BAS 918S/929S. Manual. BA Systems Petershvilevej 1 DK-3200 Helsinge
|
|
- Jordan Poole
- 5 years ago
- Views:
Transcription
1 BAS 918S/929S BA Systems Petershvilevej 1 DK-3200 Helsinge
2 Table of content Introduction... 3 Materials included... 4 Product mount... 5 Installation... 6 Terminals description... 9 Functional description Option Module connection Modbus BACnet BAS918S configuration BAS929S configuration Scheme list Scheme introduction Scheme 1, Central heating Scheme 2, Central heating and Hot water tank Scheme 3, Central heating with Heat Exchanger Scheme 4, Central heating with Heat Exchanger and Hot water tank Scheme 5, Dual Central heating Scheme 6, Dual Central heating with Heat Exchanger Basic Controller operation Menu structure Scheme selection Scheme activation Regulation mode Scheme setup Info Screen Watch Screen Setup for IP access BA Systems Petershvilevej 1 DK-3200 Helsinge 2
3 Introduction: Thank you for choosing a BAS 918S/929S controller. Please make sure that you have received the correct controller version and all the materials included. The difference between the two controllers are only the supported I/O. Please look at the following illustrations. The controller is scheme-based. This means that a set of preinstalled control schemes may be selected. Each scheme is shown as a process diagram named Scheme. The installation to be used is the selected. Once a scheme has been selected it can be customized. Please see the description of the different schemes later in this manual. On the next pages in this manual you will be guided through the physical installation and maneuvering the single button user interface. Technical data Power supply 24VAC/DC or 240VAC Power < 6W Thermal Storage -20 C to +70 C Operational -10 C to +60 C Humidity Mechanical Real time clock User interface Max. 90% RH, on condensing ABS/PC, IP x x 53 mm 570 g ±12 minutter pr year at 20 C. The RTC can run more than 1 year without power applied. Can be adjusted over the IP (ethernet) connection, either directly or through the SCADA system. 3.5 inch colorscreen and two-way scroll wheel with pushbuttom select. Digital outputs Analog outputs Analog inputs Communication Digital inputs Solid state relay BAS918S: 6 channals BAS929S: 11 channels Max 1A ved 240VAC/DC, must be protected against inductive loads. BAS918S: 2 channals BAS929S: 4 channals Port 1..4: 0/2-10VDC Port 3,4:, 0/4..20mA BAS918S: 8 channals BAS929S: 10 channals Port 1..10: ohm () Port 1,3,5,7,9,10: 0/2-10V Port 9,10:0/4-20 ma DC Port 9,10: ohm (TC) 10/100 Mbit ethernet USB-Host or USB-Device Optional internal module: KX, O, MBUS, WMBUS eller RS485 4 x potential free contacts or max 12VDC. BA Systems Petershvilevej 1 DK-3200 Helsinge 3
4 Materials included: 1. Produkt socket 2. Produkt front 3. 4 pcs. of, 3.9mm x 32 mm screws for wall mount 4. Cable relief bracket for cable retention at socket 5. 2 pcs. of 3.0mm x 8 mm screws for cable relief bracket mounting (4) BA Systems Petershvilevej 1 DK-3200 Helsinge 4
5 Product mount: The socket (1) may be wall mounted using 4 screws (3). Cable insertion may be done form behind into the socket or from the connector end of the front. See illustration below. screw (3) screw (3) Cut out area when cables inserted from behind Cut out area when cables inserted from this end screw (3) screw (3) Cable relief bracket Use a sharp knife to cut the plastic along or within the lines of the markings. When cutout is made in the connector end of the front, cables are inserted here and may be retained in the socket using the cable releif bracket. BA Systems Petershvilevej 1 DK-3200 Helsinge 5
6 Installation: Generic socket connections are defined in placement and function in the following drawings and descriptions. This indicates the maximum I/O configuration for the BAS9XXS controller. Please note that the variant you have bought may have reduced configuration. BA Systems Petershvilevej 1 DK-3200 Helsinge 6
7 Controller profile: BA Systems Petershvilevej 1 DK-3200 Helsinge 7
8 Controller front: Dimensions for wall mount are indicated from above drawing. BA Systems Petershvilevej 1 DK-3200 Helsinge 8
9 Terminal descriptions: Terminal label 240VAC 24VAC/DC DOX (1-11) DIX (1-4) DICOM STPB Definition 2 terminals = ul = phase (ine) 100V-240V AC, 50Hz or 60Hz 2 terminals = ul / DC- = fase / DC+ 24VAC, 50Hz - 60Hz or 24VDC, minimum 10W 2 terminals per I/O channels, Electronic relay. o polarization required. Potential free contact inputs with one common terminal (DICOM) to be used in relation with each DIX terminal. 4 terminals for Stepper motor connection, maximum 4W drive capability. Up to 24V drive. otes Power supply. May be substituted by 24VAC or 24VDC When connected, 240VAC is disconnected in the controller internally. May supply 24VDC/4W when 240VAC is sourcing power. AC or DC maximum 1A maximum 1A 3750V Rms isolation DICOM is a 5V DC voltage, sourcing maximum 50mA out. Protected against voltage inputs up to +75V peak. AC voltage protection only by resistive fuse. 24VAC/DC power supply for extended drive capability. Max 20W pr channal. STPA Secondary Stepper motor connection. As above. 2 terminals combined with AO current output capability. ot coexisting, i.e. controller mounted with either AO current output or second stepper motor capability OPX (1-3) 3 terminals for communication module support Module to be mounted from factory and must be ordered when the controller is ordered. Modules available: MBUS RS485 KX O WMBUS AOX (1-4) AIX (1-10) 2 terminaler for each analog output channel. Must be polarized as indicated by + and signs. Output type 0/2-10V with max 10mA load 0/4 20mA current loop, channel 3 and 4 only, combined with Stepper motor output A. 2 terminals for each I/O channel. Must be polarized as indicated by + and signs. Capability per I/O number: Channel 1..10: ohm () Channel 1,3,5,7,9,10: 0/2-10V Channel 9,10:0/4-20 ma DC Channel 9,10: ohm (TC) When using current mode the terminal is still to be used at the primary terminal block. Protected against reverse polarity and input voltages up to 40V Protected against reverse polarity and input voltages up to 40V. BA Systems Petershvilevej 1 DK-3200 Helsinge 9
10 Functional description: Power supply The Controller is supplied by the terminals 240VAC, accepting 90VAC-264VAC, 50Hz - 60Hz. or By the terminals 24VAC/DC, accepting 24VAC/50Hz/10% and alternatively 24VDC/25%. If both power inputs are connected, the internal circuit will select the 24V source. The 240V source is then disconnected internally.when 240VAC supply is used, the 24V pin set will output 24V DC. Maximum power output is 4W. In the center of the controller socket, 2 set of 10 pole terminal blocks are placed. By default all terminals in each block has been shorted by a mounted shorting circuit (alternative circuits can be ordered). The intension with this is to assemble ul (-) and Phase (+) connections internally distributing connections from here. Only one supply line into the controller is then required. Alternative use will also apply. Digital outputs All ports are galvanic isolated from other channels as well as from the internal controlling circuit. The circuit for one output (2 signal wires) is an Electronic relay, which may connect AC or DC signals. This relay will apply a voltage drop of approximately 1V in closed state. When operating a digital signal, this 1V drop may corrupt the signal level interpretation. In this case a secondary relay must be inserted. Please see visualization below. Circulation Pump BAS9XXS COTROER 0-10V RU 0 "DO" REAY COECTED HAS 1V DROP OVER THE TERMIAS DOXB DOXA. DO2B DO2A D01B D01A Circulation Pump BAS9XXS COTROER 0-10V RU VAC/DC DOXB DOXA. DO2B DO2A D01B D01A SECODARY REAY 0V BA Systems Petershvilevej 1 DK-3200 Helsinge 10
11 Digital inputs Intended for use as potential free contacts. A change in contact state can be measured, as well as pulses from repeated state change, can be counted (from metering devices). Maximum puls counting frequency is 25Hz. All inputs are galvanic connected, but isolated from the internal controlling circuit. Typical connection seen below. Connect to DICOM POTETIA FREE COTACT Connect to DI(X) If more potential free contacts are to be mounted, one wire from each must be connected to the DICOM terminal. BAS9XXS COTROER Connect to DICOM DICOM POTETIA FREE COTACT 1 POTETIA FREE COTACT 2 POTETIA FREE COTACT 3 POTETIA FREE COTACT 4 Connect to DI4 Connect to DI3 Connect to DI2 Connect to DI1 DI4 DI3 DI2 DI1 Analog inputs Please note the different configuration capabilities for each individual channel. More information is seen on page 9. All channels are galvanic interconnected as well as connected to the internal controlling circuit. An advantage of this is that there is only one common reference. 5 WIRE CABE As shown above, a 5 wire cable is sufficient for connection to 4 pcs of thermal sensors. Please note though, that sensor calibration is recommended because of increased voltage drop over the common reference. BA Systems Petershvilevej 1 DK-3200 Helsinge 11
12 Analog input continued ote: It is not recommended to use a reference shared for sensor signals as well as for Pumps, Valves or Motor loads. Also, current loop analog input signals must have a dedicated reference connection. Analog inputs configured for voltage measurements may have common reference. When connecting 4 x, 2 x 0/4mA-20mA, 2 x 0/2V-10V minimum 12 wires will be required. 12 WIRE CABE 4-20mA 4-20mA 0-10V 0-10V If one cable is used for analog signals mixed with supply wires for pumps, valves or motors, it may be necessary to use twisted pair cables to suppress noise. In this case each analog input must have a specific reference wire twisted with the + analog input wire. Example, connecting Pressure Transmitter: 24V SUPPY - + BAS9XXS COTROER PRESSURE TRASMITTER TERMIAS 24VAC/DC 0V 0-10V 4-20mA SUPPY COECTED AT THE OAD, TO AVOID DISTURBIG THE AAOG MEASUREMET AI(X)- AI(X)+ BA Systems Petershvilevej 1 DK-3200 Helsinge 12
13 Analog outputs BAS918S includes 2 channels, and BAS929S 4 channels. See table page 9. All channels are galvanic interconnected as well as connected to the internal controlling circuit. Channal 3 and 4 has voltage output on one set of terminals (AO{X}) and current loop on another set (AO{X}_I). See page 15. The signal reference for 3 and 4 for voltage as well as current loop terminals are located on AO3- and AO4-. For inspiration see the following example. Example, Motor Valve connection: 24V SUPPY BAS9XXS COTROER + - MOTOR VAVE 24VAC/DC 0V COTRO 0-10V POSITIO 0-10V AO(X)- AO(X)+ AI(X)+ REFERECE VOTAGE FOR AAOG IPUTS AD AAOG OUTPUTS ARE COECTED I THE COTROER, SO OE REFERECE WIRE IS SUFFICIET Stepmotor output ports Is not available on the current versions of the BAS9XXS controllers. Please contact the supplier for more information. BA Systems Petershvilevej 1 DK-3200 Helsinge 13
14 Option modules The controller may have an internal module mounted, enalbing different communication interfaces over the OP terminals or communicating wireless with an antenna mounted. Currently the following modules are available 1. RS MBUS 3. Wireless MBUS (OMS) 4. O 5. KX Cabled interfaces are all, except module 3, using OP1-3 terminals, see below. Only authorized personel may do module mounting, So when requesting this option, the controller must be ordered with this included, from the supplier. Connection: For cabled bus interfaces, below modules may be mounted. MBUS RS485 KX O As described previously, the terminals OP1-3 are used for connection. Below wiring table defines how to connect. Terminal label MBUS RS485 KX O OP1 BUS PUS A (PUS) BUS + ET A OP2 - GD KEY (Short to - BUS- for configuration mode) OP3-24V (BUS MIUS) B (MIUS) BUS - ET B Bus interfaces with differential signaling (all except MBUS) must use twisted pair cabling. One pair for a bus interface, RS485, KX or O. BA Systems Petershvilevej 1 DK-3200 Helsinge 14
15 MODBUS Available parameters are shown for each controlling scheme. The controller may be configured for Modbus/RTU via TCP/IP, or if a RS485 module is mounted, Modbus/RTU via RS485. Communication parameters are 19200,n,8,1. Bus ID and Bus impedance termination may be set in the controller information menu. For each scheme, a specific modbus parameter list is defined, The information is to be interpreted according to below: Holding Register Fcn 3/6 x10 Fcn 3/6 x1 Input Register Fcn 4 x10 Fcn 4 x1 The register to be addressed, read or write Modbus Holding register read/write. The value must be divided by 10 to get the physical value. I.e. 136 correlates to Remember to multiply by 10 if a value is to be written into the controller register. As above without any scaling The register to be read from Modbus Input register read. The value must be divided by 10 to get the physical value. I.e. 97 correlates to 9.7 As above without any scaling BACnet Available parameters are shown for each controlling scheme. The controller is always using BACnet port BAC0/47808 and is given the name BAS9XXS Device. The controller ID can be configured by the menu system, operated through the scroll button. The ID is by default set to 1. BA Systems Petershvilevej 1 DK-3200 Helsinge 15
16 BAS 918S configuration: BA Systems Petershvilevej 1 DK-3200 Helsinge 16
17 BAS 929S configuration: BA Systems Petershvilevej 1 DK-3200 Helsinge 17
18 Scheme list: For every controlling scheme loaded into the controller, the following sections will define a process diagram, cabling according to this and a description of Modbus parameters available. The list below defines available schemes: 1. Central heating 2. Central heating and Hot water tank 3. Central heating with Heat Exchanger 4. Central heating with Heat Exchanger and Hot water tank 5. Dual Central heating 6. Dual Central heating with Heat Exchanger BA Systems Petershvilevej 1 DK-3200 Helsinge 18
19 Scheme introduction: Outdoor sensor Is a global parameter, defined as When connected to one controller, the value will be available for all controllers in the network (same IP segment). ocal sensor fault, will be compensated by using a sensor available in the network. If no local sensor fault, the local sensor value will be used. Sensor fault will only be displayed if neither local nor global sensor are detected. Only one outdoor sensor is required for an installation. Scaling For metering applications, a conversion factor must be defined. This is called scaling. So when a controlling scheme is selected, a scaling factor may be requested before it can be actvated. Important: Scaling setup for the controller and the metering unit must be identical. Water metering Water metering in the following control scemes is optional. Scheme selection therefore includes of water metering on or off selection. Symbol description Symbol Description Flow meter Modulation control valve Outdoor sensor Gate valve Pump Temperature sensor Hot water tank with sensor Heat exchanger Pressure transmitter BA Systems Petershvilevej 1 DK-3200 Helsinge 19
20 Scheme 1, process diagram: Central heating (CH) DI1 AI1 DO1 AI2 AO1 AI3 BAS918S or BAS929S BA Systems Petershvilevej 1 DK-3200 Helsinge 20
21 Terminals for PHASE connection Terminals for U connection E DICOM AO4_I AO3_I OP3 BAS 918S/929S Scheme 1, wiring diagram: 240VAC installation Circulation pump Power supply Water meter DI4 DI3 DI2 DI1 DO11B DO11A DO10B DO10A DO9B DO9A DO8B DO8A DO7B DO7A DO6B DO6A DO5B DO5A DO4B DO4A DO3B DO3A DO2B DO2A DO1B DO1A 24VAC/ 24VAC/ 240VAC/ 240VAC/ 240VAC/ 24VAC/ 24VDC+ 240VAC/ 24VAC/ 24VDC- OP1 OP2 AO4+ AO4 AO3+ AO3 AO2+ AO2 AO1+ AO1 AI10+ AI10 AI9+ AI9 AI8+ AI8 AI7+ AI7 AI6+ AI6 AI5+ AI5 AI4+ AI4 AI3+ AI3 AI2+ AI2 AI1+ AI1 Motor valve Return Forward Out door 240VAC ote: label indicates PHASE connection, i.e. all wires with must be connected label indicates U connection, i.e. all wires with must be connected Motor valves will often have a common terminal for U and Analog reference (-). If so AO and U must be connected. Water metering scaling to be defined when selecting controlling scheme. Above wiring assumes that the components Circulation pump and Motor valve is to be supplied by 240VAC. BA Systems Petershvilevej 1 DK-3200 Helsinge 21
22 Terminals for PHASE connection Terminals for U connection E DICOM AO4_I AO3_I OP3 BAS 918S/929S Scheme 1, wiring diagram: 24VAC or 24VDC installation Circulation pump Power supply Water meter DI4 DI3 DI2 DI1 DO11B DO11A DO10B DO10A DO9B DO9A DO8B DO8A DO7B DO7A DO6B DO6A DO5B DO5A DO4B DO4A DO3B DO3A DO2B DO2A DO1B DO1A 24VAC/ 24VAC/ 240VAC/ 240VAC/ 240VAC/ 24VAC/ 24VDC+ 240VAC/ 24VAC/ 24VDC- OP1 OP2 AO4+ AO4 AO3+ AO3 AO2+ AO2 AO1+ AO1 AI10+ AI10 AI9+ AI9 AI8+ AI8 AI7+ AI7 AI6+ AI6 AI5+ AI5 AI4+ AI4 AI3+ AI3 AI2+ AI2 AI1+ AI1 Motor valve Return Forward Out door ote: 24VAC label indicates PHASE connection, i.e. all wires with must be connected label indicates U connection, i.e. all wires with must be connected Motor valves will often have a common terminal for U and Analog reference (-). If so AO and U must be connected. Water metering scaling to be defined when selecting controlling scheme. 24VAC as well as 24VDC may be used as supply. Above wiring assumes that Circulation pump and Motor valve is selected to support the same supply as the controller. BA Systems Petershvilevej 1 DK-3200 Helsinge 22
23 Scheme 1, description: Central heating control Basic The control topology for central heating is a mixing loop with outdoor compensation of incoming flow. Return limiter control is supported and may be enabled when controlling scheme is selected. Regulation The incoming flow is controlled by the motor valve. Regulation is from 0 100%. The incoming flow is then regulated in relation to the outdoor, also called climate compensation, defined as follows. Outdoor Values in C Forward At daytime, the circulation pump is stopped when the exceeds 20 C. The pump is reactivated if the drops below 18 C. At nighttime, the circulation pump is stopped above 18 C and reactivated below 16 C. Regulation stop is achieved by shutting of the motor valve and stopping the circulation pump. These are all default values that may be changed Default activation: The circulation pump is activated once every 24 hours if no other regulation is detected. The valve for regulation is likewise activated once every 24 hours if no other regulation is detected. BA Systems Petershvilevej 1 DK-3200 Helsinge 23
24 Scheme 1, Modbus parameter list: Description Data format Holding Register fcn 3/6 x10 fcn 3/6 x1 Input Register fcn 4 x10 Central heating Summer daytime Setpoint 1 x Vinter daytime Setpoint 2 x Summer nighttime Setpoint 3 x Vinter nighttime Setpoint 4 x Forward temp at -20 C outdoor temp. 5 x Forward temp at -15 C outdoor temp. 6 x Forward temp at -10 C outdoor temp. 7 x Forward temp at -5 C outdoor temp. 8 x Forward temp at 0 C outdoor temp. 9 x Forward temp at 5 C outdoor temp. 10 x Forward temp at 10 C outdoor temp. 11 x Forward temp at 15 C outdoor temp. 12 x Forward temp at 20 C outdoor temp. 13 x ight compensation 14 x ight compensation until this 15 x o night compensation below this 16 x Forced displacement 17 x Forced displacement reset time (seconds) 18 x Return maximum 19 x Set state (0:Auto, 1:Stop, 2:Start) 20 x Return limiter forced set point 1 x Pump state (0:Off,1:On) 2 x Status (0:Stop, 1:Manuel, 2:Auto run, 3:Auto stop) 3 x Energy state (0:Auto, 1:Vinter, 2:Force start, 3:Force stop, 4:Day/off, 5:ight/off) 4 x Values measured Out door sensor 5 x Forward 6 x ot used (returns 0) 7 x Return 8 x Motor valve position i percent 9 x Pump Stop/Start 10 x fcn 4 x1 BA Systems Petershvilevej 1 DK-3200 Helsinge 24
25 Scheme 1, BACnet parameter list: Description Analog Value Analog Input Data format Central Heating Summer daytime Setpoint Vinter daytime Setpoint Summer nighttime Setpoint Vinter nighttime Setpoint Forward temp at -20 C outdoor temp. Forward temp at -15 C outdoor temp. Forward temp at -10 C outdoor temp. Forward temp at -5 C outdoor temp. Forward temp at 0 C outdoor temp. Forward temp at 5 C outdoor temp. Forward temp at 10 C outdoor temp. Forward temp at 15 C outdoor temp. Forward temp at 20 C outdoor temp. ight compensation ight compensation until this o night compensation below this Forced displacement Forced displacement reset time (seconds) Return maximum Set state (0:Auto, 1:Stop, 2:Start) Return limiter forced set point Pump state (0:Off,1:On) Status (0:Stop, 1:Manuel, 2:Auto run, 3:Auto stop) Energy state (0:Auto, 1:Vinter, 2:Force start, 3:Force stop, 4:Day/off, 5:ight/off) Values measured Out door sensor Forward Return ot used (returns 0) Motor valve position i percent Pump Stop/Start CV1_Summerday CV1_Vinterday CV1_Summernight CV1_Vinternight CV1_Tm20 CV1_Tm15 CV1_Tm10 CV1_Tm05 CV1_Tp00 CV1_Tp05 CV1_Tp10 CV1_Tp15 CV1_Tp20 CV1_ATSK CV1_AT_MAX CV1_AT_DIS CV1_VAMEMES CV1_VM_SET_T CV1_Retmax CV1_OMS CV1_Set_beg _CV1_CP301 CV1_STATE CV1_SV_stat _CV1_TC901 _CV1_TC301 _CV1_TC401 _EMPTY CV1_MV401 _CV1_CP301 BA Systems Petershvilevej 1 DK-3200 Helsinge 25
26 Scheme 2, process diagram: Central heating (CH) and Hot water tank (HWT) AI1 DO1 Centralvarme blandesløjfe med varmtvandsbeholder AI2 AO1 AI3 AI5 AI7 DO2 AO2 AI6 DI1 BAS918S or BAS929S BA Systems Petershvilevej 1 DK-3200 Helsinge 26
27 Terminals for PHASE connection Terminals for U connection E E DICOM AO4_I AO3_I OP3 BAS 918S/929S Scheme 2, wiring diagram: 240VAC installation Circulation pump HWT Circulation pump CH Power supply Water meter DI4 DI3 DI2 DI1 DO11B DO11A DO10B DO10A DO9B DO9A DO8B DO8A DO7B DO7A DO6B DO6A DO5B DO5A DO4B DO4A DO3B DO3A DO2B DO2A DO1B DO1A 24VAC/ 24VAC/ 240VAC/ 240VAC/ 240VAC/ 24VAC/ 24VDC+ 240VAC/ 24VAC/ 24VDC- OP1 OP2 AO4+ AO4 AO3+ AO3 AO2+ AO2 AO1+ AO1 AI10+ AI10 AI9+ AI9 AI8+ AI8 AI7+ AI7 AI6+ AI6 AI5+ AI5 AI4+ AI4 AI3+ AI3 AI2+ AI2 AI1+ AI1 Motor valve HWT Motor valve CH Circulation HWT Return HWT Tank HWT Return CH Forward CH Outdoor 240VAC ote: label indicates PHASE connection, i.e. all wires with must be connected label indicates U connection, i.e. all wires with must be connected Motor valves will often have a common terminal for U and Analog reference (-). If so AO and U must be connected. Water metering scaling to be defined when selecting controlling scheme. Above wiring assumes that the components Circulation pump and Motor valve is to be supplied by 240VAC. BA Systems Petershvilevej 1 DK-3200 Helsinge 27
28 Terminals for PHASE connection Terminals for U connection E E DICOM AO4_I AO3_I OP3 BAS 918S/929S Scheme 2, wiring diagram: 24VAC or 24VDC installation Circulation pump HWT Circulation pump CH Power supply Water meter DI4 DI3 DI2 DI1 DO11B DO11A DO10B DO10A DO9B DO9A DO8B DO8A DO7B DO7A DO6B DO6A DO5B DO5A DO4B DO4A DO3B DO3A DO2B DO2A DO1B DO1A 24VAC/ 24VAC/ 240VAC/ 240VAC/ 240VAC/ 24VAC/ 24VDC+ 240VAC/ 24VAC/ 24VDC- OP1 OP2 AO4+ AO4 AO3+ AO3 AO2+ AO2 AO1+ AO1 AI10+ AI10 AI9+ AI9 AI8+ AI8 AI7+ AI7 AI6+ AI6 AI5+ AI5 AI4+ AI4 AI3+ AI3 AI2+ AI2 AI1+ AI1 Motor valve HWT Motor valve CH Circulation HWT Return temperaturn HWT Tank HWT Return CH Forward CH Outdoor 24VAC ote: label indicates PHASE connection, i.e. all wires with must be connected label indicates U connection, i.e. all wires with must be connected Motor valves will often have a common terminal for U and Analog reference (-). If so AO and U must be connected. Water metering scaling to be defined when selecting controlling scheme. 24VAC as well as 24VDC may be used as supply. Above wiring assumes that Circulation pump and Motor valve is selected to support the same supply as the controller. BA Systems Petershvilevej 1 DK-3200 Helsinge 28
29 Scheme 2, description: Central heating control: Basic The control topology for central heating is a mixing loop with outdoor compensation of incoming flow. Return limiter control is supported and may be enabled when controlling scheme is selected. Regulation The incoming flow is controlled by the motor valve. Regulation is from 0 100%. The incoming flow is then regulated in relation to the outdoor, also called climate compensation, defined as follows. Outdoor Values in C Forward At daytime, the circulation pump is stopped when the exceeds 20 C. The pump is reactivated if the drops below 18 C. At nighttime, the circulation pump is stopped above 18 C and reactivated below 16 C. Regulation stop is achieved by shutting of the motor valve and stopping the circulation pump. These are all default values that may be changed Default activation The circulation pump is activated once every 24 hours if no other regulation is detected. The valve for regulation is likewise activated once every 24 hours if no other regulation is detected. BA Systems Petershvilevej 1 DK-3200 Helsinge 29
30 Scheme 2, description continued: Hot water heater: Basic Hot water is supplied from a Hot water tank. Return limiter control is supported.. Regulation A sensor inputs the value for regulating a motor valve in the return flow. Regulation is from 0-100%. Hot Water Tank regulation values are given by a Day-setpoint and as a ightsetpoint. Each controlled by a timer. By default the day value is 55 C and night value 45 C. Default timer setting activates Day-setpoint only. egionella drive is by default set to Sunday from until 70 C Tank is reached or until o clock. All setpoints/timers may be adjusted in the controlling scheme parameters. Circulation pump The Hot water circulation pump is controlled by a real time clock based timer for start / stop. BA Systems Petershvilevej 1 DK-3200 Helsinge 30
31 Scheme 2, modbus parameter list: Description Data format Holding Register fcn 3/6 x10 fcn 3/6 x1 Input Register fcn 4 x10 Central heating/control Summer daytime Setpoint 1 x Vinter daytime Setpoint 2 x Summer nighttime Setpoint 3 x Vinter nighttime Setpoint 4 x Forward temp at -20 C outdoor temp. 5 x Forward temp at -15 C outdoor temp. 6 x Forward temp at -10 C outdoor temp. 7 x Forward temp at -5 C outdoor temp. 8 x Forward temp at 0 C outdoor temp. 9 x Forward temp at 5 C outdoor temp. 10 x Forward temp at 10 C outdoor temp. 11 x Forward temp at 15 C outdoor temp. 12 x Forward temp at 20 C outdoor temp. 13 x ight compensation 14 x ight compensation until this 15 x o night compensation below this 16 x Forced displacement 17 x Forced displacement reset time (seconds) 18 x Return maximum 19 x Set state (0:Auto, 1:Stop, 2:Start) 20 x Return limiter forced set point 1 x Pump state (0:Off,1:On) 2 x Status (0:Stop, 1:Manuel, 2:Auto run, 3:Auto stop) 3 x Energy state (0:Auto, 1:Vinter, 2:Force start, 3:Force stop, 4:Day/off, 5:ight/off) 4 x Central Heating/Values measured Out door sensor 5 x Forward 6 x ot used (returns 0) 7 x Return 8 x Motor valve position i percent 9 x Pump Stop/Start 10 x fcn 4 x1 BA Systems Petershvilevej 1 DK-3200 Helsinge 31
32 Scheme 2, modbus parameter list continued: Description Holding Register fcn 3/6 x10 fcn 3/6 x1 Input Register fcn 4 x10 fcn 4 x1 Data format Hot Water Tank/control Daytime setpoint 21 x ighttime setpoint 22 x Return limiter maximum 23 x egionalla process (0:Off, 1:Sunday, 2:Monday... 7:Saturday, 8:All days 24 x Return limiter forced set point 11 x Pump state (0:Off, 1:On) 12 x Status (0:Stop, 1:Dag, 2:at, 3:egionella) 13 x Hot Water Tank/Values measured Tank 14 x Return (if selected) 15 x Circulation 16 x Motor valve position in percent 17 x Pump state (0:Off, 1:On) 18 x BA Systems Petershvilevej 1 DK-3200 Helsinge 32
33 Scheme 2, BACnet parameter list: Description Analog Value Analog Input Data format Central heating/control Summer daytime Setpoint Vinter daytime Setpoint Summer nighttime Setpoint Vinter nighttime Setpoint Forward temp at -20 C outdoor temp. Forward temp at -15 C outdoor temp. Forward temp at -10 C outdoor temp. Forward temp at -5 C outdoor temp. Forward temp at 0 C outdoor temp. Forward temp at 5 C outdoor temp. Forward temp at 10 C outdoor temp. Forward temp at 15 C outdoor temp. Forward temp at 20 C outdoor temp. ight compensation ight compensation until this o night compensation below this Forced displacement Forced displacement reset time (seconds) Return maximum Set state (0:Auto, 1:Stop, 2:Start) Return limiter forced set point Pump state (0:Off,1:On) Status (0:Stop, 1:Manuel, 2:Auto run, 3:Auto stop) Energy state (0:Auto, 1:Vinter, 2:Force start, 3:Force stop, 4:Day/off, 5:ight/off) Central Heating/Values measured Out door sensor Forward Return ot used (returns 0) Motor valve position i percent Pump Stop/Start CV1_Summerday CV1_Vinterday CV1_Summernight CV1_Vinternight CV1_Tm20 CV1_Tm15 CV1_Tm10 CV1_Tm05 CV1_Tp00 CV1_Tp05 CV1_Tp10 CV1_Tp15 CV1_Tp20 CV1_ATSK CV1_AT_MAX CV1_AT_DIS CV1_VAMEMES CV1_VM_SET_T CV1_Retmax CV1_OMS CV1_Set_beg CV1_CP301 CV1_STATE CV1_SV_stat _CV1_TC901 _CV1_TC301 _CV1_TC401 _EMPTY CV1_MV401 _CV1_CP301 BA Systems Petershvilevej 1 DK-3200 Helsinge 33
34 Scheme 2, BACnet parameter list continued: Description Analog Value Analog Input Data format Hot Water Tank/control Daytime setpoint ighttime setpoint Return limiter maximum egionalla process (0:Off, 1:Sunday, 2:Monday... 7:Saturday, 8:All days Return limiter forced set point Pump state (0:Off, 1:On) Status (0:Stop, 1:Dag, 2:at, 3:egionella) Hot Water Tank/Values measured Tank Return (if selected) Circulation Motor valve position in percent Pump state (0:Off, 1:On) VB1_day VB1_nat VB1_Retmax VB1_egio VB1_Set_beg _VB1_CP401 VB1_s _VB1_TC301 _VB1_TC401 _VB1_TC402 _VB1_MV401 _VB1_CP401 BA Systems Petershvilevej 1 DK-3200 Helsinge 34
35 Scheme 3, process diagram: Central heating with Heat Exchanger DI1 AI1 DO1 AI2 AO1 AI3 AI4 BAS918S or BAS929S BA Systems Petershvilevej 1 DK-3200 Helsinge 35
36 Terminals for PHASE connection Terminals for U connection E DICOM AO4_I AO3_I OP3 BAS 918S/929S Scheme 3, wiring diagram: 240VAC installation Circulation pump Power supply Water meter DI4 DI3 DI2 DI1 DO11B DO11A DO10B DO10A DO9B DO9A DO8B DO8A DO7B DO7A DO6B DO6A DO5B DO5A DO4B DO4A DO3B DO3A DO2B DO2A DO1B DO1A 24VAC/ 24VAC/ 240VAC/ 240VAC/ 240VAC/ 24VAC/ 24VDC+ 240VAC/ 24VAC/ 24VDC- OP1 OP2 AO4+ AO4 AO3+ AO3 AO2+ AO2 AO1+ AO1 AI10+ AI10 AI9+ AI9 AI8+ AI8 AI7+ AI7 AI6+ AI6 AI5+ AI5 AI4+ AI4 AI3+ AI3 AI2+ AI2 AI1+ AI1 Motor valve Secondary return Primary return Forward Outdoor 240VAC ote: label indicates PHASE connection, i.e. all wires with must be connected label indicates U connection, i.e. all wires with must be connected Motor valves will often have a common terminal for U and Analog reference (-). If so AO and U must be connected. Water metering scaling to be defined when selecting controlling scheme. Above wiring assumes that the components Circulation pump and Motor valve is to be supplied by 240VAC. BA Systems Petershvilevej 1 DK-3200 Helsinge 36
37 Terminals for PHASE connection Terminals for U connection E DICOM AO4_I AO3_I OP3 BAS 918S/929S Scheme 3, wiring diagram: 24VAC or 24VDC installation Circulation pump Power supply Water meter DI4 DI3 DI2 DI1 DO11B DO11A DO10B DO10A DO9B DO9A DO8B DO8A DO7B DO7A DO6B DO6A DO5B DO5A DO4B DO4A DO3B DO3A DO2B DO2A DO1B DO1A 24VAC/ 24VAC/ 240VAC/ 240VAC/ 240VAC/ 24VAC/ 24VDC+ 240VAC/ 24VAC/ 24VDC- OP1 OP2 AO4+ AO4 AO3+ AO3 AO2+ AO2 AO1+ AO1 AI10+ AI10 AI9+ AI9 AI8+ AI8 AI7+ AI7 AI6+ AI6 AI5+ AI5 AI4+ AI4 AI3+ AI3 AI2+ AI2 AI1+ AI1 Motor valve Secondary return Primary return Forward Outdoor 24VAC ote: label indicates PHASE connection, i.e. all wires with must be connected label indicates U connection, i.e. all wires with must be connected Motor valves will often have a common terminal for U and Analog reference (-). If so AO and U must be connected. Water metering scaling to be defined when selecting controlling scheme. 24VAC as well as 24VDC may be used as supply. Above wiring assumes that Circulation pump and Motor valve is selected to support the same supply as the controller. BA Systems Petershvilevej 1 DK-3200 Helsinge 37
38 Scheme 3, description: Central heating control: Basic The control topology for central heating is a mixing loop with outdoor compensation of incoming flow. Return limiter control is supported and may be enabled when controlling scheme is selected. Regulation The incoming flow is controlled by the motor valve. Regulation is from 0 100%. The incoming flow is then regulated in relation to the outdoor, also called climate compensation, defined as follows. Outdoor Values in C Forward At daytime, the circulation pump is stopped when the exceeds 20 C. The pump is reactivated if the drops below 18 C. At nighttime, the circulation pump is stopped above 18 C and reactivated below 16 C. Regulation stop is achieved by shutting of the motor valve and stopping the circulation pump. These are all default values that may be changed Default activation The circulation pump is activated once every 24 hours if no other regulation is detected. The valve for regulation is likewise activated once every 24 hours if no other regulation is detected. BA Systems Petershvilevej 1 DK-3200 Helsinge 38
39 Scheme 3, modbus parameter list: Description Data format Holding Register fcn 3/6 x10 fcn 3/6 x1 Input Register fcn 4 x10 Central heating Summer daytime Setpoint 1 x Vinter daytime Setpoint 2 x Summer nighttime Setpoint 3 x Vinter nighttime Setpoint 4 x Forward temp at -20 C outdoor temp. 5 x Forward temp at -15 C outdoor temp. 6 x Forward temp at -10 C outdoor temp. 7 x Forward temp at -5 C outdoor temp. 8 x Forward temp at 0 C outdoor temp. 9 x Forward temp at 5 C outdoor temp. 10 x Forward temp at 10 C outdoor temp. 11 x Forward temp at 15 C outdoor temp. 12 x Forward temp at 20 C outdoor temp. 13 x ight compensation 14 x ight compensation until this 15 x o night compensation below this 16 x Forced displacement 17 x Forced displacement reset time (seconds) 18 x Return maximum 19 x Set state (0:Auto, 1:Stop, 2:Start) 20 x Retur limiter forced setpoint 1 x Pump state (0:Off,1:On) 2 x Status (0:Stop, 1:Manuel, 2:Auto run, 3:Auto stop) 3 x Energy state (0:Auto, 1:Vinter, 2:Force start, 3:Force stop, 4:Day/off, 5:ight/off) 4 x Values measured Out door sensor 5 x Forward 6 x ot used (returns 0) 7 x Return 8 x Motor valve position i percent 9 x Pump Stop/Start 10 x fcn 4 x1 BA Systems Petershvilevej 1 DK-3200 Helsinge 39
40 Scheme 3, BACnet parameter list: Description Analog Value Analog Input Data format Central Heating/control Summer daytime Setpoint Vinter daytime Setpoint Summer nighttime Setpoint Vinter nighttime Setpoint Forward temp at -20 C outdoor temp. Forward temp at -15 C outdoor temp. Forward temp at -10 C outdoor temp. Forward temp at -5 C outdoor temp. Forward temp at 0 C outdoor temp. Forward temp at 5 C outdoor temp. Forward temp at 10 C outdoor temp. Forward temp at 15 C outdoor temp. Forward temp at 20 C outdoor temp. ight compensation ight compensation until this o night compensation below this Forced displacement Forced displacement reset time (seconds) Return maximum Set state (0:Auto, 1:Stop, 2:Start) Return limiter forced set point Pump state (0:Off,1:On) Status (0:Stop, 1:Manuel, 2:Auto run, 3:Auto stop) Energy state (0:Auto, 1:Vinter, 2:Force start, 3:Force stop, 4:Day/off, 5:ight/off) Central Heating/Values measured Out door sensor Forward Return ot used (returns 0) Motor valve position i percent Pump Stop/Start CV1_Summerday CV1_Vinterday CV1_Summernight CV1_Vinternight CV1_Tm20 CV1_Tm15 CV1_Tm10 CV1_Tm05 CV1_Tp00 CV1_Tp05 CV1_Tp10 CV1_Tp15 CV1_Tp20 CV1_ATSK CV1_AT_MAX CV1_AT_DIS CV1_VAMEMES CV1_VM_SET_T CV1_Retmax CV1_OMS CV1_Set_beg _CV1_CP301 CV1_STATE CV1_SV_stat _CV1_TC901 _CV1_TC301 _CV1_TC401 _EMPTY CV1_MV401 _CV1_CP301 BA Systems Petershvilevej 1 DK-3200 Helsinge 40
41 Scheme 4, process diagram: Central heating with heat exchanger and hot water supply AI1 DO1 AI2 AO1 AI3 AI4 AI5 AI7 DO2 AO2 AI6 DI1 BAS918S or BAS929S BA Systems Petershvilevej 1 DK-3200 Helsinge 41
42 Terminals for PHASE connection Terminals for U connection E E DICOM AO4_I AO3_I OP3 BAS 918S/929S Scheme 4, wiring diagram: 240VAC installation Circulation pump HWT Circulation pump CH Power supply Water meter DI4 DI3 DI2 DI1 DO11B DO11A DO10B DO10A DO9B DO9A DO8B DO8A DO7B DO7A DO6B DO6A DO5B DO5A DO4B DO4A DO3B DO3A DO2B DO2A DO1B DO1A 24VAC/ 24VAC/ 240VAC/ 240VAC/ 240VAC/ 24VAC/ 24VDC+ 240VAC/ 24VAC/ 24VDC- OP1 OP2 AO4+ AO4 AO3+ AO3 AO2+ AO2 AO1+ AO1 AI10+ AI10 AI9+ AI9 AI8+ AI8 AI7+ AI7 AI6+ AI6 AI5+ AI5 AI4+ AI4 AI3+ AI3 AI2+ AI2 AI1+ AI1 Motor valve HWT Motor valve CH Circulation HWT Return HWT Tank HWT Secondary return CH Primary return CH Forward CH Outdoor 240VAC ote: label indicates PHASE connection, i.e. all wires with must be connected label indicates U connection, i.e. all wires with must be connected Motor valves will often have a common terminal for U and Analog reference (-). If so AO and U must be connected. Water metering scaling to be defined when selecting controlling scheme. Above wiring assumes that the components Circulation pump and Motor valve is to be supplied by 240VAC. BA Systems Petershvilevej 1 DK-3200 Helsinge 42
43 Terminals for PHASE connection Terminals for U connection E E DICOM AO4_I AO3_I OP3 BAS 918S/929S Scheme 4, wireing diagram 24VAC or 24VDC installation Circulation pump HWT Circulation pump CH Power supply Water meter DI4 DI3 DI2 DI1 DO11B DO11A DO10B DO10A DO9B DO9A DO8B DO8A DO7B DO7A DO6B DO6A DO5B DO5A DO4B DO4A DO3B DO3A DO2B DO2A DO1B DO1A 24VAC/ 24VAC/ 240VAC/ 240VAC/ 240VAC/ 24VAC/ 24VDC+ 240VAC/ 24VAC/ 24VDC- OP1 OP2 AO4+ AO4 AO3+ AO3 AO2+ AO2 AO1+ AO1 AI10+ AI10 AI9+ AI9 AI8+ AI8 AI7+ AI7 AI6+ AI6 AI5+ AI5 AI4+ AI4 AI3+ AI3 AI2+ AI2 AI1+ AI1 Motor valve HWT Motor valve CH Circulation HWT Return HWT Tank HWT Secondary return CH Primary return CH Forward CH Outdoor 24VAC ote: label indicates PHASE connection, i.e. all wires with must be connected label indicates U connection, i.e. all wires with must be connected Motor valves will often have a common terminal for U and Analog reference (-). If so AO and U must be connected. Water metering scaling to be defined when selecting controlling scheme. 24VAC as well as 24VDC may be used as supply. Above wiring assumes that Circulation pump and Motor valve is selected to support the same supply as the controller. BA Systems Petershvilevej 1 DK-3200 Helsinge 43
44 Scheme 4, description: Central heating control: Basic The control topology for central heating is a mixing loop with outdoor compensation of incoming flow. Return limiter control is supported and may be enabled when controlling scheme is selected. Regulation The incoming flow is controlled by the motor valve. Regulation is from 0 100%. The incoming flow is then regulated in relation to the outdoor, also called climate compensation, defined as follows. Outdoor Values in C Forward At daytime, the circulation pump is stopped when the exceeds 20 C. The pump is reactivated if the drops below 18 C. At nighttime, the circulation pump is stopped above 18 C and reactivated below 16 C. Regulation stop is achieved by shutting of the motor valve and stopping the circulation pump. These are all default values that may be changed Default activation The circulation pump is activated once every 24 hours if no other regulation is detected. The valve for regulation is likewise activated once every 24 hours if no other regulation is detected. BA Systems Petershvilevej 1 DK-3200 Helsinge 44
45 Scheme 4, description continued: Hot water heater: Basic Hot water is supplied from a Hot water tank. Return limiter control is supported.. Regulation A sensor inputs the value for regulating a motor valve in the return flow. Regulation is from 0-100%. Hot Water Tank regulation values are given by a Day-setpoint and as a ightsetpoint. Each controlled by a timer. By default the day value is 55 C and night value 45 C. Default timer setting activates Day-setpoint only. egionella drive is by default set to Sunday from until 70 C Tank is reached or until o clock. All setpoints/timers may be adjusted in the controlling scheme parameters. Circulation pump The Hot water circulation pump is controlled by a real time clock based timer for start / stop. BA Systems Petershvilevej 1 DK-3200 Helsinge 45
46 Scheme 4, modbus parameter list: Description Data format Holding Register fcn 3/6 x10 fcn 3/6 x1 Input Register fcn 4 x10 Central heating/control Summer daytime Setpoint 1 x Vinter daytime Setpoint 2 x Summer nighttime Setpoint 3 x Vinter nighttime Setpoint 4 x Forward temp at -20 C outdoor temp. 5 x Forward temp at -15 C outdoor temp. 6 x Forward temp at -10 C outdoor temp. 7 x Forward temp at -5 C outdoor temp. 8 x Forward temp at 0 C outdoor temp. 9 x Forward temp at 5 C outdoor temp. 10 x Forward temp at 10 C outdoor temp. 11 x Forward temp at 15 C outdoor temp. 12 x Forward temp at 20 C outdoor temp. 13 x ight compensation 14 x ight compensation until this 15 x o night compensation below this 16 x Forced displacement 17 x Forced displacement reset time (seconds) 18 x Return maximum 19 x Set state (0:Auto, 1:Stop, 2:Start) 20 x Return limiter forced setpoint 1 x Pump state (0:Off,1:On) 2 x Status (0:Stop, 1:Manuel, 2:Auto run, 3:Auto stop) 3 x Energy state (0:Auto, 1:Vinter, 2:Force start, 3:Force stop, 4:Day/off, 5:ight/off) 4 x Central Heating/Values measured Out door sensor 5 x Forward 6 x ot used (returns 0) 7 x Return 8 x Motor valve position i percent 9 x Pump Stop/Start 10 x fcn 4 x1 BA Systems Petershvilevej 1 DK-3200 Helsinge 46
47 Scheme 4, modbus parameter list continued: Description Holding Register fcn 3/6 x10 fcn 3/6 x1 Input Register fcn 4 x10 fcn 4 x1 Data format Hot Water Tank/control Daytime setpoint 21 x ighttime setpoint 22 x Return limiter maximum 23 x egionalla process (0:Off, 1:Sunday, 2:Monday... 7:Saturday, 8:All days 24 x Return limiter forced set point 11 x Pump state (0:Off, 1:On) 12 x Status (0:Stop, 1:Dag, 2:at, 3:egionella) 13 x Hot Water Tank/Values measured Tank 14 x Return (if selected) 15 x Circulation 16 x Motor valve position in percent 17 x Pump state (0:Off, 1:On) 18 x BA Systems Petershvilevej 1 DK-3200 Helsinge 47
48 Scheme 4, BACnet parameter list: Description Analog Value Analog Input Data format Central heating/control Summer daytime Setpoint Vinter daytime Setpoint Summer nighttime Setpoint Vinter nighttime Setpoint Forward temp at -20 C outdoor temp. Forward temp at -15 C outdoor temp. Forward temp at -10 C outdoor temp. Forward temp at -5 C outdoor temp. Forward temp at 0 C outdoor temp. Forward temp at 5 C outdoor temp. Forward temp at 10 C outdoor temp. Forward temp at 15 C outdoor temp. Forward temp at 20 C outdoor temp. ight compensation ight compensation until this o night compensation below this Forced displacement Forced displacement reset time (seconds) Return maximum Set state (0:Auto, 1:Stop, 2:Start) Return limiter forced set point Pump state (0:Off,1:On) Status (0:Stop, 1:Manuel, 2:Auto run, 3:Auto stop) Energy state (0:Auto, 1:Vinter, 2:Force start, 3:Force stop, 4:Day/off, 5:ight/off) Central Heating/Values measured Out door sensor Forward Return ot used (returns 0) Motor valve position i percent Pump Stop/Start CV1_Summerday CV1_Vinterday CV1_Summernight CV1_Vinternight CV1_Tm20 CV1_Tm15 CV1_Tm10 CV1_Tm05 CV1_Tp00 CV1_Tp05 CV1_Tp10 CV1_Tp15 CV1_Tp20 CV1_ATSK CV1_AT_MAX CV1_AT_DIS CV1_VAMEMES CV1_VM_SET_T CV1_Retmax CV1_OMS CV1_Set_beg CV1_CP301 CV1_STATE CV1_SV_stat _CV1_TC901 _CV1_TC301 _CV1_TC401 _EMPTY CV1_MV401 _CV1_CP301 BA Systems Petershvilevej 1 DK-3200 Helsinge 48
49 Scheme 4, BACnet parameter list continued: Description Analog Value Analog Input Data format Hot Water Tank/control Daytime setpoint ighttime setpoint Return limiter maximum egionalla process (0:Off, 1:Sunday, 2:Monday... 7:Saturday, 8:All days Return limiter forced set point Pump state (0:Off, 1:On) Status (0:Stop, 1:Dag, 2:at, 3:egionella) Hot Water Tank/Values measured Tank Return (if selected) Circulation Motor valve position in percent Pump state (0:Off, 1:On) VB1_day VB1_nat VB1_Retmax VB1_egio VB1_Set_beg _VB1_CP401 VB1_s _VB1_TC301 _VB1_TC401 _VB1_TC402 _VB1_MV401 _VB1_CP401 BA Systems Petershvilevej 1 DK-3200 Helsinge 49
50 Scheme 5, process diagram: Dual Central heating DI1 AI1 DO1 AI2 AO1 AI3 CH1 DO2 AI5 AO2 AI6 CH2 BAS918S or BAS929S BA Systems Petershvilevej 1 DK-3200 Helsinge 50
51 Terminals for PHASE connection Terminals for U connection E E DICOM AO4_I AO3_I OP3 BAS 918S/929S Scheme 5, wiring diagram: 240VAC installation Circulation pump CH2 Circulation pump CH1 Power supply Water meter DI4 DI3 DI2 DI1 DO11B DO11A DO10B DO10A DO9B DO9A DO8B DO8A DO7B DO7A DO6B DO6A DO5B DO5A DO4B DO4A DO3B DO3A DO2B DO2A DO1B DO1A 24VAC/ 24VAC/ 240VAC/ 240VAC/ 240VAC/ 24VAC/ 24VDC+ 240VAC/ 24VAC/ 24VDC- OP1 OP2 AO4+ AO4 AO3+ AO3 AO2+ AO2 AO1+ AO1 AI10+ AI10 AI9+ AI9 AI8+ AI8 AI7+ AI7 AI6+ AI6 AI5+ AI5 AI4+ AI4 AI3+ AI3 AI2+ AI2 AI1+ AI1 Motor valve CH2 Motor valve CH1 Return CH2 Forward CH2 Return CH1 Forward CH1 Outdoor 240VAC ote: label indicates PHASE connection, i.e. all wires with must be connected label indicates U connection, i.e. all wires with must be connected Motor valves will often have a common terminal for U and Analog reference (-). If so AO and U must be connected. Water metering scaling to be defined when selecting controlling scheme. Above wiring assumes that the components Circulation pump and Motor valve is to be supplied by 240VAC. BA Systems Petershvilevej 1 DK-3200 Helsinge 51
52 Terminals for PHASE connection Terminals for U connection E E DICOM AO4_I AO3_I OP3 BAS 918S/929S Scheme 5, wiring diagram: 24VAC or 24VDC installation Circulation pump CH2 Circulation pump CH1 Power supply Water meter DI4 DI3 DI2 DI1 DO11B DO11A DO10B DO10A DO9B DO9A DO8B DO8A DO7B DO7A DO6B DO6A DO5B DO5A DO4B DO4A DO3B DO3A DO2B DO2A DO1B DO1A 24VAC/ 24VAC/ 240VAC/ 240VAC/ 240VAC/ 24VAC/ 24VDC+ 240VAC/ 24VAC/ 24VDC- OP1 OP2 AO4+ AO4 AO3+ AO3 AO2+ AO2 AO1+ AO1 AI10+ AI10 AI9+ AI9 AI8+ AI8 AI7+ AI7 AI6+ AI6 AI5+ AI5 AI4+ AI4 AI3+ AI3 AI2+ AI2 AI1+ AI1 Motor valve CH2 Motor valve CH1 Return CH2 Forward Temperature CH2 Return CH1 Forward CH1 Outdoor 24VAC ote: label indicates PHASE connection, i.e. all wires with must be connected label indicates U connection, i.e. all wires with must be connected Motor valves will often have a common terminal for U and Analog reference (-). If so AO and U must be connected. Water metering scaling to be defined when selecting controlling scheme. 24VAC as well as 24VDC may be used as supply. Above wiring assumes that Circulation pump and Motor valve is selected to support the same supply as the controller. BA Systems Petershvilevej 1 DK-3200 Helsinge 52
53 Scheme 5, description: Central heating control: Basic The control topology for central heating is a mixing loop with outdoor compensation of incoming flow. Return limiter control is supported and may be enabled when controlling scheme is selected. Regulation The incoming flow is controlled by the motor valve. Regulation is from 0 100%. The incoming flow is then regulated in relation to the outdoor, also called climate compensation, defined as follows. Outdoor Values in C Forward At daytime, the circulation pump is stopped when the exceeds 20 C. The pump is reactivated if the drops below 18 C. At nighttime, the circulation pump is stopped above 18 C and reactivated below 16 C. Regulation stop is achieved by shutting of the motor valve and stopping the circulation pump. These are all default values that may be changed Default activation The circulation pump is activated once every 24 hours if no other regulation is detected. The valve for regulation is likewise activated once every 24 hours if no other regulation is detected. BA Systems Petershvilevej 1 DK-3200 Helsinge 53
54 Scheme 5, modbus parameter list: Description Data format Holding Register fcn 3/6 x10 fcn 3/6 x1 Input Register fcn 4 x10 Central heating circuit 1/control Summer daytime Setpoint 1 x Vinter daytime Setpoint 2 x Summer nighttime Setpoint 3 x Vinter nighttime Setpoint 4 x Forward temp at -20 C outdoor temp. 5 x Forward temp at -15 C outdoor temp. 6 x Forward temp at -10 C outdoor temp. 7 x Forward temp at -5 C outdoor temp. 8 x Forward temp at 0 C outdoor temp. 9 x Forward temp at 5 C outdoor temp. 10 x Forward temp at 10 C outdoor temp. 11 x Forward temp at 15 C outdoor temp. 12 x Forward temp at 20 C outdoor temp. 13 x ight compensation 14 x ight compensation until this 15 x o night compensation below this 16 x Forced displacement 17 x Forced displacement reset time (seconds) 18 x Return maximum 19 x Set state (0:Auto, 1:Stop, 2:Start) 20 x Return limiter forced setpoint 1 x Pump state (0:Off,1:On) 2 x Status (0:Stop, 1:Manuel, 2:Auto run, 3:Auto stop) 3 x Energy state (0:Auto, 1:Vinter, 2:Force start, 3:Force stop, 4:Day/off, 5:ight/off) 4 x Centarl Heating circuit 1/Values measured Out door sensor 5 x Forward 6 x ot used (returns 0) 7 x Return 8 x Motor valve position i percent 9 x Pump Stop/Start 10 x fcn 4 x1 BA Systems Petershvilevej 1 DK-3200 Helsinge 54
905U Wireless. New Products... New Solutions. The wireless alternative to expensive cabling... Simple but Reliable. Easy to Use
Wireless New Products... New Solutions The range of telemetry modules provide remote monitoring and control by radio or twisted-pair wire, over short or long distances. Transducer signals connected at
More informationPLC-K506 Series FEATURES DESCRIPTION FEATURES
FEATURES Two High Speed Counters Two Pulse Train Outputs Two Pulse Width Modulation Outputs Inputs 10 Outputs 1 RS232 Port 2 RS485 Ports Supports Modbus RTU Protocol Communicate With Up to 32 Devices DESCRIPTION
More informationKNC-PLC-K506 Series FEATURES DESCRIPTION FEATURES
FEATURES Two High Speed Counters Two Pulse Train Outputs Two Pulse Width Modulation Outputs Inputs 10 Outputs 1 RS232 Port 2 RS485 Ports Supports Modbus RTU Protocol Communicate with up to 32 devices DESCRIPTION
More informationThe wireless alternative to expensive cabling...
The wireless alternative to expensive cabling... ELPRO 905U Wireless Solutions for Process Applications New Products... New Solutions The ELPRO 905U range of telemetry modules provide remote monitoring
More informationAC CURRENT GENERATOR POC-6000 (current from 0 to 1000 ARMS)
AC CURRENT GENERATOR PERFORMANCES Wide range of current 50 db dynamic range Signal-to-noise ratio: 80 db open loop protection Stability < 0,1% Very low THD distortion < 0,3% External synchronization Build-up
More informationB850 Boiler House Energy Monitor
Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without
More informationThe wireless alternative to expensive cabling...
The wireless alternative to expensive cabling... ELPRO 105U Wireless Solutions for Process Applications New Products... New Solutions The ELPRO 105U range of wireless I/O provides a low cost alternative
More informationThe wireless alternative to expensive cabling...
The wireless alternative to expensive cabling... ELPRO 905U Wireless Solutions for Process Applications New Products... New Solutions The ELPRO 905U range of wireless I/O provides a low cost alternative
More informationB850 Boiler House Energy Monitor
Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without
More informationDXRL (DPM-RL) DMX RELAY DRIVER With optional 0-10 Volt Converter. ELM Video Technology, Inc. Innovative DMX and MIDI Products DESCRIPTION SETTINGS
.xx DESCRIPTIO The DXR (DPM-R) is a DMX to relay driver and controller, with an optional 0 to 10 volt converter. Control 12VDC relays up to 100mA each from any DMX console or any DMX generating device.
More information4-20mA, 0-10V and general process measuring bargraph displays
Page 1 of 6 Digital panel meters Large displays Bargraphs Transmitters 4-20mA, 0-10V process input bargraph displays Display almost any physical variable... The bargraph displays on this page accept most
More informationRI-D440. Three Phase easywire Multifunction DIN Rail Energy Meter. Telephone : +44 (0) Displayed Parameters
RI-D440 Three Phase easywire Multifunction DIN Rail Energy Meter Four module DIN rail mounted Energy pulse LED 330mV Input from easywire CTs (or -/1A and -/5A current transformer input with TAS-SCTEWA
More informationOVEN INDUSTRIES, INC. Model 5C7-362
OVEN INDUSTRIES, INC. OPERATING MANUAL Model 5C7-362 THERMOELECTRIC MODULE TEMPERATURE CONTROLLER TABLE OF CONTENTS Features... 1 Description... 2 Block Diagram... 3 RS232 Communications Connections...
More informationTemperature Transmitters - DIN Rail Mounted
XTD Features - Non-programmable Models Sensor Types: Models for thermocouple Types J, K, or T Models for RTD Type Pt100 3-wire Select from a variety of pre-configured measuring ranges Internal cold junction
More informationRI-F200 Series. Single and Three Phase Multifunction Energy Meter. Telephone : +44 (0) Displayed Parameters
RI-F200 Series Single and Three Phase Multifunction Energy Meter DIN 96 panel mounted -/1A or -/5A current transformer input Single phase or three phase network compatible Programmable voltage and current
More informationTemperature Transmitters - Head Mounted
XTH Features - Non-programmable Models Sensor Types: Models for thermocouple Types J, K, or T Models for RTD Type Pt100 3-wire Select from a variety of pre-configured measuring ranges Internal cold junction
More informationBAS Integration Manual
Snow Melting Control 680 Introduction BAS Integration Manual Snow Melting 680_B 10/15 Replaces: 04/15 The Snow Melting Control 680 can communicate with a Building Automation System (BAS) using either BACnet
More informationIndustrial Modbus I/O Modules
Industrial Modbus I/O Modules Modbus I/O Modules Introduction & Features Digital Input / Output Modules Analog Input / Output Modules Modbus I/O Modules The Best Choice For Your SCADA Applications Introduction
More informationModbus communication module for TCX2: AEX-MOD
Modbus communication module for TCX2: Communication Specification TCX2 is factory installed in TCX2 series controllers with -MOD suffix, and is also available separately upon request for customer installation
More informationCetetherm IQ Heat Midi/Maxi
Cetetherm IQ Heat Midi/Maxi Preconfigured DDC solution for Midi and Maxi. Ready to plug-in. Built in web pages for remote control. Quick feedback during alarms and deviations. No licens or extra programs
More informationvacon 100 flow ac drives application manual
vacon 100 flow ac drives application manual vacon 1 TABLE OF CONTENTS Document: DPD01083A Version release date: 16.11.12 Corresponds to software package FW0159V121106.vcx 1. Vacon 100 FLOW - Quick Startup
More informationAdvanced Ladder Logic Full IEC Languages 25A for <1 24 VDC DC Switched
EXL6 OCS Datasheet for HE- EXL1E0, HE- EXL1E2, HE- EXL1E3, HE- EXL1E4, HE- EXL1E5, HE- EXL1E6 HEXT371C100, HEXT371C112, HEXT371C113, HEXT371C114, HEXT371C115, HEXT371C116 1. Specifications Required Power
More informationInstallation Guide. ECL Comfort 310, application A Table of Contents
1.0 Table of Contents 1.0 Table of Contents... 1 1.1 Important safety and product information..................... 2 2.0 Installation... 6 2.1 Before you start.....................................................
More information269 Troubleshooting Guide 11/4/98 1
269 Troubleshooting Guide 11/4/98 1 Table of Contents Phase currents 3 Communications. 6 RTDs.. 9 Ground Fault Currents... 13 Output Relays. 15 Analog Output 17 Switch Inputs...18 11/4/98 2 Phase Currents
More informationJacket heater, etc Mounting bracket for Pipe wrapping. (Optional) Temperature sensor. Output (To heater) (Optional)
Temperature Controller with Built-in SSR SB SB General Description SB is a channel temperature controller with Built-in SSR (Solid state relay) designed for flexible heating solutions such as heat trace
More informationInstallation Guide. ECL Comfort 310, application A Table of Contents
1.0 Table of Contents 1.0 Table of Contents... 1 1.1 Important safety and product information..................... 2 2.0 Installation... 5 2.1 Before you start.....................................................
More informationSRC-110 Series Zone Controllers with Modbus RTU
Product sheet CT2.142 Type SRC-110-MOD SRC-110 Series Zone Controllers with Modbus RTU The SRC-110 series controllers have been designed for zone heating and cooling control. The controllers have 3 analogue
More informationElectronic Circuit Breaker with reset input ESS20-1..
Electronic Circuit Breaker with reset input ESS0-.. Description The special device ESS0-.. is a further extension of the product line electronic circuit breakers. Type ESS0-.. has a width of only. mm and
More informationElectronic Circuit Breaker ESS20-0..
Description Electronic circuit breaker type ES-0.. is designed to ensure selective disconnection of individual loads in systems which are powered by a DC 4 V switch-mode power supply. DC 4 V power supplies,
More informationH7625A, H7635A, H7626A, H7636A Series 2000 Humidity/Temperature Sensors
H765A, H7635A, H766A, H7636A Series 000 Humidity/Temperature Sensors WALL-MOUNT MODELS APPLICATI The H765A, H766A, H7635A and H7636A Wall-Mount Humidity/Temperature Sensors are universal Relative Humidity
More informationIntegra 1560 and 1580 Digital Transducer Systems
Integra 1560 and 1580 multi function transducers provide high accuracy
More informationEngineering Guideline. pac-carriers Type for Yokogawa Centum VP
Engineering Guideline pac-carriers Type 9195 for Yokogawa Centum VP pac-carrier Type 9195 2 Engineering Guideline / Yokogawa Centum VP 26.0.2018 pac-carrier Type 9195 Integrated solutions for Yokogawa
More informationUSB-TEMP and TC Series USB-Based Temperature Measurement Devices
USB-Based Temperature Measurement Devices Features Temperature and voltage measurement USB devices Thermocouple, RTD, thermistor, or semiconductor sensor measurements Eight analog inputs Up to ±10 V inputs*
More informationNdrive Series. Digital Servo Amplifiers PWM. Wide output power range from 10 A peak to 200 A peak at 320 VDC. 2- or 3-phase AC line input or DC input
Ndrive PWM Amplifiers/Drives Ndrive Series Digital Servo Amplifiers PWM Wide output power range from 10 A peak to 200 A peak at 320 VDC 2- or 3-phase AC line input or DC input CE approved and NRTL safety
More informationNdrive Series. Digital Servo Amplifiers PWM. Wide output power range from 10 A peak to 200 A peak at 320 VDC. 2- or 3-phase AC line input or DC input
Ndrive PWM Amplifiers/Drives Ndrive Series Digital Servo Amplifiers PWM Wide output power range from 10 A peak to 200 A peak at 320 VDC 2- or 3-phase AC line input or DC input CE approved and NRTL safety
More informationZlinx Wireless I/O. Peer-to-Peer and Modbus I/O PRODUCT INFORMATION B&B ELECTRONICS
Zlinx Wireless Modbus I/O-0712ds page 1/5 Modular, Customizable Wire Replacement 128 / 256 Bit AES Encryption Software Selectable RF Transmit Power Software Selectable Over-the-air Data Rate Modbus ASCII
More informationBAC-IO9 BACnet MS/TP Input / Output Modules, Wall Mounted
Product sheet MOD Type BAC-IO9 BAC-IO9 BACnet MS/TP Input / Output Modules, Wall Mounted BAC-IO9 and BAC-IO9-AI have been designed to be a compact wall mounted BACnet MS/TP input and output modules. The
More informationSoloist. Position Controller and Servo Amplifier PWM. Single axis digital servo controller with integral power supply and amplifier
Soloist Position Controller and Servo Amplifier PWM Single axis digital servo controller with integral power supply and amplifier Advanced software architecture shortens customer development time; use
More informationH7625A, H7635A, H7626A, H7636A Series 2000 Humidity/Temperature Sensors
H765A, H765A, H766A, H766A Series 000 Humidity/Temperature Sensors WALL-MOUNT MODELS INSTALLATI INSTRUCTIS APPLICATI The H765A, H766A, H765A and H766A Wall-Mount Humidity/Temperature Sensors are universal
More informationFC Series Signal Conditioners
FC Series Signal Conditioners FC-33 DC Selectable Signal Conditioner with 3-way isolation Field configurable input and output ranges of 0-5V, 0-10 V, 0-20 ma and 4-20 ma with 1500 VDC isolation between
More informationPMAC770 Multifunction Power Meter. Installation & Operation Manual V2.0 ZHUHAI PILOT TECHNOLOGY CO., LTD.
PMAC770 Multifunction Power Meter Installation & Operation Manual V2.0 ZHUHAI PILOT TECHNOLOGY CO., LTD. Danger and warning! This device can be installed only by professionals. The manufacturer shall not
More informationExcel 15 S7760A COMMAND DISPLAY
Excel 15 S7760A MAND DISPLAY INSTALLATION INSTRUCTIONS PRODUCT DESCRIPTION The S7760A Command can be used to monitor and control H equipment, lighting, and other miscellaneous loads in a distributed network.
More informationHigh Performance Process & Temperature Controllers
C22 C62 C82 C83 High Performance Process & Temperature Controllers C72 C42 R22 01. Multi Color LCD Display 02. High Accuracy 18 Bit A-D Input and 15 Bit D-A Output 03. 200 msec Sampling Rate 04. True Universal
More informationTC 204 Heating Controller
TC 204 Heating Controller ver. 1.32-01 The TC204 is a multi-purpose heating controller with built-in programs for different types of heating systems. General Data Power requirement 24 volts ac, 2 va Inputs
More informationThe wireless alternative to expensive cabling...
The wireless alternative to expensive cabling... ELPRO 105U ISO 9001 Certified New Products... New Solutions The ELPRO 105 range of telemetry modules provide remote monitoring and control by radio or twisted-pair
More informationVFSC9 ELECTRONIC SPEED CONTROLLER. Mounting and operating instructions
ELECTRONIC SPEED CONTROLLER Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 5 WIRING
More informationLAUREL ELECTRONICS, INC.
LAUREL ELECTRONICS, INC. Laureate True RMS AC Voltage & Current Meter with 1 Cycle Update at 50/60 Hz Features True AC or AC plus DC RMS measurement with crest factor of 3.0 at FS Fast response: reading
More informationCoMo Injection/CoMo Injection Basic
Electronics & Software CoMo Injection/CoMo Injection Basic Zero-Defect Production during Injection Molding thanks to Process Monitoring Type 2869B CoMo Injection is a production optimization, control and
More informationECB-103 BACnet B-ASC 10-Point Programmable Controllers
D a t a s h e e t BACnet B-ASC 10-Point Programmable Controllers Overview The is a microprocessor-based programmable controller designed to control terminal units such as fan coil unit, heat pump unit,
More informationWireless Room Temperature and Humidity Transmitter (Units without Temperature Setpoint or Override) Installation and Operating Instructions
Wireless Temperature and Humidity Overview and Indentification The Wireless Temperature and Humidity measures the room temperature and Relative Humidity and transmits the data at 418MHz or 433MHz RF to
More informationCoMo Injection/CoMo Injection Basic
Electronics & Software CoMo Injection/CoMo Injection Basic Zero-Defect Production during Injection Molding thanks to Process Monitoring Type 2869B CoMo Injection is a production optimization, control and
More informationPEAKTRONICS AMI-103. AC Motor Interface AMI-103 AMI-103A AMI-103B FEATURES
PEAKTRONICS The Peaktronics AC Motor Interface is used to interface common electrical control signals to AC actuators. The unit provides the motor drive circuits, protection circuits, and isolation between
More informationPROCESS & TEMPERATURE CONTROLLERS
PROCESS & TEMPERATURE CONTROLLERS NOVA PD54 Series Thermocouple, RTD, & Process Inputs High Accuracy Auto-Tuning PID Heating & Cooling Models Universal Power Supply 1-24 VAC Up to 3 Relays & 2 Analog Outputs
More informationLK Wireless Room Control Cq
LK Wireless Room Control Cq Description LK Wireless Room Control Cq consists of a LK Room Thermostat Cq-n (transmitter) and a LK Receiver Unit Cq 8 (8 channel receiver unit). The range also includes a
More informationNetBiter I/O Extender 4RO 6RTD 8DIO - DAIO User Manual Revision 1.00
NetBiter I/O Extender 4RO 6RTD 8DIO DAIO User Manual Revision 1.00 IntelliCom Innovation AB Linjegatan 3D SE302 50 Halmstad SWEDEN Phone +46 35 18 21 70 Fax +46 35 18 21 99 email info@intellicom.se www
More informationPowerFlex 400 AC Drive Guide Specification
PowerFlex 400 AC Drive Guide Specification Adjustable Frequency Drives 3.0 50HP @ 200 to 240V AC 3.0 350HP @ 380 to 480V AC PART 1 GENERAL 1.01 Quality Assurance A. The manufacturer shall have minimum
More informationDesign Characteristics. FlexDrive II. Series
AC AC DC DC FlexDrive II Series Design Characteristics Brushless AC Servo Baldor s FlexDrive II series are designed to provide reliable and durable operation. Options are available to operate either resolver
More informationSX (690 V) System configuration
SX (690 V) High performance Vector Control IP54 full range Compact design & Robustness Built-in Filter according to C3 Class Built-in Fuses (From 200 kw) Safety according EN13849-1 and EN62061 standards
More informationVariable Frequency Drives
Table of Contents Variable Frequency Drives Product Product Code Resource Documents Page # Introduction F-3 SED2 154-042 F-5 with Conventional Bypass Option SED2 154-044 F-9 with Electronic (E) Bypass
More informationData sheet CPU 313SC (313-5BF13)
Data sheet CPU 313SC (313-5BF13) Technical data Order no. Type 313-5BF13 CPU 313SC General information Note - Features SPEED-Bus - SPEED7 technology 24 x DI, 16 x DO, 4 x AI, 2 x AO, 1 x AI Pt100 128 kb
More informationProgrammable transmitter of temperature, relative humidity and other derived humidity values with 4-20 ma outputs Instruction Manual
T3110 TRANSMITTER Programmable transmitter of temperature, relative humidity and other derived humidity values with 4-20 ma outputs Instruction Manual Instruction manual for use of T3110 transmitter Transmitter
More informationDigital Room Sensor Technical Guide
www.orioncontrols.com Digital Room Sensor Technical Guide TABLE OF CONTENTS OVERVIEW... 3 BASIC OPERATION... 4 Sensor Operation... 4 LED Operation... 4 MOUNTING AND WIRING... 5 Environmental Requirements...
More informationMULTIFUNCTION GRAPHICAL UNIT MGU 800
MULTIFUNCTION GRAPHICAL UNIT MGU 800 For display, recording and evaluation of process instruments signals (level, temperature, pressure, etc.) 3.5" TFT display, multi-language menu Variety of possible
More informationOperation. Displayed channel. Measuring range. Status indication/ remote control Key lock Measuring mode/ time constant. Scale.
Electronics & Software Type 5080A... Multichannel Laboratory This universal laboratory charge amplifier can be used for force and torque measurements with piezoelectric dynamometers or force plates. Piezoelectric
More information3DM phase Digital Stepper Drive
3DM2283 3-phase Digital Stepper Drive 150-220VAC, 0.5-8.2A peak, Auto-configuration, Low Noise Anti-Resonance provides optimal torque and nulls mid-range instability Motor auto-identification and parameter
More informationRelay Driver Overview and Applications
Relay Driver Overview and Applications Describes Basic and Advanced Settings for common and alternative/novel uses for the Relay driver (RD-1). Morningstar s Relay Driver (RD-1) is a fully programmable
More informationExcellent low-cost Process & Temperature Controllers
C22 C62 C82 C83 Excellent low-cost Process & Temperature Controllers C72 C42 R22 01. High Quality LCD Display 02. High Accuracy 18 Bit A-D Input and 15 Bit D-A Output 03. The Fast Sampling Rate in 200
More informationProduct type designation. General information. Hardware product version 01. Firmware version V2.6. Engineering with. update.
6ES7313-6CF03-0AB0 SIMATIC S7-300, CPU 313C-2DP COMPACT CPU WITH MPI, 16 DI/16 DO, 3 FAST COUNTERS (30 KHZ), INTEGRATED DP INTERFACE, INTEGRATED 24V DC POWER SUPPLY, 64 KBYTE WORKING MEMORY, FRONT CONNECTOR
More informationCD-Pxx-00-0 Series Duct Mount CO 2 Transmitter
Installation Instructions CD-Pxx-00-0 Issue Date February 4, 006 CD-Pxx-00-0 Series Duct Mount CO Transmitter Application Requirements FCC Compliance Statement This equipment has been tested and found
More informationOcean Controls KT-5221 Modbus IO Module
Ocean Controls Modbus IO Module 8 Relay Outputs 4 Opto-Isolated Inputs 2 Analog Inputs (10 bit) 1 PWM Output (10 bit) 4 Input Counters Connections via Pluggable Screw Terminals 0-5V or 0-20mA Analog Inputs,
More informationSystem configuration. Ratings 400 V Class three-phase 90 to 800 kw 690 V Class three-phase 90 to 1000 kw SX-D. Frequency inverters.
~ ~ SX High performance Vector Control IP54 full range. Compact design & Robustness Built-in Filter according to C3 Class Built-in Fusses (From 200 kw) Safety according EN13849-1 and EN62061 standards
More informationInverter Drive /Vector Drive Motors & Controls
H2 Inverter/ Encoderless Vector Inverter Drive /Vector Drive & Controls 3/4 thru 50 180-264 VAC 3 Phase - 50/60 Hz 3/4 thru 60 340-528 VAC 3 Phase - 50/60 Hz 3/4 thru 60 515-660 VAC 3 Phase - 60 Hz HVAC
More informationTROVIS 5500 Automation System TROVIS 5578 Heating and District Heating Controller. Mounting and Operating Instructions EB 5578 EN
TROVIS 5500 Automation System TROVIS 5578 Heating and District Heating Controller Mounting and Operating Instructions EB 5578 EN Firmware version 2.2x Edition May 2015 Definition of signal words DANGER!
More informationTemperature Controller model MFC-301/T-Dry. Version for Dry Transformers and Motors. Technical Manual. Licht
Temperature Controller model MFC-301/T-Dry Version for Dry Transformers and Motors Technical Manual Licht Contents 1 Introduction 2 2 Operating principle 3 2.1 General principle 3 2.2 RTD operation 3 3
More informationDO NOT USE UNIT POWER
Wiring Basics General Rules Use Dedicated Power with Networked Systems DO NOT USE UNIT POWER Use Separate Power for all Relays Both of these precautions help eliminate the potential for noise on the communication
More informationData sheet CPU 314ST/DPM (314-6CF02)
Data sheet CPU 314ST/DPM (314-6CF02) Technical data Order no. Type 314-6CF02 CPU 314ST/DPM General information Note - Features SPEED-Bus SPEED7 technology, SPEED-Bus 8 x DI, 8 x DIO, 4 x AI, 2 x AO, 1
More informationELECTRONIC THERMOSTAT: T920
μnistδt ELECTRONIC THERMOSTAT: T One analog output DESCRIPTION The T series thermostats are microcomputer-based, proportional and integral (PI) devices with one analog 0 to 0 output. They can be used with
More informationData Acquisition Modules/ Distributed IO Modules
User Manual Data Acquisition Modules/ Distributed IO Modules Future Design Controls, Inc. 7524 West 98 th Place / P.O. Box 1196 Bridgeview, IL 60455 888.751.5444 - Office: 888.307.8014 - Fax 866.342.5332
More informationData sheet CPU 013C (013-CCF0R00)
Data sheet CPU 013C (013-CCF0R00) Technical data Order no. 013-CCF0R00 Type CPU 013C Module ID - General information Note - Features SPEED7 technology 16 x DI, 12 x DO, 2 x AI, from which are 4 input channels
More informationAnalogue temperature controllers
Analogue temperature controllers CT8A Input by J-K thermo-couple or by thermo-resistance Pt 00 (-wire) regulation modes : ON/OFF or proportional derivative selected by wiring Relay output Specifications
More informationRISH Master 3430 DIGITAL MULTI-FUNCTION TRANSDUCER. Electro-Meters
measures important electrical parameters in phase and single phase etwork & replaces the multiple analog panel meters. It measures electrical parameters like AC current, Voltage, frequency, Power, Energy
More informationValve Island with Electronic I/O
Screw in Temperature /Switch with display for ON/OFF Control Indication, monitoring, transmission and ON/OFF control in one device Extra large display Menu guided parametrisation Complete communication
More informationZZxD-Nx-xR Series. Wireless Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION
Modular, Customizable Wire Replacement Modbus ASCII /RTU Compatible Wide Operating Temperature Active Repeater Functionality 10 to 48 VDC & 24 VAC Input Power Zlinx Wireless Modbus I/O - flexible enough
More informationSX (400 V) System configuration
~ ~ SX (400 V) High performance Vector Control IP54 full range. Compact design & Robustness Built-in Filter according to C3 Class Built-in Fuses (From 200 kw) Safety according EN13849-1 and EN62061 standards
More informationPULSE/FREQUENCY/CONDITIONER USER GUIDE
PULSE/FREQUENCY/CONDITIONER USER GUIDE D2560-02-02 CN5220 1600F USER GUIDE Page 1 of 13 PULSE/FREQUENCY/CONDITIONER USER GUIDE FREQUENCY INPUT PSU 1 2 + - SUPPLY (to4) Vdc (to32) Vac UNIVERSL Excitation
More informationTROVIS 5500 Automation System TROVIS 5578 Heating and District Heating Controller. Mounting and Operating Instructions EB 5578 EN
TROVIS 5500 Automation System TROVIS 5578 Heating and District Heating Controller Mounting and Operating Instructions EB 5578 EN Firmware version 2.30 Edition November 2017 Definition of signal words DANGER!
More informationElectro Controls. Input-Output Modules WattsIndustries.co.uk
Electro Controls Input-Output Modules - 2017 WattsIndustries.co.uk Input-Output Modules Section 08 B.M.S INPUT - OUTPUT MODULES SINGLE AND ADJUSTABLE RELAY ESRM.. Volt free contacts DIN RAIL mounted relay
More informationTable of Contents. HWIO-Gateway User Manual
User Manual HWIO-Gateway INUX AB Katrinedalsg. 3, 504 51 Borås http://www.inux.se Copyright 2009 Uppdaterad 2010-01-12 Copyright 2009 INUX AB 1 Table of Contents 1. Product overview...3 2. License...3
More informationPROMUX Distributed MODBUS I/O Modules Catalog and Design Guide
PROMUX Distributed MODBUS I/O Modules Catalog and Design Guide 14/11/2006 V10 P.O.Box 24 Stanfield 3613 SOUTH AFRICA Tel: +27 (031) 7028033 Fax: +27 (031) 7028041 Email: proconel@proconel.com Web: www.proconel.com
More informationInductive Sensors Single or Dual Loop Detectors Type LD with teach-in
Inductive Sensors Single or Dual Loop Detectors Type LD with teach-in Single or Dual loop detector Automatically adjustment of detection level Manual sensitivity for compensations of variations Easy installation
More informationPRELIMINARY DATA SHEET. RI-F400 Series. easywire Single and Three Phase Multifunction Energy Meter
Telephone : 44 (0) 1245 428500 PRELIMIARY DATA SHEET RIF400 Series easywire Single and Three Phase Multifunction Energy Meter DI 96 panel mounted 330mV Input from easywire CTs (or /1A and /5A current transformer
More informationPLA 33. Power line analyzer. User and service manual. version 2.4
PLA 33 Power line analyzer User and service manual version 2.4 Content. Front control panel and terminal plate...3 7.2.2. System frequency setting...0 2. Device description...4 7.2.3. Password protection...0
More informationvacon 100 flow ac drives application manual
vacon 100 flow ac drives application manual PREFACE VACON 3 PREFACE Document ID: DPD01083D Date: 15.10.2014 Software version: FW0159V010 ABOUT THIS MANUAL This manual is copyright of Vacon Plc. All Rights
More informationINTRODUCING SOME GREAT NEW PRODUCTS FROM OUR DWYER INSTRUMENTS RANGE:
Unit 1 / 14 Biscayne Way Jandakot WA 6104 P.O. Box 3232, Success WA 6964 Tel: (08) 9414 7666 Fax: (08) 9414 7677 Email: dg@dginstruments.com.au Website: www.dginstruments.com.au A.B.N: 59 113 005 959 DATE:
More information- Wiring Brochure Universal Reset Module 423e
- Wiring Brochure Universal Reset Module 4e W 4e 0/08 Information Brochure Choose controls to match application Application Brochure Design your mechanical applications Rough In Wiring Rough-in wiring
More informationBAPI-Stat 4 X-Combo, Room %RH and Temp. Sensor BA/BS4XC Installation & Operating Instructions
Overview and Identification The BAPI-Stat 4 X-Combo () Room Unit features 4 output channels and optional local indication of temperature and humidity. Additional options include Temperature Setpoint, Humidity
More informationSRC-110 Series Zone Controllers. BACnet MS/TP. Product sheet CT2.143 SRC-110-BAC
Product sheet CT2.143 Type SC-110-BAC SC-110 Series Zone Controllers with BACnet MS/TP The SC-110 series controllers have been designed for zone heating and cooling control. The controllers have 3 analogue
More informationSCADA and Telemetry Solutions. SCADALink IO900. Modular Wireless I/O System. User Manual Version V1.3 for SCADALink IO900 BENTEK SYSTEMS LTD
Modular Wireless I/O System User Manual Version V. for BENTEK SYSTEMS LTD #, 0 Ave S.E. Calgary, AB, Canada TB 0L Ph:(0) Fax:(0) email: sales@scadalink.com web: The is a Modular Wireless I/O System that
More informationInstruction. INFOCAL 8 Energy calculator. 1.0 Table of contents. 2.0 Safety notes and product information
Instruction INFOCAL 8 Energy calculator 1.0 Table of contents 1.0 Table of contents...1 2.0 Safety notes and product information...1 3.0 Installation of energy calculator...2 4.0 Installation of temperature
More informationHD 48V01T... HD 4977T...
RH-26 HD 4807T HD 4907T HD 48V07T HD 4901T... HD 4801T... HD 4917T... HD 48V01T... HD 4977T... HD 4817T... HD 48V17T... HD 4877T... HD 48V77T... HD 4807T, HD 48V07T, HD 48S07T, HD 4801T..., HD 48V01T...,
More information