11/4/2013. NERC RS Meeting October 28, 2013 Sullivan s Island, SC. Troy Blalock SERC NERC RS Representative

Size: px
Start display at page:

Download "11/4/2013. NERC RS Meeting October 28, 2013 Sullivan s Island, SC. Troy Blalock SERC NERC RS Representative"

Transcription

1 NERC RS Meeting October 28, 2013 Sullivan s Island, SC Troy Blalock SERC NERC RS Representative 2 1

2 Preface: Members of the NERC Resource Subcommittee, whom are representatives of the Eastern Interconnection, are working with Balancing Authorities within the same interconnection on a voluntary basis to support a pilot program in an effort to improve frequency response. Frequency Response is defined as automatic and sustained change in the power consumption or output of a device such as generator that occurs within 5-20 seconds of and is in a direction to oppose a change in the Interconnection Frequency. 3 Frequency response as so defined has been historically declining except for more recent years in the Eastern Interconnection. Typically exhibits the lazy L of primary frequency response withdrawal. 4 2

3 The current initiative focus is on the existing generator fleet with respect to : 1) completeness and accuracy of the data provided in the 2010 NERC Generator Survey, 2) to improve their frequency response capabilities and; 3) for Balancing Authorities and/ or Reliability Coordinators to installs tool(s) to monitor individual generator performance within their authority of control and communicate performance results to the individual generators. 5 Eastern Interconnection: Deadband Setting Given? Yes (2531, 57.21%) No (1893, 42.79%) 6 3

4 % Eastern Interconnection: Deadband Settings er of Units within Range Numbe % % % % 25.99% % % % % % 0 Deadband Setting [mhz] 36 mhz NERC Policy One 7 For all individual generators Eastern Interconnection Phase 2 (including nuclear) 400 MW or larger, July 2014 Survey BAs will request generators to Generation November 2014 provide a completed generator Changes (.036 and survey of governor settings and Proportional) related data by January 1, For all individual generators(excluding nuclear and combined cycles steam turbines) 400 MW or larger, BA s will request generators to modify all dead bands greater than 36 mhz to at most 36 mhz and install proportional response by June 1, If generator advises it is unable to meet timing, then generator should provide reasonable time to complete. Phase 1 Jan 2014 Survey June 2014 Changes (.036 and Proportional) Total Number of Generators (4508) Greater than 400 (309, 6.83%) Between MW (1540, 34.16%) Nuclear (88, 1.95%) 8 4

5 For all individual generators 100 MW to 400 MW, BA s willrequest generators to provide a completed generator survey of current governor settings and related data by July 1, Phase 2 July 2014 Survey November 2014 Changes (.036 and Proportional) Eastern Interconnection Generation For all individual generators 100 MW to 400 MW, BA s will request generators to modify all dead bands greater than 36 mhz to at most 36 mhz and install proportional response by November 1, If generator advises it is unable to meet timing, then generator should provide reasonable time to complete. Phase 1 Jan 2014 Survey June 2014 Changes (.036 and Proportional) Total Number of Generators (4508) Greater than 400 (309, 6.83%) Between MW (1540, 34.16%) Nuclear (88, 1.95%) 9 Balancing Authority send Generator Survey Form to their Generators Balancing Authorities review data from Generators for accuracy and agreement Send completed survey form with Contact info to NERC Coordinating Effort with Modeling Working Groups 10 5

6 Troy Blalock, P.E. South Carolina Electric & Gas Company Transmission Operations Center 601 Old Taylor Rd. Cayce, SC Mail Code J42, Cayce, SC Office #: Cell #: Fax #:

7 Statistical Analysis of Variable Generation Matthew Varghese Resource Subcommittee Meeting October

8 Objectives Relating Variable Generation to CPS1 & CPS10 Metric Frequency Events from ERCOT & CPS1 metric Acknowledgement: Sydney Niemeyer minute Wind data for 1 month & CPS10 metric Acknowledgement: Terry Bilke 2 RELIABILITY ACCOUNTABILITY

9 1. Frequency Event Data & CPS1 CPS1 metric calculated for Event Data 262 Frequency Events in ERCOT from 2008 to 2013 Calculations of CPS1 by Sydney Niemeyer. Sample ERCOT Data Format for the Frequency Event File # UTC (t-0) B-A CPS1 MW Loss FR MW/0.1 Hz System LOAD MW Total Wind MW % of Wind/Total Generation 1 11/01/2008 6:32: , /06/ :20: , /17/ :01: , /21/2008 2:32: , /02/2008 5:20: , , /14/2008 7:23: , /16/ :45: , , /28/ :47: , , /16/ :13: , /25/ :19: , , RELIABILITY ACCOUNTABILITY

10 1. ERCOT Single BA Interconnection DEFINITIONS of CPS1 for a single BA Interconnection: CPS1 = 100* [2 - ((Frequency Error) 2 /( 1) 2 )] 1 = Hz for ERCOT CPS1 < 200 % if Frequency Error is non zero CPS1 is 200 % if Frequency Error is zero 4 RELIABILITY ACCOUNTABILITY

11 1. Explanation of Results Definition of p value With (1-p)% confidence, null hypothesis H0 is rejected For linear regression, the null hypothesis H0 is: The slope of the linear regression is zero CPS1 = 24.5*Wind/Total Gen The p value is With ( ) = 94.74% confidence, H0 is rejected CPS1 = *Total Wind MW The p value is With ( ) = 89.87% confidence, H0 is rejected 5 RELIABILITY ACCOUNTABILITY

12 1. Wind & the Up Direction Margin Wind typically operates at maximum output. With no margin in the up direction, Interconnections get benefit only for high frequency excursions from these generators. Can the CPS1 VG metric detect this lack of margin? Yes. The CPS1 VG metric is influenced by the efficiency of wind curtailment. If wind is ramping up as frequency declines, this results in good CPS1. If wind is curtailed as frequency increases, this also results in good CPS1. 6 RELIABILITY ACCOUNTABILITY

13 2. Multiple BA Interconnection Proposal - Calculating CPS10 of a fictitious wind BA with 10 Minute Data One approach is to determine the support of the wind in terms of CPS10. The aggregate wind is treated as a Balancing Authority (BA). The size of the BA is the MW value at t+n-1. If generation was 2000MW at t+n-1, think of it as a 2000MW BA. Its bias obligation then would be -20MW/0.1Hz. Wind BA s ACE as the difference between MW value at t+n and MW at t+n-1. If wind ramped up 20MW, it would look like an ACE of 20 MW. It should be straightforward to calculate CPS10 for the wind BA. If wind is ramping up as frequency declines, this results in good CPS10. If it provides droop with the decline, even better CPS10. 7 RELIABILITY ACCOUNTABILITY

14 2. Wind BA CPS10 & BAAL violations If 50 MW less, then assume the wind had an ACE of -50MW. Calculate a CPS10 for the average frequency for 10 minute blocks. BAAL triggers roughly at about -500% CPS10. BAAL is triggered in a 10 minute period, the wind is outside limits. BAAL violation is approximated by non-recovery of CPS10. If CPS10 does not recover to normal CPS within two subsequent periods. The wind dragged and didn't start move in the right direction for 30 minutes. 8 RELIABILITY ACCOUNTABILITY

15 2. Scatterplot of CPS10 BA vs. Wind by Terry Bilke 9 RELIABILITY ACCOUNTABILITY

16 2. CPS10 of BA vs. WIND by Terry Bilke Regression Analysis: CPS10 of BA versus CPS10 of WIND The regression equation is CPS10 of BA = CPS10 of WIND Predictor Coef SE Coef T P Constant CPS10 of WIND S = R-Sq = 2.2% R-Sq(adj) = 2.1% 10 RELIABILITY ACCOUNTABILITY

17 2. Summary of CPS10 for BA by Terry Bilke 11 RELIABILITY ACCOUNTABILITY

18 2. Summary of CPS10 for WIND BA by Terry Bilke 12 RELIABILITY ACCOUNTABILITY

19 2. Conclusions about WIND as a BA There is a small correlation between the BA s CPS10 and the wind. 41 periods over this month where CPS10 of the wind exceeded BAAL limits. So if the wind were a BA there were 41 violations for more than 30 minutes. It didn t trigger a problem for the BA. Future studies should consider a smaller BA that had a good share of wind. Absent some additional controls or regulation service, a wind farm would have a difficult time being a Balancing Authority. 13 RELIABILITY ACCOUNTABILITY

20 Background Material

21 1. CPS1 vs. Total Wind MW 15 RELIABILITY ACCOUNTABILITY

22 1. CPS1 vs. Total Wind MW Linear Regression Equation CPS1 = *Total Wind MW RELIABILITY ACCOUNTABILITY

23 1. CPS1 vs. % Wind/Total Gen 17 RELIABILITY ACCOUNTABILITY

24 1. CPS1 vs. % Wind/Total Gen Linear Regression Equation CPS1 = 24.5*Wind/Total Gen RELIABILITY ACCOUNTABILITY

25 Consortium for Electric Reliability Technology Solutions NERC Applications Status NERC Applications Status for Resources Subcommittee Gil Tam, Frank Carrera & Song Xue Sullivan s Island, SC October 29-30, 2013 Agenda Update on EPG/CERTS Support to NERC RS Effective November 1, 2013, Mr. Frank Carrera and Ms. Song Xue will assume responsibilities bl to provide support to NERC RS as follows: EPG day to day support for all NERC/CERTS applications will be coordinated by Pankaj Mishra under the supervision of Frank Carrera Song Xue will provide support on all on going grid performance analysis and reporting Monthly Frequency Response Event Reports Quarterly Interconnection Frequency Control Performance Reports Monthly BAAL Reports NERC Application Status t Summary Inadvertent Web based Application Status HQ Frequency Response Event Detection Threshold Analysis and Recommendation Page 1 1

26 NERC Applications Status Summary Application Resource Adequacy (ACE Frequency) Inadvertent Area Interchange Error (AIE) NERC Applications Status and Authorized Users (Many companies have several authorized users) Release 7.0 Current Production version 170 authorized users. Release 8.0 with updated Maps will be released 11/1/2013 Release 3.5 Current Production version 286 authorized users - New data entry website was published in July FRCC data through Oct have been uploaded in application data base. - Release 4.0 with updated Maps will be released 11/1/2013 Release 1.0 Current production version 122 authorized users Intelligent Alarms Frequency Monitoring and Analysis (FMA) Automated Reliability Reports (ARR) Release 1.0 Current production version 131 authorized users Release 2.5 Current production version 121 authorized users Release 1.0 Current production version 60 authorized users Monthly reports through September 2013 and Seasonal reports through Summer 2013 have been posted in ARR website. Page 2 CERTS/NERC Application Data Base Update All applications have been updated per the NERC CPS2 Bounds Report published on September 16, 2013 The maps in the Inadvertent and Resource Adequacy applications have been updated and will be released on 11/1/2013 EPG is committed to maintaining the accuracy of the Balancing Authority information within the applications twice a year in accordance with the published NERC CPS2 Bounds Report Page 3 2

27 New Web based Inadvertent Application Implementation EPG and NERC IT staff have completed the Web based Inadvertent Application Upgraded to new operating system (Windows 7 with 64 bits) User Guide is complete and posted on: Tabitha Hernandez completed Field Testing and identified several enhancements EPG released application to all authorized users on July 19, 2013 Users can continue to use old application Users of existing Inadvertent application can use same NERC assigned username and password to access new Web based application at following link: EPG has completed many of the recommended enhancements for the Inadvertent Website (details on next slide) User Training EPG can provide a one hour training session via WebEx, if necessary Page 4 Web based Inadvertent Application Enhancements Completed Inadvertent Worksheet: AddedTotals to Worksheet for Data EntryUsers Refrained the Blue Data entry screen from displaying by default Adding/Removing Interchange partners is reflected in the current month Inadvertent Reports: Removed Duplicate Month/Year line items Added a Pop Up with details on Reliability Region Status (Lock Status, Number of BA s Submitted) Added link within Pop Up to navigate directly to selected Region for detailed reports Unlocked drop down items to quickly change report criteria Page 5 3

28 Inadvertent Application Questions for NERC RS Should the Pseudo Balancing Authority be Removed? Was created by the Inadvertent Working Group circa 2008 as a crutch to balance the Eastern Interconnection on a monthly basis The addition of FRCC BA data negates the need for the Pseudo Balancing Authority Should all users be allowed to view Monthly Interconnection Reports? (A request from some BAs) Currently only Administrators have access to any reports in the system. Users have asked for reporting tools that span are above their privileges. Since the new Web based Inadvertent application is operational, should the old Inadvertent application be decommissioned? More users are having problem loading/using the old application. The Web based Inadvertent application has more functionalities than the old application except for the map. Eliminate duplicate application. New features can be incorporated in the new application. July 2013 Page 6 HQ Frequency Event Detection Threshold Analysis The current frequency delta threshold for HQ is 300 mhz The number of events detected have increased substantially over the last several months. 25 events were detected in July for a year to date total of 88 events CERTS/EPG analyzed the results of the last 9 months events detected to determine if the current frequency delta threshold of 300 mhz should be revised (see following slide) Page 7 4

29 Month Jan Feb Mar April May June July August September Total: HQ Frequency Event Detection Threshold Analysis Frequency Delta 300 mhz 350 mhz 400 mhz Gen - 3; Load - 1 Gen - 2; Load - 0 Gen - 1; Load Gen - 2; Load - 2 Gen - 2; Load - 0 Gen - 1; Load Gen - 1; Load - 1 Gen - 0; Load - 1 Gen - 0; Load Gen - 2; Load - 3 Gen - 2; Load - 1 Gen - 2; Load Gen - 4; Load - 6 Gen - 4; Load - 4 Gen - 3; Load Gen - 9; Load - 6 Gen - 9; Load - 3 Gen - 8; Load Gen - 15; Load - 10 Gen - 10; Load - 6 Gen - 9; Load Gen - 8; Load - 9 Gen - 3; Load - 5 Gen - 2; Load Gen - 2; Load - 4 Gen - 2; Load - 3 Gen - 2; Load Gen - 46; Load - 42 Gen - 34; Load - 23 Gen - 28; Load - 11 Page 8 HQ Frequency Event Detection Threshold Recommendation Based on results of analysis, CERTS/EPG recommends that the frequency event detection threshold for HQ be revised as follows: 400 mhz for loss of Generation events 350 mhz for loss of Load events Implementation of these revised thresholds will keep the number of events detected manageable and still provide sufficient number (2 to 3) of candidate events per month for BAL 003 The RS decided to revise the HQ detection threshold to 350 mhz for loss of Generation and for loss of Load events. Page 9 5

30 Q & A Page 10 EPG Personnel Contact Information NERC Application Support: Pankaj Mishra Mishra@electricpowergroup.com i (626) Ext. 136 Frank Carrera Carrera@electricpowergroup.com (626) Ext. 131 Grid Performance Analysis & Reporting: Song Xue Xue@electricpowergroup.com (626) Ext. 135 Page 11 6

31 Consortium for Electric Reliability Technology Solutions NERC Grid Performance Metrics Analysis Frequency Control & Time Error Correction Performance Report 3rd Quarter 2013 Song Xue & Gil Tam Sullivan s Island, SC October 29-30, 2013 Page 0 Interconnection Frequency Control Performance Reports Reports for all four interconnections through September 2013 were prepared p and submitted to the respective interconnection representatives and Larry Kezele for review Per RS request, EPG has summarized each performance metric for all four interconnections on a single slide to facilitate review The Time Error Correction report summary for WECC through September 2013 is included in this report If ERCOT, EI and HQ can provide time error correction dt data in spreadsheet format (i.e., date, start & stop time), EPG can produce similar time error correction reports EPG will continue to produce these reports for future RS quarterly meetings Page 1 1

32 Monthly CPS1, Page 2 Monthly CPS2, Page 3 2

33 Frequency Deviation Profile, * * Through September Only Page 4 Frequency Profile, * * Through September Only Page 5 3

34 Frequency Profile January through December * Through September Only Page 6 Frequency Error 3rd Quarter, * * Through September Only Page 7 4

35 Frequency Error 2 nd Quarter, * * Through September Only Page 8 Frequency Error 1 st Quarter, * * Through September Only Page 9 5

36 Frequency Error 4 th Quarter, Page 10 Daily Frequency Performance 2010 Page 11 6

37 Daily Frequency Performance 2011 Page 12 Daily Frequency Performance 2012 Page 13 7

38 Daily Frequency Performance 2013 Page 14 1 Minute Frequency Profile, * * Through September Only Page 15 8

39 10 Minute Frequency Profile, * * Through September Only Page 16 Daily RMS1, * * Through September Only Page 17 9

40 Daily RMS1 Boxplot, * * Through September Only Page 18 Daily Average Frequency Error Boxplot, * Through September Only Page 19 10

41 Daily RMS1 Control Plot, 2013* * Through September Only Page 20 Daily Average Frequency Error Control Plot * Through September Only Page 21 11

42 Y WECC TIME ERROR STATISTICS July 2013 Total Number of Time Error Corrections 21 Fast Time Error Corrections 10 Slow Time Error Corrections 11 Net Total Duration of TE Correction (Hrs) Hours Fast Time Error Corrections 59.5 Hours Slow Time Error Corrections 55.6 Hours Average Duration of Time Error Corrections(Hrs) 5.5 Hours Fast Time Error Corrections 6.0 Slow Time Error Corrections 5.1 Actual Time Error Correction Achieved Second s Page 22 August WECC TIME ERROR STATISTICS August 2013 Total Number of Time Error Corrections 13 Fast Time Error Corrections 5 Slow Time Error Corrections 8 Net Total Duration of TE Correction (Hrs) 78.8 Hours Fast Time Error Corrections 28.0 Hours Slow Time Error Corrections 50.8 Hours Average Duration of Time Error Corrections(Hrs) 6.1 Hours Fast Time Error Corrections 5.6 Slow Time Error Corrections 6.3 Actual Time Error Correction Achieved Second s Page 23 12

43 September WECC TIME ERROR STATISTICS September 2013 Total Number of Time Error Corrections 12 Fast Time Error Corrections 5 Slow Time Error Corrections 7 Net Total Duration of TE Correction (Hrs) 66.5 Hours Fast Time Error Corrections 30.6 Hours Slow Time Error Corrections 35.9 Hours Average Duration of Time Error Corrections(Hrs) 5.5 Hours Fast Time Error Corrections 6.1 Slow Time Error Corrections 5.1 Actual Time Error Correction Achieved Second s Page 24 WECC Time Error Statistics, 2013 Summary Annual Totals (YTD) Total Number of Time Error Corrections 137 Fast Time Error Corrections 73 Slow Time Error Corrections 64 Net Total Duration of TE Correction (Hrs) Hours Fast Time Error Corrections Hours Slow Time Error Corrections Hours Average Duration of Time Error Corrections(Hrs) 5.86 Hours Fast Time Error Corrections 6.00 Slow Time Error Corrections 5.69 Actual Time Error Correction Achieved Second s 13.9 minutes Page 25 13

44 Q & A Page 26 14

45 Daily Avg Daily Epsilon 1 (RMS) Eastern Interconnection RMS1 by Year (through October 21, 2013) Year Eastern Interconnection Daily Frequency Error (through October 21, 2013) Year

46 Sample Range Sample Mean Sample Range Sample Mean Xbar-R Chart of Daily Ave Freq Error by Week (10/1/12 to 10/21/13) UCL= _ X= LCL= Sample UCL= _ R= LCL= Sample Tests performed with unequal sample sizes Xbar-R Chart of Daily RMS1 by Week (10/1/12 to 10/21/13) UCL= _ X= LCL= Sample UCL= _ R= LCL= Sample Tests performed with unequal sample sizes

47 NERC Resources Subcommittee Eastern Interconnection Time Error Report 3Q Time Error Summary Y ear Mo onth # OF CO (FA ORRECTIONS AST) # OF CO (SL ORRECTIONS LOW) TOTAL HO OURS (FAST) TOTAL HO OURS (SLOW) AVERAGE (FA E DURATION AST) AVERAGE (SL E DURATION LOW) FEB MAR MAY JUN AUG SEP NOV DEC 1

48 400 Monthly Time Error Summary - Total Hours Total Hours on Correction Fast Slow 45 Monthly Time Error Summary - Number of Corrections Number of corrections Fast Slow 2

49 400 Yearly Time Error - Fast Corrections vs Total Hours Number of Corrections Number of Fast TEC's Total Hours Fast 3

50 ERCOT Frequency Control and Time Correction Report Resources Subcommittee Meeting Sullivan Island, SC October 30, 2013 Frequency Profile, CPS1 & 2 and Daily Frequency RMS1. ERCOT FREQUENCY CONTROL REPORT 1

51 NERC CPS ERCOT CPS1 By Day - September-2013 ERCOT Monthly CPS1 = Day CPS 1 Avg CPS 1 Peak Energy ERCOT Peak Energy NERC CPS 2 100% 98% 96% 94% 92% 90% 88% 86% 84% 82% 80% ERCOT CPS2 By Day - September-2013 ERCOT Monthly CPS2 = Day CPS 2 Avg CPS 2 Peak Energy ERCOT Peak Energy 2

52 170 ERCOT CPS1 CPS1 12 Month Rolling Average = CPS1 Average e Monthly Average 12 Month Rolling Average 100 ERCOT CPS2 Score* *ERCOT as a single control area is exempt from CPS2. These scores are For Information Only CPS Month CPS2 3

53 4 Daily RMS1 of ERCOT Frequency /1/2000 7/1/2000 1/1/2001 7/1/2001 1/1/2002 7/1/2002 1/1/2003 7/1/2003 1/1/2004 7/1/2004 1/1/2005 7/1/2005 1/1/2006 7/1/2006 1/1/2007 7/1/2007 1/1/2008 7/1/2008 1/1/2009 7/1/2009 1/1/2010 7/1/2010 1/1/2011 7/1/2011 1/1/2012 7/1/2012 1/1/2013 7/1/2013 Daily RMS1 of ERCOT Frequency /1/2004 4/1/2004 7/1/ /1/2004 1/1/2005 4/1/2005 7/1/ /1/2005 1/1/2006 4/1/2006 7/1/ /1/2006 1/1/2007 4/1/2007 7/1/ /1/2007 1/1/2008 4/1/2008 7/1/ /1/2008 1/1/2009 4/1/2009 7/1/ /1/2009 1/1/2010 4/1/2010 7/1/ /1/2010 1/1/2011 4/1/2011 7/1/ /1/2011 1/1/2012 4/1/2012 7/1/ /1/2012 1/1/2013 4/1/2013 7/1/2013

54 Daily RMS1 of ERCOT Frequency /1/2007 4/1/2007 7/1/ /1/2007 1/1/2008 4/1/2008 7/1/ /1/2008 1/1/2009 4/1/2009 7/1/ /1/2009 1/1/2010 4/1/2010 7/1/ /1/2010 1/1/2011 4/1/2011 7/1/2011 Comparing July 2010 vs July 2013 profile of frequency in 5 mhz bins 10/1/2011 1/1/2012 4/1/2012 7/1/ /1/2012 1/1/2013 4/1/2013 7/1/ <= HZ < Jul-10 Jul

55 Comparing August 2010 vs August 2013 profile of frequency in 5 mhz bins <= HZ < Comparing September 2010 vs September 2013 profile of frequency in 5 mhz bins <= HZ < Aug-10 Aug Sep-10 Sep-13 6

56 50000 ERCOT Frequency Profile Comparison January through December of each Year One Minute Occurances System Change Request 773 Adjust Generation To Be Dispatched by a percentage of the Regulation Service Deployed. Modification installed May 23, Metrics developed to determine improvement in utilization of Regulation Service. 7

57 Percent of 15 minute Inetervals when both Reg UP and Reg Down were Deployed % SCR 773 was implemented on May 23, % 87.19% 85.00% 80.51% 83.16% 80.87% 80.00% 77.77% 76.95% 75.90% 73.81% 75.00% 72.53% 71.57% 71.61% 71.33% 71.15% 70.43% 68.18% 71.78% 70.80% 70.19% 70.00% 68.62% 67.44% 66.04% 65.58% 65.09% 65.86% 66.87% 65.17% 64.89% 65.00% 63.51% 61.72% 62.43% 59.91% 59.86% 60.32% 60.00% 55.00% 53.47% 50.00% 45.00% 40.00% 35.00% 30.00% 25.00% 20.00% 15.00% 10.00% 5.00% 0.00% Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Time Error, Number of Time Corrections and Total Hours in Time Correction. ERCOT TIME ERROR AND TIME CORRECTIONS PERFORMANCE 8

58 ERCOT Time Error Corrections July None. None. ERCOT Time Error Corrections August 9

59 None. ERCOT Time Error Corrections September None. ERCOT Time Error Corrections October through 28th 10

60 350 Monthly Cumulative TEC Monthly TEC Hours (Nov 2011 to Oct 2012) Monthly TEC Hours (Nov 2012 to August 2013) HOURS November 2.5 December January February March April May June July August September October Time Correction History Time Corrections Total Hours on Avg Hours Avg Corrections % Time on Year Month Days Fast Slow Count Control Per Correction Per Day Correction 2012 Jan % Feb % Mar % Apr % May % Jun % Jul % Aug % Sep % Oct % Nov % Dec % 2013 Jan % Feb % Mar % Apr % May % Jun % Jul % Aug % Sep % Oct % 11

61 Monthly TEC comparison Monthly TEC Hours (Nov 2011 to Oct 2012) Monthly TEC Hours (Nov 2012 to October 28, 2013) Hours November December January February March April May June July August September October 10 November-2011 ERCOT Time Error & Time Change October Loss - Daily Time - Gain 2 0 October-2012 Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sep Oct Time Error Time Change Time Error 12

62 ERCOT Time Error & Time Change November October Loss - Daily Time - Gain 2 0 October-2013 Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sep Oct Time Error Time Change Time Error Monthly Hours on Time Correction 90 Total Hours on Correction Between October 2001 and June 2013, only three months had zero TEC. Since June 2013 there havebeen 4 consecutive months with no TEC Hours on Control 13

63 Monthly Time Correction Summary Number of Corrections Slow Fast What Changed? Regulation Deployment feedback into Generation To Be Dispatched was added. ERCOT identified generators not following Startup procedures and worked with generators to improve performance. Load Frequency Control (LFC) tuning improved Regulation Deployments. Primary Frequency Response performance improved. More generators delivering sustained PFR. 14

64 Performance as measured by BAL for current year. ERCOT INTERCONNECTION FREQUENCY RESPONSE PERFORMANCE ERCOT Primary Frequency Response BAL Bias and Frequency Response Measure Page 1 Date/Time (t-0) BA BA BA Relay Lmt Value "A" Information Value "B" Information SEFRD (FRM) Time Bias R1 for Bias for R1 BA Time Zone DelFreq Time DelFreq DelFreq MW/Load Lost Adjustment MW/Load Lost Adjustment (MW/0.1Hz) (MW/0.1Hz) 12/10/ :32:54 CST :32: /12/2012 7:31:10 CST :31: /25/2012 4:30:20 CST :30: /2/ :41:26 CST :41: /13/ :35:06 CST :35: /15/ :04:14 CST :04: /19/ :10:16 CST :10: /22/ :06:24 CST :06: /4/ :47:48 CST :47: /7/ :05:56 CST :05: /15/ :39:50 CDT :39: /18/ :21:22 CDT :21: /2/ :25:34 CDT :25: /9/ :21:40 CDT :21: /23/ :19:30 CDT :19: /29/ :59:14 CDT :59: /7/2013 3:07:26 CDT :07: /11/ :13:48 CDT :13: /17/ :38:22 CDT :38: /22/ :11:30 CDT :11: /29/ :47:34 CDT :47: /30/ :46:22 CDT :46: /4/ :04:26 CDT :04: /11/ :56:36 CDT :56: /12/ :45:22 CDT :45: /25/ :47:46 CDT :47: /26/ :09:56 CDT :09: /21/ :00:50 CDT :00:

65 ERCOT Primary Frequency Response BAL Bias and Frequency Response Measure Page 2 Date/Time (t-0) BA BA BA Relay Lmt Value "A" Information Value "B" Information SEFRD (FRM) Time Bias R1 for Bias for R1 BA Time Zone DelFreq Time DelFreq DelFreq MW/Load Lost Adjustment MW/Load Lost Adjustment (MW/0.1Hz) (MW/0.1Hz) 7/25/2013 1:15:52 CDT :15: /2/ :35:08 CDT :35: /11/2013 5:43:36 CDT :43: /12/2013 2:58:06 CDT :58: /18/ :45:34 CDT :45: /20/ :19:12 CDT :19: /24/ :46:10 CDT :46: /29/ :55:24 CDT :55: /3/ :25:10 CDT :25: /25/2013 9:17:30 CDT :17: /8/ :56:08 CDT :56: /12/ :23:26 CDT :23: FRM - Average Estimated Frequency Response MW/0.1 Hz using SEFRD for R FRM - Regression Estimated Frequency Response MW/0.1Hz using SEFRD for R FRM - Median Estimated Frequency Response MW/0.1Hz for BA Compliance to R1, minimum Frequency Response Historical and current year to date totals. ERCOT INTERCONNECTION TOTAL ENERGY AND TOTAL ENERGY FROM WIND RESOURCES 16

66 ERCOT Total Energy 45,000,000 40,000,000 35,000,000 30,000,000 MWH 25,000,000 20,000,000 15,000,000 10,000,000 5,000,000 0 January February March April May June July August September October November December ERCOT Total Energy from Wind Generation 4,000,000 3,500,000 3,000,000 2,500,000 MWH 2,000,000 1,500,000 1,000, ,000 0 January February March April May June July August September October November December

67 ERCOT % Energy from Wind Generation 16.00% 14.00% 12.00% 10.00% 8.00% 6.00% 4.00% 2.00% 0.00% January February March April May June July August September October November December Questions? 18

Demonstration of PFR Improvement September ERCOT Operations Planning

Demonstration of PFR Improvement September ERCOT Operations Planning Demonstration of PFR Improvement September 2017 ERCOT Operations Planning Agenda Overview BAL-001-TRE-1 Standard Applicability to Alternative Resources Ancillary Service Products & Dispatch Improvements

More information

NERC Interconnections Frequency Response Statistics, Typical Frequency Events Profiles, and Observations on NERC-FRI Report Statistics

NERC Interconnections Frequency Response Statistics, Typical Frequency Events Profiles, and Observations on NERC-FRI Report Statistics Consortium for Electric Reliability Technology Solutions NERC Interconnections Frequency Response Performance NERC Interconnections 2009 2012 Frequency Response Statistics, Typical Frequency Events Profiles,

More information

Robert W. Cummings - NERC Director of System Analysis and Reliability Initiatives William Herbsleb - Chairman of Frequency Response Standard Drafting

Robert W. Cummings - NERC Director of System Analysis and Reliability Initiatives William Herbsleb - Chairman of Frequency Response Standard Drafting Generator Governor and Information Settings Webinar Robert W. Cummings - NERC Director of System Analysis and Reliability Initiatives William Herbsleb - Chairman of Frequency Response Standard Drafting

More information

BAL Standard Project Frequency Response and Frequency Bias Setting Industry Webinar

BAL Standard Project Frequency Response and Frequency Bias Setting Industry Webinar BAL-003-1 Standard Project 2007-12 Frequency Response and Frequency Bias Setting Industry Webinar Terry L. Bilke Midwest ISO, Inc. David F. Lemmons Xcel Energy, Inc. Sydney L. Niemeyer NRG Texas LP November

More information

Procedure for ERO Support of Frequency Response and Frequency Bias Setting Standard. Event Selection Process

Procedure for ERO Support of Frequency Response and Frequency Bias Setting Standard. Event Selection Process This procedure outlines the Electric Reliability Organization (ERO) process for supporting the Frequency Response Standard (FRS). A Procedure revision request may be submitted to the ERO for consideration.

More information

Frequency Response Initiative Industry Advisory Generator Governor Frequency Response

Frequency Response Initiative Industry Advisory Generator Governor Frequency Response Frequency Response Initiative Industry Advisory Generator Governor Frequency Response Troy Blalock South Carolina Electric and Gas Bob Cummings NERC Reliability Initiatives and System Analysis Rich Bauer

More information

Standard BAL Frequency Response and Frequency Bias Setting

Standard BAL Frequency Response and Frequency Bias Setting A. Introduction Title: and Frequency Bias Setting Number: BAL-003-1 Purpose: To require sufficient from the Balancing (BA) to maintain Interconnection Frequency within predefined bounds by arresting frequency

More information

Standard Development Timeline

Standard Development Timeline Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard is adopted by the NERC Board of Trustees (Board).

More information

NARUC. Summer Committee Meetings. Staff Subcommittees on Electricity & Electric Reliability

NARUC. Summer Committee Meetings. Staff Subcommittees on Electricity & Electric Reliability NARUC Summer Committee Meetings Staff Subcommittees on Electricity & Electric Reliability NARUC Summer Committee Meetings Agenda 10:00-11:00 am Tour of the Newtown Creek Biodigester Plant 1:00 2:00 pm

More information

Reference Document Balancing Authority Area Footprint Change Tasks

Reference Document Balancing Authority Area Footprint Change Tasks 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 Reference Document Balancing Authority Area Footprint Change Tasks Purpose The purpose of this reference

More information

Alberta Reliability Standard Frequency Response and Frequency Bias Setting BAL-003-AB-1.1

Alberta Reliability Standard Frequency Response and Frequency Bias Setting BAL-003-AB-1.1 1. Purpose The purpose of this reliability standard is to: (a) require sufficient frequency response from the ISO to maintain Interconnection frequency within predefined bounds by arresting frequency deviations

More information

Forward Looking Frequency Trends Technical Brief ERS Framework 1 Measures 1, 2, and 4: Forward Looking Frequency Analysis

Forward Looking Frequency Trends Technical Brief ERS Framework 1 Measures 1, 2, and 4: Forward Looking Frequency Analysis Forward Looking Frequency Trends Technical Brief ERS Framework 1 Measures 1, 2, and 4: Forward Looking Frequency Analysis The NERC Planning Committee and Operating Committee jointly created the Essential

More information

Calculating and Using Reporting ACE in a Tie Line Bias Control Program

Calculating and Using Reporting ACE in a Tie Line Bias Control Program Calculating and Using Reporting ACE in a Tie Line Bias Control Program Introduction: Tie Line Bias 1 (TLB) control has been used as the preferred control method in North America for 75 years. In the early

More information

Informational Filing Regarding BAL-001-2, Docket No. RM (Errata to Include Attachment)

Informational Filing Regarding BAL-001-2, Docket No. RM (Errata to Include Attachment) VIA ELECTRONIC FILING October 1, 2018 Ms. Kimberly D. Bose Secretary Federal Energy Regulatory Commission 888 First Street, NE Washington, D.C. 20426 Re: Informational Filing Regarding BAL-001-2, Docket

More information

NERC Training Document Understand and Calculate Frequency Response

NERC Training Document Understand and Calculate Frequency Response N E R C Assisting System Personnel In Keeping Current NERC Training Document Understand and Calculate Frequency Response Developed by: NERC Training Resources Working Group February 20, 2003 Subject: Understand

More information

2018 Frequency Response Annual Analysis

2018 Frequency Response Annual Analysis 2018 Frequency Response Annual Analysis November 2018 NERC Report Title Report Date I Table of Contents Preface... iii Executive Summary... iv Recommendations... iv Introduction... v Chapter 1 : Interconnection

More information

Reliability Guideline: Generating Unit Operations During Complete Loss of Communications

Reliability Guideline: Generating Unit Operations During Complete Loss of Communications 1 1 1 1 1 1 1 1 0 1 0 1 0 1 Reliability Guideline: Generating Unit Operations During Complete Loss of Communications Preamble It is in the public interest for the North American Electric Reliability Corporation

More information

Reliability Guideline: Generating Unit Operations During Complete Loss of Communications

Reliability Guideline: Generating Unit Operations During Complete Loss of Communications 1 1 1 1 1 1 1 1 0 1 0 1 0 1 Reliability Guideline: Generating Unit Operations During Complete Loss of Communications Preamble: It is in the public interest for the North American Electric Reliability Corporation

More information

Final ballot January BOT adoption February 2015

Final ballot January BOT adoption February 2015 Standard PRC-024-21(X) Generator Frequency and Voltage Protective Relay Settings Standard Development Timeline This section is maintained by the drafting team during the development of the standard and

More information

Reliability Guideline Integrating Reporting ACE with the NERC Reliability Standards

Reliability Guideline Integrating Reporting ACE with the NERC Reliability Standards Reliability Guideline Integrating Reporting ACE with the NERC Reliability Standards Applicability: Balancing Authorities (BAs) Introduction and Purpose: It is in the public interest for NERC to develop

More information

Load-Frequency Control and Reserves Network Code. David Bunney JESG 19 March 2013

Load-Frequency Control and Reserves Network Code. David Bunney JESG 19 March 2013 Load-Frequency Control and Reserves Network Code David Bunney JESG 19 March 2013 Agenda Overview and Timescales Stakeholder Engagement Overview of the Code More detailed discussion on Frequency Quality

More information

Operationalizing Phasor Technology. Model Validation. Webinar. Ken Martin. March 4, Presented by. Page 0

Operationalizing Phasor Technology. Model Validation. Webinar. Ken Martin. March 4, Presented by. Page 0 Operationalizing Phasor Technology Model Validation Webinar March 4, 2014 Presented by Ken Martin Page 0 Model Use and Validation for Operations and Planning Compare System Performance with Model Prediction

More information

Table of Contents Error! Bookmark not defined.

Table of Contents Error! Bookmark not defined. Table of Contents Table of Contents... 1 Introduction... 2 Background... 2 Rationale by Requirement... 204 Requirement 1... 204 Background and Rationale... 204 Requirement 2... 268 Background and Rationale...

More information

Informational Filing, Interim Report on Balancing Authority ACE Limit Field Trial Docket No. RM

Informational Filing, Interim Report on Balancing Authority ACE Limit Field Trial Docket No. RM VIA ELECTRONIC FILING July 31, 2014 Ms. Kimberly D. Bose Secretary Federal Energy Regulatory Commission 888 First Street, NE Washington, D.C. 20426 Re: Informational Filing, Interim Report on Balancing

More information

Table of Contents. NERC 2016 Frequency Response Annual Analysis September 2016 ii

Table of Contents. NERC 2016 Frequency Response Annual Analysis September 2016 ii 2016 Frequency Response Annual Analysis September 2016 I Table of Contents Preface... iii This Report... iv Executive Summary... v Recommendations... v Findings... vii Interconnection Frequency Characteristic

More information

Informational Filing, Frequency Response Annual Analysis Docket No. RM

Informational Filing, Frequency Response Annual Analysis Docket No. RM VIA ELECTRONIC FILING November 29, 2018 Ms. Kimberly D. Bose Secretary Federal Energy Regulatory Commission 888 First Street, NE Washington, D.C. 20426 Re: Informational Filing, Frequency Response Annual

More information

Frequency Response Standard Whitepaper

Frequency Response Standard Whitepaper NORTH AMERICAN ELECTRIC RELIABILITY COUNCIL Princeton Forrestal Village, 116-390 Village Boulevard, Princeton, New Jersey 08540-5731 Frequency Response Standard Whitepaper April 6, 2004 Prepared by the

More information

Standard PRC Generator Frequency and Voltage Protective Relay Settings. A. Introduction. See the Implementation Plan for PRC

Standard PRC Generator Frequency and Voltage Protective Relay Settings. A. Introduction. See the Implementation Plan for PRC A. Introduction 1. Title: Generator Frequency and Voltage Protective Relay Settings 2. Number: PRC-024-2 3. Purpose: Ensure Generator Owners set their generator protective relays such that generating units

More information

Implementation Plan Project Balancing Authority Reliability-based Controls - Reserves

Implementation Plan Project Balancing Authority Reliability-based Controls - Reserves Implementation Plan Project 2010-14.1 Balancing Authority Reliability-based Controls - Reserves Implementation Plan for Approvals Required Prerequisite Approvals None Revisions to Glossary Terms The following

More information

Frequency Response Initiative Report

Frequency Response Initiative Report Frequency Response Initiative Report The Reliability Role of Frequency Response August 31, 2012 Draft 3353 Peachtree Road NE Suite 600, North Tower Atlanta, GA 30326 404-446-2560 www.nerc.com NERC s Mission

More information

Transmission Availability Data System (TADS) DATA REPORTING INSTRUCTION MANUAL

Transmission Availability Data System (TADS) DATA REPORTING INSTRUCTION MANUAL Transmission Availability Data System (TADS) DATA REPORTING INSTRUCTION MANUAL Version History Version History Version Date October 17, 2007 November 20, 2007 New Major Changes P. 4. Table 1.5, third row

More information

Informational Filing, Frequency Response Annual Analysis Docket No. RM

Informational Filing, Frequency Response Annual Analysis Docket No. RM VIA ELECTRONIC FILING March 20, 2015 Ms. Kimberly D. Bose Secretary Federal Energy Regulatory Commission 888 First Street, NE Washington, D.C. 20426 Re: Informational Filing, Response Annual Analysis Docket

More information

2015 Frequency Response Annual Analysis

2015 Frequency Response Annual Analysis 2015 Frequency Response Annual Analysis September 16, 2015 I Table of Contents Preface... iii This Report... iv Executive Summary... v Recommendations... v Findings... vi Interconnection Frequency Characteristic

More information

Standard BAL-005-0b Automatic Generation Control

Standard BAL-005-0b Automatic Generation Control A. Introduction 1. Title: Automatic Generation Control 2. Number: BAL-005-0b 3. Purpose: This standard establishes requirements for Balancing Authority Automatic Generation Control (AGC) necessary to calculate

More information

Standard PRC Generator Frequency and Voltage Protective Relay Settings. A. Introduction

Standard PRC Generator Frequency and Voltage Protective Relay Settings. A. Introduction A. Introduction 1. Title: Generator Frequency and Voltage Protective Relay Settings 2. Number: PRC-024-1 3. Purpose: Ensure Generator Owners set their generator protective relays such that generating units

More information

Standard BAL b Automatic Generation Control

Standard BAL b Automatic Generation Control A. Introduction 1. Title: Automatic Generation Control 2. Number: BAL-005-0.2b 3. Purpose: This standard establishes requirements for Balancing Authority Automatic Generation Control (AGC) necessary to

More information

Frequency Response Standard Background Document November, 2012

Frequency Response Standard Background Document November, 2012 Frequency Response Standard Background Document November, 2012 3353 Peachtree Road NE Suite 600, North Tower Atlanta, GA 30326 404-446-2560 www.nerc.com Table of Contents Table of Contents... 1 Introduction...

More information

generation greater than 75 MVA (gross aggregate nameplate rating) Generation in the ERCOT Interconnection with the following characteristics:

generation greater than 75 MVA (gross aggregate nameplate rating) Generation in the ERCOT Interconnection with the following characteristics: A. Introduction 1. Title: Verification of Models and Data for Turbine/Governor and Load Control or Active Power/Frequency Control Functions 2. Number: MOD-027-1 3. Purpose: To verify that the turbine/governor

More information

Harmonizing the Changing Resource Mix Keeping the Grid Together

Harmonizing the Changing Resource Mix Keeping the Grid Together Harmonizing the Changing Resource Mix Keeping the Grid Together Robert W. Cummings Senior Director of Engineering and Reliability Initiatives i-pcgrid March 30, 2017 NERC-IEEE Memorandum of Understanding

More information

Informational Filing Regarding 2017 Frequency Response Annual Analysis Report Docket No. RM

Informational Filing Regarding 2017 Frequency Response Annual Analysis Report Docket No. RM VIA ELECTRONIC FILING November 29, 2017 Ms. Kimberly D. Bose Secretary Federal Energy Regulatory Commission 888 First Street, NE Washington, D.C. 20426 Re: Informational Filing Regarding 2017 Frequency

More information

NATIONAL INSTITUTE OF ECONOMIC AND SOCIAL RESEARCH ESTIMATES OF MONTHLY GDP. Embargo until hours on 11 th January 2013

NATIONAL INSTITUTE OF ECONOMIC AND SOCIAL RESEARCH ESTIMATES OF MONTHLY GDP. Embargo until hours on 11 th January 2013 NATIONAL INSTITUTE OF ECONOMIC AND SOCIAL RESEARCH ESTIMATES OF MONTHLY GDP Embargo until 15.00 hours on 11 th January 2013 Our monthly estimates of GDP suggest that output declined by 0.3 per cent in

More information

Standard BAL b Automatic Generation Control

Standard BAL b Automatic Generation Control A. Introduction 1. Title: Automatic Generation Control 2. Number: BAL-005-0.2b 3. Purpose: This standard establishes requirements for Balancing Authority Automatic Generation Control (AGC) necessary to

More information

Minutes Frequency Response Initiative Meeting

Minutes Frequency Response Initiative Meeting Minutes Frequency Response Initiative Meeting April 27, 2010 Tucson Electric Co. Office Tucson, Arizona A meeting of the NERC Frequency Response Initiative Team was held on April 27, 2010 at the Ameren

More information

Frequency Response Characteristic Survey Training Document

Frequency Response Characteristic Survey Training Document Frequency Response Characteristic Survey Training Document Training Document Subsections Frequency Response Characteristic Response to Internal and External Generation/Load Imbalances Frequency Bias versus

More information

Standard BAL b3 Automatic GenerationBalancing Authority Control DRAFT

Standard BAL b3 Automatic GenerationBalancing Authority Control DRAFT A. Introduction 1. Title: Balancing Authority ControlAutomatic Generation Control 2. Number: BAL-005-30.2b 3. Purpose: This standard establishes requirements for acquiring necessary data for the Balancing

More information

BACCARAT: A LONGITUDINAL MICRO-STUDY

BACCARAT: A LONGITUDINAL MICRO-STUDY BACCARAT: A LONGITUDINAL MICRO-STUDY FIELD RESULTS FROM ONE ATLANTIC CITY CASINO, JANUARY 2004 TO JUNE 2010 CENTER FOR GAMING RESEARCH, JULY 2010 Baccarat is the most important game in the world s biggest

More information

Success Story: Practical Use of Synchrophasor Technology in ISO-NE Operations

Success Story: Practical Use of Synchrophasor Technology in ISO-NE Operations 2018-10- 23 PHILADELPHIA, PA Success Story: Practical Use of Synchrophasor Technology in ISO-NE Operations NASPI Work Group Meeting Xiaochuan Luo TECHNICAL MANAGER BUSINESS ARCHITECTURE AND TECHNOLOGY

More information

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION North American Electric Reliability Corporation ) ) Docket No. RM13-11-000 INFORMATIONAL FILING OF THE NORTH AMERICAN ELECTRIC RELIABILITY

More information

European Update. 3 rd December 2015

European Update. 3 rd December 2015 European Update Place your chosen image here. The four corners must just cover the arrow tips. For covers, the three pictures should be the same size and in a straight line. 3 rd December 2015 1. General

More information

Number patterns on a spreadsheet

Number patterns on a spreadsheet A1 SS Number patterns on a spreadsheet This sheet will help you to create your own number patterns on a spreadsheet. Do the steps one at a time. You will soon feel more confident with a spreadsheet program.

More information

Assessing the Feasibility of Wind Power Production for the University of Rhode Island s Bay Campus

Assessing the Feasibility of Wind Power Production for the University of Rhode Island s Bay Campus University of Rhode Island DigitalCommons@URI Senior Honors Projects Honors Program at the University of Rhode Island 2009 Assessing the Feasibility of Wind Power Production for the University of Rhode

More information

Balancing Authority ACE Limit Proof-of-Concept Field Trial Project

Balancing Authority ACE Limit Proof-of-Concept Field Trial Project Balancing Authority ACE Limit Proof-of-Concept Field Trial Project 2010-14 Eastern Interconnection Update Discussion March 29, 2011 DISCUSSION STARTING AT 2:30 PM EDT Bob Klueber Midwest ISO Balancing

More information

Economic & Housing Outlook

Economic & Housing Outlook Economic & Housing Outlook By Lawrence Yun, Ph.D. Chief Economist, National Association of REALTORS Presentation at Northern Arizona Association of REALTORS November 30, 2017 Tax Reform Mortgage interest

More information

Standard Development Timeline

Standard Development Timeline Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Description of Current Draft

More information

Using Synchrophasors for Frequency Response Analysis in the Western Interconnection. Bonneville Power Administration -- WECC JSIS Chair

Using Synchrophasors for Frequency Response Analysis in the Western Interconnection. Bonneville Power Administration -- WECC JSIS Chair 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2014 Grid of the Future Symposium Using Synchrophasors for Frequency Response Analysis in the Western Interconnection

More information

How Full-Converter Wind Turbine Generators Satisfy Interconnection Requirements

How Full-Converter Wind Turbine Generators Satisfy Interconnection Requirements How Full-Converter Wind Turbine Generators Satisfy Interconnection Requirements Robert Nelson Senior Expert Engineering Manager and Manager of Codes, Standards, and Regulations Siemens Wind Turbines -

More information

Proposed Language in BAL-003-1/Comments New Standard or Other Action R1. Each Balancing Authority shall This. Attachment A.

Proposed Language in BAL-003-1/Comments New Standard or Other Action R1. Each Balancing Authority shall This. Attachment A. in Approved Standard Translation to R1. Each Balancing Authority shall review its Frequency Bias Each Balancing Authority shall report its previous year s Settings by January 1 of each Frequency Response

More information

EE 742 Chapter 9: Frequency Stability and Control. Fall 2011

EE 742 Chapter 9: Frequency Stability and Control. Fall 2011 EE 742 Chapter 9: Frequency Stability and Control Fall 2011 Meeting demand with generation Large and slow changes (24 hr) in power demand are met by unit commitment Medium and relatively fast changes (30

More information

Texas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event

Texas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event Texas Reliability Entity Event Analysis Event: May 8, 2011 Loss of Multiple Elements Category 1a Event Texas Reliability Entity July 2011 Page 1 of 10 Table of Contents Executive Summary... 3 I. Event

More information

Area Control Error (ACE) Equation Special Cases

Area Control Error (ACE) Equation Special Cases Area Control Error (ACE) Equation Special Cases Purpose: It is the obligation of each Balancing Authority to manage its Area Control Error in accordance with NERC reliability standards. This Standard provides

More information

Table 1 - Assignment of BA Obligations... 8

Table 1 - Assignment of BA Obligations... 8 Dynamic Transfer Reference Guidelines Version 2 June 2010 Table of Contents Table of Contents Chapter 1 Overview... 3 Purpose... 3 Terms... 3 Chapter 2 Dynamic Schedule Versus Pseudo-tie Fundamentals...

More information

Lessons Learned in Model Validation for NERC Compliance

Lessons Learned in Model Validation for NERC Compliance Lessons Learned in Model Validation for NERC Compliance usa.siemens.com/digitalgrid NERC Modeling, Data, and Analysis MOD 025 2: Generator Real and Reactive Power Capability Demonstration MOD 026 1: Verification

More information

Transmission Availability Data System (TADS) Data Reporting Instruction Manual

Transmission Availability Data System (TADS) Data Reporting Instruction Manual Version History Transmission Availability Data System (TADS) Data Reporting Instruction Manual August 8, 2013 For Calendar Year 2013 3353 Peachtree Road NE Suite 600, North Tower Atlanta, GA 30326 404-446-2560

More information

Estimation of Fault Resistance from Fault Recording Data. Daniel Wong & Michael Tong 2014-November-5

Estimation of Fault Resistance from Fault Recording Data. Daniel Wong & Michael Tong 2014-November-5 Estimation of Fault Resistance from Fault Recording Data Daniel Wong & Michael Tong 2014-November-5 Agenda Project Background & Introduction Fault Resistance & Effect Estimation Algorithm Estimation Results

More information

Operationalizing Phasor Technology

Operationalizing Phasor Technology ELECTRIC POWER GROUP WEBINAR SERIES Operationalizing Phasor Technology Operationalizing Phasor Technology System Events Deciphering the Heartbeat of the Power Grid July 16, 2013 Webinar John W. Ballance

More information

NPCC Regional Reliability Reference Directory # 12. Underfrequency Load Shedding Program Requirements

NPCC Regional Reliability Reference Directory # 12. Underfrequency Load Shedding Program Requirements NPCC Regional Reliability Reference Directory # 12 Under frequency Load Shedding Program Requirements Task Force on System Studies Revision Review Record: June 26 th, 2009 March 3 rd, 2010 Adopted by the

More information

Synchronized Measurement Data for Frequency Response Analysis

Synchronized Measurement Data for Frequency Response Analysis Synchronized Measurement Data for Frequency Response Analysis Ryan D. Quint, North American Electric Reliability Corporation Pavel Etingov, Pacific Northwest National Laboratory Dao Zhou, University of

More information

Transmission Availability Data System Phase II Final Report

Transmission Availability Data System Phase II Final Report Transmission Availability Data System Phase II Final Report Prepared by the Transmission Availability Data System Task Force for the NERC Planning Committee Approved by the Planning Committee on: Table

More information

Recently, the SS38 Working Group on Inter-Area Dynamic Analysis completed two study reports on behalf of the UFLS Regional Standard Drafting Team.

Recently, the SS38 Working Group on Inter-Area Dynamic Analysis completed two study reports on behalf of the UFLS Regional Standard Drafting Team. December 7 th, 2010 NPCC Full Member Committee; Please find attached a draft revised NPCC Regional Reliability Directory #12 Underfrequency Load Shedding Program Requirements and a draft revised NPCC UFLS

More information

GUIDELINES FOR UTILIZATION OF FREQUENCY AND TIME ERROR DEVICES AND CALIBRATING TIE LINE SIGNAL

GUIDELINES FOR UTILIZATION OF FREQUENCY AND TIME ERROR DEVICES AND CALIBRATING TIE LINE SIGNAL Document name Category Document date March 11, 2003 Adopted/approved by GUIDELINES FOR UTILIZATION OF FREQUENCY AND TIME ERROR DEVICES AND CALIBRATING TIE LINE SIGNAL ( ) Regional Reliability Standard

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements Applicability 1(1) Section 502.1 applies to the ISO, and subject to the provisions of subsections 1(2), (3) and (4) to any: (a) a new wind aggregated generating facility to be connected to the transmission

More information

Final Long-Term Duty Cycle Report Primary Frequency Response (PFR) Duty Cycle Battery Pack: EnerDel, Channel 4 and Battery Module: A123 #5, Channel 1

Final Long-Term Duty Cycle Report Primary Frequency Response (PFR) Duty Cycle Battery Pack: EnerDel, Channel 4 and Battery Module: A123 #5, Channel 1 Final Long-Term Duty Cycle Report Primary Frequency Response (PFR) Duty Cycle Battery Pack: EnerDel, Channel 4 and Battery Module: A123 #5, Channel 1 July 2015 PREPARED FOR National Renewable Energy Laboratory

More information

Recreation Facility Hours

Recreation Facility Hours NORMAL HOURS Recreation Facility Hours August 1, 2016 July 31, 2017 Last Revised: July 29, 2016 Effective Dates 2016: AUG 23 31, SEP 1 2, SEP 6 16, SEP 18 23, SEP 25 30, OCT 1 7, OCT 9 18, OCT 24 30, NOV

More information

Lessons Learned in Model Validation for NERC Compliance

Lessons Learned in Model Validation for NERC Compliance Lessons Learned in Model Validation for NERC Compliance usa.siemens.com/digitalgrid NERC Modeling, Data, and Analysis MOD 025 2: Generator Real and Reactive Power Capability Demonstration MOD 026 1: Verification

More information

Indication of Dynamic Model Validation Process

Indication of Dynamic Model Validation Process Indication of Dynamic Model Validation Process Document Identifier Written by David Cashman Document Version Draft Checked by Date of Current Issue November 2013 Approved by Jon O Sullivan Disclaimer EirGrid,

More information

Site Name. Bird Dimensions Species Hen harrier = data input required length (m) 0.55 = model calculates value wing span (m) 1.

Site Name. Bird Dimensions Species Hen harrier = data input required length (m) 0.55 = model calculates value wing span (m) 1. Site Name Loch Urr Bird Dimensions Species Hen harrier = data input required length (m) 0.55 = model calculates value wing span (m) 1.4 speed (m/sec) 8 Turbine Dimensions Height of tower (m) 80 Blade length

More information

PJM Regulation Study Update

PJM Regulation Study Update PJM Regulation Study Update July 19, 2016 Eric J. Endress Engineer, Performance Compliance Acronym Definitions RegD = Regulation D, Dynamic Regulation RegA = Regulation A, Traditional Regulation ACE =

More information

Grid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017

Grid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017 Grid codes and wind farm interconnections CNY Engineering Expo Syracuse, NY November 13, 2017 Purposes of grid codes Grid codes are designed to ensure stable operating conditions and to coordinate the

More information

Endorsed Assignments from ERS Framework

Endorsed Assignments from ERS Framework ERSTF Completion Endorsed Assignments from ERS Framework Ref Number Title ERS Recommendatio n Ongoing Responsibility 1 Synch Inertia at Interconnection Level Measure 2 Initial Frequency Deviation Measure

More information

Bayport Securitisation (RF) Ltd Investor Report February 2013

Bayport Securitisation (RF) Ltd Investor Report February 2013 Bayport Securitisation (RF) Ltd Investor Report February 2013 Financial statistics for the period ended February 2013 Feb 13 Jan 13 Dec 12 Nov 12 Oct 12 Sep 12 Aug 12 Jul 12 Jun 12 May 12 Apr 12 Mar 12

More information

National Radio Channels. PPM measurement October 2017

National Radio Channels. PPM measurement October 2017 National Radio Channels PPM measurement October 17 Background This overview describes the development of radio broadcasting at national levels with updated figures from October 17. The Norwegian Media

More information

Bayport Securitisation (RF) Ltd Investor Report May 2013

Bayport Securitisation (RF) Ltd Investor Report May 2013 Bayport Securitisation (RF) Ltd Investor Report May 2013 Financial statistics for the period ended May 2013 May 13 Apr 13 Mar 13 Feb 13 Jan 13 Dec 12 Nov 12 Oct 12 Sep 12 Aug 12 Jul 12 Jun 12 Performance

More information

Agenda Item 3h Attachment 9

Agenda Item 3h Attachment 9 Agenda Item 3h Attachment 9 BALANCING AND FREQUENCY CONTROL (Part 1) A Technical Concepts Document Prepared by the NERC Resources Subcommittee November 9, 2009 Table of Contents Introduction... 3 Background...

More information

Economic & Real Estate Outlook. Tax Reform. Michigan 4/26/18

Economic & Real Estate Outlook. Tax Reform. Michigan 4/26/18 Economic & Real Estate Outlook By Lawrence Yun, Ph.D. Chief Economist, National Association of REALTORS Presentations at Michigan REALTORS Broker Summit Plymouth, MI April 25, 2018 Tax Reform Mortgage

More information

WFPS1 WIND FARM POWER STATION GRID CODE PROVISIONS

WFPS1 WIND FARM POWER STATION GRID CODE PROVISIONS WFPS1 WIND FARM POWER STATION GRID CODE PROVISIONS WFPS1.1 INTRODUCTION 2 WFPS1.2 OBJECTIVE 2 WFPS1.3 SCOPE 3 WFPS1.4 FAULT RIDE THROUGH REQUIREMENTS 4 WFPS1.5 FREQUENCY REQUIREMENTS 5 WFPS1.6 VOLTAGE

More information

Economic and Housing Market Outlook

Economic and Housing Market Outlook Economic and Housing Market Outlook By Lawrence Yun, Ph.D. Chief Economist, National Association of REALTORS Presentations At Raleigh Regional Association of REALTORS At Orange-Chatham Association of REALTORS

More information

Fundamentals of Statistical Monitoring: The Good, Bad, & Ugly in Biosurveillance

Fundamentals of Statistical Monitoring: The Good, Bad, & Ugly in Biosurveillance Fundamentals of Statistical Monitoring: The Good, Bad, & Ugly in Biosurveillance Galit Shmuéli Dept of Decision & Info Technologies Robert H Smith School of Business University of Maryland, College Park

More information

IEEE sion/1547revision_index.html

IEEE sion/1547revision_index.html IEEE 1547 IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces http://grouper.ieee.org/groups/scc21/1547_revi sion/1547revision_index.html

More information

SWAN LAKE INTEGRATED WATERSHED MANAGEMENT PLAN SURFACE WATER HYDROLOGY REPORT 1

SWAN LAKE INTEGRATED WATERSHED MANAGEMENT PLAN SURFACE WATER HYDROLOGY REPORT 1 SWAN LAKE INTEGRATED WATERSHED MANAGEMENT PLAN SURFACE WATER HYDROLOGY REPORT 1 1. General Description Figure 1 provides a map of the Swan Lake Watershed. The watershed is characterized by two major parallel

More information

Using Synchrophasor System Data for Establishing Operating Range for Operators Guidance and Detection and Analysis of Significant Events

Using Synchrophasor System Data for Establishing Operating Range for Operators Guidance and Detection and Analysis of Significant Events 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http://www.cigre.org 2015 Grid of the Future Symposium Using Synchrophasor System Data for Establishing Operating Range for Operators Guidance

More information

A Guide to Linked Mortality Data from Hospital Episode Statistics and the Office for National Statistics

A Guide to Linked Mortality Data from Hospital Episode Statistics and the Office for National Statistics A Guide to Linked Mortality Data from Hospital Episode Statistics and the Office for National Statistics June 2015 Version History Version Changes Date Issued Number 1 14/Dec/2010 1.1 Modified Appendix

More information

IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces

IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces IEEE PES Boston Chapter Technical Meeting IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces P1547 Chair David

More information

1200 MW Fault Induced Solar Photovoltaic Resource Interruption Disturbance Report

1200 MW Fault Induced Solar Photovoltaic Resource Interruption Disturbance Report 1200 MW Fault Induced Solar Photovoltaic Resource Interruption Disturbance Report Rich Bauer Associate Director Reliability Risk Management / Event Analysis Mid C Seminar July 19, 2017 Western Interconnection

More information

Project Balancing Authority Reliability-based Controls Reliability Standard BAL-005-1

Project Balancing Authority Reliability-based Controls Reliability Standard BAL-005-1 Implementation Plan Project 2010-14.2.1 Balancing Authority Reliability-based Controls Reliability Standard BAL-005-1 Requested Approval s Requested Retirement BAL-005-0.2b Automatic Generation Control

More information

The Value of Frequency Keeping and Governor Response to New Zealand

The Value of Frequency Keeping and Governor Response to New Zealand The Value of Frequency Keeping and Governor Response to New Zealand Josh Schipper (Presenter), Alan Wood 2, Conrad Edwards 3, Allan Miller Electric Power Engineering Centre (EPECentre), University of Canterbury

More information

Keeping it up to Speed Off-Nominal Frequency Operations. CETAC 2018 San Ramon

Keeping it up to Speed Off-Nominal Frequency Operations. CETAC 2018 San Ramon Keeping it up to Speed Off-Nominal Frequency Operations CETAC 2018 San Ramon 1 Welcome CETAC 2018 San Ramon Valley Conference Center General Class Information: Safety/Fire evacuation In event of emergency,

More information

Lecture 15 EMS Application II Automatic Generation Contol. Davood Babazadeh

Lecture 15 EMS Application II Automatic Generation Contol. Davood Babazadeh Lecture 15 EMS Application II Automatic Generation Contol Davood Babazadeh 2015-12-03 Outline Generation Control - Why - How AGC design - Area Control Error - Parameter Calculation 2 Course road map 3

More information

BAYPORT SECURITISATION (RF) LTD INVESTOR REPORT DECEMBER 2014

BAYPORT SECURITISATION (RF) LTD INVESTOR REPORT DECEMBER 2014 BAYPORT SECURITISATION (RF) LTD INVESTOR REPORT DECEMBER 2014 Financial statistics for the period ended December 2014 Dec 14 Nov 14 Oct 14 Sept 14 Aug 14 Jul 14 Jun 14 May 14 Apr 14 Mar 14 Feb 14 Jan 14

More information

You may review a blank copy of the application form by clicking on this pdf link. *Last Name *First Name Middle *Position Title.

You may review a blank copy of the application form by clicking on this pdf link. *Last Name *First Name Middle *Position Title. *Last Name *First Name Middle *Position Title *Institution *Department *Address 1: Address 2: *City: Postal Code: State / Province / Region: Country Please Select *Telephone # Fax # *E Mail: *Username:

More information

Standard MOD Area Interchange Methodology

Standard MOD Area Interchange Methodology A. Introduction 1. Title: Area Interchange Methodology 2. Number: MOD-028-2 3. Purpose: To increase consistency and reliability in the development and documentation of Transfer Capability calculations

More information