AC-SENSOR 63 UND 250 AC-SENSOR 63 AND 250

Size: px
Start display at page:

Download "AC-SENSOR 63 UND 250 AC-SENSOR 63 AND 250"

Transcription

1 AC-SENSOR INSTALLATIONSANLEITUNG INSTALLATION GUIDE DE EN AC-SENSOR 63 UND 250 INSTALLATIONSANLEITUNG AC-SENSOR 63 AND 250 INSTALLATION GUIDE

2 1 Scope of delivery Check the delivery for completeness and externally visible damage. Contact your specialist dealer in case of an incomplete delivery or damage. Power meter AC-Sensor (63 or 250) 2 Validity Sleeves for passing through external conductors Operating instructions This document is intended for qualified persons. The activities described here must only be carried out by persons have the following minimum qualification: Instruction in the installation and commissioning of electrical devices Training with respect to electrical hazards and locally applicable safety requirements Knowledge of the applicable standards and directives Familiarity and compliance with this document and all safety instructions. DATE: 09/2018 INSTALLATION GUIDE Rev AZ-TM-PME-0930 Subject to changes 2018 SOLARWATT GmbH PAGE 15

3 3 Intended use The AC Sensor 63 or 250 (referred to hereinafter as ACS) power meter is a device that detects the electrical measurements at a 1 or 3-phase AC voltage connection and transmits the value via CAN bus. The device is intended exclusively for private use with a MyReserve battery storage system and the EnergyManager. This product is not an active electric energy meter as defined by EU Directive 2004/92/EC (IDE). The ACS must not be used for billing purposes. The data that the device records may differ from the data of the energy meter used for billing. The ACS must only be connected in the household junction box on the consumer side downstream from the energy meter of the power supply company. It is suited exclusively for use indoors in a switch box or meter cabinet. The ACS is approved for use in Member States of the EU, as well as Switzerland and Australia. Its use is permitted exclusively in compliance with the specifications of the accompanying documentation. Any other use will result in property damage and personal injury. Modifications and installation of additional components are prohibited for safety reasons. The accompanying documentation is an integral component of the product. The user of the product must have read and observed the documentation and keep it accessible at all times. 4 Safety HAZARD Life-threatening danger due to electric shock! The live parts carry extremely dangerous voltages. Only use the ACS in a dry environment and keep it away from liquids. Only operate the ACS behind a cover or with a contact guard in a switch cabinet. Disconnect the ACS before cleaning it and only clean it using a dry cloth. IMPORTANT Damage or destruction of the ACS with improper use! Connection of mains voltage to the CAN bus terminals can damage or destroy the device. Operation outside of the specified technical data can damage or destroy the device (see "Technical data" at the end of this guide). PAGE 16 Version: 09/2018 INSTALLATION GUIDE Rev AZ-TM-PME-0930 Subject to changes 2018 SOLARWATT GmbH

4 5 Product description The ACS detects the electrical output for feeding and withdrawing and sends it to the MyReserve battery storage system, which is then regulated accordingly. When seen from the household fuse, the ACS is installed directly downstream of the power supply company meter. 6 Layout 6 RU (10.8 cm) Connection area for external conductor and neutral conductor (voltage measurement) (A) MyReserve CAN communication (B) EnergyManager CAN communication (C) AC-Sensor 63: Feed pass throughs for conductors from the main switch to the load(s) AC-Sensor 250: Feed pass throughs for conductors with current transformer clamps (current measurement) (D) DATE: 09/2018 INSTALLATION GUIDE Rev AZ-TM-PME-0930 Subject to changes 2018 SOLARWATT GmbH PAGE 17

5 7 Connection and commissioning 7.1 ACS 63 IMPORTANT Observe the 5 safety rules! HAZARD Life-threatening danger due to electric shock! Extremely dangerous voltage runs through the household junction box. Disconnect the connection point and secure against re-connection. Ensure that the conductors that are connected to the ACS 63 or should be disconnected from it are de-energized. 1. Insert the sleeves included with the AC Sensor 63 into feeds for external conductors (D). NOTE If you are using cables with diameters > 10 mm, the included sleeves cannot be used as feed-through aids. Please note that the sleeves can no longer be removed once the cables are fed through! 2. Mount the ACS 63 on a top-hat rail. For this purpose, hook the device on the upper edge of the top-hat rail and press down until it clicks into place. 3. Pull the three phase conductors L1, L2 and L3, through the openings D. NOTE With a single-phase network, a house connection cable having a diameter 16mm² and an incoming current 63A, only connect the neutral conductor and the phase conductor to terminal L3. With a single-phase network, a house connection cable having a diameter >16mm² and an incoming current > 63A, use the Phase Splitter and the Phase Splitter Installation Guide from SOLARWATT. Please observe all local standards and connection guidelines when installing the AC Sensor 50/63. PAGE 18 Version: 09/2018 INSTALLATION GUIDE Rev AZ-TM-PME-0930 Subject to changes 2018 SOLARWATT GmbH

6 4. Connect neutral conductor N and the phase conductors L1, L2 and L3 to the terminals in connection area A. Attention: It must be ensured that each phase conductor that is connected to L1, L2 and L3 has the same potential as the corresponding phase conductor that runs through the openings D. If the phase conductors are transposed in the openings D or in connection area A, incorrect power levels are measured. With a single-phase network, only connect the neutral conductor and the phase conductor to terminal L3. In the process, observe the permissible connection cross-section. 5. Connect the CAN-MR interface to the CAN communication of the MyReserve. When a EnergyManager is in use, connect the CAN-EM interface, then to the CAN communication of the EnergyManager. 6. Cover the ACS 63 with the cover or contact guard of the junction box. 7. Re-connect the power to the junction box. Additionally required material (not included in the scope of delivery): Cable for CAN communication (min. Cat5.e with wires twisted in pairs) Three-phase conductor circuit breaker arranged in the meter cabinet near the ACS 63, easily accessible and identified as a breaker for the ACS 63 with tripping characteristic B10A or B16A NOTE The safeguarding of the conductors for voltage measurement can also be executed with a double tap on an existing circuit breaker in compliance with applicable standards and the manufacturer's specifications. The following figures show the connection of the single-phase and three-phase ACS 63 to MyReserve and incorporating the EnergyManager. They are sample connections. For more exact specifications for the connection, contact the responsible power supply company. Single-phase connection Three-phase connection DATE: 09/2018 INSTALLATION GUIDE Rev AZ-TM-PME-0930 Subject to changes 2018 SOLARWATT GmbH PAGE 19

7 With a single-phase network, a house connection cable having a diameter 16mm² and an incoming current 63A, only connect the neutral conductor and the phase conductor to terminal L3. With a single-phase network, a house connection cable having a diameter > 16mm² and an incoming current > 63A, use the Phase Splitter and the Phase Splitter Installation Guide from SOLARWATT. Please observe all local standards and connection guidelines when installing the AC Sensor 63. MyReserve and ACS 63 with 3-phase measurement circuit diagram PAGE 20 Version: 09/2018 INSTALLATION GUIDE Rev AZ-TM-PME-0930 Subject to changes 2018 SOLARWATT GmbH

8 MyReserve and ACS 63 and EnergyManager with 3-phase measurement circuit diagram DATE: 09/2018 INSTALLATION GUIDE Rev AZ-TM-PME-0930 Subject to changes 2018 SOLARWATT GmbH PAGE 21

9 7.2 ACS 250 HAZARD Life-threatening danger due to electric shock! Extremely dangerous voltage runs through the household junction box. Disconnect the connection point and secure against re-connection. Ensure that the conductors that are connected to the ACS 63 or should be disconnected from it are de-energized. 1. Mount the ACS 250 on a top-hat rail. For this purpose, hook the device on the upper edge of the top-hat rail and press down until it clicks into place.. 2. Mount the current transformer clamps on the phase conductor of the main cables. Please ensure that the clamps are facing the right direction of the flow of current. 3. The secondary windings (S1,S2) need to go through the pipes of the correct corresponding phases. The secondary windings must be terminated at the clamps. NOTE Please observe all local standards and connection guidelines when installing the AC Sensor. 4. Connect neutral conductor N and the phase conductors L1, L2 and L3 to the terminals in connection area A. Attention: It must be ensured that each phase conductor that is connected to L1, L2 and L3 has the same potential as the corresponding phase conductor that runs through the openings D. If the phase conductors are transposed in the openings D or in connection area A, incorrect power levels are measured. With a single-phase network, only connect the neutral conductor and the phase conductor to terminal L3. In the process, observe the permissible connection cross-section. 5. Connect the CAN-MR interface to the CAN communication of the MyReserve. When a EnergyManager is in use, connect the CAN-EM interface, then to the CAN communication of the EnergyManager. 6. Cover the ACS 250 with the cover or contact guard of the junction box. 7. Re-connect the power to the junction box. Additionally required material (not included in the scope of delivery): Current transformer clamps 250/5A, min. 1VA Cable for CAN communication (min. Cat5.e with wires twisted in pairs) Three-phase conductor circuit breaker arranged in the meter cabinet near the ACS 250, easily accessible and identified as a breaker for the ACS 250 with tripping characteristic B10A or B16A PAGE 22 Version: 09/2018 INSTALLATION GUIDE Rev AZ-TM-PME-0930 Subject to changes 2018 SOLARWATT GmbH

10 NOTE The safeguarding of the conductors for voltage measurement can also be executed with a double tap on an existing circuit breaker in compliance with applicable standards and the manufacturer's specifications. The following figures show the connection of the single-phase and three-phase ACS 250 to MyReserve and incorporating the EnergyManager. They are sample connections. For more exact specifications for the connection, contact the responsible power supply company. Single-phase connection DATE: 09/2018 INSTALLATION GUIDE Rev AZ-TM-PME-0930 Subject to changes 2018 SOLARWATT GmbH PAGE 23

11 Three-phase connection PAGE 24 Version: 09/2018 INSTALLATION GUIDE Rev AZ-TM-PME-0930 Subject to changes 2018 SOLARWATT GmbH

12 MyReserve and ACS 250 with 3-phase measurement circuit diagram DATE: 09/2018 INSTALLATION GUIDE Rev AZ-TM-PME-0930 Subject to changes 2018 SOLARWATT GmbH PAGE 25

13 8 Faults Error Possible cause ACS 63 troubleshooting ACS 250 troubleshooting No Power supply Make sure that at least the neutral conductor and one phase conductor are connected in connection field A, with the neutral conductor connected to terminal L3. Make sure that at least the neutral conductor and one phase conductor are connected to terminal L3. No Measurement data CAN bus not connected correctly Make sure that the connections H, L and GND from the ACS 63 are connected correctly to the receiving device. Make sure that the connections H, L and GND from the ACS 250 are connected correctly to the receiving device. Error Restart the ACS 63 by switching off the corresponding circuit breaker and wait at least 3 seconds before switching it on again. Restart the ACS 250 by switching off the corresponding circuit breaker and wait at least 3 seconds before switching it on again. Implausible measurements Incorrect installation Two or more phase conductors interposed Reconnect and re-commissioning the device, ensuring that the phase conductors exit opening area D (see figure p. 17) in the right direction. Make sure that phase conductors L1, L2 and L3 in connection area D and A (see figure p. 17) are connected to the same phase rail. Carry out the connection and commissioning again and make sure that the phase conductors L1, L2 and L3 are in the right direction to their respective terminals. Make sure the assignment of the phase conductors L1, L2 and L3 on the current transformers is correct and connected to the corresponding terminals of the ACS 250. The secondary winding of one or more current transformer clamps is connected in a wrong direction. Check the direction of the secondary winding of the current transformer clamps. PAGE 26 Version: 09/2018 INSTALLATION GUIDE Rev AZ-TM-PME-0930 Subject to changes 2018 SOLARWATT GmbH

14 9 Technical specifications DATE: 09/2018 INSTALLATION GUIDE Rev AZ-TM-PME-0930 Subject to changes 2018 SOLARWATT GmbH PAGE 27

15 Der ACS muss nach den vor Ort gültigen Entsorgungsvorschriften für Elektronikschrott entsorgt werden. The ACS must be disposed of in accordance with the locally applicable waste disposal regulations for electronic scrap. KONTAKT Sie interessieren sich für unsere Produkte und Leistungen? Wir beraten Sie gern. Rufen Sie uns einfach an! Bei technischen Problemen mit dem Produkt wenden Sie sich an die Servicehotline. Wir benötigen folgende Daten um Ihnen gezielt helfen zu können: Typ und Seriennummer des ACS (abzulesen am Typenschild) Typ und Seriennummer des Gerätes, welches die Messwerte vom ACS am CAN-Bus empfängt möglichst detaillierte Fehlerbeschreibung SOLARWATT GmbH Maria-Reiche-Str. 2a Dresden Germany Tel Fax info@solarwatt.de Zertifiziert nach ISO 9001 und ISO BS OHSAS 18001:2007 CONTACT Are you interested in our products and services? We ll be glad to advise you. Just give us a call. If you are experiencing technical problems with the product, please use the service hotline. We will need the following information to assist you further: Type and serial number of the ACS (can be read on the type plate) Type and serial number of the device receiving the measurements form the ACS on the CAN bus Provide as much detail as possible when describing the error SOLARWATT GmbH Maria-Reiche-Str. 2a Dresden Germany Tel Fax info@solarwatt.de Certified according to ISO 9001 and ISO BS OHSAS 18001:2007

Operating instructions Transformer Switching Relay TSRL

Operating instructions Transformer Switching Relay TSRL Operating instructions Transformer Switching Relay TSRL 1 8 Table of contents 1 Introduction... 3 1.1 Notes on operating instructions...3 1.2 Explanation of icons and symbols...3 1.3 Intended use and foreseeable

More information

External brake resistor AX2090-BW5x

External brake resistor AX2090-BW5x Documentation External brake resistor AX2090-BW5x Accessories for Beckhoff servo drive AX5000 Version: Date: 1.3 2018-03-14 Table of content Table of content 1 Foreword... 5 1.1 Notes on the documentation...

More information

PHV RO High Voltage Passive Probe. Instruction Manual

PHV RO High Voltage Passive Probe. Instruction Manual PHV 1000-3-RO High Voltage Passive Probe Instruction Manual Copyright 2012 PMK GmbH All rights reserved. Information in this publication supersedes that in all previously published material. Specifications

More information

ZipLevel A / Rev 0508-GB. Operation manual

ZipLevel A / Rev 0508-GB. Operation manual 029.020A / Rev 0508-GB GB Operation manual Professional precision altimeter The ZipLevel is a professional altimeter which enables you to scale and level on your own also around corners with accuracy

More information

Current / residual current and voltage transformers. Current / residual current and voltage transformers

Current / residual current and voltage transformers. Current / residual current and voltage transformers Current / residual current and voltage transformers Current / residual current and voltage transformers 1 Overview Current transformer overview DIN rail current transformer with fuse Current transformer...

More information

SUNNY BEAM REPEATER Transmission Range Increase for Sunny Beam

SUNNY BEAM REPEATER Transmission Range Increase for Sunny Beam SUNNY BEAM REPEATER Transmission Range Increase for Sunny Beam User Manual SBeamRep-BEN091911 98-0002611 Version 1.1 EN SMA Solar Technology AG Table of Contents Table of Contents 1 Notes on this Manual..............................

More information

U ACTIVE SAT DISTRIBUTION FIELD

U ACTIVE SAT DISTRIBUTION FIELD U 911... 946 ACTIVE SAT DISTRIBUTION FIELD Illustrations front view U 911 Controller port Indicator lamps Remote feed ON/OFF Labeling field Measurement points outputs Y outputs X input Y input X Bus port

More information

Radio receiver FS20 EAM

Radio receiver FS20 EAM OPERATING INSTRUCTIONS Version 12/06 Radio receiver FS20 EAM (for FS20 DIN rail system) Item no. 62 30 12 Introduction Dear customer, Thank you for purchasing this product. This product meets the requirements

More information

PHV 1000-RO High Voltage Passive Probe. Instruction Manual

PHV 1000-RO High Voltage Passive Probe. Instruction Manual PHV 1000-RO High Voltage Passive Probe Instruction Manual Copyright 2014 PMK GmbH All rights reserved. Information in this publication supersedes that in all previously published material. Specifications

More information

Operating Manual * * Differential pressure transmitter. Table of Contents. 1 Safety guidelines. 1.1 General Information

Operating Manual * * Differential pressure transmitter. Table of Contents. 1 Safety guidelines. 1.1 General Information *09005137* BA_EN_DE50 Rev.A 11/12 *09005137* d e v e l o p i n g s o l u t i o n s DE50 Operating Manual Differential pressure transmitter Table of Contents 1 Safety guidelines 2 Application purpose 3

More information

MRG 512-PRO PQ Flex Mobile universal measurement device Supplementary description to the operation manual UMG 512-PRO

MRG 512-PRO PQ Flex Mobile universal measurement device Supplementary description to the operation manual UMG 512-PRO Doc. no. 2.054.018.2 Subject to technical changes. www.janitza.com Mobile universal measurement device MRG 512-PRO PQ Flex Supplementary description to the operation manual UMG 512-PRO Janitza electronics

More information

Radio bus system Radio-universal dimming actuator, 1-gang. 1 Safety instructions. 2 Device components. Order-No. : Operating instructions

Radio bus system Radio-universal dimming actuator, 1-gang. 1 Safety instructions. 2 Device components. Order-No. : Operating instructions Order-No. : 1135 00 Operating instructions 1 Safety instructions Electrical equipment may only be installed and fitted by electrically skilled persons. Failure to observe the instructions may cause damage

More information

Safety instructions and installation

Safety instructions and installation 1 Safety instructions and installation Thank you for deciding to purchase the innovative Frama Starter / Matrix F10 / Matrix F12 franking system. The information below in this operating manual is intended

More information

Instruction manual for STA 1 sectional door operator

Instruction manual for STA 1 sectional door operator Instruction manual for STA 1 sectional door operator Sectional door operator STA 1 / Rev. 0.3 1 GB 1. Contents 3. General safety instructions 1. Contents 2 2. Key to symbols 2 3. General safety instructions

More information

MRG 96RM-E Flex RCM Mobile universal measurement device Supplementary description to the operation manual UMG 96RM-E

MRG 96RM-E Flex RCM Mobile universal measurement device Supplementary description to the operation manual UMG 96RM-E Doc. no. 2.040.127.0.b Subject to technical changes. www.janitza.com Mobile universal measurement device MRG 96RM-E Flex RCM Supplementary description to the operation manual UMG 96RM-E Janitza electronics

More information

MAVOWATT 4 Multifunction Power Meter

MAVOWATT 4 Multifunction Power Meter Operating nstructions MAVOWATT 4 Multifunction Power Meter 3-348-721-02 3/3.04 1 2 A V 3 4 5 6 Figure 1 2 GOSSEN METRAWATT GMBH Operating controls 1 Connection terminals Current, Voltage,, 2 Mirror scale

More information

Accessories Solar Datatechnology Wireless-Set485-01/-Set485-02

Accessories Solar Datatechnology Wireless-Set485-01/-Set485-02 Accessories Solar Datatechnology Wireless-Set485-01/-Set485-02 Installation Guide WirelessSet485-IEN091511 98-0009411 Version 1.1 EN SMA Solar Technology AG Table of Contents Table of Contents 1 Notes

More information

PKT 512A-RO High Impedance Passive Cable Divider

PKT 512A-RO High Impedance Passive Cable Divider PKT 512A-RO High Impedance Passive Cable Divider Instruction Manual Copyright 2011 PMK GmbH All rights reserved. Information in this publication supersedes that in all previously published material. Specifications

More information

Tube Facing Tool.

Tube Facing Tool. www.swagelok.com Tube Facing Tool This manual contains important information for the safe and effective operation of the Swagelok TF72 series tube facing tool. Users should read and understand its contents

More information

Operating manual GTL 241 GTL 251. Temperature probe. Please keep the manual for future use.

Operating manual GTL 241 GTL 251. Temperature probe. Please keep the manual for future use. Operating manual Temperature probe GTL 241 GTL 251 Please keep the manual for future use. L01.0.2X.6C-02 GREISINGER electronic GmbH Hans-Sachs-Str. 26 93128 Regenstauf Germany Fon +49(0)9402-9383-0 Fax

More information

Signal converter for electromagnetic flowmeters

Signal converter for electromagnetic flowmeters Quick Start Signal converter for electromagnetic flowmeters Electronic revision: ER 3.0.xx The documentation is only complete when used in combination with the relevant documentation for the flow sensor.

More information

TETRIS 1000 High Impedance Active Probe. Instruction Manual

TETRIS 1000 High Impedance Active Probe. Instruction Manual TETRIS 1000 High Impedance Active Probe Instruction Manual Copyright 2015 PMK GmbH All rights reserved. Information in this publication supersedes that in all previously published material. Specifications

More information

Wireless Receiver E28Q Mounting and Operating Instructions (Original operating instructions)

Wireless Receiver E28Q Mounting and Operating Instructions (Original operating instructions) EN Wireless Receiver E28Q Wireless Receiver E28Q Mounting and Operating Instructions (Original operating instructions) Always read before initial operation! 28509900_E28Q_EN_2012-05-08.doc 1 / 12 1 Data

More information

Top spin Nr /

Top spin Nr / Top spin Nr. 1840 0000 / 1840 1000 Bedienungsanleitung 21-6680 28052014 / A Made in Germany Ideas for dental technology Top spin Nr. 1840 0000 / 1840 1000 Contents 1. Introduction...2 1.1 Symbols...2 2.

More information

Magnetic Inductive Flow Sensor induq

Magnetic Inductive Flow Sensor induq Operating manual (Translation) Operating manual... page 1-16 Magnetic Inductive Flow Sensor induq Series VMZ SIKA Ba_VMZ_en 10/2014. Please keep this operating manual for future reference. If the device

More information

MultiMeter-Pocket CAT III 1000 V

MultiMeter-Pocket CAT III 1000 V 02 10 18 26 34 42 50 58 66 74 82 DE GB NL DK FR ES IT PL FI PT SE AC DC AC DC CAT III 1000 V 90 98 106 114 122 130 138 146 154 162 170 NO TR RU UA CZ EE LV LT RO BG GR ! Read the operating instructions

More information

Electrical devices may only be mounted and connected by electrically skilled persons.

Electrical devices may only be mounted and connected by electrically skilled persons. Order No. : 2126 00 Operating instructions 1 Safety instructions Electrical devices may only be mounted and connected by electrically skilled persons. Serious injuries, fire or property damage possible.

More information

Operating Instructions PROFITEST H+E TECH. Diagnostics Unit for Electric Charging Stations (Type 2 Connector Socket and Plug) /3.

Operating Instructions PROFITEST H+E TECH. Diagnostics Unit for Electric Charging Stations (Type 2 Connector Socket and Plug) /3. Diagnostics Unit for Electric Charging Stations (Type 2 Connector Socket and Plug) 3-349-878-03 1/3.16 Opening the Instrument / Repairs The instrument may only be opened by authorized, trained personnel

More information

1 Safety instructions. 2 Device components. 3 Function. KNX Heating actuator 6gang RMD 230 V. Order-No. :

1 Safety instructions. 2 Device components. 3 Function. KNX Heating actuator 6gang RMD 230 V. Order-No. : Order-No. : 7531 60 03 Operation- and Assembly Instructions 1 Safety instructions Electrical equipment may only be installed and fitted by electrically skilled persons. Failure to observe the instructions

More information

Antenna Splitter ASA 1. Instruction manual

Antenna Splitter ASA 1. Instruction manual Antenna Splitter ASA 1 Instruction manual Contents Contents Important safety instructions... 2 The ASA 1 active antenna splitter... 4 Combination possibilities of ASA 1/ASA 1-1G8... 5 Delivery includes...

More information

OPERATION MANUAL ELECTRONIC FREQUENCY CONVERTER HFO-E

OPERATION MANUAL ELECTRONIC FREQUENCY CONVERTER HFO-E OPERATION MANUAL ELECTRONIC FREQUENCY CONVERTER HFO-E Lievers Holland PO Box 103 3640 AC Mijdrecht Tel: +31 (0)297-231900 Fax: +31 (0)297-231909 E-mail: info@lieversholland.nl - www.lieversholland.nl CONTENT

More information

Reactive Power Control Relay RM 2106 / 2112 Operating Instructions. FRAKO Kondensatoren- und Anlagenbau

Reactive Power Control Relay RM 2106 / 2112 Operating Instructions. FRAKO Kondensatoren- und Anlagenbau Reactive Power Control Relay RM 2106 / 2112 Operating Instructions FRAKO Kondensatoren- und Anlagenbau www.frako.com Figure 1 Front view a b c d e Display for active capacitor stages Display for inductive

More information

TWS One Headset UHF wireless system. user manual

TWS One Headset UHF wireless system. user manual TWS One Headset UHF wireless system user manual Musikhaus Thomann Thomann GmbH Hans-Thomann-Straße 1 96138 Burgebrach Germany Telephone: +49 (0) 9546 9223-0 E-mail: info@thomann.de Internet: www.thomann.de

More information

Instruction manual for STA 1 sectional door operator

Instruction manual for STA 1 sectional door operator Instruction manual for STA 1 sectional door operator GB Sectional door operator STA 1 / Rev. 0.0 1 1. Contents 3. General safety instructions 1. Contents 2 2. Key to symbols 2 3. General safety instructions

More information

ATS Elektronik GmbH Manual version 1.04

ATS Elektronik GmbH Manual version 1.04 MANUAL MTL381 Remote Expander MTM800 FUG / MTM5400 ATS Elektronik GmbH Manual version 1.04 All information in this manual has been compiled after careful investigation, but cannot be considered to be assured

More information

Instruction manual ADN-W AM. Antenna Module

Instruction manual ADN-W AM. Antenna Module Instruction manual ADN-W AM Antenna Module For your safety www www.sennheiser.com Manual Contents For your safety... 1 The ADN-W AM antenna module... 1 Package contents... 2 Components required for wireless

More information

E205 Long Range Wireless Modem V1.0 Data Sheet

E205 Long Range Wireless Modem V1.0 Data Sheet E205 Long Range Wireless Modem V1.0 Data Sheet The Long Range Wireless Modem E205 is a radio transmitter / receiver designed for transparent wireless data transmission over long distances. It operates

More information

USER S MANUAL. Rail-mounted temperature transmitter ATL

USER S MANUAL. Rail-mounted temperature transmitter ATL IO.ATL (ENG) USER S MANUAL Rail-mounted temperature transmitter ATL APLISENS S.A., 03-192 Warszawa, ul. Morelowa 7 tel. +48 22 814 07 77; fax +48 22 814 07 78 www.aplisens.pl, e-mail: aplisens@aplisens.pl

More information

Instruction Manual MSC710 MSC710-U MSC710-I

Instruction Manual MSC710 MSC710-U MSC710-I Instruction Manual MSC710 MSC710-U MSC710-I Sensor controller for inductive displacement and gauging sensors series LVDT MICRO-EPSILON MESSTECHNIK GmbH & Co. KG Koenigbacher Strasse 15 94496 Ortenburg

More information

Digital Function Generator

Digital Function Generator Digital Function Generator 13654-99 PHYWE Systeme GmbH & Co. KG Robert-Bosch-Breite 10 37079 Göttingen Germany Tel. +49 (0) 551 604-0 Fax +49 (0) 551 604-107 E-mail info@phywe.de Operating Instructions

More information

Installation Instructions RF-identification system Read/write head DTM434 DTM435 DTM436 DTM437

Installation Instructions RF-identification system Read/write head DTM434 DTM435 DTM436 DTM437 Installation Instructions RF-identification system Read/write head DTM434 DTM435 DTM436 DTM437 UK 80262951 / 00 04 / 2017 Content 1 Preliminary note...4 1.1 Symbols used...4 1.2 Warnings used...4 2 Safety

More information

SPLIT.CONVERTER. User's Manual. Version 2.0

SPLIT.CONVERTER. User's Manual. Version 2.0 SPLIT.CONVERTER User's Manual Version 2.0 Copyright All rights reserved. Permission to reprint or electronically reproduce any document or graphic in whole or in part for any reason is expressly prohibited,

More information

Operating instructions Fail-safe delay timer AZS About this document. Content

Operating instructions Fail-safe delay timer AZS About this document. Content 8 Appendix 8.1 Wiring example...4 8.2 Integral System Diagnostics (ISD)....5 9 EU Declaration of conformity Operating instructions.............pages 1 to 6 Original x.000 / 11.2017 / v.a. - 101126753-

More information

OPERATION MANUAL ELECTRONIC FREQUENCY CONVERTER HFO E

OPERATION MANUAL ELECTRONIC FREQUENCY CONVERTER HFO E OPERATION MANUAL ELECTRONIC FREQUENCY CONVERTER HFO E Lievers Holland Postbus 103 3640 AC Mijdrecht Tel: +31 (0)297 231900 Fax: +31 (0)297 231909 E mail: info@lieversholland.nl www.lieversholland.nl Operation

More information

Commissioning and Maintenance of Power Factor Correction Systems

Commissioning and Maintenance of Power Factor Correction Systems Dear Customer, We would like to thank you for choosing a power factor correction system from FRAKO Kondensatoren- und Anlagenbau GmbH. It is a pleasure to welcome you into the ever-expanding circle of

More information

Radio System Strobe Wizard Plus Freemask

Radio System Strobe Wizard Plus Freemask Radio System Strobe Wizard Plus Freemask User manual Translation of the original German user manual Doc. No.: 900.0509.00 Version: 09/2017 Contents Information about this manual and about the manufacturer...

More information

www.samsondoors.co.uk 0800 328 6250 TR20A116 RE / 02.2012 DE EN FR NL IT ES PT Anleitung für Montage und Betrieb Funk-Codetaster FCT 3 BiSecur Instructions for fitting and operating Radio code switch FCT

More information

MEDIUM VOLTAGE PRODUCT. KOKM Cable current instrument transformers Instruction for Installation, use and maintenance

MEDIUM VOLTAGE PRODUCT. KOKM Cable current instrument transformers Instruction for Installation, use and maintenance MEDIUM VOLTAGE PRODUCT KOKM Cable current instrument transformers Instruction for Installation, use and maintenance 2 KOKM CABLE CURRENT INSTRUMENT TRANSFORMERS INSTRUCTION FOR INSTALLATION, USE AND MAINTENANCE

More information

Installation Manual DOC R1 Date: 05/27/99. Plug-in Meter Installation Manual

Installation Manual DOC R1 Date: 05/27/99. Plug-in Meter Installation Manual Installation Manual DOC-4004-5015-R1 Date: 05/27/99 Plug-in Meter Installation Manual Document Number: Doc-4004-5015-R1 Document Release Date: 5/99 Copyright 1999 TeCom Inc. All rights reserved. No part

More information

ContiConnect. Yard Reader Station. Installation manual

ContiConnect. Yard Reader Station. Installation manual ContiConnect Yard Reader Station GB Installation manual Table of Contents Yard Reader Station 1 General Information...5 1.1 Subject of this installation manual...5 1.2 Target groups...5 1.3 Information

More information

TWS One Vocal UHF wireless system. user manual

TWS One Vocal UHF wireless system. user manual TWS One Vocal UHF wireless system user manual Musikhaus Thomann Thomann GmbH Hans-Thomann-Straße 1 96138 Burgebrach Germany Telephone: +49 (0) 9546 9223-0 E-mail: info@thomann.de Internet: www.thomann.de

More information

TR20A116-D RE / 08.2016 DE EN FR NL IT ES PT Anleitung für Montage und Betrieb Funk-Codetaster FCT 3 BiSecur Instructions for fitting and operating Radio code switch FCT 3 BiSecur Instructions de montage

More information

Out 1 sin / cos 1Vpp. sin / cos 1Vpp. Out 3. sin / cos 1Vpp. Out 4 sin / cos 1Vpp. Interface type SV211 SinCos signal splitter with 4 SinCos outputs

Out 1 sin / cos 1Vpp. sin / cos 1Vpp. Out 3. sin / cos 1Vpp. Out 4 sin / cos 1Vpp. Interface type SV211 SinCos signal splitter with 4 SinCos outputs Operating Manual Out 1 sin / cos 1Vpp Input: sin / cos 1 Vpp Out 2 sin / cos 1Vpp Out 3 sin / cos 1Vpp SV 211 Out 4 sin / cos 1Vpp Interface type SV211 SinCos signal splitter with 4 SinCos outputs Product

More information

HBV 800BK / NV / VW electro-acoustic violin

HBV 800BK / NV / VW electro-acoustic violin HBV 800BK / NV / VW electro-acoustic violin user manual Musikhaus Thomann Thomann GmbH Hans-Thomann-Straße 1 96138 Burgebrach Germany Telephone: +49 (0) 9546 9223-0 E-mail: info@thomann.de Internet: www.thomann.de

More information

Industrial motor controller for brushed DC motors 12 VDC

Industrial motor controller for brushed DC motors 12 VDC Industrial motor controller for brushed DC motors 12 VDC Design for output currents up to 5 A Control with the following functions: - reversal of direction of rotation - rotational speed control (external)

More information

Panther. Installation instructions. Receivers PN-RX-MN5 (PN-R8-1) PN-RX-MN5E (PN-R8-10) PN-RX-MD11 (PN-R8-6) PN-RX-MD11E (PN-R8-11)

Panther. Installation instructions. Receivers PN-RX-MN5 (PN-R8-1) PN-RX-MN5E (PN-R8-10) PN-RX-MD11 (PN-R8-6) PN-RX-MD11E (PN-R8-11) Provided by: www.hoistsdirect.com Panther Installation instructions Receivers PN-RX-MN5 (PN-R8-1) PN-RX-MN5E (PN-R8-10) PN-RX-MD11 (PN-R8-6) PN-RX-MD11E (PN-R8-11) IM-PN-RX101-A01-EN Language: English

More information

FMG90 Series Electromagnetic Flow Meter

FMG90 Series Electromagnetic Flow Meter . FMG90 Series Electromagnetic Flow Meter - 2 - Series FMG90 Series FMG90 Table of contents page 0 About this operating manual... 4 1 Device description... 5 1.1 Delivery, unpacking and accessories...

More information

Manual for authorised electricians. Power meters. KD-401 Art.-Nr Version X00

Manual for authorised electricians. Power meters.  KD-401 Art.-Nr Version X00 Manual for authorised electricians Power meters KD-401 Art.-Nr. 22118 Version X00 info@sonnenbatterie.de www.sonnenbatterie.de EN IMPORTANT Read this documentation carefully before installation. Retain

More information

400 MHz Passive High-Voltage Probe R&S RT-ZH

400 MHz Passive High-Voltage Probe R&S RT-ZH Manual 400 MHz Passive High-Voltage Probe R&S RT-ZH11 1409.7737.02 Printed in Germany Test and Measurment Manufacturer ROHDE & SCHWARZ For comprehensive information about Rohde and Schwarz, please visit

More information

Troubleshooting for Growatt TL&MTL. (Ver1.2)

Troubleshooting for Growatt TL&MTL. (Ver1.2) Troubleshooting for Growatt TL&MTL (Ver1.2) 2013-7-15 Version Date Note Ver1.1 2013.7.15 First draft Ver1.2 2013.7.29 Remove Hungary in Country code list table, Hungary choose VDE 0126 Content General...

More information

TR20A120 RE / 02.2012 DE EN FR NL IT ES PT Anleitung für Montage und Betrieb Funk-Codetaster FCT 10 BiSecur Instructions for fitting and operating Radio code switch FCT 10 BiSecur Instructions de montage

More information

Active Transmitter Combiner 8:1 AC 3200-II. Instruction manual

Active Transmitter Combiner 8:1 AC 3200-II. Instruction manual Active Transmitter Combiner 8:1 AC 3200-II Instruction manual Contents Contents Important safety instructions... 2 The AC 3200-II active transmitter combiner 8:1... 4 Delivery includes... 4 Connection

More information

Installation Instructions RF-identification system Read/write head ANT513

Installation Instructions RF-identification system Read/write head ANT513 Installation Instructions RF-identification system Read/write head ANT513 80262946 / 00 04 / 2017 Contents 1 Preliminary note...4 1.1 Symbols used...4 2 Safety instructions...4 2.1 General...4 2.2 Radio

More information

Installation Instructions RF identification system Read/write head ANT430 ANT431

Installation Instructions RF identification system Read/write head ANT430 ANT431 Installation Instructions RF identification system Read/write head ANT430 ANT431 UK 80262949 / 00 04 / 2017 Contents 1 Preliminary note...4 1.1 Symbols used...4 2 Safety instructions...4 2.1 General...4

More information

roger schult Vintage 3-Band EQ W2395c Operating Manual Quick Guide

roger schult Vintage 3-Band EQ W2395c Operating Manual Quick Guide roger schult Vintage 3-Band EQ W2395c Operating Manual Quick Guide W2395c Operating Manual for api 500 system Version 03.2014 roger schult D 50374 Erftstadt Peter-May-Str. 104-1 - Table of Contents Page

More information

Industrial motor controller for brushed DC motors 24 VDC

Industrial motor controller for brushed DC motors 24 VDC Industrial motor controller for brushed DC motors 24 VDC Design for output currents up to 5 A Control with the following functions: - reversal of direction of rotation - open-loop speed control (external)

More information

PU202 Level converter & encoder signal generator without potential separation

PU202 Level converter & encoder signal generator without potential separation Operating Manual PU202 Level converter & encoder signal generator without potential separation Product features: Converts HTL signals from 10 up to 30 V (A / B / Z) into the corresponding TTL / RS422 format

More information

SmartBlock I/O Module - HE579DAC107/HE579DAC207 8/4 Channel Current and Voltage Output 0-5V / 0-10V / 4-20mA / 0-20mA - CsCAN

SmartBlock I/O Module - HE579DAC107/HE579DAC207 8/4 Channel Current and Voltage Output 0-5V / 0-10V / 4-20mA / 0-20mA - CsCAN SmartBlock I/O Module - HE579DAC107/HE579DAC207 8/4 Channel Current and Voltage Output 0-5V / 0-10V / 4-20mA / 0-20mA - CsCAN 1. SPECIFICATIONS / DIMENSIONS ANALOG OUT Number of Outputs 8 (207) or 4 (107)

More information

i.gear Terres Quickguide Telescopic antenna Magnetic base antenna MCX adapter USB 2.0 cable

i.gear Terres Quickguide Telescopic antenna Magnetic base antenna MCX adapter USB 2.0 cable i.gear Terres EN Index EN 7 b Operating instructions Thank you for buying the i.gear Terres. We are confident that this product will be the source of much enjoyment. Please read the following instructions

More information

2.7. IT system floor-standing distribution cabinet Series -IPS-F/EDS

2.7. IT system floor-standing distribution cabinet Series -IPS-F/EDS Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 65 35305 Grünberg Tel.: 0640 807-0 Fax: 0640 807-259 IT system floor-standing distribution cabinet Series -IPS-F/EDS for supplying power to medical locations

More information

Mounting instruction and operating manual. Access Point (UK) HmIP-HAP-UK

Mounting instruction and operating manual. Access Point (UK) HmIP-HAP-UK Mounting instruction and operating manual Access Point (UK) HmIP-HAP-UK Package contents Quantity Description 1 Homematic IP Access Point (UK) 1 Plug-in mains adapter 1 Network cable 2 Screws 2 Plugs 1

More information

AC 3. Active Antenna Combiner. Instruction manual

AC 3. Active Antenna Combiner. Instruction manual AC 3 Active Antenna Combiner Instruction manual Contents Contents Important safety instructions... 2 The AC 3 active transmitter combiner... 4 Delivery includes... 4 Operating controls... 5 Block diagram...

More information

I n s t a l l a t i o n M a n u a l. T E D P r o L i t e A B C. f o r. Shop for The Energy Detective products online at: Rev 3.

I n s t a l l a t i o n M a n u a l. T E D P r o L i t e A B C. f o r. Shop for The Energy Detective products online at: Rev 3. Rev 3.5 I n s t a l l a t i o n M a n u a l f o r T E D P r o H o m e T E D P r o L i t e A B C Shop for The Energy Detective products online at: 1.877.766.5412 IMPORTANT: The installation of your TED

More information

Cable Identifying Generator LCI TX / LCI TX-440

Cable Identifying Generator LCI TX / LCI TX-440 Operation manual Cable Identifying Generator LCI TX / LCI TX-440 Mess- und Ortungstechnik Measuring and Locating Technologies Elektrizitätsnetze Power Networks Kommunikationsnetze Communication Networks

More information

Operating manual IMPORTANT! READ CAREFULLY BEFORE USE. KEEP FOR THE ENTIRE LIFE OF THE PRODUCT. Heat meters. Deltamess TKS-WM compact heat meter

Operating manual IMPORTANT! READ CAREFULLY BEFORE USE. KEEP FOR THE ENTIRE LIFE OF THE PRODUCT. Heat meters. Deltamess TKS-WM compact heat meter Operating manual IMPORTANT! READ CAREFULLY BEFORE USE. KEEP FOR THE ENTIRE LIFE OF THE PRODUCT. Heat meters Deltamess TKS-WM compact heat meter 1 Contents Safety and warranty... 3 Radio system... 3 Lithium

More information

Model 5100F. Advanced Test Equipment Rentals ATEC (2832) OWNER S MANUAL RF POWER AMPLIFIER

Model 5100F. Advanced Test Equipment Rentals ATEC (2832) OWNER S MANUAL RF POWER AMPLIFIER Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) OWNER S MANUAL Model 5100F RF POWER AMPLIFIER 0.8 2.5 GHz, 25 Watts Ophir RF 5300 Beethoven Street Los Angeles, CA 90066

More information

Panther. Installation instructions. Receivers PN-R15-1 PN-R15-2 PN-R15-13 PN-R IM-PN-RX103-A03-EN Language: English (original)

Panther. Installation instructions. Receivers PN-R15-1 PN-R15-2 PN-R15-13 PN-R IM-PN-RX103-A03-EN Language: English (original) Panther Installation instructions Receivers IM-PN-RX0-A0-EN Language: English (original) PN-R5- PN-R5-2 PN-R5- PN-R5-4 CONTENTS Chapter : CUSTOMER INFORMATION Chapter 2: FUNCTIONAL SAFETY 6 Chapter : PRODUCT

More information

Technical Documentation

Technical Documentation Technical Documentation for metratec QuasarMX HF RFID Reader Date: April 2015 Version: 1.4 Technical Documentation metratec QuasarMX Page 1 of 13 Table of Contents 1 General Information / Security Advice...3

More information

JBus/Modbus Communication Card

JBus/Modbus Communication Card JBus/Modbus Communication Card Installation and Operation 05/2018 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries

More information

Broadband Step-Up Transformer. User Manual

Broadband Step-Up Transformer. User Manual Broadband Step-Up Transformer User Manual 990-1930 09/2004 Introduction Introduction About this unit The APC Step-Up Transformer provides 220 V power from 60 VAC Broadband cable systems. Safety Electrical

More information

UR200SI / UR200WE ENGLISH

UR200SI / UR200WE ENGLISH ENGLISH Hersteller Wörlein GmbH Tel.: +49 9103/71670 Gewerbestrasse 12 Fax.: +49 9103/716712 D 90556 Cadolzburg Email. info@woerlein.com GERMANY Web: www.woerlein.com UR200SI / UR200WE ENVIRONMENTAL PROTECTION

More information

- 4 - Fig. 3b. Fig. 1b. Fig. 2. Fig. 2b MT 300

- 4 - Fig. 3b. Fig. 1b. Fig. 2. Fig. 2b MT 300 MP 00 Manual 1 7 6 9 8 5 1 1 10 11 1 Fig. 1a Fig. 1b MT 00 Breite Buche Erle Pappel Balsa 0 0,5 0,8 0,8 0,8 max. Zustellung mm 0 0, 0,6 0,8 0,8 60 0, 0, 0, 0,8 80 0,1 0,1 0, 0,6 n Messerwelle = 6.000/min

More information

Instruction Manual ICM 3091N Digital AC Clampmeter EN FR IT DE ES

Instruction Manual ICM 3091N Digital AC Clampmeter EN FR IT DE ES Instruction Manual ICM 3091N Digital AC Clampmeter EN FR IT DE ES TABLE OF CONTENTS / EN TITLE TABLE OF CONTENTS PAGE 1. SAFETY INFORMATION... 1 2. TECHNICAL SPECIFICATIONS... 2 3. PARTS & CONTROLS...

More information

AT Advanced Wire Tracer. Users Manual

AT Advanced Wire Tracer. Users Manual AT-1000 Advanced Wire Tracer Users Manual AT-1000 Advanced Wire Tracer English Users Manual AT1000_Rev001 2008 Amprobe Test Tools. All rights reserved. Limited Warranty and Limitation of Liability Your

More information

OPTITEMP TT 20 Technical Datasheet

OPTITEMP TT 20 Technical Datasheet OPTITEMP TT 20 Technical Datasheet Analog PC-programmable two-wire transmitters for Pt100 Efficient PC-configuration without recalibration Very stable output Very fast response time The documentation is

More information

DeltaSol AX HE * * Differential temperature controller Manual for the specialised craftsman

DeltaSol AX HE * * Differential temperature controller Manual for the specialised craftsman DeltaSol X HE Differtial temperature controller Manual for the specialised craftsman Installation Operation Functions and options Troubleshooting *110633* 110633 Thank you for buying this RESOL product.

More information

LINETRAXX RCMB42. AC/DC sensitive residual current monitor for electric vehicle charging systems

LINETRAXX RCMB42. AC/DC sensitive residual current monitor for electric vehicle charging systems IETRAXX RCMB42 AC/DC sensitive residual current monitor for electric vehicle charging systems RCMB42x_D00167_04_D_XXE/08.2018 IETRAXX RCMB42 AC/DC sensitive residual current monitor for electric vehicle

More information

- Wiring Brochure Universal Reset Module 423e

- Wiring Brochure Universal Reset Module 423e - Wiring Brochure Universal Reset Module 4e W 4e 0/08 Information Brochure Choose controls to match application Application Brochure Design your mechanical applications Rough In Wiring Rough-in wiring

More information

Safety. Operating instructions Communications module ACM WAVE SYSTEM RF for gas meters with Absolute ENCODER AE2 with and without smart valve DANGER

Safety. Operating instructions Communications module ACM WAVE SYSTEM RF for gas meters with Absolute ENCODER AE2 with and without smart valve DANGER Edition 02.10 D GB NL SK www.docuthek.com Operating instructions ommunications module AM WAVE SYSTEM RF for gas meters with Absolute ENODER AE2 with and without smart valve Translation from the German

More information

OPTITEMP TT 10 C/R Technical Datasheet

OPTITEMP TT 10 C/R Technical Datasheet OPTITEMP TT 10 C/R Technical Datasheet Analogue 2-wire temperature transmitter Temperature linear 4...20 ma output Rangeable with solder pads and potentiometers Easy wiring through large center hole The

More information

INTELLIMETER REGISTER

INTELLIMETER REGISTER INTELLIMETER REGISTER MODEL RG2 INSTALLATION AND CONNECTIONS INSTALLATION MANUAL WARNING: Any work on or near energized metering equipment can present a danger of electrical shock. All work on these products

More information

Fault 514: communication error between the meter and the SH5K+

Fault 514: communication error between the meter and the SH5K+ Fault 514: communication error between the meter and the SH5K+ Fault 514 indicates that there is a communication error between the meter and the inverter. 1 Summary It is best to call us as soon as possible

More information

IEM 200 R UHF receiver. user manual

IEM 200 R UHF receiver. user manual IEM 200 R UHF receiver user manual Musikhaus Thomann Thomann GmbH Hans-Thomann-Straße 1 96138 Burgebrach Germany Telephone: +49 (0) 9546 9223-0 E-mail: info@thomann.de Internet: www.thomann.de 17.11.2015,

More information

instructions Version 6.0

instructions Version 6.0 instructions Version 6.0 D Montage Edelstahl-Standsäulen Seite...3 GB Installation Stainless Steel Vertical Column Page... 19 FR Notice de montage des colonnes en acier inox Page...35 GB GB Contact Important

More information

LMM31. Dimmer Micromodule, 1 load USER MANUAL 20410/ LMM31 ALL RIGHTS RESERVED MARMITEK

LMM31. Dimmer Micromodule, 1 load USER MANUAL 20410/ LMM31 ALL RIGHTS RESERVED MARMITEK LMM31 Dimmer Micromodule, 1 load USER MANUAL 20410/20111019 LMM31 ALL RIGHTS RESERVED MARMITEK TABLE OF CONTENTS TABLE OF CONTENTS... 2 SAFETY WARNINGS... 3 HOW DOES MARMITEK X-10 WORK?... 4 ADRESSES...

More information

RAIL MOUNTED NETWORK METER TYPE N27D USER S MANUAL

RAIL MOUNTED NETWORK METER TYPE N27D USER S MANUAL RAIL MOUNTED NETWORK METER TYPE N27D USER S MANUAL 1 Contents 1. Application... 5 2. meter set... 6 3. BASIC REQUIREMENTS, OPERATIONAL SAFETy... 6 4. installation... 10 4.1. Mounting... 10 4.2. External

More information

Wireless wall transmitter, 1-gang with inscription space, Wireless wall transmitter, 3-gang with inscription space

Wireless wall transmitter, 1-gang with inscription space, Wireless wall transmitter, 3-gang with inscription space Wireless wall transmitter, 1-gang with inscription space Order No. : 5331.. Wireless wall Order No. : 5333.. Operating instructions 1 Safety instructions Electrical devices may only be mounted and connected

More information

TETRIS User's Guide. High Impedance Active Probe DO177-1

TETRIS User's Guide. High Impedance Active Probe DO177-1 TETRIS 1500 High Impedance Active Probe User's Guide DO177-1 TETRIS 1500 Copyright 2010 Ltd. All rights reserved. Information in this publication supersedes that in all previously published material. Specifications

More information

Electromotoric actuators for stroke valves

Electromotoric actuators for stroke valves s ACVATIX Electromotoric actuators for stroke valves SAS.. Electromotoric actuators with 5.5 mm stroke and 400 N positioning force SAS31.. Operating voltage AC 230 V, 3-position control signal Operating

More information

HAWK5000 Operators Manual

HAWK5000 Operators Manual HAWK5000 Operators Manual Keison Products P.O. Box 2124, Chelmsford CM1 3UP, England Tel: +44 (0) 1245 600560 Fax: +44 (0) 1245 600030 Email: sales@keison.co.uk www.keison.co.uk KANE INTERNATIONAL LIMITED

More information