269 Troubleshooting Guide 11/4/98 1

Size: px
Start display at page:

Download "269 Troubleshooting Guide 11/4/98 1"

Transcription

1 269 Troubleshooting Guide 11/4/98 1

2 Table of Contents Phase currents 3 Communications. 6 RTDs.. 9 Ground Fault Currents Output Relays. 15 Analog Output 17 Switch Inputs /4/98 2

3 Phase Currents Phase Current Specification Conversion: calibrated RMS, sample time 2ms range: 0.05 to 12 phase C.T. primary amps setpoint full scale: 12 phase C.T. primary amps setpoint accuracy: ± 0.5% of full scale (0.05 to 2 phase C.T. primary amps setpoint) ± 1.0% of full scale (over 2 phase C.T. primary amps setpoint) Frequency: Hz C.T. Burden Due to Connection of 269 Plus Relay CT INPUT BURDEN (AMPS) (VA) (m)ohms PHASE CT (1A) PHASE CT (5A) CT Thermal Withstand Phase CTs : 3 - continuous 6-40 sec 12-3 sec 11/4/98 3

4 Checking Phase Current The displayed phase current accuracy can examined using the following procedure: If motor is running, examine readings on relay display under Actual Values Page #1. The display will look as follows I1= XXXX I2= XXXX I3= XXXX (AMPS) --- Check to see if these currents are within the specification listed on the previous page. Attach a clamp-on current meter to the secondary of the CTs. With this value, we can ascertain what the primary current readings should be. The calculation is as follows: Displayed Current = Measured Secondary Current x (Phase CT Primary / Phase CT secondary) If the Phase currents displayed do not match what you have calculated, contact the Service Dept... for more info at (905) /4/98 4

5 Communications Serial Communication Link Wiring 11/4/98 5

6 Communications Type: RS485 2-wire, half duplex, isolated Baud Rate: 300, 1200, 2400 Protocol: Subset of Modbus RTU Functions: Read / Write setpoints (03/16) Read actual values (03/ 04) RS485 communications was chosen to be used with the 269 Plus because it allows communications over long distances of up to 4000 ft. However, care must be taken for it to operate properly and trouble free. The recommendations listed below must be followed to obtain reliable communications: a) A twisted, shielded pair (preferably a 24 gage Belden 9841 type or 120ohm equivalent) must be used, and routed away from power carrying cables, such as power supply and CT cables. b) No more than 32 devices (269 Plus's, PQM's, or any other non-multilin device that communicates using the same protocol) can co-exist on the same link. If however, more than 32 devices should be daisy chained together, a REPEATER must be used. The shields of all 269 Plus units should also be daisy chained together and grounded at the MASTER (PC/PLC) only. This is due to the fact that if shields are grounded at different points, a potential difference between grounds might exist, which can result in placing one or more 269 Plus transceiver chips (chip used for communications) in an unknown state, i.e... not receiving nor sending, and the corresponding 269 Plus communications might be erroneous, intermittent or unsuccessful. 11/4/98 6

7 c) Two sets of 120ohm/0. 25W resistor and 1nF/50V capacitor in series must be used (value matches the characteristic impedance of the line). One set at the 269 Plus end, connected between the positive and negative terminals (#46 & #47 on 269 Plus) and the second at the other end of the communications link. This is to prevent reflections and ringing on the line. If a different value resistor is used, it runs the risk of over loading the line and communications might be erroneous, intermittent or totally unsuccessful. d) It is highly recommended that connection from the 269 Plus communication terminals be made directly to the interfacing Master Device (PC/PLC/DCS), without the use of any stub lengths. This is also to minimize ringing and reflections on the line. Multilin SCI & F485 RS232/RS485 converters have been fully tested with the 269PLUS relay. Third party converters are available, however they may not function the same due to possible timing issues. The 269PLUS will allow you to address up to 254 slaves in Setpoints Page #5- Slave Address = x. This essential for the master to determine the device that it is communicating with. 11/4/98 7

8 RS485 Communications Failure Check Ensure that the 269PLUS is powered on. Check Slave Address on Setpoints Page #5. It must match the address that the master is trying to communicate with. Ensure the communication wiring is connected as shown on Page #3 and that no wires are loose or shorting out. The 232/485 converter must be showing the Transmit & DTR LED flashing. If not, no Data Packets are being received by the 269PLUS and there may be a problem with the Converter configuration or the Master configuration. The Master baud rate must be set at 2400 ( This is the default- contact factory if alternate baud rate is required) Ensure you are using a 10 Bit Data Packet with 1 start bit, 8 data bits, and one stop bit. If you are trying to communicate with a PLC or DCS, visit our website at for a list of PLCs we have interfaced with, as well as any other items required to achieve a successful connection. If none of the above suggestions provide a solution, contact Technical Support for more information at (905) /4/98 8

9 RTDs sensor types: RTD Inputs 10 OHM copper 100 OHM nickel 120 OHM nickel 100 OHM platinum (specified with order) display accuracy: ± 2 C trip/alarm setpoint range: C dead band: 3 C maximum lead resistance: 25% of RTD 0 C resistance RTD Connections 11/4/98 9

10 RTD Connections a) Use a 3 wire twisted, shielded pair to connect the RTDs from the motor to the 269 Plus. The shields should be connected to the proper terminals on the back of the 269 Plus. b) RTD shields are internally connected to the 269 Plus ground (terminal #42) and must not be grounded anywhere else. c) RTD signals can be characterized as very small, sensitive signals. Therefore, cables carrying RTD signals should be routed away from power carrying cables such as power supply and CT cables. d) If, after wiring the RTD leads to the 269 Plus, the RTD temperature displayed by the Relay is zero, then check for the following conditions: 1 - shorted RTD / cabling 2 - RTD hot and compensation leads are reversed, i.e. hot lead in compensation terminal and compensation lead in hot terminal. 3 - There is no compensation lead connected. (I.e- only using a hot and return wire) ******If two wires are to be used with the RTDs, there must be a jumper placed from the Return to the Compensation. This type of connection is not recommended for 10Cu RTDs. 11/4/98 10

11 RTD Measurements Test The correct operation of each of the RTD inputs can be tested by simulating RTDs with potentiometers. To test a 269 Plus relay configured for use with 100 OHM platinum RTDs, 100 OHM potentiometers and resistors can be used. These should be connected to each RTD as shown below. Page #12 shows RTD resistance for various temperatures. Individual, actual stator and bearing RTD temperatures can be viewed in ACTUAL VALUES mode, page 2. Viewing RTD temperatures on this page, requires a period of 11 secs. to update the screen with the temperature. To force the 269 to read a specific RTD, without the delay, use setpoint Page #6. Once at that page, press the Line down key until you see the following: TEMPERATURE = XXXXXXXXXXXXX FORCED RTD # X Press the value up key until the desired RTD is shown. To test overtemperature trip/alarm functions the simulated RTD potentiometers should be adjusted to correspond to high RTD temperatures. Stator RTD Voting in Setpoint Values page 5 should be defeated first. This allows for individual trip/alarm overtemperature reading. 11/4/98 11

12 11/4/98 12 TEMP C OHMS 100 OHM Pt (DIN 43760) OHMS 120 OHM Ni OHMS 100 OHM Ni OHMS 10 OHM Cu

13 Ground Fault Input Ground Fault Specifications conversion: calibrated RMS, sample time 2ms range: 0.1 to 1.0 G/F C.T. primary amps setpoint (5 Amp secondary C.T.) 1.0 to 10.0 amps, 50:0.025A (2000:1 ratio) full scale: 1 G/F C.T. primary amps setpoint (5 Amp secondary C.T.) 10 amps (2000:1 C.T.) accuracy: ± 4% of G/F C.T. primary amps setpoint (5 Amp secondary C.T.) ± 0.3 amps primary (2000:1 C.T.) Frequency: Hz C.T. Burden Due to Connection of 269 Plus Relay CT INPUT BURDEN (AMPS) (VA) (m) G/F CT (5A) G/F CT (50:0.025) CT Thermal Withstand Ground Fault CT 5 amp tap: 3 - continuous 6-40 sec 12-3 sec G/F (2000:1): 6 - continuous 11/4/98 13

14 Checking Ground Fault Input Examine readings on relay display under Actual Values Page #1. The display will look as follows GROUND FAULT CURRENT G/F = XX.X AMPS Check to see if this current is within the specification listed on the previous page. Attach a clamp-on current meter to the secondary of the CTs. With this value, we can ascertain what the primary current readings should be. The calculation is as follows: Displayed Current = Measured Secondary Current x (Ground Fault CT Primary / Ground Fault CT secondary) If the Ground Fault current displayed does not match what you have calculated, contact the Service Dept... for more info at (905) /4/98 14

15 Output Relays Relay Contacts VOLTAGE MAKE/CARRY MAKE/CARRY BREAK CONTINUOUS 0.2 sec 30 VDC RESISTIVE 125 VDC VDC VDC INDUCTIVE 125 VDC (L/R=7ms) 250 VDC RESISTIVE 120 VAC VAC INDUCTIVE 120 VAC PF= VAC CONFIGURATION FORM C NO/NC CONTACT MATERIAL SILVER ALLOY MINIMUM PERMISSIBLE LOAD: 5 VDC, 100 ma 12 VAC, 100 ma 11/4/98 15

16 Testing Output Relays To test the operation of the 269 Plus output relays and the switchgear connected to them the "EXERCISE: XXXXX RELAY" setpoint in page 6 of SETPOINTS mode can be used. The motor must be stopped in order for this function to operate. Any or all of the output relays can be toggled using this setpoint. Press The SETPOINTS Page #6 key, then press PAGE down until you see the following message: PAGE 6 : SETPOINT VALUES MULTILIN SERVICE CODES Press the LINE down until the following message is shown: EXERCISE RELAY: XXXXXXXX Press the VALUE up key until the required relay is shown, then press the STORE key. This will cause the selected output relay to change state, along with the corresponding LED indicator. This process can be repeated for all relays. ******** This test should be performed with an ohmmeter connected across the output contacts to verify the expected operation** 11/4/98 16

17 Analog Output Analog Current Output PROGRAMMABLE OUTPUT 0-1 ma 0-20 ma 4-20 ma MAX LOAD MAXOUTPUT 1.01mA 20.2mA 20.2mA accuracy: ± 1% of full scale reading polarity: terminal 58 ("-") must be at ground potential (i.e.. output is not isolated) Isolation: non-isolated, active source Update time: 250 msec max. Analog Output Testing To test the operation of the 269 Plus analog output and the devices connected to them the "Analog Out Forced" setpoint in page 6 of SETPOINTS mode can be used. *****This may cause a trip, depending on your configuration. Connect a DC Ammeter to terminals 58 & 59. Press The SETPOINTS Page #6 key, then press PAGE down until you see the following message: PAGE 6 : SETPOINT VALUES MULTILIN SERVICE CODES Press the LINE down until the following message is shown: ANALOG OUT FORCED: TO: XXXXX SCALE Press the VALUE up key until the required scale is shown, then press the STORE key. This will cause the selected scale of output current to energize. This process can be repeated for all scales. ******** This test can be performed with an ammeter connected across the output terminals to verify the output current********* 11/4/98 17

18 Switch Inputs The 269Plus relay has 6 dry contact inputs To test the operation of the 269 Plus switch inputs and the connected equipment, the "Status = xxxxxx" setpoint in page 6 of SETPOINTS mode can be used. *****This may cause a trip if the motor is running Connect a switch or a short across the inputs you wish to check. Press The SETPOINTS Page #6 key, then press PAGE down until you see the following message: PAGE 6 : SETPOINT VALUES MULTILIN SERVICE CODES Press the LINE down until the following message is shown: STATUS = XXXXXXXX FOR: XXXXX SWITCH Press the VALUE up key until the required input is shown. This will allow you to view the status of the hardware inputs. This process can be repeated for all inputs. If there is no response to the shorting of an input (i.e.- Short), verify the terminals that are shorted. If problem still persists, contact the factory at (905) /4/98 18

19 Visit our website for further information at 11/4/98 19

1 INTRODUCTION ORDER CODE / INFORMATION

1 INTRODUCTION ORDER CODE / INFORMATION INTRODUCTION ORDER CODE / INFORMATION 269/269Plus * * * * * * 269/269Plus SV D/O.4 ORDER CODE / INFORMATION Motor management relay Standard version Drawout version Phase CT Ground CT (required for D/O

More information

MOTOR PROTECTION RELAY. Instruction Manual. GE Power Management

MOTOR PROTECTION RELAY. Instruction Manual. GE Power Management g GE Power Management 239 MOTOR PROTECTION RELAY Instruction Manual 239 Motor Protection Relay Firmware Revision: 2.6x 239PC Software: 2.6x or newer Manual P/N: 1601-0060-D9 Copyright 2002 GE Multilin

More information

g GE POWER MANAGEMENT

g GE POWER MANAGEMENT 469 FREQUENTLY ASKED QUESTIONS 1 Can not communicate through the front port RS232 Check the following settings Communication port on your computer ( com1, com2 com3 etc ) Parity settings must match between

More information

current transformers or VAC secondary voltage from our SIGNAL CONVERTERS Selection Chart

current transformers or VAC secondary voltage from our SIGNAL CONVERTERS Selection Chart NK Technologies ADC series signal converters use sensor outputs (4 0 ma, 0 5 and 0 10 VDC) and convert these to digital RS485 outputs. The CTC series accept either 5 A secondary current from Analog to

More information

MOTOR MANAGER RELAY INSTRUCTION MANUAL. Copyright 1993 Multilin All Rights Reserved. The 301 is CSA approved. 215 Anderson Avenue 9746 Whithorn Dr.

MOTOR MANAGER RELAY INSTRUCTION MANUAL. Copyright 1993 Multilin All Rights Reserved. The 301 is CSA approved. 215 Anderson Avenue 9746 Whithorn Dr. 301 MOTOR MANAGER RELAY INSTRUCTION MANUAL Software Rev: 301.D1.20 Manual P/N: 1601-0014-D4 Copyright 1993 Multilin All Rights Reserved The 301 is CSA approved. CANADA USA Multilin Multilin Division of

More information

VersaPoint I/O Module

VersaPoint I/O Module Module provides two-input channels for resistive temperature sensors. It supports platinum or nickel sensors according to the DIN standard and SAMA Directive. In addition, CU10, CU50, CU53, KTY81 and KTY84

More information

A Super trainer with advanced hardware and software features only found in very expensive equipment.

A Super trainer with advanced hardware and software features only found in very expensive equipment. PLC Trainer PTS T100 LAB EXPERIMENTS A Super trainer with advanced hardware and software features only found in very expensive equipment. You won t find any similar equipment among our competitors at such

More information

NetBiter I/O Extender 4RO 6RTD 8DIO - DAIO User Manual Revision 1.00

NetBiter I/O Extender 4RO 6RTD 8DIO - DAIO User Manual Revision 1.00 NetBiter I/O Extender 4RO 6RTD 8DIO DAIO User Manual Revision 1.00 IntelliCom Innovation AB Linjegatan 3D SE302 50 Halmstad SWEDEN Phone +46 35 18 21 70 Fax +46 35 18 21 99 email info@intellicom.se www

More information

MM200 Motor Management System

MM200 Motor Management System Title page Digital Energy Multilin MM200 Motor Management System Low voltage motor protection and control QuickStart Guide MM200 revision: 1.1x Manual P/N: 1601-9030-A3 GE publication code: GEK-113401B

More information

sw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS

sw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS INSTRUCTIONS MANUAL IM831-U v0.92 HRI-R40W sw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS INDEX: GENERAL TYPES ACESSORIES AND OPTIONS

More information

Data Acquisition Modules/ Distributed IO Modules

Data Acquisition Modules/ Distributed IO Modules User Manual Data Acquisition Modules/ Distributed IO Modules Future Design Controls, Inc. 7524 West 98 th Place / P.O. Box 1196 Bridgeview, IL 60455 888.751.5444 - Office: 888.307.8014 - Fax 866.342.5332

More information

RTD Input Module. Product Specifications and Installation Data 1 DESCRIPTION 2 INSTALLATION

RTD Input Module. Product Specifications and Installation Data 1 DESCRIPTION 2 INSTALLATION RTD Input Module Product Specifications and Installation Data 1 DESCRIPTION The HE693RTD720 Input Modules allow RTD temperature sensors to be directly connected to the PLC without external signal processing

More information

NO WARRANTIES OF ANY KIND ARE IMPLIED ON THE INFORMATION CONTAINED IN THIS DOCUMENT.

NO WARRANTIES OF ANY KIND ARE IMPLIED ON THE INFORMATION CONTAINED IN THIS DOCUMENT. MODBUS/BECO2200-M3425A Communication Data Base for M-3425A Integrated Protection System Device I.D. = 150 Specifications presented herein are thought to be accurate at the time of publication but are subject

More information

489 Generator Management Relay Instruction Manual

489 Generator Management Relay Instruction Manual Digital Energy Multilin Firmware Revision: 4.0X Manual Part Number: 1601-0150-AF Manual Order Code: GEK-106494P Copyright 2011 GE Multilin 489 Generator Management Relay Instruction Manual GE Multilin

More information

Improve asset protection and utilization

Improve asset protection and utilization QUALITROL 509 ITM Intelligent transformer monitor Improve asset protection and utilization Immediately know your transformer health with TransLife Optimize loading and equipment life Simplify root cause

More information

INSTRUCTIONS MANUAL DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS HRI-R40W

INSTRUCTIONS MANUAL DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS HRI-R40W Page 2 / 16 INDEX: GENERAL TYPES ACESSORIES AND OPTIONS INSTALLATION WIRING DIAGRAMS CONNECTING TERMINALS DIAGRAMS WIRING DIAGRAM DESCRIPTION WORKING DESCRIPTION AND KEYBOARD WORKING DESCRIPTION AND PROGRAMMING

More information

Advanced, accurate and intelligent monitoring for your transformer

Advanced, accurate and intelligent monitoring for your transformer QUALITROL 505 ITM Intelligent transformer monitor Advanced, accurate and intelligent monitoring for your transformer The power to know your transformer health immediately with TransLife Advanced thermal

More information

PROMUX Distributed MODBUS I/O Modules Catalog and Design Guide

PROMUX Distributed MODBUS I/O Modules Catalog and Design Guide PROMUX Distributed MODBUS I/O Modules Catalog and Design Guide 12/03/2012 V11.0 P.O.Box 164 Seven Hills 1730 NSW AUSTRALIA Tel: +61 2 96248376 Fax: +61 2 9620 8709 Email: proconel@proconel.com Web: www.proconel.com

More information

Ocean Controls KT-5221 Modbus IO Module

Ocean Controls KT-5221 Modbus IO Module Ocean Controls Modbus IO Module 8 Relay Outputs 4 Opto-Isolated Inputs 2 Analog Inputs (10 bit) 1 PWM Output (10 bit) 4 Input Counters Connections via Pluggable Screw Terminals 0-5V or 0-20mA Analog Inputs,

More information

FC-33, DC SELECTABLE SIGNAL CONDITIONER

FC-33, DC SELECTABLE SIGNAL CONDITIONER FC-33, DC SELECTABLE SIGNAL CONDITIONER Description. The FC-33 is a DIN rail or side mount, selectable input/output signal conditioner with 1500VDC isolation between input and output, and 1500VDC isolation

More information

PROMUX Distributed MODBUS I/O Modules Catalog and Design Guide

PROMUX Distributed MODBUS I/O Modules Catalog and Design Guide PROMUX Distributed MODBUS I/O Modules Catalog and Design Guide 14/11/2006 V10 P.O.Box 24 Stanfield 3613 SOUTH AFRICA Tel: +27 (031) 7028033 Fax: +27 (031) 7028041 Email: proconel@proconel.com Web: www.proconel.com

More information

LAUREL ELECTRONICS, INC.

LAUREL ELECTRONICS, INC. LAUREL ELECTRONICS, INC. Laureate True RMS AC Voltage & Current Meter with 1 Cycle Update at 50/60 Hz Features True AC or AC plus DC RMS measurement with crest factor of 3.0 at FS Fast response: reading

More information

489 Generator Management Relay

489 Generator Management Relay GE Grid Solutions 489 Generator Management Relay Instruction Manual Product version: 4.0x GE publication code: 1601-0150-AM (GEK-106494W) 1601-0150-AM Copyright 2016 GE Multilin Inc. All rights reserved.

More information

Multimeter 500CVD21 RTU500 series

Multimeter 500CVD21 RTU500 series Remote Terminal Units - Data sheet Multimeter 500CVD21 RTU500 series CT/VT interface with 4 voltage and 24 current inputs for direct monitoring of 3/4 wire 0 300 V AC (line to earth), 0...500 V AC (phase

More information

Line-to-line RMS Volts, 3 phases 4 digits (XXX.X) Volts

Line-to-line RMS Volts, 3 phases 4 digits (XXX.X) Volts digital ac POWER MONITOR DESCRIPTION The DSP is a three-phase, three-element multifunction digital transducer with outputs for voltage, current, and power via serial communication. Applications include

More information

DRG-SC Series Signal Conditioners

DRG-SC Series Signal Conditioners DRG-SC Series Signal Conditioners DRG-SC Series 245 Basic unit Models Available for Thermocouples, RTDs, DC Voltage and Current, Frequency, Strain Gage Bridge, AC Voltage and Current Field Configurable

More information

DSCL, DSCP, SCTP. Industrial Loop Isolators and Transmitters DSCL, DSCP, SCTP. Industrial Loop Isolators and Transmitters

DSCL, DSCP, SCTP. Industrial Loop Isolators and Transmitters DSCL, DSCP, SCTP. Industrial Loop Isolators and Transmitters Industrial Loop Isolators and Transmitters DSCL,, SCTP DSCL,, SCTP Industrial Loop Isolators and Transmitters Description Dataforth s DSCL,, and SCTP series of products is a complete family of loop and

More information

WATT TRANSDUCER. Instruction Manual

WATT TRANSDUCER. Instruction Manual WT 9200 WATT TRANSDUCER Instruction Manual IM-2 September 2003 USA: 6428 Ridglea Drive, Watauga, Texas 76148 Tel/Fax 1-817-427-2060/2067 E-mail: wes@westecinstruments.com SPECIFICATIONS Power Supply Input

More information

MM200 Motor Management System

MM200 Motor Management System Digital Energy Multilin MM200 Motor Management System Low voltage motor protection and control QuickStart Guide MM200 revision: 1.2x Manual P/N: 1601-9030-A6 GE publication code: GEK-113401E Copyright

More information

PACSystems* RX3i IC695ALG600-DD

PACSystems* RX3i IC695ALG600-DD November 2012 The PACSystems * Universal Analog Input module IC695ALG600 provides eight general purpose input channels and two Cold Junction Compensation (CJC) channels. Inputs are divided into two equal

More information

PACSystems* RX3i IC695ALG600

PACSystems* RX3i IC695ALG600 July 2010 PACSystems* RX3i IC695ALG600 The PACSystems * Universal Analog Input module IC695ALG600 provides eight general purpose input channels and two Cold Junction Compensation (CJC) channels. Inputs

More information

MINI 048 / JUN 2003 PAGE 1. Temperature I/O Module HE500OCS048 / HE500OCS078 HE500RCS078

MINI 048 / JUN 2003 PAGE 1. Temperature I/O Module HE500OCS048 / HE500OCS078 HE500RCS078 MINI 048 / 078 07 JUN 2003 PAGE 1 Temperature I/O Module HE500OCS048 / HE500OCS078 HE500RCS078 Mini OCS/RCS 1 SPECIFICATIONS Relay Outputs Number of Channels 2 N.O. Relays Maximum Load Current (resistive)

More information

Isolated RTD Modules Product Specifications and Installation Data

Isolated RTD Modules Product Specifications and Installation Data Isolated RTD Modules Product Specifications and Installation Data 1 DESCRIPTION The Horner APG Isolated Resistance Temperature Detector (RTD) Input Modules allow RTD temperature sensors to be directly

More information

DO NOT USE UNIT POWER

DO NOT USE UNIT POWER Wiring Basics General Rules Use Dedicated Power with Networked Systems DO NOT USE UNIT POWER Use Separate Power for all Relays Both of these precautions help eliminate the potential for noise on the communication

More information

MM2 STOP. MOTOR MANAGER 2 Instruction Manual. GE Industrial Systems

MM2 STOP. MOTOR MANAGER 2 Instruction Manual. GE Industrial Systems g GE Industrial Systems MM2 MOTOR MANAGER 2 Instruction Manual MM2 Firmware Revision: 5.2x MM2 Software Revision: 5.2x or newer Manual P/N: 1601-0056-DS (GEK-106294D) Copyright 2007 GE Multilin RUNNING

More information

Microprocessor Control Board Set Up Procedures (OR PLC)

Microprocessor Control Board Set Up Procedures (OR PLC) Microprocessor Control Board Set Up Procedures (OR-00 PLC) SWITCHES/PUSHBUTTONS Push Buttons at display SW Enter button SW Back button SW Down SW UP Back light on/off switch Rotary switches on main board

More information

T E L I S T E L I S reinvents conversion and transmission of measures

T E L I S T E L I S reinvents conversion and transmission of measures T E L I S 9000 T E L I S reinvents conversion and transmission of measures Its graphic screen display, and its joystick make user-frendly and easily programmable device. Its USB front face plug enables

More information

PACSystems* RX3i. Isolated RTD Input Module, 8 Channels, IC695ALG508-CA. Module Features. GFK-2501C November 2012

PACSystems* RX3i. Isolated RTD Input Module, 8 Channels, IC695ALG508-CA. Module Features. GFK-2501C November 2012 November 2012 PACSystems* RX3i Isolated RTD Input Module, 8 Channels, IC695ALG508-CA Isolated RTD Input module IC695ALG508 provides eight isolated differential RTD input channels. Each channel can be individually

More information

745 Transformer Protection System Communications Guide

745 Transformer Protection System Communications Guide Digital Energy Multilin 745 Transformer Protection System Communications Guide 745 revision: 5.20 GE publication code: GEK-106636E GE Multilin part number: 1601-0162-A6 Copyright 2010 GE Multilin GE Multilin

More information

RISH EM 3490 SS Kilowatt Hour Energy Meter With Rs485 RISH EM 3490 SS. Application : Product Features: Indication: Pulse Indication:

RISH EM 3490 SS Kilowatt Hour Energy Meter With Rs485 RISH EM 3490 SS. Application : Product Features: Indication: Pulse Indication: Application : RISH Master 3490 SS is a 96mm x 96mm panel mounted kilowatt hour meter it measures active energy with class 1.0 accuracy having auto-resetting 8 digit seven segment LED counter. The unit

More information

BU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on supply lines for medical locations ISOLTESTER-DIG-RZ/RS/PLUS

BU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on supply lines for medical locations ISOLTESTER-DIG-RZ/RS/PLUS INSTRUCTION MANUAL BU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on supply lines for medical locations ISOLTESTER-DIG-RZ/RS/PLUS 1/23 More information than that reported

More information

RRTD - Remote RTD Module Instruction Manual

RRTD - Remote RTD Module Instruction Manual GE Grid Solutions RRTD - Remote RTD Module Instruction Manual RRTD Revision: 59CMB151.000 Manual P/N: 1601-0104-BA Copyright 2017 GE Multilin Inc.. All rights reserved. GE Multilin RRTD - Remote RTD Module

More information

MICROPROCESSOR-BASED METERING EQUIPMENT SECTION 16901C PART 2

MICROPROCESSOR-BASED METERING EQUIPMENT SECTION 16901C PART 2 PART 1 PART 2 PRODUCTS 2.01 MANUFACTURERS A. Eaton products B.. C.. The listing of specific manufacturers above does not imply acceptance of their products that do not meet the specified ratings, features

More information

VARIO RTD 2. Function. I/O Extension Module With Two Analog Input Channels for the Connection of Temperature Shunts (RTD) User Manual

VARIO RTD 2. Function. I/O Extension Module With Two Analog Input Channels for the Connection of Temperature Shunts (RTD) User Manual I/O Extension Module With Two Analog Input Channels for the Connection of Temperature Shunts (RTD) User Manual 02/2003 # % # # This data sheet is only valid in association with the documents of the used

More information

Industrial Modbus I/O Modules

Industrial Modbus I/O Modules Industrial Modbus I/O Modules Modbus I/O Modules Introduction & Features Digital Input / Output Modules Analog Input / Output Modules Modbus I/O Modules The Best Choice For Your SCADA Applications Introduction

More information

SLU SERIES Universal Phase Monitor/Relay SLU-100-ASA and SLU-100-ASD

SLU SERIES Universal Phase Monitor/Relay SLU-100-ASA and SLU-100-ASD SLU SERIES Universal Phase Monitor/Relay SLU-100-ASA and SLU-100-ASD Plug-In MILLIMETERS DIN Rail DESCRIPTION Phase Monitor Relays (3-Phase Monitors) provide cost-effective protection against premature

More information

DUAL OUTPUT AC CURRENT/VOLTAGE TRANSDUCER

DUAL OUTPUT AC CURRENT/VOLTAGE TRANSDUCER OPERATOR S MANUAL DUAL OUTPUT AC CURRENT/VOLTAGE TRANSDUCER Masibus Automation & Instrumentation Pvt. Ltd. B/30, GIDC Electronics Estate, Sector-25, Gandhinagar-382044, Gujarat, India Web Site: www..com

More information

PACSystems* RX3i IC695ALG600-EE Universal Analog Input Module

PACSystems* RX3i IC695ALG600-EE Universal Analog Input Module June 2017 The PACSystems Universal Analog Input module IC695ALG600 provides eight general purpose input channels and two Cold Junction Compensation (CJC) channels. Inputs are divided into two equal groups

More information

ioselect Z-NET Z-4RTD 4 Channel RTD Input Module

ioselect Z-NET Z-4RTD 4 Channel RTD Input Module 4 Channel nput Module : PT00, PT000, PT500 & N00: 2, 3 & 4 wire 500 V solation, 6-way Modbus Communications Adjustable Sampling Time Accuracy to 0.2 C Configuration and Setup Software EC 63 Flexible Power

More information

Instruction Manual. Description Calibration. Excitation Sensor and Reverse Power Relay

Instruction Manual. Description Calibration. Excitation Sensor and Reverse Power Relay Publication 351-05028-00, 05/11/05 Instruction Manual Description Calibration Excitation Sensor and Reverse Power Relay 511-00820-01 511-00820-02 Page 1 Kato Engineering Inc. P.O. Box 8447 Mankato, MN

More information

UL CONDITIONS OF ACCEPTABILITY

UL CONDITIONS OF ACCEPTABILITY Certificate Number: 1018011-1 Date: 2016-10-06 UL CONDITIONS OF ACCEPTABILITY Company Name: FUTURE DESIGN CONTROLS INC File-CCN: E197216 - QUYX2 Product Description: Process Control Equipment, Electrical

More information

INPUT RESISTANCE OR CLAMP VOLTAGE. 2 Years 23 C ±5 Voltage mv 3 10 nv > 10 G

INPUT RESISTANCE OR CLAMP VOLTAGE. 2 Years 23 C ±5 Voltage mv 3 10 nv > 10 G Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 www.keithley.com Model 2010 Low-Noise Multimeter Specifications DC CHARACTERISTICS CONDITIONS: MED (1 PLC) 1 or SLOW (5 PLC)

More information

ISOLATED 4-20 ma TRANSMITTERS

ISOLATED 4-20 ma TRANSMITTERS 500 SERIES FOR DEMANDING APPLICATIONS Isolated to 1500 V rms Two-Wire 4-20 ma Operation 9-50 V Compliance Turndown Ratio to 10:1 NMV Protection to 120 Vac -40 to +85 C (-40 to 185 F) Operation Shock Resistance

More information

+ 24V 3.3K - 1.5M. figure 01

+ 24V 3.3K - 1.5M. figure 01 ELECTRICITY ASSESSMENT 35 questions Revised: 08 Jul 2013 1. Which of the wire sizes listed below results in the least voltage drop in a circuit carrying 10 amps: a. 16 AWG b. 14 AWG c. 18 AWG d. 250 kcmil

More information

ULTRASONlC FlOWMETER SAMPLE BOOK. TYPE:LRF-3300S Concentrating on Flow Measurement

ULTRASONlC FlOWMETER SAMPLE BOOK. TYPE:LRF-3300S Concentrating on Flow Measurement ULTRASONlC FlOWMETER SAMPLE BOOK TYPE:LRF-3300S Concentrating on Flow Measurement Introduction LRF-3300S is a wall-mount, clamp- on type ultrasonic flowmeter which use the transfer time technology. Clamp

More information

April 1994 UCM-420A. Setpoint Controller. Operating and Installation Instructions

April 1994 UCM-420A. Setpoint Controller. Operating and Installation Instructions April TM UCM-A Setpoint Controller Operating and Installation Instructions A LARGE number of applications in a SMALL package... REMOTE SETPOINT CONTROLLER LOCAL SETPOINT CONTROLLER - ma SIGNAL GENERATOR

More information

Digital Multifunction Instrument - Rish Master 3440

Digital Multifunction Instrument - Rish Master 3440 Application Rish Master 3440 measures important electrical parameters in 3 phase and single phase etwork & replaces the multiple analog panel meters. It measures electrical parameters like AC current,

More information

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment T/3000 Substation Maintenance and Commissioning Test Equipment MULTI FUNCTION SYSTEM FOR TESTING SUBSTATION EQUIPMENT SUCH AS: CURRENT, VOLTAGE AND POWER TRANSFORMERS, ALL TYPE OF PROTECTION RELAYS, ENERGY

More information

OHIO SEMITRONICS, INC. DIGITAL AC POWER MONITOR OSI SPECIFICATIONS

OHIO SEMITRONICS, INC. DIGITAL AC POWER MONITOR OSI SPECIFICATIONS DIGITAL AC POWER MONITOR DESCRIPTION The DSP is a three-phase, three-element multifunction digital transducer with outputs for voltage, current, and power via serial communication. Applications include

More information

GE Fanuc IC695ALG600. Rx3i PacSystem

GE Fanuc IC695ALG600. Rx3i PacSystem GE Fanuc IC695ALG600 http://www.pdfsupply.com/automation/ge-fanuc/rx3i-pacsystem/ic695alg600 Rx3i PacSystem UNIVERSAL ANALOG MODULE. 8 CHANNELS OF ANALOG CONFIGURABLE IC695A IC695AL IC695ALG 919-535-3180

More information

ALPHA 50 MULTIFUNCTION METER (ALPHA SERIES)

ALPHA 50 MULTIFUNCTION METER (ALPHA SERIES) Alpha Series www.sifamtinsley.co.uk Multifunction Meters Transducers & Isolators Temperature Controllers Converters & Recorders Digital Panel Meters Current Transformers Analogue Panel Meters Shunts ALPHA

More information

Modbus communication module for TCX2: AEX-MOD

Modbus communication module for TCX2: AEX-MOD Modbus communication module for TCX2: Communication Specification TCX2 is factory installed in TCX2 series controllers with -MOD suffix, and is also available separately upon request for customer installation

More information

Back to the Basics Current Transformer (CT) Testing

Back to the Basics Current Transformer (CT) Testing Back to the Basics Current Transformer (CT) Testing As test equipment becomes more sophisticated with better features and accuracy, we risk turning our field personnel into test set operators instead of

More information

ELKOR MOC1 TRANSDUCER SET - MANUAL

ELKOR MOC1 TRANSDUCER SET - MANUAL ELKOR MOC1 TRANSDUCER SET - MANUAL Elkor MOC1 Power Transducer - Product Description The MOC1 true RMS 3 phase transducer is a micro-processor based metering product that provides a cost effective and

More information

BusWorks 900EN Series Modbus TCP/IP 10/100M Industrial Ethernet I/O Modules

BusWorks 900EN Series Modbus TCP/IP 10/100M Industrial Ethernet I/O Modules BusWorks 900EN Series Modbus TCP/IP 10/100M Industrial Ethernet I/O Modules Six Differential Current Inputs Six Differential Voltage Inputs USER S MANUAL ACROMAG INCORPORATED Tel: (248) 295-0880 30765

More information

RI-D440. Three Phase easywire Multifunction DIN Rail Energy Meter. Telephone : +44 (0) Displayed Parameters

RI-D440. Three Phase easywire Multifunction DIN Rail Energy Meter. Telephone : +44 (0) Displayed Parameters RI-D440 Three Phase easywire Multifunction DIN Rail Energy Meter Four module DIN rail mounted Energy pulse LED 330mV Input from easywire CTs (or -/1A and -/5A current transformer input with TAS-SCTEWA

More information

WD series DIN Rail or Screw Mounted Protective Relays

WD series DIN Rail or Screw Mounted Protective Relays WD series DIN Rail or Screw Mounted Protective Relays WD25 Paralleling (Synch Check) Relays WD2759 Over/undervoltage Relays WD32 Reverse Power Relays WD47 Phase Sequence Relays WD5051 Single- or Three-Phase

More information

mmint Modbus translator module installation and use

mmint Modbus translator module installation and use Instructional Leaflet IL66A7508H09 Supersedes July 2009 mmint Modbus translator module installation and use Contents Description Page List of figures... 2 List of tables.... 2 Section 1: General description...

More information

R24 DISPLAY MODULE WITH ACTIVE OUTPUT AND RELAY

R24 DISPLAY MODULE WITH ACTIVE OUTPUT AND RELAY Čapkova 22 678 01 Blansko tel.: +420 516 416942, 419995 fax: +420 516 416963 R24 DISPLAY MODULE WITH ACTIVE OUTPUT AND RELAY Display module is designed for measuring the resistance, the signal from the

More information

RUDOLF Digital power analyzer. Advanced Version

RUDOLF Digital power analyzer. Advanced Version RUDOLF Digital power analyzer Advanced Version Digital power analyzer Advanced Version Company Introduction Bridex Singapore Pte Ltd is founded in 1978 as a manufacturer of instruments transformer for

More information

MU110-8R(K) Digital output module 8 channel. User guide

MU110-8R(K) Digital output module 8 channel. User guide MU110-8R(K) Digital output module 8 channel User guide MU110-8R(K)_2019.01_0296_EN All rights reserved Subject to technical changes and misprints akytec GmbH Vahrenwalder Str. 269 A 30179 Hannover Germany

More information

High Performance Process & Temperature Controllers

High Performance Process & Temperature Controllers C22 C62 C82 C83 High Performance Process & Temperature Controllers C72 C42 R22 01. Multi Color LCD Display 02. High Accuracy 18 Bit A-D Input and 15 Bit D-A Output 03. 200 msec Sampling Rate 04. True Universal

More information

Data Sheet. RISH Master Record %THD

Data Sheet. RISH Master Record %THD Data Sheet %THD Application : measures important electrical parameters & replaces the multiple analog panel meters. It measures electrical parameters like AC current, Voltage, frequency, active energy

More information

MU110-16R(K) Digital output module 16 channel. User guide

MU110-16R(K) Digital output module 16 channel. User guide MU110-16R(K) Digital output module 16 channel User guide MU110-16R(K)_2016.12_0220_EN All rights reserved Subject to technical changes and misprints akytec GmbH Vahrenwalder Str. 269 A 30179 Hannover Germany

More information

Model 6517B Electrometer / High Resistance Meter Specifications

Model 6517B Electrometer / High Resistance Meter Specifications VOLTS Accuracy (1 Year) 1 / C 2V 10µV 0.025+4 0.003+2 20V 100µV 0.025+3 0.002+1 200V 1mV 0.06+3 0.002+1 NMRR: 2V and 20V range > 60dB, 200V range > 55dB. 50Hz or 60Hz 2 CMRR: >120dB at DC, 50Hz or 60Hz.

More information

Single Channel Loop Detector

Single Channel Loop Detector Single Channel Loop Detector Model LD120T Series The LD120T is a series of single channel inductive loop detectors. The use of microprocessor and surface mount technology enables a large number of functions

More information

A Few Applications For Signal Conditioners

A Few Applications For Signal Conditioners A Few Applications For Signal Conditioners Signal Conditioners are used to isolate, amplify, filter, and convert a variety of input signals to clean output signals that can be more easily handled by process

More information

Harris IRT Enterprises Multi-Channel Digital Resistance Tester Model XR

Harris IRT Enterprises Multi-Channel Digital Resistance Tester Model XR Harris IRT Enterprises Multi-Channel Digital Resistance Tester Model 6012-06XR Specifications & Dimensions 2 Theory of Operation 3 System Block Diagram 4 Operator Controls & Connectors 5 Test Connections

More information

A local 3.5 mm network jack allows a convenient way to connect an installation or diagnostic tool to the network without disconnecting any wires.

A local 3.5 mm network jack allows a convenient way to connect an installation or diagnostic tool to the network without disconnecting any wires. FEATURES - Extends wiring distance of FTT-10 LonWorks Networks. - Up to 5 repeaters can be daisy chained together to create a multi-segment repeater of up to 10 channels. - Low cost alternative to routers

More information

7SD/7SH/7SM Temperature Controllers

7SD/7SH/7SM Temperature Controllers 7SD/7SH/7SM Temperature ADVANTAGE EZ Series 7SD, 7SH, 7SM 1/16 DIN Temperature 3Digit LED Display Thermocouple and RTD Input Autotuning NEMA 4X Field onfigurable 100 to 40 Vac Switching Power Supply Programmable

More information

TD_485 Transceiver Modules Application Guide 2017

TD_485 Transceiver Modules Application Guide 2017 TD_485 Transceiver Modules Application Guide 2017 1. RS485 basic knowledge... 2 1.1. RS485 BUS basic Characteristics... 2 1.2. RS485 Transmission Distance... 2 1.3. RS485 bus connection and termination

More information

The wireless alternative to expensive cabling...

The wireless alternative to expensive cabling... The wireless alternative to expensive cabling... ELPRO 905U Wireless Solutions for Process Applications New Products... New Solutions The ELPRO 905U range of telemetry modules provide remote monitoring

More information

489 Generator Management Relay

489 Generator Management Relay GE Digital Energy 489 Generator Management Relay SELECT CURVE STYLE: Voltage Dependent 489 STATUS GENERATOR STATUS OUTPUT RELAYS 489 IN SERVICE BREAKER OPEN R1 TRIP SETPOINT ACCESS BREAKER CLOSED R2 AUXILIARY

More information

PIE 525. Diagnostic Thermocouple RTD & Milliamp Calibrator Operating Instructions. Practical Instrument Electronics

PIE 525. Diagnostic Thermocouple RTD & Milliamp Calibrator Operating Instructions. Practical Instrument Electronics PIE 525 Diagnostic Thermocouple RTD & Milliamp Calibrator Operating Instructions Practical Instrument Electronics Tel: 585.872.9350 Fax: 585.872.2638 sales@piecal.com www.piecal.com Contents General Operations

More information

MicroManager. Torque Mode CTCW/Loadcell Control. Instruction Manual MM3000-CTCW

MicroManager. Torque Mode CTCW/Loadcell Control. Instruction Manual MM3000-CTCW MicroManager Torque Mode CTCW/Loadcell Control Instruction Manual MM3000-CTCW Table of Contents 1. General Description... 5 2. Specifications... 5 2.1 Electrical... 5 2.2 Physical... 6 3. Installation...

More information

Contents. Warranty and Disclaimer 2 Introduction 3

Contents. Warranty and Disclaimer 2 Introduction 3 Contents Warranty and Disclaimer 2 Introduction 3 Physical Dimensions Board Layout 4 Usage Using the Relay board 5 Setting the start address 5 Configuration Jumper 6 Using the Relays 7 Using the DMX connectors

More information

Efficient Energy Systems 3315ENG.

Efficient Energy Systems 3315ENG. Efficient Energy Systems 3315ENG http://cleantechnica.com/2012/01/09/republican-fight-against-new-light-bulb-efficiency-regulations/ Topics Power and Energy Energy Auditing Efficient lighting Energy Harvesting

More information

MicroManager. Velocity Mode PID Dancer/Loadcell Control. Instruction Manual MM3000-PID

MicroManager. Velocity Mode PID Dancer/Loadcell Control. Instruction Manual MM3000-PID MicroManager Velocity Mode PID Dancer/Loadcell Control Instruction Manual MM3000-PID Table of Contents 1. General Description... 5 2. Specifications... 5 2.1 Electrical... 5 2.2 Physical... 6 3. Installation...

More information

ULTRASONIC FLOW METER FT101

ULTRASONIC FLOW METER FT101 Introduction F t101 is a wall-mount, clamp- on type ultrasonic flowmeter which use the transfer time technology. Clamp on type ultrasonic flowmeter is easy to install and no need to cut off the pipe, that

More information

USER S MANUAL EMPOWER POWER METER TRINITY. Empower Operational Manual

USER S MANUAL EMPOWER POWER METER TRINITY. Empower Operational Manual USER S MANUAL EMPOWER POWER METER This document contains the latest technical information about Empower which is a micro-controller based Power meter. The product Empower is sophisticated electronic equipment,

More information

RISH EM 3490 DS Dual Source Energy Meter (With All Display Parameters) RISH EM 3490 DS. Application : Product Features:

RISH EM 3490 DS Dual Source Energy Meter (With All Display Parameters) RISH EM 3490 DS. Application : Product Features: (With All Display Parameters) Application : RISH EM 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network

More information

The wireless alternative to expensive cabling...

The wireless alternative to expensive cabling... The wireless alternative to expensive cabling... ELPRO 905U Wireless Solutions for Process Applications New Products... New Solutions The ELPRO 905U range of wireless I/O provides a low cost alternative

More information

HI 2204LT Loop Powered Level Weight Transmitter OPERATION AND INSTALLATION MANUAL

HI 2204LT Loop Powered Level Weight Transmitter OPERATION AND INSTALLATION MANUAL Loop Powered Level Weight Transmitter OPERATION AND INSTALLATION MANUAL Corporate Headquarters 9440 Carroll Park Drive San Diego, CA 92121 Phone: (858) 278-2900 FAX: (858) 278-6700 Web-Site: http://www.hardysolutions.com

More information

DPF-MAC Auto power factor controller

DPF-MAC Auto power factor controller Digital Electric& Electronics System DPF-MAC Auto power factor controller MULTI POWER FACTOR AUTOMATIC MULTI POWER FACTOR AUTOMATIC Introduction DPF-MAC increases usage efficiency by controlling the power

More information

Variable Speed Brushed DC Motor Drive

Variable Speed Brushed DC Motor Drive The driving force of motor control & electronics cooling. Equinox: Variable Speed Brushed DC Motor Drive Navigator Equinox The Equinox variable speed brushed DC motor drive with Navigator Programmer is

More information

N. TEST TEST DESCRIPTION

N. TEST TEST DESCRIPTION Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy meters and transducers Primary injection testing capabilities

More information

Application: Product Features: On site programmable PT/CT ratios: User selectable CT Secondary 5A/1A. User selectable PT Secondary

Application: Product Features: On site programmable PT/CT ratios: User selectable CT Secondary 5A/1A. User selectable PT Secondary Application: Rish Master 3440 measures important electrical parameters in 3 phase and single phase etwor & replaces the multiple analog panel meters. t measures electrical parameters lie AC current,, frequency,

More information

Electronically Commutated (EC) Motor Control with Solo, Select and Sync PWM Boards

Electronically Commutated (EC) Motor Control with Solo, Select and Sync PWM Boards Electronically Commutated (EC) Motor Control with Solo, Select and Sync PWM Boards The Solo, Select and Sync PWM boards provide a pulse-width modulated (PWM) signal to the EC motor to control fan speed.

More information

Selection guide. Communication accessories. Communication accessory selection guide. Characteristics

Selection guide. Communication accessories. Communication accessory selection guide. Characteristics Communication accessories Selection guide There are 2 types of Sepam communication accessories: b communication interfaces, which are essential for connecting Sepam to the communication network b converters

More information

INSTALLATION AND MAINTENANCE MANUAL FOR GROUND MONITOR GM-250 COPYRIGHT 1983 AMERICAN MINE RESEARCH, INC.

INSTALLATION AND MAINTENANCE MANUAL FOR GROUND MONITOR GM-250 COPYRIGHT 1983 AMERICAN MINE RESEARCH, INC. INSTALLATION AND MAINTENANCE MANUAL FOR GROUND MONITOR GM-250 COPYRIGHT 1983 AMERICAN MINE RESEARCH, INC. MANUAL PART NUMBER 180-0036 ORIGINAL: 1-17-83 REVISION: B (8-26-86) NOT TO BE CHANGED WITHOUT MSHA

More information