1 Unison Echo Overview The Echo is a ceiling mounted sensor that utilizes passive infrared (PIR) technology, providing reliable vacancy and occupancy detection for lighting control. The sensor allows for both auto on and auto off functionality along with any commands supplied from local stations. The provides 360 degree coverage of the installed location and is available in three models: E-OCC-SR- with small room lens covers 450 sq. ft. at 8 ft./ 800 sq. ft. at 10 ft. E-OCC - with standard room lens covers 1,800 sq. ft. at 8 ft./ 3,000 sq. ft. at 10 ft. E-OCC-HC - with high ceiling lens covers 300 sq. ft. at 10 ft./ 7,000 sq. ft. at 40 ft. Each sensor is available in white or black finish. Lens masks are provided to allow customized occupancy detection fields as required by each installation. Custom Configuration This document guides you through the installation and local configuration of the Echo. For more detailed information about custom configuration options available for the Echo using EchoAccess, reference the EchoAccess Mobile App integrated help system. To use the configuration settings applied using EchoAccess, DIP switch 2 must be enabled. Reference DIP Switch Settings on page 7. Corporate Headquarters Middleton, Wisconsin, USA Tel Service: (Americas) service@etcconnect.com London, UK Tel +44 (0) Service: (UK) service@etceurope.com Rome, IT Tel +39 (06) Service: (UK) service@etceurope.com Holzkirchen, DE Tel +49 (80 24) Service: (DE) techserv-hoki@etcconnect.com Hong Kong Tel Service: (Asia) service@etcasia.com Web: Copyright 2016 ETC. All Rights Reserved. Product information and specifications subject to change. ETC intends this document to be provided in its entirety. 7186M2181 Rev A Released Echo Occupancy/Vacancy Sensor Page 1 of 12 Electronic Theatre Controls, Inc.
2 Wire Specification Sensors connect to the EchoConnect communication bus. EchoConnect is a bidirectional protocol that uses one pair of wires (data + and data -) for both data and power. ETC recommends using Belden 8471 (or approved equal) Class II wire. The total combined length of an EchoConnect wire run (using Belden 8471, or equal) may not exceed 1,640 feet (500m). All control wiring should be installed and terminated by a qualified installer and should follow standard wiring installation practices. Leave approximately 10 inches (254mm) of wiring in the back box for connection to allow slack for future service needs. ETC requires that all sensors be grounded. Pull an additional 14 AWG (1.5mm 2 ) wire for grounding when control wires are not installed in grounded metal conduit. - When using Category5 (or equivalent) cable on the EchoConnect communication bus, please note the following: - Cat5 wiring must be terminated using EchoConnect Cat5 Termination Kit and must be installed using a bus topology. Refer to the installation guide that is provided with the Cat5 Termination Kit (7186A1207) for information to terminate Cat5 wiring. - Not all topologies are supported using Cat5; careful planning is required to ensure the proper termination kits are available and the wire is pulled appropriately. Installation Environment s are intended for installation to a finished ceiling surface, ceiling tile mounted, attached to a round fixture junction box or single-gang RACO switch box. The sensor operates in ambient temperatures of 0 C to 40 C, with a maximum of 90% non-condensing humidity. ETC recommends paying special attention to the installation environment: The sensor must have an unobstructed view of the room. Do not mount behind or near tall cabinets, shelves, hanging light fixtures, etc. Do not install the sensor within eight feet from an HVAC airflow duct/ vent. Install the sensor where it cannot easily sense movement in areas outside of the intended space, such as hallways, glass partitions, or adjacent rooms. If the installation location cannot avoid these Echo Occupancy/Vacancy Sensor Page 2 of 12 Electronic Theatre Controls, Inc.
3 conditions, portions of the lens can be masked to block the sensor view of these undesired areas. Reference Lens Masking on page 10. Parts and Supplies The following parts and supplies are included with the ordered: Soft ceiling tile adaptor 2 each screws, 6-32 x 3/4 and 1 3/4 EchoConnect & ESD ground 3 lens masks wire pigtails - Follow all local code requirements for terminating wire. - Use appropriately sized wire nuts (not provided) to secure each termination. The EchoConnect pigtail is only required when the sensor is installed in series with other stations or sensors. If you are not continuing the data run, direct termination on the control board is recommended. Installation The is provided with a twist-lock mounting plate that can be mounted to a junction box, finished ceiling, or soft ceiling tile. Determine the installation method and follow the detailed instructions: See Junction Box Installation on page 4. See Soft Ceiling Tile Installation on page 5. See Lens Masking on page 10. Echo Occupancy/Vacancy Sensor Page 3 of 12 Electronic Theatre Controls, Inc.
4 Junction Box Installation Step 3: Step 4: Step 5: Terminate wires here Step 1: Step 2: Pull the Belden 8471 (or equivalent) and 14 AWG (2.5mm 2 ) ground wire to the junction box. If you are installing the sensor in series with other sensors or stations (continuing the data run), use the provided EchoConnect pigtail, ESD ground pigtail and connectors (not provided) to make the terminations. If you are not continuing the data run, proceed to Step 3. a: Strip each wire to the appropriate length, depending on the wire nut or other termination used (wire nuts are not provided). b: Twist the data - (typically black) EchoConnect wire, the black lead from the EchoConnect pigtail, and any continuing EchoConnect (typically black) wire together and secure with a wire nut. c: Repeat the above steps for the data + (typically white) EchoConnect wire and the ESD ground wire. Orient the smooth side of the mounting plate to the junction box and pull the EchoConnect wires (or terminated pigtail) from the junction box through the provided holes near the center of the mounting plate. Secure the mounting plate to the junction box using the screws provided (both short and long screws are provided for convenience). Strip each wire 5/16 (8mm) and terminate the EchoConnect (white and black wires) and the ground wire (green/yellow) to the EchoConnect terminal block located on the sensor controller. Torque each termination to in-lb. a: Terminate the white incoming wire to the data + terminal. b: Terminate the black incoming wire to the data - terminal. c: Terminate the green/yellow (ground) wire to the ground terminal. Echo Occupancy/Vacancy Sensor Page 4 of 12 Electronic Theatre Controls, Inc.
5 Step 6: Attach the sensor to the mounting plate by aligning the tabs on the sensor with the slots on the mounting plate, then twist clockwise until the two are secured into place. Soft Ceiling Tile Installation EchoConnect pigtail and connectors (optional use) Poke the adapter through the ceiling tile, then bend it over for a secure fit. Terminate wires here Step 1: Pull the Belden 8471 (or equivalent) and 14 AWG (2.5mm 2 ) ground wire to the installation location. Step 2: If you are installing the sensor in series with other sensors or stations (continuing the data run), use the provided EchoConnect pigtail, ESD ground pigtail and connectors (not provided) to make the terminations. If you are not continuing the data run, proceed to Step 3. a: Strip each wire to the appropriate length, depending on the wire nut or other termination used (wire nuts are not provided). b: Twist the data - (typically black) EchoConnect wire, the black lead from the EchoConnect pigtail, and any continuing EchoConnect (typically black) wire together and secure with the wire nut. c: Repeat the above steps for the data + (typically white) EchoConnect wire, and for the ESD ground wires. Step 3: Create a hole for wire pass-through in the ceiling tile by poking through the center hole or oblong hole of the mounting plate, then pull the wires through. Echo Occupancy/Vacancy Sensor Page 5 of 12 Electronic Theatre Controls, Inc.
6 Step 4: Step 5: Orient the smooth side of the mounting plate to the finished side of the ceiling tile and align and insert the soft ceiling tile adapter through the holes provided near the center of the mounting plate. Reference the graphic on the previous page. Poke the tines of the adapter through the ceiling tile, then bend each tine over in opposite directions for a secure fit on the unfinished side of the ceiling tile. Step 6: Sensor Configuration Strip each wire 5/16 (8mm) and terminate the EchoConnect (white and black wires) and ground wire (green/yellow) to the EchoConnect terminal block located on the sensor control board. Torque each termination to in-lb. a: Terminate the white incoming wire to the data + terminal. b: Terminate the black incoming wire to the data - terminal. c: Terminate the green/yellow (ground) wire to the labeled ground terminal. The Echo participates in an Echo system using the configured Space and Address, which are selectable using the rotary switches on the rear panel of the sensor. Additional DIP switches and the [Mode] button, also located on the rear panel, set the sensor functionality and the occupancy detected action. Set Space and Address Two rotary switches on the rear panel of the controller provide for assignment of the sensor Space and Address. By default, these switches are set to Space 1, Address 1. Commands are shared by all devices within a given space. Step 1: Set the Space rotary switch to the desired number (1 thru 16) for the space you want the sensor to control. Step 2: Set the Address rotary switch to desired address (1 thru 16) for the sensor identification in the selected space. Do not duplicate a device Address within the same Space. Echo Occupancy/Vacancy Sensor Page 6 of 12 Electronic Theatre Controls, Inc.
7 DIP Switch Settings DIP switches on the rear panel of the Occupancy Sensor provide for additional configuration options including Use Custom Config, Vacancy Timeout, Enable/Disable PIR detection LED, and the ability to restore the sensor to its factory defaults. DIP Switch 2 DIP switch 2 enables Custom Config which instructs the sensor to use settings that are configured using the EchoAccess Mobile App. This setting is Off by default. When Custom Config is set to Off, the default position, local DIP switch settings for Vacancy Timeout and Enable PIR LED are used. Sensor actions can be adjusted using the program [Mode] button. When Custom Config is set to On, all other local DIP switch settings are ignored. Instead, the settings made by the EchoAccess Mobile App for Vacancy Timeout, Enable PIR LED, and Occupancy actions are used. DIP Switch 3&4 DIP switch 3 & 4 set the Vacancy Timeout to 5, 15, 30 minutes, or Auto. See Vacancy Timeout on page 9. 5 min = Switches 3 and 4 are Off. 15 min = Switch 3 is Off and Switch 4 is On (default). 30 = Switch 3 is On and Switch 4 is Off. Auto = Both switches are On. See Auto Vacancy Timeout on page 10. DIP Switch 5 DIP switch 5 enables/disables the red PIR detection LED. When the switch is Off, the PIR LED disables unless it is in Walk Test mode. When set to On, the red PIR LED will illuminate the sensor lens when movement is detected. The default position is On. DIP Switch 8 DIP switch 8 provides a Restore Defaults at Boot function. The factory defaults are restored by setting this DIP switch On, and cycling power to the station. The default position is Off. DIP switches 1, 6, and 7 are not currently used and are reserved for future development. Leave them at their default Off setting. Echo Occupancy/Vacancy Sensor Page 7 of 12 Electronic Theatre Controls, Inc.
8 Power Up and Test Power Up All EchoConnect terminations in the system must be made before applying power to the system and sensor. When the sensor is powered up, the PIR LED illuminates for one minute for calibration and warm-up, and then returns to normal operation. Configuration Sensor configuration for Basic config mode (DIP switch 2 set to Off) can be accomplished locally on the sensor using the other available DIP switches, [MODE] button and LED, and the Auxiliary button. See Preset below, and Vacancy Timeout on page 9 for local configuration instructions. Preset The [MODE] button and LED found on the rear panel of the sensor sets the sensor into Program Mode. Both the [MODE] button and LED, and the Auxiliary A button are used for configuration of the occupancy action. The A button and Mode LED are used to program the preset that is activated with an occupancy state change. The Mode LED blinks to indicate the current preset number used. When vacancy is detected, the sensor will activate a Space Off command. When functionality other than Space Off is required, place the sensor in Custom config mode (DIP switch 2 On). Customization of the Occupancy Sensor and all actions are configured using the EchoAccess Mobile App. For more detailed information about custom configuration options available for the Echo using EchoAccess, reference the EchoAccess Mobile App integrated help system. Echo Occupancy/Vacancy Sensor Page 8 of 12 Electronic Theatre Controls, Inc.
9 Auxiliary button Walk Test button MODE button MODE LED rear panel view Step 1: Step 2: Step 3: Step 4: Press and hold the [MODE] button for 3 seconds to enter Program Mode. Program Mode allows adjustment of the preset that activates for occupancy detection. By default, this is Preset 1. The A button, located on the front of the sensor, blinks to indicate the preset number controlled by the occupancy action. Press and release the A button the number of times to set the new preset. (For example: press and release ten times to set Preset 10.) The A button blinks the number of the preset used for the occupancy event action. Press and release the [MODE] button to save the current setting. The Mode/Sensor count LED turns off and the A button again blinks out the saved preset index. Attach the sensor to the mounting plate by aligning the tabs on the sensor with the slots on the mounting plate, then twist clockwise until the two are locked into place. Vacancy Timeout Vacancy timeout is the amount of time the sensor waits to take action after no movement is detected. By default, vacancy timeout is set to 15 minutes (indicated by DIP switch 3 set to Off and 4 set to On). When the vacancy timeout ends, the grace period begins. When the sensor detects vacancy, the vacancy timeout period begins. If the sensor does not detect occupancy again during the vacancy timeout period, the lights turn off and a 30 second grace period begins. Echo Occupancy/Vacancy Sensor Page 9 of 12 Electronic Theatre Controls, Inc.
10 Grace Period The sensor features a 30 second grace period after a vacancy timeout occurs to help prevent false vacancy detection. During this grace period, if the sensor detects occupancy, it will restore the previous lighting condition. Auto Vacancy Timeout The Auto vacancy timeout setting varies vacancy the timeout between 5 and 30 minutes depending on how often it identifies an occupancy trigger after a vacancy timeout occurs (during the grace period). Lens Masking Lens masks are provided in the packaging for your convenience, used to block a section of the lens from detecting occupancy. Step 1: As needed, trim the lens mask to fit the desired area to be blocked. Step 2: Gently press down on the sensor lens, which will give only slightly, and insert the lens mask. Step 3: Rotate the lens mask around the dome to block the required area from occupancy sensing. PIR Detection The PIR detection automatically adjusts its sensitivity to eliminate nuisance tripping. When the sensor powers on, the red PIR LED illuminates for approximately 60 seconds to identify Power Up state. Sensor configuration is not allowed. During this time, no events are triggered. Echo Occupancy/Vacancy Sensor Page 10 of 12 Electronic Theatre Controls, Inc.
11 Test s offer a Walk Test mode which shortens the vacancy timer to 10 seconds, allowing for simple and quick verification of the sensors coverage and range in the installed space. Walk-Test mode automatically exits and the sensor returns to normal operation after 5 minutes and can be manually terminated early by pressing the [Walk Test] button. Auxiliary button Walk Test button Enable Walk Test Mode Step 1: Step 2: Step 3: Step 4: Step 5: Prepare the site for configuration. a: Make certain the sensor and lighting loads are powered and connected for control by the Echo controller. b: You will need direct access to the in order to place it into Walk Test mode. Press the [Walk Test] button on the front of the sensor to enable the Walk Test feature at the sensor. A green LED will begin to flash, indicating Walk Test is enabled and the vacancy/no vacancy occupancy timer will be shortened to 10 seconds. Move throughout the space including corners and areas that may specifically be obscured from line of sight to the sensor. Each time the sensor detects movement, the lens will illuminate red. Adjust the lens masking, if installed, blocking certain areas of the installed space from sensor detection. See Lens Masking on page 10. Walk Test mode will automatically exit after five minutes from the time it was enabled. To manually exit the Walk Test mode, press either of the buttons on the sensor. Echo Occupancy/Vacancy Sensor Page 11 of 12 Electronic Theatre Controls, Inc.
12 0 Small Room side view 8ft 2.4m 12ft 3.7m 15ft 4.6m 5ft 1.5m 0 5ft 1.5m 15ft 4.6m Large Room side view 0 8ft 2.4m 12ft 3.7m 40ft 12.2m 30ft 9.1m 0 30ft 9.1m 40ft 12.2m 0 High Ceiling side view 30ft 9.1m 40ft 12.2m 40ft 12.2m 30ft 9.1m 0 30ft 9.1m 40ft 12.2m Echo Occupancy/Vacancy Sensor Page 12 of 12 Electronic Theatre Controls, Inc.
ETC Installation Guide
Unison Echo Light Sensor Overview The provides light level measurement and lighting control for the connected Echo control system. The sensor measures lighting conditions to maintain a programmed lighting
More informationWireless Ceiling Mount Sensor
Wireless Ceiling Mount Sensor Lutron s occupancy and vacancy sensors are wireless ceiling-mounted battery-powered passive infrared (PIR) sensors that automatically control lights via RF communication to
More informationv3 360 Passive Infrared Line Voltage Occupancy Sensor
SPECIFICATIONS CI-355 v3 360 Passive Infrared Line Voltage Occupancy Sensor with Light Level feature Voltages... 120//230/277/347VAC, 50/60Hz Load Ratings @120VAC...0-800W Ballast/Tungsten/LED @230VAC
More informationCONTENTS OF THE BOX. *PIR sensor only **Dual Technology and PIR sensors only. Description PIR Ultrasonic Dual Technology
Instruction Bulletin 63249-420-283A4 08/2009 Wall Mount Occupancy Sensor SLSWPS1500, SLSWUS1500, SLSWDS1500 INTRODUCTION Wall Mounted Occupancy Sensors are Class 2 devices ideal for use in business or
More informationOccupancy Sensors for High-Bay Applications
Wired for High-Bay Applications for High-Bay Applications 369606b 1 12.08.2017 Features Surface-mount and end-mount models available. 180 and 360 coverage lenses available. Low-voltage, passive infrared
More informationDual Technology Wall Mount Occupancy Sensor
Occupant -1 02.01.06 Dual Technology Wall Mount Occupancy Sensor Models Available The Series wall-mount dual-technology sensors are used in spaces with pendant fixtures, ceiling fans, or high ceilings
More informationInfrared Wall Mount Occupancy Sensor
LOS-WIR 1 07.16.10 Infrared Wall Mount Occupancy Sensor The LOS-WIR wall-mounted passive infrared sensor is used in spaces with pendant fixtures, ceiling fans, or high ceilings (more than 12 ft./3.7 m).
More informationLRF20CR2BPWH Ceiling MNT Wireless Occ Sensor
3804 South Street 75964-7263, TX Nacogdoches Phone: 936-569-7941 Fax: 936-560-4685 LRF20CR2BPWH Ceiling MNT Wireless Occ Sensor Lutron Catalog Number Manufacturer Description Weight per unit Product Category
More informationRadio Powr SavrT Occupancy / Vacancy Sensor
369480c 1 01.25.13 Radio Powr SavrT Occupancy / Vacancy Sensor LutronR Radio Powr SavrT occupancy/vacancy sensors are wireless, battery-powered passive infrared (PIR) sensors that automatically control
More informationETC Installation Guide
ETC Installation Guide Unison Using this Guide This document is intended to guide you through the installation of the DRd Semi-Recessed installation kit. Reference the Unison DRd Rack Enclosure Installation
More informationDual Technology Wall Mount Occupancy Sensor
LOS-WDT 1 11.04.08 Dual Technology Wall Mount Occupancy Sensor Models Available The wall-mount dual-technology sensors are used to control lighting in spaces that have pendant fixtures, ceiling fans, or
More informationRadio Powr SavrTM Wireless Occupancy / Vacancy Ceiling Sensor
Radio Powr SavrTM Wireless Occupancy / Vacancy Sensor Lutron Radio Powr SavrTM occupancy/vacancy sensors are wireless, battery-powered, passive infrared (PIR) sensors that automatically control lights
More informationTaxonomies, Classifications, and Categories Residential dimmers, motion sensors, controls, & photo cells Wireless occupancy/vacancy sensor
3804 South Street 75964-7263, TX Nacogdoches Phone: 936-569-7941 Fax: 936-560-4685 LRF20CR2BPWH Lutron Occupancy Sensor 1 Way FM 434 R2 Lutron Catalog Number Manufacturer Description Weight per unit Product
More informationwith Light Level, Isolated Relay and Manual On features
DT-200 version 3 Dual Technology Low Voltage Occupancy Sensor with Light Level, Isolated Relay and Manual On features SPECIFICATIONS Voltage... 18-28VDC/VAC Current Consumption... 25mA Power Supply...WattStopper
More informationmicroos Occupant Sensors One Way microostm Occupant Sensor Two Way microostm Occupant Sensor Sensors
microos Occupant Occupant Sensor microos-1 12.9.03 Lutron s One Way and Two Way microos Occupant enable Lutron systems to change light levels when a space is occupied and/or unoccupied. Occupant sensors
More informationwww.greenelectricalsupply.com Wireless Wall-Mount Sensor Lutron wall-mounted occupancy and vacancy sensors are wireless, battery-powered, passive infrared (PIR) sensors that automatically control lights
More informationCX-100. Installation Instructions. PIR Occupancy Sensor SPECIFICATIONS
SPECIFICATIONS CX-1 PIR Occupancy Sensor Voltage... 24VDC Current Consumption... 19mA* Power Supply... WattStopper Power Pack Isolated Relay Rating... 1A@24VDC Time Adjustment... 15 seconds 3 minutes Sensitivity
More informationDual Technology Ceiling Mount Sensor
Dual Technology Ceiling Mount Sensor 369653c 1 02.07.13 The LOS-CDT Series dual technology ceiling-mount sensors can integrate into LutronR systems or function as stand-alone controls using a LutronR power
More informationWireless Ceiling Motion Sensor for Occupancy / Vacancy Detection with integrated diagnostic tools INSTALLATION GUIDE
MOS-21 Wireless Ceiling Motion Sensor for Occupancy / Vacancy Detection with integrated diagnostic tools INSTALLATION GUIDE This guide covers all models of MOS-21 Ceiling occupancy sensor. The MOS-21 product
More informationWireless Ceiling Mount Sensor for Occupancy / Vacancy Detection INSTALLATION GUIDE
MOS-IR/DT Wireless Ceiling Mount Sensor for Occupancy / Vacancy Detection INSTALLATION GUIDE This guide covers all models of MOS-IR and MOS-DT ceiling occupancy sensor. The MOS-IR product family includes:
More informationwww.greenelectricalsupply.com Radio Powr SavrT Wireless Occupancy / Vacancy Ceiling Sensor LutronR Radio Powr SavrT occupancy/vacancy sensors are wireless, battery-powered passive infrared (PIR) sensors
More informationInstallation Instructions
WS-250 & WS-250-347 Passive Infrared Wall Switch Occupancy Sensor SPECIFICATIONS WS-250 Voltages...120 or 277VAC, 60Hz Load Requirements @ 120VAC, 60Hz... 0-800W ballast & tungsten, 1/6 hp @ 277VAC, 60Hz...
More informationInstallation Instructions
WS 301/WS-301-347 Passive Infrared Wall Switch Occupancy Sensor WS-301 SPECIFICATIONS WS-301-347 WS-301 Voltages...120 or 277VAC, 50/60Hz Load Requirements @ 120VAC...0~1000W ballast, E-ballast, LED, tungsten,
More informationEco-$mart, Inc. TOLL FREE:(888) FAX:(941)
Eco-$mart, Inc. TOLL FREE:(888)329-2705 FAX:(941)377-9460 info@eco-smart.com www.eco-smart.com Fluorescent High Bay Occupancy Sensor Module Installation Instructions Hubbell Building Automation 9601 Dessau
More informationSource 4WRD. Installation and User Manual. PAR and PARNel Fixture Bodies. Version Part Number: 7067M Rev: B Released:
Source 4WRD PAR and PARNel Fixture Bodies Installation and User Manual Version 1.1.0 Part Number: 7067M1220-1.1.0 Rev: B Released: 2017-06 ETC, Source Four, Source 4WRD, PARNel, Sensor, and Unison are
More informationHomeWorks QS One-Way Transmitter Frequency Changing Procedures. Rev. B 11/17/2014
HomeWorks QS One-Way Transmitter Frequency Changing Procedures Rev. B 11/17/2014 Overview Certain RF devices in the HomeWorks QS product family are one way transmitters (OWT). In other words, they do not
More informationEBDHS-AT-DD. RF ceiling PIR presence detector DALI / DSI dimming. Product Guide. Overview. Features
Product Guide EBDHS-AT-DD RF ceiling PIR presence detector DALI / DSI dimming Overview The EBDHS-AT-DD is a passive infrared (PIR) motion sensor combined with two output channels capable of controlling
More informationEBDSM-PRM Product Guide
EBDSM-PRM Product Guide Ceiling PIR presence/absence detector Overview The EBDSM-PRM PIR (passive infrared) presence detector provides automatic control of lighting loads with optional manual control.
More informationWireless Occupancy Sensor User Guide
Wireless Occupancy Sensor Wireless Occupancy Sensor User Guide This Manual covers both the Wide angle and the Narrow long range occupancy sensor. Dialight Part Numbers described here-in are: WOSU22BG2
More informationInstallation Instructions
SPECIFICATIONS WS-200 Automatic PIR Wall Switch Voltages...........................120 or 277VAC, 60Hz Requirements @ 120VAC, 60Hz........0-800W ballast & tungsten @ 277VAC, 60Hz.................0-1200W
More informationVive Integral Fixture Controls
3691039e 1 05.21.18 This device is designed to operate as part of a Vive lighting control system. If used in a standalone (non-system) application functionality is limited to default settings. The Vive
More information2 Pendant Adjustment. Pendant Slider Plate. 3/4 (19mm) IP, (29mm) O.D. Knockouts. 1/2 (13mm) IP, (22mm) O.D. Knockout
CXB Series LED Luaire Universal Hook and Cord, and Optional Junction box or Pendant Mount with Sensor IMPORTANT SAFEGUARDS When using electrical equipment, basic safety precautions should always be followed
More information- 2 JOINER ALIGNERS - 2 JOINING BRACKETS - 4 HEX BOLTS. Factory pre-installed mud flange TOOLS REQUIRED: Phillips screwdriver, 5/16 nut driver.
- 2 JOINER ALIGNERS - 2 JOINING BRACKETS - 4 HEX BOLTS TruGroove Drywall A3 MOUNTING Ceiling INSTALLATION System Overview These instructions review how to install drywall trim versions of TruGroove recessed
More informationEBDHS-MB-AT-DD. RF ceiling PIR presence detector DALI / DSI dimming. Product Guide. Overview. Features
Product Guide EBDHS-MB-AT-DD RF ceiling PIR presence detector DALI / DSI dimming Overview The EBDHS-MB-AT-DD is a passive infrared (PIR) motion sensor combined with two output channels capable of controlling
More informationInstallation Instructions Standalone or continuous run configurations - 2 JOINER ALIGNERS - 2 JOINING BRACKETS - 4 HEX BOLTS
- 2 JOINER ALIGNERS - 2 JOINING BRACKETS - 4 HEX BOLTS TruGroove Drywall A3 MOUNTING Ceiling INSTALLATION System Overview These instructions review how to install trimless drywall versions of TruGroove
More informationSource 4WRD HPL to LED Retrofit
Source 4WRD HPL to LED Retrofit Installation and User Manual Version 1.1.0 Part Number: 7067M1200-1.1.0 Rev: C Released: 2017-07 ETC, Source Four, Source 4WRD, Sensor, and Unison are either registered
More informationDLA-E (Philips EvoKit) The DLA-E is designed to install in the mounting slot of the Philips EvoKit SR retrofit kit.
DA Sensor INSTAATION INSTRUCTIONS PRODUCT SAFETY! Digital ight Agent (DA) hardware must be installed in accordance with the applicable installation code by a person familiar with the construction and operation
More informationA-dec 574L and 575L Dental Lights on a Cabinet or Wall INSTALLATION GUIDE
A-dec 574L and 575L Dental Lights on a Cabinet or Wall INSTALLATION GUIDE A-dec 574L Dental Light Mounted on an A-dec Inspire TM 59 Central Console Before You Begin. Turn off the power to the system before
More informationPowPak Dimming Module with EcoSystem
PowPak Dimming Module with EcoSystem 369-427f 1 04.03.12 The PowPak Dimming Module with EcoSystem is a radio frequency (RF) control that operates up to 32 EcoSystem ballasts based on input from controls
More informationTechnical Application Guide
Lighting Control Wireless Occupancy Sensor, Wireless Multi Sensor Technical Application Guide Easily enhance your smart lighting system with the Philips wireless occupancy sensor and multi sensor, which
More informationModel PRESET 8 Installation and Operations Manual
Model PRESET 8 Installation and Operations Manual Doug Fleenor Design, Inc. 396 Corbett Canyon Road Arroyo Grande, CA 93420 (805) 481-9599 Voice and FAX Manual revision March 2, 2015 Page 1 of 7 5 4 3
More information1: White buttons Used by the user on a daily basis. 2: Grey buttons Used only upon first startup.
Fig. 1 Lock/ unlock 30 1000 Light 1 100 300 zone 1 Learn actual lux LED 600 2000 0,4 0,6 0,8 1,0 1,2 Time 1 Light 2 zone 2 1,4 1,6 Factor of lux zone 1 Pulse 2min 5min Time Time 2 10min 15min 30min 1 2
More information3000W MULTI PIR LIGHT CONTROLLER
3000W MULTI PIR LIGHT CONTROLLER Cat No. MLB3000 Black Cat No. MLW3000 White Installation & Operating Instructions INSTALLATION & OPERATING INSTRUCTIONS E G Dusk/Dawn Time Override/Holiday Mode F H Lens
More informationRPMSP Series Installation Guide
RPMSP Series Installation Guide Contents 1. Overview... page 1 2. Unpacking the Projector...2 3. Projector Configuration...2 4. Projector Throw Distance and Mounting...9 5. Projection Lens Focus...9 6.
More informationInstalling the FSP-211 Sensor in Light Fixture
(grey) WATTSTOPPER VOLTAGE HIGH/LOW/OFF PIR FIXTURE INTEGRATED OUTDOOR PHOTO/MOTION SENSOR Product Overview The is a passive infrared (PIR) outdoor sensor that raises or lowers the electric lighting level
More informationCXB Series SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE. LED Luminaire TO INSTALL: INSTALLATION INSTRUCTIONS INSTRUCTIONS D INSTALLATION
CXB Series LED Luaire Junction Box, Pendant and Hook and Cord IMPORTANT SAFEGUARDS When using electrical equipment, basic safety precautions should always be followed including the following: READ AND
More informationFSP-211 DIGITAL HIGH/LOW PIR FIXTURE INTEGRATED SENSOR
FSP-211 DIGITAL HIGH/LOW PIR FIXTURE INTEGRATED SENSOR CAUTIONS INSTALLATION INSTRUCTIONS IMPORTANT SAFEGUARDS When using electrical equipment, basic safety precautions should always be followed including
More information3000W multi Pir light controller
3000W multi Pir light controller Cat No. MLB3000 - Black Cat No. MLW3000 - White Installation & Operating Instructions INSTALLATION & operating instructions SECTION ONE GENERAL INFORMATION The unit utilises
More informationHigh/Low Bay Passive Infrared Occupancy Sensor
Models Sensors: HBP-111-L7, with IR remote capability HBP-112-L7, no IR capability High/Low Bay Passive Infrared Occupancy Sensor Mounting Modules: HBP-EM1 extender module HBP-SM1 surface mount module
More informationHigh Bay Occupancy Sensor for Use with Electronic Ballast HID Luminaires
Instruction Bulletin 63249-500-08A6 05/2011 High Bay Occupancy Sensor for Use with Electronic Ballast HID Luminaires SLSPIP210EB and SLSPIP210EBCT INTRODUCTION Figure 1: High Bay Occupancy Sensor for Use
More informationTekLink TL100 with Passive Infrared Sensing System Overview
TekLink TL100 with Passive Infrared Sensing System Overview 1.0 Control Systems CS 1 TekLink TL100 with Infrared Application Guide Contents 1.0 Introduction 2 2.0 Basic Operating Principles 3 3.0 Normal
More informationLOAD AWG Solid CU Wire Only LINE NEUT FSP-211. High/Low PIR Occupancy Sensor 230 VAC, 50 Hz 1200W max ballast 5E4
DESCRIPTION AND OPERATION The is a motion sensor that dims lighting from high to low based on movement. This slim, low-profile sensor is designed for installation inside the bottom of a light fixture body.
More informationEBDSPIR-AT-DD. RF ceiling PIR presence detector DALI / DSI dimming. Product Guide. Overview. Features
Product Guide EBDSPIR-AT-DD RF ceiling PIR presence detector DALI / DSI dimming Overview The EBDSPIR-AT-DD is a passive infrared (PIR) motion sensor combined with two output channels capable of controlling
More informationSensors. EasySense. Fixture-Mount for Basic Grouping
Sensors EasySense Fixture-Mount for Basic Grouping The Philips EasySense fixture-mount sensor is the ideal solution for per-fixture control of new light fixtures. It combines occupancy sensing, daylight
More informationSensors. EasySense. Fixture-Mount for Basic Grouping
Sensors EasySense Fixture-Mount for Basic Grouping The Philips EasySense fixture-mount sensor is the ideal solution for per-fixture control of new light fixtures. It combines occupancy sensing, daylight
More informationWireless 900 MHz Receiver
Overview and Identification The 900 MHz unit receives a repeated or re-transmitted RF signal from one or more wireless temperature or humidity transmitters. The signal from the transmitter (418 MHz) is
More informationEasyAir Office sensor advanced grouping SNS200
Sensors EasyAir office sensor advanced grouping SNS200 Datasheet EasyAir Office sensor advanced grouping SNS200 The Philips EasyAir office sensor is the ideal solution for per-luminaire control of new
More informationHIGH/LOW/OFF PIR OUTDOOR PHOTO/MOTION SENSOR IN IP66 ENCLOSURE WITH BLUETOOTH
HIGH/LOW/OFF PIR OUTDOOR PHOTO/MOTION SENSOR IN IP66 ENCLOSURE WITH BLUETOOTH Product Overview The FSP-3x1B is a family of passive infrared (PIR) outdoor sensors that raise or lower the electric lighting
More informationCES SENSORS INSTALLATION AND MAINTENANCE MANUAL (IMM)
CES SENSORS INSTALLATION AND 205_CES_R.1_7-8-10 A Division of PLCMultipoint GENERAL INTRODUCTION 1. Please read these instructions carefully to prevent any possible injury or equipment damage. 2. Installer
More informationSensors. EasySense. Fixture-Mount for EvoKit
Sensors EasySense Fixture-Mount for EvoKit The Philips EasySense fixture-mount sensor is the ideal solution for per-fixture control of new light fixtures. It combines occupancy sensing, daylight harvesting
More informationASSEMBLY AND INSTALLATION INSTRUCTIONS
T0103 ASSEMBLY AND INSTALLATION INSTRUCTIONS WARNING: TO AVOID RISK OF ELECTRICAL SHOCK, BE SURE TO SHUT OFF POWER WHILE INSTALLING OR SERVICING THIS FIXTURE. NOTES: 1. Before installing, consult local
More informationwww.electricalsupply.com MaestroR Occupancy Sensor C LR Dimmer LutronR MaestroR occupancy sensor C LR dimmers are lighting controls with passive infrared sensors that automatically control the lights in
More informationEasyAir Office sensor advanced grouping SNS200
Sensors EasyAir office sensor advanced grouping SNS200 Datasheet EasyAir Office sensor advanced grouping SNS200 The Philips EasyAir office sensor is the ideal solution for per-luminaire control of new
More informationSensors. EasySense. Fixture-Mount (with Ceiling-Mount Option)
Sensors EasySense Fixture-Mount (with Ceiling-Mount Option) The Philips EasySense fixture-mount sensor is the ideal solution for per-fixture, stand-alone control of new light fixtures. It combines occupancy
More informationThis document is intended for Lighting Control Systems professionals
This document is intended for Lighting Control Systems professionals This document applies to fixture with factory installed SVPD1, SVPD2, SVPD3 integrated sensors. Table of contents Quick Reference Guide...
More informationFixed Wall Arm. Installation Guide. Part number Rev E 2012 PolyVision Corporation All rights reserved
Fixed Wall Arm Installation Guide Part number 2002003-001 Rev E 2012 PolyVision Corporation All rights reserved Table of contents Important Safety Instructions... 3 Overview... 4 Important considerations...
More informationCopyright Black Box Corporation. All rights reserved Park Drive Lawrence, PA Fax
Copyright 2003. Black Box Corporation. All rights reserved. 1000 Park Drive Lawrence, PA 15055-1018 724-746-5500 Fax 724-746-0746 JULY 2003 RM3010A RM315-R2 RM323-R2 RM329 RM451 RM457 RM3020A RM316 RM324-R2
More informationMIL-STD B (SH) UPDATE
MIL-STD-2042-5B (SH) UPDATE Method 5A1 Insert Equipment and materials (to be added to table 5A1-I) Pliers 3.2.2.2 Cable and fiber preparation for Fiber Systems International backshells. Step 1: Ensure
More informationPowPak Relay Module. PowPak Relay Module Energi TriPak Series Wireless Lighting Control
PowPak Relay Module Energi TriPak Series Wireless Lighting Control PowPak Relay Module 369549c 1 10.07.14 The PowPak Relay Module is a radio frequency (RF) device capable of controlling up to 5 A of general-purpose
More informationSensors. EasySense. Fixture-Mount for Advanced Grouping
Sensors EasySense Fixture-Mount for Advanced Grouping The Philips EasySense fixture-mount sensor is the ideal solution for per-fixture control of new light fixtures. It combines occupancy sensing, daylight
More informationSensors. EasySense. Fixture-Mount Advanced Grouping for Evokit
Sensors EasySense Fixture-Mount Advanced Grouping for Evokit The Philips EasySense fixture-mount sensor is the ideal solution for per-fixture control of new light fixtures. It combines occupancy sensing,
More informationPowPak Relay Module with Softswitch
PowPak Relay Module with Softswitch The PowPak Relay Module with Softswitch is a radio frequency (RF) device that uses Lutron patented Softswitch technology to control up to 16 A of general-purpose load
More informationIMPORTANT SAFEGUARDS READ AND FOLLOW ALL SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
FSP-2X1 Digital High/Low Pir Fixture Integrated Sensor INSTALLATION INSTRUCTIONS IMPORTANT SAFEGUARDS When using electrical equipment, basic safety precautions should always be followed including the following:
More informationETC. ColorSource Series GENERAL INFORMATION ORDERING INFORMATION. ColorSource Linear RJ45
GENERAL INFORMATION ColorSource Linear combines the bright, bold output of the ColorSource family with a sleek linear design to create a versitile and affordable strip light. Whether being used to create
More informationInstallation Instructions
Designer Wall Switch Occupancy Single Pole (One Location) or Multi-Location Rated: 12/277V, 6Hz Cat. No. ODS1Ø-IDx Incandescent 8W - 6.67A @ 12V Fluorescent 12VA - 1A @ 12V 27VA - 1A @ 277V Supplemental
More informationArched Top Lantern Pendant Assembly and Installation Instructions. Country of Destination: US/CN UK/EU/AUS Middle East
CAUTION: Arched Top Lantern Pendant Assembly and Installation Instructions Country of Destination: US/CN UK/EU/AUS Middle East BEFORE INSTALLING FIXTURE, MAKE SURE THE POWER TO THE CIRCUIT IS TURNED OFF
More informationMAS SENSORS INSTALLATION AND MAINTENANCE MANUAL (IMM)
MAS SENSORS INSTALLATION AND 205_MAS_R.1_6-14-10 A Division of PLCMultipoint GENERAL INTRODUCTION 1. Please read these instructions carefully to prevent any possible injury or equipment damage. 2. Installer
More informationSensors. EasySense. Fixture-Mount for Advanced Grouping
Sensors EasySense Fixture-Mount for Advanced Grouping The Philips EasySense fixture-mount sensor is the ideal solution for per-fixture control of new light fixtures. It combines occupancy sensing, daylight
More informationSensors. Datasheet. EasyAir SNS200
Sensors EasyAir SNS200 Datasheet EasyAir SNS200 The Philips EasyAir SNS200 is the ideal solution for per-luminaire control of new light luminaires. It combines occupancy sensing, daylight harvesting and
More informationInstallation Instructions
TECH SUPPORT The Watt Stopper, Inc. 2800 De La Cruz Blvd. Santa Clara, CA 95050, USA Tel: 1(800)879-8585 1(972)578-1699 Fax: 1(972)422-1311 www.wattstopper.com Outdoor 180 & 270 PIR Motion s Model#s: EW-100-120
More informationPowPak CCO Module. PowPak CCO Module Energi TriPak Series Wireless Lighting Control
PowPak CCO Module 369433g 1 07.21.16 The PowPak CCO Module is a low-voltage radio frequency (RF) control that provides a single dry contact closure output based on input from Pico controls and Radio Powr
More informationTeacherGeek Launcher Example Build
LAUNCHER EXAMPLE BUILD TeacherGeek Launcher Example Build TeacherGeek, 2011 LAUNCHER EXAMPLE BUILD TeacherGeek 2 LAUNCHER BASE PARTS A B D F E C G LAUNCHER EXAMPLE BUILD TeacherGeek 3 ASSEMBLING THE LAUNCHER
More informationSELECTABLE MODE HIGH/LOW/OFF PIR FIXTURE INTEGRATED INDOOR/OUTDOOR MOTION/PHOTO SENSOR
SELECTABLE MODE HIGH/LOW/OFF PIR FIXTURE INTEGRATED INDOOR/OUTDOOR MOTION/PHOTO SENSOR FSP-22 FSP-212 * Models FSP-22, 12-32VDC Use with dim-to-off driver or ballast or with Wattstopper power pack FSP-212,
More informationBest Practices Guide Polycom SoundStructure and HDX Microphones
Best Practices Guide Polycom SoundStructure and HDX Microphones This document introduces HDX microphones and the best practices for using the HDX microphones with SoundStructure devices. In addition this
More informationA-dec 6300 Ceiling-Mount Dental Light INSTALLATION GUIDE
A-dec 6300 Ceiling-Mount Dental Light INSTALLATION GUIDE Recommended Tools Hex key set Plumb bob Drill 3/16" drill bit 6' piece of tubing Level Phillips head screwdriver Tape measure Anti-static strap
More informationFC-SENSOR, FC-VSENSOR, FCJ-010, FCJ-ECO
The PowPak wireless fixture control is a radiofrequency (RF) device that controls either the Lutron EcoSystem or 0 10 V- electronic fluorescent ballasts and LED drivers (depending on model). This is based
More informationInstruction Manual. StealthLock, Keyless Invisible Security
Instruction Manual 1 Thank you for purchasing StealthLock. StealthLock is an innovative solution for keyless invisible security. Using radio frequency technology, StealthLock allows you to secure almost
More informationASSEMBLY AND INSTALLATION INSTRUCTIONS
T0412 / T0413 ASSEMBLY AND INSTALLATION INSTRUCTIONS WARNING: NOTES: 1. Before installing, consult local electrical codes for wiring and grounding requirements. 2. READ AND SAVE THESE INSTRUCTIONS. Hardware
More informationOccupancy Sensor Placement and Technology. Best Practices Crestron Electronics, Inc.
Occupancy Sensor Placement and Technology Best Practices Crestron Electronics, Inc. Crestron product development software is licensed to Crestron dealers and Crestron Service Providers (CSPs) under a limited
More informationTURN OFF POWER ARRETEZ LE COURANT DESCONECT LA CORRIENTE. Tap Button (tap on/off) Raise Alt. Button Lower. Alt. PIR Hi Med Low Min.
Maestro 0-0 V Sensor Applications Application Note #6 Revision A October 0 This document serves as a supplement to the Maestro 0-0 V Dimmer Sensor Installation Guide for the following model numbers: MS-Z0-XX:
More informationEasyAir office sensor standalone SNS100
Sensors EasyAir office sensor standalone SNS100 Datasheet EasyAir office sensor standalone SNS100 The Philips EasyAir office sensor is the ideal solution for per-luminaire, stand-alone control of new light
More informationAPES HD-7700 Version Operator s Training Manual
APES-14-77 HD-7700 Version Operator s Training Manual Issue A1 09/03 P/N 900599 Performance Design Inc. 2350 East Braniff St. Boise Idaho 83716 This manual contains very important safety information and
More informationO ccupancy and Light Level Sensor L ow Vo l tage Ceiling Fixture Mount
FS - 2 0 5 v 2 O ccupancy and Light Level Sensor L ow Vo l tage Ceiling Fixture Mount SPECIFICATIONS Power Voltage.......................................24VDC Current Consumption...........................6.5
More informationFraming & Electrical Rough-in for Recess Mount IS Panel System
Framing & Electrical Rough-in for Recess Mount IS Panel System Overview Careful pre-planning and design lay-out are critical to successfully installing a Recess Mount IS (Infra- Sauna) Panel System. The
More informationETC. Selador Pearl. Model Description. Selador Pearl 21 (two cell) Selador Pearl 42 (four cell) Selador Pearl 63 (six cell)
G e n e r a l i n f o r m a t i o n The Selador Series Pearl uses the power of white LEDs to provide a highly efficient fixture for video and event production. A carefully chosen array of 3200K warm white
More informationSensors. Datasheet. EasyAir SNS200
Sensors EasyAir SNS200 Datasheet EasyAir SNS200 The Philips EasyAir SNS200 is the ideal solution for per-luminaire control of new light luminaires. It combines occupancy sensing, daylight harvesting and
More informationAMANO PIX-21. Electronic Time Recorder. Operation Manual
AMANO PIX-21 Electronic Time Recorder Operation Manual External View Page 1 Removing the Cover & Packing Materials 1. Lift the printer block and remove the spacer. 2. Insert the key provided and turn clockwise
More informationWARNINGS & SAFETY INFORMATION: PLEASE READ CAREFULLY AND KEEP A COPY ON THE PROPERTY FOR FUTURE REFERENCE!
WARNINGS & SAFETY INFORMATION: PLEASE READ CAREFULLY AND KEEP A COPY ON THE PROPERTY FOR FUTURE REFERENCE! General Safety Information To reduce the risk of death, personal injury or property damage from
More informationCustom Pendant- Hardwire Assembly and Installation Instructions
Custom Pendant- Hardwire Assembly and Installation Instructions CAUTION: BEFORE INSTALLING FIXTURE, MAKE SURE THE POWER TO THE CIRCUIT IS TURNED OFF AT THE MAIN FUSE BOX / CIRCUIT BREAKER UTILITY BOX.
More informationHIGH/LOW/OFF PIR OUTDOOR PHOTO/MOTION SENSOR IN IP66 ENCLOSURE FOR FLEXIBLE MOUNTING
HIGH/LOW/OFF PIR OUTDOOR PHOTO/MOTION SENSOR IN IP66 ENCLOSURE FOR FLEXIBLE MOUNTING Product Overview The FSP-2x1B is a family of passive infrared (PIR) outdoor sensors that raise or lower the electric
More information