Post-Event Analysis of a Compound Event in the ERCOT System Using Synchrophasor Data

Similar documents
Use of Synchronized Phasor Measurements for Model Validation in ERCOT

Sarma (NDR) Nuthalapati, PhD

Synchrophasor Technology PMU Use Case Examples

Wide-Area Measurements to Improve System Models and System Operation

Use of the Power System Outlook (PSO) and SMART 1 Programs to View PSLF Dynamic Simulation Data Files

Using Synchrophasor System Data for Establishing Operating Range for Operators Guidance and Detection and Analysis of Significant Events

Uses of Synchrophasor BD NSF Workshop 2017

SYNCHROPHASOR TECHNOLOGY GLOSSARY Revision Date: April 24, 2011

Texas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event

Using Synchrophasors for Frequency Response Analysis in the Western Interconnection. Bonneville Power Administration -- WECC JSIS Chair

Analysis of Effect on Transient Stability of Interconnected Power System by Introduction of HVDC Link.

Power System Reliability and Transfer Capability Improvement by VSC- HVDC (HVDC Light )

Test Cases Library and Real-life Oscillation Examples

Use of Synchrophasors to Detect Control System and Circuit Breaker Reclosing Issues

Events Captured and Findings To Date. John Ballance and Abhijeet Agarwal EPG John Adams and Jian Chen ERCOT

A New Subsynchronous Oscillation (SSO) Relay for Renewable Generation and Series Compensated Transmission Systems

GRID RELIABILITY MONITORING

Energy-Based Damping Evaluation for Exciter Control in Power Systems

Reliability Guideline: Generating Unit Operations During Complete Loss of Communications

In addition to wide-area monitoring systems, synchrophasors offer an impressive range of system benefits, including:

Reliability Guideline: Generating Unit Operations During Complete Loss of Communications

Experiences of Using Synchrophasors at Duke Energy

Harmonizing the Changing Resource Mix Keeping the Grid Together

Wide Area Control Systems (1.4) Mani V. Venkatasubramanian Washington State University (

Frequency Prediction of Synchronous Generators in a Multi-machine Power System with a Photovoltaic Plant Using a Cellular Computational Network

Phasor-based wide area monitoring in the South African power system

SynchroPhasor use at OG&E. Austin D. White P.E. Steven E. Chisholm Oklahoma Gas & Electric

1200 MW Fault Induced Solar Photovoltaic Resource Interruption Disturbance Report

Generator Parameter Validation (GPV)

ABB Inc. April 1, 2016 Slide 1

System Protection and Control Subcommittee

Wind Power Facility Technical Requirements CHANGE HISTORY

Table of Contents Error! Bookmark not defined.

Doãn Văn Đông, College of technology _ Danang University. 2. Local Techniques a. Passive Techniques

THE ROLE OF SYNCHROPHASORS IN THE INTEGRATION OF DISTRIBUTED ENERGY RESOURCES

Use of a Sub Harmonic Protection Relay to Detect SSO Conditions Associated with Type-III Windfarms and Series Compensated Transmission Systems

Zambezi (previously Caprivi) Link HVDC Interconnector: Review of Operational Performance in the First Five Years

Grid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017

Synchrophasors and the Smarter Grid

Response of Grid Interconnected Solar PV inverters to Transmission System Faults

Interconnection-Wide Oscillation Analysis: Baselining Oscillation Modes in the North American Power System Objective Purpose

Contingency Analysis using Synchrophasor Measurements

VOLTAGE STABILITY OF THE NORDIC TEST SYSTEM

Recent Progress on Forced Oscillation Detection and Source Locating Findings at Peak Reliability. NASPI Work Group Meeting

A New Approach Applied to Adaptive Centralized Load Shedding Scheme

State Estimation Advancements Enabled by Synchrophasor Technology

Considerations and Recommendations for the Harmonisation of Under Frequency Loadshedding Schemes in Multi Zone Meshed Grids

COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR)

Frequency Response Initiative Industry Advisory Generator Governor Frequency Response

AEP s 765kV Transmission Line Model Validation for Short Circuit and System Studies. T. YANG, Q. QIU, Z. CAMPBELL American Electric Power USA

Sub/super-synchronous harmonics measurement method based on PMUs

Real-time Monitoring of Power Oscillations and Modal Damping in the European ENTSO-E System

Measurement tools at heart of Smart Grid need calibration to ensure reliability

Success Story: Practical Use of Synchrophasor Technology in ISO-NE Operations

Operationalizing Phasor Technology

Determination of Smart Inverter Power Factor Control Settings for Distributed Energy Resources

Robert W. Cummings - NERC Director of System Analysis and Reliability Initiatives William Herbsleb - Chairman of Frequency Response Standard Drafting

Power System Stability. Course Notes PART-1

SDG&E Transmission Synchrophasor Project Update

Operationalizing Phasor Technology. Model Validation. Webinar. Ken Martin. March 4, Presented by. Page 0

Frequency Response Standard Background Document November, 2012

Distribution Fault Location

Forced Oscillation Event Analysis

Facilitating Bulk Wind Power Integration Using LCC HVDC

Fault Location Using Sparse Wide Area Measurements

Wide Area Monitoring with Phasor Measurement Data

Practical PMU Applications for Utilities

Turning Synchrophasor Data Into Actionable Information

Generation and Load Interconnection Standard

Optimal sizing of battery energy storage system in microgrid system considering load shedding scheme

Generation and Load Interconnection Standard

A Topology-based Scheme for Adaptive Underfrequency Load Shedding

How Full-Converter Wind Turbine Generators Satisfy Interconnection Requirements

Keeping it up to Speed Off-Nominal Frequency Operations. CETAC 2018 San Ramon

ATC s Mackinac Back-to-Back HVDC Project: Planning and Operation Considerations for Michigan s Eastern Upper and Northern Lower Peninsulas

Forward Looking Frequency Trends Technical Brief ERS Framework 1 Measures 1, 2, and 4: Forward Looking Frequency Analysis

Wide-Area Monitoring and Control of Power Systems using Real-Time Hardware-in-the-Loop Simulations

1400 MW New Zealand HVDC Upgrade: Introducing Power Modulation Controls and Round Power Mode

A Software Tool for Real-Time Prediction of Potential Transient Instabilities using Synchrophasors

Assessment of Impact of Data Quality on PMU-Based Applications USA

Controlled Islanding Followed by Load Shedding Based on Rate of Frequency Decline

Improvement of Rotor Angle Stability and Dynamic Performance of AC/DC Interconnected Transmission System

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76

Stability Issues of Smart Grid Transmission Line Switching

UNIT-4 POWER QUALITY MONITORING

The Value of Frequency Keeping and Governor Response to New Zealand

ELEMENTS OF FACTS CONTROLLERS

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75

Hybrid Anti-Islanding Algorithm for Utility Interconnection of Distributed Generation

Synchrophasors: Definition, Measurement, and Application

Introduce system protection relays like underfrequency relays, rate of change of frequency relays, reverse - power flow

Modeling and Evaluation of Geomagnetic Storms in the Electric Power System

Inverter-Based Resource Disturbance Analysis

2013 Grid of the Future Symposium. Effect of GIC and GIC Capability of EHV Power Transformers A Case Study on an AEP 765 kv Power Transformer Design

Testing and Validation of Synchrophasor Devices and Applications

POWER SYSTEM BACKUP PROTECTION USING SYNCHRONIZED PMU

Adamantios Marinakis, Scientist, 12 th IEEE SB Power Engineering Symposium, Leuven, Enhancing Power System Operation with WAMS

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

POWER SYSTEM OSCILLATIONS

ENHANCED DISTANCE PROTECTION FOR SERIES COMPENSATED TRANSMISSION LINES

Transcription:

21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2014 Grid of the Future Symposium Post-Event Analysis of a Compound Event in the ERCOT System Using Synchrophasor Data S. RAJAGOPALAN, S. NUTHALAPATI, T. MORTENSEN, B. BLEVINS Electric Reliability Council of Texas USA SUMMARY This paper presents experiences in the use of synchronized phasor measurement technology in the Electric Reliability Council of Texas (ERCOT) interconnection, USA. The paper discusses the post-event analysis of a compound event in the ERCOT system involving a fault, which, due to relay mis-operation, induced a loss of generation event. The relay mis-operation in response to the fault tripped one of two 345kV circuits interconnecting a generating station to the ERCOT transmission system. Thereby an imbalance occurred between the loading of the generator and the mechanical energy of its turbine system, which led to a rapid reduction in the power output of the generator as the turbine controls closed the intercept valves to protect the equipment from over-speed. This paper presents the insights gained from studying the synchrophasor data and points out the various indicators that determine the characteristics of the event. The owners (also the operators) of the effected equipment corroborated the conclusions drawn from the post-event analysis. This paper demonstrates a new use case for synchrophasor technology that helps identify and correct possibly incorrect operation of the equipment. KEYWORDS Synchrophasor Phasor Measurement Unit Phasor Data Concentrator Frequency Impulse Ramp Power Load Unbalance Voltage Phase Fault. Sidharth.Rajagopalan@ercot.com

1. Introduction The Electric Reliability Council of Texas Inc. (ERCOT) serves as the independent system operator (ISO) for most of the state of Texas. The ISO manages delivery of electric power to 24 million customers in Texas, representing 85 percent of the state s electric load and 75 percent of Texas land area. The ERCOT electric grid consists of around 41,500 miles of transmission and more than 550 generating units [1]. The total installed generation capacity for peak demand in ERCOT is 74,000 MW and its recorded peak load is 68,305 MW. There is more than 11,000 MW of wind generation capacity installed and operating in the ERCOT market, and in March 2014, the total wind generation reached a record 10,296 MW, which was 29% of the load at the time [2]. Most of the generated power in ERCOT is consumed in industrial and urban load centers in East, Central and South Texas, while most of the wind energy is installed in the north-west part of the state because of abundant wind resources there. This separation between resources and load centers has created some unique challenges in the integration of renewable resources, and in meeting the growing demand for power while also effectively ensuring the reliability of the grid [3 5]. Since synchronized Phasor Measurement Units (PMUs) were first introduced in the early 1980s, they have been recognized as suitable tools to modernize power system monitoring and control [6]. In the recent years, various applications of PMUs in power systems have been studied and the technology is becoming popular due to its versatility [7, 8]. Applications of phasor measurements have been extended to power system monitoring [9, 10], protection [11] and control [12]. Recognizing the potential benefits of synchronized phasor measurements, or synchrophasors, ERCOT started a collaborative effort in 2008 to implement this technology in its Operations and Planning processes. This effort, coordinated by the Center for the Commercialization of Electric Technology (CCET) under a grant from the Department of Energy, has engaged various entities, including ERCOT Transmission Service Providers (TSPs) and a software application provider [13]. As PMUs have been installed across the ERCOT grid, several real-time and off-line data processing and analysis tools have been acquired for ERCOT engineers to monitor and study the incoming synchrophasor data. Analyses using the synchrophasor data have indicated that synchronized phasor measurements can greatly improve both ERCOT Operations procedures and Planning studies. [14] gives the details of some of the applications of synchrophasor data in ERCOT. This paper presents a real-time example of the application of PMU data for post-event analysis of a compound event in the ERCOT system. Section II describes the present state of the ERCOT PMU network, including the locations of the PMUs and the structure of the communications systems. Section III presents a specific example of the application of synchrophasor data in ERCOT for post-event analysis Section IV summarizes the conclusions arising from this analysis. 2. The ERCOT PMU Network This section discusses the locations of PMUs and their effects on different applications in ERCOT. Also presented is the current state of the communication network tying the PMUs and Phasor Data Concentrators (PDCs) together. 2.1. Present PMU Locations in the ERCOT Grid In principle, PMUs should be installed across the ERCOT transmission grid to provide good observability for the entire network. Currently, synchrophasor data is 1

available only from PMUs installed on the networks of TSPs participating in the collaborative effort (discussed in Section I). Fig. 1 shows the geographical locations of the existing PMUs in the ERCOT system. At the time of writing this paper, there are 76 PMUs connected to ERCOT PMU network. That number is expected to go up to at least 100 PMUs in the coming months. The data presented in this paper was obtained from the installed PMUs shown in Fig. 1. Note that not all PMU data sources were always available for the recorded events due to communication constraints or outages. Fig. 1 PMU locations in the ERCOT grid Although more PMUs will provide a clearer overall picture of the grid with a resolution of 30 samples per second, even the limited number of PMUs in the current ERCOT grid have shown that they can be valuable in post-event dynamic analysis, real-time small signal stability monitoring and generator model validation [14]. PMUs installed in the West and North areas (see Fig. 1) allow ERCOT to monitor the stability conditions on the interface between these two regions. In addition, as most of wind generation is installed in West Texas, the data from PMUs located close to wind power plants has also helped ERCOT validate dynamic wind generation models [14]. 2.2. Synchrophasor Data and Communications A communications network has been built to transfer synchrophasor data from the individual PMUs to the ERCOT control center, where the incoming data is streamed to real-time applications and archived for off-line studies. 2

Fig. 2 The Synchrophasor data communication network As shown in Fig. 2, participating TSPs gather the data packets from individual devices in their PDCs where it can be made available for real-time visualization and also for local data storage. The ERCOT PDC receives the data from the respective PDCs of the TSPs. The ERCOT PDC synchronizes this data using the attached time stamp, and provides the data stream to real-time visualization applications in the ERCOT control center and also archives the data for offline studies. The ERCOT Secured Private Wide Area Network (WAN) forms the basis for all data communications between ERCOT and the participating TSPs. For data management, both the TSPs local PDCs and the ERCOT PDC archive the phasor data. ERCOT saves streamed synchrophasor data up to 400 days, and archives select event data over a longer timeframe. A real-time application installed in the ERCOT control center monitors the incoming stream of synchrophasor data and automatically creates event files when it detects a disturbance which may then be archived. 3. Application of PMU Data for Post-Event Analysis This section presents the post-event analysis conducted by ERCOT engineers for a compound event on the grid. In the process of analyzing a loss-of-generation event using PMU data, ERCOT engineers discovered other disturbances immediately before the loss of generation. This triggered a more in-depth analysis of these disturbances. Using the work detailed by A. Allen et al. in [15], the various trends in system frequency were analyzed. The event began with a phase-to-ground fault (determined by PMU frequency and voltage), which was followed by three separate frequency ramps. Since SCADA telemetry indicated that only the third frequency ramp was caused by a generator going 3

offline, ERCOT requested information from the operator of the power plant about a possible load rejection/imbalance event. The operator confirmed that the load imbalance had indeed happened while the TSP in the area confirmed the occurrence of the fault as well as a relay mis-operation in response to the fault at the Point of Interconnection (POI) of the generating station. Fig. 3 shows a one-line of the region. A phase-to-ground fault on a 138 kv bus section at the sub-station marked as S2, one bus away from the POI of generating unit G1, was followed by mis-operation of relays at the POI (sub-station S1 in the one-line). The clearing of the fault caused the 345kV circuit connecting the sub-stations S1 and S2 to be tripped, causing a transient imbalance between the loading and mechanical power of unit G1. This finally led to the tripping of the generator and a total frequency swing of 0.217 Hz. Fig. 3 One-line of the 345kV system near the event and the relative location of the PMUs 3.1. The Power Load Unbalance (PLU) relay The PLU relay is designed to rapidly close control/intercept valves under load imbalance conditions in order to reduce generation and protect the turbine from an over-speed event. The relay compares the loading on the generator to the mechanical energy in the turbine [16, 17] and trips if the difference is more than a set percentage, typically 40% or 0.4 per unit, and the load decreases faster than a set rate, typically equivalent to going from rated load to no load in 35 milli-seconds [16]. Once the unbalanced condition has cleared and a set time delay has passed, the PLU relay is reset and the intercept valves open, allowing load to be restored to the generator. However, the load reference used by the valves does not return to the value before the event, but remains at the value reached when the PLU relay is reset [16]. 3.2. System Frequency Fig. 4 shows the frequency trend captured by the PMUs on the ERCOT grid over the course of this event. A. Allen et al. classified frequency trends captured by PMUs during various types of system events into three categories [15]: 1. Frequency Impulse a. Half-Impulse b. Full-Impulse 2. Frequency Transient 4

3. Frequency Ramp The frequency characteristic (Fig. 4) recorded by the PMUs on the ERCOT system shows two of these three distinct characteristics the Impulse and the Ramp. Fig. 4 System Frequency recorded by the PMUs on the ERCOT Grid during this event Fig. 5 Representation of a system fault in the measured frequency from the PMUs 3.3. System Phase-to-Ground Fault The phase-to-ground fault on the system occurred approximately 30 cycles before the onset of the loss-of-generation event. This is seen to be represented by one of the 5

characteristic frequency trends identified in [15] specifically, the half/full impulse (see Fig. 5). The authors note here, that such a frequency impulse from PMU data records is not a characteristic of the physical/rotational inertia of the system, but rather a result of the fact that the frequency measured by a PMU is a function (derivative) of the voltage phase angle of the point of measurement [6]. That the event which occurred was indeed a fault was confirmed by examining the voltage magnitudes at the two PMUs (PMU1 and PMU2) identified in the oneline of the region. As expected, there is a sharp (near instantaneous) drop in the voltage recorded by the PMUs, which is the characteristic of voltage near a fault. 3.4. Loss of Generation Fig. 6 Phase Voltages measured by PMUs near the event The loss of generation event can be easily identified from the frequency trend recorded by the PMUs. Following the classifications in [15], the frequency ramp, marked FR1 in Fig. 7, corresponds directly with the first loss of generation event. As Fig, 4 shows, there were three such ramp events involving the loss of generation in this compound event. They are marked FR1, FR2 and FR3 in Fig. 7. FR1 and FR3 were caused by near-instantaneous loss-of-generation events and FR2 was the slow decay of frequency over several tens of seconds that happened in the interval between FR1 and FR3. Following the fault on the system and clearance with the tripping of the line between sub-stations S1 and S2 in the one-line, the system experienced the first lossof-generation event. In this first event, the generation from the unit 'G1' dropped by approximately 575 MW, causing the frequency to decline from 59.99 Hz to 59.846 Hz, a drop of 0.144 Hz, in around 3 seconds. With the loading on the unit being drastically reduced due to the loss of one of the lines interconnecting the unit to the ERCOT system, a power load unbalance greater than 40% was detected by the generator-turbine control system. This caused the activation of the PLU circuit, leading to the steam intercept valves being rapidly closed in order to limit the turbine 6

mechanical energy and protect the generator from over-speed. This was the cause of the first frequency event detected by the PMUs on the ERCOT synchrophasor network. However, the unit did not go offline during this event. Fig. 7 Three frequency sub-events FR1, FR2 and FR3 Fig. 8 Unit output as telemetered by SCADA (PI chart, times are not exact) 7

Following the arrest of frequency decline by the system's inherent inertia, the governor response of the system set in with AGC acting to restore system frequency to its pre-event state. The PLU condition cleared (difference between mechanical energy and electrical load reduced below 40%) and following the time delay, the PLU control circuit disengaged and the intercept valves were opened allowing the generator to take on load again. Approximately 10 seconds after inception of event FR1, the line connecting stations S1 and S2 reclosed. This appears as the second impulse in the frequency demarcated in Fig. 4 as the reclosing of the line from S1 to S2. That this impulse frequency did indeed correspond to a reclosing event and not a fault was confirmed by an examination of the voltage magnitudes of PMU1 and PMU2 at the corresponding time-stamp as shown in Fig. 6. By the time the line reclosed, the unit loading had been partially restored to approximately 500 MW (according to SCADA telemetry from the unit, see Fig. 8). The excess steam that was trapped in the reheat section while the PLU circuit was active was dissipated. Therefore, when the loading on the unit increased after the reclosing, there was not enough pressure in the reheat to sustain it and generation decayed once again, which can be seen as the slow ramp down of frequency in Fig. 7 marked as event FR2'. This is also referred to as 'run back'. Finally, due to the generation becoming too low, the unit tripped leading to the second frequency event detected by the PMUs designated as FR3. 4. Conclusions This paper presents a real-time example of using synchrophasor data to perform postevent analysis of complex events in the ERCOT system. Aided by the insight obtained from analysing the synchrophasor data, engineers at ERCOT were able to communicate with the transmission owner as well as the owner/operator of the power plant and confirm the facts. Responses from the transmission owner allowed ERCOT engineers to finalize the correct sequence of relaying events and establish the cause for the relay mis-operation. Detailed responses from the plant operator established the PLU circuit parameters and showed that the PLU operated as designed. However, the loss of a unit, which was not in the clearing zone of the fault, has caused the plant operator to start discussions with their vendor to determine if the loss of generation was necessary and whether the PLU parameters need to be changed. This paper demonstrated a new use case for synchrophasor technology that helps identify and correct possibly incorrect operation of the equipment. Such event analyses with synchrophasor data are now performed regularly at ERCOT for a variety of system disturbances. These analyses have helped to do model validation and correct generator control-system parameters, if required [14]. The analysis presented in this paper also has useful information for planning studies at ERCOT. These studies have not commonly accounted for the possibility of contingent loss of generation due to power load unbalance caused by a fault near the POI of a generator. One conclusion of this study was to investigate the possibility of other generators on the system being tripped during a fault that should not necessarily isolate the generator/plant from the grid. 8

BIBLIOGRAPHY [1] About ERCOT (webpage: http://www.ercot.com/about/index.html) [2] ERCOT Quick Facts May 2014 (ERCOT, May 2014). [3] ERCOT CREZ Reactive Power Compensation Study (ERCOT, 2010). [4] Shun-Hsien Huang, John Schmall, Jose Conto, John Adams, Yang Zhang, Cathey Carter Voltage Control Challenges on Weak Grids with High Penetration of Wind Generation: ERCOT Experience (IEEE PES General Meeting, San Diego, USA, July 2012). [5] John Schmall, Sidharth Rajagopalan, Yang Zhang, Jose Conto Modeling of Wind Parks at ERCOT (IEEE PES General Meeting, San Diego, USA, July 2012). [6] A. G. Phadke, J. S. Thorpe Synchronized Phasor Measurements and their Applications (New York, Springer 2008). [7] K.E. Martin Phasor Measurement Systems in the WECC (IEEE PES General Meeting, Montreal, Canada, June 2006). [8] J.H. Chow, L. Vanfretti, A. Armenia et al. Preliminary Synchronized Phasor Data Analysis of Disturbance Events in the US Eastern Interconnection (IEEE PES Power Systems Conference and Exposition, March 2009). [9] J. De La Ree, V. Centeno, J.S. Thorp, A.G. Phadke Synchronized Phasor Measurement Applications in Power Systems (IEEE Trans. Smart Grid, vol.1, no.1, pp.20-27, June 2010). [10] R. Emami, A. Abur Robust Measurement Design by Placing Synchronized Phasor Measurements on Network Branches (IEEE Trans. Power System, vol.25, no.1, pp.38-43, February 2010) [11] V. Centeno, A. G. Phadke, A. Edris, et al. An Adaptive Out-of-step Relay [for Power System Protection] (IEEE Trans. Power Del., vol. 12, no.1, pp.61-71, Jan. 1997) [12] Y. Zhang, A. Bose PMU-based wide-area damping control system design (IEEE PES General Meeting, San Diego, USA, July 2012). [13] CCET Technology Solutions for Wind Integration in ERCOT (DOE Report, September 2013) [14] Jian Chen, Prakash Shrestha, Shun-Hsien Huang, N. D. R Sarma et al. Use of Synchronized Phasor Measurements for Dynamic Stability Monitoring and Model Validation in ERCOT (IEEE PES General Meeting, San Diego, USA, July 2012). [15] A. Allen, S. Santoso, E. Muljadi Algorithm for Screening Phasor Measurement Unit Data for Power System Events and Categories and Common Characteristics for Events Seen in Phasor Measurement Unit Relative Phase-Angle Differences and Frequency Signals (NREL Technical Report, May 2013) [16] P. Kundur Power System Stability and Control (McGraw Hill Inc., 1994) [17] J. Kure-Jensen, W. Barker Speedtronic Mark V Steam Turbine Control System (GE Power Generation Paper GER-3687C, 1996) 9