Parallel Operation of Distributed Generators by Virtual Synchronous Generator Control in Microgrids
|
|
- Daniela Cummings
- 5 years ago
- Views:
Transcription
1 Niagara 2016 Symposium on Microgrids October 2021, 2016 Niagara, Canada Parallel Operation of Distributed Generators by Virtual Synchronous Generator Control in Microgrids Jia Liu* and Toshifumi Ise Osaka University, Japan October 21, 2016
2 2 Contents Introduction Parallel Inverters Synchronous Generator Inverter Conclusion
3 3 Contents Introduction Parallel Inverters Synchronous Generator Inverter Conclusion
4 Inertial feature of Synchronous Generators 4 Synchronous Generator Kinetic Energy of Rotating Mass Swing Equation Frequency fluctuation under active power transition limited by the inertia DC/AC Inverter No intrinsic relation Undesirable frequency dynamics
5 5 Concept of VSG Control Conventional Droop Control Load Sharing Smooth Transition between Islanding and Gridconnection Swing Equation Emulation Inertia Support Virtual Synchronous Generator (VSG) Control A New Concept of Inverter Control in AC Microgrid
6 6 Objectives Conventional droop control To apply VSG control to DCAC inverters in microgrids Two topics to be discussed Parallel Inverters Synchronous Generator Inverter
7 What is the benefit? 7 Without Frequency Restoration Slower frequency variation rate Frequency during Loading transition With Frequency Restoration Less maximum frequency deviation Frequency during Threephase ground fault cleared in 0.1 s Less maximum frequency deviation
8 8 Contents Introduction Parallel Inverters Synchronous Generator Inverter Conclusion
9 .. 9 Microgrid: Parallel Inverters DG1 S base1 =10kVA DG2 S base2 =5kVA L f1 :1mH pu L f2 :1mH pu 2 parallel DGs equipped with VSG control C f1 :10μF 66.31pu C f2 :10μF 33.16pu * P 0 _ i V out1 V out2 *, Q 0_ i I out1 I out2 MGCC Grid 100m 22mm 2 (0.14j0.015)Ω R * line1:0.035pu L * line1: pu 100m 22mm 2 (0.14j0.015)Ω R * line2:0.0175pu L * line2: pu BK3 Fluctuated loading BK1 BK2 V bus BUS Load1 Load2 Microgrid Central Controller (MGCC) Frequency and voltage restoration
10 ... VSG Control Scheme (Basic Part) 10 ^ V bus E 0. (Constant) k q V Q Droop Controller k q :V Q droop coef. Q 0 :Set value of reactive power Q 0 Q 0 ^ Distributed Generator P in Swing Equation Function Energy Storage V Q Droop Q ref PI bus E 0 Governor Model P 0 V bus Estimator ω g Q ref. Z ls ω m LPF 1/s E Stator Impedance Adjuster θ m P out Q out V pwm θ pwm Frequency Detector Power Meter L f V out(abc) PWM C f V out(αβ) abc/αβ Z line I out(abc) I out(αβ) BUS. Swing Equation J:Virtual inertia D:Damping factor ω m :Virtual rotor frequency ω m ω 0 (Constant) k p P 0 P in ω P Droop Controller k p : ω P droop coef. P 0 :Set value of active power
11 ... Z ls Q 0 ^ Distributed Generator P in Swing Equation Function Energy Storage V Q Droop Q ref PI bus E 0 Governor Model P 0 V bus Estimator ω g ω m LPF v out_β i out_α i out_β R line ω m L line R line v out_α v line_α v line_β 1/s P out Q out VSG Control Scheme E Stator Impedance Adjuster θ m v^ bus_α v^ bus_β V pwm θ pwm Frequency Detector αβ/ρθ Power Meter Estimate bus voltage for proper reactive power sharing (Enhanced Part) ^ V bus L f V out(abc) PWM C f V out(αβ) abc/αβ Z line I out(abc) I out(αβ) BUS. I out I thresh 0 E θ m i out_α i out_β ρθ/αβ R ls ω m Bus voltage estimator L ls R ls Stator Impedance Adjuster e α v pwm_α e β v pwm_β k Z v Zls_α v Zls_β ΔZ ls 1 1 ( X / R) 1 1 ( R / X ) 2 2 αβ/ρθ Stator Impedance Adjuster V pwm θ pwm L ls0 11 Virtual ΔR ls = R ls Stator Impedance Calculator ΔL L 1/ω ls ls 0 Constant part Transient power sharing Increased damping Transient part Overcurrent limiting
12 12 Control Parameters Parameter Value Parameter Value 10 kva 5 kva 200 V pu rad/s 8 s 1 pu 17 pu 0.05 s 1 pu 6.39 mh 0 pu mh 20 pu 1.79 pu 5 pu 5
13 Droop Control Simulation Results Loading Transition VSG Control 13 Reduced frequency deviation Islanding Loading Transition Islanding Loading Transition
14 Simulation Results ThreePhase Ground Fault Droop Control VSG Control 14 Reduced frequency deviation 3P Ground Fault 3P Ground Fault
15 .. Fault Current During ThreePhase Ground Fault 15 Without Transient Stator Impedance With Transient Stator Impedance I out I thresh 0 k Z ΔZ ls 1 1 ( X / R) 1 1 ( R / X ) 2 2 Virtual ΔR ls = R ls Stator Impedance Calculator ΔL L 1/ω ls ls 0 L ls0 E θ m ρθ/αβ e α v pwm_α e β v pwm_β αβ/ρθ V pwm θ pwm i out_α ω m i out_β R ls L ls R ls v Zls_α v Zls_β Stator Impedance Adjuster Fault Current is limited by Transient Stator Impedance
16 16 Effect of Constant Stator Reactance Without Constant Stator Reactance With Constant Stator Reactance Simulation Oscillation eliminated Oscillation damped Islanding Loading Transition P 0_2 Change Islanding Loading Transition P 0_2 Change Experiment Oscillation eliminated Oscillation damped Loading Transition P 0_2 Change Loading Transition P 0_2 Change
17 StateSpace Model of Islanded Microgrid 17 Disturbance: Loading Transition Change of Active Power Set Value Output: Frequency Active Power The damping ratio of oscillation in output parameters is determined by the eigenvalues of state matrix A
18 18 Relation between Output Reactance and Damping Ratio Total output reactance X increases Damping ratio ζ increases Oscillation can be damped by increasing output reactance
19 19 Transient Load Sharing When the disturbance is a loading transition If the total output reactance of each VSG is of the same per unit value, poles are cancelled by zeros and oscillation is eliminated
20 .. 20 Design of Constant Stator Reactance I out I thresh 0 k Z ΔZ ls 1 1 ( X / R) 1 1 ( R / X ) 2 2 Virtual ΔR ls = R ls Stator Impedance Calculator ΔL L 1/ω ls ls 0 L ls0 E θ m ρθ/αβ e α v pwm_α e β v pwm_β αβ/ρθ V pwm θ pwm i out_α R ls ω m L ls i out_β R ls v Zls_α v Zls_β Stator Impedance Adjuster
21 21 Effect of Constant Stator Reactance Without Constant Stator Reactance With Constant Stator Reactance Simulation Reactive power sharing improved Islanding Loading Transition P 0_2 Change Islanding Loading Transition P 0_2 Change Experiment Reactive power sharing improved Loading Transition P 0_2 Change Loading Transition P 0_2 Change
22 22 Cause of Poor Reactive Power Sharing If the input of droop controller is equal, reactive power should be shared properly ω P Droop V Q Droop
23 . Bus Voltage Estimator for Proper Reactive Power Sharing 23 ^ V bus E 0. (Constant) k q V Q Droop Controller k q :V Q droop coef. Q 0 :Set value of reactive power Q 0 Q ref. Z ls Q 0 ^ Distributed Generator P in Swing Equation Function Energy Storage V Q Droop Q ref PI bus E 0 Governor Model P 0 ω g ω m 1/s E Stator Impedance Adjuster θ m V pwm θ pwm Frequency Detector L f V out(abc) PWM C f V out(αβ) abc/αβ Z line I out(abc) I out(αβ) BUS V bus Estimator LPF P out Q out Power Meter. v out_β i out_α ω m L line i out_β R line R line v out_α v line_α v line_β v^ bus_α v^ bus_β αβ/ρθ Estimate bus voltage for proper reactive power sharing ^ V bus Bus voltage estimator
24 24 Contents Introduction Parallel Inverters Synchronous Generator Inverter Conclusion
25 25 Microgrid: SG Inverter Standalone microgrid in remote area SG (10 kva): Roundrotor moved by gas engine DG (10 kva): Photovoltaic panels Load: Threephase loads and singlephase Loads
26 26 Issues of Small Rating SG SG Controller SG Parameters Parameter Value Parameter Value 200 V 1 pu 10 kva 0 pu rad/s 20 pu 0.16 s 5 pu 20 pu 1 s s AVR LPF cutoff frequency 20 Hz Poor inertia Impedance Model pu pu 0.01 pu 6.55 s s 0.85 s s Slow governor response
27 27 Simulation of Single SG Operation Initial loading : 3P 1 kw, 0.5 kvar Connected loading : 1P 4.8 kw, 2.1 kvar Ripples due to 3P unbalance introduced by 1P loading Slow governor response cannot restore this frequency drop immediately Rotor frequency decreased rapidly due to poor inertia
28 28 Control Requirements of DG 1. Reduce SG rotor frequency deviation If SG rotor frequency drop below 90%, SG may be unstable Virtual Synchronous Generator (VSG) Control Generate virtual inertia to provide transient frequency support Share active and reactive power with the SG 2. Eliminate NegativeSequence Current from SG Prevent SG from overheating and torsional stresses Active power filter (APF) 3. Both 12 should be realized in ONE inverter
29 .. 29 Proposed Modified VSG Control Q 0 V out_dg Q Droop Governor Model P 0 Distributed Generator P out_dg Q ref_dg P in_dg Swing Equation Function ω g_dg LPF Energy Storage PI ω m_dg 1/s E 0 I out _ sg( dq) Q out_dg E dg θ m_dg Z ls V comp(αβ) SG Neg.Seq. Compensation θ g_sg L f Stator Impedance Adjuster I out_dg DDSRF C f V pwm θ pwm Z line abc/ αβ PWM I out_dg(αβ) BUS I out_dg(abc) V out_dg(abc) I out_sg(abc) V out_sg(abc)
30 .... Q 0 V out_dg Q Droop Governor Model P 0 Distributed Generator P out_dg Q ref_dg P in_dg Swing Equation Function ω g_dg LPF Energy Storage PI ω m_dg 1/s E 0 I out _ sg( dq) Q out_dg E dg θ m_dg Z ls V comp(αβ) SG Neg.Seq. Compensation θ g_sg L f Stator Impedance Adjuster I out_dg DDSRF C f V pwm θ pwm Z line abc/ αβ PWM I out_dg(αβ) BUS I out_dg(abc) V out_dg(abc) I out_sg(abc) V out_sg(abc) Applied to both DG and SG voltage and current to extract positive and negative sequence components Output power, voltage and current of DG are calculated from only positive sequence components Prevent ripples due to negative sequence from entering the controller DDSRF Double Decoupled Synchronous Reference Frame (DDSRF) Decomposition V αβ T θ g T I αβ T θ g T θ g ω g T 2 T 2 T 2 T 2 V dqf V dqf I dqf I dqf PLL LPF LPF LPF LPF v q V dq V dq I dq I dq 30 LPF: 1 st order low pass filter (cutoff frequency 40 Hz)
31 .. SG Neg.Seq. Compensation 31 Q 0 V out_dg Q Droop Governor Model P 0 Distributed Generator P out_dg Q ref_dg P in_dg Swing Equation Function ω g_dg LPF Energy Storage PI ω m_dg 1/s E 0 I out _ sg( dq) Q out_dg E dg θ m_dg Z ls V comp(αβ) SG Neg.Seq. Compensation θ g_sg L f Stator Impedance Adjuster I out_dg DDSRF C f V pwm θ pwm Z line abc/ αβ PWM I out_dg(αβ) BUS I out_dg(abc) V out_dg(abc) I out_sg(abc) V out_sg(abc) Stator Impedance Adjuster SG Neg.Seq. Compensation Control SG Neg.Seq. to be 0
32 32 Parameter Design of Inverter Parameter Value Parameter Value 200 V 1 pu 10 kva 0 pu rad/s 20 pu 0.16 s 5 pu 8.7 pu 0 s mh 0.69 pu mh 5 PI Controller for Reactive Power 0.05 pu PI Controller for SG Neg.Seq. Compensation 0.1 pu 0.01 s All parameters in red should be set equal to SG in per unit value to ensure proper transient and steady power sharing 20 Hz Design of Parameters in blue will be discussed in detail
33 33 Set equal to SG in order to share transient active power? Low frequency oscillation indicated by oscillatory conjugated eigenvalues
34 34 Constant Virtual Stator Inductance Output reactance of DG and SG should be set equal to share transient power, but how about the value? Connection of DG
35 35 Simulation of 1P Loading Transition SG only Initial loading : 3P 1 kw, 0.5 kvar Connected loading : 1P 4.8 kw, 2.1 kvar Improved SG rotor frequency deviation (Frequency Support of VSG) SG VSG Initial loading : 3P 2 kw, 1 kvar Connected loading : 1P 9.6 kw, 4.2 kvar (2x of SG only case)
36 36 Simulation of 1P Loading Transition w/o DDSRF and SG Neg. Seq. with DDSRF and SG Neg. Seq. Ripples due to unbalance have been eliminated
37 37 Phase Current w/o DDSRF and SG Neg. Seq. with DDSRF and SG Neg. Seq. Balanced SG current
38 38 Contents Introduction Parallel Inverters Synchronous Generator Inverter Conclusion
39 39 Conclusion Conclusion VSG control can provide inertia support for microgrids, leading to less fluctuant frequency Parallel inverters and SG inverter operations were established, and several related issues were solved Future Plan Operation of Multiple SGs Multiple inverters
40 Thank you for your kind attention! For more details, please refer to: J. Liu, Y. Miura, H. Bevrani, and T. Ise, Enhanced virtual synchronous generator control for parallel inverters in microgrids, IEEE Transactions on Smart Grid., doi: /TSG J. Liu, Y. Miura, T. Ise, J. Yoshizawa, and K. Watanabe, Parallel operation of a synchronous generator and a virtual synchronous generator under unbalanced loading condition in microgrids, 8th International Power Electronics and Motion Control Conference (IPEMCECCE Asia), Hefei, China, 2016, pp J. Liu, Y. Miura, and T. Ise, Power quality improvement of microgrids by virtual synchronous generator control, 10th Electric Power Quality and Supply Reliability Conference (PQ2016), Tallinn, Estonia, 2016.
Integration of Photovoltaic Energy to the Grid, Using the Virtual Synchronous Generator Control Technique
Journal of Energy and Power Engineering 12 (2018) 329-339 doi: 10.17265/1934-8975/2018.07.001 D DAVID PUBLISHING Integration of Photovoltaic Energy to the Grid, Using the Virtual Synchronous Agada Ihuoma
More informationA Static Synchronous Compensator for Reactive Power Compensation under Distorted Mains Voltage Conditions
10 th International Symposium Topical Problems in the Field of Electrical and Power Engineering Pärnu, Estonia, January 10-15, 2011 A Static Synchronous Compensator for Reactive Power Compensation under
More informationPower Quality Improvement using Shunt Passive Filter
Power Quality Improvement using Shunt Passive Filter Assistant Professor, Department of Electrical Engineering Bhutta Group of Institutions, India Abstract: The electricity supply would, ideally, show
More informationImproved Real/Reactive Power Management and Controls for Converter-Based DERs in Microgrids
Improved Real/Reactive Power Management and Controls for Converter-Based DERs in Microgrids Masoud Karimi and Thaer Qunais Mississippi State University karimi@ece.msstate.edu 1. Introduction: Electric
More informationInduction Machine Test Case for the 34-Bus Test Feeder -Distribution Feeders Steady State and Dynamic Solutions
Induction Machine Test Case for the 34-Bus Test Feeder -Distribution Feeders Steady State and Dynamic Solutions Induction Machine Modeling for Distribution System Analysis panel IEEE PES General Meeting
More informationTransition from Grid Connected Mode to Islanded Mode in VSI fed Microgrids
Transition from Grid Connected Mode to Islanded Mode in VSI fed Microgrids Dibakar Das, Gurunath Gurrala, U Jayachandra Shenoy Department of Electrical Engineering Indian Institute of Science, Bangalore-5612
More informationIncreasing Dynamic Stability of the Network Using Unified Power Flow Controller (UPFC)
Increasing Dynamic Stability of the Network Using Unified Power Flow Controller (UPFC) K. Manoz Kumar Reddy (Associate professor, Electrical and Electronics Department, Sriaditya Engineering College, India)
More informationPOWER QUALITY AND INVERTER-GENERATOR INTERACTIONS IN MICROGRIDS
POWER QUALITY AND INVERTER-GENERATOR INTERACTIONS IN MICROGRIDS A Thesis Presented to The Academic Faculty by Andrew Paquette In Partial Fulfillment of the Requirements for the Degree Doctor of Philosophy
More informationCHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE
98 CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE 6.1 INTRODUCTION Process industries use wide range of variable speed motor drives, air conditioning plants, uninterrupted power supply systems
More informationImproving the Transient and Dynamic stability of the Network by Unified Power Flow Controller (UPFC)
International Journal of Scientific and Research Publications, Volume 2, Issue 5, May 2012 1 Improving the Transient and Dynamic stability of the Network by Unified Power Flow Controller (UPFC) K. Manoz
More informationDigSILENT Modelling of Power Electronic Converters for Distributed Generation Networks
DigSILENT Modelling of Power Electronic Converters for Distributed Generation Networks R. Kabiri D. G. Holmes B. P. McGrath School of Electrical and Computer Engineering RMIT University, Melbourne, Australia
More informationControl of Power Converters for Distributed Generation
Mechatronics Industrial Advisory Board 2004 Control of Power Converters for Distributed Generation Ph.D. Student: Min Dai Advisor: Prof. Ali Keyhani Department of Electrical and Computer Engineering The
More informationNew Direct Torque Control of DFIG under Balanced and Unbalanced Grid Voltage
1 New Direct Torque Control of DFIG under Balanced and Unbalanced Grid Voltage B. B. Pimple, V. Y. Vekhande and B. G. Fernandes Department of Electrical Engineering, Indian Institute of Technology Bombay,
More informationA Control Method of Parallel Inverter for Smart Islanding of a Microgrid
A Control Method of Parallel Inverter for Smart Islanding of a Microgrid M. Hojo 1, K. Amo 1, T. Funabashi 2 and Y. Ueda 2 1 Institute of Technology and Science, the University of Tokushima 2-1 Minami-josanjima,
More informationControl of Active and Reactive Power Ripple to Mitigate Unbalanced Grid Voltages
Control of Active and Reactive Power Ripple to Mitigate Unbalanced Grid Voltages R. Kabiri D. G. Holmes B. P. McGrath School of Electrical and Computer Engineering RMIT University, Melbourne, Australia
More informationAalborg Universitet. Published in: I E E E Transactions on Smart Grid. DOI (link to publication from Publisher): /TSG.2015.
Aalborg Universitet Inducverters: PLL-Less Converters with Auto-Synchronization and Emulated Inertia Capability Ashabani, Mahdi; Freijedo Fernandez, Francisco Daniel; Golestan, Saeed; Guerrero, Josep M.
More informationVoltage Support and Reactive Power Control in Micro-grid using DG
International OPEN ACCESS Journal Of Modern Engineering Research (IJMER) Voltage Support and Reactive Power Control in Micro-grid using DG Nagashree. J. R 1, Vasantha Kumara. T. M 2, Narasimhegowda 3 1
More informationInternational Journal of Advance Engineering and Research Development
Scientific Journal of Impact Factor (SJIF): 4.72 International Journal of Advance Engineering and Research Development Volume 4, Issue 4, April -2017 e-issn (O): 2348-4470 p-issn (P): 2348-6406 Damping
More informationSystem Stability and Virtual Synchronous Machines. Why we need grid forming converters, and the metrological challenges of incentivising them.
System Stability and Virtual Synchronous Machines. Why we need grid forming converters, and the metrological challenges of incentivising them. Dr Andrew Roscoe. 8 th January 2018 HPoPEIPS High Penetration
More informationAn Optimized Synchronous Techniques of Single Phase Enhanced Phase Locked Loop (EPLL)
IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 11, Issue 3 Ver. IV (May. Jun. 2016), PP 36-42 www.iosrjournals.org An Optimized Synchronous
More informationTransient stability improvement by using shunt FACT device (STATCOM) with Reference Voltage Compensation (RVC) control scheme
I J E E E C International Journal of Electrical, Electronics ISSN No. (Online) : 2277-2626 and Computer Engineering 2(1): 7-12(2013) Transient stability improvement by using shunt FACT device (STATCOM)
More informationSinusoidal Current Control based Shunt Active Power Filter for Current Harmonics Reduction
Sinusoidal Current Control based Shunt Active Power Filter for Current Harmonics Reduction Anju Yadav 1, K. Narayanan 2, Binsy Joseph 3 1, 2, 3 Fr. Conceicao Rodrigues College of Engineering, Mumbai, India
More informationA Hierarchical Control Scheme for Compensating Voltage Distortions in an Inverter Based Microgrid
Research Article Journal of Energy Management and Technology (JEMT) Vol. 1, Issue 3 52 A Hierarchical Control Scheme for Compensating Voltage Distortions in an Inverter Based Microgrid MORTEZA AFRASIABI
More informationCHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS
86 CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 5.1 POWER QUALITY IMPROVEMENT This chapter deals with the harmonic elimination in Power System by adopting various methods. Due to the
More informationLevel 6 Graduate Diploma in Engineering Electrical Energy Systems
9210-114 Level 6 Graduate Diploma in Engineering Electrical Energy Systems Sample Paper You should have the following for this examination one answer book non-programmable calculator pen, pencil, ruler,
More informationMODIFYING THE THREE-PHASE SYNCHRONOUS REFERENCE FRAME PHASE-LOCKED LOOP TO REMOVE UNBALANCE AND HARMONIC ERRORS
MODIFYING THE THREE-PHASE SYNCHRONOUS REFERENCE FRAME PHASE-LOCKED LOOP TO REMOVE UNBALANCE AND HARMONIC ERRORS by Suzan Zeynep Eren A thesis submitted to the Department of Electrical and Computer Engineering
More informationModle 6 : Preventive, Emergency and Restorative Control. Lecture 29 : Emergency Control : An example. Objectives. A simple 2 machine example
Modle 6 : Preventive, Emergency and Restorative Control Lecture 29 : Emergency Control : An example Objectives In this lecture you will learn the following An example to illustrate the system angular instability
More informationArvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India
e t International Journal on Emerging Technologies 4(1): 10-16(2013) ISSN No. (Print) : 0975-8364 ISSN No. (Online) : 2249-3255 Control of Synchronous Generator Excitation and Rotor Angle Stability by
More informationPublished in: Proceedings of the 3rd IEEE Energy Conversion Congress and Exposition (ECCE 2011)
Aalborg Universitet Controlled Inverters with Seamless Transition between Islanding and Grid Connected Operations Hu, ShangHung ; Kuo, ChunYi ; Lee, TzungLin; Guerrero, Josep M. Published in: Proceedings
More informationComparison of Various Reference Current Generation Techniques for Performance Analysis of Shunt Active Power Filter using MATLAB Simulation
International Journal of Current Engineering and Technology E-ISSN 2277 4106, P-ISSN 2347 5161 2016 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijcet Research Article Comparison
More informationA Control Topology to Magnify VSC Coupled Weak Grids Performance with Self- Synchronization Capability
A Control Topology to Magnify VSC Coupled Weak Grids Performance with Self- Synchronization Capability Valluri Aravind 1, A. Durga Prasad 2 P.G. Student, Department of Electrical & Electronics Engineering,
More informationWILEY CONTROL OF POWER INVERTERS IN RENEWABLE ENERGY AND SMART GRID INTEGRATION. Qing-Chang Zhong. Tomas Hornik IEEE PRESS
CONTROL OF POWER INVERTERS IN RENEWABLE ENERGY AND SMART GRID INTEGRATION Qing-Chang Zhong The University of Sheffield, UK Tomas Hornik Turbo Power Systems Ltd., UK WILEY A John Wiley & Sons, Ltd., Publication
More informationUniversity of Kurdistan. Adaptive virtual impedance scheme for selective compensation of voltage unbalance and harmonics in microgrids
University of Kurdistan Dept. of Electrical and Computer Engineering Smart/Micro Grid Research Center smgrc.uok.ac.ir Adaptive virtual impedance scheme for selective compensation of voltage unbalance and
More informationPower Quality enhancement of a distribution line with DSTATCOM
ower Quality enhancement of a distribution line with DSTATCOM Divya arashar 1 Department of Electrical Engineering BSACET Mathura INDIA Aseem Chandel 2 SMIEEE,Deepak arashar 3 Department of Electrical
More informationA Control Topology to Enhance Performance of Weak Grid under Different Power Levels
A Control Topology to Enhance Performance of Weak Grid under Different Power Levels R. Kavitha 1, N. Priya 2 1 M.E- Power Systems Engineering, Valliammai Engineering College, Chennai, India 2 Assistant
More informationINVESTIGATION OF HARMONIC DETECTION TECHNIQUES FOR SHUNT ACTIVE POWER FILTER
IOSR Journal of Electronics & Communication Engineering (IOSR-JECE) ISSN(e) : 2278-1684 ISSN(p) : 2320-334X, PP 68-73 www.iosrjournals.org INVESTIGATION OF HARMONIC DETECTION TECHNIQUES FOR SHUNT ACTIVE
More informationFuel cell power system connection. Dynamics and Control of Distributed Power Systems. DC storage. DC/DC boost converter (1)
Dynamics and Control of Distributed Power Systems Fuel cell power system connection Ian A. Hiskens University of Wisconsin-Madison ACC Workshop June 12, 2006 This topology is fairly standard, though there
More informationCoordinated Control of Power Electronic Converters in an Autonomous Microgrid
University of South Carolina Scholar Commons Theses and Dissertations 1-1-2013 Coordinated Control of Power Electronic Converters in an Autonomous Microgrid Gholamreza Dehnavi University of South Carolina
More informationMicrogrids and Energy Management SURYANARAYANA DOOLLA POWER ENGINEERING LAB DEPARTMENT OF ENERGY SCIENCE AND ENGINEERING INDIAN INSTITUTE OF
Microgrids and Energy Management SURYANARAYANA DOOLLA POWER ENGINEERING LAB DEPARTMENT OF ENERGY SCIENCE AND ENGINEERING INDIAN INSTITUTE OF TECHNOLOGY BOMBAY 1 Why Distributed Generation? Increase in
More informationA Fuzzy Controlled PWM Current Source Inverter for Wind Energy Conversion System
7 International Journal of Smart Electrical Engineering, Vol.3, No.2, Spring 24 ISSN: 225-9246 pp.7:2 A Fuzzy Controlled PWM Current Source Inverter for Wind Energy Conversion System Mehrnaz Fardamiri,
More informationControl strategy for seamless transition from islanded to interconnected operation mode of microgrids
J. Mod. Power Syst. Clean Energy (217) 5(2):169 176 DOI 1.17/s4565-16-229- Control strategy for seamless transition from islanded to interconnected operation mode of microgrids C. N. PAPADIMITRIOU 1, V.
More informationA MATLAB-SIMULINK APPROACH TO SHUNT ACTIVE POWER FILTERS
A MATLAB-SIMULINK APPROACH TO SHUNT ACTIVE POWER FILTERS George Adam, Alina G. Stan (Baciu) and Gheorghe Livinţ Department of Electrical Engineering Technical University of Iaşi 700050, Iaşi, Romania E-mail:
More informationAn Adaptive V-I Droop Scheme for Improvement of Stability and Load Sharing In Inverter-Based Islanded Micro grids
IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331 PP 33-40 www.iosrjournals.org An Adaptive V-I Droop Scheme for Improvement of Stability and Load Sharing
More informationPhase-Locked Loops for Grid-Tied Inverters: Comparison and Testing
This paper is a postprint of a paper submitted to and accepted for publication by, and is subject to Institution of Engineering and Technology Copyright. The copy of record is available at IET Digital
More informationPak. J. Biotechnol. Vol. 13 (special issue on Innovations in information Embedded and communication Systems) Pp (2016)
COORDINATED CONTROL OF DFIG SYSTEM DURING UNBALANCED GRID VOLTAGE CONDITIONS USING REDUCED ORDER GENERALIZED INTEGRATORS Sudhanandhi, K. 1 and Bharath S 2 Department of EEE, SNS college of Technology,
More informationGrid Code Violation during Fault Triggered Islanding of Hybrid Micro-grid
Grid Code Violation during Fault Triggered Islanding of Hybrid Micro-grid Mazheruddin H. Syed, Student Member, IEEE, H.H. Zeineldin and M.S. El Moursi, Member, IEEE Department of Electrical Power Engineering
More informationImproved Grid Synchronization Algorithm for DG System using DSRF PLL under Grid disturbances
ISSN : 2248-9622, Vol. 4, Issue 11( Version - 4), November 2014, pp.48-54 RESEARCH ARTICLE OPEN ACCESS Improved Grid Synchronization Algorithm for DG System using DSRF PLL under Grid disturbances R.Godha
More informationInstantaneous power calculation based on intrinsic frequency of single-phase virtual synchronous generator
J. Mod. Power Syst. Clean Energy (07) 5(6):970 978 https://doi.org/0.007/s40565-07-07-5 Instantaneous power calculation based on intrinsic frequency of single-phase virtual synchronous generator Yangyang
More informationPower System Stability Enhancement Using Static Synchronous Series Compensator (SSSC)
Vol. 3, Issue. 4, Jul - Aug. 2013 pp-2530-2536 ISSN: 2249-6645 Power System Stability Enhancement Using Static Synchronous Series Compensator (SSSC) B. M. Naveen Kumar Reddy 1, Mr. G. V. Rajashekar 2,
More informationAvailable online at ScienceDirect. Procedia Technology 21 (2015 ) SMART GRID Technologies, August 6-8, 2015
Available online at www.sciencedirect.com ScienceDirect Procedia Technology 21 (2015 ) 310 316 SMART GRID Technologies, August 6-8, 2015 A Zig-Zag Transformer and Three-leg VSC based DSTATCOM for a Diesel
More informationINTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY
INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY A PATH FOR HORIZING YOUR INNOVATIVE WORK IMPROVED CONTROL METHOD OF GUPQC UNDER DISTORTED AND UNBALANCED LOAD CONDITION
More informationStrathprints Institutional Repository
Strathprints Institutional Repository Yu, Mengran and Roscoe, Andrew J. and Booth, Campbell D. and Dysko, Adam and Ierna, Richard and Zhu, Jiebei and Urdal, Helge (2016) Use of an inertia-less virtual
More informationControl of grid connected inverter system for sinusoidal current injection with improved performance
Control of grid connected inverter system for sinusoidal current injection with improved performance Simeen. S. Mujawar. Electrical engineering Department, Pune University /PVG s COET, Pune, India. simeen1990@gmail.com
More informationResonance Damping in a Higher Order Filter (LCL) in an Active Front End Operation
Resonance Damping in a Higher Order Filter (LCL) in an Active Front End Operation A Project Report Submitted for partial fulfillment of degree Master of Engineering In Electrical Engineering By NILANJAN
More informationA novel active current disturbance method
, pp.60-64 http://dx.doi.org/10.14257/astl.2015.111.12 A novel active current disturbance method Wu Tiezhou *, Xiong Jinlong, Wu Xiaomin, Luo Meng Hubei University of technology, Hubei collaborative Innovation
More informationANALYTICAL AND SIMULATION RESULTS
6 ANALYTICAL AND SIMULATION RESULTS 6.1 Small-Signal Response Without Supplementary Control As discussed in Section 5.6, the complete A-matrix equations containing all of the singlegenerator terms and
More informationHISTORY: How we got to where we are. March 2015 Roy Boyer 1
HISTORY: How we got to where we are March 2015 Roy Boyer 1 Traditional Stability Analysis: 1. Maintain synchronism of synchronous machines 2. Simplifying assumptions: 1. Balanced positive sequence system
More information5DESIGN PARAMETERS OF SHUNT ACTIVE FILTER FOR HARMONICS CURRENT MITIGATION
5DESIGN PARAMETERS OF SHUNT ACTIE FILTER FOR HARMONICS CURRENT MITIGATION Page 59 A.H. Budhrani 1*, K.J. Bhayani 2, A.R. Pathak 3 1*, 2, 3 Department of Electrical Engineering,..P. Engineering College
More informationA Modified Direct Power Control Strategy Allowing the Connection of Three-Phase Inverter to the Grid through LCL Filters
A Modified Direct Power Control Strategy Allowing the Connection of ThreePhase Inverter to the Grid through C Filters. A. Serpa and J. W. Kolar Power Electronic Systems aboratory Swiss Federal Institute
More informationSizing Generators for Leading Power Factor
Sizing Generators for Leading Power Factor Allen Windhorn Kato Engineering 24 February, 2014 Generator Operation with a Leading Power Factor Generators operating with a leading power factor may experience
More informationIMPROVING EFFICIENCY OF ACTIVE POWER FILTER FOR RENEWABLE POWER GENERATION SYSTEMS BY USING PREDICTIVE CONTROL METHOD AND FUZZY LOGIC CONTROL METHOD
IMPROVING EFFICIENCY OF ACTIVE POWER FILTER FOR RENEWABLE POWER GENERATION SYSTEMS BY USING PREDICTIVE CONTROL METHOD AND FUZZY LOGIC CONTROL METHOD T PRAHLADA 1, P SUJATHA 2, P BHARATH KUMAR 3 1PG Scholar,
More informationShunt Active Power Filter with Selective Harmonics Compensation for LV distribution grid
International Conference on Renewable Energies and Power Quality (ICREPQ 15) La Coruña (Spain), th to 27 th March, 215 exçxãtuäx XÇxÜzç tçw céãxü dâtä àç ]ÉâÜÇtÄ (RE&PQJ) ISSN 2172-38 X, No.13, April 215
More informationA Hierarchical Control Approach for Voltage Unbalance Compensation in A Droop Controlled Micro-Grid
IJCTA, 9(29), 2016, pp. 213-223 International Science Press 213 A Hierarchical Control Approach for Voltage Unbalance Compensation in A Droop Controlled Micro-Grid K. Swathi* and K.Bhavana** Abstract :
More informationImproved PLL for Power Generation Systems Operating under Real Grid Conditions
ELECTRONICS, VOL. 15, NO., DECEMBER 011 5 Improved PLL for Power Generation Systems Operating under Real Grid Conditions Evgenije M. Adžić, Milan S. Adžić, and Vladimir A. Katić Abstract Distributed power
More informationIslanding Detection and Frequency Circuit Measurement by Power Distribution Relation Depending on the Angle
215 International Journal of Smart Electrical Engineering, Vol.5, No.4, Fall 2016 ISSN: 2251-9246 pp. 215:220 Islanding Detection and Frequency Circuit Measurement by Power Distribution Relation Depending
More informationCONTROL OF A FOUR LEG INVERTER FOR UNBALANCED POWER NETWORKS 1
CONTROL OF A FOUR LEG INVERTER FOR UNBALANCED POWER NETWORKS 1 Jofey Simon, 1 MTPS,CUFE,Bangalore,India Email: 1 jofey000@gmail.com Abstract The operations of three-phase, four-leg inverter under unbalanced
More informationNORTH CAROLINA INTERCONNECTION REQUEST. Utility: Designated Contact Person: Address: Telephone Number: Address:
NORTH CAROLINA INTERCONNECTION REQUEST Utility: Designated Contact Person: Address: Telephone Number: Fax: E-Mail Address: An is considered complete when it provides all applicable and correct information
More informationEMERGING distributed generation technologies make it
IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 20, NO. 4, NOVEMBER 2005 1757 Fault Analysis on Distribution Feeders With Distributed Generators Mesut E. Baran, Member, IEEE, and Ismail El-Markaby, Student Member,
More informationInvestigation of negative sequence injection capability in H-bridge Multilevel STATCOM
Investigation of negative sequence injection capability in H-bridge Multilevel STATCOM Ehsan Behrouzian 1, Massimo Bongiorno 1, Hector Zelaya De La Parra 1,2 1 CHALMERS UNIVERSITY OF TECHNOLOGY SE-412
More informationISSUES OF SYSTEM AND CONTROL INTERACTIONS IN ELECTRIC POWER SYSTEMS
ISSUES OF SYSTEM AND CONTROL INTERACTIONS IN ELECTRIC POWER SYSTEMS INDO-US Workshop October 2009, I.I.T. Kanpur INTRODUCTION Electric Power Systems are very large, spread over a wide geographical area
More informationThe Research of Super Capacitor and Battery Hybrid Energy Storage System with the THIPWM
Sensors & Transducers 204 by IFSA Publishing, S. L. http://www.sensorsportal.com The Research of Super Capacitor and Battery Hybrid Energy Storage System with the THIPWM Jianwei Ma, 2 Shanshan Chen, 2
More informationSimulation and Comparison of DVR and DSTATCOM Used For Voltage Sag Mitigation at Distribution Side
Simulation and Comparison of DVR and DSTATCOM Used For Voltage Sag Mitigation at Distribution Side 1 Jaykant Vishwakarma, 2 Dr. Arvind Kumar Sharma 1 PG Student, High voltage and Power system, Jabalpur
More informationActive Power Filter with Fast PI Controller Using Matlab/simulink
Active Power Filter with Fast PI Controller Using Matlab/simulink Dipak Badgujar,Anil Kumar Chaudhary,C.Veeresh, Email:dipakbadgujar84@gmail.com,anilkumar6352@gmail.com Abstract In a modern power system,
More informationControl Of Shunt Active Filter Based On Instantaneous Power Theory
B.Pragathi Department of Electrical and Electronics Shri Vishnu Engineering College for Women Bhimavaram, India Control Of Shunt Active Filter Based On Instantaneous Power Theory G.Bharathi Department
More informationMODELING AND ANALYSIS OF IMPEDANCE NETWORK VOLTAGE SOURCE CONVERTER FED TO INDUSTRIAL DRIVES
Int. J. Engg. Res. & Sci. & Tech. 2015 xxxxxxxxxxxxxxxxxxxxxxxx, 2015 Research Paper MODELING AND ANALYSIS OF IMPEDANCE NETWORK VOLTAGE SOURCE CONVERTER FED TO INDUSTRIAL DRIVES N Lakshmipriya 1* and L
More informationRenewable Interconnection Standard & Experimental Tests. Yahia Baghzouz UNLV Las Vegas, NV, USA
Renewable Interconnection Standard & Experimental Tests Yahia Baghzouz UNLV Las Vegas, NV, USA Overview IEEE Std 1547 Voltage limitations Frequency limitations Harmonic limitations Expansion of IEEE Std
More informationAN EXPERIMENTAL STUDY OF FREQUENCY DROOP CONTROL IN A LOW- INERTIA MICROGRID ANDREW MARK BOLLMAN THESIS
AN EXPERIMENTAL STUDY OF FREQUENCY DROOP CONTROL IN A LOW- INERTIA MICROGRID BY ANDREW MARK BOLLMAN THESIS Submitted in partial fulfillment of the requirements for the degree of Master of Science in Electrical
More informationLiterature Review for Shunt Active Power Filters
Chapter 2 Literature Review for Shunt Active Power Filters In this chapter, the in depth and extensive literature review of all the aspects related to current error space phasor based hysteresis controller
More informationApplication of Dynamic Voltage Restorer for Voltage Balancing with ASD Load Using DQO Transformation
International Journal of Electrical Engineering. ISSN 0974-2158 Volume 4, Number 8 (2011), pp. 889-898 International Research Publication House http://www.irphouse.com Application of Dynamic Voltage Restorer
More informationReceived: 18 July 2017; Accepted: 24 August 2017; Published: 30 August 2017
energies Review Overview of AC Microgrid Controls with Inverter-Interfaced Generations Md Alamgir Hossain 1, * ID, Hemanshu Roy Pota 1, Walid Issa 2 and Md Jahangir Hossain 3 1 School of Engineering &
More informationMicrogrid Connection Management based on an Intelligent Connection Agent
Microgrid Connection Management based on an Intelligent Connection Agent J. Rocabert 1, Student Member, IEEE, G. Azevedo 2, Student Member, IEEE, I. Candela 1, Member, IEEE, R. Teoderescu 3, Member, IEEE,
More informationModified three phase Unified Power Quality Conditioner with capacitor midpoint topology
IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 6, Issue 4 (Jul. - Aug. 2013), PP 48-54 Modified three phase Unified Power Quality Conditioner
More informationDevelopment of a Frequency-stabilizing Scheme for Integrating Wind Power Generation into a Small Island Grid
Preprints of the 8th IFAC World Congress Milano (Italy) August 8 September, Development of a Frequencystabilizing Scheme for Integrating Wind Power Generation into a Small Island Grid K. Yamashita, O.
More informationInternational Journal of Advance Engineering and Research Development CONTROL OF REDUCED-RATING DYNAMIC VOLTAGE RESTORER
Scientific Journal of Impact Factor (SJIF): 5.71 International Journal of Advance Engineering and Research Development Volume 5, Issue 06, June -2018 e-issn (O): 2348-4470 p-issn (P): 2348-6406 CONTROL
More informationCombined active and reactive power control strategy to improve power system frequency stability with DFIGs
The 6th International Conference on Renewable Power Generation (RPG) 19 20 October 2017 Combined active and reactive power control strategy to improve power system frequency stability with DFIGs Congwei
More informationAGN 022 Conditions for Parallel Operation
Application Guidance Notes: Technical Information from Cummins Generator Technologies AGN 022 Conditions for Parallel Operation SYNCHRONISATION The parallel operation of Generating Sets is common, to share
More informationHow Full-Converter Wind Turbine Generators Satisfy Interconnection Requirements
How Full-Converter Wind Turbine Generators Satisfy Interconnection Requirements Robert Nelson Senior Expert Engineering Manager and Manager of Codes, Standards, and Regulations Siemens Wind Turbines -
More informationUnified Power Quality Conditioner based on an Indirect Matrix Converter with a PV panel
Unified Power Quality Conditioner based on an Indirect Matrix Converter with a PV panel Nathan Araujo, Student, IST Abstract The main goal of this master thesis is to propose a Unified Power Quality Conditioner
More informationImplementation of SRF based Multilevel Shunt Active Filter for Harmonic Control
International Journal of Engineering Research and Development e-issn: 2278-067X, p-issn: 2278-800X, www.ijerd.com Volume 3, Issue 8 (September 2012), PP. 16-20 Implementation of SRF based Multilevel Shunt
More informationPower Quality Improvement Utilizing Photovoltaic Generation Connected to a Weak Grid
Power Quality Improvement Utilizing Photovoltaic Generation Connected to a Weak Grid Hanny H. Tumbelaka Member, IEEE Electrical Engineering Department Petra Christian University Surabaya, Indonesia tumbeh@petra.ac.id
More informationEE 742 Chapter 9: Frequency Stability and Control. Fall 2011
EE 742 Chapter 9: Frequency Stability and Control Fall 2011 Meeting demand with generation Large and slow changes (24 hr) in power demand are met by unit commitment Medium and relatively fast changes (30
More informationImpacts of P-f & Q-V Droop Control on MicroGrids Transient Stability
Available online at www.sciencedirect.com Physics Procedia 24 (212) 276 282 212 International Conference on Applied Physics and Industrial Engineering Impacts of P-f & Q-V Droop Control on MicroGrids Transient
More informationInitial Application Form for Connection of Distributed Generation (>10kW)
Please complete the following information and forward to Vector Contact Details Primary Contact (who we should contact for additional information) Contact person Company name Contact numbers Daytime: Cell
More informationSystem Protection and Control Subcommittee
Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),
More informationA NEW POWER SIGNAL PROCESSOR FOR CONVERTER- INTERFACED DISTRIBUTED GENERATION SYSTEMS
A NEW POWER SIGNAL PROCESSOR FOR CONVERTER- INTERFACED DISTRIBUTED GENERATION SYSTEMS by Davood Yazdani A thesis submitted to the Department of Electrical Engineering In conformity with the requirements
More informationVoltage Sags in Distribution Systems with Induction Motor Loads Fed by Power Converters and Voltage Mitigation using DVR and D-STATCOM
International Journal of Electrical Engineering. ISSN 0974-2158 Volume 5, Number 7 (2012), pp. 889-902 International Research Publication House http://www.irphouse.com Voltage Sags in Distribution Systems
More informationSCIENCE & TECHNOLOGY
Pertanika J. Sci. & Technol. 25 (S): 249-256 (217) SCIENCE & TECHNOLOGY Journal homepage: http://www.pertanika.upm.edu.my/ Synchronous Reference Frame Fundamental Method in Shunt Active Power Filter for
More informationInvestigation of D-Statcom Operation in Electric Distribution System
J. Basic. Appl. Sci. Res., (2)29-297, 2 2, TextRoad Publication ISSN 29-434 Journal of Basic and Applied Scientific Research www.textroad.com Investigation of D-Statcom Operation in Electric Distribution
More informationSMALL WIND TURBINE CONTROL WITH FREQUENCY SUPPORT FOR INTEGRATION IN MICROGRIDS
Bulletin of the Transilvania University of Braşov Series I: Engineering Sciences Vol. 6 (55) No. 2-2013 SMALL WIND TURBINE CONTROL WITH FREQUENCY SUPPORT FOR INTEGRATION IN MICROGRIDS Ioan ȘERBAN 1 Abstract:
More informationInteractive Distributed Generation Interface for Flexible Micro-Grid Operation in Smart Distribution Systems
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, VOL. 3, NO. 2, APRIL 2012 295 Interactive Distributed Generation Interface for Flexible Micro-Grid Operation in Smart Distribution Systems Alireza Kahrobaeian and
More information