Universal tool for residual current monitoring. Smart Energy & Power Quality Solutions

Size: px
Start display at page:

Download "Universal tool for residual current monitoring. Smart Energy & Power Quality Solutions"

Transcription

1 Smart Energy & Power Quality Solutions Universal tool for residual current monitoring

2 Janitza electronics Ethernet level (TCP/IP) Server SQL database Client 1 to... Mobile Web server Grid visualisation software ProData UMG 512-PRO UMG 509-PRO UMG 96RM-E UMG 604-PRO UMG 605-PRO Feld bus level (e. g. Modbus RTU) UMG 20CM ProData UMG 104 UMG 96RM UMG 103-CBM Analogue- / Status- / Pulse input level Water meter Status message Gas meter Alarm lamp Temperature measurement UMG 508 / UMG 604 = Janitza power analyser UMG 512 / UMG 605 = Janitza power quality analyser UMG 96RM / UMG 96RM-E / UMG 103-CBM / UMG 104 = Janitza multifunctional measurement devices for energy measrument technology UMG 20CM = Janitza Residual current monitoring (RCM) and energy data acquisition Press contact:: Janitza electronics GmbH Ms. Stefanie Hollingshaus Manager marketing communication Vor dem Polstück Lahnau Germany Phone: Fax: stefanie.hollingshaus@janitza.de Web:

3 Whitepaper AN1030/V01 Author Dipl.-Ing. (FH) Gerald Fritzen Key Account Manager Janitza electronics GmbH Increased safety, increased system availability, reduced risk of fire An insulation measurement is required for the repeat testing of fixed electrical systems per DGUV V3, for which the system must be switched off. Production processes and administration processes are interrupted. This means an increase in work and often also significant costs. In order to avoid this, the standards offer an alternative: Continuous residual current monitoring, with which it is also possible to locate faults faster. With continuous RCM monitoring, it is possible to avoid shut-downs and minimise test work. Constant checking of the system takes place, which enables the immediate detection of faults. Conventional recurrent testing is unable to guarantee this. Faults are often detected only after years have passed. Highly automated production systems, computer centres and systems with constant processes (e.g. food sector, cable fabrication, paper production) require a reliable power supply - often even high availability, i.e. an availability of at least 99.9%, frequently even %. If availability of 99% sounds extremely good then it is necessary to consider that this equates to a failure time of 87.7 hours, in comparison to 0.53 minutes with the six nines ( %). The numerous servers, automation systems, lifts, safety systems, communication devices, storage media and network components do not generally tolerate voltage interruptions or undervoltage > 10ms. A basic precondition for all further measures is a reliable installation. TN-S systems are state-of-the-art and are also prescribed in the majority of critical applications. In contrast to the previously customary TN-C systems, they exhibit more favourable EMC characteristics for example. Additionally, they enable residual current monitoring (in 3

4 checking for residual currents in TN-S systems. With a comprehensive RCM system, faults in TN-S systems are located directly. So that the user is able to react before a critical level is reached. It is also possible to avoid shut-downs due to residual current circuit breakers (RDCs). This applies in particular to quietly rising residual currents (e.g. triggered by an insulation fault), overly high operating currents or any other overloading of system parts and consumers (image 2). Image 2: Principle of residual current monitoring. short RCM), as illustrated in image 1. RCM measuring devices such as the UMG 96RM-E / UMG 509-PRO / UMG 512-PRO / UMG 20CM from Janitza are suitable for monitoring alternating currents, pulsing DC currents per IEC/TR ( ) and can be used for continuously RCM the functionality The basic functionality of the residual current principle is shown in image 3. Here, the phase and neutral conductor of the protected output are fed through the summation current transformer, the ground wire is left out. The image provides a better overview due to the highly simplified wiring. In practical terms, all three phases and the neutral conductor run through the summation current transformer. In case of systems without a neutral conductor, for example with controlled drives, only the three phases run through the summation current transformer. If the system is in fault-free condition, the summation current is zero or close to zero (within a Image 1: Modern TN-S systems exhibit more favourable EMC characteristics than the old TN-C systems. 4

5 Image 3: Report prior to switching off an aim of residual current monitoring. Image 4: Defective motor insulation leads to a short circuit to ground and residual current against the PE phase. tolerable range), meaning that the current induced in the secondary circuit is also zero or close to zero. If, however, residual current flows away to ground due to a fault, the current differential in the secondary circuit will result in a current being logged and evaluated by the RCM measuring device (image 4). Modern RCM measuring devices accept different threshold value settings here (image 5). A static threshold value has the disadvantage that it is either too high with a part load, or too low with a full load, i.e. either insufficient protection is provided or erroneous alarms are issued, which may have negative effects on the attentiveness of the monitoring personnel over time. For this reason it is advisable to use RCM measuring devices with dynamic threshold value formation. In this case the residual current threshold value is formed on the basis of the actual load conditions and is therefore optimally aligned with the respective applicable load (image 6). Through parameterisation (i.e. stipulation of the typical residual current in "GOOD" condition) of the system in new condition and constant monitoring, all changes to the system state after the point of start-up can be detected. This also enables detection of creeping residual currents. On the basis of historic progressions of the load and residual current, it is possible to determine the GOOD condition and define an expedient residual current threshold value. Integrated measuring device storage and superimposed SCADA systems or the energy data acquisition software GridVis facilitate chronological statements and analyses. Image 5: Comprehensive configuration options for RCM threshold value formation (e.g. dynamic threshold value formation) in the energy data acquisition software GridVis. Image 6: Parameters of residual and operating current monitoring. 5

6 Source EMC manual: Wilhelm Rudolph Table A2 per IEC 64/1120/CDV: Orientation aid: Examples for maximum ground wire / residual currents with AC voltage Equipment (devices) from protection class I: Current consumer for connection via connector devices up to and including 32 A: For rated currents I_n of devices: Maximum threshold values of the ground wire currents: < = 4 A 2 ma > 4 to > = 10 A 0.5 ma / A > 10 A 5 ma Current consumer with fixed connection, without special precautions for the ground wire or current consumer with connection via connector device for over 32 A For rated currents I_n of devices: Maximum threshold values of the ground wire currents: < = 7 A 3.5 ma > 7 A to < = 20 A 0.5 ma / A > 20 A 10 ma Image 7: Threshold values are empirical values, and must be stipulated depending on the type of consumer. Orientation aids are provided by works such as the EMC manual from Wilhelm Rudolph. RCM in practice Listing every standard and specification that has been written in relation to RCM would go beyond the purpose of this contribution. However, a number of general rules do serve as starting points: For example, work with individual current circuits should continue to take place with fixed threshold values such as 30 ma, or with a fire protection objective with 300 ma. With frequency converters, the maximum residual currents in the datasheets should not be exceeded. The following always applies: Threshold values are empirical values, and must be stipulated depending on the type of consumer. Orientation aids are provided by works such as the EMC manual from Wilhelm Rudolph (image 7). It is also necessary to select the right residual current acquisition equipment. The table in image 8 provides an overview. The challenge of high availability A typical application for RCM systems is the computer centre. IT technology itself places high demands on the supply, frequently even requiring high availability, i.e. an availability of at least 99.9 %. However, particularly critical are applications in which the loss of data simply cannot be allowed to occur. BITKOM therefore writes the following in its guidelines for "Operationally reliable computer centres": In computer centres the maximum availability requirements apply. The energy supply must therefore be permanently guaranteed. Therefore comprehensible is the requirement that the power supply to the computer centre itself, and to all areas in the same building to which data cables run, must be designed as a TN-S system. Essential for assured operation is permanent self-monitoring of a clean TN-S system and the issue of signals to a permanently manned desk, e.g. in the control centre. The electrician then ascertains the action requirement based on the respective signals, and is able to prevent damage through targeted service measures. With the Janitza complete solution, it is possible to realise the safety criterion "RCM residual current monitoring" of this type of EMC-optimised TN-S system (image 9). Reduced testing costs with RCM RCMs not only ensure the maximum in safety, they also help to reduce costs. Recurrent testing, as prescribed for example in DGUV V3 Electrical systems and operating equipment, is time-intensive and therefore costly. RCM monitoring systems reduce test costs and save time, whilst also ensuring increased safety. Fixed electrical systems and operating equipment are considered to be monitored constantly if they are permanently maintained by electrical engineers and tested by measuring equipment within the framework of operations (e.g. monitoring of the insulation resistance). Through permanent RCM measurement, monitoring systems are able to deliver the required degree of constant testing. 6

7 Application Type of residual current Form of residual current Installation location Correct function with 1 Ohmic consumers, resistance heaters, electric bulbs, purely inductive and capacitive consumers, lighting systems with conventional ballast and transformer, direct-start motors with no electronic control and regulation, etc. Sinus-form alternating current No longer topical because systems with such equipment are now rare Type AC Alternating current-sensitive Single-phase electronic devices, and devices with electronic control and regulation, such as: Power units, computers, TV, printers, UPS, lighting systems with electronic ballast or electronic transformer, dishwashers, washing machines, microwaves, single-phase drives, heat pumps, circulation pumps, etc. Single-phase dimmers and devices with phase angle or trailing phase control Single-phase electronic devices operated in a three-phase network, split into phases (2 + 3) (a low DC component arises due to a superimposing of pulsing residual currents) Pulsing alternating current (positive or negative half-wave) Phase angle-controlled half-wave currents Phase angle from 90 el Phase angle from 135 el Pulsing alternating current superimposed with smooth DC current of max. 6 ma All areas, in particular single-phase e.g. apartments, small offices, etc Standard switch for modern household Type A Alternating current + pulse current-sensitive 5 6 Devices with three-phase current bridge circuits and pure DC current systems, e.g. photovoltaic systems (on the collector side) Regulated three-phase drives (FC), e.g. regulated three-phase motors (heat pumps, circulating pumps, etc.), three-phase UPS systems, three-phase dimmers, medical three-phase devices (computed tomography, X-rays, etc.), etc. Smooth DC current High frequency up to 1000 Hz and higher Industry, in particular 4-pole, with PV systems also 2-pole DC and in all systems in which pure DC residual currents may arise, e.g. construction site Type B Alternating current + pulse current + DC current = All-currentsensitive Image 8: Overview of types of residual current circuit breaker and their application. 7

8 Under certain preconditions, it is also possible to avoid RCDs with continuous RCM monitoring. These are: Signal connection and immediate reaction in case of a fault Function testing of the signalling equipment Electrician on site Plugs inaccessible to laypersons The following always applies: Residual current monitoring devices (RCMs) are not protective devices, however they may be used to monitor residual currents in electrical systems. Residual current monitoring devices (RCMs) emit an audible or an audible and visible signal if the predefined residual current value is exceeded. Image 9: Constant 3-in-1 monitoring (EnMS + PQ + RCM) of an EMC-optimised TN-S system. New draft standard for recurrent testing DIN VDE : / IEC Low voltage electrical installations Part 6: Verification Extract: Recurrent testing Where circuit is permanently monitored by an RCM in accordance with IEC or an IMD in accordance with IEC , it is not necessary to measure the insulation resistance if the functioning of the IMD or RCM is correct. Potential savings: Reduction in the test costs due to omission of the insulation measurement Avoiding a system shut-down enables constant operation No shut-down of sensitive consumers, which could be damaged by a high test voltage No high personnel costs and administration work due to shut-downs Permanent testing for residual currents = improvement in EMC and minimisation of faults in controls and data lines (See: VDE and / VDS2349 and 2046 / TRBS1201 / DGUV V3 / New draft standard for recurrent testing DIN VDE : / IEC ) Particularly noteworthy here is that RCM renders the cost-intensive measurement of insulation resistances at least partially superfluous, whilst constant testing of the insulation characteristics takes place. In order to carry out conventional insulation measurements, fixed systems and consumers must be switched off. Furthermore, there is a risk that the high test voltage used for the insulation measurement may damage sensitive electronic components. The test accuracy and scope can be significantly reduced by constant monitoring. However, this must be determined on an applicationspecific basis. Acceptance and risk evaluation of comprehensive RCM monitoring by an expert or the employers' liability insurance association is advisable, although not mandatory. It is also explicitly noted at this point that the following work must be carried out despite constant RCM measurement: Visual inspection for externally visible defects Protective measures and switch-off conditions Loop resistances and testing of the continuity of ground wires Function tests 8

9 Association of insurers requires RCM The VdS has said the following on the subject of power supply systems: "In the case of power supply systems with PEN phase, operational currents - which may cause damage - flow through the entire ground and potential equalisation system (see section 3.3). With new electrical system installations it is therefore necessary to plan TN systems as TN-S systems. In the case of existing TN-C systems, modification to a TS-S system is advised. TN-S systems must be realised from the supply (handover) point where possible. In order to guarantee the functionality of a TN-S system on a permanent basis (no conductor short between the N and PE phase, interchanging of the N and PE phase) this must be monitored by a residual current measurement device (RCM). If the set trigger value is reached, a perceivable optical and acoustic error signal must be issued, in order that the defect can be eliminated immediately. In order that signal issuance is successful, this should be sent to a manned desk where applicable. If signalling is dispensed with then the forced shut-down of the faulty current circuit is required..." Planning residual current monitoring Planning can be roughly divided into the following steps: Risk estimation Stipulate measuring points (with residual currents, it must be possible to quickly locate fault sources) Construct measurable distribution systems Label CGP and test points clearly Stipulate, document and set threshold values Stipulate two autonomous signal routes (signal on site, signal in a permanently manned control centre) Test signal routes by imprinting faults (function testing) Train personnel on site (actions in case of a fault) Acceptance by an expert is advisable Image 10: Comprehensive RCM monitoring of the power supply takes place at all levels: From CGP and outputs requiring monitoring in the LVDS, subdistribution systems, right through to individual critical loads. 9

10 Summary and outlook Comprehensive RCM monitoring of the power supply takes place at all levels: From CGP and outputs requiring monitoring in the LVDS and sub-distribution systems, right through to individual critical loads (image 10). However, RCM is a monitoring measure through which to ensure a reliable power supply. Janitza has its UMG 512- PRO (image 11), UMG 96RM-E and UMG 20CM series for this. Together with the GridVis energy data acquisition software and the integrated alarm management, solutions for three areas are united within a common system environment and just one measuring device per measurement point: Energy management according to ISO (acquisition of V, A, Hz, kwh, kw, kvarh, kvar ) Power quality monitoring (harmonics, flicker, voltage dips, transients, etc.) Residual current monitoring RCM This consolidation of the three different functions within a single measuring device brings with it the major advantage that both the assembly and installation, as well as the remaining infrastructure (current transformer, communication lines and equipment, database, software, analysis tools and reporting software, etc.) are only Image 11: The 3-in-1 power quality analyser from Janitza: UMG 512-PRO. required once. Furthermore, all data is logged centrally in a database and can be conveniently processed with a single software application, which in turn significantly increases the acceptance among users. Source references: VdS (Association of Insurers) DIN VDE standards BG: DGUV Specification 3 Electrical systems and operating equipment (BGV A 3) ((Image Source)) Janitza electronics GmbH 10

11 Smart Energy & Power Quality Solutions Janitza electronics GmbH Vor dem Polstück 6 D Lahnau Germany Tel.: Fax: info@janitza.de Document no.: Edition 07/2017 All rights to technical changes are reserved. Important Message Janitza electronics GmbH offers a collection of application reports addressed with in-depth expertise on the topics of Power Quality Monitoring (PQM), Power Management (PM), Power Quality Solutions (PQS), Residual Current Monitoring (RCM) and Energy Management Systems (EnMS). Furthermore, case studies and reference projects are treated. These application notes are meant to our worldwide distributors and agents, as well as its own sales people to train and provide the necessary basic knowledge. On the other hand, they should serve to answer repetitive questions quickly and new trends technically to be transmitted. Each issue covers a self-contained application theme, a specific solution or a technical topic of general interest. It is to share the broad application know-how of Janitza electronics GmbH and its experts, which was established with partners from the PQM, PM, PQS, RCM and EnMSover a long-term period around the world. Some parts of this publication may make statements on the application, use or availability in certain fields or applications. These statements are based on our experience, typical uses and typical requirements associated with specific applications. However, it is the customer or the user to check whether a product of Janitza electronics GmbH with its specifications and standards specified for the particular use is applicable. This application report may be amended by us without further information and brought up to date. This is indicated by the document number. Our products are specified in detail in our catalogues and manuals.

Smart Energy & Power Quality Solutions. Portable energy measurement devices COMPACT FLEXIBLE PRECISE

Smart Energy & Power Quality Solutions. Portable energy measurement devices COMPACT FLEXIBLE PRECISE Portable energy measurement devices COMPACT FLEXIBLE PRECISE Portable energy measurement devices COMPACT FLEXIBLE PRECISE The portable energy measurement devices from Janitza Stay flexible with the portable

More information

Smart Energy & Power Quality Solutions. Residual current monitoring (RCM) and energy data acquisition in a single device

Smart Energy & Power Quality Solutions. Residual current monitoring (RCM) and energy data acquisition in a single device Smart Energy & Power Quality Solutions Residual current monitoring (RCM) and energy data acquisition in a single device The RCM system solution RCM Modbus GridVis Analysis software Harmonics Alarm management

More information

Smart Energy & Power Quality Solutions. UMG 96RM Universal measurement instrument (EN 50160, IEEE 519, ITIC)

Smart Energy & Power Quality Solutions. UMG 96RM Universal measurement instrument (EN 50160, IEEE 519, ITIC) Smart Energy & Power Quality Solutions UMG 96RM Universal measurement instrument (EN 50160, IEEE 519, ITIC) UMG 96RM UMG 96RM Universal measurement instrument Unrivalled in its class The UMG 96RM is a

More information

Networks IT, TN, TT networks 3 and 4-phase networks Up to 4 single-phase networks. Measured data memory 256 MByte Flash 32 MB SDRAM

Networks IT, TN, TT networks 3 and 4-phase networks Up to 4 single-phase networks. Measured data memory 256 MByte Flash 32 MB SDRAM Power quality Colour graphical display Ethernet connection Ethernet-Modbus gateway Graphic programming Alarm management UMG 508 Multifunction power analyser Communication Profibus (DP/V0) Modbus (RTU,

More information

UMG 96L / UMG 96. UMG 96L / UMG 96 Universal measurement device. Threshold value monitoring. Pulse outputs. Networks TN-, TT-Networks

UMG 96L / UMG 96. UMG 96L / UMG 96 Universal measurement device. Threshold value monitoring. Pulse outputs. Networks TN-, TT-Networks Threshold value monitoring Pulse outputs UMG 96L / UMG 96 Universal measurement device Measuring accuracy Energy: Class 2 Current.../1 A,.../5 A Voltage L - N: ± 1 % Networks TN-, TT-Networks 2 digital

More information

Power quality Harmonics up to 40th harmonic Rotary field components Distortion factor THD-U / THD-I

Power quality Harmonics up to 40th harmonic Rotary field components Distortion factor THD-U / THD-I Memory 256 MB Alarm management Residual current measurement Homepage Ethernet-Modbus gateway BACnet (optional) UMG 96 RM-E Power analyser with Ethernet and RCM Communication Modbus (RTU, TCP, Gateway)

More information

Transienten. Datenspeicher

Transienten. Datenspeicher 25. 40. 63. Grenzwertüberwachung Oberschwingungen Power quality RCM Residual current monitoring Transienten Ethernet connection Ethernet-Modbus gateway Graphic programming Alarm management 32 MB 128 MB

More information

Dimension diagrams All dimensions in mm. Typical connection UMG 604-PRO. Power Analyser UMG 604-PRO. Front view. Side view. Versorgungsspannung

Dimension diagrams All dimensions in mm. Typical connection UMG 604-PRO. Power Analyser UMG 604-PRO. Front view. Side view. Versorgungsspannung Dimension diagrams All dimensions in mm 73 mm 10 mm 35 mm 44 mm 90 mm 90 mm 107,5 mm 50 mm 76 mm 82 mm Front view Side view Typical connection An. In R32 RS485 Dig. I/O Versorgungsspannung Auxiliary Supply

More information

UMG 509-PRO. Multifunction power analyser with RCM

UMG 509-PRO. Multifunction power analyser with RCM UMG 509-PRO Multifunction power analyser with RCM Power quality RCM Residual current monitoring Ethernet connection Ethernet-Modbus gateway Graphic programming Alarm management Communication Profibus (DP/V0)

More information

Catalogue 2016: Issue July. The 3-in-1 of energy measuring technology: Energy management, power quality, residual current monitoring

Catalogue 2016: Issue July. The 3-in-1 of energy measuring technology: Energy management, power quality, residual current monitoring Smart Energy & Power Quality Solutions Catalogue 2016: Issue July The 3-in-1 of energy measuring technology: Energy management, power quality, residual current monitoring Catalogue 2016 01 02 03 04 05

More information

Power quality Harmonics up to 40th harmonic Unbalance, rotary field indication Distortion factor THD-U / THD-I

Power quality Harmonics up to 40th harmonic Unbalance, rotary field indication Distortion factor THD-U / THD-I Harmonics Temperature input Measurement accuracy 0.5 Memory 4 MByte UMG 104 Energy measurement device for DIN rails Communication Profibus (DP / V0 optional) Modbus RTU Power quality Harmonics up to 40th

More information

Catalogue 2018 Issue January POWER SIMPLY SAVE. Energy management, Power quality monitoring and analysis, Residual current monitoring (RCM)

Catalogue 2018 Issue January POWER SIMPLY SAVE. Energy management, Power quality monitoring and analysis, Residual current monitoring (RCM) Smart Energy & Power Quality Solutions Catalogue 2018 Issue January POWER SIMPLY SAVE Energy management, Power quality monitoring and analysis, Residual current monitoring (RCM) Catalogue 2018 01 02 03

More information

PEM353. Universal measuring device

PEM353. Universal measuring device 353 Universal measuring device 353_D00335_00_D_XXEN/06.2018 353 Universal measuring device Product description The digital universal measuring device 353 is used to record and display measured quantities

More information

MRG 512-PRO PQ Flex Mobile universal measurement device Supplementary description to the operation manual UMG 512-PRO

MRG 512-PRO PQ Flex Mobile universal measurement device Supplementary description to the operation manual UMG 512-PRO Doc. no. 2.054.018.2 Subject to technical changes. www.janitza.com Mobile universal measurement device MRG 512-PRO PQ Flex Supplementary description to the operation manual UMG 512-PRO Janitza electronics

More information

Current / residual current and voltage transformers. Current / residual current and voltage transformers

Current / residual current and voltage transformers. Current / residual current and voltage transformers Current / residual current and voltage transformers Current / residual current and voltage transformers 1 Overview Current transformer overview DIN rail current transformer with fuse Current transformer...

More information

MRG 96RM-E Flex RCM Mobile universal measurement device Supplementary description to the operation manual UMG 96RM-E

MRG 96RM-E Flex RCM Mobile universal measurement device Supplementary description to the operation manual UMG 96RM-E Doc. no. 2.040.127.0.b Subject to technical changes. www.janitza.com Mobile universal measurement device MRG 96RM-E Flex RCM Supplementary description to the operation manual UMG 96RM-E Janitza electronics

More information

We take care of it. Special Publication. Power Quality PQ-Box 100/200. Expert opinions: Emergency power supply for hospitals and computer centres.

We take care of it. Special Publication. Power Quality PQ-Box 100/200. Expert opinions: Emergency power supply for hospitals and computer centres. We take care of it. Special Publication Power Quality PQ-Box 100/200 Expert opinions: Emergency power supply for hospitals and computer centres. Power Quality PQ-Box 100/200 Emergency power supply for

More information

VARIMETER. Residual current monitor (RCM) Insulation monitoring device (IMD) Insulation fault detection system (EDS) Our experience. Your safety.

VARIMETER. Residual current monitor (RCM) Insulation monitoring device (IMD) Insulation fault detection system (EDS) Our experience. Your safety. VARIMETER Residual current monitor (RCM) Insulation monitoring device (IMD) Insulation fault detection system (EDS) Our experience. Your safety. Residual current and insulation monitoring Maximum availability,

More information

KNX Powerline PL 110. KNX Association

KNX Powerline PL 110. KNX Association KNX Powerline PL 110 Table of Contents 1 Introduction...3 2 Standardisation...3 3 Transmission Process...4 3.1 Phase Coupling...5 3.2 Telegram Transmission...6 3.2.1 Training Sequence...6 3.2.2 Preamble

More information

Why the IT system is often the best choice for power supply systems of all types

Why the IT system is often the best choice for power supply systems of all types Why the IT system is often the best choice for power supply systems of all types Let us start initially with a clear commitment: the IT system ("unearthed system") is a type of system infrequently used

More information

Caution - leakage currents! Leakage currents in fault-current protected environments

Caution - leakage currents! Leakage currents in fault-current protected environments Caution - leakage currents! Leakage currents in fault-current protected environments Herbert Blum Product Manager EMC > General situation > Leakage current vs. fault current > Leakage currents from frequency

More information

UMG 96RM Basic Device

UMG 96RM Basic Device Smart Energy & Power Quality Solutions Power Analyser Basic Device Data sheet Dok.-Nr. 2.040.172.0 02/2019 DEVICE VIEWS Front view Rear view Side view Bottom view max. 6 96 91,5 104 91,5 97 42 Cut-out

More information

Digital Fault Recorder Deployment at HVDC Converter Stations

Digital Fault Recorder Deployment at HVDC Converter Stations Digital Fault Recorder Deployment at HVDC Converter Stations On line continuous monitoring at HVDC Converter Stations is an important asset in determining overall system performance and an essential diagnostic

More information

METRATESTER 5+ Tester for DIN VDE /6.15

METRATESTER 5+ Tester for DIN VDE /6.15 3-348-817-03 15/6.15 Applications Electrical safety testing of electrical equipment: per DIN VDE 0701-0702: 2008 by means of measurement of: Protective conductor resistance Insulation resistance Protective

More information

Power Quality Solutions PQSine P-Series of Active Harmonic Filters and Power Optimizers

Power Quality Solutions PQSine P-Series of Active Harmonic Filters and Power Optimizers EPCOS Product Brief 2017 Power Quality Solutions of Active Harmonic Filters and Power Optimizers EPCOS has been offering a comprehensive range of key components for power factor correction (PFC) and power

More information

1 2 3 GridVis Pulse output 2 tariffs Modbus MID M-Bus

1 2 3 GridVis Pulse output 2 tariffs Modbus MID M-Bus speicher MID energy meter ECSEM series Emax 2 Tariffs GridVis 7 Tariffs 8 Tariffs 14 Tariffs 0,2 kwh Class 0,5 kwh Class 1,0 kwh Class Pulse output Tarife 2 tariffs Messgenauigkeit Modbus MID M-Bus eratureingang

More information

Smart Energy & Power Quality Solutions. Power Quality Analyser UMG 512-PRO. Data sheet

Smart Energy & Power Quality Solutions. Power Quality Analyser UMG 512-PRO. Data sheet Smart Energy & Power Quality Solutions Power Quality Analyser Data sheet Dok.-Nr. 2.054.030.0 02/2019 DEVICE VIEWS Front view Rear view Side view Bottom view Cut-out size: 92 +0,8 mm x 92 +0,8 mm. All

More information

Safe and efficient power transmission in wind turbines

Safe and efficient power transmission in wind turbines Totally Integrated Power SIVACON 8PS Safe and efficient power transmission in wind turbines LDM busbar trunking system www.siemens.com/busbar Contents Totally Integrated Power 2 SIVACON 8PS busbar trunking

More information

Current Module, 3-channel, MDRC SM/S , GH Q R0111

Current Module, 3-channel, MDRC SM/S , GH Q R0111 , GH Q631 0034 R0111 SK 0086 B 99 Load and residual currents can be measured simultaneously using the current module. There are 3 isolated and independent measuring circuits available for this. The current

More information

PHOENIX CONTACT - 05/2008. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area.

PHOENIX CONTACT - 05/2008. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area. Primary-switched power supply with SFB technology, 1 AC, output current 20 A INTERFACE Data Sheet 103129_en_01 PHOENIX CONTACT - 05/2008 1 Description QUINT POWER power supply units highest system availability

More information

UMG 103. UMG 103 Universal measurement device for DIN rails. GridVis Analysis software. Harmonics. Measurement accuracy 0.5.

UMG 103. UMG 103 Universal measurement device for DIN rails. GridVis Analysis software. Harmonics. Measurement accuracy 0.5. Harmonics GridVis Analysis software Modbus interface Measurement accuracy 0.5 Universal measurement device for DIN rails Communication Protocols: Modbus RTU / Slave Interface RS485 Power quality Harmonics

More information

Residual Current Operated Circuit-Breakers (RCCBs)

Residual Current Operated Circuit-Breakers (RCCBs) Product Overview Residual Current Operated Circuit-Breakers (RCCBs) Residual current operated circuit-breakers Number of poles Rated current A Rated residual current ma MW Auxiliary contacts can be mounted

More information

Reactive Power Control Relay RM 2106 / 2112 Operating Instructions. FRAKO Kondensatoren- und Anlagenbau

Reactive Power Control Relay RM 2106 / 2112 Operating Instructions. FRAKO Kondensatoren- und Anlagenbau Reactive Power Control Relay RM 2106 / 2112 Operating Instructions FRAKO Kondensatoren- und Anlagenbau www.frako.com Figure 1 Front view a b c d e Display for active capacitor stages Display for inductive

More information

QUINT-PS/ 1AC/24DC/20

QUINT-PS/ 1AC/24DC/20 Primary-switched power supply with SFB technology, 1 AC, output current 20 A INTERFACE Data sheet 103129_en_04 1 Description PHOENIX CONTACT - 02/2010 Features QUINT POWER power supply units Maximum system

More information

PQ-Box 100 Network Analyzer for Low-, Medium- and High-Voltage Networks

PQ-Box 100 Network Analyzer for Low-, Medium- and High-Voltage Networks GB Technical data Issue 06/2009 PQ-Box 100 Network Analyzer for Low-, Medium- and High-Voltage Networks Fault detection Evaluation of voltage quality according to EN50160 and IEC61000-2-2 Fault recorder

More information

Testing and Certification.

Testing and Certification. Testing and Certification The VDE Institute is a worldwide partner for industry customers, business, government authorities, the electrical trade and consumers. www.vde.com/institute Our world is changing.

More information

QUINT-PS/ 3AC/24DC/10

QUINT-PS/ 3AC/24DC/10 Primary-switched power supply with SFB technology, 3 AC, output current 10 A INTERFACE Data sheet 103131_en_01 1 Description PHOENIX CONTACT - 09/2009 Features QUINT POWER power supply units Maximum system

More information

PHOENIX CONTACT - 06/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

PHOENIX CONTACT - 06/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area. Primary-switched power supply with SFB technology, 1 AC, output current 20 A INTERFACE Data Sheet 103383_en_00 1 Description PHOENIX CONTACT - 06/2008 Features QUINT POWER power supply units highest system

More information

TN, TT & IT Earthing Arrangements

TN, TT & IT Earthing Arrangements TN, TT & IT Earthing Arrangements In IT and TN-C networks, residual current devices are far less likely to detect an insulation fault. In a TN-C system, they would also be very vulnerable to unwanted triggering

More information

ENERIUM. A powerful solution for energy management and the environment

ENERIUM. A powerful solution for energy management and the environment ENERIUM A powerful solution for energy management and the environment Sustainable development A responsible commitment Vital for the production of all the products and services we consume, electricity

More information

UMG 509-PRO Power Quality Analyser User manual and technical data Part no Doc. no

UMG 509-PRO Power Quality Analyser User manual and technical data Part no Doc. no Part no. 33.03.217 Power Quality Analyser User manual and technical data www.janitza.com Doc. no. 2.059.011.2.g 01/2019 Janitza electronics GmbH Vor dem Polstück 6 D-35633 Lahnau Support tel. +49 6441

More information

Power Quality and Energy Measurement PEM575

Power Quality and Energy Measurement PEM575 Power Quality and Energy Measurement _D00016_03_D_XXEN/12.2015 Power Quality and Energy Measurement Product description The digital universal measuring device is suited for measuring and displaying electrical

More information

Side view View from below Rear view

Side view View from below Rear view Dimension diagrams All dimensions in mm Side view View from below Rear view Cut out: 138 +0,8 x 138 +0,8 mm Typical connection SPS SPS 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 DSUB-9 5 4 3 2 1 8 7 6 5 4

More information

Power Quality and Energy Measurement PEM533

Power Quality and Energy Measurement PEM533 Power Quality and Energy Measurement _D00013_02_D_XXEN/11.2014 Power Quality and Energy Measurement 0.5 S Product description The digital universal measuring device is suited for measuring and displaying

More information

Power quality report. A Manufacturing Plant

Power quality report. A Manufacturing Plant Power quality report Prepared for A Manufacturing Plant 6 May 2016 by Dr Angelo De Francesco Power Quality Consultant Page 1 Contents 1 EXECUTIVE SUMMARY... 4 2 INTRODUCTION... 5 2.1 SITE MONITORED...

More information

Orbital GFI Inverter Series

Orbital GFI Inverter Series Orbital GFI Inverter Series Datasheet Key Features One, split or three phases and up to 25 kva Superior efficiency of 95% CAN Bus control and DAQ Power quality and EMC compliance in accordance with European

More information

Accessories. Accessories

Accessories. Accessories Accessories Accessories Voltage transformer Voltage transformer Powerful and precise Input, 3-pole Output is 3-pole + N Use in IT networks without neutral line For reducing the measurement voltage for

More information

CROSS Chassis from 160 A to 450 A

CROSS Chassis from 160 A to 450 A CROSS Chassis from 160 A to 450 A STS CATALOGUE Important note! The technical data enclosed is for general information. Please note that the operating instructions and references indicated on the products

More information

UMG 512 Operation manual and technical data

UMG 512 Operation manual and technical data Part no. 33.03.196 (UL) Power Quality Analyser UMG 512 Operation manual and technical data www.janitza.com Doc no. 2.054.009.0.p Janitza electronics GmbH Vor dem Polstück 1 D-35633 Lahnau Support Tel.

More information

UMG 512-PRO Power Quality Analyser User manual and technical data Part no Doc. no d 01/2018

UMG 512-PRO Power Quality Analyser User manual and technical data Part no Doc. no d 01/2018 Part no. 33.03.196 Power Quality Analyser User manual and technical data Doc. no. 1.054.009.2.d 01/2018 Janitza electronics GmbH Vor dem Polstück 6 D-35633 Lahnau Support tel. +49 6441 9642-22 Fax +49

More information

Device Interconnection

Device Interconnection Device Interconnection An important, if less than glamorous, aspect of audio signal handling is the connection of one device to another. Of course, a primary concern is the matching of signal levels and

More information

2.7. IT system floor-standing distribution cabinet Series -IPS-F/EDS

2.7. IT system floor-standing distribution cabinet Series -IPS-F/EDS Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 65 35305 Grünberg Tel.: 0640 807-0 Fax: 0640 807-259 IT system floor-standing distribution cabinet Series -IPS-F/EDS for supplying power to medical locations

More information

QUINT-PS/ 3AC/24DC/40

QUINT-PS/ 3AC/24DC/40 Primary-switched power supply unit with SFB technology, 3 AC, output current 40 A INTERFACE Data sheet 103133_en_00 1 Description PHOENIX CONTACT - 07/2009 Features QUINT POWER power supply units Maximum

More information

AC/DC sensitive residual current monitoring module RCMB121-

AC/DC sensitive residual current monitoring module RCMB121- AC/DC sensitive residual current monitoring module RCMB121- for safe charging of electrical vehicles according to IEC 62752 for IC-CPD and IEC 60364-7-722 for Wall Boxes Preliminary datasheet Vorläufiges

More information

QUINT-PS AC/24DC/40

QUINT-PS AC/24DC/40 Power supply unit INTERFACE Data sheet 102315_en_02 1 Description PHOENIX CONTACT 2010-04-23 Features QUINT POWER power supply units for plant and special engineering reliably start heavy loads with high

More information

Power factor correction and harmonic filtering. Automatic power factor regulators

Power factor correction and harmonic filtering. Automatic power factor regulators Power factor correction and harmonic filtering Automatic power factor regulators Automatic power factor reguladors R.1 - Automatic power factor regulators Selection table R1-4 computer Plus-T Intelligent

More information

UNDERSTANDING POWER QUALITY

UNDERSTANDING POWER QUALITY Technical Note No. 1 June 1998 UNDERSTANDING POWER QUALITY This Technical Note describes the range of problems, what causes them, what they affect and what could be done to manage them. Integral Energy,

More information

UMG 96L. Universal Measuring Device. Operating Instructions. Brief instructions see last page

UMG 96L. Universal Measuring Device. Operating Instructions. Brief instructions see last page Art. Nr. 33.03.053 Universal Measuring Device UMG 96L Operating Instructions Brief instructions see last page Supply Mean value www.janitza.de Peak value Minimum value Key 1 Key 2 Programming mode Sum

More information

P331-2 set ESD generator (IEC )

P331-2 set ESD generator (IEC ) User manual Probe set set ESD generator (IEC 61000-4-2) Copyright January 2017 LANGER GmbH 2017.01.09 User manual Table of contents: Page 1 ESD generator (IEC 61000-4-2) 3 1.1 Design and function of the

More information

ELECTRICAL POWER ENGINEERING

ELECTRICAL POWER ENGINEERING Introduction This trainer has been designed to provide students with a fully comprehensive knowledge in Electrical Power Engineering systems. The trainer is composed of a set of modules for the simulation

More information

MINI-PS AC/24DC/1.3

MINI-PS AC/24DC/1.3 Power supply unit INTERFACE Data sheet 102894_en_03 1 Description PHOENIX CONTACT 2015-11-17 Features MINI POWER power supplies for MCR technology In measurement and control technology (MCR), modular electronics

More information

Power systems 2: Transformation

Power systems 2: Transformation Power systems 2: Transformation Introduction In this series of articles, we will be looking at each of the main stages of the electrical power system in turn. s you will recall from our Introduction to

More information

Power Distribution System SVS18

Power Distribution System SVS18 Power Distribution System SVS8 Description The power distribution system SVS8 optimises the DC V distribution in automation and process control, in the production area of the chemical industry and in power

More information

E S C R I P T I V E B U L L E T I N .,.,.,. Bulletin DB-106. October, Square D Company Power System Studies ---1 I SQU ARED COMPANY --

E S C R I P T I V E B U L L E T I N .,.,.,. Bulletin DB-106. October, Square D Company Power System Studies ---1 I SQU ARED COMPANY -- D.,.,.,. E S C R I P T I V E B U L L E T I N Bulletin DB-106 Square D Company October, 1990 ---1 I SQU ARED COMPANY -- Electrical Power Distribution System - The Heart of the Business From small commercial

More information

Power Quality Report. A Manufacturing Plant

Power Quality Report. A Manufacturing Plant Power Quality Report Prepared for A Manufacturing Plant 6 May 2016 by Dr Angelo De Francesco Power Quality Consultant CHK Power Quality Pty Ltd Page 1 Contents 1 EXECUTIVE SUMMARY... 4 2 INTRODUCTION...

More information

Application note. 0 % / 70 % feed-in regulation

Application note. 0 % / 70 % feed-in regulation Application note 0 % / 70 % feed-in regulation Application note 0 % / 70 % feed-in regulation PV feed-in regulation depending on owner's electricity consumption Contents Precondition.... Balancing settlement

More information

Device circuit breakers Selective power distribution: branch out, individual adaptation, modular extension

Device circuit breakers Selective power distribution: branch out, individual adaptation, modular extension Power & Signal Quality TRABTECH Device circuit breakers Selective power distribution: branch out, individual adaptation, modular extension Interference-free mains supply and signal transmission A constant

More information

Residual current circuit breakers (RCCBs)

Residual current circuit breakers (RCCBs) Residual current circuit breakers (RCCBs) Description Automatically trips in event of earth leakage fault Provides protection against direct & indirect contact with live parts Technical data IS 12640-1,

More information

QUINT-PS-24DC/24DC/10

QUINT-PS-24DC/24DC/10 QUINT-PS-24/24/10 QUINT - converter, primary switched mode, input: 24 V, output: 24 V /10 A INTERFACE Data Sheet PHOENIX CONTACT - 02/2006 Description The QUINT - converter 24 V/10 A converts the voltage

More information

Power Quality under the microscope

Power Quality under the microscope We take care of it. Power Quality Power Quality under the microscope Change in the producer and consumer structure The change in the producer and consumer structure of the Central European power grids

More information

Totally Integrated Power SIVACON 8PS LDM busbar trunking system siemens.com/ldm-system

Totally Integrated Power SIVACON 8PS LDM busbar trunking system siemens.com/ldm-system Safe and efficient power transmission in wind turbines Totally Integrated Power SIVACON 8PS LDM busbar trunking system siemens.com/ldm-system Contents Totally Integrated Power 2 SIVACON 8PS busbar trunking

More information

FIB / FIC. r with Overcurrent Protection (RCBO) Doepke. » effi cient. » reliable. » fl exible. » future-oriented

FIB / FIC. r with Overcurrent Protection (RCBO) Doepke. » effi cient. » reliable. » fl exible. » future-oriented Doepke The experts in residual current protection technology Residual Current Circuit-Breakers it- r with Overcurrent Protection (RCBO) FIB / FIC» effi cient» reliable» fl exible» future-oriented Doepke

More information

Excitation Systems THYRIPART. Compound-Excitation System for Synchronous Generators. Power Generation

Excitation Systems THYRIPART. Compound-Excitation System for Synchronous Generators. Power Generation Excitation Systems Compound-Excitation System for Synchronous Generators Power Generation Operating Characteristics Load dependent Short circuit supporting Low voltage gradient dv/dt Black start capability

More information

Welcome to the rd. Annual Northern Ohio. 3 rd Energy Management Conference September 30, 2008

Welcome to the rd. Annual Northern Ohio. 3 rd Energy Management Conference September 30, 2008 Welcome to the rd Annual Northern Ohio 3 rd Energy Management Conference September 30, 2008 Recover Lost Dollars Demand Side Electrical Energy Savings By Improving Distribution System Efficiency, Capacity

More information

Produkt-Datenblatt. Technische Daten, Spezifikationen. MEsstechnik fängt mit ME an. Kontakt

Produkt-Datenblatt. Technische Daten, Spezifikationen. MEsstechnik fängt mit ME an.  Kontakt Produkt-Datenblatt Technische Daten, Spezifikationen Kontakt Technischer und kaufmännischer Vertrieb, Preisauskünfte, Angebote, Test-Geräte, Beratung vor Ort: Tel: (0 81 41) 52 71-0 FAX: (0 81 41) 52 71-129

More information

ABB i-bus EIB / KNX Analogue Input AE/S 4.2

ABB i-bus EIB / KNX Analogue Input AE/S 4.2 Product Manual ABB i-bus EIB / KNX Analogue Input AE/S 4.2 Intelligent Installation Systems This manual describes the functionality of Analogue Input AE/S 4.2. Subject to changes and errors excepted. Exclusion

More information

TEST REPORT DIN V VDE V :2006 Automatic disconnecting device

TEST REPORT DIN V VDE V :2006 Automatic disconnecting device age 1 of 23 TEST REORT Automatic disconnecting device Report Reference No...: GZ10080033-1 Date of issue...: August 18, 2010 Total number of pages... 23 pages Testing Laboratory...: Address...: Tested

More information

Keep the power running safely at sea. Vigilohm Insulation Monitoring For reliable electrical network availability in Marine

Keep the power running safely at sea. Vigilohm Insulation Monitoring For reliable electrical network availability in Marine Keep the power running safely at sea Vigilohm Insulation Monitoring For reliable electrical network availability in Marine 2 3 What is at stake on a ship? Ships are a very unique type of building. When

More information

QUICK SETUP GUIDE SECULIFE IP

QUICK SETUP GUIDE SECULIFE IP QUICK SETUP GUIDE SECULIFE IP The SECULIFE IP is capable of executing all measurements for testing the effectiveness of safety measures in electrical systems as required by IEC 60364-4 / VDE 0100-600,

More information

RUDOLF Digital power analyzer. Advanced Version

RUDOLF Digital power analyzer. Advanced Version RUDOLF Digital power analyzer Advanced Version Digital power analyzer Advanced Version Company Introduction Bridex Singapore Pte Ltd is founded in 1978 as a manufacturer of instruments transformer for

More information

Power Quality and Energy Measurement PEM575

Power Quality and Energy Measurement PEM575 Power Quality and Energy Measurement _D00016_00_D_XXEN/06.2013 Power Quality and Energy Measurement Product description The digital universal measuring device is suited for measuring and displaying electrical

More information

Cable test vans and systems

Cable test vans and systems Cable test vans and systems Prepared for anything BAUR s cable fault location and diagnostics systems Would you like to test and assess new installations and existing cable locations efficiently? To rectify

More information

UMG 103-CBM. Universal measurement device for DIN rails

UMG 103-CBM. Universal measurement device for DIN rails Universal measurement device for DIN rails Harmonics GridVis Analysis software Modbus interface Measurement accuracy 0.5 Communication Protocols: Modbus RTU / Slave Interface RS485 Accuracy of measurement

More information

Power Processor - Series 700F 10KVA to 150KVA

Power Processor - Series 700F 10KVA to 150KVA Power Processor - Series 700F 10KVA to 150KVA Power Conditioning and Regulation for Commercial & Industrial Equipment General Specifications PART 1 - GENERAL 1.1 DESCRIPTION This specification defines

More information

PHOENIX CONTACT - 09/2009

PHOENIX CONTACT - 09/2009 Electronic miniature circuit-breaker CLIPLINE Data sheet 03906_en_0 PHOENIX CONTACT - 09/2009 Description The EC-E... electronic miniature circuit-breaker selectively protects all 24 V DC load circuits

More information

METRAClip87 and 88 Clamp Multimeters

METRAClip87 and 88 Clamp Multimeters 3-349-795-03 1/7.14 Current and frequency measurement via clamp meter: METRAClip87: 1500 A AC TRMS and 1500 A DC METRAClip88: 2000 A AC TRMS and 3000 A DC Multimeter functions via connector sockets: V

More information

Network Analyzer for Low-, Medium- and High-Voltage Networks

Network Analyzer for Low-, Medium- and High-Voltage Networks Technical data Network nalyzer for Low-, Medium- and High-Voltage Networks Model PQ-Box 150 1 Fault detection 1 Evaluation of voltage quality according to EN50160 and IEC61000-2-2 (2-4) 1 FFT nalysis up

More information

Reliable power onboard and offshore

Reliable power onboard and offshore Reliable power onboard and offshore AccuSine PCS+ Active Harmonic Filters For electrical network reliability and quality in Marine 2 What causes harmonics in Marine applications? Power electronics with

More information

GOSSEN METRAWATT. Testers

GOSSEN METRAWATT. Testers Testers 45 Testers Protective measures in electrical systems are intended to prevent bodily injury due to accidents involving electrical current. Of course they also prevent property damage caused by electrical

More information

NETWORK INNOVATION COMPETITION ANGLE-DC PROJECT HOLISTIC CIRCUIT CONDITION MONITORING SYSTEM REPORT

NETWORK INNOVATION COMPETITION ANGLE-DC PROJECT HOLISTIC CIRCUIT CONDITION MONITORING SYSTEM REPORT NETWORK INNOVATION COMPETITION PROJECT HOLISTIC CIRCUIT CONDITION MONITORING SYSTEM REPORT NOVEMBER 17 Version: 1.0 Authored by: Andrew Moon Engineering Consultant and Project Manager Kevin Smith Lead

More information

Renewable energy Reliable and efficient use of the power of nature

Renewable energy Reliable and efficient use of the power of nature Renewable energy Reliable and efficient use of the power of nature Solutions for electrical safety Electrical safety for efficient use of renewable energy Making efficient and reliable use of natural energy

More information

Power Meter PQM (EnerSure Enkapsis) Guide Form Specification PART 1: GENERAL

Power Meter PQM (EnerSure Enkapsis) Guide Form Specification PART 1: GENERAL Power Meter PQM (EnerSure Enkapsis) Guide Form Specification PART 1: GENERAL 1.01 SUMMARY: The following technical specification describes the requirements of the high accuracy standalone 3 phase Power

More information

Product overview. Residual current monitoring. AC, pulsed DC and AC/DC sensitive residual current monitors RCM, RCMA, RCMB

Product overview. Residual current monitoring. AC, pulsed DC and AC/DC sensitive residual current monitors RCM, RCMA, RCMB Product overview Residual current monitoring AC, pulsed DC and AC/DC sensitive residual current monitors RCM, RCMA, RCMB Multi-channel, AC, pulsed DC and AC/DC sensitive residual current monitoring systems

More information

For Isotropic Measurement of Magnetic and Electric Fields

For Isotropic Measurement of Magnetic and Electric Fields Field Analyzers EFA-300 For Isotropic Measurement of Magnetic and Electric Fields Evaluation of Field Exposure compared to Major Standards and Guidance (selectable) Shaped Time Domain (STD) an innovative

More information

PHOENIX CONTACT

PHOENIX CONTACT Electronic circuit breaker CLIPLINE Data sheet 102898_en_03 PHOENIX CONTACT 2010-12-17 1 Description The electronic circuit breaker can be used in applications that cover all aspects of the switched-mode

More information

Power Quality implications of new residential appliances. EEA Conference & Exhibition 2010, June 2010, Christchurch

Power Quality implications of new residential appliances. EEA Conference & Exhibition 2010, June 2010, Christchurch Power Quality implications of new residential appliances Stewart Hardie 1 and Neville Watson 2 1 EPECentre, Christchurch, New Zealand 2 University of Canterbury, Christchurch, New Zealand Presenter: Stewart

More information

7P Series - Surge Protection Device (SPD) Features 7P P P

7P Series - Surge Protection Device (SPD) Features 7P P P Features 7P.09.1.255.0100 7P.01.8.260.1025 7P.02.8.260.1025 SPD Type 1+2 Surge arrester range - single phase system / three phase system Surge arresters suitable in low-voltage applications in order to

More information

Power Quality and Energy Measurement PEM735

Power Quality and Energy Measurement PEM735 Power Quality and Energy Measurement PEM75 PEM75_D00084_01_D_XXEN/01.2015 Power Quality and Energy Measurement PEM75 class A Product description The digital universal measuring device PEM75 is suited for

More information

measurement technology overview

measurement technology overview measurement technology overview measurement technology basic for successful energy management The right choice save money! Due to the majority of the costs of energy management system are with the infrastructure

More information

I -limiter The world s fastest switching device

I -limiter The world s fastest switching device I S -limiter 2 I S -limiter The world s fastest switching device Reduces substation cost Solves short-circuit problems in new substations and substation extensions Optimum solution for interconnection

More information