Occupancy Sensor OCS 100C Setup Guide

Size: px
Start display at page:

Download "Occupancy Sensor OCS 100C Setup Guide"

Transcription

1 Sensor OCS 00C Setup Guide The OCS 00C is a ceiling mounted occupancy sensor that incorporates ultrasonic (US) and passive infrared (PIR) into a dual technology sensor. The US sensor emits ultrasonic sound waves into an area and measures the speed of their return to detect the presence of people. Frequency changes are caused by the movement of people, which is detected by the US waves. The PIR sensor detects the presence of people based on the difference between the heat generated by moving people versus the ambient room temperature. The OCS 00C has a VDC power input, ground/common connection, normally open/closed relay, photocell, and occupancy output connections. Front Panel Features Ultrasonic Sensors Ultrasonic Sensors Figure. OCS 00C Front Panel Features Control Green LED (status indicator) Infrared/Photocell Lens Green LED Retainer (status indicator) Ring Infrared/Photocell Lens Green Retainer LED Ring (status indicator) Green LED (status indicator) Ultrasonic sensors () Detect movement in the room, based on ultrasonic sound waves. Green LED status indicators () Flash when the ultrasonic sensors detect occupancy. Infrared/Photocell lens Diffracts the incoming light and directs the light to the infrared/photocell sensor. The infrared/ photocell sensor, controls and DIP switches are located behind the lens. Red LED status indicator Located behind the infrared lens, this LED flashes when the infrared sensor detects occupancy. Retainer Ring Holds the optional IR mask in place. Remove to access all controls and DIP switches. DIP Switches A DIP Switches (A) Red Infrared Sensitivity Dial Black Timer Dial A ON B ON Figure. OCS 00C Controls DIP Switches (B) Green Ultrasonic Range Dial Blue Photocell Dial The settings for DIP Switches B (timer adjust) and B (sensitivity adjust) can be set to: Automatic mode The sensors automatically adjust for changes in usage and seasons, eliminating the need for manual adjustments and improving system performance. Manual mode The user sets the parameters of the sensors using the following dials. NOTE: A OPERATION OFF ON Not used Not used* Not used Threshold Auto threshold adjustment* The black timer dial is inactive when the B timer adjust DIP Switch is in Automatic mode. High sensitivity (low turn on threshold) LED indicators LEDs enabled* LEDs disabled Automatic adjust reset Toggle to reset (Default: OFF) *Default DIP Switches B B OPERATION OFF ON Strong airflow compensator Disabled* Enabled Over doorway mount Disabled* Enabled Timer adjust Automatic Manual* Sensitivity adjust Automatic Manual* *Default The red infrared sensitivity dial and green ultrasonic range dial are inactive when the B sensitivity adjust DIP Switch is set to Automatic mode.

2 Sensor OCS 00C Setup Guide (Continued) Black Timer Dial (see figure on the previous page) The occupancy sensor has a built in timer feature. When the sensor detects motion, it instantly triggers ON (high). Once occupancy is no longer detected, the timer begins. If no motion is detected and the timer expires, then the sensor triggers OFF (low). Use the black timer dial to set the amount of time before the sensor triggers OFF. NOTE: B DIP Switch must be set to ON for Manual mode, in order to adjust the timer manually. Ranges from 8 minutes to minutes. Full counter clock wise (CCW) = 8 minutes Full clock wise (CW) = minutes To enter the test mode (8 second timer) follow the steps below:. Open the retainer ring.. Rotate the black timer dial to about midway ( o clock).. Return to minimum setting (full CCW).. The timer will remain in the 8 second test mode for hour, then automatically reset to 8 minutes. 5. To manually force the timer out of the 8 second test mode, turn the timer adjustment approximately /6 inch clockwise. The setting is slightly above minimum (just above the 8 minute setting. Red Infrared Sensitivity Dial Adjust this dial to increase or decrease infrared sensitivity. Turn clockwise (CW) to increase sensitivity. Turn counter clockwise (CCW) to decrease sensitivity. The factory default setting is at 75%. Green Ultrasonic Range Dial Adjust this dial to increase or decrease ultrasonic sensitivity. Turn clockwise (CW) to increase sensitivity. Turn counter clockwise (CCW) to decrease sensitivity. The factory default setting is at 50%. NOTE: B DIP Switch must be set to ON for Manual mode, in order to adjust the Red Infrared Sensitivity Dial or the Green Ultrasonic Range Dial manually. Blue Photocell Dial The photocell prevents the sensor from turning on when the area is adequately lit with natural light and motion is detected. The sensor must be mounted directly over an area that is representative of the average, natural room lighting. Before setting the photocell control, wait until the natural light is brightest (optional). Adjust this dial to increase or decrease photocell sensitivity. Turn counter clockwise to decrease photocell sensitivity, causing it to activate with less light. Turn clockwise to increase photocell sensitivity, requiring brighter light to activate the sensor. Factory default is 00% (full clockwise). Full clockwise Photocell sensor is disabled. Range 0 to 000 LUX

3 Mask Patterns and Sensor Coverage An infrared mask may be needed to achieve the desired sensory coverage. Any area masked will block the PIR sensor from detecting motion in that area. Hallway Hallway Specific Area Masked No Mask Needed Center Mount (mask blocks sensor seeing out doorway into hallway) Corner Mount (no mask needed) Conference Room Mask 80º Mask Full Mask Using the Infrared Mask Rectangular Areas Over the Door Typical Mask Patterns Specific Areas to Mask ' (7 m) ' ( m) ' (0 m) ' (7 m) 67E Appliance Control Headquarters (Inside USA/Canada Only) USA - West FAX Rev. A OCS 00C U.S. Patents: 6559, 59609, 5699, 560, 6505, 60785, D06, 69, , Not Used Threshold (max Disabled) Center of Sensor Coverage Sensory Coverage US Minor Motion IR Minor Motion US Major Motion IR Major Motion NOTE: These coverage dimensions are achieved when the OCS 00C is installed 0 feet ( m) above the coverage area. 5' ( m) 6' (0 m) Figure. Mask Patterns and Sensor Coverage Diagrams

4 Sensor OCS 00C Setup Guide (Continued) Installation OCS 00C Parts Installation Method Nut Secure mounting post to the ceiling tile with nut and washer. Washer Cutting End Threaded Mounting Post Mounting Post Cover Plate Twist and lock threaded mounting post into the cover plate. Drill into ceiling tile. Cover Plate Adjustment Knobs Red: Infrared Range - 75% Default Black: Timer - 8 min to max - min Default Green: Ultrasonic Range -50% Default Blue: Photocell - max Default Match either arrow shown here with the arrow on the twist-lock cover plate. Then inserts the tabs into the slots. Twist until ratchet action indicates engagement. Center of Sensor Coverage Range of adjustment (click turn) 0 Adjustment Cover Plate Connect building wiring to wiring harness with wire nuts. Insert wiring through mounting post. A Not Used 67E Appliance Control Headquarters (Inside USA/Canada Only) USA - West FAX Rev. A Switch Settings: All switches OFF for full automatice operation U.S. Patents: 6559, 59609, 5699, 560, 6505, 60785, D06, 69, , A Threshold: OFF = low sensitivity, ON = high sensitivity A LED Control: OFF = LEDs active, ON = LEDs disabled A Automatic Adjust Reset: Toggle to reset OCS 00C B Strong Airflow Compensator: OFF = disable, ON = enable B Over Doorway Mounting: OFF = disable, ON = enable B Timer Adjust: OFF = automatic, ON = manual B Sensitivity Adjust: OFF = automatic, ON = manual Made in China Black : Ground Red: +VDC Blue: control output Grey: & Photocell control Relay Contacts: Blue/White = common Black/White = N.C. Yellow/White = N.O. output Connections Sensor Body Sensor Body 5 Attach sensor body to cover plate by aligning arrows and twist lock into place. Conference Room * Mask Full Mask 80º Mask * * Infrared Lens w/ Retainer Ring Installation Method Nut and Washer ( ea) Secure cover plate to the ceiling. NOTE: *Only use a mask if the PIR sensor needs to be blocked. Only one mask should be installed at any given time. ATTENTION: All structural steps and electrical installation must be performed by qualified personnel in accordance with local and national building codes and electrical codes. Toute étape structurelle et installation électrique, doit être effectuée par un personnel qualifié, conformément aux codes du bâtiment, aux codes incendie et sécurité, et aux codes électriques, locaux et nationaux. Only connect to Class III SELV systems. Connectez l unité uniquement à des systèmes fonctionnant en très basse tension de sécurité (TBTS) de classe III. Figure. Installation Diagram Insert wiring through cover plate. Mounting Bolts () Connect building wiring to wiring harness with wire nuts. Sensor Body Screw and mount the twist-lock cover plate.

5 M -S G L OCS 00C Wiring Diagram 5A MAX IPCP PRO 550 Control Processor Dual Zone 00-0V ~ 50-60Hz Sensor with VDC Power Supply BUS ID Single Zone 7 PWR OUT = 9W SWITCHED VDC 0W MAX TOTAL Tx Rx G TxRxG Tx Rx G TxRx G RTSCTS S G S G S G S G +V +S -S G ebus G VDC ECM DIO8 ECM DIO8 ebus Control Module Sensor with VDC Power Supply S B +V +S G S B ebus + V OUT DIGITAL I/O G G Tx Rx G TxRxG Tx Rx G TxRx G RTSCTS COM Ground (Black) + V (Red) PC.5 A MAX S G S G S G S G IR/SERIAL E t PC Power Module Ground (Black) Control Signal # (Blue) Ground (Black) + V (Red) B RELAYS Control Signal # (Blue) Figure 5. OCS 00C Wiring Diagram Blue/White Black/White Yellow/White PC Wiring ATTENTION: V OUT V OUT.5 MAX A 75 ma MAX Relay Contacts Common V IN + V (Red) Ground (Black) FLEX I/O Normally closed when unoccupied Normally open when unoccupied IPCP PRO 550 LAN A6-XX-XX-XX MAC: A6-XX-XX-XX S/N: ####### E###### OCS 00C Sensor Control Signal # (Blue) OCS 00C Sensor OCS 00C Sensor Black Red Blue Gray NOTE: Connections Ground + VDC control output and photocell control output The gray wire is used when the control system needs to know when the area is adequately lit with natural light and when motion is detected (for example, automatic lighting control through an control system). When wiring the blue or gray wires of the OCS to products with Digital or FLEX Input ports, configure the ports as Input without pull up. The sensor provides approximately VDC in the ON (High) state and 0 VDC in the OFF (Low) state. NOTE: Relay contacts could be used to trigger third party devices, such as HVAC, based on occupancy. Do not connect power until you have read the ATTENTION: notices on the next page. Ne branchez pas l alimentation avant d avoir lu les mises en garde «ATTENTION:» de la page suivante. Remove power from the system before making any connections. Mettez le système hors tension avant d effectuer tout raccordement. The OCS 00C requires VDC. If the sensors are connected to a device that does not provide VDC, use the included PC power module:. Connect a VDC power source to the VDC input on the supplied PC power converter, using a -pole captive screw connector.. Wire the PC VDC -pole captive screw connector to the black and red wires on the OCS 00C. A VDC pass-through is available to power additional VDC devices. V Power Source PC.5 A MAX V IN B V OUT V OUT.5 MAX A 75 ma MAX Sensor Additional Devices PC Power Module 5

6 Troubleshooting Problem Possible Cause Test Solution Sensor remains on. Constant noise. Reduce both green and red knobs by / turn and remove noise source. Move sensor to a less noisy area within the room. Sensor remains on too long. Timer setting is too high. Check DIP switch settings. Reduce timer setting. Hallway traffic turns sensor on. Infrared sensor can see into the hallway. Put sensor in timer test mode and walk the hallway. Move sensor, so it cannot see into the hallway. Safety Instructions For information on safety guidelines, regulatory compliances, EMI/EMF compatibility, accessibility, and related topics, see the Safety and Regulatory Compliance Guide on the website. FCC Class A Notice This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 5 of the FCC rules. The Class A limits provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause interference. This interference must be corrected at the expense of the user. NOTE: For more information on safety guidelines, regulatory compliances, EMI/EMF compatibility, accessibility, and related topics, see the Safety and Regulatory Compliance Guide on the website. Power Attention ATTENTION: These products are intended for use with a UL Listed LPS type power source. Ces produits doivent être utilisés avec une source d alimentation de type LPS certifiée UL. Use of a non-lps or unlisted power supply will void all regulatory compliance certification. L utilisation d une source d alimentation non-listée ou non-listée LPS annulera toute certification de conformité réglementaire. Unless otherwise stated, the AC/DC adapters are not suitable for use in air handling spaces or in wall cavities. The power supply is to be located within the same vicinity as the AV processing equipment in an ordinary location, Pollution Degree, secured to the equipment rack within the dedicated closet, podium, or desk. Sauf mention contraire, les adaptateurs CA/CC ne conviennent pas à une utilisation dans les espaces d aération ou dans les cavités murales. La source d alimentation doit être placée à proximité de l équipement dans un emplacement ordinaire soumis à un degré de pollution de catégorie II, solidement fixé au rack d équipement d une baie technique, d un pupitre, ou d un bureau. The installation must always be in accordance with the applicable provisions of National Electrical Code ANSI/NFPA 70, article 75 and the Canadian Electrical Code part, section 6. Cette installation doit toujours être conforme aux dispositions applicables du Code américain de l électricité (National Electrical Code) ANSI/NFPA 70, article 75, et du Code canadien de l électricité, partie, section 6. The power supply shall not be permanently fixed to building structure or similar structure. La source d alimentation ne devra pas être fixée de façon permanente à la structure de bâtiment ou à d autres structures similaires Electronics All rights reserved. All trademarks mentioned are the property of their respective owners Rev. F 05 8

Occupancy Sensor OCS 100C Setup Guide

Occupancy Sensor OCS 100C Setup Guide Sensor OCS 00C Setup Guide The OCS 00C is a ceiling mounted occupancy sensor that incorporates ultrasonic (US) and passive infrared (PIR) into a dual technology sensor. The US sensor emits ultrasonic sound

More information

Occupancy Sensor OCS 100C Setup Guide

Occupancy Sensor OCS 100C Setup Guide Sensor OCS 00C Setup Guide The OCS 00C is a ceiling mounted occupancy sensor that incorporates ultrasonic (US) and passive infrared (PIR) into a dual technology sensor. The US sensor emits ultrasonic sound

More information

Occupancy Sensor OCS 100W Setup Guide

Occupancy Sensor OCS 100W Setup Guide Sensor OCS 100W Setup Guide The OCS 100W is a wall-mounted occupancy sensor that incorporates ultrasonic (US) and passive infrared (PIR) into a dual technology sensor. The US sensor emits ultrasonic sound

More information

Occupancy Sensor OCS 100W Setup Guide

Occupancy Sensor OCS 100W Setup Guide Sensor OCS 100W Setup Guide The OCS 100W is a wall-mounted occupancy sensor that incorporates ultrasonic (US) and passive infrared (PIR) into a dual technology sensor. The US sensor emits ultrasonic sound

More information

ECM S10 Partition Sensor Setup Guide

ECM S10 Partition Sensor Setup Guide Product Category EC Partition ensor etup uide EC is a pollution degree product with a rated impulse voltage of V. Construction of Control is defined as Independently ounted. The purpose of the control

More information

Dual Technology Ceiling Mount Sensor

Dual Technology Ceiling Mount Sensor Dual Technology Ceiling Mount Sensor 369653c 1 02.07.13 The LOS-CDT Series dual technology ceiling-mount sensors can integrate into LutronR systems or function as stand-alone controls using a LutronR power

More information

Dual Technology Wall Mount Occupancy Sensor

Dual Technology Wall Mount Occupancy Sensor Occupant -1 02.01.06 Dual Technology Wall Mount Occupancy Sensor Models Available The Series wall-mount dual-technology sensors are used in spaces with pendant fixtures, ceiling fans, or high ceilings

More information

Dual Technology Wall Mount Occupancy Sensor

Dual Technology Wall Mount Occupancy Sensor LOS-WDT 1 11.04.08 Dual Technology Wall Mount Occupancy Sensor Models Available The wall-mount dual-technology sensors are used to control lighting in spaces that have pendant fixtures, ceiling fans, or

More information

CONTENTS OF THE BOX. *PIR sensor only **Dual Technology and PIR sensors only. Description PIR Ultrasonic Dual Technology

CONTENTS OF THE BOX. *PIR sensor only **Dual Technology and PIR sensors only. Description PIR Ultrasonic Dual Technology Instruction Bulletin 63249-420-283A4 08/2009 Wall Mount Occupancy Sensor SLSWPS1500, SLSWUS1500, SLSWDS1500 INTRODUCTION Wall Mounted Occupancy Sensors are Class 2 devices ideal for use in business or

More information

with Light Level, Isolated Relay and Manual On features

with Light Level, Isolated Relay and Manual On features DT-200 version 3 Dual Technology Low Voltage Occupancy Sensor with Light Level, Isolated Relay and Manual On features SPECIFICATIONS Voltage... 18-28VDC/VAC Current Consumption... 25mA Power Supply...WattStopper

More information

INSTALLATION MANUAL ES-SUB-WIRELESS-KIT ES-SUB-WIRELESS-RCVR

INSTALLATION MANUAL ES-SUB-WIRELESS-KIT ES-SUB-WIRELESS-RCVR INSTALLATION MANUAL ES-SUB-WIRELESS-KIT ES-SUB-WIRELESS-RCVR FCC STATEMENT This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC

More information

ETC Installation Guide

ETC Installation Guide Unison Echo Overview The Echo is a ceiling mounted sensor that utilizes passive infrared (PIR) technology, providing reliable vacancy and occupancy detection for lighting control. The sensor allows for

More information

Infrared Wall Mount Occupancy Sensor

Infrared Wall Mount Occupancy Sensor LOS-WIR 1 07.16.10 Infrared Wall Mount Occupancy Sensor The LOS-WIR wall-mounted passive infrared sensor is used in spaces with pendant fixtures, ceiling fans, or high ceilings (more than 12 ft./3.7 m).

More information

2 Pendant Adjustment. Pendant Slider Plate. 3/4 (19mm) IP, (29mm) O.D. Knockouts. 1/2 (13mm) IP, (22mm) O.D. Knockout

2 Pendant Adjustment. Pendant Slider Plate. 3/4 (19mm) IP, (29mm) O.D. Knockouts. 1/2 (13mm) IP, (22mm) O.D. Knockout CXB Series LED Luaire Universal Hook and Cord, and Optional Junction box or Pendant Mount with Sensor IMPORTANT SAFEGUARDS When using electrical equipment, basic safety precautions should always be followed

More information

BT11 Hardware Installation Guide

BT11 Hardware Installation Guide Overview The Mist BT11 delivers a BLE Array AP with internal antennas that are used for BLE based location. 1 Understanding the Product Included in the box: BT11 Mounting bracket with mounting hardware

More information

CXB Series SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE. LED Luminaire TO INSTALL: INSTALLATION INSTRUCTIONS INSTRUCTIONS D INSTALLATION

CXB Series SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE. LED Luminaire TO INSTALL: INSTALLATION INSTRUCTIONS INSTRUCTIONS D INSTALLATION CXB Series LED Luaire Junction Box, Pendant and Hook and Cord IMPORTANT SAFEGUARDS When using electrical equipment, basic safety precautions should always be followed including the following: READ AND

More information

SUPERPLANE 2.5 INSTALLATION INSTRUCTIONS WALL/SURFACE BACK MOUNT. A nd Avenue, Unit 1 Oakland,

SUPERPLANE 2.5 INSTALLATION INSTRUCTIONS WALL/SURFACE BACK MOUNT. A nd Avenue, Unit 1 Oakland, INSTALLATION INSTRUCTIONS SUPERPLANE 2.5 WALL/SURFACE BACK MOUNT A 1035 22nd Avenue, Unit 1 Oakland, CA 94606 P 510.489.2530 E TalkToUs@alwusa.com W alwusa.com SP2.5 - Safety & Warnings! 1. Read all instructions.

More information

v3 360 Passive Infrared Line Voltage Occupancy Sensor

v3 360 Passive Infrared Line Voltage Occupancy Sensor SPECIFICATIONS CI-355 v3 360 Passive Infrared Line Voltage Occupancy Sensor with Light Level feature Voltages... 120//230/277/347VAC, 50/60Hz Load Ratings @120VAC...0-800W Ballast/Tungsten/LED @230VAC

More information

Lenovo regulatory notice for wireless adapters

Lenovo regulatory notice for wireless adapters Lenovo regulatory notice for wireless adapters - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - This manual contains regulatory information for the following Lenovo products:

More information

IMPORTANT SAFEGUARDS READ AND FOLLOW ALL SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE

IMPORTANT SAFEGUARDS READ AND FOLLOW ALL SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE FSP-2X1 Digital High/Low Pir Fixture Integrated Sensor INSTALLATION INSTRUCTIONS IMPORTANT SAFEGUARDS When using electrical equipment, basic safety precautions should always be followed including the following:

More information

NetPA AT Series Setup Guide

NetPA AT Series Setup Guide DProduct NetPA Series Setup uide This guide provides basic instructions for an experienced technician to install the and NetPA 0070V Networked Power Amplifiers. Both the and NetPA 0070V models are collectively

More information

INSTALLATION INSTRUCTION Silo Multiples - New Construction Housing MT-4*15, MT-4*10

INSTALLATION INSTRUCTION Silo Multiples - New Construction Housing MT-4*15, MT-4*10 IMPORTANT SAFETY INSTRUCTIONS 1. Read all instructions before installing. 2. System is intended for installation by a qualified electrician in accordance with the National Electrical Code and local regulations.

More information

WRZ-SST-120 Wireless Sensing System Tool

WRZ-SST-120 Wireless Sensing System Tool WRZ-SST-120 Wireless Sensing System Tool WRZ-SST-120 24-10563- 55, Rev. C (barcode for factory use only) Part No. 24-10563-55, Rev. C Issued March 2017 Applications The WRZ-SST-120 Wireless Sensing System

More information

Polycom VoxBox Bluetooth/USB Speakerphone

Polycom VoxBox Bluetooth/USB Speakerphone SETUP SHEET Polycom VoxBox Bluetooth/USB Speakerphone 1725-49004-001C Package Contents Micro USB Cable 1.21 m 4 ft Carrying Case Security USB Cable 3 m 10 ft L-Wrench Optional Accessories Security USB

More information

FCC Certification Notice: IC Certification

FCC Certification Notice: IC Certification Users Manual VP4450 FCC Certification This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2)

More information

XtremeRange 5. Model: XR5. Compliance Sheet

XtremeRange 5. Model: XR5. Compliance Sheet XtremeRange 5 Model: XR5 Compliance Sheet Modular Usage The carrier-class, 802.11a-based, 5 GHz radio module (model: XR5) is specifically designed for mesh, bridging, and infrastructure applications requiring

More information

Installation Instructions

Installation Instructions CD-W00-x0-1 Series Wall Mount CO 2 Transmitters Installation Instructions CD-W00-00-1, CD-W00-N0-1 Part No. 24-9601-94, Rev. E Issued August 14, 2014 North American Emissions Compliance United States This

More information

ROUND LIGHTPLANE 1 3D FLUSH

ROUND LIGHTPLANE 1 3D FLUSH INSTALLATION INSTRUCTIONS ROUND LIGHTPLANE 1 3D FLUSH RLP1/3D/F Flush Mount Configuration LED A 1035 22nd Avenue, Unit 1 Oakland, CA 94606 P 510.489.2530 E TalkToUs@alwusa.com W alwusa.com Safety & Warnings!

More information

INSTALLATION INSTRUCTIONS SUPERPLANE 4 WALL MOUNT. A nd Avenue, Unit 1 Oakland, CA P E W alwusa.

INSTALLATION INSTRUCTIONS SUPERPLANE 4 WALL MOUNT. A nd Avenue, Unit 1 Oakland, CA P E W alwusa. INSTALLATION INSTRUCTIONS SUPERPLANE 4 WALL MOUNT A 1035 22nd Avenue, Unit 1 Oakland, CA 94606 P 510.489.2530 E TalkToUs@alwusa.com W alwusa.com SP4 - Safety & Warnings! 1. Read all instructions. 2. Install

More information

Axon Signal Unit Installation Manual

Axon Signal Unit Installation Manual Introduction The Axon Signal Unit (ASU) is part of a communications platform that interacts with an emergency vehicle s light bar. When the light bar activates, all properly equipped Axon Flex systems

More information

NV-WA40W. Installation and User Guide

NV-WA40W. Installation and User Guide NV-WA40W Installation and User Guide Introduction The NV-WA40W-AMP is a versatile 40-watt in wall zone amplifier perfectly suited to a variety of tasks. Its design allows two line level sources to be permanently

More information

Blue Node. User Manual

Blue Node. User Manual Blue Node User Manual CONTACT US LX Suite 101, 4 Cornwallis St, Eveleigh, 2015 National Innovation Centre Australian Technology Park Sydney, Australia +612 9209 4133 IoTCores.com.au LX IoT Cores Blue Node

More information

SUPERPLANE TM 4 RECESSED SP4R

SUPERPLANE TM 4 RECESSED SP4R Oakland, INSTALLATION INSTRUCTIONS SUPERPLANE TM RECESSED SPR TGrid ATZ Slot n A 1035 22nd Avenue, Unit 1 CA 606 P 510.8.2530 E TalkToUs@alwusa.com W alwusa.com SPR - Safety & Warnings! 1. Read all instructions.

More information

TE-6300P Series Temperature Sensors

TE-6300P Series Temperature Sensors TE-6300P Series Temperature Sensors Installation Instructions TE-63xxP-1 Part No. 24-4034-107, Rev. M Issued April 30, 2014 Supersedes August 26, 2013 Applications To meet plenum rating where Underwriters

More information

DCH-G020 mydlink Connected Home Hub

DCH-G020 mydlink Connected Home Hub DCH-G020 mydlink Connected Home Hub User s Manual Version 01.0 Oct. 15 th, 2014 Manual Page 1 10/16/2014 1. PRODUCT DESCRIPTION The DCH-G020 is a Connected Home Z-Wave Gateway used to control a variety

More information

TABLE OF CONTENTS. PixMob Broadcaster 1

TABLE OF CONTENTS. PixMob Broadcaster 1 TABLE OF CONTENTS 1- PixMob HUB Page 2 2- FCC Statements Page 4 3- IC Statements Page 5 4- Installation Page 6 5- Hub menu s Page 7 6- Troubleshooting Page 10 7- Hub characteristics Page 10 1 1. PixMob

More information

12 24 VAC/VDC ±10% (inhibited when voltage is applied) min. pulse width duration = 50 ms. Normal mode or Background Analysis mode

12 24 VAC/VDC ±10% (inhibited when voltage is applied) min. pulse width duration = 50 ms. Normal mode or Background Analysis mode DESCRIPTION SUPERSCAN-T Door-Mounted, Presence Sensor for Automatic, Pedestrian Doors SuperScan-T sensors are intended to be used with pedestrian, swing door systems. ENGLISH 1 1. Lens. Master circuit

More information

TC-LINK -200 Wireless 12 Channel Analog Input Sensor Node

TC-LINK -200 Wireless 12 Channel Analog Input Sensor Node LORD QUICK START GUIDE TC-LINK -200 Wireless 12 Channel Analog Input Sensor Node The TC-Link -200 is a 12-channel wireless sensor used for the precise measurement of thermocouples. Calibration is not required.

More information

Wireless Ceiling Mount Sensor for Occupancy / Vacancy Detection INSTALLATION GUIDE

Wireless Ceiling Mount Sensor for Occupancy / Vacancy Detection INSTALLATION GUIDE MOS-IR/DT Wireless Ceiling Mount Sensor for Occupancy / Vacancy Detection INSTALLATION GUIDE This guide covers all models of MOS-IR and MOS-DT ceiling occupancy sensor. The MOS-IR product family includes:

More information

CX-100. Installation Instructions. PIR Occupancy Sensor SPECIFICATIONS

CX-100. Installation Instructions. PIR Occupancy Sensor SPECIFICATIONS SPECIFICATIONS CX-1 PIR Occupancy Sensor Voltage... 24VDC Current Consumption... 19mA* Power Supply... WattStopper Power Pack Isolated Relay Rating... 1A@24VDC Time Adjustment... 15 seconds 3 minutes Sensitivity

More information

Mid-Power Expansion Unit (MxU) Quick Installation Sheet

Mid-Power Expansion Unit (MxU) Quick Installation Sheet Mid-Power Expansion Unit (MxU) Quick Installation Sheet CMA-597-AEN GENERAL INFORMATION 1. THE MxU supports the 2.5 GHz TDD band and is installed in conjunction with the mid-power remote unit (MRU) (ordered

More information

INSTALLATION AND SETUP GUIDE

INSTALLATION AND SETUP GUIDE INSTALLATION AND SETUP GUIDE K4460-1V6 2/06 Rev C ADEMCO 6150RF Keypad/Transceiver GENERAL INFORMATION The 6150RF Keypad/Transceiver is a combination unit incorporating a normally-open relay output and

More information

HIGH/LOW/OFF PIR OUTDOOR PHOTO/MOTION SENSOR IN IP66 ENCLOSURE WITH BLUETOOTH

HIGH/LOW/OFF PIR OUTDOOR PHOTO/MOTION SENSOR IN IP66 ENCLOSURE WITH BLUETOOTH HIGH/LOW/OFF PIR OUTDOOR PHOTO/MOTION SENSOR IN IP66 ENCLOSURE WITH BLUETOOTH Product Overview The FSP-3x1B is a family of passive infrared (PIR) outdoor sensors that raise or lower the electric lighting

More information

12V 7Ah 3.15A AC V +12V DC. Paxton Net2 plus 12V DC 12V DC EXIT /100 Ethernet. INPUT AC V 50 / 60 Hz 1.2A OUTPUT DC 13.

12V 7Ah 3.15A AC V +12V DC. Paxton Net2 plus 12V DC 12V DC EXIT /100 Ethernet. INPUT AC V 50 / 60 Hz 1.2A OUTPUT DC 13. Paxton ins-0006 3 4 - + +V DC V V V V V - 4V Clock/D V Clock/D V DC V DC 0 00 0/00 Ethernet Paxton Net plus I RS485 CAT5 TX RX V INPUT AC 00-4 50 / 60 Hz.A OUTPUT DC 3.8V A AC 00-4 V 7Ah 3.5A - +V DC +

More information

High Bay Occupancy Sensor for Use with Electronic Ballast HID Luminaires

High Bay Occupancy Sensor for Use with Electronic Ballast HID Luminaires Instruction Bulletin 63249-500-08A6 05/2011 High Bay Occupancy Sensor for Use with Electronic Ballast HID Luminaires SLSPIP210EB and SLSPIP210EBCT INTRODUCTION Figure 1: High Bay Occupancy Sensor for Use

More information

SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE LED SURFACE AMBIENT LUMINAIRE FACTORY SETTINGS. Configuration Value

SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE LED SURFACE AMBIENT LUMINAIRE FACTORY SETTINGS. Configuration Value LD URFAC AMBINT LUAIR OCCUPANCY NOR ACCORY: -WRAC-OC-1 For use with ssentia by Cree Wrap and L eries Luminaire INTALLATION INTRUCTION INTRUCTION D INTALLATION IMPORTANT AFGUARD When using electrical equipment,

More information

Installation Instructions

Installation Instructions Designer Wall Switch Occupancy Single Pole (One Location) or Multi-Location Rated: 12/277V, 6Hz Cat. No. ODS1Ø-IDx Incandescent 8W - 6.67A @ 12V Fluorescent 12VA - 1A @ 12V 27VA - 1A @ 277V Supplemental

More information

1100DH High Power Wireless Receiver

1100DH High Power Wireless Receiver 00DH High Power Wireless Receiver INSTALLATION GUIDE Description The 00DH High Power Wireless Receiver provides two-way, supervised communication using 900 MHz frequencyhopping spread-spectrum technology.

More information

High/Low Bay Passive Infrared Occupancy Sensor

High/Low Bay Passive Infrared Occupancy Sensor Models Sensors: HBP-111-L7, with IR remote capability HBP-112-L7, no IR capability High/Low Bay Passive Infrared Occupancy Sensor Mounting Modules: HBP-EM1 extender module HBP-SM1 surface mount module

More information

microos Occupant Sensors One Way microostm Occupant Sensor Two Way microostm Occupant Sensor Sensors

microos Occupant Sensors One Way microostm Occupant Sensor Two Way microostm Occupant Sensor Sensors microos Occupant Occupant Sensor microos-1 12.9.03 Lutron s One Way and Two Way microos Occupant enable Lutron systems to change light levels when a space is occupied and/or unoccupied. Occupant sensors

More information

Installing the FSP-211 Sensor in Light Fixture

Installing the FSP-211 Sensor in Light Fixture (grey) WATTSTOPPER VOLTAGE HIGH/LOW/OFF PIR FIXTURE INTEGRATED OUTDOOR PHOTO/MOTION SENSOR Product Overview The is a passive infrared (PIR) outdoor sensor that raises or lowers the electric lighting level

More information

HIGH/LOW/OFF PIR OUTDOOR PHOTO/MOTION SENSOR IN IP66 ENCLOSURE FOR FLEXIBLE MOUNTING

HIGH/LOW/OFF PIR OUTDOOR PHOTO/MOTION SENSOR IN IP66 ENCLOSURE FOR FLEXIBLE MOUNTING HIGH/LOW/OFF PIR OUTDOOR PHOTO/MOTION SENSOR IN IP66 ENCLOSURE FOR FLEXIBLE MOUNTING Product Overview The FSP-2x1B is a family of passive infrared (PIR) outdoor sensors that raise or lower the electric

More information

Taxonomies, Classifications, and Categories Residential dimmers, motion sensors, controls, & photo cells Wireless occupancy/vacancy sensor

Taxonomies, Classifications, and Categories Residential dimmers, motion sensors, controls, & photo cells Wireless occupancy/vacancy sensor 3804 South Street 75964-7263, TX Nacogdoches Phone: 936-569-7941 Fax: 936-560-4685 LRF20CR2BPWH Lutron Occupancy Sensor 1 Way FM 434 R2 Lutron Catalog Number Manufacturer Description Weight per unit Product

More information

Installation Instructions

Installation Instructions TECH SUPPORT The Watt Stopper, Inc. 2800 De La Cruz Blvd. Santa Clara, CA 95050, USA Tel: 1(800)879-8585 1(972)578-1699 Fax: 1(972)422-1311 www.wattstopper.com Outdoor 180 & 270 PIR Motion s Model#s: EW-100-120

More information

260X190mm/105 克铜版纸 / 黑白印刷

260X190mm/105 克铜版纸 / 黑白印刷 260X190mm/105 克铜版纸 / 黑白印刷 5172301 1 FEATURES A-Control Panel A1-Bass Volume Adjustment A2-Volume Adjustment A3-Audio Input Jack A4-Audio Output Jack for linking multiple chairs A5-Wire mode / Bluetooth

More information

802.11a/n/b/g/ac WLAN Module AMB7220

802.11a/n/b/g/ac WLAN Module AMB7220 AboCom 802.11a/n/b/g/ac WLAN Module AMB7220 User s Manual FCC Certification Federal Communication Commission Interference Statement This equipment has been tested and found to comply with the limits for

More information

INSTALLATION INSTRUCTIONS Oculux 3.5 Architectural Remodel

INSTALLATION INSTRUCTIONS Oculux 3.5 Architectural Remodel SAFETY INSTRUCTION IMPORTANT: NEVER attempt any work without shutting off the electricity. - Read all instructions before installing. - System is intended for installation by a qualified electrician in

More information

PowerView Remote Control Guide

PowerView Remote Control Guide FRONT: OPEN Group 3 Group 4 Group 2 Group 5 LEFT ARROW Sends the middle rail DOWN on Top-Down/Bottom-Up or Duolite products Group 1 Group 6 RIGHT ARROW Sends the middle rail UP on Top-Down/Bottom-Up or

More information

Pser G uide oduct Manual

Pser G uide oduct Manual ADC-T2000 Hub User Product Guide Manual Hub Product Manual 1 Set Up Required Standard home router with active Internet connection Z-Wave devices to be installed Indicator Lights White Flashing: no internet

More information

Indoor Contact Input Photosensor

Indoor Contact Input Photosensor General Information Indoor Contact Input Photosensor INSTALLATION SHEET Model# PPS-4 The Indoor Contact Input Photosensor (PPS-4) can be used with any Greengate lighting controller and may also be used

More information

Murata Bluetooth mesh Node. Installation Guide

Murata Bluetooth mesh Node. Installation Guide Murata Bluetooth mesh ode Installation Guide Shipped Components Murata Bluetooth mesh ode (BCC2ZZ1PR) ocknut Page 1 Caution Installation and maintenance must be done in accordance with local, state and

More information

Occupancy Sensors for High-Bay Applications

Occupancy Sensors for High-Bay Applications Wired for High-Bay Applications for High-Bay Applications 369606b 1 12.08.2017 Features Surface-mount and end-mount models available. 180 and 360 coverage lenses available. Low-voltage, passive infrared

More information

Installation Instructions

Installation Instructions WS-250 & WS-250-347 Passive Infrared Wall Switch Occupancy Sensor SPECIFICATIONS WS-250 Voltages...120 or 277VAC, 60Hz Load Requirements @ 120VAC, 60Hz... 0-800W ballast & tungsten, 1/6 hp @ 277VAC, 60Hz...

More information

GNSS multiconstellation, GPS+Glonass as a minimum; GSM; Accelerometer; SIM on Chip; Watch Dog; Power Management; RF transceiver; CAN Bus interface

GNSS multiconstellation, GPS+Glonass as a minimum; GSM; Accelerometer; SIM on Chip; Watch Dog; Power Management; RF transceiver; CAN Bus interface ZTE AT21 User Guide 1.1 Reference Architecture The reference architecture of the Kernel module is shown here below The main HW architecture features and physical constraints are summarized below: GNSS

More information

MPR kHz Reader

MPR kHz Reader MPR-5005 Page 1 Doc# 041326 MPR-5005 125kHz Reader Installation & Operation Manual - 041326 MPR-5005 Page 2 Doc# 041326 COPYRIGHT ACKNOWLEDGEMENTS The contents of this document are the property of Applied

More information

Clock Radio CR2307 INSTRUCTION MANUAL

Clock Radio CR2307 INSTRUCTION MANUAL Clock Radio CR2307 INSTRUCTION MANUAL Warnings and Precautions TO PREVENT FIRE OR SHOCK HAZARDS, DO NOT EXPOSE THIS UNIT TO RAIN OR MOISTURE. This symbol, located on back or bottom of the unit, is intended

More information

VIBRATION AND TEMPERATURE SENSOR (FY01) USER GUIDE (For FCC/IC Certification) Version: 0.7

VIBRATION AND TEMPERATURE SENSOR (FY01) USER GUIDE (For FCC/IC Certification) Version: 0.7 VIBRATION AND TEMPERATURE SENSOR (FY01) USER GUIDE (For FCC/IC Certification) Version: 0.7 TABLE OF CONTENTS 1. OVERVIEW... 4 1.1 Features... 4 1.2 Applications... 4 2. GETTING STARTED... 4 3. VIBRATION

More information

Tork EasyCube. User Manual.

Tork EasyCube. User Manual. Tork EasyCube User Manual www.torkusa.com 1 Introduction - Tork EasyCube Tork EasyCube delivers actionable washroom insights through a web user interface. The service consists of Tork dispensers equipped

More information

ODSOD-ID. D u a l - R e l ay Decora Wall Sw i t c h Occupancy Sensor

ODSOD-ID. D u a l - R e l ay Decora Wall Sw i t c h Occupancy Sensor D u a l - R e l ay Decora Wall Sw i t c h Occupancy Sensor ODSOD-ID The OD S 0 D - ID Occupancy Sensor Controls two separate lighting loads from a single unit Features new self-adjusting occupancy sensor

More information

EBDHS-MB-AT-DD. RF ceiling PIR presence detector DALI / DSI dimming. Product Guide. Overview. Features

EBDHS-MB-AT-DD. RF ceiling PIR presence detector DALI / DSI dimming. Product Guide. Overview. Features Product Guide EBDHS-MB-AT-DD RF ceiling PIR presence detector DALI / DSI dimming Overview The EBDHS-MB-AT-DD is a passive infrared (PIR) motion sensor combined with two output channels capable of controlling

More information

Technical Application Guide

Technical Application Guide Lighting Control Wireless Occupancy Sensor, Wireless Multi Sensor Technical Application Guide Easily enhance your smart lighting system with the Philips wireless occupancy sensor and multi sensor, which

More information

VP1801 Reader Motor Control

VP1801 Reader Motor Control EN Quick start manual VP1801 Reader Motor Control This sheet is only intended as quick start. See service manual for detailed instructions. The VP1801 is a Velos component that is used to identify animals

More information

INSTALLATION INSTRUCTION OCULUX 3 LED - New Construction

INSTALLATION INSTRUCTION OCULUX 3 LED - New Construction R3BNICA-10 SAFETY INSTRUCTION IMPORTANT: NEVER attempt any work without shutting off the electricity. Read all instructions before installing. System is intended for installation by a qualified electrician

More information

1: White buttons Used by the user on a daily basis. 2: Grey buttons Used only upon first startup.

1: White buttons Used by the user on a daily basis. 2: Grey buttons Used only upon first startup. Fig. 1 Lock/ unlock 30 1000 Light 1 100 300 zone 1 Learn actual lux LED 600 2000 0,4 0,6 0,8 1,0 1,2 Time 1 Light 2 zone 2 1,4 1,6 Factor of lux zone 1 Pulse 2min 5min Time Time 2 10min 15min 30min 1 2

More information

DU3 Ultrasonic Vehicle Detector

DU3 Ultrasonic Vehicle Detector DU3 Ultrasonic Vehicle Detector INSTALLATION/MAINTENANCE INSTRUCTIONS The DU3 is a vehicle detector unit with selfcontained electronics, designed for use with a drive-thru timer system. It should be installed

More information

Illuminati Wireless Light and Color Meter Model IM100. User Manual

Illuminati Wireless Light and Color Meter Model IM100. User Manual Illuminati Wireless Light and Color Meter Model IM100 User Manual About the IM100 The Illuminati IM100 is the world s first Bluetooth-enabled wireless light and color meter. Use it with your smartphone

More information

Model: VR-1A INSTALLATION AND OPERATING INSTRUCTIONS

Model: VR-1A INSTALLATION AND OPERATING INSTRUCTIONS INTRODUCTI Model: VR-1A INSTALLATI AND OPERATING INSTRUCTIS SINGLE-FUNCTI WIRELESS CTROL SYSTEM FOR OPERATING HI/LOW SERVO MOTOR IF YOU CANNOT READ OR UNDERSTAND THESE INSTALLATI INSTRUCTIS DO NOT ATTEMPT

More information

RFC1000. Wireless Transceiver for the RFOT, Therm A lert and RF2000A data loggers. Product User Guide

RFC1000. Wireless Transceiver for the RFOT, Therm A lert and RF2000A data loggers. Product User Guide RFC1000 Wireless Transceiver for the RFOT, Therm A lert and RF2000A data loggers Product User Guide Product User Guide Table of Contents Product Overview... 3 Software Installation... 4 Activating & Deploying

More information

INSTALLATION INSTRUCTION Accent

INSTALLATION INSTRUCTION Accent WARNING IMPORTANT: NEVER attempt to do any work without shutting off the electricity. 1. Read all instructions before installing. 2. System is intended for installation by a qualified electrician in accordance

More information

Installation Instructions RF8010/RF8310 RF8010/RF8310: EXTERNAL ANTENNA

Installation Instructions RF8010/RF8310 RF8010/RF8310: EXTERNAL ANTENNA Installation Instructions RF8010/RF8310 HES, Inc. 22630 N. 17th Ave. Phoenix, AZ 85027 800-626-7590 1 Product Description Dimensions Orientation Compatibility Access Control Systems Proximity Cards Frequency

More information

INSTALLATION INSTRUCTION Accent

INSTALLATION INSTRUCTION Accent WARNING IMPORTANT: NEVER attempt to do any work without shutting off the electricity. 1. Read all instructions before installing. 2. System is intended for installation by a qualified electrician in accordance

More information

INSTALLATION INSTRUCTION Adjustable Spot - Endurance Sign Lighting

INSTALLATION INSTRUCTION Adjustable Spot - Endurance Sign Lighting WARNING IMPORTANT: NEVER attempt to do any work without shutting off the electricity. 1. Read all instructions before installing. 2. System is intended for installation by a qualified electrician in accordance

More information

Warning: Electrical Hazard... 3 Safety Instruction Sheet for STG Product Overview What s in the box?... 4

Warning: Electrical Hazard... 3 Safety Instruction Sheet for STG Product Overview What s in the box?... 4 STG-2412 User Guide Warning: Electrical Hazard... 3 Safety Instruction Sheet for STG-2412... 3 Product Overview... 4 What s in the box?... 4 Using STG-2412 for Mixing, Processing, and Recording... 5 Software

More information

Wireless Occupancy Sensor User Guide

Wireless Occupancy Sensor User Guide Wireless Occupancy Sensor Wireless Occupancy Sensor User Guide This Manual covers both the Wide angle and the Narrow long range occupancy sensor. Dialight Part Numbers described here-in are: WOSU22BG2

More information

Model: VR-2A INSTALLATION AND OPERATING INSTRUCTIONS

Model: VR-2A INSTALLATION AND OPERATING INSTRUCTIONS Model: VR-2A INSTALLATI AND OPERATING INSTRUCTIS MULTI-FUNCTI WIRELESS REMOTE CTROL SYSTEM FOR OPERATING SERVO MOTOR VALVE, MANUALLY AND WITH A THERMOSTAT FUNCTI IF YOU CANNOT READ OR UNDERSTAND THESE

More information

Need Help? SA /

Need Help? SA / 1 FEATURES A-Control Panel A1-Vibration adjustment A2-Bass Volume Adjustment A3-Volume Adjustment A4-Audio Input Jack A5-Audio Output Jack for linking multiple chairs A6-Wire mode / Bluetooth mode Switch

More information

CSD Series Current Devices Solid Core with Relay

CSD Series Current Devices Solid Core with Relay CSD Series Current Devices Solid Core with Installation Instructions CSD-SA1E1-1 CSD-SA1E2-1 Part No. 24-10345-26, Rev. F Issued March 31, 2014 Supersedes April 5, 2013 Applications The Current Switch

More information

EA200 uhf EA200 vhf User Guide

EA200 uhf EA200 vhf User Guide EA200 uhf EA200 vhf User Guide 1 2 TABLE OF CONTENTS RF Safety & FCC... 4 Safety & Information... 5 Electromagnetic Interference Compliance... 6 Industry Canada Compliance... 7 Computer Software Copyrights...

More information

3 GHz Carrier Backhaul Radio. Model: AF-3X. Tel: +44 (0) Fax: +44 (0) LINK GPS MGMT DATA DATA

3 GHz Carrier Backhaul Radio. Model: AF-3X.   Tel: +44 (0) Fax: +44 (0) LINK GPS MGMT DATA DATA LINK GPS MGMT DATA DATA MGMT GPS LINK 3 GHz Carrier Backhaul Radio Model: AF-3X LINK GPS MGMT DATA 3 GHz Carrier Backhaul Radio Model: AF-3X LINK GPS MGMT DATA DATA MGMT GPS LINK Introduction Thank you

More information

Installation Instructions RF5910

Installation Instructions RF5910 Installation Instructions RF5910 HES, Inc. 22630 N. 17th Ave. Phoenix, AZ 85027 800-626-7590 1 Product Description Dimensions Orientation Compatibility Access Control Systems Proximity Cards Frequency

More information

Qt 600. Sound Masking - Paging - Music Installation Guide. Purchase date: Install date: MAC Address

Qt 600. Sound Masking - Paging - Music Installation Guide. Purchase date: Install date: MAC Address Qt 600 Sound Masking - Paging - Music Installation Guide Contents TOPIC System Overview Installing The Control Module Installing Qt PRO Emitters Connecting to Software Installing Audio Inputs Installing

More information

LRF20CR2BPWH Ceiling MNT Wireless Occ Sensor

LRF20CR2BPWH Ceiling MNT Wireless Occ Sensor 3804 South Street 75964-7263, TX Nacogdoches Phone: 936-569-7941 Fax: 936-560-4685 LRF20CR2BPWH Ceiling MNT Wireless Occ Sensor Lutron Catalog Number Manufacturer Description Weight per unit Product Category

More information

ETC Installation Guide

ETC Installation Guide Unison Echo Light Sensor Overview The provides light level measurement and lighting control for the connected Echo control system. The sensor measures lighting conditions to maintain a programmed lighting

More information

APM 6998 WiFi Module Manual

APM 6998 WiFi Module Manual Host Revision Information APM 6998 WiFi Module Manual Host Hardware Revision Host Module Driver Version Module Hardware Revision T3x Rev D1 v8.1.4.4 001E Host PCB Design Guidelines The following guidelines

More information

Operating Instructions

Operating Instructions UVX-300 Luminescence sensor Operating Instructions CAUTIONS AND WARNINGS CAUTION: The discrete output must not be connected to outputs from other sensors (i.e. outputs from multiple sensors must not be

More information

Evaluation Kit ATA8520-EK1-F and Extension Board ATA8520-EK3-F (US Version) Kit Content ATAN0157 APPLICATION NOTE

Evaluation Kit ATA8520-EK1-F and Extension Board ATA8520-EK3-F (US Version) Kit Content ATAN0157 APPLICATION NOTE ATAN0157 Evaluation Kit ATA8520-EK1-F and Extension Board ATA8520-EK3-F (US Version) APPLICATION NOTE Kit Content The ATA8520-EK1-F kit includes the following components: Standalone board 902MHz antenna

More information

Interface Manual Tank Level Float Stick System

Interface Manual Tank Level Float Stick System 1 Interface Manual Tank Level Float Stick System SignalFire Model: Sentinel-FS-3BIS The SignalFire Sentinel Float Stick Node is an Intrinsically Safe device with the following features: - Standard SignalFire

More information

FOR TRAINING PURPOSES ONLY DATED MATERIAL. Aperio Hub AH20/AH30 Installation Instructions. ASSA ABLOY, the global leader in door opening solutions

FOR TRAINING PURPOSES ONLY DATED MATERIAL. Aperio Hub AH20/AH30 Installation Instructions. ASSA ABLOY, the global leader in door opening solutions perio Hub H20/H30 Installation Instructions Covers WL-260 3 May 2011 SS LOY, the global leader in door opening solutions 1 H20/H30 - Table of Contents 2 H20/H30 - FCC and Industry Canada Statements 3 H20/H30

More information

XT-4850C FCC ID: GKM-XT4850C IC: IC: 10281A-XT4850C

XT-4850C FCC ID: GKM-XT4850C IC: IC: 10281A-XT4850C XT-4850C User Guide Model: XT-4850C FCC ID: GKM-XT4850C IC: IC: 10281A-XT4850C Version 2 1 Table of Contents Document Change History... 3 1 Introduction... 4 1.1 Feature Matrix... 4 2 Hardware Description...

More information

Installation Instructions

Installation Instructions SPECIFICATIONS WS-200 Automatic PIR Wall Switch Voltages...........................120 or 277VAC, 60Hz Requirements @ 120VAC, 60Hz........0-800W ballast & tungsten @ 277VAC, 60Hz.................0-1200W

More information