HANDBOOK NORDAC SK 500E / SK 520E. Frequency inverter. SK 500E A... SK 500E A (0.25kW 7.5kW, 230/400V)

Size: px
Start display at page:

Download "HANDBOOK NORDAC SK 500E / SK 520E. Frequency inverter. SK 500E A... SK 500E A (0.25kW 7.5kW, 230/400V)"

Transcription

1 HANDBOOK NORDAC SK 500E / SK 520E Frequency inverter SK 500E A... SK 500E A (0.25kW 7.5kW, 230/400V) SK 520E A... SK 520E A (0.25kW 7.5kW, 230/400V) BU 0500 GB Getriebebau NORD GmbH & Co. KG

2 NORDAC SK 500E / 520E Handbook Safety instructions N O R D A C SK 500E / SK 520E frequency inverter Safety and operating instructions for drive power converters (as per: Low voltage guideline 73/23/EEC ) 1. General information During operation, drive power converters may have, depending on their protection class, live, bare, moving or rotating parts or hot surfaces. Unauthorised removal of covers, improper use, incorrect installation or operation leads to the risk of serious personal injury or material damage. Further information can be found in this documentation. All transportation, installation and initialisation and maintenance work must be carried out by qualified personnel (comply with IEC 364, CENELEC HD 384, DIN VDE 0100, IEC 664 and DIN VDE 0110, and national accident prevention regulations). For the purposes of these basic safety instructions, qualified personnel are persons who are familiar with the erection, installation, initialisation and operation of this product and who have the relevant qualifications for their work. 2. Proper use Drive power converters are components intended for installation in electrical systems or machines. When being installed in machines, the drive power converter cannot be initialised (i.e. implementation of the proper use) until it has been ensured that the machine meets the provisions of the EC directive 89/392/EEC (machine directive); EN must also be complied with. Initialisation (i.e. implementation of the proper use) is only permitted when the EMC directive (89/336/EEC) is complied with. The drive power converters meet the requirements of the low voltage directive 73/23/EEC. The harmonised standards in pren 50178/DIN VDE 0160, together with EN /VDE 0660 Part 500 and EN 60146/VDE 0558 were applied for the drive power converter. Technical data and information for connection conditions can be found on the rating plate and in the documentation, and must be complied with. 3. Transport, storage Information regarding transport, storage and correct handling must be complied with. 4. Erection The erection and cooling of the equipment must be implemented as per the regulations in the corresponding documentation. The drive power converter must be protected against impermissible loads. During transport and handling in particular, components must not be deformed and/or insulation distances must not be changed. Touching of electronic components and contacts must be avoided. Drive power converters have electrostatically sensitive components that can be easily damaged by incorrect handling. Electrical components must not be mechanically damaged or destroyed (this may cause a health hazard!). 5. Electrical connections When working on live drive power converters, the applicable national accident prevention regulations must be complied with (e.g. VBG 4). The electrical installation must be implemented as per the applicable regulations (e.g. cable cross-section, fuses, ground lead connections). Further information is contained in the documentation. Information about EMC-compliant installation such as shielding, earthing, location of filters and installation of cables can be found in the drive power converter documentation. These instructions must be complied with even with CE marked drive power converters. Compliance with the limit values specified in the EMC regulations is the responsibility of the manufacturer of the system or machine. 6. Operation Systems where drive power converters are installed must be equipped, where necessary, with additional monitoring and protective equipment as per the applicable safety requirements, e.g. legislation concerning technical equipment, accident prevention regulations, etc. Modifications to the drive power converter using the operating software are permitted. After the drive power converter is disconnected from the power supply, live equipment components and power connections should not be touched immediately because of possible charged capacitors. Comply with the applicable information signs located on the drive power converter. All covers must be kept closed during operation. 7. Maintenance and repairs The manufacturer documentation must be complied with. These safety instructions must be kept in a safe place! 2 BU 0500 GB

3 NORDAC SK 500E / 520E Handbook About the present document Documentation Designation: BU 0500 GB Mat. No Device series: SK 500E and SK 520E Version history Designation of previous editions Software version Comment BU 0500 GB, March 2005 V 1.1 R1 First edition, based on BU 0750 DE BU 0500 GB, May 2005 V 1.1 R2 Revised, completed, corrected BU 0500 GB, June 2005 V 1.2 R0 P220 completed and corrected, P466/P554 added, EMC standards BU 0500 GB, August 2005 V 1.2 R0 Mains/motor jumper figure, array levels with SK TU3- PAR note, P107 lifting mechanism, P215, P P470 terminal numbers BU 0500 GB, December 2005 V 1.3 R1 Brake resistors, address NED, attention hot, output current 2,2kW/230V, P415 process controller, EMC for 400V units, E13.2 supplement BU 0500 GB, May 2006 V 1.3 R1 DIP switch voltage/current for analogue input 1/2, corrected Editor Getriebebau NORD GmbH & Co. KG Rudolf- Diesel- Str. 1 D Bargteheide Phone +49 (0) / Fax +49 (0) / Proper use of frequency inverters Compliance with the operating instructions is the prerequisite for trouble-free operation and the performance of any warranty claims. For this reason you must read the operating instructions before you start using the device! The operating instructions contain important service notes. It must therefore be stored in the vicinity of the device. Frequency inverters SK 500E / 520E are devices for industrial and commercial systems for operation of three-phase asynchronous motors with cage rotor. These motors must be suitable for operation on frequency inverters; connection of other loads to the devices is not permitted. Frequency inverters SK 500E / 520E are devices for stationary installation in control cabinets. It is imperative that all specifications regarding the technical data and permissible conditions at the installation site be heeded. Commissioning (start of proper operation) is only permitted when the machine s compliance with the EMC directive (89/336/EEC) has been established and the final product s conformity with the machine directive 89/392/EEC was certified (observe EN 60204). Getriebebau NORD GmbH & Co. KG, 2005 BU 0500 GB 3

4 NORDAC SK 500E / 520E Handbook 1 GENERAL INFORMATION Overview Delivery Scope of delivery Safety and installation information Approvals European EMC guideline UL and cul approval Type code / device variant ASSEMBLY AND INSTALLATION Installation SK 500E / 520E dimensions SK 500E / 520E wall mount bracket EMC kit Brake resistor (BR) Electrical data BR Dimension food-print BR Dimension chassis BR Wiring guidelines Electrical connections Electrical power unit connections Mains connection (X1 - PE, L1, L2/N, L3) Multi-function relays (X3-1, 2, 3, 4) Motor cable (X2 - U, V, W, PE) Braking resistor terminal (X2 - +B, -B) Direct coupling (X2 - +B, -DC) Network input jumper A Motor output jumper B Internal jumper interconnection Electrical connection of control unit Control terminal details Colour and pin assignment for incremental encoders DISPLAY AND OPERATION Modules Technology unit overview SimpleBox, SK CSX ControlBox, SK TU3-CTR ParameterBox, SK TU3-PAR ParameterBox parameters ParameterBox error messages Profibus module, SK TU3-PBR, -24V CANopen bus module SK TU1-CAO DeviceNet module, SK TU3-DEV InterBus module, SK TU3-IBS AS interface, SK TU3-AS BU 0500 GB

5 Table of contents 4 COMMISSIONING Factory settings Minimum configuration for control connections PARAMETERISATION Operating parameter display Basic parameters Motor data/characteristic curve parameters Control parameters Control terminals Extra functions Information Parameter overview, user settings FAULT MESSAGES SimpleBox/ControlBox display Table of possible error messages TECHNICAL DATA General data SK 500E / 520E Electrical data, 230 V Electrical data, 400 V Electrical data for UL/cUL approval ADDITIONAL INFORMATION Set point processing in SK 500E / 520E Process controller Process controller application example Process controller parameter settings Electromagnetic compatibility (EMC) EMC limit value classes Reduced output power Reduced output current due to pulse frequency Reduced over current due to time Reduced over current due to output frequency Reduced output current due to mains voltage Reduced output current due to heat sink temperature FI circuit breaker operation Maintenance and servicing information KEYWORD INDEX REPRESENTATIVES / BRANCHES BU 0500 GB 5

6 NORDAC SK 500E / 520E Handbook 1 General information The NORDAC SK 500E / 520E series is based on the tried and tested NORD platform. The distinguishing features of this equipment are the compact design and excellent control characteristics. These devices are provided with sensorless vector current control system which constantly ensures an optimised voltage-to-frequency ratio based on the simulated operation of a three-phase asynchronous motor. This has the following significance for the drive: the highest level of start-up and overload torque at constant speed. The modular technology boxes allow this device series to be adapted to individual demands. Owing to the huge variety of setting options these inverters are capable of controlling any three-phase motor. The output ranges from 0.25kW to 7.5kW with integrated line filter. The overload capacity of this equipment is for 3.5 seconds at 200% and for 60 seconds at 150%. The present manual applies to device software V1.3 R1 (P707) of the SK 500E / 520E. Other frequency inverter software versions may result in differences. Download the latest manual from the Internet ( if necessary. 1.1 Overview Characteristics of the SK 500E base unit: Heavy starting torque and precise motor speed control setting by sensorless current/vector control. Can be mounted adjacent to each other without additional spacing Permitted environmental temperature range 0 to 50 C (please refer to technical data) Integrated EMC line filter for limit class A1 as per EN55011 Automatic stator impedance measurement or determination of exact motor data Programmable direct current braking Integrated brake chopper for 4 quadrant drive 5 digital inputs, 2 analogue inputs, 2 relay outputs and 1 analogue output Four separate online switchable parameter sets RS232/485 interface via RJ12 connector Additional characteristics of the SK 520E base unit: 2 CANbus interfaces via RJ45 connector Additional RS485 interface via terminals 2 digital inputs and 2 digital outputs Rotation speed feedback via incremental encoder input Safe stop function in preparation NOTE: The SK 500E and SK 520E base units feature different characteristics. This will be accordingly pointed out in the present manual. 6 Subject to technical changes BU 0500 GB

7 1. General information 1.2 Delivery Check the equipment immediately after delivery/unpacking for transport damage such as deformation or loose parts. If there is any damage, contact the carrier immediately and implement a thorough assessment. Important! This applies even if the packaging is undamaged. 1.3 Scope of delivery Standard version: IP20 Integrated brake chopper Integrated EMC line filter for limit curve A1 as per EN55011 Cover for technology box slot Shielding clamp for control terminals Cover for the control terminals Instruction manual Available accessories: Brake resistor for energy recovery RS232 RS485 interface converter (supplementary description BU 0010) NORD CON, PC / Parameterisation Software > < eplan Macros for constructing electrical circuit diagram > < EMV- Kit (SK EMC 1-1, SK EMC 1-2) Chap. 2.4 Technology box, Chap.3.2: SK CSX-0, SimpleBox, removable control panel, 4-digit 7 segment LED display, single-button operation SK TU3-CTR, ControlBox, removable control panel, 4-digit 7 segment LED display, keyboard SK TU3-PAR, ParameterBox, removable control panel, multi-line clear text LCD, keyboard SK TU3-PBR, additional module for Profibus communication (1.5 MBaud) SK TU3-PBR-24V, Profibus, with external 24 V supply (12 MBaud) SK TU3-CAO, CANopen, bus interface SK TU3-DEV, DeviceNet, bus interface SK TU3-IBS, InterBus, bus interface SK TU3-AS1, AS interface NOTE: Additional BUS descriptions are available... > < BU 0500 GB Subject to technical changes 7

8 NORDAC SK 500E / 520E Handbook 1.4 Safety and installation information NORDAC SK 500E / 520E frequency inverters are equipment for use in industrial high voltage systems and are operated at voltages that could lead to severe injuries or death if they are touched. Installation and other work is only permitted by qualified electricians and when the device is disconnected. The manual must always be available for these persons and must be complied with. Local regulations for the installation of electrical equipment as well as for accident prevention are to be observed. The equipment continues to carry hazardous voltages for up to 5 minutes after being switched off at the mains. Mains impedance must be at least 100 μh per circuit in case of single-phase operation (230 V). Otherwise, a line choke must be connected in series. To ensure safe separation from mains, all power cable poles to the frequency inverter must be separated. Even during motor standstill (e.g. caused by a release block, blocked drive or output terminal short circuit), the line connection terminals, motor terminals and braking resistor terminals may still conduct hazardous voltages. A motor standstill is not identical to galvanic isolation from the mains. Caution: Even parts of the control card and, in particular, the connection plug for the removable technology units can conduct hazardous voltages. The control terminals are mains voltage free. Caution: Under certain settings the inverter can start automatically after the mains are switched on. The inverter is only intended for permanent connection and may not be operated without effective earthing connections that comply with local regulations for high leakage currents (> 3.5mA). VDE 0160 requires the installation of a second earthing conductor or an earthing conductor crosssection of at least 10 mm 2. Normal FI-circuit breakers are not suitable as the sole protection in three-phase frequency inverters when local regulations do not permit a possible DC proportion in the fault current. The standard FI circuit breaker must comply with the new design as per VDE NORDAC SK 500E / 520E frequency inverters are maintenance-free when used correctly. The cooling surfaces must be regularly cleaned with compressed air if the ambient air is dusty. ATTENTION The heat sink and all other metal parts can heat up to temperatures exceeding 70 C. Install the unit only with sufficient distance to adjacent components. Before working on components allow for a sufficient cooling period. WARNING DANGER TO LIFE! The power unit can continue to carry voltages for up to 5 minutes after being switched off at the mains. Inverter terminals, motor cables and motor terminals may carry voltage! Touching open or free terminals, cables and equipment components can lead to severe injury or death! 8 Subject to technical changes BU 0500 GB

9 1. General information CAUTION Children and the general public must be kept away from the equipment! The device may only be used for the purpose intended by the manufacturer. Unauthorised modifications and the use of spare parts and additional equipment that has not be bought from or recommended by the equipment manufacturer can lead to fire, electric shock and injury. Keep this instruction manual in an accessible location and ensure that every operator uses it! WARNING This product is covered under marketing classification IEC In a domestic environment, this product can cause high frequency interference, which may require the user to take appropriate measures. An appropriate measure would be the inclusion of a recommended line filter. 1.5 Approvals European EMC guideline If the NORDAC SK 500E / 520E is installed according to the instructions in this handbook, it will meet all requirements of the EMC guideline, as per the EMC product standard for motoroperated systems EN (see also chapter 8.3 Electromagnetic Compatibility [EMC].) UL and cul approval (Use in North America) - in preparation - Suitable for use on a circuit capable of delivering not more than 5000 rms symmetrical amperes, Volts or Volts (three phase) and when protected by J class fuses. as indicated." Suitable for use with a mains supply with maximum short circuit current (symmetrical) of 5000 A, V or V (3 phase) and protected by a "J class fuse" as described in Chapter 7.4. NORDAC SK 500E / 520E frequency inverters have motor overload protection. Further technical detail can be found in Chapter 7.4. BU 0500 GB Subject to technical changes 9

10 NORDAC SK 500E / 520E Handbook 1.6 Type code / device variant SK 500E A Noise suppression filter class: O = without, A or B limit value Mains voltage: x23 = 230 V, x40 = 400 V Number of mains phases: 1 = single-phase, 3 = 3-phase * Power digit to the left of the separator: 0 = 0.xx, 1 = 0x.x0, 2 = 0xx.0 Rated device power (xx): 25 = 0.25kW, 37 = 0.37kW, = 7.5kW Device series: SK 500E / SK 520E *) 3 also applies to combination devices suitable for single- and 3-phase operation (also refer to technical data) Wall mount bracket Optional technology box Additional control terminals: SK 520E only Control terminals Encoder input: SK 520E only Optional EMC kit: Shielding bracket, clamp and toroidal ferrite 10 Subject to technical changes BU 0500 GB

11 2 Assembly and installation 2 Assembly and Installation 2.1 Installation NORDAC SK 500E / 520E frequency inverters are available in various sizes depending on the output. Heed a suitable installation position. The equipment requires sufficient ventilation to protect against overheating. Guide values apply here for the space above and below the inverter to neighbouring components that could restrict the air flow. (above > 100 mm, below > 100 mm) Mounting can be adjacent. The installation position must be vertical. Make sure that the heat sink fins at the rear of the device are on a level surface to ensure proper cooling. 100mm 100mm Warm air must be able to escape above the equipment! If several frequency inverters are arranged above each other, ensure that the air entry temperature limit is not exceeded. (see also chap. 7, technical data). In this case, it is recommended that any obstacles (e.g. a cable duct) are mounted between the inverters so that the direct air flow (rising warm air) is interrupted. Heat loss: Ensure sufficient ventilation when the devices are installed in a control cabinet. The lost heat is approximately 5% (depending on the device size and configuration) of the rated frequency inverter output. BU 0500 GB Subject to technical changes 11

12 NORDAC SK 500E / 520E Handbook 2.2 SK 500E / 520E dimensions Device type Size Housing dimensions Wall mount (chap. 2.3) A B C D, approx. Weight ca. [kg] SK 5xxE-250- SK 5xxE-750- SK 5xxE-111- SK 5xxE-221- SK 5xxE-301- SK 5xxE-401- SK 5xxE-551- SK 5xxE-751- BG * BG * BG BG *) if FP brake resistors in use = 88 mm (chap. 2.5) all dimensions in [mm] B C A 12 Subject to technical changes BU 0500 GB

13 2 Assembly and installation 2.3 SK 500E / 520E wall mount bracket The SK 500E / 520E comes with 2 suitable brackets for panel mounting. These can be pushed into the heat sink at the device rear as shown in the illustration. No accessories are needed to do this! As an alternative you can also push the wall mount brackets laterally into the heat sink in order to minimise the required control cabinet depth if necessary. Make sure to always cover the heat sink rear with a level surface and to install the device in a vertical position. This will result in optimum convection and ensure trouble-free operation. A D B BU 0500 GB Subject to technical changes 13

14 NORDAC SK 500E / 520E Handbook 2.4 EMC kit To comply with the conducted radio interference suppression level B1 (see chapt. 8.4), the optional EMC kit must be implemented. It comprises a shielding bracket, a clamp and a toroidal ferrite. Fasten the shielding bracket at the lower edge (below the U-V-W terminals) with the two housing screws. The screen clamp serves to connect a large motor cable shielding area to the shielding bracket. Simply route the 3 lines for the motor phases (U-V-W) through the toroidal ferrite (without PE!). Do this as close as possible to the terminals without shielding. Device type Size EMC kit SK 5xxE-250- SK 5xxE-750- SK 5xxE-111- SK 5xxE-221- SK 5xxE-301- SK 5xxE-401- SK 5xxE-551- SK 5xxE-751- BG1 BG2 BG3 BG4 SK EMC 1-1 Mat. Nr SK EMC 1-2 Mat. Nr Subject to technical changes BU 0500 GB

15 2 Assembly and installation 2.5 Brake resistor (BR) When dynamically braking a 3 phase motor (reducing the frequency) electrical energy is fed back into the inverter. To avoid an overvoltage shutdown of the inverter, an external brake resistor can be used. The internal brake chopper (an electronic switch) then pulses the intermediate circuit voltage onto the brake resistor (threshold level approx 420V/720V dc, according to supply voltage). The brake resistor transforms the surplus energy into heat. VORSICHT The heat sink and all other metal parts can heat up to temperatures exceeding 70 C. Install the unit only with sufficient distance to adjacent components. Before working on components allow for a sufficient cooling period. For inverter powers up to 2,2 kw a standard resistor for mounting directly below the inverter can be used (SK BR4-..., IP40). The resistor can be equipped with an optional thermal switch (Bimetalic, 180 C threshold) to report a possible overload. Fixing material is included in the lateral slot. The resistor and the optional thermal switch are connected to the inverter via wires. Approvals: UL, cul SK BR4-... size 1 SK BR4-... size 2 For inverter powers 3kW to 7.5kW stand alone chassis resistors are available (SK BR2-..., IP00). These resistors must be mounted in the switching cabinet close to the inverter. As standard a thermal switch is fitted to the resistor to report overloading. The resistor and the thermal switch are connected to the inverter via terminals and wires. Approvals: UL, cul SK BR2-... size 3 SK BR2-... size 4 BU 0500 GB Subject to technical changes 15

16 NORDAC SK 500E / 520E Handbook Electrical data BR Inverter type Resistor type resistance perm. power SK 5xxE A SK 5xxE A SK 5xxE A SK 5xxE A SK 5xxE A SK 5xxE A SK 5xxE A SK 5xxE A SK 5xxE A SK 5xxE A SK 5xxE A SK 5xxE A SK 5xxE A SK 5xxE A SK 5xxE A SK 5xxE A energy absorption * SK BR4-240/ Ω 100 W 1.0 kws SK BR4-150/ Ω 100 W 1.0 kws SK BR4-75/ Ω 200 W 4.0 kws connecting cable /-clamp 2 x 1.9 mm 2 AWG 14/19 L = 0.5m SK BR2-35/400-C 35 Ω 400 W 6.0 kws 2 x 10 mm 2 SK BR4-400/ Ω 100 W 0.75 kws SK BR4-220/ Ω 200 W 4.0 kws SK BR2-100/400-C 100 Ω 400 W 6.0 kws SK BR2-60/600-C 60 Ω 600 W 7.5 kws 2 x 1.9 mm 2 AWG 14/19 L = 0.5m 2 x 10 mm 2 *) maximal once in 120s Temperature switch, Bimetal enclosure voltage Strom dimensions Connecting cable /-clamp cable 2 x 0.8 mm 2 2,5 A with cosϕ=1 width +10mm SK BR4-... IP Vac AWG 18 1,6 A with cosϕ=0.6 (one-sided) L = 0.5m 250 Vac 10 A clamps SK BR2-... IP Vac 15 A intern 2 x 4 mm 2 30 Vdc 5 A 16 Subject to technical changes BU 0500 GB

17 2 Assembly and installation Dimension food-print BR Resistor type Frame size A B C D Mounting size SK BR4-240/100 SK BR4-150/100 BG SK BR4-75/200 SK BR4-100/400 SK BR4-220/200 BG C = depth of the Inverter + food-print BR All dimensions in mm B C B C A D NORDAC SK 500E / 520E A D NORDAC SK 500E / 520E Dimension chassis BR SK BR4-... frame size 1 SK BR4-... frame size 2 optional temperature switch Resistor type A B C Mounting size D E SK BR2-100/400-C SK BR2-35/400-C SK BR2-60/600-C All dimensions in mm C B E D A SK BR2-... frame size 3/4 (frame size varied by the power) BU 0500 GB Subject to technical changes 17

18 NORDAC SK 500E / 520E Handbook 2.6 Wiring guidelines The frequency inverter has been developed for use in an industrial environment. In this environment, high levels of electromagnetic interference can have an effect on the frequency inverter. In general, correct installation ensures safe and problem-free operation. In order to conform to the EMC guidelines, the following instructions should be adhered to. (1) Ensure that all equipment in the control cabinet or panel is securely earthed using short earthing cables that have large cross-sections and which are connected to a common earthing point or earthing bar. It is particularly important that each controller (e.g. automation device) is connected to the frequency inverter with a short, large profile cable and to the same grounding point as the inverter itself. Flat conductors (e.g. metal brackets) are preferable as they have low impedance at higher frequencies. (2) The PE lead of the motor controlled by the frequency inverter must be connected as directly as possible to the earth connection of the associated frequency inverter. The presence of a central earthing bar and the grouping together of all PE conductors to this bar normally ensures safe operation. (see also chap. 8.3/8.4 EMC) (3) Where possible, screened cables should be used for control signals. During installation, the shielding at the cable end should be carefully closed off, and care taken that the wires do not have long runs without shielding. The shields of analogue set point cables should only be earthed on one side on the frequency inverter. (4) The control cables must be kept distant from load cables by using separate cable ducts, etc. If cables cross, then an angle of 90 should be used where possible. (5) Ensure that the contactors in the cabinet are interference protected, either by RC circuits in the case of AC contactors or by free-wheeling diodes for DC contactors, for which the interference traps must be positioned on the contactor coils. Varistors for over-voltage limitation are also effective. This interference suppression is particularly important when the contactors are controlled by the relays of the frequency inverter. (6) Use screened or armoured cable for the load connections (motor cables) and earth the screening/armour at both ends. If possible, earthing should directly occur on the conductive control cabinet mounting plate of the EMC kit shielding bracket (chapt. 2.4). In addition, it is essential to use wiring suitable for EMC. (see also chap. 8.3/8.4 EMC) An optional output choke is available on request. The safety regulations must be complied with under all circumstances when installing frequency inverters! Note The control cables, line cables and motor cables must be laid separately. In no case should they be laid in the same protective pipes/installation ducts. The test equipment for high voltage insulations must not be used on cables that are connected to the frequency inverter. 18 Subject to technical changes BU 0500 GB

19 2 Assembly and installation 2.7 Electrical connections WARNING THIS EQUIPMENT MUST BE EARTHED. Safe operation of the equipment presupposes that qualified personnel mount and operate it in compliance with the instructions provided in this handbook. In particular, the general and regional mounting and safety regulations for work on high voltage systems (e.g. VDE) must be complied with as must the regulations concerning professional use of tools and the use of personal protection equipment. Dangerous voltages can be present at the line input and the motor connection terminals even when the frequency inverter is switched off. Always use insulated screwdrivers on these terminal fields. Ensure that the input voltage source is not live before setting up or changing connections to the unit. Make sure that the inverter and motor have the correct supply voltage set. BU 0500 GB Subject to technical changes 19

20 NORDAC SK 500E / 520E Handbook 2.8 Electrical power unit connections The line and brake resistor terminals are located on the frequency inverter top. The motor and brake resistor terminals are located on the frequency inverter bottom. The control terminals can be reached from the frequency inverter front. To do so, push the terminal cover (underneath the TU slot) down and remove it if necessary. The terminals are now accessible. X1 - PE L3 L2 L1 X L1 / L L2 / N L3 / - PE Heed the following before connecting the device: 1. Ensure that the electrical supply is of the correct voltage and is suitable for the current required (see Chapter 7, Technical data) 2. Ensure that suitable circuit breakers with the nominal current range are inserted between the electrical supply and the frequency inverter. 3. Connect the line voltage directly to the line terminals L 1 -L 2 /N-L 3 -PE (depending on the device). 4. A four core shielded cable must be used to connect the motor. The cable must be connected to the motor terminals PE-U-V-W. 5. When shielded motor cables are used (recommended), the cable shield must be connected to as much surface as possible on the EMC kit shielding bracket (Chapt. 2.4), but at least to the conductive assembly plate of the control cabinet. X2 - PE U V W +B -B -DC Ext. braking resistor M 3~ NOTE: When using particular wiring sleeves, the maximum cable cross section may be reduced. Screwdriver: for connecting the power module use a cross-point screwdriver (Pozidriv/Supadriv size: 1). NOTE: If synchronous machines or several motors are connected parallel to a device, the frequency inverter must be driven by a linear voltage/frequency characteristic curve P211 = 0 and P212 = 0. NOTE: The use of shielded cables is essential in order to maintain the specified noise suppression level. (see also chapt. 8.4 EMC limit value classes) NOTE: This unit can cause RFI interference. In residential areas RFI suppression may be required. (Details in Ch. 8.3/8.4) 20 Subject to technical changes BU 0500 GB

21 2 Assembly and installation Mains connection (X1 - PE, L1, L2/N, L3) Special protection is not required on the frequency inverter mains input. We recommend to use standard mains fuses (see Technical data) and a master power switch or contactor. 230 V devices from 0.25 kw to 2.2 kw may be operated either with one 230 V (L/N = L1/L2) or three 230 V (L1/L2/L3) phases. All 400 V devices and 3 kw must be supplied with three-phase mains voltage (L1/L2/L3) only. For more detailed specifications please refer to the technical data in chapt. 7. NOTE: The use of these frequency inverters on the IT network is possible after an adaptation with the jumper. For more details see chapt Cable cross-section: mm 2 solid cable mm 2 flexible cable AWG Multi-function relays (X3-1, 2, 3, 4) Parameters P434 through P443 let you set the function of these relays as desired. The maximum contact rating is 230 V AC / 24 V DC, 2 A. In the factory setting, the closed contact on terminals 3-4 (output 2, P441) indicates the frequency inverter s operational readiness. The contact is open when an error message is pending or the frequency inverter is de-energised. In the factory setting, terminals 1-2 (output 1, P434) can drive a mechanic motor brake that is thus accordingly released or applied. The appropriate delays ( secs) must be specified in parameters P107/P114 to optimise the timing. Cable cross-section: mm 2 solid cable mm 2 flexible cable AWG BU 0500 GB Subject to technical changes 21

22 NORDAC SK 500E / 520E Handbook Motor cable (X2 - U, V, W, PE) The motor cable may have a total length of 100 m in case a standard cable is used. If a shielded motor cable is used, or the cable is routed in a well earthed metallic cable duct, the maximum length of 30 m should not be exceeded. For longer cable lengths, an additional output choke (accessory) must be used. Note: Please also refer to chapter 8.4 EMC limit value classes. Note: For multiple motor use the total cable length consists of the sum of the individual cable lengths. Cable cross-section: mm 2 solid cable mm 2 flexible cable AWG Braking resistor terminal (X2 - +B, -B) Terminals +B/ -B are provided for connecting a suitable braking resistor. A shielded cable should be selected that is as short as possible. Note: Please note that the braking resistor generates a significant amount of heat. Attention! Terminals +B, -DC can be used for direct coupling of several frequency inverters. Never connect a braking resistor to -DC! Further details on direct coupling can be found in chapt Cable cross-section: mm 2 solid cable mm 2 flexible cable AWG Subject to technical changes BU 0500 GB

23 2 Assembly and installation Direct coupling (X2 - +B, -DC) Direct coupling in drive technology is feasible if several drives in a system operate as motor and generator. In this case the energy from the drive acting as the generator is fed back into the drive motor. There are advantages with regard to energy consumption and the use of braking resistors. However, the following must be considered: (1) Use a cable as short as possible between devices to be connected. (2) Make sure coupling is established only after the ready signal has been received. Otherwise there is a risk that all frequency converters are loaded via one charge circuit. (3) Make sure the coupling is separated as soon as one of the devices is no longer operable. (4) To ensure a high availability, use a (low-power) braking resistor. (5) Frequency inverters may also be operated without mains choke when coupling devices of the same power (identical type) and when identical mains impedances apply (identical cable length to the mains bar). Otherwise, implement a mains choke in each frequency inverter s power cable. Principle view of a direct coupling: L1 / L L2 / N L3 / - PE PE L3 L2 L1 PE L3 L2 L1 U1 Ready signal from all frequency inverters U2 PE U V W +B -B -DC PE U V W +B -B -DC M 3~ Coupling when frequency inverters are ready M 3~ BU 0500 GB Subject to technical changes 23

24 NORDAC SK 500E / 520E Handbook Network input jumper A Set this jumper to position 0 to make frequency inverts SK 500E / 520E suitable for the IT network. Please note that this will change the specified radio interference suppression level. Further details can be found in chapt. 8.3 EMC. = IT network operation = position 0 Device top side = n/a = position 1 = normal position = position Motor output jumper B These jumpers make the device suitable for IT networks and reduce the frequency inverter leakage current against PE. This may be necessary if several frequency inverters are operated on one FI-circuit breaker. Please note that this will change the specified radio interference suppression level. Further details can be found in chapt. 8.3 EMC. = IT network operation = position 0 Device bottom side = normal position = position 1 = reduced leakage current = position Internal jumper interconnection L1 L2/N L3 Cx Cx Cx ~ = L = ~ M Cy Cy Cy Cyzk Cyzk Cyzk Cyzk Jumper A Jumper B 24 Subject to technical changes BU 0500 GB

25 2 Assembly and installation 2.9 Electrical connection of control unit The control terminals are located under the frequency inverter front panel. The configuration depends on the device type (SK 500E or SK 520E). Terminal blocks: Spring clamp terminal blocks can be released with a small screwdriver Cable cross-section: mm 2, AWG 26-16, solid or flexible Cable: Lay and shield separately from the line/motor cables Control voltages: (short-circuit proof) 5V ± 20%, max. 250mA, for supplying an incremental encoder 10V, max. 5mA, reference voltage for an external potentiometer 15V ± 20%, max. 150mA, for supplying the digital inputs or an incremental encoder Analogue output V, max. 20mA, for an external display unit NOTE AGND and DGND are common reference potentials for analogue or digital inputs. 5 / 15V can be taken from several terminals if necessary. The sum total of drawn currents must not exceed 250mA / 150mA. Terminal blocks: X7: Additional digital inputs and outputs for SK 520E only X4: Analogue inputs and outputs +10V max. 5mA V or 0/4...20mA X5: digital inputs and power supply R i ca. 4.5kΩ +15V max. 150mA +5V max. 250mA DIP switch: Selects analogue inputs AIN1 / AIN2 current/voltage setpoint I = current 0/4...20mA V = voltage V ATTENTION: AIN2 upper DIP switch AIN1 lower DIP switch X6: Incremental encoder input Encoder, e.g.: 10-30V,TTL,RS pulses/rev. for SK 520E only BU 0500 GB Subject to technical changes 25

26 NORDAC SK 500E / 520E Handbook Control terminal details Terminal Function [factory setting] Data Description/ circuit recommendations Parameter Terminal block X3 1 K1.1 2 K1.2 3 K2.1 4 K2.2 Output 1 (K1) [Brake control] Output 2 (K2) [ready / error] Relais NO contact Brake control P V AC / 24 V DC, 2 A Error / ready for operation P Terminal block X4 11 VO +10V 10 V reference voltage 10 V; 5 ma 12 AGND/0V Reference potential of analogue signals 14 AIN1 Analogue input 1 [set point frequency] 16 AIN2 Analogue input 2 [no function] 17 AOUT1 Analogue output [no function] 0 V analogue V= V, R i =10 kω, I=0/ ma, R i =250 Ω, switch with DIP switch, reference potential GND V when digital functions are used V, 20 ma, reference potential GND The analogue input controls the frequency inverter output frequency R = 10k Possible digital functions are described in parameters P420...P425. P P Can be used for external display or processing by a downstream machine. P418/419 Terminal block X5 21 DIG1 Digital input 1 22 DIG2 Digital input 2 23 DIG3 Digital input 3 [IN right] [IN right] [parameter set bit0] 24 DIG4 Digital input 4 [fixed frequ. 1, P429] 25 DIG5 Digital input 5 [no function] 42 VO +15V 15 V power supply 40 DGND Reference potential of digital signals V, R i =6.1 kω V, R i =2.2 kω, suitable for PTC evaluation with +5V supply 15 V ± 20%, 150 ma 0 V digital ground Each digital input has a reaction time of 1 2 ms motor - PTC V DGND Power supply for the digitale input or an encoder 41 VO +5V 5 V power supply 5 V ± 20%, 250 ma Power supply for motor PTC P420 P421 P422 P423 P Subject to technical changes BU 0500 GB

27 2 Assembly and installation Terminal Function [factory setting] Data Description/ circuit recommendations Parameter Terminal block X6 (SK 520E only) 40 DGND Reference potential of digital signals 51 ENCA+ Track A 0 V digital The incremental encoder input is suitable for exact speed regulation or auxiliary set point functions. 52 ENCA- Track A inverted 53 ENCB+ Track B 54 ENCB- Track B inverted TTL, RS pulses/rev. We recommend to use an encoder system with V supply voltage, for compensate a voltage drop due to long cable connections. P300 P327 Terminal block X7 (SK 520E only) RS485 data line 26 DIG6 digital input 6 27 DIG7 digital input 7 [no function] [no function] 5 DOUT1 Output 3 (DOUT 1) [no function] 7 DOUT2 Output 4 (DOUT 2) [no function] Baud rate Baud V, R i =3.3 kω as described for X5 Digital output 15 V, max. 20 ma 42 VO +15V 15 V supply 15 V ± 20%, 150 ma 40 DGND Reference potential of digital signals 0 V digital Bus connection, parallel to RJ12 connector For evaluation in a controller. The function range corresponds to that of the relays (P434/441). P502 P513 P425 P470 P450 P452 P455 P457 BU 0500 GB Subject to technical changes 27

28 NORDAC SK 500E / 520E Handbook Terminal Function [factory setting] Data Description/ circuit recommendations Parameter RJ12, RS485/RS232 connector block 1 RS485 A 2 RS485 B RS485 data line Baud rate Baud 3 GND Reference potential of bus signals TXD RXD RS232 data line 6 +5V Internal 5 V power supply 0 V digital Baud rate Baud 5 V ± 20%, 250 ma RS485_A RS485_B GND TXD RXD +5V RJ12: pin No. 1 6 P502...P513 optional Adapter cable RJ12 to SUB-D9... for the direct connection of an PC with NORD CON length 3m function RS 232 (RxD, TxD, GND) Mat. Nr x RJ45, CANbus/CANopen connector block (SK 520E only) 1 CAN_H 2 CAN_L CANbus signal 3 CAN_GND CANbus GND Baud rate 500 kbaud 4 nc 5 nc no function 6 CAN_SHD Cable shield 7 CAN_GND CANbus GND RJ45 connectors are wired in parallel. Terminator resistor R=120 Ω DIP 2 (left of sockets) CAN _H CAN _L CAN _GN D nc nc CAN _SHLD CAN _GN D CAN _24V CAN _H CAN _L CAN _GN D nc nc CAN _SHLD CAN _GN D CAN _24V P502...P515 8 CAN_24V External 24V power supply RJ45: pin No Subject to technical changes BU 0500 GB

29 2 Assembly and installation 2.10 Colour and pin assignment for incremental encoders Function Incremental encoder cable colours SK 520E assignment 10-30V supply X5.42 VO +15V brown / green (5V if available only) (X5.41 VO +5V) 0 V supply white / green X6.40 DGND Track A brown X6.51 ENC A+ Track A inverted green X6.52 ENC A- Track B grey X6.53 ENC B+ Track B inverted pink X6.54 ENC B- Track 0 red -- Track 0 inverted black -- Cable shield Spread out and linked to the frequency inverter housing and to the shielding angle NOTE: When deviating from the standard equipment (A.781.4, 10-30V encoder, TTL/RS485) for the motors, please pay attention to the accompanying data sheet or consult your supplier. RECOMMENDATION: To increase operational safety, in particular when using long connection cables, we recommend to use a higher supply voltage (15V/24V) and an incremental encoder for 10-30V. ATTENTION The rotational direction of the incremental encoder should correspond to that of the motor. Therefore, depending on how the encoder has been mounted onto the motor (possibly the wrong way round) you must set a negative pulse number in parameter P301. BU 0500 GB Subject to technical changes 29

30 NORDAC SK 500E / 520E Handbook 3 Display and operation The delivery state features 2 LEDs (green/red) visible from the outside. These indicate the current device state. The green LED indicates the presence of mains voltage and, during operation, the overload level of the frequency inverter output by flashing increasingly faster. The red LED indicates pending errors by flashing at an interval corresponding to the error number code (chapt. 6). 3.1 Modules By combining different modules for display, control and parameterisation, the NORDAC SK 500E / 520E can be conveniently adapted to various demands. Alphanumerical display and operating modules can be used for simple initialisation. For more complex tasks, various connections to a PC or an automation system can be selected. The Technology Unit, SK TU3-... is plugged onto the frequency inverter from the outside and is thus conveniently accessible and replaceable whenever needed. LED red/green WARNING Modules must not be inserted or removed unless the device is free of voltage. The slots are for use with the respective modules only. Installation of a technology box separate to the frequency inverter is not possible. It must be connected directly to the frequency inverter. Further detailed information can be found in the option handbooks Subject to technical changes BU 0500 GB

31 3.1 Modules 3.2 Technology unit overview Option Description Data SimpleBox SK CSX-0 ControlBox SK TU3-CTR ParameterBox SK TU3-PAR Profibus module SK TU3-PBR Profibus module SK TU3-PBR-24V CANopen module SK TU3-CAO DeviceNet module SK TU3-DEV InterBus Module SK TU3-IBS AS interface SK TU3-AS1 For commissioning, parameterisation, configuration and control of the frequency inverter. No function to store a data set. For commissioning, parameterisation, configuration and control of the frequency inverter. Data set storage function via P550 is possible. For commissioning, parameterisation, configuration and control of the frequency inverter. Maximum 5 total data set are possible to store. This option enables control of the SK 500E / 520E via the Profibus DP serial port. This option enables control of the SK 500E / 520E via the Profibus DP serial port. This option enables control of the SK 500E / 520E via the CANbus serial port, using the CANopen protocol This option enables control of the SK 500E / 520E via the DeviceNet serial port. using the DeviceNet protocol. This option enables control of the SK 500E / 520E via the InterBus serial port. Actuator sensor interface is a bus system for the lower field bus layer suitable for simple control tasks. 4-digit, 7-segment LED display, single-button operation Mat. No digit, 7-segment LED display, keyboard Mat. No digit backlit LCD, keyboard Mat. No Baud rate: 1.5 MBaud Connector: Sub-D9 Mat. No Baud rate: 12 MBaud Connector: Sub-D9 External 24 V power supply, 2-pole terminal block Mat. No Baud rate: up to 1 MBit/s Connector: Sub-D9 Mat. No Baud rate: 500 kbit/s 5 pole screw clamp Mat. No Baud rate: 500 kbit/s (2 Mbit/s) Connectors: 2 x Sub-D9 Mat. No sensors / 2 actuators 5-/8-pole screw clamp Mat. No Mounting The technology boxes must be installed as follows: 1. Switch off the mains voltage, observe the waiting period. 2. Slide control terminal cover down somewhat or remove it. 3. Remove the dummy cover by rotating the unlocking device on the bottom edge upwards. Remove the fixation screw next to the latch if necessary. 4. Hook in the technology unit at the upper edge and let it engage by pushing slightly. Make sure the connectors make proper contact and fasten with screws if necessary (accessory kit). 5. Close control terminal cover again. BU 0500 GB Subject to technical changes 31

32 NORDAC SK 500E / 520E Handbook SimpleBox, SK CSX-0 This option is used as a simple parameterisation and display tool for frequency inverter SK 500E / 520E. Characteristics 4-digit, 7-segment LED display Single-button frequency inverter operation Display of active parameter set and operating value The 4-digit 7-segment display shows horizontal dashes after the SimpleBox was installed and the mains voltage switched on. These indicate the operational readiness of the frequency inverter. The display toggles between 0.0 Hz and the value in P113 if a jog frequency was set in parameter P113. If the frequency inverter is enabled, the display changes automatically to the operating value selected in parameter >Selection Display Value< P001 (factory setting = current frequency). The current parameter set is shown by the 2 LEDs below the display in binary code. NOTE Settings may only be carried out by qualified personnel in compliance with safety and warning information. Mounting You can install the SimpleBox on any Technology Unit (SK TU3-...) or the dummy cover from above. To remove, simply pull it off after having unplugged the RJ12 connector (actuate the release lever on the RJ12 connector). Connection Directly connect the SimpleBox with the RJ12 connector/cable (RS485) to the socket on the frequency inverter top edge. If necessary, use DIP switch 1 (left) to enable a bus terminator resistor for the RS485 interface. This may be necessary if the frequency inverter is remotely controlled by a higher level controller. RJ12 Device top side 2 RJ45, for SK 520E only 32 Subject to technical changes BU 0500 GB

33 3.1 Modules SimpleBox functions: 7-segment LED display LEDs Shows the currently set operating value (selection in P001) or the error codes (chapt. 6). During parameterisation, the parameter numbers or the parameter values are shown. The LEDs indicate in the operating display (P000) the current operating parameter set and during parameterisation the current parameter set being parameterised. The display appears in binary form here = P1 1 2 = P2 1 2 = P3 1 2 = P4 Turn button to the right Turn button to the left Press button briefly Press button longer Turn the button to the right to increase the parameter number / parameter value. Turn the button to the left to decrease the parameter number / parameter value. Press button briefly = "ENTER" function to store an altered parameter value, or to switch between parameter number and parameter value. Pressing the button for longer causes the display to switch to the next higher level without saving any parameter values that may have been changed. Menu structure with the SimpleBox Operating values display (and ready to operate), following mains ON P7-- P6-- P5-- P0-- P001 P002 P1-- P100 P101 P2-- P200 P201 P3-- P300 P301 P4-- P400 P401 P003 P114 P220 P327 P483 NOTE: Parameters P502, P701 through 706, P707, P718, P741/742 and P745/746 also have an array level, in which further settings can be made, e.g. P502 ENTER P_01 ENTER off setting: Master function 1 value VALUE P_02 ENTER off setting: Master function 2 value BU 0500 GB Subject to technical changes 33

34 NORDAC SK 500E / 520E Handbook ControlBox, SK TU3-CTR This option is used as a simple parameterisation, display and control tool for frequency inverter SK 500E / 520E. Characteristics 4-digit, 7-segment LED display Direct control of a frequency inverter Display of active parameter set and operating value Storage of a complete inverter data record (P550) The 4-digit 7-segment display shows horizontal dashes after the ControlBox was installed and the mains voltage switched on. These indicate the operational readiness of the frequency inverter. The display toggles between 0.0 Hz and the value in P113 if a jog frequency was set in parameter P113. If the frequency inverter is enabled, the display changes automatically to the operating value selected in parameter >Selection Display Value< P001 (factory setting = current frequency). The current parameter set is shown by the 2 LEDs next to the display on the left in binary code. NOTE The digital frequency set point is set to 0Hz by default. To check whether the drive is working, a desired frequency value must be input via the key. Otherwise a jog frequency must be input via the appropriate parameter >Jog Frequency< (P113). Settings may only be carried out by qualified personnel in compliance with safety and warning information. ATTENTION: The motor may start immediately after pressing the START key! 34 Subject to technical changes BU 0500 GB

35 3.2 TechnologyBox ControlBox functions: Press to switch on the frequency inverter. It is now enabled with any set jog frequency (P113). A preset minimum frequency (P104) may be supplied. Parameter >Interface< P509 and P510 must = 0. 7-segment LED display LEDs 1 2 Press to switch off the frequency inverter. The output frequency is reduced to the minimum frequency (P505) and the output shuts down. During operation shows the current operating value set (selection in P001) or an error code. During parameterisation, the parameter numbers or the parameter values are shown. The LEDs indicate in the operating display (P000) the current operating parameter set and during parameterisation the current parameter set being parameterised. The display is coded in binary form here. 1 2 = P1 1 2 = P2 The motor rotation direction changes when this key is pressed. ""Rotation to the left" is indicated by a minus sign. Attention! Take care when operating pumps, worm gearing, ventilators, etc. Blocking of the key via parameter P = P3 Press key to INCREASE frequency. During parameterisation the parameter number / parameter value is increased 1 2 = P4 Press key to REDUCE frequency. During parameterisation the parameter number / parameter value is reduced. Press "ENTER" to store an altered parameter value, or to switch between parameter number or parameter value. NOTE: If a changed value is not to be stored, the storing the change. key can be used to exit the parameter, without BU 0500 GB Subject to technical changes 35

36 NORDAC SK 500E / 520E Handbook Control with the ControlBox: The inverter can only be controlled via the Control Box if it has not previously been enabled via the control terminals or via a serial interface (P509 = 0 and P510 = 0). If the "START" key is pressed, the frequency inverter changes to the operating display (selection P001). The inverter supplies 0Hz or a minimum frequency set to a higher value (P104) or jog frequency (P113). Parameter set display Emergency stop (press simultaneously) START STOP Phase seq. reversal Store current frequency as jog frequency Reduce frequency Increase frequency Set frequency = 0Hz (press simultaneously) Parameter set display: The LEDs indicate in the operating display (P000) the current operating parameter set and during parameterisation ( P000) the current parameter set being parameterised. The display appears in binary form here. Switching the parameter set is possible via parameter P100, even during operation (control with ControlBox). Desired frequency value: The current desired frequency value depends on the setting in the parameters Jog Frequency (P113) and Minimum Frequency (P104). This value can be altered during keyboard operation with the and value keys and permanently stored in P113 as the jog frequency by pressing the ENTER key. Emergency stop: By simultaneous operation of the STOP key and the "Change direction key", an emergency stop can be initiated. 36 Subject to technical changes BU 0500 GB

37 3.2 TechnologyBox Parameterisation with the ControlBox The parameterisation of the frequency inverter can take place in the various operating modes. All parameters can always be changed Online. Switching to the parameter mode occurs in differing ways depending upon the operating condition and enabling source. 1. If a release is not present via the Control Box (press STOP key if necessary), the control terminals or the serial interface, you can switch to the parameterisation mode directly from the operating value display using the or value keys. P 0 / P 7 2. If a release signal is present on the control terminals or a serial interface and the frequency inverter is producing an output frequency, you can also switch to parameterisation mode direct from the operating display using the or value keys. P 0 / P 7 3. If the inverter is released via the Control Box ( START key), the parameterisation mode can be reached by pressing the START and ENTER keys simultaneously. 4. Switching back to control mode is achieved by pressing the START key. Parameter set display Switching from parameterisation to control (see item 3) Switching from control to parameterisation whilst the drive is running (see item 3) Select menu group, show parameter value Previous menu group /parameter number Next menu group/ parameter number One level back each time, to operating value display Changing parameters To access the parameterisation area one of the or value keys must be pressed. The display changes to the menu group display P 0... P 7. Press the ENTER key to access the menu group and the value keys to select the desired parameter. All parameters are arranged in order in the individual menu groups, in a continuous scroll pattern. In this area it is therefore possible to scroll forwards and backwards. Each parameter features a parameter No. P x x x. Refer to Chapter 5 "Parameterisation" for a description of the parameters. NOTE: Parameters P502, P701 through 706, P707, P718, P741/742 and P745/746 also have an array level, in which further settings can be made, e.g. P502 ENTER P_01 ENTER off Setting: Master function 1 value VALUE P_02 ENTER off Einstellung: Master function 2 value BU 0500 GB Subject to technical changes 37

38 NORDAC SK 500E / 520E Handbook Menu structure with the ControlBox Operating values display (and ready to operate), following mains ON P7-- P6-- P5-- P0-- P001 P002 P003 P1-- P100 P101 P2-- P200 P201 P3-- P300 P301 P4-- P400 P401 P114 P220 P327 P483 In order to change a parameter value, the parameter no. is displayed. ENTER key must be pressed when the corresponding Changes can then be made using the or VALUE keys and must be confirmed with for them to be stored or to quit the parameter. So long as a changed value has not been confirmed by pressing ENTER, the value display will flash, indicating that this value has not yet been stored in the frequency inverter. During parameter changes, to make the display more legible, the display does not blink. If a change is not to be adopted, the "DIRECTION" key can be pressed to leave the parameter. Parameter set display Do not adopt changed values Adopt changed values Reduce the value Increase value Value to factory setting 38 Subject to technical changes BU 0500 GB

39 3.2 TechnologyBox ParameterBox, SK TU3-PAR This option is for ease of parameterisation and control of the frequency inverter, as well as the display of current operating settings and conditions. Up to 5 data sets can be stored and managed in this device. This facilitates commissioning of series applications. NOTE: To use the ParameterBox (external manual operation/control cabinet box) SK PAR-2H /-2E on the SK 500E/520E, it must at least feature software version 3.5 R1. Connect SK PAR-2H /-2E to a stabilised external 5V power supply to ensure safe operation. Characteristics of the Parameter Box Illuminated, high resolution LCD graphics screen Large-screen display of individual operating parameters 6 language display Help text for fault diagnosis 5 complete frequency inverter data sets can be stored in memory, loaded and edited For use as a display for different usage parameters Standardisation of individual operating parameters to enable the display of specific system data Direct control of a frequency inverter ParameterBox information After having plugged the ParameterBox onto the frequency inverter and switched on the power for the first time must first select the menu language: German or English. The box then automatically performs a bus scan in order to identify the connected frequency inverter. In the display that follows, the frequency inverter type, its current operating mode and state can be identified. After being released, the frequency inverter display mode changes to the 3 current operating values (frequency, voltage, current). The current operating settings displayed can be selected from a list of 19 possible value options (in the >Display< / > Values< menu). NOTE The digital frequency set point is set to 0Hz by default. To check whether the motor is working, a frequency set point must be entered with the key or a jog frequency via the respective menu level >Parameterise<, >Base parameters< and the respective parameter >Jog frequency< (P113) Settings may only be carried out by qualified personnel in compliance with safety and warning information. ATTENTION: The motor may start immediately after pressing the START key! BU 0500 GB Subject to technical changes 39

40 NORDAC SK 500E / 520E Handbook ParameterBox functions LC display Graphic, backlit LC display for displaying operational values and parameters for the connected frequency inverter and ParameterBox parameters. Using the SELECTION keys enables toggling between the menu levels and menu items. Press the and keys together to go to the next higher level. The contents of individual parameters can be altered with the VALUES keys. Press the and keys together to load the default values of the parameter selected. When controlling the frequency inverter via the keypad, use the VALUE keys to select the frequency set point. With P002/P003 set to small values the ramp time is limited to 0.17 secs/hz. Press the ENTER key to switch to the selected menu group or accept the changed menu items or parameter values. NOTE: If a parameter is to remain, without a new value being stored, then the selection keys can be directly used for the purpose. If the frequency inverter is currently controlled via the keyboard (not the control terminals), the actual frequency can be saved in the jog frequency parameter (P113) by pressing the ENTER key. START key for switching on the frequency inverter. STOP key for switching off the frequency inverter. The direction of rotation of the motor changes when the DIRECTION key is pressed. Rotational direction left is indicated by a minus sign. Attention! Take care when operating pumps, worm gearing, ventilators, etc. NOTE: Only available if this function is not blocked in parameter P509 or P540. LEDs ON ERROR The LEDs signal the current status of the ParameterBox. ON The ParameterBox is connected to the power supply and is operational. ERROR An error has occurred when processing data or in the connected frequency inverter. LC display Frequency inverter type Device power, mains voltage Current operating values: Frequency, voltage, current 500E 1.1kW / 230V 1 Fi/Hz U/V I/A ONLINE FU P1 R LAEUFT Connected to the frequency inverter Device state: parameter set, direction of rotation and status 40 Subject to technical changes BU 0500 GB

41 3.2 TechnologyBox Menu structure The menu structure comprises various levels, which are built in a ring structure. Press the ENTER key to go to the next level. Press the SELECTION keys together to go back. 500E 1.1kW / 230V 1 Fi/Hz U/V I/A ONLINE FU P1 R LAEUFT U1 U2 U3 U4 U OK Display 1 Parameterisation 1 Parameter 1 administration Optional features 1 P Bus scan P Object selection P Copy - source P Language P FI selection Operating Displays 2 >ENTER< (to level 3) P Copy - target P Operating mode P Display mode Base parameters 2 >ENTER< (to level 3) P Copy - start P Auto Bus Scan P Values for display Motor data 2 >ENTER< (to level 3) P Load default values P Contrast P Standardisat. factor P Delete storage P Set password P0 2 back Frequency inverter menu structure Chapt. 5 parameterisation P0 2 back P Box password P0 P zurück Reset Box Parameters P0 2 back P0 P NORDAC zurück p-box Version 3.5 R1 P0 2 back >Display< (P11xx), >Parameter administration< (P12xx) and >Options< (P13xx) are purely Parameter Box parameters and have nothing directly to do with the inverter parameters. Use the >Parameterisation< menu to enter the frequency inverter menu structure; if applicable, after object selection when frequency inverter data records have already been stored in the ParameterBox. Chapter 5 of the present handbook describes the frequency inverter parameters. BU 0500 GB Subject to technical changes 41

42 NORDAC SK 500E / 520E Handbook Language selection, brief description The following steps should be carried out to change the language used in the ParameterBox display. You can choose between Deutsch [German] and English display language when you switch on the ParameterBox for the first time. Use the selection keys (right/left arrows) to select and the ENTER key to confirm your selection. In the example below German was selected when the device was switched on for the first time. After this selection, the following display should appear (varies depending upon output and options). Initial display 500E 1.1kW/230V 1 > NORDAC < Frequenzumrichter ONLINE FU P1 ESperre Use the or SELECTION key to go to the Optionen menu Optionen >ENTER< ONLINE FU P1 ESperre 1 then press >ENTER P Sprache Deutsch... ONLINE FU P1 ESperre Using the Values key, select the desired language... English... Français... Espanol... Sverige... Nederlands After selection press >ENTER< P Language English (p.e.) ONLINE FU P1 Locked 1 Press the and SELECTION keys simultaneously Options >ENTER< ONLINE FU P1 Locked 500E 1.1kW/230V 1 Press the and SELECTION keys simultaneously > NORDAC < Frequency Inverter ONLINE FU P1 Locked 42 Subject to technical changes BU 0500 GB

43 3.2 TechnologyBox Controlling the frequency inverter with the ParameterBox The frequency inverter can only be fully controlled by the ParameterBox if the parameter >Interface< (P509) is set to >CU or keyboard< (0) (factory setting) and if the frequency inverter has not already been enabled via the CU. START (Enable) No inverter control function STOP (Enable) Increase frequency Phase seq. reversal Reduce frequency Save current frequency Note: If the frequency inverter is enabled in this mode, then the parameter set selected for this frequency inverter in the Menu >Parameterisation< >Base parameters< under the >Parameter set< parameter is used. Attention! After the START command, the frequency inverter can start immediately or with a preprogrammed frequency (minimum frequency P104 or jog frequency P113). Parameterisation with the ParameterBox To enter the parameterisation mode, select the >Parameterisation< menu group in level 1 of the ParameterBox and confirm with ENTER key. This displays the parameter level of the connected frequency inverter. SELECTION keys VALUE keys Selection forward Increase value Simultaneous operation one menu level back Simultaneous operation Load factory setting Selection back Reduce value One menu level forward or adopt parameter value BU 0500 GB Subject to technical changes 43

44 NORDAC SK 500E / 520E Handbook Screen layout during parameterisation If the setting of a parameter is changed, the value flashes until it is confirmed with the ENTER key. To load the default setting of the parameter to be edited, both VALUE keys must be pressed together. In this case also, the setting must be confirmed with the ENTER key to confirm the change. If the change is not accepted, press the SELECTION key to call up the last value saved and press the SELECTION key again to leave the parameter. Parameter to be edited (No.) Parameter set to be edited Parameter to be edited (text) Current parameter value P102 PS1 3 Start-up time 2.90 s ONLINE FU P1 Ready Menu structure level Control object status Current ParameterBox status Control object selected Active parameter set in control object NOTE: The bottom line of the display is used to display the current status of the box and the frequency inverter to be controlled. NOTE: Parameters P502, P701 through 706, P707, P718, P741/742 and P745/746 also have an array level, in which further settings can be made. The desired array level must first be selected (see Parameterisation, chapt. 5) and confirmed with ENTER. You can now make the desired parameter settings. P502 PS1 [01] 3 Master function value Off ONLINE FU P1 Ready Array level of selected parameter. e.g. [01], [02], [03] Subject to technical changes BU 0500 GB

45 3.2 TechnologyBox ParameterBox parameters The following main functions are assigned to the menu groups: Menu group No. Main function Display (P10xx): Select operating values and display layout Parameterisation (P11xx): Program connected frequency inverter and all storage objects Parameter administration (P12xx): Copy and save entire parameter sets from storage objects and frequency inverter Optional features (P14xx): Set ParameterBox functions and all automatic processes Parameter display Parameter P1001 Bus scan P1002 FI selection P1003 Display mode P1004 Values for display P1005 Standardisation factor Setting value / description / note This parameter starts a bus scan. A progress indicator appears in the display during the process. After a bus scan, the parameter is "Off". Depending on the result of this process, the ParameterBox goes into "ONLINE" or "OFFLINE" operating mode. Selection of current object to parameterise/control. The display and operating actions in the ongoing process relate to the object selected. Only the devices recognised during the bus scan are displayed in the inverter selection list. The current object is displayed in the status line. Value range: FU, S1... S5 ParameterBox operating value display selection Default: Any 3 values next to each other List: Any 3 values with units, one on top of the other Large size display: Any 1 value with units ParameterBox current value display selection. The value selected is placed in the first position of an internal list for the display value and is then also used in the Large Display mode. Possible current values for display: actual frequency voltage current Speed instantaneous current set point frequency Link voltage Current bus value 1 unstandardised The first display list value is scaled with the standardisation factor. Should this standardisation factor deviate from 1.00, the unit of the scaled value is no longer displayed. Value range: to ; resolution 0.01 Parameterisation Parameter P1101 Object selection Setting value / description / note Selection of object to be parameterised. The ongoing parameterisation process relates to the object selected. Only the inverters and storage objects recognised during the bus scan are displayed in the selection list. This parameter is not shown when only one frequency inverter is connected and no memory location is occupied! Value range: FU, S1... S5 BU 0500 GB Subject to technical changes 45

46 NORDAC SK 500E / 520E Handbook Parameter administration Parameter P1201 Copy - source P1202 Copy - target P1203 Copy - start P1204 Load default values P1205 Delete storage Setting value / description / note Selection of current source object to copy. Only the frequency inverters and storage objects recognised during the bus scan are displayed in the selection list. Value range: FU, S1... S5 Selection of current target object to copy. Only the frequency inverters and storage objects recognised during the bus scan are displayed in the selection list. Value range: FU, S1... S5 In this parameter a transfer procedure is initiated, in which all parameters selected under the parameter >Copying Source< are transferred to one item defined under the parameter >Copying Target<. An information window appears for acknowledgement when overwriting data. The transfer starts after acknowledgement. With this parameter, the parameters of the object selected are described with default values. This function is particularly important when editing storage objects. A virtual frequency inverter can only be loaded and edited with the ParameterBox by using this parameter. Value range: FU, S1... S5 With this parameter, the data of the storage object selected is deleted. Value range: S1... S5 Optional features Parameter P1301 Language P1302 Operating mode P1303 Auto Bus Scan P1304 Contrast P1305 Set password P1306 Box password Setting value / description / note Language selection for operating the ParameterBox Languages available: German English Dutch French Spanish Swedish ParameterBox operating mode selection Offline: The ParameterBox operates autonomously. The frequency inverter data set is not accessed. The ParameterBox storage objects can be parameterised and administrated. Online: A frequency inverter is connected to the ParameterBox interface. The frequency inverter can be parameterised and controlled. A bus scan starts automatically when the "ONLINE" operating mode is selected. PC slave: Only possible with the p-box or SK PAR-2H / -2E ParameterBox Setting the power-on behaviour. Off: No Bus Scan is carried out; frequency inverters connected before switch-off are polled following the next switch-on. On: At switch-on at the Parameter Box, a Bus Scan is carried out automatically. ParameterBox display contrast setting Value range: 0% %; Resolution 1% Use this parameter to set a password. If any value other than 0 is entered in this parameter, then the ParameterBox settings or connected frequency inverter parameters cannot be changed. If the Password function is to be reset, the password selected in the >Set Password< parameter must be entered here. If the correct password is selected, all of the ParameterBox functions can be used again. 46 Subject to technical changes BU 0500 GB

47 3.2 TechnologyBox Parameter P1307 Reset Box Parameters P1308 Software version Setting value / description / note Use this parameter to reset the ParameterBox to its factory settings. All ParameterBox settings and data in the storage objects will be deleted. Displays ParameterBox (NORDAC p-box) software version. Keep available, if required ParameterBox error messages Display Error Cause Remedy Communication errors 200 PARAMETER NUMBER NOT PERMISSIBLE 201 PARAMETER VALUE CANNOT BE CHANGED 202 PARAMETER OUTSIDE VALUE RANGE 203 FAULTY SUB INDEX 204 NO ARRAY PARAMETERS These error messages are caused by EMC interference or differing participant software versions. Check the ParameterBox software version and that of the inverter connected. Check the wiring of all components and for possible EMC interference 205 WRONG PARAMETER TYPE 206 INCORRECT RESPONSE IDENTIFIER USS INTERFACE 207 USS INTERFACE CHECKSUM FAULT Communication between frequency inverter and ParameterBox is malfunctioning (EMC), safe operation cannot be guaranteed. Check the frequency inverter connection. Use a shielded cable between devices. Lay the BUS cable separately from the motor cables. 208 FAULTY STATUS RECOGNITION USS INTERFACE Communication between frequency inverter and ParameterBox is malfunctioning (EMC), safe operation cannot be guaranteed. Check the frequency inverter connection. Use a shielded cable between devices. Lay the BUS cable separately from the motor cables. 209_1 INVERTER IS NOT RESPONDING The ParameterBox is waiting for an answer from the connected frequency inverter. The waiting period has expired without an incoming answer. Check the frequency inverter connection. The frequency inverter's USS parameter settings have been changed during operation. BU 0500 GB Subject to technical changes 47

48 NORDAC SK 500E / 520E Handbook Display Error Cause Remedy Identification errors 220 DEVICE NOT RECOGNISED Device ID not found. The connected frequency inverter is not listed in the ParameterBox database, no communication can be established. Please contact your Nord representative. 221 SOFTWARE VERSION NOT RECOGNISED Software version not found. The connected frequency inverter software version is not listed in the ParameterBox database, no communication can be established. Please contact your Nord representative. 222 CONFIGURATION NOT RECOGNISED There is an unrecognised module in the frequency inverter (customer interface). Please check the modules installed in the frequency inverter. If necessary, check the ParameterBox software version and that of the frequency inverter connected. 223 BUS CONFIGURATION CHANGED A different device to that which was saved responds when restoring the last bus configuration. This error only occurs if the >Auto Bus Scan< parameter is set to OFF and a different device is connected to the ParameterBox. Activate the Auto Bus Scan Function. 224 DEVICE IS NOT SUPPORTED The frequency inverter type used with the Parameter Box is not supported! The Parameter Box cannot be used with this frequency inverter. 225 INVERTER CONNECTION BLOCKED Accessing a device which is not online (previous Time Out error). Carry out a bus scan via the >Bus Scan< parameter (P1001). Parameter Box operating errors 226 SOURCE AND TARGET ARE DIFFERENT DEVICES 227 SOURCE EMPTY 228 THIS COMBINATION IS NOT PERMITTED 229 OBJECT SELECTED IS EMPTY 230 DIFFERENT SOFTWARE VERSIONS Copying of different object types (from / to different frequency inverters) is not possible. Copying data from a deleted (empty) storage object Same copy source and target. The command cannot be carried out. Attempt to parameterise a deleted storage object Warning Copying objects with differing software versions can lead to problems transferring parameters. 48 Subject to technical changes BU 0500 GB

49 3.2 TechnologyBox Display Error 231 INVALID PASSWORD 232 BUS SCAN ONLY WHEN IN ONLINE MODE ONLINE Cause Remedy Attempt to change a password without entering a valid box password in parameter >Box Password< P A bus scan (searching for a connected frequency inverter) is only possible in ONLINE mode. Warnings 240 OVERWRITE DATA? YES NO 241 DELETE DATA? YES 242 MOVE SW VERSION? CONTINUE 243 MOVE SERIES? CONTINUE NO CANCEL CANCEL These warnings refer to potentially serious changes, which must be additionally confirmed. After selecting the next step, confirm with "ENTER". 244 DELETE ALL DATA? YES NO Inverter control errors 250 THIS FUNCTION IS NOT ENABLED! 251 CONTROL COMMAND UNSUCCESSFUL 252 CONTROL IS NOT POSSIBLE OFFLINE 253 ERROR ACKNOWLEDGEMENT UNSUCCESSFUL The required function is not enabled in the frequency inverter's >Interface< parameter. Change the value of the parameter >Interface< of the associated frequency inverter to the required function. More detailed information can be obtained from the operating instructions for the frequency inverter. The control command could not be implemented by the inverter, as a higher priority function, e.g. Emergency Stop or an OFF signal to the control terminals of the frequency inverter, is present. Calling up a control function in Offline mode. Change the ParameterBox operating mode in the >Operating Mode< parameter P1302 to Online and repeat action. Acknowledgement of a fault on the frequency inverter was unsuccessful; the error report is still pending. Inverter Fault Messages "FAULT NO. FROM INVERTER INVERTER FAULT "INVERTER FAULT TEXT" A fault has occurred in the frequency inverter with the number displayed. The frequency inverter error number and text are displayed. BU 0500 GB Subject to technical changes 49

50 NORDAC SK 500E / 520E Handbook Profibus module, SK TU3-PBR, -24V Numerous different automation devices can exchange data using Profibus. PLCs, PCs, operating and monitoring devices can all communicate via one uniform bus in serial bit mode. Data exchange is subject to DIN parts 1 and 2 and upgrades specific to the application in part 3 of this standard. As far as European field bus standardisation is concerned, the Profibus is integrated into the European field bus standard pr EN The terminating resistor for the last bus participant is located in the Profibus standard plug. Detailed information can be found in the operating instructions BU 0020 or contact the supplier of the frequency inverter. Profibus status LEDs BR (green) BE (red) Data traffic on the send cable Data traffic on the receive cable CANopen bus module SK TU1-CAO The CANopen interface on the NORDAC frequency inverter enables the parameterisation and control of the devices in accordance with CANopen specifications Up to 127 participants can be addressed on a single Bus. A terminating resistor is integrated and can be switched on. The transfer rate (10kBaud and 500kBaud) and the Bus addresses are set using coding switch dials or the applicable parameters. For detailed information please refer to the operating instructions BU 0060 or contact the supplier of the frequency inverter. CANopen Status LEDs Component Status LEDs CR (green) CE (red) DR (green) DE (red) CANopen RUN LED CANopen ERROR LED Module status Module error 50 Subject to technical changes BU 0500 GB

51 3.2 Technologie Box DeviceNet module, SK TU3-DEV DeviceNet is an open communication profile for distributed industrial automation systems. It is based on the CAN Bus system. Up to 64 participants can be linked to one Bus system. That transfer rate (125, 250, 500 kbit/s) and the Bus addresses are set using coding switch dials or the applicable parameters. For detailed information please refer to the operating instructions BU 0080 or contact the supplier of the frequency inverter. DeviceNet Status LEDs Component Status LEDs MS (red/green) NS (red/green) DS (green) DE (red) Module Status Network (bus) status Module status Module error InterBus module, SK TU3-IBS With InterBus up to 256 subscribers with greatly differing automation devices can exchange data. PLCs, PCs, operating and monitoring devices can all communicate via one uniform bus in serial bit mode. NORDAC inverters are remote bus subscribers. The data width is variable (3 words; 5 words), at a baud rate of 500 kbit/s (optional 2Mbit/s). An additional terminating resistor is not necessary as it is already integrated. Addressing is carried out automatically by means of the physical arrangement of the subscribers. An external 24V supply is required for uninterrupted Bus operation. For detailed information please refer to the operating instructions BU 0070 or contact the supplier of the frequency inverter. Component Status LEDs ST (red/green) Module error/ready. InterBus Status LEDs UL (green) RC (green) BA (green) RD (yellow) TR (green) Power supply ready. Remote Check, connection to the previous InterBus unit is o.k. Bus Active, InterBus data traffic. Remote bus Disabled, connection to the next InterBus unit is turned off. Transmit, data traffic from/to this InterBus unit. BU 0500 GB Subject to technical changes 51

52 NORDAC SK 500E / 520E Handbook AS interface, SK TU3-AS1 Actuator sensor interface (AS interface) is a bus system for the lower field bus layer suitable for simple control tasks. The transmission principle is based on a single-master system with cyclic polling. A maximum of 31 slaves (or 62 A/B slaves) can be operated on an up to 100 m long, unshielded two-wire cable using any network topology (tree / line / star). The AS interface cable (yellow) transmits data and energy, a second twowire cable for an auxiliary low voltage (24 V) is possible (black). Addressing occurs via the master also providing further management functions, or via a separate addressing device. Transmission of the 4-bit user data (per direction) occurs cyclically featuring an effective error protection with a maximum cycle time of 5 ms. Transmission of larger data volumes is additionally possible for some slave profiles (e.g. slave profile 7.4). The bus system is defined in the AS-Interface Complete Specification. For detailed information please refer to the operating instructions BU 0090 or contact the supplier of the frequency inverter. Status LEDs Digital I/O LEDs AS-i I/O LEDs Device S/E (red/green) AS- Int. PWR/FLT (red/green) OUT 1 2 (yellow) IN (yellow) DI (yellow) DO (yellow) Module error/ready. Standard status display for AS-Interface Slaves. Conditions of the AS-Interface bits, which are received/send out of the master. Conditions at the digital input/output. 52 Subject to technical changes BU 0500 GB

53 4 Commissioning 4 Commissioning Once the mains supply has been connected to the frequency inverter, it will be ready for use after a few moments. In this state, the application requirements can be input into the frequency inverter, i.e. parameterisation. A completely comprehensive description of all the parameters is set out in chapter 5. The connected motor should only be started using the enable signal once successful application-specific input of the parameters by qualified personnel has been achieved. ATTENTION DANGER TO LIFE! The frequency inverter is not equipped with a master power switch and is therefore always live when connected to the mains voltage. For this reason, a connected motor can also be live. 4.1 Factory settings All frequency inverters supplied by Getriebebau NORD are pre-programmed with the factory setting for standard applications with 4-pole DS standard motors (same performance and voltage). For use with motors of differing performance and power, the data from the rating plate of the motor must be input into parameters P201...P207 under the menu group >Motor Data<. NOTE: All motor data can be programmed with parameter P200. This parameter is reset to 0 = no change after this function was used! The data is automatically loaded into parameters P201 P209 once, and from here it can again be compared with the data from the motor rating plate. P200 motor list: 0 = no change 8 = 0.37kW 400V 1 = no motor 9 = 0.50PS 460V 2 = 0.25kW 230V 10 = 0.55kW 230V 3 = 0.33PS 230V 11 = 0.75PS 230V 4 = 0.25kW 400V 12 = 0.55kW 400V 5 = 0.33PS 460V 13 = 0.75PS 460V 6 = 0.37kW 230V 14 = 0.75kW 230V 7 = 0.50PS 230V... P204 P207 P200 P201 P Hz 3~ Mot IEC 56 IM B3 230 / 400 V Δ/Y EN60034 IP55 Rot. KL 16 Th.Cl.F 60 Hz 460 V Y 9,0 / 5,2 A 5,2 A 2,2 kw 2,5 kw cosϕ 0,74 cosϕ 0, /min 1765 /min P203 P202 RECOMMENDATION: For the unrestricted use of the drive unit, it is necessary to input the most precise motor data possible according to the rating plate. In particular, we recommend that you perform an automatic stator resistance measurement with parameter P220. In order to determine the stator resistance, set P220 = 1 and confirm by pressing "ENTER". The value adjusted to the line resistance will be stored in parameter P208 (dependant upon P207). BU 0500 GB Subject to technical changes 53

54 NORDAC SK 500E / 520E Handbook 4.2 Minimum configuration for control connections If the frequency inverter is to be controlled by digital and analogue inputs, this can be done straightaway in the delivery condition. Settings are not necessary for the moment. Minimum circuitry VO +10V AGND/0V AIN R = 10k Potentiometer, 10kOhm (Function = P400) (Range = P104/105) DIG 1 VO +15V Switch, ON/OFF (Function = P420) Basic parameters If the current setting of the frequency inverter is not known, it is recommended to apply the factory settings P523 = 1. In this configuration the frequency inverter is pre-programmed for standard applications. If necessary, the optional SimpleBox SK CSX-0 or ControlBox SK TU3-CTR can be used to edit the following parameters. Operating values display (and ready to operate), following mains ON P7-- Information P5-- Additional parameter P0-- Display parameter P1-- Base parameters P2-- Motor data P4-- Control terminals P523 Load factory data The current output frequency is displayed by default P102 Start-up time s P103 Braking time s Motor data See 4.1 Basic Settings P400 Funct. Analog. inputs V - Frequency - P420 Funct. digit. input 1 - IN right - P104 Min. frequency Hz P105 Max. frequency Hz 54 Subject to technical changes BU 0500 GB

55 5 Parameterisation 5 Parameterisation During operation, there are four switchable parameter sets. All parameters are visible in the delivery state but can be partially hidden with parameter P003. All parameters can be edited "online". NOTE: As there are dependencies between the parameters, it is possible for invalid internal data and operating faults to be generated. During operation, only the inactive parameters or uncritical settings should be edited. The individual parameters are combined in various parameter sets. The first digit of the parameter number indicates the Menu Group assignment. Menu group No. Main function Operating parameter display For selecting the display value physical unit. Basic parameters (P1--): Include basic frequency inverter settings, e.g. connection and disconnection modes and are sufficient for standard applications together with the motor data. Motor / characteristic curve parameters (P2--): Setting motor-specific data, important for ISD current control and characteristic curve selection by dynamic and static boost setting. Control parameters (P3--): (for SK 520E with encoder input only) Setting of the control parameters (current controller, rotation speed controller etc.) for rotation speed feedback in SK 520E. Control clams (P4--): Analogue input and output scaling, specification of digital input functions and relay outputs, as well as PID controller parameters. Extra functions (P5--): Functions dealing with e.g. the interface, pulse frequency or fault acknowledgement. Information (P7--): For display of e.g. current modes, old fault messages, device status reports or software version. Array parameter xx Some parameters in these groups can be programmed or exported in multiple levels (arrays). After parameter selection the array level must also be selected here. NOTE: Parameter P523 can be used to load the default settings for all parameters at any time. This can be helpful, for example, when commissioning an inverter, whose parameters no longer conform to the default settings. ATTENTION: All current parameter settings will be lost, if P523= 1 is set and confirmed with "ENTER". To safeguard the current settings, these can be transferred to the ControlBox or ParameterBox stores. BU 0500 GB Subject to technical changes 55

56 NORDAC SK 500E / 520E Handbook Availability of the parameters Due to particular configurations, parameters are subject to specific conditions. The tables below (chap. 5.1 onwards) list all parameters with appropriate notes. Example Parameter text Array values Parameter number Parameter value range Parameter factory setting available for SK 520E only Supervisor parameters (S) are dependent on the setting in P003 Parameter selection in P100 dependent on the parameter set Array parameter display Some parameters allow settings or views to be displayed in several arrays. After selection of one of these parameters the array level appears that must also be selected. When the ControlBox is used, the array level is indicated by _ - 0 1, in the ParameterBox (shown to the right) the array level selection option appears in the display top right. ParameterBox SK TU3-PAR Parameterisation with ControlBox, SK TU3-CTR: P502 ENTER P_01 ENTER off Setting: Master function 1 value VALUE P_02 ENTER off Setting: Master function 2 value 56 Subject to technical changes BU 0500 GB

57 5.1 Operating parameter display 5.1 Operating parameter display The following text uses the abbreviation FI for frequency inverter. Parameter Setting value / description / note Device Supervisor P000 Operating parameter display Parameter set The SimpleBox (SK CSX-0) or ControlBox (SK TU3-CTR) displays provide an online indication of the operating value selected in parameter P001. P [ 0 ] If required you can read important information on the drive's operating state. Display selection 0 = Actual frequency [Hz], is the current output frequency being supplied by the frequency inverter. 1 = Rotation speed [1/min], is the actual rotation speed as calculated by the FI. 2 = Set frequency [Hz], the output frequency equivalent to the current set point. This need not match the current output frequency. 3 = Current [A], is the actual output current as measured by the FI. 4 = Torque Current [A], is the torque developing output current of the FI. 5 = Voltage [V AC], is the current alternating voltage being output by the FI. 6 = DC Link [V DC], is the internal direct current of the FI. Amongst other things, this depends on the mains supply voltage. 7 = cos ϕ, the current calculated value of the power factor. 8 = Apparent power [kva], is the apparent power calculated by the FI. 9 = Effective power [kw], is the effective power calculated by the FI. 10 = Torque [%], is the current torque calculated by the inverter. 11 = Field [%], is the current field in the motor calculated by the FI. 12 = Hours run, is the length of time that the mains electricity supply has been applied to the FI. 13 = Hours run enabled, is the length of time that the FI has been enabled. 14 = Analogue input 1 [%], current value at analogue input 1 of the FI. 15 = Analogue input 2 [%], current value at analogue input 2 of the FI. 16 =... Reserved (18) 19 = Heat sink temperature [ C], displays the current heat sink temperature. 20 = Motor load [%], average motor load based on the known motor data (P201...P209). 21 = Braking resistor load [%], average braking resistor load based on the known braking resistor data (P556...P557). 22 =... Reserved (63) BU 0500 GB Subject to technical changes 57

58 NORDAC SK 500E / 520E Handbook Parameter Setting value / description / note Device Supervisor Parameter set P002 Display factor S [ 1.00 ] The operating value in parameter P001 >Selection of operating value display< is multiplied with the scaling factor and displayed in P000 >Operating value<. It is therefore possible to display installation specific operating values such as the flow rate. P [ 1 ] Supervisor code 0 = The supervisor parameters are not visible. 1 = All parameters are visible. 2 = Only menu group 0 >Operating value< (P P003) is visible. 3 = , as value Subject to technical changes BU 0500 GB

59 5.2 Basic parameters 5.2 Basic parameters Parameter Setting value / description / note Device Supervisor Parameter set P100 Parameter set S [ 0 ] Selection of parameter set to be parameterised. 4 parameter sets are available. P identifies all parameter set-dependent parameters. The selection of the operating parameter set is done via a digital input or the BUS control. Switching can take place during operation (online). Setting Digital input function [8] Digital input function [17] LEDs ControlBox 0 = Parameter set 1 LOW LOW 1 = Parameter set 2 HIGH LOW 2 = Parameter set 3 LOW HIGH = Parameter set 4 HIGH HIGH 1 2 If enabled via the keyboard (ControlBox, PotentiometerBox or ParameterBox), the operating parameter set will match the settings in P100. P101 Copy parameter set S [ 0 ] After confirmation with the ENTER key, a copy of the parameter set selected in P100 >Parameter set< is written to the parameter set dependent on the value selected here 0 = Do not copy 1 = Copies the active parameter set to Parameter set 1 2 = Copies the active parameter set to Parameter set 2 3 = Copies the active parameter set to Parameter set 3 4 = Copies the active parameter set to Parameter set 4 P102 Start-up time P s [ 2.00 ] The start-up time is the time equivalent to the linear frequency increase from 0Hz to the set maximum frequency (P105). If working with an actual set point <100%, the start-up time reduces linearly according to the set point set. Under certain conditions the run-up time can be extended, e.g. FI overload, delay in desired value, curving or if the current limit is reached. P103 Braking time P s [ 2.00 ] The braking time is the time equalling the linear frequency decrease from the set maximum frequency (P105) to 0 Hz. If working with an actual set point <100%, the braking time reduces accordingly. Under certain conditions the braking time can be extended, e.g. by the selected >Switch off mode< (P108) or >Ramp rounding< (P106). BU 0500 GB Subject to technical changes 59

60 NORDAC SK 500E / 520E Handbook Parameter Setting value / description / note Device Supervisor Parameter set P104 Minimum frequency P Hz [ 0.0 ] The minimum frequency is the frequency supplied by the FI as soon as it is enabled and no additional set point is present. In combination with set points (e.g. analogue set point or fixed frequencies), these are added to the set minimum frequency. This frequency will be undershot if a. the drive accelerates from the standstill. b. the FI is locked. The frequency then reduces to the absolute minimum (P505) before it is blocked. c. the FI reverses. The change in the rotation field takes place at the absolute minimum frequency (P505). This frequency can be continuously undershot if during acceleration or braking the function "Maintain frequency" (Function Digital input = 9) was executed. P105 Maximum frequency P Hz [ 50.0 ] The frequency supplied by the FI after being enabled and once the maximum set point is present, e.g. analogue set point equivalent to P403, an appropriate fixed frequency or maximum via the ControlBox. This frequency can be exceeded by the slip compensation (P212), the "Maintain frequency" function (digital input function = 9) and the change to another parameter set with a lower maximum frequency. P106 Ramp smoothing S P % [ 0 ] This parameter enables a rounding for the run-up and brake ramps to be achieved. This is necessary for applications, where smooth, but dynamic speed changes are required. A rounding is carried out for every set point value change. The value to be set is based on the start-up and braking times, although values <10% have no influence. For the entire start-up or braking time, including rounding, the following applies: P106 t = t + t t tot tot STARTUP BRAKING TIME P102 = t P103 P102 + t P103 [%] 100% [%] 100% P106 Output frequency Currently % from P102 Currently % from P103 Setpoint frequency P102 P103 Time 60 Subject to technical changes BU 0500 GB

61 5.2 Basic parameters Parameter Setting value / description / note Device Supervisor Parameter set P107 Brake application time P s [ 0.00 ] Recommendation: Lifting mechanism with brake without rotation speed feedback P114 = secs P107 = secs P201 P208 = Motor data P434 = 1 (ext. brake) P505 = Hz Electromagnetic brakes have a physically dependent delayed reaction time during application. This can lead to load sags with lifting mechanism applications because the brake delays before taking the load. This application time can be taken into account with parameter P107 (Brake control). Within the adjustable application time, the frequency inverter supplies the set absolute minimum frequency (P505) and so prevents start-up against the brake and load sag when stopping. See also here the parameter >Ventilation time< P114 NOTE: For the control of electromagnetic braking (especially for lifting operations) an internal relay should be used Function 1, external brakes (P434/441). The minimum absolute frequency (P505) should never be less than 2.0Hz. NOTE: When a time > 0 is set in P107 or P114, the magnetising current (field current) strength is checked at FI power-on. Without a sufficient magnetising current present the FI remains in the magnetising state and the motor brake is not released. Set P539 to 2 or 3 in order to cause a switch-off and an error message (E016) in such a case. Output frequency Signal IN Signal OUT for safe start-up P112 = 402 (off) P536 = 2.1 (off) P537 = 201 (off) P539 = 2/3 (I SD monitoring) against load sag P214 = % (lead) P505 P114 or P107, if P114 = 0 Brake ventilated P107 Time BU 0500 GB Subject to technical changes 61

62 NORDAC SK 500E / 520E Handbook Parameter Setting value / description / note Device Supervisor Parameter set P108 Switch off mode S P [ 1 ] This parameter determines the manner in which the output frequency is reduced after "Blocking" (controller enable low): 0 = Block voltage: The output signal is switched off immediately. The FI no longer supplies an output frequency. In this case, the motor is braked only by mechanical friction. Immediately switching the FI on again can lead to an error message. 1 = Ramp: The current output frequency is reduced proportionally to the remaining braking time from P103/P = Ramp with delay: As with ramp, but the brake ramp is prolonged in generator operation or the output frequency is increased with static operation. Under certain circumstances, this function can hinder overvoltage disconnection or reduce the braking resistor's power loss. NOTE: This function must not be programmed if defined deceleration is required, e.g. with lifting mechanisms. 3 = Instant DC braking: The FI immediately switches to the pre-selected direct current (P109). This DC current is supplied for the remaining proportion of the >DC brake time< (P110). Depending on the relationship of actual output frequency to max. frequency (P105) the >DC brake time< is reduced in proportion. The time taken for the motor to stop depends on the application. The time taken to stop depends on the mass inertia of the load, the friction and the DC current set (P109). With this type of braking, no energy is returned to the FI; there is substantial heat loss in the rotor. 4 = Constant brake distance: The brake ramp acts with a delay, if not moved with the maximum output frequency (P105). This leads to a similar braking distance from various current frequencies. NOTE: This function cannot be used as a positioning function. This function should not be combined with a ramp round-off (P106). 5 = Combi braking Dependent on the current DC link (UZW), a high frequency voltage is applied to the fundamental mode (linear characteristic curve only, P211 = 0 and P212 = 0). If possible, the braking time (P103) is adhered to. additional heating in the motor! 6 = Quadratic ramp: The braking ramp does not have a linear course, but is quadratically descending. 7 = Quadratic ramp with delay: Combination of functions 2 and 6 8 = Quadratic combined braking: Combination of functions 5 and 6 9 = Constant acceleration power: Only applies in field weakening range! The drive is accelerated and braked with constant electric power. The braking ramp course is dependent on the load. 10 = Distance travelled calculator: Constant distance between current frequency / speed and the set minimum output frequency (P104). 11 = Constant acceleration power with delay: Combination of functions 2 and = Constant acceleration power with delay (as 11) with additional chopper unload P109 DC brake current S P % [ 100 ] Current setting for the functions of DC current braking (P108 = 3) and combined braking (P108 = 5). The correct set value is dependent on the mechanical load and the stopping time required. A higher set value can bring large loads to a standstill more quickly. The 100% setting relates to a current value as stored in the >Nominal current< parameter P Subject to technical changes BU 0500 GB

63 5.2 Basic parameters Parameter Setting value / description / note Device Supervisor Parameter set P110 Time DC brake on S P s [ 2.00 ] The time that the motor is applied, during the direct current braking (P108= 3) function, with the current selected in the >DC brake current< parameter. Depending on the relationship of actual output frequency to max. frequency (P105) the >DC brake time< is reduced in proportion. Time starts when the enable is removed and can be cancelled with a new enable. P111 P factor torque limit S P % [ 100 ] Directly affects the behaviour of the drive at torque limit. The basic setting of 100% is sufficient for most drive tasks. If values are too high the drive tends to vibrate as it reaches the torque limit. If values are too low, the programmed torque limit can be exceeded. P112 Instantaneous current limit S P % / 401 [ 401 ] With this parameter, a limit value can be set for the torque generating current. This can prevent a mechanical overload of the drive. It cannot provide any protection against a mechanical blockade (start-up against a blockade). A safety clutch as protection cannot be dispensed with. The torque current limit can also be set over an infinite range of settings using an analogue input. The maximum desired value (comp. equivalent to 100%, P403 / P408) thus corresponds to the value set in P112. The limit value 20% of torque current can also not be under-shot by a smaller analogue desired value (P400/405 = 2) (in the servo mode with P300 = 1, not below 10%)! 401 = OFF is for the switching torque current limit off! This is also the basic setting for the frequency inverter. P113 Jog frequency S P Hz [ 0.0 ] When using the ControlBox or ParameterBox for FI control, the jog frequency is the starting value following successful enabling. As an alternative, when control is via the control terminals, the jog frequency can be activated via one of the digital inputs. The setting of the jog frequency can be done directly via this parameter or, if the FI is enabled via the keyboard, by pressing the ENTER key. In this case the current output frequency is adopted into parameter P113, and is available for a later start-up. NOTE: Specified desired values via the control terminals, e.g. jog frequency, fixed frequencies or desired analogue value are added using the correct sign. The set maximum frequency (P105) cannot be exceeded in this case, and the minimum frequency (P104) cannot be undershot. P114 Brake ventilation time S P s [ 0.00 ] Electromagnetic brakes have a physically dependent delayed reaction time during ventilation. This can lead to the motor running when the brake is still applied, which will cause the FI to trip out and display an overcurrent report. This ventilation time can be taken into account under parameter P114 (Braking control). During the adjustable ventilation time the frequency inverter supplies the set absolute minimum frequency (P505) thus preventing movement against the brake. See also here >Brake application time< P107 (setting example). NOTE: If the brake ventilation time is set to "0", then P107 is the brake ventilation and application. BU 0500 GB Subject to technical changes 63

64 NORDAC SK 500E / 520E Handbook 5.3 Motor data/characteristic curve parameters Parameter Setting value / description / note Device Supervisor Parameter set P200 Motor list P [ 0 ] With this parameter, the motor data factory settings can be changed. The parameter P201...P209 default setting is a 4-pole DS standard motor with the nominal FI power. Select one of the possible digits and press the ENTER key to set all of the following motor parameters (P201 to P209) to the selected rated power. The motor data is based on 4-pole standard motors. 0 = No data change 1 = No motor: At this setting, the FI operates without current control, slip compensation and pre-magnetisation time, and is therefore not recommended for motor applications. Possible applications are induction furnaces or other applications with coils and transformers. The following motor data is set: 50.0Hz / 1500rpm / 15.0A / 400V / 0.00kW / cos ϕ=0.90 / star / R S 0.01Ω / I IDLING 6.5A 2 = 0.25kW 230V 14 = 0.75kW 230V 26 = 2.2 kw 230V 40 = 7.5 kw 230V 3 = 0.33PS 230V 15 = 1.0 PS 230V 27 = 3.0 PS 230V 41 = 10.0 PS 230V 4 = 0.25kW 400V 16 = 0.75kW 400V 28 = 2.2 kw 400V 42 = 7.5 kw 400V 5 = 0.33PS 460V 17 = 1.0 PS 460V 29 = 3.0 PS 460V 43 = 10.0 PS 460V 6 = 0.37kW 230V 18 = 1.1 kw 230V 30 = 3.0 kw 230V 44 = 11.0 kw 400V 7 = 0.50PS 230V 19 = 1.5 PS 230V 31 = 3.0 kw 400V 45 = 15.0 PS 460V 8 = 0.37kW 400V 20 = 1.1 kw 400V 32 = 4.0 kw 230V 46 = 15.0 kw 400V 9 = 0.50PS 460V 21 = 1.5 PS 460V 33 = 5.0 PS 230V 47 = 20.0 PS 460V 10 = 0.55kW 230V 22 = 1.5 kw 230V 34 = 4.0 kw 400V 48 = 18.5 kw 400V 11 = 0.75PS 230V 23 = 2.0 PS 230V 35 = 5.0 PS 460V 49 = 25.0 PS 460V 12 = 0.55kW 400V 24 = 1.5 kw 400V 36 = 5.5 kw 230V 50 = 22.0 kw 400V 13 = 0.75PS 460V 25 = 2.0 PS 460V 37 = 7.5 PS 230V 51 = 30.0 PS 460V 38 = 5.5 kw 400V 52 = 30.0 kw 400V 39 = 7.5 PS 460V 53 = 40.0 PS 460V NOTE: Control of the motor set is possible via parameter P205 as P200 is reset to 0 after input confirmation. P201 Nominal frequency S P Hz [ ] The nominal motor frequency determines the U/f break point, at which the FI supplies the nominal current (P204) to the output. P202 Nominal rotation speed S P rpm [ *** ] The nominal motor speed is important for correct calculation and control of the motor slippage and the speed display (P001= 1). *** The setting values are dependent upon the rated frequency inverter power or the selection in parameter P Subject to technical changes BU 0500 GB

65 5.3 Motor data/characteristic curve parameters Parameter Setting value / description / note Device Supervisor Parameter set P203 Nominal current S P A [ *** ] The nominal motor current is a significant parameter for current vector control. P204 Nominal voltage S P V [ ] The >Nominal voltage< matches the mains voltage to the motor voltage. In conjunction with the nominal frequency, this produces the current/frequency characteristic curve. P205 Nominal power P kw [ *** ] The nominal motor output is used to check the motor set via P200. P206 cos ϕ S P [ *** ] The motor cos ϕ is a significant parameter for current vector control. P207 Motor circuit S P = Star 1 = Delta [ *** ] The motor connection is decisive for stator resistance and measurement (P220) and hence for current vector control. P208 Stator resistance S P Ω [ *** ] Motor stator resistance line resistance with a DS motor. Has a direct influence on FI current control. Too high a value may lead to a possible overcurrent, too low to a low motor torque. Parameter P220 can be used for simple measurement. Parameter P208 can be used for manual adjustment or as information on the result of the automatic measurement. NOTE: The stator resistance must be measured automatically by the FI for optimum function of current vector control. P209 Idling current S P A [ *** ] This value is always calculated automatically from the motor data, if the >cosϕ< P206 and >Nominal current< P203 parameters are changed. NOTE: If the value is to be entered directly, then it must be set as the last motor data. This is the only way to guarantee that the value is not overwritten. P210 Static boost increase S P % [ 100 ] The static boost influences the current, which forms the magnetic field. This is equivalent to the idling current of the respective motor and is therefore load-independent. The idling current is calculated via the motor data. The default 100% setting is sufficient for typical applications. The setting values are dependent upon the rated frequency inverter power or the selection in parameter P200. BU 0500 GB Subject to technical changes 65

66 NORDAC SK 500E / 520E Handbook Parameter Setting value / description / note Device Supervisor Parameter set P211 Dynamic boost increase S P % [ 100 ] The dynamic boost influences the torque-generating current and is therefore the load-dependent parameter. The default 100% setting is also sufficient for typical applications. Too high a value may lead to an FI overcurrent. Under load therefore, the output voltage will be raised too sharply. Too low a value will lead to insufficient torque. P212 Slip compensation S P % [ 100 ] Slip compensation increases the output frequency, dependent on load, to keep the DS asynchronous motor speed approximately constant. The default 100% setting is optimal when used with DS asynchronous motors and correct motor data settings. If several motors (different load and/or power) are being driven by one FI, then the slip compensation P212 = 0% should be set. This prevents any adverse influences. This is equally valid for induction motors, that are constructed without slip. P213 ISD control boost S P % [ 100 ] This parameter influences the control dynamic of the frequency inverter's current vector control (ISD control). High settings make the controller fast, low settings slow. This parameter can be adjusted to suit the type of application, e.g. to avoid unstable operation. P214 Derivative torque S P % [ 0 ] This function enables a value for the expected torque requirement to be stored into the current controller. This function can be used in lifting applications for a better load transfer during start-up. NOTE: Motor torque is entered with a positive symbol, generator torque is identified by a negative symbol. The exact opposite applies to anticlockwise rotating field direction. P215 Lead boost S P % [ 0 ] Only with linear characteristic curves (P211 = 0% and P212 = 0%). For drives, which require a high starting torque, this parameter provides the option of switching on an additional current in the start phase. The application time is restricted and can be selected at parameter >Lead boost time< P216. All current and torque current limits (P112, P536, P537 up to 22kW ) that may have been set are disabled during the lead boost time. P216 Lead boost time S P s [ 0 ] Only with linear characteristic curves (P211 = 0% and P212 = 0%). Effect time for increased starting current. 66 Subject to technical changes BU 0500 GB

67 5.3 Motor data/characteristic curve parameters Parameter Setting value / description / note Device Supervisor P2xx Control/characteristic curve parameter Parameter set Output voltage P204 P211 P210 P215 NOTE: typical settings for... P220 P216 Current vector controller (factory setting) P201 to P209 = Motor data P210 = 100% P211 = 100% P212 = 100% P213 = 100% P214 = 0% P215 = n/a P216 = n/a Parameter identification Output frequency P201 Time Linear rev./freq. characteristic curve. P201 to P209 = Motor data P210 = 100% (static boost) P211 = 0% P212 = 0% P213 = n/a P214 = n/a P215 = 0% (dynamic boost) P216 = 0s (dyn. boost time)... up to 240s [ 0 ] The FI automatically determines the motor data with this parameter. In most cases, this results in a significantly improved drive behaviour because DS asynchronous motors are subject to manufacturing tolerances not documented on the rating plate. Identification of all parameters takes some time; do not interrupt the power supply in the meantime. Select a suitable motor in P200 or set parameters P201...P208 manually if the drive behaviour is unsatisfactory. 0 = No identification 1 = Identification R S : The stator resistance only (indicated in P208) is determined by repeated measurements. 2 = Motor identification: all motor parameters (P202, P203, P206, P208, P209) are determined. Procedure: a) Perform motor data identification with cold motor. Motor temperature increase is taken into account during operation. b) The maximum motor power must not be higher by more than one or lower by more than 3 power levels than the rated FI power. c) You should set the motor data as per the rating plate or P200; however, the rated frequency (P201), the rated speed (P202), the voltage (P204), the power (P205) and the Motor connection (P207) should be known at least. d) Error message E019 is generated if identification could not be successfully completed. Also see chap. 6 Error messages. e) Successful motor identification is possible with cables of up to 20 m length. NOTE: P220 is set = 0 after parameter identification. BU 0500 GB Subject to technical changes 67

68 NORDAC SK 500E / 520E Handbook 5.4 Control parameters In SK 520E only when an incremental encoder is used. Connection see chapt Parameter Setting value / description / note Device Supervisor Parameter set P300 Servo mode SK 520E P [ 0 ] This parameter enables the speed regulation with speed measurement via incremental encoder. This results in a very stable speed behaviour down to motor standstill. 0 = Off 1 = On NOTE: An incremental encoder must be connected for correct functioning (see chapt. 2.10) and the correct pulse number specified in parameter P301. P301 Encoder pulse number SK 520E [ 6 ] Input of the pulse-count per rotation of the attached incremental encoder. If the direction of rotation of the encoder does not match that of the FI, (according to installation and wiring), it is possible to compensate for this by choosing the corresponding negative increment numbers = 500 Increments 1 = 512 Increments 2 = 1000 Increments 3 = 1024 Increments 4 = 2000 Increments 5 = 2048 Increments 6 = 4096 Increments 7 = 5000 Increments 17 = Increments 8 = -500 Increments 9 = -512 Increments 10 = Increments 11 = Increments 12 = Increments 13 = Increments 14 = Increments 15 = Increments 16 = Increments P310 Rotation speed control P SK 520E P % [ 100 ] P Share of the encoder (proportional increase). Boost factor, by which the rotation speed differential is multiplied out from the desired and actual frequency. A value of 100% means that a rotation speed differential of 10% produces a desired a value of 10%. Values and that are too high can cause the output rotation speed to oscillate. P311 Rotation speed control I SK 520E P %/ms [ 20 ] I Share of the encoder (Integration share). The integration share of the control completely eliminates any control deviation. The value indicates the size of the desired value change per m/s is. Values at that are too low allow the control to slowdown (reset time is too long). P312 Torque current control P SK 520E S P % [ 200 ] Current control for the torque current. The higher the current control parameters are set, the more precisely the desired value of the current is maintained. Excessively high values in P312 generally lead to high-frequency vibrations at low speeds. On the other hand, excessively high values in P313 generally produce low frequency vibrations across the whole rotation speed range. If the value "Zero" is entered into P312 and P313, then the torque current control is switched off. In this case only the motor model lead is used. 68 Subject to technical changes BU 0500 GB

69 5.4 Control parameters Parameter Setting value / description / note Device Supervisor Parameter set P313 (P) Torque current control I SK 520E S P %/ms [ 125 ] I Share of the torque current control. (See also P312 >Torque current control P<) P314 Torque current control limit SK 520E S P V [ 400 ] Determines the maximum voltage increase from the torque current control. The higher the value, the greater is the maximum effect that can be exercised by the torque current control. Excessive values in P314 can lead particularly to instability when crossing to the weak field zone (see P320). The value for P314 and P317 should always be set roughly the same, so that field and torque current control are balanced. P315 Field current control P SK 520E S P % [ 200 ] Current control for the field current. The higher the current control parameters are set, the more precisely the desired value of the current is maintained. Excessively high values for P315 generally lead to high frequency vibrations at low speeds. On the other hand excessively high values that P316 mostly produce low frequency vibrations across the whole rotation speed range. If the value "zero" is entered into P315 and P316, then the field current control is switched off. In this case only the motor model lead is used. P316 Field current control I SK 520E S P %/ms [ 125 ] I Share of the field current control. See also P315 >Field current control P< P317 Field current control limit SK 520E S P V [ 400 ] Determines the maximum voltage increase from the torque current control. The higher the value, the greater is the maximum effect that can be exercised by the field current control. Excessive values in P317 can lead particularly to instability when crossing to the weak field zone (see P320). The value for P314 and P317 should always be set roughly the same, so that field and torque current control are balanced. P318 Weak field control P SK 520E S P % [ 150 ] The weak field control reduces the desired field value when the synchronic rotation speed is exceeded. Generally, the weak field control has no function; for this reason, the weak field control need only be set, if the rotation speeds are to exceed the nominal motor rotation speeds. Excessive values for P318 / P319 will lead to control vibration. If the values are too low, the field is not weakened sufficiently during dynamic acceleration or delay times. Setting back the current control prevents it from inputting the desired current value. P319 Weak field control I SK 520E S P %/ms [ 20 ] Affects only the weak field area, see P318 >Weak field control P< P320 Weak field control limit SK 520E S P % [ 100 ] The weak field limit determines, at which speed / current the control will begin to weaken the field. At a set value of 100% the control will begin to weaken the field at approximately the synchronic speed. If values much larger than the standard values have been set at P314 and/or P317, then the weak field limit should be correspondingly reduced, so that the current control is in fact available throughout the control range. BU 0500 GB Subject to technical changes 69

70 NORDAC SK 500E / 520E Handbook Parameter Setting value / description / note Device Supervisor Parameter set P321 Rotation speed control increase I SK 520E S P [ 0 ] During brake ventilation time (P107/P114), the I share of the rotation speed control is raised. This leads to better loader take-up, especially during vertical movement. 0 = P311 x 1 1 = P311 x 2 2 = P311 x 4 3 = P311 x 8 4 = P311 x 16 P325 Encoder function SK 520E [ 0 ] The actual rotation speed value, supplied by an incremental encoder to the FI, can be used for various functions by the inverter. 0 = Rotation speed measurement. Servo mode: The actual rotation speed value of the motor is used for the Servo mode of the FI. For this function the ISD control cannot be switched off. 1 = PID actual frequency value: The actual rotation speed of a system is used for rotation speed control. This function can also be used for controlling a motor with a linear characteristic curve. It is also possible to use an incremental encoder for rotation control that is not mounted directly onto the motor. P413 P416 determine the control. 2 = Frequency addition: The rotation speed deduced is added to the current desired value. 3 = Frequency subtraction: The rotation speed deduced is subtracted from the current desired value. 4 = Maximum frequency: The maximum possible output frequency / rotation speed is limited by the rotation speed of the encoder. P326 Encoder conversion SK 520E [ 1.00 ] If the incremental encoder is not mounted directly onto the motor shaft, then the current correct conversion ratio of motor rotation speed to encoder rotation speed must be set. Motor speed P326 = encoder speed only when P325 = 1, 2, 3 or 4, therefore not in Servo mode (motor rotation speed control) P327 Drag error limit SK 520E rpm [ 0 ] The limit value for a permitted maximum drag fault can be set. If this value is reached, the FI switches off and indicates error E = OFF only when P325 = 0, therefore in Servo mode (motor rotation speed control) 70 Subject to technical changes BU 0500 GB

71 5.5 Control terminals 5.5 Control terminals Parameter Setting value / description / note Device Supervisor Parameter set P400 Function analogue input 1 P [ 1 ] The frequency inverter's analogue input can be used for various functions. It is to be noted that only one of the functions given below is possible. If for example, an actual PID frequency was selected, the frequency set point cannot be an analogue signal. The set point can, for example, be specified via a fixed frequency. Analogue functions: 0 = Off, the analogue input has no function. After the FI has been enabled via the control terminals, it will supply any set minimum frequency (P104). 1 = Set frequency, the given analogue range (P402/P403) varies the output frequency between the set minimum and maximum frequencies (P104/P105). 2 = Torque current limit, based on the set torque current limit (P112), this can be altered by means of an analogue value. 100% set point here corresponds to the set torque current limit. 20% cannot be undershot (with P300 = 1, not below 10%)! 3 = Actual PID frequency *, is required to construct a control loop. The analogue input (actual value) is compared with the set point (e.g. fixed frequency). The output frequency is changed as much as possible until the actual value equals the set point. (see control variables P413...P415) 4 = Frequency addition **, the supplied frequency value is added to the set point. 5 = Frequency subtraction **, the supplied frequency value is subtracted from the set point. 6 = Current limit, based on the set current limit (P536), this can be altered by means of an analogue value. 7 = Maximum frequency, the maximum frequency of the FI is varied. 100% correspond to the setting in parameter P411. 0% correspond to the setting in parameter P410. The values for the minimum/maximum output frequency (P104/P105) cannot be exceeded or undershot. 8 = Actual PID frequency limitation *, as Function 3 Actual PID Frequency; however, the output frequency cannot fall below the programmed minimum frequency value in parameter P104. (no rotation direction reversal) 9 = Actual PID frequency monitoring *, as Function 3 Actual PID Frequency; however, the FI switches off the output frequency, when the minimum frequency P104 is reached. 10 = Torque servo mode, in the Servo mode P300 the motor torque can be set using this function. 11 = Lead torque, function that enables a value for the anticipated torque requirement to be loaded into the controller (interference factor switching). This function can be used to improve the load take-up of hoists with separate load detection. 12 = reserved 13 = Multiplication, the set point is multiplied with the analogue value supplied. The analogue value aligned to 100% corresponds to a multiplication factor of continued on the following pages BU 0500 GB Subject to technical changes 71

72 NORDAC SK 500E / 520E Handbook Parameter Setting value / description / note Device Supervisor Parameter set 14 = Actual value process controller *, activates the process controller, analogue input 1 is connected to the actual value encoder (compensator, pressure sensor, flow volume meter, etc.). The mode (0-10 V or 0/4-20 ma) is set in P = Set point process controller *, as function 14, however the set point is specified (e.g. by a potentiometer). The actual value must be specified using a different input. 16 = Lead process control *, adds an additional settable set point according to the process control. *) further details regarding the process controller can be found in chapt. 8.2 and P400. **) The limits of these values are formed by the parameters -Minimum frequency additional set points- P410 and -Maximum frequency additional setpoints- P411. Digital functions: 21 = Enable right 22 = Enable left 23 = Phase seq. reversal 24 = Fixed frequency 1 25 = Fixed frequency 2 26 = Fixed frequency 3 27 = Fixed frequency 4 28 = Parameter switch Bit 0 29 = Hold frequency 30 = Block voltage 31 = Quick stop 32 = Error acknowledgement 33 = PTC resistor input 34 = Remote control 35 = Jog frequency 36 = Maintain frequency motor pot 37 = Parameter switch Bit 1 38 = Watchdog 39 = Set point 1 on/off 40 = Set point 2 on/off 41 = Fixed frequency 5 42 =... Reserved (49) 50 = PID Control on/off 51 = Lock enable right 52 = Lock enable left 53 = reserved 67 = Increase jog frequency motor pot 68 = Decrease jog frequency motor pot 69 = reserved 70 = Bit 0 fixed frequency array 71 = Bit 1 fixed frequency array 72 = Bit 2 fixed frequency array 73 = Bit 3 fixed frequency array 74 = Bit 4 fixed frequency array 75 = 82 reserved A detailed description of the digital functions follows the description of parameters P420...P425. The functions of digital inputs corresponds to those of the analogue inputs. Permissible voltage when using the digital functions: V 72 Subject to technical changes BU 0500 GB

73 5.5 Control terminals Parameter Setting value / description / note Device Supervisor Parameter set P401 Mode analogue input 1 S [ 0 ] 0 = 0 10V limited: An analogue set point smaller than the programmed adjustment 0% (P402) does not lead to undershooting of the programmed minimum frequency (P104). Therefore does not lead to any rotation direction reversal. 1 = 0 10V: A set point smaller than the programmed adjustment 0% (P402) does not lead to undershooting of the programmed minimum frequency (P104). This allows a change in rotation direction with a simple voltage source and potentiometer to be carried out. e.g. internal set point with rotation direction change: P402 = 5V, P104 = 0Hz, potentiometer 0 10V rotation direction reversal at 5V when potentiometer is in the central position. When reversing (hysteresis = ± P505), the drive is at a standstill if the minimum frequency (P104) is lower than the absolute minimum frequency (P505). A brake controlled by the FI engages during the hysteresis time. The drive reverses when the minimum frequency is reached if the minimum frequency (P104) exceeds the absolute minimum frequency (P505). In the hysteresis range ± P104 the FI provides the minimum frequency (P104); a brake controlled by the FI does not engage. 2 = 0 10V monitored: If the minimum set point (P402) is undershot by 10% of the differential value from P403 and P402, the FI output switches off. Once the set point is greater than [P402 (10%*(P403-P402))], it will again deliver an output signal. E.g. set point 4-20 ma: P402: Adjustment 0% = 1V; P403: Adjustment 100% = 5V; -10% equals -0.4V; i.e. 1-5V (4-20mA) normal working range, 0.6-1V = minimum frequency set point, output switch off occurs below 0.6V (1.2mA). f / Hz P105 (fmax) P104 (fmin) OFF = 2.0V - 10% * 8.0V = 1.2V P402 = 2.0V = 8.0V P403 = 10,0V U/V 3 = - 10V 10V: An analogue set point smaller than the programmed adjustment 0% (P402) could lead to a rotation direction reversal. This allows a change in rotation direction with a simple voltage source and potentiometer to be carried out. e.g. internal set point with rotation direction change: P402 = 5V, P104 = 0Hz, potentiometer 0 10V rotation direction reversal at 5 V when potentiometer is in the central position. When reversing (hysteresis = ± P505), the drive is at a standstill if the minimum frequency (P104) is lower than the absolute minimum frequency (P505). A brake controlled by the FI has not engaged during the hysteresis time. The drive reverses when the minimum frequency is reached if the minimum frequency (P104) exceeds the absolute minimum frequency (P505). In the hysteresis range ± P104 the FI provides the minimum frequency (P104); a brake controlled by the FI does not engage. BU 0500 GB Subject to technical changes 73

74 NORDAC SK 500E / 520E Handbook Parameter Setting value / description / note Device Supervisor P402 Adjustment analogue input 1 0% S Parameter set V [ 0.00 ] This parameter sets the voltage that should correspond with the minimum value of the selected function for the analogue input 1. This value is equal to the set point set by the P104 >Minimum frequency< in the default setting (set point). Typical setpoints and corresponding settings: 0 10 V 0.00 V 2 10 V 2.0 V (for function 0-10 V monitored) 0 20 ma 0.00 V (internal resistance approx. 250Ω) 4 20 ma 1.00 V (internal resistance approx. 250Ω) P403 Adjustment analogue input 1 100% S V [ ] This parameter sets the voltage that should correspond with the maximum value of the selected function for the analogue input 1. This value is equal to the set point set by the P105 >Maximum frequency< in the default setting (set point). Typical setpoints and corresponding settings: 0 10 V V 2 10 V V (for function 0-10 V monitored) 0 20 ma 5.00 V (internal resistance approx. 250Ω) 4 20 ma 5.00 V (internal resistance approx. 250Ω) P P403 P401 = V limited P401 = V not limited output frequency P105 output frequency P105 positive positive P V 2.5V 5.0V 10.0V P402 P403 setpoint voltage P104 negative 0.0V 2.5V 5.0V 10.0V P402 P403 setpoint voltage 74 Subject to technical changes BU 0500 GB

75 5.5 Control terminals Parameter Setting value / description / note Device Supervisor Parameter set P404 Filter analogue input 1 S ms [ 100 ] Adjustable digital low-pass filter for the analogue signal. Interference peaks are flattened, the reaction time is extended. P405 Function analogue input 2 P [ 0 ] This parameter is identical with P400. P406 Mode analogue input 2 S [ 0 ] 0 = 0 10V limited 1 = 0 10V 2 = 0 10V monitored 3 = - 10V 10V This parameter is identical with P401. P402/403 change to P406/407. P V [ 0.00 ] P V [ ] Adjustment analogue input 2 0% This parameter is identical with P402. Adjustment analogue input 2 100% This parameter is identical with P403. S S P409 Filter analogue input 2 S ms [ 100 ] P410 This parameter is identical with P404. Minimum frequency additional setpoints P Hz [ 0.0 ] P Hz [ 50.0 ] Is the minimum frequency, that can have an effect on the set point by means of the additional setpoints. Auxiliary setpoints are all frequencies that are additionally delivered to the inverter for further functions. Actual frequency PID Frequency addition Frequency subtraction Auxiliary setpoints via BUS Process controller Minimum frequency above analogue set point (potentiometer) Maximum frequency additional setpoints Is the maximum frequency, that can have an effect on the set point by means of the additional setpoints Auxiliary setpoints are all frequencies that are additionally delivered to the inverter for further functions. Actual frequency PID Frequency addition Frequency subtraction Auxiliary setpoints via BUS Process controller Maximum frequency above analogue set point (potentiometer) P BU 0500 GB Subject to technical changes 75

76 NORDAC SK 500E / 520E Handbook Parameter Setting value / description / note Device Supervisor Parameter set P412 process controller set point value S P V [ 5.0 ] For fixed specification of a set point for the process controller that should only be rarely modified. Only with P400 = (process controller). Further details can be found in Chapter 8.2. P413 P-percentage PID controller S P % [ 10.0 ] This parameter is only effective, if the function Current PID frequency has been selected. The P percentage of the PID controller determines the frequency jump during a system deviation with reference to the negative deviation. e.g.: With a setting of P413 = 10% and an offset of 50%, 5% is added to the current set point. P414 I- percentage PID controller S P %/ms [ 1.00 ] This parameter is only effective, if the function Actual PID frequency has been selected. The I-percentage of the PID controller determines the frequency change, dependent on time, during a negative deviation. P415 D- percentage PID controller S P %ms [ 1.0 ] This parameter is only effective, if the function Actual PID frequency has been selected. The D-percentage of the PID controller determines the frequency change, across time, during a negative deviation. P416 Ramp PID controller S P s [ 2.00 ] This parameter is only effective, if the function Actual PID frequency has been selected. Ramp for PID set point main setpoint fixed frequency 1-5 start-off frequency analogue input 1 analogue input 2 ControlBox scaling P400-P404 scaling P405-P409 max. frequency P105 setpoint ramp P416 max. frequency P105 (monitored, limited) max. frequency P105 (not limited) bus setpoint 1,2,3 secondary setpoint source analogue input 1 analogue input 2 scaling P400-P404 scaling P405-P409 min. frequency P104 max. frequency P410 additional setpoint PID controller P413 (P-component) P414 ( I-component) P415 (D-component) frequency ramp P102, P103 bus setpoint 2 bus setpoint 3 min. frequency P104 (monitored, limited) - max. frequency P105 (not limited) enc min. frequency P411 additional setpoint Illustration: PID- Controller flow chart P417 Analogue output offset S P V [ 0.0 ] In the analogue output function an offset can be entered in order to simplify the processing of the analogue signal in other equipment. If the analogue output has been programmed with a digital function, then in this parameter the difference between the switch-on point and the switch-off point can be set (hysteresis). 76 Subject to technical changes BU 0500 GB

77 5.5 Control terminals Parameter Setting value / description / note Device Supervisor Parameter set P418 Function analogue output P [ 0 ] Analogue functions: An analogue voltage ( V) can be taken from the control terminals (max. 5mA). Various functions are available, the following applies: 0V analogue voltage always corresponds to 0% of the selected value. 10V always corresponds to the rated motor values (if not otherwise mentioned) multiplied by the P419 standardisation factor, e.g. 10V= Rated motor value x P419 /100% 0 = no function, no output signal at terminals. 1 = Actual frequency, the analogue voltage is proportional to the frequency inverter output frequency. 2 = Actual speed, this is the synchronous speed calculated by the FI based on the existing set point. Load-dependent speed fluctuations are not taken into account. If Servo mode is being used, the measured speed will be supplied via this function. 3 = Output, the effective value of the output current delivered by the FI. 4 = Torque current, displays the motor load torque calculated by the FI. (100% = P112) 5 = Voltage, this is the output voltage delivered by the FI. 6 = DC-Link, is the DC voltage in the frequency inverter. This is not based on the rated motor data. 10V standardised at 100% is equivalent to 450V DC (230V) or 850V DC (480V)! 7 = Value of P542, the analogue output can be set using parameter P542 independently of the current operating status of the FI. During Bus control (parameter order) this function can supply such things as an analogue value from the FI, triggered by the controller. 8 = Apparent power, is the current apparent power of the motor calculated by the FI. 9 = Effective power, is the current effective power calculated by the FI. 10 = Torque [%], is the current torque calculated by the inverter. 11 = Field [%], is the current field in the motor calculated by the FI. 12 = Output frequency ±, the analogue voltage is proportional to the output frequency of the FI, where the null point has been shifted to 5V. For rotation to the right, values between 5V and 10V are output, and for rotation to the left values between 5V and 0V. 13 = Actual rotation speed ±, is the synchronous rotation speed calculated by the FI, based on the current set point, where the null point has been shifted to 5V. For rotation to the right, values between 5V and 10V are output, and for rotation to the left values between 5V and 0V. If Servo mode is being used, the measured speed will be supplied via this function. 14 = Torque [%] ±, is the current torque calculated by the FI, where the null point has been shifted to 5V. For drive torque, values of between 5V and 10V output, and for generating torque, values of between 5V and 0V. 30 = Set point frequency before ramp, displays the frequency resulting from any upstream controllers (ISD, PID,...). This is then the set frequency for the power level after it has been adapted via the start-up or braking ramp (P102, P103). 31 = Value via BUS, the analogue output is controlled via a bus system. The process data is directly transferred (P546, P547, P548).... continued on the following pages BU 0500 GB Subject to technical changes 77

78 NORDAC SK 500E / 520E Handbook Parameter Setting value / description / note Device Supervisor Parameter set Digital functions: All relay functions described in Parameter >Function Relay 1< P434 can also be transferred via the analogue output. If a condition is met, 10V is present at the output terminals. A negation of the function can be specified in Parameter >Standardisation analogue output< P = External Brake 16 = Inverter working 17 = Current limit 18 = Instantaneous current limit 19 = Frequency limit 20 = Set point reached 21 = Error 22 = Warning 23 = Overcurrent warning 24 = Motor overheating warning 25 = Torque current limit active 26 = Value of P541, external control 27 = Generator torque current limit 28 = reserved 34 = reserved 44 = Bus In Bit 0 45 = Bus In Bit 1 46 = Bus In Bit 2 47 = Bus In Bit 3 48 = Bus In Bit 4 49 = Bus In Bit 5 50 = Bus In Bit 6 51 = Bus In Bit 7 52 = Output via bus P419 Standardisation analogue output P % [ 100 ] Analogue functions P418 (= , 30, 31) This parameter can be used to modify the analogue output to the required working range. The maximum analogue output (10 V) is equal to the standardised value of the corresponding selection. Therefore, if this parameter is increased from 100% to 200% at a constant operating point, the analogue output voltage is halved. 10 V output signal then represent double the nominal value. This logic is reversed with negative values. A set point of 0% is then output with 10 V at the output and -100% with 0V. Digital functions P418 (= , ) For the functions Current limit (= 17), Torque Current limit (= 18) and Frequency limit (= 19) the switching threshold can be set using this parameter. A value of 100% refers to the corresponding motor nominal value here (see also P435). With a negative value, the output function is output negated (0/1 1/0). 78 Subject to technical changes BU 0500 GB

79 5.5 Control terminals Parameter Setting value / description / note Device Supervisor P420 Function digital input 1 Parameter set Enable right as factory setting, control terminal 21 [ 1 ] Various functions can be programmed. These can be taken from the following table. P421 Function digital input Enable left as factory setting, control terminal 22 [ 2 ] Various functions can be programmed. These can be taken from the following table. P422 Function digital input Parameter switch Bit 0 as factory setting, control terminal 23 [ 8 ] Various functions can be programmed. These can be taken from the following table. P423 Function digital input Fixed frequency 1 (P429) as factory setting, control terminal 24 [ 4 ] Various functions can be programmed. These can be taken from the following table. P424 Function digital input [ 0 ] No function as factory setting, control terminal 25 Various functions can be programmed. These can be taken from the following table. P425 Function digital input 6 SK 520E [ 0 ] No function as factory setting, control terminal 26 Various functions can be programmed. These can be taken from the following table. Function digital input 7 = P470 (SK 520E only), control terminal Function descriptions are given on the following pages. BU 0500 GB Subject to technical changes 79

80 NORDAC SK 500E / 520E Handbook List of the possible functions of the digital inputs P P425, P470 Value Function Description Signal 00 No function Input switched off Enable right The FI supplies an output signal with a clockwise rotation field if a positive set point is applied. 0 1 flank (P428 = 0) 02 Enabled left The FI supplies an output signal with a counter clockwise rotation field if a positive set point is applied. 0 1 flank (P428 = 0) high high Provide a high level for the enable signal (connect control terminals 21-42) if the drive is to start up at power-on (P428 = 1). The FI is blocked if the functions enabled right and enabled left are applied at the same time. 03 Phase seq. reversal Causes the rotation field to reverse (combined with enabling right or left). 04 Fixed frequency 1 1 The frequency from P429 is added to the current set point value. high 05 Fixed frequency 2 1 The frequency from P430 is added to the current set point value. high 06 Fixed frequency 3 1 The frequency from P431 is added to the current set point value. high 07 Fixed frequency 4 1 The frequency from P432 is added to the current set point value. high If several fixed frequencies are applied at the same time, then they are added algebraically according to sign. In addition the analogue set point value (P400) and, if necessary, the minimum frequency (P104) are added. 08 Parameter switch Bit 0 Selection of the active parameter set 1 4 (P100). high high 09 Hold frequency During the run-up or braking phase, a Low level will cause the output frequency to be "maintained". A High level allows the ramp to proceed. low 10 Voltage block 2 The FI output voltage is switched off, and the motor coasts down. low 11 Emergency stop 2 The FI reduces the frequency according to the programmed emergency stop time from P Fault acknowledgement 2 Fault acknowledgement with an external signal. If this function is not programmed, a fault can also be acknowledged by setting enable (P506) to low. 13 PTC resistor input 2 Analogue evaluation of the present signal. Switching threshold approx. 2.5 V. Switch-off delay =2 sec, warning after 1 sec. 14 Remote control 2 With Bus system control at the Low level is switched to control via control terminals. 15 Jog frequency 1 The frequency fixed value can be set using the UP / DOWN and ENTER keys (P113) when control occurs with the ControlBox or ParameterBox. 16 Maintain frequency motor pot As setting value 09, is not, however, maintained beneath the minimum frequency P104 and above the maximum frequency P Parameter switch Bit 1 Selection of the active parameter set 1 4 (P100). high 18 Watchdog 2 Input must see a High flank cyclically (P460), otherwise error E012 will cause a shutdown. Function starts with the first High flank. 19 Set point 1 on/off 20 Set point 2 on/off Analogue input switch-on and switch-off 1/2 (High = ON). The low signal sets the analogue input to 0%, which does not result in a standstill for a minimum frequency (P104) > the absolute minimum frequency (P505). 21 Fixed frequency 5 1 The frequency from P433 is added to the current set point value. high low 0 1 flank level high high low 0 1 flank high... continued on the following pages 80 Subject to technical changes BU 0500 GB

81 5.5 Control terminals Value Function Description Signal reserved Impulse functions: Description on the following page. 30 PID controller on/off Switching on and off the PID controller/process controller function (High = EIN) 31 Lock enable right 2 Blocks the >Enable right/left< via a digital Input or Bus control. low 32 Lock enable left 2 Does not depend on the actual direction of rotation of the motor (e.g. following negated set value). low high Impulse functions: Description on the following page reserved 47 Increase frequency 48 Reduce frequency The output frequency can be continuously varied together with enable R/L. Both inputs must simultaneously be High for 0.5 secs in order to store a current value in P113. This value is used as the next start-up value for the same direction selection, otherwise start occurs with f MIN. high high 49 reserved 50 Bit 0 fixed frequency array 51 Bit 1 fixed frequency array 52 Bit 2 fixed frequency array 53 Bit 3 fixed frequency array 54 Bit 4 fixed frequency array reserved Binary encoded digital inputs for generating up to 32 fixed frequencies. (P465: ) high high high high high 1 2 If no digital inputs are programmed for left or right enabling, then the issue of a fixed frequency or the jog frequency will cause the frequency inverter to be enabled. The rotation field direction depends on the sign of the set point value. Also applies to Bus control (RS232, RS485, CANbus, CANopen, DeviceNet, Profibus, InterBus, AS Interface)... continued on the following pages BU 0500 GB Subject to technical changes 81

82 NORDAC SK 500E / 520E Handbook Impulse input functions: kHz (for DIG 2 and DIG 3 only) The respective input will evaluate the present impulse frequency for these functions. The frequency range 2kHz through 22kHz covers the value range of 0 to 100%. The inputs operate up to a maximum impulse frequency of 32kHz. The voltage may range between 15V and 24V, the duty cycle between 50% and 80%. Value Function Description Signal 26 Torque current limit 2 Adjustable load limit, when reached the output frequency is reduced. P112 Impulses 27 Actual PID frequency 2 3 Possible actual value return for PID controller Impulses 28 Frequency Addition 2 3 Addition to other frequency setpoints Impulses 29 Frequency Subtraction 2 3 Subtraction from other frequency setpoints Impulses 33 Current limit 2 Based on the set current limit (P536), this can be changed using the digital/analogue input. 34 Maximum frequency 2 3 The maximum FI frequency in the analogue zone is set. 100% correspond to the setting in parameter P411. 0% correspond to the setting in parameter P410. The values for the minimum/maximum output frequency (P104/P105) cannot be exceeded or undershot. Impulses Impulses 35 Actual PID controller frequency limited Actual PID controller frequency monitored 2 3 Needed to form a control loop. The digital/analogue input (current value) is compared with the set point value (e.g. other analogue input or fixed frequency). The output frequency is changed as much as possible until the actual value equals the set point. (see control variables P413 P416) The output frequency cannot fall below the programmed minimum frequency value in parameter P104.. (no rotation direction change!) As function 35 >Current PID frequency<, however as the >Minimum frequency< P104 is reached the FI switches off the output frequency. Impulses Impulses 37 Servo mode torque 2 In Servo mode the motor torque can be set or limited via this function. 38 Lead torque 2 A function that enables a value for the anticipated torque requirement to be applied to the control (interference factor switching). This function can be used to improve the load take-up of hoists with separate load detection. P214 Impulses Impulses 39 Multiplication 3 This factor multiplies the main set point value. Impulses 40 PI process controller actual value Impulses as P400 = PI process controller set point Impulses Further process controller details can be found in chapt PI process controller lead Impulses 2 3 Also applies to Bus control (RS232, RS485, CANbus, CANopen, DeviceNet, Profibus, InterBus, AS Interface) The limits of these values are formed by the parameters >Minimum frequency additional set points< P410 and >Maximum frequency additional setpoints< P Subject to technical changes BU 0500 GB

83 5.5 Control terminals Parameter Setting value / description / note Device Supervisor Parameter set P426 Rapid stop time P s [ 0.10 ] Used to set the braking time for the rapid stop function which can be triggered via a digital input, bus actuation, keyboard or automatically in cases of errors. The rapid stop time is the time required for the linear frequency reduction from the maximum frequency (P105) to 0 Hz. If an actual set point <100% is used, the rapid stop time decreases accordingly. P427 Rapid stop during malfunction S [ 0 ] Activation of an automatic emergency stop the following fault 0 = OFF: Automatic emergency stop following fault is disabled 1 = Mains supply failure: Automatic emergency stop following mains supply failure 2 = Fault: Automatic emergency stop following fault 3 = Mains supply failure and faults: Automatic emergency stop following mains supply failure and faults P428 Automatic start up S P [ 0 ] To be enabled in the default setting (P428 = 0 Off) the FI requires a flank (signal change from "low high") at the current digital input. With On 1 the inverter reacts at a High level. This function is only possible if control of the FI is being carried out using the digital inputs. (see P509=0/1) In certain cases, the FI has to run up directly following mains switch on. P428 = 1 On can be set for this purpose. If the enable signal is permanently switched on, or provided with a cable jumper, the FI runs up immediately. P429 Fixed frequency 1 P Hz [ 0 ] Following its issue via a digital input and in enabling of the FI (right or left), the fixed frequency is used as a set point value. A negative setting value will cause a rotation and direction change (dependent upon the enable rotation direction P420 P425, P470). If several fixed frequencies are issued at the same time, the individual values are added up according to their sign. This applies also for combination with the jogger frequency (P113), with the analogue set point value (if P400 = 1) all the minimum frequency (P104). The frequency limits (P104 = f min, P105 = f max ) cannot be exceeded or undershot. If none of the digital inputs is programmed for enabling (right or left), the fixed frequency alone will cause enabling. A positive fixed frequency corresponds to enabling right, a negative to enabling left.. P430 Fixed frequency 2 P Hz [ 0 ] For a functional description of the parameter, see P429 >Fixed frequency 1< P431 Fixed frequency 3 P Hz [ 0 ] For a functional description of the parameter, see P429 >Fixed frequency 1< P432 Fixed frequency 4 P Hz [ 0 ] For a functional description of the parameter, see P429 >Fixed frequency 1< BU 0500 GB Subject to technical changes 83

84 NORDAC SK 500E / 520E Handbook Parameter Setting value / description / note Device Supervisor Parameter set P433 Fixed frequency 5 P Hz [ 0 ] For a functional description of the parameter, see P429 >Fixed frequency 1< P434 Function output 1 (K1) P [ 1 ] Control terminals 1/2: Settings 3 to 5 and 11 work with a 10% hysteresis, i.e. the relay contact picks up (fct. 11 opens) when the limit value is reached and opens (fct. 11 closes) when it falls beneath a low value of 10%. Setting/function Relay contact... with limit value or function 0 = No function open 1 = External brake, to control a mechanical brake on the motor. The relay operates at a programmed absolute minimum frequency (P505). For typical brakes a set point delay of secs should be programmed (see also P107). closes A mechanical brake should have direct AC switching (Please pay attention to the technical specifications of the relay contacts) 2 = FI is running, the closed relay contact sends a voltage to the inverter output (U - V - W). 3 = Current limit, based on the motor nominal current set in P203. By means of the standardisation (P435) this value can be adjusted 4 = Torque current limit, based on motor data settings in P203 and P206. Signals a corresponding torque load on the motor. By means of the standardisation (P435) this value can be adjusted 5 = Frequency limit, based on motor nominal frequency setting in P201. By means of the standardisation (P435) this value can be adjusted 6 = Set point reached, indicates that the FI has completed the frequency increase or decrease. Set point frequency = actual frequency! With difference of 1 Hz and more Set point not reached - contact drops out. 7 = Fault, global fault report, the fault is active or not yet acknowledged. Ready for operation-closes 8 = Warning, global warning, a limited value was reached, that could lead to subsequent FI switch off. 9 = Overcurrent warning, e.g. 130% FI nominal current for 30 seconds 10 = Motor overheating (warning): The motor temperature is evaluated via a digital input. Motor is too hot. Warning occurs immediately, overheating switch off after 2 seconds. 11 = Torque current limit/current limit active (warning): Limit value in P112 or P536 has been reached. P435 is of no importance. Hysteresis = 10%. 12 = Relay via P541 external control, using parameter P541 (bit0) the relay can be controlled independently of the current operating status of the FI. 13 = Torque limit gen. active: Limit value in P112 has been reached in the generating field. Hysteresis = 10% closes closes closes closes closes opens opens opens opens opens closes closes 84 Subject to technical changes BU 0500 GB

85 5.5 Control terminals Parameter Setting value / description / note Device Supervisor Parameter set 14 = reserved = Bus IO In Bit 0 / Bus In Bit 0 closes 31 = Bus IO In Bit 1 / Bus In Bit 1 closes Further details in the BUS handbooks 32 = Bus IO In Bit 2 / Bus In Bit 2 closes 33 = Bus IO In Bit 3 / Bus In Bit 3 closes 34 = Bus IO In Bit 4 / Bus In Bit 4 closes 35 = Bus IO In Bit 5 / Bus In Bit 5 closes 36 = Bus IO In Bit 6 / Bus In Bit 6 closes 37 = Bus IO In Bit 7 / Bus In Bit 7 closes 38 = Output via BUS closes P435 Standardisation output 1 P % [ 100 ] Modification of the relay function limit values. With a negative value, the output function is output negated. Current limit = x [%] P203 >Rated motor current< Torque current limit = x [%] P203 P206 (calculated rated motor torque) Frequency limit = x [%] P201 >Rated motor frequency< Values that fall within +/-20% are limited internally to 20%. P436 Hysteresis output 1 S P % [ 10 ] Difference between switch-on and switch-off point to prevent oscillation of the output signal. P441 Function output 2 (K2) P [ 7 ] Control terminals 3/4: Functions are identical with P434! P442 Standardisation output 2 P % [ 100 ] Functions are identical with P435! P443 Hysteresis output 2 S P % [ 10 ] Functions are identical with P436! P450 Function output 3 (DOUT 1) SK 520E P [ 0 ] Control terminals 5/40: Functions are identical with P434! Digital output, 15 V against DGND. P451 Standardisation output 3 SK 520E P % [ 100 ] Functions are identical with P435! BU 0500 GB Subject to technical changes 85

86 NORDAC SK 500E / 520E Handbook Parameter Setting value / description / note Device Supervisor Parameter set P452 Hysteresis output 3 SK 520E S P % [ 10 ] Functions are identical with P436! P455 Function output 4 (DOUT 2) SK 520E P % [ 10 ] Control terminals 7/40: Functions are identical with P434! Digital output, 15 V against DGND. P456 Standardisation output 4 SK 520E P % [ 100 ] Functions are identical with P435! P457 Hysteresis output 4 SK 520E S P % [ 10 ] Functions are identical with P436! P460 Time Watchdog S 0.0 / s [ 10.0 ] P Hz [ 0 ] P Hz [ 0.0 ] = The time interval between the expected watchdog signals (programmable function of digital inputs P420 P425). If this time interval passes without a pulse being registered, a switch off occurs with an E012 error message. 0.0 = Customer error, as soon as a low-high flank is registered at the digital input (function 18), the FI switches off with error E012. Fixed frequency array In the array levels up to 31 different fixed frequencies can be set, which in turn can be selected with functions for the digital inputs. Minimum frequency process controller Using the minimum frequency process controller the controller portion can be kept to a minimum with a guide value of zero in order to allow for mechanical compensator alignment. Further details in P400 and chapter 8.2. P P470 Function digital input 7 SK 520E Control terminals 27/40: Functions are identical with P420...P425! P Switch on/off delay S ,000 s [ ] Adjustable switch on/off delay for the digital inputs and the digital functions of analogue inputs. Can be used as switch-on filter or simple sequence control. [01] = Digital input 1 [02] = Digital input 2 [03] = Digital input 3 [04] = Digital input 4 [05] = Digital input 5 [06] = Digital input 6 (SK 520E only) [07] = Digital input 7 (SK 520E only) [08] = Digital function analogue input 1 [09] = Digital function analogue input 2 Positive values = switch-on delay Negative values = switch-off delay 86 Subject to technical changes BU 0500 GB

87 5.5 Control terminals Parameter Setting value / description / note Device Supervisor Parameter set P Function Bus I/O In Bits S [ 12 ] The Bus I/O In Bits are regarded as digital inputs. They can be set to the same functions (P ). [01] = Bus I/O In Bit 1 [02] = Bus I/O In Bit 2 [03] = Bus I/O In Bit 3 [04] = Bus I/O In Bit 4 [05] = Bus I/O Initiator 1 [07] = Bus I/O Initiator 3 [08] = Bus I/O Initiator 4 [09] = Marker 1 [10] = Marker 2 [11] = Bit 8 BUS control word [06] = Bus I/O Initiator 2 [12] = Bit 9 BUS control word For possible functions of the Bus In Bits please refer to the table of digital input functions P420...P425. For further details please refer to the AS Interface handbook, BU P Function Bus I/O Out Bits S [ 10 ] The Bus I/O Out Bits are regarded as multifunction relay outputs. They can be set to the same functions (P / P ). [01] = Bus I/O Out Bit 1 [02] = Bus I/O Out Bit 2 [03] = Bus I/O Out Bit 3 [04] = Bus I/O Out Bit 4 [05] = Bus I/O Actuator 1 [06] = Bus I/O Actuator 2 [07] = Marker 1 [08] = Marker 2 [09] = Bit 10 BUS status word [10] = Bit 13 BUS status word For possible functions of the Bus Out Bits please refer to the table of relay functions P434. For further details please refer to the AS Interface handbook, BU P Standardisation Bus I/O Out Bits S % [ 100 ] Modification of the relay functions limit values/ Bus Out Bits. With a negative value, the output function is output negated. If the set values are positive the relay contact closes, if they are negative the relay contact opens when the limit value is reached. P % Hysteresis Bus I/O Out Bits S [ 10 ] Difference between switch-on and switch-off point to prevent oscillation of the output signal. BU 0500 GB Subject to technical changes 87

88 NORDAC SK 500E / 520E Handbook 5.6 Extra functions Parameter Setting value / description / note Device Supervisor Parameter set P [ 0 ] Leading function value S P Selection of up to 3 master values: [01] = master value 1 [02] = master value 2 [03] = master value 3 Selection of possible master value settings: 0 = Off 1 = Actual frequency 2 = Actual speed 3 = Current 4 = Instantaneous current 5 = Status of digital inputs and outputs 6 = reserved 7 = reserved 8 = Set point frequency 9 = Fault report 10 = reserved 11 = reserved 12 = Digital Out Bit = reserved 14 = reserved 15 = reserved 16 = reserved 17 = Value analogue input 1 18 = Value analogue input 2 19 = Set point frequency master value 20 = Set point frequency after master value ramp 21 = Actual frequency without slippage master value P503 Leading function output S [ 0 ] To use the Master function output, the frequency inverter controller source must be selected in P509. The master value to be transferred via the BUS interface is determined in parameter P = Off 1 = USS 2 = CAN (up to 250 kbaud) P504 Pulse frequency S khz [ 6.0 ] The internal pulse frequency for actuating the power component can be changed with this parameter. A high set value leads to less noise from the motor, but also to higher EMC radiation and a possibly reduced motor torque. NOTE: The radio interference level limit curve A 1 as per EN is adhered to when 6.0 khz is set if the wiring guidelines are complied with. Further details can be found in chapt. 8.4 EMC Limit Value Classes. NOTE: Raising the pulse frequency leads to a reduction of the output current against time (I 2 t characteristic curve). Further details can be found in chapt. 8.5 Power derating. P505 Absolute minimum frequency S P Hz [ 2.0 ] Specifies the frequency value that the FI may not undershoot. The FI switches off or goes to 0.0 Hz if the set point is lower than the absolute minimum frequency. At the absolute minimum frequency, braking control (P434 or P441) and the set point value delay (P107) are carried out. If a setting value of "Null" is selected, the brake relay does not switch during reversing. When controlling hoists, this value should be set at a minimum of 2Hz. The FI current control is operable from 2 Hz onwards, and a connected motor can supply sufficient torque. NOTE: Output frequencies < 2 Hz cause a current limitation. Further details can be found in chapt. 8.5 Power derating. 88 Subject to technical changes BU 0500 GB

89 5.6 Additional parameters Parameter Setting value / description / note Device Supervisor Parameter set P506 Automatic fault acknowledgement S [ 0 ] In addition to the manual fault acknowledgement, an automatic one can also be selected.. 0 = No automatic fault acknowledgement = Number of permissible automatic fault acknowledgments within one mains-on cycle. After mains-off and switching on again, the complete total is once again available. 6 = Always, a fault message will always be automatically acknowledged when the cause is no longer present. 7 = ENTER key, acknowledgement is only possible using the ENTER key or power-off. No acknowledgement is generated by removing enabling! P [ 1 ] P [ 1 ] P [ 0 ] PPO type With the Technology unit Profibus, DeviceNet or InterBus only See also supplementary description BU 0020, BU 0080, BU 0070 Profibus address Profibus address, only with the Profibus Technology unit See also the additional description for the Profibus control BU 0020 Source control word Selection of the interface from which the FI is controlled. 0 = Control terminals or keyboard control ** with the ControlBox (when P510=0), the ParameterBox (not ext. p-box) or the BUS I/O Bits. 1 = Control terminal only *, FI control is only possible via the digital and analogue inputs or the BUS I/O Bits. 2 = USS control word *, the control signals (enable, rotation direction, etc.) are transferred via the RS485 interface, the set point via the analogue input or the fixed frequencies. 3 = CAN control word * 4 = Profibus control word * 5 = InterBus Control word* 6 = CANopen control word * 7 = DeviceNet Control word * 8 = reserved 9 = CAN Broadcast * NOTE: For details on the current Bus systems: please refer to the current Options Description. BU 0020 = Profibus BU 0030 = CANbus BU 0050 = USS BU 0060 = CANopen BU 0070 = InterBus BU 0080 = DeviceNet BU 0090 = AS-Interface *) Keyboard control (ControlBox, ParameterBox) is blocked, parameterisation is still possible. **) If the communication during keyboard control is blocked (time out 0.5 sec), the FI will block without error message. BU 0500 GB Subject to technical changes 89

90 NORDAC SK 500E / 520E Handbook Parameter Setting value / description / note Device Supervisor Parameter set P Set point source S [ 0 ] Selection of set point source to be parameterised. [01] = Main set point source [02] = Secondary set point source Selection of the interface from which the FI is controlled. 0 = Auto: The source of the additional set point is automatically derived from the setting of the parameter P509 >Interface< 1 = Control terminals, digital and analogue inputs control the frequency, also fixed frequencies 2 = USS 3 = CAN 4 = Profibus 5 = InterBus 6 = CANopen 7 = DeviceNet 8 = reserved P511 USS Baud rate S [ 3 ] P [ 0 ] Setting of the transfer rate (transfer speed) via the RS485 interface. All bus slaves must have the same Baud rate setting. 0 = 4800 Baud 1 = 9600 Baud USS address Used to set the FU Bus address. 2 = Baud 3 = Baud P513 Telegram down time S 0.0 / s [ 0.0 ] P [ 4 ] Monitoring function of the active bus interface. After a valid telegram has been received, the next must arrive within the set time. Otherwise the FI will signal a malfunction and will switch off with the error message E010 >Bus Time Out<. Monitoring is switched off at a setting value of 0.0. CAN Baud rate Used to set the transfer rate (transfer speed) via the CANbus interface. All bus slaves must have the same Baud rate setting. Further information can be obtained from the BU 0030 CANbus handbook. 0 = 10 kbaud 1 = 20kBaud 2 = 50kBaud 3 = 100kBaud 4 = 125kbaud 5 = 250kBaud 6 = 500kBaud 7 = 1 Mbaud * (for test purposes only) P [ 50 ] CAN address Setting of the CANbus address. *) safe use cannot be guaranteed 90 Subject to technical changes BU 0500 GB

91 5.6 Additional parameters Parameter Setting value / description / note Device Supervisor Parameter set P516 Masking frequency 1 S P Hz [ 0.0 ] The output frequency is masked around the set frequency value (P517). This range passes with the set braking and start up ramp, it cannot be permanently displayed at the output. No frequencies below the absolute minimum frequency may be set. 0 = Masking frequency inactive P517 Masking window 1 S P Hz [ 2.0 ] Masking window for >Masking frequency 1< P516. This frequency value is added to and subtracted from the masking frequency. Masking window 1: P516 - P P516 + P517 P518 Masking frequency 2 S P Hz [ 0.0 ] The output frequency is masked around the set frequency value (P519). This range passes with the set braking and start up ramp, it cannot be permanently displayed at the output. No frequencies below the absolute minimum frequency may be set. 0 = Masking frequency inactive P519 Masking window 2 S P Hz [ 2.0 ] Masking window for >Masking frequency 2< P518. This frequency value is added to and subtracted from the masking frequency. Masking window 2: P518 - P P518 + P519 P520 Flying start S P [ 0 ] This function is used to connect the FI to already rotating motors, e.g. in ventilation drives. In rotational speed controlled mode (Servo mode P300 = ON) only frequencies of >100Hz are tracked. 0 = Switched off, no flying start. 1 = Both directions, the FI will search for a speed of rotation in either direction. 2 = Set point value direction, search in the direction of the present set point value only. 3 = Both directions, only following mains supply interruption and faults 4 = Set point value direction, only following mains supply interruption and faults P521 Flying start resolution S P Hz [ 0.05 ] This parameter can be used to change the search pitch during flying start. Values that are too large affect accuracy and cause the FI to shutdown with an overcurrent message. If values are too small, the tracking time is prolonged greatly. P522 Flying start offset S P Hz [ 0.0 ] A frequency value that can be added to the frequency value found in order, e.g. to always reach the motoric range and therefore avoid the generational and the chopper range. BU 0500 GB Subject to technical changes 91

92 NORDAC SK 500E / 520E Handbook Parameter Setting value / description / note Device Supervisor P523 Default setting Parameter set [ 0 ] The selected parameter range is reset to the default setting by selecting the appropriate value and confirming it with the ENTER key. Once the setting has been carried out, the value of the parameter returns automatically to = No change: Does not alter the parameterisation. 1 = Load default setting: The complete parameterisation of the FI reverts to the factory setting. All originally parameterised data is lost. 2 = Default data without Bus: All FI parameters, not the Bus parameters, revert to the factory setting. P535 I 2 t Motor S [ 0 ] When calculating the motor temperature, the output current, time and the output frequency (cooling) are taken into account. If the temperature limit is reached then switch off occurs and error message E002 (motor overheating) is produced. Possible positive or negative acting ambient conditions cannot be taken into account here. 0 = Switched off 1 = Switched on P536 Current limit S / 2.1 (-fold rated FI current) [ 1.5 ] The FI output current is limited to the set value. If this limit value is reached, the FI reduces the current output frequency. Multiplier with the FI nominal current gives the limit value 2.1 = OFF is for switching off this limit value. At the same time this is the basic setting for this parameter. P537 Pulse switch-off S % / 201 [ 150 ] This function prevents immediate switch off of the inverter if there is an appropriate overload. The output current is limited to the set value with pulse switch-off enabled. This limitation is achieved by briefly switching off the final stage transistors; the current output frequency remains unchanged % = limit value related to the rated FI current 201 = Function is switched off NOTE: The value set here can be undershot by a smaller value in P536. The pulse switch-off can be undershot by the power derating (cf. chapt. 8.5) for low output frequencies (< 4.5 Hz) or high pulse frequencies (> 6 khz or 8 khz, P504). NOTE: When pulse switch-off is disabled (P537=201) and a high pulse frequency is selected in parameter P504, the frequency inverter will automatically reduce the pulse frequency in case of performance limits. The pulse frequency goes back to the original value when the frequency inverter load has dropped again. 92 Subject to technical changes BU 0500 GB

93 5.6 Additional parameters Parameter Setting value / description / note Device Supervisor Parameter set P538 Mains voltage monitoring S [ 3 ] For safe operation of the frequency inverter the power supply must meet a certain quality. If a brief interruption of a phase occurs or if the power supply drops below a certain limit value the inverter will display a malfunction. Under certain operating conditions it may be possible that this error message must be suppressed. In this case, the input monitoring can be modified. 0 = Switched off: No monitoring of the supply voltage. 1 = Phase error only: only phase errors will produce a fault report. 2 = Undervoltage only: only low voltage will produce a fault report. 3 = Phase error and undervoltage: Low voltage and phase error will produce a fault report. 4 = DC supply: In case of direct DC supply the input voltage is assumed to be a fixed value of 480V. Phase error and mains undervoltage monitoring are disabled in this case. NOTE: Use with inappropriate mains voltage supply may completely destroy the FI! P539 Output monitoring S P [ 0 ] This protective function monitors the output current on terminals U-V-W and checks its plausibility. Error message E016 is issued in case of an error. 0 = Switched off: No monitoring. 1 = Motor phase error only: The output current is measured and checked for symmetry. In case of asymmetry the FI switches off and issues error message E = Magnetization monitoring only: The magnetization current (field current) is checked upon FI power-on. The FI switches off and issues error message E016 if the magnetization current is insufficient. This occurs independently of parameters P107/P114, a motor brake will not be ventilated. 3 = Motor phase and magnetization monitoring NOTE: This function is ideal as an additional protection for lifting mechanism applications but is not approved as a sole personal protection measure. BU 0500 GB Subject to technical changes 93

94 NORDAC SK 500E / 520E Handbook Parameter Setting value / description / note Device Supervisor Parameter set P540 Rotation direction mode S P [ 0 ] For safety reasons, this parameter can be used to prevent a rotation direction reversal and thus the wrong rotation direction. 0 = No rotation direction limitation 1 = Rotation direction reversal blocked, the rotation direction key via the Parameter box is blocked. 2 = CW only *, clockwise direction only is possible. Selection of the "wrong direction" will produce an output of 0Hz. 3 = CCW only *, counter-clockwise direction only is possible. Selection of the "wrong direction" will produce an output of 0Hz. 4 = Enable direction only, rotation direction only possible in line with the enable signal, otherwise 0 Hz is supplied. 5 = Monitored CW only *, clockwise direction only is possible. Selection of the "wrong direction" will cause the FI to be switched off. 6 = Monitored CCW only *, counter-clockwise direction only is possible. Selection of the "wrong direction" will cause the FI to be switched off. 7 = Monitored enable direction only, rotation direction only possible in line with the enable signal, otherwise the FI is switched off. *) applies to keyboard (SK TU3) and control terminal control, ControlBox direction key is also blocked. P541 Set relay S F1F (hex) [ 0000 ] This function provides the opportunity to control the relay and the digital outputs independently of the frequency inverter status. For this purpose, the corresponding output must be set to the function External Control. This function can either be used manually or with a Bus control. Bit 0 = Output 1 (K1) Bit 1 = Output 2 (K2) Bit 2 = Output 3 (DOUT1) Bit 3 = Output 4 (DOUT2) Bit 4 = Dig. AOut 1 (analogue output 1) Bit 5 7 = reserved Bit 8 = Bus Out Bit 0 Bit 9 = Bus Out Bit 1 Bit 10 = Bus Out Bit 2 Bit 11 = Bus Out Bit 3 Bit 12 = Bus Out Bit 4 Bit 13 = Bus Out Bit 5 Min. value Max. value Bit Bit 11-8 Bit 7-4 Bit F 1 F binary hex binary hex BUS: The corresponding value is written into the parameter, thereby setting the relays and/or digital outputs. ControlBox: Directly specify the hex code when using a ControlBox. ParameterBox: Each individual output can be separately selected in clear text and activated. 94 Subject to technical changes BU 0500 GB

95 5.6 Additional parameters Parameter Setting value / description / note Device Supervisor Parameter set P542 Set analogue output S V [ 0.0 ] Use this function to set the FI analogue output independently of its current operating state. To do this, the relevant analogue output must be set to the function External controller (P418 = 7). This function can either be used manually or with a Bus control. The value set here will, once confirmed, be produced at the analogue output. P543 Bus actual value 1 S P [ 1 ] The return value 1 can be selected for bus actuation in this parameter. NOTE: Further details can be found in the respective BUS instruction manuals or the description for P = Off 1 = Actual frequency 2 = Actual speed 3 = Current 4 = Torque current (100% = P112) 5 = Status of digital inputs and outputs 1 6 = 7 reserved 8 = Set point frequency 9 = Error number 10 = 11 reserved 12 = Bus Out Bits = 16 reserved 17 = Analogue input 1 value (P400) 18 = Analogue input 2 value (P405) 19 = Set point frequency master value (P503) 20 = Set point frequency after master value ramp 21 = Actual frequency without slippage master value P544 Bus actual value 2 S P [ 0 ] This parameter is identical with P543. Condition is PPO 2 or PPO 4 type (P507). P545 Bus actual value 3 S P [ 0 ] This parameter is identical with P543. Condition is PPO 2 or PPO 4 type (P507). 1 the assignment of dig. inputs for P543/ 544/ 545 = 5 Bit 0 = DigIn 1 Bit 1 = DigIn 2 Bit 2 = DigIn 3 Bit 3 = DigIn 4 Bit 4 = DigIn 5 Bit 5 = DigIn 6 (SK 520E) Bit 6 = DigIn 7 (SK 520E) Bit 7 = reserved Bit 8 = reserved Bit 9 = reserved Bit 10 = reserved Bit 11 = reserved Bit 12 = Out 1 Bit 13 = Out 2 Bit 14 = Out 3 (SK 520E) Bit 15 = Out 4 (SK 520E) BU 0500 GB Subject to technical changes 95

96 NORDAC SK 500E / 520E Handbook Parameter Setting value / description / note Device Supervisor Parameter set P546 Bus set point value 1 function S P [ 1 ] A function is assigned to the delivered set point value 1 for bus actuation in this parameter. NOTE: 0 = Off Further details can be found in the respective BUS instruction manuals or the description for P = Set point frequency (16 Bit) 2 = torque current limit (P112) 3 = actual frequency PID 4 = frequency addition 5 = frequency subtraction 6 = current limit (P536) 7 = maximum frequency (P105) 8 = actual PID frequency limited 9 = actual PID frequency monitored 10 = Servo mode torque (P300) 11 = derivative torque (P214) 12 = reserved 13 = Multiplication 14 = PI process controller actual value 15 = PI process controller set point 16 = PI process controller lead 17 = Digital In Bits = reserved 19 = Output status (P434/441/450/455=38) 20 = Analogue output value (P418=31) 21 = 24 reserved P547 Bus set point value 2 function S P [ 0 ] This parameter is identical with P546. P548 Bus set point value 3 function S P [ 0 ] This parameter is identical with P546. P549 Pot Box function S [ 0 ] A function is assigned in this parameter to the delivered set point when control is via the PotentiometerBox (SK TU3-POT). (Explanations can be found in the P400 description.) 0 = Off 1 = Set point frequency 2 = Torque current limit 3 = Actual frequency PID 4 = Frequency addition 5 = Frequency subtraction 6 = Current limit 7 = Maximum frequency 8 = Actual PID frequency limited 9 = Actual PID frequency monitored 10 = Torque 11 = Derivative torque 12 = reserved 13 = Multiplication 14 = PI process controller actual value 15 = PI process controller set point 16 = PI process controller lead SK CSX-0: You can use the SimpleBox (see chapt ) on the frequency inverter to control the drive if P549=1 is set and the operating value display P000 is selected. Keeping the key pressed for some time starts the drive, briefly pressing it stops the drive. The rotational speed can be varied in the positive and negative range with the rotary knob. If a ParameterBox SK TU3-PAR is in us, there is no control function available with the SimpleBox. NOTE: Please note that the drive can only be stopped by briefly pressing the key in the operating value display or by disconnecting the device from mains. 96 Subject to technical changes BU 0500 GB

97 5.6 Additional parameters Parameter Setting value / description / note Device Supervisor P550 Back up data record Parameter set [ 0 ] Within the optional ControlBox it is possible to store a data set (parameter set ) from the attached frequency inverter. This is stored inside the box in a non-volatile store and can therefore be transferred to other SK 500E / 520E devices with the same database version (comp. P742). 0 = No function 1 = Frequency inverter ControlBox, the dataset is written from the attached inverter into the ControlBox. 2 = ControlBox Frequency inverter, the dataset is written from the ControlBox to the attached inverter. 3 = FU ControlBox, the inverter's data set is exchanged with the control box. With this variant, no data is lost. They are continuously exchangeable. NOTE: If parameterisation from old frequency inverters is to be loaded into frequency inverters with new software (P707), then that ControlBox must previously have been formatted (=1) by the new frequency inverter (P550=1). Then, the data set to be copied from the old FI can be read and copied to the new one. P551 Drive profile S On / Off [ 0 = Off ] This parameter is used, depending on the option, to activate the DS401 CANopen profile or the Interbus Drivecom profile. P554 Min. chopper trigger point S % [ 65 ] With this parameter, the motor braking chopper trigger threshold can be changed. The factory setting is an optimised value for a great number of applications. This parameter value can be increased for applications where energy is intermittently fed back (crank operation) in order to minimise the power loss on the braking resistor. Increasing this setting will cause the FI to switch off faster in case of an overload. P555 Chopper power limit S % [ 100 ] With this parameter it is possible to program a manual (peak) power limit for the brake resistor. The switch-on delay (modulation level) for the braking chopper can only rise to a certain maximum specified limit. Once this value has been reached, irrespective of the level of the DClink, the FI switches the resistance to without current. The result would be an overvoltage switch-off of the FI. P556 Braking resistor S Ω [ 120 ] Value of the braking resistor for the calculation of the maximum brake power to protect the resistor. Once the maximum continuous output (P557) has been reached, then an I 2 t limit error (E003) is initiated. P557 Brake resistor power S kw [ 0.00 ] Continuous resistor output (nominal power) for the calculation of the maximum braking power = Monitoring disabled BU 0500 GB Subject to technical changes 97

98 NORDAC SK 500E / 520E Handbook Parameter Setting value / description / note Device Supervisor Parameter set P558 Magnetisation time S P 0 / 1 / ms [ 1 ] ISD control can only function correctly when there is a magnetic field in the motor. For this reason a direct current is applied to the motor before start up. The duration is motor size dependent and is automatically set in the FI factory settings. This magnetisation time can be adjusted or deactivated for time-critical applications. 0 = Switched off 1 = Automatic calculation = Accordingly set time in [ms] NOTE: Settings that are too low can reduce the dynamics and start-up torque. P559 DC lag period S P s [ 0.50 ] Following a stop signal and the braking ramp, a direct current is briefly applied to the motor to fully bring the drive to a stop. The current application time can be set via this parameter, dependent on the mass inertia. The current level depends on the previous braking procedure (current vector control) or the static boost (linear characteristic). P560 Store in EEPROM S [ 1 ] 0 = Alterations to the parameter settings will be lost, if the FI is disconnected from the mains supply. 1 = All parameter changes are automatically written to the EEPROM, and remain stored there when the FI is disconnected from the mains supply. NOTE: If USS communication is being used to carry out parameter changes, care must be taken that the maximum number of write cycles (100,000) is not exceeded. 98 Subject to technical changes BU 0500 GB

99 5.7 Information 5.7 Information Parameter Setting value / description / note Device Supervisor P700 Current fault Parameter record Current pending fault. Further details in chapter 6 Fault messages. SimpleBox/ControlBox: Description of the individual error numbers can be read under paragraph Malfunction messages. ParameterBox: Errors are displayed in plain text, further information can be obtained from paragraph Malfunction messages. P Previous fault This parameter stalls the previous 5 faults. Further details in chapter 6 Fault messages. The control box must be used to select the corresponding memory location (array parameter) and confirmed using the ENTER key to read the stored error code. P Freq. previous fault S Hz This parameter stores the output frequency that was being delivered at the time the fault occurred. Values for the last 5 faults are stored. The control box must be used to select the corresponding memory location (array parameter) and confirmed using the ENTER key to read the stored value. P Current previous fault S A This parameter stores the output current that was being delivered at the time the fault occurred. Values for the last 5 faults are stored. The control box must be used to select the corresponding memory location (array parameter) and confirmed using the ENTER key to read the stored value. P Voltage previous fault S V AC This parameter stores the output voltage that was being delivered at the time the fault occurred. Values for the last 5 faults are stored. The control box must be used to select the corresponding memory location (array parameter) and confirmed using the ENTER key to read the stored value. P UZW previous fault S V DC This parameter stores the DC-link that was being delivered at the time the fault occurred. Values for the last 5 faults are stored. The control box must be used to select the corresponding memory location (array parameter) and confirmed using the ENTER key to read the stored value. BU 0500 GB Subject to technical changes 99

100 NORDAC SK 500E / 520E Handbook Parameter Setting value / description / note Device Supervisor Parameter record P Parameter set previous fault S This parameter stores the parameter set code that was active when the fault occurred. Data for the previous 5 faults are stored. The control box must be used to select the corresponding memory location (array parameter) and confirmed using the ENTER key to read the stored error code. P Software version/revision This parameter indicates the FI software and revision number. This can be of importance if different FIs are to be set to identical values = Version number (1.1) = Revision number (2) P708 Status digital inputs (SK 520E) (binary) or FF (hexadecimal) Displays the status of the digital inputs in binary/hexadecimal code. This display can be used to check the input signals. Bit 0 = Digital input 1 Bit 1 = Digital input 2 Bit 2 = Digital input 3 Bit 3 = Digital input 4 Bit 4 = Digital input 5 Bit 5 = Digital input 6 (SK 520E) Bit 6 = Digital input 7 (SK 520E) Bit 7 = Analogue input 1 digital function Bit 8 = Analogue input 2 digital function Minimum value Maximum value Bit 11-8 Bit 7-4 Bit F F binary hex binary hex Control Box: binary bits will be converted to a hex value and displayed. ParameterBox: the bits will be displayed ascending from right to left in binary format. P709 Voltage analogue input V Displays the measured analogue input value 1. P710 Analogue output voltage V Displays the delivered value of analogue output 1. ( V ) P711 Status multifunction relay (SK 520E) FF (hex) Displays the current status of the signal relays. Bit 0 = Output 1 (K1) Bit 1 = Output 2 (K2) P712 Voltage analogue input 2 Bit 2 = Output 3 (DOUT 1) (SK 520E only) Bit 3 = Output 4 (DOUT 2) (SK 520E only) V Displays the measured analogue input value Subject to technical changes BU 0500 GB

101 5.7 Information Parameter Setting value / description / note Device Supervisor P714 Period of use Parameter record h This parameter indicates the period of time the FI was under power and ready for operation. P715 Period of release h This parameter indicates the period of time the FI was released and fed current to the output. P716 Current frequency Hz Displays the current output frequency. P717 Current rotation speed rpm Displays the current motor speed calculated by the FI. P Current set frequency Hz Displays the frequency specified by the set point. (see also 8.1 Set point processing) = current set point frequency from set point source = current set point frequency following processing in the FI status machine = current set point frequency following frequency ramp P719 Actual current A Displays the current output current. P720 Current torque current A Displays the currently calculated torque generating output current (active current). The motor data P201...P209 is the basis for this calculation. negative values = generating, positive values = drive. P721 Actual field current A Displays the actual calculated field current (reactive current). The motor data P201...P209 is the basis for this calculation. P722 Current voltage V Displays the current AC voltage delivered at the FI output. P723 Current voltage component Ud V Displays the current field voltage components. P724 Current voltage component Uq V Displays the current torque voltage components. BU 0500 GB Subject to technical changes 101

102 NORDAC SK 500E / 520E Handbook Parameter Setting value / description / note Device Supervisor P725 Current cos ϕ Parameter record Displays the drive s current calculated cos ϕ. P726 Apparent power kva Displays the current calculated apparent power. The motor data P201...P209 is the basis for this calculation. P727 Mechanic power kw Displays the current calculated effective power at the motor. The motor data P201...P209 is the basis for this calculation. P728 Mains voltage V Displays the current mains voltage being applied to the FI. P729 Torque % Displays the current calculated torque. The motor data P201...P209 is the basis for this calculation. P730 Field % Displays the current field in the motor calculated by the FI. The motor data P201...P209 is the basis for this calculation. P Current parameter record Displays the current operating parameter record. 0 = Parameter set 1 1 = Parameter set 2 2 = Parameter set 3 3 = Parameter set 4 P732 U phase current S A Displays the actual U phase current. NOTE: Because of the measurement procedure, either with symmetrical output currents, this value can vary from the value in P719. P733 V phase current S A Displays the actual V phase current. NOTE: Because of the measurement procedure, either with symmetrical output currents, this value can vary from the value in P719. P734 W phase current S A Displays the actual W phase current. NOTE: Because of the measurement procedure, either with symmetrical output currents, this value can vary from the value in P Subject to technical changes BU 0500 GB

103 5.7 Information Parameter Setting value / description / note Device Supervisor Parameter record P735 Rotation speed encoder SK 520E S rpm Displays the current rotation speed supplied by the incremental encoder. P736 DC link current V DC Displays the current link voltage. P737 Current braking resistor load % This parameter informs of the current braking resistor load in generator operation when parameters P556 and P557 are set correctly. With P556 = 0 and P557 = 0 settings this parameter informs of the FI braking chopper load. P738 Current motor load % Displays the current motor load. The motor data P201...P209 is the basis for this calculation. P739 Current heat sink temperature C Displays the current FI heat sink temperature. P Bus In process data FFFF (hex) This parameter informs of the current control word and the setpoints transferred via the bus systems = Control word = Set point = Set point = Set point = Bus I/O In Bits (P480) = Parameter data In = Parameter data In = Parameter data In = Parameter data In = Parameter data In = Set point = Set point = Set point 3 S Control word, source from P509. Set point data from main set point P The displayed value indicates any Bus In Bit sources in disjunction. Data during parameter transfer. Set point data from secondary set point P BU 0500 GB Subject to technical changes 103

104 NORDAC SK 500E / 520E Handbook Parameter Setting value / description / note Device Supervisor Parameter record P Bus Out process data FFFF (hex) This parameter informs of the status word and the setpoints/actual values transferred via the bus systems = Status Word = Actual value 1 (P543) = Actual value 2 (P544) = Actual value 3 (P545) = Bus I/O In Bits (P480) = Parameter data Out = Parameter data Out = Parameter data Out = Parameter data Out = Parameter data Out = Master function 1 actual value = Master function 2 actual value = Master function 3 actual value S Status word, source from P509. The displayed value indicates any Bus Out Bit sources in disjunction. Data during parameter transfer. Master function actual value P502 / P503. P742 Database version S Displays the internal FI database version. P743 Inverter type Display of the inverter power in kw, e.g. "1.50" frequency inverter with 1.5 kw nominal power. P FFFF (hex) Configuration stage This parameter displays the option modules recognised by the frequency inverter. Display occurs in hexadecimal code (SimpleBox, ControlBox, bus system). The display occurs in clear text when the ParameterBox is used. Encoder = 01xx Standard = xx00 IO Extension = xx01 P745 Module version Version of the integrated modules (only when own processor is present). P746 Module status S FFFF (hex) Status of the integrated modules (when active). P Inverter voltage range Specifies the mains voltage range the FI is rated for. 0 = V 1 = V 2 = V P750 Over current statistics S Total of over current reports during the period of use P Subject to technical changes BU 0500 GB

105 5.7 Information Parameter Setting value / description / note Device Supervisor Parameter record P751 Over voltage statistics S Total of overvoltage reports during the period of use P714. P752 Mains supply faults S Total of mains supply faults during the period of use P714. P753 Overheating statistics S Total of overheating faults during the period of use P714. P754 Lost parameter statistics S Total of lost parameters during the period of use P714. P755 System faults statistics S Total of system faults during the period of use P714. P756 Time out statistics S Total of time out faults during the period of use P714. P757 Customer fault statistics S Total customer Watchdog faults during the period of use P714. P Operating hours latest fault This parameter indicates the operating hours counter status (P714) at the time of the respective latest fault. Array corresponds to the latest fault BU 0500 GB Subject to technical changes 105

106 NORDAC SK 500E / 520E Handbook 5.8 Parameter overview, user settings (P) parameter set dependent, these parameters can be set in four separate parameters sets. S Supervisor- Parameters, depending on P003. Parameter No. Designation Factory setting Supervisor Setting after commissioning P 1 P 2 P 3 P 4 OPERATING DISPLAYS (5.1) P000 Operating parameter display P001 Selection of display value 0 P002 Display factor 1.00 S P003 Supervisor code 1 0= S-Parameters are not visible 1= all Parameters are visible BASIC PARAMETERS (5.2) P100 Parameter set 0 S P101 Copy parameter set 0 S P102 (P) Acceleration time [s] 2.0 P103 (P) Deceleration time [s] 2.0 P104 (P) Minimum frequency [Hz] 0.0 P105 (P) Maximum frequency [Hz] 50.0 P106 (P) Ramp smoothing [%] 0 S P107 (P) Brake reaction time [s] 0.00 P108 (P) Disconnection mode 1 S P109 (P) DC brake current [%] 100 S P110 (P) Time DC brake on [s] 2.0 S P111 (P) P Factor torque limit [%] 100 S P112 (P) Torque current limit [%] 401 (off) S P113 (P) Jog frequency [Hz] 0.0 S P114 (P) Brake delay off [s] 0.00 S MOTOR DATA / CHARACTERISTIC CURVE PARAMETERS (5.3) P200 (P) Motor list 0 P201 (P) Nominal frequency [Hz] 50.0 * S P202 (P) Nominal speed [rpm] 1385 * S P203 (P) Nominal current [A] 4.8 * S P204 (P) Nominal voltage [V] 230 * S P205 (P) Nominal power [kw] 1.10 * P206 (P) cos phi 0.78 * S P207 (P) Star / Delta connection [star=0/delta=1] 1 * S P208 (P) Stator resistance [Ω] 6.28* S P209 (P) No load current [A] 3.0 * S P210 (P) Static boost [%] 100 S P211 (P) Dynamic boost [%] 100 S 106 Subject to technical changes BU 0500 GB

107 5.8 Parameter overview, user settings Parameter No. Designation Factory setting Supervisor Setting after commissioning P 1 P 2 P 3 P 4 P212 (P) Slip compensation [%] 100 S P213 (P) ISD control loop gain [%] 100 S P214 (P) Torque pre control [%] 0 S P215 (P) Boost pre control [%] 0 S P216 (P) Time boost pre control [s] 0.0 S P220 Parameter identification 0 *) dependent on FI power, and on P200 / P220 SPEED CONTROL (5.4) encoder input, SK 520E only P300 (P) Servo mode [Off / On] 0 P301 Incremental encoder 6 P310 (P) speed controller P [%] 100 P311 (P) speed controller I [%/ms] 20 P312 (P) Torque current control P [%] 200 S P313 (P) Torque current control I [%/ms] 125 S P314 (P) Torque current control limit [V] 400 S P315 (P) Field current control P [%] 200 S P316 (P) Field current control I [%/ms] 125 S P317 (P) Field current control Limit [V] 400 S P318 (P) Weak field control P [%] 150 S P319 (P) Weak field control I [%/ms] 20 S P320 (P) Weak field limit [%] 100 S P321 (P) speed control I brake off 0 S P325 Encoder function 0 P326 Ratio encoder 1.00 P327 Speed slip error [rpm] 0 (off) CONTROL CLAMPS (5.5) P400 Function analogue input 1 1 P401 Mode analogue input 1 0 S P402 Adjustment 1: 0% [V] 0.0 S P403 Adjustment 1: 100% [V] 10.0 S P404 Filter analogue input 1 [ms] 100 S P405 Function analogue input 2 1 P406 Mode analogue input 2 0 S P407 Adjustment 2: 0% [V] 0.0 S P408 Adjustment 2: 100% [V] 10.0 S P409 Filter analogue input 2 [ms] 100 S P410 (P) Min. freq. aux. setpoint [Hz] 0.0 P411 (P) Max. freq. aux. setpoint [Hz] 50.0 BU 0500 GB Subject to technical changes 107

108 NORDAC SK 500E / 520E Handbook Parameter No. Designation Factory setting Supervisor Setting after commissioning P 1 P 2 P 3 P 4 P412 (P) Set point process control [V] 5.0 S P413 P414 P415 (P) (P) (P) PID controller P component [%] PID controller I component [%/ms] PID controller D component [%ms] 10.0 S 1.0 S 1.0 S P416 (P) Ramp time PI setpoint [s] 2.0 S P417 (P) Offset analogue output [V] 0.0 S P418 (P) Function analogue output 0 P419 (P) Norm. analogue output [%] 100 P420 digital input 1 1 P421 digital input 2 2 P422 digital input 3 8 P423 digital input 4 4 P424 digital input 5 0 P425 digital input 6 0 P426 (P) Quick stop time [s] 0.10 P427 Quick stop on Error 0 S P428 (P) Automatic starting [Off / On] 0 S P429 (P) Fixed frequency 1 [Hz] 0.0 P430 (P) Fixed frequency 2 [Hz] 0.0 P431 (P) Fixed frequency 3 [Hz] 0.0 P432 (P) Fixed frequency 4 [Hz] 0.0 P433 (P) Fixed frequency 5 [Hz] 0.0 P434 (P) Output 1 function (K1) 1 P435 (P) Output 1 standardisation [%] 100 P436 (P) Output 1 hysteresis [%] 10 S P441 (P) Output 2 function (K2) 7 P442 (P) Output 2 standardisation [%] 100 P443 (P) Output 2 hysteresis [%] 10 S P450 (P) Output 3 function (DOUT 1) 0 P451 (P) Output 3 standardisation [%] 100 P452 (P) Output 3 hysteresis [%] 10 S P455 (P) Output 4 function (DOUT 2) 0 P456 (P) Output 4 standardisation [%] 100 P457 (P) Output 4 hysteresis [%] 10 S P460 Time watchdog [s] 10.0 S P465 Fixed frequency array [-01-31] P466 (P) Max. process controller freq. 0.0 P470 Digital input Subject to technical changes BU 0500 GB

109 5.8 Parameter overview, user settings Parameter No. Designation Factory setting Supervisor Setting after commissioning P 1 P 2 P 3 P 4 P475 delay on/off switch S P480 function Bus I/O In Bits 12 S P481 Function Bus I/O Out Bits 10 S P482 Norm. Bus I/O Out Bits [%] 100 S P483 Hyst. Bus I/O Out Bits [%] 10 S EXTRA FUNCTIONS (5.6) P502 Leading function value 0 S P503 Leading function output 0 S P504 Pulse frequency [khz] 6.0 S P505 (P) Abs. minimum frequency [Hz] 2.0 S P506 Automatic fault acknowledgement 0 S P507 PPO type 1 P508 Profibus address 0 P509 Source control word 0 P510 Set point source 0 (auto) S P511 USS baud rate 3 S P512 USS address 0 P513 Telegram time-out [s] 0.0 S P514 CANbus baud rate 4 P515 CANbus address 50 P516 (P) Skip frequency 1 [Hz] 0.0 S P517 (P) Skip frequency area 1 [Hz] 2.0 S P518 (P) Skip frequency 2 [Hz] 0.0 S P519 (P) Skip frequency area 2 [Hz] 2.0 S P520 (P) Flying start 0 S P521 (P) Flying start resolution [Hz] 0.05 S P522 (P) Flying start offset [Hz] 0.0 S P523 Factory setting 0 P535 I 2 t motor 0 S P536 Current limit 1.5 S P537 Pulse switch-off [%] 150 S P538 Mains volt. monitor 3 S P539 (P) Output monitoring 0 S P540 Rotation direction mode 0 S P541 Set output 0000 (hex) P542 Set analogue output [V] 0.0 S P543 (P) Bus - actual value 1 1 S P544 (P) Bus - actual value 2 0 S P545 (P) Bus - actual value 3 0 S BU 0500 GB Subject to technical changes 109 S

110 NORDAC SK 500E / 520E Handbook Parameter No. Designation Factory setting Supervisor Setting after commissioning P 1 P 2 P 3 P 4 P546 (P) Function Bus - set point 1 1 S P547 (P) Function Bus - set point 2 0 S P548 (P) Function Bus - set point 3 0 S P549 PotentiometerBox function 0 S P550 Back up data record 0 P551 Drive profile 0 S P554 Min. chopper trigger point [%] 65 S P555 P Chopper limit [%] 100 S P556 Brake resistor [Ω] 120 S P557 Brake resistor type [kw] 0 S P558 (P) Magnetisation time [ms] 1 S P559 (P) DC lag period [s] 0.50 S P560 Store in EEPROM 1 S Parameter No. Designation Current status or displayed value INFORMATION (5.7), read only P700 (P) Current fault P701 Previous fault P702 Freq. previous fault P703 Current previous fault P704 Voltage previous fault P705 UZW previous fault P706 P set previous fault P707 P708 P709 P710 P711 P712 P714 P715 P716 P717 P718 P719 P720 P721 Software version (/revision) Status digital inputs (bin/hex) Voltage analogue input 1 [V] Voltage analogue output [V] Output status [hex] Voltage analogue input 2 [V] Period of operation [h] Period of enablement [h] Actual frequency [Hz] Actual speed [rpm] Actual set frequency 1..3 [Hz] Actual current [A] Actual torque current [A] Actual field current [A] 110 Subject to technical changes BU 0500 GB

111 5.8 Parameter overview, user settings Parameter No. Designation Current status or displayed value INFORMATION (5.7), read only P722 Actual voltage [V] P723 Voltage-d [V] P724 Voltage-q [V] P725 Current cos phi P726 Apparent power [kva] P727 Mechanical power [kw] P728 Input voltage [V] P729 Torque [%] P730 Field [%] P731 Parameter set P732 U phase current [A] P733 V phase current [A] P734 W phase current [A] P735 Rotation speed encoder [rpm] P736 Link voltage [V] P737 Current braking resistor load [%] P738 Motor load [%] P739 Heat sink temperature [ C] P740 Bus In process data [hex] P741 Bus Out process data [hex] P742 Database version P743 Inverter type P744 Configuration stage P745 Module version P746 Module status P747 Inverter voltage range 230/400 V P750 Stat. overcurrent P751 Stat. overvoltage P752 Stat. network fault P753 Stat. overtemperature P754 Stat. parameter loss P755 Stat. system error P756 Stat. timeout P757 Stat. customer error P799 Fault duration BU 0500 GB Subject to technical changes 111

112 NORDAC SK 500E / 520E Handbook 6 Fault messages Faults cause the frequency inverter to shut down in order to prevent a damage to the device. The following options are available to reset (acknowledge) a fault: 1. by switching the mains off and on again, 2. with an appropriately programmed digital input (P420 P425 / P470 = Function 12), 3. by removing the "enable" at the inverter (if no digital input is programmed for acknowledgement), 4. with a bus acknowledgement or 5. through P506, the automatic malfunction acknowledgement. Device LEDs: The delivery state features 2 LEDs (green/red) visible from the outside. These indicate the current device state. The green LED indicates the presence of mains voltage and, during operation, the overload level of the frequency inverter output by flashing increasingly faster. The red LED indicates pending errors by flashing at an interval corresponding to the error number code (chapt. 6.2). 6.1 SimpleBox/ControlBox display The SimpleBox or ControlBox displays a fault with its number preceded by the letter "E". In addition the current fault is displayed in parameter P700. The last fault reports are stored in parameter P701. Further information on the frequency inverter status when faults occur can be taken from parameters P702 to P706 / P799. If the cause of the fault is no longer present, the fault display in the SimpleBox / ControlBox blinks, and the fault can be acknowledged with the Enter key. 6.2 Table of possible error messages Display in the ControlBox Group Detail in P700 / P701 Error Text in the ParameterBox Cause Remedy E Inverter overheating Error signal from output stage module (static) Reduce ambient temperature (<50 C or <40 C, see also chapt. 7 Technical data) Check control cabinet ventilation E Motor over temperature (PTC) Only if a digital input is programmed (Function 13). 2.1 Motor over temperature (I 2 t) Only if I 2 t- Motor (P535) is programmed. Motor temperature sensor has triggered Reduce motor load Increase motor speed Use motor external fan I 2 t motor has beer triggered Reduce motor load Increase motor speed 112 Subject to technical changes BU 0500 GB

113 Display in the ControlBox Group E003 Detail in P700 / P701 Error Text in the ParameterBox Cause Remedy 6 Fault messages 3.0 Inverter over-current I 2 t limit triggered, e.g. > 1.5 x I n for 60 secs (please note also P504) Permanent overload at frequency inverter output 3.1 Chopper over current U 2 t limit for braking chopper triggered (please see also P555, P556, P557) 3.2 Over-current derating monitor 125% 3.3 Over-current derating monitor 150% Avoid overload at brake resistor Derating (power reduction) at f < 2 Hz 125% over-current for 50ms Derating (power reduction) at f < 2 Hz 150% over-current E Over-current module Error signal from module (briefly) E005 E006 Short-circuit, or earthing at frequency inverter output Use external output inductor (motor cable is too long) 5.0 DC link over voltage Frequency inverter DC link voltage is too high Dissipate return energy through a brake resistor Extend braking time (P103) If necessary set switch-off mode (P108) with delay (not for lifting equipment) Extend rapid stop time (P426) 5.1 Over-voltage mains Mains voltage is too high 6.0 DC link undervoltage (charging error) 6.1 Mains electricity supply undervoltage Please verify 380 V-20% V+10% or V ± 10% Frequency inverter mains supply / DC link voltage too low Check mains supply (380 V-20% to 480 V+10%) 480 V+10% or V ± 10% E Mains phase failure One of the three mains input phases these, is, or was interrupted. Please verify mains phases 380 V-20% to 480 V+10% or V ± 10%, possibly too low? All three mains phases must be present symmetrically. OFF NOTE: OFF appears in the display if the three mains phases are reduced equally, i.e. if a normal mains switch-off occurs. BU 0500 GB Subject to technical changes 113

114 NORDAC SK 500E / 520E Handbook Display in the ControlBox Group E008 Detail in P700 / P701 Error Text in the ParameterBox 8.0 EEPROM parameter loss (maximum value exceeded) Cause Remedy Error in EEPROM data NOTE: Software version of stored data set does not match software version of frequency inverter. Faulty parameters are automatically reloaded (factory setting). EMV interference (see also E020) 8.1 Invalid inverter type EEPROM faulty 8.2 External EEPROM copy error (ControlBox) 8.3 Customer interface incorrectly detected (KSE equipment) 8.4 Incorrect database version Check ControlBox for correct position. ControlBox EEPROM faulty (P550 = 1). Frequency inverter configuration incorrectly detected. Switch mains supply off and on again. 8.7 Original and mirror differ E ControlBox error SPI bus faulty, no communication with ControlBox. E Telegram time out (P513) 10.2 External component telegram time-out 10.4 External component initialisation failure External component system failure 10.8 External component communication fault E ADU customer interface error Check ControlBox for correct position. Switch mains supply off and on again. Telegram transfer is faulty, check external connection. Check Bus Protocol program process. Check Bus master. Check P746. Component not correctly plugged in. Check Bus component current supply. Further details can be found in the current additional Bus instructions. Connection fault / fault in the external component Reference voltage of customer interface faulty (10V/15V). Only displayed when control is implemented via control terminals (P509 = 0/1). Check control terminal connection for short circuit. E Customer Watchdog/customer error The Watchdog function is elected at a digital input, and the impulse at the corresponding digital input continues for longer than that set in parameter P460 >Watchdog time<. 114 Subject to technical changes BU 0500 GB

115 Display in the ControlBox Group E013 E016 Detail in P700 / P701 Error 13.0 reserved Text in the ParameterBox Cause Remedy 13.1 Rotation speed drag error Drag error limit reached Drag error switch-off monitoring Increase value in P Fault messages Drag error monitoring triggered, the motor could not reach the set point. Increase value for torque limit in P112. Increase value for current limit in P Motor phase error One motor phase is not connected Motor current monitoring during braking Check P539. Check motor connection Required magnetising current not reached at start-up. Check P539. Check motor connection E Safety loop The safety loop triggered while the frequency inverter was released. - in preparation. - E019 E Parameter identification error 19.1 Wrong star/delta motor connection 20.0 reserved 20.1 Watchdog 20.2 Stack Overflow 20.3 Stack Underflow 20.4 Undefined Opcode 20.5 Protected Instruction 20.6 Illegal Word Access 20.7 Illegal Instruction Access 20.8 EPROM error 20.9 reserved 21.0 NMI error (not used by hardware) 21.1 PLL error 21.2 ADU Overrun 21.3 PMI Access Error Automatic identification of connected motor failed Check motor connection Check motor data settings (P201...P209) System error. Error in program execution, triggered by EMC interference. Please comply with wiring guidelines in chapt Use additional external mains filter. (chapt. 8.3 / 8.4 EMC) Earth inverter extremely well. BU 0500 GB Subject to technical changes 115

116 NORDAC SK 500E / 520E Handbook 7 Technical data 7.1 General data SK 500E / 520E Function Specification Output frequency Pulse frequency Typical overload capacity Protective measures against Regulation and control Hz khz, default = 6 khz Power reduction > 8 khz for 230 V device, > 6 khz for 400 V device 150% for 60 sec., 200% for 3.5 sec. Over-heating of the frequency inverter Overvoltage and undervoltage Short-circuit, earth fault, overload, idling Non-sensor vector current control (ISD), linear V/f characteristic Analogue set point input / PID input 2x V, 0/ ma, scalable, digital V Analogue set point resolution Analogue output 10 bits related to the measurement range V scalable Set point consistency analogue < 1% digital < 0.02% Motor temperature monitoring Digital input Electrical isolation I 2 t motor (UL/cUL approved), PTC / bimetal switch (not UL/cUL) 5x (2.5 V) V, R i = (2.2 kω) 6.1 kω, cycle time = ms additionally for SK 520E: 2x V, R i = 6.1 kω, cycle time = ms Control terminals (digital and analogue inputs) Control outputs 2 relays 28 V DC / 230 V AC, 2 A (output 1, 2) additionally for SK 520E: 2 digital 15 V outputs, 20 ma (output 3, 4) Interfaces Default: RS 485 (USS) RS 232 (single slave) CANbus (for SK 520E) CANopen (for SK 520E) Frequency inverter efficiency ca. 95%, according to the size Option: Profibus DP InterBus CANbus / CANopen DeviceNet AS Interface Ambient temperature 0 C C (S1-100% duty cycle), 0 C C (S3-70% duty cycle 10 min) Storage and transport temperature Long-term storage Protection type Max. mounting altitude above sea level Waiting period between two power-up cycles Connection terminals Mains/motor/braking resistor Control unit Relay 1/2 RS485 / RS232 CANbus / CANopen -20 C /70 C, max. 85% humidity with no condensation Connect frequency inverters to mains for 60 minutes at least once per year. Maintain this cycle throughout the storage period. IP20 up to 1000 m: no power reduction m 1%/ 100 m power reduction (up to 2000 m over-voltage cat.3) m Compliance with over-voltage category 2 only, an external overvoltage protection on the mains input is required 60 secs for all devices in normal operating cycle 4 mm 2 flexible with cable sleeves, 6 mm 2 with solid cable 1.0 mm 2 with cable sleeves 1.5 mm 2 with cable sleeves 1x RJ12 (6-pole) 2x RJ45 (8-pole) SK 520E only Screw terminal tightening torque: Nm 116 Subject to technical changes BU 0500 GB

117 7 Technical data 7.2 Electrical data, 230 V Size 1 Unit type: SK 500E... SK 520E A A A A Motor rated power 230V 0.25 kw 0.37 kw 0.55 kw 0.75 kw (4 pole standard motor) 240V 1 / 3 hp ½ hp ¾ hp 1 hp Mains phases Number 1 / 3 AC Mains voltage V, ± 10%, Hz Output voltage 3 AC 0 mains voltage Rated output current rms [A] Min. braking resistor Accessories 240 Ω 190 Ω 140 Ω 100 Ω Rated input current 1 / 3 AC rms [A] 3.7 / / / / 5.6 Rec. mains fuse 1 / 3 AC slow-blow [A] 10 / / / / 10 Type of ventilation free convection Weight approx. [kg] 1.4 Size 2 / 3 Unit type: SK 500E... SK 520E A A A A A Motor rated power 230V 1.1 kw 1.5 kw 2.2 kw 3.0 kw 4.0 kw (4 pole standard motor) 240V 1½ hp 2 hp 3 hp 4 hp 5 hp Mains phases Number 1 / 3 AC 3 AC Mains voltage V, ± 10%, Hz Output voltage 3 AC 0 mains voltage Rated output current rms [A] Min. brake resistance Accessories 75 Ω 62 Ω 43 Ω 33 Ω 27 Ω Rated input current 1 / 3 AC rms [A] 12.0 / / / Rec. mains fuse 1 / 3 AC slow-blow [A] 16 / / / Type of ventilation Fan cooling (temperature-controlled) Weight approx. [kg] BU 0500 GB Subject to technical changes 117

118 NORDAC SK 500E / 520E Handbook 7.3 Electrical data, 400 V Size 1 / 2 Unit type: SK 500E... SK 520E A A A A A Motor rated power 400V 0.55 kw 0.75 kw 1.1 kw 1.5 kw 2.2 kw (4 pole standard motor) 480V ¾ hp 1 hp 1½ hp 2 hp 3 hp Mains phases Number 3 AC Mains voltage Output voltage V, -20% / +10%, Hz 3 AC 0 mains voltage Rated output current rms [A] Min. braking resistor Accessories 390 Ω 300 Ω 220 Ω 180 Ω 130 Ω Rated input current rms [A] Rec. mains fuse slow-blow [A] Type of ventilation free convection Weight approx. [kg] Fan, temperature controlled Size 3 / 4 Unit type: SK 500E... SK 520E A A A A Motor rated power 400V 3.0 kw 4.0 kw 5.5 kw 7.5 kw (4 pole standard motor) 480V 4 hp 5 hp 7½ hp 10 hp Mains phases Number 3 AC Mains voltage V, -20% / +10%, Hz Output voltage 3 AC 0 mains voltage Rated output current rms [A] Min. brake resistance Accessories 91 Ω 75 Ω 56 Ω 43 Ω Rated input current rms [A] Rec. mains fuse slow-blow [A] Type of ventilation Fan cooling (temperature-controlled) Weight approx. [kg] Subject to technical changes BU 0500 GB

119 7 Technical data 7.4 Electrical data for UL/cUL approval The data given in this section should be taken into account in order to comply with the UL/cUL approval. Size V mains Unit type: SK 500E... SK 520E A A A A Motor rated power (4 pole standard motor) 220V 0.25 kw 0.37 kw 0.55 kw 0.75 kw 240V 1 / 3 hp ½ hp ¾ hp 1 hp FLA 1 / 3 AC [A] 4 / 3 5 / 4 7 / 5 9 / 6 Rec. mains fuse J Class Fuse LPJ 10A LPJ 10A LPJ 16A / 10A LPJ 16A / 10A Size 2 / V mains Unit type: SK 500E... SK 520E A A A A A Motor rated power 220V 1.1 kw 1.5 kw 2.2 kw 3.0 kw 4.0 kw (4 pole standard motor) 240V 1½ hp 2 hp 3 hp 4 hp 5 hp FLA 1 / 3 AC [A] 11 / 8 14 / / Rec. mains fuse J Class Fuse LPJ 16A LPJ 16A LPJ 20A LPJ 20A LPJ 25A Size 1 / 2-400V mains Unit type: SK 500E... SK 520E A A A A A Motor rated power 380V 0.55 kw 0.75 kw 1.1 kw 1.5 kw 2.2 kw (4 pole standard motor) V ¾ hp 1 hp 1½ hp 2 hp 3 hp FLA [A] Rec. mains fuse J Class Fuse LPJ 10A LPJ 10A LPJ 10A LPJ 10A LPJ 10A Size 3 / 4-400V mains Unit type: SK 500E... SK 520E A A A A Motor rated power 380V 3.0 kw 4.0 kw 5.5 kw 7.5 kw (4 pole standard motor) V 4 hp 5 hp 7½ hp 10 hp FLA [A] Rec. mains fuse J Class Fuse LPJ 16A LPJ 16A LPJ 20A LPJ 25A BU 0500 GB Subject to technical changes 119

120 NORDAC SK 500E / 520E Handbook 8 Additional information 8.1 Set point processing in SK 500E / 520E Main setpoint sources Function Dig. input: Rotation direction Frequency main setpoint Fixed frequency 1-5 Jog frequency (also for Controlbox) P429-P433 P113 Scaling Analogue input 1 Analogue input 2 Control Box / Potentiometer Box Scaling P400-P404 Scaling P405-P409 P549 P105 P104 Interf ace P ±1 Bus setpoint 1,2,3 P546-P548 Auxiliary setpoint sources Analogue input 1 Analogue input 2 Potentiometer Box Bus setpoint 2 Bus setpoint 3 Inc Auxiliary setpoint standardisation Frequency addition / Frequency subtraction Scaling P400 P400-P404 Scaling P405-P409 P549 Bus selection P510 n Scaling P411 P410 P405 P549 P547 P548 P325 Function auxiliary setpoint 120 Subject to technical changes BU 0500 GB

121 8 Additional information Limitation Function auxiliary setpoint PID controller - P f P416 IST M aski ng frequencies f s f P516- P519 Min/Max limitation P105 P104 P505 Frequency ramp f s P102,P103 P106,P107 P108,P114 t Current limitation P112 P111 P536,P537 SET FREQUENCY f max m max I max Actual frequency value Maximum frequency Torque limit Current limit BU 0500 GB Subject to technical changes 121

122 NORDAC SK 500E / 520E Handbook 8.2 Process controller The process controller is a PI controller that allows to limit the controller output. In addition, the output is standardised to a percentage of the reference set point. This provides the opportunity to control any downstream drive with the master set point value and readjust the PI control. Reference set point Analogue input 1 or 2 (P400=4 or P405=4) PID controller ramp P416 Setpoint ramp Min. limitation P466 Set point P412 ( V) P-factor P413 I-factor P414 Max. limitation P415 Start-up time P102 Actual value + - PI controller x1 X x2 y + + x1*x2 y= 100 % Setpoint ramp Analogue input 1 or 2 (P400=14 or P405=14) Lead process control Analogue input (P400=16) pict.: flowchart process controller Process controller application example Controlled drive via CR Compensating roller = CR (dancer roller) Pilot machine M 0V M M Centre 5V nominal position M Actual CR position via pot 0 10 V 10V pict.: example process controller 122 Subject to technical changes BU 0500 GB

123 8 Additional information Set point of pilot machine Enable right Actual position CR AIN1 Dig.1 Dig.2 Frequency inverter f Set point of pilot machine Controller limit P415 in % of set point Controller limit P415 Nominal position CR via parameter P412 t pict.: example process controller Process controller parameter settings (Example: Set frequency: 50 Hz, control limits: +/- 25 %) P105 (maximum frequency) [Hz] : Setpoint freq. [ Hz] Setpoint freq % [ Hz] P415 [%] 50Hz 25% Example: 50Hz + = 62.5 Hz 100% P400 (Fct. Analogue input 1) : "4" (frequency addition) P411 (set frequency) [Hz] : Set frequency with 10 V at analogue input 1 Example: 50 Hz P412 (Set point process controller) P413 (P controller) [%] P414 (I controller) [%/ms] P415 (Limitation +/-) [%] : CR middle position / Default setting 5 V (adapt if necessary) : Default setting 10 % (adapt if necessary) : recommended 0.1 %/ms : Controller limitation (see above) note: The parameter P415 has different functionality in PID controller and Process controller function. Example: 25 % of set point P416 (Ramp before controller) [s] P420 (Fct. digital input 1) P405 (Fct. analogue input 2) : Default setting 2 s (if necessary, adjust to controller behaviour) : "1" Enable right : "14" actual value PID process controller BU 0500 GB Subject to technical changes 123

124 NORDAC SK 500E / 520E Handbook 8.3 Electromagnetic compatibility (EMC) All electrical equipment that have an intrinsic, independent function and are placed on the market as individual units for users must comply from January 1996 with the EEC directive EEC/89/336. There are three different ways for manufacturers to display compliance with this directive: 1. EC declaration of conformity This is a declaration from the manufacturer stating that the requirements in the applicable European standards for the electrical environment of the equipment have been met. Only those standards which are published in the Official Journal of the European Community can be cited in the manufacturer declaration. 2. Technical documentation Technical documentation can be produced which describes the EMC characteristics of the device. This documentation must be authorised by one of the Responsible bodies named by the responsible European government. This makes it possible to use standards that are still being prepared. 3. EC type test certificate This method only applies to radio transmitter equipment. SK 500E / 520E frequency inverters, therefore, have a single function, if they are linked to other equipment (e.g. a motor). The base units cannot therefore carry the CE mark that would confirm compliance with the EMC directive. Precise details are therefore given below about the EMC behaviour of this product, based on the proviso that it is installed according to the guidelines and instructions described in this documentation. Class A, group 2: General, for industrial environments Complies with the EMC standard for power drives EN , for use in secondary environments (industrial) and when not generally available. Class A, group 1: Interference suppressed, for industrial environments In this operating class, the manufacturer can certify that his equipment meets the requirements of the EMC directive for industrial environments with respect to their EMC behaviour in power drives. The limit values correspond to the basic standards EN and EN for interference resistance and interference emission in industrial environments. Class B, group 1: Interference suppressed for domestic, commercial and light industry environments In this operating class, the manufacturer can certify that his equipment meets the requirements of the EMC directive for domestic, commercial and light industry environments with respect to their EMC behaviour in power drives. The limit values correspond to the basic standards EN and EN for interference resistance and interference emission. NOTE The NORDAC SK 500E / 520E frequency inverters are designed solely for commercial applications. They do not therefore meet the requirements of the standard EN for radiation of harmonics. This unit can cause RFI interference. In residential areas RFI suppression may be required. (Details in chapt. 8.3/8.4) 8.4 EMC limit value classes Please ensure, that these limit value classes are only reached if the standard pulse frequency (6 khz) is being used, and the length of the shielded motor cable does not exceed the limits. In addition, it is essential to use wiring suitable for EMC. (Switch box / Cable clamping) The motor cable shielding is to be applied on both sides (inverter shield angle and the metal motor terminal box). 124 Subject to technical changes BU 0500 GB

125 8 Additional information Device type max. motor cable, shielded Jumper position cf chapt Conducted emission 150 khz 30 MHz Class A 1 Class B 1, with EMC kit SK 5xxE A SK 5xxE A SK 5xxE A SK 5xxE A m 5m 2-2 5m m 5m 2-2 5m - Overview of standards that, as per EN for adjustable speed electrical power drive systems product standard, are used for testing and measuring: Interference emission Conducted emission (interference voltage) EN A 1 B 1 with EMC kit Radiated emission (interfering field strength) EN Interference resistance EN , EN A 1 - ESD, discharge of static electricity EN kV (CD), 8kV (AD) EMF, high frequency electromagnetic fields EN V/m; MHz Burst on control cables EN kV Burst on line and motor cables EN kV Surge (phase-phase / phase-ground) Conducted disturbance variable due to high frequency fields EN EN kV / 2kV 10V, MHz Voltage fluctuations and drops EN %, -15%; 90% Voltage dissymmetry and frequency changes EN %; 2% Wiring recommendations Braking resistor (accessory part) Shield angle V and/or V 50-60Hz L 1 L 2 /N L 3 PE B+ L1 L2 L3 PE B- U V W PE U V W M 3 ~ SK 500E / 520E BU 0500 GB Subject to technical changes 125

126 NORDAC SK 500E / 520E Handbook 8.5 Reduced output power The SK 500E / 520E frequency inverter series has been designed for specific overload situations. Example: a 1.5-fold over-current is possible for 60 secs. A 2-fold over-current is possible for ca. 3.5 secs. The overload resistance is reduced in the following cases: o Output frequencies < 2 Hz and direct voltages (stationary needle) o Pulse frequencies exceeding the rated pulse frequency (P504) o Raised mains voltages > 400V o High temperature of the heat sink The following characteristic curves allow the respective power reduction to be read Reduced output current due to pulse frequency This illustration shows the allowed current for 230V and 400V devices caused by the pulse frequency. For 400V devices the reduction starts with a pulse frequency of 6kHz. For 230V devices with a pulse frequency of 8kHz. These curves reflect the power loss in the frequency inverter s final stage. The current must be lowered with increasing pulse frequency in order to keep the power loss near to constant. I / I N k 400V( f k pulse) 400V f puls k 230V( k f 230Vpulse) f puls Pulse frequency [khz] 126 Subject to technical changes BU 0500 GB

127 8 Additional information Reduced over current due to time The possible overload resistance depends on the overload duration. The following tables list some appropriate values. Once such a limit value was reached the frequency inverter must have sufficient time to regenerate at a low load. The limit values given in the table are reduced if the device is operated in the overload area at brief intervals. 230 V devices: Reduced overload resistance (ca.) due to pulse frequency (P504) and time Pulse frequency [khz] Time [s] > % 150% 170% 180% 180% 200% % 140% 155% 165% 165% 180% 12 96% 130% 145% 155% 155% 160% 14 90% 120% 135% 145% 145% 150% 16 82% 110% 125% 135% 135% 140% 400 V devices: Reduced overload resistance (ca.) due to pulse frequency (P504) and time Pulse frequency [khz] Time [s] > % 150% 170% 180% 180% 200% 8 100% 135% 150% 160% 160% 165% 10 90% 120% 135% 145% 145% 150% 12 78% 105% 120% 125% 125% 130% 14 67% 92% 104% 110% 110% 115% 16 57% 77% 87% 92% 92% 100% BU 0500 GB Subject to technical changes 127

128 NORDAC SK 500E / 520E Handbook Reduced over current due to output frequency A monitoring circuit determining the IGBTs (integrated gate bipolar transistor) temperature caused by the high current is provided in order to protect the final stage in case of low output frequencies. A pulse cut-out (P537) with variable limit is assumed in order to prevent currents above the limit indicated in the diagram. For this reason, currents exceeding the rated current by factor 1.1 cannot be assumed at standstill and 6 khz pulse frequency. I / I N impermissible range x ( f) In_60sec ( f) In_1sec ( f) f Output frequency [Hz] Please refer to the following tables for the upper pulse cut-out limit values resulting from various pulse frequencies. Depending on the pulse frequency, the value ( ) you can set in parameter P537 is always limited to the value given in the tables. Values below this limit can be set as desired. 230 V devices: Reduced overload resistance (ca.) due to pulse frequency (P504) and output frequency Pulse frequency [khz] Output frequency [Hz] % 170% 150% 140% 130% 120% 110% % 153% 135% 126% 117% 108% 100% % 136% 120% 112% 104% 96% 95% % 127% 112% 105% 97% 90% 90% % 119% 105% 98% 91% 84% 85% 400 V devices: Reduced overload resistance (ca.) due to pulse frequency (P504) and output frequency Pulse frequency [khz] Output frequency [Hz] % 170% 150% 140% 130% 120% 110% 8 165% 140% 123% 115% 107% 99% 90% % 127% 112% 105% 97% 90% 82% % 110% 97% 91% 84% 78% 71% % 97% 86% 80% 74% 69% 63% % 85% 75% 70% 65% 60% 55% 128 Subject to technical changes BU 0500 GB

129 8 Additional information Reduced output current due to mains voltage The thermal device configuration is based on the rated currents. Consequently, it is not possible to draw higher currents to keep the output power constant in case of lower mains voltages. In case of mains voltages above 400 V the permissible permanent output currents are reduced inversely proportional in order to compensate for the increased switching losses. I / I N k Unetz ( Unetz) Unetz 480 Mains voltage [V] Reduced output current due to heat sink temperature The output current reduction also considers the heat sink temperature in order to allow for a higher load, in particular with higher clock pulses and low heat sink temperatures. The reduction is correspondingly increased with high heat sink temperatures. Ambient temperature and device ventilation conditions can thus be optimised. 8.6 FI circuit breaker operation The frequency inverters are designed for operation on a 30 ma AC/DC sensitive FI circuit breaker. The leakage currents towards PE must be reduced if several frequency inverters are operated on one FI circuit breaker. Further details can be found in chapt BU 0500 GB Subject to technical changes 129

130 NORDAC SK 500E / 520E Handbook 130 Subject to technical changes BU 0500 GB

131 8 Additional information 8.7 Maintenance and servicing information In normal use, NORDAC SK 500E frequency inverters are maintenance free. Please note the General data in chapt If the frequency inverter is operated in dusty air, the cooling surfaces must be regularly cleaned with compressed air. If any air intake filters have been built into the switch box, then these should also be regularly cleaned, or replaced. When directing queries to our technical support please make sure to specify the exact device type (rating plate/display) with accessories and options if necessary, the used software version (P707) and the serial number (rating plate). Repair The equipment must be sent to the following address if it needs repairing: NORD Electronic DRIVESYSTEMS GmbH Tjüchkampstraße Aurich Germany For queries about repairs please contact: Getriebebau NORD GmbH & Co. KG Telephone: / or Fax: / If a frequency inverter is sent in for repair, no liability can be accepted for any added components, e.g. such as line cables, potentiometers, external displays, etc.! Please remove all non-original parts from the frequency inverter. Internet information You can find the comprehensive manuals in German and in English on our Internet site. You can also obtain this manual from your local representative if necessary. BU 0500 GB 131

132 NORDAC SK 500E / 520E Handbook 9 Keyword index A Accessories... 7 Adapterkabel RJ Array parameter... 33, 37, 44 AS interface...52 B basic parameters...59 Basic parameters...54 brake chopper...15 Brake control...61 Brake distance...62 brake resistor...15 Brake ventilation time...63 Braking chopper... 22, 97 Braking control...63 Braking resistor...22, 117, 118 C Cable cross section... 21, 22, 25 Cable duct...11 CANbus...28 CANopen...50 CANopen bus...28 CE mark Characteristics... 6 Charging error Control parameters...68 Control terminals... 25, 71 Control voltages...25 ControlBox...34 Controlling...36 CSA... 9 CUL... 9 D DC brake DC braking Delivery condition Derivative torque DeviceNet Digital inputs Dimensions Direct coupling Display and operation Display and operation Distance travelled calculator.. 62 DS Standard motor dynamic braking E EC declaration of conformity 124 EEC directive EEC/89/ Efficiency Electrical connections EMC EMC guideline...9 EMC kit EMC standard EN EN extra functions F fault reset faults FI-circuit breaker...8 H Heat loss...11 I I2t limit IEC Incremental encoder...29 Information...99 Initialisation...53 Input monitoring...93 Installation...11 Installation instructions... 8 instantaneous current limit...63 InterBus...51 Interference emission Interference resistance Internet IT network...24 IT Network...21 J Jumper...24 L Language selection...42 Leakage current...24 Lifting mechanism with brake.61 load factory setting...92 Load sag...61 Long-term storage Lost heat...11 Low voltage guideline BU 0500 GB

133 9 Keyword index M Mains connection Mains voltage monitoring Maintenance and servicing information Master function Menu group Minimum configuration Motor cable Motor cable length Motor data...53, 64 Motor list Mounting altitude Multi-function relay Multiple motor use N NORDAC SK 500E / 520E... 6 O OFF operating displays Outline Instructions Output monitoring Over current Over temperature Over voltage overvoltage shutdown P Parameter identification...67 Parameter loss Parameter overview ParameterBox...39 ParameterBox error messages 47 ParameterBox parameters...45 Parameterisation... 37, 55 Period of use PI process controller Potentiometer...25 PotentiometerBox...96 Power reduction Power-up cycles Process controller72, 82, 86, 122 Profibus...50 Pulse frequency...88 Pulse switch-off...92 Q Queries R Rating plate...53 Reduced output power Reference voltage...25 RJ Rotation direction...94 Rotation speed S Safety Information... 2 SimpleBox Simulated operation... 6 SK BR SK BR SK EMC SK TU SK TU3-CTR SK TU3-PAR Slip compensation Standard version... 7 Storage Synchronous machines System error T Technical data Technology box... 7 Technology unit Terminal cross section 21, 22, 25 thermal switch Type code U UL/cUL UL/cUL approval... 9 USS Time Out V Ventilation W Watchdog Weight wiring guidelines BU 0500 GB 133

134 NORDAC SK 500E / 520E Handbook 10 Representatives / branches NORD branches worldwide: Brazil NORD Motoredutores do Brasil Ltda. Rua Dr. Moacyr Antonio de Morais, 700 Parque Santo Agostinho Guarulhos São Paulo CEP Tel.: Fax: info@nord-br.com Canada NORD Gear Limited 41, West Drive CDN - Brampton, Ontario, L6T 4A1 Tel.: Fax: info@nord-ca.com Mexico NORD GEAR CORPORATION Mexico Regional Office Av. Lázaro Cárdenas 1007 Pte. San Pedro Garza Garcia, N.L. México, C.P Tel.: Fax: HGonzalez@nord-mx.com India NORD Gear Drive Systems (India) Pvt. Ltd. 21 Vedas Centre D.P. Road AUNDH Pune Maharashtra Tel: +91-2(0) Fax: +91-2(0) info@nord-in.com Indonesia PT NORD Indonesia Jln. Raya Serpong KM. 7 Kompleks Rumah Multi Guna Blok D No. 1 Pakulonan (Serpong) - Tangerang West Java - Indonesia Tel.: Fax: info@nord-ri.com P.R. China NORD (Beijing) Power Transmission Co.Ltd. No. 5 Tangjiacun, Guangqudonglu, Chaoyangqu Beijing Tel.: (-787) Fax: nordac@nord-cn.com Singapore NORD Gear Pte. Ltd. 33 Kian Teck Drive, Jurong Singapore Tel.: Fax: info@nord-sg.com United States NORD Gear Corporation 800 Nord Drive / P.O. Box 367 USA - Waunakee, WI Tel.: Fax: info@nord-us.com P.R. China NORD (Suzhou) Power Transmission Co.Ltd. 地址 : 苏州工业园区长阳街 510 号 No. 510 Changyang Street, Suzhou Ind. Park, Jiangsu, China. P.C : 总机 Tel: 传真 Fax: Kweng@nord-cn.com 134 BU 0500 GB

135 10 Addresses NORD branches in Europe: Austria Getriebebau NORD GmbH Deggendorfstr. 8 A Linz Tel.: Fax: info@nord-at.com Belgium NORD Aandrijvingen Belgie N.V. Boutersem Dreef 24 B Zandhoven Tel.: Fax: info@nord-be.com Croatia NORD Pogoni d.o.o. Obrtnicka 9 HR Krizevci Tel.: Fax: nord-pogoni@kc.htnet.hr Czech. Republic NORD Pohánèci Technika s.r.o Palackého 359 CZ Hradec Králové Tel.: (-11) Fax: hzubr@nord-cz.com France / Frankreich NORD Réducteurs sarl. 17 Avenue Georges Clémenceau F Villepinte Cedex Tel.: Fax: info@nord-fr.com Italy NORD Motoriduttori s.r.l. Via Newton 22 IT San Giovanni in Persiceto (BO) Tel.: Fax: info@nord-it.com Poland NORD Napedy Sp. z.o.o. Ul. Grottgera 30 PL Wieliczka Tel.: Fax: biuro@nord-pl.com Spain NORD Motorreductores Ctra. de Sabadell a Prats de Llucanès Aptdo. de Correos 166 E Sabadell Tel.: Fax: info@nord-es.com Turkey NORD-Remas Redüktör San. ve Tic. Ltd. Sti. Tepeören Köyü TR Tuzla Istandbul Tel.: Fax: info@nord-tr.com Denmark NORD Gear Danmark A/S Kliplev Erhvervspark 28 Kliplev DK Aabenraa Tel.: Fax: info@nord-dk.com Great Britain NORD Gear Limited 11, Barton Lane Abingdon Science Park GB - Abingdon, Oxfordshire OX 14 3NB Tel.: Fax: info@nord-uk.com Netherlands NORD Aandrijvingen Nederland B.V. Voltstraat 12 NL HA Hillegom Tel.: Fax: info@nord-nl.com Russian Federation OOO NORD PRIVODY Ul. A. Nevsky 9 RU St.Petersburg Tel.: Fax: info@nord-ru.com Sweden NORD Drivsystem AB Ryttargatan 277 / Box 2097 S Upplands Väsby Tel.: Fax: info@nord-se.com Finland NORD Gear Oy Aunankorvenkatu 7 FIN Tampere Tel.: Fax: info@nord-fi.com Hungary NORD Hajtastechnika Kft. Törökkö u. 5-7 H Budapest Tel.: Fax: info@nord-hg.com Norway Nord Gear Norge A/S Solgaard Skog 7, PB 85 N-1501 Moss Tel.: Fax: info@nord-no.com Slowakia NORD Pohony, s.r.o Stromová 13 SK Bratislava Tel.: Fax: info@nord-sk.com Switzerland Getriebebau NORD AG Bächigenstr. 18 CH Arnegg Tel.: Fax: info@nord-ch.com Ukraine GETRIEBEBAU NORD GmbH Repräsentanz Vasilkovskaja, 1 office KIEW Tel.: Fax: vtsoka@nord-ukr.com BU 0500 GB 135

136 NORD offices in Germany Getriebebau NORD GmbH & Co. KG Rudolf- Diesel- Str Bargteheide Tel.: / Fax: / info@nord-de.com Northern branch Southern branch Getriebebau NORD GmbH & Co. KG Rudolf- Diesel- Str Bargteheide Tel.: / Fax: / NL-Bargteheide@nord-de.com Getriebebau NORD GmbH & Co. KG Katharinenstr Filderstadt- Sielmingen Tel.: / Fax: / NL-Stuttgart@nord-de.com Bremen sales office Getriebebau NORD GmbH & Co. KG Stührener Weg Bassum Tel.: / Fax: / NL-Bremen@nord-de.com Agency: Hans-Hermann Wohlers Handelsgesellschaft mbh Ellerbuscher Str Löhne Tel.: / Fax: / NL-Bielefeld@nord-de.com Nuremberg sales office Getriebebau NORD GmbH & Co. KG Schillerstr Stein Tel.: / Fax: / NL-Nuernberg@nord-de.com Munich sales office Getriebebau NORD GmbH & Co. KG Untere Bahnhofstr. 29a Germering Tel.: / Fax: / NL-Muenchen@nord-de.com Western branch Getriebebau NORD GmbH & Co. KG Großenbaumer Weg Düsseldorf Tel.: / Fax: / NL-Duesseldorf@nord-de.com Eastern branch Getriebebau NORD GmbH & Co. KG Leipzigerstr Chemnitz Tel.: / Fax: / NL-Chemnitz@nord-de.com Butzbach sales office Getriebebau NORD GmbH & Co. KG Marie- Curie- Str Butzbach Tel.: / Fax: / NL-Frankfurt@nord-de.com Berlin sales office Getriebebau NORD GmbH & Co. KG Heinrich- Mann- Str Schöneiche Tel.: / Fax: / NL-Berlin@nord-de.com Mat. Nr / 1806

MANUAL NORDAC SK 700E. Frequency inverter. SK 700E A... SK 700E O-VT (1.5kW 160kW, 3~ V) SK 700E with option: Parameterbox

MANUAL NORDAC SK 700E. Frequency inverter. SK 700E A... SK 700E O-VT (1.5kW 160kW, 3~ V) SK 700E with option: Parameterbox MANUAL NORDAC SK 700E Frequency inverter SK 700E-151-340-A... SK 700E-163-340-O-VT (1.5kW 160kW, 3~ 380-480V) SK 700E with option: Parameterbox BU 0700 EN Getriebebau NORD GmbH & Co. KG NORDAC SK 700E

More information

BU NORDAC SK 750E Manual for Frequency inverters

BU NORDAC SK 750E Manual for Frequency inverters GB BU 0750 NORDAC SK 750E Manual for Frequency inverters Safety information SK 750E Frequency Inverter Safety and operating instructions for drive power converters (as per: Low Voltage Directive 2006/95/EEC

More information

BU NORDAC SK 700E Frequency inverter manual

BU NORDAC SK 700E Frequency inverter manual GB BU 0700 NORDAC SK 700E Frequency inverter manual NORDAC SK 700E Operating Manual N O R D A C SK 700E frequency inverters Safety and operating instructions for drive power converters (as per: Low Voltage

More information

MANUAL. NORDAC SK 5xxE. Frequency inverter. SK 5xxE O... SK 5xxE O (0.25kW 0.75kW, 1~ 115V, output 3~ 230V)

MANUAL. NORDAC SK 5xxE. Frequency inverter. SK 5xxE O... SK 5xxE O (0.25kW 0.75kW, 1~ 115V, output 3~ 230V) MANUAL NORDAC SK 5xxE Frequency inverter SK 5xxE-250-112-O... SK 5xxE-750-112-O (0.25kW 0.75kW, 1~ 115V, output 3~ 230V) SK 5xxE-250-323-A... SK 5xxE-401-323-A (0.25kW 4.0kW, 1/3~ 230V) SK 5xxE-550-340-A...

More information

Intelligent Drive Systems, Worldwide Services SK 700E F 3070 GB

Intelligent Drive Systems, Worldwide Services SK 700E F 3070 GB Intelligent Drive Systems, Worldwide Services SK 700E Universal application Modular High-Performance Inverter NORDAC SK 700E The NORDAC SK 700E frequency inverter is designed for the power range between

More information

The frequency inverter continues to carry hazardous voltages for up to 5 minutes after it was switched off.

The frequency inverter continues to carry hazardous voltages for up to 5 minutes after it was switched off. Getriebebau NORD GmbH & Co. KG Getriebebau-Nord-Straße 1 22941 Bargteheide, Germany www.nord.com o SK BRI4-1-200-100 Part number: 275 272 008 Internal braking resistor for connection to a NORDAC FLEX SK

More information

BU 0180 SK 180E 190E. Manual for Frequency inverters BU 0180 GB

BU 0180 SK 180E 190E. Manual for Frequency inverters BU 0180 GB GB BU 0180 K 180E 190E BU 0180 GB-0914 1 Manual for Frequency inverters K 180E Manual for frequency inverters About this document NORD frequency inverters afety and operating instructions for drive power

More information

NORDAC SK 500E / SK 520E Condensed Instructions

NORDAC SK 500E / SK 520E Condensed Instructions NORDAC SK 500E / SK 520E Condensed Instructions SK 500E-250-323-A... SK 500E-751-340-A SK 520E-250-323-A... SK 520E-751-340-A 1 General Owing to sensorless vectorial current control which involves evaluation

More information

External brake resistor AX2090-BW5x

External brake resistor AX2090-BW5x Documentation External brake resistor AX2090-BW5x Accessories for Beckhoff servo drive AX5000 Version: Date: 1.3 2018-03-14 Table of content Table of content 1 Foreword... 5 1.1 Notes on the documentation...

More information

The frequency inverter continues to carry hazardous voltages for up to 5 minutes after it was switched off.

The frequency inverter continues to carry hazardous voltages for up to 5 minutes after it was switched off. o SK BRW4-2-200-200 Part number: 275 273 408 External brake resistor for direct wall mounting of decentralised frequency inverters Only qualified electricians are allowed to install and commission the

More information

maxon document number:

maxon document number: maxon document number: 791272-04 1 Table of contents... 2 2 Table of figures... 3 3 Introduction... 4 4 How to use this guide... 4 5 Safety Instructions... 5 6 Performance Data... 6 6.1 Motor data... 6

More information

Installation and Operational Instructions for ROBA -switch Type 017._00.2

Installation and Operational Instructions for ROBA -switch Type 017._00.2 OBA -switch Type 017._00.2 Guidelines on the Declaration of Conformity A conformity evaluation has been carried out for the product in terms of the EC Low Voltage Directive 2014/35/ EC and the EMC Directive

More information

120/240 Watt AC-DC Front End with PFC W Series Convert Select 120 Convert Select 240

120/240 Watt AC-DC Front End with PFC W Series Convert Select 120 Convert Select 240 Industrial Environment AC-DC Converters >100 Watt W Series 120/240 Watt AC-DC Front End with PFC W Series Convert Select 120 Convert Select 240 Rugged 35 mm DIN-rail snap-fit design 3000 V AC input to

More information

1 Introduction. 1.1 General installation information

1 Introduction. 1.1 General installation information 1 Introduction Nearly every electrical component emits electromagnetic radiation during its operation. This has effects on the quality of the useful signals especially at the communication level, in which

More information

smd frequency inverter

smd frequency inverter S03B These Instructions contain important technical data and describe installation, operation and commissioning of the smd frequency inverter. are only valid for smd frequency inverters with software rev

More information

VERSATILE FREQUENCY INVERTER FOR CONTROL CABINET APPLICATIONS

VERSATILE FREQUENCY INVERTER FOR CONTROL CABINET APPLICATIONS Intelligent Drivesystems, Worldwide Services VERSATILE FREQUENCY INVERTER FOR CONTROL CABINET APPLICATIONS EN NORDAC PRO SK 500E FREQUENCY INVERTER www.nord.com NORDAC PRO SK 500E THE ALL-ROUNDER THE NORDAC

More information

ATV12HU40M3 variable speed drive ATV12-4kW - 5hp V - 3ph - with heat sink

ATV12HU40M3 variable speed drive ATV12-4kW - 5hp V - 3ph - with heat sink Characteristics variable speed drive ATV12-4kW - 5hp - 200..240V - 3ph - with heat sink Main Range of product Altivar 12 Product or component type Product destination Product specific application Assembly

More information

Frequency converters VAU 4/4 VAU(w) 7.5/3 VAU 11-22/3

Frequency converters VAU 4/4 VAU(w) 7.5/3 VAU 11-22/3 Operating Instructions Frequency converters VAU 4/4 VAU(w) 7.5/3 VAU 11-22/3 28100241500 05/15 Contents 1 General information...4 1.1 Notes relating to the documentation...4 1.1.1 Warnings...4 1.1.2 Warning

More information

Installation and Operational Instructions for ROBA -multiswitch Type 019._00.2

Installation and Operational Instructions for ROBA -multiswitch Type 019._00.2 Guidelines on the Declaration of Conformity A conformity evaluation has been carried out for the product in terms of the EU Low Voltage Directive 2014/35/ EU and the Electromagnetic Compatibility (EMC)

More information

EY-EM 527: Remote I/O module, ecolink527

EY-EM 527: Remote I/O module, ecolink527 Product data sheet 94.078 EY-EM 527: Remote I/O module, ecolink527 How energy efficiency is improved Regulation, control, monitoring and optimisation of operational systems, e.g. room automation or HVAC

More information

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W ADC5000 SERIES AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications 60W, 125W and 250 W Input voltage 230/115 VAC voltages 12, 24, 36 or 48 VDC Statistical MTBF >3 000

More information

ATV12H018F1 variable speed drive ATV kW hp V - 1ph

ATV12H018F1 variable speed drive ATV kW hp V - 1ph Characteristics variable speed drive ATV12-0.18kW - 0.25hp - 100..120V - 1ph Main Range of product Altivar 12 Product or component type Product destination Product specific application Assembly style Component

More information

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink Characteristics variable speed drive ATV12-0.37kW - 0.55hp - 100..120V - 1ph - with heat sink Main Range of product Altivar 12 Product or component type Product destination Product specific application

More information

ATV12HU22M2. Main. Range of product Altivar 12. Component name Quantity per set Set of 1. Built-in fan. Motor power hp Communication port protocol

ATV12HU22M2. Main. Range of product Altivar 12. Component name Quantity per set Set of 1. Built-in fan. Motor power hp Communication port protocol Product datasheet Characteristics ATV12HU22M2 Complementary Main Range of product Altivar 12 Product or component type Product destination Product specific application Assembly style Component name Variable

More information

RMO500 M I C R O O H M M E T E R

RMO500 M I C R O O H M M E T E R M I C R O O H M M E T E R Reference Manual IBEKO POWER AB Sweden 2 IBEKO POWER AB Manual Version:. MV.01 IBEKO POWER AB 2003 This Reference Manual is a publication of IBEKO POWER AB, 18 125 Lidingö, Sweden.

More information

Manual. MOVITRAC LTE-B+/LTP-B Accessories Braking Resistors, Filters, Chokes, Shielding * _0618*

Manual. MOVITRAC LTE-B+/LTP-B Accessories Braking Resistors, Filters, Chokes, Shielding * _0618* rive Technology \ rive Automation \ System Integration \ Services *23540052_0618* Manual MOVITRAC LTE-B+/LTP-B Accessories Braking Resistors, Filters, Chokes, Shielding Edition 06/2018 23540052/EN SEW-EURORIVE

More information

GB MI Frequency inverters. Migration Guide SK 700E to SK 5xxE

GB MI Frequency inverters. Migration Guide SK 700E to SK 5xxE GB MI 0700 Frequency inverters Migration Guide to Pos: 2 /Migrati onsleitfaden/ - SK 500E/0. Prol og/0.3 Dokumentation - Versi onsliste [MI 0700] @ 2\mod_1359466500742_388.docx @ 54775 @ @ 1 Pos: 3 /----------

More information

NSD Safety Mat Controller Modules Both Modules are compliant to OSHA & ANSI Standards - EN ISO EN EN 81-1 EN NSD VDC

NSD Safety Mat Controller Modules Both Modules are compliant to OSHA & ANSI Standards - EN ISO EN EN 81-1 EN NSD VDC Datasheet NSD Safety Mat Controller Modules Both Modules are compliant to OSHA & ANSI Standards - EN ISO 13849-1 EN 62061 EN 81-1 EN 50156-1 Approvals NSD-3580 24 VDC NSD-3590 115 TO 230 VAC Technical

More information

Power supply CP-T 24/10.0 Primary switch mode power supply

Power supply CP-T 24/10.0 Primary switch mode power supply Data sheet Power supply CP-T 24/10.0 Primary switch mode power supply The CP-T range of three-phase power supply units is the youngest member of ABB s power supply family. In terms of design and functionality,

More information

Frequency converter VAU 4/4 VAU(w) 7.5/3 VAU 11-22/3

Frequency converter VAU 4/4 VAU(w) 7.5/3 VAU 11-22/3 operating instructions Quick start guide Frequency converter VAU 4/4 VAU(w) 7.5/3 VAU 1122/3 28100241501 03/15 1 www.beckerinternational.com Table of Contents 1. Safety information...15 1.1 Warning symbols

More information

Manual. MOVITRAC LTE-B/LTP-B Accessories Braking Resistors, Filters, Chokes, Shielding * _0515*

Manual. MOVITRAC LTE-B/LTP-B Accessories Braking Resistors, Filters, Chokes, Shielding * _0515* rive Technology \ rive Automation \ System Integration \ Services *21302197_0515* Manual MOVITRAC LTE-B/LTP-B Accessories Braking Resistors, Filters, Chokes, Shielding Edition 05/2015 21302197/EN SEW-EURORIVE

More information

OPERATING INSTRUCTIONS. NORDAC compact Frequency Inverter

OPERATING INSTRUCTIONS. NORDAC compact Frequency Inverter OPERATING INSTRUCTIONS NORDAC compact Frequency Inverter SK 250/1 FNC... SK 2200/1 FNC SK 250/2 NC... SK 22000/2 NC SK 1500/3 NC... SK 37000/3 NC SK 7500/4 NC... SK 37000/4 NC BU 3300/96 GB October 1996

More information

EY-EM 522, 523: Remote I/O module, ecolink522, 523

EY-EM 522, 523: Remote I/O module, ecolink522, 523 Product data sheet 94.077 EY-EM 522, 523: Remote I/O module, ecolink522, 523 How energy efficiency is improved Regulation, control, monitoring and optimisation of operational systems, e.g. room automation

More information

Power supply CP-T 48/5.0 Primary switch mode power supply

Power supply CP-T 48/5.0 Primary switch mode power supply Data sheet Power supply CP-T 48/5.0 Primary switch mode power supply The CP-T range of three-phase power supply units is the youngest member of ABB s power supply family. In terms of design and functionality,

More information

MINI-PS AC/24DC/1.3

MINI-PS AC/24DC/1.3 Power supply unit INTERFACE Data sheet 102894_en_03 1 Description PHOENIX CONTACT 2015-11-17 Features MINI POWER power supplies for MCR technology In measurement and control technology (MCR), modular electronics

More information

Installation and Operating Instructions for Phase Demodulator Type _.2

Installation and Operating Instructions for Phase Demodulator Type _.2 Guidelines on the Declaration of Conformity A conformity evaluation has been carried out for the product in terms of the EU Low Voltage Directive 2014/35/EU and the Electromagnetic Compatibility (EMC)

More information

VARAN Stepper Module VST 012

VARAN Stepper Module VST 012 VARAN Stepper Module VST 012 The VST 012 is a VARAN module designed for the control of a stepper motor up to a maximum 10 A RMS. The available operating modes are full step, half step and micro step. The

More information

Power supply CP-D 24/4.2 Primary switch mode power supply

Power supply CP-D 24/4.2 Primary switch mode power supply Data sheet Power supply CP-D 24/4.2 Primary switch mode power supply The CP-D range of modular power supply units in MDRC design (modular DIN rail components) is ideally suited for installation in distribution

More information

Technical manual. Microstep driver SMC11. NANOTEC ELECTRONIC GmbH & Co. KG Gewerbestraße 11 D Landsham near Munich, Germany

Technical manual. Microstep driver SMC11. NANOTEC ELECTRONIC GmbH & Co. KG Gewerbestraße 11 D Landsham near Munich, Germany Technical manual Microstep driver NANOTEC ELECTRONIC GmbH & Co. KG Gewerbestraße 11 D-85652 Landsham near Munich, Germany Tel. +49 (0)89-900 686-0 Fax +49 (0)89-900 686-50 info@nanotec.de Editorial Editorial

More information

Power supply CP-T 24/40.0 Primary switch mode power supply

Power supply CP-T 24/40.0 Primary switch mode power supply Data sheet Power supply CP-T 24/40.0 Primary switch mode power supply The CP-T range of three-phase power supply units is the youngest member of ABB s power supply family. In terms of design and functionality,

More information

Ref /b VARMECA 10 Variable speed motors and geared motors. Parameter-setting manual

Ref /b VARMECA 10 Variable speed motors and geared motors. Parameter-setting manual en L This manual is to be given to the end user L L PE 9 0 4 5 6 Parameter-setting manual NOTE LEROY-SOMER reserves the right to modify the characteristics of its products at any time in order to incorporate

More information

Electronic Circuit Breaker ESS1 for System SVS1

Electronic Circuit Breaker ESS1 for System SVS1 Electronic Circuit Breaker for System SVS Description The electronic circuit breaker is designed to ensure selective disconnection of individual s in industrial systems which are powered by a DC 24 V switch

More information

2.7. IT system floor-standing distribution cabinet Series -IPS-F/EDS

2.7. IT system floor-standing distribution cabinet Series -IPS-F/EDS Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 65 35305 Grünberg Tel.: 0640 807-0 Fax: 0640 807-259 IT system floor-standing distribution cabinet Series -IPS-F/EDS for supplying power to medical locations

More information

Operating instructions Fail-safe delay timer AZS About this document. Content

Operating instructions Fail-safe delay timer AZS About this document. Content 8 Appendix 8.1 Wiring example...4 8.2 Integral System Diagnostics (ISD)....5 9 EU Declaration of conformity Operating instructions.............pages 1 to 6 Original x.000 / 11.2017 / v.a. - 101126753-

More information

Index 2. G Gain settings 4 31 Glossary of terms A 2 Grommets 2 13

Index 2. G Gain settings 4 31 Glossary of terms A 2 Grommets 2 13 Index A A Group functions 3 9 AC reactors 5 3 Acceleration 1 15, 3 8 characteristic curves 3 26 second function 3 24 two-stage 4 19 Acceleration stop function 3 21 Access levels 3 5, 3 36, 4 25 Access

More information

Power supply CP-T 24/20.0 Primary switch mode power supply

Power supply CP-T 24/20.0 Primary switch mode power supply Data sheet Power supply CP-T 24/20.0 Primary switch mode power supply The CP-T range of three-phase power supply units is the youngest member of ABB s power supply family. In terms of design and functionality,

More information

maxon motor maxon motor control 4-Q-EC Servoamplifier DES 70/10 Order number

maxon motor maxon motor control 4-Q-EC Servoamplifier DES 70/10 Order number control 4-Q-EC Servoamplifier DES 70/10 Order number 228597 April 2006 Edition The DES (Digital EC Servoamplifier) is a very efficient digital servoamplifier with sinusoidal current commutation for perfectly

More information

Variable frequency drives; 1-/3-phase 230 V; 10.5 A; 2.2 kw; EMC filters; braking transistor

Variable frequency drives; 1-/3-phase 230 V; 10.5 A; 2.2 kw; EMC filters; braking transistor DATASHEET - DC1-12011FB-A20CE1 Technical data General Variable frequency drives; 1-/3-phase 230 V; 10.5 A; 2.2 kw; EMC filters; braking transistor Part no. DC1-12011FB-A20CE1 Catalog No. 185815 Eaton Catalog

More information

Product Manual. item Servo Positioning Controller C 3-Series. designed for Functional Safety. item Industrietechnik GmbH Telephone: +49-(0)

Product Manual. item Servo Positioning Controller C 3-Series. designed for Functional Safety. item Industrietechnik GmbH Telephone: +49-(0) Product Manual item Servo Positioning Controller C 3-Series designed for Functional Safety item Industrietechnik GmbH Telephone: +49-(0)212-6580-0 Friedenstraße 107-109 Fax: +49-(0)212-6580-310 42699 Solingen

More information

SIMEAS-T. Operating Instructions Transducer without auxiliary power. 7KG6111 and 7KG6101. Operating Instructions

SIMEAS-T. Operating Instructions Transducer without auxiliary power. 7KG6111 and 7KG6101. Operating Instructions Operating Instructions SIMEAS-T s Operating Instructions Transducer without auxiliary power for alternating current for alternating voltage for alternating voltage with expanded end range 7KG6111 and 7KG6101

More information

Brief description of KR 15 controllers

Brief description of KR 15 controllers Brief description of KR 15 controllers E N E R G Y R E C O V E R Y Page 2 Page 4 Page 5 Page 6 Page 9 1. Function of the controller 2. Terminal connections 3. Technical data 4. Initial operation 5. Manual

More information

Power supply CP-E 24/0.75

Power supply CP-E 24/0.75 2CDC 271 016 F0t06 a OUTPUT L+, L : terminals output b INPUT L, N, PE: terminals input c LOW: red LED output voltage too low d OK: green LED output voltage OK e OUTPUT Adjust: rotary potentiometer output

More information

AND UTOMATION OLUTIONS. Operating instructions Part 1. General information and power section. Frequency inverter 400 V. 4.0 kw

AND UTOMATION OLUTIONS. Operating instructions Part 1. General information and power section. Frequency inverter 400 V. 4.0 kw I NDUSTRY A P ROCESS AND UTOMATION OLUTIONS S Operating instructions Part General information and power section VCB Frequency inverter 400 V 4.0 kw... 355.0 kw GB Operating instructions Part General information

More information

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink Characteristics variable speed drive ATV12-0.37kW - 0.55hp - 100..120V - 1ph - with heat sink Product availability : Stock - Normally stocked in distribution facility Price* : 191.76 USD Main Range of

More information

Power supply CP-D 24/1.3

Power supply CP-D 24/1.3 2CDC 271 027 F0t07 a OUTPUT ++/ : terminals output Features Rated output voltage 24 V DC Output voltage adjustable via front face potentiometer OUTPUT Adjust Rated output current 1.3 A Rated output power

More information

Power supply CP-E 24/20.0

Power supply CP-E 24/20.0 2CDC 271 027 F0008 a OUTPUT L+, L+, L, L-: terminals output b INPUT L, N, PE: terminals input c 13-14: terminals - signalling contact d OUTPUT OK: green LED output voltage OK e OUTPUT LOW: red LED output

More information

Out 1 sin / cos 1Vpp. sin / cos 1Vpp. Out 3. sin / cos 1Vpp. Out 4 sin / cos 1Vpp. Interface type SV211 SinCos signal splitter with 4 SinCos outputs

Out 1 sin / cos 1Vpp. sin / cos 1Vpp. Out 3. sin / cos 1Vpp. Out 4 sin / cos 1Vpp. Interface type SV211 SinCos signal splitter with 4 SinCos outputs Operating Manual Out 1 sin / cos 1Vpp Input: sin / cos 1 Vpp Out 2 sin / cos 1Vpp Out 3 sin / cos 1Vpp SV 211 Out 4 sin / cos 1Vpp Interface type SV211 SinCos signal splitter with 4 SinCos outputs Product

More information

Power supply CP-T 48/20.0 Primary switch mode power supply

Power supply CP-T 48/20.0 Primary switch mode power supply Data sheet Power supply CP-T 48/20.0 Primary switch mode power supply The CP-T range of three-phase power supply units is the youngest member of ABB s power supply family. In terms of design and functionality,

More information

Brief Manual ACTIVE N3878

Brief Manual ACTIVE N3878 Brief Manual ACTIVE 30V single-three phase ( sizes) 0.55 kw - 0.75 kw - 1.1 kw 1.5 kw -. kw - 3.0 kw 400V three phase (4 sizes) 0.55 kw - 0.75 kw - 1.1 kw 1.5 kw -. kw - 3.0 kw 4.0 kw - 5.5 kw - 7.5 kw

More information

PU202 Level converter & encoder signal generator without potential separation

PU202 Level converter & encoder signal generator without potential separation Operating Manual PU202 Level converter & encoder signal generator without potential separation Product features: Converts HTL signals from 10 up to 30 V (A / B / Z) into the corresponding TTL / RS422 format

More information

IF30. User's manual. Description. Table of contents IF30

IF30. User's manual. Description. Table of contents IF30 User's manual IF30 Description IF30 is an encoder interface unit designed to convert the output signals delivered by so-called sine-cosine-encoders and similar measuring systems (devices which deliver

More information

Electronic Circuit Breaker ESS1 for System SVS1

Electronic Circuit Breaker ESS1 for System SVS1 Electronic Circuit Breaker for System SVS Description The electronic circuit breaker is designed to ensure selective disconnection of individual s in industrial systems which are powered by a DC 24 V switch

More information

Siemens OPERATING INSTRUCTIONS FOR MICROMASTER ECO & MIDIMASTER ECO V1.19. Variable speed drive for Fans and Pumps (HVAC) from 0,75kW to 315kW

Siemens OPERATING INSTRUCTIONS FOR MICROMASTER ECO & MIDIMASTER ECO V1.19. Variable speed drive for Fans and Pumps (HVAC) from 0,75kW to 315kW Siemens OPERATING INSTRUCTIONS FOR MICROMASTER ECO & MIDIMASTER ECO V1.19 Variable speed drive for Fans and Pumps (HVAC) from 0,75kW to 315kW Siemens G85139-H1751-U555-D1 0 of 23 CONTENS SAFETY AND CE

More information

D SERIES EM16 IP 20 / NEMA 1 & IP 66 / NEMA 4X COMPACT VECTOR CONTROL DRIVE EM 16 COMPACT VECTOR CONTROL DRIVE

D SERIES EM16 IP 20 / NEMA 1 & IP 66 / NEMA 4X COMPACT VECTOR CONTROL DRIVE EM 16 COMPACT VECTOR CONTROL DRIVE D SERIES EM16 IP 20 / NEMA 1 & IP 66 / NEMA 4X COMPACT VECTOR CONTROL DRIVE EM 16 COMPACT VECTOR CONTROL DRIVE 1 2 SERIES 1 2 pag. 4 pag. 5 Applications Model identification 3 pag. 5 4 pag. 6 Capacity

More information

System configuration. Ratings 400 V Class three-phase 90 to 800 kw 690 V Class three-phase 90 to 1000 kw SX-D. Frequency inverters.

System configuration. Ratings 400 V Class three-phase 90 to 800 kw 690 V Class three-phase 90 to 1000 kw SX-D. Frequency inverters. ~ ~ SX High performance Vector Control IP54 full range. Compact design & Robustness Built-in Filter according to C3 Class Built-in Fusses (From 200 kw) Safety according EN13849-1 and EN62061 standards

More information

Servo Positioning Controller ARS 2300 FS

Servo Positioning Controller ARS 2300 FS Servo Positioning Controller ARS 2300 FS Functional Safety Product Manual Metronix Meßgeräte und Elektronik GmbH Telephone: +49-(0)531-8668-0 Kocherstraße 3 Fax: +49-(0)531-8668-555 38120 Braunschweig

More information

D SERIES LM16. COMPACT DRIVE V/f and SLV CONTROL. LM16 COMPACT DRIVE V/f and SLV CONTROL

D SERIES LM16. COMPACT DRIVE V/f and SLV CONTROL. LM16 COMPACT DRIVE V/f and SLV CONTROL D SERIES LM16 COMPACT DRIVE V/f and SLV CONTROL LM16 COMPACT DRIVE V/f and SLV CONTROL 1 2 SERIES 1 2 page 4 page 6 Introduction Fields of application 3 page 7 4 page 8 Designation Product offer 5 6 page

More information

MU110-16R(K) Digital output module 16 channel. User guide

MU110-16R(K) Digital output module 16 channel. User guide MU110-16R(K) Digital output module 16 channel User guide MU110-16R(K)_2016.12_0220_EN All rights reserved Subject to technical changes and misprints akytec GmbH Vahrenwalder Str. 269 A 30179 Hannover Germany

More information

Power supply CP-E 24/2.5

Power supply CP-E 24/2.5 2CDC 271 015 F0t06 a OUTPUT L+, L : terminals output b DC OK: terminal signalling output c INPUT L, N, PE: terminals input d OUTPUT OK: green LED output voltage OK e OUTPUT Adjust: potentiometer adjustment

More information

Operating Instructions

Operating Instructions Level and Pressure Operating Instructions VEGATOR 620, 621, 622 max. 0 10 min. 0 10 on VEGATOR 622! 6 7 8 9 10 11 12 13 14 in out Contents Contents Safety information... 2 Note Ex area... 2 1 Product description

More information

Installation and Operational Instructions for ROBA -switch Type 017._00.2

Installation and Operational Instructions for ROBA -switch Type 017._00.2 Manufacturer s Declaration This product is intended for installation in a machine or system, based on the machine directive 2006/42/EC. It is forbidden to start use of the product until the machine or

More information

8V General information. 2 Order data 8V

8V General information. 2 Order data 8V 8V05.00-8V05.00- General information Modular mechanical design using plug-in modules Integrated line filter Integrated braking resistor All connections are made using plug-in connectors Integrated electronic

More information

Intelligent Drivesystems, Worldwide Services. Control cabinet inverter SK 500E 0.25 to 160 kw Product overview

Intelligent Drivesystems, Worldwide Services. Control cabinet inverter SK 500E 0.25 to 160 kw Product overview Intelligent rivesystems, orldwide Services GB Control cabinet inverter 500E 0.25 to 160 k Product overview NOR RIVESYSTEMS Intelligent rivesystems, orldwide Services One for all The 500E product family

More information

8V General information. 2 Order data 8V

8V General information. 2 Order data 8V 8V80.00-8V80.00- General information Modular mechanical design using plug-in modules Integrated line filter Integrated or optional external braking resistor All connections are made using plug-in connectors

More information

MU110-8R(K) Digital output module 8 channel. User guide

MU110-8R(K) Digital output module 8 channel. User guide MU110-8R(K) Digital output module 8 channel User guide MU110-8R(K)_2019.01_0296_EN All rights reserved Subject to technical changes and misprints akytec GmbH Vahrenwalder Str. 269 A 30179 Hannover Germany

More information

Manual. Frequency Inverter. Series KFU 2- / 4- 0,55 to 3,0 kw 230 V KFU 2-0,55 to 132 kw 400 V KFU 4- KN E

Manual. Frequency Inverter. Series KFU 2- / 4- 0,55 to 3,0 kw 230 V KFU 2-0,55 to 132 kw 400 V KFU 4- KN E Manual Frequency Inverter Series KFU 2- / 4-0,55 to 3,0 kw 230 V KFU 2-0,55 to 132 kw 400 V KFU 4- KN 620.1108 E General Information about the Documentation The present documentation refers to the frequency

More information

Installation instructions for encoders. RM3xxx RM7xxx RN3xxx RN7xxx /02 08/2015

Installation instructions for encoders. RM3xxx RM7xxx RN3xxx RN7xxx /02 08/2015 Installation instructions for encoders RMxxx RM7xxx RNxxx RN7xxx 897/ 8/ Contents Preliminary note.... Notes on this document.... Symbols used... Safety instructions.... General.... Installation and connection...

More information

Reactive Power Control Relay RM 2106 / 2112 Operating Instructions. FRAKO Kondensatoren- und Anlagenbau

Reactive Power Control Relay RM 2106 / 2112 Operating Instructions. FRAKO Kondensatoren- und Anlagenbau Reactive Power Control Relay RM 2106 / 2112 Operating Instructions FRAKO Kondensatoren- und Anlagenbau www.frako.com Figure 1 Front view a b c d e Display for active capacitor stages Display for inductive

More information

High-quality digital indicator for panel mounting Model DI35-M, with multi-function input Model DI35-D, with two inputs for standard signals

High-quality digital indicator for panel mounting Model DI35-M, with multi-function input Model DI35-D, with two inputs for standard signals Accessories High-quality digital indicator for panel mounting Model DI35-M, with multi-function input Model DI35-D, with two inputs for standard signals WIKA data sheet AC 80.03 Applications Machine building

More information

Power supply CP-D 12/2.1

Power supply CP-D 12/2.1 2CDC 271 025 F0t07 a OUTPUT ++/ : terminals output Features Rated output voltage 12 V DC Output voltage adjustable via front face potentiometer OUTPUT Adjust Rated output current 2.1 A Rated output power

More information

Instruction manual for STA 1 sectional door operator

Instruction manual for STA 1 sectional door operator Instruction manual for STA 1 sectional door operator Sectional door operator STA 1 / Rev. 0.3 1 GB 1. Contents 3. General safety instructions 1. Contents 2 2. Key to symbols 2 3. General safety instructions

More information

IRT AT-Small. Technical Manual. quality IN MOTION. quality IN MOTION

IRT AT-Small. Technical Manual. quality IN MOTION.   quality IN MOTION IRT quality IN MOTION www.irtsa.com 2000 AT-Small Technical Manual IRT quality IN MOTION E2 0 8 4 1 5 September 2013-Rev. 4 UL Requirements Drives Series 2000 / 4000 AT 1. Field wiring terminal to use

More information

EC 45 flat with integrated electronics Document ID: en Operating Manual

EC 45 flat with integrated electronics Document ID: en Operating Manual EC 45 flat with integrated electronics Document ID: 919801en Operating Manual Edition June 2017 The EC 45 flat with integrated electronics is a brushless, speed-controlled 1-quadrant drive. It is available

More information

Power supply CP-E 12/10.0 Primary switch mode power supply Data sheet

Power supply CP-E 12/10.0 Primary switch mode power supply Data sheet 2CDC 271 024 F0008 OUTPUT L+, L+, L-, L-: terminals - output INPUT L, N, PE: terminals - input OUTPUT OK: green LED - output voltage OK OUTPUT LOW: red LED - output voltage too low OUTPUT Adjust: potentiometer

More information

TAC ATV38, IP55. Variable Speed Drives for Asynchronous Motors. 3-phase. 380/460 V, Hz

TAC ATV38, IP55. Variable Speed Drives for Asynchronous Motors. 3-phase. 380/460 V, Hz TAC ATV8, IP55 Variable Speed Drives for Asynchronous Motors. -phase. 80/460 V, 50-60 Hz E-60-24 24 May 2004 ATV 8 IP55 drives are specifically designed for pump and fan applications powered by a three-phase

More information

Siemens AG Allows easy and consistent configuration with one series of overload relays (for small to large loads)

Siemens AG Allows easy and consistent configuration with one series of overload relays (for small to large loads) Overview Features Benefits 3RU11 3RB20/3RB21 3RB22/3RB23 Sizes Are coordinated with the dimensions, connections S00...S3 S00... S12 S00... S12 and technical characteristics of the other devices in the

More information

CROSS Chassis from 160 A to 450 A

CROSS Chassis from 160 A to 450 A CROSS Chassis from 160 A to 450 A STS CATALOGUE Important note! The technical data enclosed is for general information. Please note that the operating instructions and references indicated on the products

More information

Power supply CP-E 48/5.0 Primary switch mode power supply Data sheet

Power supply CP-E 48/5.0 Primary switch mode power supply Data sheet 2CDC 271 028 F0008 OUTPUT L+, L+, L-, L-: terminals - output Features Rated output voltage 48 V DC Output voltage adjustable via front-face rotary potentiometer OUTPUT Adjust Rated output current 5 A Rated

More information

VFSC9 ELECTRONIC SPEED CONTROLLER. Mounting and operating instructions

VFSC9 ELECTRONIC SPEED CONTROLLER. Mounting and operating instructions ELECTRONIC SPEED CONTROLLER Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 5 WIRING

More information

SX (400V) System configuration

SX (400V) System configuration ~ ~ SX (400V) High performance Vector Control IP54 full range. Compact design & Robustness Built-in Filter according to C3 Class Built-in Fusses (From 200 kw) Safety according EN13849-1 and EN62061 standards

More information

Ambient Conditions Storage Conditions Installation Minimum Clearances and Air Flow...2 3

Ambient Conditions Storage Conditions Installation Minimum Clearances and Air Flow...2 3 CHAPTER INSTALLATION 2 AND WIRING Contents of this Chapter... Ambient Conditions..............................2 2 Storage Conditions...............................2 2 Installation.....................................2

More information

INSTALLATION AND OPERATION MANUAL IODA INPUT/OUTPUT MULTI-FUNCTION BOARD (Part No. 9668)

INSTALLATION AND OPERATION MANUAL IODA INPUT/OUTPUT MULTI-FUNCTION BOARD (Part No. 9668) INSTALLATION AND OPERATION MANUAL IODA INPUT/OUTPUT MULTI-FUNCTION BOARD (Part No. 9668) Use with Models KBDA-24D, 27D, 29, 45, 48 See Safety Warning, on page 4. RoHS The information contained in this

More information

EMC Data Sheet CSD100 Model size 4 to 6. Variable Speed AC drive for permanent magnet motors

EMC Data Sheet CSD100 Model size 4 to 6. Variable Speed AC drive for permanent magnet motors EMC Data Sheet CSD100 Model size 4 to 6 Variable Speed AC drive for permanent magnet motors Safety Warnings A Warning contains information which is essential for avoiding a safety hazard. A Caution contains

More information

Signal converter for electromagnetic flowmeters

Signal converter for electromagnetic flowmeters Quick Start Signal converter for electromagnetic flowmeters Electronic revision: ER 3.0.xx The documentation is only complete when used in combination with the relevant documentation for the flow sensor.

More information

SX (400 V) System configuration

SX (400 V) System configuration ~ ~ SX (400 V) High performance Vector Control IP54 full range. Compact design & Robustness Built-in Filter according to C3 Class Built-in Fuses (From 200 kw) Safety according EN13849-1 and EN62061 standards

More information

21 VA (l max 20 5 ms) Connection Cable 1 m, 4 x 0.75 mm 2 Functional data Factory settings Variable Setting Torque Inhibiting torque

21 VA (l max 20 5 ms) Connection Cable 1 m, 4 x 0.75 mm 2 Functional data Factory settings Variable Setting Torque Inhibiting torque echnical data sheet GK4A- Communicative SuperCap rotary actuator with emergency setting function and extended functionalities for adjusting air dampers in ventilation and air-conditioning systems for building

More information

Original operating instructions Fail-safe inductive sensor GM504S / / 2010

Original operating instructions Fail-safe inductive sensor GM504S / / 2010 Original operating instructions Fail-safe inductive sensor GM504S 704070 / 01 06 / 2010 Contents 1 Preliminary note 3 1.1 Explanation of symbols 3 2 Safety instructions 4 2.1 Safety-related requirements

More information

QUINT-PS AC/24DC/40

QUINT-PS AC/24DC/40 Power supply unit INTERFACE Data sheet 102315_en_02 1 Description PHOENIX CONTACT 2010-04-23 Features QUINT POWER power supply units for plant and special engineering reliably start heavy loads with high

More information

3TK28 Safety Relays. General data. 7/70 Siemens LV

3TK28 Safety Relays. General data. 7/70 Siemens LV 3TK28 Safety Relays General data Overview SIRIUS safety relays are the key elements of a consistent and cost-effective safety chain. Be it EMERGENCY-STOP disconnection, protective door monitoring or the

More information

This data sheet is only valid in association with the IL SYS INST UM E user manual.

This data sheet is only valid in association with the IL SYS INST UM E user manual. Inline counter terminal, version for extreme conditions, 1 counter input, 1 control input, 1 output, 24 V DC, 500 ma Data sheet 106148_en_03 PHOENIX CONTACT 2015-11-04 1 Description The terminal is designed

More information