FIELP 48 Field-Mounted ontroller Introduction Features & enefits The need for only one wire pair to communicate with the control room reduces wiring costs ombines multiple loop components in a single package for reduced hardware and maintenance costs Improves loop accuracy by using digital technology and by eliminating data communication errors among multiple components. The ability to communicate with the controller from a remote, central location improves operations Implementation of the HRT communication protocol facilitates use with many control system devices Factory onfigured ptions (Fs) reduce configuration time for standard control strategies Flexible input options accommodate existing I/ escription The FIELP 48 Field-Mounted ontroller supports an advanced single-loop control applications, while reducing installed costs. The FIELP controller lowers hardware costs by providing multiple loop components in one package and decreases wiring costs by reducing to one the number of wire pairs needed to transmit data to a central control room. The loop components integrated within the FIELP controller are based on the proven technology of several other instruments, including the iemens ontrollers, pressure transmitters, and I/P and P/I converters. This combination allows the FIELP controller to provide an innovative, reliable controller that can be mounted directly at the process site. The FIELP controller includes a TYPE 4X (IP65) enclosure and a hazardous area design (intrinsically safe and nonincendive) to allow installation at the process site. It offers several choices of direct process inputs, optional pneumatic or thermocouple/rt inputs, and an optional pneumatic output, all of which are in addition to the standard complement of 4-0 m inputs and discrete I/. The FIELP controller also minimizes wiring costs via the HRT protocol. With HRT digital signal, the FIELP controller transmits process data to a control room over one standard wire pair, instead of the three to four wire pairs required by a typical loop. Using HRT also allows the FIELP controller to communicate with many other devices, because HRT has the largest base of any field communications protocol. The FIELP controller accommodates control strategies ranging from basic PI control to sophisticated loops, such as ratio, bias, single-station cascade, dual-loop and feed-forward control. ircuits are configured via the same function block technique employed with the Model 5 Process utomation ontroller, where the user simply selects the desired blocks, connects them, and sets parameters, such as gains and timer values. Moreover, the FIELP controller provides over 60 pre-configured function blocks containing more than 00 functions. In addition, the FIELP controller provides many preconfigured control strategies (Fs). Each F can be used as is, or customized as needed, significantly reducing configuration time for standard control requirements. The FIELP controller is configured locally or at a remote P. The station s pushbuttons allow the FIELP controller to be configured at the faceplate..8
FIELP 48 Field-Mounted ontroller Technical data pecifications Electrical Power upply (48_) Input: V P = 4.0-8.0 Vdc Power: onsumption: 4.4 Watts (max.) Power upply (48E_) Input: 0-64 Vac, 47 to 6 Hz Voltage election: uto-sensing Power onsumption: V -Wire Transmitter Power (48E_) Voltage: -Powered: 4.5 V less than V P -Powered: Vdc (nominal) urrent: 80 m (max.), short circuit protected Heat issipation -Powered:.5 TU/hr. -Powered: 4.6 TU/hr. Mounting Type: Panel, " Pipe, or Wall Panel utout:.5" H x 0.0" W, ±0. mm H x 54 mm W, ±.5 mm Environmental Hazardous rea lassification 48: Intrinsically afe lass I; ivision ; Groups, lass II; ivision ; Groups E, F, G lass III; ivision 48E: FM/ lass I; ivision ; Groups,, & E ompliant mbient Temperature Range -40 to 85 o (-40 to 85 o F) Humidity 0 to 00% E usceptibility 5,000 volts discharged to case and keyboard 5,000 volts to any terminal connection urge Protection I/IEEE 7.0,.5 kv Inputs nalog Inputs tandard alibration: to 5 Vdc Zero: 0 to Vdc pan: 4 to 5 Vdc Input Impedance: > megohm Type: ingle-ended (non-isolated) ormal Mode Rejection: -64 d @ 60 Hz Maximum ontinuous Input: ±0 Vdc ccuracy: < ±0.85 % per 50 o igital Inputs Logic (): to 0 Vdc Logic 0 (FF): 0 to 5 Vdc Type: pto-coupled (isolated) Input Impedance: 00 ohms Pneumatic Inputs (ptional) 5 PIG (0 kpa) ensor: tandard alibration: to 5 psig (0.7 kpa to 0 kpa) Zero: 0 to 4 psig (0 to 7.6 kpa) pan: to 5 psig (8.7 kpa to 0 kpa) 0 PIG (07 kpa) ensor: Zero: 0 to 8 psig (0 to 55. kpa) pan: 4 to 0 Psig (65 kpa to 07 kpa) ccuracy: ±0.5% of span Temperature Effect: < 0.06% per o Input Types Thermocouple: R,, T,, J, K, E, RT: I:a = 0.00850W/ o U: a = 0.000W/ o (00, 00 & 500 W available) mv Wide: Zero: -5 to 00 mvdc pan: 5 to 5 mvdc mv arrow: Zero: -0 to 5 mvdc pan: to 5 mvdc Input Impedance: > megohm irect Process Pressure (ptional) Types: Gauge, ifferential, bsolute ee information on direct process pressure input, page. utputs nalog utputs tandard alibration: 4 to 0 m ccuracy: < ±0.% of span Load: Power: < [(V-6.8)/.6]W Power: < 680W ignal Reference: egative terminal is controller common Temperature Effect: ±0.5% per 50 o iscrete utputs Type: pen collector transistor (emitter tied to controller common) Load Voltage: 0 Vdc (max.) Load urrent: 00 m (max.) Voltage: 0.V @ 00 m FF Leakage: 0.5 u @ 0 Vdc Isolated iscrete utputs Type: pto Transistor Load Voltage: 0 Vdc (max.) Load urrent: 50 m (max.) Voltage: 5.0 V @ 0 m; 0.5 V @ m FF Leakage:.0 m @ 0 Vdc Relay utputs Type: Epoxy sealed witch: PT (Form ) Rating: @ 50 Vac Pulse Integrator utput Type: pen collector transistor (emitter tied to common) Load Voltage: 0 Vdc (max.) Load urrent: 00 m (max.) Voltage: 0. V @ 00 m FF Leakage: 0.5 u @ 0 Vdc.
FIELP 48 Field-Mounted ontroller Technical data Function locks ontrol strategies within the FIELP controller are designed using the following function blocks, which are stored in memory. The blocks are used by assigning an execution sequence number to each block. Type escription Input nalog Input (-5 Vdc) Input iscrete Input Input Pneumatic Input Input Process Pressure Input Input Thermocouple/RT/mV Input utput nalog utput (4-0 mdc) utput iscrete utput utput Isolated iscrete utput utput Isolated Relay utput utput Pulse Integrator utput utput Pneumatic utput (-5/-7 PI) ontrol Ratio ontrol ias ontrol HI/L etpoint Limit ontrol verride elector ontrol Pushbutton Transfer witch ontrol Process larms ontrol ontroller (PI, I, P, PIG) ontrol uto/manual Transfer ontrol Integrator/Totalizer ontrol etpoint Track & Hold ontrol General -Purpose Track & Hold ontrol General-Purpose Hold ontrol Logic (,, R, R, XR) ontrol eviation mplifier ontrol quare Root Extractor ontrol Pulse Integrator ontrol Math (add, subtract, multiply, divide) ontrol Gain & ias ontrol Lag ontrol Lead ontrol Rate Limiter ontrol ead Time Table ontrol 0-egment haracterizer ontrol Repeat ycle Timer ontrol General-Purpose Transfer ontrol atch witch ontrol Quad omparator ontrol elay Timer ontrol ne hot Timer ontrol ual Transfer witch peration perator isplay peration Password ecurity peration HRT Interface Qty., 48 / 0 Qty., 48E / 0 td./ pt. Model umber rder o. Intrinsically afe 48- Field-Mounted ontroller on-incendive 48E- Field-Mounted ontroller 6 - Power upply 0-64 Vac, 47-6 Hz 0-64 Vac, 47-6 Hz (E ompliant) 4-8 Vdc, non-isolated perator s isplay Full-Function Full-Function with acklight Process Pressure Input irect-onnected /P ensor 4 irect-onnected Pressure ensor 4 P (gauge & absolute) Removable plug for future R sensor mounting ot Required nalog ption oard () 5 PIG Pneumatic Input () 5 PIG Pneumatic Inputs () 0 PIG Pneumatic Input () 0 PIG Pneumatic Inputs F Thermocouple/RT/Millivolt Input T ot Required nalog utput o. ptions 4-0 m urrent 5 PIG Pneumatic 0 PIG Pneumatic esign Level urrent esign Reserved o Modifications Reserved Reserved ommunications HRT H Electrical onnections /4 PT.5 Metric Hazardous rea lassifications 5 FM/ lass I; iv.; 4 Groups,, & lass I; iv.; Groups & Y EEF Type E ompliant E ot Required ) nalog input # is not available when the option for () or () pneumatic inputs is used, and analog input # is not available when the option for () pneumatic inputs is used. ) nalog output # is used to drive the I/P output and is not available as a current output when the pneumatic output option is used. ) Model 48E only. 4) Refer to the information on direct process pressure input on page. for the model number used to specify sensor options. For example, the differential pressure version of the irect onnect output option () of each model number is used to indicate a FIELP application. 5) ther agency approvals pending. 6) pproved intrinsic safety barriers are required for iv. installations..0
FIELP 48 Field-Mounted ontroller ccessories tandard onfigurations The most common types of control have been configured at the factory and stored in the FIELP controller s memory. These control strategies, called Fs, can be easily recalled from memory and used as is or modified to meet individual requirements. They include: ingle-loop PI controller External-set PI controller Ratio-set PI controller ascade controller ual-loop controller ccessories FIELP onfiguration oftware (P/ 5-48Vx.xx ) - P-based software package for configuring the FIELP controller (-based). Resistor Kit (P/ 66-) For use with 4-0 m inputs (50W). Permanent Instrument Tag The instrument name-plate can be stamped with up to three lines of text (at up to 0 characters per line). Extended Mounting racket (P/ 66-88) Provides additional room for mounting. rder when wall mounting a FIELP unit with direct-connected /P sensor or when pipe-mounting a FIELP unit with a three-valve manifold and a /P sensor. hould not be used in an area with excessive vibration. Mounting racket (P/ 66-7) Hart Modem (P/ 675-5 The Hart modem is a ell 0T style modem for use with the P configuration software package. 4 V ac/dc arrier/upply Kit (P/ 66-40 tahl 8/ 0-58-60-0) This approved barrier/supply combination powers the Model 48 when installed in iv., lass, Groups, & ; lass ll, Groups E, F & G; and lass lll areas. The barrier/supply converts its nominal 4 Vac/dc input into an approved, barrier protected 5 Vdc power source for the Model 48. 0/40 Vac arrier/upply Kit (P/ 66-4 tahl 8/ 0-58-60-50) This approved barrier/supply combination powers the Model 48 when installed in iv., lass, Groups & ; lass ll, Groups E, F & G; and lass lll areas. The barrier/supply converts its nominal 0/40 Vac input into an approved, barrier protected 5 Vdc power source for the Model 48. Hart ignal arrier Kit (P/ 66-4 tahl 00/0/-06-05-0) This approved barrier conditions Hart signals passing to the Model 48 when installed in iv., lass, Groups, & ; lass ll; Groups E, F, & G; and lass lll areas. Model umber ifferential Pressure bsolute Pressure Gauge Pressure Input Range: pan Limits Min/Max 0./5" H 0 (model 40 only) 0.75/5" H 0 (model 40 only) 0/450" H 0.6/450 PI 00/5500 PIG (model 40G only) utput irect onnection to Model 48 Field Mounted ontroller or pare apsule Process iaphragm -76 (tandard on Ranges, F, and G) 6L (tandard on Ranges & ) ody Parts Wetted Vent/rain Process onnection 6 End / PT (tandard on all Ranges) 6 ide (top) / PT (model 40 only) 6 ide (bottom) / PT(model 40 only) 6 ide (dual) / PT(model 40 only) 6 End /4 PT(model 40 only) 6 ide (top) /4 PT(model 40 only) 6 ide (bottom) /4 PT(model 40 only) 6 ide (dual) /4 PT(model 40 only) -76 End / PT -76 ide (top) / PT(model 40 only) -76 ide (bottom) / PT(model 40 only) Hasttelloy -76 ide (dual) / PT(model 40 only) -76 End /4/ PT(model 40 only) -76 ide (top) /4 PT(model 40 only) -76 ide (bottom) /4 PT(model 40 only) -76 ide (dual) /4 PT(model 40 only) Fill Fluid ilicone 00 (tandard on ll Ranges) Inert Paratherm utput Indicator ot Required tandard ptions xygen leaned olting (model 40 only) olting (model 40 only) ot Required Mounting racket ot Required Housing ot Required Hazardous rea lassifications on-pproved rder o. 40-40- 40G- - F G H E F G H E F G H X E ) x.xx specifies the software s version number. This will be defined by iemens as the latest version number..
FIELP 48 Field-Mounted ontroller imensional drawings imensions Panel utout:.5± 0. (±.5) High X 0.0±0. (54±.5) Wide Panel Thickness: /6" (4.76) maximum Except for panel cutout, all dimensions are nominal and for reference only. The FIELP controller with a pressure sensor must mount on a panel or pipe..