grip from rear of instrument. DO NOT RELEASE. Press quick-clips outward and remove. gasket panel terminals mounting bracket 96 mm (.8 in.) mm (. in.) Optional Rear Cover 9 mm (.6 in.) latch System Pwr Loop - System Pwr Loop 4 Output - Output Sensr Gnd (SHIELD) Sensr IN (RED) Sensr V (BLACK) 96 mm (.8 in.) FRONT VIEW Field Mount & Panel Mount 4 mm (.7 in.) 64 mm (.5 in.) 06 mm (4. in.) SIDE VIEW Field Mount 4 mm (.6 in.) 56 mm (. in.) 97 mm (.8 in.) SIDE VIEW Panel Mount Panel Mount Installation Detail quick-clips. Specifications General Compatible electrodes: GF SIGNET -70 Twist-Lock ph/orp Preamplifier/-7X Electrodes Accuracy: ±0.0 ph, ± mv ORP Enclosure: Rating: NEMA 4X/IP65 front Case: PBT Panel case gasket: Neoprene Window: Polyurethane coated polycarbonate Keypad: Sealed 4-key silicone rubber Weight: Approx. 5g ( oz.) Display: Alphanumeric x 6 LCD Contrast: User selected, 5 levels Update rate: second Electrical Power: to 4 VDC ±0%, regulated, 60 ma max. Sensor input range: ph: 0.00 to 4.00 ph Temp. (ph only) K Balco, -5 to 0 C (- to 48 F) ORP: -000 to 000 mv, isolated (0KΩ I.D. resistance T, T-) Two 4 to 0 ma Outputs: Passive, isolated, fully adjustable and reversible 4 to 0 ma outputs are independently source selectable for ORP, or ph or temperature. Max loop impedance: 50 Ω V 5 Ω 8 V 600 Ω 4 V Update rate: 0.5 seconds Accuracy: ±0.0 5 C, 4 V Two Open-collector outputs: Isolated, 50 ma sink or source, 0 VDC max. pull-up voltage Programmable for: High or Low operation, w/adjustable Hysteresis Proportional Pulse operation (400 pulses/minute maximum) Environmental Operating temperature: -0 to 70 C (4 to 58 F) Storage temperature: -5 to 80 C (5 to 76 F) Relative humidity: 0 to 95%, non-condensing Maximum altitude: 000 m (656 ft) Insulation category: II Pollution degree: Standards and Approvals CSA, CE, UL listed Immunity: EN5008- Emissions: EN550 Class B Manufactured under ISO 900 and ISO ph/orp Transmitter SIGNET page of
2 . Electrical Connections Caution: Failure to fully open terminal jaws before removing wire may permanently damage instrument. Wiring Procedure. Remove in. (-6 mm) of insulation from wire end.. Press the orange terminal lever downward with a small screwdriver to open terminal jaws.. Insert exposed (non-insulated) wire end in terminal hole until it bottoms out. 4. Release orange terminal lever to secure wire in place. Gently pull on each wire to ensure a good connection. Wiring Removal Procedure. Press the orange terminal lever downward with a small screwdriver to open terminal jaws.. When fully open, remove wire from terminal. Wiring Tips: Do not route sensor cable in conduit containing AC power wiring. Electrical noise may interfere with sensor signal. Routing sensor cable in grounded metal conduit will help prevent electrical noise and mechanical damage. Seal cable entry points to prevent moisture damage. Only one wire should be inserted into a terminal. Splice double wires outside the terminal. Terminals -4: Passive current loop -4 VDC ±0% required for system power and current loop output. Max. loop impedance: 50 Ω V 5 Ω 8 V 600 Ω 4 V 8 Terminals -6: Sensor connections -4 are mv (ph or ORP) input from the electrode. 5-6 are Temperature input from the ph electrode or 0K Ω id resistor from ORP electrode Output Temp - (WHITE) Temp (GREEN) Iso. GND (BLUE) mv Input (BROWN) 4 Loop - 7 Output Earth GND Loop 6 Output - Sensr Gnd (SHIELD) System Pwr Loop - System Pwr Loop 5 Output 0 9 V- (BLACK) V (RED) Internal open-collector output circuit S 5Ω D Isolation Output -- Output Terminals 9-: Preamplifier power and grounds 9-0 are DC voltages from the 8750 to power the preamplifier. - are ground terminals for the sensor and for earth ground. Terminals 5-8: Open-collector Outputs Two transistor outputs, programmable in CALIBRATE menu as: High or Low setpoint with adjustable hysteresis Proportional pulse up to 400 pulses per minute May be disabled (Off) if not used. page of SIGNET ph/orp Transmitter
3 . Sensor Input Connections Terminals * White (Temp) Green (Temp) Blue (ISO GND) Brown (mv input) Silver (Shield) Black (V-) Red (V) * (connection of terminal 4 to Earth GND may reduce electrical interference) Preamp: GF SIGNET 70 ph Electrodes GF SIGNET 74, 74-HF GF SIGNET 76 ORP Electrodes: GF SIGNET 75 GF SIGNET 77 Transmitter ph/orp 400 ft. ( m). System Power/Loop Connections Stand-alone application, no current loop used Transmitter Terminals Loop 4 NC Loop System Power Loop System Power Loop NC Power Supply 4 VDC Connection to a PLC/Recorder, separate supply Connection to a PLC with built-in power supply Loop Loop System Power Loop System Power Loop Transmitter Terminals 4 PLC or Recorder Power Supply 4 VDC The current loop is a passive circuit. -4 VDC must be provided from an external source. Channel 4-0 ma Channel 4-0 ma Loop Loop System Power Loop System Power Loop Transmitter Terminals 4 Internal PLC Connection PLC Terminals Channel 4-0 ma Channel 4-0 ma Power Supply 4 VDC Example: Two transmitters connected to PLC/Recorder with separate power supply Transmitter Terminals PLC or Recorder Channel 4-0 ma in Channel 4-0 ma in Channel 4-0 ma in Channel ma in Transmitter Terminals Loop 4 4 Loop Loop System Power Loop System Power Loop Loop System Power Loop System Power Loop Power Supply 4 VDC ph/orp Transmitter SIGNET page of
4 . Open Collector Output The Open Collector output can be used as a switch that responds when the process value moves above or below a setpoint, or it can be used to generate a pulsing signal with a rate proportional to the process value. Low: Output triggers when process variable is less than the setpoint. The output will relax when the process variable moves above the setpoint plus the hysteresis value. Proportional Pulsing The Open Collector output will generate a 00 ms pulse at the rate defined by settings in the CALIBRATE menu (see page 6) In the example below: The output will be 0 pulses/min. at ph values less than 5.0. The output will be 50 pulses/min. at 7.5 ph. The output will be 00 pulses/min. at ph values above 0 ph. High: Output triggers when process variable is greater than the setpoint. The output will relax when the process variable moves below the setpoint plus the hysteresis value. Hysteresis Low Setpoint High Setpoint Process Relay energized Relay relaxed Time 0 pulses Process 5 0 Starting point Open Collector Output Rate: 0 to 00 Pulses/min. 00 pulses Pulse rate endpoint Hysteresis Time VIEW menu During normal operation, ProcessPro displays the VIEW menu. When using the CALIBRATE or OPTIONS menus, ProcessPro will return to the VIEW menu if no activity occurs for 0 minutes. To select the item you want displayed, press the UP or DOWN arrow keys. The items will scroll in a continuous loop. Changing the display selection does not interrupt system operations. No keycode is necessary to change display selection. Output settings cannot be edited from the VIEW menu. ph/orp 0.0 ph 5.0 C View Menu for ph Display 7.00 ph.6 ºC Description Monitor the Temperature input from the sensor. This is the permanent display. All of the VIEW displays below are temporary. The permanent display will return after ten minutes. Input: 07 mv Monitor the millivolt input from the electrode. Use this display to determine the relative condition of your electrode during periodic calibration. (7 ph buffer = 0 mv, ±50 mv) Loop Output: 4.6 ma Monitor the 4-0 ma Loop output. Last CAL: > Monitor date for scheduled maintenance or date of last calibration. (See description in Calibrate Menus.) EASY CAL: > Easy Cal is the fastest and simplest periodic calibration method. Requires 4 ph, 7 ph and 0 ph. (Any two) page 4 of SIGNET ph/orp Transmitter
5 ProcessPro Editing Procedure: Step. Press and hold key: seconds to select the CALIBRATE menu 5 seconds to select the OPTIONS menu. Step. The Key Code is UP-UP-UP-DOWN keys in sequence. After entering the Key Code, the display will show the first item in the selected menu. Step. Scroll menu with UP or DOWN arrow keys. Step 4. Press RIGHT ARROW key to select menu item to be edited. The first display element will begin flashing. Step 5. Press UP or DOWN keys to edit the flashing element. RIGHT ARROW key advances the flashing element. Step 6. Press key to save the new setting and return to Step. Notes on Step : The View Menu is normally displayed. The CALIBRATE and OPTIONS menus require a KEY CODE. Notes on Step : If no key is pressed for 5 minutes while display is showing "Enter Key Code", the display will return to the VIEW menu. Press & hold for access: CALIBRATE: ---- Enter Key Code CALIBRATE: *--- Enter Key Code VIEW CALIBRATE s 5s CALIBRATE: **-- Enter Key Code CALIBRATE: ***- Enter Key Code OPTIONS Temperature > First item in CALIBRATE menu Notes on Steps and 4: Refer to pages 6 and 7 for complete listing of menu items and their use. From the Step display, pressing the UP and DOWN keys simultaneously will return the display to the VIEW menu. If no key is pressed for 0 minutes, display will also return to the VIEW menu. Temperature > Step Step : Finished Editing? Press the UP and DOWN keys simultaneously after saving the last setting to return to normal operation. Output Setpnt: 0.0 ph> Step 4 Notes on Steps 5 and 6: All output functions remain active during editing. Only the flashing element can be edited. RIGHT ARROW key advances the flashing element in a continuous loop. Edited value is effective immediately after pressing key. If no key is pressed for 0 minutes unit will restore the last saved value and return to step. Step 6 (pressing key) always returns you to Step. Repeat steps -6 until all editing is completed. Output Setpnt: 0.00 ph Output Setpnt: ph Output Setpnt: ph Step 5 Step 5: Made an Error? Press the UP and DOWN keys simultaneously while any element is flashing. This will recall the last saved value of the item being edited and return you to Step ph/orp Transmitter SIGNET Step 6 Output Setpnt: ph Output Setpnt: 9.00 ph > Output Setpnt: Saving page 5 of
6 Calibrate Menu for ph Display (Factory settings shown) Temperature > Description Provides a maximum 5ºC offset to match temperature measurement to external reference. Standard > Slope > Loop Source: ph > Applies a linear offset to the ph measurement. The ideal value is the average ph of your application. (A sample of your application at process temperature is recommended.) Applies a slope to the ph measurement. The slope value and the standard value must be at least ph units apart. The ideal values are the minimum and maximum values of your process. Select ph or Temperature as the source for this current loop output. Loop Range: ph > Select the minimum and maximum values for this 4-0 ma current loop output. Output Source: ph > Output Mode: Low > Select ph or Temperature as the source for this open collector output. Select the mode of operation for the open collector output: High, Low or proportional Pulse. The signal may be disabled if not in use. Output Setpnt: 4.00 ph > In Low or High mode, the open collector output will be activated when the ph reaches this value. Output Hys: 0.50 ph > In Low or High mode, the open collector output will be deactivated at Setpoint ± Hysteresis, depending on High or Low setpoint selection. (See details on page 4.) Output Range: > Output PlsRate: 0 Pulses/min > If the output is in PULSE mode, set the start and end point of the range and also set the maximum pulse rate. (The maximum PULSE rate setting is 400 pulses per minute.) The combined output range and pulse rate settings shown here indicate: "Start pulsing when the ph value is 4 and increase the pulse rate up to the maximum of 0 pulses per minute when the ph value reaches 8" Last CAL: > Use this note pad to record important dates, such as annual recertification or scheduled maintenance. All Output functions will repeat for Output; All Loop functions will repeat for Loop. page 6 of SIGNET ph/orp Transmitter
7 EASY CAL Procedure - ph This procedure simplifies system calibration using standard 4.0, 7.0, 0.0 ph buffers only. If these ph buffers are not available, calibrate the system via the CALIBRATE menu, using the STANDARD and SLOPE settings. Access the CALIBRATE menu and set sensor temperature before performing EASY CAL for new electrode installations. Access EASY CAL menu from the view menu. EASY CAL: ---- Enter Key Code Press UP, UP, UP, DOWN buttons in sequence to enter menu, XXXX will appear during code entry. To Calibrate: Response: To Accept: Place Sensor in ph Buffer # Place electrode tip in first ph buffer ph 7.0 = 0 mv ph 4.0 = 77 ph 0 = -77 Limit ± 50 mv Place Sensor in ph Buffer # Place electrode tip in second ph buffer. * 6.90 ph -005 mv Allow for stabilization 0 seconds* *.9 ph 79 mv to accept Allow for stabilization Press to accept second buffer calibration. 0 seconds* * 6.90 ph -005 mv * 7.00 ph -005 mv *.9 ph 79 mv * 4.00 ph 79 mv Theoretical mv values 5 C mv To exit menus and return to VIEW press UP and DOWN button at the same time Display returns to VIEW Menu in 0 minutes or when is pressed Good Easy Cal Press <> Options Menu for ph Display (Factory settings shown) Description Contrast: > Averaging: Off > Output Active: Low > Adjust the LCD contrast for best viewing. A setting of is lower contrast, 5 is higher. Select lower contrast if the display is in warmer ambient surroundings. OFF provides the most instantaneous output response to changes in input value. LOW averaging = 4 seconds, HIGH averaging = 8 seconds of input signal. Active HIGH: This setting is used to turn a device (pump, valve) ON at the setpoint. Active LOW: This setting is used to turn a device (pump, valve) OFF at the setpoint. Temp Display: ºC > Select temperature units: ºC or ºF. Loop Adjust: 4.00 ma > Loop Adjust: 0.00 ma > Adjust the minimum and maximum current output. The display value represents the precise current output. Adjustment limits:.80 ma < 4.00 ma > 5.00 ma 9.00 ma < 0.00 ma >.00 ma Use this setting to match the 8750 loop output to any external device. Test Loop: > Press UP or DOWN keys to manually order any output current value from.6 ma to.00 ma to test current loop output. Test Output: Press UP or DOWN keys to manually toggle the state of the open collector output. > All Output and Loop functions will repeat for Output and Loop ph/orp Transmitter SIGNET page 7 of
8 Calibrate Menu for ORP Display (Factory settings shown) Standard > Slope > Loop Range: mv > Output Mode: Off > Description Applies a linear offset to the ORP measurement. If you are using a single-point calibration, use this function. The ideal value is the average ph of your application. (A sample of your application at process temperature is recommended.) Applies a slope to the ORP measurement. This function should only be used in a two-point calibration. The slope value and the standard value must be at least ph units apart. The ideal values are the minimum and maximum values of your application. Select the minimum and maximum ORP values for the 4-0 ma Current loop output. Maximum settings are -000 mv to 000 mv. Select the mode of operation for the Open Collector output: High, Low or proportional Pulse. The signal may also be disabled if not in use. Output Setpnt: -500 mv > In Low or High Mode, the Open Collector output will be activated when the ORP reaches this value. Output Hys: 0 mv > Output Range: mv > Output PlsRate: 0 Pulses/Min > Last Cal: > In Low or High mode, the Open Collector output will be deactivated at Setpoint ± Hysteresis, depending on High or Low Setpoint selection. (See details on page 4.) If the output is in PULSE mode, set the start and end point of the range and also set the maximum pulse rate. (The maximum PULSE rate setting is 400 pulses per minute.) The combined Output Range and Pulse rate settings shown here indicate: "Start pulsing when the ORP value is -500 and increase the pulse rate up to the maximum of 0 pulses per minute when the ORP value reaches 500" Use this note pad to record important dates, such as annual recertification or scheduled maintenance. page 8 of SIGNET ph/orp Transmitter
9 EASY CAL Procedure - ORP This procedure simplifies system calibration using standard 4.0 ph and 7.0 ph buffers saturated with Quinhydrone. To calibrate using any other ORP buffer solutions, use the Standard and Slope functions in the CALIBRATE menu. Access EASY CAL menu from the view menu. EASY CAL: ---- Enter Key Code Press UP, UP, UP, DOWN buttons in sequence to enter menu, will appear during code entry. To Calibrate: Response: To Accept: Place Sensor in ORP Buffer # Place electrode tip in first ph buffer; ph mv ph mv Place Sensor in ORP Buffer # Place electrode tip in second (different) ph buffer. ph mv ph mv To exit menus and return to VIEW press UP and DOWN button at the same time * ORP: 84 mv Input: 8 mv Allow for stabilization 0 seconds* * ORP: 6 mv Input: 60 mv to accept Allow for stabilization Press to accept second buffer calibration. 0 seconds* Display returns to VIEW Menu in 0 minutes or when is pressed * ORP: 84 mv Input: 8 mv * ORP: 87 mv Input: 8 mv * ORP: 6 mv Input: 60 mv * ORP: 64 mv Input: 60 mv Good Easy Cal Press <> * For best results, gently stir the submerged electrode for approximately 5 seconds during the stabilization period. Large temperature differences from process fluids to buffers may require longer stabilization time. Technical notes: The difference between the actual mv and value shown is a good indication of the condition of the electrode. Differences in excess of 50 mv may indicate a need to service the electrode. Options Menu for ORP Display (Factory settings shown) Contrast: > Description Adjust the LCD contrast for best viewing. A setting of is lower contrast, 5 is higher. Select lower contrast if the display is in warmer ambient surroundings. Averaging: Off > OFF provides the most instantaneous output response to changes in input value. LOW averaging = 4 seconds, HIGH averaging = 8 seconds of input signal. Longer averaging produces more stable display and output response. Output Active: Low > Active HIGH: This setting is used to turn a device (pump, valve) ON at the setpoint. Active LOW: This setting is used to turn a device OFF at the setpoint. Loop Adjust: 4.00 ma > Loop Adjust: 0.00 ma > Adjust the minimum and maximum current output. The display value represents the precise current output. Adjustment limits:.80 ma < 4.00 ma > 5.00 ma 9.00 ma < 0.00 ma >.00 ma Use this setting to match the 8750 loop output to any external device. Test Loop: > Press UP or DOWN keys to manually order any output current value from.6 ma to.00 ma to test current loop output. Test Output: > Press UP or DOWN keys to manually toggle the state of the open collector output ph/orp Transmitter SIGNET page 9 of
10 Troubleshooting - ph Display Condition Possible causes Suggested Solutions During Easy Cal: "Out of Range Use Manual CAL". Required 4, 7 or 0 buffers not being used.. Sensor is depleted too severely to use Easy Cal. Use ph 4, 7, 0 buffers. Clean probe and retry EASY CAL.. Use Manual calibration for Standard and Slope if mv offset exceeds 50 mv. During Easy Cal: "Same Buffer" Sensor was not moved from buffer # to buffer #.. Place sensor in correct buffer solution.. Use fresh buffer. During CALIBRATE Std: "Standard too close to Slope!". ph Standard value within ph units of Slope value. ph Sensor efficiency is inadequate. Use ph values at least ph units apart.. Clean ph sensor; replace if necessary. Use fresh buffer. During CALIBRATE Slope: "Slope too close to Standard!". ph Slope value within ph units of Standard value. ph Sensor efficiency is inadequate. Use ph values at least ph units apart.. Clean ph sensor; replace if necessary. Use fresh buffer. During CALIBRATE: "Out of Range Check Sensor". No temperature or mv signal from sensor detected.. No connection between ph sensor and preamplifier.. Check all wiring, contacts in preamplifier.. Verify sensor is securely installed.. Replace ph sensor. During normal operation: Constant "5.00 ph" or constant "0.00 ph" with good temp value mv input is less than 0 ph or greater than 5 ph.. Recalibrate system.. Replace ph sensor. Replace preamplifier. During normal operation: "Check Sensor?". No temperature or mv signal from sensor detected.. No connection between ph sensor and preamplifier.. Check all wiring, contacts in preamplifier.. Verify sensor is securely installed.. Replace ph sensor. The mv value from the sensor when placed in a 7 ph buffer represents the sensor offset. Signet recommends servicing/replacing the sensor when the offset exceeds 50 mv. The -759 ph/orp system tester allows simple system troubleshooting. page 0 of SIGNET ph/orp Transmitter
11 Troubleshooting - ORP Display Condition Possible causes Suggested Solutions During Easy Cal: "Out of Range Use Manual CAL". Required 4, 7 buffers with quinhydrone not being used.. Sensor is depleted too severely to use Easy Cal. Use ph 4, 7 buffers saturated with quinhydrone.. Clean probe and retry EASY CAL.. Use Manual calibration for Standard and Slope if mv offset exceeds 50 mv. During Easy Cal: "Same Buffer" Sensor was not moved from buffer # to buffer #.. Place sensor in correct buffer solution.. Use fresh buffer. During CALIBRATE Std: "Standard too close to Slope!". ORP Standard value within 0 mv of Slope value. ORP Sensor efficiency is inadequate. Use ORP values at least 0 mv apart.. Clean ORP sensor; replace if necessary. Use fresh buffer. During CALIBRATE Slope: "Slope too close to Standard!". ORP Slope value within 0 mv of Standard value. ORP Sensor efficiency is inadequate. Use ORP values at least 0 mv apart.. Clean ORP sensor; replace if necessary. Use fresh buffer. During CALIBRATE: "Out of Range Check Sensor". No mv signal or sensor id from sensor detected.. No connection between ORP sensor and preamplifier.. Check all wiring, contacts in preamplifier.. Verify sensor is securely installed.. Replace ORP sensor. During normal operation: Constant "-000" or constant ""000" mv input is less than -999 or greater than Recalibrate system.. Replace ph sensor. Replace preamplifier. During normal operation: "Check Sensor?". No temperature or mv signal from sensor detected.. No connection between ph sensor and preamplifier.. Check all wiring, contacts in preamplifier.. Verify sensor is securely installed.. Replace ORP sensor ph/orp Transmitter SIGNET page of
12 Ordering Information Mfr. Part No. Code Description ph/orp transmitter Field mount P ph/orp transmitter Panel mount ph/orp transmitter Field mount with relays P ph/orp transmitter Panel mount with relays ph/orp transmitter Field mount with single input/dual output P ph/orp transmitter Panel mount with single input/dual output Accessories Mfr. Part No. Code Description Twist-Lock Flat ph electrode -74-HF Twist-Lock Flat ph hydrofluoric acid resistant electrode (<%) Twist-Lock Bulb ph electrode -76-DI Twist-Lock Bulb ph electrode for process liquids (< I00 µs) Twist-Lock Flat ORP Electrode Twist-Lock Bulb ORP Electrode Twist-Lock Preamplifier, /4 in. NPT Twist-Lock Preamplifier, ISO 7/-R /4 P Red sensor cap for in-line installations P Blue sensor cap for in-line installations ph/orp system tested (includes bypass adapter) Acapter Cable P55-0P PVC Pipe Adapter P55-0C CPVC Pipe Adapter P55-0V PVDF Pipe Adapter O-ring, FPM (standard) O-ring, EPR O-ring, Kalrez Universal mounting kit Splashproof rearº cover RC Filter kit (for relay use) /4 Integral mounting kit /4" NPT mount junction box Heavy duty wall mount bracket ph buffer kit Model 00 retrofit adapter Surface mount bracket x 5 inch adapter plate for GF Signet retrofit Liquid-tight connector kit, sets, / in. NPT Liquid-tight connector kit, set, / in. NPT Liquid-tight connector kit, set, PG VDC Power Supply 7.5 W, 00mA VDC Power Supply 5 W, 600mA VDC Power Supply 0 W,. A VDC Power Supply 50 W,. A VDC Power Supply 00 W, 4. A ph/orp Wet-Tap, / in. NPT ph/orp Wet-Tap, in. NPT ph/orp Wet-Tap, ISO 7/-R Wet-Tap Assembly, ISO 7/-R -76-WT Twist-Lock ph Electrode (use with 79 Wet-Tap) -77-WT Twist-Lock ORP Electrode (use with 79 Wet-Tap) PP Clamp-on Saddle,.5 in. x / in. (ASTM, NPT) PP Clamp-on Saddle, in. x / in. (ASTM, NPT PP Clamp-on Saddle, 4 in. x / in. (ASTM, NPT) PP Clamp-on Saddle, 6 in. x in. (ASTM, NPT) PP Clamp-on Saddle, 8 in. x in. (ASTM, NPT) PP Clamp-on Saddle, 0 in. x in. (ASTM, NPT) PP Clamp-on Saddle, in. x in. (ASTM, NPT) SIGNET Signet Scientific Company, 40 Aerojet Avenue, El Monte, CA U.S.A. Tel. (66) Fax (66) For Worldwide Sales and Service, visit our website: Or call (in the U.S.): (800) GEORGE FISCHER Piping Systems /(D-4/0) English Signet Scientific Company 00 Printed in U.S.A. on recycled paper
Signet ph/orp Transmitter * *
Signet 8750-3 ph/orp *3-8750.090-3* 3-8750.090-3 Rev. G 0/06 English English CAUTION! Remove power to unit before wiring input and output connections. Follow instructions carefully to avoid personal injury.
More informationSignet Flow Transmitter
Signet 80- Flow *-80.090-* English -80.090- Rev. L 0/ English WARNING! Remove power to unit before wiring input and output connections. Follow instructions carefully to avoid personal injury. Contents.
More information+GF+ SIGNET Temperature Transmitter Instructions
GF SIGNET 80- Temperature Transmitter Instructions ENGLISH -80.090- B-/00 English CAUTION! Remove power to unit before wiring input and output connections. Follow instructions carefully to avoid personal
More informationContents 1. Installation
ENGLISH 880.090 D0/0 English CAUTION! Remove power to unit before wiring input and output connections. Follow instructions carefully to avoid personal injury. Contents. Installation. Specifications. Electrical
More informationCAUTION! Remove power to unit before wiring input and output connections. Follow instructions carefully to avoid personal injury.
SIGNET 8850 Conductivity/Resistivity Transmitter ENGLISH 8850.090 C/0 English CAUTION! Remove power to unit before wiring input and output connections. Follow instructions carefully to avoid personal injury.
More informationSignet Conductivity/Resistivity Transmitter
Signet 88503 Conductivity/Resistivity Transmitter English *38850.0903* 38850.0903 Rev. G 3/06 English CAUTION! Remove power to unit before wiring input and output connections. Follow instructions carefully
More informationSignet Conductivity/Resistivity Transmitter
Signet 8803 Conductivity/Resistivity Transmitter English *3880.0903* 3880.0903 Rev. K 11/1 English CAUTION! Remove power to unit before wiring input and output connections. Follow instructions carefully
More informationSIGNET 8860 Dual Channel Conductivity/Resistivity Controller
OUTPUT OPTION RELAY 3,4 OPEN COLL 3,4 SHLD ISO GND TEMP 1 SGNL 1 SHLD ISO GND TEMP 2 SGNL 2 - OPEN COLL 4 L N 3-8860.090 C 4/03 English CAUTION! Remove power to unit before wiring input and output connections.
More informationConductivity/Resistivity Transmitter
88502 Conductivity/Resistivity Transmitter English *38850.0902* 38850.0902 Rev.H 8/06 English CAUTION! Remove power to unit before wiring input and output connections. Follow instructions carefully to
More informationDial-type digital bar graph. LEDs for Open Collector, Relays and Warning Indicator
Specifications General Input Channels One Input Types Digital (S 3 L) Serial ASCII, TTL level, 9600 bps Frequency Range 0.5 to 1500 Hz Accuracy 0.5% of reading Measurement Types Flow, ph/orp, Conductivity/Resis
More informationSignet 9900 Transmitter
Signet 9900 Transmitter Member of the SmartPro Family of Instruments Features Panel Mount Field Mount Multi-Parameter input selection Large auto-sensing backlit display with at a glance visibility Dial-type
More informationSignet 9900 Transmitter
Signet 9900 Transmitter Member of the SmartPro Family of Instruments Features Panel Mount Field Mount Multi-Parameter input selection Large auto-sensing backlit display with at a glance visibility Dial-type
More informationSignet 2751 DryLoc ph/orp Smart Sensor Electronics
Signet 2751 DryLoc ph/ Smart Sensor Electronics Features Probe health monitoring, glass impedance and broken glass detection Memory chip interface that allows for transferable calibration, runtime data,
More informationSignet 9950 Dual Channel Transmitter
Signet 9950 Dual Channel Transmitter Member of the SmartPro Family of Instruments Features One instrument for multiple sensor types Multiple language support for (Gen 2a) or later in Simplified Chinese,
More informationSignet 9950 Dual Channel Transmitter
Signet 9950 Dual Channel Transmitter Member of the SmartPro Family of Instruments Features One instrument for multiple sensor types Multiple language support for Simplified Chinese, English, French, German
More informationSignet 2750 DryLoc ph/orp Sensor Electronics
Signet 2750 DryLoc ph/ Sensor Electronics Features In-line integral mount and submersible installation versions Automatic temperature compensation Auto configuration for ph or operation In-line 2750 Submersible
More informationSignet 9900 Transmitter
Signet 9900 Transmitter Member of the SmartPro Family of Instruments Features Multiple sensor types supported with one instrument Dial-type digital bar graph Modules are field installable and replaceable
More informationSignet ph/orp Electrodes General Purpose
Signet 2724-2726 ph/orp Electrodes General Purpose Compatible with ALL Signet ph/orp instruments and SmartPro transmitters Features Patented reference design for exceptional performance and prolonged life
More informationCX105 Conductivity/Resistivity Transmitter
CX105 Conductivity/Resistivity Transmitter User Manual REV A.15 Sensorex Corporation, USA 11751 Markon Drive Garden Grove, CA. 92841 U.S.A. www.sensorex.com IMPORTANT SAFETY INFORMATION Please read and
More informationSignet ph/orp Electrodes
Signet 2724-2726 ph/orp Electrodes Compatible with ALL Signet ph/orp Instruments Features Flat Protected Bulb Patented reference design for exceptional performance* Mounts in Signet standard fittings from
More informationSignet 8900 Multi-Parameter Controller
Signet 8900 Multi-Parameter Controller Member of the ProcessPro Family of Instruments Features Measures Flow, ph, ORP, Conductivity, Pressure, Level and Temperature Multi-language display ¼ DIN enclosure
More information8900 Multi-Parameter Controller
F L O W + GF + XX DN XX X XX SE N S OR IN PU TS COM M PO RT / O U T O UT RE LA Y 2 RE LA Y 1 RE LA Y RE LA Y S I G N E T L o o p 1 L o o p 2 D a t a 6 1 2 7 8 9 N / C S I G N E T - 2 0 m A I n p u t -808-2
More informationSignet 9900 Transmitter
Signet 9900 Transmitter Member of the SmartPro Family of Instruments Features Panel Mount Field Mount Multi-Parameter input selection Large auto-sensing backlit display with at a glance visibility Dial-type
More informationSignet 9900 Transmitter
Signet 9900 Transmitter Member of the SmartPro Family of Instruments Features Field Mount Multi-Parameter input selection Large auto-sensing backlit display with at a glance visibility Dial-type digital
More informationSignet 9900 Transmitter
Signet 9900 Transmitter Member of the SmartPro Family of Instruments Features Panel Mount Field Mount NEW! Modbus Module supports RS485 Serial Modbus Communications Multiple sensor types supported with
More informationSignet 9900 Transmitter
Signet 9900 Transmitter *3-9900.090* 3-9900.090 Rev. C 08/13 Operating Instructions English Quick Start Look for the Quick Start icon to quickly set up your new 9900. Your new Signet 9900 Transmitter needs
More informationph or ORP Transmitter
ph or ORP Transmitter Programmable outputs: two transistor and single or dual analog 4-20 ma (Process + Temp) Removable backlighted display Universal process connection Compatible with 120 mm ph/ ORP probes
More informationDigital conductivity transmitter
Digital conductivity transmitter Compact version with integrated conductivity electrodes Remote version with seperated transmitter for short (15 ft.) or long (1500 ft.) distance Commissioning is easy due
More informationSignet 2610 Process Optical Dissolved Oxygen Sensor
Signet 2610 Process Optical Dissolved Oxygen Sensor *3-2610.090* 3-2610.090 Rev. A 04/12 English Operator's Manual Introduction System Description Your new RDO Pro is a rugged, reliable sensor designed
More informationSignet 9900 Transmitter
English Signet 9900 Transmitter *3-9900.090* 3-9900.090 Rev. E 06/14 Operating Instructions Quick Start Look for the Quick Start icon to quickly set up your new 9900. Your new Signet 9900 Transmitter needs
More informationSignet 9900 Transmitter
Signet 9900 Transmitter *3-9900.090* 3-9900.090 Rev. A2 08/11 Operating Instructions English Quick Start Your new Signet 9900 Transmitter needs to be calibrated and the sensor needs to be initialized prior
More informationDigital flow transmitter for continuous flow measurement
Digital flow transmitter for continuous flow measurement Compact or remote version for DN 06 to 400, PN10 Shows both flow rate and volume (with two totalizers) Automatic-calibration: TEACH-IN Simulation:
More informationThe transducer component converts the measured signal and displays the actual value.
Digital inductive conductivity transmitter System Integration Provides low Total Cost of Ownership PEEK/PPA version for CIP applications TEACH IN and SIMULATION Function Approval PVDF Version PEEK Version
More informationM1 Series. Humidity - Temperature Transmitter INSTRUCTION MANUAL
M1 Series Humidity - Temperature Transmitter INSTRUCTION MANUAL 20031110 -2- CONTENTS Overview... 3 Operation... 4 Power supply... 4 Operating range and limits... 4 Temperature compensation of the humidity
More informationTUpH 396RVP and 398RVP Retractable ph/orp Sensors
Instruction Sheet TUpH Sensors LIQ_MAN_ABR_396RVP-398RVP September 2013 TUpH 396RVP and 398RVP Retractable ph/orp Sensors Specifications SPECIFICATIONS 396RVP 398RVP Measurements and Ranges ph: 0-14; ORP:
More informationType PLC Fitting. Valve for Continuous control. Diaphragm valve. Output
Digital Inductive conductivity transmitter Optimal solution for conductivity measurements in difficult fluids (polluted, dirty,...) PEEK/PPA version for CIP applications Large range of process connections
More informationRoline L1 Series. Humidity - Temperature Transmitters INSTRUCTION MANUAL
Roline L1 Series Humidity - Temperature Transmitters INSTRUCTION MANUAL 20030314 CONTENTS Overview... 3 Operation... 5 Power supply... 5 Operating range and limits... 5 Temperature compensation of the
More informationUltrasonic level transmitter, non-contact
Ultrasonic level transmitter, non-contact Type 8175 can be combined with... Compact, remote versions for level measurement up to 10 m Multi language menu control Interference echo filter Automatic calibration:
More informationDigital inductive conductivity transmitter
Digital inductive conductivity transmitter Optimal solution for conductivity measurements in difficult fluids (polluted, dirty,...) PEEK/PPA version for CIP applications Large range of process connections
More information* * Signet 2610 Process Optical Dissolved Oxygen Sensor. Operator's Manual. Introduction. English. System Description.
Signet 2610 Process Optical Dissolved Oxygen Sensor *32610.090* 32610.090 Rev. C 08/13 English Operator's Manual Introduction System Description Your new RDO Pro is a rugged, reliable sensor designed to
More informationRemote Controlled FOUNDATION Fieldbus Two-Wire ph/orp Transmitter
Model 4081 ph/orp Product Data Sheet PDS 71-4081P February 2000 Remote Controlled FOUNDATION Fieldbus Two-Wire ph/orp Transmitter REMOTE COMMUNICATION IS SIMPLE; use the hand-held infrared remote controller,
More informationDigital flow ELEMENT transmitter for continuous flow measurement
ELEMENT Transmitter Digital flow ELEMENT transmitter for continuous flow measurement Type can be combined with... PN10, DN15 to DN400 fluidic process connection Programmable outputs : one or two transistor
More informationValve Island with Electronic I/O
Screw in Temperature /Switch with display for ON/OFF Control Indication, monitoring, transmission and ON/OFF control in one device Extra large display Menu guided parametrisation Complete communication
More informationModel Sono-Trak Transit Time
Model Sono-Trak Transit Time Ultrasonic Flow Meter Engineered for performance excellence, the Sono-Trak Transit Time ultrasonic meter combines non-invasive, bi-directional measurement with advanced ultrasonic
More informationGE Sensing. Introduction. Wiring Diagrams (Typical) Field Calibration. Installing the Sensor
clear mode enter clear mode enter GE Sensing Introduction The GE Telaire Vaporstat 900 sensor measures in applications in the range of 0 to 0 F dew point. The sensor package is designed for wall mounting.
More informationIDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODEL: MODEL: Multimeter Service Information
IDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODEL: 61-340 MODEL: 61-342 Multimeter Service Information The Service Information provides the following information: Precautions and safety information Specifications
More informationElectromagnetic Flow Transmitter
Electromagnetic Flow Transmitter Sensor in solid state technology Working as a transmitter and/or as an On/Off controller Automatic-calibration of full scale: Teach-In Clean in place (CIP) Type can be
More informationTroubleshooting Guide for Aquatrac Smart AS and Flex
Troubleshooting Guide for Aquatrac Smart AS and Flex Part 1 Sensors and Analog Signals Alpha Release July 28 th, 2000 Alpha Release Page 1 of 21 Preface Welcome to the Aquatrac troubleshooting guide. This
More informationCL900. True RMS 1000V 2000A 60MΩ ENGLISH. INSTRUCTION MANUAL 2000A Digital Clamp Meter. Measurement Technology
ENGLISH INSTRUCTION MANUAL 2000A Digital Clamp Meter True RMS Measurement Technology NON-CONTACT VOLTAGE TESTING INRUSH CURRENT LOW IMPEDANCE DATA HOLD RANGE HOLD AUDIBLE CONTINUITY DIODE TEST CAPACITANCE
More informationMODEL: M2DYS SEN TRONIC AG
Super-mini Signal Conditioners Mini-M Series CURRENT LOOP SUPPLY Functions & Features Powers a 20 ma DC current loop Short circuit protection Applicable to smart transmitters CE marking UL approval Typical
More informationDigital flowmeter for continuous flow measurement
8025 Flowmeter INSERTION Digital flowmeter for continuous flow measurement Compact or remote version for DN06 to DN400, PN10 Displays both flow rate and volume (with two totalizers) On site calibration
More informationDigital flowmeter for continuous flow measurement
8025 Flowmeter INSERTION Digital flowmeter for continuous flow measurement Compact or remote version for DN06 to DN400, PN10 Displays both flow rate and volume (with two totalizers) On site calibration
More informationBulb ph and ORP Electrodes
Bulb ph and ORP Electrodes Type: PH200C, PH200 CS, PH222 CD, PH223 CD, PH635 CD, ORP500 C, ORP500 CS, ORP222 CD, Main Features Epoxy or glass body. Single or double junction technology. Large gel reference
More informationS8000 Series ph/orp Electrode Platform. Self Cleaning Flat Surface ph/orp Electrodes LIQUID ANALYTICAL SOLUTIONS THE NEXT GENERATION
THE NEXT GENERATION Self Cleaning Flat Surface ph/orp Electrodes Resist Coating Resist Abrasion Modular Plug and Play Configurable Enhanced ERP Reference System PPS Construction S8000 Series ph/orp Electrode
More informationDigital flow ELEMENT transmitter for continuous flow measurement
Digital flow ELEMENT transmitter for continuous flow measurement Type 8036 can be combined with... DN06 to DN65 fluidic process connection Programmable outputs : one or two transistor output(s) and single
More informationInstruction manual SMART 96-2 / WG-2 ph
Instruction manual SMART 96-2 / WG-2 ph Stand: 06.09.2015 SMART 96-2 / WG-2 ph / mv Instructions for Installation Configuration PH-mV / Temp. 0...20 ma 4...20mA 20 ma PH-mV / Temp. 0...20 ma 4...20mA 20
More informationUser s Guide DPU91 SERIES. Transmitter. Shop online at omega.com For latest product manuals:
TM User s Guide Shop online at omega.com e-mail: info@omega.com For latest product manuals: www.omegamanual.info DPU91 SERIES Transmitter TM omega.com info@omega.com U.S.A. Headquarters: Servicing North
More informationConductivity Transmitter
Conductivity Transmitter Programmable outputs: two transistor and single or dual analog 4-20 ma Removable backlighted display Universal process connection Type can be combined with... Three cell constants
More informationPROCESS & TEMPERATURE CONTROLLERS
PROCESS & TEMPERATURE CONTROLLERS NOVA PD54 Series Thermocouple, RTD, & Process Inputs High Accuracy Auto-Tuning PID Heating & Cooling Models Universal Power Supply 1-24 VAC Up to 3 Relays & 2 Analog Outputs
More informationEXPERT-LINE. KOBO-pH. Transmitter for ph-value and ORP Model APM-X
KOBO-pH Transmitter for ph-value and ORP Model APM-X measuring monitoring analysing EXPERT-LINE Measuring range: ph value: 0 to 14 ORP: -1500 to +1500 mv (0-100%) For general-purpose use with: Analogue
More informationMODEL: W2DYS SEN TRONIC AG. Mini-MW Series
MODEL: WDYS Space-saving Dual Output Signal Conditioners Mini-MW Series CURRENT LOOP SUPPLY Functions & Features Powers a 0 ma DC current loop Short circuit protection Applicable to smart transmitters
More informationSignet 9950 Dual Channel Transmitter
English Signet 9950 Dual Channel Transmitter *3-9950.090* 3-9950.090 Rev. 7 02/19 Operating Instructions (see pg. 11) Description 3-9950-1, -2 NOTE: Prior to installation, Check www.gfsignet.com for software
More informationLST400 Ultrasonic level / open channel flow transmitter
Data sheet DS/LST400 EN Rev.C LST400 Ultrasonic level / open channel flow transmitter Measurement made easy Reduced installation cost Easy access terminations Integrated echo display makes for easy troubleshooting
More informationKENCO Loop Powered Magnetostrictive Transmitter. KMD SERIES Operation and Installation Manual. Table of Contents
KENCO ENGINEERING COMPANY P.O. BOX 470426, TULSA, OK 74147-0426 PHONE: (918) 663-4406 FAX: (918) 663-4480 http://www.kenco-eng.com e-mail: info@kenco-eng.com KENCO Loop Powered Magnetostrictive Transmitter
More informationph / ORP Measurement mypro CPM 431
Technical Information TI 173C/24/ae ph / ORP Measurement mypro CPM 431 Two-wire transmitter for ph and ORP with HART communication for use in hazardous or non-hazardous areas Areas of application The analysis
More informationCOMPACT-LINE. KOBO-RP Transmitter for ORP Model ARM-Z
KOBO-RP Transmitter for ORP Model ARM-Z measuring monitoring analysing COMPACT-LINE Measuring range -1999 to +1999 mv Switchable from ORP to ph ph or mv/orp (Oxidation Reduction Potential) and temperature
More informationSEM104 SERIES. SEM104P Pt100 Temperature Transmitter. SEM104TC Thermocouple Temperature Transmitter INDEX SECTION CONTENTS PAGE NO.
INDEX SECTION CONTENTS PAGE NO. SEM104 SERIES SEM104P Pt100 Temperature Transmitter SEM104TC Thermocouple Temperature Transmitter SEM104P 1 1.0 DESCRIPTION 2 2.0 SPECIFICATION 2 3.0 INSTALLATION 24 4.0
More informationProcess displays For standard signals, temperature, resistance measurement
Features Inputs: Voltage ±10 V, ±200 V / Current ±20 ma / thermocouples J,K,T,N,Pt100,Pt1000 / resistance measurement / potentiometer Display range can be linearised Two limits output Min, Max functions
More informationDigital batch controller
INSERTION Digital batch controller Type 8025 can be combined with... Compact or remote version for DN06 to DN400, PN10 Dosing On site calibration by Teach-In Check of input/output signals Total and daily
More informationABB ph/orp analyzer and probe package
Water Technologies & Solutions fact sheet ABB ph/orp analyzer and probe package Series AX466 dual input analyzer description and use AX466 analyzers incorporate the latest technology to provide highly
More informationAC/DC Clamp Meter. Owner's Manual. Model No Safety Operation Maintenance Español
Owner's Manual AC/DC Clamp Meter Model No. 82369 CAUTION: Read, understand and follow Safety Rules and Operating Instructions in this manual before using this product. Safety Operation Maintenance Español
More informationModel 50 Ground Loop ph Sensor Model 55 Solution Ground ph Sensor
Model 50 Ground Loop ph Sensor Model 55 Solution Ground ph Sensor Features Patented Plunger 1 ph Electrode Design Patented Porous 2 Teflon Liquid Junctions Double Junction Reference Cell Integral Differential
More informationAdvanced Ladder Logic Full IEC Languages 25A for <1 24 VDC DC Switched
EXL6 OCS Datasheet for HE- EXL1E0, HE- EXL1E2, HE- EXL1E3, HE- EXL1E4, HE- EXL1E5, HE- EXL1E6 HEXT371C100, HEXT371C112, HEXT371C113, HEXT371C114, HEXT371C115, HEXT371C116 1. Specifications Required Power
More informationCOMPACT-LINE. KOBO-pH Transmitter for ph-value Model APM-Z
KOBO-pH Transmitter for ph-value Model APM-Z measuring monitoring analysing COMPACT-LINE Measuring range ph -1 to 14 Switchable from ph to ORP Display of ph value, mv/orp (Oxidation Reduction Potential)
More informationCALYS 50. Field multifunction calibrator for basic use
Field multifunction calibrator for basic use CALYS 50 field multifunction calibrator is the perfect tool for advanced process maintenance and use on test bench in all industries. Suitable for all field
More informationCALYS 100. Field precision documenting multifunction calibrator
Field precision documenting multifunction calibrator is a precision documenting multifunction calibrator within CALYS range. It is the perfect tool for advanced process maintenance and use on test bench
More informationWM1, WIND, W400, W100, W600: ORP Sensor Troubleshooting Guide (Electrode and Housing)
WM1, WIND, W400, W100, W600: ORP Sensor Troubleshooting Guide (Electrode and Housing) Table of Contents Section 1: Sensor (Electrode) Responds Slowly... 2 Section 2: Sensor Reading is Stuck on one Value...
More informationCurrent Loop Interface Module M 2025D
CONTROLS Current Loop Interface Module M 2025D Current-to-Voltage Analog Converter used with the M 2001 Series Digital Tapchanger Control and M-2948 Tap Position Sensors to provide positive tap position
More informationCALYS 75. Field documenting multifunction calibrator
Field documenting multifunction calibrator is a field documenting multifunction calibrator within CALYS range. It is the perfect tool for advanced process maintenance and use on test bench in all industries.
More informationUSER'S MANUAL DMR-6700
USER'S MANUAL Multimeter True RMS DMR-6700 CIRCUIT-TEST ELECTRONICS www.circuittest.com Introduction This meter measures AC/DC Voltage, AC/DC Current, Resistance, Capacitance, Frequency (electrical & electronic),
More informationMagnetostrictive Level Transmitter
Magnetostrictive Level Transmitter Magnetostrictive Level Transmitter Overview Söm-Tek TM The SKMT liquid level transmitter satisfies the demand for an analog communication interface for sightglass (bypass
More information1000TR. Instructions
1000TR ph Instructions CONTENTS 1. INTRODUCTION... 2 1.1 COMMON INTRODUCTION... 2 1.2 PARTS & ACCESSORIES... 2 2. INSTALLATION... 3 2.1 CASING... 3 2.2 MOUNTING... 3 2.3 ELECTRICAL INSTALLATION... 3 2.3.1
More informationCOMPACT-LINE. Transmitter for ph-value
Transmitter for ph-value measuring monitoring analysing COMPACT-LINE Measuring range ph -1 to 14 Switchable from ph to ORP Display of ph value, mv/orp (Oxidation Reduction Potential) and temperature Simple
More informationA new approach to static electricity countermeasures
Advanced intelligent Sensors NEW ELECTROSTATIC SENSOR EF-SSERIES A new approach to static electricity countermeasures Measurement of surface potentials while a production line is running Phone: 8.894.42
More informationMM V 10A ENGLISH. INSTRUCTION MANUAL Auto-Ranging DATA HOLD AUDIBLE CONTINUITY MIN / MAX TEMPERATURE DIODE TEST CAPACITANCE
INSTRUCTION MANUAL Auto-Ranging Digital Multimeter MM400 DATA HOLD AUDIBLE CONTINUITY MIN / MAX TEMPERATURE DIODE TEST CAPACITANCE 600V 10A 40MΩ 2 GENERAL SPECIFICATIONS Klein Tools MM400 is an auto-ranging
More informationTECHNICAL DATA ELECTRO CHEMISTRY DIFFERENTIAL PH AND ORP. phd sc Digital Diferrential PH and ORP Sensors
TECHNICAL DATA ELECTRO CHEMISTRY phd sc Digital Diferrential PH and ORP Sensors ELECTRO CHEMISTRY Ordering Information phd sc Digital Differential ph/orp Sensors All digital sensors include built-in digital
More informationSeries 10-ZSE30A(F)/10-ISE30A
Series 10-ZSEA(F)/10-ISEA RoHS 2-Color Display High-Precision Digital Pressure Switch Clean series For positive For vacuum/ compound Rated range ISEA 0.1 to 1 MPa How to Order 10 ISEA 01 N M 01 N01 C4H
More informationEndress Hauser. SmarTec M CLD 133 Conductivity Measurement
Technical Information / Operating Instructions TI 281C/07/en/08.02 No. 51506567 SmarTec M Conductivity Measurement Compact conductivity transmitter with inductive sensor and integrated temperature compensation
More informationOPTISENS PH 8390 Technical Datasheet
OPTISENS PH 8390 Technical Datasheet ph sensor for water and wastewater industry Large PTFE diaphragm and integrated Pt100 Robust sensor design for harsh applications Low maintenance costs and a long life
More informationCALYS 150. Advanced documenting multifunction calibrator thermometer
Advanced documenting multifunction calibrator thermometer, most advanced documenting multifunction instrument of the range, works not only as a simulator (IN / OUT) but also as a dual channel thermometer
More informationFST Series HUMIDITY-TEMPERATURE TRANSMITTERS INSTRUCTION MANUAL
FST Series HUMIDITY-TEMPERATURE TRANSMITTERS INSTRUCTION MANUAL 20020628 CONTENTS DESCRIPTION... 3 OPERATION... 4 Power Supply...4 Output Range...4 Temperature Operating Range and Temperature Limits...4
More informationBATCHMATE 1500 Batch Control Computer Technical Bulletin
TS-5(C) BATCHMATE 5 Batch Control Computer Technical Bulletin DESCRIPTION The BATCHMATE features an 8 digit.55-in. alphanumeric LED display. The pulse input model will accept up to 2, pulses per second
More informationTwo-Wire Programmable Transmitter for:
TM Smart Process Instrumentation Revision 2 Two-Wire Programmable Transmitter for: Industrial Thermocouple or RTD Temperature Measurements Highlights: Exceptional speed and accuracy Guaranteed measurement
More informationET-3888 True RMS Clamp Meter. User Manual
ET-3888 True RMS Clamp Meter User Manual Index Introduction... 3 Safety Notes... 4 Features... 5 Specifications... 6-8 Instrument Layout... 9 Measurement... 10 Maintenance... 11 Page 2 1. Introduction
More informationSITRANS F flowmeters SITRANS F US. Transmitter FUS060. Overview
Overview Function Displays and keypad Operation of the SITRANS FUS060 transmitter can be carried out using: Keypad and display unit HART communicator PC/laptop and SIMATIC PDM software via HART communication
More informationHBPH-MK2 Brine/NH3 Leakage Sensor
INSTRUCTION MANUAL HBPH-MK2 Brine/NH3 Leakage Sensor DIFFERENTIAL 2-WIRE (4-20 ma) ph Sensor TABLE OF CONTENTS General Information... 2 Specifications... 2 Installation... 3 Cold Liquid applications...
More informationKey Number I II III IV V _ - - _ - - _ - _, _,
Issue 7 Page 1 of 8 Series 7773 Electrode Mounting Model Selection Guide Instructions Select the desired key number. The arrow to the right marks the selection available. Make one selection per table,
More informationCorporate Profile. needs and product demands. CON 08X /03 Rev 0
Corporate Profile A leader in the field of electrochemical instrumentation, Eutech Instruments is a dynamic company rapidly positioning itself globally as a leading manufacturer of electrochemical instrumentation
More informationMODEL: M2SES SEN TRONIC AG [3] OUTPUT
Super-mini Signal Conditioners Mini-M Series HIGH/LOW SELECTOR Functions & Features Monitors two DC input signals and transmits an output signal proportional to the higher or lower input CE marking UL
More informationCurrent Loop Interface Module M-2025C
CONTROLS Interface Module M-2025C Current-to-Voltage Analog Converter used with the M-2001 Series Digital Tapchanger Control and M-2948/M-2949 Tap Position Sensors to provide positive tap position knowledge
More information