PC10 Intelligent Transmitter Configurator Version 4.0

Size: px
Start display at page:

Download "PC10 Intelligent Transmitter Configurator Version 4.0"

Transcription

1 Instruction MI April 1997 PC10 Intelligent Transmitter Configurator Version 4.0 Installation and Operation

2 MI April 1997

3 Contents Figures... Tables... ix xii 1. Introduction... 1 Overview... 1 Features... 1 PC10 Standard Equipment... 2 PC10 Optional Equipment... 2 Reference Documents... 3 Software License Installation... 5 Hardware Installation... 5 Software Installation... 6 Standard Installation... 6 Custom Installation... 6 System Defaults Operation... 7 Running PC Menu Structure... 9 On-line Help Password Protection PC10 Operation Reading Transmitter Measurements (Meas) Transmitter Calibration Functions (Calibrate) Configuring Transmitters (Configure) Moving Around on the Configuration Screen Changing Parameter Values on the Configuration Screen Exiting from the Configuration Screen Transmitter Diagnostics (Test) Xmtr Status Set ma/pulse Output (Loop Cal) Set Digital Output Go On-line iii

4 MI April 1997 Contents Go Off-line Display Raw Input DOS Shell Transmitter Database Storage (File) Save Xmtr to File Preconfigure Transmitter Write Config File to Xmtr Restore Xmtr from File Copy Xmtr File Delete Xmtr File Xmtr File Comments Select DOS Path Backup Database Files List Xmtr Files Transfer HHT Files Transfer Files from HHT to PC Transfer Files from PC to HHT Printing Transmitter Databases (Report) Report Type Report Data Report Destination Print/Quit On-line Help Screens (Help) PC10 Defaults Set PC10 Defaults Serial Port Printer Port Monitor Type Measurement Display Password Access Level Change PC10 Password Quit Appendix A. Troubleshooting PC10 Error Messages Diagnostic Procedures PC10 Files Transmitter Status Error Messages Transmitter Diagnostic Error Messages Appendix B. Calibration Data , 860, I/A Series Pressure Transmitters Functions iv

5 Contents MI April 1997 Calibration Re-Zero Transmitter Point Calibration Point Calibration ReRange ma Calibration Default Calibration Point Conversion (820 Transmitters Only) Point Conversion (820 Transmitters Only) RTT10 Temperature Transmitters Functions Calibration Re-Zero Transmitter Point Calibration Point Calibration ReRange Custom Input Curve ma Calibration Restore Factory Calibration Enable Custom Curve Restore Factory ma RTT20 Temperature Transmitters Point Calibration Point Calibration and 5- Point Calibration Custom Input Curve IMT10/IMT20 Magnetic Flow Transmitters Flow Calibration ReRange ma Calibration IMT25 Magnetic Flow Transmitters ma Calibration Reset Totals Empty Pipe Detect CFT10 Mass Flow Transmitters Re-Zero Transmitter ma Calibration Startup Zero Restore Factory ma Zero Total CFT15 Mass Flow Transmitters Re-Zero Transmitter Startup Zero Zero Total v

6 MI April 1997 Contents Vortex Flow Meters Functions ma Calibration ReRange Zero Total Set Low Flow Cut-In ITEC Electrodeless Conductivity Transmitters Top Level Menu Picks Restore Factory Calibration Screen Bench Calibration Screen Bench Calibration Screen 2 (Low Calibration Point) Bench Calibration Screen 3 (High Calibration Point) Solution 1 Pt Span Screen 1(Application 1) Solution 1 Pt Span Screen Solution 1-Point Offset (Screen 1) Solution 1-Point Offset (Screen 2) Solution 2 Point Calibration (Screen 1) Solution 2 Point Calibration (Screen 2) Solution 2 Point Calibration (Screen 3) Temperature Sensor Calibration (Screen 1) Temperature Sensor Calibration (Screen 2) ma Calibration (Screen 1) Default Calibration ITPH ph/orp/ise Transmitters Top Level Menu Picks Point Manual Calibration (Screen 1) Point Manual Calibration (Screen 2) Point Absolute Calibration (Screen 1) Point Absolute Calibration (Screen 2) Point Manual Calibration (Screen 1) Point Manual Calibration (Screen 2) Point Manual Calibration (Screen 3) Automatic Calibration (Screen 1) Automatic Calibration (Screen 2) Automatic Calibration (Screen 3) Temperature Sensor Calibration (Screen 1) Temperature Sensor Calibration (Screen 2) ma Calibration Default Calibration Appendix C. Configuration Data General Characteristics (All Transmitters) , 860, I/A Series Pressure Transmitter Configuration , 860 Configuration Screen vi

7 Contents MI April 1997 I/A Series Configuration Screen , 860, I/A Series Configuration Fields RTT10 Temperature Transmitter Configuration RTT10 Configuration Screen RTT10 Configuration Fields RTT20 Temperature Transmitter Configuration RTT20 Configuration Screens RTT20 Configuration Fields IMT10/IMT20 Magnetic Flow Transmitter Configuration IMT10/IMT20 Configuration Screen IMT10/IMT20 Configuration Fields IMT25 Magnetic Flow Transmitter Configuration IMT25 Configuration Screens IMT25 Configuration Fields CFT10 Mass Flowmeter Configuration CFT10 Configuration Screen CFT10 Configuration Fields CFT10 Configuration Screen (Screen 2) CFT10 Configuration Fields (Screen 2) CFT15 Mass Flowmeter Configuration CFT15 Configuration Screen CFT15 Configuration Fields Vortex Flowmeter Configuration Vortex Configuration Screen Vortex Configuration Fields ITEC Transmitter Configuration ITEC Configuration Screen # ITEC Configuration Fields (Screen #1) ITEC Configuration Screen # ITEC Configuration Fields (Screen #2) ITPH ph/orp/ise Transmitter Configuration ITPH Configuration Screen # ITPH Configuration Fields (Screen #1) ITPH Configuration Screen # ITPH Configuration Fields (Screen #2) Appendix D. Sample Reports Pressure Transmitter Reports Configuration Report Database Report Pressure Transmitter Reports Configuration Report vii

8 MI April 1997 Contents 860 Database Report I/A Series Pressure Transmitter Reports I/A Series Configuration Report I/A Series Database Report RTT10 Temperature Transmitter Reports RTT10 Configuration Report RTT10 Database Report RTT20 Temperature Transmitter Reports RTT20 Configuration Report RTT20 Database Report IMT10/IMT20 Magnetic Flow Transmitter Reports IMT10/IMT20 Configuration Report IMT10/IMT20 Database Report IMT25 Magnetic Flow Transmitter Reports IMT25 Configuration Report IMT25 Database Report CFT10 Mass Flowmeter Transmitter Reports CFT10 Configuration Report CFT10 Database Report CFT15 Mass Flowmeter Transmitter Reports CFT15 Configuration Report CFT15 Database Report Vortex Transmitter Reports Vortex Configuration Report Vortex Database Report ITEC Transmitter Reports ITEC Configuration Report ITEC Database Report ITPH Transmitter Reports ITPH Configuration Report ITPH Database Report Appendix E. Glossary Index viii

9 Figures 1 Connection Diagram Without Power Supply Option Connection Diagram With Power Supply Option Title Screen for PC Warning Message Screen PC10 Menu Structure PC10 Menu Structure Continued Top Level Menu Screen Enter Password Screen Measurement Screen (820 Flow Transmitter Example) Trend Display Calibration Options Menu (820 shown) Configuration Screen for 820 Series Transmitter Example: Setting Measurement Units for an 823DP-M Exiting from Configuration Screen Test - Diagnostic Functions Screen Transmitter Status (820) Test Set ma Output (Output Override) Test Set Pulse Output for CFT Test Display Raw Inputs (820) File Menu Screen Select a Database File Preconfigure Transmitter Database Screen Write Config File Screen Transmitter File List Screen File Option (820) Xmtr Comments File Option Add File Comments Select DOS Path Backup Database Files Screen Backup Database Files Screen Backup Database Files Screen List Xmtr Files Transfer HHT Files Menu Selection Transfer HHT Files Initial Screen Transfer HHT Files File Transfer Prompt Transfer HHT Files Sending File from HHT to PC Transfer HHT Files Receiving Records from HHT Transfer HHT Files Edit Filename Transfer HHT Files Initial Screen Transfer HHT Files File Transfer Prompt Transfer HHT Files Select Filename Transfer HHT Files Sending File from PC to HHT Report (Initial Screen) Select Report Data ix

10 MI April 1997 Figures 44 Set Report Destination Help Menu Screen PC10 Modem and Transmitter Connection Help Password Help Screen Set PC10 Defaults Screen Select Measurement Display Change Password Access Level Change PC10 Password Screen Fault Analysis Chart Point Calibration (820) ReRange Screen (820) ReRange Screen (820) (Alternate Screen) ma Calibrate Screen Default Calibration Screen Point Conversion Screen Point Conversion Screen Point Calibration (RTT10) ReRange Screen (RTT10) Custom Input Curve (RTT10) ma Calibrate Screen Flow Calibration (IMT20/IMT10) ReRange Screen (IMT20/IMT10) ma Calibrate Screen (IMT20/IMT10) Re-Zero Transmitter Screen 1 (CFT10) Re-Zero Transmitter Screen 2 (CFT10) ma Calibrate Screen CFT10 Startup Zero (1) CFT10 Startup Zero (2) ma Calibrate Screen ReRange Screen (Vortex) Zero Total Screen (Vortex) Set Low Flow Cut-In Display Current Setting Set Low Flow Cut-In Choose New Setting Set Low Flow Cut-In Automatic Selection in Progress Set Low Flow Cut-In Calibration Complete Top Level Menu Picks Restore Factory Calibration Screen Bench Calibration Screen Bench Calibration Screen 2 (Low Calibration Point) Bench Calibration Screen 3 (High Calibration Point) Solution 1 Pt Span (Screen 1) Solution 1 Pt Span (Screen 2) Solution 1-Point Offset (Screen 1) Solution 1-Point Offset (Screen 2) Solution 2 Point Calibration (Screen 1) Solution 2 Point Calibration (Screen 2) Solution 2 Point Calibration (Screen 3) Temperature Sensor Calibration (Screen 1) x

11 Figures MI April Temperature Sensor Calibration (Screen 2) ma Calibrate Screen Default Calibration Screen Top Level Menu Picks Point Manual Calibration (Screen 1) Point Manual Calibration (Screen 2) Point Absolute Calibration (Screen 1) Point Absolute Calibration (Screen 2) Point Manual Cal (Screen 1) Point Manual Cal (Screen 2) Point Manual Cal (Screen 3) Automatic Calibration (Screen 1) Automatic Calibration (Screen 2) Automatic Calibration (Screen 3) Temperature Sensor Calibration (Screen 1) Temperature Sensor Calibration (Screen 2) ma Calibrate Screen Default Calibration Screen , 860 Configuration Screen I/A Series Configuration Screen RTT10 Configuration Screen RTT20 Configuration Screen RTT20 Configuration Screen IMT20 Configuration Screen IMT25 Configuration Screen IMT25 Configuration Screen IMT25 Configuration Screen CFT10 Configuration Screen (Screen 1) CFT10 Configuration Screen (Screen 2) CFT15 Configuration Screen CFT15 Configuration Screen CFT15 Configuration Screen Vortex Configuration Screen ITEC Configuration Screen (1 of 2) ITEC Configuration Screen (2 of 2) ITPH Configuration Screen (1 of 2) ITPH Configuration Screen (2 of 2) xi

12 Tables 1 Measurement Information Displayed Calibration Options vs. Transmitter Type Configuration Options vs. Transmitter Type Status Message Password Access Levels Error Messages Transmitter Status Error Message Transmitter Diagnostic Error Messages , 860, I/A Series Configuration Fields RTT10 Configuration Fields RTT20 Configuration Fields IMT20 (IMT10) Configuration Fields IMT25 Configuration Fields CFT10 Configuration Fields Screen 1 of CFT10 Configuration Fields Screen 2 of CFT15 Configuration Fields Vortex Configuration Fields ITEC Configuration Fields Screen 1 of ITEC Configuration Fields Screen 2 of ITPHConfiguration Fields Screen 1 of ITPH Configuration Fields Screen 2 of xii

13 1. Introduction Overview The Model PC10 Configurator is a hardware/software package that supports remote communication and configuration for all Foxboro Intelligent Transmitters. It provides all of the functionality of the Foxboro Hand-Held Terminal (HHT) with the superior display, keyboard, storage, and printing capabilities of a personal computer system. Because more data can be displayed on a PC screen, virtually all operations require fewer keystrokes on the PC10 than they would on the HHT. Use of a PC allows additional functionality such as unlimited transmitter database storage, printouts, output trending, enhanced diagnostic capability, and on-line help screens. The package includes an external modem that allows operation with any IBM XT-compatible or better computer having a minimum of 495K RAM and a serial communication port. Communication with Intelligent Transmitters uses proven frequency shift keying (FSK) techniques that do not affect transmitter output signal. Operations can be password protected if desired one level allows recalibration and another level allows reconfiguration and recalibration. Whether used in conjunction with or as an alternative to the Hand-Held Terminal, the PC10 Configurator is a powerful and effective tool for improving efficiency of your engineering, installation, and maintenance operations. NOTE: A video tape describing the features, installation, and operation of the PC10 is included as part of the PC10 package. We recommend that you watch the video tape before installing and operating the PC10. Features Supports all Foxboro Intelligent Transmitters Emulates Hand-Held Terminal Functions - Accurate reranging without recalibration - Remotely set transmitter output to calibrate other devices in the loop - Preconfigure, copy, and clone databases - Upload and download transmitter databases Added Functionality - Unlimited transmitter database storage on floppy or hard disk - Upload/download databases to HHT Memory Paks - Full screen transmitter database display - Printout of transmitter databases - Output trending to aid in loop tuning (requires VGA monitor) - Three levels of password protection 1

14 MI April Introduction - Enhanced transmitter diagnostic capability - On-line help screens Reliable Communications - Field-proven FSK communication - RFI/EMI protection - Communications do not affect output - Read-after-write security Easy to Install - Works with any IBM-compatible PC (XT or better) - External proprietary modem - Automatic installation of software - No switches to set - Optional power supply attaches directly to modem PC10 Standard Equipment The standard PC10 product includes the following items: PC10 Software (high density 5.25 and 3.5 inch diskettes) One Foxboro PC10 external modem (may be attached by Velcro strips to back side of laptop computers) One 5-foot cable (desktop PC to modem) One 1-foot cable (laptop PC to modem) One 9-pin to 25-pin adapter One 5-foot cable for connecting the modem to transmitter loop wiring or for connecting the optional power supply to a transmitter Velcro strips Two test clips Instructional videotape PC10 Optional Equipment You may also specify the following optional items: Power supply (120 V ac-to-24 V dc) with cord. (Power supply is for the transmitter only when used with the PC10 the PC10 modem is powered through the computer serial port.) 2

15 1. Introduction MI April 1997 Reference Documents Transmitter Type Description Master Instruction I/A Series Intelligent Transmitters 820 Series Intelligent Transmitters 860 Series Intelligent Transmitters I/A Series Intelligent Pressure Transmitters IMT10 I/A Series Magflow Transmitters IMT20 I/A Series Magflow Transmitters IMT25 I/A Series Magflow Transmitters CFT10 Series Mass Flow Transmitters CFT15 Series Mass Flow Transmitters Vortex Intelligent Flowmeters 870ITEC Electrodeless Conductivity Transmitters 870ITPH ph/ise/orp Transmitters RTT10 Series Temperature Transmitters RTT20 Series Temperature Transmitters Wiring Guidelines MI Operation/Calibration/Configuration with HHT Operation/Calibration/Configuration with HHT Installation, Calibration, Configuration, and Maintenance Operation/Calibration/Configuration with HHT MI MI MI MI MI MI MI Operation/Calibration/Configuration MI Operation/Calibration/Configuration MI Operation/Calibration/Configuration MI with HHT Operation/Calibration/Configuration MI Operation/Calibration/Configuration MI with HHT Operation/Configuration with MI Integral Keypad Operation/Calibration/Configuration MI with HHT Operation/Configuration with MI Integral Keypad Operation/Calibration/Configuration MI with HHT Operation/Calibration/ Configuration MI Installation, Configuration, Operation, and Maintenance Installation, Configuration, Operation, and Maintenance Operation/Calibration/ Configuration with HHT Installation, Configuration, Operation, Calibration, Maintenance Operation/Calibration/ Configuration with HHT MI MI MI MI MI

16 MI April Introduction LEGAL NOTICE IMPORTANT LEGAL NOTICE; PLEASE READ CAREFULLY THE FOLLOWING TERMS AND CONDITIONS APPLY TO THE USE OF THIS PC10 SOFTWARE: The use of this software is authorized only if you are an original purchaser of the PC10 software from The Foxboro Company of Foxboro, MA, USA. If you are not an original purchaser of the PC10 software (from The Foxboro Company), you are NOT AUTHORIZED to use this software. FURTHER, IF YOU ARE NOT AN ORIGINAL PURCHASER OF THE PC10 SOFTWARE (FROM THE FOXBORO COMPANY), DOWNLOAD AND USE OF THE SOFTWARE WILL SUBJECT YOU TO ANY AND ALL LIABILITY ASSOCIATED THEREWITH UNDER APPLICABLE LAWS. Authorized use of this software in no way transfers title or ownership of the software to the recipient. Title and ownership remain with The Foxboro Company. Software License License Grant: All software programs which are embodied in human readable source form or machine readable object form and which include, but which are not limited to, programs having a series of instructions, statements and data, and related materials provided by Foxboro, are the property of Foxboro and/or others and are subject to the terms set forth in this License, in which Purchaser (of this License) is provided solely with a personal and nonexclusive license to use such programs solely for his/her internal business purposes in the country in which the software was furnished and for execution on the system for which it was provided. Copyright and Title: No title to the intellectual property in the software programs or material is transferred to Purchaser under this license. All software and its copyrights are owned by Foxboro and/or its suppliers. The software is protected by the United States copyright laws and international treaty provisions. Therefore, Purchaser must treat the Software like any other copyrighted material (e.g., a book or musical recording) except that Purchaser may make copies of the programs for use only with the system for which such programs were acquired. Purchaser must reproduce and include the copyright notice on any backup copy. Restricted Use: Purchaser shall not export or re-export the programs and material without the appropriate United States and Foreign government licenses. Purchaser agrees not to reverse engineer, decompile, or disassemble the Software. Purchaser may not rent or lease the Software to any third parties, but may transfer the Software and written materials on a permanent basis provided no copies are retained and the recipient agrees to the terms of this Software License. Software Upgrades: When Foxboro introduces new INtelligent devices, the software must be revised to incorporate the new device. You can upgrade the software free of charge by downloading it from the Foxboro Internet site ( 4

17 2. Installation Hardware Installation The hardware should be connected as shown in Figure 1 and Figure 2. Note that the PC10 is intended for use in ordinary non-hazardous locations only. See Warning Note below. 24 Vdc POWER SUPPLY + - BNC CABLE 250-OHM RESISTOR + INTELLIGENT TRANSMITTER PC10 MODEM RS-232 CABLE TO SERIAL PORT OF COMPUTER TO TRANSFER FILES TO THE HHT, DISCONNECT TRANSMITTER AND CONNECT BNC CABLE DIRECTLY TO HHT CABLE. POLARITY IS NOT IMPORTANT. HAND-HELD TERMINAL (HHT) Figure 1. Connection Diagram Without Power Supply Option 120 Vac/24 Vdc TRANSFORMER/RECTIFIER POWER CONNECTOR OPTIONAL POWER SUPPLY UNIT (WITH 250-OHM SERIES RESISTOR) BNC RED + BLACK INTELLIGENT TRANSMITTER BNC PC10 MODEM RS-232 CABLE TO SERIAL PORT OF COMPUTER Figure 2. Connection Diagram With Power Supply Option WARNING: As the PC10 is NOT certified as intrinsically safe, do NOT connect it to an intrinsically safe circuit that does not contain a barrier. In such situations, use the HHT; the output circuit of the HHT is certified as intrinsically safe. You can use the PC10 on an intrinsically safe circuit that does contain a barrier, provided you connect the PC10 to the power supply side of the barrier. 5

18 MI April Installation If hard copy reports are required, a standard text printer with a parallel interface connected to the PC printer port (LPT1 or LPT2) must be provided. Reports can also be saved to text files and printed later. Software Installation Installation should be performed from the DOS prompt only; do not attempt to install the software while running Windows. To install the PC10 Software Configurator, insert the PC10 install diskette (PN B0196AA or PN B0196AB) in diskette drive A: (or B:) and type: A:\INSTALL (or B:\INSTALL). The installation procedure is automatic and will prompt you for necessary information. The installation program will verify that the PC has the hardware and memory necessary to load and run PC10. During the installation process, you will be required to designate program path location, the communication port, and the printer port. PC10 configuration values are selected by choosing menu options. The blinking menu item designates the currently selected option. To abort the installation procedure at any time, press ESC. Standard Installation The standard installation installs the PC10 configurator on the C: drive in the following directories: C:\PC10 Program Files C:\PC10\DATA Transmitter Database Files Custom Installation If you select a custom installation, you are asked to enter the drive and path for the directory in which the PC10 files will reside. You will also be asked for the name and path of the directory for the data files. System Defaults After installation is complete, you may change the system defaults selected during installation by using the Defaults/Set PC10 Defaults menu sequence described on page 52. The password originally defaults to FOXBORO. It is recommended that you change the password the first time you start the program. See page 54 for information on setting up password. 6

19 3. Operation Running PC10 To run the program, type PC10 from your root directory. The title screen, which will appear for 10 seconds and is shown in Figure 3, can be cleared by pressing any key. The main top menu screen will appear, as shown in Figure 7. You can move the highlight from item to item by using the arrow keys, including HOME and END, or by pressing the highlighted letter of the menu item. You can select the highlighted menu item by pressing ENTER. 4.0 September 1, 1996 Figure 3. Title Screen for PC10. When the PC10 program starts, an attempt is made to communicate with a connected transmitter, and the following message appears: Checking Communications: please wait... If the software was not started with the command switch PC10 F and no transmitter is connected, a communication failure is reported. Note that the modem has two indicating lights Listen and Talk. When the Listen light is on, the modem is in the receive mode, ready to accept incoming data. When the PC10 attempts to communicate with the transmitter, the modem is in the send mode and the Talk light blinks on and off. Also note that upon exit from PC10, you will be in the root directory. 7

20 MI April Operation All PC10 functions, except those listed below, require a connected transmitter. The exceptions are: File Preconfigure Xmtr File Delete Xmtr File File Copy Xmtr File File Xmtr File Comments File Transfer HHT Files File List Xmtr Files File Backup Xmtr Files Test DOS Shell Help Reports Data From File Defaults If you would like to run the PC10 program for preconfiguration or file operations and would like to disable the initial communication check, run the program by typing PC10 F. Once you have invoked a function, the transmitter parameters necessary for the selected function are read from the transmitter. If the function selected will modify the transmitter output, the following message is displayed, which you must confirm in order to proceed: Good Figure 4. Warning Message Screen When this message is displayed, the only responses that will allow the operation in progress to continue are to press Y (upper or lower case) and Enter or to press an arrow key and Enter to select YES or NO any other key will abort the operation and return you to the main menu. IMPORTANT MESSAGE: It is highly recommended that Save Xmtr to File (under the File top menu item) be the first operation you perform on any transmitter. This will allow you to restore the transmitter to its original configuration if any mistakes are made in configuring or calibrating the transmitter. It will also permit you to restore transmitter performance to factory settings after replacing a defective amplifier. 8

21 3. Operation MI April 1997 Menu Structure The overall menu structure is illustrated in Figure 5 and Figure 6. The top-level menu screen is shown in Figure 7. Meas Calibrate Configure Test File Report Help Defaults Quit CONTINUED ON FIGURE 6 Xmtr Status Set ma/pulse Output Set Digital Output Go On-line Go Off-line Display Raw Input DOS Shell Self-Test Save Xmtr to File Preconfigure/Edit Xmtr File Write Config File to Xmtr Restore Xmtr from File Copy Xmtr File Delete Xmtr File Xmtr File Comments Select DOS Path Backup Database Files Transfer HHT Files List Xmtr Files Set PC10 Defaults Change PC10 Password PC10 INFORMATION PC10 MODEM AND TRANSMITTER CONNECTION PC10 MODEM CONN. WITH OPT. PWR. SUPPLY PC10 PC10 MODEM MODEM CONN. CONNECTION WITH OPT. FOR PWR. HHT TRANSFER SUPPLY PC10 PASSWORD MODEM CONNECTION CONFIGURATION FOR HHT TRANSFER FILE PC10 OPERATIONS PASSWORD CONFIGURATION TRANSFER FILE OPERATIONS FILE FROM HHT TO PC TRANSFER FILE FROM PC TO HHT PC10 TRANSFER REQUIRED FILE FROM FILES HHT TO PC CUSTOMIZING TRANSFER FILE THE FROM HELP PC MENU TO HHT VORTEX PC10 REQUIRED DIAGNOSTIC FILESMESSAGES & ACTIONS VORTEX CUSTOMIZING TRANSMITTER THE HELP CALIBRATION MENU PRESSURE SERIES DIAG. MESSAGES & ACTIONS 820 VORTEX PRESSURE DIAGNOSTIC STATUS MESSAGES MESSAGES & ACTIONS 820 VORTEX PRESSURE TRANSMITTER TRANSMITTER CALIBRATION CALIBRATION 860 PRESSURE & I/A PRESSURE SERIES DIAG. TRANSMITTER MESSAGES CALIBRATION & ACTIONS 870EC 820 PRESSURE DIAGNOSTIC STATUS MESSAGES MESSAGES & ACTIONS 870EC TRANSMITTER CALIBRATION 870PH/ORP/ISE 820 PRESSURE DIAG. TRANSMITTER MESSAGES CALIBRATION & ACTIONS 870PH/ORP/ISE 860 & I/A PRESSURE TRANSMITTER TRANSMITTER CALIBRATION CALIBRATION RTT10 870EC TEMPERATURE DIAGNOSTIC MESSAGES TRANSMITTER & ACTIONS CALIBRATION RTT20 870EC TEMPERATURE TRANSMITTER CALIBRATION TRANSMITTER CALIBRATION IMT10/IMT20 DIAG. MESSAGES & ACTIONS IMT10/IMT20 870PH/ORP/ISE TRANSMITTER DIAG. MESSAGES CALIBRATION & ACTIONS IMT25 870PH/ORP/ISE MAGFLOW TRANSMITTER CALIBRATION CFT10CFT15 RTT10 TEMPERATURE MASS FLOW TRANSMITTER TRANS. CALIBRATION CFT10/CFT15 RTT20 TEMPERATURE DIAG. MESSAGES TRANSMITTER & ACTIONS CALIBRATION IMT10/IMT20 DIAG. MESSAGES & ACTIONS IMT10/IMT20 TRANSMITTER CALIBRATION IMT25 MAGFLOW TRANSMITTER CALIBRATION CFT10CFT15 MASS FLOW TRANS. CALIBRATION CFT10/CFT15 DIAG. MESSAGES & ACTIONS Figure 5. PC10 Menu Structure 9

22 MI April Operation CONTINUED FROM FIGURE Series Re-Zero Transmitter 1-Point Calibration 2-Point Calibration ReRange ma Calibration Default Calibration 2-Point Conversion 5-Point Conversion Vortex ReRange ma Calibration Zero Total Set Low Flow Cut-In IMT10/IMT20 Flow Calibration ReRange ma Calibration IMT25 ma Calibration Reset Totals Empty Pipe Setup CFT10 Re-Zero Transmitter ma Calibration Restore Factory ma Start-Up Zero Zero Total RTT10 Re-Zero Transmitter 1-Point Calibration 2-Point Calibration Custom Input Curve ReRange ma Calibration Restore Factory Cal Enable Custom Curve Restore Factory ma RTT20 1-Point Calibration 2-Point Calibration 3-Point Calibration 5-Point Calibration Custom Input Curve ReRange ma Calibration Restore Factory Cal 870ITEC Bench Calibration Solution 1 Pt Span Solution 1 Pt Offset Solution 2 Pt Cal Temp Sensor Calib ma Calibration Default Calib 870ITPH 1 Point Manual Calib 1 Point Absolute Cal 2 Point Manual Calib Automatic Calib Temp Sensor Calib ma Calibration Default Calib CFT15 Re-Zero Transmitter Start-Up Zero Zero Total 860, I/A Series Pressure Re-Zero Transmitter 1-Point Calibration 2-Point Calibration ReRange ma Calibration Default Calibration Figure 6. PC10 Menu Structure Continued 10

23 3. Operation MI April 1997 Top Level Menu Picks Help Line Xmtr Info Good Figure 7. Top Level Menu Screen The bottom three lines of the Top Level Menu Screen contain status information concerning the PC10 program and the connected transmitter, as follows: Line Help Line Xmtr Info Line 1 Xmtr Info Line 2 Description Description of special keys that are applicable to this screen Transmitter Type: (820, 860, RTT10, RTT20, CFT10, CFT15, IMT10/IMT20, IMT25, I/A Series Pressure, Vortex, 870 ph/orp/ise, 870EC) Communication Mode:(4 to 20 ma or Digital) Transmitter Mode: (On-line/Off-line/Calibrate/Local/On-line Remote) Time Transmitter Status: (Good/Failed) Transmitter Tag Number Date On-line Help Each main menu item and all items on the configuration screen have an associated help file. When a field or menu item is selected, press F1 to display the associated help screen. 11

24 MI April 1997 Password Protection There are three levels of password protection: 3. Operation Level Privileges Description 1 Unlimited no password protection 2 Configuration functions require a password. All others do not. 3 Configuration and calibration functions require a password. All others do not. User may perform all functions without entering a password. User is required to enter a password before performing: Configure File Write Config File to Xmtr File Restore Xmtr from file User is required to enter a password before performing any function that modifies the transmitter database. The password level is set in the Defaults menu, as described on page 52. If a password is configured, the following message appears before the selected function is invoked: Figure 8. Enter Password Screen Once the password is entered, each subsequent call of the function will not require you to enter a password. Note that the password is case sensitive. 12

25 3. Operation MI April 1997 PC10 Operation Reading Transmitter Measurements (Meas) The MEAS function continuously reads and displays measurement information from the transmitter, as shown in Figure 9. You can close the display by pressing any key. If a measurements is out of range, it is displayed with a red background. If the transmitter has a status error, an error message will be displayed on the measurement screen. Measurements are updated approximately once per second. Figure 9. Measurement Screen (820 Flow Transmitter Example) The measurement information displayed per transmitter type is shown in Table 1. Table 1. Measurement Information Displayed Transmitter Type Measurement Information Displayed 820 Series Measurement #1 Measurement #2 (if configured) Transmitter Temperature ma Output (if in 4 to 20 ma mode) 860 Series Measurement #1 Measurement #2 (if configured) Transmitter Temperature ma Output (if in 4 to 20 ma mode) RTT10 Single Input RTT10 Dual Input Measurement #1 Transmitter Temperature ma Output (if in 4 to 20 ma mode) Difference, Average, or Redundant Measurement (as configured) RTD 1 RTD 2 ma Output (if in 4 to 20 ma mode) 13

26 MI April Operation Table 1. Measurement Information Displayed (Continued) Transmitter Type Measurement Information Displayed RTT20 Measurement #1 Transmitter Temperature ma Equivalent (analog only) IMT20/ IMT10 IMT25 CFT10 CFT15 I/A Series Pressure Transmitter Vortex Process Flow Measurement ma Output Flow Measurement Forward Total Reverse Total Net Total Grand Total ma Equivalent (analog only) Mass Flow Measurement Density Measurement Temperature Measurement Total Measurement Volumetric Flow Measurement % Solids Measurement ma Output (if trend is disabled) Pulse Output (if trend is disabled) Alarm 1 State (if trend is disabled) Alarm 2 State (if trend is disabled) Mass Flow Measurement Density Measurement Temperature Measurement Total Measurement Volumetric Flow Measurement % Solids Measurement ma Output #1(if trend is disabled) ma Output #2(if trend is disabled) ma Output #3(if trend is disabled) Pulse Output (if trend is disabled) Alarm 1 Contact (if trend is disabled) Alarm 2 Contact (if trend is disabled) Measurement #1 Measurement #2 if Meas 2 is on, electronics temperature if Meas 2 is off Transmitter Temperature ma Output (if in 4 to 20 ma mode) Flow Measurement Total Measurement Transmitter Temperature ma Output (if in 4 to 20 ma mode) 14

27 3. Operation MI April 1997 Table 1. Measurement Information Displayed (Continued) Transmitter Type 870ITEC and 870ITPH Primary Measurement Solution Temperature Absolute Measurement Measurement Information Displayed If measurement trend display is enabled (see PC10 Defaults on page 52), the lower half of the screen will show the trend of the primary measurement, as illustrated in Figure 10. Figure 10. Trend Display Transmitter Calibration Functions (Calibrate) The calibration menu contains the calibration operations for all Foxboro Intelligent Transmitters. Only those calibration functions applicable to the connected transmitter are displayed. Figure 11. Calibration Options Menu (820 shown) 15

28 MI April Operation Table 2. Calibration Options vs. Transmitter Type Transmitter Type Calibration Options Description 820 Series Intelligent Transmitters 860 Series Intelligent Transmitters and I/A Series Pressure Transmitters RTT10 Intelligent Temperature Transmitters Re-Zero Transmitter 1-Point Calibration 2-Point Calibration ReRange ma Calibration Default Calibration 2-Point Conversion 5-Point Conversion Re-Zero Transmitter 1-Point Calibration 2-Point Calibration ReRange ma Calibration Default Calibration Re-Zero Transmitter 1-Point Calibration 2-Point Calibration Custom Input Curve ReRange ma Calibration Restore Factory Cal Enable Custom Curve Restore Factory ma Re-Zero transmitter. Calibrate transmitter at Lower Range Value. Calibrate transmitter at Lower and Upper Range Values. Rerange to another input span without using calibration equipment. Trim ma output. Set transmitter to the default calibration and configuration. Replace amplifier using a two-point calibration. Replace amplifier using a five-point calibration. Re-Zero transmitter. Calibrate transmitter at Lower Range Value. Calibrate transmitter at Lower and Upper Range Values. Rerange to another input span without using calibration equipment. Trim ma output. Set transmitter to the default calibration and configuration. Re-Zero transmitter. Calibrate transmitter at Lower Range Value. Calibrate transmitter at Lower and Upper Range Values. Enter up to 12 data points to calibrate input. Rerange to another input span without using calibration equipment. Trim ma output. Set transmitter back to factory calibration (disable custom calibration). Set transmitter calibration back to custom calibration curve. Restore 4 to 20 ma back to factory calibration. 16

29 3. Operation MI April 1997 RTT20 Intelligent Temperature Transmitter IMT10/IMT20 Magnetic Flow Transmitters IMT25 Magnetic Flow Transmitters CFT10 I/A Series Mass Flowmeter CFT15 I/A Series Mass Flowmeter Vortex Series Mass Flowmeter Table 2. Calibration Options vs. Transmitter Type (Continued) Transmitter Type Calibration Options Description 1-Point Calibration 2-Point Calibration 3-Point Calibration 5-Point Calibration Custom Input Curve ReRange ma Calibration Restore Factory ma Flow Calibration ReRange ma Calibration ma Calibration Reset Totals Empty Pipe Setup Re-Zero Transmitter ma Calibration Restore factory ma Startup Zero Zero Total Re-Zero Transmitter Startup Zero Zero Total ReRange ma Calibration Zero Total Set Low Flow Cut-In Calibrate transmitter at any 1-, 2-, 3-, or 5-points within the configured range. Enter up to 22 data points to calibrate input. Rerange to another input span without using calibration equipment. Trim ma output. Set transmitter back to factory calibration (disable custom calibration). Calibrate transmitter at a known flow rate. Set 20 ma output point. Trim ma output. Trim ma Output Reset Totalizer Perform Empty Pipe Calibration Procedure Re-Zero transmitter. Trim ma output. Restore 4-20 ma back to factory calibration. Zero transmitter upon initial flow tube calibration. Reset total to zero. Re-Zero transmitter. Zero transmitter upon initial flow tube calibration. Reset total to zero. Rerange to another input span without using calibration equipment. Trim ma output. Zero Transmitter Total Set Low Flow Cut-In 17

30 MI April Operation Table 2. Calibration Options vs. Transmitter Type (Continued) Transmitter Type Calibration Options Description 870ITEC Electrodeless Conductivity Transmitter Bench Calibration This permits you to perform off-line calibration for 3 applications of an 870ITEC transmitter. The zero point is set with the sensor suspended in air. The second point is set by using a loop through a sensor connected to a decade resistance box. Solution 1 Pt Span This option is a 1-point span calibration for up to 3 applications, using known reference solutions. A 1- point calibration is valid only if a 2-point calibration was previously performed. Solution 1 Pt Offset This enables you to set the offset (bias) for up to 3 applications, using known reference solutions. This is used to correct for a zero shift. A 1-point calibration is valid only if a 2-point calibration was previously performed. Solution 2 Pt Calib This option is a 2-point span calibration for up to 3 applications, using known reference solutions. Temp Sensor Calib This option is a calibration of the temperature sensor, using a known temperature solution reference. ma Calibration This enables you to set the 4 ma and 20 ma points for the transmitter output signal. Default Calibration This option permits you to restore calibration automatically to the default values. WARNING: This places the transmitter into a default configuration and calibration. Suggest you reconfigure and perform a bench calibration after a default. 18

31 3. Operation MI April 1997 Table 2. Calibration Options vs. Transmitter Type (Continued) Transmitter Type Calibration Options Description 870ITPH ph/orp/ise Transmitter 1Point Manual Calib 1Point Absolute Calib 2Point Manual Calib Automatic Calib Temp Sensor Calib ma Calibration Default Calibration This permits you to perform a manual calibration of an 870ITPH transmitter. A manual calibration permits you to enter or edit solution values. A single point calibration may only be used if you have previously performed a 2-point calibration. This option applies only to ORP applications and is used instead of a manual calibration. It is a 1-point span calibration, using known reference solutions. This enables you to set the span and offset, using known reference solutions. It is not applicable to ORP measurements. This option provides a buffer-recognition mechanism that locks in the buffer value representing the millivolt and temperature values measured by the sensor, using known reference solutions (buffers). This option is a calibration of the temperature sensor, using a known reference temperature solution. This enables you to set the 4 ma and 20 ma points for the transmitter output signal. This option permits you to restore calibration automatically to the default values. WARNING: This places the transmitter into a default configuration and calibration. Suggest you reconfigure and perform a bench calibration after a default. Appendix B contains detailed explanations of all calibration functions. Configuring Transmitters (Configure) When you select Configure from the top level menu, a configuration screen will appear, showing all the parameters that can be configured on the type of transmitter currently connected to the system. The screen for an 820 Transmitter is shown in Figure

32 MI April Operation Figure 12. Configuration Screen for 820 Series Transmitter Table 3. Configuration Options vs. Transmitter Type Transmitter Type Display Only Display and Change 820 Series Intelligent Transmitters Transmitter Model Code Transmitter Revision Date of Manufacture Date of Last Calibration Tag Number Tag Name (Service Description) Location Device Name (I/A Series Letterbug) Transmitter Output (4-20 ma/digital) Square Root/Linear Output Measurement #1 Units Measurement #2 Units Lower Range Value Upper Range Value Damping Failsafe Mode Temperature Failure Strategy 20

33 3. Operation MI April 1997 Table 3. Configuration Options vs. Transmitter Type (Continued) Transmitter Type Display Only Display and Change 860 Series Intelligent Transmitters I/A Series Pressure Transmitters RTT10 Intelligent Temperature Transmitters Transmitter Model Code Transmitter Revision S/N Date of Manufacture Date of Last Calibration Transmitter Model Code Transmitter Revision Date of Manufacture Date of Last Calibration Transmitter Model Code Transmitter Revision Date of Manufacture Date of Last Calibration Tag Number Tag Name (Service Description) Location Device Name (I/A Series Letterbug) Transmitter Output (4-20 ma/digital) Square Root/Linear Output Measurement #1 Units Measurement #2 Units Lower Range Value Upper Range Value Damping Failsafe Mode Temperature Failure Strategy Tag Number Tag Name (Service Description) Location Device Name (I/A Series Letterbug) Transmitter Output (4-20 ma/digital) Square Root/Linear Output Measurement #1 Units Measurement #2 Units Lower Range Value Upper Range Value Damping Failsafe Mode Temperature Failure Strategy External Zero Tag Number Tag Name (Service Description) Location Device Name (I/A Series Letterbug) Transmitter Output (4 to 20 ma/digital) Transmitter Configuration (Single/Dual) Transmitter Input Type (RTD/TC/mV) Measurement #1 Units Lower Range Value Upper Range Value Damping Failsafe Mode Noise Rejection Filter 21

34 MI April Operation Table 3. Configuration Options vs. Transmitter Type (Continued) Transmitter Type Display Only Display and Change RTT20 Intelligent Temperature Transmitter IMT10/ IMT20 Intelligent Transmitters Transmitter Model Code Transmitter Revision Date of Manufacture Date of Last Calibration Transmitter Model Code Transmitter Revision Date of Manufacture Date of Last Calibration Tag Number Tag Name (Service Description) Device Name (I/A Series Letterbug) Location Input Type Sensor Configuration (2, 3, or 4-wire RTD) Linearization Mode (EGU or Dewpoint Measurement Unit (C, F, K, R, mv, ohms) Lower Range Value (LRV) Upper Range Value (URV) Calibrator s Initials Output Mode (4 to 20 ma/digital) Fault Detection (On/Off) ma Output Failsafe (On/Off) ma Failsafe Direct ma Failsafe Value Damping (0 to 30 seconds) Sensor Validation (0.0 to 10.0 seconds) Intelligent Smoothing (0 to 30 seconds) Power Supply Frequency (Hz) Noise Filter (Standard/High) INTEGRAL INDICATOR Push Buttons (Enable/Disable) Optional Indicator Language Top Line Display Bottom Line Label COLD JUNCTION Secondary Meas Units (C or F) Tag Number Tag Name (Service Description) Location Device Name (I/A Series Letterbug) Flow Tube Size Flow Tube Lining Meter Factor Measurement #1 Units Upper Range Value Display Upper Range Value (P5) Damping (P4) Pulse Scale (P3) Transmitter Baud Rate (600/4800) 22

35 3. Operation MI April 1997 IMT25 Intelligent Transmitters Table 3. Configuration Options vs. Transmitter Type (Continued) Transmitter Type Display Only Display and Change Transmitter Transmitter Serial Number Transmitter Model Code Tube Model Code Tube Serial Number Meter Factor Tag Number Tag Name Device Name (I/A Series Letterbug) Location Line Frequency MEASUREMENT CONFIGURATION Flow Rate Units Flow Rate Slope Flow Rate Format Output Mode (Analog/Digital) Digital Mode Analog Mode Flow Direction Flow Rate Damping Noise Reduction (On/Off) Upper Range Value 1, 2, and 3 Pulse Output Mode Pulse Out URV Rate Max Frequency Total Max Frequency Empty Pipe Detect (On/Off) LOCAL DISPLAY CONFIGURATION Default Screen Dual Display (On/Off) Display Line 1 Display Line 2 Flow Display Damping Local Totalizer (On/Off) Totalizer Units Custom Units Custom Slope Fwd/Rev/Net Tot Frmt Grand Total Format DIAGNOSTICS Rate Response Diag. (Up/Downscale) Display Response Diag. PASSCODES Passcodes 1 and 2 (On/Off) Passcodes 1 and 2 Protect Passcodes 1 and 2 (####) 23

36 MI April Operation IMT25 Intelligent Transmitters (Continued) Table 3. Configuration Options vs. Transmitter Type (Continued) Transmitter Type Display Only Display and Change ALARM CONFIGURATION Alarms (On/off) Alarm Clear Display Response Rate Out Response High Flow Rate Setpoint Deadband Low Flow Rate Setpoint Deadband High Fwd Total 1 Setpoint High Fwd Total 2 Setpoint Empty Pipe CONTACT INPUT/OUTPUT Contact 1 Function Contact 1 Operation Contact 2 Function Contact 2 Operation Relay 1 Function Relay 1 Alarm Relay 1 Operation Relay 1 Suppress Relay 2 Function Relay 2 Alarm Relay 2 Operation Relay 2 Suppress 24

37 3. Operation MI April 1997 CFT10 I/A Series Mass Flowmeter Table 3. Configuration Options vs. Transmitter Type (Continued) Transmitter Type Display Only Display and Change Transmitter Model Code Transmitter Revision Date of Manufacture Date of Last Calibration Transmitter Serial Number Tag Number Tag Name (Service Description) Location Device Name (I/A Series Letterbug) Mass Flow Units Density Units Temperature Units Total Configuration & Units Volumetric Flow Units ma Output Connection ma Upper Range Value ma Lower Range Value ma Damping Pulse Output Connection Pulse Upper Range Value Pulse Lower Range Value Pulse Damping Pulse Trip Flow Direction Slug Flow Time % Solids Configuration % Solids Fluid Parameters Alarm 1 Config. (Type/Level/Hysteresis) Alarm 2 Config. (Type/Level/Hysteresis) Flow Tube Parameters 25

38 MI April Operation CFT15 I/A Series Mass Flowmeter Table 3. Configuration Options vs. Transmitter Type (Continued) Transmitter Type Display Only Display and Change Transmitter Model Code Transmitter Revision Date of Manufacture Date of Last Calibration Transmitter Serial Number Tag Number Tag Name (Service Description) Device Name (I/A Series Letterbug) Location Mass Flow Units Density Units Temperature Units Volume Flow Units OUTPUTS Pulse Mode Pulse Trip Lower Range Value Upper Range Value Damping Preset Value Totalize Option Alarm 1 & 2 Alarm Level Alarm Hysteresis Alarm Power 4 to 20 ma - Output #1, 2, and 3 ma Mode (On/Off) Lower Range Value Upper Range Value Damping Preset Value MODBUS Address Baud Parity Delay Flow Direction % SOLIDS CONFIGURATION Component A & B Tag Density Thermal Expansion % Solids Mode Mass Flow Mode Total Mode Volume Flow Mode Reference Temperature 26

39 3. Operation MI April 1997 Table 3. Configuration Options vs. Transmitter Type (Continued) Transmitter Type Display Only Display and Change CFT15 I/A Series Mass Flowmeter (Continued) Vortex Flowmeter Transmitter Firmware Revision Date of Manufacture Date of Last Calibration Transmitter Ref. No. Flowing K-Factor FLOWTUBE PARAMETERS Tube Serial Number Density Coefficients 1, 2, 3, and 4 Nominal Capacity Flow Coefficients 1, 2, 3, and 4 Transmitter Model Code Reference Number Reference K-Factor Tag Number Tag Name (Service Description) Device Name (I/A Series Letterbug) Location Fluid Type Measurement Units Noise Rejection Signal Condition Low Flow Correction Flowing Temperature Flowing Density Base Density Fluid Viscosity Mating Pipe Piping Configuration Upstream Distance Added K-Factor Bias Upper Range Value Output Mode Damping ma Failsafe Scaled Pulse Out Pulse Resolution 27

40 MI April Operation 870ITEC Electrodeless Conductivity Transmitter Table 3. Configuration Options vs. Transmitter Type (Continued) Transmitter Type Display Only Display and Change Transmitter Type Transmitter Model Code Transmitter Firmware Rev. Date of Manufacture Sales Order No. Last Calibration Date Tag Number Tag Name Device Name Location No. of Applications Application Select Sensor Type Output Mode Damping Primary Units (for appl. selected) Primary Full Scale Temp. Compensation ma Output Output Range Min Output Range Max Failsafe Mode Failsafe Value Temp Units Temperature Mode Failure Value Manual Temp Temp Sensor Type Stability Indicators: Measurement Time Var Temperature Stability Time Stability Var Application Trigger Value(s) Local Display Configuration Display Timeout Major/Minor Passcodes App N Second Measurement(s) Diagnostics Enable/disable Leakage, ATC Short, Comp. Range, ATC Open, ma Range, Meas Range 28

41 3. Operation MI April ITPH ph/ise/orptransmitters Table 3. Configuration Options vs. Transmitter Type (Continued) Transmitter Type Display Only Display and Change Transmitter Type Transmitter Firmware Rev. Transmitter Model Code Date of Manufacture Sales Order No. Last Calibration Date Tag Number Tag Name Device Name Location Sensor Type Output Mode Electrode Temp Compensation Chemical Composition Buffers Output Mode ma Output Output Range Min Output Range Max Failsafe Mode Failsafe Value Temp Sensor Type Stability Indicators: Measurement Time Var Temperature Stability Time Stability Var Local Display Configuration Display Timeout Major/Minor Passcodes Second Measurement(s) Damping ac Frequency Diagnostics Glass Glass Limit Glass Cutoff Leakage Low Slope Low Slope Limit Preamp ATC Short ATC Open Coat Coat Limit Aging 4 to 20 ma Range Comp Range Measurement Range 29

42 MI April Operation Moving Around on the Configuration Screen The parameter being edited is highlighted on the screen. To move the highlight to the next item, press ENTER or TAB. To move to the previous item, press Shift-TAB. PgUp and PgDn move to the first and last items on the screen. Changing Parameter Values on the Configuration Screen Parameters that would normally be keyed in by the user on the HHT, such as numbers and strings, are edited with the keyboard. Entering an out-of-range value causes the system to beep and reject the entry. Changing a parameter may automatically change other parameters that depend on it; the new values are displayed immediately. Parameters that are selected from menus with the HHT are selected from submenus in PC10. The submenu opens when you highlight the parameter and press F3. When the submenu is opened, either the current value of the item or Quit is preselected. To leave the parameter unchanged, press ENTER again to close the menu and move to the next item on the configuration screen. To change the item, move the highlight to the desired choice, using the arrow keys, and then press ENTER. An example is shown in Figure 13. If an item must be selected from a menu, the Help line will display <F3> Choices to indicate that a menu of options is available. Figure 13. Example: Setting Measurement Units for an 823DP-M Exiting from the Configuration Screen Confirm changes made on this screen by pressing F4. If all data is valid, you will have the option to download changes to the transmitter, as shown in Figure

43 3. Operation MI April 1997 Good Figure 14. Exiting from Configuration Screen To quit the operation without making any changes permanent, press N. You will then return to the top level menu. To save the changes, press Y. You will then be asked to put the control loop in Manual. Put the loop in Manual, then press Y to continue. The data will be downloaded to the connected transmitter. As an alternative to pressing the Y or N key, move the cursor to the correct answer and then press ENTER. Transmitter Diagnostics (Test) This group of functions allows you to verify the status of the transmitter, set the transmitter output to a specific value for testing other devices in a loop, and exit to a DOS shell. The menu of options is shown in Figure 15. Figure 15. Test - Diagnostic Functions Screen 31

44 MI April 1997 Xmtr Status 3. Operation This function interrogates the transmitter and displays any status or diagnostic errors. To correct any problem, follow the applicable diagnostic procedures described on page 66 in Appendix A. The screen for an 820 Transmitter is shown in Figure 16. Figure 16. Transmitter Status (820) Explanations of status screen messages are listed in Table 4. Table 4. Status Message Type of Message Message Explanation Transmitter Status Failed Transmitter indicates a status error, which is explained on the screen. Good Transmitter health is OK. Transmitter Mode On-line Transmitter is running and generating measurements. On-line Local CFT10 transmitter is On-line and not connected to I/A Series system. On-line Remote CFT10 transmitter is On-line and control is with the I/A Series system (local changes not allowed). Local Transmitter is in local override mode used to set ma and digital output to requested value. Calibrate Transmitter is being calibrated. Measurements are active. Off-line Transmitter is Off-line and not updating measurements. Transmitter is Off-line during database downloads. Diagnostic Error Specific transmitter diagnostic errors See Appendix A, page 72, for error codes and recommended actions. 32

45 3. Operation MI April 1997 Set ma/pulse Output (Loop Cal) The transmitter can be set to output a ma value to test or adjust other devices in the loop. To set the ma output, first select the output units (in ma, measurement units, or %) and then enter the desired output value. The data entry screen (Figure 17) shows the allowable output range and units. NOTE: If you are using the CFT10 or CFT15 transmitter, you may select to set either the ma or pulse output to any desired value. This operation may be repeated until you press ESC, at which time the transmitter is placed back on-line and you return to the main menu. Good Figure 17. Test Set ma Output (Output Override) Figure 18. Test Set Pulse Output for CFT10 33

46 MI April Operation Set Digital Output The transmitter can be set to output a digital value to test I/A Series system wiring and displays. (I/A Series Version 4.0 or later is required.) Both Measurement #1 and Measurement #2 outputs can be set. First, select the measurement and then enter the desired output value. This operation may be repeated until you press ESC, at which time the transmitter is placed back On-line and you return to the main menu. Go On-line This function sets the transmitter back to On-line mode. All functions automatically return to transmitter On-line status unless the transmitter was disconnected during operation. The transmitter normally remains On-line unless you are configuring or calibrating it. Go Off-line This function sets the transmitter Off-line. Normally, the transmitter should remain On-line. It should be placed Off-line only during diagnostic checkout. Display Raw Input This function reads the raw inputs for the selected transmitter The inputs are displayed as follows (the twirler moves every time the reading is updated): Transmitter Type Display 820 Frequency of Input 1 (pressure input) Frequency of Input 3 (temperature input) 860 mv Input 1 (pressure input) mv Input 3 (temperature input) I/A Series Pressure CFT10 CFT15 Vortex IMT25 mv Input 1 (pressure input) mv Input 3 (temperature input) Coriolis Frequency (valid frequency Hz) Slug Flow Recoveries Tube Drive Frequency Slug Recoveries Vortex Shedding Frequency Upper Limit Frequency Elect Voltage (POS): Elect Voltage (NEG): Coil Current (POS): Coil Current (NEG): 34

47 3. Operation MI April 1997 DOS Shell Good Figure 19. Test Display Raw Inputs (820) This function takes you to a DOS Shell (memory permitting). You can return to PC10 by typing exit at the DOS prompt. Be careful, however, not to start another copy of PC10 while you are shelled out to DOS! When you select this function, the screen displays a message similar to the following: Microsoft(R) MS-DOS(R) Version 5.00 (C)Copyright Microsoft Corp Type EXIT to rtn.. C:\PC10\> Programs that can be run from the DOS shell depend upon the memory available in the PC. Transmitter Database Storage (File) The FILE menu contains the transmitter database and file manipulation functions. The pulldown menu for selecting the functions is shown in Figure 20. Figure 20. File Menu Screen 35

48 MI April Operation Transmitter database files may be saved to keep a record of each transmitter configuration. These files may be used for restoring transmitter configuration, pre-configuration, and for copying a file to another transmitter. Comments may be added to transmitter files for keeping a maintenance history. Files are stored using the first eight characters of the tag number. The file extensions indicate the transmitter type and index number. For example, Transmitter Tag = FT102A - EAST 1 Transmitter Type = 820 Series would be defaulted to: FT102A_E.P01 where P indicates transmitter type code 01 is the index number The transmitter type codes are: 820 Series: P 860 Series: Q RTT10: T CFT15: D I/A Series Pressure: X Vortex: V IMT10/IMT20: M IMT25: I ph/ise/orp: H EC: E CFT10: C RTT20: R To avoid overwriting existing database files, the index number in the file extension automatically increments each time you add a file with the same tag number. Whenever you must select a database file, the following information is displayed for each file (as shown in Figure 21): Tag Number Date created Time created File name Files that contain comments are indicated by +notes 36

49 3. Operation MI April 1997 Save Xmtr to File Figure 21. Select a Database File This function reads all parameters from the connected transmitter and saves them to a file stored on the PC. After all parameters are uploaded, you must enter a filename to save the file. You may use either the default file name (Tag Number) or enter a custom name. To set the directory in which the files will be stored, use the Set DOS Path function, as described on page 41. It is highly recommended that Save Xmtr to File (under the File top menu item) be the first operation you perform on any transmitter. This will allow you to restore the transmitter to its original configuration if you make a mistake in configuring or calibrating the transmitter. Preconfigure Transmitter Select this option to preconfigure a database and save it in a file for later downloading to a transmitter or to modify an existing transmitter file. To do this, you first select a transmitter type to be preconfigured, as follows: Figure 22. Preconfigure Transmitter Database Screen 37

50 MI April Operation After you select the transmitter type and press ENTER, you have the option to modify an existing database file. If you want to modify an existing file, press Y when prompted. Otherwise, a default database of the selected type will be loaded. You can then edit all configurable parameters using the configuration data entry screen. Refer to Appendix C for configurations screens for various transmitter types. After configuration operations are completed, the new information is then saved back to the database file. The database can then be downloaded to the transmitter by using the Write Config File to Xmtr option, which is described in the next section. Write Config File to Xmtr This function writes a previously configured transmitter database file (configuration parameters only) to the connected transmitter. Note that the database file must be the same type as the transmitter. Good Figure 23. Write Config File Screen Select the datafile to be written to the transmitter by moving the highlight to the desired file with the arrow keys and then pressing ENTER. The list of files is displayed as follows: 38

51 3. Operation MI April 1997 Good Figure 24. Transmitter File List Screen The configuration parameters are then downloaded to the connected transmitter. NOTE: When writing the configuration file for a CFT10/CFT15 transmitter, the tube coefficients will not be downloaded to the transmitter. Selecting Restore Xmtr from File will download the tube coefficients. Restore Xmtr from File This function restores the complete transmitter database file back to the transmitter. It should be used whenever you replace an assembly. To perform this operation, you first select a file that contains the database to be reloaded into the transmitter. Note that only a file that was created with Save Xmtr to File can be restored. Also, the database must be the same type as the transmitter. WARNING: Before using this function, it is HIGHLY RECOMMENDED that you back up the existing transmitter database with a Save Xmtr to File operation. Since the factory does not maintain the databases on every transmitter shipped, overwriting the original coefficients with different values may result in permanent loss of the accuracy and repeatability resulting from factory calibration. Copy Xmtr File This function allows you to duplicate transmitter files and to create backup files. Since duplicate transmitter files do not have the same maintenance history as the original files, comments are not copied to the duplicate files. To copy the maintenance history, use the Copy Comments function in the Xmtr File Comments menu. 39

52 MI April Operation Delete Xmtr File This function deletes a selected transmitter file. Xmtr File Comments This function permits you to keep a maintenance history for the transmitter. You can use it to add comments to the data file, view comments already written, or copy the comments to another data file. You can enter comments four lines at a time. The comments are automatically date stamped when they are written to the file. These operations are intended to facilitate maintaining the service record of a transmitter. Note that comments are stored in the PC10 file and are not stored in transmitter memory. Good Figure 25. File Option (820) Xmtr Comments Good Figure 26. File Option Add File Comments 40

53 3. Operation MI April 1997 Select DOS Path This function sets the drive and path to the subdirectory that contains the desired datafiles. You may specify any valid drive and path. All transmitter database file read and write operations will be to the specified subdirectory. After you have entered a new path, check the displayed value to be sure it is correct. If you enter an incorrect path, an error message will be displayed. Note that the directory selected must already exist; PC10 will not attempt to create a directory that does not exist. Good Figure 27. Select DOS Path Backup Database Files This function allows you to backup database files to a target directory and path that you specify. The sequence of screens is shown in Figure 28 through Figure 30. From the File menu, select Backup to start the backup operation (or Quit to quit). Good Figure 28. Backup Database Files Screen 1 41

54 MI April Operation Select the type of transmitter files to be copied to the target directory. Figure 29. Backup Database Files Screen 2 Enter the target directory into which the files are to be copied. Figure 30. Backup Database Files Screen 3 The files are then copied to the target directory. List Xmtr Files Good This function permits you to display a directory of transmitter files directly. From the File menu, select List Xmtr Files and press ENTER. The screen shown in Figure 31 will then appear. Scroll the list up and down with the arrow keys. To exit, press ESC. 42

55 3. Operation MI April 1997 Good Transfer HHT Files Figure 31. List Xmtr Files This function permits you to exchange transmitter database files with the Hand-Held Terminal (HHT). To do this operation, you need an HHT with Software P/N L0122EV or later, and a Memory Pak installed in the HHT. Note that the PC10 can store more of the transmitter database than the HHT. Therefore, when you transfer a file from the HHT to the PC, you should display a report to determine what data is not available. All unavailable data is displayed in the database report as 0 or blank. Unavailable Dates are shown as not stored. To transfer files, execute the procedures described below. The example reports in Appendix D show which fields are available in the HHT. This function does not apply to the IMT25, RTT20, CFT15, 870EC, and 870PH. 43

56 MI April Operation Transfer Files from HHT to PC From the File menu, select Transfer HHT Files. Good Figure 32. Transfer HHT Files Menu Selection Press ENTER to display the initial screen. Figure 33. Transfer HHT Files Initial Screen Select TRANSFER and press ENTER to start the file transfer. A prompt will appear as shown below. At this time, the PC is waiting for the HHT to initiate the data transfer.. 44

57 3. Operation MI April 1997 Figure 34. Transfer HHT Files File Transfer Prompt On the HHT, select Setup - MemPak - FileXfer. The display will show: Press H to transfer files from HHT to the PC. Press Y. Press Y. 4M HHT _to_ PC PC to HHT mp Transfer HHT Files to PC? Y/Q Select FileXfer on PC; Y to Cont To Select, Press EXE on TagNumber Press Y. All files on the MemPak will scroll. When desired file is displayed, press EXE to select. FT102A -EXE to Select- 45

58 MI April Operation Press EXE. Loading File Please Wait HHT is reading file. Please wait. Xfer data to PC Record 1 of 15 Data is being transferred to the PC10. The sequence of screens displayed on the PC is as follows:. Figure 35. Transfer HHT Files Sending File from HHT to PC Figure 36. Transfer HHT Files Receiving Records from HHT 46

59 3. Operation MI April 1997 When the transfer is complete, the HHT screen will display: Edit PC Filename Y to Continue This prompt tells you that the file transfer is complete and that you should now edit the filename on the PC10. The PC10 will display the Edit Filename screen as follows: Figure 37. Transfer HHT Files Edit Filename Transfer Files from PC to HHT Press ENTER to display the initial screen. Figure 38. Transfer HHT Files Initial Screen 47

60 MI April Operation Select TRANSFER and press ENTER to start the file transfer. A prompt will appear as shown. The PC10 is waiting for the HHT to initiate the file transfer. Figure 39. Transfer HHT Files File Transfer Prompt On the HHT, select Setup - MemPak - FileXfer. The display will show: Press P to transfer files from PC to the HHT. Press Y. 4M HHT_to_PC PC_to_HHT mp Transfer PC File to HHT? Y/Q Select FileXfer on PC; Y to Cont The HHT will send a message to the PC that the transfer is ready to begin. Checking PC Please Wait A prompt will appear, telling you to select a filename in the PC10 program: Select Filename on PC; Y to Cont 48

61 3. Operation MI April 1997 Select a filename from the list of PC10 files via the screen below: Figure 40. Transfer HHT Files Select Filename After selecting a filename, press Y on the HHT to begin the transfer. Press Y. Select Filename on PC; Y to Cont Xfer File to HHT Record 1 of 15 The transfer then starts, displaying the following screen on the PC: Figure 41. Transfer HHT Files Sending File from PC to HHT When transfer is complete, the HHT will display: Transfer is complete. Saving to MemPak Please Wait 49

62 MI April 1997 Printing Transmitter Databases (Report) 3. Operation This group of functions permits you to generate transmitter database reports and output them to the screen, to a printer, or to a file. The initial screen is shown in Figure 42. Report Type Figure 42. Report (Initial Screen) This function allows you to select either a Complete Transmitter Database or a Transmitter Configuration by pressing F3, moving the highlight to the type of report you want, and pressing ENTER. Examples of both report types are shown in Appendix D. A Transmitter Configuration is identical to the configuration screen; a Complete Transmitter Database is the complete database in raw format. Report Data This function permits you to read report data from the connected transmitter or from a transmitter database file previously saved. If the file contains comments, they will also be printed. Good Figure 43. Select Report Data 50

63 3. Operation MI April 1997 Report Destination This function permits you to select Printer, Screen, or Text File as the destination of the report. If you select Printer when PRINT is selected, the report is sent to the printer port named under Defaults. If you select Text File, you are prompted for the name of a text file, which will be created in the directory specified by the Select DOS Path operation in the File menu. The screen is shown in Figure 44. Print/Quit Good Figure 44. Set Report Destination PRINT starts printing the report. QUIT cancels the print operation. On-line Help Screens (Help) This function displays a list of available help files, as shown in Figure 45. After you make your selection, the appropriate help screen is displayed. Figure 45. Help Menu Screen 51

64 MI April Operation Typical examples of Help screens are shown in the following screens. Good Figure 46. PC10 Modem and Transmitter Connection Help PC10 Defaults Good Figure 47. Password Help Screen This group of functions permits you to set up the defaults for the system and to set the PC10 password and access level. 52

65 3. Operation MI April 1997 Set PC10 Defaults This function permits you to set defaults for serial port, printer port, monitor type, type of display (tabular or trend), and the password access level. The screen display is shown in Figure 48. Serial Port Figure 48. Set PC10 Defaults Screen This function selects the serial port (COM1 or COM2) used to communicate with the transmitter. The PC10 modem card must be connected to the port selected. Otherwise, no communication will be available to the transmitter and an error message will be displayed. Printer Port This function selects the parallel port (LPT1 or LPT2) to which reports will be sent when the report destination is set to Printer. The PC10 supports parallel printers only. To use a serial printer, save the report to a file and print the report using the DOS Type or Copy commands. Monitor Type Good PC10 can automatically distinguish between a Hercules graphics adapter and a CGA, EGA, or VGA card, but cannot tell if the monitor connected to a color graphics card is a color monitor. Set this default to force PC10 to use screen attributes that will assure good contrast on a monochrome screen. 53

66 MI April Operation Measurement Display This function permits you to display the measurements as a standard text display or as a trend display. If the trend display is enabled, the trend of Measurement #1 will appear at the bottom of the measurement display. The trend display is available for VGA monitors only. Good Password Access Level Figure 49. Select Measurement Display This function permits you to select the password accessibility level, as shown in Figure 50. Move the highlight to Password Access Level, press F3 for the options, select the desired access level and press ENTER. Figure 50. Change Password Access Level 54

67 3. Operation MI April 1997 The three levels of password protection are listed in the following table: Table 5. Password Access Levels Level Privileges Description 1 Unlimited no password protection User may perform all functions without entering a password. 2 Configuration functions require a password. All others do not. User is required to enter a password before performing: Configure File Write Config File to Xmtr File Restore Xmtr from file 3 Configuration and calibration functions require a password. All others do not. Change PC10 Password User is required to enter a password before performing any function that modifies the transmitter database. This function permits you to change your password, using the screen shown in Figure 51. Note that you are required to enter the old password before entering a new password. Also note that the password is case sensitive. If PC10 rejects a password that you know is correct, check the Caps Lock light on your PC. Quit Good Figure 51. Change PC10 Password Screen This functions exits from the PC10 Configurator and saves all default settings. 55

68 MI April Operation 56

69 Appendix A. Troubleshooting PC10 Error Messages The table below lists the error messages that may appear during operation. Each message displays the error and a recommended action to correct the indicated problem. Table 6. Error Messages Message Abort Function? All Changes will be Lost! Aborting print operation A file cannot be copied to itself. Select another database file. Bad record in the parameter file. Reload from install diskettes. Calibration Data is Out of Range. Check calibration data and recalibrate. Calibration was not successful! Go to HELP screen for more information. Cannot execute DOS shell. Contact Foxboro for help. Cannot open file help file (ITCHELP.DAT). No Help files are Available Cannot perform this operation while xmtr is in the Write Protect Mode. You must disable Write Protect Mode to complete this operation. CFT10 Flow Zero Calibration. Set flow to zero before proceeding. CFT15 Flow Zero Calibration. Set flow to zero before proceeding. Confirmation of Password Failed. Password will not be changed. Conversion is not Complete. - Do you want to restore original database? Explanation/Action User selected ESCAPE during procedure. Select NO to return to screen or YES to quit. The printer didn t respond. Print report to a data file until printer is working. Select another database file. A database definition file is required for each transmitter type. The files are automatically loaded during the install procedure. If these files have been corrupted, you must re-install the files from the distribution diskettes. If the re-install does not correct the problem, contact Foxboro for help. Check calibration data and recalibrate. Check the HELP screen to determine the cause. Contact Foxboro. Re-load help files from install diskette. (Reinstall PC10.) Disable Write Protect Mode and retry. Set flow to zero before proceeding. Set flow to zero before proceeding. The old password must be entered correctly in order to change the password. During 820 conversion, the database has already been changed. You should restore the database before quitting the procedure. 57

70 Appendix A. Troubleshooting MI April 1997 Table 6. Error Messages (Continued) Message Conversion not Complete. - Do you want to abort procedure? CRC error in transferred database. Please return HHT and PC to menu and try again. Custom Measurement Units are for Custom Inputs Only. Select Standard Measurement Units. Database Change was made with the Local Key Pad. Please Verify: Line Size / Meter Factor / Flow Upper Range. Database file is not complete - Cannot use for Restore. This data cannot be written to the connected transmitter! Data Entry Screen is not in current directory. Selected operation cannot be performed. Data Not in Recommended Range (5 Up and 4 Down). Do you want to override? Data Point Beyond Transmitter Range. - Do you want to override? Data Points Not Within Recommended Span (10%). - Do you want to override? Default datafile cannot be deleted. Check file attributes and write protect on disk. Directory name invalid. Check directory names on drive and re-enter. Directory specified does not exist. Display Upper Range Invalid. 1.0 <= Display Upper Range <= Do you want to write the correct file validation? During 820 conversion, the conversion procedure has not been completed. Aborting may cause the database to be invalid. An error has occurred while transferring a database file to or from the HHT. Try again. If error persists, contact Foxboro. The custom units are only valid for special RTT10 transmitters. Select units from remaining selections. A change was made using the IMT20/IMT10 local display pushbuttons. The local changes are not automatically reflected in the database displayed. Check values and change to the correct settings where necessary. An attempt was made to download a complete database file using File-Restore Xmtr for a file that was not originally saved with the File-Save Xmtr to File function. To download configuration data only, select Write File to Xmtr. The data entry screen files are required for each screen. The files are automatically loaded during the install procedure. If these files have been inadvertently deleted, you must re-install the files from the distribution diskette. If the re-install does not correct the problem, contact Foxboro for help. Conversion data point should be entered as 5 points upscale, and 4 points downscale to correct for hysteresis. Conversion data point is bad. Select No to enter a good value. Select Yes to use values entered. Conversion data points are bad. Select No to enter good values. Select Yes to use values entered. These files are necessary files and cannot be deleted. Check name and re-enter. Explanation/Action You must create the directory in DOS before selecting this directory. IMT10/IMT20 Display Upper Range Value is out of range. Re-enter data. File validation is incorrect. Select YES to correct the file. Then print a report to verify the file data. 58

71 Appendix A. Troubleshooting MI April 1997 Table 6. Error Messages (Continued) Message Error Message Not Found. Please check if ITCERROR.DAT is in current directory. Error Reading Data Entry Screen from Disk. Selected operation cannot be performed. File and connected transmitter are not same type. This data cannot be written to the connected transmitter! File Exists! Do you want to Overwrite? File Selected is a PC10 Default File. No Comments are Available. File transfer procedure step is out of sequence. Please return HHT and PC to menu and try again. File validation had been corrected. You should immediately print a report of this file and inspect it. Flow Zero Operation Aborted. Check flowtube status. Function is not valid for Transmitter if BOTH measurements are in EITHER square root mode or linear %. Function is not valid for transmitter in digital mode. Select <Configure> to change transmitter mode. Help file not found. Invalid Configuration: Measurement #1 is not zero based. It will be set to zero based, full scale, pressure units. Explanation/Action The error file contains all PC10 error messages. The file is automatically loaded during the install procedure. If this file has been inadvertently deleted, you must re-install the file from the distribution diskettes. If the re-install does not correct the problem, contact Foxboro for help. The data entry screen files are required for each screen. The files are automatically loaded during the install procedure. If these files have been inadvertently deleted, you must re-install the files from the distribution diskettes. If the re-install does not correct the problem, contact Foxboro for help. Data cannot be written if you try to download a database file that is different from that of the connected transmitter. Check the transmitter type and print a report of the database file to determine which is correct. The file selected already exists. Select YES to overwrite the old file with the new file. The old file will be unrecoverable. User has selected to add, copy, or read comments from a default file. The default files are for system use only and may not be modified. An error has occurred while transferring a database file to or from the HHT. Try again. If error persists, contact Foxboro. Print a file of this report and check it. User elected to abort the CFT10 flow calibration. Change mode of one measurement or abort function. Select <Configure> to change transmitter mode. Re-load help files from install diskette. No action required. Measurement will be set to zero based, full scale, pressure units. 59

72 MI April 1997 Appendix A. Troubleshooting Table 6. Error Messages (Continued) Message Invalid Configuration: Measurement #2 is not zero based. It will be set to zero based, full scale, pressure units. Invalid Configuration: Measurement #1 is in square root mode. It will automatically be set to linear mode. Invalid Configuration: Measurement #2 is in square root mode. It will automatically be set to linear mode. Invalid Entry. Please Re-enter. Invalid Flowtube Data. Change Model Code and/or Reference K-Factor. Invalid System Date and Time. Set System Date and Time via DOS Shell. Lining Material Invalid for Selected Linesize. ma Output must be configured for 0-20 ma or 4-20mA. Select <Config> to change configuration before doing ma Calibration. Measurement #2 Units not Configured. Cannot Swap Measurement #1 and Measurement #2 Units. New Scale Factor is Out of Range. Check Calibration Data and Re-Calibrate. Not Applicable for Transmitter Revision. Selected operation cannot be performed. Not Enough Memory to Display Data Entry Screen. Selected operation cannot be performed. No help files are available. Reload help files from install diskette. No target file given for this operation. A target file must be selected to copy comments. Nothing received from HHT. Start file transfer with HHT. No transmitter database files were found. Reload program from Install Diskettes or call Foxboro for assistance. Explanation/Action No action required. Measurement will be set to zero based, full scale pressure units. No action required. Measurement will automatically be set to linear mode. No action required. Measurement will automatically be set to linear mode. Re-enter. Change Model Code and/or Reference K-Factor. The computer date and time are invalid. Exit to DOS and set the date and time. Select correct IMT10/IMT20 lining material for flow tube selected. Select <Config> to change configuration before doing ma calibration. The pressure secondary units cannot be off if you want to swap the measurement units. Set the secondary units, then select swap. The IMT10/IMT20 calibration produced a bad scale factor. Verify that the flow applied and entered is correct. The function selected does not apply for the transmitter revision or type connected. Check if computer has the necessary memory required by PC10. You may have to unload one or more memory-resident programs in order to run PC10. Reload help files from install diskette. The copy procedure requires two files to be selected: a source and a target. During File Transfer, the HHT is not sending the database. The HHT software must be L0122EV or later. There are no files in the directory selected. Select new directory or save files to the current directory. 60

73 Appendix A. Troubleshooting MI April 1997 Table 6. Error Messages (Continued) Message Old password is incorrect. Correct password must be entered to change to new password. Password Confirmed. Setting New PC10 Password. Password Incorrect. Selected Operation cannot be performed. Password must be at least six characters long. Please re-enter new password. Password Validation Failed! Contact Foxboro for help. Points must be either monotonically increasing or decreasing. Please Re-enter. Printer not responding. Aborting print operation. Pulse Resolution selected is below the minimum allowed value. Set Pulse Resolution to the minimum setting. Pulse Resolution has been set to the minimum allowed value. Select Configure to verify or change Pulse Resolution. Pulse Scale Out of Range. 0.1 <= Pulse <= Scale Factor Out of Range. Check Meter Factor, LineSize, and Flow Upper Range. Select <Test-Xmtr Status> to Check Transmitter Health. Sorry, trend display is only available with VGA video. The measurement will use the standard display. Source directory & target directory are the same. A file cannot be copied to itself. Span Too Small. Check Pressure Applied. Stability Error - Measurement Reading Invalid. Check Pressure Source and Re-Calibrate Point. Explanation/Action Enter correct old password; then you may change to new password. The password has been changed. The correct password must be entered to perform the selected function. Re-enter new password using at least six characters. The password stored on disk has been corrupted. Enter points in increasing or decreasing order. Printer on selected port is not responding. Check if printer is online and the PC10 printer port (Defaults) is set correctly. Set Pulse Resolution to minimum setting. Select Configure to verify or change Pulse Resolution. Re-enter correct IMT10/IMT20 pulse scale value. Check the IMT10/IMT20 tube configuration and correct necessary values. Transmitter indicates a status error. The Test function will check the transmitter status and display any errors. Select a new target directory to copy the file into. During pressure calibration, the calibration pressure is too low. Check calibration points and pressure source. The pressure source is not stable enough for the operation. Check fittings and source before continuing. 61

74 MI April 1997 Appendix A. Troubleshooting Table 6. Error Messages (Continued) Message Tag Numbers are different. Do you want to continue? The calibration points are invalid. Points must be entered from low point to high point. The Custom LRV and URV Values Cannot be Equal. Please Re-enter. The ma Calibration is Out of Range. Check equipment and recalibrate. The calibration value is at the low limit. Please try a smaller change or accept the current value. The calibration value is at the high limit. Please try a smaller change or accept the current value. There are no comments in this database file. Select another database file. The RTT10 Custom Curve is Not Valid. Select Custom Curve to set Custom Calibration. The RTT10 Custom Curve is Off. Transmitter is Using Factory Calibration. The RTT10 Custom Curve is On. Transmitter is Using Custom Calibration. Transmitter database was NOT saved. Check file attributes and write protect on disk. Transmitter database was NOT saved. Please check transmitter connections and port setting. Transmitter data not completely written. Redo from start or perform <File-Restore Xmtr>. Transmitter is Connected to I/A Series System in Remote Mode. Put Transmitter Offline from I/A Series System to make Local Changes. Explanation/Action The database file being downloaded to the transmitter has a different tag number. Confirm the file is correct before proceeding with the download. Re-enter calibration points from low point to high point. Enter LRV and URV values that are not equal. The calibration performed was out of range. Transmitter will be set to a valid state. Check ma output and re-calibrate if necessary. Enter a smaller change or accept the current value. Enter a smaller change or accept the current value. User has elected to read or copy comments from a file that does not contain comments. User has selected to turn-on custom curve but it is invalid. Valid data points must be entered before using the custom calibration. None transmitter is already configured as desired. None transmitter is already configured as desired. Check file attributes and write protect on disk. Check transmitter connections and port setting. An error has occurred while writing data to the transmitter. Verify transmitter is still communicating and has not been disconnected. Re-try procedure. CFT10 transmitter is connected to I/A Series system. Local changes cannot be made until the transmitter is put offline at the I/A Series station. 62

75 Appendix A. Troubleshooting MI April 1997 Table 6. Error Messages (Continued) Message Transmitter is in Signal Lock Mode (External Contact Closed). Open External Contact to make Transmitter Changes with PC10. Transmitter is in Sqroot Mode. Change to Linear to Calibrate? Transmitter is Not On-line. Retry? Transmitter is Off-line (Measurements Invalid!). Transmitter Module Incompatible. Unable to perform Restore operation. Transmitter must be in Analog Mode. Select <Config> to Change Transmitter Mode. Transmitter must be in Digital Mode. Select <Config> to Change Transmitter Mode. Transmitter not On-line - Set On-line? Transmitter Responded with a Mode Error. Select <Test - Go On-line> and Repeat Operation. Unable to access text string file. (ITCSTRNG.DAT). Please check drive and directory specifications. Unable to allocate enough memory. Contact Foxboro for help. Explanation/Action The IMT10/IMT20 transmitter cannot be changed when the external contact is closed. The pressure transmitter must be calibrated in linear mode. If YES is selected, the transmitter will be changed to linear during calibration and back when calibration is complete. Transmitter did not go online. The transmitter has been put offline; return transmitter to online and measurements will again be valid. The wrong 820 database file was selected to download to the transmitter. Check the file (by printing a report) and the transmitter type. Transmitter is in the wrong mode for the function selected. The mode may be changed in the configuration screen. Transmitter is in the wrong mode for the function selected. The mode may be changed in the configuration screen. The transmitter must be online for measurements to be valid. The transmitter was left in the wrong mode. Put transmitter back online and repeat procedure. The text file contains all PC10 normal operation messages. The file is automatically loaded during the install procedure. If this file has been inadvertently deleted, you must re-install the file from the distribution diskettes. If the re-install does not correct the problem, contact Foxboro for help. If message occurs during file operation, there are too many data files in the selected drive for the amount of memory available. Try to change directories and display fewer files. If the message occurs when trying to run the DOS shell, there is not enough memory to perform a DOS Shell function. You must exit PC10 to perform DOS functions. 63

76 MI April 1997 Appendix A. Troubleshooting Table 6. Error Messages (Continued) Message Unable to communicate with transmitter. Please check transmitter connections and port setting. Unable to delete file. Check file attributes and write protect on disk. Unable to create a file using this name. Unable to open database file. Unable to load all data from database file. Please check file and directory specifications. Unable to load default database from file. Please check drive and directory specifications. Unable to load transmitter parameter table. Check for parameter files in current directory. Unable to load transmitter parameter table. Bad record in parameter file. Reload from install diskette. Unable to load all data from database file. Unable to locate COMMAND.COM; no COMSPEC environment variable. Cannot execute DOS shell. Unable to open configuration file (ITCCFG.DAT) in current directory. Check available disk space. Unable to open database file. Please check drive and directory specifications. Explanation/Action The transmitter is not responding. Check if PC10 modem is connected correctly and the correct communication port has been selected. See Diagnostic Procedures on page 66. The transmitter file selected for deletion cannot be deleted. Make sure you have write permission for the file and that the disk is not write protected. File name is not valid. Enter a valid file name and proceed. Check file and directory specifications. A database default file is required for each transmitter type. The files are automatically loaded during the install procedure. If these files have been inadvertently deleted, you must re-install the files from the distribution diskettes. If the re-install does not correct the problem, contact Foxboro for help. A database definition file is required for each transmitter type. If the files have been inadvertently deleted, you must re-install the files from the distribution diskettes. If the re-install does not correct the problem, contact Foxboro for help. Reload from install diskette. The file has been corrupted. Re-save file from the transmitter. DOS shell is not available. You must exit PC10 to perform DOS functions. The start-up configuration file is not available. The configuration file contains the system default information (comm port, printer port) and the password. To start the program without the configuration file, you must go to the PC10 directory, type ITC nopassword. A default configuration will be used. Go to Defaults-Set PC10 Defaults to set correct configuration. Upon exiting PC10, a new configuration file will be written. The password must immediately be set. The file cannot be opened. Verify that the name and path are correct. 64

77 Appendix A. Troubleshooting MI April 1997 Table 6. Error Messages (Continued) Message Unable to open target file for this operation. Check file attributes and write protect on disk. Unable to read <parameter>. Unable to read transmitter database. Check Transmitter Connection and Parameter Table. Unable to read transmitter ID information. Please check transmitter connections and port setting. Unable to write <parameter>. Unrecognized transmitter type. Upper range value is not within range. Please re-enter. Value is Out of Range. Please Re-Enter. Warning: Low Flow Cut In and Upper Range Value are not within recommended span. Check value entered. Warning! The file validation failed! File may be corrupt! You should immediately print a report of this file and inspect it! Warning: Transmitter Sensor Types Differ. Check Transmitter Upper Range Limit. Xmtr Status Error. Select <Test-Xmtr Status> to Evaluate. You must change the master password before PC10 will run. Please re-enter new password. Explanation/Action The target file selected cannot be opened. Verify that path exists and that disk is not write protected. The parameter designated could not be read. Check Transmitter Type and PC10 Revision. Check transmitter type and revision. Check the PC10 version and verify that the transmitter is supported. Make sure the parameter file has not been corrupted. Check transmitter type and revision. Check the PC10 version and verify that the transmitter is supported. The parameter designated could not be written. Check Transmitter Type and PC10 Revision. Check Transmitter Type and PC10 Revision. Enter upper range value that is within range of transmitter. Value entered is out of range. Check value before proceeding. Check value entered; re-enter new value. Each database file is validated as it is loaded. If the validation fails, the file should be printed and inspected to be sure data has not been corrupted. The type of file selected for the restore is different from that of the connected transmitter. Before proceeding, verify that the file is the correct one to write to the transmitter. Transmitter indicates a status error. The Test function will check the transmitter status and display any errors. Re-enter new password. 65

78 MI April 1997 Diagnostic Procedures Appendix A. Troubleshooting If a problem occurs during PC10 operation, an error message is usually displayed that will help you localize the fault and take appropriate action. If this does not work, use the following general troubleshooting procedure: 1. Check the loop wiring and verify that power is present on all devices and that all devices are connected properly. 2. Check the LEDs on the modem to determine the modem status. When the Listen light is on, the modem is in the receive mode, ready to accept incoming data. When the PC10 attempts to communicate with the transmitter, the modem is in the send mode and the Talk light blinks on and off. If the Listen light is not on, make sure you are set to the correct communication port. 3. To determine whether the problem is a communication failure, a computer failure, or a transmitter failure, substitute an HHT for the computer and see if the problem persists. If the HHT works correctly, see failure analysis flow chart (Figure 52) at the end of this Appendix. If the HHT does not work, check the transmitter. 4. If the computer is OK and communication is OK, use the PC10 Test - Diagnostic functions to check transmitter status. If a FAIL condition is present, take action to correct that condition. 5. If the transmitter, communication system, and computer are OK, check the PC10 software. Verify that all files reside in the specified directories. If this does not identify the problem, try reloading the PC10 software and/or restoring database files from your backup. 6. If all else fails, contact Foxboro Technical Assistance Center at FOXBORO. When calling, please have available all pertinent information about your PC (processor type, speed, RAM, disk size, etc.), your software (Version No.), and a description of your problem. It is also helpful if your PC is running PC10 at the time you call. 66

79 Appendix A. Troubleshooting MI April 1997 PC10 Files The following is a list of PC10 files and descriptions. File PC10.BAT ITC.EXE Description PC10 batch file that will change to your PC10 directory and run the PC10 executable. PC10 executable program. 820.P Transmitter default configuration file. 860.Q Transmitter default configuration file. RTT10.T00 RTT10 Transmitter default configuration file. RTT20.R00 RTT20 Transmitter default configuration file. IMT20.M00 IMT20 Transmitter default configuration file. IMT25.I00 IMT25 Transmitter default configuration file. CFT10.C00 CFT10 Transmitter default configuration file. CFT15.D00 CFT15 Transmitter default configuration file. PRESSURE.X00 I/A Series Pressure Transmitter default configuration file VORTEX.V00 Vortex Transmitter default configuration file 870EC.E00 870ITEC Transmitter default configuration file 870PH.H00 870ITPH Transmitter default configuration file ITCCFG.DAT PC10 default file containing comm port, printer port, and encoded password. ITCHELP.DAT File containing all available help screens for help menu item. ITCTITLE.DAT PC10 initial title screen. ITCSTRNG.DAT File containing all PC10 ascii text messages. ITCERROR.DAT File containing all PC10 error messages. PARAM0.DAT 820 parameter definition table. PARAM1.DAT RTT10 parameter definition table. PARAM2.DAT IMT20 parameter definition table. PARAM3.DAT CFT10 parameter definition table. PARAM4.DAT 860 parameter definition table. PARAM5.DAT Vortex parameter definition table. PARAM6.DAT I/A Series parameter definition table. PARAM7.DAT 870ITEC parameter definition table. PARAM8.DAT 870ITPH parameter definition table. PARAM9.DAT IMT25 parameter definition table. PARAM10.DAT RTT20 parameter definition table. PARAM11.DAT CFT15 parameter definition table. *.FRM Binary files containing all data entry screens. *.HLP Text files for help menu item displays. *.WIN Binary files containing all on-line help screens. 67

80 MI April 1997 Appendix A. Troubleshooting If any of these files are deleted, re-install them from the installation diskette. Note that the PC10 program will run without the *.WIN or the *.HLP files, but no help will be available. All other files are required for PC10 operation. Transmitter Status Error Messages Table 7 lists status error messages, explanations, and recommended actions for various transmitter types. Table 7. Transmitter Status Error Message Message Explanation Recommended Action 820,860,I/A Series Pressure Transmitters Busy Transmitter is busy. If problem persists, select Test - Go On-line. If this does not clear problem, contact Foxboro. Init Required Transmitter is re-initializing on reset. If problem persists, select Test - Go On-line. If this does not clear problem, contact Foxboro. Diagnostic Error Sec Status Err Programming EEPROM Bad Message Bad Function Poor Health S1 Out of Rng S2 Out of Rng S3 Out of Rng Indicates an active diagnostic error. Indicates an error in second status. Transmitter is writing data to EEPROM. Transmitter received a bad message. Transmitter received a bad message. Transmitter is indicating poor health because of another status or diagnostic error. Sensor input out of range. (860) transmitter board temperature out of range. (820) transmitter board temperature out of range. (860) transmitter sensor temperature out of range. See diagnostic error message to determine problem and corrective action. The second status error is shown in Column 2 of the screen display. If problem persists, select Test - Go On-line. If this does not clear problem, contact Foxboro. Select Test - Go On-line. If this does not clear problem, contact Foxboro. Select Test - Go On-line. If this does not clear problem, contact Foxboro. See other error reported. Replace sensor. Transmitter may be configured to continue operating and use a default temperature for measurement compensation. Transmitter may be configured to continue operating and use a default temperature for measurement compensation. Replace sensor. RTT10/RTT20 Transmitters Busy Transmitter is busy. If problem persists, select Test - Go On-line. If this does not clear problem, contact Foxboro. 68

81 Appendix A. Troubleshooting MI April 1997 Init Required Sec Status Err Programming EEPROM Bad Message Bad Function Transmitter is re-initializing on reset. Indicates an error in second status. Transmitter is writing data to EEPROM. Transmitter received a bad message. Transmitter received a bad message. If problem persists, select Test - Go On-line. If this does not clear problem, contact Foxboro. The second status error is shown in Column 2 of the screen display. If problem persists, select Test - Go On-line. If this does not clear problem, contact Foxboro. Select Test - Go On-line. If this does not clear problem, contact Foxboro. Select Test - Go On-line. If this does not clear problem, contact Foxboro. Bad Sensor #1 Sensor #1 malfunction. Check and/or replace Sensor #1. Bad Sensor #2 Sensor #2 malfunction. Check and/or replace Sensor #2. Standards Fail Internal RTT10 tests have failed. Replace electronics. IMT10/IMT20 Transmitters Busy Transmitter is busy. If problem persists, select Test - Go On-line. If this does not clear problem, contact Foxboro. Initializing Diagnostic Error Sec Status Err Transmitter is re-initializing on reset. Indicates an active diagnostic error. Indicates an error in second status. If problem persists, select Test - Go On-line. If this does not clear problem, contact Foxboro. See diagnostic error message to determine problem and corrective action. The second status error is shown in Column 2 of the screen display. Signal Lock External contact is set. Set by user; no action required. Bad Message Transmitter received a bad message. Select Test - Go On-line. If this does not clear problem, contact Foxboro. IMT25 Transmitters Busy Transmitter is busy. If problem persists, select Test - Go On-line. If this does not clear problem, contact Foxboro. Init Required Initializing is required. If problem persists, select Test - Go On-line. If this does not clear problem, contact Foxboro. Diagnostic Error Sec Status Err Table 7. Transmitter Status Error Message (Continued) Message Explanation Recommended Action Indicates an active diagnostic error. Indicates an error in second status. See diagnostic error message to determine problem and corrective action. The second status error is shown in Column 2 of the screen display. Signal Lock External contact is set. Set by user; no action required. In Startup Transmitter cannot exit its boot code. Correct Diagnostic Error or Secondary Status Error also displayed. Empty Error Pipe is empty. See Empty Pipe Detection in MI

82 MI April 1997 Appendix A. Troubleshooting Electrode Error Coil Error Unreliable measurement of electrode voltage. Unreliable measurement of coil current. CFT10/CFT15 Transmitters Busy Set if EEPROM write is in progress and pending. Initializing Transmitter is re-initializing on reset. Init Required Transmitter is re-initializing on reset. Diagnostic Error Sec Status Error Tube Imbalance Indicates an active diagnostic error. Indicates an error in second status. The tube is partially filled and cannot run. Transmitter unable to generate a reliable measurement of electrode voltage. See MI for additional information. Transmitter unable to generate a reliable measurement of coil current. See MI , for additional information. If problem persists, select Test - Go On-line. If this does not clear problem, contact Foxboro. If problem persists, select Test - Go On-line. If this does not clear problem, contact Foxboro. If problem persists, select Test - Go On-line. If this does not clear problem, contact Foxboro. See diagnostic error message to determine problem and corrective action. The second status error is shown in Column 2 of the screen display. Check flowmeter and process conditions. Cycle power to transmitter. Tube Alarm There is a tube failure. Check flowmeter and process conditions. Bad Message Transmitter received a Select Test - Go On-line. If this does not clear problem, bad message. contact Foxboro. Bad Function Flow Alarm Density Alarm Temperature Alarm Transmitter received a bad message. Indicate presence of a flowmeter alarm condition. Indicate presence of a flowmeter alarm condition. Indicate presence of a flowmeter alarm condition. Vortex Flow Meters Busy Set if EEPROM write is in progress and pending. Init Required Transmitter is re-initializing on reset. Table 7. Transmitter Status Error Message (Continued) Message Explanation Recommended Action Select Test - Go On-line. If this does not clear problem, contact Foxboro. Check flowmeter and process conditions. Check flowmeter and process conditions. Check flowmeter and process conditions. If problem persists, select Test - Go On-line. If this does not clear problem, contact Foxboro. If problem persists, select Test - Go On-line. If this does not clear problem, contact Foxboro. 70

83 Appendix A. Troubleshooting MI April 1997 Table 7. Transmitter Status Error Message (Continued) Message Explanation Recommended Action Diagnostic Error Sec Status Err Programming EEPROM Bad Message Poor Health V-Freq Out of Rng X-Freq Out of Rng Indicates an active diagnostic error. Indicates an error in second status. Transmitter is writing data to EEPROM. Transmitter received a bad message. Transmitter is indicating poor health because of another status or diagnostic error. Vortex frequency is out of range (high). Transmitter temperature is less than -40 C or higher than 80 C. 870ITEC/870ITPH Transmitters Busy Set if EEPRON write is in progress and pending. Init Required Transmitter is re-initializing on reset. Diagnostic Error Programming EEPROM Bad Message Stability Error Poor Health Indicates an active Diagnostic error. Transmitter is writing data to EEPROM. Transmitter is indicating it received a bad message. Transmitter is indicating the raw measurement has been unstable. Transmitter is indicating poor health because of another status or diagnostic error. See diagnostic error message to determine problem and corrective action. The second status error is shown in Column 2 of the screen display. If problem persists, select Test - Go On-line. If this does not clear problem, contact Foxboro. Select Test - Go On-line. If this does not clear problem, contact Foxboro. See other error reported. Check flow and process conditions. Check ambient and process temperature. If problem persists, select Test-Go On-line. If this does not clear problem, contact Foxboro. If problem persists, select Test-Go On-line. If this does not clear problem, contact Foxboro. See diagnostic error message to determine problem and corrective action. If problem persists, select Test-Go On-line. If this does not clear the problem, contact Foxboro. Select Test-Go On-line. If this does not clear the problem, contact Foxboro. Check Transmitter installation manual to verify correct wiring. Select Test-Go On-line. If this does not clear the problem, contact Foxboro. See other diagnostic error messages. 71

84 MI April 1997 Transmitter Diagnostic Error Messages Appendix A. Troubleshooting Table 8 lists the diagnostic error codes and recommended actions for various transmitter types. Table 8. Transmitter Diagnostic Error Messages Code Error Message Recommended Action 820, 860, I/A Series Pressure Transmitters 01 CPU Instruct Error Replace amplifier. 02 ROM Checksum Error Replace amplifier. 03 EEPROM Chksum Err Make a change to the transmitter database and download to the transmitter. If this does not clear problem, replace amplifier. 04 RAM Error Replace amplifier. 05 Power Supply Fail Replace amplifier. 06 Battery Failure Replace amplifier. 07 Input Range Error See status to indicate which input is out of range and make necessary correction. 08 Output I/O Error Replace amplifier. 09 Communication Err Replace amplifier. 0A Math Error Check transmitter database and correct any problems. If problem persists, replace amplifier. 0B RealTime Clock Err Replace amplifier. 0C Input 1 = 0 Sensor input bad, check sensor. 0D Wrong MCU Replace amplifier. 0E Device Failure Replace amplifier. 20 Input 1 > Up Limit Sensor input too high, check sensor. 21 Input 2 > Up Limit (860) transmitter board temperature out of range. Transmitter may be configured to continue operating and use a default temperature for measurement compensation. 22 Input 3 > Up Limit (820) transmitter board temperature out of range. Transmitter may be configured to continue operating and use a default temperature for measurement compensation. (860) transmitter sensor temperature out of range. Replace sensor. 25 Input 2 < Low Limit (860) transmitter board temperature out of range. Transmitter may be configured to continue operating and use a default temperature for measurement compensation. 72

85 Appendix A. Troubleshooting MI April 1997 Table 8. Transmitter Diagnostic Error Messages (Continued) Code Error Message Recommended Action 820, 860, I/A Series Pressure Transmitters (continued) 26 Input 3 < Low Limit (820) transmitter board temperature out of range. Transmitter may be configured to continue operating and use a default temperature for measurement compensation. (860) transmitter sensor temperature out of range. Replace sensor. 29 Input 2 = 0 (860) transmitter board temperature out of range. Transmitter may be configured to continue operating and use a default temperature for measurement compensation. 2F Offline Cfg w/err Replace amplifier. IMT10/IMT20 Transmitters (For additional information, see MI ) 02 ROM Checksum Error Contact Foxboro. 0C Hardware Failure Check line frequency reference voltage per Power Supply Tests procedure. If voltage is incorrect, install new power supply assembly. If voltage is correct, electronics module may be defective. 0D ShortWire/BadSwitch Install new electronics module. 10 Amplifier Bad Install new electronics module. 11 Amplifier Bad Install new electronics module. 12 Coil/Amp/Electrodes Check if correct flowtube size is being used for the process flow range. If correct, re-range transmitter for greater flow rate. Check for buildup of material in flowtube. If present, clean inside of flowtube. 13 Electrodes/Wiring See if buildup of material on electrodes has occurred. If so, clean inside of flowtube. If not, check electrodes and replace if defective. 73

86 MI April 1997 Appendix A. Troubleshooting Table 8. Transmitter Diagnostic Error Messages (Continued) Code Error Message Recommended Action IMT10/IMT20 Transmitters (continued) 14 OpenWire/Coil/LoDrve Check coil wire connections. If connections are OK, disconnect coil drive wires from transmitter and measure resistance between wires. Should be between 1 and 100 Ω. Also measure resistance between each wire and ground. Should be infinite. If resistance values are correct, transmitter power supply or electronics module may be defective. If fault cannot be determined and transmitter is integrally mounted to flowtube, flow tube coils are probably defective. If transmitter is remotely mounted from flowtube, verify that coil drive wires are securely connected. If fault cannot be determined, disconnect coil wires from terminals and measure resistance between terminals. Should be between 1 and 100 Ω. Then verify that resistance between each terminal and ground is infinite. If any resistance is incorrect, the flowtube coil is probably defective. If resistances are correct, install new coil drive wires between flowtube and transmitter. For installation details, refer to MI B External RAM Bad Install new electronics module. 20 Under Range Fill flowtube with process liquid. Verify that conductivity is 5 µs/cm. 21 Over Range Verify that correct flowtube is being used for the process flow range. If correct, re-range transmitter for greater flow rate. 22 Over Range Verify that correct flowtube is being used for the process flow range. If correct, re-range transmitter for greater flow rate. 30 Factory Data Lost Install new electronics module. 31 Invalid P1-P5 Data Check configuration. Reconfigure if necessary. 32 Invalid HHT Data Check PC10/HHT configuration. Reconfigure if necessary. IMT25 Transmitters (For Additional information, see MI ) Invalid Multi Range Reconfigure with a valid Multi Range. Signal Lock See Help message under CI n Operation. A to D Cal Failed Contact Foxboro for assistance. Empty Pipe Uncalibrated Perform Empty Pipe Calibration. 74

87 Appendix A. Troubleshooting MI April 1997 Total Rollover Need Pos Elec Need Neg Elec Need Pos Coil Reconfigure Total Format if necessary and Reset Totals. Check signal wiring between the flowtube and transmitter. Check wiring and flowtube coil. Need Neg Coil Coil Low See MI Coil High Coil Unstable Elec High Elec Unstable Elec Low Empty Unstable Empty Unable to Cal Alarm High Flow Make process change or reconfigure Alm Setpt. Alarm Low Flow Alarm Hi Fwd Tot 1 Alarm Hi Fwd Tot 2 Alarm Empty Pipe Pulse Lag Total CFT10/CFT15 Transmitters 02 ROM Checksum Error Contact Foxboro. 03 EEPROM Chksum Contact Foxboro. EOP ROM Chksum 06 (CFT15 only) 07 (CFT15 only) Table 8. Transmitter Diagnostic Error Messages (Continued) Code Error Message Recommended Action EOP EEPROM Chksum Make process change or reconfigure Tot Alm Setpt and reset totals. Make process change or, if not empty, check wiring and recalibrate. Totalizer is putting out pulses at the maximum rate but falling behind the actual total. Reconfigure totalizer display format so that each pulse represents a larger volume. Press 0 on transmitter keypad while viewing fault from STATUS menu to attempt to clear message. If message persists, contact Foxboro. Press 0 on transmitter keypad while viewing fault from STATUS menu to attempt to clear message. If message persists, contact Foxboro. 13 EEPROM Write Error Contact Foxboro. 14 (CFT15 only) EOP EEPROM Write Press 0 on transmitter keypad while viewing fault from STATUS menu to attempt to clear message. If message persists, contact Foxboro. 1F4 Analog Supply Low Analog power supply voltage is low. Contact Foxboro. 75

88 MI April 1997 Appendix A. Troubleshooting Table 8. Transmitter Diagnostic Error Messages (Continued) Code Error Message Recommended Action 1F5 Analog Supply High Analog power supply voltage is high. Contact Foxboro. 1F6 Drive Supply Low Drive power supply voltage is low. Contact Foxboro. 1F7 Drive Supply High Drive power supply voltage is high. Contact Foxboro. 2BE IPL Comms Failure Contact Foxboro. (CFT15 only) 258 Proc Brd Temp Low The processor PWA temperature is too low. Measurements are invalid. Relocate the transmitter or adjust the temperature. 259 Proc Brd Temp High The processor PWA temperature is too high. Measurements are invalid. Relocate the transmitter or adjust the temperature. 25A Cur Brd Temp Low The current PWA temperature is too low. Measurements are invalid. Relocate the transmitter or adjust the temperature. 25B Cur Brd Temp High The processor PWA temperature is too high. Measurements are invalid. Relocate the transmitter or adjust the temperature. 2BC Sensor Stalled Signal received from flowtube sensors is below minimum required level. Measurement invalid. Contact Foxboro. 2BD Tube Imbalance An imbalance has been detected between sensors in the flowtube. Transmitter switches OFFLINE. All measurement stops. Contact Foxboro. 320 RTD Meas Below Min Resistance for temperature measurement is below minimum required. Measurements invalid. Contact Foxboro. 321 RTD Meas Above Max Resistance for temperature measurement is above maximum allowed. Measurements invalid. Contact Foxboro. 322 Osc. Freq High Flowtube driving oscillator frequency is above the maximum allowed. Measurements invalid. Contact Foxboro. 323 Osc. Freq Low Flowtube driving oscillator frequency is below the minimum required. Measurements invalid. Contact Foxboro. 76

89 Appendix A. Troubleshooting MI April 1997 Table 8. Transmitter Diagnostic Error Messages (Continued) Code Error Message Recommended Action 324 Phase Diff High Excessive signal phase difference between sensors. Flow measurement and total invalid. Confirm that mass flow rate does not exceed maximum mass flow rate of flowtube. Contact Foxboro. 384 Process Temp Low Process temperature below lower flowmeter limit. Adjust process temperature. 385 Process Temp High Process temperature exceeds upper flowmeter limit. Adjust process temperature. 386 Process Dens Low Process density below lower flowmeter limit. Adjust process density. 387 Process Dens High Process density exceeds upper flowmeter limit. Adjust process density. 388 Flow Over Rev Lim Flow exceeds calibration limit in the reverse direction. Adjust process or calibration limit, as required. 389 Flow Over Fwd Lim Flow exceeds calibration limit in the forward direction. Adjust process or calibration limit, as required. Vortex Transmitters 02 ROM Checksum Error Replace amplifier. 03 EEPROM Chksum Err Make a change to the transmitter database and download to the transmitter. If this does not clear problem, replace amplifier. 04 RAM Error Replace amplifier. 0A Math Error Check transmitter database and correct any problems. If problem persists, replace amplifier. 0C Sensor Elec Failure Attempt to cycle power. If problem persists, contact Foxboro. 0E Core Failure Attempt to cycle power. If problem persists, contact Foxboro. 20 Vortex Freq High Check meter specifications against flow requirements. 21 Xmtr Temp High Check process temperature. Contact Foxboro. 25 Xmtr Temp Low Check process temperature. Contact Foxboro. 2F Offline Cfg w/ Error Take transmitter offline, modify a parameter or mode, change parameter or mode back to previous value and place transmitter online. If problem persists, contact Foxboro. 32 Bad Database Cfg Check transmitter database and correct any wrong settings. Re-initialize transmitter. If problem persists, contact Foxboro. 77

90 MI April 1997 Appendix A. Troubleshooting Table 8. Transmitter Diagnostic Error Messages (Continued) Code Error Message Recommended Action 870ITEC Transmitters Probe Error Transmitter is indicating a probe error has been detected. Temp Comp Error Unstable Temperature Unstable Measurement Display Underrange Display Overrange RTD Cal Tolerance Meas Stability Therm Cal Tolerance Cal Comp Error ma Underrange ma Overrange Transmitter is indicating the temperature measurement subsection has encountered a problem. The transmitter has detected an unstable temperature measurement. The transmitter has detected an unstable process measurement. The transmitter has detected that the primary measurement is too low. The transmitter has detected that the primary measurement has exceeded the configured scale. The RTD calibration is not within tolerance. The primary measurement is not stable for the calibration. The thermistor calibration is not within tolerance. The transmitter has detected an error in the previous calibration. The transmitter has detected that the computed value of the ma output is too low. The transmitter has computed the value of the ma output is too high. See other diagnostic error messages. Check ATC connection. Verify process temperature. Select Test-Go On-line. If this does not clear the problem, contact Foxboro. Check ATC connections as described in the Transmitter Installation manual. Select Test-Go Online. If this does not clear problem, contact Foxboro. Check measurement probe connection as described in the Transmitter Installation manual. Select Test- Go On-line. If this does not clear problem, contact Foxboro. Check probe connection as described in the Transmitter Installation manual. Select Test-Go Online. If this does not clear problem, contact Foxboro. Check probe connection as described in the Transmitter Installation manual. Select Test-Go Online. If this does not clear problem, contact Foxboro. Recalibrate the RTD, as described in the manual. If this does not clear the problem, contact Foxboro. Check all connections as described in the Transmitter Installation manual. If the problem persists, call Foxboro. Recalibrate the thermistor, as described in the manual. If the problem persists, contact Foxboro. Recalibrate the transmitter. If the problem persists, contact Foxboro. Check the ma output lower range. Check process. Check the ma output upper range. Check process. 78

91 Appendix A. Troubleshooting MI April 1997 Table 8. Transmitter Diagnostic Error Messages (Continued) Code Error Message Recommended Action ATC Open The transmitter has detected that the ATC measurement is outside the range for the selected ATC. 870ITEC Transmitters (Continued) Cal Required The transmitter requires a calibration. Cal Required APP 1 Cal Required APP 2 Cal Required APP 3 Comp Underrange Comp Overrange Leak Error Calibration is required for application. Calibration is required for application. Calibration is required for application. Compensation table lookup is out of the table range. Compensation table lookup is out of the table range. The transmitter diagnostic function has detected a leak error. 870ITPH Transmitters Probe Error Transmitter is indicating a probe error has been detected. Temp Comp Error Amplifier Error Unstable Temperature Transmitter is indicating the temperature measurement subsection has encountered a problem. The transmitter has detected an out of range PH/ORP/ISE error. The transmitter has detected an unstable temperature measurement. Check ATC connections in the Transmitter Installation manual. Select Test-Go On-line. If this does not clear problem, contact Foxboro. Perform a calibration as described under Calibration section. Perform a calibration as described under Calibration section. Perform a calibration as described under Calibration section. Perform a calibration as described under Calibration section. Check process. Verify probe connections. Select Test-Go On-line. If this does not clear problem, contact Foxboro. Check process. Verify probe connections. Select Test-Go On-line. If this does not clear problem, contact Foxboro. Check probe and transmitter connections as described in the Transmitter Installation manual. Select Test-Go On-line. If this does not clear problem, contact Foxboro. See other diagnostic error messages. Check ATC connection. Verify process temperature. Select Test-Go On-line. If this does not clear problem, contact Foxboro. Check probe. Select Test-Go On-line. If this does not clear problem, contact Foxboro. Check ATC connections as described in the Transmitter Installation manual. Select Test-Go Online. If this does not clear problem, contact Foxboro. 79

92 MI April 1997 Appendix A. Troubleshooting Unstable Measurement Display Underrange The transmitter has detected an unstable process measurement. The transmitter has detected that the primary measurement is too low. 870ITPH Transmitters (Continued) Display Overrange RTD Cal Tolerance Meas Stability Therm Cal Tolerance Cal Slope Error Cal Comp Error ma Underrange ma Overrange ATC Open Cal Required Comp Underrange Table 8. Transmitter Diagnostic Error Messages (Continued) Code Error Message Recommended Action The transmitter has detected that the primary measurement has exceeded the configured scale. The RTD calibration is not within tolerance. The primary measurement is not stable for the calibration. The thermistor calibration is not within tolerance. A slope error has occurred as a result of the previous calibration. The transmitter has detected an error in the previous calibration. The transmitter has detected that the computed value of the ma output is too low. The transmitter has computed the value of the ma output is too high. The transmitter has detected that the ATC measurement is outside the range for the selected ATC. The transmitter requires a calibration. Compensation table lookup is out of the table range. Check measurement probe connection as described in the Transmitter Installation manual. Select Test- Go On-line. If this does not clear problem, contact Foxboro. Check probe connection as described in the Transmitter Installation manual. Select Test-Go Online. If this does not clear problem, contact Foxboro. Check probe connection as described in the Transmitter Installation manual. Select Test-Go Online. If this does not clear problem, contact Foxboro. Recalibrate the RTD, as described in the manual. If this does not clear the problem, contact Foxboro. Check all connections as described in the Transmitter Installation manual. If the problem persists, contact Foxboro. Recalibrate the thermistor, as described in the manual. If the problem persists, contact Foxboro. Check probe and recalibrate transmitter. If the problem persists, contact Foxboro. Recalibrate the transmitter. If the problem persists, contact Foxboro. Check the ma output lower range. Check process. Check the ma output upper range. Check process. Check ATC connections in the Transmitter Installation manual. Select Test-Go On-line. If this does not clear problem, contact Foxboro. Perform a calibration as described under Calibration section. Check process. Verify probe connections. Call Foxboro if the problem persists. 80

93 Appendix A. Troubleshooting MI April 1997 Table 8. Transmitter Diagnostic Error Messages (Continued) Code Error Message Recommended Action Comp Overrange Leak Error Pre Amp Failure Compensation table lookup is out of the table range. The transmitter diagnostic function has detected a leak error. The transmitter diagnostic function has detected an overrange condition on the raw measurement. Check process. Verify probe connections. Call Foxboro if the problem persists. Check probe and transmitter connections as described in the Transmitter Installation manual. Select Test-Go On-line. If this does not clear problem, contact Foxboro. Check probe and transmitter connections as described in the Transmitter Installation manual. Select Test-Go On-line. If this does not clear problem, contact Foxboro. NOTE: Corrective action for AGING error is to check the value of the slope in the STATUS menu. The glass or ISE electrode may be reaching the end of its useful life if the SLOPE differs greatly from the theoretical value (100% for the univalent electrodes). 81

94 MI April 1997 Appendix A. Troubleshooting Start over at Step #1. You missed something Figure 52. Fault Analysis Chart 82

95 Appendix B. Calibration Data This appendix describes the calibration procedures and data required for the types of transmitters used with the PC10 configurator. 820, 860, I/A Series Pressure Transmitters This section describes the calibration functions and procedures applicable to 820, 860, and I/A Series pressure transmitters. Functions The calibration functions you can perform on 820 and 860 Series transmitters are: Re-Zero Transmitter 1-Point Calibration 2-Point Calibration ReRange ma Calibration Default Calibration 2-Point Conversion (820 Series Transmitters only) 5-Point Conversion (820 Series Transmitters only) Each of the functions is described in this section. Calibration The transmitter output may be re-calibrated with any of the following procedures Re-Zero Transmitter 1-Point Calibration 2-Point Calibration The Re-Zero and 1-Point Calibration procedures adjust the transmitter output. The Re-Zero procedure assumes that the Lower Range Value (LRV) is zero. The 1-Point Calibration procedure allows you to specify the Lower Range Value (LRV), which may or may not be zero. The 2-Point Calibration procedure allows you to specify both Lower Range (LRV) and Upper Range Values (URV). Each transmitter is calibrated at the factory to a specified range. If the new range is the same as the factory range, you should perform only a re-zero or a 1-point calibration procedure. If, however, the rerange operation changes the span by a 2-to-1 ratio or greater, you may need to perform a 2-point calibration. (Refer to MI , MI , and MI , ReRange, for equations that define measurement accuracy after reranging.) If the new span is 83

96 MI April 1997 Appendix B. Calibration Data less than 2x or 1/2 of the existing span, perform a ReRange rather than a calibration with pressure equipment. For all calibration procedures, calibration points are read from the transmitter at the start of the procedure. Also note that if the transmitter is configured for a square root output, the PC10 will place it in linear mode during calibration and reset it to square root mode at the end of the procedure. NOTE: Transmitters must be calibrated using forward action (increasing input increases output). If your transmitter has reverse output action (increasing input decreases output), calibrate it so that calibrated LRV = desired URV and calibrated URV = desired LRV. Then, after calibration, change the LRV and URV back to the correct values. Similarly, if LRV pressure is negative or if URV = 0, calibrate the transmitter so that LRV = 0 and URV = a positive value equal to the span of the transmitter. After you complete the calibration procedure, reset the LRV and URV to the desired values. Example: To calibrate for a range of 100 to 0 inches H 2 O, first calibrate the LRV to 0inches H 2 0 and then calibrate the URV to 100 inches H 2 O. Then rerange the LRV to 100 inches H 2 O and rerange the URV to 0 inches H 2 0. Re-Zero Transmitter In this function, the system first prompts you to set the transmitter input to zero. The measurement screen is then displayed, so that you can verify that the measurement is actually at zero. The system then reads five calibration points, generates a new offset value, and loads the new value into the transmitter. The transmitter is then automatically placed on-line and you return to the Calibrate menu. NOTE: If the transmitter was previously calibrated incorrectly, the measurement from the transmitter may not agree with the applied pressure. For example, if 50 inches H 2 O was applied during calibration, but the user typed in 25 inches H 2 O by mistake, the measured pressure, after downloading the new calibration data to the transmitter, would be in error by 25 inches H 2 O. 1-Point Calibration In this function, you calibrate the transmitter at the Lower Range Value (LRV). You must enter the desired value of the LRV calibration point, as shown in Figure 53. After entering the values, you then apply a known reference pressure for the calibration point and observe the measured value on the screen. (If they do not agree, see note above.) If they agree, press ENTER. The calibration procedure is then complete and you return to the Calibrate menu. 84

97 Appendix B. Calibration Data MI April Point Calibration Figure Point Calibration (820) This function calibrates the transmitter output at two points, the Lower Range Value (LRV) and the Upper Range Value (URV). The sequence of steps is as follows: 1. Apply pressure for the LRV point. 2. Press ENTER. The system then takes five readings and averages the results to calculate the new offset. 3. Apply a known pressure for the URV point. 4. Press ENTER. The system then takes five readings and averages the results to calculate the new slope. The system then loads the new slope and offset into the transmitter. The procedure is now complete and the system returns you to the main Calibrate menu. ReRange Good This function permits you to change the Lower Range Value (LRV) and/or the Upper Range Value (URV) without applying pressure to the transmitter. If you make a very large change in range (turndown ratio greater than 2), however, you may want to recalibrate in order to maintain desired accuracy. (Refer to MI and MI Section for a discussion of accuracy following a rerange operation.) The procedure for performing a ReRange operation is as follows: 1. From the Calibrate menu, select ReRange and press ENTER. This will bring up either the screen shown in Figure 54 or the one in Figure 55 depending on whether Measurement #2 is On or Off and whether the Primary and Secondary is Linear or Square Root. 2. Move to the Lower Range Value (LRV) field and enter the new value. 85

98 MI April 1997 Appendix B. Calibration Data 3. Move to the Upper Range Value (URV) field and enter the desired new value. Note that the new value cannot exceed the value shown in the bottom left corner of the window nor can it be a value that would yield a span less than the minimum span shown in the bottom right corner of the window. 4. When the values are acceptable, press F4 to save and exit from the screen. The PC10 will then download the new values to the transmitter and return you to the Calibrate menu. Good Figure 54. ReRange Screen (820) Figure 55. ReRange Screen (820) (Alternate Screen) 86

99 Appendix B. Calibration Data MI April 1997 ma Calibration As the transmitter was accurately calibrated at the factory, this function is not normally required. To determine whether or not you need to perform this function, insert an accurate ma meter in the loop wiring. If the meter reading does not agree with the ma value shown by the transmitter, you should perform an ma calibration. Make adjustments as required to make the meter readings agree with the ma values reported on the PC10 from the transmitter. To perform an ma calibration, execute the following procedure: 1. From the main Calibrate menu, select ma Calibrate and press ENTER. 2. A screen appears that asks you to select an adjustment option that will change the transmitter 4 ma output (small or large increase or decrease). Select the type of change you want to make and press ENTER. Good Figure 56. ma Calibrate Screen 3. Observe the modified output at the upper right of the screen. If further changes are needed, select the desired change and press ENTER. If acceptable, select Quit and press ENTER. 4. You are then asked to repeat the steps for the 20 ma point. Press Y to continue or N to terminate the procedure. 5. When calibration is complete, you are asked if you want to save the changes to the transmitter. To do so, press Y. The system then saves the new value to the transmitter and returns you to the main Calibrate menu. NOTE: After calibrating a transmitter with a 4-20 ma output signal, use Loop- Cal/mA procedure to check the underrange and overrange output values to make sure they extend beyond 4 ma and 20 ma respectively. 87

100 MI April 1997 Appendix B. Calibration Data Default Calibration A default calibration restores the transmitter database to stored default values. WARNING: This operation should be performed only if the transmitter does not operate correctly. After downloading, the transmitter must be RE-CALIBRATED and RE-CONFIGURED. To perform this operation, execute the following procedure: 1. From the main Calibrate menu, select Default Calibration and press ENTER. This will display the screen shown in Figure 57. Good Figure 57. Default Calibration Screen 2. Press W to write the default calibration to the transmitter (or Q to quit). 2-Point Conversion (820 Transmitters Only) This procedure is used when you convert a conventional 820 to an intelligent 820 or when you replace an intelligent amplifier and a complete database file does not exist. If the complete database file was created previously, using the File - Save Xmtr to File command, do NOT perform a 2-point conversion. Instead, do a File - Restore Transmitter Database operation. To perform a 2-point conversion, execute the following procedure: 88

101 Appendix B. Calibration Data MI April From the main Calibrate menu, select 2-Point Conversion and press ENTER. The screen shown in Figure 58 will then appear. Good Figure Point Conversion Screen 2. You then have the option to enter a new model code. 3. The database will be loaded into the transmitter and you will be asked to confirm or enter the Lower Range Value (LRV) and Upper Range Value (URV). 4. Then, you are asked if you want to apply Lower Calibration Pressure (LRV). The screen will show measured values with the pressure applied. Press ENTER when the reading is stable. 5. The system will ask if you want to apply the upper range calibration pressure. 6. When the procedure is complete, the new data is loaded into the transmitter and you are returned to the main Calibrate menu. 5-Point Conversion (820 Transmitters Only) This procedure is used when you convert a conventional 820 to an Intelligent 820 or when you replace an intelligent amplifier and a complete database file does not exist. If the complete database file was created previously, using the File - Save Xmtr to File command, do NOT perform a 5-point conversion. Instead, do a File - Restore Transmitter Database operation. The 5-Point Conversion is used when you need greater accuracy than afforded by the 2-Point Conversion. To perform this function, execute the following procedure: 89

102 MI April 1997 Appendix B. Calibration Data 1. From the main Calibrate menu, select 5-Point Conversion and press ENTER. The screen shown in Figure 59 will then appear. Good Figure Point Conversion Screen 2. To proceed, press C. 3. You may then select the new model code (823DP-M). 4. The screen will display 9 calibration points (5 increasing pressures and 4 decreasing pressures).the recommended process values will be shown. To change any value, select the value and enter a new value. 5. The system will then prompt you to apply pressure for Point 1 (increasing pressure). The measurement will be displayed and calibration will proceed. 6. The process repeats for each additional point. 7. When you have entered and accepted all 9 points, the calibration is loaded into the transmitter and you are returned to the main Calibrate menu. RTT10 Temperature Transmitters This section describes the calibration functions and procedures applicable to the RTT10 Series transmitters. Functions The calibration functions you can perform on RTT10 Series transmitters are: Re-Zero Transmitter 1-Point Calibration 2-Point Calibration Custom Input Curve ReRange 90

103 Appendix B. Calibration Data MI April 1997 ma Calibration Restore Factory Calibration Enable Custom Curve Restore Factory ma Each of the functions is described in this section. Calibration RTT10 calibration allows you to correct the transmitter output for differences between the input sensor and the standard curve for sensors of that type. The Re-Zero, 1-Point, and 2-Point Calibrations automatically calculate the temperature points and offset values. The custom curve function allows you to enter up to ten sets of points, but you must determine the offset values. Re-Zero Transmitter In this function, the software first prompts you to set the transmitter input to zero. The measurement screen is then displayed, so that you can verify that the measurement is actually at zero. (If it is not, you will have to correct the problem before continuing the procedure.) The software then reads five calibration points, generates a new offset value, and loads the new value into the transmitter. The transmitter is then automatically placed On-line and you are returned to the Calibrate menu. 1-Point Calibration In this function, you calibrate the transmitter at the Lower Range Value (LRV). You must enter the desired value of the LRV calibration point, as shown in Figure 53. After entering the values, you then apply a known reference temperature (or mv) for the calibration point and observe the measured value on the screen. (If they do not agree, performing this procedure should correct the problem.) If they agree, press ENTER. The calibration procedure is then complete and you return to the Calibrate menu. 91

104 MI April 1997 Appendix B. Calibration Data 2-Point Calibration Figure Point Calibration (RTT10) This function calibrates the transmitter output at two points, the Lower Range Value (LRV) and the Upper Range Value (URV). The sequence of steps is as follows: 1. Apply temperature or mv value for the LRV point. 2. Press ENTER. The system takes five readings and averages the results to calculate the new LRV offset. 3. Apply temperature or mv value for the URV point. 4. Press ENTER. The system takes five readings and averages the results to calculate the new URV offset. The system then loads the values into the transmitter. The procedure is now complete and the system returns you to the main Calibrate menu. ReRange Good This function permits you to change the Lower Range Value (LRV) and the Upper Range Value (URV) without applying an input to the transmitter sensor. The procedure for performing a ReRange operation is as follows: 1. From the Calibrate menu, select ReRange and press ENTER. This will bring up the screen shown in Figure From the screen of Figure 54, move to the Lower Range Value (LRV) field and enter the new value. 3. Move to the Upper Range Value (URV) field and enter the desired new value. Note that the new value cannot exceed the value shown in the bottom left corner of the window nor can it be a value that would yield a span less than the minimum span shown in the bottom right corner of the window. 92

105 Appendix B. Calibration Data MI April When the values are acceptable, press F4 to save and exit from the screen. The system will then download the new values to the transmitter and return you to the Calibrate menu. Good Custom Input Curve Figure 61. ReRange Screen (RTT10) This function permits you to correct for inaccuracies in the input sensor by entering measurement and offset values for 12 points on the curve. The system then calculates a smooth input curve that follows these 12 data points. To perform this function, execute the following procedure: 1. From the Calibrate menu, select Custom Input Curve and press ENTER. The system will read the database from the transmitter and then display the screen shown in Figure 62. Good Figure 62. Custom Input Curve (RTT10) 93

106 MI April 1997 Appendix B. Calibration Data 2. As instructed by the displayed text, enter measurement value and temperature offset for each of the points necessary to describe your custom curve. You may enter up to 12 points. For example, if a measurement was and you wanted , enter as the measurement and 0.25 as the offset. 3. When done, press F4 to save and exit from the screen. You are then asked if you want to save the changes to the transmitter. Press Y to do so (N to abort). 4. If you press Y, the new data is loaded into the transmitter and you are returned to the main Calibrate menu. ma Calibration As the transmitter was accurately calibrated at the factory, this function is not normally required. To determine whether or not you need to perform this function, insert an accurate ma meter in the loop wiring. If the meter reading does not agree with the ma value shown by the transmitter, you should perform an ma calibration. Make adjustments as required to make the meter readings agree with the ma values reported on the PC10 from the transmitter. To perform an ma calibration, execute the following procedure: 1. From the main Calibrate menu, select ma Calibrate and press ENTER. 2. A screen appears that asks you to select an adjustment option that will change the transmitter 4 ma output (small or large increase or decrease). Select the type of change you want to make and press ENTER. Good Figure 63. ma Calibrate Screen 3. Observe the modified output at the upper right of the screen. If further changes are needed, select the desired change and press ENTER. If acceptable, select Quit and press ENTER. 4. You are then asked to repeat the steps for the 20 ma point. Press Y to continue or N to terminate the procedure. 94

107 Appendix B. Calibration Data MI April When calibration is complete, you are asked if you want to save the changes to the transmitter. To do so, press Y. The system then saves the new value to the transmitter and returns you to the main Calibrate menu. Restore Factory Calibration This function disables and saves a custom curve and restores the factory calibration curve to the transmitter. To perform this operation, execute the following procedure: 1. From the main Calibrate menu, select Restore Factory Cal and press ENTER. You are then asked if you want to save changes to the transmitter. To do so, press Y (or N to abort). 2. If the loop is in manual, press Y. The factory data is then loaded into the transmitter, it is placed On-line, and you are returned to the main Calibrate menu. Enable Custom Curve This function enables a custom input curve that you previously entered and saved. To perform this function, execute the following: 1. From the Calibrate menu, select Enable Custom Curve and press ENTER. You will then be asked if you want to save changes to transmitter. Press Y to do so. 2. If the loop is in manual, press Y. The custom curve is then loaded into the transmitter, it is placed On-line, and you are returned to the main Calibrate menu. Restore Factory ma This function restores the factory ma calibration to the transmitter. To perform this function, execute the following: 1. From the Calibrate menu, select Restore Factory ma and press ENTER. You will then be asked if you want to save changes to transmitter. To save the changes, press Y. (The transmitter must be in Analog mode to perform this operation.) 2. If you press Y to save the changes, you are asked if the loop is in manual. (The loop must be in manual mode to perform this operation.) 3. If the loop is in manual mode, press Y. The custom curve is then loaded into the transmitter, the transmitter is placed On-line, and you are returned to the main Calibrate menu. RTT20 Temperature Transmitters The calibration functions and procedures applicable to the RTT20 Series transmitters are: 1-Point Calibration 2-Point Calibration 95

108 MI April 1997 Appendix B. Calibration Data 3-Point Calibration 5-Point Calibration Custom Input Curve ReRange ma Calibration Restore Factory ma The 1-, 2-, 3-, and 5-Point Calibration and the Custom Input Curve functions are similar to those described in the previous section on the RTT10 except as noted below. The ReRange, macalibration, and Restore Factory ma functions are the same as those described for the RTT10. 1-Point Calibration The RTT20 permits you to select any temperature within the configured range that is of particular interest to you. You are not required to use the LRV as the calibration point. The net effect is that a constant offset is utilized over the entire sensor curve. To view or change the value entered, see note in Custom Input Curve section below. 2-Point Calibration The RTT20 permits you to select any two temperatures in the region of interest within the configured range of the transmitter. You are not required to use the LRV and URV as the calibration points. The temperatures must be increasing in value. The resulting offsets are then straightline calculated to the LRV and URV. Picture an offset line defining the correction to the standard, starting from the LRV, passing through the two calibration points, and continuing to the URV. To view or change any value entered, see note in Custom Input Curve section below. CAUTION: After performing this calibration, the transmitter should only be used within that configured range LRV and URV). If a rerange or reconfiguration is performed, the transmitter must either be recalibrated or the calibration data cleared. 3- and 5- Point Calibration The RTT20 permits you to select any three (or five) temperatures in the region of interest within the configured range of the transmitter. The temperature must be increasing in value. The resulting offsets are then straightline calculated to the LRV and URV. Picture an offset line defining the correction to the standard, starting from the LRV, passing through the three (or five) calibration points, and continuing to the URV. To view or change any values entered, see note in Custom Input Curve section below. CAUTION: After performing this calibration, the transmitter should only be used within that configured range LRV and URV). If a rerange or reconfiguration is performed, the transmitter must either be recalibrated or the calibration data cleared. 96

109 Appendix B. Calibration Data MI April 1997 Custom Input Curve The custom curve screen functions a little differently. If the Number of Points field is 0, then the transmitter is using the factory installed calibration. There is no enable or disable of the custom curve. If the number of points is 2 to 22, then the transmitter will use the calibration data displayed. To Enable the calibration data, the number of points field will be nonzero and calibration data must appear in the appropriate fields. To Disable the Calibration, press [F5] to clear all values. NOTE: Since it is not possible to leave the default values in memory when performing a custom input curve calibration, it is strongly recommended that the transmitter data base, with the Number of Points = 0, be stored to a file prior to making drastic changes in the calibration data. CAUTION: If all the Measurement/Reference fields are 0, then the number of points must be 0 prior to exiting the custom curve screen. If the number of points is not zero (2-22) and no measured/reference data is entered into the fields on the custom curve data screen, then the transmitter will drive its output to whatever 0 means for that sensor. The transmitter will not respond to any change in input in this condition. The format for entering data in the custom curve screen is to enter a Measurement value and a Reference value. For example, if a measurement value was but you wanted , enter as the measurement number and as the reference number. NOTE: The calibration data from any of the above calibration options is stored in the custom curve memory locations. Therefore, if you wish to view or change a specific data point, you can enter the custom curve selection and view, edit, or clear all values. IMT10/IMT20 Magnetic Flow Transmitters This section describes the calibration functions and procedures applicable to the IMT10 and IMT20 Series magflow transmitters. The calibration functions you can perform on IMT10 and IMT20 Series transmitters are: Flow Calibration ReRange ma Calibration Each of the functions is described in this section. Flow Calibration This function permits you to calibrate the transmitter at a single point with a known flow rate. To perform the function, execute the following procedure: 97

110 MI April 1997 Appendix B. Calibration Data 1. From the Calibrate menu, select Flow Calibration and press ENTER. The screen shown in Figure 64 will then appear. 2. To change the value of the calibration point, move the highlight to Flow Calibration point and enter a new value. 3. Apply an accurate and stable flow rate to the transmitter. The PC10 will calculate a new meter factor to correct the calibration. 4. Press F4 to save the calibration and exit. You will then return to the main Calibrate menu. ReRange Good Figure 64. Flow Calibration (IMT20/IMT10) This function permits you to change the Flow Upper Range Value (URV) and the Display Upper Range Value without applying flow to the transmitter. The procedure for performing a ReRange operation is as follows: 1. From the Calibrate menu, select ReRange and press ENTER. This will bring up the screen shown in Figure Move to the Upper Range Value (URV) field and enter the desired new value. Note that the new value cannot exceed the value shown in the bottom left corner of the window nor can it be a value that would yield a span less than the minimum span shown in the bottom right corner of the window. 3. When the values are acceptable, press F4 to save and exit from the screen. The system will then download the new values to the transmitter and return you to the Calibrate menu. 98

111 Appendix B. Calibration Data MI April 1997 ma Calibration Good Figure 65. ReRange Screen (IMT20/IMT10) As the transmitter was accurately calibrated at the factory, this function is not normally required. To determine whether or not you need to perform this function, insert an accurate ma meter in the loop wiring. If the meter reading does not agree with the ma value shown by the transmitter, you should perform an ma calibration. Make adjustments as required to make the meter readings agree with the ma values reported on the PC10 from the transmitter. To perform an ma calibration, execute the following procedure: 1. From the main Calibrate menu, select ma Calibrate and press ENTER. 2. A screen appears that asks you to select an adjustment option that will change the transmitter 4 ma output (small or large increase or decrease). Select the type of change you want to make and press ENTER. 3. Observe the modified output at the upper right of the screen. If further changes are needed, select the desired change and press ENTER. If acceptable, select Quit and press ENTER. 4. You are then asked to repeat the steps for the 20 ma point. Press Y to continue or N to terminate the procedure. 5. When calibration is complete, you are asked if you want to save the changes to the transmitter. To do so, press Y. The system then saves the new value to the transmitter and returns you to the main Calibrate menu. 99

112 MI April 1997 Appendix B. Calibration Data Figure 66. ma Calibrate Screen (IMT20/IMT10) IMT25 Magnetic Flow Transmitters This section describes the calibration functions and procedures applicable to the IMT25 Series Magnetic Flow Transmitters. The calibration functions you can perform on IMT25 Series transmitters are: ma Calibration Reset Totals Empty Pipe Detect Each of the functions is described in this section. ma Calibration See previous section on ma Calibration for the IMT10/IMT20 Transmitters. Reset Totals Good This procedure will reset the transmitter totals. The Forward, Reverse, and Net Totals are reset as a group. The Grand Total is individually reset. Empty Pipe Detect The Empty Pipe Detector can be used to force the transmitter outputs to stay at zero when the flowtube is empty. The empty pipe circuit must be calibrated to the fluid in the flowtube. The flowtube must be full of process fluid (flowing or still) to use this calibration procedure. The calibration procedure leaves the empty pipe detector in the ON condition. The detector can be turned off in the Configuration menu. 100

113 Appendix B. Calibration Data MI April 1997 CFT10 Mass Flow Transmitters This section describes the calibration functions and procedures applicable to the CFT10 mass flow transmitters. The calibration functions you can perform on CFT10 transmitters are: Re-Zero Transmitter ma Calibration Startup Zero Restore Factory ma Zero Total Each of the functions is described in this section. Re-Zero Transmitter This function permits you to reset the zero point for the transmitter. To execute the operation, use the following procedure: 1. From the Calibrate menu, select Re-Zero Transmitter and press ENTER. The system will then display a screen that prompts you to set flow to zero before proceeding. To proceed, press any key. 2. The screen shown in Figure 67 will then appear. When the value stabilizes, press ENTER to accept. The system takes 300 readings. Figure 67. Re-Zero Transmitter Screen 1 (CFT10) 3. The screen shown in Figure 68 then appears. To save the new offset, press Y (N to abort). 101

114 MI April 1997 Appendix B. Calibration Data Figure 68. Re-Zero Transmitter Screen 2 (CFT10) If you press Y, the data is saved to the transmitter and you are returned to the main Calibrate menu. ma Calibration As the transmitter was accurately calibrated at the factory, this function is not normally required. To determine whether or not you need to perform this function, insert an accurate ma meter in the loop wiring. If the meter reading does not agree with the ma value shown by the transmitter, you should perform an ma calibration. Make adjustments as required to make the meter readings agree with the ma values reported on the PC10 from the transmitter. To perform an ma calibration, execute the following procedure: 1. From the main Calibrate menu, select ma Calibrate and press ENTER. 102

115 Appendix B. Calibration Data MI April A screen appears that asks you to select an adjustment option that will change the transmitter 4 ma output (small or large increase or decrease). Select the type of change you want to make and press ENTER. Figure 69. ma Calibrate Screen 3. Observe the modified output at the upper right of the screen. If further changes are needed, select the desired change and press ENTER. If acceptable, select Quit and press ENTER. 4. You are then asked to repeat the steps for the 20 ma point. Press Y to continue or N to terminate the procedure. 5. When calibration is complete, you are asked if you want to save the changes to the transmitter. To do so, press Y. The system then saves the new value to the transmitter and returns you to the main Calibrate menu. Startup Zero This function is used to set the zero only on initial installation of the transmitter. After the initial installation is complete, use the Re-Zero Transmitter function to reset the zero. To perform this operation, execute the following procedure: 1. From the Calibrate menu, select Startup Zero and press ENTER. 2. The system will display a warning about placing the loop in manual to avoid a process upset. Press Y to continue (or N to abort). 3. The system will then display a warning to set the flow to zero. Press any key to acknowledge the message and continue. 4. The screen shown in Figure 70 will then appear. When the reading stabilizes, press ENTER to accept it. 103

116 MI April 1997 Appendix B. Calibration Data Figure 70. CFT10 Startup Zero (1) 5. The screen shown in Figure 71 then appears, notifying you that the procedure is in progress and asking if you want to continue. Press Y to continue the calibration and the flow zero will be repeated two more times. Figure 71. CFT10 Startup Zero (2) 6. The new flow offset will then be displayed (same screen as Figure 68) asking if you want to save the new zero flow offset. If you do, press Y. The data is loaded into the transmitter and you are automatically returned to the main Calibrate menu. 104

117 Appendix B. Calibration Data MI April 1997 Restore Factory ma This function restores the factory ma calibration to the transmitter. To perform this function, execute the following: 1. From the Calibrate menu, select Restore Factory ma and press ENTER. You will then be asked if you want to save changes to transmitter. To save the changes, press Y. (The transmitter must be in Analog mode to perform this operation.) 2. If you press Y to save the changes, you are asked if the loop is in manual. (The loop must be in manual mode to perform this operation.) 3. If the loop is in manual mode, press Y. The custom curve is then loaded into the transmitter, the transmitter is placed On-line, and you are returned to the main Calibrate menu. Zero Total This section will set the transmitter total measurement to zero. Select Zero to reset or Quit to abort. CFT15 Mass Flow Transmitters This section describes the calibration functions and procedures applicable to the CFT15 mass flow transmitters. The calibration functions you can perform on CFT15 transmitters are: Re-Zero Transmitter Startup Zero Zero Total Each of the functions is described in this section. Re-Zero Transmitter See previous section on Rezero Transmitter for the CFT10 Transmitters. Startup Zero See previous section on Startup Zero for the CFT10 Transmitters. Zero Total This section will set the transmitter total measurement to zero. Select Zero to reset or Quit to abort. 105

118 MI April 1997 Vortex Flow Meters Appendix B. Calibration Data This section describes the calibration functions and procedures applicable to vortex flow meters. Functions The calibration functions you can perform on vortex flow meters are: ReRange ma Calibration Zero Total Set Low Flow Cut-In Each of the functions is described in this section. ma Calibration As the transmitter was accurately calibrated at the factory, this function is not normally required. To determine whether or not you need to perform this function, insert an accurate ma meter in the loop wiring. If the meter reading does not agree with the ma value shown by the transmitter, you should perform an ma calibration. Make adjustments as required to make the meter readings agree with the ma values reported on the PC10 from the transmitter. To perform an ma calibration, execute the following procedure: 1. From the main Calibrate menu, select ma Calibrate and press ENTER. 2. A screen appears that asks you to select an adjustment option that will change the transmitter 4 ma output (small or large increase or decrease). Select the type of change you want to make and press ENTER. Figure 72. ma Calibrate Screen 106

119 Appendix B. Calibration Data MI April Observe the modified output at the upper right of the screen. If further changes are needed, select the desired change and press ENTER. If acceptable, select Quit and press ENTER. 4. You are then asked to repeat the steps for the 20 ma point. Press Y to continue or N to terminate the procedure. 5. When calibration is complete, you are asked if you want to save the changes to the transmitter. To do so, press Y. The system then saves the new value to the transmitter and returns you to the main Calibrate menu. ReRange This function permits you to change the Flow Upper Range Value (URV). The procedure for performing a ReRange operation is as follows: 1. From the Calibrate menu, select ReRange and press ENTER. This will bring up the screen shown in Figure Move to the Upper Range Value (URV) field and enter the desired new value. Note that the new value cannot exceed the value shown in the bottom right corner of the window nor can it be a value that would yield a span less than the minimum span shown in the bottom left corner of the window. 3. When the values are acceptable, press F4 to save and exit from the screen. The system will then download the new values to the transmitter and return you to the Calibrate menu. Zero Total Figure 73. ReRange Screen (Vortex) This function permits you to reset the flow total for the transmitter to zero. To execute the operation, use the following procedure: 107

120 MI April 1997 Appendix B. Calibration Data 1. From the Calibrate menu, select Zero Total and press ENTER. 2. The screen shown in Figure 74 appears. You must select either Zero to reset the flow total or Quit to leave the menu without changing the flow total. Select the type of change you want to make and press ENTER. Figure 74. Zero Total Screen (Vortex) 3. If you have chosen to zero the total flow, the total flow measurement is reset to zero. The system then returns you to the Calibrate menu. Set Low Flow Cut-In This function permits you to set the low flow cut-in level for the transmitter. You can also set a manual low flow cut-in level. To execute the operation, use the following procedure: 1. From the Calibrate menu, select Set Low Flow Cut-In and press ENTER. 2. The screen shown in Figure 75 will then appear. The current low flow cut-in level is displayed. 108

121 Appendix B. Calibration Data MI April 1997 Figure 75. Set Low Flow Cut-In Display Current Setting 3. To continue on and set a new low flow cut-in level, select Set and press ENTER. The screen shown in Figure 76 then appears. Figure 76. Set Low Flow Cut-In Choose New Setting 4. Use the arrow keys to choose the appropriate flow setting, then press ENTER. If you choose Automatic Selection, a screen will appear asking you to confirm that the flow is off. After you confirm that the flow is off, the system displays a screen like that shown in Figure

122 MI April 1997 Appendix B. Calibration Data If you choose to select one of the preset low flow cut-in settings, the system displays the screen shown in Figure 77. Figure 77. Set Low Flow Cut-In Automatic Selection in Progress 5. It takes the system between 30 and 60 seconds to complete the automatic selection process. When it has finished, it displays the screen shown in Figure 78. Figure 78. Set Low Flow Cut-In Calibration Complete 6. Press any key to save the data to the transmitter and return to the main Calibrate menu. 110

123 Appendix B. Calibration Data MI April ITEC Electrodeless Conductivity Transmitters This section describes the calibration functions and procedures applicable to 870ITEC Electrodeless Conductivity Transmitters. Top Level Menu Picks Bench Calibration Solution Pt Span Solution 1 Pt Offset Solution 2 Pt Calib Temp Sensor Calib ma Calibration Default Calibration Use Arrow Keys to select Calibration Option and then Press Enter The calibration options are: Bench Calibration Solution 1 Pt Span Solution 1 Pt Offset Solution 2 Pt Calib Temp Sensor Calib ma Calibration Default Calibration Figure 79. Top Level Menu Picks This permits you to perform off-line calibration (2-point span and offset for up to 3 applications) of an 870ITEC transmitter. The zero point is set with the sensor suspended in air. The second point is set by using a loop of wire through the sensor and a decade resistance box. This option is a 1-point span calibration for up to 3 applications, using known reference solutions. A 1-point calibration is valid only if a 2- point calibration was previously performed. This enables you to set the offset (bias) for up to 3 applications, using known reference solutions. This is used to correct for a zero shift. This option is a 2-point span calibration for up to 3 applications, using known reference solutions. This option is a calibration of the temperature sensor, using a known temperature solution reference. This enables you to set the 4 ma and 20 ma points for the transmitter output signal. This option permits you to restore calibration automatically to the default values. Use the arrow keys to select the desired option and then press ENTER. 111

124 MI April 1997 Restore Factory Calibration Screen Appendix B. Calibration Data This screen, which appears after occurrence of any error, permits you to restore the factory calibration automatically. To restore the original calibration, select Restore and press Enter. To leave the screen, select Quit and press Enter. Figure 80. Restore Factory Calibration Screen Bench Calibration Screen 1 This screen appears when you select Bench Calibration from the pick list. You are permitted to set a low and a high calibration point for each of three applications. To proceed, select the desired application and press ENTER. The highlight then moves to the first item. You can then enter a new value if you wish. Press Enter to accept the entry and move to the next field. (The date is entered automatically by the system.) When done, press F4 to save the entries and exit. To Quit at any time, press ESC. Figure 81. Bench Calibration Screen 1 112

125 Appendix B. Calibration Data MI April 1997 Bench Calibration Screen 2 (Low Calibration Point) This screen permits you to save the Low Calibration Point for the selected application. To proceed, place the clean, dry sensor in air, select Calib and then press ENTER to execute the calibration. To stop, select Quit and press ENTER. Figure 82. Bench Calibration Screen 2 (Low Calibration Point) Bench Calibration Screen 3 (High Calibration Point) This screen permits you to save the High Calibration Point for the selected application. To proceed, run a wire through the sensor bore and connect to a decade resistance box. Set the decade box to the desired value, select Calib, and then press ENTER to execute the calibration. To stop, select Quit and press ENTER. Figure 83. Bench Calibration Screen 3 (High Calibration Point) 113

126 MI April 1997 Solution 1 Pt Span Screen 1(Application 1) Appendix B. Calibration Data This option permits you to set a calibration point (1-point span) for up to three applications. This should be used only if you have previously performed a 2-point calibration. Using the arrow keys, select the application and then press Enter. The highlight then moves the Solution 1 value. Enter a new value and then press Enter. This moves the highlight to the next item, Calibrator s Initials. Enter a new value and press Enter. When done, press F4 to save and exit. To quit at any time, press ESC. Figure 84. Solution 1 Pt Span (Screen 1) Solution 1 Pt Span Screen 2 This screen appears after you have saved the previous screen entries. To proceed, immerse the sensor in Solution 1, select Calib, and then press Enter. This calibrates the transmitter to read the measured value of Solution 1as the value entered in the previous screen. To Quit at any time, select Quit and then press ENTER. Figure 85. Solution 1 Pt Span (Screen 2) 114

127 Appendix B. Calibration Data MI April 1997 Solution 1-Point Offset (Screen 1) This option permits you to set a 1-point offset for up to three applications and is normally used to correct for zero shift. Using the arrow keys, select the application and then press Enter. The highlight then moves to the Solution 1 value. Enter a new value and then press Enter. This moves the highlight to the next item, Calibrator s Initials. Enter a new value and press Enter. When done, press F4 to save and exit. To quit at any time, press ESC. Figure 86. Solution 1-Point Offset (Screen 1) Solution 1-Point Offset (Screen 2) This screen appears after you have saved the previous screen entries. To proceed, immerse the sensor in Solution 1, select Calib, and then press Enter. This calibrates the transmitter to read the offset of Solution 1as the value entered in the previous screen. To Quit at any time, select Quit and then press ENTER. Figure 87. Solution 1-Point Offset (Screen 2) 115

128 MI April 1997 Solution 2 Point Calibration (Screen 1) Appendix B. Calibration Data This option permits you to perform a 2-point calibration for up to three applications. Using the arrow keys, select the application and then press Enter. The highlight then moves the Solution 1 value. Enter a new value and then press Enter. Repeat for Solution 2. Repeat for the next item, Calibrator s Initials. Enter a new value and press Enter. When done, press F4 to save and exit. To quit at any time, press ESC. Figure 88. Solution 2 Point Calibration (Screen 1) Solution 2 Point Calibration (Screen 2) This screen appears after you have saved the previous screen entries. To proceed, immerse the sensor in Solution 1, select Calib, and then press Enter. This calibrates the transmitter to read the measured value of Solution 1 as the value entered in the previous screen. To Quit at any time, select Quit and then press ENTER. Figure 89. Solution 2 Point Calibration (Screen 2) 116

129 Appendix B. Calibration Data MI April 1997 Solution 2 Point Calibration (Screen 3) This screen appears after you have saved the previous screen entries. To proceed, immerse the sensor in Solution 2, select Calib, and then press Enter. This calibrates the transmitter to read the measured value of Solution 2 as the value entered in the previous screen. To Quit at any time, select Quit and then press ENTER. Figure 90. Solution 2 Point Calibration (Screen 3) Temperature Sensor Calibration (Screen 1) This option permits you to calibrate the temperature sensor to the known temperature of a reference solution. When the screen first appears, the Enter Solution Temperature field is highlighted. Enter the correct temperature value and press Enter. The highlight moves to the next field. Enter a new value and press Enter. When done, press F4 to save and exit. To Quit, press ESC. Figure 91. Temperature Sensor Calibration (Screen 1) 117

130 MI April 1997 Temperature Sensor Calibration (Screen 2) Appendix B. Calibration Data This screen appears after you have saved the previous screen entries. To proceed, immerse the sensor in the solution, select Calib, and then press Enter. This calibrates the transmitter to read the temperature of the solution as the value entered in the previous screen. To Quit at any time, select Quit and then press ENTER. Figure 92. Temperature Sensor Calibration (Screen 2) ma Calibration (Screen 1) As the transmitter was accurately calibrated at the factory, this function is not normally required. To determine whether or not you need to perform this function, insert an accurate ma meter in the loop wiring. If the meter reading does not agree with the ma value shown by the transmitter, you should perform an ma calibration. Make adjustments as required to make the meter readings agree with the ma values reported on the PC10 from the transmitter. To perform an ma calibration, execute the following procedure: 1. From the main Calibrate menu, select ma Calibrate and press ENTER. 118

131 Appendix B. Calibration Data MI April A screen appears that asks you to select an adjustment option that will change the transmitter 4 ma output (small or large increase or decrease). Select the type of change you want to make and press ENTER. Figure 93. ma Calibrate Screen 3. Observe the modified output at the upper right of the screen. If further changes are needed, select the desired change and press ENTER. If acceptable, select Quit and press ENTER. 4. You are then asked to repeat the steps for the 20 ma point. Press Y to continue or N to terminate the procedure. 5. When calibration is complete, you are asked if you want to save the changes to the transmitter. To do so, press Y. The system then saves the new value to the transmitter and returns you to the main Calibrate menu. Default Calibration A default calibration restores the transmitter database to stored default values. WARNING: This operation should be performed only if the transmitter does not operate correctly. After downloading, the transmitter must be RE-CALIBRATED and RE-CONFIGURED. To perform this operation, execute the following procedure: 119

132 MI April 1997 Appendix B. Calibration Data 1. From the main Calibrate menu, select Default Calibration and press ENTER. This will display the screen shown in Figure 94. Figure 94. Default Calibration Screen 2. Press W to write the default calibration to the transmitter (or Q to quit). 870ITPH ph/orp/ise Transmitters Top Level Menu Picks 1 Point Manual Calib 1 Point Absolute Cal 2 Point Manual Cal Automatic Calib Temp Sensor Calib ma Calibration Default Calibration Good TAG# Figure 95. Top Level Menu Picks 120

133 Appendix B. Calibration Data MI April 1997 The calibration options are: 1Point Manual Calib 1Point Absolute Calib 2Point Manual Calib Automatic Calib Temp Sensor Calib ma Calibration Default Calibration This permits you to perform a manual calibration (1-point offset) of an 870ITPH transmitter. A manual calibration permits you to enter or edit solution values. A single point calibration may only be used if you have previously performed a 2-point calibration. This option applies only to ORP applications and is used instead of a manual calibration. It is a 1-point offset calibration, using known reference solutions. This enables you to set the span and offset, using known reference solutions. It is not applicable to ORP measurements. This option provides a buffer-recognition mechanism that locks in the buffer value representing the millivolt and temperature values measured by the sensor, using known reference solutions (buffers). This option is a calibration of the temperature sensor, using a known reference temperature solution. This enables you to set the 4 ma and 20 ma points for the transmitter output signal. This option permits you to restore calibration automatically to the default values. Use the arrow keys to select the desired option and then press ENTER. 1 Point Manual Calibration (Screen 1) This option permits you to set a calibration point (1-point offset) for up to three applications. Using the arrow keys, select the application and then press Enter. The highlight then moves the Solution 1 value. Enter a new value and then press Enter. This moves the highlight to the next item, Calibrator s Initials. Enter a new value and press Enter. When done, press F4 to save and exit. To quit at any time, press ESC. Good TAG# Figure Point Manual Calibration (Screen 1) 121

134 MI April Point Manual Calibration (Screen 2) Appendix B. Calibration Data This screen appears after you have saved the previous screen entries. To proceed, immerse the sensor in Solution 1, select Calib, and then press Enter. This calibrates the transmitter to read the measured value of Solution 1 as the value entered in the previous screen. To Quit at any time, select Quit and then press ENTER. Good TAG# Figure Point Manual Calibration (Screen 2) 1 Point Absolute Calibration (Screen 1) This option is used for ORP applications instead of a 1-point manual calibration. To proceed, enter the calibrator s initials and then press Enter. Press F4 to Save and Exit. To Quit, press ESC. Good TAG# Figure Point Absolute Calibration (Screen 1) 122

135 Appendix B. Calibration Data MI April Point Absolute Calibration (Screen 2) When this screen appears, immerse the sensor in the solution, select Calib, and then press Enter. When the system stabilizes, the calibration is complete. Good TAG# Figure Point Absolute Calibration (Screen 2) 2 Point Manual Calibration (Screen 1) This option permits you to set span and offset, using two known reference solutions (buffers). To proceed, use the arrow keys to highlight the first field. Enter the desired value for Solution 1 and press Enter. Repeat for Solution 2. Then, enter the calibrator s initials and press Enter again. Press F4 to save and exit from the screen or press ESC to quit. Good TAG# Figure Point Manual Cal (Screen 1) 123

136 MI April Point Manual Calibration (Screen 2) Appendix B. Calibration Data When this screen appears, immerse the sensor in Solution 1, select Calib, and then press Enter. This will calibrate one point. Good TAG# Figure Point Manual Cal (Screen 2) 2 Point Manual Calibration (Screen 3) When this screen appears, immerse the sensor in Solution 2, select Calib, and then press Enter. This will calibrate the second point, completing the procedure. Good TAG# Figure Point Manual Cal (Screen 3) 124

137 Appendix B. Calibration Data MI April 1997 Automatic Calibration (Screen 1) This option provides a buffer-recognition mechanism that locks in the buffer value representing millivolts and temperature being reported from the sensor, using known reference solutions. The algorithm checks each buffer starting with Buffer 1 and selects the first one for which this ph is within 0.5 ph of the average ph for the buffer. If not within 0.5 ph of any buffer table, no buffer is selected. When this initial screen appears, enter the Calibrator s initials and then press Enter to accept. Next, press F4 to save and exit from the screen. To Quit, press ESC. Good TAG# Figure 103. Automatic Calibration (Screen 1) Automatic Calibration (Screen 2) When this screen appears, place the sensor in Solution 1. Then select Calib and press Enter. When stability is achieved, the Screen 3 will appear. Good TAG# Figure 104. Automatic Calibration (Screen 2) 125

138 MI April 1997 Automatic Calibration (Screen 3) Appendix B. Calibration Data When this screen appears, place the sensor in Solution 2. Then select Calib and press Enter. Wait for the system to stabilize. The calibration is then complete. Good TAG# Figure 105. Automatic Calibration (Screen 3) Temperature Sensor Calibration (Screen 1) This option permits you to calibrate the temperature sensor to the known temperature of a solution. When the screen first appears, the Enter Solution Temperature field is highlighted. Enter the correct temperature value and press Enter. The highlight moves to the next field. Enter a new value and press Enter. When done, press F4 to save and exit. To Quit, press ESC. Good TAG# Figure 106. Temperature Sensor Calibration (Screen 1) 126

139 Appendix B. Calibration Data MI April 1997 Temperature Sensor Calibration (Screen 2) This screen appears after you have saved the previous screen entries. To proceed, immerse the sensor in the solution, select Calib, and then press Enter. This calibrates the transmitter to read the temperature of the solution as the value entered in the previous screen. To Quit at any time, select Quit and then press ENTER. Good ma Calibration Figure 107. Temperature Sensor Calibration (Screen 2) As the transmitter was accurately calibrated at the factory, this function is not normally required. To determine whether or not you need to perform this function, insert an accurate ma meter in the loop wiring. If the meter reading does not agree with the ma value shown by the transmitter, you should perform an ma calibration. Make adjustments as required to make the meter readings agree with the ma values reported on the PC10 from the transmitter. To perform an ma calibration, execute the following procedure: 1. From the main Calibrate menu, select ma Calibrate and press ENTER. 2. A screen appears that asks you to select an adjustment option that will change the transmitter 4 ma output (small or large increase or decrease). Select the type of change you want to make and press ENTER. 127

140 MI April 1997 Appendix B. Calibration Data Good TAG# Figure 108. ma Calibrate Screen 3. Observe the modified output at the upper right of the screen. If further changes are needed, select the desired change and press ENTER. If acceptable, select Quit and press ENTER. 4. You are then asked to repeat the steps for the 20 ma point. Press Y to continue or N to terminate the procedure. 5. When calibration is complete, you are asked if you want to save the changes to the transmitter. To do so, press Y. The system then saves the new value to the transmitter and returns you to the main Calibrate menu. Default Calibration A default calibration restores the transmitter database to stored default values. WARNING: This operation should be performed only if the transmitter does not operate correctly. After downloading, the transmitter must be RE-CALIBRATED and RE-CONFIGURED. To perform this operation, execute the following procedure: 128

141 Appendix B. Calibration Data MI April From the main Calibrate menu, select Default Calibration and press ENTER. This will display the screen shown in Figure 109. Figure 109. Default Calibration Screen 2. Press W to write the default calibration to the transmitter (or Q to quit). 129

142 MI April 1997 Appendix B. Calibration Data 130

143 Appendix C. Configuration Data General Characteristics (All Transmitters) When Configure is selected, all configuration parameters are uploaded from the transmitter. When you execute Configure, the configuration screen for the connected transmitter is displayed. Use this screen to specify the desired configuration, using menu picks and data entry fields. If a data entry field is invalid, a message is displayed. You must enter an acceptable value before proceeding. If any fields are invalid, you must enter acceptable selections before the screen will be accepted and downloaded. Data is accepted by pressing F4. Configuration is aborted by pressing ESC. Pressing F1 displays a help screen for the selected field. 820, 860, I/A Series Pressure Transmitter Configuration Configuration screens for the 820, the 860 and I/A Series pressure transmitters are shown in Figure 110 and Figure , 860 Configuration Screen Figure , 860 Configuration Screen 131

144 MI April 1997 Appendix C. Configuration Data I/A Series Configuration Screen Figure 111. I/A Series Configuration Screen 820, 860, I/A Series Configuration Fields Table , 860, I/A Series Configuration Fields Field Tag Number Tag Name Device Name Location Output Type Sqroot/Linear Sqroot/Linear User Entry Any identification (up to 12 characters). Any service description (up to 14 characters). Any 6-character I/A Series Letterbug. NOTE: To disable enhanced protocol name checking with I/A Series Versions 3.0 or later, set name to DevNam. Any location (up to 14 characters). Menu selection (digital or 4-20 ma). If digital, the 4-20 ma output is disabled. Menu selection (square root for flow measurement, linear for pressure or differential pressure measurement). If in square root mode, lower and upper range values are not selectable because the transmitter is ranged in pressure units only. Changing output (sqroot/linear) automatically updates affected fields (Measurement Units, Upper/Lower Range Values). 820 Rev N or later 860 Rev 2 or later I/A Series Pressure #2 Measurement output can be set independently of #1 Measurement. 132

145 Appendix C. Configuration Data MI April 1997 Table , 860, I/A Series Configuration Fields (Continued) Field Measurement #1 Units Measurement #1 Lower Range Value Measurement #1 Upper Range Value Measurement #1 Upper Range Limit Measurement #2 Units Measurement #2 Lower Range Value Measurement #2 Upper Range Value Measurement #2 Upper Range Limit Damping ma Output Fail Safe Temp Fail Mode Sqroot Cutoff User Entry Changing engineering units automatically updates affected fields (Upper/Lower Range Values, Upper Range Limit). Pressure Units: Select from menu of common pressure units or select Custom to enter user-configured units. Custom Application: 0-100%, 100-0%, or custom application units. Flow Units: Custom flow units for transmitter in square root mode only. Swap: Exchange Measurement #1 and #2 Units. Value at which transmitter will output 4 ma. Value and span checking are done when the screen is accepted by pressing F4. Value at which transmitter will output 20 ma. Value and span checking are done when the screen is accepted by pressing F4. Value of upper range limit, in measurement units (display only). Same options as Measurement #1. Also may select to turn Measurement #2 off. Measurement #2 units are valid for 820 Rev J or later and all 860 versions. Value at which transmitter will output 4 ma. Value and span checking are done when the screen is accepted by pressing F4 (display only). Value at which transmitter will output 20 ma. Value and span checking are done when the screen is accepted by pressing F4 (display only). Value of upper range limit, in measurement units (display only). Menu selection (0, 0.25, 0.5, 1, 2, 4, 8, 16, 32 seconds). Configure ma output to go upscale or downscale when a transmitter failure occurs. Configure transmitter to fail or continue to operate if the temperature sensor fails. Menu selection (Active or Cutoff). For 820 Rev N or later 860 Rev 2 or later I/A Series Pressure: Configure cutoff when transmitter is in sqroot mode to be either active (linear w/ pressure) or cutoff at 10% of flow. 133

146 MI April 1997 Appendix C. Configuration Data RTT10 Temperature Transmitter Configuration RTT10 Configuration Screen RTT10 Configuration Fields Figure 112. RTT10 Configuration Screen The following table defines acceptable entries for RTT10 configuration fields. Table 10. RTT10 Configuration Fields Field Tag Number Tag Name Device Name Location Output Mode Input Type Measurement Type Measurement Units Lower Range Limit User Entry Any identification (up to 12 characters). Any service description (up to 14 characters). Any 6-character I/A Series Letterbug. NOTE: To disable enhanced protocol name checking with I/A Series Versions prior to 4.0, set name to DevNam. Any location (up to 14 characters). Menu selection (digital or 4-20 ma). If digital, the 4-20 ma output is disabled. Menu Selection (TC, RTD, mv, or Special). The special option is valid only if transmitter was ordered with special input. Changing the input type automatically changes upper and lower limits. Display only: single input, dual average, dual difference, or dual redundant. For dual option to be valid, transmitter must be ordered from the factory with this option. Menu selection of common temperature units (if transmitter is in mv, units are not changeable). Value of lower range limit, in measurement units (display only). 134

147 Appendix C. Configuration Data MI April 1997 Table 10. RTT10 Configuration Fields (Continued) Field Lower Range Value Upper Range Value Upper Range Limit Damping ma Output Fail Safe Noise Rejection User Entry Value at which transmitter will output 4 ma. Value and span checking are done when screen is accepted by pressing F4. Value at which transmitter will output 20 ma. Value and span checking are done when screen is accepted by pressing F4. Value of upper range limit, in measurement units (display only). Menu selection (0, 0.25, 0.5, 1, 2, 4, 8, 16, 32 seconds) of damping factor. Menu selection of upscale or downscale. Configures output to go upscale or downscale when a transmitter failure occurs. A filter value, in seconds, of the time during which noise in the transmitter output signal is rejected. A low value decreases filtering action; a high value increases filtering action. Valid only for RTT10 Rev H or later. RTT20 Temperature Transmitter Configuration RTT20 Configuration Screens Figure 113. RTT20 Configuration Screen 1 135

148 MI April 1997 Appendix C. Configuration Data Figure 114. RTT20 Configuration Screen 2 136

149 Appendix C. Configuration Data MI April 1997 RTT20 Configuration Fields The following table defines acceptable entries for RTT20 configuration fields. Refer to MI for additional information. Table 11. RTT20 Configuration Fields Field Tag Number Tag Name Device Name Location Input Type Sensor Config Linearization Mode Measurement Units Lower Range Limit Lower Range Value Upper Range Value Upper Range Limit Calibrator s Initials Output Mode Fault Detection ma Output Failsafe ma Failsafe Direct User Entry Enter maximum of 12 characters. Enter maximum of 14 characters. Enter 6-character I/A Series Letterbug. NOTE: To disable enhanced protocol name checking with I/A Series Versions prior to 4.0, set name to DevNam. Enter maximum of 14 characters. Select type of thermocouple, RTD, or mv or ohm source. If ohms, select 2-, 3-, or 4- wire. If RTD, select 2-, 3-, or 4-wire or Dual 2-wire redundant, average, or difference. Select EGU or Dewpoint. Set to EGU to make the output linear with temperature. Set to Dewpoint only when the output is to be linear with dewpoint. Select C, F, K, R, mv, or ohms. If the input is configured for mv or ohms, the engineering units should be mv or ohms respectively. Read only parameter. Displays LRV of transmitter. Specify output lower range value limit (In 4-20 ma output transmitter, the value at which transmitter will output 4 ma). Specify output upper range value limit (In 4-20 ma output transmitter, the value at which transmitter will output 20 ma). Read only parameter. Displays URL of transmitter. Enter up to six characters. Select Digital or 4-20 ma. Select On or Off. Select On or Off. Select Upscale or Downscale. ma Failsafe Value Specify between 3.6 and 3.8 ma for downscale failsafe; between and 23.0 ma for upscale failsafe. Damping Select 0, 0.25, 0.5, 1, 2, 4, 8, 16, 32 seconds. Sensor Validation Specify between 0.0 and 10.0 seconds. Intelligent Smooth Specify between 0 and 30 seconds. Power Supply Freq Select 50 or 60 Hz. Power Supply Filter Select High or Std. Integral Indicator Type Installed Read only parameter; Displays one line, three line, or none. Push Buttons Select Enabled or Disabled. 137

150 MI April 1997 Appendix C. Configuration Data Table 11. RTT20 Configuration Fields (Continued) Field Language Top Line Display Bottom Line Label Cold Junction Secondary Meas. Units User Entry Select English, French, German, or Spanish. Select one of five choices. Enter maximum of seven characters. Select C or F. IMT10/IMT20 Magnetic Flow Transmitter Configuration IMT10/IMT20 Configuration Screen Figure 115. IMT20 Configuration Screen 138

151 Appendix C. Configuration Data MI April 1997 IMT10/IMT20 Configuration Fields The following table defines acceptable values for IMT20 (or IMT10) configuration fields. Refer to MI for additional information. Table 12. IMT20 (IMT10) Configuration Fields Field Entry Tag Number Any identification up to 12 characters. The first 8 characters will become the transmitter file name. Tag Name Any service description up to 14 characters. Optional, used for reference only. Device Name Any 6-character I/A Series Letterbug. NOTE: To disable enhanced protocol name checking with I/A Series Versions prior to 4.0, set name to DevNam. Location Any location up to 14 characters. Optional, used for reference only. Line Size Nominal diameter of the flow tube (select from menu). Lining Material Material from which the flow tube lining is fabricated (menu selection of available materials). Meter Factor Flowtube Cal Factor, a unique number for each tube found on the tub data plate. Pulse Output If used, select: Low - Variable (see Pulse Scale Value ) High - Fixed (0 to 2000 Hz) Pulse Scale Value If Low - variable was selected, enter a value between.1 and Hz. (This will be to output in pps when the flow rate through the tube is equal to the Flow Upper Range value.) Measurement Menu selection affecting display and the digital output (Engineering Configuration Units or %). Engineering Units Menu selection of common flow units or enter custom units. Changing measurement units automatically updates affected fields (Upper Range Value). Display Upper Range If Engineering Units was selected, enter a value between 10 and 999. Flow Upper Range Value of upper range calibration for the flowtube. Limit of values depends on flowtube size and engineering units. Upper Range Limit No entry needed, reference from internal lookup table. Damping Menu selection (Auto, 0.25, 0.5, 1, 2, 4, 8, 16, 32 seconds). Damp on Power Menu selection (Yes/No) to damp measurements on power-up. Comm. Baud Rate Menu selection (600/4800 Baud). Used to select output if connected to an I/A Series system. 139

152 MI April 1997 Appendix C. Configuration Data IMT25 Magnetic Flow Transmitter Configuration IMT25 Configuration Screens Figure 116. IMT25 Configuration Screen 1 Figure 117. IMT25 Configuration Screen 2 140

153 Appendix C. Configuration Data MI April 1997 IMT25 Configuration Fields Figure 118. IMT25 Configuration Screen 3 The following table defines acceptable values for IMT25 configuration fields. Refer to MI for additional information. Table 13. IMT25 Configuration Fields Field Entry Tube Model Code Enter maximum of 32 characters (found on tube data plate). Tube Serial Number Enter maximum of 16 characters (found on tube data plate). Meter Factor Flowtube Cal Factor, a unique number for each tube found on the tube data plate. Tag Number Enter maximum of 12 characters. The first 8 characters will become the transmitter file name. This field applies only if Output Mode is specified as Digital. Tag Name Enter maximum of 14 characters. Optional, used for reference only. Device Name Enter the 6-character I/A Series Letterbug. Applies only if Output Mode is specified as Digital. NOTE: To disable enhanced protocol name checking with I/A Series Versions prior to 4.0, set name to DevNam. Location Enter maximum of 14 characters. Optional, used for reference only. Line Frequency Select 50 or 60 Hz. If using a dc powered transmitter, select the local ac powered frequency to ensure optimal performance. Measurement Configuration Flow Rate Units Specify units as GPM, GPH, GPD, LPM, LPH, LPD, or Custom. Flow Rate Slope If custom slope, specify slope in form +#.####e+##. Flow Rate Format Select one of eight choices. Output Mode Select Digital or Analog. 141

154 MI April 1997 Appendix C. Configuration Data Field Digital Mode Analog Mode Flow Direction Flow Rate Damping Noise Reduction Upper Range Value 1, 2, and 3 Pulse Output Mode Pulse Output URV Rate Max Frequency Total Max Freq. Empty Pipe Detect Table 13. IMT25 Configuration Fields (Continued) Entry Select Unidirectional or Bidirectional flow. Select Unidirectional, Unidirectional Multi-Range, Bidirectional Dual Range, or Bidirectional Split Range. Select Positive, Reverse, BiDir Positive, or BiDir Reverse. Specify the damping response time for the analog output and pulse rate output between 00.0 and 99.9 seconds. Select On or Off. Specify Upper Range Value (s) in units previously specified. Select Off, Pulse Rate, or Pulse Total. Specify value between minimum and maximum URV of the flowtube (not greater than ). Select 1000, 2000, 5000, or Hz. Select 10 or 100 Hz. Select On or Off. Local Display Configuration Default Screen Select one of seven choices. Dual Display Select On or Off. Display Line 1 Select one of six choices. Display Line 2 Select one of six choices. Flow Display Damping Specify the damping response time for the local display between 00.0 and 99.9 seconds. Local Totalizer Select On or Off. Totalizer Units Select Gal, Lit, or Custom. Totalizer Slope If custom slope, specify slope in form +#.####e+##. Fwd/Rev/Net Format Select one of eight choices. Grand Total Format Select one of eight choices. Diagnostics Rate Response Diagnostics Select Go Upscale or Go Downscale. Display Response Diagnostics Select Blink or Don t Blink. Passcodes Passcodes 1 and 2 Select On or Off. Passcodes 1 and 2 Protect Select Setup, Totals Reset, or Setup & Totals. Passcodes 1 and 2 (####) Specify four digit passcode between 0000 and Alarm Configuration Alarms On/Off Select On or Off. 142

155 Appendix C. Configuration Data MI April 1997 Table 13. IMT25 Configuration Fields (Continued) Field Alarm Clear Display Response Rate Output Response High Flow Rate Set Point Deadband Low Flow Rate High Fwd Total 1 Set Point High Fwd Total 2 Set Point Empty Pipe Contact Input/Output Contact 1 Function Contact 1 Operation Contact 2 Function Contact 2 Operation Relay 1 Function Relay 1 Alarm Relay 1 Operation Relay 1 Suppress Relay 2 Function Relay 2 Alarm Relay 2 Operation Relay 2 Suppress Entry Select Manual or Auto. Select Blink or Don t Blink. Select No Effect, Go Upscale, or Go Downscale. Select On or Off. Enter Set Point in flow rate units previously configured. Enter Deadband in flow rate units previously configured. Similar to High Flow Rate. Select On of Off. Enter Set Point in flow rate units previously configured. Select On of Off. Enter Set Point in flow rate units previously configured. Select On or Off. Select Off, Ack Alarm, Reset Net Total, Reset Gr Total, Reset All Total, Multi-range, or Signal Lock. Select Normally Closed or Normally Open. Similar to Contact 1 Function. Similar to Contact 1 Operation. Select Off, Alarm, Alarm & Diag, Diagnostics, or Flow Direction. If Function is Alarm or Alarm & Diag, select High Rate, Low Rate, High Fwd Tot 1, High Fwd Tot 2, Empty Pipe, or Any Alarm. Select Normally Closed or Normally Open. Select Yes or No. Similar to Relay 1 Function. Similar to Relay 1 Alarm. Similar to Relay 1 Operation. Similar to Relay 1 Suppress. 143

156 MI April 1997 Appendix C. Configuration Data CFT10 Mass Flowmeter Configuration CFT10 Configuration Screen Figure 119. CFT10 Configuration Screen (Screen 1) CFT10 Configuration Fields The following table defines acceptable entries for CFT10 configuration fields. More information is available in MI Table 14. CFT10 Configuration Fields Screen 1 of 2 Field Tag Number: Tag name: Location: Device Name: User Entry Any identification up to 12 characters long. The first 8 characters will become the transmitter filename. Any service description up to 14 characters long. Optional entry used for reference only. Any location up to 14 characters long. Optional entry used for reference only. Any 6-character I/A Series Letterbug. If connected to an I/A Series system, the device name must be the letterbug of the Coriolis Interface Block (CORINT). 144

157 Appendix C. Configuration Data MI April 1997 Table 14. CFT10 Configuration Fields Screen 1 of 2 (Continued) Measurement Units: Mass Flow: Density: Field Temperature: Volume Flow: Total Measurement Configuration: If measurement are changed, any related output values (ma, pulse, alarm 1, alarm 2) are automatically updated. (g/s, g/min, kg/s, kg/min, kg/h, t/min, t/h, t/d, oz/s, oz/min, lb/s, lb/min, lb/h, lb/d, ton/min, ton/h, ton/d) (g/cm 3, kg/m 3, oz/in 3, lb/ft 3, lb/yd 3, tn/yd 3, kg/l, lb/gal) ( K, C, F, R) User Entry (USgps, USgpm, USgph, IMPgps, IMPgpm, IMPgph, l/s, l/min, l/h) Total by: (Mass/Volume) Mass Flow Units: (kg, g, tonne, oz, lb, tons) Volume Flow Units: (Liters, USgal, IMPgal) Totalizer Increment: (0.0001, 0.001, 0.01, 0.1, 1.0, 10, 100, 1000, 10,000) User may select CUSTOM measurement units for any of above measurements. If CUSTOM is selected, user must enter measurement units label, slope conversion for the base units, and the units offset conversion (usually 0.0). Base units for custom measurement conversion are: Mass Flow = kg/s Density = kg/m 3 Temperature = K Totalized Mass Flow = kg Totalized Volumetric Flow = kl Volumetric Flow = kl/s 145

158 MI April 1997 Appendix C. Configuration Data Table 14. CFT10 Configuration Fields Screen 1 of 2 (Continued) Pulse Output Configuration ma Mode Field User Entry Minimum spans are checked when screen is accepted. Pulse Mode: (Mass Flow, Density, Temperature, Total, Vol. Flow, Solids, Off, Preset) Pulse Trip: Selects the pulse trip value (selectable only if pulse output is connected for Total) Lower Range Value: Pulse Low Range Value (10 Hz) (Selectable only if pulse is connected to measure Mass Flow, Density, Temperature, Volumetric Flow, % Solids) Upper Range Value: Pulse Upper Range Value (10000 Hz) (Selectable only if pulse is connected to measure Mass Flow, Density, Temperature, Volumetric Flow, % Solids) Damping: Pulse Damping (Selectable only if pulse is connected to measure Mass Flow, Density, Temperature, Volumetric Flow, % Solids.) Preset Value: Sets pulse to fixed preset value. (Selectable only if pulse is configured for Preset.) Totalize Option: Sets the totalizer frequency to one of four values: (Off, 5 Hz, 10 Hz, or 15 Hz). Minimum spans are checked when screen is accepted. Select ma Output Configuration: 4-20 ma: Mass Flow, Density, Temperature, Vol Flow % Solids, Off, Preset 0-20 ma: Density, Temperature, Vol Flow,% Solids Lower Range Value: (4 or 0 ma) (selectable only if ma is connected for Mass Flow, Density, Temperature, Vol. Flow, % Solids) Upper Range Value: (20 ma) (selectable only if ma is connected for Mass Flow, Density, Temperature, Vol. Flow, % Solids) Damping: ma Damping (selectable only if ma is connected for Mass Flow, Density, Vol. Flow, % Solids, or Temperature) Preset Value: Sets ma to fixed preset value (selectable only if ma is configured for Preset). 146

159 Appendix C. Configuration Data MI April 1997 Table 14. CFT10 Configuration Fields Screen 1 of 2 (Continued) Alarm 1 Alarm 2 Field User Entry Alarm 1 contact type: (Preset Off, Preset On, Mass Flow High, Mass Flow Low, Density High, Density Low, Temp High, Temp Low, Volume Flow High, Volume Flow Low, % Solids High, % Solids Low, Pulse Overrun, Fault Only) Alarm Level: Alarm Trip level (Selectable only if configured for a level alarm). Alarm Hysteresis: Alarm deadband (Selectable only if alarm is configured for a level alarm.) Alarm Power: Select to power alarm contact on alarm or when no alarm exists. Same as Alarm 1 above. CFT10 Configuration Screen (Screen 2) Figure 120. CFT10 Configuration Screen (Screen 2) 147

160 MI April 1997 Appendix C. Configuration Data CFT10 Configuration Fields (Screen 2) Table 15. CFT10 Configuration Fields Screen 2 of 2 Field User Entry Flow Direction Slug Time % Solids Configuration Select flow tube direction: (Forward, reverse, positive bi-directional, negative bi-directional) Set the allowable time (in multiples of 10 seconds) for flow slug to exist before alarm is triggered (10 to 2550 seconds) Component A Tag: Label of Component A Density: Density of Component A Thermal Expansion: Thermal Expansion of Component A Component B Tag: Label of Component B Density: Density of Component B Thermal Expansion: Thermal Expansion of Component B Reference Temperature Reference Temperature for Thermal Expansion % Solids Mode Select % Solids Measurement: (Comp A by Mass, Comp B by Mass, Comp A by Volume, Comp B by Volume) Mass Flow Mode Select mass flow configuration: (Component A and B, Component A, Component B) Total Mode Select mass flow configuration: (Component A and B, Component A, Component B) Volume Flow Mode Select volumetric flow configuration: (Component A and B, Component A, Component B) Flow Tube Parameters (stamped on flow tube data plate) Tube Serial No. Density Coef 1. Density Coef 2. Density Coef 3. Density Coef 4. Nominal Capacity Flow Coef 1 Flow Coef 2 Flow Coef 3 Flow Coef 4 148

161 Appendix C. Configuration Data MI April 1997 CFT15 Mass Flowmeter Configuration CFT15 Configuration Screen Figure 121. CFT15 Configuration Screen 1 Figure 122. CFT15 Configuration Screen 2 149

162 MI April 1997 Appendix C. Configuration Data CFT15 Configuration Fields Figure 123. CFT15 Configuration Screen 3 The following table defines acceptable values for CFT15 configuration fields. Refer to MI for additional information. Table 16. CFT15 Configuration Fields Field Tag Number Tag Name Device Name Location Mass Flow Units Density Units Temperature Units Volume Flow Units Total By Units Increment On Slug Outputs Pulse Mode Pulse Trip Lower Range Value Upper Range Value Damping Entry Enter maximum of 12 characters. The first 8 characters will become the transmitter file name. Enter maximum of 14 characters. Optional, used for reference only. Enter maximum of six characters. Enter maximum of 14 characters. Optional, used for reference only. Select one of nineteen choices. Select one of nine choices. Select R, F, C, K, or Custom. Select one of 10 choices. Select By Mass or By Volume. Select from list of choices. Select from list of choices. Select from list of choices. Select one of eight choices. Select from list of choices if Pulse Mode is Total. Enter Value (LRV URV). Enter Value (LRV URV). Select one of eight choices from No Damping to 16 seconds. 150

163 Appendix C. Configuration Data MI April 1997 Field Table 16. CFT15 Configuration Fields (Continued) Entry Preset Value Enter value if Pulse Mode is Preset Totalize Option Select 5 Hz, 10 Hz, 15 Hz or Off. Alarm 1 Select one of fourteen alarm types. Alarm Level Enter value if Alarm Type is a level type alarm. Alarm Hysteresis Enter value if Alarm Type is a level type alarm. Alarm Power Select While Alarm Off or While Alarm On. Alarm 2 Similar to Alarm mA Output #1 ma Mode Select one of seven choices. Lower Range Value Enter value if ma Mode is not Off or Preset. Upper Range Value Enter value if ma Mode is not Off or Preset. Damping Select one of eight choices from No Damping to 16 seconds. Preset Value Enter value. 4-20mA Output #2: Similar to 4-20mA Output # mA Output #3: Similar to 4-20mA Output #1. Modbus Address Enter address from 1 to 247. Baud Select 1200, 2400, 4800, 9600, or baud. Parity Select Odd, Even, or None Delay Select 0, 20, 50, 150, or 300. Transmitter Flow Direction Select Positive, BiDir Positive, BiDir Negative, or Negative. Slug Time Enter value from 10 to 2550 seconds. % Solids Configuration Component A Tag Enter maximum of six characters. Density Enter value. Thermal Expansion Enter value. Component B Tag, Density and Thermal Expansion: Similar to Component A above. % Solids Mode Select Comp A by Mass, Comp B by Mass, Comp A by Vol, or Comp B by Vol. Mass Flow Mode Select Comp A, Comp B, or Comp A + B. Total Mode Select Comp A, Comp B, or Comp A + B by Mass or by volume. Volume Flow Mode Select Comp A, Comp B, or Comp A + B. Reference Temp Enter value. Flow Tube Parameters (from Flowtube Data Plate) 151

164 MI April 1997 Appendix C. Configuration Data Table 16. CFT15 Configuration Fields (Continued) Field Tube Serial No. Density Coef 1 Density Coef 2 Density Coef 3 Density Coef 4 Nominal Capacity Flow Coef 1 Flow Coef 2 Flow Coef 3 Flow Coef 4 Entry Enter data from flowtube data plate. Vortex Flowmeter Configuration Vortex Configuration Screen Figure 124. Vortex Configuration Screen 152

165 Appendix C. Configuration Data MI April 1997 Vortex Configuration Fields The following table defines acceptable entries for Vortex configuration fields. More information is available in MI Table 17. Vortex Configuration Fields Field Transmitter Tags; Tag Number: Tag name: Device Name: Location: Fluid Type Measurement Units Noise Rejection Signal Condition Low Flow Correction Flowing Temperature Flowing Density Base Density Mating Pipe Piping Configuration Upstream Distance Added K-Factor Bias Low Flow Cut-In Upper Range Value Output Mode Damping User Entry Any identification up to 12 characters long. The first 8 characters will become the transmitter filename. Any service description up to 14 characters long. Optional entry used for reference only. Any 6-character I/A Series Letterbug. Any location up to 14 characters long. Optional entry used for reference only. Menu selection (Liquid, Gas, or Steam) Menu selection (standard units depending upon fluid type) Menu selection (On/Off) Menu selection (On/Off) Menu selection (On/Off; only available if Fluid Type = Liquid) Flow temperature used to set thermal expansion correction to K-factor Used to automatically compute flow limits; also used to compute mass flow (if selected) Flow defaults: Liquid lb/ft 3 (water at 0 psig and 70 F) Gas lb/ft 3 (air at 100 psig and 70 F) Steam lb/ft 3 (sat. steam at 125 psig) (Gas only) units are the same as Flowing Density and if selected, Standard Volume Units Menu selection (Schedule 10, Schedule 40, Schedule 80, PN16, PN40, PN64, PN100) Menu selection (Straight, 1 Elbow/Parallel, 1 Elbow/Perpendclr, 2 Elbow/Close/Para, 2 Elbow/Close/Perp, 2 Elbow/5 Dia/Para, 2 Elbow/5 Dia/Perp, Reducer) Upstream pipe length in pipe diameters User-defined bias in percent to correct reference K-factor Menu selection (Automatic selection or manually selected value) Upper range flow value; if transmitter is in 4-20mA mode, URV is the value corresponding to 20 ma Menu selection (Digital/4-20 ma) Menu selection (0,0.25,0.5,1,2,4,8,16,32 seconds) 153

166 MI April 1997 Appendix C. Configuration Data Table 17. Vortex Configuration Fields (Continued) Field User Entry Scaled Pulse Out Menu selection (Off, 10 Hz Max, 100 Hz Max) Pulse Resolution Menu selection (0.001, 0.01, 0.1, 1.0, 10.0, 100.0, ) ma Failsafe Menu selection of upscale or downscale. Configure ma and scaled pulse output to go upscale or downscale when a transmitter failure occurs. 870ITEC Transmitter Configuration 870ITEC Configuration Screen #1 Figure ITEC Configuration Screen (1 of 2) 870ITEC Configuration Fields (Screen #1) The following table defines acceptable entries for 870ITEC configuration fields. More information is available in MI Table ITEC Configuration Fields Screen 1 of 2 Field Transmitter Tags; Tag Number: Tag Name: Device Name: User Entry Any identification up to 12 characters long. The first 8 characters become the transmitter filename. Any service description up to 14 characters long. Optional entry used for reference only. Any 6-character I/A Series Letterbug. If connected to an I/A Series system, the device name must be the letterbug of the Coriolis Interface Block (CORINT). 154

167 Appendix C. Configuration Data MI April 1997 Table ITEC Configuration Fields Screen 1 of 2 (Continued) Field User Entry Location: Number of Applications Application Select Any location up to 14 characters long. Optional entry used for reference only. Select the number of applications (1, 2, or 3). Select the particular application from pick list (1, 2, 3, or Auto). (See Note 1 below about configuring and calibrating multiple applications.) Select sensor type from pick list. Select output mode (digital or 4-20 ma) Select damping time from pick list (1, 5, 10, 20, 40, 120 sec) Sensor Type Output Mode Damping Application #N (Repeat for each application selected) Primary Units For selected application, select primary units from pick list. Primary Full Scale Select full scale range from list. Full Scale Limit Display of value from range selected. Temp Compensation Select from list. If custom is selected, screens appear for you to enter values. (See Note 2 below about viewing previously stored values of temperature compensation.) ma Output Output Range Min Output Range Max Failsafe Mode Failsafe Value Calibration Date If 4-20 selected, select output assignment from list (primary meas/temp/absolute). If 4-20 selected, enter value. If 4-20 selected, enter value. If 4-20 selected, select On/Off/Pulse. If ON selected, enter value. Display only (not editable). NOTES: 1. When using multiple applications, each application requires separate configuration and calibration information. After you calibrate an application, the PC10 software may not restore the transmitter configuration information to the Number of Applications and Application Select choices to which it was set prior to the calibration. To circumvent this anomaly: (1) download the correct multiple application information to the transmitter, (2) perform the application calibration in the normal manner, and (3) verify the transmitter configuration and restore the multiple application information to the original, if necessary. 2. If you upload a previously stored configuration from the transmitter, the screen displays the maximum possible percentage range value rather than the currently stored value. Use the local display on the transmitter to verify that the stored value is correct. As an alternative, you can re-enter the desired value in the 870ITEC Configuration Screen and download to the transmitter. 155

168 MI April ITEC Configuration Screen #2 Appendix C. Configuration Data Figure ITEC Configuration Screen (2 of 2) 870ITEC Configuration Fields (Screen #2) The following table defines acceptable entries for 870ITEC configuration fields. More information is available in MI Table ITEC Configuration Fields Screen 2 of 2 Field User Entry Temperature Configuration Temperature Units Select C or F. Temperature Mode Select auto or manual. Failure Value Enter value. Manual Temp Enter value (if manual selected). Temp Sensor Type Select from list. Stability Indicators Measurement Select on or off. Stability Time Select from list (5 to 60 sec). Stability Var Enter value from 1 to 9. Temperature Select on or off. Stability Time Select from list. Stability Var Enter value from 1 to 9. Application Trigger Application 1 Hi: Enter value (conductivity units only). Application 2 Lo Enter value (conductivity units only). 156

169 Appendix C. Configuration Data MI April 1997 Table ITEC Configuration Fields Screen 2 of 2 (Continued) Field Application 2 Hi: Enter value (conductivity units only). Application 3 Lo: Enter value (conductivity units only). Local Display Configuration Display Timeout Enter value. Major Passcode Enter value (up to 4 digits). Minor Passcode Enter value (up to 4 digits). App 1 Second Meas Enter value. App 2 Second Meas Enter value. App 3 Second Meas Enter value. Diagnostics Leakage Select enable/disable. ATC Short Select enable/disable. Compens. Range Select enable/disable. ATC Open Select enable/disable. ma Range Select enable/disable. Measurement Range Select enable/disable. 870ITPH ph/orp/ise Transmitter Configuration 870ITPH Configuration Screen #1 User Entry Figure ITPH Configuration Screen (1 of 2) 157

170 MI April ITPH Configuration Fields (Screen #1) Appendix C. Configuration Data The following table defines acceptable entries for 870ITPH configuration fields. More information is available in MI Table ITPHConfiguration Fields Screen 1 of 2 Field Transmitter Tags; Tag Number: Tag name: Device Name: Location: Sensor Type Output Mode Electrode Temp. Range Chemical Composition Buffers Output Mode ma Output Output Range Min Output Range Max Failsafe Mode Failsafe Value User Entry Any identification up to 12 characters long. The first 8 characters will become the transmitter filename. Any service description up to 14 characters long. Optional entry used for reference only. Any 6-character I/A Series Letterbug. If connected to an I/A Series system, the device name must be the letterbug of the Coriolis Interface Block (CORINT). Any location up to 14 characters long. Optional entry used for reference only. Select from list (ph, ISE, ORP). Select 0.1 ph or 0.01 ph. Select Glass/Antimony/Other. Select Custom/Standard/Ammonia. Not Applicable. Select American/Nist/European/Special. Select digital or 4-20 ma. Select Primary Measurement (from pick list). Enter value for ph only (0.00 min). Enter value for ph only(14.00 max). Select on/off/pulse. If on or pulse is selected, enter value. Temp. Units Select C or F. Temp. Mode Select auto or manual. Failsafe Value If auto is selected, enter value. Temp. Sensor Type Select from list of RTD types. 158

171 Appendix C. Configuration Data MI April ITPH Configuration Screen #2 Figure ITPH Configuration Screen (2 of 2) 870ITPH Configuration Fields (Screen #2) The following table defines acceptable entries for 870ITPH configuration fields. More information is available in MI Press ENTER to move from one field to the next. Press F3 to <ESC> to Quit and F1 for on-line help. When done, press F4 to Save and Exit from the screen. Note that the sequence of fields highlighted varies with the options selected. A field is not highlighted unless it can be edited by the user. Table ITPH Configuration Fields Screen 2 of 2 Field User Entry Stability Indicators Measurement Select on/off. Stability Time Select from pick list (5 to 60 sec). Stability Var Enter value from 1 to 9. Temperature Select on/off. Stability Time Select from list (5 to 60 sec). Stability Var Enter value from 1 to 9 C. Local Display Configuration Display Timeout Enter value (3 digits). Major Passcode Enter value (4 digits). Minor Passcode Enter value (4 digits). Second Meas Select temp/absolute/ma. Damping Select from list (1 to 120 sec). 159

RTT20 I/A Series Temperature Transmitter

RTT20 I/A Series Temperature Transmitter Instruction MI 020-460 October 1996 RTT20 I/A Series Temperature Transmitter Operation, Configuration, and Calibration Using a HART Communicator MI 020-460 October 1996 Contents General Description...

More information

OVEN INDUSTRIES, INC. Model 5C7-362

OVEN INDUSTRIES, INC. Model 5C7-362 OVEN INDUSTRIES, INC. OPERATING MANUAL Model 5C7-362 THERMOELECTRIC MODULE TEMPERATURE CONTROLLER TABLE OF CONTENTS Features... 1 Description... 2 Block Diagram... 3 RS232 Communications Connections...

More information

Micro Motion Filling Mass Transmitters with Modbus

Micro Motion Filling Mass Transmitters with Modbus Configuration and Use Manual MMI-20018283, Rev AC April 2013 Micro Motion Filling Mass Transmitters with Modbus Configuration and Use Manual Micro Motion customer service Email Worldwide: flow.support@emerson.com

More information

PROCESS & TEMPERATURE CONTROLLERS

PROCESS & TEMPERATURE CONTROLLERS PROCESS & TEMPERATURE CONTROLLERS NOVA PD54 Series Thermocouple, RTD, & Process Inputs High Accuracy Auto-Tuning PID Heating & Cooling Models Universal Power Supply 1-24 VAC Up to 3 Relays & 2 Analog Outputs

More information

Calibration Instruction Manual Emerson 475 Field Communicator. Manual Revision FC.2

Calibration Instruction Manual Emerson 475 Field Communicator. Manual Revision FC.2 Calibration Instruction Manual Emerson 475 Field Communicator Manual Revision FC.2 ABM 2 Wire Radar with HART ABM Sensor Technologies Inc 2013, all rights reserved. Emerson is a registered trademark of

More information

8000 SERIES PRECISION MULTIMETER VERIFICATION AND ADJUSTMENT GUIDE

8000 SERIES PRECISION MULTIMETER VERIFICATION AND ADJUSTMENT GUIDE 8000 SERIES PRECISION MULTIMETER VERIFICATION AND ADJUSTMENT GUIDE TRANSMILLE LTD. Version 1.1 : Apr 2015 TABLE OF CONTENTS PREPARING FOR CALIBRATION... 4 INTRODUCTION... 4 CALIBRATION INTERVAL SELECTION...

More information

HART Mode. Users Guide. July Fluke Corporation. All rights reserved. All product names are trademarks of their respective companies.

HART Mode. Users Guide. July Fluke Corporation. All rights reserved. All product names are trademarks of their respective companies. 754 HART Mode Users Guide July 2011 2011 Fluke Corporation. All rights reserved. All product names are trademarks of their respective companies. LIMITED WARRANTY AND LIMITATION OF LIABILITY This Fluke

More information

Series F4P Communications Guide

Series F4P Communications Guide Series F4P Communications Guide 1/4 DIN Temperature/Process Controller with Guided Setup 98 Registered Company Winona, Minnesota USA Watlow Controls 1241 Bundy Blvd., P.O. Box 5580, Winona, Minnesota USA

More information

KENCO Loop Powered Magnetostrictive Transmitter. KMD SERIES Operation and Installation Manual. Table of Contents

KENCO Loop Powered Magnetostrictive Transmitter. KMD SERIES Operation and Installation Manual. Table of Contents KENCO ENGINEERING COMPANY P.O. BOX 470426, TULSA, OK 74147-0426 PHONE: (918) 663-4406 FAX: (918) 663-4480 http://www.kenco-eng.com e-mail: info@kenco-eng.com KENCO Loop Powered Magnetostrictive Transmitter

More information

Global Water Instrumentation, Inc.

Global Water Instrumentation, Inc. Global Water Instrumentation, Inc. 151 Graham Road P.O. Box 9010 College Station, TX 77842-9010 T: 800-876-1172 Int l: (979) 690-5560, Fax: (979) 690-0440 E-mail : globalw@globalw.com Radar Level Transmitters

More information

Intelligent Communicator DCR3000

Intelligent Communicator DCR3000 Intelligent Communicator DCR3000 The Model DCR3000 Intelligent Communicator is designed for data communication over a 4 to 20mA DC output transmission line connected with Hitachi Intelligent Sensor series

More information

CHAPTER 1 INTRODUCTION...

CHAPTER 1 INTRODUCTION... GSE 460 and 465 Technical Reference Manual Manual TABLE OF CONTENTS CHAPTER 1 INTRODUCTION...1-1 INTRODUCTION...1-2 About This Manual...1-2 Conventions...1-2 CHAPTER 2 INSTALLATION...2-1 INSTALLATION...2-1

More information

LBI Installation & Operation

LBI Installation & Operation Installation & Operation EDACS Power Monitor Unit ericssonz CONTENTS TABLE OF CONTENTS Page INTRODUCTION... 6 DESCRIPTION... 6 APPLICATION NOTES... 7 VAX SITE CONTROLLER COMPUTER... 7 APPLICATION SOFTWARE

More information

815LT Submersible Smart Level Transmitter

815LT Submersible Smart Level Transmitter These instructions provide information for installation, process connection, electrical connection, configuration, operation and maintenance of the 815LT Submersible Smart Level Transmitter. The 815LT

More information

Micro Motion Model 2700 Transmitters with Configurable Input/Outputs 2700***B 2700***C. Configuration and Use Manual Supplement

Micro Motion Model 2700 Transmitters with Configurable Input/Outputs 2700***B 2700***C. Configuration and Use Manual Supplement P/N MMI-20015781, Rev. AA September 2009 Micro Motion Model 2700 Transmitters with Configurable Input/Outputs Configuration and Use Manual Supplement 2700***B 2700***C Configuration Operation Maintenance

More information

USER MANUAL PN (old part number = 916-8A00-002) REV F RELEASED

USER MANUAL PN (old part number = 916-8A00-002) REV F RELEASED Gold Line VDT Issue 1, Rev. F: 09/03/96 Gold Line VDT USER MANUAL PN 9110.00164 (old part number = 916-8A00-002) REV F RELEASED Specifications subject to change without notice Copyright 1996 Glenayre All

More information

MI June Instruction. I/A Series Intelligent Pressure Transmitters. Operation, Configuration, and Calibration Using a HART Communicator

MI June Instruction. I/A Series Intelligent Pressure Transmitters. Operation, Configuration, and Calibration Using a HART Communicator Instruction MI 020-366 June 2008 I/A Series Intelligent Pressure Transmitters Operation, Configuration, and Calibration Using a HART Communicator MI 020-366 June 2008 Contents Introduction... 1 General

More information

815PT Smart Pressure Transmitter

815PT Smart Pressure Transmitter 815PT Smart Pressure Transmitter General Instructions These instructions provide information for installation, process connection, electrical connection, configuration, operation and maintenance of the

More information

HC-220 PID Controller

HC-220 PID Controller HC-220 PID Controller Operation and Maintenance Manual The information contained in this manual was current at the time of printing. The most current versions of all Hydro Instruments manuals can be found

More information

The LEBOW 7554 Operator's Manual 7.2

The LEBOW 7554 Operator's Manual 7.2 The LEBOW 7554 Operator's Manual 7.2 This manual covers operating version 7.2 of the LEBOW 7554. 11 February 1999 Lebow Products Inc Lebow Products Inc 1728 Maplelawn Rd Troy, MI 48084 1 (800) 803-1164

More information

USER MANUAL. EPP Intelligent Positioner Control Unit 1/22.

USER MANUAL. EPP Intelligent Positioner Control Unit 1/22. USER MANUAL - Intelligent Positioner Control Unit 1/22 Table of contents: 1 General... 3 1.1 Safety instructions... 3 2 Application... 4 3 Electrical specifications and terminals... 5 3.1 Control loop...

More information

Uni-Mux XQL Multi-Channel Data Acquisition Module

Uni-Mux XQL Multi-Channel Data Acquisition Module Uni-Mux XQL Multi-Channel Data Acquisition Module Uni-Mux XQL Multi-Channel Data Acquisition Module * 8 channel differential inputs. * 16 channel single ended inputs. * User programmable via P.C. software.

More information

Copyright 2014 YASKAWA ELECTRIC CORPORATION All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or

Copyright 2014 YASKAWA ELECTRIC CORPORATION All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or Copyright 2014 YASKAWA ELECTRIC CORPORATION All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic,

More information

1000TR. Instructions

1000TR. Instructions 1000TR ph Instructions CONTENTS 1. INTRODUCTION... 2 1.1 COMMON INTRODUCTION... 2 1.2 PARTS & ACCESSORIES... 2 2. INSTALLATION... 3 2.1 CASING... 3 2.2 MOUNTING... 3 2.3 ELECTRICAL INSTALLATION... 3 2.3.1

More information

BATCHMATE 1500 Batch Control Computer Technical Bulletin

BATCHMATE 1500 Batch Control Computer Technical Bulletin TS-5(C) BATCHMATE 5 Batch Control Computer Technical Bulletin DESCRIPTION The BATCHMATE features an 8 digit.55-in. alphanumeric LED display. The pulse input model will accept up to 2, pulses per second

More information

TI25 - Pre-Instructional Survey

TI25 - Pre-Instructional Survey TI25 - Pre-Instructional Survey Name: Date: 1. Scheduled maintenance that is planned, with materials on hand, personnel on site, and production planning advised is called maintenance. a. predictive b.

More information

Instruction Notes for 108A L Sensor Input

Instruction Notes for 108A L Sensor Input Operation Manual Instruction Notes for 108A L14-1800 Digital Control Module ON/OFF Main Power Switch Alarm Limits/ Cycle Switch Load Outlet (x2) General Description Sensor Input This temperature control

More information

GE Sensing. Introduction. Wiring Diagrams (Typical) Field Calibration. Installing the Sensor

GE Sensing. Introduction. Wiring Diagrams (Typical) Field Calibration. Installing the Sensor clear mode enter clear mode enter GE Sensing Introduction The GE Telaire Vaporstat 900 sensor measures in applications in the range of 0 to 0 F dew point. The sensor package is designed for wall mounting.

More information

MHPS MHPS. Modular pressure transmitter. Technical documentation. Table of content. Characteristics - applications - technical data

MHPS MHPS. Modular pressure transmitter. Technical documentation. Table of content. Characteristics - applications - technical data Technical documentation Table of content Page 2: Page 3: Page 4: Page 5: Page 6: Page 7: Page 8: Characteristics - applications - technical data Technical data - input quantity - output quantity Electrical

More information

Instruction Manual ABM HART Gateway Software. Instruction Manual Revision A.1

Instruction Manual ABM HART Gateway Software. Instruction Manual Revision A.1 Instruction Manual ABM HART Gateway Software Instruction Manual Revision A.1 Table of Contents Section 1: Getting Started... 3 1.1 Setup Procedure... 3 1.2 Quick Setup Guide for Ultrasonic Sensors... 11

More information

Temperature Transmitters

Temperature Transmitters USER'S MANUAL Rev: 2 March 1999 1 4 - + NEXT ENTER MG001470 XTC TM Series 343 Temperature Transmitters MOORE PRODUCTS CO., Spring House, PA 19477-0900 An ISO 9001 registered company. SECTION AND TITLE

More information

The wireless alternative to expensive cabling...

The wireless alternative to expensive cabling... The wireless alternative to expensive cabling... ELPRO 905U Wireless Solutions for Process Applications New Products... New Solutions The ELPRO 905U range of telemetry modules provide remote monitoring

More information

Rosemount 648 Wireless Temperature Transmitter

Rosemount 648 Wireless Temperature Transmitter Rosemount 648 Wireless Temperature Transmitter with Rosemount X-well Technology Title Page Rosemount 648 Wireless Temperature Transmitter Rosemount 648 Wireless Hardware Revision HART Device Revision

More information

Model RFT9709 Transmitter Instruction Manual

Model RFT9709 Transmitter Instruction Manual Model RFT9709 Transmitter Instruction Manual March 1999 Model RFT9709 Transmitter Instruction Manual For technical assistance, phone the Micro Motion Customer Service Department: In the U.S.A., phone

More information

NWS300 Field Type Smart Meter

NWS300 Field Type Smart Meter OM2-5190-0910 NWS300 Field Type Smart Meter User's Manual Copyright, Notices and Trademarks 1998-2014 Azbil Corporation All Rights Reserved. While this information is presented in good faith and believed

More information

Alemite FCS Fluid Control System

Alemite FCS Fluid Control System 343000 343000-1 Alemite FCS Fluid Control System Installation and Operation Guide 670996 TABLE OF CONTENTS DISCLAIMER... 3 BEFORE YOU BEGIN........................................................ 4 1.0

More information

LVTX-10 Series Ultrasonic Sensor Installation and Operation Guide

LVTX-10 Series Ultrasonic Sensor Installation and Operation Guide LVTX-10 Series Ultrasonic Sensor Installation and Operation Guide M-5578/0516 M-5578/0516 Section TABLE OF CONTENTS 1 Introduction... 1 2 Quick Guide on Getting Started... 2 Mounting the LVTX-10 Series

More information

Sarasota CM200 Sarasota HME900 Density Converter Electronics

Sarasota CM200 Sarasota HME900 Density Converter Electronics Sarasota CM00 Sarasota HME00 Density Converter Electronics Users of Sarasota density meters or specific gravity analyzers are offered the choice of a HART compatible, field mounted density converter, or

More information

SERIES 344 TERMPERATURE TRANSMITTERS

SERIES 344 TERMPERATURE TRANSMITTERS USER S MANUAL UM344-2 Issue 1 August 1995 XTC TRANSMITTERS SERIES 344 TERMPERATURE TRANSMITTERS USER S MANUAL UM344-2 CONTENTS TABLE OF CONTENTS SECTION AND TITLE PAGE 1.0 INTRODUCTION...1-1 1.1 SECTION

More information

I/A Series Intelligent Temperature Transmitter Model RTT20 Transmitter with Analog 4 to 20 ma Output, or with FoxCom or HART Communication Protocol

I/A Series Intelligent Temperature Transmitter Model RTT20 Transmitter with Analog 4 to 20 ma Output, or with FoxCom or HART Communication Protocol Product Specifications PSS 2A-1F4 A I/A Series Intelligent Temperature Transmitter Model RTT20 Transmitter with Analog 4 to 20 ma Output, or with FoxCom or HART Communication Protocol The Intelligent Temperature

More information

The wireless alternative to expensive cabling...

The wireless alternative to expensive cabling... The wireless alternative to expensive cabling... ELPRO 105U Wireless Solutions for Process Applications New Products... New Solutions The ELPRO 105U range of wireless I/O provides a low cost alternative

More information

Mastr III P25 Base Station Transmitter Tune-up Procedure

Mastr III P25 Base Station Transmitter Tune-up Procedure Mastr III P25 Base Station Transmitter Tune-up Procedure 1. Overview The Mastr III Base Station transmitter alignment is performed in several steps. First, the Transmit Synthesizer module is aligned to

More information

Model 332 Temperature Controller

Model 332 Temperature Controller 94 Instruments Model 332 Temperature Controller Features Operates down to 500 mk with appropriate NTC RTD sensors Model 332 Temperature Controller Two sensor inputs Supports diode, RTD, and thermocouple

More information

Remote Controlled FOUNDATION Fieldbus Two-Wire ph/orp Transmitter

Remote Controlled FOUNDATION Fieldbus Two-Wire ph/orp Transmitter Model 4081 ph/orp Product Data Sheet PDS 71-4081P February 2000 Remote Controlled FOUNDATION Fieldbus Two-Wire ph/orp Transmitter REMOTE COMMUNICATION IS SIMPLE; use the hand-held infrared remote controller,

More information

INSTRUCTION MANUAL FOR ULTRASONIC/MICROWAVE SENSORS

INSTRUCTION MANUAL FOR ULTRASONIC/MICROWAVE SENSORS INSTRUCTION MANUAL FOR ULTRASONIC/MICROWAVE SENSORS 1)Install PROBE_GatewayPC Software on PC.Remove previous installation. In Windows Control Panel go to the Programs and Features, select Probe_GatewayPC_Net

More information

Series 70 Servo NXT - Modulating Controller Installation, Operation and Maintenance Manual

Series 70 Servo NXT - Modulating Controller Installation, Operation and Maintenance Manual THE HIGH PERFORMANCE COMPANY Series 70 Hold 1 sec. Hold 1 sec. FOR MORE INFORMATION ON THIS PRODUCT AND OTHER BRAY PRODUCTS PLEASE VISIT OUR WEBSITE www.bray.com Table of Contents 1. Definition of Terms.........................................2

More information

The wireless alternative to expensive cabling...

The wireless alternative to expensive cabling... The wireless alternative to expensive cabling... ELPRO 905U Wireless Solutions for Process Applications New Products... New Solutions The ELPRO 905U range of wireless I/O provides a low cost alternative

More information

Process Calibrator. TechChek 820

Process Calibrator. TechChek 820 Process Calibrator TechChek 80 CONTENTS GENERAL... TURN ON... CONNECTIONS... TILT STAND...4 CHANGING BATTERIES...4 RESTORING DEFAULT SETTINGS... CONFIGURING TEMPERATURE SCALES... ENABLING AUTO-OFF... SELECTING

More information

Instruction Manual T-800 Series Current Transmitter. Model T-800L Model T-800LT Model T-800TT

Instruction Manual T-800 Series Current Transmitter. Model T-800L Model T-800LT Model T-800TT Instruction Manual T-800 Series Current Transmitter Model T-800L Model T-800LT Model T-800TT M323 Rev G1 September 10, 2009 JOWA USA, Inc. 59 Porter Road Littleton, MA 01460-1431 USA Telephone: 978-486

More information

Gentec-EO USA. T-RAD-USB Users Manual. T-Rad-USB Operating Instructions /15/2010 Page 1 of 24

Gentec-EO USA. T-RAD-USB Users Manual. T-Rad-USB Operating Instructions /15/2010 Page 1 of 24 Gentec-EO USA T-RAD-USB Users Manual Gentec-EO USA 5825 Jean Road Center Lake Oswego, Oregon, 97035 503-697-1870 voice 503-697-0633 fax 121-201795 11/15/2010 Page 1 of 24 System Overview Welcome to the

More information

+GF+ SIGNET Temperature Transmitter Instructions

+GF+ SIGNET Temperature Transmitter Instructions GF SIGNET 80- Temperature Transmitter Instructions ENGLISH -80.090- B-/00 English CAUTION! Remove power to unit before wiring input and output connections. Follow instructions carefully to avoid personal

More information

905U Wireless. New Products... New Solutions. The wireless alternative to expensive cabling... Simple but Reliable. Easy to Use

905U Wireless. New Products... New Solutions. The wireless alternative to expensive cabling... Simple but Reliable. Easy to Use Wireless New Products... New Solutions The range of telemetry modules provide remote monitoring and control by radio or twisted-pair wire, over short or long distances. Transducer signals connected at

More information

Universal Controller

Universal Controller Universal Controller Overview and Configuration Manual Overview... 1 About this Manual... 1 Introduction... 5 Hardware Overview... 5 Software Overview... 7 Interpreting Flow Diagrams... 8 Foreign Language

More information

TC LV-Series Temperature Controllers V1.01

TC LV-Series Temperature Controllers V1.01 TC LV-Series Temperature Controllers V1.01 Electron Dynamics Ltd, Kingsbury House, Kingsbury Road, Bevois Valley, Southampton, SO14 OJT Tel: +44 (0) 2380 480 800 Fax: +44 (0) 2380 480 801 e-mail support@electrondynamics.co.uk

More information

RUN MAN OUT1 OUT2 FL40

RUN MAN OUT1 OUT2 FL40 MAN RUN OUT1 OUT2 FL40 Iso 5167 mass flow computer Installation and user manual rev. 12/2015 PRELIMINARY INFORMATION This document haves copyright reserved, C Arian. Referred trademarks are of property

More information

Signal Conditioning Amplifier

Signal Conditioning Amplifier 2300 System Micro-Measurements FEATURES Accepts all strain gage inputs (foil and piezoresistive), potentiometers, DCDT s, etc Selectable bridge excitation, 0.7 to 15 VDC (11 steps), plus 0.2 to 7 VDC continuously

More information

TEK-TROL HART GATEWAY SOFTWARE. Operating Instruction Manual.

TEK-TROL HART GATEWAY SOFTWARE. Operating Instruction Manual. TEK-TROL HART GATEWAY SOFTWARE Operating Instruction Manual www.tek-trol.com Table of Contents 1 Getting Started... 2 1.1 Setup Procedure... 2 1.2 Quick Setup Guide for Radar Sensors... 10 2 Level device

More information

Micromate User Manual

Micromate User Manual Microcoin Table of Contents Page Essential Information 2 1.0 Connection and Configuration 3 1.1 Connection 3 1.2 Switch On 4 1.3 Configuration for Use 4 2.0 Check the Configuration of a Validator 5 2.1

More information

JBus/Modbus Communication Card

JBus/Modbus Communication Card JBus/Modbus Communication Card Installation and Operation 05/2018 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries

More information

SFC Smart Field Communicator Model STS103. Specification 34-ST /24/06. Description. Function. Page 1 of 5

SFC Smart Field Communicator Model STS103. Specification 34-ST /24/06. Description. Function. Page 1 of 5 SFC Smart Field Communicator Model STS103 Description The hand-held SFC Smart Field Communicator is a battery-powered device which establishes secure two-way communications between Honeywell Smart and

More information

ADI-100 Interrupter. Operator s Manual. 526 S. Seminole Bartlesville, OK /

ADI-100 Interrupter. Operator s Manual. 526 S. Seminole Bartlesville, OK / ADI-100 Interrupter Operator s Manual 526 S. Seminole Bartlesville, OK 74003 918/336-1221 www.sescocp.com ADI - 100 Interrupter FEATURES Clock Accuracy 100% during GPS lock Clock Drift 30 µsec per degree

More information

ACT-3X Tachometer / Totalizer / Ratemeter User Manual and Reference Guide

ACT-3X Tachometer / Totalizer / Ratemeter User Manual and Reference Guide ACT-3X Tachometer / Totalizer / Ratemeter User Manual and Reference Guide Rev 1.0, 021110 Safeguards and Precautions 1. Read and follow all instructions in this manual carefully, and retain this manual

More information

FOH201 User manual 1

FOH201 User manual 1 FOH201 User manual 1 WARNINGS WARNING: HIGH PRESSURE! High pressure gases and liquids are potentially hazardous. Energy stored in these gases or liquids can be released suddenly and with extreme force.

More information

PID500 FULL FEATURED PID TEMPERATURE CONTROLLERS

PID500 FULL FEATURED PID TEMPERATURE CONTROLLERS PID500 FULL FEATURED PID TEMPERATURE CONTROLLERS DESCRIPTION FEATURES * Compact Size: 1/16 DIN * Dual LED displays for simultaneous indication of process temperature and set point (Lower display selectable

More information

USER MANUAL ENGLISH 1450 COIN COUNTER & SORTER

USER MANUAL ENGLISH 1450 COIN COUNTER & SORTER USER MANUAL ENGLISH 1450 COIN COUNTER & SORTER INTRODUCTION ENGLISH Thank you for purchasing the Safescan 1450 coin counter and sorter. For proper use and maintenance, we advise to read this user manual

More information

LS3300 AC Power Calibrator Simple Adjustment Procedure for Voltage, Current, and Frequency

LS3300 AC Power Calibrator Simple Adjustment Procedure for Voltage, Current, and Frequency User s Manual AC Power Calibrator Simple Adjustment Procedure for Voltage, Current, and Frequency The instrument should be adjusted by a qualified engineer at a qualified facility with sufficient precision.

More information

MFJ ENTERPRISES, INC.

MFJ ENTERPRISES, INC. Screwdriver Antenna Controller Model MFJ-1926 INSTRUCTION MANUAL CAUTION: Read All Instructions Before Operating Equipment! MFJ ENTERPRISES, INC. 300 Industrial Park Road Starkville, MS 39759 USA Tel:

More information

Thermo Scientific Orion Star A329 Portable ph/ise/conductivity/rdo/do Meter. Reference Guide

Thermo Scientific Orion Star A329 Portable ph/ise/conductivity/rdo/do Meter. Reference Guide Thermo Scientific Orion Star A329 Portable ph/ise/conductivity/rdo/do Meter Reference Guide Ross and the COIL trade dress are trademarks of Thermo Fisher Scientific, Inc. and its subsidiaries. AQUAfast,

More information

INSTRUCTION MANUAL Redox sensor M 1322 C

INSTRUCTION MANUAL Redox sensor M 1322 C INSTRUCTION MANUAL Redox sensor M 1322 C From version 2.01 2013 Controlmatik ABW d.o.o. 2 1. General... 7 1.1 Assembly... 8 1.2 Storage of Redox probes... 9 1.3 Connection to the electrical power supply...

More information

5700A/5720A Series II Multi-Function Calibrator

5700A/5720A Series II Multi-Function Calibrator 5700A/5720A Series II Multi-Function Calibrator Operator Guide PN 601648 May 1996 1996 Fluke Corporation, Inc. All rights reserved. Printed in U.S.A. Contents What is in this Guide?... 2 Safety Summary...

More information

FIELD DEVICES - PRESSURE

FIELD DEVICES - PRESSURE FIELD DEVICES - PRESSURE o Log Product Specifications PSS 2A-1F4 A I/A Series Intelligent Temperature Transmitter Model RTT20 Transmitter with Analog 4 to 20 ma Output or HART Communication Protocol The

More information

DOC AS950 Controller. 06/2016, Edition 8. Basic Operations Fonctionnement de base Funcionamiento básico Operações básicas 基本操作基本操作

DOC AS950 Controller. 06/2016, Edition 8. Basic Operations Fonctionnement de base Funcionamiento básico Operações básicas 基本操作基本操作 DOC026.97.80493 AS950 Controller 06/2016, Edition 8 Basic Operations Fonctionnement de base Funcionamiento básico Operações básicas 基本操作基本操作 English...3 Français... 24 Español... 48 Português... 73 中文...

More information

Micro Motion Model 5700 Transmitters with FOUNDATION Fieldbus

Micro Motion Model 5700 Transmitters with FOUNDATION Fieldbus Configuration and Use Manual MMI-20029970, Rev AB January 2018 Micro Motion Model 5700 Transmitters with FOUNDATION Fieldbus Configuration and Use Manual Safety messages Safety messages are provided throughout

More information

USB-TEMP and TC Series USB-Based Temperature Measurement Devices

USB-TEMP and TC Series USB-Based Temperature Measurement Devices USB-Based Temperature Measurement Devices Features Temperature and voltage measurement USB devices Thermocouple, RTD, thermistor, or semiconductor sensor measurements Eight analog inputs Up to ±10 V inputs*

More information

Micro Motion Model 1700 Transmitters with Analog Outputs 1700***A. Configuration and Use Manual Supplement. Configuration Operation Maintenance

Micro Motion Model 1700 Transmitters with Analog Outputs 1700***A. Configuration and Use Manual Supplement. Configuration Operation Maintenance P/N MMI-20015780, Rev. AA September 2009 Micro Motion Model 1700 Transmitters with Analog Outputs Configuration and Use Manual Supplement 1700***A Configuration Operation Maintenance Micro Motion customer

More information

8510 AC Spindle Drive System

8510 AC Spindle Drive System 8510 AC Spindle Drive System Manual Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application,

More information

IXIAN TM class V 1.5. EC Transmitter This is an evolving document. EC Transmitter IXIAN TM. Features

IXIAN TM class V 1.5. EC Transmitter This is an evolving document. EC Transmitter IXIAN TM. Features class V 1.5 EC Transmitter This is an evolving document check back for updates. Features 4 20mA output Reads conductivity from 0.07µs to 100,000µs Accuracy +/- 2% Calibrate remotely through a PLC or directly

More information

PROSOFT User Manual 3.03 VERSION

PROSOFT User Manual 3.03 VERSION Via monte Nero, 40/B 21049 TRADATE (VA) ITALY hone: +39 (0)331841070 Fax:+39 (0)331841950 - e-mail:datexel@datexel.it - www.datexel.it ROSOFT User Manual 3.03 VERSION GENERAL DESCRITION ROSOFT is a software

More information

Contents. Overview Introduction...3 Capabilities...3 Operating Instructions Installation...4 Settings... 5

Contents. Overview Introduction...3 Capabilities...3 Operating Instructions Installation...4 Settings... 5 User s Manual Contents Overview................................................................. 3 Introduction..............................................................3 Capabilities...............................................................3

More information

User s Manual. Model US1000 Digital Indicating Controller Functions. IM 5D1A01-02E 2nd Edition IM 5D1A01-02E

User s Manual. Model US1000 Digital Indicating Controller Functions. IM 5D1A01-02E 2nd Edition IM 5D1A01-02E User s Manual Model US1000 Digital Indicating Controller Functions 2nd Edition Introduction This instruction manual describes the functions of the US1000 Digital Indicating Controller in detail. Read

More information

Programmable K-Factor Scaler B and Programming Software Kit B

Programmable K-Factor Scaler B and Programming Software Kit B Programmable K-Factor Scaler B220-885 and Programming Software Kit B220-900 INSTALLATION & INSTRUCTION MANUAL 8635 Washington Avenue Racine, Wisconsin 53406 Toll Free: 800.235.1638 Phone: 262.639.6770

More information

Technical Bulletin, Communicating with Honeywell TM ST3000/STT3000 Smart Transmitters

Technical Bulletin, Communicating with Honeywell TM ST3000/STT3000 Smart Transmitters Last Updated: 10-March-2009 TB-960704B Technical Bulletin, Communicating with Honeywell TM ST3000/STT3000 Smart Transmitters OMNI FLOW COMPUTERS, INC. 12620 West Airport Boulevard, Suite 100 Sugar Land,

More information

Mercury Firmware Release Notes

Mercury Firmware Release Notes Mercury Firmware Release Notes Version 1.4.43 14 October 2013 Mercury Support Oxford Instruments Nanotechnology Tools Limited tel: +44 (0)1865 393311 fax: +44 (0)1865 393333 email: helpdesk.nanoscience@oxinst.com

More information

The wireless alternative to expensive cabling...

The wireless alternative to expensive cabling... The wireless alternative to expensive cabling... ELPRO 105U ISO 9001 Certified New Products... New Solutions The ELPRO 105 range of telemetry modules provide remote monitoring and control by radio or twisted-pair

More information

Metaphase ULC-2. Technologies ULC. Metaphase. Technologies Version 7.X August 2015 USER MANUAL. metaphase-tech.com. pg. 1

Metaphase ULC-2. Technologies ULC. Metaphase. Technologies Version 7.X August 2015 USER MANUAL. metaphase-tech.com. pg. 1 ULC Version 7.X August 2015 USER MANUAL pg. 1 Overview Universal LED Controller () provides independent true constant-current or voltage control of two LED loads from 0.02 to 4 Amps continuous (DC) with

More information

Troubleshooting Guide for Aquatrac Smart AS and Flex

Troubleshooting Guide for Aquatrac Smart AS and Flex Troubleshooting Guide for Aquatrac Smart AS and Flex Part 1 Sensors and Analog Signals Alpha Release July 28 th, 2000 Alpha Release Page 1 of 21 Preface Welcome to the Aquatrac troubleshooting guide. This

More information

EULAMBIA ADVANCED TECHNOLOGIES LTD. User Manual EAT-EOM-CTL-2. Alexandros Fragkos

EULAMBIA ADVANCED TECHNOLOGIES LTD. User Manual EAT-EOM-CTL-2. Alexandros Fragkos EULAMBIA ADVANCED TECHNOLOGIES LTD User Manual Alexandros Fragkos (alexandros.fragkos@eulambia.com) 11/28/2016 28/11/2016 User Manual User Manual 28/11/2016 Electro-Optic Modulator Bias Control Unit v2.0

More information

g GE POWER MANAGEMENT

g GE POWER MANAGEMENT 469 FREQUENTLY ASKED QUESTIONS 1 Can not communicate through the front port RS232 Check the following settings Communication port on your computer ( com1, com2 com3 etc ) Parity settings must match between

More information

LC-10 Chipless TagReader v 2.0 August 2006

LC-10 Chipless TagReader v 2.0 August 2006 LC-10 Chipless TagReader v 2.0 August 2006 The LC-10 is a portable instrument that connects to the USB port of any computer. The LC-10 operates in the frequency range of 1-50 MHz, and is designed to detect

More information

ADAM-4022T Serial Base Dual Loops PID Controller User s Manual

ADAM-4022T Serial Base Dual Loops PID Controller User s Manual ADAM-422T Serial Base Dual Loops PID Controller User s Manual Warning Message : The ADAM-422T is recommended to be used in general purposed air conditioning application. When using this product in applications

More information

HART Compatible Intelligent 2-wire DIN Rail Transmitters

HART Compatible Intelligent 2-wire DIN Rail Transmitters HART Compatible Intelligent 2-wire DIN Rail Transmitters MESO-L is a Smart and universal 2-wire DIN Rail transmitter for temperature and other measurement applications. MESO-LX is the Intrinsic Safe version

More information

XDC 6000 Watt and Watt Series Digital Programmable DC Power Supply. Operating Manual

XDC 6000 Watt and Watt Series Digital Programmable DC Power Supply. Operating Manual XDC 10-600 XDC 20-300 XDC 30-200 XDC 40-150 XDC 60-100 XDC 80-75 XDC 100-60 XDC 150-40 XDC 300-20 XDC 600-10 XDC 10-1200 XDC 20-600 XDC 30-400 XDC 40-300 XDC 60-200 XDC 80-150 XDC 100-120 XDC 150-80 XDC

More information

USER'S MANUAL. UM341-2 Rev: 2 July XTC Transmitters Series 341 Pressure Transmitters with Model 275 HART Communicator

USER'S MANUAL. UM341-2 Rev: 2 July XTC Transmitters Series 341 Pressure Transmitters with Model 275 HART Communicator USER'S MANUAL UM341-2 Rev: 2 July 1998 XTC Transmitters Series 341 Pressure Transmitters with Model 275 HART Communicator UM341-2 CONTENTS SECTION AND TITLE TABLE OF CONTENTS PAGE 1.0 INTRODUCTION... 1-1

More information

WRM-10 TM TRANSFORMER WINDING RESISTANCE METER

WRM-10 TM TRANSFORMER WINDING RESISTANCE METER WRM-10 TM TRANSFORMER WINDING RESISTANCE METER USER S MANUAL Vanguard Instruments Company, Inc. 1520 S. Hellman Ave. Ontario, California 91761, USA TEL: (909) 923-9390 FAX: (909) 923-9391 June 2009 Revision

More information

Projects Connector User Guide

Projects Connector User Guide Version 4.3 11/2/2017 Copyright 2013, 2017, Oracle and/or its affiliates. All rights reserved. This software and related documentation are provided under a license agreement containing restrictions on

More information

Table of Contents. Instruction Manual - TORBAL DRX 5 Series

Table of Contents. Instruction Manual - TORBAL DRX 5 Series Table of Contents Chapter 1.CAUTIONARY NOTES AND PRECAUTIONS... 3 Chapter 2.SPECIFICATIONS... 4 Chapter 3.Keys and display indicators... 5 Chapter 4.Parts Description... 6 Chapter 5.Unpacking the balance

More information

MicroManager. Velocity Mode PID Dancer/Loadcell Control. Instruction Manual MM3000-PID

MicroManager. Velocity Mode PID Dancer/Loadcell Control. Instruction Manual MM3000-PID MicroManager Velocity Mode PID Dancer/Loadcell Control Instruction Manual MM3000-PID Table of Contents 1. General Description... 5 2. Specifications... 5 2.1 Electrical... 5 2.2 Physical... 6 3. Installation...

More information

ISOLATED 4-20 ma TRANSMITTERS

ISOLATED 4-20 ma TRANSMITTERS 500 SERIES FOR DEMANDING APPLICATIONS Isolated to 1500 V rms Two-Wire 4-20 ma Operation 9-50 V Compliance Turndown Ratio to 10:1 NMV Protection to 120 Vac -40 to +85 C (-40 to 185 F) Operation Shock Resistance

More information

USER AND INSTALLATION MANUAL

USER AND INSTALLATION MANUAL USER AND INSTALLATION MANUAL Software version 1.0.18 INSTALLATION MANUAL TABLE OF CONTENTS INTRODUCTION 2 WARNINGS 2 TECHNICAL SPECIFICATIONS 2 CONNECTION LAYOUT 3 ELECTRONIC CONNECTIONS 4 RS-485 LINE

More information

Fits Tiger 320 Series UNIVERSAL FREQ/COUNTER INPUT MODULE

Fits Tiger 320 Series UNIVERSAL FREQ/COUNTER INPUT MODULE Fits Tiger 320 Series UNIVERSAL /ER INPUT MODULE Sensor. Magnetic, Namur, Source, Sink. De-coupling. 0.02 Hz high pass filter. Signal Type., (mv) or digital logic. Input Connector. Freq. Input (CH) Up/Down

More information