User Manual Frequency Inverter Vector 54 1ph. User manual. Frequency Inverter VECTOR 54 1ph. 0,09 kw - 0,75 kw

Size: px
Start display at page:

Download "User Manual Frequency Inverter Vector 54 1ph. User manual. Frequency Inverter VECTOR 54 1ph. 0,09 kw - 0,75 kw"

Transcription

1 User manual Frequency Inverter VECTOR 54 1ph 0,09 kw - 0,75 kw Version: 49/2013 Date: Page 1 of 34

2 Warranty According to the current general terms of delivery and payment MSF- Vathauer Antriebstechnik GmbH & Co. KG provides a warranty of 12 months (in single shift) after delivery on all electronic devices covering design, material or faulty workmanship. MSF- Vathauer Antriebstechnik reserves the right to change the contents of this operation manual and the product specifications contained therein without prior notice. The copyright of this documentation is reserved by MSF-Vathauerer Antriebstechnik GmbH & Co. KG. Attention! Read this manual carefully and completely. Start with the installation and commissioning only after reading. Technical changes reserved. Page 2 of 34

3 Index Warranty Safety and application instructions for VECTOR General Intended Usage Transport and Storage Installation Electrical connection Operation Maintenance and servicing Safety and Installation considerations... 7 European EMC directive Assembly and Installation Installation Cabling directives of superior controls Grounding, earthen, potential compensation Filtering Screening signal- and control cables Coupling into motor cables Technical Features Menu structure Connection diagrams Connection I/O- Module Power unit single phase Minimum terminal-connection single phase Programmable parameter sets Running up time Running down time Quick stop Motor frequency Minimum rotating field frequency Maximum rotating field frequency Digital output (frequency) Digital output (current) Time dynamic boost DC brake Duration of the DC braking Current limit Forward sheet-metal seat pan truncation In- and Outputs (I/O-Module) Digital Inputs Minimum rotating field frequency fmin Parameter set changeover Clockwise rotation - start right Counter-clockwise rotation -start left Release Analogue Output Analogue Output Offset...21 Page 3 of 34

4 7.9. Analogue Output Factor Digital Output Controller values Working mode Motor-nominal-current Motor Cos ϕ P section I section Settings Switching frequency (clock) frequency Type of Set value Set value - Offset Set value - Hysteresis Fade out frequency1, fade out frequency I²t current Regulation Factory settings Operating values Application notes Dynamic braking by means of a braking chopper Motor protection Technical data Electrical data Measurments Annex Parameter set 1 and In -and Outputs Regulation values Settings Analogue output Pin figuration Incremental encoder...34 Page 4 of 34

5 1. Safety and application instructions for VECTOR General As long as any electrical equipment and machinery is switched on, the operator may touch voltage leading and non-isolated conductors or rotating parts as well as hot surfaces. At removing the covers and the prescribed protections, in handling the machine improperly, or during service work or improper use, there is the danger of death or severe injuries or material damage. All works with transport, installation and commissioning as well as maintenance have to be done by properly trained personnel (regard IEC 364 res. CENELEC HD 384 or DIN VDE 0100 and IEC report 664 or DIN VDE 0110 and national accident prevention regulations or VGB 4). Qualified personnel in terms of these basic security considerations are persons that are used to installation; assembly, commissioning and operation of the product and that have qualifications according to their work (defined in IEC 364 or DIN VDE 0105) Intended Usage Frequency Inverters are components for installation within machines that are operated in industrial plants. The commissioning of the frequency Inverter is prohibited until it is ascertained that the machine that includes the frequency Inverters follows the restrictions of the EU directive 2006/42/EG (machine directive). The frequency Inverters match the protection goals of the low voltage directive 72006/95/EG and the harmonized norms of the series EN 50178/ DIN VDE 0160 in connection with EN / DIN VDE 0660 part 500 and EN / DIN VDE The operation is only permitted according to the EMC directive (04/108/EG). The technical data and information to connection conditions are to be found on the rating plate or the documentation and have to be completely fulfilled Transport and Storage The considerations for transport, storage and the appropriate handling must be regarded. Damages recognized after delivery must be immediately announced to the transport company. If applicable, notify the distributor before commissioning. Regard the environmental conditions according to pren Page 5 of 34

6 1.4. Installation The installation and cooling of the device must be in accordance with the provisions of the relevant documentation. The frequency Inverters must be protected from excessive strain. They are to handle only in a way, so that no components are bent and / or isolating distances altered. The contact of electronic components and terminals must be avoided. Frequency Inverters contain electrostatic sensitive devices. These components can be easily destroyed by improper handling. Built-in electrical components must not be destroyed (potential health hazard) Electrical connection At working at current Inverters with supplied power regard the valid national accident prevention regulations (e.g. VGB 4). The electrical installation has to be done according to the valid directives (e.g. cable diameters, fuse protection, ground wire connection). More detailed information is to be found in the documentation. Compliance with the limits for the plant according to the EMC juridical directive is in responsibility of the manufacturer of the plant. Considerations for the EMC-compatible installation like screening, grounding, alignment of filters and lying of cables are to be found in the documentation of the frequency Inverters Operation Plants that contain frequency Inverters have to be provided, if applicable, with additional observation and security installations according to the concerning valid security directives, e.g. act on technical work equipment, accident prevention regulations etc. The documentation of the manufacturer has to be regarded. After disconnection of the frequency Inverters from the supply voltage, voltage conducting device parts and cable conductors must not be immediately touched because of possibly charged condensers. Please regard the according notification signs at the frequency Inverters. During operation all covers must kept closed Maintenance and servicing The documentation of the manufacturer has to be regarded. Page 6 of 34

7 1.8. Safety and Installation considerations Frequency Inverters from MSF-Vathauer Antriebstechnik are operating resources for the deployment in industrial high-voltage plants and are operated with voltages that may cause heavy injuries or death when touching! Installations and works may only be executed by qualified electrical trained personnel and at voltage free device. The user manual has to be available at any time and has to be consequently regarded. The local directives for building electrical plants and accident prevention regulations must be fulfilled. The device is up to 5 minutes after disconnecting from the voltage conducted with dangerous voltage. Due to this, opening of the device or removing the cover res. the I/O module and the display device is only permitted 5 minutes after disconnecting the device from voltage. Before turning the mains voltage on all covers must be mounted again. Also at motor standstill (e.g. due to electronics lock, short circuit at the output clamps or blocked drive) the voltage circuit clamps, motor clamps and clamps for the brake resistance may conduct dangerous voltage. A motor standstill is not identical with a galvanic disconnection from the mains voltage. Attention: The Inverter may, depending on the settings, start automatically after powering the mains voltage. Attention! Danger to Life! The power supply conducts voltage under certain circumstances for up to 5 minutes after turning off the mains voltage. Inverter clamps, drive cables and drive clamps may conduct voltage! Touching open or free clamps, cables and device parts may cause heavy injuries or death! Attention Children and the public must not have access to the device! The device may only be used for the purpose intended by the manufacturer. Unauthorized changes and the use of replacement parts and additional devices that are not sold or approved by the manufacturer may cause fire, electric shocks and injuries. Keep the manual in reach and make it available for every user! European EMC directive If the vector field power is installed according to the recommendations of this manual it fulfills the requirements of the EMC directive according to the EMC product norm for motor driven systems EN Page 7 of 34

8 2. Assembly and Installation 2.1. Installation The devices require adequate ventilation. The hot air has to be dissipated above the Inverter! 2.2. Cabling directives of superior controls The frequency Inverters are developed for the operation in industrial environments where high values of electromagnetic interferences are expected. In general, a professional installation ensures a risk less and error-free operation. If limits are required that exceed the EMC directive limits, the following directives are recommended. 1. Please make sure that all devices in the control cabinet are connected together at a shared grounding point or rail with short cores and great diameter are properly grounded. It is especially important that every control device connected to the inverters (e.g. automation devices) are connected via a short core with high diameter at the same grounding point like the inverter. 2. The PE conductor of the drive controlled by the Inverter should preferably directly connected to the ground connection connected with the heat sink together with the PE of the power supply of the concerning inverter. The existence of a central grounding rail within the control cabinet and the connection of all ground cables to this rail normally guarantees an error-free operation. 3. As far as possible you should use screened cables for the control. The cable ends have to be terminated carefully and it must be taken care that the cores are not unscreened over long distances. The screen of analogue set point cables should only be grounded at the frequency Inverter single-sided. Not used cores of the control cores should be grounded. 4. The control cores have to be laid in the most possible distance from the load cores using separated cable trenches etc. Cable crosses should possibly get an ankle of Make sure that contactors and relays in the control cabinets are suppressed either by RC connection or varistors in case of AC contactors or by free wheeling diodes at DC contactors, wherein the interference suppression bust be attached to the coils. The suppression is especially important if the contactors are controlled by the relay in the frequency Inverter (optional). 6. Use screened cores for the load connections and ground the screening at both ends, if possible directly at the PE output of the Inverter. 7. If the drive should run within an environment sensible to electro-magnetic interference, the usage of interference filters is recommended to reduce the gridbound and radiated interferences of the Inverter. In this case install the filter as near as possible to the inverter and take care for grounding. 8. Choose the lowest possible toggle frequency. This minimizes the intensity of the electro-magnetic interference created by the frequency Inverter. At installation of the Inverters you must not disregard safety directives! Page 8 of 34

9 2.3. Measures to secure the EMC in machinery and plants The following measures are to secure the EMC, which are of absolute necessity to the Inverter technology. The Inverter fulfills the demands of the high noise immunity and the slight-noise emissions for the usage in industries, under the guidelines of this manuals installation consideration. 2.4 Grounding, earthen, potential compensation The correct professional grounding or earthen guarantees the protection of the staff against dangerous touch voltages (input, output and intermediate circuit voltage) and through parasitic current inductance and low-impedance potential compensation an important measure to reduce electromagnetic influences Filtering Filters are inserted into the lead-bound transfer way between the source of interference and the interference suppressor, which is to reduce lead-bound transmissions and to increase the noise immunity. Additional, external filter may have a negative effect on the noise emission! 2.6. Screening signal- and control cables Screening is used for decoupling fields between two spatially separate areas, i.e. is also used to decrease the emission of electromagnetic radiation and to increase the noise immunity. The consistent use of metal cases is one of the most important standard measures to safeguard the EMC Coupling into motor cables The use of twisted core cables can essentially reduce inductive couplings into a circuit. Cable screens must reduce capacitive, inductive and electromagnetic interferences. It is important to note that to reduce low frequency capacitive interference, it is often sufficient to place a one sided screening, whereas inductive and high frequency electromagnetic interference can only be prevented by screening both sides of the cable. The screening must not be used as a protection earthen!!! Page 9 of 34

10 3. Technical Features The Vector 54 is a frequency-inverter with a modulated attachment, which in it s basic, offers excellent market value for goods by using simple applications. With extra-integrated modules it can be alternated for a controlled drive with vector-control or upgraded to a positioning type. The centerpiece is a 16-bit signal processor with an internal flash for the renewal of the pulse and control-technique-duties. Through a serial- SPI interface the processor is able to communicate with one or more intelligent modules. Under the term of intelligent modules belong the ones which serve the purpose of changing the protocol, such as Interbus-S, Profibus, CAN-Bus, as well as systems which give the frequency- Inverter SPS-functionality with a multitude of interconnected inputs, or a plain-text LC-Display and are able to save parameters inside the module. To the passive modules belong the ones, which give the frequency Inverter extra digital inand outputs, a rotary-encoder-input, and the adaptation to RS 232and RS 485 interface. The modular mount simplifies flexible processing of customer wishes and customer orientated developments. This is the result of years of experience with the demands of the frequency-inverter for practical use. The menu-surface is clearly arranged and very well structured. Special functions The practical design offers the following advantages: Different installation positions optimize the installation, and minimize the space requirement in the switch cabinet. Furthermore a braking chopper is integrated in the VECTOR 54 A plug-on type operator interface offers the following advantages: LC-Graphic display Plain text display On-line parameterization Easy parameterization via comfortable PC user surface: RS-232 interface (optional) 2 programmable parameter sets of freely selectable set values Programmable input/output terminals Page 10 of 34

11 High operational safety due to: Aluminum casing and standard input/output filters provide high noise immunity and only Low noise emissions Short-circuit protection Potential separated nominal value input The new CCDS-SYSTEM (current-control dynamic scan) prevents the Inverter from switching-off at short time excess current flow (e.g. dynamic acceleration) Page 11 of 34

12 4. Menu structure Parametersets Parameterset 1 Run up time R Run down time R In-and Outputs Parameterset 2 Run up time L Run down time L Controller value Quickstop Motor nominal frequency Settings Min. Frequency R Max. Frequency R Operating values Min. Frequency L Max. Frequency L End Frequency digital Out Static Boost Dynamic Boost Time dynamic Boost DC-brake Time DC-brake Current limit Pan trunction Digital In 1 Digital In 2 Digital In 3 Digital In 4 Analogue Out Analogue Out Offset Analogue Out Factor Digital Out Relay 0) General fault message 1) Overvoltage 2 (at circuit) 2) Undervoltage (at circuit) 3) Fault on power unit 4) Set value = Actual value 5) Rotary field right /CW 6) Multi- Function (Frequency) 7) Temperature too high (Inverter) 8) FU ready 9) Motor turns (Null Monitoring) 10) PTC- temperature too high (motor) 11) Multifunction (current incl. Current limit 12) Parameterset 1 or 2 active 13) DC-brake active 14) Pulsoutput (only at digital output) working modus rated outp. current Cos ϕ P- share I- share il V/F = linear V/F = square Vector Clock frequency 2/4/8/16 khz Set value Set value offset Set value hysteresis Fade out frequency 0-10V Range fade out frequency 10-0V I²t Current V Operation V Factory setting 2-10V 10-2V 5-10V 10-5V Nominal value 0-20mA Actual value 20-0mA Temperature 4-20mA Current 20-4mA DC link voltage Serial interface Softwareversion FU Display Softwareversion Display Page 12 of 34

13 5. Connection diagrams 5.1. Connection I/O- Module ϑ V Referenzspannung reference voltage analoger Analogue Sollwerteingang preset value input GND GND (Analog) (Analogue) Analogausgang Analogue output +15V +15V (max. (max 100mA) 100mA) Start- Start-clockwise Rechtslauf (right) Start- Linkslauf counter-clockwise (left) minimale Min. rotating Drehfeldfrequenz field-frequency Parametersatzumschaltung set-changing Freigabe Release GND (Digital) Digitalausgang output 1 Externe External Versorgungsspannung supply voltage Digitalausgang output 2 PTC-Motor Motortemperaturüberwachung temperature-control PTC-Motor Motortemperaturüberwachung temperature-control Relaisausgang Relay output (No (Schließerkontakt) contact) Relaisausgang Relay output (Common (gem. Kontakt) contact) Relaisausgang Relay output (NC (Öffnerkontakt) contact) The relay contact can be loaded with 250V AC, 7A max! Attention: The digital-inputs (terminals 6,7,8,9) are designed for a control voltage of 12 30V! The Open- Collector- outputs (terminal 12, 13) can be loaded with 30V/40mA at max! Page 13 of 34

14 5.2. Power unit single phase Page 14 of 34

15 5.3. Minimum terminal-connection single phase The above drawing shows the min.-required terminal-connection of the digital inputs. Page 15 of 34

16 6. Programmable parameter sets Two independent parameter sets are available for the parameterization, in which the runningup, - running downtimes as well as the min.-and max. rotating field frequency for the rightand left rotation can be adjusted separately Running up time Time during which the motor would reach the previously set maximum frequency starting at 0 Hz using a ramp set value. An extension of the running-up time arrives by decreasing the running-down-slope, shortenings by increasing the running-down-slope (Hz/s) The quotient: maximum frequency/running-up time yields the so-called ramp. This designates the change of the rotating field frequency change per time unit. A steep ramp is equivalent to a short running-up time. A flat ramp is equivalent to a long running-up time. The set running-up times must always be application-specific, taking into account the physical realities resulting there from. Especially short running-up times can influence the motor stability or cause a switch-off of the Inverter due to an excess current. A sensible feeling is also required in the selection of sufficiently long running-up times for large centrifugal masses The running-up times are separately adjustable for clockwise and counterclockwise turnings Running down time Time during which the motor would reach 0 Hz starting at the previously set maximum frequency using a ramp set value of 0 V. An extension of the running-down time derives by decreasing the running down ramp, a shortening arrives by increasing the running down ramp. (Hz/s) Essentially, the explanations given in the section Running-up times also apply here. When inappropriate short running-down ramps are selected (especially with large centrifugal masses) over voltages in the intermediate circuit can cause a switch-off of the Inverter. Since in this state of operation, the rotating field frequency applied to the motor is slightly less than the frequency of the motor shaft, energy will be fed back (generator operation) resulting in an inadmissible increase of the intermediate circuit voltage in the Inverter. If the special application does not admit longer running-down times, use a braking chopper to reduce the excessive intermediate circuit voltage. The braking chopper will convert the energy produced in the generator operation into heat losses. The running-down times are separately adjustable for clockwise and counterclockwise turnings. Page 16 of 34

17 6.3. Quick stop Time during which the motor would reach 0 Hz starting at the previously set maximum Frequency, by taking away the release. An extension of the running-down time arrives by decreasing the running down ramp, a shortening arrives by increasing the running down ramp. The setting of the ramp is done in parameter sets 1 and Motor frequency Input of the frequency in Hz of the connected motor Minimum rotating field frequency The minimum rotating field frequency to be set in advance below which the Inverter should not drop even if the lowest set value is applied to the analogue input. The minimum rotating field frequency is separately adjustable for clockwise and counterclockwise turnings. Attention: Only a pre-setting of a min. frequency = 0 Hz will result in a frequency of 0 Hz with an applied set value of 0 volt. With a set frequency >0 Hz, a frequency of 0 Hz can only be obtained via a STOP frequency Maximum rotating field frequency In advanced set maximum rotating field frequency, which the Inverter should never exceed, even if the highest possible set value (admissible range: 0 V to 10 V) is applied to the analogue input. The maximum rotating field frequency is separately adjustable for clockwise and counterclockwise turnings. 6.7 Digital output (frequency) Set rotating field frequency at which to switch the digital output. This relay function is activated by specifying values other than Digital output (current) To be set current level at which the digital output should switch. To activate this relay function, the value entered for the Digital output parameter must be of a value which is higher than ZERO. Page 17 of 34

18 6.9. Static Boost Deviating from the linear V/f characteristics, this voltage increase is specified in percent of the nominal voltage to increase the starting torque at low rotating field frequencies. With low rotations, the copper resistance of the stator winding strongly influences the operating characteristics of the motor. Without a voltage correction, the breakdown torque is significantly reduced towards low rotating field frequencies. During slow starts, it could happen that the motor does not start due a too high breakaway torque to be obtained. By using a voltage increase - the so-called BOOST - the starting torque is increased. The amount of the BOOST is specified in percentage of the nominal voltage at 0 Hz. Starting at this value, the voltage is continually raised with an increasing frequency and thus approaches the normal (linear) V/f characteristic: V/f = const. A constantly available voltage increase is called static BOOST. The range of the voltage increase extends to about a frequency of up to of 2/3 of the kink frequency. To prevent a torque jump during the transition of the BOOST to the V/f=constant characteristics, all characteristics of the static BOOST end at the V/f characteristic. Good starting torques is achieved with a BOOST setting of 8%. Exaggerated high values results in an increased motor temperature, which may destroy in the destruction of the motor by, overheat, particularly if no separate fan is used. a high BOOST value can also cause an excessive currant, which will likewise switch the Inverter off. Bild Normed output voltage as a function of frequency and boost 6.10 Dynamic boost Deviating from the linear V/f characteristics, this time limit voltage increase is specified in percent of the nominal voltage for increasing the starting torque at low rotating field frequencies. By using the dynamic boost the motor is exposed to a thermally limited minimal burden. The dynamic boost is added to a static boost, which may exits. The same explanations apply as for the static boost. Page 18 of 34

19 6.11 Time dynamic boost During the running up operations, the dynamic boost is activated for the set duration when the 1Hz is exceeded DC brake The value specified in a percentage of the nominal voltage, which determines the stopping torque (torque at standstill) of the motor ( DC brake ). Note: Despite a high torque generated by the motor at a rotating field frequency of 0 Hz, the motor shaft can slowly be rotated by an externally applied torque, as this is not a regulated system Duration of the DC braking The time for which the DC brake is active. To prevent a thermal overload of the motor, the DC brake is limited to a maximum of 25 seconds, and it is activated when it reaches 0 Hz. DC braking can either be activated by applying a set value of 0 V, or by a STOP command. DC braking remains active for the entire preset time if the set value is not increased again during the braking or a START command is given. Reversing does not activate DC braking Current limit On exceeding of the current limit set in the particular parameter sets the rotary field frequency is reduced to a value, in which the motor current the set current limit no longer exceeds. The reduction can be carried out up to a rotating field frequency of about 8 Hz Forward sheet-metal seat pan truncation At enabling the forward sheet-metal seat pan truncation the rotary field frequency rises and falls not linear anymore. It rather follows an S curve. At usage of the forward sheet-metal seat pan truncation, the high and low runtime lengthens with factor 2. Frequency Time Page 19 of 34

20 7. In- and Outputs (I/O-Module) 7.1. Digital Inputs The pins 6,7,8 and 9 are digital inputs and are assigned with the following functions Clockwise start (right) Counter clockwise start (left) Minimum rotating field frequency fmin Parameter set changeover Minimum rotating field frequency fmin. During active function is maintained regardless of the nominal value, the minimum field frequency 7.3. Parameter set changeover 1-2 The current parameter set is chosen through the digital inputs. A parameter set wanted by wiring the corresponding inputs is taken over online Clockwise rotation - start right Activating this function will result in acceleration of the motor with the set acceleration time in the selected parameter set until reaching the required set value in the specified direction. Deactivation at an inactive Start-CCW-function will cause a run-down at the set ramp of the selected parameter set down to a standstill. If the ramp of the corresponding parameter set is deactivated, the shaft is immediately released Counter-clockwise rotation -start left Refer to Clockwise rotation start in the opposite sense of rotation. At additional activation of Clockwise rotation start, Start right (clockwise) has priority and reversing process takes place Release Activating the input causes an initialization of the control and the power unit of the Inverter where, at it s end the operational readiness of the unit is. The opening of the input causes an immediate release of the Quick Stop function, its deceleration time is set in the parameter sets. Page 20 of 34

21 7.7. Analogue Output The analogue output can be connected with different functions like e.g. the rotary field frequency in 1/10 Hz (address 38). The complete list of the functions of the analogue output can be found in the appendix Analogue Output Offset This function allows you to shift the output voltage of the analogue output from the zero point Analogue Output Factor This function spreads the output voltage for a configurable factor Digital Output The digital output may be act upon the following functions: 0) Sum error message 1) Overvoltage 2 (at intermediate circuit) 2) Undervoltage (at intermediate circuit) 3) Error at power section 4) Set point = effective value 5) Rotary field right direction 6) Multi-function (frequency) 7) Over temperature Inverter 8) FU ready for operation 9) Motor turning (Null control) 10) PTC over temperature (Motor) 11) Multi-function (current) incl. current limit 12) Parameter set 1 or 2 active 13) DC brake active 14) Pulse output 8. Controller values 8.1 Working mode A selection can be made between the linear V/f characteristic (with the output voltage proportional to the rotating field frequency) and the square characteristic ( fan characteristic" with a squared output voltage increase in relation to the rotating field frequency). The reference point is the kink frequency. As a third option is the usage for Vector-control 8.2. Motor-nominal-current Input of the motor-nominal-current according to the rating plate of the connected DC-motor Motornennstrom Page 21 of 34

22 8.3. Motor Cos ϕ Input of the motor-nominal-current Cos. ϕ. according to the rating plate of the connected DCmotor 8.4. P section Setting of the P section of the PI controller 8.5. I section Setting of the I section of the PI controller Note: To ensure the correct function of the frequency Inverter, the motor nominal current, the power factor Cos ϕ and the motor nominal frequency must comply with the rating plate of the connected motor! 9. Settings 9.1. Switching frequency (clock) frequency Frequency at which the inverter of the power section is switched The following values are possible: 2, 4, 8, and 16 khz. Note: With the exception of 16 khz, the switching frequency will be noticed as a more or less loud secondary noise. The lower the switching frequency, the lower the switching power losses in the power circuit, the less the Inverter will warm up. The best motor characteristics are achieved from 2 khz upwards. The switching frequency of 16 khz should only be used in exceptional cases due to the increased heating of the Inverter. If this is used a sufficient ventilation of the inverter must be guaranteed and the power may have to be reduced. Page 22 of 34

23 9.2. Type of Set value Presetting the set value can alternatively be achieved by specifying the following parameter: A control voltage of 0-10V, 10-0V, V, V, 2-10V, 10-2V, 5-10V, 10-5V. An impressed current of 0-20mA, 20-0mA, 4-20mA, 20-4mA. By means of a PC via the RS-232 interface By means of an operating interface. Regardless of the setting of the preset value in the menu structure a setting must also be done with the DIP-switch on the I/O-module according to the following table.. Type of S2 S3 S4 S5 Set value S V On Off Off On Off V Off On Off On Off mA On Off On On Off mA On Off On On Off 0-100kHz Off Off Off Off On The preset value of the Inverter must be wired regardless of which preset value specification is selected. Page 23 of 34

24 9.3. Set value - Offset Specification of an offset e.g. to compensate for interferences Figures in the following two diagrams show how the original characteristic is influenced by a positive or negative offset. The setting of the set value offset follows in steps of 0,1 Hz. Bild Setpoint offset at 10-0V, 0-20mA setpoint Bild Setpoint offset at 10-0V, 20-0mA setpoint 9.4. Set value - Hysteresis The setpoint hysteresis serves to stabilize the predefined Rotating field frequency Page 24 of 34

25 9.5. Fade out frequency1, fade out frequency2 To suppress resonance effects in drive systems, a frequency range can be defined in which no stationary operation will be possible. The definition of a frequency range is made by means of programming a fade-out frequency ±2 Hz. A reference value specification within this range causes an offset of the actual value (refer to figure 9.5.1) above or below the limit frequencies.. Picture Rotating field frequency using the skip frequency Page 25 of 34

26 9.6. I²t current The I²t function is used to avoid a thermal overload of the motor, and/or to avoid a motor operation over an extended period of time in an unintended operating status (e.g. shaft blocking). For this purpose, the current value must remain above the normal operating status. A long period of time must be entered accordingly to avoid a shutdown of the inverter caused by short current peaks Regulation This menu item regulates the setting if the frequency Inverter runs through the I/O-module or the display 9.8. Factory settings The factory setting is activated by the display and causes an overwriting of every parameter with the preset factory values. 10. Operating values The "Operating values" menu item enables an operation status request with regard to the following visible messages: Operation value unit explanation Preset value Hz instantaneous preset value of the rotary field Frequency actual value Hz instantaneous value of the rotary field Frequency Conv. Temperature C instantaneous Inverter Temperature Current Amp instantaneous intermediate circuit- active current TC voltage V instantaneous intermediate circuit- active voltage Software version Inverter - version number of the software used for the inverter Software version display - version number of the software used for the display Page 26 of 34

27 11. Application notes Dynamic braking by means of a braking chopper The built-in braking chopper equipped with an external braking resistor enables dynamic braking of large masses and does not initiate a switch-off of the Inverter. When breaking a centrifugal mass at a relatively short running-down time (brake time), the mass inertia of the entire drive works as a generator torque. This braking operating is equivalent to an energy feedback of the drive resulting in a temporary circuit voltage increase up to the point where the excessive voltage switch-off is initiated. By routing this braking energy into a resistor, the switching off can be prevented. The braking chopper compares the temporary circuit voltage with a reference voltage, which has a voltage level below the over-voltage tripping level. When the reference voltage is exceeded a power transistor connects the braking resistor to the temporary circuit voltage. The resistor then converts the power generated by the motor into a heat loss. The braking power can be calculated as a function of the activation time (ED) of the braking resistors. Thus the breaking chopper can be individually adapted to the drive. Recommendations for the selection of brake resistors Vector 54 1-ph Resistor Peak Power I max Ω 1kW 2,5A Ω 1kW 2,5A Ω 1kW 2,5A Ω 1kW 2,5A Ω 1kW 2,5A Ω 1kW 2,5A Ω 1kW 2,5A The resistors used must be suited to the current and the peak power. The electric strength of the resistors must be 1000V. The necessary average braking power is calculated from the peak and the operating time of the chopper. Nom. power (W)= operating-time ED (s) * peak power (W) Cycle time (s) The practice showed that for most applications, resistors with a nominal continuous power of 60 Watts are sufficient. Page 27 of 34

28 11.2. Motor protection Despite a high-grade sine modulation, additional losses occur in the motor in powering standard 3-phase asynchronous motors. Even at nominal revolutions, these losses require a power reduction the extent on which essentially depends on the exploitation of the temperature limits of the motor. For drives of a square counter-torque (e.g. fans) and 50 Hz as maximum rotating field frequency, the imposed power reduction is usually around 0-10%. For drives of a constant counter-torque (compressors, conveyer belts, etc.), the power reduction has to be selected accordingly larger, depending on the range of the adjustment. To guarantee the safe operation of a motor in the adjustment range, the stationary load torque must lie below the continuous operating characteristic of the motor to guarantee a safe operation of a motor. During operation and starting, the drive will momentarily be in a position to submit or corresponding to the current limitation of the Inverter. The setting of the voltage increase (static Boost) essentially determines the maximum torque below 10 Hz. During a continuous operation, an excessive high boost setting for the lower rotating field frequency range (up to 15 Hz) can cause the motor to overheat. A comprehensive thermal protection of the self-cooling motor can be achieved by means of a temperature sensor (e.g. PTC thermistor or thermal time-delay switch) built into the motor. For revolutions above 120% of the nominal speed, the performance of the motor has to be checked.. Bild Operating characteristics of a frequency-controlled asynchronous machine Page 28 of 34

29 12. Technical data 12.1 Electrical data Type Vector Vector Vector Vector Vector Vector Output Output power of 0,2 KVA 0,25 KVA 0,35 KVA 0,85 KVA 1,3 KVA 1,6 KVA motor side apparatus Max. motor power 0,09 kw 0,12 kw 0,18 kw 0,37 kw 0,55 kw 0,75 kw Rated output current A A A A A 4,0 A Max. output voltage 3 x 230 V 3 x 230 V 3 x 230 V 3 x 230 V 3 x 230 V 3 x 230 V Output frequency Hz Hz Hz Hz Hz Hz Output choke Internal Internal Internal Internal Internal Internal Input Input voltage 230V±15 % 230V±15 % 230V±15 % 230V±15% 230V±15 % 230V ± 15% Mains side Mains filter Internal Internal Internal Internal Internal Internal Mains frequency 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz Fusing (no motor protection) A T A T A T A T A T 8 A T General Protection class IP 54 IP 54 IP 54 IP 54 IP 54 IP 54 Data Ambient temperature 0 40 C 0 40 C 0 40 C 0 40 C 0 40 C 0 40 C Ambient humidity % % % % rel. Not % rel. % rel. rel. Not rel. Not rel. Not dewing Not Not dewing dewing dewing dewing dewing Power loss Ca. W 25 Ca. W 30 Ca. W 35 Ca. W 35 Ca. W 40 Ca. 45 W Power reduction at 16 khz: Installation height above 3000m 1% per 100m Note the mains filter and RCD: The discharge currents caused by the mains filter can lead to tripping of residual current circuit breaker In case of failure the fault currents can block the triggering of the AC - or pulse-current sensitive FI circuit breaker. Therefore, the operation is only with a universal current sensitive FI - circuit breaker recommended. Page 29 of 34

30 12.2 Measurments D B C F 1 0 A E Measurements Vector 54 0,09 0,75 kw 280er case with 30er cover Vector 54 0,09 0,75 kw 250er case with 10er cover A 65 mm 65 mm B 290 mm 290 mm C 312 mm 312 mm D 90 mm 90 mm E 112 mm 112 mm F 5 mm 5 mm Page 30 of 34

31 13. Annex Parameter set 1 and 2 Characteristics Variables Factory settings Run.-up time right- cw 0, Hz/s 50Hz/s Run-down time right - cw 0, Hz/s 50Hz/s Run-up time left -ccw 0, Hz/s 50Hz/s Run-down time left ccw 0, Hz/s 50Hz/s Quick stop 0, Hz/s 50Hz/s Motor nominal frequency 0-400Hz 50Hz Min. frequency right- cw 0-400Hz 0Hz Max.frequency right- cw 0-400Hz 50Hz Min. frequency left - ccw 0-400Hz 0Hz Max. frequency left -ccw Hz -50Hz Frequency Digital-Output 0-400Hz 40Hz Static boost 0-30% 5% Dynamic boost 0-30% 6% Duration dynamic boost 0-25s 0s DC brake 0-20% 0% Duration DC brake 0-25s 0s Current limit 0 400A 5,4A Pan truncation 0, 1 0 Page 31 of 34

32 13.2. In -and Outputs Characteristics Variables Factory settings Digital input 1 Start right - cw Start clockwise (right) Digital input 2 Start Left - ccw Start counterclockwise (left) Digital input 3 Minimal frequency Minimal frequency Digital input 4 Parameter set changeover 1-2 Parameter set changeover 1-2 Analogue output See Analogue output Offset bit 0 Analogue output factor bit 1024 Digital output 1 Relay output Collective fault message Over voltage Under voltage Over current Set value = Actual value Rotary field right Multifunction (frequency) Over temperature FU stand by Motor turns (zero observation) Over temperature motor (PTC) Multifunction (current) Parameter 1 / 2 activated DC-brake activated Pulse output (corresponds with rotary field frequency, only at digital output) Collective fault message Regulation values Characteristics Variables Factory setting Working mode Linear V/f characteristic Linear V/f characteristic Square V/f characteristic Vector control Motor-nominal-current 0-20A 3,4A Motor Cos. ϕ 0-100% 80% P- share PI- controller I- share PI- controller Page 32 of 34

33 13.4. Settings Characteristics Variables Factory setting Clock frequency 2,4,6,8,16kHz 8kHz Set value assignment 0-10V 0-10V 10-0V V V 2-10V 10-2V 5-10V 10-5V 0-20mA 20-0mA 4-20mA 20-4mA Interface Display Set value offset 0-100Hz 0Hz Set value hysteresis Fade out frequency 0-400Hz 0Hz Field fade out frequency 0-200Hz 0Hz I²t- current 0-30A 20A Operation Inputs Display Inputs Analogue output The following shows the address and with it the connection to the function of the analogue output. Address Function 36 Set- speed 38 Actual- speed 40 Module temperature 41 Intermediate circuit voltage 57 Phase current U 58 Phase current V 59 Phase current W Page 33 of 34

34 13.6 Pin figuration Incremental encoder The following table shows the pin figuration of the incremental encoder. 21 K0 22 K0 none 23 K1 24 K1 none 25 K2 26 K2 none 27 GND 28 +5V (Output) 29 Screen Attention: Make sure that the motor is connected to the correct phase. I f the motor is connected correctly, the shaft will then complete at switched release a counter moment. At incorrect phasing and release the shaft can be rotated manually. Page 34 of 34

EC 45 flat with integrated electronics Document ID: en Operating Manual

EC 45 flat with integrated electronics Document ID: en Operating Manual EC 45 flat with integrated electronics Document ID: 919801en Operating Manual Edition June 2017 The EC 45 flat with integrated electronics is a brushless, speed-controlled 1-quadrant drive. It is available

More information

Excitation Systems THYRIPART. Compound-Excitation System for Synchronous Generators. Power Generation

Excitation Systems THYRIPART. Compound-Excitation System for Synchronous Generators. Power Generation Excitation Systems Compound-Excitation System for Synchronous Generators Power Generation Operating Characteristics Load dependent Short circuit supporting Low voltage gradient dv/dt Black start capability

More information

Technical manual. Microstep driver SMC11. NANOTEC ELECTRONIC GmbH & Co. KG Gewerbestraße 11 D Landsham near Munich, Germany

Technical manual. Microstep driver SMC11. NANOTEC ELECTRONIC GmbH & Co. KG Gewerbestraße 11 D Landsham near Munich, Germany Technical manual Microstep driver NANOTEC ELECTRONIC GmbH & Co. KG Gewerbestraße 11 D-85652 Landsham near Munich, Germany Tel. +49 (0)89-900 686-0 Fax +49 (0)89-900 686-50 info@nanotec.de Editorial Editorial

More information

EN 50178, IEC

EN 50178, IEC Type: DF51 322 1K5 Article No.: 289107 Sales text """Frequency inverter DF51(1,5 kw; 230V) Ordering information Rated voltage U e V Max. rated operational current I e A 7.1 Rated power for motors at 230

More information

EFC 3600 Frequency converter for higher energy efficiency and improved process control

EFC 3600 Frequency converter for higher energy efficiency and improved process control EFC 3600 Frequency converter for higher energy eiciency and improved process control 2 Valuable energy used responsibly Rising energy costs and increasing demands on the environmentally sound products

More information

[ 4 ] Using pulse train input (F01 = 12)

[ 4 ] Using pulse train input (F01 = 12) [ 4 ] Using pulse train input (F01 = 12) Selecting the pulse train input format (d59) A pulse train in the format selected by the function code d59 can give a frequency command to the inverter. Three types

More information

ATV12H018F1 variable speed drive ATV kW hp V - 1ph

ATV12H018F1 variable speed drive ATV kW hp V - 1ph Characteristics variable speed drive ATV12-0.18kW - 0.25hp - 100..120V - 1ph Main Range of product Altivar 12 Product or component type Product destination Product specific application Assembly style Component

More information

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink Characteristics variable speed drive ATV12-0.37kW - 0.55hp - 100..120V - 1ph - with heat sink Main Range of product Altivar 12 Product or component type Product destination Product specific application

More information

Excitation Systems RG3 - T4. Transistorized Excitation Systems for Synchronous Generators. Power Generation

Excitation Systems RG3 - T4. Transistorized Excitation Systems for Synchronous Generators. Power Generation Excitation Systems RG3 - T4 Transistorized Excitation Systems for Synchronous Generators Power Generation Operating Characteristics Reliability High availability Digital control facilities Very good control

More information

PD2. Manual. Plug & Drive PD2 -1-

PD2. Manual. Plug & Drive PD2 -1- Manual Plug & Drive PD2-1- 2002 Nanotec Electronic GmbH Gewerbestr. 11 85652 Landsham / Pliening Phone:(089) 900 686-0 Fax: (089) 900 686-50 Internet: www.nanotec.com All rights reserved. This documentation

More information

6.9 Jump frequency - Avoiding frequency resonance

6.9 Jump frequency - Avoiding frequency resonance E581595.9 Jump frequency - Avoiding frequency resonance : Jump frequency : Jumping width Function Resonance due to the natural frequency of the mechanical system can be avoided by jumping the resonant

More information

HPVFP High Performance Full Function Vector Frequency Inverter

HPVFP High Performance Full Function Vector Frequency Inverter Advanced User Manual HPVFP High Performance Full Function Vector Frequency Inverter HP VER 1.00 1. HPVFP Parameter Set Overview...3 1.1. About this section...3 1.2. Parameter Structure Overview...3 1.3.

More information

ATV12HU40M3 variable speed drive ATV12-4kW - 5hp V - 3ph - with heat sink

ATV12HU40M3 variable speed drive ATV12-4kW - 5hp V - 3ph - with heat sink Characteristics variable speed drive ATV12-4kW - 5hp - 200..240V - 3ph - with heat sink Main Range of product Altivar 12 Product or component type Product destination Product specific application Assembly

More information

Ref /b VARMECA 10 Variable speed motors and geared motors. Parameter-setting manual

Ref /b VARMECA 10 Variable speed motors and geared motors. Parameter-setting manual en L This manual is to be given to the end user L L PE 9 0 4 5 6 Parameter-setting manual NOTE LEROY-SOMER reserves the right to modify the characteristics of its products at any time in order to incorporate

More information

FUJI Inverter. Standard Specifications

FUJI Inverter. Standard Specifications FUJI Inverter o Standard Specifications Norminal applied motor The rated output of a general-purpose motor, stated in kw. That is used as a standard motor. Rated capacity The rating of an output capacity,

More information

Excitation Systems. Service Generators SIPOL. Transistorized Excitation Systems for Synchronous Generators. Power Generation

Excitation Systems. Service Generators SIPOL. Transistorized Excitation Systems for Synchronous Generators. Power Generation Excitation Systems Service Generators Transistorized Excitation Systems for Synchronous Generators Power Generation Operating Characteristics High availability Reliability Digital control facilities Very

More information

Index 2. G Gain settings 4 31 Glossary of terms A 2 Grommets 2 13

Index 2. G Gain settings 4 31 Glossary of terms A 2 Grommets 2 13 Index A A Group functions 3 9 AC reactors 5 3 Acceleration 1 15, 3 8 characteristic curves 3 26 second function 3 24 two-stage 4 19 Acceleration stop function 3 21 Access levels 3 5, 3 36, 4 25 Access

More information

Instruction manual for STA 1 sectional door operator

Instruction manual for STA 1 sectional door operator Instruction manual for STA 1 sectional door operator Sectional door operator STA 1 / Rev. 0.3 1 GB 1. Contents 3. General safety instructions 1. Contents 2 2. Key to symbols 2 3. General safety instructions

More information

VARAN Stepper Module VST 012

VARAN Stepper Module VST 012 VARAN Stepper Module VST 012 The VST 012 is a VARAN module designed for the control of a stepper motor up to a maximum 10 A RMS. The available operating modes are full step, half step and micro step. The

More information

Manual. Frequency Inverter. Series KFU 2- / 4- 0,55 to 3,0 kw 230 V KFU 2-0,55 to 132 kw 400 V KFU 4- KN E

Manual. Frequency Inverter. Series KFU 2- / 4- 0,55 to 3,0 kw 230 V KFU 2-0,55 to 132 kw 400 V KFU 4- KN E Manual Frequency Inverter Series KFU 2- / 4-0,55 to 3,0 kw 230 V KFU 2-0,55 to 132 kw 400 V KFU 4- KN 620.1108 E General Information about the Documentation The present documentation refers to the frequency

More information

ATV12HU22M2. Main. Range of product Altivar 12. Component name Quantity per set Set of 1. Built-in fan. Motor power hp Communication port protocol

ATV12HU22M2. Main. Range of product Altivar 12. Component name Quantity per set Set of 1. Built-in fan. Motor power hp Communication port protocol Product datasheet Characteristics ATV12HU22M2 Complementary Main Range of product Altivar 12 Product or component type Product destination Product specific application Assembly style Component name Variable

More information

KSC-10 Kelvin Speed controller 10A Rev.00 of 23/01/17

KSC-10 Kelvin Speed controller 10A Rev.00 of 23/01/17 Kelvin Speed controller 10A Tel : +34 93 422 70 33 1 The KSC-10 is a 1 Quadrant digital servo amplifier for direct current motor with permanent magnets of up to 600 Watts. It permits speed regulation in

More information

Instruction manual for STA 1 sectional door operator

Instruction manual for STA 1 sectional door operator Instruction manual for STA 1 sectional door operator GB Sectional door operator STA 1 / Rev. 0.0 1 1. Contents 3. General safety instructions 1. Contents 2 2. Key to symbols 2 3. General safety instructions

More information

Intelligent Drive Systems, Worldwide Services SK 700E F 3070 GB

Intelligent Drive Systems, Worldwide Services SK 700E F 3070 GB Intelligent Drive Systems, Worldwide Services SK 700E Universal application Modular High-Performance Inverter NORDAC SK 700E The NORDAC SK 700E frequency inverter is designed for the power range between

More information

Stepper Motor Power Stage with ServiceBus

Stepper Motor Power Stage with ServiceBus ZMX + Stepper Motor Power Stage with ServiceBus Manual 2111-A008 GB phytron ZMX + Stepper Motor Power Stage with ServiceBus 12/2008 Manual MA 2111-A008 GB Manual ZMX + 2008 All rights with: Phytron-Elektronik

More information

System configuration. Ratings 400 V Class three-phase 90 to 800 kw 690 V Class three-phase 90 to 1000 kw SX-D. Frequency inverters.

System configuration. Ratings 400 V Class three-phase 90 to 800 kw 690 V Class three-phase 90 to 1000 kw SX-D. Frequency inverters. ~ ~ SX High performance Vector Control IP54 full range. Compact design & Robustness Built-in Filter according to C3 Class Built-in Fusses (From 200 kw) Safety according EN13849-1 and EN62061 standards

More information

ZMX + Stepper Motor Power Stage with ServiceBus MANUAL 2111-A015 EN. Extreme. Precision. Positioning.

ZMX + Stepper Motor Power Stage with ServiceBus MANUAL 2111-A015 EN. Extreme. Precision. Positioning. ZMX + Stepper Motor Power Stage with ServiceBus MANUAL 2111-A015 EN Extreme. Precision. Positioning. phytron ZMX + Stepper Motor Power Stage with ServiceBus Hardware V5.0 TRANSLATION OF THE GERMAN ORIGINAL

More information

Invertek Optidrive E3 Frequency Inverter (IP20, 3ph output) Easy Start Guide

Invertek Optidrive E3 Frequency Inverter (IP20, 3ph output) Easy Start Guide Invertek Optidrive E3 Frequency Inverter (IP20, 3ph output) Easy Start Guide The Invertek Optidrive E3 Frequency Inverter range is available to order from inverterdrive.com This guide is intended to complement

More information

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink Characteristics variable speed drive ATV12-0.37kW - 0.55hp - 100..120V - 1ph - with heat sink Product availability : Stock - Normally stocked in distribution facility Price* : 191.76 USD Main Range of

More information

In the event of a failure, the inverter switches off and a fault code appears on the display.

In the event of a failure, the inverter switches off and a fault code appears on the display. Issue 03/05 Faults and Alarms 5 Faults and Alarms 5.1 Fault messages In the event of a failure, the inverter switches off and a fault code appears on the display. NOTE To reset the fault code, one of three

More information

Manual. MOVITRAC LTE-B/LTP-B Accessories Braking Resistors, Filters, Chokes, Shielding * _0515*

Manual. MOVITRAC LTE-B/LTP-B Accessories Braking Resistors, Filters, Chokes, Shielding * _0515* rive Technology \ rive Automation \ System Integration \ Services *21302197_0515* Manual MOVITRAC LTE-B/LTP-B Accessories Braking Resistors, Filters, Chokes, Shielding Edition 05/2015 21302197/EN SEW-EURORIVE

More information

maxon motor maxon motor control 1-Q-EC Amplifier DEC 24/1 Order numbers , , , ,

maxon motor maxon motor control 1-Q-EC Amplifier DEC 24/1 Order numbers , , , , maxon motor control 1-Q-EC Amplifier DEC 24/1 Order numbers 249630, 249631, 249632, 318305, 381510 September 2009 edition The DEC (Digital EC Controller) is a 1-quadrant amplifier for controlling electronically

More information

MINI-PS AC/24DC/1.3

MINI-PS AC/24DC/1.3 Power supply unit INTERFACE Data sheet 102894_en_03 1 Description PHOENIX CONTACT 2015-11-17 Features MINI POWER power supplies for MCR technology In measurement and control technology (MCR), modular electronics

More information

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W ADC5000 SERIES AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications 60W, 125W and 250 W Input voltage 230/115 VAC voltages 12, 24, 36 or 48 VDC Statistical MTBF >3 000

More information

The new Yaskawa Varispeed G7 Inverter

The new Yaskawa Varispeed G7 Inverter The new Yaskawa Varispeed G7 Inverter Unique new 3-level PWM flux vector Constant or variable torque applications control method 0.4 kw to 300 kw power range Exceptional low speed/high torque control Quick

More information

Brief description of KR 15 controllers

Brief description of KR 15 controllers Brief description of KR 15 controllers E N E R G Y R E C O V E R Y Page 2 Page 4 Page 5 Page 6 Page 9 1. Function of the controller 2. Terminal connections 3. Technical data 4. Initial operation 5. Manual

More information

Installation and Operational Instructions for ROBA -switch Type 017._00.2

Installation and Operational Instructions for ROBA -switch Type 017._00.2 OBA -switch Type 017._00.2 Guidelines on the Declaration of Conformity A conformity evaluation has been carried out for the product in terms of the EC Low Voltage Directive 2014/35/ EC and the EMC Directive

More information

Operating Instructions

Operating Instructions Operating Instructions Torque Transducer Type CD9515 Series Please read instruction carefully. Important Advice: The torque transducers of type CD9515 are suitable for applications in laboratories (for

More information

D SERIES EM16 IP 20 / NEMA 1 & IP 66 / NEMA 4X COMPACT VECTOR CONTROL DRIVE EM 16 COMPACT VECTOR CONTROL DRIVE

D SERIES EM16 IP 20 / NEMA 1 & IP 66 / NEMA 4X COMPACT VECTOR CONTROL DRIVE EM 16 COMPACT VECTOR CONTROL DRIVE D SERIES EM16 IP 20 / NEMA 1 & IP 66 / NEMA 4X COMPACT VECTOR CONTROL DRIVE EM 16 COMPACT VECTOR CONTROL DRIVE 1 2 SERIES 1 2 pag. 4 pag. 5 Applications Model identification 3 pag. 5 4 pag. 6 Capacity

More information

NX Series Inverters. HVAC Pocket Programming Guide

NX Series Inverters. HVAC Pocket Programming Guide NX Series Inverters HVAC Pocket Programming Guide HVAC Pocket Programming Guide HVAC Pocket Programming Guide / Contents This guide provides a single reference document for the user of NXL HVAC (product

More information

ESR. The Dynamic Solution. Main Characteristics. Applications. ESR Pollmeier GmbH

ESR. The Dynamic Solution. Main Characteristics. Applications. ESR Pollmeier GmbH Modular Multi-Axis Servo System for Any Type of Servo Motors Servo Power Modules for Direct Mains Connection Motion Control Modules for Coordinated Axis Motion MidiDrive C (3 400/480 V AC) Servo Power

More information

Power supply CP-E 24/2.5

Power supply CP-E 24/2.5 2CDC 271 015 F0t06 a OUTPUT L+, L : terminals output b DC OK: terminal signalling output c INPUT L, N, PE: terminals input d OUTPUT OK: green LED output voltage OK e OUTPUT Adjust: potentiometer adjustment

More information

Max. sp Min. spe Negativ speed s Synchro out speed refere selection Menu 13. g t x (-1) UMV 4301

Max. sp Min. spe Negativ speed s Synchro out speed refere selection Menu 13. g t x (-1) UMV 4301 Réf. 335-4.33 / a -.98.5 X-.39 Synchro output speed reference Menu 3 Max. sp Min. spe Negativ speed s.4 Synchro out speed refere selection Menu 3 Skip frequency Skip width.29.3.3 g t Run Run FWD REV 27

More information

Quick Reference Guide. DF5-... Frequency Inverters 02/02 AWB GB

Quick Reference Guide. DF5-... Frequency Inverters 02/02 AWB GB DF5-... Frequency Inverters 1 st published 22, edition 02/02 Moeller GmbH, 53105 Bonn Author: Holger Friedrich Editor: Michael Kämper Translator: Dominik Kreuzer All brand and product names are trademarks

More information

SX (400V) System configuration

SX (400V) System configuration ~ ~ SX (400V) High performance Vector Control IP54 full range. Compact design & Robustness Built-in Filter according to C3 Class Built-in Fusses (From 200 kw) Safety according EN13849-1 and EN62061 standards

More information

TAC ATV38, IP55. Variable Speed Drives for Asynchronous Motors. 3-phase. 380/460 V, Hz

TAC ATV38, IP55. Variable Speed Drives for Asynchronous Motors. 3-phase. 380/460 V, Hz TAC ATV8, IP55 Variable Speed Drives for Asynchronous Motors. -phase. 80/460 V, 50-60 Hz E-60-24 24 May 2004 ATV 8 IP55 drives are specifically designed for pump and fan applications powered by a three-phase

More information

D.C. BRUSHLESS MOTORS DRIVE. BLD07-IT Service Manual

D.C. BRUSHLESS MOTORS DRIVE. BLD07-IT Service Manual D.C. BRUSHLESS MOTORS DRIVE BLD07-IT Service Manual INTECNO s.r.l. Via Caduti di Sabbiuno n. 9/E 40011 Anzola Emilia (BO) - Italy tel. 051.19985350 fax 051.19985360 www.intecno-srl.com INDEX Description

More information

Installation and Operational Instructions for ROBA -multiswitch Type 019._00.2

Installation and Operational Instructions for ROBA -multiswitch Type 019._00.2 Guidelines on the Declaration of Conformity A conformity evaluation has been carried out for the product in terms of the EU Low Voltage Directive 2014/35/ EU and the Electromagnetic Compatibility (EMC)

More information

815-BR SERVO AMPLIFIER FOR BRUSH SERVOMOTORS

815-BR SERVO AMPLIFIER FOR BRUSH SERVOMOTORS 815-BR SERVO AMPLIFIER FOR BRUSH SERVOMOTORS USER GUIDE September 2004 Important Notice This document is subject to the following conditions and restrictions: This document contains proprietary information

More information

Orbital GFI Inverter Series

Orbital GFI Inverter Series Orbital GFI Inverter Series Datasheet Key Features One, split or three phases and up to 25 kva Superior efficiency of 95% CAN Bus control and DAQ Power quality and EMC compliance in accordance with European

More information

Operating Instructions

Operating Instructions 4XH35QB151210 Small General Frequency Converter Operating Instructions 220V 0.75KW 5.5KW 400V 0.75KW 15KW Please read the instruction carefully and understand the contents so that it can be installed and

More information

TECO F510 Inverter. Quick Start Guide. Step 1. Supply & Motor connection

TECO F510 Inverter. Quick Start Guide. Step 1. Supply & Motor connection Quick Start Guide TECO F510 Inverter This guide is to assist you in installing and running the inverter and verify that it is functioning correctly for it s main and basic features. For detailed information

More information

SX (690 V) System configuration

SX (690 V) System configuration SX (690 V) High performance Vector Control IP54 full range Compact design & Robustness Built-in Filter according to C3 Class Built-in Fuses (From 200 kw) Safety according EN13849-1 and EN62061 standards

More information

Inverter MICROMASTER 410

Inverter MICROMASTER 410 Inverter MICROMASTER 40 /2 Description /4 Circuit diagrams /6 Technical data /7 Selection and ordering data /8 Options /0 Dimension drawings Siemens DA 5.2 2005/2006 / MICROMASTER 40 Description Inverter

More information

GS1 Parameter Summary Detailed Parameter Listings...4 9

GS1 Parameter Summary Detailed Parameter Listings...4 9 CHAPTER AC DRIVE 4 PARAMETERS Contents of this Chapter... GS1 Parameter Summary...............................4 2 Detailed Parameter Listings..............................4 9 Motor Parameters.........................................4

More information

RAIL MOUNTED NETWORK METER TYPE N27D USER S MANUAL

RAIL MOUNTED NETWORK METER TYPE N27D USER S MANUAL RAIL MOUNTED NETWORK METER TYPE N27D USER S MANUAL 1 Contents 1. Application... 5 2. meter set... 6 3. BASIC REQUIREMENTS, OPERATIONAL SAFETy... 6 4. installation... 10 4.1. Mounting... 10 4.2. External

More information

Quick Reference Guide. DF5-... Frequency Inverters 02/02 AWB GB. For Immediate Delivery call KMParts.com at (866)

Quick Reference Guide. DF5-... Frequency Inverters 02/02 AWB GB. For Immediate Delivery call KMParts.com at (866) DF5-... Frequency Inverters 1 st published 22, edition 02/02 Moeller GmbH, 53105 Bonn Author: Holger Friedrich Editor: Michael Kämper Translator: Dominik Kreuzer All brand and product names are trademarks

More information

Power supply CP-E 24/20.0

Power supply CP-E 24/20.0 2CDC 271 027 F0008 a OUTPUT L+, L+, L, L-: terminals output b INPUT L, N, PE: terminals input c 13-14: terminals - signalling contact d OUTPUT OK: green LED output voltage OK e OUTPUT LOW: red LED output

More information

QUINT-PS/ 3AC/24DC/10

QUINT-PS/ 3AC/24DC/10 Primary-switched power supply with SFB technology, 3 AC, output current 10 A INTERFACE Data sheet 103131_en_01 1 Description PHOENIX CONTACT - 09/2009 Features QUINT POWER power supply units Maximum system

More information

RMO500 M I C R O O H M M E T E R

RMO500 M I C R O O H M M E T E R M I C R O O H M M E T E R Reference Manual IBEKO POWER AB Sweden 2 IBEKO POWER AB Manual Version:. MV.01 IBEKO POWER AB 2003 This Reference Manual is a publication of IBEKO POWER AB, 18 125 Lidingö, Sweden.

More information

LENORD. +BAUER... automates motion. GEL 2037 with heavy duty flange or tooth wheel adapter. Technical information Version General.

LENORD. +BAUER... automates motion. GEL 2037 with heavy duty flange or tooth wheel adapter. Technical information Version General. GEL 2037 with heavy duty flange or tooth wheel adapter LENORD +BAUER... automates motion. Technical information Version 2014-07 General Multiturn absolute rotary encoders with a resolution of up to 25

More information

External brake resistor AX2090-BW5x

External brake resistor AX2090-BW5x Documentation External brake resistor AX2090-BW5x Accessories for Beckhoff servo drive AX5000 Version: Date: 1.3 2018-03-14 Table of content Table of content 1 Foreword... 5 1.1 Notes on the documentation...

More information

Computer-14d - xx - 144a

Computer-14d - xx - 144a POWER FACTOR REGULATOR Computer-14d - xx - 144a INSTRUCTION MANUAL ( M 981 602 / 98B ) (c) CIRCUTOR S.A. -------- POWER FACTOR REGULATOR COMPUTER- 14d --------- Page 2 1.- POWER FACTOR REGULATORS COMPUTER-14d-144a

More information

1800 Series Attachable Loop-Powered Digital Indicators Operating Manual

1800 Series Attachable Loop-Powered Digital Indicators Operating Manual 1800 Series Attachable Loop-Powered Digital Indicators Operating Manual 1010 West Bagley Road, Berea, Ohio 44017 P 440.243.0888 F 440.243.3472 www.noshok.com Index 1 INTRODUCTION 3 2 SAFETY REGULATIONS

More information

smd frequency inverter

smd frequency inverter S03B These Instructions contain important technical data and describe installation, operation and commissioning of the smd frequency inverter. are only valid for smd frequency inverters with software rev

More information

References 1 for asynchronous motors 1

References 1 for asynchronous motors 1 References 1 DF56902 DF5690 DF56901 ATS 01N10FT ATS 01N212QN ATS 01N20LY for 0.7 to kw motors power Nominal current Reference (2) Weight Single phase -phase 20 V 210 V 20 V 20 V 400 V 460 V kw HP kw HP

More information

SX (400 V) System configuration

SX (400 V) System configuration ~ ~ SX (400 V) High performance Vector Control IP54 full range. Compact design & Robustness Built-in Filter according to C3 Class Built-in Fuses (From 200 kw) Safety according EN13849-1 and EN62061 standards

More information

A Subsidiary of Regal-Beloit Corporation. AC Inverter Terminology

A Subsidiary of Regal-Beloit Corporation. AC Inverter Terminology AP200-9/01 Acceleration The rate of change in velocity as a function of time. Acceleration usually refers to increasing velocity and deceleration to decreasing velocity. Acceleration Boost During acceleration,

More information

Industrial motor controller for brushed DC motors 24 VDC

Industrial motor controller for brushed DC motors 24 VDC Industrial motor controller for brushed DC motors 24 VDC Design for output currents up to 5 A Control with the following functions: - reversal of direction of rotation - open-loop speed control (external)

More information

maxon motor maxon motor control 4-Q-EC Servoamplifier DES 70/10 Order number

maxon motor maxon motor control 4-Q-EC Servoamplifier DES 70/10 Order number control 4-Q-EC Servoamplifier DES 70/10 Order number 228597 April 2006 Edition The DES (Digital EC Servoamplifier) is a very efficient digital servoamplifier with sinusoidal current commutation for perfectly

More information

TA8435H/HQ TA8435H/HQ PWM CHOPPER-TYPE BIPOLAR STEPPING MOTOR DRIVER. FEATURES TOSHIBA BIPOLAR LINEAR INTEGRATED CIRCUIT SILICON MONOLITHIC

TA8435H/HQ TA8435H/HQ PWM CHOPPER-TYPE BIPOLAR STEPPING MOTOR DRIVER. FEATURES TOSHIBA BIPOLAR LINEAR INTEGRATED CIRCUIT SILICON MONOLITHIC TOSHIBA BIPOLAR LINEAR INTEGRATED CIRCUIT SILICON MONOLITHIC TA8435H/HQ TA8435H/HQ PWM CHOPPER-TYPE BIPOLAR STEPPING MOTOR DRIVER. The TA8435H/HQ is a PWM chopper-type sinusoidal micro-step bipolar stepping

More information

ROLL TO ROLL FUNCTION MANUAL FR-A (0.4K)-04750(90K)-R2R FR-A (0.4K)-06830(280K)-R2R FR-A (315K)-12120(500K)-R2R

ROLL TO ROLL FUNCTION MANUAL FR-A (0.4K)-04750(90K)-R2R FR-A (0.4K)-06830(280K)-R2R FR-A (315K)-12120(500K)-R2R INVERTER ROLL TO ROLL FUNCTION MANUAL FR-A820-00046(0.4K)-04750(90K)-R2R FR-A840-00023(0.4K)-06830(280K)-R2R FR-A842-07700(315K)-12120(500K)-R2R Roll to Roll Function The FR-A800-R2R inverter has dedicated

More information

Technical Documentation

Technical Documentation Technical Documentation PROAM-21 Power amplifier for directional valves Grundlage der Funktionsbeschreibung und zur Prüfung der Module (keine Produktdokumentation). AMCA HYDRAULIC FLUID POWER B.V. P.O.BOX

More information

OPERATING INSTRUCTIONS. NORDAC compact Frequency Inverter

OPERATING INSTRUCTIONS. NORDAC compact Frequency Inverter OPERATING INSTRUCTIONS NORDAC compact Frequency Inverter SK 250/1 FNC... SK 2200/1 FNC SK 250/2 NC... SK 22000/2 NC SK 1500/3 NC... SK 37000/3 NC SK 7500/4 NC... SK 37000/4 NC BU 3300/96 GB October 1996

More information

This data sheet is only valid in association with the IL SYS INST UM E user manual.

This data sheet is only valid in association with the IL SYS INST UM E user manual. Inline counter terminal, version for extreme conditions, 1 counter input, 1 control input, 1 output, 24 V DC, 500 ma Data sheet 106148_en_03 PHOENIX CONTACT 2015-11-04 1 Description The terminal is designed

More information

VFD - D700 Series Specifications. The latest low-cost variable speed control solution for centrifugal pumps.

VFD - D700 Series Specifications. The latest low-cost variable speed control solution for centrifugal pumps. VFD - D700 Series Specifications The latest low-cost variable speed control solution for centrifugal pumps. Built-in PID Control to maintain pressure, flow, measured value, and much more 125% overload

More information

Ametek, Inc. Rotron Technical Products Division. 100 East Erie St., Suite 200 Kent, Ohio User's Guide. Number Revision F

Ametek, Inc. Rotron Technical Products Division. 100 East Erie St., Suite 200 Kent, Ohio User's Guide. Number Revision F Ametek, Inc. Rotron Technical Products Division 100 East Erie St., Suite 200 Kent, Ohio 44240 User's 120 Volt, 800 Watt and 240 Volt, 1200 Watt Brushless Motor Drive Electronics 5.7" (145 mm) and 7.2"

More information

ACTIVE. Application manual - Crane drives Brake control and load detection Configurations 160, 260 and 460

ACTIVE. Application manual - Crane drives Brake control and load detection Configurations 160, 260 and 460 ACTIVE Application manual - Crane drives Brake control and load detection Configurations 160, 260 and 460 General points on the documentation The present documentation supplements the manual for hoisting

More information

Siemens OPERATING INSTRUCTIONS FOR MICROMASTER ECO & MIDIMASTER ECO V1.19. Variable speed drive for Fans and Pumps (HVAC) from 0,75kW to 315kW

Siemens OPERATING INSTRUCTIONS FOR MICROMASTER ECO & MIDIMASTER ECO V1.19. Variable speed drive for Fans and Pumps (HVAC) from 0,75kW to 315kW Siemens OPERATING INSTRUCTIONS FOR MICROMASTER ECO & MIDIMASTER ECO V1.19 Variable speed drive for Fans and Pumps (HVAC) from 0,75kW to 315kW Siemens G85139-H1751-U555-D1 0 of 23 CONTENS SAFETY AND CE

More information

Parallel. Parallel. data transmission. Technical Information TR - ECE - TI - GB /05/2016

Parallel. Parallel. data transmission. Technical Information TR - ECE - TI - GB /05/2016 TR - ECE - TI - GB - 0054-01 04/05/2016 Parallel Parallel data transmission Technical Information TR-Electronic GmbH D-78647 Trossingen Eglishalde 6 Tel.: (0049) 07425/228-0 Fax: (0049) 07425/228-33 email:

More information

Type CP-S, CP-C & CP-A Switch mode

Type CP-S, CP-C & CP-A Switch mode Switch mode power CP-S, CP-C & CP-A Switch mode Characteristics CP-S and CP-C range Output current 5 A, 10 A and 20 A Integrated power reserve of up to 50 % 5 A and 10 A devices with pluggable connecting

More information

TOSHIBA BIPOLAR LINEAR INTEGRATED CIRCUIT MULTI-CHIP TA84002F/FG PWM CHOPPER-TYPE 2 PHASE BIPOLAR STEPPING MOTOR DRIVER

TOSHIBA BIPOLAR LINEAR INTEGRATED CIRCUIT MULTI-CHIP TA84002F/FG PWM CHOPPER-TYPE 2 PHASE BIPOLAR STEPPING MOTOR DRIVER TOSHIBA BIPOLAR LINEAR INTEGRATED CIRCUIT MULTI-CHIP TA84002F/FG PWM CHOPPER-TYPE 2 PHASE BIPOLAR STEPPING MOTOR DRIVER The TA84002F/FG is designed to drive both windings of a two-phase bipolar stepping

More information

SCA-SS (70V, 10A)

SCA-SS (70V, 10A) Manual SCA-SS-70-10 V 2.3 01/04 page 1 SCA-SS-70-10 (70V, 10A) The servo-amplifier SCA-SS-70-10 is a powerful PWM-module for brushed DC motors with an output range up to 700 Watt. Six operation modes are

More information

1525-BRS INFORMATION MANUAL SERV O D YN A M ICS. D y n ad r iv e Ave Crocker Suite 10 Valencia, CA

1525-BRS INFORMATION MANUAL SERV O D YN A M ICS. D y n ad r iv e Ave Crocker Suite 10 Valencia, CA 28231 Ave Crocker Suite 10 Valencia, CA 91355 818-700-8600 Servodynamics.com INFORMATION MANUAL 1525-BRS SERV O D YN A M ICS U SA www.servodynamics.com D y n ad r iv e Bru sh INDEX Page INTRODUCTION 2

More information

Power supply CP-D 24/4.2 Primary switch mode power supply

Power supply CP-D 24/4.2 Primary switch mode power supply Data sheet Power supply CP-D 24/4.2 Primary switch mode power supply The CP-D range of modular power supply units in MDRC design (modular DIN rail components) is ideally suited for installation in distribution

More information

MICROMASTER. Applications Handbook. User Documentation

MICROMASTER. Applications Handbook. User Documentation MICROMASTER Applications Handbook User Documentation Issue A1 IMPORTANT NOTICE Not all inverters currently have UL approval. UL listing can be determined by examining the inverter's Rating Label. For UL

More information

MICROMASTER. Operating Instructions

MICROMASTER. Operating Instructions MICROMASTER Operating Instructions Contents Safety Instructions...2 1. OVERVIEW...3 2. INSTALLATION...4 3. FRONT PANEL CONTROLS & BASIC OPERATION...14 4. OPERATING MODES...17 5. SYSTEM PARAMETERS...20

More information

Power supply CP-T 48/20.0 Primary switch mode power supply

Power supply CP-T 48/20.0 Primary switch mode power supply Data sheet Power supply CP-T 48/20.0 Primary switch mode power supply The CP-T range of three-phase power supply units is the youngest member of ABB s power supply family. In terms of design and functionality,

More information

VF-nC1 Adjustable Speed Drive Engineering Specification

VF-nC1 Adjustable Speed Drive Engineering Specification PART 1 - GENERAL 1.0 Scope This specification shall cover Toshiba VF-nC1 AC Variable Frequency Drives, 6 pulse for 100V single-phase 0.1 to 0.75kW, 200V single-phase 0.2 to 2.2kW and 200V threephase 0.1

More information

ATV212HU22M3X variable speed drive ATV kW - 3hp - 240V - 3ph - wo EMC - IP21

ATV212HU22M3X variable speed drive ATV kW - 3hp - 240V - 3ph - wo EMC - IP21 Product data sheet Characteristics ATV212HU22M3X variable speed drive ATV212-2.2kW - 3hp - 240V - 3ph - wo EMC - IP21 Product availability : Stock - Normally stocked in distribution facility Price* : 618.00

More information

Power supply CP-T 24/20.0 Primary switch mode power supply

Power supply CP-T 24/20.0 Primary switch mode power supply Data sheet Power supply CP-T 24/20.0 Primary switch mode power supply The CP-T range of three-phase power supply units is the youngest member of ABB s power supply family. In terms of design and functionality,

More information

INSTALLATION AND OPERATION MANUAL IODA INPUT/OUTPUT MULTI-FUNCTION BOARD (Part No. 9668)

INSTALLATION AND OPERATION MANUAL IODA INPUT/OUTPUT MULTI-FUNCTION BOARD (Part No. 9668) INSTALLATION AND OPERATION MANUAL IODA INPUT/OUTPUT MULTI-FUNCTION BOARD (Part No. 9668) Use with Models KBDA-24D, 27D, 29, 45, 48 See Safety Warning, on page 4. RoHS The information contained in this

More information

PHOENIX CONTACT

PHOENIX CONTACT Electronic circuit breaker CLIPLINE Data sheet 102898_en_03 PHOENIX CONTACT 2010-12-17 1 Description The electronic circuit breaker can be used in applications that cover all aspects of the switched-mode

More information

Thyristor power controller B DI1002 V1.0 Manual/Operating instructions

Thyristor power controller B DI1002 V1.0 Manual/Operating instructions 1 B DI1002 V1.0 Manual/Operating instructions 2 1 Introduction Before you put the thyristor controller into operation, please read these operating instructions. Keep them in safe place accessible for all

More information

PROXIMITY SENSOR TERMINOLOGY

PROXIMITY SENSOR TERMINOLOGY Never use this desk reference for installation or operation of equipment. Refer to manual for installation and operation instructions. The following descriptions refer to the European standard EN 60947-5-2.

More information

QUINT-PS/ 1AC/24DC/20

QUINT-PS/ 1AC/24DC/20 Primary-switched power supply with SFB technology, 1 AC, output current 20 A INTERFACE Data sheet 103129_en_04 1 Description PHOENIX CONTACT - 02/2010 Features QUINT POWER power supply units Maximum system

More information

QUINT-PS/ 3AC/24DC/40

QUINT-PS/ 3AC/24DC/40 Primary-switched power supply unit with SFB technology, 3 AC, output current 40 A INTERFACE Data sheet 103133_en_00 1 Description PHOENIX CONTACT - 07/2009 Features QUINT POWER power supply units Maximum

More information

Lexium integrated drives

Lexium integrated drives Description ILp for CANopen, PROFIBUS DP, RS ILA with AC synchronous servo motor Description ILA comprise control electronics with a fieldbus interface for CANopen DS, PROFIBUS DP or RS and an AC synchronous

More information

Electronically Commutated (EC) Motor Control with Solo, Select and Sync PWM Boards

Electronically Commutated (EC) Motor Control with Solo, Select and Sync PWM Boards Electronically Commutated (EC) Motor Control with Solo, Select and Sync PWM Boards The Solo, Select and Sync PWM boards provide a pulse-width modulated (PWM) signal to the EC motor to control fan speed.

More information