0,.527+(50 Š FRQWUROOHUZLWKGLJLWDOLQSXW

Size: px
Start display at page:

Download "0,.527+(50 Š FRQWUROOHUZLWKGLJLWDOLQSXW"

Transcription

1 0,.527+(50 Š 07B'B5² FRQWUROOHUZLWKGLJLWDOLQSXW MT600D 08/10 Rev.6/Soft.3 English version THERMOPROZESS s.r.o. Riegrova 2668/6c Ceske Budejovice tel.: fax:

2 If there is any default of the device could cause a damage, the equipment with the controller must be fitted with the independent protection unit (thermal cut-out/limiter). 2

3 User part 1 Introduction MIKROTHERM MT600-_D is a temperature/process controller with 1 input for measurement, 1 control / auxiliary input and 2 outputs. Buying a new controller, see the chapter Installation and configuration of controller If you have the device installed from the producer of device, see the chapter Final User Final User If you are a final user, you will get the device in the customised operation and you can view and change only the parameters that you need for your own work. There is a special part for you in manual User Part. If you are a new user of the device, focus on the following chapters: Basic terms this chapter explains the key functions, modes of controller, info and error messages.. In the whole manual you will be referred to the terms explained in this chapter. User level In this level you can scroll through mode of controller, configure and set selected parameters, etc Tips for operation and troubleshooting you will find in the chapter Tips. Installation and configuration of controller For installation and controller s configuration the configuration and service part of the manual is assigned. It is assumed that you know the basic operation of device described in the chapter Basic terms and you are authorised for the installation and you know how to set up the device. Information on the installation of the device you will find in chapter Installation Wiring is described in chapter Wiring Guidelines at first power-up are in chapter Putting into operation For further information on the operation see chapter Configuration level and Tips for configuration For service worker it is convenient to find out the options in the chapter Service level After the complete set up of device it is recommended to write down parameter values in table on page 35. There is a blank table for writing of programmes on the same page. 3

4 User part 2 Basic terms The controller can be used for the control of temperature or other quantity ( for simple description the temperature will be used further). To avoid problems in the operation of device the user must be able to manage its operation. 2.1 Operation and description of the controller Before you start, it is necessary to explain the principals for control. On the front panel board you can see 2 displays, 3 control lights and 4 keys. The device is set and configured via menu. The features of keys and displays is shown on the following picture: functions of indicators indicates actual process value in Basic MODE when set it shows parameter value upper display lower display indicates the state of control output indicates the state of alarm,/signal output indicates set point value in basic MODE. when set it shows type of parameter diodemode, indicate run of programme key function Short-term press: listing in menu confirming of set values Long-term press (3 seconds): entry to operation level upper display lower display Short-term press: return to Basic MODE Long-term press: starting, ending of decreasing of set value press 2keys together (for 3 seconds) to change levels from lower to higher ones ( configuration, service) increasing of set value The tables for menu and the descriptions of parameters are in the following chapters. 4

5 User part Setting parameters In the user part the setting of parameters is described in the table of this format: Confirm Display Procedure Return Confirm, indicates the key, with which you go through menu and confirm the parameters to be set Display, shows the data displayed on lower display Procedure, meaning of parameter and procedure how to set it Return, return to basic mode without editing/setting the parameter Important: You can view only the parameters which are necessary. Parameters are selected and adjusted with arrow keys If the parameter is not confirmed by the key stated in column Confirm, it is not set Returning to basic mode by the key Return, then the parameter is not set During automatic return to basic mode the parameter is not set. The controller returns to basic mode automatically if no key is pressed for 60 seconds and automatic return is allowed (in configuration level, menu SYS, parameter Aret = on). 2.2 Modes of controller Mode of controller is indicated by the diode MODE, see page 4. The 3 following modes will be often used in the description of the controller. Basic, diode MODE is not lit, the controller s output is turned OFF or the controller maintains the process value at the set point value. Running a programme, diode MODE is lit, the controller runs by a programme. Setting, the upper display appears the actual value, the lower display appears the type of parameter. 2.3 Information and error messages Information and error messages are indicated only in basic mode. Information messages, upper display ---- error of input sensor or the input is not set. Information messages, lower display Aut automatic setting/autotuning of PID parameters is running, see page 12. ProG indicates the running of a programme. 5

6 User part ramp ramp function is active. Man manual operation of the controlling. IdSP.idle set point value is active IdSP. Error messages, lower display Err0 error in EPROM. Switch the controller OFF and ON again. If the problem persists, contact your supplier. Err1 consequential error in EEPROM, The troubleshooting error can be made only by experienced user who knows the user setup of the controller and he is able to recover it after mending. Try to delete the data with function rst (service level, see page 25). Before putting the controller into operation it is necessary to configure and set the controller completely again. If the trouble persists, contact your supplier. Err2 error in EEPROM. The troubleshooting error can be made only by experienced user who knows the user setup of the controller and he is able to recover it after mending. Try to correct the data automatically with function Corr (service level see page 25). Before putting the controller into operation it is inevitable to check if all the parameters were put right. If the trouble persists, contact your supplier. Err3 error in A/D converter. It can be caused by electrical impulse at input, too low temperature and excessive humidity, etc. Switch the controller OFF and ON again. If the problem persists, contact your supplier. 6

7 User part 2.4 Overview of levels, menu Total overview of programme levels and menu is shown below. The entry to menu is indicated by the keys, long-term press is approximately 3 seconds. basic mode Short press User menu Short press return from operat., configuration and service level Double press Start and end of programme (if allowed) User level Long press Operation level Operation level Only for experienced user Long press Configuration level Long press Service level Configuration level Service level Using of single menus and levels: User menu enables the quickest access for user. The list of parameters in menu can be selected, see page 33. Start and end of a programme, it is possible to start as well as end up a simple programme. Operation level is accessible for user after the setting of all the necessary parameters. Most of menu in user level can be inhibited(denied) to user. Configuration level is intended for configuration of device. In this level you can set most of parameters of operation level. It is recommended to lock the menu after setting. Service level provides you with parameters for servicing. 7

8 User part 3 User level This level is intended for the prompt access to most common parameters. 3.1 User menu User menu provides the user with the simplest access for setting, configuring and viewing of the parameters. You can choose and set the list of parameters and their sequence that will be in user menu. The controller is in basic MODE or in running a programme, see page 5. The upper display indicates the process value, the lower display indicates the set point value. By pressing key you can scroll through user menu. Confirm Display Procedure Return Ein The status of auxiliary input. Important: tend o2of A-M IdSP Aut CAL1 (out1) (out2) Informative parameter that indicates the time remaining to the end of soak in format hour.minutes. Turn OFF permanent alarm / signalling by setting YES and confirm. To choose the type of operation: Auto, automatic operation, the controller adjusts the output power itself. Man, manual operation, the output power is adjusted by the user. Setting of idle set point value. Starting ( on), stopping ( off) of autotuning/automatic setting of PID parameters. Calibration of sensor. The set value is added to the process value. Range: -999 to 999 C. Shows the setup parameters of the control output (Pb1, It1, de1, Ct1, hys1). The description of the parameters is in operation level. Shows alarm / signal limits (o2lo, o2hi). The description of the parameters is in operation level. (ProG) Shows the parameters for editing a programme (rate, SP2, hold). The description of the parameters is in operation level. uout Shows the actual supplied power in %. The table shows the parameters that can be accessible in user menu. Each parameter in this menu can be permitted or not for the operator and the operator has only important parameters available. The sequence of parameters is optional and can be set. The inscriptions in column Display in brackets (out1, out2, ProG) are not displayed. There are the corresponding parameters, named in column Procedure (Pb1, It1, de1, ), displayed instead of the inscriptions in column Display. You will find the procedure how to create the user menu on page 33. 8

9 4 Operation level User part In this level you can configure and set the parameters which are available to the user. To enter the operation level from basic MODE press for 3 seconds key. EIn tend o2of Values of parameters are adjusted by keys. A-M IdSP Aut CAL1 out1 YES out2 YES Pb1 ProG YES rate o2lo o2hi It1 de1 SP2 Ct1 hold hys1 9

10 User part 4.1 Global parameters of operation level In the following table there are the parameters of operation level described that can not be allocated to single menu. The parameters are placed one after another. Confirm Display Procedure Return EIn Informative parameter indicating the state of auxiliary input (if fitted) tend o2of A-M IdSP Aut CAL1 Informative parameter that indicates the time remaining to the end of soak in format hour.minutes. Turn OFF permanent alarm / signalling by setting YES and confirm. To choose the type of operation: Auto, automatic operation, the controller adjusts the output power itself. Man, manual operation, the output power is adjusted by the user. Idle set point value that can be turned ON by digital input. Range: SP1L to SP1h Starting ( on), stopping ( off) of autotuning/automatic setting of PID parameters. Calibration of sensor. The set value is added to the process value. Range: -999 to 999 C. 4.2 out1, setting parameters of control output Menu is intended for manual setting of PID parameters or for improving parameters with regard to offset of the controlling. Confirm Display Procedure Return Pb1 It1 de1 Ct1 hys1 Proportional band. Range: 1 to 2499 C. Integral value. Range: off, 0.1 to 99.9 minutes. Derivative value. Range: off, 0.01 to 9.99 minutes. Time cycle. Range: 1 to 99 seconds for ot1 = ht, CL, 5 to 99 seconds for ot1 = ht2, CL2. Hysteresis, this parameter is set only for ON/OFF control. Range: 1 to 249 C. 10

11 User part 4.3 out2, alarm set points / signal set points Alarm / signal set points take action when the process temperature leaves a defined range or the deviation from set point value is higher, see page 29. Confirm Display Procedure Return o2lo o2hi Low alarm / signal set points. Range: -499 to o2hi C for ot2 = ALPr, SGPr to 0 C for ot2 = ALdE, SGdE. High alarm / signal set points. Range: o2lo to 2499 C for ot2 = ALPr, SGPr. 0 to 999 C for ot2 = ALdE, SGdE. 4.4 Prog, editing a programme The controller can be programmed to control the temperature via simple programme, type - rate and soak.. Confirm Display Procedure Return rate SP2 hold Ramp rate at set point value SP2 defined by a programme. Range: 1 to 99 C/hour. or C/min. Scale for ramp function can be set in configuration level, menu SYS, parameter rp S. Setting of the second set point value for a programme. Range: SP1L to SP1h. Time of soak (in format hours.minutes) at set point value SP2. Range: 0 to hours. 11

12 User part 5 Tips In this chapter the tips for operating and setting of the controller and the troubleshooting some problems are described for an operator. 5.1 Autotuning automatic setting of PID parameters The controller is fitted with the function that sets automatically PID parameters. Procedure of starting autotuning: The controller must switch the control output, it means the control output must not be turned OFF (in basic MODE there must not be on lower display off). You can start the automatic optimization with parameter Aut = on. You will find parameter in operation level, menu GlbL or you can set it accessible in user menu. The controller explores the characteristics of system from switching ON/OFF on the output and determines optimal PID parameters. It can cause an overshoot and large fluctuations. Important: Autotuning can not take effect in ON/OFF control, i.e. ot1 = ht2 or CL2. Autotune set point value for autotunig is set by the actual process value, by the actual set point value and by the parameter AtSP. It is calculated this way: Autotune set point value = actual process value + (actual set point value - actual process value) x AtSP / 100. Parameter AtSP is found in configuration level, menu SYS, see page Automatic and manual operation Automatic operation for controlling requires feedback (in other words the measurement of process value and control actions). The operator adjusts set point value and the controller operates the output power that is supplied to the system. At manual operation for controlling the operator adjusts the request output power. Setting of automatic or manual operation In operation level, select automatic or manual type of operation via parameter A-M. If A-M = Auto, automatic operation is set, if A-M = Man, manual operation is set. 12

13 Important: User part At manual operation the controller can not influence the output power that is only adjusted by the operator. The behaviour of system is then fully under operator` s control. At manual operation the writing Man blinks on lower display. The controller remains in the selected type of operation even after the voltage supply interruption. 5.3 Simple programme The controller enables the control in time by a simple programme rate and soak. set point value SP2 hold rate time Setup parameters of programme Parameter hold (hour.minute) determines the time period of soak at set point value SP2 ( C). Parameter rate determines the ramp rate to the set point value SP2. The scale of parameter rate can be selected in configuration level, menu SYS, parameter rps ( C/hour. or C/min.). Starting and ending a programme You can start or end a programme by double pressing. When in a programme the control diode MODE is lit, on lower display blinks ProG. Important: When editing a programme the actual parameters are only accessible ( parameter rate need not be displayed). The time remaining to the end of soak can be viewed with parameter tend. The supply voltage interruption does not break the programme. After the resumption of the supply voltage the controller resumes in a programme automatically. 13

14 Configuration and service part 6 Installation The controller is designed to be mounted to the panel cutout. Slide the controller into the cutout and fix it with 2 flanges, that are supplied with the controller. The installation requires the access to the back of the panel. Mounting dimmensions Width x height x overall length: 72 x 72 x 159 mm (including terminalboard). Behind panel length: 150 mm (including terminalboard). Cutout in the panel: 66 x 67 mm (width x height). The thickness of panel: max. 12 mm. Mounting Make the panel cutout. Slide the controller into the panel cutout. Insert the flanges from backward, slide the hooks into the holes for holding on both sides of the controller, with the heads of the screws in the direction from the panel. Tighten the screws firmly on the flanges. The controller is installed, then its wiring follows, see page

15 7 Wiring Configuration and service part To avoid potential electric shock, use safety practices laid down by national standards when wiring and connecting this unit to a power source. Failure to do so could result in such damage, and / or injury. The wiring must be done only by the authorised person. When you carry out the wiring it is necessary to fix the outer connecting wires in the manner so to avoid the reduction of insulation between the category supply voltage and safe voltage in case of loosening a wire from the terminal. It is inevitable to fix wires of supply voltage (terminal 1, 2), output 1 (terminal 3, 4), output 2 (terminal 5, 6), as close as possible to the terminals of the controller. Supply voltage Before you connect the unit to a supply power source, check the level of supply voltage. 230VAC 50Hz Po 200 ma

16 Configuration and service part Thermocouple and RTD input When you connect the thermocouple you need to use the compensating or thermocouple lead of the corresponding type. It is necessary to connect it with respect to polarity or 3-wire connection of RTD platinum sensor. 3 wire connection compensates perfectly the resistance of wires, if all 3 wires have the same electrical resistance Process input Voltage input, input impedance 10 kω Current input, input impedance 40 Ω U + - I + 16

17 Configuration and service part Connecting of auxiliary input Auxiliary input can be controlled by mechanical switch or DC voltage logic level 0 = 0-1VDC logic level 1 = 2,4-15VDC ENT- ENT+ Control output 1 Open collector / DC voltage output is intended to switch solid state relays SSR, it is not galvanic isolated. DC voltage output electromechanical relay - + max. 30 ma, voltage in open state appro. 10V. 230VAC/ 5A or 30VDC/5A output 2, alarm / signal 230VAC/ 5A or 30VDC/5A

18 Configuration and service part 8 Putting into operation The initial set-up can be done only by the qualified and authorised person. The wrong set-up can cause serious damage. When you power the controller up for the first time, you must enter the most necessary data to the controller for its problem-free operation: type of sensor, position of decimal point scale for measured/process values appearing on display for process inputs operational range of set point value set-up for the control output 8.1 Guidelines Let s suppose that the controller is installed in the panel and you have just power it up for the first time. Parameters of initial operation are the following: In1, set the input sensor. The description of this parameter see on page 20. dec1, set the decimal point. The description of this parameter see on page 20. rl1, rh1, parameters for setting of scale for process inputs. These are not displayed for thermal inputs. The description of these parameters see on page 20. SP1L, SP1h, the limits for set point range. The description of these parameters see on page 22. ot1, setting of the control output. The description of this parameter see on page 21. The further information regarding the input setting is found on page 26, regarding the output setting on page 27. Important: All the parameters that were set in the initial setting can be later changed in configuration level. Another options of the configuration are in the chapter Tips for configuration on page

19 Configuration and service part 9 Configuration level The configuration level is intended for basic setting of the controller. In this level the control output is turned OFF and alarm, signal and event output is deactivated. To enter the configuration level from operation level press for 3 seconds keys. To return from the configuration level press the key. PASS Set InP1 EIn out1 out2 StPt Setting of the input of the controller Setting of the auxiliary (control) digital input Setting of the control output Setting of alarm/signal output Setting of parameters for set point value In1 EI ot1 ot2 SP1L dec1 EISG PLd1 Lat2 SP1h rl1 SPL1 SIL2 SP1C rh1 PLu1 o2sd Ftr1 hys2 SYS oper KEYb LoC Setting of system parameters Setting of parameters for operation menu o2lo o2hi rate Setting of user menu Setting of locks AtSP SP1 SP2 KMod SP1 rp S IdSP hold StP1 oper ramp CAL1 StP2 SEt rdy Pb1 StP3 PASS ArEt It1 StP4 de1 Ct1 hys1 19

20 Configuration and service part The entry to configuration level can be locked by the password, see page 24. In this case the parameter PASS appears first ( the requirement of password). If you do not write the right password, the entry to configuration level is inhibited. 9.1 InP1, setting of input Display In1 dec1 rl1 rh1 Ftr1 Meaning Setting of input sensor. Thermocouple input: no input is not set J thermocouple J, range -200 to 900 C. K thermocouple K, range -200 to 1360 C. t thermocouple T, range -200 to 400 C. n thermocouple N, range -200 to 1300 C. E thermocouple E, range -200 to 700 C. r thermocouple R, range 0 to 1760 C. S thermocouple S, range 0 to 1760 C. b thermocouple B, range 300 to 1820 C. C thermocouple C, range 0 to 2320 C. d thermocouple D, range 0 to 2320 C. rtd sensor Pt100, range -200 to 800 C. Process input: no input is not set ma, range -499 to 2499 units ma, range -499 to 2499 units V, range -499 to 2499 units V, range -499 to 2499 units V, range -499 to 2499 units Setting of decimal point for the showing on display. Thermocouple and RTD input: 0 without decimal point 0.0 one decimal figure Process input: 0 without decimal point. 0.0 one decimal figure two decimal figures three decimal figures. Together with parameter rh1 defines the scale of the process ranges for the showing of values on display. Range: -499 to rh1. Together with parameter rl1 defines the scale of the process ranges for the showing of values on display. Range: rl1 to Set filter time constant for input signal. The more value is set, the more influence the filter has, see page 26. Range: off, 0.1 to 60.0 seconds. 20

21 Configuration and service part 9.2 EIn, auxiliary input Display EI EISG Meaning Options for auxiliary input. no it is not used. otof switching the control output OFF. LoC the locking of the keyboard on the front panel. IdSP switching over between primary (SP1) and idle secondary set point value (IdSP). ProG starting/ending a programme. Settings of logic for the assessment of the auxiliary digital input state. rise rising edge changes the state. FALL falling edge changes the state. hi input is turned ON with high level. Lo input is turned ON with low level. 9.3 out1, control output Display ot1 PLd1 SPL1 Plu1 Meaning Function of the control output: ht switches ON/OFF the heating, PID controlling CL switches ON/OFF the cooling, PID controlling ht2 switches ON/OFF the heating, 2-state (ON/OFF) controlling CL2 switches ON/OFF the cooling, 2-state (ON/OFF) controlling Output power limit when process value is below SPL1, set in %. Range: 0 to 100 %. Setting the power limit set point between low range and high range for the power limit. Range: -499 to 2499 C. Output power limit when process value is above SPL1, set in %. Range: 0 to 100 %. 9.4 out2, alarm / signal output Display ot2 Lat2 SIL2 Meaning Function of alarm / signal output: no output is not activated ALPr alarm defined by the absolute value ALdE alarm defined by the deviation from the set point value SGPr signalling defined by the absolute value SGdE signalling defined by the deviation from the set point Setting alarm / signal latching (a latched alarm remains active after the alarm condition passed): off temporary alarm / signalling on permanent(latched) alarm / signalling alarm / signal silencing after the switching ON of the controller: off the function is turned ON on the function is turned OFF 21

22 Configuration and service part o2sd hys2 The selection of active limits for alarm / signalling: LohI low and high limits are active hi high limit is only active Lo low limit is only active The hysteresis of switching for alarm / signal output. Range: 1 to 249 C. 9.5 StPt, features of set point value Display SP1L SP1h SP1C The limit of low range for set point value. Range: -499 to SP1h C. The limit of high range for set point value. Range: SP1L to 2499 C. Meaning The controlling of the set point value. SP the controller maintains the set point value PG1 the controller runs by the programme PG1 PG2 the controller runs by the programme PG2 PG3 the controller runs by the programme PG3 PG4 the controller runs by the programme PG4 The description of the programmes are on page SYS, system parameters Display AtSP rp S ramp rdy ArEt Meaning Setting of helping Auto-tune set point value for autotuning of PID parameters. This parameter is a percentage of the process value and normal set point value. Range: 0 to 100 %. The scale for setting of ramp rate: hour ramp rate in C /hour. Min ramp rate in C /minute. Ramp rate to set point value when the controller maintains the constant set point value. The scale of ramp function is set by the parameter rp S. Range: off, 1 to 99 C/hour ( C/minute). This parameter is used for the controlling via a programme. It adjusts the range where the counting of timer is allowed. Range: off, 1 to 99 C. How to allow the automatic return from open menu: off automatic return is not allowed. on automatic return from open menu after 1 minute of key inactivity. 22

23 Configuration and service part 9.7 oper, setting parameters in operation level The parameters of operation level are accessible in configuration level for easier setting of the controller (there is no need to switch over between operation and configuration level). Display SP1 IdSP CAL1 Pb1 It1 de1 Ct1 hys1 o2lo o2hi rate SP2 hold Set point value SP1. Meaning Parameters are described in the chapter Operation level. 9.8 KEYb, setting of user menu Display Kmod StP1 StP2 StP3 StP4 Meaning Function of key. ProG with this key in basic MODE you can start/end a programme. off the key is deactivated and it is not possible start/end a programme. The parameter that is placed on 1. position of user menu: no there is no parameter. EIn the state of auxiliary input. TEnd time remaining to the end of soak. o2of turning OFF permanent alarm / signalling. A-M automatic / manual operation. IdSP idle set point value. Aut autotuning automatic optimization PID parameters. CAL1 calibration of sensor. out1 setup parameters of the control output (Pb1, It1, ). out2 alarm / signal limits (o2lo, o2hi). ProG parameters for editing a programme (rate, SP2, hold). uout actual supplied power of the control output. Parameter that is placed on 2. position of user menu. The list is the same as in StP1. Parameter that is placed on 3. position of user menu. The list is the same as in StP1. Parameter that is placed on 4. position of user menu. The list is the same as in StP1. 23

24 Configuration and service part 9.9 LoC, lock Display SP1 oper Meaning The lock for set point value SP1. off the change of set point value is allowed on the change of set point value is not allowed. The lock for operation level: off operation level is accessible on operation level is not accessible. SEt PASS The lock for configuration level: off configuration level is accessible without the password. on configuration level is accessible with the password. The password for the entry to configuration level. Range: 0 to

25 Configuration and service part 10 Service level This level is intended for servicing. You can get to service level from configuration level by pressing keys To return from service level press the key. for 3 seconds. Display Meaning SoFt The number of software version. Amb Actual ambient temperature in C. 1u60 Measured voltage, input 1. Range 60mV. 1rtd Measured resistance, input 1. Range 350 Ω. Pr I Process current input. Range 20mA. Pr u Process voltage input. Range 10V. t Lo The lowest operational temperature of the controller in C. EI Measured voltage, digital input, range 10 V. t hi The highest operational temperature of the controller in C. Corr rst rst rst rst rst Function for automatic correction of the broken parameters. By setting Corr = YES the correction function is activated. Function for deleting of all the parameters and data and adjusting of the controller to factory(default) setting. By setting rst = YES this function is activated, because it is the essential action, this setting YES must be confirmed 5 times. 25

26 Configuration and service part 11 Tips for configuration In this chapter the tips for setting the device will be presented Measurement The right selection, the installation, the wiring, the location of sensor in the equipment and the corresponding setting of parameters of the controller have the essential importance for the correct function. Configuration parameters of input for measurement are in configuration level, menu InP1. Setting of input sensor Set the corresponding input sensor in parameter In1. You will find the survey of input sensors in the chapter Technical parameters, see page 36. You can set the position of decimal point by parameter dec1. You can set the displaying without decimal point or with 1 decimal figure for thermal sensors, and for process sensors you can set without decimal point, with 1 decimal figure or with 2 decimal figures. You can set the limit for set point value in configuration level, menu StPt, parameters SP1L and SP1h, see page 22. Important: Thermocouple and RTD inputs have the detection of improperly wired sensor. When the sensor is open or broken, the control output will turn OFF, the alarm output is activated, the signal output is deactivated.. Process inputs do not have the detection of improperly wired sensor. Input filter If the process value is distorted by interference, you can use the digital filter. The more the filter coefficient is Ftr1, the more the filter smooths the input signal. When Ftr1 = off the filter is turned OFF. process value without filter with filter time 26 time

27 Configuration and service part Measurement range of process inputs In configuration level, menu InP1, with the parameters rl1, rh1 and dec1 you can set the limits for the measurement range of the process inputs. Example of setting of process input: You want to display the input signal 4 to 20 ma in the range 6.0 to Set dec1 = 0.0, rl1 = 6.0 a rh1 = The distribution between values 6.0 and 24.0 will be linear. Displayed process value ma 20 ma input signal 11.2 Control, the control output You can select in the controller ON/OFF (2 state) or PID controlling for heating or cooling. If PID controlling is set, you can use the autotuning function for finding optimal PID parameters, see page 12 and the power limit function, see page 29. Parameters for configuration of the control output are in configuration level, menu out1. ON/OFF control ON/OFF control is selected by setting ot1 = ht2 (heating control) or CL2 (cooling control). It is used for less exacting application. It is not possible to achieve zero hysteresis value on principle. The process value rises and drops about set point value in the characteristic way. Process value Set point value hysteresis The state of the control output ON time OFF time 27

28 Configuration and service part PID control PID control is selected by setting ot1 = ht (heating) or CL (cooling). It provides the precise control. For the correct function of the controller, however, it is necessary to set properly PID parameters. Autotuning for setting of PID parameters is described on page 12. PID parameters have the following meaning: Pb proportional band, is set in measured units. It is the band about the set point value in which the controller keeps the temperature. It integral factor, in minutes. Integral factor compensates the loss of system. A low integral value causes a fast integrating action. de derivative factor, in minutes. Derivative responses to fast changes and tries to react against them. The more value is, the more derivative factor reacts. If the control output is 2 state (ON/OFF) (relay or SSR), the power is (given in %) transferred to the output with so called pulse width modulation. In each time cycle (parameter Ct1, that is in operation level, menu out1) the control output is switched ON once and once OFF. The more the power is necessary, the wider the width of switching is. The output responses are illustrated in the third part of the drawing. Process value setpoint value Output power 100 % time the state of the control output ON time Time cycle OFF þdv Example of pulse width modulation of the output: Time cycle is 10 seconds, the power requested is 30%. The output is ON for 3 seconds and OFF for 7 seconds. Time cycle is 10 seconds, the power requested is 5%. The output is ON for 0,5 second and OFF for 9,5 seconds. 28

29 Important: Configuration and service part The duration of time cycle has the influence on the quality of control. The longer the cycle is, the less the quality of control is. If the electromechanical unit (relay, switching contactor) is used for the control output, the duration of time cycle must be set longer with regard to lifetime of switch. Power limit function You can improve the quality of control by limiting of the output power. Process value Power limit high PLu1 SPL1 Power limit low PLd1 time Example how to use the power limit function: When rising at set point value the big overshoot occurs. One of possible solution is the power limit in the vicinity of set point value. The procedure is the following: Find out the power supplied to the stable system. Set SPL1 on the value by several o C less than set point value. Set power limit PLd1 to 100%. Set power limit Plu1 approx. by 10 to 20% higher than the power supplied to the stable system Alarm, signalling The second output (output 2) can be used for alarm or signalling. The parameters for the output configuration are in configuration level, menu out2, you will find setting of alarm / signal limits o2lo and o2hi in operation level, menu out2. Setting of alarm / signal output Set the function with parameter ot2 : ot2 = no, the output is not used. ot2 = ALPr, alarm defined by absolute value. ot2 = ALdE, alarm defined by the deviation from set point value. ot2 = SGPr, signalling defined by absolute value. ot2 = SGdE, signalling defined by the deviation from set point value. 29

30 Important: Configuration and service part Relay in standby MODE means active alarm, deactivated signalling. When controller is switched OFF, error of sensor, error of controller the alarm is active. When controller is OFF, sensor error, error of controller the signalling is deactivated. Alarm / signalling, absolute value: process value Active Deactivated o2hi Active o2lo time Alarm / signalling, the deviation from set point value: o2hi process value Active Set point value Deactivated o2lo Active time Temporary, permanent (latched) alarm / signalling Alarm / signalling can be temporary (LAt2 = off) or permanent (LAt2 = on). Temporary alarm / signalling will turn automatically off when the alarm / signal condition is over. Turn OFF permanent(latched) alarm / signalling when the alarm / signal condition is over by the function o2of that is found in operation level. This function can be set also in user menu. Permanent alarm / signalling is also turned off after the supply voltage interruption. Silencing of alarm / signalling Silencing of alarm / signalling can be used to disable alarm / signalling at the startup rising to the set point value. This state should not be evaluated as error because the system is not yet stable. This function is set with parameter SIL2: SIL2 = off, function is not active SIL2 = on, alarm / signalling can be activated after the process value at the startup rising reached the allowed range for the first time (between alarm limits). 30

31 Configuration and service part process value Active When startup alarm/signalling is deactivated Deactivated Active time Active sides of alarm / signalling With parameters o2sd you can choose the active side of alarm / signalling: o2sd = LohI, both sides(limits) are active. o2sd = hi, only high alarm / signal side(limit) is active. o2sd = Lo, only low alarm / signal side(limit) is active Digital input Digital input of model MT600- _D-_-0 0 serves for the operator (or superior - MASTER system, for example programmable automatic) to control the chosen function of the controller via external switch or DC voltage. Setting Digital input is initiated with parameter EI in configuration level, menu EIn. These functions are available: no digital input is not used otof turning the control output OFF LoC locking of the keyboard on the front panel IdSP switching over between actual and idle set point value ProG starting/ending a programme You can set the logic assessment for input signal with parameter EISG. Lo input is turned ON with low level hi input is turned ON with high level rise rise edge changes the state FALL fall edge changes the state input signal high level 31

32 Configuration and service part 11.5 Programme The controller can be programmed in time by a simple programme. This function is selected in configuration level, menu StPt, parameter SP1C: SP1C = SP, the controller maintains the process at set point value, however, it is possible to use the ramp function. SP1C = PG1, PG2, PG3, PG4, one of the following programmes is used: set point value SP2 SP1C= PG1 hold set point value SP2 SP1C= PG2 hold rate SP1 SP1 time time set point value SP2 SP1C= PG3 hold set point value SP2 SP1C= PG4 hold rate output is OFF output is OFF time time Guaranteed time of soak You can ensure the guaranteed time of soak by parameter rdy. This parameter defines the permitted deviation from the set point SP2. When the process value reaches the range of the permitted deviation the time of soak is triggered. Parameter rdy is found in configuration level, menu SYS. SP2 Range rdy Set point value Process value Time of soak is triggerred time 32

33 Configuration and service part 11.6 Setting of user menu User menu, see page 8, provides a user with the simplest access for viewing and setting parameters. The list of parameters that will be present in user menu, and their sequence are optionally set. You can create user menu in configuration level, menu KEYb, see page 23. Example how to create user menu: You want to place on the first (1.) position of user menu parameter Aut, on 2. position PID parameters (Pb1, It1, ) out1. Proceed as follows: Set parameter StP1 = Aut. Set parameter Stp2 = out1. 3 and 4 positions are used, for the parameters StP3 and StP4 set no. You will look over the result in user menu How to lock menu and parameters If your controller is configured and set you can lock: The setting of set point value SP1. The access to operation level.. The access to configuration level and protect it with password. You will find the parameters for locking in configuration level, menu LoC, see page 24. Important: You can simplify the setting of the controller for user by locking single items. By locking single items you will prevent a user from inappropriate actions to setting of the controller Ramp function Ramp function will ensure the reaching of the set point value SP1 by linearization rising. In this manner you can protect the system or material that must not be exposed to large changes of temperature. You can set the ramp function with parameter ramp that is found in configuration level, menu SYS. Set the scale for the ramp function with parameter rp S. SP1 Set point value linearized rising time 33

34 Important: Configuration and service part The ramp function is possible to use only for maintaining the process value at the set point value (SP1C = SP). The ramp function is activated only after the powering the controller up at start rising before the set point value is reached for the first time. When the ramp function is active, on lower display the writing ramp blinks. 34

35 Configuration and service part 12 Table of parameters Write down your own complete setting of the controller to the table below.. InP1 EIn out1 out2 StPt In1 EI ot1 ot2 SP1L dec1 EISG PLd1 Lat2 SP1h rl1 SPL1 SIL2 SP1C rh1 PLu1 o2sd Ftr1 hys2 SYS oper KEYb LoC AtSP SP1 rate KMod SP1 rp S IdSP SP2 StP1 oper ramp CAL1 hold StP2 SEt rdy Pb1 StP3 PASS ArEt It1 StP4 de1 Ct1 hys1 o2lo o2hi 35

36 Technical parameters 13 Technical parameters The controller is intended for use in industrial or laboratory equipment, the category of pollution / overvoltage II (maximum 2kV). Control PID, PI, PD, P control, autotuning/automatic setting of PID parameters 2-step (ON/OFF) control the control of heating or cooling Alarm / signalling absolute or relative defined by the set point value temporary or permanent alarm / signalling silencing of alarm / signalling at startup of the controller selection of limits high/low, low, high Controlling(regulation) to set point value programmed control of the type - rate and soak control to the constant set point value Indicators and keys 2 10mm LED displays for displaying 4 figures 3 LED diodes ( output 1, output 2, MODE of the controller) 4 keys, setting is done via menu Sensors, inputs Thermocouple input is isolated or non-isolated, the detection of bad-wired/broken sensor. Resistance input Pt100 platinum (RTD - resistance temperature detector), 2-or 3- wire, DIN curves, the detection of bad-wired/broken sensor: no it is not set J thermocouple J, range -200 to 900 C K thermocouple K, range -200 to 1360 C t thermocouple T, range -200 to 400 C n thermocouple N, range -200 to 1300 C E thermocouple E, range -200 to 700 C r thermocouple R, range 0 to 1760 C S thermocouple S, range 0 to 1760 C b thermocouple B, range 300 to 1820 C C thermocouple C, range 0 to 2320 C d thermocouple D, range 0 to 2320 C 36

37 Technical parameters rtd sensor Pt100, range -200 to 800 C Process input, input impedance 40 Ω for current inputs, 10 kω for voltage inputs, without the detection of bad-wired/broken sensor : no none ma, range -499 to 2499 units ma, range -499 to 2499 units V, range -499 to 2499 units V, range -499 to 2499 units V, range -499 to 2499 units Control (auxiliary) input Digital Voltage, logic levels 0-1 VDC/2,4-15 VDC, input impedance 10 kω or electromechanical contact, levels 0-2 kω/>23 kω; switching ON by the logic level or rising/falling edge. Outputs Open collector/dc driver, 10VDC for switching ON, max. 30 ma electromechanical relay, 230VAC/5A or 30VDC/5A, only switching ON, without RC suppression unit Accuracy of inputs thermocouple input, calibration accuracy ±0,1% of range (min. 540 C), ±1 digit, temperature stability ±0,1 C/ C of ambient temperature RTD Pt100 input, calibration accuracy ±0,1% of range (min. 540 C), ±1 digit, temperature stability ±0,05 C/ C of ambient temperature process input, DC voltage ranges ±10 mv, ±1 digit, DC current ranges ±20 ua, ±1 digit, temperature stability ±100 ppm/ C of ambient temperature voltage stability ±0,01%/% of change in supply voltage Supply voltage 230 VAC +10%/-15%, 50/60 Hz, internal slow fuse 2 A/250 V input power max. 6 VA data stored in memory upon power failure Operating environment 0 to 50 ºC 0 to 90 % relative humidity, non-condensing 37

38 Technical parameters Shipping and storage -20 to 70 ºC Dimensions width x height x length, 72 x 72 x 158 mm depth behind panel surface 149 mm cutout into the panel 66 x 68 mm (width x height) 13.1 Warranty The supplier provides 36-month warranty on defects in material and workmanship on this controller with the exception on defects caused by mechanical or electrical wearing out of the outputs. This warranty does not also apply to damage resulting from inappropriate transportation and storage, misuse, wrong wiring, ambient influences (especially effects of electrical overvoltage, electrical values and temperatures of inadmissible intensity, chemical materials, mechanical damage) electrical or mechanical overloading of inputs and outputs. Certification electrical safety: EN , clause 5.1, 5.1.4, 6, 6.7, 6.8.2, 6.8.4, 6.10, 6.11, 8.2, 9, 10. electromagnetic compatibility: EN , EN 55011, EN , EN , EN , EN , EN , EN , EN Description of model MT600 - a b c d 0 0 a: input for measurement T = thermal (thermocouple and RTD) P = process (current, voltage) b: control (auxiliary) input D = digital S = resistance sensor of position A = communication line EIA 485 X = communication line RS 232 c: output 1 K = Open collector/ssr driver R = electromechanical relay d: output 2 R = electromechanical relay e f: customary model 0 0 = factory model 38

39 14 Index 1 Introduction Basic terms Operation and description of the controller Modes of controller Information and error messages Overview of levels, menu User level User menu Operation level Global parameters of operation level out1, setting parameters of control output out2, alarm set points / signal set points Prog, editing a programme Tips Autotuning automatic setting of PID parameters Automatic and manual operation Simple programme Installation Wiring Putting into operation Guidelines Configuration level InP1, setting of input EIn, auxiliary input out1, control output out2, alarm / signal output StPt, features of set point value SYS, system parameters oper, setting parameters in operation level KEYb, setting of user menu LoC, lock Service level Tips for configuration Measurement Control, the control output Alarm, signalling Digital input Programme Setting of user menu How to lock menu and parameters Ramp function Table of parameters Technical parameters Warranty Description of model Index

Users manual. Ht40A. User - friendly programmable controller. HTH8 s.r.o. Ht40A, 08/03, soft 4.03/rev. 2

Users manual. Ht40A. User - friendly programmable controller. HTH8 s.r.o. Ht40A, 08/03, soft 4.03/rev. 2 Users manual Ht40A User - friendly programmable controller Ht40A, 08/0, soft 4.0/rev. 2 HTH8 s.r.o. Eimova 880, 572 0 Polička Czech Republic tel.: +420 46 69 55 fax: +420 46 69 5 e-mail: info@hth8.cz www.hth8.cz

More information

MT825-A, controller user s manual

MT825-A, controller user s manual MIKROTHERM 825 MT825A 11/09 Rev.7/Soft.4.3 MT825-A, controller user s manual THERMOPROZESS s.r.o. Riegrova 2668/6c 370 01 České Budějovice Czech Republic Tel.: +420 387 313 182 Fax: +420 385 340 947 E-Mail:

More information

PROCESS & TEMPERATURE CONTROLLERS

PROCESS & TEMPERATURE CONTROLLERS PROCESS & TEMPERATURE CONTROLLERS NOVA PD54 Series Thermocouple, RTD, & Process Inputs High Accuracy Auto-Tuning PID Heating & Cooling Models Universal Power Supply 1-24 VAC Up to 3 Relays & 2 Analog Outputs

More information

UNICONT. PMG-400 Universal controller and display unit USER'S AND PROGRAMMING MANUAL 1. pmg4111a0600p_01 1 / 24. ST edition

UNICONT. PMG-400 Universal controller and display unit USER'S AND PROGRAMMING MANUAL 1. pmg4111a0600p_01 1 / 24. ST edition UNICONT PMG-400 Universal controller and display unit USER'S AND PROGRAMMING MANUAL 1 ST edition pmg4111a0600p_01 1 / 24 TABLE OF CONTENTS 1. GENERAL DESCRIPTION... 3 2. ORDER CODE... 3 3. TECHNICAL DATA...

More information

APPENDIX APPENDIX A 1

APPENDIX APPENDIX A 1 A 1 SPECIFICATIONS Ratings Supply voltage 100 to 240 VAC, 50/60 Hz 24 VAC, 50/60 Hz/24 VDC Operating voltage range 85 to 110% of rated supply voltage Power consumption 7VA 4VA/2.5W Sensor input Thermocouple

More information

Instruction Notes for 108A L Sensor Input

Instruction Notes for 108A L Sensor Input Operation Manual Instruction Notes for 108A L14-1800 Digital Control Module ON/OFF Main Power Switch Alarm Limits/ Cycle Switch Load Outlet (x2) General Description Sensor Input This temperature control

More information

Series 942 User's Manual

Series 942 User's Manual Series 942 User's Manual TOTAL CUSTOMER SATISFACTION 1/4 DIN Microprocessor-Based Ramping Control Watlow Controls 1241 Bundy Blvd., P.O. Box 5580, Winona, MN 55987-5580, Phone: 507/454-5300, Fax: 507/452-4507

More information

Fuzzy Temperature Controllers E5AF

Fuzzy Temperature Controllers E5AF Fuzzy Temperature Controllers 1/4 DIN Controller Combines Fuzzy and PID Control For Fast Response to Process Disturbances Advanced PID control provides optimal response during start-up and steadystate

More information

PID500 FULL FEATURED PID TEMPERATURE CONTROLLERS

PID500 FULL FEATURED PID TEMPERATURE CONTROLLERS PID500 FULL FEATURED PID TEMPERATURE CONTROLLERS DESCRIPTION FEATURES * Compact Size: 1/16 DIN * Dual LED displays for simultaneous indication of process temperature and set point (Lower display selectable

More information

High Performance Process & Temperature Controllers

High Performance Process & Temperature Controllers C22 C62 C82 C83 High Performance Process & Temperature Controllers C72 C42 R22 01. Multi Color LCD Display 02. High Accuracy 18 Bit A-D Input and 15 Bit D-A Output 03. 200 msec Sampling Rate 04. True Universal

More information

8003 1/8 DIN Temperature Controller

8003 1/8 DIN Temperature Controller 8003 1/8 DIN Temperature Controller Issue Date April 1994 USER S MANUAL 0037-75212 Contents Model Identification... Page ii Dimensions and Panel Cutout...1 Wiring...2 Hardware Setup...3 Configuration Mode...4

More information

OVEN INDUSTRIES, INC. Model 5C7-362

OVEN INDUSTRIES, INC. Model 5C7-362 OVEN INDUSTRIES, INC. OPERATING MANUAL Model 5C7-362 THERMOELECTRIC MODULE TEMPERATURE CONTROLLER TABLE OF CONTENTS Features... 1 Description... 2 Block Diagram... 3 RS232 Communications Connections...

More information

Excellent low-cost Process & Temperature Controllers

Excellent low-cost Process & Temperature Controllers C22 C62 C82 C83 Excellent low-cost Process & Temperature Controllers C72 C42 R22 01. High Quality LCD Display 02. High Accuracy 18 Bit A-D Input and 15 Bit D-A Output 03. The Fast Sampling Rate in 200

More information

Analogue temperature controllers

Analogue temperature controllers Analogue temperature controllers CT8A Input by J-K thermo-couple or by thermo-resistance Pt 00 (-wire) regulation modes : ON/OFF or proportional derivative selected by wiring Relay output Specifications

More information

Introduction To Temperature Controllers

Introduction To Temperature Controllers Introduction To Temperature Controllers The Miniature CN77000 is a full featured microprocessor-based controller in a 1/16 DIN package. How Can I Control My Process Temperature Accurately and Reliably?

More information

INSTRUCTION MANUAL FOR PROGRAMMABLE CONTROLLER PCD-33A

INSTRUCTION MANUAL FOR PROGRAMMABLE CONTROLLER PCD-33A INSTRUCTION MANUAL FOR PROGRAMMABLE CONTROLLER PCD-33A Preface Thank you for purchasing our Programmable Controller PCD-33A. This manual contains instructions for the mounting, functions, operations and

More information

INSTRUCTIONS FOR INSTALLATION AND USE. LTR15

INSTRUCTIONS FOR INSTALLATION AND USE. LTR15 LTR15 Thank you for having chosen a LAE electronic product. Before installing the instrument, please read these instructions carefully to ensure maximum performance and safety. 1. INSTALLATION 1.1. LTR15

More information

Series Valve Temperature Controller. Instruction Sheet

Series Valve Temperature Controller. Instruction Sheet 2013/10/03 Series Valve Temperature Controller Instruction Sheet Thank you very much for choosing Delta DTV series valve temperature controller. Please read this instruction sheet before using your DTV

More information

7SD/7SH/7SM Temperature Controllers

7SD/7SH/7SM Temperature Controllers 7SD/7SH/7SM Temperature ADVANTAGE EZ Series 7SD, 7SH, 7SM 1/16 DIN Temperature 3Digit LED Display Thermocouple and RTD Input Autotuning NEMA 4X Field onfigurable 100 to 40 Vac Switching Power Supply Programmable

More information

Series 982 User s Manual

Series 982 User s Manual Series 982 User s Manual Includes 981, 982, 983 and 984 1/8 DIN Microprocessor-Based, Ramping Controller User Levels: New User...go to page 1.1 Experienced User...go to page 2.1 Expert User...go to page

More information

- SMART TUNE- PID CONTROL - UNIVERSAL, 3 WIRE- TC, RTD AND LINEAR INPUT - AUX- REMOTE SET POINT/ TRIM INPUT - 2x ISOLATED CONTROL AND RETRANSMISSION

- SMART TUNE- PID CONTROL - UNIVERSAL, 3 WIRE- TC, RTD AND LINEAR INPUT - AUX- REMOTE SET POINT/ TRIM INPUT - 2x ISOLATED CONTROL AND RETRANSMISSION ADVANCED - CONTROLLERS - SMART TUNE- PID CONTROL - UNIVERSAL, 3 WIRE- TC, RTD AND INPUT - AUX- REMOTE SET POINT/ TRIM INPUT - 2x ISOLATED CONTROL AND RETRANSMISSION (ma) OUTPUTS - 4x EVENT OR ALARM OUTPUTS

More information

Instructions for Tempco Control Enclosure PCM10001 through PCM10004

Instructions for Tempco Control Enclosure PCM10001 through PCM10004 Visionary Solutions for Industry Since 1972 ISO 9001 Certified Temperature Controllers & Sensors Heating Elements Process Heating Systems Instructions for Tempco Control Enclosure PCM10001 through PCM10004

More information

DC1010/DC1020/DC1030/DC1040

DC1010/DC1020/DC1030/DC1040 05/0 0-10-10-0-EN Page 1 of DC1010/DC1020/DC100/DC1040 DIGITAL CONTROLLERS Specification Overview The DC1000 Series are microprocessorbased controllers designed with a high degree of functionality and

More information

SYL-2352P Ramp and Soak PID Temperature Controller Version 1.2 (May 2016)

SYL-2352P Ramp and Soak PID Temperature Controller Version 1.2 (May 2016) AUBER INSTRUMENTS Instruction Manual WWW.AUBERINS.COM SYLP Ramp and Soak PID Temperature Controller Version 1. (May 16) Caution This controller is intended to control equipment under normal operating conditions.

More information

+GF+ SIGNET Temperature Transmitter Instructions

+GF+ SIGNET Temperature Transmitter Instructions GF SIGNET 80- Temperature Transmitter Instructions ENGLISH -80.090- B-/00 English CAUTION! Remove power to unit before wiring input and output connections. Follow instructions carefully to avoid personal

More information

Micro-controller X Model: PXE4. Operation Manual. INP-TN5A1887a-E

Micro-controller X Model: PXE4. Operation Manual. INP-TN5A1887a-E Micro-controller X Model: PXE4 Operation Manual INP-TN5A1887a-E 2 BEFORE USE Thank you very much for purchasing Fuji s digital controller. (1) Be sure to read this manual and grasp the concept before operating

More information

ENGLISH. General features 2. Technical features 3. Installation 10. Preliminary operations 12. Front panel description 13.

ENGLISH. General features 2. Technical features 3. Installation 10. Preliminary operations 12. Front panel description 13. LDI 35 OPERATING INSTRUCTIONS General features 2 Technical features 3 Installation 10 Preliminary operations 12 Front panel description 13 Operating mode 15 Important: We suggest you keep the original

More information

PROGRAMMABLE CONTROLLER

PROGRAMMABLE CONTROLLER SERIES FP21 High Accuracy ±0.1% Programmable 9 Patterns and 9 Steps (81 Steps Max.) Auto-Tuning PID RA / DA Selectable User-Selectable Inputs (Thermocouple) User-Selectable Ranges Programmable Scaling

More information

SHIMADEN PROGRAMMABLE CONTROLLER

SHIMADEN PROGRAMMABLE CONTROLLER SHIMADEN PROGRAMMABLE CONTROLLER Shimaden, Temperature and Humidity Control Specialists SERIES FP21 High Accuracy ±0.1% Programmable 9 Patterns and 9 Steps (81 Steps Max.) Auto-Tuning PID RA / DA Selectable

More information

Configuration Example of Temperature Control

Configuration Example of Temperature Control Controllers Technical Information Configuration Example of Control controllers The following is an example of the configuration of temperature control. Controller Relay Voltage Current SSR Cycle controller

More information

C C1 C2 AL1 AL2 AL3. Micro-controller X. Model: PXR SEL PXR-4. Operation Manual. ECNO:406a

C C1 C2 AL1 AL2 AL3. Micro-controller X. Model: PXR SEL PXR-4. Operation Manual. ECNO:406a C C1 C2 AL1 AL2 AL3 Micro-controller X Model: PXR PXR-4 SEL Operation Manual ECNO:406a Table of Contents 1 Part Names and Functions... 4 2 Operations... 5 2-1 Parameter list... 5 2-2 Basic operations...

More information

8000 SERIES PRECISION MULTIMETER VERIFICATION AND ADJUSTMENT GUIDE

8000 SERIES PRECISION MULTIMETER VERIFICATION AND ADJUSTMENT GUIDE 8000 SERIES PRECISION MULTIMETER VERIFICATION AND ADJUSTMENT GUIDE TRANSMILLE LTD. Version 1.1 : Apr 2015 TABLE OF CONTENTS PREPARING FOR CALIBRATION... 4 INTRODUCTION... 4 CALIBRATION INTERVAL SELECTION...

More information

General Specifications

General Specifications General Specifications Model UT, UT Temperature Controller GS CE-E GENERAL UT series temperature controllers provide only the functions and size you require for your application. /6 DIN sizes is available.

More information

Temperature Controllers E5 J

Temperature Controllers E5 J Temperature Controllers Advanced PID Controller with Fuzzy Logic-Based Adaptive Tuning Provides Optimum Performance Available in 3 standard DIN sizes: Choose 1/4, 1/8 and 1/16 DIN Fuzzy adaptive tuning

More information

DIGITAL PROGRAM CONTROLLER

DIGITAL PROGRAM CONTROLLER KP1000 SERIES DIGITAL PROGRAM CONTROLLER The KP1000 series is a 96x96mm digital program controller with the indicating accuracy of ±0.1%, the control cycle of approximately 0.1 seconds and maximum 19 program

More information

Microprocessor-based Temperature Controller

Microprocessor-based Temperature Controller R 1100 The Temperature Controller Heat-only Controller Heating-off-Cooling Controller DIN-Format: 96 x 96 mm Installation depth: 67 mm Microprocessor-based Temperature Controller Description And Operating

More information

MICRO-CONTROLLER X (48 48 mm)

MICRO-CONTROLLER X (48 48 mm) PX series digital temperature controller MICRO-CONTROLLER X ( mm) DATA SHEET PXG PXG is a compact size temperature controller of front panel size mm. To cope with any of versatile uses as a temperature

More information

Description of functions Controller system VR660 / A200R

Description of functions Controller system VR660 / A200R Description of functions Controller system VR660 / A00R Local bus RS VR660/A00R e 56 76-0.07 Camille Bauer AG Aargauerstrasse 7 CH-560 Wohlen/Switzerland Phone + 56 68 Fax + 56 68 5 5 e-mail: info@camillebauer.com

More information

Digital Controller Intelligent, User-friendly Digital Controller and Programmer Controlled with ease with a support software which is input via the communication jack on the front panel. Minute adjustment

More information

CT325 Miniature DC Temperature Controller

CT325 Miniature DC Temperature Controller CT325 Miniature DC Temperature Controller Overview The CT325 Miniature DC Temperature Controller is designed for use with Minco Thermofoil heaters and RTD or thermistor sensors. It offers inexpensive on/off

More information

GL101B Intelligent Temperature Controller User s Guide

GL101B Intelligent Temperature Controller User s Guide GL101B Intelligent Temperature Controller User s Guide 1 Caution Abnormal operating conditions can lead to one or more undesirable events that, in turn, could lead to injury to personnel or damage to the

More information

Models UT550/UT520 Digital Indicating Controllers User s Manual for Loop Control for Backup

Models UT550/UT520 Digital Indicating Controllers User s Manual for Loop Control for Backup Instruction Manual Models UT550/UT520 Digital Indicating Controllers User s Manual for Loop Control for Backup IM 05D01C02-45E IM 05D01C02-45E 1st Edition Blank Page Introduction Thank you

More information

SHIMADEN PROGRAM CONTROLLER

SHIMADEN PROGRAM CONTROLLER Shimaden, Temperature and Humidity Control Specialists C %RH SHIMADEN PROGRAM CONTROLLER approved BASIC FEATURES Full multi-input and multi-range performance User selectable Thermocouple, RTD, V, mv and

More information

DIGEM f 96 x 48 EK. Applications. Description

DIGEM f 96 x 48 EK. Applications. Description 3-349-002-03 1/7.98 Front panel dimensions: 96 x 48 mm LED display: red or green, 14 mm high Max. display range: 19 999 to + 32 765 Modular connectors for flexible use Simple adjustments at front panel

More information

Signet Flow Transmitter

Signet Flow Transmitter Signet 80- Flow *-80.090-* English -80.090- Rev. L 0/ English WARNING! Remove power to unit before wiring input and output connections. Follow instructions carefully to avoid personal injury. Contents.

More information

SR25. SHIMADEN DIGITAL CONTROLLER Shimaden, Temperature and Humidity Control Specialists MICROPROCESSOR-BASED AUOT-TUNING PID CONTROLLER

SR25. SHIMADEN DIGITAL CONTROLLER Shimaden, Temperature and Humidity Control Specialists MICROPROCESSOR-BASED AUOT-TUNING PID CONTROLLER SHIMADEN DIGITAL CONTROLLER Shimaden, Temperature and Humidity Control Specialists SERIES SR25 MICROPROCESSOR-BASED AUOT-TUNING PID CONTROLLER High Accuracy ±0.1% High Sampling Cycle 0.1 sec. Auto-Tuning

More information

K3P ENG.qxd 23/10/ Pagina 1

K3P ENG.qxd 23/10/ Pagina 1 K3P ENG.qxd 23/10/2003 12.30 Pagina 1 - CLEAR PROGRAM STATUS DISPLAY - DIRECT PROGRAM PARAMETER ADJUSTMENT - 8 INDEPENDENT PROGRAMS - 10 SEGMENTS FOR EACH PROGRAM - "SET - POINT TRACKING " AND "GUARANTEED

More information

R24 DISPLAY MODULE WITH ACTIVE OUTPUT AND RELAY

R24 DISPLAY MODULE WITH ACTIVE OUTPUT AND RELAY Čapkova 22 678 01 Blansko tel.: +420 516 416942, 419995 fax: +420 516 416963 R24 DISPLAY MODULE WITH ACTIVE OUTPUT AND RELAY Display module is designed for measuring the resistance, the signal from the

More information

DIGITAL INDICATING CONTROLLER

DIGITAL INDICATING CONTROLLER DB00 SERIES DIGITAL INDICATING CONTROLLER The DB00 series is a digital indicating controller with the indicating accuracy of ±0.% and the control cycle of approximately 0. seconds. Various functions including

More information

MPS SERIES. INSTALLATION and TECHNICAL MANUAL MPS 4 MPS 5 MPS 9 4 PV

MPS SERIES. INSTALLATION and TECHNICAL MANUAL MPS 4 MPS 5 MPS 9 4 PV MPS SERIES INSTALLATION and TECHNICAL MANUAL PV AT M AL1 AL2 SP1 4 PV AT SV SV M SP1 SP2 AL1 AL2 AL3 P SP2 P MPS 4 MPS 5 PV M AL1 SV AT SP1 AL2 SP2 AL3 P MPS 9 ITALMEC ELETTRONICA P.O. Box 34 40069 ZOLA

More information

RUN HLD MAN PRG. Features

RUN HLD MAN PRG. Features DCP3 Digital Controller Programmer 57-77-3-15 5/ Page 1 of 16 Specification Function The DCP3 is a high-function digital controller programmer supporting up to 19 program profiles with up to 3 segments

More information

General Purpose Digital Controllers Specifications

General Purpose Digital Controllers Specifications General Purpose Digital Controllers Specifications DC1010 - DC1020 - DC1030 - DC1040 51-52-03-33 August 2003 Overview The DC1000 family of microprocessor based controllers combines a high degree of functionality

More information

RI-F200 Series. Single and Three Phase Multifunction Energy Meter. Telephone : +44 (0) Displayed Parameters

RI-F200 Series. Single and Three Phase Multifunction Energy Meter. Telephone : +44 (0) Displayed Parameters RI-F200 Series Single and Three Phase Multifunction Energy Meter DIN 96 panel mounted -/1A or -/5A current transformer input Single phase or three phase network compatible Programmable voltage and current

More information

GL102 Intelligent Temperature Controller User s Guide

GL102 Intelligent Temperature Controller User s Guide GL102 Intelligent Temperature Controller User s Guide 1 Caution Abnormal operating conditions can lead to one or more undesirable events that, in turn, could lead to injury to personnel or damage to the

More information

Computer-14d - xx - 144a

Computer-14d - xx - 144a POWER FACTOR REGULATOR Computer-14d - xx - 144a INSTRUCTION MANUAL ( M 981 602 / 98B ) (c) CIRCUTOR S.A. -------- POWER FACTOR REGULATOR COMPUTER- 14d --------- Page 2 1.- POWER FACTOR REGULATORS COMPUTER-14d-144a

More information

Micro-controller X SV C1 C2 AL1 AL2 SEL. Model: PXR3. Operation Manual TN5A2704-E

Micro-controller X SV C1 C2 AL1 AL2 SEL. Model: PXR3. Operation Manual TN5A2704-E C1 C2 AL1 AL2 SEL Micro-controller X Model: PXR3 Operation Manual TN5A2704-E Table of Contents 1 Part Names and Functions... 5 2 Operations... 6 2-1 Parameter list... 6 2-2 Basic operations... 11 2-3 Parameter

More information

EIO /2009. Zelio Control. Temperature Controller User guide 04/2009 EIO

EIO /2009. Zelio Control. Temperature Controller User guide 04/2009 EIO EIO0000000232 04/2009 Zelio Control Temperature Controller User guide 04/2009 EIO0000000232.00 www.schneider-electric.com Schneider Electric assumes no responsibility for any errors that may appear in

More information

CX105 Conductivity/Resistivity Transmitter

CX105 Conductivity/Resistivity Transmitter CX105 Conductivity/Resistivity Transmitter User Manual REV A.15 Sensorex Corporation, USA 11751 Markon Drive Garden Grove, CA. 92841 U.S.A. www.sensorex.com IMPORTANT SAFETY INFORMATION Please read and

More information

SYL-2362A2 PID TEMPERATURE CONTROLLER

SYL-2362A2 PID TEMPERATURE CONTROLLER SYL-2362A2 PID TEMPEATUE CONTOLLE INSTUCTION MANUAL Version 2.4 Caution This controller is intended to control equipment under normal operating conditions. If failure or malfunction of it could lead to

More information

Model Number Structure

Model Number Structure Current Sensor CSM DS_E Solid-state, Plug-in Current Sensor Applicable to motor overcurrent protection and 3-phase AC current detection. Inverse-type, start-up lock type, and instantaneous type overcurrent

More information

Single Loop Controller SDC35/36

Single Loop Controller SDC35/36 No. CP SS 180E Single Loop Controller SDC35/36 Features The DigitroniK SDC35/36 is a digital indicating controller featuring multi-range inputs and PID control system using new algorithms "RationaLOOP"

More information

Ordering Information. Stepping Relay Unit G9B. Model Number Legend

Ordering Information. Stepping Relay Unit G9B. Model Number Legend Stepping Relay Unit CSM DS_E_4_1 Ideal for Controlling Pumps and Production Lines with Six or Twelve Stepping Circuits Built-in relays switch 2 A at 250 VAC or 30 VDC. Initialization of stepping with reset

More information

General Specifications

General Specifications General Specifications MODEL UT50L Limit Controller GS 5DD-0E Overview The UT50L is an FM approved limit controller that can be configured either as a high limit or as a low limit controller by a user.

More information

Temperature Controller

Temperature Controller Temperature Controller 1/8 IN - 48 x 96mm Platinum Series X400 Line Cost Effective Solutions This 48x96mm size controller of the Platinum Series, provides a high degree of functionality and reliability

More information

SHIMADEN DIGITAL INDICATORS

SHIMADEN DIGITAL INDICATORS Shimaden, Temperature and Humidity Control Specialists C %RH Series SD16 & SHIMADEN DIGITAL INDICATORS & NRTL /C approved BASIC FEATURES DIN Size 48 x 96 mm ±.3% High Accuracy Indication Large 2 mm bright

More information

SHIMADEN DIGITAL INDICATORS

SHIMADEN DIGITAL INDICATORS Shimaden, Temperature and Humidity Control Specialists C %RH Series SD16A & SHIMADEN DIGITAL INDICATORS approved,ul applied BASIC FEATURES compliance DIN Size 48 x 96 mm ±.3% High Accuracy Indication Large

More information

Process displays For standard signals, temperature, resistance measurement

Process displays For standard signals, temperature, resistance measurement Features Inputs: Voltage ±10 V, ±200 V / Current ±20 ma / thermocouples J,K,T,N,Pt100,Pt1000 / resistance measurement / potentiometer Display range can be linearised Two limits output Min, Max functions

More information

Digital Multifunction Instrument - Rish Master 3440

Digital Multifunction Instrument - Rish Master 3440 Application Rish Master 3440 measures important electrical parameters in 3 phase and single phase etwork & replaces the multiple analog panel meters. It measures electrical parameters like AC current,

More information

Models UT550/UT520 Digital Indicating Controllers User s Manual for Single-loop Control

Models UT550/UT520 Digital Indicating Controllers User s Manual for Single-loop Control User s Manual Models UT550/UT520 Digital Indicating Controllers User s Manual for Single-loop Control IM 05D01C02-41E IM 05D01C02-41E 3rd Edition Blank Page Introduction i Thank you for purchasing

More information

N2000S UNIVERSAL PROCESS CONTROLLER FOR SERVO POSITIONING OPERATING MANUAL. (Manual Key): toggles the AUTO/MANUAL mode.

N2000S UNIVERSAL PROCESS CONTROLLER FOR SERVO POSITIONING OPERATING MANUAL. (Manual Key): toggles the AUTO/MANUAL mode. N000S UNIVERSAL PROCESS CONTROLLER FOR SERVO POSITIONING OPERATING MANUAL Status Display/: shows the present value of the process variable (). When accessing the programmable parameters it indicates the

More information

Bulletin E-90-OCN Series CN7200, CN7600, CN7800, CN7500 Microprocessor Based Temperature Process Control

Bulletin E-90-OCN Series CN7200, CN7600, CN7800, CN7500 Microprocessor Based Temperature Process Control Bulletin E-90-OCN Series CN7200, CN7600, CN7800, CN7500 Microprocessor Based Temperature Process Control Specifications - Installation and Operating Instructions OMEGA ENGINEERING, INC. 1-888 - TC - OMEGA

More information

Analog outputs (option) Output 1 + 2: 0(4) 20 ma or 0 10 V

Analog outputs (option) Output 1 + 2: 0(4) 20 ma or 0 10 V Page / JUMO AQUIS 500 CR Transmitter/Controller for conductivity, TDS, resistivity and temperature Compliant with USP Brief description The instrument is used for the conductive measurement/control

More information

Fuzzy Temperature Controllers E5EF

Fuzzy Temperature Controllers E5EF Fuzzy Temperature lers EEF / DIN lers Combine Fuzzy and PID For Fast Response to Process Disturbances dvanced PID control for optimal response during startup and steadystate operation Fuzzy and PID control

More information

Digital Temperature Controller

Digital Temperature Controller www.hynux.com Digital Temperature Controller Economical price Convenient functions High speed sampling High accuracy temperature controlling AX2 AX3 AX4 AX7 AX9 Actualized the highly accurate temperature

More information

DC1010/DC1020/DC1030/DC1040/Compact type DIGITAL CONTROLLERS Specification

DC1010/DC1020/DC1030/DC1040/Compact type DIGITAL CONTROLLERS Specification 01 May 20 30-10-10--EN Page 1 of DC1010/DC1020/DC1030/DC1040/Compact type DIGITAL CONTROLLERS Specification Overview The DC1000 Series are microprocessorbased controllers designed with a high degree of

More information

LabCon User Manual. Multi-Purpose Temperature Controller Temp High SP

LabCon User Manual. Multi-Purpose Temperature Controller Temp High SP LabCon Basic Multi-Purpose Temperature Controller 42.5 Temp High SP C 42.5 CONTENTS 1. FRONT PANEL LAYOUT 1 2. BASIC OPERATION 2 3. OPERATOR PARAMETERS 5 4. SUPERVISORY PARAMETERS 7 5. FACTORY PARAMETER

More information

PROGRAM CONTROLLER OUTLINE

PROGRAM CONTROLLER OUTLINE Specifications Sheet No.SPEC-1232E (1st Edition) EC1200A PROGRAM CONTROLLER OUTLINE The EC1200 can, totally and with high precision, control and monitor such factors as temperature, temperature balance

More information

Table of Contents Panel Mount Controllers Analog Series C-Series Controller Software Legacy Series Power Controllers Analog Series P-Series

Table of Contents Panel Mount Controllers Analog Series C-Series Controller Software Legacy Series Power Controllers Analog Series P-Series Table of Contents Panel Mount Controllers C-Series C-Series 32C...4-5 C-Series 16C...6-7 C-Series 18C and 19C...8-9 C-Series 25C...10-11 C-Series OTC25...12-13 C-Series OTC25 Limit... 14 Legacy Series

More information

Infinite Thermal Solutions Inc.

Infinite Thermal Solutions Inc. Page 1 ITSMT Series Temperature Controllers MT 48 VM Operating Manual Auto Tuning, Digital Electronic, DIN Sized Temperature Controllers US Easy Control Fuzzy + PID Run/Stop Operated on the Panel Multi-Input

More information

Model Number Structure

Model Number Structure Single-phase Voltage Relay CSM DS_E_3_1 Ideal for voltage monitoring for industrial facilities and equipment. Monitor for overvoltages or undervoltages. Manual resetting and automatically resetting supported

More information

This Errata Sheet contains corrections or changes made after the publication of this manual.

This Errata Sheet contains corrections or changes made after the publication of this manual. Errata Sheet This Errata Sheet contains corrections or changes made after the publication of this manual. Product Family: DL4 Date: September 12, 218 Manual Number D4-ANLG-M Revision and Date th Ed., Rev.

More information

SHIMADEN DIGITAL INDICATOR

SHIMADEN DIGITAL INDICATOR Shimaden, Temperature and Humidity Control Specialists C %RH Series SD24 & KR16A SHIMADEN DIGITAL INDICATOR BASIC FEATURES ohigh Accuracy ±0.1% FS+1 digit o1/1000ºc Resolution Indication Possible (Pt input

More information

SUNDIAL Light Dimmer. User's Manual

SUNDIAL Light Dimmer. User's Manual Light Dimmer User's Manual 1. PRECAUTIONS Although fuses at the input and outputs of the controller protect its circuits in case of an overload or overvoltage, we recommend installing an additional protection

More information

Models UT350/UT320 Digital Indicating Controllers

Models UT350/UT320 Digital Indicating Controllers User s Manual Models UT350/UT320 Digital Indicating Controllers User s Manual IM 05D01D02-41E IM 05D01D02-41E 4th Edition Blank Page Introduction i Thank you for purchasing the UT350/UT320

More information

- SMART TUNE - PID CONTROL - UNIVERSAL, 3 WIRE - TC, RTD AND LINEAR INPUT - 2 INDEPENDENT SET POINT RAMP UP/ DOWN PROFILES - SERVO VALVE POSITIONER

- SMART TUNE - PID CONTROL - UNIVERSAL, 3 WIRE - TC, RTD AND LINEAR INPUT - 2 INDEPENDENT SET POINT RAMP UP/ DOWN PROFILES - SERVO VALVE POSITIONER MULTI - FUNTION ONTROLLERS - SMART TUNE - PID ONTROL - UNIVERSAL, 3 WIRE - T, RTD AND LINEAR INPUT - 2 INDEPENDENT SET POINT RAMP UP/ DOWN PROFILES - SERVO VALVE POSITIONER WITH POTENTIOMETER FEEDBAK -

More information

High-precision process calibrator Model CED7000

High-precision process calibrator Model CED7000 Calibration technology High-precision process calibrator Model CED7000 WIKA data sheet CT 85.51 Applications Research and development laboratories Calibration service companies and service industry Industry

More information

AI-700 / 500 INTELLIGENT INDICATING/ALARMING INSTRUMENT. Operation Instruction

AI-700 / 500 INTELLIGENT INDICATING/ALARMING INSTRUMENT. Operation Instruction AI-700 / 500 INTELLIGENT INDICATING/ALARMING INSTRUMENT Operation Instruction CONTENTS Page MAIN FEATURES... 2 ORDERING CODE.3 TECHNICAL SPECIFICATION.5 FRONT PANEL AND OPERATION..7 PARAMETER AND SETTING...

More information

ARTIFICIAL INTELLIGENCE TEMPERATURE CONTROLLER AI-208. User Manual

ARTIFICIAL INTELLIGENCE TEMPERATURE CONTROLLER AI-208. User Manual ARTIFICIAL INTELLIGENCE TEMPERATURE CONTROLLER AI-208 User Manual I. Model Code Symbol 1. Basal function of instrument AI-208G: SSR voltage output (5VDC/30mA), no alarm output. AI-208GL1: SSR voltage output(5vdc/30ma)

More information

! "! # $ % & ' ( ) " * % +, # # -. / ( ! " ! # $ % &

! ! # $ % & ' ( )  * % +, # # -. / ( !  ! # $ % & Manual HT55 2. General 2.1 Unpacking and inspecting The product must be inspected for possible shipping damage when it is unpacked. If damage is found then the freight carrier, railway company or postal

More information

TEMPERATURE CONTROLLER 48 x 48 mm RE70 TYPE USER S MANUAL

TEMPERATURE CONTROLLER 48 x 48 mm RE70 TYPE USER S MANUAL TEMPERATURE CONTROLLER 48 x 48 mm RE70 TYPE USER S MANUAL 1 RE70-09 User's Manual 2 Contents: 1. Application... 3 2. Controller set... 3 3. Basic requirements, operational safety... 3 4. Installation...

More information

AI-501 INTELLIGENT INDICATING/ALARMING INSTRUMENT. Operation Instruction

AI-501 INTELLIGENT INDICATING/ALARMING INSTRUMENT. Operation Instruction AI-501 INTELLIGENT INDICATING/ALARMING INSTRUMENT Operation Instruction CONTENTS Page MAIN FEATURES... 2 ORDERING CODE.3 TECHNICAL SPECIFICATION.5 FRONT PANEL AND OPERATION..6 PARAMETER AND SETTING...

More information

TC LV-Series Temperature Controllers V1.01

TC LV-Series Temperature Controllers V1.01 TC LV-Series Temperature Controllers V1.01 Electron Dynamics Ltd, Kingsbury House, Kingsbury Road, Bevois Valley, Southampton, SO14 OJT Tel: +44 (0) 2380 480 800 Fax: +44 (0) 2380 480 801 e-mail support@electrondynamics.co.uk

More information

Contents. English User Manual Regulators

Contents. English User Manual Regulators Contents Safety warnings Page 28 Technical specifications Page 28 Description of instrument Page 31 Electrical connections Page 31 Glossary Page 32 Operation Page 37 Setting the regulation parameters Page

More information

General Specifications

General Specifications General Specifications GS 05F01D01E MODEL UM351 Digital Indicator with Alarms with Active Color PV Display General Model UM351 Digital Indicator with Alarms is a precision alarm instrument provided with

More information

Series F4P Communications Guide

Series F4P Communications Guide Series F4P Communications Guide 1/4 DIN Temperature/Process Controller with Guided Setup 98 Registered Company Winona, Minnesota USA Watlow Controls 1241 Bundy Blvd., P.O. Box 5580, Winona, Minnesota USA

More information

MICRO-CONTROLLER X (96 96 mm)

MICRO-CONTROLLER X (96 96 mm) PX series digital temperature controller MICRO-CONTROLLER X ( mm) DATA SHEET PXG PXG is a compact size temperature controller of front panel size mm. To cope with any of versatile uses as a temperature

More information

DC Voltage Hawk II H235 Series Advanced Digital Panel Meter

DC Voltage Hawk II H235 Series Advanced Digital Panel Meter % DC Voltage Hawk II H35 Series Advanced Digital Panel Meter Easily Programmed from the Front Panel User-Friendly Software Functions Include: Password Display Scaling Decimal Point Selection Set Point

More information

PIECAL 311 Automated Universal RTD Calibrator Operating Instructions. Product Description

PIECAL 311 Automated Universal RTD Calibrator Operating Instructions. Product Description Product Description Easy to use With the PIECAL 311 you can check & calibrate all your RTD instruments and measure RTD Sensors. Automatic indication of connections on the display for simple hookups. Take

More information

I/A Series Model 718TC 1/8 DIN Temperature Controller with ma Output

I/A Series Model 718TC 1/8 DIN Temperature Controller with ma Output Instruction MI 018-573 February 1997 I/A Series Model 718TC 1/8 DIN Temperature Controller with ma Output Foxboro and I/A Series are trademarks of The Foxboro Company. Siebe is a registered trademark of

More information

Please enter the identity code of your device here!

Please enter the identity code of your device here! Operating Instructions DULCOMETER D1C Part 2: Adjustment and Operation, Measured Variable Conductive Conductivity ProMinent D1C2-Leit.-001-GB Conductivity 100 µs/cm DULCOMETER STOP START Conductivity 100

More information