TEC226x-3 and TEC220x-3 Series LONWORKS Network Staged Thermostats

Size: px
Start display at page:

Download "TEC226x-3 and TEC220x-3 Series LONWORKS Network Staged Thermostats"

Transcription

1 TEC226x-3 and TEC220x-3 Series LONWORKS Network Staged Thermostats Technical Bulletin Code No. LIT Issued September 8, 2006 Network Variables (NVs) and Configuration Parameters (CPs) List Network Variable Inputs (NVIs) Table Network Variable Outputs (NVOs) Table Configuration Properties (CPs) Commanding Thermostats Remotely Understanding LONWORKS Network Configuration Tools Differences Changing the Thermostat s Settings Using a LONWORKS Network Configuration Tool Service Pin Adding a Thermostat to the Network Automation Engine (NAE) LONWORKS Thermostat Mapping Preparation Space Comfort Controller Object Using Status/Command Screens ncigenopts Thermostat Command Table Maximum Heating Setpoint Table Minimum Cooling Setpoint Table Calibration Room Sensor and Calibration Outdoor Air Sensor Table Keypad Lockout Levels Table Heating Lockout Table Cooling Lockout Table ncimultiopts Roof Top Unit Thermostat Command Table Change Over Setpoint Table Mixed Air Setpoint Table ncimultiopts Heat Pump Thermostat Command Table High Balance Point Table TEC226x-3 and TEC220x-3 Series LONWORKS Network Staged Thermostats Technical Bulletin 1

2 Low Balance Point Table Schedules Time and Date Table Commanding a Schedule Schedule Table Commanding nvispacetemp for Testing and Override Purposes MCL Tool Instructions Lonwatcher Instructions Troubleshooting Guide Technical Specifications TEC226x-3 and TEC220x-3 Series LonWorks Network Staged Thermostats TEC226x-3 and TEC220x-3 Series LONWORKS Network Staged Thermostats Technical Bulletin

3 TEC226x-3 and TEC220x-3 Series LONWORKS Network Staged Thermostats Technical Bulletin Network Variables (NVs) and Configuration Parameters (CPs) List Table 1 shows the NVs and CPs for the TEC226x-3 and TEC220x-3 Series thermostats. Each Network Variable Input (NVI), Network Variable Output (NVO), and Network Configuration Input (NCI) has a reference number, and some objects have a subcategory number. The Sub column lists the thermostat s Enumeration (Enum) options for each NV or CP. The Byte column shows the byte number for each of the entry fields in the ncigenopts and ncimultiopts Status/ Command screens. Table 1: NVs and CPs per Model (Part 1 of 4) No Sub Byte Point Name Model TEC Econ, Prog. TEC Econ, NonProg. TEC Multi-Stage, Prog. TEC Multi-Stage, NonProg. TEC Single Stage, Prog. TEC Single Stage, NonProg. TEC Heat Pump, Prog. TEC Heat Pump, NonProg. 0 nvispacetemp x x x x x x x x 1 nvioutdoortemp x x x x x x x x 2 nvioccmancmd x x x x x x x x 3 nviapplicmode x x x x x x x x 4 nvisetpoint x x x x x x x x 5 nvitimeset x N/A X N/A X N/A X N/A 6 ncidaysched[0] X N/A X N/A X N/A X N/A 7 ncidaysched[1] X N/A X N/A X N/A X N/A 8 ncidaysched[2] X N/A X N/A X N/A X N/A 9 ncidaysched[3] X N/A X N/A X N/A X N/A 10 ncidaysched[4] X N/A X N/A X N/A X N/A 11 ncidaysched[5] X N/A X N/A X N/A X N/A 12 ncidaysched[6] X N/A X N/A X N/A X N/A 13 ncisetpts X X X X X X X X 1 0 occupied_cool x x x x x x x x 3 2 unoccupied_cool x x x x x x x x 4 3 occupied_heat x x x x x x x x 6 5 unoccupied_heat x x x x x x x x 14 ncigenopt X X X X X X X X 1 0 Temperature Units x x x x x x x x TEC226x-3 and TEC220x-3 Series LONWORKS Network Staged Thermostats Technical Bulletin 3

4 Table 1: NVs and CPs per Model (Part 2 of 4) No Sub Byte Point Name Model TEC Econ, Prog. TEC Econ, NonProg. TEC Multi-Stage, Prog. TEC Multi-Stage, NonProg. TEC Single Stage, Prog. TEC Single Stage, NonProg. TEC Heat Pump, Prog. TEC Heat Pump, NonProg. 2 1 DI1 Configuration x x x x x x x x 3 2 DI2 Configuration x x x x x x x x 4 3 Power-Up Delay x x x x x x x x 5 4 Frost Protection x x x x x x x x 6 5 Heat Maximum setpoint x x x x x x x x 7 6 Cool Minimum setpoint x x x x x x x x 8 7 Anticycle x x x x x x x x 9 8 Heating Stages Cycles Per x x x x x x x x Hour 10 9 Cooling Stages Cycles Per x x x x x x x x Hour Deadband x x x x x x x x Fan Control x x x x x x x x Fan Delay x x x x x x x x Tempory Occ Time x x x x x x x x Calibration Room Sensor x x x x x x x x Calibration Outdoor Sensor x x x x x x x x Outside Air Heating Lockout x x x x x x x x Outside Air Cooling Lockout x x x x x x x x Number of Events x N/A x N/A x N/A x N/A Auxiliary Contact x x x x x x x x Configuration Progressive recovery x N/A x N/A x N/A x N/A Keypad Lockout Levels x x x x x x x x 15 ncimultiopt X X X X N/A N/A X X 1 0 Reversing Valve N/A N/A N/A N/A N/A N/A x x Configuration 2 1 Heating Stages x x x x N/A N/A N/A N/A 3 2 Cooling or Heat Pump Stages x x x x N/A N/A x x 4 3 Economizer Minimum x x N/A N/A N/A N/A N/A N/A Damper Position 5 4 Economizer Changeover x x N/A N/A N/A N/A N/A N/A Setpoint 6 5 High Balance Setpoint N/A N/A N/A N/A N/A N/A x x 7 6 Mechanical Cooling Enable x x N/A N/A N/A N/A N/A N/A 8 7 Comfort / Economy Mode N/A N/A N/A N/A N/A N/A x x 4 TEC226x-3 and TEC220x-3 Series LONWORKS Network Staged Thermostats Technical Bulletin

5 Table 1: NVs and CPs per Model (Part 3 of 4) No Sub Byte Point Name Model TEC Econ, Prog. TEC Econ, NonProg. TEC Multi-Stage, Prog. TEC Multi-Stage, NonProg. TEC Single Stage, Prog. TEC Single Stage, NonProg. TEC Heat Pump, Prog. TEC Heat Pump, NonProg. 9 8 Mixed Air Setpoint x x N/A N/A N/A N/A N/A N/A 10 9 Low Balance Setpoint N/A N/A N/A N/A N/A N/A x x Auxiliary Compressor Interlock N/A N/A N/A N/A N/A N/A x x 16 ncihvactype X X X X X X X X 17 ncisccmodel X X X X X X X X 1 Thermostat Model x x x x x x x x 2 Software Version x x x x x x x x 18 nvospacetemp X X X X X X X X 19 nvounitstatus X X X X X X X X 1 mode x x x x x x x x 2 heat_output_primary x x x x x x x x 3 heat_output_secondary N/A N/A N/A N/A N/A N/A x x 4 cool_output x x x x x x x x 5 econo_output x x N/A N/A N/A N/A N/A N/A 6 Fan_output x x x x x x x x 7 in_alarm x x x x x x x x 20 nvooutdoortemp X X X X X X X X 21 nvodischairtemp X X N/A N/A N/A N/A N/A N/A 22 nvoeffectoccup X X X X X X X X 23 nvosccstatus X X X X X X X X 2 Fan x x x x x x x x 3 Cooling Stage 1 x x x x x x x x 4 Cooling Stage 2 x x x x N/A N/A x x 5 Auxiliary Contact x x x x x x x x 6 Heating Stage 1 x x x x x x x x 7 Heating Stage 2 / O/B x x x x N/A N/A x x reversing valve 9 Service Alarm x x x x x x x x 10 Filter Alarm x x x x x x x x 13 DI2 Status x x x x x x x x 14 DI1 Status x x x x x x x x 16 Set Clock Alarm x N/A x N/A x N/A x N/A 17 Frost Protection Alarm x x x x x x x x 24 nvoeffectsetpt X X X X X X X X TEC226x-3 and TEC220x-3 Series LONWORKS Network Staged Thermostats Technical Bulletin 5

6 Table 1: NVs and CPs per Model (Part 4 of 4) No Sub Byte Point Name Model TEC Econ, Prog. TEC Econ, NonProg. TEC Multi-Stage, Prog. TEC Multi-Stage, NonProg. TEC Single Stage, Prog. TEC Single Stage, NonProg. TEC Heat Pump, Prog. TEC Heat Pump, NonProg. 25 nvosetpoint X X X X X X X X 26 ncisndhrtbt X X X X X X X X 27 nciminouttm X X X X X X X X 28 ncircvhrtbt X X X X X X X X 29 ncimajver X X X X X X X X 30 nciminver X X X X X X X X 31 ncilocation x x x x x x x x 6 TEC226x-3 and TEC220x-3 Series LONWORKS Network Staged Thermostats Technical Bulletin

7 Network Variable Inputs (NVIs) Table Table 2: NVIs (Part 1 of 2) Parameter NVI Name and SNVT Type Room Temperature Outdoor Air Temperature Occupancy System Mode nvispacetemp SNVT_temp_p nvioutdoortemp SNVT_temp_p nvioccmancmd SNVT_occupancy nviapplicmode SNVT_hvac_mode Range and Enumeration Definition Valid Range: -40 to 122 F (-40 to 50.0 C) Default Null (release) Value: F ( C) 0x7FFF represents invalid data. Note: This NVI allows the temperature setpoint for the occupied mode to be changed via the network. When bound or written to, the internal temperature reading (internal sensor) is no longer used. To change the thermostat back to using its internal sensor, break the bind for bound stats, or for commanded stats, issue a reset to the thermostat. This NVI is subject to the Receive Heartbeat Time, ncircvhrtbt. Valid Range: -40 to 122 F (-40 to 50.0 C) Default Null (release) Value: F ( C) 0x7FFF represents invalid data Note: This NVI provides outdoor air temperature information to the thermostat from a bound network temperature value or when an outside air sensor is connected to the OS and Scom terminals. Once bound, or when the outside air sensor is connected, the thermostat automatically displays the value. 0 = OC_OCCUPIED 1 = OC_UNOCCUPIED 2 = OC_BYPASS 3 = OC_STANDBY (Not used) 0XFF = OC_NUL (Release to internal schedule) Note: This NVI commands the Space Comfort Controller into different occupancy modes. It is typically sent by a supervisory node to manually control occupancy modes, or to override the scheduled occupancy. Default Null Value: OC_NUL = 0xFF 0 = HVAC_AUTO (Default) 1 = HVAC_HEAT 2 = HVAC_MRNG_WRMUP (Not used) 3 = HVAC_COOL 4 = HVAC_NIGHT_PURGE (Not used) 5 = HVAC_PRE_COOL (Not used) 6 = HVAC_OFF 7 = HVAC_TEST (Not used) 8 = HVAC_EMERG_HEAT (Not used) 9 = HVAC_FAN_ONLY (Not used) 10 = HVAC_FREE_COOL (Not used) 11 = HVAC_ICE (Not used) 12 = HVAC_MAX_HEAT (Not used) 13 = HVAC_ECONOMY (Not used) 14 = HVAC_DEHUMID (Not used) 15 = HVAC_CALIBRATE (Not used) 16 = HVAC_EMERG_COOL (Not used) 17 = HVAC_EMERG_STEAM (Not used) 0XFF = HVAC_NUL (Not used) Note: This NVI coordinates the Space Comfort Controller with any node that may need to control the heat/cool changeover of the unit. This NVI is subject to the Receive Heartbeat Time, ncircvhrtbt. TEC226x-3 and TEC220x-3 Series LONWORKS Network Staged Thermostats Technical Bulletin 7

8 Table 2: NVIs (Part 2 of 2) Parameter NVI Name and SNVT Type Occupied Cooling and Heating Setpoints Date and Time nvisetpoint SNVT_temp_p nvitimeset SNVT_time_stamp Range and Enumeration Definition Occupied Cooling - Valid Range: 54 to 100 F (12 to 37.5 C) Occupied Heating - Valid Range: 40 to 90 F (4.5 to 32 C) Standby Cool Setpoint (Not used) Standby Heat Setpoint (Not used) Default Null (release) Value: F ( C) 0x7FFF represents invalid data Note: This NVI allows the temperature setpoints for the occupied mode to be changed via the network. The unoccupied setpoints are not changed. Note: If one setpoint of a pair of heating and cooling setpoints (for example, Occupied Heat Setpoint and Occupied Cool Setpoint) is overridden, the other setpoint of the pair may be automatically adjusted by the thermostat to maintain the minimum deadband between the two setpoints. Sub Name Valid Range Default Value 1 year 0 to month 0 to day 0 to hour 0 to minute 0 to second 0 to 59 0 Note: This NVI is used to set the time and date of the Space Comfort Controller. TEC226x-3 models only. 8 TEC226x-3 and TEC220x-3 Series LONWORKS Network Staged Thermostats Technical Bulletin

9 Network Variable Outputs (NVOs) Table All NVOs are updated no faster than the Minimum Send Time (nciminouttm) configuration value, if used. An NVO transmits immediately when its value changes significantly. Additionally, this variable is also transmitted as a heartbeat output on a regular basis as dictated by the Maximum Send Time (ncisndhrtbt) configuration value. Table 3: NVOs (Part 1 of 4) Parameter Room Temperature Unit Status Outdoor Temperature NVO Name and SNVT Type nvospacetemp SNVT_temp_p nvounitstatus SNVT_hvac_status nvooutdoortemp SNVT_temp_p Range and Enumeration Definition Valid Range: -40 to 122 F (-40 to 50 C) Default Null (release) Value: F ( C) 0x7FFF represents invalid data. Note: This NVO monitors the effective space temperature sensor that the Space Comfort Controller is using for control. This output echos the value of the input. In the event of a sensor failure, the value F ( C or 0x7FFF) is sent as an invalid value. Sub Name Valid Value 1 mode HVAC_HEAT HVAC_MRNG_WRMUP (Not used) HVAC_COOL HVAC_NIGHT_PURGE (Not used) HVAC_PRE_COOL (Not used) HVAC_HVAC_OFF HVAC_HVAC_TEST (Not used) HVAC_HVAC_EMERG_HEAT (Not used) HVAC_FAN_ONLY (Not used) HVAC_MAX_HEAT (Not used) 2 heat_output_primary 0 to 100% 3 heat_output_secondary 0 to 100% 4 cool_output 0 to 100% 5 econ_output 0 to 100% 6 fan_output 0 to 100% 7 In_alarm 0 = No alarms 1 = Alarm On 0xFFF = Alarm disabled (Not used) Note: This NVO reports the Space Comfort Controller status. It combines the Operating mode, the capacity of heating and cooling used, and an indicates if any alarms are present in the object. Valid Range: -40 to 122 F (-40 to 50 C) Default Null (release) Value: F ( C) 0x7FFF represents invalid data Note: This NVO is used to monitor the outdoor air temperature. In the event of a sensor failure, the value F ( C or 0x7FFF) is sent as an invalid value. Note: For this to function, an outside air sensor must be connected to the OS and Scom terminals. TEC226x-3 and TEC220x-3 Series LONWORKS Network Staged Thermostats Technical Bulletin 9

10 Table 3: NVOs (Part 2 of 4) Parameter NVO Name and SNVT Type Supply Temperature Occupancy nvodischairtemp SNVT_temp_p nvoeffectoccup SNVT_occupancy Range and Enumeration Definition Valid Range: -40 to 122 F (-40 to 50 C) Default Null (release) Value: F ( C) 0x7FFF represents invalid data Note: This NVO is used to monitor the temperature of the air that leaves the Space Comfort Controller. In the event of a sensor failure, the value F ( C or 0x7FFF) is sent as an invalid value. Note: For this to function, a supply air sensor must be connected to the MS and Scom terminals. 0 = OC_OCCUPIED 1 = OC_UNOCCUPIED 2 = OC_BYPASS 3 = OC_STANDBY (Not used) 0XFF = OC_NUL (Release to internal schedule) Note: OC_BYPASS can be initiated by either OccManCmd or a local input. NvoEffectOccup is only in OC_BYPASS for the duration of the ToccTime (ncigenopts), until reinitiated by either a transition of the local input or an update to nvioccmancmd. This NVO indicates the actual occupancy mode of the unit. The information is typically reported to a supervisory controller or provided to another Space Comfort Controller to coordinate operation of multiple units. Default Null Value: OC_NUL = 0xFF 10 TEC226x-3 and TEC220x-3 Series LONWORKS Network Staged Thermostats Technical Bulletin

11 Table 3: NVOs (Part 3 of 4) Parameter NVO Name and SNVT Type Thermostat s I/O Status Setpoint nvosccstatus UNVT_thermo_state nvoeffectsetpt SNVT_temp_p Range and Enumeration Definition Sub Name Valid Value Default Value 1 Reserved 1 Not Used N/A 2 Fan 0 = Off N/A 1 = On 3 Cooling Stage 1 0 = Off N/A 1 = On 4 Cooling Stage 2 0 = Off N/A 1 = On 5 Auxiliary Contact 0 = Off N/A 1 = On 6 Heating Stage 1 0 = Off 1 = On N/A 7 Heating Stage 2 / O/B Reversing Valve 0 = Off 1 = On N/A 8 Reserved 2 Not Used N/A 9 Service Alarm 0 = Off N/A 1 = On 10 Filter Alarm 0 = Off N/A 1 = On 11 Reserved 3 Not Used N/A 12 Reserved 4 Not Used N/A 13 DI2 Status 0 = Activated 1 = Not Activated N/A 14 DI1 Status 0 = Activated 1 = Not Activated N/A 15 Reserved 5 Not Used N/A 16 Set Clock Alarm 0 = Off N/A 1 = On 17 Frost Protection Alarm 0 = Off N/A 1 = On 18 Reserved 6 Not Used N/A 19 Reserved 7 Not Used N/A 20 Reserved 8 Not Used N/A 21 Reserved 9 Not Used N/A 22 Reserved 10 Not Used N/A Note: This NVO reports the status of the Space Comfort Controller s inputs and outputs. Valid Range: 40 to 100 F (4.5 to 37.5 C) Default Null (release) Value: F ( C) 0x7FFF represents invalid data Note: This NVO is used to monitor the effective temperature setpoint, which may depend on ncisetpoints, nvoeffectoccup, nvisetpoint, and any local setpoint adjustment. For example, if the occupancy state is unoccupied and the heat/cool state is heat, the effective setpoint would be equal to the unoccupied heating setpoint defined in ncisetpoints. TEC226x-3 and TEC220x-3 Series LONWORKS Network Staged Thermostats Technical Bulletin 11

12 Table 3: NVOs (Part 4 of 4) Parameter NVO Name and SNVT Type Local Setpoint Output nvosetpoint SNVT_temp_p Range and Enumeration Definition Valid Range: 40 to 100 F (4.5 to 37.5 C) Default Null (release) Value: F ( C) 0x7FFF represents invalid data Note: This NVO monitors the space temperature setpoint. 12 TEC226x-3 and TEC220x-3 Series LONWORKS Network Staged Thermostats Technical Bulletin

13 Configuration Properties (CPs) Table 4: CP and NCIs (Part 1 of 2) Parameter CP Name and NCI Type Function Schedule Temperature Setpoints HVAC Unit Type Identifier nciday_sched[x] x = 0 to 6 nci_day_sched ncisetpts SNVT_temp_setp ncihvac_type SNVT_hvac_type Sub Name Default Value 1 occupied_event_1 0 2 unoccupied_event_ occupied_event_3 0 4 unoccupied_event_ Valid Range: 0 to 1439 minutes 2 or 4 events can be entered, depending on the nb_of_events variable. Starting and ending times are entered in minutes. For example, 11:59 pm is equal to 1439 minutes (23 hours * 60 minutes + 59 minutes) Note: This CP defines the schedule for every day of the week (from Monday (Day 0) to Sunday (Day 6). This NCI is linked with the nvoeffectoccup variable. Sub Name Valid Range Default Value 1 occupied_cool 54 to 100 F 75 F (24 C) (12 to 37.5 C) 2 standby_cool Not Used N/A 3 unoccupied_cool 54 to 100 F 80 F (26.5 C) (12 to 37.5 C) 4 occupied_heat 40 to 90 F 72 F (22 C) (4.5 to 32 C) 5 standby_heat Not Used N/A 6 unoccupied_heat 40 to 90 F (4.5 to 32 C) 62 F (16.5 C) Note: This CP defines the space temperature setpoints for various heat, cool, and occupancy modes. The stand-by setpoints can be modified, but are not used by the controller, as it does not support Stand-By occupancy mode. Value Identifier Name 0 HVT_GENERIC Not Used 1 HVT_FAN_COIL Fan Coil Unit 2 HVT_VAV Not Used 3 HVT_HEAT_PUMP Heat Pump 4 HVT_ROOFTOP Rooftop Unit 5 HVT_UNIT_VENT Not Used 6 HVT_CHIL_CEIL Not Used 7 HVT_RADIATOR Not Used 8 HVT_AHU Not Used 9 HVT_SLF_CONT Not Used Note: This CP helps the user identify the type of equipment being monitored. TEC226x-3 and TEC220x-3 Series LONWORKS Network Staged Thermostats Technical Bulletin 13

14 Table 4: CP and NCIs (Part 2 of 2) Parameter CP Name and NCI Type Function Thermostat s Model Number Maximum Send Time Minimum Send Time Minimum Receive Time Major Hardware or Software Revisions Minor Hardware or Software Revisions Location Label ncisccmodel UNVT_model_numb er ncisendhrtbt SNVT_time_sec nciminouttm SNVT_time_sec ncircvhrtbt SNVT_time_sec ncimajver SCPT_maj_ver nciminver SCPT_min_ver ncilocation SNVT_str_asc Sub Name Valid Range Default Value 1 Thermostat Model 01 = TEC = TEC = TEC = TEC = TEC = TEC = TEC = TEC Depends on the model being used 2 Software Version N/A 0 Note: Use this CP to determine the model number and software version of the thermostat. Valid Range: 0 to 6,553.4 seconds Default Null Value: 0.0 seconds (no automatic update) Note: Setting ncisendhrtbt to 0 disables the Send Heartbeat mechanism. Note: This NV defines the maximum period of time that expires before the specified NVOs are automatically updated. Valid Range: 0 to 6,553.4 seconds Default Null Value: 0.0 seconds (no minimum send time) Note: Setting ncircvhrtbt to 0 disables the Minimum Send Time mechanism. Note: This NV defines the minimum period of time between automatic NVO transmissions. Valid Range: 0 to 6,553.4 seconds Default Null Value: 0.0 seconds (no failure detected) Note: Setting ncircvhrtbt to 0 disables the Receive Heartbeat mechanism. Note: This NV is used to control the maximum time that elapses after the last update to a specified NVI before the Space Comfort Controller starts to use its default values. Valid Range: 0 to 255 Note: This NV defines the major module hardware and software revisions. Valid Range: 0 to 255 Note: This NV defines the minor module hardware and software revisions. Valid Range: Any NULL terminated ASCII string of 31 bytes total length. Note: This CP can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chip s 6 byte location string. The location relates to the object and not to the node. This does not function in MCL Tool. 14 TEC226x-3 and TEC220x-3 Series LONWORKS Network Staged Thermostats Technical Bulletin

15 Commanding Thermostats Remotely Understanding LONWORKS Network Configuration Tools Differences LONWORKS network configuration tools use different numbering schemes in their Status/Command screens. In the ncigenopts and ncimultiopts Status/ Command screens, MCL Tool begins its first data entry location with Byte 0, whereas Lonwatcher begins with Byte 1. The byte entry location number depends on which Tool you are using. Table 5: LONWORKS Network Configuration Tool Terminology Differences LONWORKS Network Configuration Tool ncigenopts Screen ncimultiopts Screen MCL Tool Byte 0 to Byte 27 Byte 0 to Byte 9 Lonwatcher Byte 1 to Byte 28 Byte 1 to Byte 10 LonMaker Not directly changeable Not directly changeable Figure 1 shows the ncigenopts Status/Command screen in MCL Tool on the left, with the equivalent Lonwatcher screen on the right. Figure 1: MCL Tool and Lonwatcher Status/Command Screens Changing the Thermostat s Settings Using a LONWORKS Network Configuration Tool Once a thermostat is configured and online, you can use a LONWORKS network configuration tool to change its default settings. This means you do not have to go to the thermostat and manually make the changes. TEC226x-3 and TEC220x-3 Series LONWORKS Network Staged Thermostats Technical Bulletin 15

16 To change most of the thermostat s configuration properties: 1. Using a LONWORKS network configuration tool, open the the thermostat s ncigenopts Status/Command screen. Note: See Table 5 for the byte entry location numbering differences. 2. From Table 6, find the desired configuration property and enter the corresponding value into its respective byte location in the ncigenopts Status/ Command screen. Note: Some configuration properties require you to enter a range number in a specific byte location, followed by a corresponding value in the next byte location. You must enter both the range number and value before commanding the thermostat. 3. Command the thermostat. The configuration changes are implemented. 4. Enter any Heat Pump of Roof Top Unit specific configuration property changes in the ncimultiopts Status/Command screen. 5. Command the thermostat. The configuration changes are implemented. Service Pin To broadcast the thermostat s Neuron ID over the LONWORKS network: 1. Simultaneously press and hold the Up Arrow and Down Arrow for five seconds. The Status LED flashes once every five seconds to indicate the thermostat s Neuron ID is being broadcast on the LONWORKS network. 2. For manual entry, the Neuron ID is also on a label on the Echelon chip under the thermostat cover. Adding a Thermostat to the Network Automation Engine (NAE) Once a thermostat has been commissioned, it must be added to the NAE before its points can be mapped. To do this, select the LONWORKS Integration under the NAE (refresh the tree view if required to see a newly added LONWORKS Integration) and choose Field Device from the Insert menu. Assisted Definition using Auto Discovery is the easiest way to add a new thermostat online; however, this requires that the thermostat that is to be added is connected and ready to communicate. Refer to the LONWORKS Integration with NAE Technical Bulletin (LIT ) for instructions on how to add a LONWORKS device. 16 TEC226x-3 and TEC220x-3 Series LONWORKS Network Staged Thermostats Technical Bulletin

17 LONWORKS Thermostat Mapping Preparation Before mapping a TEC22xx-3 Thermostat into an NAE: 1. Decide which point objects within the thermostat need to be mapped. Only map the point objects that need to be viewed on a regular basis, since excessive mapping lowers system performance. Suggested point objects for mapping include: Room Temp, System Mode, Fan Status, Occupied Heat Setpoint, Occupied Cool Setpoint, Unoccupied Heat Setpoint, and Unoccupied Cool Setpoint. In addition, alarm points may be mapped if they are used, and other point objects may be mapped if required. Use the Engineering view to examine infrequently used point objects. 2. Verify that a LONWORKS Integration is defined in the NAE. The commissioned thermostat is mapped as a LONWORKS device under a LONWORKS Integration. Refer to the LONWORKS Integration with NAE Technical Bulletin (LIT ) for instructions on how to define a LONWORKS network Integration. At this point, the thermostat and the required point objects inside the thermostat can be mapped. TEC226x-3 and TEC220x-3 Series LONWORKS Network Staged Thermostats Technical Bulletin 17

18 Space Comfort Controller Object Figure 2: TEC22xx-3 Space Comfort Controller Object Using Status/Command Screens There are three main status/command screens used to command the TEC22xx-3 thermostats remotely: ncigenopts - contains most configuration settings for all TEC22xx-3 models ncimultiopts - Heat Pump (TEC and TEC2262-3) ncimultiopts - Roof Top Unit (TEC2203-3, TEC2263-3, TEC2204-3, and TEC2264-3) 18 TEC226x-3 and TEC220x-3 Series LONWORKS Network Staged Thermostats Technical Bulletin

19 Figure 3 shows the ncigenopts screen with the cells labeled. Figure 3: ncigenopts Status/Command Screen TEC226x-3 and TEC220x-3 Series LONWORKS Network Staged Thermostats Technical Bulletin 19

20 ncigenopts Thermostat Command Table Use the information in Table 6 to configure the thermostat remotely. Table 6: ncigenopts Thermostat Command Table (Part 1 of 3) MCL Tool Byte Number (Lonwatcher Byte Number) Stat Menu Name Description Byte and Range 0 (1) Temperature Units Fahrenheit or Celsius 1 (2) DI1 0 = None 1 = RemNSB 2 = RemOVR 3 = Filter 4 = Service 2 (3) DI2 0 = None 1 = RemNSB 2 = RemOVR 3 = Filter 4 = Service 0 = Celsius 1 = Fahrenheit (Default) 0 = None 0 = None 3 (4) Pwr del Power-Up Delay 10 = 10 seconds (Default) Range = 10 to 120, in 1 second increments 4 (5) Frost pr Frost Protection 0 = Off (Default) 1 = On Note: If Frost pr is set to On and the temperature falls below 42 F (5.6 C), the thermostat goes into emergency mode. Once in emergency mode, it remains there until commanded otherwise. 5 (6) Heat max Occupied and Unoccupied maximum Heating setpoint range number 6 (7) Heat max Occupied and Unoccupied maximum Heating setpoint value number 7 (8) Cool min Occupied and Unoccupied minimum Cooling setpoint range number 8 (9) Cool min Occupied and Unoccupied minimum Cooling setpoint value number Enter the setpoint s range number from Table 7. Enter the setpoint s value number from Table 7 Enter the setpoint s range number from Table 8. Enter the setpoint s value number from Table 8. 9 (10) Anticycl Minimum On/Off time for stages 0 = 0 minute Note: Anticycing can be set to 0 minutes if the equipment possess its own anticycling timer. Do not use this value unless the equipment is equipped with such timer! 1 = 1 minute 2 = 2 minutes (Default) 3 = 3 minutes 4 = 4 minutes 5 = 5 minutes 20 TEC226x-3 and TEC220x-3 Series LONWORKS Network Staged Thermostats Technical Bulletin

21 Table 6: ncigenopts Thermostat Command Table (Part 2 of 3) MCL Tool Byte Number (Lonwatcher Byte Number) Stat Menu Name Description Byte and Range 10 (11) Heat cph Heating Stages Cycles Per Hour 4 = 4 CPH (Default) Range = 3 to 8 CPH, in 1 CPH increments 11 (12) Cool cph Cooling Stages Cycles Per Hour 3 = 3 CPH 4 = 4 CPH (Default) 12 (13) Deadband Sets the minimum deadband between the heating and cooling setpoints. 11 = 2 F 17 = 3 F 22 = 4 F 13 (14) Fan cont Fan Control 0 = Off 1 = On (Default) 14 (15) Fan del Fan Delay 0 = Off (Default) 1 = On 15 (16) TOccTime Temporary occupancy time 3 = 3 Hours (Default) Range = 0 to 12 hours, in 1 hour increments 16 (17) Cal RS Sets the desired room air sensor calibration (offset) range. The offset can be added to or subtracted from the actual displayed room temperature. Enter the range number from Table (18) Cal RS Sets the desired room air sensor calibration (offset) value. The offset can be added to or subtracted from the actual displayed room temperature. 18 (19) Cal OS Sets the desired outdoor air sensor calibration (offset) range. The offset can be added to or subtracted from the actual displayed outside air temperature. 19 (20) Cal OS Sets the desired outdoor air sensor calibration (offset) value. The offset can be added to or subtracted from the actual displayed outside air temperature. 20 (21) H lock Outdoor air temperature mechanical heating lockout Range 21 (22) H lock Outdoor air temperature mechanical heating lockout Value 22 (23) C lock Outdoor air temperature mechanical cooling lockout Range Enter the value number from Table 9. Enter the range number from Table 9. Enter the value number from Table 9. Enter the range number from Table 11. Enter the value number from Table 11. Enter the range number from Table 12. TEC226x-3 and TEC220x-3 Series LONWORKS Network Staged Thermostats Technical Bulletin 21

22 Table 6: ncigenopts Thermostat Command Table (Part 3 of 3) MCL Tool Byte Number (Lonwatcher Byte Number) Stat Menu Name Description Byte and Range 23 (24) C lock Outdoor air temperature mechanical cooling lockout Value Enter the value number from Table (25) 2/4event Number of Events 2 = 2 Events (Default) 4 = 4 Events Note: Tec226x-3 models only. 25 (26) Aux cont Determines the auxiliary contact configuration. 0 = Normally Open 1 = Normally Closed 26 (27) Prog rec Progressive recovery enable 0 = Off (Default) 1 = On 27 (28) Lockout Keypad lockout levels 0 = No lockout 1 = Level 1 lockout 2 = Level 2 lockout Note: See Table 10 for lockout information. 22 TEC226x-3 and TEC220x-3 Series LONWORKS Network Staged Thermostats Technical Bulletin

23 Maximum Heating Setpoint Table Table 7: ncigenopts Maximum Heat Setpoint Range Adjustment Values MaxHeat Setpoint Setting Range Byte 5 (6) Value Byte 6 (7) MaxHeat Setpoint Setting Range Byte 5 (6) Value Byte 6 (7) MaxHeat Setpoint Setting Range Byte 5 (6) Value Byte 6 (7) 40 F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F 9 1 Note: Lonwatcher Range byte location numbers and Value byte location numbers shown in parenthesis. See Table 5 for more information on Bit/Byte use in each LONWORKS network configuration tool. TEC226x-3 and TEC220x-3 Series LONWORKS Network Staged Thermostats Technical Bulletin 23

24 Minimum Cooling Setpoint Table Table 8: ncigenopts Minimum Cooling Setpoint Range Adjustment Values MinCool Setpoint Setting Range Byte 7 (8) Value Byte 8 (9) MinCool Setpoint Setting Range Byte 7 (8) Value Byte 8 (9) MinCool Setpoint Setting Range Byte 7 (8) Calibration Room Sensor and Calibration Outdoor Air Sensor Table Using the information in Table 9, enter the range number and value number for the Cal RS or Cal OS in their respective byte entry boxes of the ncigenopts screen and command the thermostat. Value Byte 8 (9) 54 F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F Note: Lonwatcher Range byte location numbers and Value byte location numbers shown in parenthesis. See Table 5 for more information on Bit/Byte use in each LONWORKS network configuration tool. 24 TEC226x-3 and TEC220x-3 Series LONWORKS Network Staged Thermostats Technical Bulletin

25 Note: You must enter the range and value before commanding the thermostat. Table 9: Cal RS and Cal OS Command Settings Cal RS or Range Value Cal OS Cal RS Byte 16 (17) Cal RS Byte 17 (18) Temperature Cal OS Byte 18 (19) Cal OS Byte 19 (20) Setting 5 F F F F F F F F F F F Note: Lonwatcher Range byte location numbers and Value byte location numbers are shown in parenthesis. See Table 5 for more information on byte use in each LONWORKS network configuration tool. Keypad Lockout Levels Table Use the information in Table 10 to remotely configure the thermostat s keypad lockout levels. Keypad Lockout can be commanded either from the thermostat Installer Configuration menu or the ncigenopts Byte 27(28) cell. Table 10: Keypad Lockout Levels Table Level Menu Resume/ override schedules Resume sched Y/N 1. TEC226x-3 models only. Permanent occupied and unoccupied setpoints RoomTemp set Y/N Temporary setpoints using arrows System mode setting Sys Mode set Y/N Fan mode setting Schedules setting 1 Schedule set Y/N Clock setting 1 Clock set Y/N 0 Access Access Access Access Access Access Access 1 Access No access Access No access No access No access Access 2 No access No access No access No access No access No access Access TEC226x-3 and TEC220x-3 Series LONWORKS Network Staged Thermostats Technical Bulletin 25

26 Heating Lockout Table Table 11: ncigenopts H Lock Range Adjustment Values H Lock H Lock Setting Setting Range Byte 20 (21) Value Byte 21 (22) Range Byte 20 (21) Value Byte 21 (22) Cooling Lockout Table Table 12: ncigenopts C Lock Range Adjustment Values H Lock Setting Range Byte 20 (21) Value Byte 21 (22) -15 F F F F F F F F F F F F F F F F F F F F F F F F F F F F Note: Lonwatcher Range byte location numbers and Value byte location numbers shown in parenthesis. See Table 5 for more information on Bit/Byte use in each LONWORKS network configuration tool. C Lock Setting Range Byte 22 (23) Value Byte 23 (24) C Lock Setting Range Byte 22 (23) Value Byte 23 (24) C Lock Setting Range Byte 22 (23) -40 F F F F F F F F F F F F F F F F F F F F F F F F F F F F Note: Lonwatcher Range byte location numbers and Value byte location numbers shown in parenthesis. See Table 5 for more information on Bit/Byte use in each LONWORKS network configuration tool. Value Byte 23 (24) 26 TEC226x-3 and TEC220x-3 Series LONWORKS Network Staged Thermostats Technical Bulletin

27 ncimultiopts Roof Top Unit Thermostat Command Table Figure 4 shows the ncimultiopts screen for a Roof Top Unit with the cells labeled. Figure 4: ncimultiopts Roof Top Unit Status/Command Screens Use the information in Table 13 to configure the Roof Top Unit thermostat remotely. Table 13: ncimultiopts Roof Top Thermostat Command Table MCL Tool Byte Number (Lonwatcher Byte Number) Stat Menu Name Description Byte and Range 0 (1) H stage Heating stages 1 = 1 stage 2 = 2 stages (Default) 1 (2) C stage Cooling stages 1 = 1 stage 2 = 2 stages (Default) 2 (3) Not used Not used 3 (4) Min pos Minimum damper position 0 to 100 %, 0 = (Default) 4 (5) Chngstpt Changeover setpoint range number 5 (6) Chngstpt Changeover setpoint value number Enter the setpoint s range number from Table 14. Enter the setpoint s value number from Table (7) C mech Mechanical cooling allowed 0 = Off (Default) 1 = On 7 (8) Mix stpt Mixed air setpoint range number Enter the setpoint s range number from Table 15 8 (9) Mix stpt Mixed air setpoint value number Enter the setpoint s value number from Table (10) Not used Not used TEC226x-3 and TEC220x-3 Series LONWORKS Network Staged Thermostats Technical Bulletin 27

28 Change Over Setpoint Table Table 14: Chngstpt Table (Economizer Only) Setpoint Setpoint Setting Setting Range Byte 4 (5) Value Byte 5 (6) Range Byte 4 (5) Value Byte 5 (6) Setpoint Setting Range Byte 4 (5) Value Byte 5 (6) 14 F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F 4 59 Note: Lonwatcher Range byte location and Value byte location numbers shown in parenthesis. See Table 5 for more information on Bit/Byte use in each LONWORKS network configuration tool. 28 TEC226x-3 and TEC220x-3 Series LONWORKS Network Staged Thermostats Technical Bulletin

29 Mixed Air Setpoint Table Table 15: ncimultiopts Mixed Air Setpoint Range Adjustment Values Mixed Air Setpoint Setting Range Byte 7 (8) Value Byte 8 (9) Mixed Air Setpoint Setting Range Byte 7 (8) Value Byte 8 (9) Mixed Air Setpoint Setting Range Byte 7 (8) Value Byte 8 (9) 50 F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F Note: Lonwatcher Range byte location numbers and Value byte location numbers shown in parenthesis. See Table 5 for more information on Bit/Byte use in each LONWORKS network configuration tool. TEC226x-3 and TEC220x-3 Series LONWORKS Network Staged Thermostats Technical Bulletin 29

30 ncimultiopts Heat Pump Thermostat Command Table Figure 5 shows the ncimultiopts screen for a Heat Pump with the cells labeled. Figure 5: ncimultiopts Heat Pump Status/Command Screens Use the information in Table 16 to configure the Heat Pump thermostat remotely. Note: This information is valid only for the TEC and TEC Heat Pump thermostats. Table 16: ncimultiopts Heat Pump Thermostat Command Table MCL Tool Byte Number (Lonwatcher Byte Number) Stat Menu Name Description Byte and Range 0 (1) Re valve Reversing valve operation 0 = Normally Cool (O) (Default) 1 = Normally Heat (B) 1 (2) Heat pump stage Heat Pump or Cooling stages 1 = 1 stage 2 = 2 stages (Default) 2 (3) Not used Not used 3 (4) Not used Not used 4 (5) Hi b.p. High balance point range number Enter the range number from Table (6) Hi b.p. High balance point value number Enter the value number from Table (7) Comf/eco Comfort or economy mode 0 = Comfort (Default) 1 = Economy 7 (8) Lo b.p. Low balance point range number Enter the range number from Table (9) Lo b.p. Low balance point value number Enter the value number from Table (10) Comp/aux Compressor/auxiliary interlock 0 = Off (Default) 1 = On 30 TEC226x-3 and TEC220x-3 Series LONWORKS Network Staged Thermostats Technical Bulletin

31 High Balance Point Table Table 17: ncimultiopts (Heat Pump) Hi B.P. Range Adjustment Values MinCool Setpoint Setting Range Byte 4 (5) Value Byte 5 (6) MinCool Setpoint Setting Range Byte 4 (5) Value Byte 5 (6) MinCool Setpoint Setting Range Byte 4 (5) Value Byte 5 (6) 34 F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F Note: Lonwatcher Range byte location numbers and Value byte location numbers shown in parenthesis. See Table 5 for more information on Bit/Byte use in each LONWORKS network configuration tool. TEC226x-3 and TEC220x-3 Series LONWORKS Network Staged Thermostats Technical Bulletin 31

32 Low Balance Point Table Table 18: ncimultiopts (Heat Pump) Lo B.P. Range Adjustment Values Lo BP Setting Schedules Range Byte 7 (8) Time and Date Table Value Byte 8 (9) Lo BP Setting Range Byte 7 (8) Value Byte 8 (9) Lo BP Setting Use the information in Table 19 to configure the thermostat s date and time remotely. The thermostat uses this time setting for schedules. Range Byte 7 (8) Value Byte 8 (9) -40 F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F Note: Lonwatcher Range byte location numbers and Value byte location numbers shown in parenthesis. See Table 5 for more information on Bit/Byte use in each LONWORKS network configuration tool. 32 TEC226x-3 and TEC220x-3 Series LONWORKS Network Staged Thermostats Technical Bulletin

33 Note: This is only valid for the TEC226x-3 programmable thermostats. Table 19: nvitimeset Command Table Name Valid Range Default Value Year 0 to 3,000 0 Month 0 to 12 0 Day 0 to 31 0 Hour 0 to 23 0 Minute 0 to 59 0 Second 0 to 59 0 Commanding a Schedule Schedules are available for each day of the week. Use the ncidayschedule(x) CP to assign a range and value for the occupied and unoccupied time for each day that requires a schedule, then command the thermostat to accept the schedule. Changing the thermostat s 2/4event menu selection from 2.0 to 4.0 adds a second occupied and unoccupied schedule time setting for the selected day. Note: The time and date must be set for the schedules to operate properly. Use Table 20 to command the first schedule of the selected day. Table 20: UNVT ncidaysched Byte Numbers (2.0 event) Day CP Name Occupied Range Byte Number Occupied Value Byte Number Unoccupied Range Byte Number Monday ncidaysched(0) Tuesday ncidaysched(1) Wednesday ncidaysched(2) Thursday ncidaysched(3) Friday ncidaysched(4) Saturday ncidaysched(5) Sunday ncidaysched(6) Note: Bytes 4, 5, 6, and 7are used for 4.0 event schedules. Unoccupied Value Byte Number Use Table 21 to command the second schedule of the selected day. Note: The thermostat s 2/4event menu must be set to 4.0 for the commands to work. Table 21: UNVT ncidaysched Byte Numbers (4.0 event) (Part 1 of 2) Day CP Name Occupied Range Byte Number Occupied Value Byte Number Unoccupied Range Byte Number Unoccupied Value Byte Number Monday ncidaysched(0) Tuesday ncidaysched(1) Wednesday ncidaysched(2) TEC226x-3 and TEC220x-3 Series LONWORKS Network Staged Thermostats Technical Bulletin 33

34 Table 21: UNVT ncidaysched Byte Numbers (4.0 event) (Part 2 of 2) Day CP Name Occupied Range Byte Number Occupied Value Byte Number Unoccupied Range Byte Number Unoccupied Value Byte Number Thursday ncidaysched(3) Friday ncidaysched(4) Saturday ncidaysched(5) Sunday ncidaysched(6) Note: Bytes 0, 1, 2, and 3 are used for 2.0 event schedules. To command a schedule: 1. Click on an ncidaysched(x) to select the schedule day. The ncidaysched(x) Detail or Status/Command screen appears. 2. Click the Status/Command tab. The Status/Command screen appears. 3. Enter an occupied start time Range number in the byte 0 cell. 4. Enter an occupied start time Value in the byte 1 cell. 5. Enter an unoccupied start time Range in the byte 2 cell. 6. Enter an unoccupied start time Value in the byte 3 cell. Note: If the 2/4event menu is set to 4.0 you can command a second schedule for the selected day. Otherwise, skip to Step Enter the second schedule s occupied start time Range number in the byte 4 cell. 8. Enter the second schedule s occupied start time Value in the byte 5 cell. 9. Enter the second schedule s unoccupied start time Range in the byte 6 cell. 10. Enter the second schedule s unoccupied start time Value in the byte 7 cell. 11. Click Command; the schedule(s) are sent to the thermostat. Note: To cancel a schedule, enter 0s in each of the byte cells and click Command. 34 TEC226x-3 and TEC220x-3 Series LONWORKS Network Staged Thermostats Technical Bulletin

35 Schedule Table Table 22: Schedule Command Ranges and Values (Part 1 of 12) Time Range Value Time Range Value Time Range Value 12:00 AM :41 AM :22 AM :01 AM :42 AM :23 AM :02 AM :43 AM :24 AM :03 AM :44 AM :25 AM :04 AM :45 AM :26 AM :05 AM :46 AM :27 AM :06 AM :47 AM :28 AM :07 AM :48 AM :29 AM :08 AM :49 AM :30 AM :09 AM :50 AM :31 AM :10 AM :51 AM :32 AM :11 AM :52 AM :33 AM :12 AM :53 AM :34 AM :13 AM :54 AM :35 AM :14 AM :55 AM :36 AM :15 AM :56 AM :37 AM :16 AM :57 AM :38 AM :17 AM :58 AM :39 AM :18 AM :59 AM :40 AM :19 AM :00 AM :41 AM :20 AM :01 AM :42 AM :21 AM :02 AM :43 AM :22 AM :03 AM :44 AM :23 AM :04 AM :45 AM :24 AM :05 AM :46 AM :25 AM :06 AM :47 AM :26 AM :07 AM :48 AM :27 AM :08 AM :49 AM :28 AM :09 AM :50 AM :29 AM :10 AM :51 AM :30 AM :11 AM :52 AM :31 AM :12 AM :53 AM :32 AM :13 AM :54 AM :33 AM :14 AM :55 AM :34 AM :15 AM :56 AM :35 AM :16 AM :57 AM :36 AM :17 AM :58 AM :37 AM :18 AM :59 AM :38 AM :19 AM :00 AM :39 AM :20 AM :01 AM :40 AM :21 AM :02 AM TEC226x-3 and TEC220x-3 Series LONWORKS Network Staged Thermostats Technical Bulletin 35

LonWorks Integration Instructions

LonWorks Integration Instructions LonWorks Communicating Room Controllers LonWorks Integration Instructions PIR Ready SE76x7 Series Programmable & Non-Programmable Controllers for Commercial HVAC Applications CONTENTS PID History Revision

More information

Tracer LonTalk Communication Interface for ReliaTel Controls for light and large commercial units with a ReliaTel control platform

Tracer LonTalk Communication Interface for ReliaTel Controls for light and large commercial units with a ReliaTel control platform Programming Guide Tracer LonTalk Communication Interface for ReliaTel Controls for light and large commercial units with a ReliaTel platform BAYLTCI002* BAYLTCI003* BAYLTCI004* 3 to 10 Tons Packaged Rooftop

More information

Variable Air Volume Modular Assembly (VMA) 1200 Series Controllers

Variable Air Volume Modular Assembly (VMA) 1200 Series Controllers FANs 1162, 693 Issue Date 0401 APPLICATION NOTE Variable Air Volume Modular Assembly (VMA) 1200 Series Controllers Variable Air Volume Modular Assembly (VMA) 1200 Series Controller Applications... *3 Introduction...*3

More information

Zone controller TAC Xenta 102

Zone controller TAC Xenta 102 Zone controller TAC Xenta 102 Handbook TAC improves indoor climate and reduces operating costs. Air flow Heating Changeover via network variable Cooling Cooling demand 0-004-7516-1 (GB), 1999-08-18 Foreword

More information

SE7600F Series. RTU Terminal Equipment Controller with Modulating Heat. Installation Guide For Commercial HVAC Applications CONTENTS.

SE7600F Series. RTU Terminal Equipment Controller with Modulating Heat. Installation Guide For Commercial HVAC Applications CONTENTS. Room Controllers 01 RTU Terminal Equipment Controller with Modulating Heat For Commercial HVAC Applications CONTENTS Installation 2 Location 2 Installation 2 Operation Overview 3 Features overview 3 Model

More information

CONTENTS Installation Location

CONTENTS Installation Location PIR Ready VT7600 Series With & Without Local Schedule Terminal Equipment Controllers Installation Guide For Commercial HVAC Applications November 04 th, 2011 / 028-0228-R5 CONTENTS Installation Location

More information

Installation Guide. Contents. VT7600E Series RTU Terminal Equipment Controller with IAQ Control

Installation Guide. Contents. VT7600E Series RTU Terminal Equipment Controller with IAQ Control VT7600E Series RTU Terminal Equipment Controller with IAQ Control Installation Guide For Commercial HVAC Applications February 25th, 2014 / Contents Installation 2 Location 2 Installation 2 Theory of Operation

More information

Ma y 3 rd, 2012 / R4

Ma y 3 rd, 2012 / R4 PIR Ready VT76x7 Series With & Without Local Schedule & With Humidification & Dehumidification Strategy Terminal Equipment Controllers Installation Guide For Commercial HVAC Applications Ma y 3 rd, 2012

More information

CONTENTS Installation Location

CONTENTS Installation Location 1 PIR Ready SE7600 Series With & Without Local Schedule Terminal Equipment Controllers Installation Guide For Comme rcial HVAC Applications CONTENTS Installation Location Installation Theory of operation

More information

M a y 3 rd, / R4

M a y 3 rd, / R4 PIR Ready VT7600W Series With & Without Local Schedule Water Source Heat Pump Terminal Equipment Controllers Installation Guide For Commercial HV AC Ap plication s M a y 3 rd, 201 2 / 028-0 35 5- R4 CONTENTS

More information

VT7600F Series RTU Terminal Equipment Controller with Modulating Heat. Installation Guide

VT7600F Series RTU Terminal Equipment Controller with Modulating Heat. Installation Guide VT7600F Series RTU Terminal Equipment Controller with Modulating Heat Installation Guide For Commercial HVAC Applications Januar y 30 th, 2012 / 028-377-R2 CONTENTS Installation 2 Location 2 Installation

More information

VT8600 Series User Interface Guide Rooftop Unit, Heatpump and Indoor Air Quality Controller

VT8600 Series User Interface Guide Rooftop Unit, Heatpump and Indoor Air Quality Controller 1 VT8600 Series User Interface Guide Rooftop Unit, Heatpump and Indoor Air Quality Controller Version 11 2 Table of Contents Section 1 Introduction 4 User and Integrator Screens 4 Disclaimer 5 HMI Display

More information

SE8600 Series User Interface Guide Rooftop Unit, Heat Pump and Indoor Air Quality Controller

SE8600 Series User Interface Guide Rooftop Unit, Heat Pump and Indoor Air Quality Controller SE8600 Series User Interface Guide Rooftop Unit, Heat Pump and Indoor Air Quality Controller Version 10 2 HMI Display The User HMI is configurable and allows display functions such as Date, Time, Outdoor

More information

Modbus Integration Integration for Modbus Functionality for VT8300 Series

Modbus Integration Integration for Modbus Functionality for VT8300 Series Modbus Integration Integration for Modbus Functionality for VT8300 Series Building Management System *For data visualization and analysis Modbus Controller VT8000 Series room controllers 2 TABLE OF CONTENTS

More information

GUIDE SPECIFICATIONS CONTROLS SPECIFICATIONS AND CONTROL POINT DATA MAP GENERAL DESCRIPTION

GUIDE SPECIFICATIONS CONTROLS SPECIFICATIONS AND CONTROL POINT DATA MAP GENERAL DESCRIPTION GUIDE SPECIFICATIONS 256920-UGS-A-0506 Simplicity Intelli-Comfort Optional Control in 3-25 Ton Packaged Units GENERAL DESCRIPTION CONTROLS SPECIFICATIONS AND CONTROL POINT DATA MAP Equipment with Simplicity

More information

Viconics VT76x7 Series Rooftop Unit Controllers Engineering Guide Specification

Viconics VT76x7 Series Rooftop Unit Controllers Engineering Guide Specification Viconics VT76x7 Series Rooftop Unit Controllers Engineering Guide Specification General The VT76x7 series is designed for single-stage and multi-stage control of heating/cooling equipment such as rooftop

More information

Universal Controller

Universal Controller Universal Controller Overview and Configuration Manual Overview... 1 About this Manual... 1 Introduction... 5 Hardware Overview... 5 Software Overview... 7 Interpreting Flow Diagrams... 8 Foreign Language

More information

Titan Products RDU-4/TS & RDU-4/5B Time Scheduling Room Display Units

Titan Products RDU-4/TS & RDU-4/5B Time Scheduling Room Display Units Titan Products RDU-4/TS & RDU-4/5B Time Scheduling Room Display Units 1 Time Scheduling RDU-4/TS - Description of Control Operation The temperature control and time scheduling for the building space is

More information

Fan-coil intelligent unitary controller

Fan-coil intelligent unitary controller SAUTER EY-modulo 4 PDS 94147 en Product Data Sheet EY-RC401 ecos401: Fan-coil intelligent unitary controller How energy efficiency is improved Demand-led control for fan-coil and chilled beams applications

More information

IntesisBox ME-AC-LON-1 v

IntesisBox ME-AC-LON-1 v IntesisBox ME-AC-LON-1 v.1.6.10 User's Manual Rev 3 Intesis Software S.L. 2009. All Rights Reserved. Information in this document is subject to change without notice. No part of this publication may be

More information

LON I/O Module DR-N MCU4-AC Art. no.: MTN881811

LON I/O Module DR-N MCU4-AC Art. no.: MTN881811 Art. no.: MTN881811 User Manual LON I/O Module DR-N MCU4-AC Art. no.: MTN881811 Directory Directory... 1 1.... 2 2. Function... 2 3. Mounting... 3 4. Remarks... 3 5. Technical Data... 4 6. Application

More information

Home Automation, Inc. Omnistat2. RC-1000 and RC-2000 Communicating Thermostat. Serial Protocol Description

Home Automation, Inc. Omnistat2. RC-1000 and RC-2000 Communicating Thermostat. Serial Protocol Description Home Automation, Inc. Omnistat2 RC-1000 and RC-2000 Communicating Thermostat Serial Protocol Description This document contains the intellectual property of Home Automation, Inc. (HAI). HAI authorizes

More information

ECL-VAV Series Preloaded Applications. User Guide

ECL-VAV Series Preloaded Applications. User Guide ECL-VAV Series Preloaded Applications User Guide Document Revision History: Version 1.0 Initial Release March 2012 Version 1.1 Added the Occupancy Sensor Hold Time option in the system configuration ECL-VAV

More information

Excel 10 W7763C,D,E CHILLED CEILING CONTROLLERS LNS PLUG-INS

Excel 10 W7763C,D,E CHILLED CEILING CONTROLLERS LNS PLUG-INS Excel W7763C,D,E CHILLED CEILING CONTROLLERS LNS PLUG-INS HONEYWELL EXCEL 5 OPEN SYSTEM USER GUIDE CONTENTS Introduction... Description of Devices... Products Covered... Organization of Manual... Applicable

More information

TEC Controller Constant Volume with Hot Water Reheat, Application Application Note Building Technologies

TEC Controller Constant Volume with Hot Water Reheat, Application Application Note Building Technologies TEC Controller Constant Volume with Hot Water Reheat, Application 2033 Application Note 140-1023 Building Technologies Table of Contents Overview... 4 Hardware Inputs... 5 Hardware Outputs... 5 Secure

More information

BACnet Integration Manual

BACnet Integration Manual BACnet Integration Manual With & Without Scheduling Controllers For Commercial HVAC Applications CONTENTS SE7600 Series Product Overview Protocol Implementation 2 Conformance Statements (PICS) 3 Device

More information

SE7000 Series Application guide

SE7000 Series Application guide SE7000 Series Application guide Control Performance Energy savings Better building management About Schneider Electric As a global specialist in energy management with operations in more than 100 countries,

More information

Corrigo E. Lon-interface variable list Covers all versions of Corrigo E.-LON from revision Revision: 8 Date:

Corrigo E. Lon-interface variable list Covers all versions of Corrigo E.-LON from revision Revision: 8 Date: Corrigo E Lon-interface variable list Covers all versions of Corrigo E.-LON from revision 1.2-1-0 Revision: 8 Date: 11-08-19 Copyright AB REGIN, Sweden, 2011 About the manual This document covers all versions

More information

LONMARK Functional Profile: Air Velocity Sensor

LONMARK Functional Profile: Air Velocity Sensor Version 1.0 Air Velocity Sensor: 1083 LONMARK Functional Profile: Air Velocity Sensor 1083-10 1998, LONMARK Interoperability Association Overview This document describes the profile of an HVAC air velocity

More information

Honeywell. W7620 Zone Controller Water Source Heat Pump A. GENERAL RESIDENTIAL AND BUILDING CONTROL GUIDE SPECIFICATION FOR THE ENGINEER

Honeywell. W7620 Zone Controller Water Source Heat Pump A. GENERAL RESIDENTIAL AND BUILDING CONTROL GUIDE SPECIFICATION FOR THE ENGINEER Honeywell RESIDENTIAL AND BUILDING CONTROL GUIDE SPECIFICATION FOR THE ENGINEER W7620 Zone Controller Water Source Heat Pump - -.> The W7620 Zone Controller provides customized control of HVAC zone equipment.

More information

User Manual. KNX MultiLight Dali. Article number: function Technology AS. Picture: KNX MultiLight products

User Manual. KNX MultiLight Dali. Article number: function Technology AS. Picture: KNX MultiLight products User Manual KNX MultiLight Dali Article number: 44002 Picture: KNX MultiLight products function Technology AS Table of Contents 1 THE KNX MULTILIGHT DALI... 3 2 INTRODUCTION... 3 3 START-UP AND GENERAL

More information

October 25 th 2010 / R1

October 25 th 2010 / R1 PIR Ready VTR7300 Series Terminal Equipment Controller Installation Guide For Commercial and Lodging HVAC Fan Coil Applications October 25 th 2010 / 028-0298-R1 CONTENTS Installation 2 Location 2 Installation

More information

TC 204 Heating Controller

TC 204 Heating Controller TC 204 Heating Controller ver. 1.32-01 The TC204 is a multi-purpose heating controller with built-in programs for different types of heating systems. General Data Power requirement 24 volts ac, 2 va Inputs

More information

TLC3-BCR-U Series Thermostat

TLC3-BCR-U Series Thermostat OVERVIEW TLC3-BCR-U Series Thermostat Features Low power energy consumption: < 1W per unit Relays switching for outputs each up to 300W Temperature control for 2 or 4-pipe heating or cooling systems. Optional

More information

Site Controls Room Thermostat

Site Controls Room Thermostat Document No. 29-97 April, 25 Site Controls Room Thermostat Required Tools No. Phillips screwdriver /8 flat-blade screwdriver Drill with /8" drill bit Expected Installation Time 5 minutes Figure. RDY2RZ/SC

More information

Modbus VAV Controller Configuration Properties

Modbus VAV Controller Configuration Properties Modbus VAV Controller Configuration Properties Modbus Object Type: Holding Registers Name Default Min Max Units Modbus Reg # Multiplier Focus Screen Modbus Notes DeviceType 0 0 0 None 1 1 Device (Not writable)

More information

Metasys Zoning Package Commissioning

Metasys Zoning Package Commissioning Technical Bulletin Issue Date 11/01/01 TECHNICAL BULLETIN Metasys Zoning Package Commissioning Metasys Zoning Package Commissioning...2 Introduction... 2 Key Concepts... 3 HVAC PRO Software...3 Configuration

More information

User manual. KNX MultiController DALI. Article number: 5410x / 5411x. function Technology AS

User manual. KNX MultiController DALI. Article number: 5410x / 5411x. function Technology AS User manual KNX MultiController DALI Article number: 5410x / 5411x Picture: KNX MultiController DALI with Reed panel and sensor function Technology AS Table of contents 1 KNX MULTICONTROLLER... 3 2 INTRODUCTION...

More information

theben Fan Coil Actuator FCA 1 Fan Coil Actuator FCA 1 FCA Version: Jan-08 (Subject to change) Page 1 of 77

theben Fan Coil Actuator FCA 1 Fan Coil Actuator FCA 1 FCA Version: Jan-08 (Subject to change) Page 1 of 77 Fan Coil Actuator FCA 1 FCA 1 492 0 200 Version: Jan-08 (Subject to change) Page 1 of 77 Contents 1 Functional characteristics...4 1.1 Operation and display...5 1.2 Advantages of the FCA 1...5 1.2.1 Special

More information

Use of the application program. Contents. instabus EIB Application program description. September S2 Room temperature controller

Use of the application program. Contents. instabus EIB Application program description. September S2 Room temperature controller Use of the application program Product family: Product type: Manufacturer: Heating, Air conditioning, Ventilation Thermostat Siemens Name: Room temperature controller IKE 250 DELTA millennium Order no.:

More information

Functional Profile. SOMFY animeo LON Sensor Interface WM Ref

Functional Profile. SOMFY animeo LON Sensor Interface WM Ref Functional Profile SOMFY animeo LON Sensor Interface WM Ref. 1860161 Somfy Activites SA 50 Avenue du Nouveau Monde 74300 Cluses France www.somfy.com/projects Version 1.1 Revision date: 03.05.12 Ref.Nr.:

More information

Functional Profile. SOMFY animeo LON RTS Module 433 MHz WM Ref SOMFY animeo LON RTS Module 447 MHz WM Ref

Functional Profile. SOMFY animeo LON RTS Module 433 MHz WM Ref SOMFY animeo LON RTS Module 447 MHz WM Ref Functional Profile SOMFY animeo LON RTS Module 433 MHz WM Ref. 1860239 SOMFY animeo LON RTS Module 447 MHz WM Ref. 1860240 Somfy Activites SA 50 Avenue du Nouveau Monde 74300 Cluses France www.somfy.com/projects

More information

PIR Ready VT72xx & VT(R) 73xx Series 24 Vac Fan Coil and Zoning Thermostats For Commercial and Lodging HVAC Applications

PIR Ready VT72xx & VT(R) 73xx Series 24 Vac Fan Coil and Zoning Thermostats For Commercial and Lodging HVAC Applications PIR Ready VT72xx & VT(R) 73xx Series 24 Vac Fan Coil and Zoning Thermostats For Commercial and Lodging HVAC Applications BACnet Integration Manual ITG-VT(R) 72_73-BAC-E11 (028-6009 R11 Issue Date: February

More information

MicroTech II Applied Rooftop Unit Controller Protocol Information

MicroTech II Applied Rooftop Unit Controller Protocol Information Engineering Data ED 15060-10 Group: Controls Part Number: ED 15060 Date: November 2006 Supersedes: ED 15060-9 MicroTech II Applied Rooftop Unit Controller Protocol Information Networks Networks RPS/RFS/RCS/RDT/

More information

ECP-400 Series. ECP-400 Series. 24-Point Free Programmable Controller. Applications. Features

ECP-400 Series. ECP-400 Series. 24-Point Free Programmable Controller. Applications. Features ECP-400 Series 24-Point Free Programmable Controller Applications Control of equipment such as: roof top units, multistage air handling units, chillers, boilers, pumps, cooling towers, lighting systems,

More information

RAM 712 KNX room thermostat for surface-mounted and flush-mounted installation

RAM 712 KNX room thermostat for surface-mounted and flush-mounted installation RAM 712 KNX room thermostat for surface-mounted and flush-mounted installation RAM 712 712 9 200 Version: Dec-10 (subject to change) Page 1 of 65 Contents 1 Functional characteristics... 4 1.1 Operation...

More information

PIR Ready SE7200, SE7300 & SER7300 Series

PIR Ready SE7200, SE7300 & SER7300 Series PIR Ready SE7200, SE7300 & SER7300 Series 24 Vac Zoning, Fan Coil and Line-Voltage Fan Coil Controllers For Commercial and Lodging HVAC Applications CONTENTS Protocol Implementation Conformance Statement

More information

VT8300 Series Installation Guide 24 Vac Low Voltage

VT8300 Series Installation Guide 24 Vac Low Voltage VT00 Series Installation Guide Low Voltage mercial and Hotel/Lodging HVAC Fan Coil Applications CONTENTS Installation Terminal Identification & Function Terminal identification Wiring Typical Applications

More information

BACnet PTEC Controller VAV with CO2 Monitoring, Parallel Fan and AOV or Floating Point Heating, Application 6682

BACnet PTEC Controller VAV with CO2 Monitoring, Parallel Fan and AOV or Floating Point Heating, Application 6682 BACnet PTEC Controller VAV with CO2 Monitoring, Parallel Fan and AOV or Floating Point Heating, Application 6682 Application Note 140-1156 Building Technologies Table of contents Overview... 5 BACnet...

More information

Actuating Terminal Equipment Controller (ATEC) Base VAV - Cooling or Heating, Application Application Note

Actuating Terminal Equipment Controller (ATEC) Base VAV - Cooling or Heating, Application Application Note Actuating Terminal Equipment Controller (ATEC) Base VAV - Cooling or Heating, Application 2521 Application Note 140-1218 Building Technologies Table of Contents Overview... 4 Hardware Inputs... 5 Hardware

More information

Stryker CVAHU WEBs-N4 Configuration Wizard Guide

Stryker CVAHU WEBs-N4 Configuration Wizard Guide Environmental Combustion and Control Stryker CVAHU WEBs-N4 Configuration Wizard Guide August 2015 31-00088-01 Table of Contents INTRODUCTION... 9 Stryker CVAHU Controller... 9 Niagara 4 TM... 9 CVAHU Configuration

More information

Software Description SRCN_HWL_9_1_03 for SRC 04 FTT and SRC 65 FTT

Software Description SRCN_HWL_9_1_03 for SRC 04 FTT and SRC 65 FTT Software Description SRCN_HWL_9_1_03 for SRC 04 FTT and SRC 65 FTT 1 Overview The application enables the receipt and evaluation of max. nine EnOcean wireless sensors. The following sensor types are supported:

More information

BACnet VAV Controller Configuration Properties

BACnet VAV Controller Configuration Properties VAV Controller Configuration Properties Object Type: Analog Value Datatype: Real Name Default Min Max Object ID Object Name Units Notes Proportional 3 0 50 20 PropB 62 (celcius) Heat Integral 15 0 120

More information

LON DDC Controller. Unit DDC Controls. Application, Operation & Maintenance. Table of Contents

LON DDC Controller. Unit DDC Controls. Application, Operation & Maintenance. Table of Contents Table of Contents LON DDC Controller Unit DDC Controls LON Controller Overview & Features 3 Hardware Specifications 4 Typical LON Controller Wiring Schematic - CXM Single Stage Heat Pump 6 Typical LON

More information

Network VP TM Satellite User s Guide

Network VP TM Satellite User s Guide Network VP TM 2.00 Satellite User s Guide 16 to 64 stations in eight-station increments Field programmable for future upgrades Does not require EPROM(s) replacement Operates as a stand-alone controller

More information

INTAC Microprocessor Humidifier Controller

INTAC Microprocessor Humidifier Controller PURE Humidifier Company Read and Save These Instructions INTAC Microprocessor Humidifier Controller Installation Instructions Operation and Maintenance Manual 002 % Power 68% Heaters 1 2 3 4 INTAC Humidifier

More information

Model 12200A RCN PTAC/PTHP/FAN COIL CONTROL NODE OPERATION OUTPUTS G1 = FAN 1 G2 = FAN 2 G3 = FAN 3 O/B = Rev Valve W = HEAT Y = COMPRESSOR

Model 12200A RCN PTAC/PTHP/FAN COIL CONTROL NODE OPERATION OUTPUTS G1 = FAN 1 G2 = FAN 2 G3 = FAN 3 O/B = Rev Valve W = HEAT Y = COMPRESSOR Model 12200A RCN PTAC/PTHP/ COIL CONTROL NODE OPERATION OUTPUTS G1 = 1 G2 = 2 G3 = 3 O/B = Rev Valve W = HEAT Y = COMPRESSOR Operating Modes Summary (Refer to Logic Tables 1 5): 1. PTAC (Standard) Fan

More information

ECP-103 Series. ECP-103 Series. 10-Point Free Programmable Controller. Applications. Features

ECP-103 Series. ECP-103 Series. 10-Point Free Programmable Controller. Applications. Features ECP-103 Series 10-Point Free Programmable Controller Applications Control of terminal units such as VAV, FCU, UV and HPU as well as control for chilled ceiling applications. Control of many other types

More information

TAC5 Regulation + SAT KNX Module

TAC5 Regulation + SAT KNX Module TAC5 Regulation + SAT KNX Module TAC5 Regulation + SAT KNX Module Installation and user s manual TABLE OF CONTENTS 1. FUNCTIONALITIES OF THE REGULATION... 5 2. Operating PRINCIPLE... 6 2.1 KNX Network...

More information

CAT-260 Repeater Controller Computer Automation Technology, Inc

CAT-260 Repeater Controller Computer Automation Technology, Inc CAT-260 Repeater Controller Computer Automation Technology, Inc 7378 W. Atlantic Blvd. #239 Margate, Florida 33063 Phone: (954) 978-6171 Fax: (561) 465-5891 Internet: http://www.catauto.com Table of Contents

More information

SmartZone-2 & SmartZone-4

SmartZone-2 & SmartZone-4 SmartZone-2 & SmartZone-4 Quick-Start Guide UPDATED 2011-7-26 This guide is intended to give the installer a brief set of instructions about how to set up the XCI Zoning SmartZone System. For more detailed

More information

Operation. Section 4. Additional Information. Operation 4-1

Operation. Section 4. Additional Information. Operation 4-1 4-1 Section 4 WARNING: Allow only personnel with appropriate training and experience to operate or service the equipment. The use of untrained or inexperienced personnel to operate or service the equipment

More information

FCU-503 FAN COIL CONTROLLER WITH RDU-TOUCH INTERFACE

FCU-503 FAN COIL CONTROLLER WITH RDU-TOUCH INTERFACE FCU-503 FAN COIL CONTROLLER WITH RDU-TOUCH INTERFACE BACnet Enabled Description The FCU-503 is designed to provide complete control of fan coil units and / or underfloor heating circuits. The FCU-5 incorporates

More information

16-Channel Yearly Time Switch TR 648 S DCF

16-Channel Yearly Time Switch TR 648 S DCF 16-Channel Yearly Time Switch TR 648 S DCF Illustration 1 : TR 648 S DCF TR 648 S DCF EIB 648 9 201 DCF 77 Antenna 907 0 271 Obelisk 2.0 Programming set 907 0 305 Obelisk 2.1 Software 931 0 961 Page 1

More information

BACnet PTEC Controller Dual Duct 2 AVS - Constant Volume with Two Inlet Sensors and Optional Reheat, Application 6665

BACnet PTEC Controller Dual Duct 2 AVS - Constant Volume with Two Inlet Sensors and Optional Reheat, Application 6665 BACnet PTEC Controller Dual Duct 2 AVS - Constant Volume with Two Inlet Sensors and Optional Reheat, Application 6665 Application Note 140-1113 Building Technologies Table of Contents Overview... 5 BACnet...

More information

OWNERS MANUAL FOR STERLING SERIES CONTROLLERS

OWNERS MANUAL FOR STERLING SERIES CONTROLLERS OWNERS MANUAL FOR STERLING SERIES CONTROLLERS 24950 AVENUE KEARNY, VALENCIA, CALIFORNIA 91355-2142 PHONE (661) 257-3533 FAX (661) 257-9472 TABLE OF CONTENTS Selecting the Location for the Controller...3

More information

ELECTRONIC THERMOSTAT: T920

ELECTRONIC THERMOSTAT: T920 μnistδt ELECTRONIC THERMOSTAT: T One analog output DESCRIPTION The T series thermostats are microcomputer-based, proportional and integral (PI) devices with one analog 0 to 0 output. They can be used with

More information

Fan Coil Actuator FCA 2

Fan Coil Actuator FCA 2 Fan Coil Actuator FCA 2 FCA 2 4920210 Updated: Feb-16 (subject to changes) Page 1 of 89 Contents 1 Function description... 4 1.1 Operation and display... 5 1.2 Advantages of the FCA 2... 6 1.2.1 Special

More information

vacon 100 flow ac drives application manual

vacon 100 flow ac drives application manual vacon 100 flow ac drives application manual PREFACE VACON 3 PREFACE Document ID: DPD01083D Date: 15.10.2014 Software version: FW0159V010 ABOUT THIS MANUAL This manual is copyright of Vacon Plc. All Rights

More information

Modbus communication module for TCX2: AEX-MOD

Modbus communication module for TCX2: AEX-MOD Modbus communication module for TCX2: Communication Specification TCX2 is factory installed in TCX2 series controllers with -MOD suffix, and is also available separately upon request for customer installation

More information

APPLICATION GUIDE Delta Network Sensor Thermostat: BACstat II DNS-24, DNT-T103, & DNT-T221 Document Edition 3.1

APPLICATION GUIDE Delta Network Sensor Thermostat: BACstat II DNS-24, DNT-T103, & DNT-T221 Document Edition 3.1 APPLICATION GUIDE Delta Network Sensor Thermostat: BACstat II DNS-24, DNT-T103, & DNT-T221 Document Edition 3.1 Product Description The BACstat II is an intelligent 4-button room sensor/thermostat with

More information

Use of the application program. Contents. 1. Functional description General. GAMMA instabus Application program description.

Use of the application program. Contents. 1. Functional description General. GAMMA instabus Application program description. Use of the application program Product family: Product type: Manufacturer: Heating, air conditioning, ventilation Thermostat Siemens Name: Temperature controller UP 237 DELTA i-system Order no.: 5WG1 237-2AB_1

More information

BACnet VAV Controller Configuration Properties

BACnet VAV Controller Configuration Properties VAV Controller Configuration Properties Object Type: Analog Value Datatype: Real Name Default Min Max Object ID Object Name Units Notes Proportional 3 0 50 20 PropB 62 (celcius) Heat Integral 15 0 120

More information

OPERATING INSTRUCTIONS ARE ON PAGE 5. SECTION 2 Technical Data Transmitter Unit. RVHT 2 MULTI-FIT Programmable R/F Thermostat-Pair SECTION 1

OPERATING INSTRUCTIONS ARE ON PAGE 5. SECTION 2 Technical Data Transmitter Unit. RVHT 2 MULTI-FIT Programmable R/F Thermostat-Pair SECTION 1 OPERATING INSTRUCTIONS ARE ON PAGE 5 RVHT 2 MULTI-FIT Programmable R/F Thermostat-Pair SECTION 1 This Programmable Ravenheat R/F controlled room Thermostat RVHT 2, consists of 2 items: a Mobile Transmitter

More information

Use of the application program. Contents. 1. Functional description General. GAMMA instabus Application program description.

Use of the application program. Contents. 1. Functional description General. GAMMA instabus Application program description. Use of the application program Product family: Product type: Manufacturer: Heating, air conditioning, ventilation Thermostat Siemens Name: Temperature controller UP 237 DELTA i-system Order no.: 5WG1 237-2AB_1

More information

FCU-501 FAN COIL CONTROLLER WITH RDU-4 INTERFACE

FCU-501 FAN COIL CONTROLLER WITH RDU-4 INTERFACE FCU-501 FAN COIL CONTROLLER WITH RDU-4 INTERFACE BACnet Enabled Description The FCU-501 is designed to provide complete control of fan coil units and / or underfloor heating circuits. The FCU-5 incorporates

More information

SRC-110 Series Zone Controllers with Modbus RTU

SRC-110 Series Zone Controllers with Modbus RTU Product sheet CT2.142 Type SRC-110-MOD SRC-110 Series Zone Controllers with Modbus RTU The SRC-110 series controllers have been designed for zone heating and cooling control. The controllers have 3 analogue

More information

TROVIS 5500 Automation System TROVIS 5578 Heating and District Heating Controller. Mounting and Operating Instructions EB 5578 EN

TROVIS 5500 Automation System TROVIS 5578 Heating and District Heating Controller. Mounting and Operating Instructions EB 5578 EN TROVIS 5500 Automation System TROVIS 5578 Heating and District Heating Controller Mounting and Operating Instructions EB 5578 EN Firmware version 2.30 Edition November 2017 Definition of signal words DANGER!

More information

vacon 100 flow ac drives application manual

vacon 100 flow ac drives application manual vacon 100 flow ac drives application manual vacon 1 TABLE OF CONTENTS Document: DPD01083A Version release date: 16.11.12 Corresponds to software package FW0159V121106.vcx 1. Vacon 100 FLOW - Quick Startup

More information

ELECTRONIC THERMOSTAT: T951

ELECTRONIC THERMOSTAT: T951 μnistδt ELECTRONIC THERMOSTAT: T9 One floating output One contact output DESCRIPTION The T9 series thermostats are microcomputer-based, proportional and integral (PI) devices with one floating (incremental)

More information

Allure RS-Smart-Sense. End-User Manual

Allure RS-Smart-Sense. End-User Manual Allure RS-Smart-Sense End-User Manual Document Revision History: 1. Version 1.0 February 2013 2. Version 2.0 July 2013 Allure RS-Smart-Sense - User Guide v2.0 05DI-UGRSSEN-20, Distech Controls Inc., 2013.

More information

Digital Room Sensor Technical Guide

Digital Room Sensor Technical Guide www.orioncontrols.com Digital Room Sensor Technical Guide TABLE OF CONTENTS OVERVIEW... 3 BASIC OPERATION... 4 Sensor Operation... 4 LED Operation... 4 MOUNTING AND WIRING... 5 Environmental Requirements...

More information

Brief description. VAV-Compact LON en-gb Changes reserved 1. Application. Pressure measurement

Brief description.   VAV-Compact LON en-gb Changes reserved 1. Application. Pressure measurement Product information VAV-Compact LON A pressure sensor, digital VAV controller and damper actuator all in one, providing a compact solution with a communications capability for pressure-independent VAV

More information

User Manual OFF ON IN OUT ALARM RESET AURATON RTH software ver. F0F

User Manual OFF ON IN OUT ALARM RESET AURATON RTH software ver. F0F www.auraton.pl User Manual software ver. F0F OFF ON IN OUT ALARM RESET AURATON RTH Thank you for purchasing this modern, advanced, microprocessor-based temperature regulator AURATON 2025 / AURATON 2025

More information

Original instructions. SIRe Advanced. Modbus communication ... 2

Original instructions. SIRe Advanced. Modbus communication ... 2 Original instructions SIRe Advanced Modbus communication GB... 2 SIRe Modbus This manual describes how to connect SIRe Advanced with Modbus/RTU via RS485, the technical specification of the protocol in

More information

Series 70 Servo NXT - Modulating Controller Installation, Operation and Maintenance Manual

Series 70 Servo NXT - Modulating Controller Installation, Operation and Maintenance Manual THE HIGH PERFORMANCE COMPANY Series 70 Hold 1 sec. Hold 1 sec. FOR MORE INFORMATION ON THIS PRODUCT AND OTHER BRAY PRODUCTS PLEASE VISIT OUR WEBSITE www.bray.com Table of Contents 1. Definition of Terms.........................................2

More information

Model: 3003P INSTALLATION AND OPERATING INSTRUCTIONS

Model: 3003P INSTALLATION AND OPERATING INSTRUCTIONS Model: 3003P INSTALLATION AND OPERATING INSTRUCTIONS IF YOU CANNOT READ OR UNDERSTAND THESE INSTALLATION INSTRUCTIONS DO NOT ATTEMPT TO INSTALL OR OPERATE INTRODUCTION This remote control system was developed

More information

n FRONT PANEL CONFIGURATIONS

n FRONT PANEL CONFIGURATIONS INSTRUCTION MANUAL VALVE POSITIONER (for LonWorks; built-in SSR) MODEL MEXL MEXL BEFORE USE... Thank you for choosing M-System. Before use, check the contents of the package you received as outlined below.

More information

Radio Window Sensor and Temperature Sensor Programming in HomeWorks QS

Radio Window Sensor and Temperature Sensor Programming in HomeWorks QS Radio Window Sensor and Temperature Sensor Programming in HomeWorks QS Table of Contents 1. Overview... 2 2. General Operation... 2 2.1. Radio Window Sensor Communication... 2 2.2. Temperature Sensor Communication...

More information

TEC Series Wireless Thermostat Controller System for Staged Equipment

TEC Series Wireless Thermostat Controller System for Staged Equipment TEC Series Wireless System for Staged Equipment Product Bulletin TEC2001-3, TEC2002-3, TEC2003-3, TEC2004-3 Code No. LIT-12011400 Issued June 4, 2009 Supersedes March 25, 2009 The TEC Series Wireless System

More information

This document is intended for Lighting Control Systems professionals

This document is intended for Lighting Control Systems professionals This document is intended for Lighting Control Systems professionals This document applies to fixture with factory installed SVPD1, SVPD2, SVPD3 integrated sensors. Table of contents Quick Reference Guide...

More information

R PROFLAME Instruction Book Collection

R PROFLAME Instruction Book Collection 9.956.028 R00 584 PROFLAME Instruction Book Collection 4-17 18-29 584 PROFLAME System 30-39 Appendix: DIP SWITCH NUMBER (0=ON 1=OFF) 40-41 4-17 Fig. 1 The SIT is a device that allows, in conjunction with

More information

MANUAL. PT Series 365 Day Annual Timer. Tel:

MANUAL. PT Series 365 Day Annual Timer.   Tel: MANUAL PT Series 365 Day Annual Timer www.belltimers.com Tel: 1-888-327-8463 info@belltimers.com Table of Contents: Introduction Features Specifications Overview Installation Function Keys Relay Operation

More information

LONMARK Certified 14-Point Programmable Controller. Overview

LONMARK Certified 14-Point Programmable Controller. Overview LONMARK Certified 14-Point Programmable Controller Applications Meets the requirements of the following applications: Rooftop Units Fan Coil Units Heat Pump Units Unit Ventilators Small Air Handling Units

More information

ZTS-110 (Z-Thermostat)

ZTS-110 (Z-Thermostat) 1 ZTS-110 (Z-Thermostat) Table of Contents Introduction...3 Features List...4 Glossary...5 Physical Installation and Wiring...6 Installation Location... 7 Physically Installing the Thermostat... 7 Wiring...

More information

DUAL 4-20 MA NETWORK BRIDGE. Voltage. Regulator. Neuron CPU. Ohm Sense Resistor. Model 1400A Block

DUAL 4-20 MA NETWORK BRIDGE. Voltage. Regulator. Neuron CPU. Ohm Sense Resistor. Model 1400A Block NEUROLOGIC RESEARCH CORPORATION MODEL 1400A DUAL 4-20 MA NETWORK BRIDGE Instantly integrate any standard sensor into the LONWORKS digital network. Supports loop and self powered sensors. Electronics are

More information

DESCRIPTION MODEL 1450 NOTE

DESCRIPTION MODEL 1450 NOTE - Instantly integrate any standard 4-20 ma sensor into the LonWorks digital network. - Supports loop and self powered devices. - Digitally calibrated for accuracy and custom inputs. - Very stable 15 ppm

More information

Intelligent Compact Controller

Intelligent Compact Controller TCY-T0121 Intelligent Compact Controller Features Temperature control for 2-pipe, 4-pipe HVAC systems. Temperature range from 40 to 140 C. 1 independent PI and On/Off control loop to control temperature.

More information

OVEN INDUSTRIES, INC. Model 5C7-362

OVEN INDUSTRIES, INC. Model 5C7-362 OVEN INDUSTRIES, INC. OPERATING MANUAL Model 5C7-362 THERMOELECTRIC MODULE TEMPERATURE CONTROLLER TABLE OF CONTENTS Features... 1 Description... 2 Block Diagram... 3 RS232 Communications Connections...

More information

The rangefinder can be configured using an I2C machine interface. Settings control the

The rangefinder can be configured using an I2C machine interface. Settings control the Detailed Register Definitions The rangefinder can be configured using an I2C machine interface. Settings control the acquisition and processing of ranging data. The I2C interface supports a transfer rate

More information